Home
        Vibration Control System - UCSD Department of Physics
         Contents
1.    Hex Nut  Support Plate    Spanner Wrench                                       ee     Figure 3     Isolator Leveling Wrench    1  Refer to Figure 4  As shown  use one of the special wrenches to hold  the hex nut stationary  Insert the prongs of the second wrench into the  holes on the bottom of the support plate  Rotate the plate using the top  wrench to adjust the height     2  Place a level on the table top  approximately in the center     3  For each isolator  adjust the support plates as required to bring the table  to a level condition  Be sure to check the level using both the length and  width axes of the table  Verify that the centering disks are centered in  and resting on their respective guides  Figure 4           Support Plate  Isolator fully down Hex Nut  on stops     no air  applied         ne DS cor  2 55 in   65 mm  Bolt  amp  Clamp a  Nominal St    Centering Guide    Figure 4     Level Adjustment of Isolators    2 3  2 3 1    4  When the table is completely level  ensure by eye that every isolator  support plate is snug against the table bottom and that each centering  disk is centered in its guide  Figure 4      5  Use the level to confirm that the table top is still level and equally  supported by all isolator support plates  Tighten all isolator clamp bolts  snugly to secure the table to the isolators     6  Loosen the two screws securing each leveling valve to its bracket  Slide  the valve body until it is approximately 0 060 inches  1 5mm  below the  
2.  8   2 3 1 Installing Leveling Valves     nnn eeree ennen  8   DIZ Conmectime Ar LANGS  sne hee a 10   2 3 3 Adjusting Leveling Valve Sensors eeen 13   2 4 Installing tables with the Doubler Interface                  eee  14   3 Operation 17  3L Ponc Meso Operom nenten eerden dian ied ieee nce wee  17   3 2  Perormance Adjustments screeni E A 17   F Mineri Oene a a a a 18   IL TC TC AIG a ER 18   Io AO aa Dentencrwentetauneed  19   4 Troubleshooting 20  Ab    Table Top Does NobRIOat tiers mentele Le 20   4 2 Poor Isolation Performance                    unssnnnnnnnssererseennennnensseen  20    4 3  4 4  4 5  4 6    Table Top OSCiMAteS oroen nE i 21  System Leaks Air Constantly eeen eeenensenerseeeven  21  Oil Geak  Prom ISOM OR  ssensnrden dated eenderde dendert leidde aasndan  21  Adds Danie Oil steenen ordnnbekenteentdendteienehele 21    Factory Service 23    yi    List of Figures    Pieure    Isolator  POSION vorir O E 5  Figure 2     Isolator Clamps and Mounting Holes     cc eeeeeseeeeeeeeeeees 6  Fiure s   Isolator Leveling  Wreneh eren okewioleteedi nied  7  Figure 4     Level Adjustment of Isolators        sans eneeeneeennnnnnnenn  7  Proure     IPV eveline MAINE oons armere wetalnscxctrean access are 9  Figure 6     Valves attaching to isolator     ess eeneeeenenenennnnnnnenen 9  Figure 7     Orientation of Control Arm            ssseeeeeereeeessssssssssssseseeeeereeeeess 10  Pisure 3    A Ame ROUNE sceteidatspeaicaetebediet ebnaeetnidatatendatebebendabetebindeis 11 
3.  CAUTION  AN Bottled carbon dioxide  CO   is not recommended since    icing       can occur during rapid filling of the isolators        1 7    Warranty Information    Warranty information may be found on the page preceding the Table of  Contents in this manual  Should it become necessary to exercise the  watranty  contact your Newport representative to determine the proper course  of action  Newport Corporation maintains offices throughout the United  States and other locations worldwide     2    2 1  2 1 1    2 1 2    Assembly    Assembling the System    Table Installation Assistance    Optical tables are heavy  Even a small table top weighs over 500 pounds   227 Kg   Contact Newport or your local sales representative for help in  preparing your facility     Positioning the Isolators    Figure   shows the correct isolator positions for standard table sizes  Table 1  shows the correct dimensions  A  B   amp  C  for each table size        Figure 1     Isolator Position  Table Width   Table Length A B C  ft  mm  ft  mm  in  mm  in  mm  in  mm     3  900  6  1800  14  341  30  733  35 5  899   5  1500  12  3600  38  941  70  1720  82 75  2054   16  4800     Table 1     Isolator Positions       2 1 3 Installing Table Top    If your table is equipped with a Doubler Interface be sure to follow the  instructions in Section 2 4 for assembling the table sections prior to installing  them on the isolators     WARNING    Table tops are heavy  Use a forklift or other appropriate    equi
4.  Detail of Valve Connections  Single Isolator    2  Close the metering needle valve  Figure 9  on each valve and then open  it   turn for each isolator that is connected to it  For example  if the  valve controls two isolators  the needle valve is opened 1 full turn    Please note  If you have a minimum load on your optical table top  open  the metering valve about         of a turn      3  Turn on the air supply and adjust the regulator for the pressure calculated  using the formula given in Section 1 6  This pressure must not exceed  95psig  6 7 kg cm               Figure 10    Detail of Valve Connections  Two Isolators    4  Check all connections for leaks  Correct or repair any leaks before  proceeding     5  If the table does not float within several minutes  increase the air  pressure until the table floats or adjust the value height sensors to hold    2 3 3    13    the control arms further down  Confirm that the needle valves are open  Y  turn per isolator supplied     NOTE  If the table oscillates after it floats  decrease the air pressure or  close the needle valves slightly     In clean room applications the    EXH     exhaust  port on the valves may  be connected to the clean room vacuum system to capture the valve  exhaust     NOTE  Exhaust must be routed to a vacuum system  Backpressure in  the tubing will cause the exhaust air to leak from the valve     Adjusting Leveling Valve Sensors    l     After the table floats  check the position of the centering guide a
5.  Figure 9     Detail of Valve Connections  Single Isolator                                 12  Figure 10     Detail of Valve Connections  Two Isolators     12  Figure 11     Floating Height Adjustment and centering         cc eeeeeeeeeeeee 14  Figure 12     Typical Double Interface System    ceeeeeeeeeeeeeeeeees 14  Figure 13     Double Bolt Tightening Sequence                cc eeeeeeeeeeeeeeeeeees 16    Broute A  Systems ta ality a e E elek eed 18    1 1    1 2    1 3    General Information    Introduction    The Newport Vibration Control System provides an ideal working platform  for vibration sensitive devices such as interferometers  microscopes  and  balances  The table surface is isolated from floor motion using the  Stabilizer    pneumatic suspension system  The versatile Newport Vibration  Control System is available in a variety of sizes  working surfaces  and  options     These systems integrate Newport   s rigid  laminated honeycomb panel  technology and pneumatic isolation systems to provide a mounting platform  which is rigid  yet thin and light weight     It is possible to tailor the system to a wide variety of applications using the  entire range of sizes and working surfaces  A typical Newport Vibration  Control System consists of an optical table and vibration isolators     The S 2000 Stabilizer    isolation system is capable of supporting 2000  pounds per isolator  Caution must be observed to ensure that heavy payloads  are not located off center on the tab
6.  valve  Air line to isolator       Over pressure relief valve    Table height  adiustment screw    Mounting screw holes       Figure 5     IPV Leveling Valve        Table height  adiustment screw    Peet  Re Mance    Row Isolator    Figure 6     Valves attaching to isolator    The valves should be attached to the isolators as shown in Figure 6 after  installing the table top     1  Set the table height adjustment screw on each valve to the center of its  travel  Figure 6      2  Attach the leveling valve to the isolators as shown in Figure 6  Secure  the valve to the bracket using the two mounting screws and the nutplate     Position the valve at the bottom of the bracket slots until after the table is  installed and leveled     Rotate the control arm on valves    A    in Figure 7 so that they point  towards the nearest corner of the table     Rotate the control arm on valve    B    in the figure so that it points toward  the table   s center  midway between the isolators that it controls     For systems with more than four isolators  use the same basic setup just  described  Two valves control the height of the two end corners  A  amp  A   while the third valve  B  controls the height of the opposite end  Figure  8      lsalatar    IAN va            P  i    vo  pe           Control  Arm       Table Top    Figure 7     Orientation of Control Arm    2 3 2 Connecting Air Lines    l     Connect air lines to the isolators as shown in Figure 8  When cutting  tubing  be sure the en
7. If the combined center of gravity of the  payload and table top is within the    stable region     the system will be  stable  If the combined C G is inside the    may be stable region     the    3 3  3 3 1    system may be stable  If the combined C G is outside both regions  the  system will probably be unstable     May Be Stable Ragion       F   q    4       Figure 14    System Stability    3  Improving leveling response times  If the system is stable  the re   leveling response time may be decreased by increasing the system  pressure  In addition  the needle valves may be opened until the system  oscillates and then closed slightly  This is desirable if components are  moving over the surface of the table     For systems where the loads are seldom changed  slower re leveling may  be beneficial  This is accomplished by closing the needle valves slightly  and or decreasing the system pressure     All needle valves should be opened the same amount for each isolator  that they supply     4  Table loads and or load positions change  If the loads are moving or  changing significantly  the control arms may require adjustment  Each  time the load is changed  check the relationship of the centering guide to  the flange on each isolator  If the desired   inch is not maintained   adjust the overall system pressure and or the sensor positions     Newport Vibration Control Systems require little maintenance  No periodic  maintenance is required     Maintenance    Cleaning    Newport op
8. LIED  INCLUDING ANY IMPLIED WARRANTY  OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR USE   NEWPORT CORPORATION SHALL NOT BE LIABLE FOR ANY  INDIRECT  SPECIAL  OR CONSEQUENTIAL DAMAGES RESULTING  FROM THE PURCHASE OR USE OF ITS PRODUCTS     First printing 2009       2009 by Newport Corporation  Irvine  CA  All rights reserved  No part of  this manual may be reproduced or copied without the prior written approval  of Newport Corporation     This manual has been provided for information only and product  specifications are subject to change without notice  Any change will be  reflected in future printings     Newport Corporation  1791 Deere Avenue  Irvine  CA  92606 USA    Part No  90030352 Rev  B    Table of Contents    NN IGAO en eneen dennen A E i  TaDle OF COMMS ernas estar ieesteamiaieenestadedaresrereiaes 1V  LASCO TIDO CS aa E det denees vi   1 General Information 1  PE AMO ON enen lopaes fovzecea wiaetec to necedien  l   EZ Gemine Sae anke asthenie l   L3 Unpackins and IMS pe Cu 6 nerens l   L4   Batey Considera ONS ean a a N 2   Po  Table PICe ment eene dede 2   L6 Amr Supply Requirements ersiersiuipnnnaininen epaia 3   LE Warni inlonnaioi eas a a a nas 4   2 Assembly 5  2k Assembine the SysteM irene a a S 5   2 1 1 Table Installation Assistance nnn oeneeeenennnen  5   2 1 2 Positioning the Isolators                              annsnnnnnnnereeneennenn 5   DAS Astellas Table ToP eccere detains 6   22 Leveling the Taberei emelten 7   2 Asolating the Table LOPE mennen a N
9. Vibration Control System       S 2000 Stabilizer  Vibration Isolators  and Optical Table Installation Manual       User s Manual    Ss     Newport     Experience   Solutions       Warranty    Newport Corporation warrants that this product will be free from defects in  material and workmanship and will comply with Newport   s published  specifications at the time of sale for a period of one year from date of  shipment  If found to be defective during the warranty period  the product  will either be repaired or replaced at Newport s option     To exercise this warranty  write or call your local Newport office or  representative  or contact Newport headquarters in Irvine  California  You  will be given prompt assistance and return instructions  Send the product   freight prepaid  to the indicated service facility  Repairs will be made and the  instrument returned freight prepaid  Repaired products are warranted for the  remainder of the original warranty period or 90 days  whichever first occurs     Limitation of Warranty    The above warranties do not apply to products which have been repaired or  modified without Newport   s written approval  or products subjected to  unusual physical  thermal or electrical stress  improper installation  misuse   abuse  accident or negligence in use  storage  transportation or handling  This  warranty also does not apply to fuses  batteries  or damage from battery  leakage     THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES   EXPRESSED OR IMP
10. bottom of the table  Be sure the valve is not tilted  then tighten the  screws  Figure 6      Isolating the Table Top    Installing Leveling Valves    The IPV leveling valve is shown in Figure 5  Three valves are used in all  systems  regardless of the number of isolators  as only three points are  required to determine a plane  The leveling valve locations are selected such  that they form the largest triangle possible under the table  The larger the  triangle  the more stable the system will be  When two or more isolators are  controlled by the same valve  they act as a single large isolator supporting the  table at the center of force of the several isolators  The floating height of the  system is determined at the valve position  Therefore  ideally  the valves  should be located at the center of force of the isolators they control  In  practice  however  simply grouping the isolators and their control valves 1s  sufficient  The groups of isolators and their valves act as three legs for the  system  The center of gravity of the combined table and payload must be  within the triangle formed by the centers of force of the isolator groups for  the system to float  Figure 8 shows valve and isolator arrangements for  rectangular tables  Complex table shapes require isolator and valve layouts  designed specifically for each application     Table height sensor      Control arm        Isolator pressure    gauge N    Air supply         gt  cS AD    Metering wa          TE    needle
11. ds are round and cut squarely  This is best done  with a single edge razor blade  scissors will deform the tubing  causing  leaks   The connections are detailed in Figures 8  9 and 10     a  Use translucent tubing to connect the air supply to each of the  leveling valves  Use    Tee    connectors as required  Press the free  end of the tubing into the yellow collar of the valve   s    IN     connector  Be sure the connection is firm by tugging on the tube     b  Connect a length of grey tubing  supplied with the valves for use on  the valve barb fitting  between the hose barb on the valve and the  inlet connector on the isolator  Figure 9   If more than one isolator  is supplied by a valve  use    Tee    connectors as required  Figure 10    Connect the grey tube from the valve to the    Tee    and use  translucent tubing between the    Tee    and each isolator     11                  3 Isolator Schematic Leveling Valves CLN A    3 Reqd leenen T    Vt 7 Table Width  Air IN      Regulator     J  a Less 12  Filter     E Typ All Tables  ae   Air Supply st  a A m a   4 Isolator Schematic ZN       Leveling Valves   j 3 Reqd  yy   Air      a     Regulator     Filter    Air Supply ar       Leveling Valves  i 3 Reqd   A   Ait      Regulator Ss   Filter       Air Supply ap            8 Isolator Schematic A             l _  ns hen  Leveling Valves      3 Reqd    Air  Regulator  Filter    Air Supply ar      Figure 8     Air Line Routing    12        Metering needle  valve    Figure 9    
12. he following instructions are applicable only to those tables equipped with  the Doubler Interface  Figure 12 shows a typical Doubler Interface System     1  Use the procedures in Section 2 1 2 and 2 3 1 to assemble the isolators  for both table sections     2  Carefully uncrate each table top  noting the correct orientation indicated  on the crates  Carefully check the doubler faces for any damage that  might prevent them from fitting tightly together     Tabla Table    Section Saction           ae   1  tt         A   r    A r d            AA a  a a    il    A       Figure 12    Typical Double Interface System  3  Position the isolators for one table section as described in Section 2 1 2   Install valves on the appropriate isolators as shown in Figure 8     4  Install the first table section on the isolators as described in  Section 2 1 3     i Do not force the bolts  The second table section should be    10     11     12     13     15    NOTE  It may be necessary to use jack stands to support the first table  section if fewer than four isolators are located under the section     Position the second table section on three jack stands mounted on dollies   Adjust the position of the table so that it is at the same height as  and  adjacent to  the first table section     Align the two table sections using a straight edge  Carefully roll the  second table section toward the first so that the alignment dowel pins  engage in their mating holes  Be sure the bolts are aligned with t
13. heir  corresponding holes     Draw the two table sections together approximately   inch  Smm  using  the two outermost top bolts     CAUTION    easily pulled up to the first  Figure 2 13 shows correct bolt head  position during assembly     Do not cause the first table section to shift sideways on its  isolators  Doing so could damage the isolators        Tighten all of the bolts until they are finger tight or until they just begin  to move the table sections together  Do not force or over tighten the  bolts     Repeat steps G and H until the two table sections are completely drawn  together     When all bolts are snug  apply a final torque of 60 pound feet  80 N M   to all bolts using the sequence shown in Figure 13     Jack up the assembled table as required to install the remaining isolators  and leveling valves  Install the isolators and valves as described in  Section 2 1     Remove the jack stands and level the table as described in  Section 2 3     Install the air lines and float the table as described in Section 2 3     16        Female Table Male Table     Incorrect   See CAUTION    Figure 13     Double Bolt Tightening Sequence    3 1    3 2    17    Operation    Principles of Operation    The S 2000 Stabilizer    Isolators provide one of the best methods of  vibration isolation for critical applications  The system operates on the  principle of air pistons  which are equivalent of soft springs  The main  advantage of the Newport system over other designs are low ver
14. iculty  during the leveling of the table top if their irregularity 1s outside of the  adjustment range of the isolators     The S 2000 Stabilizer    isolator must be mounted so that its axis is not more  than 0 5 degrees from vertical  This is necessary for the isolator to function  properly in the horizontal mode  Note  0 5 degrees is equal to 0 09  2 2 mm   inches in 10 0 inches which is the isolator base diameter  A typical spirit  level will easily measure 0 5 degrees and can be used to check the vertical  alignment of each isolator     If the floor where the isolators are being mounted has a depression of more  than 0 09 inches under one side of the base  then the floor should be grouted  or shimmed level at this location     If the system is not located on the ground floor of the building  it should be  located near primary vertical structures such as exterior walls or support  columns  By locating the table near these structures  the effects of low  frequency floor motion will be minimized  thus increasing the performance of  the table  It is also advisable to avoid locations adjacent to major sources of  vibration from operating machinery such as elevators  air conditioning plants   or factory equipment     1 6    WARNING    The table top is attached to the isolators with clamps and hex  head bolts  In the event of an earthquake  the table may  collapse  For areas susceptible to earthquakes  we recommend  that Newport Earthquake Restraints be installed on each  Vibrat
15. ion Control System     WARNING    The table top is a metallic electrical conductor  For installations  where electrical shock is a possibility  the table top should be  grounded to prevent personal injury        Air Supply Requirements    A constant supply of air must be connected to the Vibration Control System  during operation  After initial setup and filling  the isolators consume air  only when the leveling valves adjust the pressure to compensate for changes  in the load on the table     Bottled nitrogen or mechanically compressed air may be used  The required  pressure is determined by dividing the total load  including table weight  by  the total isolator diaphragm area  25 9 in  per isolator  plus   5 10 psig     For example  if the table plus load is 2850 pounds and will be mounted on 4  isolators  the required pressure 1s     2620 lbs  4x 25 9 in     Note that the maximum operating pressure for the system is 95 psig   6 7 kg em         10 psig   37 5 psig    The Newport Model ACGP air compressor is an extremely quiet source of  clean  pressure regulated air  If another compressor or plant air is used  the  Newport model ARF Air Regulator Filter should be used to ensure  maintenance free operation  These filters prevent water and dirt from getting  into the leveling valves and causing the valves to fail due to clogging     The supply should include a valve so that the air may be shut off during  maintenance or extensive setup when the load is changed drastically    
16. le surface  This could cause overloading  of one isolator even though the average load per isolator is below the 2000  pound limit     Getting Started    Heavy payloads with very high centers of gravity  C G  may cause the  isolation system to oscillate  Please consult Section 3 2 of this manual or  Newport Applications Engineering for high C G applications     Please read this instruction manual thoroughly before assembling the table  system  The individual components have been assembled at the factory and  require only final system assembly and performance adjustment     Unpacking and Inspecting    The components of your Newport Vibration Control System are packed in  individual  labeled boxes  Be sure the number of boxes you received is equal  to the total number listed on the label  for example  if a box is labeled 1 of 4   there should be 4 boxes      1 4    1 5    Safety Considerations    Carefully inspect all components for shipping damage  Report any shipping  damage immediately to the shipping company and Newport     The following terms are used in this manual that relate to your safety     WARNING    Warning is used to indicate dangers that could result in personal  injury     CAUTION    Caution is used to indicate situations that may result in damage  to components of your Newport Vibration Control System        Table Placement    To ensure optimal performance from your Vibration Control System  it  should be located on a level surface  Uneven floors may cause diff
17. ly  refer to  Section 2 3 2   If testing with soapy water indicates that either the isolator or  valve are leaking contact Newport Customer Service     Oil Leak From Isolator    Damping oil may leak from the isolator if it is inverted or tilted more than 45  degrees  If more than   cup  30ml  of oil is lost  add additional oil  available  from Newport Corporation  as directed in Section 4 6  Losses of less than     s cup will not affect the isolator performance  Total volume of damping oil  per isolator is approximately   cup  125ml      Adding Damping Oil  If the isolator loses damping oil  additional oil may be added as follows     1  Remove the air pressure from the isolator and allow the piston to retract   Ensure that the remaining isolators will support the table or use a jack  stand to replace the isolator to be serviced  Loosen the three bolts  securing the support plate to the bottom of the table  and slide the  isolator from under the system     WARNING    The table top is heavy and may cause severe personal injury if it    falls  Be sure it is properly supported before getting underneath  the table top or removing the isolator        2  Measure the height of the support plate relative to the centering disk   Figure 2 4   Record this distance so that the isolator may be returned to  its normal position     3  Unscrew the isolator support screw  right hand thread  and remove the  plate and jack screw from the piston assembly     4  Use a funnel to add damping oil thr
18. nd  flange of all isolators  Figure 11   The gap between the guide and flange  should be 4    Ns   6mm  1 5mm   The center of the isolator centering  disk should be aligned with the float height indicator tabs  Figure 11      Adjust the Table Height sensor screw of each isolator  Figure 5  as  required to obtain this gap  When all isolators are adjusted  re check the  level of the table  NOTE  this step should require only minor  adjustments  Do not move the small set screw near the pivot of the valve  control arm     If the table is no longer level  you may have to remove the air pressure  and re adjust the height of the isolator support plates as described in  Section 2     Verify that the table is freely floating on the isolators  Move the table  gently from side to side about 14   You should not encounter any  resistance  Re check by moving the table up and down the same amount   Again  there should be no restriction of movement     Push one corner of the table down approximately 14  and release it  The  table should return to the original position within less than 4 seconds   Response time may be adjusted as described in Section 3 2     Support Plate          P Y    5      ad   1 16           Centering disk     Ps    Float height  indicator    14    Above alignment tabs Even with alignment tabs Below alignment tabs       Incorrect centering Correct centering    Figure 11     Floating Height Adjustment and centering    2 4 Installing tables with the Doubler Interface    T
19. nd of moving air  Repair or replace any clogged valve  Use  the ARF filter regulator to prevent this situation     Poor Isolation Performance    The following may lead to poor isolation performance of your system     L     Vibration may be transmitted to the table through direct physical contact  of equipment with external sources of vibration     Isolators that float too high  too low  or are not centered may conduct  floor vibration to the table top  Refer to Section 2 3 2   Figure 11   Centered isolators will remain centered unless the table and isolators are  moved relative to each other     Equipment on the table may be vibrating at a resonant frequency of other  components  Improve the rigidity of the mounting for that equipment or  remove that item from the table     Non level floor may prevent the horizontal isolation system from  functioning properly  see Section 1 5      4 3    4 4    4 5    4 6    21    Table Top Oscillates    If the table top oscillates or    hunts     you may have a set up with a high center  of mass  Refer to the information in Section 3 2 or consult your Newport  representative or Newport Corporation for further assistance     System Leaks Air Constantly    All Newport isolators and valves are pressure leak tested prior to shipment   Check all tubing connections for leaks with soapy water  Tubing that is  crushed out of round or that is not cut squarely may not seal in the push in  fittings  Use a single edge razor blade to cut the tubing clean
20. ough the support shaft hole until the  oil level is approximately 4   6 4mm  from the bottom of the piston   Allow time for the viscous oil to settle before measuring the oil level     22    Use a clean  small diameter rod to check the level  When checking the  level  be sure the rod sits on the bottom of the piston and not on the  narrow ledge at the bottom of the support shaft     Reverse Steps 2 and 3 to re assemble the isolator  Return the support  plate to the position noted in Step 2     Reinstall the isolator and apply air pressure  Make any required  adjustments to return the system to operation     23    Factory Service    To obtain information concerning factory service  contact Newport  Corporation or your Newport representative  Please have the following  information available     1  Model number   2  Purchase order number   3  Complete description of the problem     If components are to be returned to Newport Corporation  you will be given a  Return Number  which you should reference in your shipping documents     Please fill out the service form located on the next page  and have the  information ready when contacting Newport Corporation  Include the  completed service form with any parts or components that are returned     
21. pment  Be sure to use proper lifting procedures to avoid  severe personal injury        1  With the isolators located as described in Section 2 1 2  raise the table  top and position it above the isolators  Be sure each isolator is centered  within the tapped three hole patterns on the lower surface of the table                   Pal bh  af lan Isolator Clamp  mi N Hex Head bolt  A        ad af Pad ee     Flat Washer   i ri      A  3 per Isolator   ro Pa ee e  p  d k   Nae   a rs an    a mi r4 ge a   a  Pi he Men  K al i ba 7  C  a i     Oo     4 ep     5 Bae a  3 y   7  h          ee       B ee ee  i aut ern N a En       of              Ne   Ne  S  gt   Age Pn  a    A Pans y B  ae  ef Y  ee  y p  Table Bottom ADN  Surface Pe 4 J  on A    aa AN       Figure 2     Isolator Clamps and Mounting Holes    2  Gently lower the table so that is just above the top of isolators     Install three isolator clamps in the corners where each isolator is located   Figure 2   Loosely secure the clamps with the bolts  Do not tighten  the clamps at this time     4  Lower the table top until it rests on the isolator support plates     CAUTION    AN When lowering the table on to the supports  do not allow the  table to shift sideways  Doing so could damage the isolators    and cause degradation in performance        2 2 Leveling the Table    Use the following procedure to level the table  The special wrench  Figure 3   is for all adjustments     Support i  Clamp E  Bolts a       Level Adjustment 
22. tical resonant  frequency with low amplification at resonance  Q  and a Pendulum     horizontal decoupling system for effective isolation from low amplitude  vibration     Newport optical tables provide a working surface that is statically rigid with  high internal tuned damping for high dynamic rigidity and minimal response  to environmental disturbances     The leveling valves provided with the system control the height of the table  to within  0 01   0 3mm  accuracy  This tolerance is adequate for most  applications  More accurate valves are available for specialized  applications     Performance Adjustments    Once the system is assembled and the table floating  it is possible to make  minor adjustments to suit your individual needs  These adjustments involve  the system air pressure  the control arms  and needle valves     WARNING    Once the table is floating  keep fingers away from the area    between the centering guide and outer clamp of the isolators   Any object between these points may be caught if the table load  or air supply changes  causing personal injury        1  Stabilizing high center of mass loads  If your load has a high center of  mass or if the load is particularly heavy  the table may oscillate  In this  case  lower the system pressure or close the needle valves slightly  This  may improve stability and reduce the oscillation or    hunting        2  A rule of thumb for determining high center of gravity  C G  system  stability is shown in Figure 14  
23. tical table tops are made of 400 series stainless steel  This  material is relatively corrosion resistant  It may be cleaned by applying non   abrasive liquid household cleaner to a rag and wiping the table top  Avoid  abrasive cleaners as they will foul the mounting holes     All other surfaces on the table top or isolator system may be cleaned in the  same manner     3 3 2    19    Air Quality    Oil  water  or debris in the air supply may contaminate the leveling valves or  isolator damping system and degrade performance  Use of the Newport  model ARF Air Regulator and Filter in the air supply will prevent this  occurrence  The filter does require occasional cleaning     20    4    4 1    4 2    Troubleshooting    Table Top Does Not Float    Use the following procedure if the table top does not float  or lift up  when  pressure is applied to the isolators     I     Ensure that the supply pressure is 5   10 psig  0 4   0 7kg cm   above the  pressure reading of any of the leveling valves  If the load is increased   the pressure should be increased to maintain the difference between  supply and valve pressure  Refer to Section 1 6     Check to see if all air lines are connected properly and the supply  pressure is adequate  see step 1   Refer to Figures 8  9  and 10     Be sure that the needle valves are not closed completely     Check each leveling valve for clogging  To do this  press the control  arm down  Air should flow into the isolator  accompanied by the  familiar sou
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
ﻰﺳﺎﻓ  Manuale d`installazione ed uso 818749-00 GESTRA  Epson Printer TM-T88V User's Manual  CSR & アニュアルレポート2013  Integral 8GB PC3-10600  Denon DVM-4800 Multi  Cherry SmartTerminal ST-1044U  HUDOC FAQ: Foire aux questions  OWNERS AND SERVICE MANUAL  In-Ear Headset SLEH    Copyright © All rights reserved. 
   Failed to retrieve file