Appendix A - Panel & PLC Error Code Tables
Contents
1. A 24 C mar p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables Omron Error Code P499 Explanation The P499 error code is used to show any errors that are generated by the connected PLC A The P499 error message includes a four digit hexadecimal value displayed at the end of the message This value can be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the Omron Host Link communication protocols breakdown into a four digit hexadecimal value Omron Error Code P499 Message Example P499 Recv Err Code 0016 EA3 USER M Hardware User Manual 2nd Edition C mar E A 25 Appendix A Panel amp PLC Error Code Tables Omron Host Link Protocol PLC Error Code Table The following table lists the errors that can be generated by the Omron PLC when using the Host Link protocol NOTE The following errors can be generated from the designated PLC are monitored by the C more Micro panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information Panel Error Code P499 Hex Value 0x00 Normal Completion 0x01 Not executable in RUN mode 0x02 Not executable in MONITOR mode 0x03 Not executable with PROM mounted
2. 0xD210 Block number incorrect EA3 USER M Hardware User Manual 2nd Edition C mar Er A 3 1
3. PLC generated error codes for the GE Fanuc 90 30 90 70 and VersaMax SNPX protocol continue on the next page A 18 C mar p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables GE SNPX Protocol PLC Error Code Tables cont d Panel Error Code P499 Hex Value Description A framing or overrun error has occurred on an X Attach Response message when establishing a new SNP X 0x410C communication session Communications have not been established 0x410D SNP slave on CMM module requires PLC CPU privilege level 2 to operate The SNP slave has rejected a request to change to a higher or lower privilege level Ox410F An SNP X request was aborted prior to completion due to reception of a Break A BCC Block Check Code error has occurred on an X Attach Response message when establishing a new SNP X 0x420C communication session Communications have not been established SNP Request or Response message exceeds maximum data length of the CMM module Total data length for 0x420D Mailbox and all following Buffer messages is 2048 bytes The master must use a smaller data length Use multiple requests if total data length exceeds the maximum value 0x420F An X Buffer message was received containing greater than 1000 bytes of data The data is ignored An invalid message type was received when an X Attach Response was required when establishing a new SNP X 0x430C communication session Communic
4. PLC generated error codes for the GE 90 30 90 70 and VersaMax SNPX protocol continue on the next page EA3 USER M Hardware User Manual 2nd Edition C mor Er A 1 1 Appendix A Panel amp PLC Error Code Tables GE SNPX Protocol PLC Error Code Tables cont d Panel Error Code P499 Hex Value Ox2A0C An unknown message was received when an acknowledge ACK or NAK was required Ox2B0C Sequence Error An unexpected SNP message type was received Ox2C0C Received SNP message contains bad next message length value Acknowledge timeout An acknowledge ACK or NAK was not received within the configured T2 time interval A Ox2D0C slave device may generate this error if the master device has aborted after maximum response NAKs and does not NAK the next response retry Response timeout The SNP Master did not receive an SNP Response message within the configured T5 time Ox2E0C interval 0x2FOC Buffer message timeout An expected Text Buffer or Connection Data message was not received within the configured T5 time interval Serial output timeout The CMM module was unable to transmit a Break an SNP message or SNP acknowledge 0x300C ACK or NAK from the serial port May be due to missing CTS signal when the CMM module is configured to use hardware flow control 0x310C SNP slave did not receive a response from the Service Request Processor in the PLC CPU 0x320C COMMREQ timeout The COMMREQ did not complete within the configured t
5. 0x04 Address over data overflow 0x0B Not executable in PROGRAM mode Ox0C Not executable in DEBUG mode Ox0D Not executable in LOCAL mode 0x10 Parity error 0x11 Framing error 0x12 Overrun 0x13 FCS error 0x14 Format error parameter length error 0x15 Entry number data error parameter error data code error data length error 0x16 Instruction not found 0x18 Frame length error 0x19 Not executable due to Un executable error clear non registration of I O table etc 0x20 i generation impossible unrecognized remote I O unit channel over duplication of optical transmitting I O OxA0 Abort due to parity error in transmit data under process OxA1 Abort due to framing error in transmit data under process OxA2 Abort due to overrun in transmit data under process OxA3 Abort due to FCS error in transmit data under process OxA4 Abort due to format error in transmit data under process OxA5 Abort due to frame length error in transmit data under process OxA8 Abort due to entry number data error in transmit data under process OxBO Un executable due to program area capacity other than 16k bytes Description A 26 C mar p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables Omron FINS Protocol PLC Error Code Table The following table lists the errors that can be generated by the Omron PLC when using the A
6. 5 then the request will fail with Exception code 0x02 Illegal Data Address since it attempts to operate on registers 96 97 98 99 and 100 and there is no register with address 100 A value contained in the query data field is not an allowable value for server or slave This indicates a ILLEGAL DATA fault in the structure of the remainder of a complex request such as that the implied length is incorrect 0x0003 VALUE It specifically does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the application program since the Modbus protocol is unaware of the significance of any particular value of any particular register SLAVE DEVICE An unrecoverable error occurred while the server or slave was attempting to perform the requested VG FAILURE action A 4 C mor p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables Productivity Error Code P499 Explanation NOTE The following errors can be generated from the designated PLC are monitored by the C more Micro panel A and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information Panel Error Code Meaning P499 Hex Value The function code received in the query is not an allowable action for the server or slave This may be because the 0x0001
7. FINS protocol NOTE The following errors can be generated from the designated PLC are monitored by the C more Micro panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information ERR Description 0x0000 Normal Completion 0x0001 Service Canceled 0x0101 Local Error Local node not in network 0x0102 Local Error Token Timeout 0x0103 Local Error Retries Failed 0x0104 Local Error Too many send frames 0x0105 Local Error Node address range error 0x0106 Local Error Node Address Duplication 0x0201 Destination Node Error Destination Node not in network 0x0202 Destination Node Error Unit Missing 0x0203 Destination Node Error Third Node missing 0x0204 Destination Node Error Destination Node busy 0x0205 Destination Node Error Response Timeout 0x0301 Controller Error Communications Controller Error 0x0302 Controller Error CPU Unit Error 0x0303 Controller Error Controller Error 0x0304 Controller Error Unit number Error 0x0401 Service Unsupported Undefined Command 0x0402 Service Unsupported Not supported by Model Version 0x0501 Routing Table Error Destination address setting error 0x0502 Routing Table Error No routing tables 0x0503 Routing Table Error Routing table error 0x0504 Routing Table Error Too many delays 0x1001 Command Format Error Command too long 0x1002 Comma
8. Response PLC failed to Respond PLC Node C more Micro Panel Error Code Table continues on the next page EA3 USER M Hardware User Manual 2nd Edition Cer micro a 3 Appendix A Panel amp PLC Error Code Tables C more Micro Panel Error Code Table cont d Error Code Error Message Cause P499 ErrCode Received gt A PLC generated error code with a hexadecimal value of XXXX has been returned from the Recv Err Code XXXX PLC See the explanation for error code P499 proceeding each set of PLC error code tables Data cannot be written to the Serial port P500 Can tWriteS Port Data was sent to the PLC via the Serial Port If this error shows on the Panel it indicates a Hardware Problem There was an error while allocating memory for the read buffer When this error is displayed a P700 RD Buff MEM Full memory leak may have occurred Request to inaccessible memory from the HMI layer to the PLC protocol layer This error is an P701 INV PLC Address indication that there is a problem in the HMI layer A Read Write SetBit request has been sent to an invalid memory area This error is an indication that P702 INV FUN Code there is a problem in the HMI layer A PLC Write request was made to the PLC s Read Only memory area This error is an indication that P703 WRT PLC ReadOnly there is a problem in the HMI layer or the PLC protocol layer Modbus Protocols Error Code P499 Explanation The
9. Table 0x130C Invalid Set PLC Date Time mode Must be 1 4 0x140C Invalid Set PLC Date Time date time or day of week value 0x150C Unable to retrieve master device PLC time date from PLC CPU 0x150F Requested service is not permitted in a Broadcast request The master must direct the X Request message to a specific SNP X slave device 0x160C Invalid slave PLC type Must be 0 for Series 90 70 or 1 for Series 90 30 or Series 90 20 0x170C Invalid datagram type Must be 01h for normal datagram or 81h 129 for permanent datagram 0x180C Missing or too many datagram point formats Must be 1 32 0x190C Invalid datagram point format data PLC generated error codes for the GE 90 30 90 70 and VersaMax SNPX protocol continue on the next page A 16 C mar p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables GE SNPX Protocol PLC Error Code Tables cont d Panel Error Code P499 Hex Value 0x1A0C Datagram area size is too small to include data for all specified point formats 0x1B0C Invalid number of Control Program Names Must be 1 8 Ox1COC SNP X Request exceeds maximum data size 1000 bytes Must use a smaller data length Use multiple COMMREQs if necessary 0x1D0C Invalid SNP X communication session type Must be 0 for a single slave device or 1 for multiple slave devices Illegal destination SNP ID specified for SNP X slave Must be
10. X 0x500C communication session Communications have not been established 0x500F parity error has occurred in a received X Attach message framing or overrun error has occurred on an X Attach Response message when re establishing an existing SNP X 0x510C communication session Communications have not been established Ox510F framing or overrun error has occurred in a received X Attach message A BCC Block Check Code error has occurred on an X Attach Response message when re establishing an existing 0x520C SNP X communication session Communications have not been established 0x520F A BCC Block Check Code error has occurred in a received X Attach message PLC generated error codes for the GE Fanuc 90 30 90 70 and VersaMax SNPX protocol continue on the next page EA3 USER M Hardware User Manual 2nd Edition C mor E A 19 Appendix A Panel amp PLC Error Code Tables GE SNPX Protocol PLC Error Code Tables cont d Panel Error Code P499 Hex Value Description An invalid message type was received when an X Attach Response was required when re establishing an existing 0x530C SNP X communication session Communications have not been established 0x530F An invalid Message Type was received when an X Attach message was required For an X Attach message the message type must be 58h T An invalid Next Message Type value was detected
11. be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the Allen Bradley DF1 and DH485 communication protocol is represented by a hexadecimal value as shown in the following diagram Please note that the error code is broken down into three sections It is possible for more than one type of PLC error to be displayed in this value AB DF1 Protocol Error Code P499 Breakdown Remote Local EXT STS AB DF1 Protocol Multiple Error Code Examples 4 7 bits 0 3 bits byte Example 1 Example2 Example 3 ye EE EE T bits Wor i EDEN VE GE VE GEO GE GE p is is wie Jolo xJxJo o kole E le of an EXT STS Error P499 7 7 7 P499 Error Code Message or a Type maneter Value Displayed cung ili jolo nuna Displayed Hexadecimal Value EIT hex Allen Bradley PLC Error Code Displayed Example Error Recieved P499 Recv Err Code 3200 Je Remote 0x3000 Remote node host is missing disconnected or shut down Local 0 3 bits Local 0x0200 Cannot Guarantee Delivery Link Layer The remote node specified does not EXT STS ACK Command byte EXT STS 0000 None Error P499 Value Displayed P499 Recv Err Code F017 A 8 C mar E EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables Allen Bradley DF1 Protocol PLC Error Code Tables The following PLC error tables cover possible errors that
12. exist for specified module 0x4050 Request cannot be executed because memory card protect switch is on 0x4051 Specified memory cannot be accessed 0x4052 Specified memory attribute is read only and cannot be written to 0x4053 Error occurred when writing to specified memory location 0x4080 Request data error Check cabling and electrical noise 0x4082 Specified request is already being executed 0x408B The remote request cannot be performed 0x40A0 A block number out of range was specified Ox40A1 The number of blocks requested exceeds the range of the PLC Ox40A2 A step number was specified out of range Ox40A3 Step range limit exceeded Ox40A4 Specified sequence step number is out of range Ox40A5 Specified SFC device is out of range Ox40A6 Block specification and step specification are incorrect 0x4100 CPU module hardware fault 0x4101 Serial communication connection incorrect 0x4105 CPU module internal memory fault Bad CPU 0x4106 CPU is in initialization Wait until CPU is booted up 0x4107 Specified function not supported by this CPU Check memory types for that CPU 0x4110 Specified function not supported because CPU is in Stop Put CPU in Run 0x4111 System is not up yet Wait until system is up before performing request Ox4A01 The network number specified does not exist Routing not supported in C more Ox4A02 Station number specified does not exist Routing not supported in C more Description
13. following table lists the errors that can be generated by the Modbus protocols AutomationDirect CLICK AutomationDirect DirectLOGIC Modbus Koyo Modicon Modbus RTU Entivity Modbus RTU NOTE The following errors can be generated from the designated PLC are monitored by the C more Micro panel and displayed on the panel s screen as a hexadecimal value in panel error code P499 if active Panel Error Code P499 Hex Value Name Meaning The function code received in the query is not an allowable action for the server or slave This may 0x0001 ILLEGAL be because the function code is only applicable to newer devices and was not implemented in the unit FUNCTION selected It could also indicate that the server or slave is in the wrong state to process a request of this type for example because it is unconfigured and is being asked to return registered values The data address received in the query is not an allowable address for the server or slave More specifically the combination of reference number and transfer length is invalid For a controller with 100 registers the PDU addresses the first register as 0 and the last one as 99 If a request is submitted ILLEGAL DATA with a starting register address of 96 and a quantity of registers of 4 then the request will successfully ADDRESS operate address wise at least on registers 96 97 98 99 If a request is submitted with a starting register of 96 and a quantity of registers of
14. the next page A 14 C mar p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables GE SNPX Protocol PLC Error Code Tables cont d Panel Error Code P499 Hex Value PLC Error 0x010C WAIT type COMMREQ is not permitted must use NOW AIT type PLC Error 0x010E Not used PLC Error 0x010F The service request code in an X Request message is unsupported or invalid at this time This error may occur if an SNP X communication session has not been success fully established at the slave device PLC Error 0x020C COMMREQ command is not supported PLC Error 0x020E The modem command string length exceeds 250 characters Insufficient privilege level in the slave PLC CPU for the requested SNP X service PLC Error 0x020F Password protection at PLC CPU may be preventing the requested service Unsupported COMMREQ These errors are only generated when there is no protocol currently being run on a port PLC Error 0x0213 and the port receives a COMMREQ The port may be disabled or an error has occurred in processing a new configuration PLC Error 0x030C Ve is not active Must initiate a new SNP communication by sending an Attach or Long Attach COMMREQ Data Block Length is too small PLC Error 0x030E Output command string data is missing or incomplete PLC Error 0x030F Invalid slave memory type in X Request message PLC Error 0x0313 Invalid COMMREQ length PLC Error 0x040C SNP slave did not respond to Attach
15. 0 7 ASCII characters plus a terminating null character 0x1E0C 00h The Null SNP ID eight bytes of 00h may be used to specify any single device The Broadcast SNP ID eight bytes of FFh may be use to specify all slave devices on the serial link Destination SNP ID does not match SNP X session type 0x1F0C The Broadcast SNP ID is not permitted in a single slave SNP X session The Null SNP ID is not permitted in a multiple slave SNP X session Inactivity timeout T3 The SNP slave has not received any new SNP messages within the configured T3 time 0x200C interval 0x200F Invalid Message Type field in a received X Request message The message type of an X Request message must be 58h X 0x210C A Parity error has occurred on an Attach Attach Response or Update Real time Datagram message Communications have not been established Invalid Next Message Type or Next Message Length field in a received X Request message If this request does not use a buffer 0 2 bytes of data the Next Message Type must be zero If this request will be followed with a buffer 0x210F message more than 2 byte the Next Message Type must be 54h T and the Next Message Length must oe the length of the X Buffer message Valid X Buffer message lengths are 9 1008 bytes data length plus 8 bytes 0x220C A BCC Block Check Code error has occurred on an Attach Attach Response or Update Realtime Datagram message Communications have not been established 0x220F Inv
16. 8 5 GS 21 Example of a Siemens PPI error P499 Error Code Message for a Address out of range error Displayed Hexadecimal Value ojofo e hex P499 Recv Err Code 0006 A 3 0 C mar E EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables Siemens PPI Protocol PLC Error Code Table Panel Error Code P499 Hex Value Description 0x0001 Hardware Fault 0x0003 Object access not allowed 0x0004 Context not supported 0x0005 Address out of range 0x0006 Address out of range 0x0007 Write Data size mismatch 0x000A Object does not exist 0x8000 Function being used 0x8001 Action is not allowed in current mode 0x8101 Hardware fault 0x8103 Access not allowed 0x8104 Function not supported 0x8105 Address invalid 0x8106 Data Type not supported 0x8107 Data Type is not consistent with size 0x810A Object does not exist 0x8500 PDU Size is incorrect 0x8702 Address is invalid 0xD201 Block name syntax error 0xD202 Error with function parameter 0xD203 Error with block type 0xD204 No linked block 0xD205 Object already exists 0xD206 Object already exists 0xD207 Block already used in EPROM 0xD209 Block does not exist OxD20E No Block does not exist
17. 99 Hex Value 0x0 Success no error 0x10 Illegal command or format 0x20 Host has a problem and will not communicate 0x30 Remote node host is missing disconnected or shut down 0x40 Host could not complete function due to hardware fault 0x50 Addressing problem or memory protect rungs 0x60 Function not allowed due to command protection selection 0x70 Processor is in Program Mode 0x80 Compatibility mode file missing or communication zone problem 0x90 Remote node cannot buffer command 0xA0 Wait ACK 1775 KA buffer full 0xB0 Remote node problem due to download OxCO Wait ACK 1775 KA buffer full 0xDO not used OxE0 not used OxFO Error code in the EXT STS byte See the error code table on the next page Description Panel Error Code P499 Hex Value 0x0 Success no error 0x1 DST node is out of buffer space 0x2 Cannot guarantee delivery link layer The remote node specified does not ACK command 0x3 Duplicate token holder detected 0x4 Local port is disconnected 0x5 Application layer timed out waiting for response 0x6 Duplicate node detected 0x7 Station is offline 0x8 Hardware fault Description PLC generated error codes for the Allen Bradley DH485 protocol continue on the next page EA3 USER M Hardware User Manual 2nd Edition Cmor Er A 1 1 Appendix A Panel amp PLC Error Code Tables Allen Bradley DH485 Protocol PLC Err
18. PANEL amp PLC ERROR CODE TABLES In this Appendix rodu COUN ov A 2 C more Micro Panel Error Code Table cs sccsssssssssscscssecsesessesconssccavescasnssosesecae A 3 Modbus Protocols Error Code P499 Explanation ornevvennvvrrnnevnnnevennvvvnnevennnevennenene A 4 MULOMIATIONDIFECE NE vred A 4 AutomationDirect DirectLOGIC Modbus Koyo rrrrnnvrrnnvrrnnnvrnnnvrrnnnernnnernnnvennnvene A 4 MOGICON Modbus RTU cc cicccsyscsvedentendecaccecandecnsyeeeevenysscansaveacdeneinaededaceseseabaestewabcemnoons A 4 MS NU A 4 Productivity Error Code P499 Explanation oernvvvrnvvnnnevennevrnnnevennevennnnvnnenennnenennenene A 5 Do more Error Code P499 Explanation onnovvrnvvvnnvvvennevennvvnnnnevennevennnnvnnnnnnnnenennenene A 6 DirectLOGIC Error Code P499 Explanation svvrnnvvvrrnnevvrnnvvvrsnnvvvsnnvnnvnnnenvnnnnenennnene A 7 DirectLOGIC K Sequence PLC Error Code Table rovrrnnvnvvnnnvvvnnnnvvvnnnevvnnnnenennnene A 7 DirectLOGIC DirectNET PLC Error Codes rawuvnnnnvvnnnnuvvnnnnnvvnnnuvvnnnunnnnnnennnnnnunssnnene A 7 Allen Bradley Error Code P499 Explanation onovvrnnvvrnnvvvnnvevennevennevnnnnevennenennnenenneee A 8 Allen Bradley DF1 Protocol PLC Error Code Tables errrvvrnnevennvvvennevennuvennnenenneee A 9 Allen Bradley DH485 Protocol PLC Error Code Tables rrnruvrnnvvvnnvvvnnnvvsnnvveseer A 11 GE Error Code P499 Explanation rcicnvasicnsiscassisshcadeovdenesssiosaseasana
19. S 2 0 or later to support the SNP DOS Driver Ox8E0A PC Serial port configured for SNP Master driver is not open no communication can take place Ox8FOA Out of Sequence SNP message SNP message type received was not the type expected Description 0x900A Bad SNP BCC encountered Transmission was aborted after maximum retries due to a bad Block Check Code 0x910A Bad SNP communication Transmission was aborted after maximum retries due to serial errors that is parity overrun or framing errors 0x920A No SNP communication Either communication has been lost or a communication session has not been established OxC105 Invalid block state transition OxC205 The OEM key is NULL inactive 0xC305 Text length does not match traffic type 0xC405 Verify with FA Card or EEPROM failed OxC505 No task level Rack Slot configuration to read or delete OxC605 Control Program CP tasks exist but requestor not logged into main CP 0xC705 Passwords are set to inactive and cannot be enabled or disabled 0xC805 Password s already enabled and can not be forced inactive 0xC905 Login using non zero buffer size required for block commands 0xCA05 Device is write protected OxCB05 A comm or write verify error occurred during save or restore OxCC05 Data stored on device has been corrupted and is no longer reliable OxCD05 Attempt was made to read a device but no data has been stored on tt OxCE05 Specified device has insufficient mem
20. U revision number does not match OxE405 Memory Type for this selector does not exist OxE505 DOS file area not formatted OxE605 CPU model number does not match OxE705 Configuration is not valid OxE805 No user memory is available to allocate OxE905 Memory Type selector not valid in context OxEA05 Not logged in to process service request OxEB05 Task unable to be deleted OxEC05 Task unable to be created OxED05 VME bus error encountered OxEE05 Could not return block sizes OxEF05 Programmer is already attached 0xF005 Request only valid in stop mode 0xF105 Request only valid from programmer 0xF205 Invalid program cannot log in 0xF305 I O configuration mismatch 0xF405 Invalid input parameter in request 0xF505 Invalid password OxF605 Invalid sweep state to set OxF705 Required to log in to a task for service OxF805 Invalid Task Name referenced OxF905 Task address out of range OxFA05 Cannot replace I O module OxFB05 Cannot clear I O configuration OxFC05 I O configuration is invalid OxFD05 Unable to perform auto configuration OxFE05 No privilege for attempted operation OxFFO5 Service Request Error has been aborted Description A 22 C mar p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables Mitsubishi FX Protocol PLC Error Codes Only errors as listed in the C more Micro Pan
21. alid Message Type field in a received X Buffer message The message type of an X Buffer message must be 54h T 0x230C A Framing or Overrun serial error has occurred on an Attach Attach Response or Update Realtime Datagram message Communications have not been established 0x230F Invalid Next Message Type field in a received X Buffer message Since an X Buffer message is never followed by another message the Next Message Type must always be zero 0x240C An invalid SNP message type was received when an Attach Attach Response or Update Realtime Datagram message was required Communications have not been established 0x250C An invalid next message length value was specified in an Attach Attach Response or Update Realtime Datagram message Communications have not been established 0x260C An unexpected SNP message type was received when an Attach Attach Response or Update Realtime Datagram was required Communications have not been established Description 0x270C Another Break was received while SNP slave was waiting for an Attach or Update Realtime Datagram message An SNP message has been sent and retried the maximum number of times 0x280C A maximum of two retries are permitted A retry is caused by a NAK from from the remote SNP device 0x290C A received SNP message has been NAKed the maximum number of two times The NAKed message may be retransmitted a maximum of two times
22. are detected by the panel from Allen A Bradley PLCs using the DF1 protocol This includes full and half duplex communications for the MicroLogix 1000 1100 1200 1400 amp 1500 SLC 5 03 04 05 ControlLogix CompactLogix and FlexLogix and full duplex communications for the PLC5 NOTE The following errors can be generated from the designated PLC are monitored by the C more Micro panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information Panel Error Code P499 Hex Value 0x0 Success no error 0x10 Illegal command or format 0x20 Host has a problem and will not communicate 0x30 Remote node host is missing disconnected or shut down 0x40 Host could not complete function due to hardware fault 0x50 Addressing problem or memory protect rungs 0x60 Function not allowed due to command protection selection 0x70 Processor is in Program Mode 0x80 Compatibility mode file missing or communication zone problem 0x90 Remote node cannot buffer command 0xA0 Wait ACK 1775 KA buffer full 0xB0 Remote node problem due to download OxCO Wait ACK 1775 KA buffer full OxD0 not used OxE0 not used OxFO Error code in the EXT STS byte See the error code table on the next page Description Panel Error Code P499 Hex Value 0x0 Success no error 0
23. atch 0x4024 File ZR memory inaccessible by user 0x4025 File ZR memory is locked by another device 0x4026 File ZR memory password required 0x4027 Specified range is out of File ZR memory range 0x4028 File ZR memory already exist 0x4029 Specified File ZR memory capacity cannot be retrieved 0x402A Specified File ZR memory is abnormal 0x402B The requested data cannot be executed in the specified drive memory 0x402C The requested operation cannot be executed presently 0x4030 The specified data type does not exist Check the CPUs allowable data types 0x4034 The specified address is out of range The data type requested may need to be expanded in GX developer The CPU may not allow this data type 0x4032 Address qualification is incorrect 0x4033 Cannot write to system area 0x4034 Request cannot be executed because completion address for an instruction cannot be turned on PLC generated error codes for the Mitsubishi Q QnA protocol continue on the next page EA3 USER M Hardware User Manual 2nd Edition Comore A 23 Appendix A Panel amp PLC Error Code Tables Mitsubishi Q QnA Series PLC Error Codes cont d Panel Error Code P499 Hex Value 0x4040 Module doesn t support request 0x4041 Request is out of module s range 0x4042 Module cannot be accessed 0x4043 Address for specified module is incorrect 0x4044 Hardware problem
24. ations have not been established Improper Write Datagram message format Series 90 70 slave devices use a different format for this message than Series 90 30 or Series 90 20 slave devices The master must use the proper message format for this SNP slave 0x430D device The SNP master in the CMMmodule sends this message as part of the Establish Datagram COMMREQ command The datagram has been partially established but is not usable the datagram should be cancelled by using the Datagram ID returned by the COMMREQ 0x430F The SNP X slave did not receive a response from the Service Request Processor in the PLC CPU An invalid next message type value was detected in an X Attach Response message when establishing a new 0x440C SNP X communication session Communications have not been established 0x440D A datagram error occurred in a Series 90 70 slave device dual port error Ox440F PLC backplane communications error An invalid response code was detected in an X Attach Response message when establishing a new SNP X 0x450C communication session Communications have not been established An expected X Attach Response message was not received within the response timeout interval when establishing a new SNP X communication session The master has retried the X Attach message twice without receiving a response Communications have not been established parity error has occurred on an X Attach Response message when re establishing an existing SNP
25. ceesdenvanmssecansieaeteecsasaess A 13 GE SNPX Protocol PLC Error Code Tables vrnnvvvnnnvvennvvennnevennevennnvvnnevennennennenene A 14 Mitsubishi FX Protocol PLC Error Codes asvrnnvvvnnnuvennevennnuvennuvennuvnnnnuvnnnunennnneneee A 23 Mitsubishi Q QnA Series PLC Error Codes cccecsccccscscscscsccccccscscsccceees A 23 Omron Error Code P499 Explanation eoonovvrnnvvvnnvvvennevennvvennnevennuvennnvnnnennnnennennenene A 25 Omron Host Link Protocol PLC Error Code Table eerovvonnnvvnnnevennvvvnnevennenvennenene A 26 Omron FINS Protocol PLC Error Code Table sovvonnvvennevennnevennevennvvvnnevennennennenene A 27 Siemens Error Code P499 Explanation oeronvvonnevennevnnnnvvnnnvvennevennenennnevennunvennnenenneee A 30 Siemens PPI Protocol PLC Error Code Tablle ccccsccccscccsccsccscsccccccsccecs A 31 Appendix A Panel amp PLC Error Code Tables Introduction The C more Micro panels are capable of communicating over RS232 RS422 and RS485 serial networks They communicate with Productivity Series PAC s Do more PLC s CLICK PLC s all controllers in the Direct LOGIC family of PLCs utilizing various protocols and certain 3rd party PLCs For a complete list of the supported PLCs and protocols see the PLC Drivers table in Chapter 6 PLC Communications As with any network communications errors may occur To simplify identification of the possible caus
26. ddress reference exists to deleted area 0x14 Command execution failure for unknown reason possible PLC 3 histogram overflow 0x15 Data conversion error 0x16 Scanner not able to communicate with 1771 rack adapter 0x17 Type mismatch 0x18 1771 module response was not valid 0x19 Duplicated label 0x22 Remote rack fault 0x23 Timeout 0x24 Unknown error Ox1A File is open another node owns it 0x1B Another node is the program owner 0x1C Reserved 0x1D Reserved 0x1E Data table element protection violation 0x1F Temporary internal problem Description A 10 C mar p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables Allen Bradley DH485 Protocol PLC Error Code Tables The following PLC error code tables cover possible errors that are detected by the panel from A Allen Bradley PLCs using the DH485 protocol This includes all MicroLogix and SLC500 PLCs and any communication connection using an Allen Bradley AIC device using the DH485 protocol NOTE The following errors can be generated from the designated PLC are monitored by the C more Micro panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information Panel Error Code P4
27. e of the error we have provided tables listing these errors If a C more Micro panel communications error or other related data exchange error does occur the error message will appear across the top of the display screen as shown in the example below A complete table of the panel generated errors with their respective error codes error messages and the possible causes of the error follows The C more Micro panel also monitors any errors that are generated by the PLC that is connected to it If any of the PLC generated errors are detected they are displayed across the top of the panel s display embedded as a hexadecimal value in error code P499 An explanation of how the specific PLC error is identified in the panel error code P499 is shown preceeding the specific manufacturer s PLC error tables How the hexadecimal error code value is interpreted is slightly different between manufacturers so it is important to check the explanation at the beginning of each manufacturer s tables Since these errors are generated by the PLC refer to the PLC manufacturers documentation for further explanation If you have difficulty determining the cause of the error please refer to Chapter 8 Troubleshooting for some troubleshooting tips or contact our technical support group at 770 844 4200 C more Micro Panel Error Example A 2 C mar E EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables C
28. el Error Code Table shown on page A 3 can A occur when using the Mitsubishi FX protocol there are no PLC generated errors Mitsubishi Q QnA Series PLC Error Codes The following table lists the errors that can be generated by the Mitsubisht Q QnA Series PLC when using the Q QnA protocol NOTE The following errors can be generated from the designated PLC are monitored by the C more Micro panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information Panel Error Code P499 Hex Value 0x4000 Serial communications checksum error Check cable and grounding 0x4001 Unsupported request sent to PLC 0x4002 Unsupported request sent to PLC 0x4003 Global request sent to PLC that cannot be executed System protect switch is on and request was sent that cannot be executed 0x4004 Also PLC may still be booting up Description 0x4005 Packet sent is too large according to size request in header 0x4006 Serial communications could not be initialized 0x4008 CPU busy or buffer full 0x4010 Request cannot be serviced while CPU is running CPU must be stopped 0x4013 Request cannot be serviced while CPU is running CPU must be stopped 0x4021 Drive memory does not exist 0x4022 File ZR memory does not exist 0x4023 File ZR memory name and File ZR memory number do not m
29. esponse code was detected in an X Response message 0x660C An expected X Response message was not received within the response time 0x700C A parity error has occurred on an Intermediate Response message 0x700F A parity error has occurred in a received X Buffer message 0x710C A framing or overrun error has occurred on an Intermediate Response message 0x710F A framing or overrun error has occurred in a received X Buffer message 0x720C A BCC Block Check Code error has occurred on an Intermediate Response message 0x720F A BCC Block Check Code error has occurred in a received X Buffer message 0x730C An invalid message type was received when an Intermediate Response message was required 0x730F An expected X Buffer message was not received 0x740C An invalid next message type value was detected in an Intermediate Response message 0x750C An invalid response code was detected in an Intermediate Response message 0x760C An expected Intermediate Response message was not received within the response timeout interval PLC generated error codes for the GE Fanuc 90 30 90 70 and VersaMax SNPX protocol continue on the next page A 20 C mar p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables GE SNPX Protocol PLC Error Code Tables cont d Panel Error Code P499 Hex Value Ox8D0A Bad DOS Version Must have DO
30. function code is only applicable to newer devices and was not implemented in the unit selected It could also indicate that the server or slave is in the wrong state to process a request of this type for example because it is unconfigured and is being asked to return registered values Address out of range Check to make sure that the C more Micro tag and System ID match the Productivity Programming 0x0002 Software Tag Name and System ID The project file in the Productivity system and the imported CSV into C more Micro must be in sync with each other value contained in the query data field is not an allowable value for the server or slave This indicates a fault in the 0x0003 structure of the remainder of a complex request such as that the implied length is incorrect It specifically does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the application program since the Modbus protocol is unaware of the significance of any particular value of any particular register 0x0004 An unrecoverable error occurred while the server or slave was attempting to perform the requested action micro EA3 USER M Hardware User Manual 2nd Edition Cmar P A 5 Appendix A Panel amp PLC Error Code Tables Do more Error Code P499 Explanation NOTE The following errors can be generated from the designated PLC are monitored by the C more Micro panel and displayed on the panel
31. il System Configuration update is complete to continue communications 0x0B Invalid Mode Ensure that the switch on the CPU is in Term mode OxOC Mode Change Active Occurs when a PLC mode change is attempted while a mode change is in progress In some cases it takes several scans for a mode change 0x0D Mode Locked Occurs when mode change is attempted and keyswitch is not in Term 0x0E Invalid Password Enter Do more password in Password field of C more Micro Panel Manager for this device 0x0F Resource Locked Occurs when trying to update a tag that is forced Force must be removed in order to update the tag 0x010 Doc Update Active Occurs when someone attempts to access the documentation file while it is being written back to ROM 0x011 Invalid Driver Occurs when attempting to read driver data from a driver that doesn t exist 0x012 Invalid Driver Data Occurs when attempting to read a driver data type that isn t valid 0x013 Shared RAM write failed Occurs when attempting to read or write to a module s shared RAM and it fails Usually occurs when the module has A 6 C mar p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables DirectLOGIC Error Code P499 Explanation The P499 error code is used to show any errors that are generated by the connected PLC A The P499 error message includes a four digit hexadeci
32. ime interval 0x330C An SNP Request or Response was aborted prior to completion due to reception of a Break 0x340C PLC backplane communications error 0x350C Invalid Piggyback Status data memory type or address Communications have not been established 0x360C Invalid SNP Slave SNP ID Must be a 0 7 ASCII characters plus a terminating null character 00h The Null SNP ID eight bytes of 00h may be used to specify any single slave device The SNP master has received a response message containing an unexpected data length Usually indicates a 0x370C problem with the remote SNP slave device May occur when Series 90 70 commands Task Memory or Program Block Memory Read Write are issued to a Series 90 30 slave device 0x380C Response code in received SNP X response message does not match expected value Response code must equal the request code 80h 0x390C SNP X Response message exceeds maximum data size decimal 1000 bytes Data in the Response is ignored 0x400C A parity error has occurred on an X Attach Response message when establishing a new SNP X communication session Communications have not been established 0x400D The requested service is not supported by the SNP slave 0x400F Serial output timeout The slave was unable to transmit an SNP X message from the serial port May be due to missing CTS signal when the CMM module is configured to use hardware flow control Description
33. in an X Attach Response message when re establishing an 0x540C existing SNP X communication session Communications have not been established 0x540F An invalid Next Message Type value was detected in a received X Attach message For an X Attach message the Next Message Length must be zero An invalid response code was detected in an X Attach Response message when re establishing an existing SNP X 0x550C communication session Communications have not been established 0x550F An invalid request code was detected in a received X Attach message An expected X Attach Response message was not received within the response timeout interval when re establishing 0x560C an existing SNP X communication session The master has retried the X Attach message twice without receiving a response Communications have not been established 0x600C parity error has occurred on an X Response message Ox600F A parity error has occurred in a received X Request message 0x610C A framing or overrun error has occurred on an X Response message 0x610F A framing or overrun error has occurred in a received X Request message 0x620C A BCC Block Check Code error has occurred on an X Response message 0x620F A BCC Block Check Code error has occurred in a received X Request message 0x630C An invalid message type was received when an X Response message was required 0x640C An invalid next message type value was detected in an X Response message 0x650C An invalid r
34. mal value displayed at the end of the message This value can be found in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the various DirectLOGIC communication protocols breakdown into a four digit hexadecimal value DirectLOGIC PLC Error Code Displayed Example P499 Recv Err Code 0002 cy DirectLOGIC K Sequence PLC Error Code Table The following table lists the errors that can be generated by the DirectLOGIC PLC when using the K Sequence protocol NOTE The following errors can be generated from the designated PLC are monitored by the C more Micro panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information Panel Error Code eee ee P499 Hex Value p 01F8 Error setting value 020D Error in key mode 021C Password protected DirectLOGIC DirectNET PLC Error Codes There are no PLC generated errors that occur when using the DirectNET protocol EA3 USER M Hardware User Manual 2nd Edition C mor P A 7 micro Appendix A Panel amp PLC Error Code Tables Allen Bradley Error Code P499 Explanation The P499 error code is used to show any errors that are generated by the connected PLC The P499 error message includes a four digit hexadecimal value displayed at the end of the message This value can
35. message from master Description PLC Error 0x040E Serial output timeout The CMM module was unable to transmit the modem autodial output from the serial port May be due to missing CTS signal when the CMM is configured to use hardware flow control PLC Error 0x040F Invalid slave memory address or range in X Request message PLC Error 0x0413 Invalid COMMREQ status word location Unable to write SNP Status Word to local PLC memory PLC Error 0x050C may be due to invalid Status Word memory type or address PLC Error 0x050E Response was not received from modem Check modem and cable Invalid data length in X Request message PLC Error 0x050F Data length must be non zero and may not exceed decimal 1000 bytes PLC Error 0x0513 Invalid COMMREQ data PLC Error 0x060C Master device memory type is not valid in this PLC Modem responded with BUSY PLC Error 0x060E Modem is unable to complete the requested connection The remote modem is already in use retry the connection request at a later time X Buffer data length does not match the service request in X Request message PLC Error 0x060F The X Buffer message length is obtained from the Next Message Length field in the X Request message the length of the data within the buffer message is always the message length PLC Error 0x070C Master device memory address or length is zero Modem responded with NO CARRIER PLC Error 0x070E Modem is unable to c
36. more Micro Panel Error Code Table The following table includes all of the error codes and error messages that the panel will display if the listed cause is detected All of these errors involve problems that could result with the panel communicating with the connected PLC Be aware that not all of the panel errors are used with each type of PLC that can be connected to the panel Error Code Error Message PLC Com Time Out A timeout occurred after sending a request to the PLC NAK Received A negative acknowledgement NAK control code has been generated during a read write request EOT Received An end of transmission has been sent by PLC in response to a read write setbit request STX is Not Found A rae of Text STX control code was not found in the data packet received from the PLC ETX ETB NotFound Neither an End of Text ETX nor an End of Transmission Block ETB control code was found in the data packet received from the PLC LRC Not Match There was an incorrect Longitudinal Redundancy Check LRC control code in the communications packet received from the PLC This is an indication that the data in the packet is corrupted CRC Not Match There was an incorrect Cyclic Redundancy Check CRC control code in the communications packet received from the PLC This is an indication that the data in the packet is corrupted Address NotMatch The address value returned in the data packet fr
37. nd Format Error Command too short 0x1003 Command Format Error Elements Data don t match 0x1004 Command Format Error Command format error 0x1005 Command Format Error Header Error Ox1101 Parameter Error Area classification missing 0x1102 Parameter Error Access Size Error 0x1103 Parameter Error Address range error PLC generated error codes for the Omron FINS protocol continue on the next page EA3 USER M Hardware User Manual 2nd Edition C mor Er A 27 Appendix A Panel amp PLC Error Code Tables Omron FINS Protocol PLC Error Code Table cont d Panel Error Code P499 Hex Value 0x1104 Parameter Error Address range exceeded 0x1106 Parameter Error Program Missing 0x1109 Parameter Error Relational Error Ox110A Parameter Error Duplicate Data Access 0x110B Parameter Error Response too long 0x110C Parameter Error Parameter Error 0x2002 Read Not Possible Protected 0x2003 Read Not Possible Table missing 0x2004 Read Not Possible Data missing 0x2005 Read Not Possible Program missing 0x2006 Read Not Possible File missing 0x2007 Read Not Possible Data mismatch 0x2101 Write Not Possible Read Only 0x2102 Write Not Possible Protected cannot write data link table 0x2103 Write Not Possible Cannot register 0x2105 Write Not Possible Program missing 0x2106 Write Not Possible File missing 0x2107 Write No
38. om the PLC is incorrect Re INV FUN Code The function code returned in the data packet from the PLC is incorrect DataSizeNotMatch There are an incorrect number of bytes found in the data packet returned from the PLC INV Val FUN Code There is an invalid value in the function code INVALID COMMAND There was an invalid command sent to the PLC that wasn t recognized by the PLC ENQ Received If the data packet does not include a negative acknowledgement NAK 0x15 value in the defined packet field then an enquiry ENQ control code error will be displayed TransID NotMatch This error will be displayed if after checking the Transaction ID Byte in the data packet there is no match to what was requested Device Not Found APLC device designated as Device could not be found DataByte Com Err The data part of the packet received contains 0 bytes of data Out of Add Range The touch panel requested a file number larger than 255 Parity Error Parity error occurred Can tOpenS Port Can t open serial port PLC Not Match PLC Number does not match Can t Reset DCB Unable to reset the Data Communications Bit Not Connected Cable not connected properly No Other Dev Cannot detect other devices PollingListErr Panel not in polling list PLC Connection Time Out PLC Connection Time Out Memory Error Memory Type Incorrect No
39. omplete the requested connection Check the local and remote modems and the telephone line Queue Full indication from Service Request Processor in slave PLC CPU PLC Error 0x070F The slave is temporarily unable to complete the service request The master should try again later It is recommended that the master wait at least 10 msec before repeating the X Request PLC generated error codes for the GE 90 30 90 70 and VersaMax SNPX protocol continued on the next page EA3 USER M Hardware User Manual 2nd Edition C mor E A 1 5 Appendix A Panel amp PLC Error Code Tables GE SNPX Protocol PLC Error Code Tables cont d Panel Error Code P499 Hex Value 0x080C Unable to read or write master device memory locations specified in COMMREQ Usually caused by invalid memory address for this PLC SNP message exchange may have taken place 0x080E Modem responded with NO DIALTONE Modem is unable to complete the requested connection Check the modem connections and the telephone line Service Request Processor response exceeds 1000 bytes 0x080F the SNP X slave device cannot return the data in an X Response message This error applies to CMM module only Description 0x090C Master device memory data length exceeds maximum data size of CMM module 2048 bytes Must use a smaller data length Use multiple COMMREQs if total data length exceeds this maximum value 0x090E Modem res
40. or Code Tables cont d PLC Errors for Allen Bradley DH485 Protocol EXT STS Command Code for FO Command Panel Error Code P499 Hex Value Ox7 Insufficient memory module size 0000h is returned OxB Access denied privilege violation Resource not available or cannot do OxE CMD cannot be executed Invalid parameter Failure during processing Duplicate label File open by another node owner s local node address 1 byte Program owned by another node program owner s local node address 1 byte Description A 12 C mar E EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables GE Error Code P499 Explanation ry The P499 error code is used to show any errors that are generated by the connected PLC The P499 error message includes a four digit hexadecimal value displayed at the end of the message This value can be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the GE 90 30 90 70 Micro 90 and VersaMax Micro SNPX communication protocols breakdown into a four digit hexadecimal value GE Error Code P499 Message Example P499 Recv Err Code 020C EA3 USER M Hardware User Manual 2nd Edition C mar E A 13 Appendix A Panel amp PLC Error Code Tables GE SNPX Protocol PLC Error Code Tables The following table lists the errors that can be generated b
41. ory to handle request OxCF05 Specified device is not available in the system not present 0xD005 One or more PLC modules configured have unsupported revision 0xD105 Packet size or total program size does not match input 0xD205 Invalid write mode parameter 0xD305 User Program Module UPM read or write exceeded block end 0xD405 Mismatch of configuration checksum 0xD505 Invalid block name specified in datagram 0xD605 Total datagram connection memory exceeded 0xD705 Invalid datagram type specified 0xD805 Point length not allowed 0xD905 Transfer type invalid for this Memory Type selector OxDA05 Null pointer to data in Memory Type selector 0xDB05 Invalid Memory Type selector in datagram OxDC05 Unable to find connection address OxDD05 Unable to locate given datagram connection ID OxDE05 Size of datagram connection invalid OxDF05 Invalid datagram connection address PLC generated error codes for the GE Fanuc 90 30 90 70 and VersaMax SNPX protocol continue on the next page EA3 USER M Hardware User Manual 2nd Edition C mor Er A 2 1 Appendix A Panel amp PLC Error Code Tables GE SNPX Protocol PLC Error Code Tables cont d Panel Error Code P499 Hex Value OxE005 Service in process cannot login OxE105 No I O configuration to read or delete OxE205 IOS could not delete configuration or bad type OxE305 CP
42. ponded with ERROR Modem is unable to complete the requested command Check the modem command string and modem Ox0A0C Slave device memory type is missing or not valid OXOADE Modem responded with RING indicating that the modem is being called by another modem Modem is unable to complete the requested command Retry the modem command at a later time 0x0BOC Slave device memory address is missing or zero OxOBOE An unknown response was received from the modem Modem is unable to complete the requested command Check the modem command string and modem The modem response is expected to be either CONNECT or OK OxOCOC COMMREQ Data Block Length is too small When expected COMMREQ length is 6 words or less An improper length may cause other minor error codes 6 11 Ox0D0C Invalid Diagnostic Status Word DSW starting word or length OxOEOC Invalid maximum SNP message data size Must be an even value from 42 to 2048 Ox0FOC Invalid Privilege Level Must be 0 through 4 or 1 0x100C Invalid Fault Table selector Must be 1 for I O Fault Table or 2 for PLC Fault Table Unexpected Service Request Processor error Ox100F This error applies to CMM module only the unexpected SRP error code is saved in the Diagnostic Status Words in the CMM module 0x110C Invalid Fault Table starting index Must be 1 32 for I O Fault Table or 1 16 for PLC 0x120C Invalid fault count Must be 1 32 for I O Fault Table or 1 16 for PLC Fault
43. ror 0x250D Unit Error SYSMAC BUS No duplication 0x250F Unit Error Memory Error 0x2510 Unit Error SYSMAC BUS terminator missing 0x2601 Command Error No protection 0x2602 Command Error Incorrect password 0x2604 Command Error Protected 0x2605 Command Error Service already executing 0x2606 Command Error Service stopped 0x2607 Command Error No execution right 0x2608 Command Error Settings not complete 0x2609 Command Error Necessary items not set Ox260A Command Error Number already defined 0x260B Command Error Error will not clear 0x3001 Access Right Error No access right 0x4001 Abort Service aborted Description EA3 USER M Hardware User Manual 2nd Edition more A 29 Appendix A Panel amp PLC Error Code Tables Siemens Error Code P499 Explanation The P499 error code is used to show any errors that are generated by the connected PLC The P499 error message includes a four digit hexadecimal value displayed at the end of the message This value can be looked up in the specific PLC s error tables to determine the cause of the error The possible PLC generated error codes for the Siemens PPI communication protocols breakdown into a four digit hexadecimal value as shown in the following diagram Siemens PPI Error Code P499 Breakdown Relay Main response Sub response error flag code code word Lofofofofofo ofo ofo ofo ofi 1 o WU 131110 B T
44. rror occurred within the SNP task in the CMM module in this PLC This error may occur in either an SNP master or an SNP slave The minor error code contains the specific error code Description 0x000D Remote SNP Error An error occurred within the SNP slave task in the CMM module in the remote PLC The minor error code contains the specific error code 0x000E Autodial Error An error occurred while attempting to send a command string to an attached external modem The minor error code contains the specific error code 0x000F SNP X slave error An error occurred within the SNPX task in the remote slave device The minor error code contains the specific error code 0x0013 Port configurator error 0x0050 Problem with sending mail to the slave Service Request task Series 90 70 PLC CPUs only 0x0051 Problem with getting mail from the slave Service Request task Series 90 70 PLC CPUs only 0x0055 Slave SNP task timed out before receiving an SRP response Series 90 70 PLC CPUs only 0x0056 Slave SNP task could not find the requested datagram connection Series 90 70 PLC CPUs only 0x0057 Slave SNP task encountered an error in trying to write the datagram Series 90 70 PLC CPUs only 0x0058 Slave SNP task encountered an error in trying to update the datagram Series 90 70 PLC CPUs onl PLC generated error codes for the GE 90 30 90 70 and VersaMax SNPX protocol continue on
45. s screen as a hexadecimal value in panel error code P499 if active Error Code Description Resolution 0x01 Unknown Command Occurs when a message has been corrupted or protocol version is mismatched Check versions and update appropriately If versions are correct check cabling routing and switches for bad packets 0x02 Out of Sessions Too many devices connected to the CPU Reduce the number of devices connected 0x03 Illegal Operation Occurs when permission level is not sufficient for the operation performed by the panel Increase the permission level to correct the problem 0x04 Invalid Session Session number does match for sending device Re establish connection by power cycling or sending updated project 0x05 Out of Range Invalid address exists Ensure that address range is expanded and load configuration to the CPU 0x06 Invalid Argument Occurs when message cannot be parsed correctly Could occur from noise or faulty wiring 0x07 Program Update Active Wait until program update is complete 0x08 No Token Occurs when client attempts to update the project without first acquiring the program update token 0x09 Program Update Inhibited Occurs when client attempts to update the project while ST21 is true This allows the customer to use the program to prevent the project from being updated Ox0A System Configuration Update Active Wait unt
46. t Possible File name already exists 0x2108 Write Not Possible Cannot change 0x2201 Not executable in current mode Not possible during execution 0x2202 Not executable in current mode Not possible while running 0x2203 Not executable in current mode Wrong PLC mode Program 0x2204 Not executable in current mode Wrong PLC mode Debug 0x2205 Not executable in current mode Wrong PLC mode Monitor 0x2206 Not executable in current mode Wrong PLC mode Run 0x2207 Not executable in current mode Specified node not polling node 0x2208 Not executable in current mode Step cannot be executed 0x2301 No such device File device missing 0x2302 No such device Missing memory 0x2303 No such device Clock missing 0x2401 Cannot Start Stop Table missing 0x2502 Unit Error Memory Error 0x2503 Unit Error I O setting Error 0x2504 Unit Error Too many I O points 0x2505 Unit Error CPU bus error 0x2506 Unit Error I O Duplication Description PLC generated error codes for the Omron FINS protocol continue on the next page A 28 C mar p EA3 USER M Hardware User Manual 2nd Edition Appendix A Panel amp PLC Error Code Tables Omron FINS Protocol PLC Error Code Table cont d Panel Error Code P499 Hex Value 0x2507 Unit Error I O bus error 0x2509 Unit Error SYSMAC BUS 2 error Ox250A Unit Error CPU Bus Unit Er
47. x1 DST node is out of buffer space 0x2 Cannot guarantee delivery link layer The remote node specified does not ACK command 0x3 Duplicate token holder detected 0x4 Local port is disconnected 0x5 Application layer timed out waiting for response 0x6 Duplicate node detected 0x7 Station is offline 0x8 Hardware fault Description PLC generated error code for the Allen Bradley DF1 Protocol continue on the next page micro EA3 USER M Hardware User Manual 2nd Edition EC nr e A 9 Appendix A Panel amp PLC Error Code Tables Allen Bradley DF1 Protocol PLC Error Code Tables cont d Panel Error Code P499 Hex Value 0x0 not used 0x1 A field has an illegal value 0x2 Fewer levels specified in address than minimum for any address 0x3 More levels specified in address than system supports 0x4 Symbol not found 0x5 Symbol is of improper format 0x6 Address does not point to something usable 0x7 File is wrong size 0x8 Cannot complete request situation has changed since start of the command 0x9 Data or file size is too large OxA Transaction size plus word address is too large OxB Access denied improper privilege OxC Condition cannot be generated resource is not available OxD Condition already exists resource is readily available OxE Command cannot be executed OxF Histogram overflow 0x10 No access 0x11 Illegal data type 0x12 Invalid parameter or invalid data 0x13 A
48. y the GE 90 30 90 70 and VersaMax PLC when using the SNPX protocol NOTE The following errors can be generated from the designated PLC are monitored by the C more Micro panel and displayed on the touch panel s screen as a hexadecimal value in panel error code PLC 499 message if active Please refer to the PLC manufacturer s documentation for additional information Panel Error Code P499 Hex Value No error Successful completion This is the expected completion value in the COMMREQ Status Word Insufficient Privilege For Series 90 70 PLC the minor error code contains the privilege level required for the service 0x0002 request 0x0004 Protocol Sequence Error The CPU has received a message that is out of order 0x0005 Service Request Error the minor error code contains the specific error code 0x0006 Illegal Mailbox Type Service request mailbox type is either undefined or unexpected 0x0007 The PLC CPU s Service Request Queue is full The master should retry later It is recommended that the master wait a minimum of 10 msec before sending another service request Ox000A SNP DOS Driver Error The minor error code contains the specific error code lllegal Service Request The requested service is either not defined or not supported This value is returned in lieu of 0x000B the actual sa value passed in the SNP error message to avoid confusion with the normal successful COMMREQ completion 0x000C Local SNP SNP X Error An e