Home

Digital Controller PXH

image

Contents

1. If the value entered does not allow PS1 PAS1 Ch9 1 or PS2 PAS2 Ch9 2 to hold the later channels cannot be selected Parameter No Parameter name Parameter No Parameter name Parameter 01 ir Ei i 01 He r ron selection ti Basic type Motorized control type Heating cooling control type common parameter list ef Display symboli Name J Remote mode Factory Parameter Switches setting between remote auto mode operation REM Remote mode AUT Auto mode Standby command Switches controller to RUN Standby ON Control standby output OFF alarm OFF OFF Control RUN Refer to Table 7 Auto tuning command Sets auto tuning OFF non action ON1 start auto tuning Alarm latch clear command Disables alarm 1 8 latch OFF non action CLR Latch clear Palette selection Selects a PID palette to be used to control Setting range 0 to 7 Alarm settings 1 Displayed when alarm operation type 1TP chA 1 is setto 1 to 11 See table 1 Alarm 1 operation value setting 10 FS Setting possible within the input range Alarm lower limit settings 1 Displayed when alarm operation type 1TP chA 1 is set to 16 to 31 See table 1 Alarm 1 lower limit operation value 10 FS setting Setting possible within the input range Alarm upper limit settings 1 Displayed when alarm operation type 1TP chA 1
2. cho 545 System definition Parameter ae ae Factory Parameter a Display a Name Cee ananen default mask oles fe LED C2 Allocates indicator LEDs 25 32 2 assignment Setting range 0 to 255 Cooling output Note Be sure to reset or turn on the power after the parameter setting is changed zie Digital Controller Functions 6 1 Alarm functions 1 Alarm Types e The alarm types are an absolute value alarm a deviation alarm an upper lower limit alarm and a range alarm For details see Table 1 Alarm Operation Type Codes 2 Alarm function No Function Name Function Parameter set Q Hysteresis Alarm operation can be set for operation dead band alarm 1 1hYS chA 3 function hysteresis alarm 8 8hYS chA 38 ON delay After alarm ON conditions are established the alarm is alarm 1 1dLY chA 4 function ON after the ON delay setting time alarm 8 8dLY chA 39 Alarm latch Alarm goes ON once and alarm ON function status is alarm 1 10P chA 2 function maintained To release the alarm latch the following methods are used alarm 8 80P chA 37 I Turns power ON again on the controller Il Turns alarm latch settings OFF once Ill Releases latch on the alarm latch release screen LACH ch1 8 IV Executes release with DI input di01 ch9 39 to di04 ch9 42 V Executes release with communication 4 Abnormal Sets alarm relay to ON when abnormality occu
3. Control output e OUT1 MV on heating side Current SSR drive scaling Control output Ee OUT2 MV on cooling side F Current SSR drive scaling OTYP 51 Re transmission _ output 1 Re transmission _ output 2 Control output MV on cooling side Control output MV on heating side OTYP 53 Ao1 Limit scaling Ao2 Limit scaling OUT1 Current Re transmission fe OUT1 Aol output 1 i Current SSR drive jRe transmission imit OUT1 scaling output 1 Current SSR drive scaling OUT2 XPS 24V DC Transmitter E ower supply Control output _ ee OQUT2 MV on cooling side my Current SSR drive scaling Control output Do3 MV on cooling side Relay Control output MV on heating side Control output Do4 a MV on heating side Relay OTYP 54 OTYP 55 Control output ne OUT1 MV on heating side Current SSR drive LI scaling Re transmission fe OUT2 output 2 Current SSR drive scaling Control output MV on cooling side Control output MV on heating side Control output MV on cooling side AG Ao1 Limit scaling OUT1 Current SSR drive OUT2 XPS Transmitter power supply Table 5 Di Input Assignments Di1 to Di15 Di1 to Di15 Setting Value Function None Oper
4. Setting range According to rCP9 setting d10 Recipe Recipe parameter 1 setting for palette 1 setting 10 Setting range According to rCPO setting d19 Recipe Recipe parameter 10 setting for palette 1 setting 19 Setting range According to rCP9 setting d20 Recipe Recipe parameter 1 setting for palette 2 setting 20 Setting range According to rCPO setting d29 Recipe Recipe parameter 10 setting for palette 2 setting 29 Setting range According to rCP9 setting d30 Recipe Recipe parameter 1 setting for palette 3 setting 30 Setting range According to rCPO setting d39 Recipe Recipe parameter 10 setting for palette 3 setting 39 Setting range According to rCP9 setting u d40 Recipe Recipe parameter 1 setting for palette 4 setting 40 Setting range According to rCPO setting d49 Recipe Recipe parameter 10 setting for palette 4 setting 49 Setting range According to rCP9 setting d50 Recipe Recipe parameter 1 setting for palette 5 setting 50 Setting range According to rCPO setting d59 Recipe Recipe parameter 10 setting for palette 5 setting 59 Setting range According to rCP9 setting d60 d69 d70 d79 2 Recipe Recipe parameter 1 setting for palette 6 setting 60 Setting range According to rCPO setting Recipe Recipe parameter 10 setting for palette 6 setting 69 Setting range According to rCP9 setting Recipe Recipe parameter 1 setting for palette 7 setting 7
5. scale lower limit output Setting range 130 0 to 130 0 AQ1 output Sets the upper limt value of the AO1 output 105 0 limit upper limit limit Setting range 25 0 to 105 0 AO1 output Sets the lower limt value of the AO1 output 5 0 limit lower limit limit Setting range 25 0 to 105 0 AO2 output Switches the AO2 re transmission output PV It is invalid type signal when the XPS Setting range PV SV MV DV AiM is attached MVRB TV AO2 output Sets the scale upper limit value of the AO2 100 0 25 2 scale upper limit output Setting range 130 0 to 130 0 AO2 output Sets the scale lower limit value of the AO2 0 0 25 2 scale lower limit output Setting range 130 0 to 130 0 AO2 output Sets the upper limt value of the AO2 output 105 0 25 2 2 limit upper limit limit Setting range 25 0 to 105 0 5 75 AZLL A2LL AO2 output Sets the lower limt value of the AO2 output 5 0 25 limit lower limit limit Setting range 25 0 to 105 0 0 Calculation Math function type setting 25 9 For details see setting Setting range 0 to 40 Table 9 Math function Sets the scale on the full side which is As ordered 25 9 full scale utilized for mathematical calculations Setting range 19999 to 99999 Note Be sure to reset or turn on the power after the parameter setting is changed O65 Parameter ehian Factory Parameter Display Symbol
6. Fuji Electric Co Ltd FO AMELE international Sales Div Sales Group Gate City Ohsaki East Tower 11 2 Osaki 1 chome Shinagawa ku Tokyo 141 0032 Japan http www fujielectric com Phone 81 3 5435 7280 7281 Fax 81 3 5435 7425 http www fujielectric com products instruments Digital Controller Model PXH INP TN1PXHc E Thank you for purchasing the Fuji Digital Controller Once you have confirmed that this is the product you ordered please use it in accordance with the following instructions For detailed information on operating this equipment please refer to the separate operations manual User s manual in the supplied CD ROM In addition please keep this instruction manual within easy reach of the actual person using this equipment CAUTION The content of this manual is subject to change without notice The greatest care has been taken with the content of this manual to ensure accuracy however Fuji Electric shall not be held liable for damages including indirect damages caused by typographical errors absence of information or use of information in this manual CONTENTS PLEASE READ FIRST cccsseeeeeeeeeeeeeeeeeeees 3 ChF PFb motorized valve definition 37 For Proper USage ennnidnle nea 9 Heating cooling control type exclusive parameter list 1 Installation MOunting ccceeeeeseeeeeteeees 10 Ch2 Ped Control parameter ccceeee 38 2 Wiring Connection sischc
7. do exercise caution in not applying too much torque because the casing is made of plastic e The front of this equipment is wateproof in compliance with NEMA 4X standards IP66 equivalent However regarding waterproofing between the equipment and the panel use the included packing to ensure waterproofing and attach it according to the guidelines below Incorrect attachment may cause the equipment to lose its waterproof capabilities As shown in Fig 1 insert the panel after attaching the packing to the equipment case 2 As shown in Fig 2 tighten the fixture screws so that no gaps can remain between the equipment face the packing and the panels Once finished confirm that there are no changes in shape such as displaced or improperly fitted packing etc as shown in Fig 3 e Please exercise caution if the panel strength is weak and gaps develop between the packing and the panel as this will result in the loss of its waterproofing capabilities Mounting method Fig 1 Mounting Fig 3 fixture uni Screw Packing Packing gt Le Case i Case Packing me Screw Bao Good Front Panel Panel Mounting fixture Standard vertical panel attachment horizontal position installing If attached at an angle the maximum gradient is a 30 downslope ae Caution Ig Naza 3 e In order not to hamper heat radiation do not block the sides of the equip ment e Do not block the air vent
8. value 1 on cooling side Palette 1 derivative time on heating side Setting range 0 0 to 999 9 sec The derivative operation is set to OFF when setting 0 Palette 1 upper limit value on cooling side of operation output MV Setting range 25 0 to 125 0 MV lower limit value 1 on cooling side Palette 1 lower limit value on cooling side of operation output MV Setting range 25 0 to 125 0 39 Cha PL Control palette Parameter ar Expl Factory Parameter N Name Content Explanation default mask otes Setting value 7 Proportional band 7 on heating side Palette 7 SV O FS 14 1 Setting range SV lower limit value to SV upper limit value 5 0 14 1 Palette 7 proportional band on heating side Setting range 0 0 to 999 9 Two position operation is allowed when setting 0 Integral time 7 on heating side Palette 7 integral time on heating side Setting range 0 0 to 3200 0 sec The integral operation is set to OFF when setting 0 Derivative time 7 on heating side Palette 7 derivative time on heating side Setting range 0 0 to 999 9 sec Derivative operation is set to OFF when setting 0 Integration cut point upper limit value 7 ntegration cut point lower limit value 7 Palette 7 upper limit value of integration 100 FS cut point Setting range 0 to 100 FS Palette 7 lower limit value of integration 100 FS cut point Sett
9. 1 RCJ1 monitor Displays RCJ1 input RCJ2 monitor Displays RCJ2 input AO1 monitor Displays Analog output 1 output value AO2 monitor Displays Analog output 2 output value DI monitor 1 Displays DI1 to 4 status D4 __4 DI3 DI2 DH OFF Blank ON Di No DI monitor 2 Displays DI11 to 15 status OFF Blank ON Di No DO monitor 1 __A DO1 DO monitor 2 Displays DO11 to 15 status a DO15 OFF Blank DO14 ON Do No DO13 DO12 DO11 Math result monitor Alarm delay remaining time monitor Displays result of Math operation Displays the remaining time for the alarm delay of ALM1 to ALM8 asc ee The alarm option will select the unit Ch7 fon Monitor Parameter oten Eana Factory Parameter Nai Display Symbol Name omeni Exp anaon default mask otes 100 dLE DiC1 Communication Displays the status of communication Di1 5 Di monitor 1 5 Communication bis 4 ii Communication Di4 Communication Di3 Communication Di2 Communication Di1 dife dice Communication Displays the status of communication Di6 8 Di monitor 6 8 Communication Dig ____ amp t Communication Di7 Communication Di6 OA input output definition Parameter No Display Symbol PV1 full scale Se
10. 2 at 0000 to reset the password X Setting the paremater to F1C3 displays all parameters Please do not change the parameters unnecessarily It may cause a failure of this main unit 55 Model Specification PXH Model Code 9 10111213 Digit 123456738 V 0 Basic type Digit Description Notes 4 lt Dimension of front face H x W gt 96 x 96 mm 5 lt Number of control loops Function gt 1 loop basic controller 6 lt Measurement value input gt Universal input 1 point Universal input 2 points mA 7 lt Auxiliary input gt Not fitted DC voltage 1 point Oo 8 lt Version No gt 1 9 lt Output gt OUT1 OUT2 13 Not fitted Current Transmitter supply Not fitted Current Current Current Current SSR SSC driver SSR SSC driver lt Power supply gt 100 to 240 V AC lt Communication interface gt Not fitted 0 RS 485 R lt Digital input output gt Digital input DWran 10 11 12 Digital output Including relay control output 2 2 points Do3 Do4 4 points Do1 to Do4 9 points Do1 to Do4 Do11 to Do15 4 points Di1 to Di4 4 points Di1 to Di4 9 points Di1 to Di4 Di11 to Di15 lt Additional specifications gt Not fitted 0 1 2 for the 6th digit and B for the 12th digit cannot be specified at the same time 2 One digital output Do4 is occupied when relay
11. 9 ON OFF control at setting 0 Integral time 7 Derivative time 7 palette 7 integral time Setting range 0 0 to 3200 0 sec Integral control OFF at setting 0 palette 7 derivative time Setting range 0 0 to 999 9 sec Derivative control OFF at setting 0 Anti reset windup upper limit value 7 palette 7 Anti reset windup upper limit value setting Setting range 0 to 100 FS 100 FS Anti reset windup lower limit value 7 palette 7 Anti reset windup lower limit value setting Setting range 0 to 100 FS 100 FS Hysteresis setting 7 palette 7 hysteresis setting Setting range 0 to 50 FS 0 3 FS Output conver gence value 7 palette 7 Output convergence value Setting range 100 0 to 100 0 0 0 PID switch point 1 palette 1 PID switch point Setting range 25 to 125 FS O FS PID switch point 7 palette 7 PID switch point Setting range 25 to 125 FS no oR Ch7 iion Monitor Parameter Factory Parameter Symbol Name Content Explanation default mask Notes I PV1 monitor Displays Process value 1 input PV2 monitor Displays Process value 2 input Al1 monitor Displays Analog input 1 input Reading of the signal input to the terminal before input correction RSV1 monitor Displays remote set value 1 Control RSV value after input correction Local SV1 monitor Display Local set value
12. Data length Parity 8n 8 None 80 8 Odd 8E 8 Even PC Loader communication speed Selects the communication speed for PC Loader communication Setting range 96 9600 bps 192 19200 bps 384 38400 bps PC Loader bit format Selects the bit format for PC Loader communication Data length Parity Setting range Bn 8 None 80 8 Odd 8E 8 Even Communication Di1 function setting Sets the function of communication Di1 Communication Di2 function setting Sets the function of communication Di2 Communication Di3 function setting Sets the function of communication Di3 Communication Di4 function setting Sets the function of communication Di4 Communication Di5 function setting Sets the function of communication Di5 Communication Di6 function setting Sets the function of communication Di6 Communication Di7 function setting Sets the function of communication Di7 Communication Di8 function setting Sets the function of communication Di8 Note Be sure to reset or turn on the power after the parameter setting is changed Pe es Chc Lar Linearize Parameter Beha te Factory Parameter ei Display Symbol Name ONENE ANAON default mask oS Linearize table Linearize table XO for PV1 input 25 FS See 5 26 P1X0 Setting range 25 to 125 FS Linearize table Linearize table YF for PV1 input 125
13. FS P1YF Setting range 25 to 125 FS Linearize table Linearize table XO for PV2 input 25 FS P2X0 Setting range 25 to 125 FS Linearize table Linearize table YF for PV2 input 125 FS P2YF Setting range 25 to 125 FS Linearize table Linearize table XO for Ai1 input 25 FS A1X0 Setting range 25 to 125 FS Linearize table Linearize table YF for Ai1 input 125 FS A1YF Setting range 25 to 125 FS Note Be sure to reset or turn on the power after the parameter setting is changed L Mathematical Calculation Parameter ALENE Factory Parameterl Not No Display Symbol Name OMSL EXpananon default mask otes EDI k01 Constant for Sets the constant used for mathematical 38 1 Floating point Math function expressions 0 0000 setting I6 k16 38 4 ar ChE Tuning Parameter oe EEn Factory Parameter Na Display Symbol Name Omen xpanauon default mask otes ALP I ATP Auto tuning Specifies the auto tuning method type Setting range NRML 39 1 NRML Standard type AT LPV Low PV type AT reton ChG o Parameter Symbol Totalizer Factory Parameter No Display Frin TrUn Totalizer command status Starts stops latches totalizer 45 1 Setting range HoLd rUn LATcH HOLD 1 2 Pre S TrES Toin Totalizer reset command Totalizer input selection Totalized value display decimal point position Resets tot
14. X k04 X PV2 k05 X k06 X Ai1 k07 k08 k09 X k10 X PV1 k11 X k12 X PV2 k13 X k14 X Ai1 k15 k16 Mathematical expression 6f M1 k01 X PV1 X k02 X PV2 k03 X Ai1 k04 X Ai1 k05 M1 Max PV1 PV2 PV1 or PV2 whichever is larger is selected M1 Min PV1 PV2 PV1 or PV2 whichever is smaller is selected M1 Max PV1 PV2 Ai1 PV1 PV2 or Ai1 whichever is largest is selected M1 Min PV1 PV2 Ai1 PV1 PV2 or Ai1 whichever is smallest is selected Mathematical expression 5 M1 H selector 2 points L selector 2 points H selector 3 points L selector 3 points Input switching 2 points M1 PV1 when PV1 lt k01 M1 PV2 when PV1 gt k01 H L selector 2 points Expression 7 or 8 is used by Di switching with Di switching function Specify 140 for Di function for switching H L selector 3 points Expression 9 or 10 is used by Di switching with Di switching function Specify 140 for Di function for switching mi evi Ait k01 k02 PV2 X k03 k04 Flow rate compensation with PV1 Differential pressure flow rate value k01 Pressure compensation constant 1 temperature and pressure k04 Temperature compensation constant 2 value operation PV2 Fluid temperature value k03 Temperature compensation constant 1 Ai1 Differential pressure value k02 Pressure compensation constant 2 k05 Square root
15. inhibiting Prevents switching to the REMOTE mode Setting range ON OFF R_ACK use selection Selects use or non use of R_ACK Setting range INH ENA A M mode Selects the A M mode Setting range A M A Mode settings when the power turns ON Sets the mode when the power turns ON Setting range A R M Tracking method selection SV Selects ON or OFF for tracking the local set value SV Operation settings when in standby mode Sets the front display operation in the standby mode Setting range 0 lighting 1 extinction For details see Table 7 palette switching method selection Selects a palette switching factor Setting range PLTn SV PV User designation key 1 F1 User designation key 2 F2 User designation key 3 F3 Sets user assignments for function keys F1 F3 Setting range 0 to 27 For details see Table 8 Burnout direction specification MV1 Specifies the direction of the control output during a burnout Setting range HOLD LO UP EXMV Assignment for digital input 1 Assignment for digital input 4 Assignment for digital input 11 Assignment for digital input 15 di01 60 di02 70 di03 0 di04 103 Sets assignments for DI1 D14 DI11 D115 Setting range 0 to 255 For details see Table 5 Assignment for digital output 1 Assignment for digital output 4 Assignmen
16. is set to 16 to 31 See table 1 Alarm 1 upper limit operation value 10 FS setting Setting possible within the input range Alarm settings 8 Displayed when alarm operation type 8TP chA 36 is setto 1 to 11 See table 1 Alarm 8 operation value setting 10 FS Setting possible within the input range Alarm lower limit settings 8 Displayed when alarm operation type 8TP chA 36 is set to 16 to 31 See table 1 Alarm 8 lower limit operation value 10 FS setting Setting possible within the input range Alarm upper limit settings 8 Displayed when alarm operation type 8TP chA 36 is set to 16 to 31 See table 1 Alarm 8 upper limit operation value 10 FS setting Setting possible within the input range Keylock Selects parameter lock type Setting range 0 to 5 Communication All Parm SV MV Key operation No All Parm SV MV O Can be set X Cannot be set zies Parameter Display Symbol Parameter jump setting 1 c Expl Factory Parameter Name ontent Explanation default mask Notes 2 01 01 12 Press the function key when 60 is selected and the display jumps to the specified parameter Setting range l 01 to Z Z9 Parameter jump setting 2 Press the function key when 61 is selected and the display jumps to the specified parameter Setting range l 01 to Z Z9 Parameter jump se
17. local SV Transfer of SV4 to local SV Transfer of SV5 to local SV Transfer of SV6 to local SV Transfer of SV7 to local SV Selection of palette 0 Selection of palette 1 Selection of palette 2 Selection of palette 3 Selection of palette 4 Selection of palette 5 Selection of palette 6 Selection of palette 7 Parameter jump 1 Parameter jump 2 Parameter jump 3 Note 1 Do not use this setting when TPLT Ch8 92 is set to 11 or 14 52 Table 9 Type of Math function CALC Name A R x i Arithmetic expression setting of operation No math operation M1 PV1 input 3 1 sira Mathematical expression 1 Ta Ail k02 k04 Flow rate compensation with MTSO TAN EVI k03 x PV2 k05 temperature and pressure PV1 Flow rate differential pressure PV2 Temperature Ai1 Pressure A r Hi Faem Mathematical expression 2 M1 k01 X PV1 X Ai1 k02 x k04 Flow rate compensation with k03 PV2 k05 temperature and pressure PV1 Flow rate differential pressure PV2 Temperature Ai1 Pressure Mathematical expression 3 M1 k01 x PV1 x A 1 K02 __k04 Flow rate compensation with k03 PV2 k05 temperature and pressure PV1 Flow rate differential pressure PV2 Temperature Ai1 Pressure A k01 X k02 X PV1 k03 X PV2 k04 X Ai1 k05 Mathematical expression 4 M1 06X k07 X PV1 k08 X PV2 k09 X Ail k10 k01 X k02 X PV1 k03
18. see Table 3 PV2 base scale Sets the base side scale of PV2 input As ordered Setting range 19999 to 99999 For details see Table 3 PV2 decimal point position Specifies the decimal point position of PV2 input Setting range 0 to 3 3 2 1 0 No decimal point PV2 input type Sets the type of PV2 input Setting range 0 to 27 For details see Table 2 Pv2 unit Sets the measurement unit for PV2 input non No unit F F unit C C unit PV2 input zero point adjustment PV2 input span point adjustment Sets the correction value of a zero point for PV2 input Setting range 50 to 50 FS Sets the correction value of a span point for PV2 input Setting range 50 to 50 FS PV2 input cut point Sets the cut point of square root extraction calculation for PV2 input In case of OFF the square root extraction is not calculated Setting range OFF 0 0 to 125 0 Pv2 input filter Sets the time constant for PV2 input filter Setting range 0 0 to 900 0 sec PV2 linearize setting Note Be sure to reset or turn on the power after the parameter setting is changed PV2 input linearize enable disable setting Setting range OFF nrML hi C Lo C 25 input output definition Parameter E ETER Factory Parameter Not No Display Symbol Name o nenscxp ananon default mask otes 40 Ac IF AF Ait fullscale Sets the full side scale of analo
19. will be displayed 2 5 Others Please do not wipe the equipment with organic solvents such as alcohol or benzene etc If wiping is necessary do so with a neutral cleaning agent Do not use mobile phones near this instrument within 50 cm Otherwise a malfunction may occur Trouble may occur if the instrument is used near a radio TV or wireless device For Proper Usage lt Reference ltem gt lt Details gt Model Designation Confirmation e Please confirm that the model delivered matches your order ss e External dimensions 1 Installation Mounting Panel cut dimensions i e How to install on the panel 2 Wire Connection e Terminal connection diagram Vv Turn Power On AA 3 Usage Read before using How to change the temperature setting values 4 Display and Operation Methods Basic method of operation wre e List of parameters 5 Switching Parameters Table of input output alarm 6 Digital Controller Function codes J e Set up input sensor and input range 7 Controller Set up Procedure z Contraltineiiad sileda Control via auto tuning Automatic settings of parameters AA Operation Motorized valve control p e Heating cooling control AA 8 When the display does not make sense e Displays during abnormalities x Since about 15 minutes is needed until the unit becomes thermally stable wait for 15 minutes or more after turning the power on bef
20. 0 Setting range According to rCPO setting Recipe Recipe parameter 10 setting for palette 7 setting 79 Setting range According to rCP9 setting 295 Motorized control type exclusive parameter list Ch7 fon Monitor Parameter Factory Parameter Display Symbol Name Content Explanation default mask Notes 50 f Tor b MVrb Valve monitor Displays the valve opening degree 17 5 feedback value Input output definition Parameter TAE E Factory Parameter R Display Symbol Name ontent Explanation default mask otes Ai1T Ai1 input type Sets the type of Ai1 input As 23 1 Setting range 16 to 18 23 24 ordered Sets 23 or 24 when used as valve opening fead back Template Specifies the template 25 10 The range of effective setting 30 1 loop motor operated valve controller with input Math 31 1 loop SV selection type motor operated valve controller with input Math 33 1 loop motor operated valve controller 34 1 loop SV selection type motor operated valve controller Output type Selects the control output selector type As ordered 25 11 Setting range 30 to 31 Note Be sure to reset or turn on the power after the parameter setting is changed System definition Parameter EERE T Factory Parameter aa No Display Symbol Name eee default mask oles 35 6rd i brd Designates Designates control output at input error or output valve opening degree feedback anomaly at burnou
21. 2 Table 8 User Assignable Function keys 52 ChD C L Mathematical Calculation 32 Table 9 Type of Math function cceeee 53 ChE AF Tuning sdeonciectiasecenidsaacceaedoneeis 32 Table 10 Control template 0 0 0 0 cece 54 ChG fof Totalizer cc setiiceavncssenanstesincetees 33 8 Troubleshooting ChX P Recipe oo eee cecesseceeeeeenteeeeeees 35 Please read when the display does not make Motorized control type exclusive parameter list Sensej primenio ea Ra 55 Ch7 Ron MOnitor ccccceccsceeeseeeesteeeeeees 36 Model Specification ccccceeeeseeeeseeeeeseeees 56 Ch8 SEF Input output definition 36 PXH Model Code ccccccssseeeeesssteeeeesenaes 56 Ch9 595 System definition c eee 36 SP CHICAILONS scarii 59 Confirming Specifications and Accessories Before using the product confirm that it matches the type ordered For model code please refer to pages 56 to 58 Confirm that all of the following accessories are included e Digital Controller e Instruction Manual e Mounting fixture e Waterproof packing 1 pc 1 Supplied only when the communications function RS485 is selected with this model Option Name Order No PC loader communication cable ZZPPXH1 TK4H4563 Terminal covers 2 ZZPPXR1 B230 2 Two pieces are required per unit Related Information Refer to the following reference materials for d
22. Name oneni Exp anauon default mask Tora UCb1 Math function Sets the scale on the base side which is As ordered 25 9 base scale utilized for mathematical calculations Setting range 19999 to 99999 Math function Sets the decimal point position for decimal point mathematical calculations position Setting range 0 to 3 Template Specifies the template 25 10 The range of effective setting 10 Single loop basic PID control with Math function Single loop SV selection PID control with Math function Single loop basic PID control Single loop SV selection PID control Single loop input selection PID control with Math function Setup other than the above is forbidden Output type Selects the control output selector type As ordered 25 11 For details see Setting range 10 to 13 Table 4 System Sets a constant value used for templates 25 15 constant 1 The meaning of the value varies depending on template Make the setting after System checking the description of each template constant 16 Setting range 19999 to 99999 Note Be sure to reset or turn on the power after the parameter setting is changed SOT Ss Parameter Display Symbol Password 1 Sets security passwords Setting range 0000 to FFFF Factory Parameter Password 2 Sets security password Setting range 0000 to FFFF Password 3 Sets security password Setting range 0000 to FFFF Remote mode
23. OJN e N N N N N N o pS 4 A ine oO foe are fee N wo A oO for J fee o oO o 1 Contents of OR operation Manual Auto 2 Contents of OR operation Manual EX MV 3 The lamp does not come ON for current 4 to 20mA output type Table 7 Standby operation Operation during standby setting value setting value Output other MV output than MV Screen display Value of PMv1 Value of PMC1 OFF or 25 Lighting 25 to 125 Value of PMv1 Value of PMC1 OFF or 25 Extinction 25 to 125 Normal Normal Lighting Table 8 User Assignable Function Keys F key setting k i tion Kekek No function dSV display Changeover between Remote and Auto Press for 2 seconds Standby RUN changeover Alarm latch reset AT Auto tuning START STOP Timer operation start stop ALM 1 Timer operation start stop ALM 2 Timer operation start stop ALM 3 Timer operation start stop ALM 4 Timer operation start stop ALM 5 Timer operation start stop ALM 6 Timer operation start stop ALM 7 Timer operation start stop ALM 8 Totalizer RUN HOLD Totalizer RUN LATCH Totalizer RESET Transfer of SV1 to local SV Transfer of SV2 to local SV Transfer of SV3 to
24. ON default mask eles ns I External Sets external output value manipulated Setting range 25 0 to 125 0 value FF gain Sets Feed Forward gain and bias 1 bias 2 FF bias1 FF KF1 x Input B1F B2F bias Setting range 1000 0 to 1000 0 FF bias2 zoi Parameter No Display Symbol palette 1 SV Setting range SV lower limit value to SV upper limit value Proportional band 1 palette 1 proportional band Setting range 0 0 to 999 9 ON OFF control at setting 0 Integral time 1 palette 1 integral time Setting range 0 0 to 3200 0 sec Integral control OFF at setting 0 Derivative time 1 palette 1 derivative time Setting range 0 0 to 999 9 sec Derivative control OFF at setting 0 Anti reset windup upper limit value 1 palette 1 Anti reset windup upper limit value setting Setting range 0 to 100 FS 100 FS Anti reset windup lower limit value 1 palette 1 Anti reset windup lower limit value setting Setting range 0 to 100 FS 100 FS Hysteresis setting 1 palette 1 hysteresis setting Setting range 0 to 50 FS 0 3 FS Output conver gence value 1 palette 1 Output convergence value Setting range 100 0 to 100 0 0 0 Setting value 7 palette 7 SV Setting range SV lower limit value to SV upper limit value Proportional band 7 palette 7 proportional band Setting range 0 0 to 999
25. Operation mode Operation display Channel selection display Press the gt key to enter the output value MV change mode SEL Switch by key Parameter selection display SS Channel Select a desired channel No Parameter name SEL and press SEL or amp ren l ie Ii i Setting value EA u H A Refer to the parameter omneo Channel selection display changing method for details Paramar A A A AN D Select a desired channel using the q f S gt a v A orthe Ly key and then Press DISP to return mnn press the SEL or the B_ key Press SEL to Parameter selection display register After selecting a desired parameter press Select a desired parameter using the Press DISP to or gt 4 _ orthe Y_ key and then return without ress the orthe B key making _ P y registration Parameter change Parameter change status Press the gt A orthe YW key Hi Pv to change the setting ir ER i Press the S he setting Press DISP for 2 seconds nis v Prr ul AUI K Parameter selection display Increases the set value se Decreases the set value Press DISP twice gt Moves the cursor between digits Press DISP f
26. PV1B PV2F PV2B AI1F Al1B Input Type Measurement Measurement Input Type Measurement Measurement Range C Range F Range C Range F Pt100Q 0 to 150 32 to 302 J 0 to 400 32 to 752 0 to 300 32 to 572 J 0 to 1000 32 to 1832 0 to 500 32 to 932 K 0 to 400 32 to 752 pas ETD 0 to 600 32 to 1112 K 0 to 800 32 to 1472 IEC 50 to 100 58 to 212 K 0 to 1200 32 to 2192 100 to 200 148 to 392 R 0 to 1600 32 to 2912 150 to 600 238 to 1112 B 0 to 1800 32 to 3272 150 to 850 238 to 1562 Thermocouple S 0 to 1600 32 to 2912 T 200 to 200 328 to 392 T 200 to 400 328 to 752 e To use the Zener barrier for RTD input user E 0 to 800 32 to 1472 adjustment section 5 9 is required E 200 to 800 328 to 1472 PR40 20 0 to 1800 32 to 3272 Note 1 R thermocouple 0 to 500 C Proper values may not N Ree 92 10 29e B thermocouple 0 to 400 C be displayed within PL Il 0 to 1300 32 to 2372 these ranges due to the WRe5 26 0 to 2300 32 to 4172 sensor s characteristics 14to5VDC Note 2 When using at the setting below the 0 to 5V DC minimum range stated in the table above DC voltage Oto10V DC 19999 to 99999 the input accuracy is not guaranteed 0 to 10mV DC Scaling is Note 3 In the 50 FS to 50 FS display values under 0 to 50mV DC possible 199 99 will not be displayed DC current 4 to 20mA DC 0 to 20mA DC 47 Table 4 Output
27. S each at zero span 0 0 to 125 0 at OFF or cut point 0 0 to 900 0 seconds Effect of source resistance permissible wiring resistance Thermocouple voltage input mV Power supply input V Resistance bulb input 5 Relay contact output Contact capacity 6 SSR SSC drive output ON voltage pulse output OFF Max current Load resistance 59 0 1 FS per 100Q 0 1 FS per 5009 100 or less per cable 220V AC 30V DC 3A resistance load 220V AC 30V DC 1A induction load 12V DC 10 to 15V DC 0 5V DC or less 20mA DC 600Q or over 7 DC output 4 to 20mA DC 8 Motorized valve operation pulse output 9 Digital input 10 Digital output 11 Auxiliary analog input 12 Analog re transmission output 13 Transmitter power supply output 14 Communications functions 1 x1 Recommended converter RC 77 insulted from RA Systems Corp K3SC 10 insulted from Omron Corp No of points Accuracy Linearity Load resistance Contact structure Contact capacity Contact durability No of Input Specifications Contact capacity Input pulse width Digital output1 to 3 Digital output 4 Digital output 11 to 15 General type No of Input Input signal Input accuracy Max 2 points with re transmission output 0 2 FS 0 2 FS under 600Q 1a SPST contact x 2 with interlock circuit 220V AC 30V DC 1A resistance load 220V AC 30V DC 0 3A ind
28. Sets excitation non excitation output of totalizer alarm 2 Setting range 0 Excitation 1 Non excitation Pace es Che foal Parameter Totalizer No Display Symbol Operation mode Selects operation mode from Japanese and European modes Japanese mode Calculation is made using totalize factor European mode Calculation is made based on totalizer reference time and totalizer divisor Setting range 0 JPn Japanese mode 1 EnG European mode Factory Parameter Totalizer option setting Obit Sets flickering of the totalized value at the occurrence of totalized value over Totalizer is suspended while the display flickers 1bit Totalizer operation at standby 0 Continue 1 Stop 2bit Command at power ON 0 Stop 1 Start Sbit Totalizer operation at the occurrence of erroneous input 0 Add 1 Not add bit setting 0000 to 1111 Totalizer reference time Totalizer divisor Sets reference unit time for totalizer Setting range SEC Min hour dAY Divisor for totalized value scale conversion Note Addition is not performed when 0 is selected Setting range 0 to 1000000 45 7 hoUr 45 45 45 8 9 9 Totalizer multiplier Multiplier for totalized value scale conversion Setting range 0 to 1000000 Totalizer factor Totalized value display when 100 input is continued for 1 hour Setting range 20 to 9999999 The decimal point appears a
29. Type Code Table Parameter OTYP Basic type OTYP 10 OTYP 11 Control output MV 24V DC OTYP 30 Ao1 Limit scaling Motorized control type output 1 Re transmission _ output 2 Re transmission _ Control output MV OPEN Control output MV CLOSE a OUT Current scaling Pa OUT2 mn Current scaling Open Relay Close Relay OUT1 Current SSR drive OUT2 XPS Transmitter power supply Re transmission Re OUT1 Control output eo OUT1 output 1 ii Current Limit scaling MV Current SSR drive scaling Re transmission er OUT2 output 2 Current scaling aED output scaling reny Control output Do4 MV Relay OTYP 12 OTYP 13 OU Current Re transmission te t output 1 scaling 24V DC MV Control output OTYP 31 Re transmission output 1 Ao1 Limit scaling 24V DC Control output MV OPEN Control output MV CLOSE Do4 Relay 5 Close Relay OUT2 XPS Transmitter ower supply ie OUT1 Current OUT2 XPS Transmitter power supply Open Relay 48 Heating cooling control type OTYP 50 OTYP 52
30. alizer value on oFF oFF 45 1 Selects input used for totalizer 45 2 Setting range Pv1 Pv2 Ai1 AiM Math function scale Ch8 89 90 91 is adopted when 3 AiM is selected Pv1 Sets decimal point position of totalized value display Setting range 0 to 4 Totalizer cut point Sets totalizer cut point for totalizer input The input lower than the totalizer cut point is not added Setting range 0 to 100 FS Totalizer alarm 1 type Sets alarm type of totalizer alarm 1 Setting range 0 No alarm 1 Integrated value alarm 2 Totalizer batch output 3 Totalizer batch output with auto reset Totalizer alarm 1 ON pulse width Sets ON pulse width for batch control batch output alarm for totalizer alarm 1 Setting range 0 Continuous 1 100ms 2 200ms 3 500ms 4 1 sec Totalizer alarm 1 excitation non excitation setting Sets excitation non excitation output for totalizer alarm 1 Setting range 0 Excitation 1 Non excitation Totalizer alarm 2 type Totalizer alarm 2 ON pulse width Totalizer alarm 2 excitation non excitation setting Sets alarm type of totalizer alarm 2 Setting range 0 No alarm 1 Totalized value alarm 2 Totalizer batch output 3 Totalizer batch output with auto reset Sets ON pulse width for totalized value batch output alarm for totalizer alarm 2 Setting range 0 Continuous 1 100ms 2 200ms 3 500ms 4 1 sec
31. ating Conditions Status detection Edge detection ON OFF STBY standby Standby AT Auto tuning AT start AT stop Alarm latch reset Alarm1 to Alarm 8 Release all Release all Latch hold 50 to 57 Timer operating Alarm1 to Alarm 8 ON OFF 60 R ACK Remote acknowledgement Remote Local 70 SMV Manual command Manual mode Auto mode 80 PV TRK command PV tracking ON OFF EX MV External control amount EX MV MV Switching of the active expression for Math function Lo selector expression Hi selector expression Totalizer start stop reset HOLD Run LATCH Run Reset Binary data setting to constant parameter CNO1 to CNO5 1st digit Bit position 10th digit Parameter No 50 Table 6 DO and LED display Assignments DO output LED display DO01 to DO04 C1 C2 DO11 to DO15 LDO1 to LDO5 oO Oo No setting ALM1 ALM2 ALM3 ALM4 ALM5 ALM6 ALM7 ALM8 OR of ALMs Output MV 1 Output MV 2 System fault Totalizer ALM1 Totalizer ALM2 Manual MV status EX MV command status Remote SV status Local SV status PV tracking status Normal Direct action status Auto tuning AT status Remote request status Remote acknowledge R ACk Status Not Auto status Mode OR output 1 Mode OR output 2 COIN OD or Hj oO P COIN OD o yR I O
32. ccording to TdP setting Totalizer initial value The following relation holds when the value different from the current setting is selected as the initial value of totalizer Totalized value Initial value of totalizer Setting range 1999999 to 9999999 The decimal point appears according to TdP setting Totalizer alarm 1 setting Sets the operation value of totalizer alarm 1 Setting range 1999999 to 9999999 The decimal point appears according to TdP setting Totalizer alarm 2 setting Sets the operation value of totalizer alarm 2 Setting range 1999999 to 9999999 The decimal point appears according to TdP setting Re transmission output source scale Sets the totalized value that allows re transmission output to be 100 Setting range 1999999 to 9999999 The decimal point appears according to TdP setting Baie ges Recipe Parameter content Explanation EE Factory Parameter iat No Display Symbol Name Gen ErP anaon default mask oe rEPO rcPo Recipe Sets parameter to be allocated as 46 1 allocation 1 recipe 1 Setting range 0 00 to W Z9 rCP9 Recipe Sets parameter to be allocated as 46 10 allocation 10 recipe 10 Setting range 0 00 to W Z9 dog doo Recipe Recipe parameter 1 setting for palette 0 46 15 setting 0 when palette is not used Setting range According to rCPO setting dog Recipe Recipe parameter 10 setting for palette 0 setting 9 when palette is not used
33. e is 0 to 800 C Set 0 Pvib ch8 2 800 Pv1F ch8 1 Note While it is possible to set outside the standard range the standard range settings are recommended Note There are no standard ranges for DC Volt and DC Current input Set the upper and lower limits as you wish within the range 19999 to 99999 lower limit lt upper limit Note 1 Set input sensor type PV1T ch8 4 and input range settings Pv1b ch8 2 Pv1F ch8 1 and Pv1U ch8 5 in advance of all the other settings and then reset the instrument without fail Other parameters may change when these parameters are changed but this is normal Confirm all parameter values Be sure to reset the instrument after setting the input range Otherwise improper values may be displayed Be sure to check the setting after the reset AA Control Settings Objective Operation Method Explanation M What is the control purpose To heat To cool Method x Please read if controls are not responding as you expect To heat Reverse Raising the measurement value will reduce operation output operation Set rEv1 ch2 20 C gt to REV To cool Control Type Direct Raising the meas operation put What kind of control is it PID ON OFF Explanation Set rEv1 ch2 20 urement value will in crease operation out Method PID control The output signal changes within
34. ection parameter selection and parameter setting change Lamp lights when in standby mode Lamp lights when in REMOTE mode Lamp lights when in AUTO mode Lamp lights when in MANUAL mode Decreases the setting when the set value SV is displayed on the operation screen Manual valve operation is allowed when the control output value MV is displayed on the manual mode operation screen A closing signal is output while the key is pressed Used also for channel selection parameter selection and parameter setting change Lamp lights when in standby mode Lamp lights when in REMOTE mode Lamp lights when in AUTO mode Lamp lights when in MANUAL mode During the electrical current output the lamp will not light z3 RN N N a mm E OC OC 0 EN C2 bor o02 o03 bos 05 ALN PV S N M pe MERI R S A 2 E TD Cp Op O Op g pe feat a Lt G F3 AM DISP SEL f T a as ia a 5 Display N Function ame f Basic type Heating cooling control type Motorized control type C1 Lamp Lamp lights when control Kept on while valve open output 1 is ON output OPEN is ON C2 Lamp Lamp lights when control Kept on while valve close output 2 is ON output CLOSE is ON DO1 Lamp Lamp lights when digital Lam
35. etails about the items described in this manual Content Document Reference Number Specifications Catalogue ECNO 1152 User s Manual Basic control type INP TN514206 E Operation Method User s Manual Motorized valve type INP TN514357 E User s Manual Heating cooling type INP TN514557 E Communication Communication Functions Instruction Manual Modbus for Functions Digital Controller type PXH Ce Loader Functions Parameter Loader Instruction Manual for INP TN514208 E Digital Controller type PXH The latest materials can also be downloaded at the following URL http www fujielectric com products instruments PLEASE READ FIRST SAFETY WARNINGS Please read the section Safety Warnings thoroughly before using Please observe the warnings stated here as they contain important safety details The safety warning items are divided into WARNING and CAUTION categories Mishandling may lead to death or serious Warning injury Mishandling may cause injury to the user or ZN WARNE 1 1 Limitations in Use This product was developed designed and manufactured on the premise that it would be used for gen eral machinery In particular if this product is to be used for applications that require the utmost safety as described below please take into consideration the safety of the entire system and the machine by adopting such means as a fail safe design a redundancy desi
36. extractor cut point Input data value 0 0 to 100000 100 000 Flow rate compensation with nie Ai1 X k01 k02 temperature and pressure m PV2 X k03 k04 X k03 k04 value operation without square root extraction All the inputs and constants are of the same specifications as mathematical expression 20 H selector 2 points with coefficient M1 max PV1 X k01 k02 PV2 X k03 k04 L selector 2 points M1 min PV1 X k01 k02 PV2 X k03 k04 with coefficient H selector 3 points with coefficient M1 max PV1 X k01 k02 PV2 X k03 k04 Ai X k05 k06 L selector 3 points M1 min PV1 X k01 k02 PV2 X k03 k04 Ai X k05 k06 with coefficient Input switching 2 points M1 PV1 X k02 k03 when k01 gt PV1 X k02 k03 with coefficient M1 PV2 X k04 k05 when k01 lt PV1 X k02 k03 H L selector 2 points Expression 27 or 28 is used by Di switching with Di switching function Specify 140 for Di function for switching H L selector 3 points Expression 29 or 30 is used by Di switching with Di switching function Specify 140 for Di function for switching When PV1 lt k05 M1 PV1 X k01 k02 When PV2 lt k06 M1 PV2 X k03 k04 When PV1 gt k05 and PV2 lt k06 Interpolation shown below is executed k01 k02 k06 k05 Input switching 2 points with coefficient a
37. g Ai1 As ordered 23 1 input Setting range 19999 to 99999 Ail base scale Sets the scale of base side analog Ait As ordered 23 1 input Setting range 19999 to 99999 Ail decimal Specifies the decimal point position for point position analog Ai1 input Setting range 0 to 3 No decimal point Ai1 input type Sets the type of Ai1 input For details see Setting range 16 to 18 Table 2 Ai1 input zero Sets the correction value of a zero point for point adjustment Ai1 input Setting range 50 to 50 FS Ail input span Sets the correction value of a span point for point adjustment Ai1 input Setting range 50 to 50 FS Ail input cut Sets the cut point of the square root extraction point calculation for Ai1 input In case of OFF the square root extraction is not calculated Setting range OFF 0 0 to 125 0 Ai1 input filter Sets the time constant for Ai1 input filter Setting range 0 0 to 900 0sec Ai1 linearize Ai1 input linearize enable disable setting setting Setting range OFF nrML hi C Lo C AO1 output Switches the AO1 re transmission output It is invalid when type signal the control output Setting range PV SV MV DV AiM is chosen MVRB TV AO1 output Sets the scale upper limit value of the AO1 100 0 scale upper limit output Setting range 130 0 to 130 0 AO1 output Sets the scale lower limit value of the AO1 0 0
38. gn as well as the conducting of periodical inspections e Safety devices for the purpose of protecting the human body Direct control of transportation equipment e Airplanes e Space equipment e Atomic equipment etc Please do not use this product for applications which directly concern human lives 1 2 Installation and Wiring This equipment is intended to be used under the following conditions Ambient temperature 10 C to 50 C Ambient humidity 90 RH or below with no condensation Installation category II by IEC1010 1 Pollution level 2 ava Between the temperature sensor and the location where the voltage reaches the values described below secure clearance space and creepage distance as shown in the table below If such space cannot be secured the EN61010 safety compliance may become invalid Voltage used or generated Clearance Space Creepage Space by any assemblies mm mm Up to 50 Vrms or Vdc 0 2 1 2 Up to 100 Vrms or Vdc 0 2 1 4 hazardous Up to 150 Vrms or Vdc 0 5 1 6 voltage Up to 300 Vrms or Vdc 1 5 3 0 Above 300 Vrms or Vdc Please consult our distributor For the above if voltage exceeds 50Vdc called danger voltage grounding and basic insulation for all terminals of the equipment and auxiliary insulation for warning outputs is required Note that the insulation class for this equipment is as follows Before installing please confirm that the insula
39. he deviation of MV by EX MV operation Sampling cycle Hysteresis setting Sets sampling cycle for PID operation Setting range 5 to 1000 Hysteresis value during ON OFF control time Setting range 0 to 50 FS 0 3 FS The actual cycle is dT1 x 10 ms Operation output convergence value Sets output convergence value Setting range 100 0 to 100 0 0 0 Cycle time of Control output MV1 Sets proportional cycle for control output Setting range 1 to 150 sec By designation at the time of ordering Effective only for RY output and SSR drive output Control action setting Sets a control action method NRML Normal Direct action REV Reverse action REV Preset value for control output Sets MV for stanby mode Setting range 25 0 to 125 0 Refer to Table 7 Alpha Sets 2 degrees of freedom coefficient a Setting range 300 0 to 300 0 Beta Sets 2 degrees of freedom coefficient B Setting range 0 0 to 999 9 Output limiter type setting Sets whether the value should be limited at the output limit setting or the limit should be exceeded 125 25 when the output reaches the output limit setting Output operation Upper side Lower side 0 125 0 25 0 1 125 0 Limit 2 Limit 25 0 3 Limit Limit LD1 o ES Parameter Gantastievaanat Factory Parameter ast Display Symbol Name E REAP ANA
40. ibration value Value at which valve is open all the way at which valve is Setting range 0 to FFFFF fully open Valve Allows to adjust the valve calibration OFF _ Termination of calibration command CLOSE Manual calibration of fully closed position OPEN Manual calibration of fully open position AUTO Automatic calibration pac yee Heating cooling control type exclusive param eter list Parameter Aenea Factory Parameter i No Display Symbol Name Onge Sxpanaon default mask orgs MV upper limit Sets the upper limit value of operation value on output MV Heating side heating side Setting range 25 to 125 MV lower limit Sets the lower limit value of operation value on output MV Heating side cooling side Setting range 25 to 125 Dead band Sets the dead band and overlap band for heating cooling control Setting range 100 0 to 50 0 Proportional Sets the proportional band cooling side band on Setting range 0 0 to 999 9 cooling side Integral time Sets the integral time cooling side on cooling side Setting range 0 0 to 3200 00 sec Derivative time Sets the derivative time cooling side on cooling side Derivative operation is set to OFF when setting 0 Setting range 0 0 to 999 9 sec MV upper limit Sets the upper limit value of operation value on output MV cooling side cooling side Setting range 25 0 to 125 0 MV lower li
41. iciccccisontcaienescs 11 Ch4 PLE Control palette ceceeeeecees 39 3 Usage Read before using eeeeees 12 Ch7 Flom MONitOr ceeeeeecsseeeeseeeeeseeeeees 41 4 Displays and Operation Methods 0 16 Ch8 SEF Input output definition 41 5 Switching parameters cceececeeeeeeereees 17 Ch9 545 System definition ee 41 Basic type Motorized control type Heating 6 Digital Controller Functions 0 ccee 42 cooling control type common parameter list 6 1 Alarm functions cceeeeceeeeeeeeeeees 42 Ch1 oPE Operation parameter 4 18 Table 1 Alarm Operation Type Codes 43 Ch2 Ped Control parameter 0c 20 7 Setup Procedures of the Controller 44 Che PLF Control palette ecisisticaccanateiencuses 22 Table 2 Input Codes c cialicceicdccriccseratasscnues 46 Ch7 Non Monitor sssossssesseesseessnesseeeseeseena 23 Table 3 Input Range Table Standard Range 47 Ch8 SEF Input output definition 25 Table 4 Output Type Code Table 0 0 8 48 Ch9 545 System definition ee 28 Table 5 Di Input Assignments Di1 to Di15 50 ChA ALF Alarm setting c e 30 Table 6 Do and LED display Assignments 51 ChB fof Communication 0ceee 31 Table 7 Standby Operation ceceeeee 51 ChC bar Linearize eee eee eeteeeeeeeeeees 3
42. ing range 0 to 100 FS MV upper limit value 7 Palette 7 upper limit value of operation output MV Setting range 25 0 to 125 0 MV lower limit value 7 Palette 7 lower limit value of operation output MV Setting range 25 0 to 125 0 MV upper limit value 7 on heating side Palette 7 upper limit value on heating side of operation output MV Setting range 25 0 to 125 0 MV lower limit value 7 on heating side Palette 7 lower limit value on heating side of operation output MV Setting range 25 0 to 125 0 Hysteresis 7 Palette 7 hysteresis 0 3 FS Setting range 0 to 50 FS Dead band 7 Output convergence value 7 Palette 7 dead band and overlap band 0 0 for heating cooling control Setting range 100 0 to 50 0 Palette 7 output convergence value Setting range 100 0 to 100 0 Proportional band 7 on cooling side Palette 7 proportional band on cooling side Setting range 0 0 to 999 9 Two position operation is allowed when setting 0 Integral time 7 on cooling side Palette 7 proportional band on cooling side Setting range 0 0 to 3200 0 sec Integral operation is set to OFF when setting Derivative time 7 on cooling side Palette 7 derivative time on cooling side Setting range 0 0 to 999 9 sec Derivative operation is set to OFF when setting 0 MV upper limit value 7 on cooling side Palette 7 upper limit value
43. ing the parameter loader An optional PC loader communication cable is required to use the parameter loader e Use wires and Crimp style terminals of the size shown below for connections Wire size Connection using terminal cover Parts Size e Connect 2 wires of 1 25mm or smaller in size Thermocouple E together to the same terminal as shown below Compensation wire 2 Pass through Wire 1 25mm lt or smaller the top of the cover Terminal cover Crimp style terminal Compatible wire size Fastening torque 0 25 to 1 25mm 0 8N m w w E 3 63 2mm S the bottom tS of the cover fo fo y E E Fo 5 TEs 6 oS A_ A PA Wiring Connection Terminal Connection Diagram N b 9 Current SSR SSC Current SSR SSC Transmitter output driver output driver power supply output output DO4 Motorized valve Control output 1 relay opening closing output OPEN 5 COM 6 CLOSE L lo 11 1d JOO Of OII h Of 100 to 240 V AC E 50 60 Hz 7 v mV P z DC current DC voltage Resistance Thermo Measurement value input Extended Di Do g bulb couple D111 The RCJ module must be connected D12 6 in case of thermocouple input Remove it for resistance bulb input DI13 6 DI14 s6 Auxiliary analog Val
44. is allocated as control output 3 Explanation of the 9th digit of type code and output terminal function is below uro 4 13 OUT2 OUT1 Terminal Do4 Output Current Current SSR SSC Relay or Digital output Re transmission output Control output output Kind 4 to 20 mA driver 4 to 20 mA Tir nsmitter Function Control output Control output Re transmission power Of suupply Not fitted The selection of Function is specified according to the parameter 56 Fitted Motorized valve control type Og A SB ee ea 34 H 9 1 V 0 Digit Description Notes 4 lt Dimension of front face H x W gt 96 x 96 mm 5 lt Number of control loops Function gt 1 loop motorized valve controller with PFB 1 loop motorized valve controller without PFB 6 lt Measurement value input gt Universal input 1 point Universal input 2 points el 7 lt Auxiliary input gt Not fitted DC voltage 1 point lt Version No gt 9 lt Output gt OUT1 OUT2 2 Current Not fitted Current Current Current Transmitter supply 10 lt Power supply gt 100 to 240 V AC V 11 lt Communication interface gt Not fitted 0 RS 485 R 12 lt Digital input output gt Digital input Digital output Including relay con
45. is equipment Some compo nents used on this equipment have a limited life and or may deteriorate over time The warranty period for this unit including accessories is one year if the product is used properly ony ee 2 AN Caution 2 1 Cautions when Installing Please avoid installing in the following locations Locations in which the ambient temperature falls outside the range of 10 to 50 C when equipment is in use lf the power supply is AC200V the recommended maximum ambient temperature is 45 C Locations in which the ambient humidity falls outside the range of 0 to 90 RH when equipment is in use Locations with rapid temperature changes leading to dew condensation Locations with corrosive gases especially sulfide gas ammonia etc or flammable gases Locations in contact with water oil chemicals steam or hot water If the equipment gets wet there is a risk of electric shock or fire so have it inspected by the distribu tor Locations with high concentrations of atmospheric dust salt or iron particles Locations with large inductive interference resulting in static electricity magnetic fields or noise Locations in direct sunlight Locations that build up heat from radiant heat sources etc 2 2 Cautions when Attaching the Panels e Please attach the PXH with the included Fixtures 2 pieces to the top and bottom and tighten with a screwdriver The clamp torque is approximately 0 15 N m 1 5 kg cm However
46. it deviation Range upper Lower limit imit absolute absolute Lower limit deviation on Range upper Upper limit imit deviation abso ute Lower limit with hold absolute imi Range upper pris te imit lower limit i absolute with hold with hole ane Range upper Upper limit i limit lower limit deviation deviation with hold Range upper Lower limit i limit absolute deviation Lower limit deviation with hold Range upper Upper lower limit i limit deviation deviation Lower limit absolute with hold Upper limit SV upper lower deviation limit with hold aa PV rate of 0 Lower limit change deviation i in with hold Upper lower limit p V change ratio among 5 cycles of input sampling Upper lower limit deviation ON delay with hold timer Range upper lower limit deviation OFF delay timer Upper lower limit absolute ON OFF delay timer Upper lower limit deviation Upper limit TEM The Hold Function eee rk This is an alarm for situations when the alarm does not turn deviation ON immediately and the value go to outside the range once Lower limit and then reenters within the range even when the measured See i ci value is within the range of the alarm at
47. l function is below 3 Explanation of the 9th digit o Terminal Do3 Do4 Output Kind Relay Relay OUT1 Current 4 to 20 mA SSR SSC driver PIx H 9 F 1 v fo Digit Description Notes Pid 4 lt Dimension of front face H x W gt 96 x 96 mm 9 5 lt Number of control loops Function gt 1 loop heating cooling controller 6 lt Measurement value input gt Universal input 1 point E us Universal input 2 points q 2 7 lt Auxiliary input gt Not fitted ol DC voltage 1 point 1 8 lt Version No gt 1 9 lt Output gt OUT1 OUT2 3 Current Not fitted 1 Current Current 2 Current SSR SSC drive 3 Current Transmitter supply 5 SSR SSC driver Not fitted A SSR SSC driver Current B SSR SSC driver SSR SSC drive C 10 lt Power supply gt 100 to 240 V AC V 11 lt Communication interface gt Not fitted 0 RS 485 R 12 lt Digital input output gt Digital input Digital output Including relay control output 2 4 points Di1 to Di4 2 points Do3 Do4 0 4 points Di1 to Di4 4 points Do1 to Do4 A 9 points Di1 to Di4 Di11 to Di15 9 points Do1 to Do4 Do11 to Do15 I B 13 lt Additional specifications gt Not fitted 0 OUT2 Current 4 to 20 mA SSR SSC driver Trensmitter Control output or Digital output Function Control output or Digital output Control output or Re transmission output Control output Control output or Re transmission out
48. ls see setting Setting range 0 to 38 Table 1 34 1 Alarm 1 hysteresis setting Sets alarm hysteresis for alarm 1 0 3 FS Setting range 0 00 to 50 00 FS Alarm 1 delay time setting Sets delay time for alarm 1 Setting range 0 to 9999 Sets alarm options for time units The unit of time is selected by alarm options Alarm 8 type setting Sets the alarm type for alarm 8 Setting range 0 to 38 Alarm 8 option setting Sets alarm options for alarm 8 Setting range 0000 to 1111 Switching time unit 0 seconds 1 minutes non excitation output Abnormal input Latch Alarm 8 hysteresis setting Sets alarm hysteresis for alarm 8 0 3 FS Setting range 0 00 to 50 00 FS Alarm 8 delay time setting Sets delay time for alarm 8 Setting range 0 to 9999 Sets alarm options for time units The unit of time is selected by alarm options 30 ChB Lo i Communication Parameter No Display Symbol RS485 station No c Exol Factory Parameter Name ontent Explanation default mask Notes Specifies the RS485 communication station No Setting range 0 to 255 does not operate with STn4 0 RS485 communication speed Selects the communication speed for RS485 communication Setting range 96 9600 bps 192 19200 bps 384 38400 bps RS485 bit format Selects the bit format for RS485 communication Setting range
49. mit Sets the lower limit value of operation value on output MV cooling side cooling side Setting range 25 0 to 125 0 Control output Sets the proportion cycle of control output 30 0 RY proportion cycle cooling side 2 0 SSR d on cooling side Setting range 1 to 150 sec Control Sets the automatic system of control NRML actuation output cooling side system on NRML Normal actuation cooling side REV Reverse actuation Control output Sets the output value at control standby volume on cooling side cooling side Setting range 25 0 to 125 0 Output limiter Sets whether the output value on cooling type setting side should be limited or exceeded scale on cooling side off when the limit setting is reached 125 25 Setting range 0 to 3 ee es Parameter No Display Symbol Expl Factory Parameter N Nome Content Explanation default mask otes Setting value 1 Palette 1 SV Setting range SV lower limit value to SV upper limit value Proportional band 1 Palette 1 proportional band Setting range 0 0 to 999 9 ON OFF control at setting 0 Integral time 1 Palette 1 integral time Setting range 0 0 to 3200 0 sec Integral control OFF at setting 0 Derivative time 1 Palette 1 derivative time Setting range 0 0 to 999 9 sec Derivative control OFF at setting 0 Anti reset windup upper limit value 1 Palette 1 Anti rese
50. nd M1 PV1X k01 k02 k05 k05 interpolation function k06 k05 X PV2 X k03 k04 x PV1 X k01 k02 k05 ex note k05 Input switching upper value k06 Input switching lower value Calorie calculation M1 PV1 X k01 k02 PV2 X k03 k04 X Ai1 X k05 k06 1 Square root extraction cut point can be set with k06 2 Square root extraction cut point can be set with k07 53 Table 10 Control template TPLT Control template SV selection Math function oop basic PID control with Math function oop basic SV selection PID control with Math function oop basic PID control Basic type oop basic SV selection PID control oop input selection PID control with Math function oop motorized valve control with Math function oop SV selection motorized valve control with Math function Motorized control type oop motorized valve control oop SV selection motorized valve control oop heating cooling control with Math function oop SV selectable heating cooling control with Math function Heating cooling oop heating cooling control control type oop SV selectable heating cooling control 54 Troubleshooting Please read when the display does not make sense Error indications This Controller has a display function to notify when the equipment is not functioning properly When a problem occurs remove the cause immediately Once the ca
51. on cooling side of operation output MV Setting range 25 0 to 125 0 MV lower limit value 7 on cooling side Palette 7 lower limit value on cooling side of operation output MV Setting range 25 0 to 125 0 40 Cha PLS Control palette Parameter nr eer Factory Parameter ief Display Symbol Name onient xpianauon default mask QIES rEF rEF1 PID switch Palette 1 PID switch point O FS 08 1 point 1 Setting range 25 to 125 FS PID switch Palette 7 PID switch point O FS 14 1 See 5 6 point 7 Setting range 25 to 125 FS PAA Ch7 iion Monitor Parameter Sealenee eee Factory Parameter a No Display Symbol OMNE EXRANAION default mask otes I MV on MV monitor on heating heating side MV on MV monitor on cooling cooling side Input output definition Parameter aeeoea Factory Parameter Sa Display Symbol Name Onen EXR anauon default mask otes 92 Tre TPLT Template Specifies control template 53 25 10 The range of effective setting 50 Single loop heating cooling control with math function 51 Single loop SV selection heating cooling control with math function 53 Single loop heating cooling control 54 Single loop SV selection heating cooling control 93 o YP oTYP Output type Selects the control output selector type As ordered 25 11 Setting range 50 to 55 Note Be sure to reset or turn on the power after the parameter setting is changed
52. or 2 seconds gt 9 Operation mode Operation display X Parameter display in the text X Note that the display is not automatically returned from parameter setting display etc to the operation display Example Parameter symbol STbY ch1 5 Sk aa Channel No 6 Parameter No 5 Switching parameters OO Oa E R E O E E Pv EH O0 CO OD C E R R T S E A 6 5432 l 27 e i wu i Soooooooooo amp amma Totalized uni Fi F2 FAM DSP value Fi F2 z AM DISP PV totalized value SEL gt a v SV MV sl lt _ 7 switching ex s switching OO 0 a E R E R E E Operation mode Operation display Totalizer instantaneous value totalized value oC OO T T PV Math operation result mr orin r Cur Channel selection or rP Loe wu PFb fol wo Press SEL SEL or Press SEL SEL to confirm Note py r in PS forP Press DISP Pl to confirm Ch4i 4 I is displayed only when F is specified for the 5th digit of the code symbols A D S displays only Ch3 Or ChF 7 2 is displayed only when D S is specified for the 5th digit of the code symbols Password After selecting a entry Ole OGL desired channel AHE ye press SEL or a SEL pee gt
53. ore making measurements etc x It takes about 7 seconds from power ON to establish a stable output Installation mounting External Panel Cut Dimensions Outline dimensions drawing 96mm type unit mm Unit mm 1079 5 ee Mounting fixture 92 0 0 96 E C C CO CE E E c c talc Bg Waterproof packing lt Terminal RCJ module P screw M3 ane RCJ module for PV2 PC Loader interface u ul 100MIN 49 60 61 72 13 24 I 000 I il I 0000 Note In the case where a paint finish will be applied after panel hole punching take care of the finished dimensions Incase of using the packing in installation please note the below procedure The overtightening condition may occur and it makes the enclosure strained Turn the screw until the center of mounting fixture spilits into right and left and clanking soundsheard approx 5 times The clamping torque will be fitted automatically in this condition Depending on the models some terminals will remain unused terminals 37 to 60 A terminal block should not be installed onto these unused terminals A dummy cover will be installed Use a PC loader interface when us
54. p lights when digital DO2 Lamp output 1 to output 4 DO1 to joutput 1 to output 4 DO1 to DO3 Lamp DO4 is on DO4 is on DO4 Lamp The lamp functions are The lamp functions are DO5 Lamp assignable by the user assignable by the user ALM Lamp Lamp lights when alarm is Lamp lights when alarm is SV MV Lamp activated Indicates the status shown in the sub segment display SV Set value MV Control output value activated Display the type of data appearing in the lower 5 digit display section SV lights Set value MV lights Control output MV MV lights x lights Valve opening feedback MVRB MV lights blink Estimated valve opening estimated MVRB nf Alc Name Function Basic type Heating cooling control type Motorized control type Measurement value PV display red Set value SV control output MV or value opening MVRB display section orange Sub segment display Bar graph display Displays the measurement value PV during operation Also displays the parameter name when setting parameters Displays the set values SV or control output value MV during operation Displays lower 5 digits of the totalized value in totalized value display During operation When TPLT ch8 92 is set at 10 13 16 50 or 53 the loop number is displayed When TPLT ch8 92 is set at 11 14 51 54 the SV number is displayed Setting paramete
55. parameter block For parameter block Select key selection parameter selection parameter selection and parameter selection and parameter setting change setting change P key Select a digit of data value Select a digit of data value Digit selection key for a desired setting change for a desired setting change Se Function Name a Basic type Heating cooling control type Motorized control type Akey Increases the data value of a Increases the data value of a Up key desired setting change desired setting change Changes the value of aset Increases the setting when value SV when in the set value SV is operation displayed on the operation Used to select channels screen and parameters and Manual valve operation is change allowed when the control parameter settings in the output value MV is setting mode displayed on the manual mode operation screen An opening signal is output while the key is pressed Used also for channel selection parameter selection and parameter setting change Wkey Decreases the data value of Decreases the data value of Down key a desired setting change a desired setting change STBY Lamp R Lamp A Lamp 3 M Lamp Decreases the setting when the set value SV is displayed on the operation screen Decreases the setting when the control output value MV is displayed on the operation screen in manual mode Used also for channel sel
56. put Control output power suupply The selection of Function is specified according to the parameter 58 Not fitted Fitted Specificaitons 1 Power voltage 100 15 to 240V AC 10 50 60Hz 2 Power consumption 100V AC 15VA or less 220V AC 20VA or less 3 Normal operation conditions Ambient temperature Ambient humidity Storage temperature Warm up time 4 Input Input signal Input indication accuracy Thermocouple Resistance bulb DC voltage DC current Input sampling cycle Input impedance 10 C to 50 C 90 RH or less no dew condensation 20 C to 60 C 15 min or longer RTD thermocouple DC voltage DC current multi input Refer to Table 3 0 1 of FS 1digit 1 C or 1 5 C whichever is higher however Thermocouple B 0 to 400 C 5 of FS 1digit 1 C Thermocouple R 0 to 500 C 1 of FS 1digit 1 C 0 1 of FS 1 digit or 0 25 C whichever is higher 0 1 of FS 1digit 50ms Thermocouple voltage mV 1MQ or more Voltage Current Allowance input voltage Voltage V Current 1IMQ 2502 35V 10V DC 25mA DC Thermocouple resistance bulb voltage mV 5V Noise reduction ratio Normal mode Common mode Input value correction User adjustment Square root extraction First order lag filter 40dB 50 60Hz or more 120dB 50 60Hz or more 50 of F
57. rs Parameter number is displayed Display higher 2 digits of the totalized value in totalized value display Displays a bar graph of control output MV during operation Displays measurement value PV on the operation screen Displays channel name when channel is selected Displays parameter name while parameter selection setting is in progress Displays set values SV control output MV or valve opening feedback MVRB on the operation screen Displays parameter setting while parameter selection setting is in progress Display switching between control output and valve opening can be set with parameter dSPT ch9 78 Displays lower 5 digits of the totalized value in totalized value display During operation When TPLT ch8 92 is set at 30 or 33 the loop number is displayed When TPLT ch8 92 is set at 31 or 34 the SV number is displayed Setting parameters Parameter number is displayed Display higher 2 digits of the totalized value in totalized value display Displays control output MV or valve opening feedback MVRB with a bar graph during operation During the electrical current output the lamp will not light 15 4 Displays and Operation Methods When in Standby Operation To Operate standby mode set STbY ch1 to 5 to ON Operation during standby mode No alarm will be activated During Operation Mode Hi
58. rs in alarm 1 10P chA 2 alarm equipment function For unit abnormalities see the page on Troubleshooting alarm 8 80P chA 37 De energizing function Transmits to the alarm relay by excitation non excitation of an alarm output When function is ON output will be by non excitation alarm 1 10P chA 2 alarm 8 80P chA 37 ON delay function De energizing function ON 7jgpeeeegmmesseeesneeees Qammmeame i A A Alarm operation OFF q a ON DOE m Normal alarm relay operation OFF 1 ON Be sis oe tee te ON delay time relay operation OFF e p Yy lt _ gt ON delay setting time ON pasazsaassazazasar inati A Alarm determination OFF i ON asassasassssaasaar 3 ra F i With De energizing function OFF OFF i ON gasazzsazaasag anaana i p izj i A With De energizing function ON OFF l When the power is off even when the non excitation function is ON there will be no output during standby Function will be OFF 42 Table 1 Alarm Operation Type Codes Parameter 1TP chA 1 to 8TP chA 36 1TP to 8TP Alarm Type Operation Diagram 1TP to 8TP Alarm Type Operation Diagram Range 0 No alarm a PV upper lower limit absolute Upper limit Range upper absolute limit lower lim
59. s on the upper part of the terminal For the PXH9 please attach the Fixtures to the attachment holes in the center of the main unit 2 3 Cautions for Wire Connections Perform wiring beginning from the left side terminals No 1 to No 12 Do not connect anyting to the unused terminals Do not use them as relay terminals For thermocouple input use the appropriate compensating cable for resistance bulb sensors use wires with small resistance and without any resistance difference among the three wires To avoid noise conductor effects do not use input signal wires in close proximity with electric power lines or load lines Use input signal lines and output signal lines that are separated from each other and are shielded If there is a lot of noise from the power source adding an insulation transducer and using a noise filter is recommended Example TDK ZMB22R5 11 noise filter Always attach a noise filter to a panel that is grounded securely and keep the wiring between the noise filter output side and the measuring equipment power terminal wiring to a minimum length Please do not attach fuses and switches etc to the noise filter output wiring since doing so will decrease the filter s effectiveness Twisting the measuring instrument wiring is effective when connecting the wires The shorter the pitch of the twist the more effective the connection is against noise It takes preparation time before operation starts for the contac
60. t change the setting values SV OED l the key operation is not performed for 10 seconds while the SV value is flickering the value returns to the previous setting value SV STbY ch1 5 OFF Control output will be produced in accordance with the PMv1 ch2 to 22 parameter eMip Be aware that in standby mode the unit s warning alarm will not be activated either Display STBY LED stays ON PV SV display can be kept OFF During standby Return fromstandby Operation output Outputs value designated by PMv1 Bumpless restart from PMv1 Alarm output All outputs are OFF Timer operation All operations are OFF Zero start Comes Eo change the output value MV on Press the key to enter the setting value SV change mode A M key Hold operation Initial start Latch operation All operations are OFF Initial start released Non excitation output operation All outputs are OFF Non exitation operations are invalid Work in non excitation operation Communication Not affected by standby status Analog re transmission output OmA Digital output Do All outputs are OFF Digital input Di Status detection Operated Edge detection Not operated Control mode Not affected b y standby status Display Can be selected from ON OFF ON Parameter Setting
61. t HOLD Outputs to follow MV Lo Turns on CLOSE signal UP Turns on OPEN signal EXMV Controls to join EXMV setting Poff Turns off OPEN and CLOSE signals allowing MV to join MVRB LED C1 assignment Allocates indicator LEDs LED C2 Setting range 0 to 255 assignment Bar graph Select value to display on bar graph display type MON No display MV Control output MVRB Valve opening degree feedback value MVRB Operation Select value to indicate at 5 digit display screen display on bottom of operation screen type O Control output MV 1 Valve opening degree feedback value MVRB Note Be sure to reset or turn on the power after the parameter setting is changed Bae as motorized valve definition Display Symbol ater pean deiaut mask ul YP VTYP Valve type Sets control type of motorized valve Fb 44 1 Fb PFB control Fb Sr PFB estimation control Sri Estimation control 1 Sr2 Estimation control 2 Turning on power closes valve all the way Travel time Sets time required for valve 30 0S 44 to move over full stroke Automatically set in case of automatic adjust of valve Setting range 5 0 to 300 0 sec 44 2 PGP Dead band of Sets dead band of OPEN CLOSE signals 3 valve operation Setting range 0 5 to 100 0 AdPC_ Calibration value Value at which valve is closed all the way 44 6 at which valve is Setting range 0 to FFFFF fully closed Cal
62. t for digital output 11 Assignment for digital output 15 Note Be sure to reset or turn on the power after the parameter setting is changed Sets assignments for DO1 DO4 DO11 DO15 Setting range 0 to 255 28 For details see Table 6 System definition Parameter Sana Eana Factory Parameter Nai No Display Symbol Name Omen SP anaon default mask oles f LED C1 2 assignment LED C2 22 assignment LED DO1 Allocates indicator LEDs For details see assignment Setting range 0 to 255 Table 6 LED DO5 assignment LED ALM assignment Operation Sets display items during operation display setting Setting range 000 to 111 A PV totalized value Totalizer instantaneous value totalized value PV Math calculation result Parameter Skips not display unnecessary mask setting parameters Reset Resets the main unit command ON Reset OFF RUN Note Be sure to reset or turn on the power after the parameter setting is changed Eao 5 ChA ALi rom Parameter No Display Symbol Alarm 1 option setting i Alarm setting Name Content Explanation Factory default Sets alarm options for alarm 1 Setting range 0000 to 1111 Switching unit time 0 seconds 1 minutes non excitation output Unit abnormal Latch Parameter mask Notes 1 iP 1TP Alarm 1 type Sets the alarm type for alarm 1 34 1 For detai
63. t output when power is turned on If using it as a signal to an external interlock circuit please couple it with a delayed relay Concerning the output relay connecting the maximum rated load will shorten the relay s life so please attach an auxiliary relay If the output operation frequency is high selecting a SSR SSC drive output type is recommended Proportional cycles Relay output 30 seconds or more SSR SSC drive output 1 second or more When inductive loads such as magnetic opening closing equipment etc as relay output equipment are connected use of Zetrap manufactured by Fuji Device Technology Co Ltd is recommended in order to protect the connection points against opening closing surges and to ensure long term use Model names ENC241D 05A For 100V power voltage ENC471D 05A For 200V power voltage Attachment position Please connect between the relay control output connection points Refer to Fig 5 If using a thermocouple input make sure that an RCJ module is connected as shown in Fig 5 If an RCJ module is not connected the temperature measurement cannot function To use resistance bulb input instead of thermocouple input remove RCJ module Keep the removed RCJ module and do not forget to mount it back again when input is changed Take wiring resistance into consideration when using a Zener barrier In applying mV voltage do not remove the RCJ module It is dangerous to make an SSR connection when the ou
64. t windup upper limit 100 FS value setting Setting range 0 to 100 FS Anti reset windup lower limit value 1 Palette 1 Anti reset windup lower limit 100 FS value setting Setting range 0 to 100 FS MV upper limit value 1 MV lower limit value 1 Palette 1 upper limit value of operation output MV Setting range 25 0 to 125 0 Palette 1 lower limit value of operation output MV Setting range 25 0 to 125 0 MV upper limit value 1 on heating side Palette 1 upper limit value on heating side of operation output MV Setting range 25 0 to 125 0 MV lower limit value 1 on heating side Palette 1 lower limit value on heating side of operation output MV Setting range 25 0 to 125 0 Hysteresis 1 Palette 1 hysteresis 0 3 FS Setting range 0 to 50 Dead band 1 Output convergence value 1 Palette 1 dead band and overlap band for 0 0 heating cooling control Setting range 100 0 to 50 Palette 1 output convergence value Setting range 100 0 to 100 Proportional band 1 on cooling side Palette 1 proportional band on cooling side Setting range 0 0 to 999 9 Two position operation is allowed when setting 0 Integral time 1 on cooling side Palette 1 integral time on cooling side Setting range 0 0 to 3200 0 sec The integral operation is set to OFF when setting 0 Derivative time 1 on cooling side MV upper limit
65. the range of 0 to 100 according to PID calculation A stable control without a control offset can be achieved Please execute auto tuning manually The optimal P 1 D will be calculated automatically The PID value may also be set manually ON OFF control 2 position control Output is either ON 100 or OFF 0 Suitable when frequent output switching is inconvenient AR Set ch2 P1 ch2 1 to 0 0 Table 2 Input Codes Parameter PV1T PV2T AHT Input Type Code Input Type Code Resistance bulb oN 12 PL Il 13 Pt100Q IEC 1 WRe5 26 14 DC voltage Thermocouple e 1to5V DC 16 S 2 0 to 5V DC 17 PK 3 0 to 10V DC 18 PH 4 0 to 10mV DC 19 B gt 0 to 50mV DC 20 Ss 6 T 7 DC current E 8 4 to 20mA DC 26 PR40 20 9 0 to 20mA DC 27 Potentiometer e Valve opening feedback 23 with moving average filter e Valve opening feedback 24 Note 1 For PV1 and PV2 the potentiometer code 23 24 can not be selected Note 2 If with PFB PILC 5th digit D Ai1 can be set to potentiometer code 23 24 only e If without PFB PILC 5th digit S Ai1 can be set to DC current code 16 18 only Note 3 If on account of noise ect the valve opening degree feedback input suffers from an abrupt change select Ai1T 23 with moving average filter AGS Table 3 Input Range Table Standard Range Parameter PV1F
66. the time the power is er timt deviation turned on Notes Upper lower limit After changing the alarm type confirm the alarm setting absolute Amara SS alse values with hold Alarm setting values may change by changing the alarm nE type but this is normal apperener imit S Caution The alarm latch function cannot be used when winno using the OFF delay timer ALn Indicates the AL1 ch1 10 to AL8 ch1 31 alarm Upper limit absolute setting values Lower limit deviation An H Indicates the A1 H ch1 12 to A8 H ch1 33 alarm with hold setting values e An L Indicates the A1 L ch1 11 to A8 L ch1 32 alarm Upper limit deviation setting values Lower limit absolute e dLYn Indicates the 1dLY chA 4 to 8dLY chA 39 alarm with hold ON delay setting values AON setup Procedures of the Controller Does the input sensor type match the sensor input setings Select the sensor in use from Table 2 and set to PV1T ch8 4 Example Set PviT ch8 4 to 7 in the case of a T thermocouple 2 Are the input range settings in the appropriate range for the sensor in use The standard ranges for each sensor are shown in Table 2 Select the appropriate temperature range for the equipment in use and set the upper and lower limit values Lower limit gt Pvib ch8 2 Upper limit Pv1F ch8 1 Not necessary if input was specified when ordered Example If the temperature rang
67. tion class for equipment meets usage requirements Internal Circuit Digital output 1 2 Digital output 3 Digital output 4 Auxiliary analog Input 1 Ai1 Digital output 11 to 15 Output 1 Current SSR driver Basic insulation 1500VAC Be ne Digital input 11 to 15 Functional insulation 500VAC Transmitter power supply eas No insulation RS485 In cases where damage or problems with this equipment may lead to serious accidents install appro priate external protective circuits As this equipment does not have a power switch or fuses install them separately as necessary Main power switch 2point Breaker fuse rating 250V 1A For power supply wiring use wire equal to 600V vinyl insulation or above To prevent damage and failure of the equipment provide the rated power voltage To prevent shock and equipment failure do not turn the power ON until all wiring is complete Before feeding power confirm that clearance space has been secured to prevent shock and fire with the equipment Do not touch the terminal while the machine is on Doing so risks shock or equipment errors Never disassemble convert modify or repair this equipment Doing so carries the risk of abnormal operation shock and fire 1 3 Maintenance When installing and removing the equipment turn the power OFF Failing to do so may cause shock operational errors or failures Periodic maintenance is recommended for continuous and safe use of th
68. tput is set at 4 20mA because the output will be kept ON even when the MV display shows 5 Make sure to confirm the setting and the wiring before making the SSR connection When the transmitter power supply model is selected the external wiring will be connected as Fig 6 l i a 4 to 20mA DC T Pa _ 7 Transmitter i power supply Zetrap Q Trans output mitter Be 33 4 Input type code 26 ol ea 4 to 20mA DC Connected 36 Input impedance 2509 externally JLo i qe 1 1 Terminal Main unit RCJ module RCJ module for PV2 Fig 6 External wiring for the model with the transmitter power supply Fig 5 Attachement position of Zetrap and RCJ module 2 4 Key Operation Cautions Operations during Abnormality The alarm function does not work properly when an abnormality takes place unless the settings are made correctly Always verify its setting before operation If the input wiring breaks the display will read UUUU When replacing the sensor always turn the power OFF The PV display will read UUUU or LLLL when over range or under range during input However if the display limit is smaller than the over range under range the fixed number 19999 or 99999
69. trol output a3 4 points Di1 to Di4 2 points Do3 Do4 4 points Di1 to Di4 4 points Do1 to Do4 9 points Di1 to Di4 Di11 to Di15 9 points Do1 to Do4 Do11 to Do15 pa uro 13 lt Additional specifications gt Not fitted 0 1 Two universal input points and B for the 12th digit cannot be specified at the same time Select 2 universal input points when using external setting input RSV 2 D for the 5th digit and 1 for the 7th digit cannot be specified at the same time 3 Use Do4 for control output If 2 or 3 Do points are required for event output specify code A and if 4 to 8 Do points are required specify code B Terminal Do4 OUT1 OUT2 Output Rela Current Current Kind y 4 to 20 mA 4 to 20 mA Trensmitter Function Used for power valve Re transmission Re transmission suupply open close output output output Not fitted Fitted The selection of Function is specified according to the parameter 57 Heating cooling control type Digt gt 12345678 9 10111213 1 2 for the 6th digit and B for the 12th digit cannot be specified at the same time 2 One digital output Do4 or 2 points Do3 and 4 is occupied when relay is allocated as control output type code and output termina
70. ts the full side scale of PV1 input As ordered Setting range 19999 to 99999 i Factory Parameter Name Content Explanation default mask Notes For details see Table 3 PV1 base scale Sets the base side scale of PV1 input As ordered Setting range 19999 to 99999 For details see Table 3 PV1 decimal point position Specifies the decimal point position of PV1 As ordered input Setting range 0 to 3 No decimal point PV1 input type Sets the type of PV1 input Setting range 0 to 27 For details see Table 2 Pv1 unit Sets the measurement unit non No unit F F unit C C unit PV1 input zero point adjustment Sets the correction value of a zero point for PV1 input Setting range 50 to 50 FS PV1 input span point adjustment Sets the correction value of a span point for PV1 input Setting range 50 to 50 FS PV1 input cut point Sets the cut point of square root extraction calculation for PV1 input In case of OFF the square root extraction is not calculated Setting range OFF 0 0 to 125 0 Pv1 input filter PV1 linearize setting Sets the time constant for PV1 input filter Setting range 0 0 to 900 0 sec PV1 input linearize enable disable setting OFF Setting range OFF nrML hi C Lo C PV2 full scale Sets the full side scale of PV2 input As ordered Setting range 19999 to 99999 For details
71. tting 3 Press the function key when 62 is selected and the display jumps to the specified parameter Setting range l 01 to Z Z9 zA 9 Control parameter Expl Factory Parameter Name Content Explanation default mask Notes Parameter Symbol No Display Proportional band Setting range 0 0 to 999 9 ON OFF control at setting 0 Integral time Setting range 0 0 to 3200 0 seconds Integral control OFF at setting 0 240 0 Derivative time Setting range 0 0 to 999 9 seconds Derivative control OFF at setting 0 60 0 Anti reset windup Upper limit setting value Anti reset windup Lower limit setting value Integration cut point upper limit setting value Setting range 0 to 100 FS Integration cut point lower limit setting value Setting range 0 to 100 FS 100 FS 100 FS Sets by devia tion from SV Sets by devia tion from SV SV value upper limit Sets upper limit SV Setting range 25 to 125 FS 100 FS SV value lower limit Sets lower limit SV Setting range 25 to 125 FS O FS MV value upper limit Sets upper limit MV Setting range 25 0 to 125 0 FS 105 0 MV value lower limit Sets lower limit MV Setting range 25 0 to 125 0 FS MV change ratio limit Sets the limit value of deviation of MV DMV in one control cycle 50ms Setting range 0 0 to 150 0 0 0 No limit Limit is not applied to t
72. uctive load 100 000 times or more under rated load Max 9 points Non voltage contact or transistor input 12V DC 2mA 200ms or more 1a SPST contact 220V AC 30V DC 1A resistance load 1c SPDT contact 220V AC 30V DC 1A resistance load 1a SPST contact 220V AC 30V DC 1A resistance load 1 point 1 to 5V DC 0 to 5V DC 0 to 10V DC 40 2 FS Motor operated valve control type Number of input points Input signal Input accuracy Resistance range Resolution No of output Output signal Accuracy Linearity Load resistance Output contents Scaling function No of output Rating RS 485 Interface Protocol Transmission speed Transmission distance Transmission method Data format Modbus RTU is a trademark of Modicom 260 5 21 Valve opening feedback signal potentiometer 1 0 FS 100Q to 10kQ 3 wire system 0 1 FS 2 point at max Current output 4 to 20mA DC 0 2 FS 0 2 FS under 600Q PV SV DV MV AiM MVRB TV Provided 1 point 24V DC 17 to 30V DC max current 23mA short circuit protection Modbus RTU standard 9600bps 19200bps 38400bps Max 500m total connected length Asynchronous Half duplex bit serial Data length 8 bits odd even none http www ras co jp http www omron co jp
73. use has been removed turn the power OFF then ON again Display Cause Control Output Thermocouple sensor wire broken taiii RTD wiring broken The value of brd1 CH9 35 is to be the control uuu amp PV value above upper limit 5 FS or more output MV RCJ sensor not attached thermocouple input Kind of output peii RTD sensor between A B short circuited Ror EO OFF ma ewer imit value ae AO Sees The PV value is at the lower limit of 5 FS or lower UP ON or upper limit value of the AO EXMV When PV value is under 199 99 Control continues pea Note When a resistance bulb is used Lid t Note Control continues until below 5 FS is not displayed even if under 150 C Burnout occurs at below 5 FS PV not Standby mode STbo ch9 30 1 The value of PMv1 CH2 22 is to be the control displaying output MV i 1 9999 eee Control continues h F or a S smalgr hanoverrangs grunger Note Control continues until under 5 FS or V a 99999 as 105 FS Correct The main unit was not reset or the power was not PV not turned on after the scale setting was changed displayed When the key operation is not functioning properly Key operation may not be performed in the following cases Status Remedy LoC setting does not allow the parameter the display Set LoC ch1 34 at 0 Set the parameter of PS1 at F1C3 Forgot password Set parameters PAS1 and PAS2 ch9 1
74. ve opening DI15 6 input feedback input COM 100 DO11 DO12 DO13 3 DC voltage l 0 Potentiometer D014 AS D015 I O BO com v mV Resistance Thermo DC current DC voltage bulb couple The RCJ module must be connected in case of thermocouple input Remove it for resistance bulb input z Ei Usage Read before using Operating parts and their functions lt A WS CT CAC CAC CN CO OU LO oe oS a X CE XS i Fl FR R AM DISP Sib bi Operation Part aS N Function ame Basic type Heating cooling control type Motorized control type F1 key Assignable by the user Assignable by the user F2 key Assignable by the user Assignable by the user F3 key Assignable by the user Assignable by the user A M key Switches between AUTO Switches between AUTO AUTO MANUAL mode and MANUAL mode mode and MANUAL mode switch key DISP key Switches display between Switches the display switch display key the set value SV control between set value SV output MV control output MV and Press the key to return valve opening feedback from the setting mode to MVRB the operation mode Press the key to return operation screen from the setting mode to the operation mode operation screen SEL key For

Download Pdf Manuals

image

Related Search

Related Contents

製品マニュアル(詳細スペック)  EPSON LP-S9000 取扱説明書1 操作編  GEM フレックスコイル(1.5T)  Aimco Brakes Scuba Diving Equipment 100 User's Manual  超音波診断装置 計画停電時の注意事項(PDF:176K)  MST-700 Multi Switch Tester - Athens Technical Specialists Inc.  Guía de usuario ANM 2004 MF y ANM 2008 MF (ESP)  Téléchargez 360 RSE  MEGA SPOTLIGHT - Gander Mountain  製品安全データシート  

Copyright © All rights reserved.
Failed to retrieve file