Regmaster Reg6 AVR Manual

image

Contents

1. He Summit Systems REGMASTER AVR Limited REGMASTER REGULATION MASTER Generator Automatic Voltage Regulator AVR Installation User Manual Summit Systems REGMASTER AVR Limited Congratulations All Regmaster products are designed and developed using advanced technology to bring you durable products with most advanced features To ensure you get the best value for your money Regmaster manufactures products to international safety and quality standards To get the best performance and service from this product remember to carefully read and adhere to the instructions INSTRUCTIONS Reg 6 is a general purpose or universal automatic voltage regulator AVR designed for power generating sets of 1OKVA up to 2 500KVA ratings It can be installed in all generators with brushless excitation alternators It is a perfect replacement for Leroy Somer ECC Ansaldo Newage Series 3 4 and 6 Mitsubishi Electric Pirelli Caterpillar and Contrology AVRs See wiring diagrams and installation steps A SAFETY MEASURES a Reg 6 is easy to install and maintain However INSTALLATION MUST BE CARRIED OUT BY QUALIFIED PERSONS b Reg 6 is protected with one fuse For fuse replacement strictly adhere to the fuse rating as written beside the fuse c Always install reg 6 in an environment that is Ventilated Not exposed to direct sunlight or heat source Away fr
2. IF THE COIL RESISTANCE READING IS LESS Summit Systems Limited iii iv v vi REGMASTER AVR THAN 3 2 DO NOT CONNECT REG 6 OR ANY AVR TO IT An exciter winding resistance less than 3 Q indicates that the exciter winding is shorting or weak It will damage an AVR connected to it due to excess current The exciter coil should be replaced or taken for rewinding With the generator off a Connect N of Reg 6 to Neutral terminal b Connect L of Reg 6 to Live terminal c Connect X of Reg 6 to positive of exciter terminal d Connect XX of Reg 6 to negative of exciter terminal FOR GENERATORS ORIGINALLY USING CENTRE TAPPED OR HALF WINDING TAPPINGS SUCH AS NEWAGE SERIES 6 OF STANFORD ALTERNATORS CONNECT N AND L OF REG 6 TO THE LI AND L2 TERMINALS CONNECTED TO PIN NUMBER 7 AND 8 OF NEWAGE SERIAL 6 SX 460 TURN THE VOLTS AND STAB TUNING KNOBS TO FULL OFF ANTICLOCKWISE POSITION USING PRESISION SCREWDRIVERS PROPERLY AND PATIENTLY GO THROUGH THE INSTALLATION STEPS i TO iv ABOVE TO CONFIRM THAT CONNECTIONS ARE PROPERLY MADE FAULTY OR WRONG CONNECTIONS CAN CAUSE DAMAGE TO THE AVR OR GENERATOR Start the generator The red bulb in Reg 6 lights to indicate that power is present in the AVR and generator Once normal speed is reached slowly adjust the VOLT knob of Reg 6 and watch the voltage on the generator panel voltmeter and your multimeter set at 700 volts Graduall
3. at full load it could come to 50 Hz WARRANTY Reg 6 AVRs undergo rigorous and uncompromising tests before they are introduced into the market We hereby warrant to the original retail purchaser subject to the conditions set forth below that should Reg 6 prove defective by reason of improper workmanship or materials within ninety days from the date of purchase Regmaster will replace or repair at her option the Reg 6 AVR without charge for parts or labour for a 10 handling charge Any such replacement or repair will carry a thirty days limited warranty from the date of replacement or repair Summit Systems REGMASTER AVR Limited This warranty is subject to the following conditions i The Reg 6 AVR MUST NOT have been previously internally altered repaired or serviced by anyone other than Regmaster or any of her authorized agents and the AVR MUST NOT have been subject to accident abuse misuse or have been operated or installed in a manner contrary to the accompanying instructions If the AVR unit is connected contrary to instruction to an exciter winding of less than 3 Q resistance value any damage to the AVR is not covered by this warranty This cause of damage will be detected when the faulty Reg 6 is tested Gi The report MUST be made within thirty days after the defect becomes noticeable For further information and inquiries on the use installation maintenance and r
4. the exciter and connect Reg 6 using the installation steps i to iv described earlier in this manual The AVR should now build up and work IF NOT TRY THE NEXT PATTERN Battery excitation with AVR connected THIS PATTERN OF EXCITATION IS SENSITIVE AND CAN DAMAGE THE AVR IF NOT CAREFULLY DONE Connect Reg 6 to the generator using the installation steps i to iv described earlier in this manual Make sure that the VOLT and STAB adjustment knobs are fully off full anticlockwise Start the generator Run cables wires to the positive and negative of the battery Use a red cable for and a black cable for Hold the red cable on your left hand and the black cable on your right hand With the generator running place and hold the red cable on your left hand to contact X terminal of Reg 6 Summit Systems Limited REGMASTER AVR Momentarily Touch and quickly remove the black cable on your right hand to contact XX terminal of Reg 6 The AVR will build up and work Adjust voltage and stability if necessary IF A MISTAKE IS MADE BY INTERCHANGING CABLES CONNECTED TO X AND XX DURING THE EXCITATION THE AVR MAY BE DAMAGED EVEN THOUGH THE EXCITATION IS DONE QUICKLY GENERATOR REPAIRS AND TROUBLESHOOTING GUIDE Remarkable voltage drop when generator is loaded Alternator coils are overheating Output voltage fluctuates AVR is faulty Gener
5. ator governor is not working properly Alternator coils are faulty Partial contact at AVR terminals or AVR is faulty and supplying excess current to the exciter POSSIBLE FAULT CAUSES REMEDY Generator is overloaded Check and confirm AVR Run set without load and see if cols still heat Confirm if speed governor is okay Confirm that cables at AVR terminals are firmly connected Generator voltage is too high AVR is faulty Generator is over speeding Repair or replace AVR Confirm generator speed governor performance Battery is not charging Generator charging circuit or alternator is faulty Check battery charging alternator and circuit Summit soi REGMASTER AVR Limited Generator unable to carry Inductive load is not properly Check electrical and some inductive loads such installed and pose overload to mechanical installation as compressors borehole generator of inductive load pumps and heavy welding machines Initial starting current of Install a generator with a inductive load is high compared higher KVA rating to to the KVA rating of the match the initial starting generator and running current of inductive load Generator may be running lower than rated speed Use tachometer and frequency meter to AVR may be faulty or does not Confirm that the fit the generator alternator generator is running on normal speed and the outp
6. epairs of Reg 6 please call the numbers or use email address below for technical assistance NIGERIA Summit Systems Ltd Contact Persons Njoku Chinedu 07036642418 Technical Support Department 08068382749 Email info summitsystemsltd com uzngoka yahoo co uk
7. om water moisture or oil Away from flammable substances Secure and have no risk of falling FREE FROM MUCH VIBRATION As much as possible do not install it in the generator housing if the generator vibrates too much d Avoid direct contact of the circuit board with any metal part of the generator Reg 6 has a mounting prop installed on it which isolates the circuit board Do not remove it during installation Summit Systems REGMASTER AVR Limited e Avoid overloading the generating set as overloading can damage any AVR f Avoid erratic engine speed adjustment as this can damage any AVR B WIRING DIAGRAM AND INSTALLATION STEPS STAB Stability Adjustment Knob VOLT Voltage Adjustment Knob N Neutral L Live X Positive Exciter XX Negative Exciter INSTALLATION TOOLS i Functional Digital or Analog Multimeter ii Frequency meter or Tachometer for measuring engine speed iii Precision screw drivers for voltage and stability adjustment iv A generator technician should own a complete toolbox INSTALLATION STEPS 1 Make sure that the generator set is intact That is to say that the set starts and runs smoothly and the speed governor is working fine ii Use a digital multimeter digital meters are more precise and accurate than analog meters set at 200 Q resistance to measure the resistance of the exciter coil X and XX winding terminals
8. ut voltage frequency is okay POSSIBLE FAULT CAUSES REMEDY No power output in generator Connecting cables to AVR terminals are detached The generator circuit breaker tripped off Flying diodes in Check and confirm AVR connections Use battery to excite the generator If there is still no output voltage check the flying diodes exciter and field coils of the alternator If battery excitation produces an output AVR is faulty or is not properly connected generator alternator are faulty The AVR is faulty The alternator coils are faulty Check connections again or repair replace the AVR Summit tem Seen REGMASTER AVR Limited Power output Generator engine speed is Increase speed of generator engine frequency of low below 1500 RPM until the desired 50 Hz frequency is generator is low Frequency of generator reached Some sensitive equipment below 50 Hz output can only be such as split system air conditioners changed or altered by color photograph printers and varying the engine processing machines photocopiers speed UPS equipment computers and modern instruments are frequency sensitive If the voltage is full and frequency is low such equipment may not function Increase the generator speed to increase the frequency of the output If frequency is to be 50 Hz at full load ensure that the no load frequency is up to 51 or 52 Hz so that
9. y continue to adjust generator terminal voltage using the VOLT knob until the desired voltage 220 240 volts Phase to Neutral or 380 415 volts Phase to Phase is reached Make sure you use a multimeter during this adjustment because the generator panel meter can deceive you with a wrong reading if it is faulty If power flickers or is unstable slightly reduce the voltage and gradually increase the stability using the STAB knob until power becomes stable Then adjust and set the voltage BATTERY EXCITATION OR FLASHING Summit Systems REGMASTER AVR Limited After installing Reg 6 if the AVR does not build up voltage it could be that the generator field winding has lost the residual magnetism required to produce the necessary initial voltage for the AVR to build up and regulate voltage This problem can be solved by using battery excitation There are two ways to do it Battery excitation with AVR disconnected Completely disconnect REG 6 from the generator and connect a 12 or 24 volts battery depending on the battery the generator uses to the exciter terminals Connect X of generator exciter to the positive of the battery and the XX of generator exciter to the negative of the battery Start the generator and make sure that the generator terminal voltage has built up from the battery With the battery still connected VERY IMPORTANT stop the generator Then disconnect the battery from

Download Pdf Manuals

image

Related Search

Related Contents

Please read this owner`s Manual carefully before operating the unit.  ー連結可能な鋤・距離  SNPlex Genotyping System, 48  Proximity / PIN Access Controller  Installation, Care & Use Manual Manual de Instalación/Cuidado  Saneamento Básico Integrado às Comunidades Rurais e  第65号 損害賠償請求事件 口頭弁論終結日  GT15 OPTION FUNCTION BOARD/OPTION  FM-8 取扱説明書(日本語/英語版)  Lire l`article au format PDF  