Home

Manual - Kentec

image

Contents

1. 191435 13534 13534 405 35044 PROGRAMMABLE OUTPUT PORT SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 30 of 30
2. 23 19 1 Fire Indications 23 19 2 23 24 19 3 Other Indications 24 25 20 Device Default Settings 25 20 1 Inputs Devices atta an 25 20 2 DEVICES u u unn ia Qaya habia up 26 2 Panel Default 26 22 Rai Oe RG ie 26 23 RepeagterStav usq 27 Page 1 Front Panel Layout amp Internal Arrangement 28 2 Typical Connection Scheme amp Connector Pinouts 29 3 ayOurOr Circuit Bands a aa a 30 SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual 1 INTRODUCTION The SOLO is an analogue addressable fire detection and alarm control panel capable of covering a maximum of 16 zones with up to 127 individual Apollo protocol devices Solo supports loop powered sounders and if used as sensor bases the sounders do not occupy an address in the range 1 127 thus leaving these addresses free for other devices Any number of devices can be allocated to any zone ensuring that any system configuration can be easily accommodated To ensure that the system is installed and commissioned with the minimum of trouble it should be carefu
3. 12 13 8 3 Panel Sounder Delay Organising 13 8 4 Device Alarm Delay 13 8 5 Organising Delay hapas 14 8 6 View 14 8 7 Cleat EVent 14 8 8 Printer Disable 14 5 9 Prip evens 15 8 10 Loop Configuration 15 9 Panel 16 10 Volt Free 17 17 JO Fault Contact 17 10 3 Alarm 17 SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Remote Control 18 FaU 18 RESENS nan 18 11 3 INT Intermittent 18 114 18 CSUENCE 19 12 19 13 Detection 19 20 14 Battery Charserand PSU 20 21 System aqila aaa 21 16 Earth Monitoring 21 22 17 Watchdog 22 15 Operation 22 22 23 19 AMGICABONS
4. Failure of the system fuse is indicated by a blank display a continuous tone from the internal buzzer and operation of the fault contact The system is completely inoperative when the system fuse has failed and this fault should be repaired as soon as possible 16 0 EARTH FAULT MONITORING The fire alarm system should have none of its supplies or signalling lines connected to earth This ensures that two lines of different polarity or potential can not be joined by earth which may prevent the system from functioning properly or produce false alarms The control panel therefore monitors the earth connection which should be at approximately 2 5 volts above the panels OV or negative supply If the earth potential falls below 1 0 volts with respect to the panel OV the display will show POWER FAULT 001 001 Negative earth fault SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 21 of 30 16 0 EARTH FAULT MONITORING continuea If the earth potential rises above 4 0 volts with respect to the panel OV the display will show POWER FAULT 001 001 Positive earth fault Any earth fault will light the Common Fault LED sound the internal buzzer and operate the fault contact Both will also be recorded in the event register Connection of the panel to a PC via the configuration lead sometimes produces an earth fault This is quite normal and can be ignored 17
5. Sounder delay and delay time can be changed at the panel via access level 3 see section 8 3 22 0 DRIFT COMPENSATION Discovery devices are able to automatically compensate for sensitivity drift within a certain range This ensures that the sensitivity of the device remains constant over its operational life When a device becomes contaminated to a level of 85 of its compensation limits its address is addedd to a list which can be viewed under the contamination status menu Devices which are contaminated to the extent where no further compensation can be made will announce a maintenance fault at the control panel and should be cleaned or replaced at the earliest opportunity SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 26 of 30 23 0 REPEATERS The Solo can support up to 16 repeater panels via a simple 2 core wire link To communicate with repeaters the main panel must first be fitted with a repeater driver card This plugs into the expansion port shown in annex 3 The panel must be completely powered down before this card is fitted Failure to do this will result in damage to both the panel and repeater driver card Whilst the panel is powered down the repeater communication cable should be connected to the COMMS terminals at the left hand side of the terminal block on the main panel PCB observe polarity The panel then needs to be configured using a PC
6. All volt free contacts are intended for switching low power and low voltage signals only Under no circumstances should voltages or currents above the ratings listed below be exceeded Note These functions may not be used to provide any Options with Requirements as specified in EN54 2 10 1 Rem Sig Contact The Rem Sig contact is a volt free changeover which is rated at 1 amp at 30 volts DC This contact will operate upon any fire or evacuate condition and will remain operated until the panel is reset i e it will not switch off when the alarms are silenced The contact will not operated however if the panel is in zone test mode and the activation is from the zone on test Typical uses for this contact are remote signalling of the fire condition to a house system or automatic dialler The contact can be disabled for example if a fire test is being done as described in section 7 3 10 2 Fault Contact The fault contact is a volt free changeover which is rated at 1 amp at 30 volts DC This contact will operate upon any fault condition including total power failure and will self reset when the fault has cleared Typical uses for this contact are remote signalling of the fault condition to a house system or automatic dialler The contact can be disabled as described in section 7 4 10 3 Alarm Contact The alarm contact is a volt free changeover which is rated at 1 amp at 30 volts DC This contact will follow the action of
7. SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 19 of 30 13 0 DETECTION CIRCUIT Continued Upon detection of a short or open circuit the display shows LOOP FAULT 001 001 Loop open or short cct The common fault LED will flash and the buzzer will sound Both of these events will be recorded in the event register When the fault is cleared the panel must be reset 14 0 BATTERY CHARGER AND PSU The battery charger and PSU are integral to the panel The control panel requires one 12 volt 7 ampere hour battery to maintain operation for 24 hours and thereafter supply the full alarm load for half an hour The panel power supply converts the nominal 12 volts to the 24 volts and 32 volts required by the detection and sounder circuits automatically upon failure of the mains The battery is an essential part of the system and correct charging will maximise its life The output to the battery is set at the factory to the optimum recommended by battery manufacturers for use in a temperate climate and varies with temperature as follows Temperature Output 0 14 22 14 6 10 14 09 15 14 02 20 13 93 25 13 82 30 13 44 If adjustment is necessary turn the adjustment control see annex 3 very gently until the voltage is correct for the current ambient temperature The panel will display a fault message if
8. Silence button when this screen is displayed PANEL SOUNDER DELAY ORGANISING Sounders organised 8 4 Device Alarm Delay Organising The 24 local programmable outputs and the outputs of all field devices are listed as follows DEVICE ALARM DELAY ORGANISING Address 003 1 is not organised By using the Evacuate up and Reset down buttons all output addresses and local outputs can be viewed and those which are required to be delayed can be selected by pressing the Silence button The display will then show DEVICE ALARM DELAY ORGANISING Address 003 1 is organised SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 13 of 30 8 0 FACILITIES MENU access LEVEL 3 Continued 8 5 Organising Delay Time Once the outputs have been selected as organised or not as required a further press on the Enter button allows the delay time to be selected as follows ORGANISING DELAY TIME 1 minute Use the Evacuate up and Reset down buttons to select the required delay time 0 5 to 10 minutes then press Enter 8 6 View Events The system stores the last 100 events which have occurred To view these press the Evacuate up or Reset down buttons to scroll through the event log A typical event log display will show VIEW EVENTS 1 OF 25 26 01 98 11 21 System initialising 8 7 Clear Event Register Once
9. 0 WATCHDOG The Panel contains a Watchdog circuit which monitors correct execution of the operating programme If the programme stops as could happen in the event of a severe electrical storm or other interference the watchdog circuit will reset the system and attempt to start the programme running again Whether this is successful or not the Watchdog LED inside the panel will light and remain lit until the Watchdog reset switch on the main PCB is operated See annex 3 18 0 OPERATION Operation of the fire alarm system should be as simple and straightforward as possible The SOLO maintains this philosophy by utilising the minimum number of controls and highlighting the most important indications This ensures that a concise and unambiguous indication of the status of the system is presented to the user at all times 18 1 Controls There are 3 main controls required for the operation of the fire alarm system A means of sounding the alarms from the panel A means of silencing alarms from panel means of resetting the alarms from the panel All other functions associated with the essential requirements of the system are automatic and require no user intervention Operation of all of the controls with the exception of Lamp Test and More Events is inhibited until the controls are enabled by operation of the Enable Controls keyswitch Without the Enable Controls keyswitch operated pressing the reset b
10. above configure automatically Reconfigure automatically Reset CONFIGURATION MENU Transfer previously created Reconfigure from PC configuration from PC to panel Reset CONFIGURATION MENU Transfer current configuration Transfer configuration to PC to PC for storage or editing Reset CONFIGURATION MENU Make no changes Run with current configuration 5 2 Zone Allocation To allocate addresses to other zones without doing a download from a PC it is necessary to enter the menu list To do this insert the enable key and hold the Enter button until the display shows ENABLE DISABLE ZONES Zone is enabled Press the More Events button once to allow level 3 password entry Use Evacuate up Reset down and Silence next to enter the number 1000 then Enter to enter access level 3 The display will then show DEVICE CONFIGURATION Switch on write enable to view change Turn on the write enable switch The display will then show CONFIGURE ZONE Addr xxx x Device Type zone 1 The actual address and device type will of course depend on what is connected at the lowest address on the system SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 5 of 30 5 POWERING THE PANEL continuea The available addresses and local programmable outputs can now be scrolled using the Ev
11. and the SOLO configuration programme to communicate with the required number of repeaters Once the repeater s have been connected and powered the main panel should be restarted ensuring that the write enable switch is off After the panel has finished initialising the system the repeaters should display the time and date and if programmed the suppliers name as per the main panel Any events on the main panel should now be displayed immediately on all repeaters Repeaters can also silence reset or evacuate the system in the same way as the main panel can following operation of the enable switch The repeater driver card and the repeaters themselves have two LED s which flicker whilst communications are in progress These can be used as a quick indication that all is well If the LED s are on permanently or are not on at all then there is probably a fault on the communications cable If the communications cable becomes disconnected the repeaters will automatically resume communication with the control panel upon re connection SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 27 of 30 1 FIRE IN ZONE Q FIRE CONTROL PANEL secre ENA Pon 2 5116 365 0 12 MAINS ENTRY FIXING HOLES x3 K5001 PCB 100 VA 14V TRANSFORMER 22
12. available from the stand by battery Note This output may not be used to provide any options with requirements as specified in EN54 2 13 0 DETECTION CIRCUIT This control panel must be used only with Apollo Series 90 XP95 or Discovery range of devices Four terminals and out and in are provided for connection to the detection circuit which should be wired as a loop with all devices connected across the cables such that out connects to in and out connects to in see fig 4 Short circuit isolators must be fitted in the detection circuit wiring in accordance with the appropriate fire detection systems standard As aminimum these should be wired such that a short or interruption of the detection circuit will not prevent the indication of the fire alarm from more than 20 fire detectors and or call points Fitting short circuit isolators ensures that only part of the detection circuit becomes disconnected from the control panel i e the part between the isolators in the event of a short circuit fault In this respect the more isolators that are fitted the greater the system integrity but practical considerations and cost dictate that this part of the system should be very carefully planned The control panel normally supplies power and data to the detection circuit from the out and in terminals it occasionally switches off the supply from the in terminals to check for open circuit faults on the loop wiring
13. carefully commissioning the system using the PC configuration utility should be simple and straight forward The PC configuration utility has many benefits over manual configuration such as defining cause and effect logic rapid message allocation suppliers name entry day night mode setting and storage retrieval of site data and is strongly recommended as the preferred method of data entry 6 0 TESTING THE SYSTEM To ensure that the system operates as required it is first necessary to activate each device as shown on the installation plan and ensure that the correct panel response and message is displayed Once this has been established as being correct the zone and address configurations should be recorded for future reference Next the sounder outputs should be checked making sure that they operate as required and that audibility levels are acceptable If any special sounder sequencing or control of output devices has been programmed all possible logical combinations should be checked to ensure that the required response is given Finally any use made of the volt free contacts or remote control inputs at the panel should be tested to ensure that they operate as intended The system should then be ready for handover to the client who should be given copy of the operators manual and a set of keys for accessing the panel 7 0 FACILITIES MENU access LEvEL 2 A number of facilities are provided which can only be accessed a
14. known noise generating sources such as mains cables is recommended Detection circuit cable size and type is dependant on the number and type of devices used and should be calculated for each installation Cabling for sounder circuits should be sized according to sounder load and cable length but 1 5mm should suffice in the majority of cases The control panel requires 230V AC supply which should be derived from a separate fused spur labelled fire alarm do not switch off The mains supply must include an earth conductor connected to the fixed installation earthing system This equipment relies on the building installation for protection and requires a5 amp protection device The mains supply should use cable with a minimum cross section of 1 5mm SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 3 of 30 5 POWERING THE PANEL Ensure that the panel is free from swarf wire ends knockout discs and any other debris NOTE The panel can not be powered by the battery until the mains is first connected 5 1 Configuring the Panel When supplied the panel will contain no configuration and when power is first applied the display will show SYSTEM INTEGRITY CHECK For about 7 seconds followed by CONFIGURATION MENU Configure automatically Or if the evacuate button is pressed CONFIGURATION MENU Configure from PC To select either of t
15. the charging voltage is set too high as this can be dangerous causing distortion of the battery case but care must be taken to ensure that the charge voltage is not set too low or the battery will not reach its optimum capacity The battery charger output is protected by a conventional 20mm 315 mA glass fuse which protects against short circuit or battery reversal See annex 3 SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 20 of 30 14 0 BATTERY CHARGER AND PSU continuea The control panel monitors the battery connection and fuse constantly Disconnection of the battery or failure of the fuse will display POWER FAULT 001 001 Battery disconnected During a mains failure condition the panel monitors the voltage of the battery and when the voltage reaches the battery manufacturers recommended minimum voltage of 10 5 volts the display will show a low battery voltage warning If the voltage continues to fall to about 9 5 volts the battery will automatically be disconnected to prevent damage to the battery Power Ratings 230V AC mains 100VA max 5V DC supply 2 5W 14 DC supply 6W 24 DC supply 24W 32 DC supply 13 2W 15 0 SYSTEM FUSE To protect against the high current capacity of the battery a5 amp 20mm fuse is fitted which disconnects all circuitry except the current limited battery charger in the event of a major fault see annex 3
16. the panel has been commissioned the information can be cleared from the event log by pressing the Silence button The display will show CLEAR EVENT REGISTER Event register cleared 8 8 Printer Disable If the control panel is fitted with a printer it is sometimes desirable to disable the printer during testing or commissioning This is done by pressing the Silence button The display will then show PRINTER The printer is disabled To enable the printer press the Silence button again If the printer is disabled the following 2 menu items will not be available SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 14 of 30 8 0 FACILITIES MENU access LEVEL 3 Continued 8 9 Print Events Events can be printed by type as follows i Print fire events ii Print fault events H Print disable events iv Print other events Print all events To print the required events select the type using the Evacuate up and Reset down buttons then press the Silence button to start printing The display will show e g fire events PRINT EVENTS Printing fire events Whilst the printer is printing the next type can be selected or other menu items can be selected using the Enter and More Events buttons 8 10 Print loop Configuration The loop configuration can be printed in two ways i By zone 11 By address Th
17. 0 240V AC INPUT 3 AMP FUSE BS 1362 7 0 A H BATTERY KEEP ENCLOSURE FREE FROM SWARF AND DEBRIS AT ALL TIMES SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 28 of 30 2 DETECTION OTHER FIRE CIRCUIT SOUNDER SYSTEM CIRCUITS 20K XN 20K TRIP 5 a CONTROL pa RESET ALARM 5 TO COMMS A N 5 5 7 ia SUPPLIES COMMS 51 52 FAULT ALARM K5001 PCB CONNECTOR J5 ov ov ov DO NOT USE K5001 PCB 20 O O O 010 1000009 TX RS232 24 DO NOT USE COLLECTOR OUTPUTS 000000000000 2000000000000 PROCESSOR WATCHDOG RESET RESET FAULT INPUT VE 24 VOLTS SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 29 of 30 3 3505 aWYOISNVUL WOU saya ee JOVLIOA I 924 60053 924 10067 INONDO v lt ONITIOd 318VN3 1 9340 SOqHOIVA 1404 NOISNVdX3 15 9 gt 2 SLAdLNO WIANNOS
18. 30 19 0 INDICATIONS Continued Remote Fault When the remote control fault input facility is used the fault condition signalled to this input will illuminate the Remote Fault LED System Fault The System Fault indicator will illuminate in the event of failure of execution of routines associated with the main functions of the programme or corruption of the memory containing the programme or site configuration data CPU Fault Operation of the system is monitored by a Watchdog circuit which will attempt to reset the central processor unit in the event of a failure to execute the programme properly Operation of the Watchdog circuit is indicated by the Watchdog Operated LED inside the panel See fig 1 This indicator will remain lit whether the reset was successful or not until IT is reset using the Watchdog Reset switch See annex 3 If the reset is unsuccessful and the processor still fails to execute the programme properly then the CPU Fault LED will be lit 19 3 Other Indicators Supply Healthy Indicates that equipment is being supplied with power Pre alarm For sensors which are configured to report pre alarm the Pre alarm indicator will illuminate when the control panel receives a signal from a sensor which is 60 of the set fire threshold level The panel buzzer will operate but no outputs will be operated during a pre alarm condition Alarm Silenced The Alarm Silenced indicator will be illumin
19. Health and Safety at Work act 1974 to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used An article is not regarded as properly used if it is used without regard to any relevant information or advice relating to its use made available by the supplier This product should be installed commissioned and maintained by trained service personnel i IEEregulations for electrical equipment in buildings ii Codes of practice Statutory requirements iv Any instructions specifically advised by the manufacturer According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned with its use This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device shall be incorporated in the fixed wiring Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe Mains Transformer Technical Information Type 6 Input 230V AC Frequency 50 60 Hz Power 100 Out 5 14 24 amp 33V DC SOLO Single Loop Addressable Fire Control Panel Installa
20. IBUTES DEVICE PRE TRANS DISABLE PRE DAY POLL TYPE FIRE FAULT ALARM PARENT MENT ALARM NIGHT LEVEL LED DISCOVERY CALL POINT b 5 DISCOVERY iON D 5 5 5 5 DISCOVERY PHOTO D S S S S DISCOVERY HEAT D S S S S DISCOVERY DUAL D S S S S DISCOVERY MULTI CRITERIA D 5 5 5 5 XP95 CALL POINT 95 5 XP95 PHOTO 5 5 95 5 5 XP95HIGH TEMP HEAT D S S XP95 HIGH SENS PHOTO 5 5 90 5 90 5 5 590 5 5 95 SWITCH MONITOR 5 gt 5 gt XP95 MINI SWITCH D INTERRUPT XP95 SWITCH MONITOR D S S S S XP95 SWITCH MONITOR PLUS P S S S S S SELECTABLE D DEFAULT SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 25 of 30 20 0 DEVICE DEFAULT SETTINGS continuea 20 2 Output Devices DEVICE TYPE RESETABLE SILENCEABLE DELAYED PULSED 95 SOUNDER CONTROL UNIT 5 5 95 95 LOOP POWER D D 5 SOUNDER THREE CHANNEL z 5 ONE D S D S S CHANNEL I O S90 SHOP MONITOR p 5 D 3 S SELECTABLE D DEFAULT 21 0 PANEL DEFAULT SETTINGS Supplier Name Blank Passcode 1000 Sounder Delay No Delay Time 0 5 Minute Default Ring Mode Common Day Night Start 0800 Hrs Day NightEnd 1800 Hrs All of the above can be changed using the PC configuration programme
21. Solo Single Loop Analogue Addressable Fire Control Panel Apollo Protocol Installation Commissioning amp Operating Manual Issue 03 June 1999 CONTENTS Page introduction 1 2 3 sah si Sian sis Sco Vas sph a 3 4 3 5 Powering 4 1 the Panel 4 5 5 2 Zone and Text Allocation arnir A 5 6 5 3 Configuration 6 8 Testim the SY Sle 8 Facilities Menus Access Leve12 8 9 7 1 Enable Disable ZONES 9 7 2 Enable Disable Addresseg n s 9 10 7 3 Enable7 Disable Fire Contacto 10 7 4 Enable Disable Fault Contact u a L S a 10 7 5 Enable 7 Disable Sounders 10 Of Oe TEST AONE un Qu um pu h kusapa 11 1 1 Sev the System Clock sod a a 11 7 8 Contamination 11 12 7 9 Enter Level 3 12 8 Facilities menus Access Level 8 12 8 1 Zone Con S uration 12
22. abling SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 10 of 30 7 0 FACILITIES access LEVEL 2 Continued 7 6 Test Zones put one or more zones into test mode select the required zone using the Evacuate up and Reset down buttons to scroll to the desired zone number then press Silence alarm The display will show TEST ZONES Zone 15 in test mode When in test mode activation of a device in the zone under test will cause a normal response at the control panel and sound the sounders for 2 seconds The control panel will then self reset ready for the next device to be tested The Rem Sig relay contact will not operate during test mode The disablement will be displayed at access level 1 as follows DISABLEMENT 001 001 The fault contact is disabled The fault contact will not operate in response to any fault condition other than total power failure or system fuse F2 failure whilst disabled To re enable the fault contact use the same procedure as for disabling 7 7 Set the System Clock The panel contains a 24 hour clock which is battery backed To set the clock use the Evacuate up and Reset down buttons to scroll through the hours minutes etc and the Silence button to move to the next item on the clock menu i e day date year etc When the panel is in normal condition at access level 1 the
23. acuate up and Reset down buttons to select the first address to be allocated to zone 1 The zone number can be changed using the Silence next button The information entered is stored dynamically i e it is not necessary to press the Enter button to store the information it is stored as soon as the next address or zone is selected It is now possible to attach 40 character message to each address if required This is done by pressing the Enter button whilst in the Configure Zone menu and the display will show EDIT TEXT ADDR CHQ CP Letters numbers and punctuation marks can now be selected using the Evacuate up and Reset down buttons Once the desired character has been selected the Silence next button can be used to move to the next character This is repeated until the message is complete To enter the next message press the More Events button select the next address using the Evacuate up and Reset down buttons then press enter The next message can now be entered as before When all zones and messages have been entered the write enable switch must be turned off The system is now configured and will remember the programmed information even if the power is removed If things get confusing don t worry Switch off the Write Enable switch remove enable control key then re insert it and start again 5 3 PC Configuration Load the Solo configuration programme and th
24. ated only when a fire condition has been silenced Operation of a subsequent fire condition whilst the alarms are silenced will extinguish the Alarm Silenced indicator Remote Sig Operation of the fire relay contact Rem Sig is indicated by the Remote Sig indicator this will be upon any fire condition unless the fire contact has been disabled via the menu functions See section 7 3 Buzzer Silenced Silencing of the buzzer during a fault condition will be indicated by the Buzzer Silenced indicator Disabled Any disablement selected via the menu functions see section 7 or via cause effect will be indicated by illumination of the Disabled indicator Test The Test indicator will be illuminated whilst any zones are in test mode see section 7 6 SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 24 of 30 20 0 DEVICE DEFAULT SETTINGS When configuring automatically i e without using a PC to download data all device types will conform to the default settings These determine the trigger level of analogue devices the response of the panel fire fault etc to inputs and the action taken by output devices The trigger level of sensors and the default actions of all other input devices can be changed by using the PC configuration utility 20 1 Input Devices INPUT ACTIONS ATTR
25. ault contact will also be operated whilst the fault input is active and the event will be recorded in the event register 11 2 RES Reset The reset input can be used to reset the control panel from a remote location but will only operate following a Silence Alarm from either the front panel push button or the remote SIL silence input This input is Edge Triggered i e there is no danger of the system not functioning if the reset input is permanently connected to OV It is only upon connection to OV that the input activates A remote reset will be recorded in the event register as Remote Reset 11 3 INT Intermittent This input allows remote activation of all sounders in the intermittent mode i e pulsing on and off When activated the LCD will display Remote Alert The input is not latching therefore all sounder outputs will be turned off when the input is removed This allows the fire bells to be used for class change signalling in schools security alert or to be operated from the main system in a shopping precinct or other sectored site Operation of this input will not operate the Rem Sig relay contact and will be recorded in the event register as Remote Alert 11 4 CNT Continuous This input allows remote activation of all sounders in the continuous mode When activated the LCD will display RemoteEvacuate The input is not latching and all sounder outputs will be turned off when the input is removed This al
26. ce configuration found by the panel on the detection circuit and the configuration sent from the PC If the two configurations match the panel will display the time and date and the suppliers name if entered on the PC The system is now running normally and should be thoroughly tested to verify that it meets the requirements If the configurations do not match one or more fault messages will be displayed These messages can be used to reduce addressing errors on field devices as follows DISCONNECTED 002 002 Addr xxx x zone xx device type Indicates that this device was configured by the PC utility but was NOT found by the panel UNEXPECTED DEVICE 001 002 Addr xxx x Indicates that this device was not configured by the PC utility but WAS found by the panel A reasonable assumption in this situation is that the unexpected device should have the address shown by the disconnected fault SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 7 of 30 5 POWERING THE PANEL continuea This message DOUBLE ADDRESS 002 002 Addr xxx x zone xx device type Indicates that more than one device has been set to the same address There will probably be a disconnected fault present on the system at the same time as a double address fault and this device is likely to be the one incorrectly addressed If the system has been planned and the devices addressed
27. e required data file Connect the special download lead to the serial port on the computer and to the connector J5 on the panel see annex 2 amp 3 Ensure that the PC is set to communicate with the correct port under the file options menu This is usually COM 2 but if it will not work try one of the others Sometimes the PC will produce an earth fault on the panel This can be ignored To programme the control panel with a previously created configuration using the SOLO configuration utility first turn on the Write Enable switch reset via the internal Processor Reset switch see annex 2 amp 3 After the System Integrity check the display will show CONFIGURATION MENU Reconfigure automatically SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 6 of 30 5 POWERING THE PANEL continuea Press the Reset button until the display shows CONFIGURATION MENU Reconfigure from PC Press the Silence button to display PC CONFIGURATION Awaiting link system not operational Select send to panel on the PC The PC will display progress bars indicating each part of the configuration being sent After transfer the panel will display CONFIGURATION COMPLETE Turn off memory write enable switch After turning off the memory write enable switch the panel will start initialising This process involves comparing the actual devi
28. ese can be selected from the Print Loop Configuration menu by using the Evacuate up and Reset down buttons To print the selected configuration press the Silence button The display will show PRINT LOOP CONFIGURATION Printing configuration The zone configuration printout will list the addresses contained in each zone lowest numbers first and the address configuration printout will list all addresses lowest numbers first SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 15 of 30 9 0 PANEL SOUNDER OUTPUTS Two sounder outputs are provided in the panel which operate upon any fire alarm These supply a minimum of 23VDC and a maximum of 25VDC These outputs are not programmable but may be organised with a delay see section 8 3 Each output is individually fused and is capable of supplying an alarm load of 500mA or a total of 750mA over the two circuits therefore a short circuit on one output will not inhibit correct operation of the other The sounder outputs are monitored for short and open circuit faults and reverse their normal monitoring polarity when activated It is therefore necessary to use correctly polarised sounders on the system to prevent the sounders from consuming current when in the normal quiet condition To provide open circuit monitoring it is necessary to fit a monitoring resistor at the end of the sounder circuit wiring It is by pas
29. full time and date will be displayed on the top row of the display 7 8 Contamination Status Any sensors which are found to be near their calibration limits are listed here When a sensor is found to be at or beyond 85 of the point at which a maintenance fault warning will be given it is added to the list During the daily calibration routine each sensors drift is checked and if it is beyond 85 of the centre of the tolerance band the status will be displayed as per the example below CONTAMINATION STATUS Addr 123 Device Type 97 SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 11 of 30 7 0 FACILITIES MENU access LEVEL 2 Continued The lower line of the display will alternate between the information shown above and the location message for the device Further devices on the list can be viewed by scrolling with the Evacuate and Reset buttons 7 9 Enter Level 3 Password This is the last item on the menu at access level 2 and further presses of the Enter button without entering the level 3 password will continually scroll around these 9 items Entering the correct password set in the factory to 1000 will allow access to further menu items The password is entered using the Evacuate up and Reset down buttons to scroll through the numbers 0 to 9 and the Silence button to move to the next digit When the last digit has been entered pressing E
30. hese press the silence alarms button It is usual to configure automatically at this stage as this tells you exactly what the panel has found connected to the loop and this can then be compared with what is expected At the Configure Automatically prompt press the silence alarms button to configure automatically the panel will display AUTO CONFIGURATION Turn on memory write enable switch Turn on the switch located at the top of the display and wait for the progress bar to fill the screen while the panel analyses the connected devices After a couple of minutes the panel will display XXX devices found Turn off memory write enable switch Turn off the memory write enable switch The panel is now running with all devices allocated to zone 1 If the panel contains configuration data it will always run with that configuration when powered up or reset via the processor reset switch SW2 see annex 3 with the write enable switch off after intialising SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 4 of 30 5 POWERING THE PANEL continuea If powered or reset via SW2 with the write enable switch on the panel will first perform an integrity check as before then present the configuration menu but with 4 options which can be selected via the evacuate or reset switches and entered via the silence alarms switch as follows CONFIGURATION MENU As
31. lly planned before the installation is begun This involves allocating an address to each device except base sounders and allocating a message of up to 40 characters including spaces to each address to assist in the location of the devices Devices should then be grouped into zones in accordance with the appropriate fire detection systems design standard A fire alarm call point should be located near the panel The SOLO control panel offers an extensive list of features and options for the control and monitoring of plant equipment and sounders which can be configured via the PC configuration programme The Apollo range of compatible devices includes optical and ionization smoke sensors heat sensors switch monitors and relay or bell controllers Interfaces to conventional detection systems can also be catered for using zone monitoring devices Important This control panel should be used only with Apollo Series 90 XP95 or Discovery range of fire system components The control panel has the following options with requirements as defined in EN54 2 1 Fault signals from points 2 Coincidence detection 3 Delay of the actioning of outputs 4 Disablement of each address point 5 Test condition 6 Fire alarm devices sounders SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 1 of 30 2 Suppliers of articles for use at work are required under section 6 of the
32. lows the fire bells to be activated by other systems without the need to silence the alarms then reset at the panel Activation of this input will not operate the Rem Sig relay contact and will be recorded in the event register as Remote Evacuate SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 18 of 30 11 0 REMOTE CONTROL INPUTS Continued 11 5 SIL Silence The silence input can be used to silence the alarm from a remote location This input is Edge Triggered there is no danger of the system not functioning correctly if the silence input is permanently connected to OV Itis only upon connection to OV that the input activates A remote silence will be recorded in the event register as Remote Silence Alarm 12 0 AUX 24V AUXILIARY 24V DC An independently fused auxiliary 24V DC supply is available for powering equipment related to the fire alarm system The output is fused by a self reset fuse and therefore will not need replacing if it is tripped The panel will display AUX 24 V Supply Fuse Failed when the fuse is tripped and this message will also be recorded in the event register The aux supply is continuously rated for 250mA The minimum voltage is 23VDC and the maximum voltage is 25VDC The AUX 24V output should be used with caution particularly if used to permanently power other equipment as its use can have a considerable effect on the stand by time
33. n the system Disablements will be displayed at access level 1 as follows DISABLEMENT 001 001 Zone 1 Only fire inputs are suppressed during disablements The More Events button can be used to view all active disablements at access level 1 Zones can be re enabled using the same procedure as for disabling 7 2 Enable Disable Addresses To disable one more addresses sub addresses first select the address to be disabled using the Evacuate up or Reset down buttons then press Silence to disable The display will show ENABLE DISABLE ADDRESSES Address xxx x is disabled When a disablement is selected the buzzer will sound a continuous tone for 3 seconds and the Disabled LED will light and remain lit for as long as there any active disablements on the system Disablements will be displayed at access level 1 as follows DISABLEMENT 001 001 Addr xxx x zone xx If a location message has been assigned to the disabled address the second line of the display will alternate between the address zone and device type and the message SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 9 of 30 7 0 FACILITIES MENU access LEVEL 2 Continued Only fire inputs are suppressed during disablements The More Events button can be used to view all active disablements at access level 1 Addresses can be re enabled using the same pr
34. nfiguration package this facility does allow on site editing in situations where a PC may not be available and to correct minor mistakes SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 12 of 30 8 0 FACILITIES MENU access LEVEL 3 Continued From the configure zone menu select the address for which the message is to be edited or allocated then press Enter The display will show EDIT TEXT ADDR 001 0 ATG E In the bottom left of the display a cursor marks the position where the first character of the message will appear Upper and lower case letters numbers from 0 to 9 and punctuation marks can then be selected using Evacuate up and Reset down buttons To move to the next character press the Silence button When the message is complete the next address which requires message entry or editing can be selected by first pressing More Events then using the Evacuate up and Reset down buttons A press on the Enter button then allows entry editing of the message for that address 8 3 Panel Sounder Delay Organising The panel has two common conventional sounder circuits which can be delayed to allow confirmation of a fire condition if required To enable the delay facility press the Silence button when this screen is displayed PANEL SOUNDER DELAY ORGANISING Sounders not organised To disable the delay facility press the
35. nter will display the first item on the access level 3 menu It is possible via the PC configuration programme to change the password to any 4 digit number If entering the default password 1000 does not allow access to level 3 then this has been done To find the access level 3 password if this occurs it will be necessary to capture the configuration file from the panel using the SOLO configuration package and data transfer lead 8 0 FACILITIES MENU access LeveL 3 To enter access level 3 enter the password factory set at 1000 using the Evacuate and reset buttons then press Enter 8 1 Zone Configuration As described in section 5 manual configuration if the panel has not been configured using the PC configuration package all devices are placed in zone upon initialisation This menu allows any device or sub device to be placed in any zone Upon activation of the Write Enable switch the display will show CONFIGURE ZONE Addr 001 0 ATG E zone 1 To change the zone number press the Silence button until the required zone appears then press the Evacuate up or Reset down buttons to select the next address Repeat the procedure until all addresses appear in the required zones When all devices have been zoned press enter to edit text 8 2 Edit Text It is possible using the panel push buttons to enter text messages of up to 40 characters Although this is much better achieved using the PC co
36. ocedure as for disabling 7 3 Enable Disable Fire Contact To disable the fire contact press the Silence button The display will show ENABLE DISABLE FIRE CONTACT Fire contact 1 disabled The disablement will be displayed at access level 1 as follows DISABLEMENT 001 001 Fire contact is disabled The Rem Sig fire contact will not operate in response to any fire conditions whilst disabled To re enable the fire contact use the same procedure as for disabling 7 4 Enable Disable Fault Contact To disable the fault contact press the Silence button The display will show ENABLE DISABLE FAULT CONTACT Fault contact is disabled The disablement will be displayed at access level 1 as follows DISABLEMENT 001 001 The fault contact is disabled The fault contact will not operate in response to any fault condition other than total power failure or system fuse F2 failure whilst disabled To re enable the fault contact use the same procedure as for disabling 7 5 Enable Disable Sounders To disable the sounders press the silence button The display will show ENABLE DISABLE SOUNDERS Sounders are disabled The sounders connected to the panel loop powered sounders and bell controller outputs which are programmed to respond as sounders will not operate in response to any fire or evacuate condition To re enable the sounders use the same procedure as for dis
37. operation of the Silence button during a fire condition operation of the Reset button will reset the fire condition at the control panel and reset the detector or detectors which initiated the fire condition If the fire condition was initiated by call points or switch input devices then these must be restored to normal before Reset is operated otherwise the fire condition will return For details on the use of the Enter button see section 7 of this manual 19 0 INDICATIONS 19 1 Fire Indicators The primary indications on the control panel are those associated with the fire condition A common fire indicator will illuminate in the event of a fire detector call point or input device being operated accompanied by one or more Fire in Zone indicators to identify the zone in which the fire originated The common fire indicator will also illuminate if the Evacuate button is pressed and will remain lit until the condition is silenced then reset 19 2 Fault Indicators Common Fault The Common Fault indicator will illuminate upon any fault condition Further information about the nature of the fault can be obtained from the display or other fault indicators Sounder Fault An open or short circuit on the cabling to the sounder circuits connected to the control panel will illuminate the Sounder Fault indicator SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 23 of
38. sing a small monitoring current through this End of Line resistor that the control panel is able to detect breaks in the sounder circuit cables The panel is supplied with 20K end of line monitoring resistors and these should be used whenever possible However the circuits will tolerate any value of resistor between 7K and 42K If asounder open or short circuit fault occurs the panel will display SOUNDER 1 FAULT 001 001 Open or short circuit on sounder circuit 1 Or sounder circuit 2 if on the other circuit During the fault condition the buzzer will sound a continuous tone and the Sounder Fault and Common Fault LED s will flash The buzzer may be silenced by pressing the Silence button whereupon the Sounder Fault and Common Fault LED s will light continuously the buzzer will Beep every 7 seconds and the Buzzer Silenced LED will light A subsequent sounder fault will resound buzzer extinguish the Buzzer Silenced LED cause the Sounder Fault and Common Fault LEDs to start flashing The second fault can be viewed by pressing the More Events button Sounder faults are not latched by the control panel and fault conditions will clear with 10 seconds of the fault being removed Sounder circuit fuses are of the self reset type and require no maintenance or replacement SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 16 of 30 10 0 VOLT FREE CONTACTS
39. t access level 2 or access level 3 Access level 3 can be reached by entering the correct password at access level 2 or switching on the write enable switch To access the facilities menus insert the enable key and hold down the Enter button until the first menu item appears Further presses on the Enter button cycle forward through the menu items and presses on the More Events button cycle backwards through the menu items SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 8 of 30 7 0 FACILITIES MENU access LEVEL 2 Continued Note Pressing More Events with Enable Disable Zones on the display takes you directly to password entry If no buttons are pressed for more than 100 seconds the panel will revert to access level 2 or if the key is removed to access level 1 i e buttons not enabled The following describes each of the available facilities in the order that they will appear using the Enter button to cycle through them 7 1 Enable Disable Zones To disable one or more zones first select the zone to be disabled using the Evacuate up or Reset down buttons then press Silence to disable The display will show ENABLE DISABLE ZONES Zone XX is disabled When a disablement is selected the buzzer will sound a continuous tone for 3 seconds and the Disabled LED will light and remain lit for as long as there are any active disablements o
40. the panel sounder outputs i e it will de activate when the Silence alarm button is pressed and if the panel sounders are delayed then operation of this contact will also be delayed Typical uses for this contact are to activate sounders on a remote alarm system or trigger door release relays The alarm contact will be disabled and enabled with the sounders as described in section 7 9 SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 17 of 30 11 0 REMOTE CONTROL INPUTS The following inputs allow the basic controls of the panel to be duplicated by remote systems such as shopping precinct interfaces house fire control panels or control desks All of the inputs are activated by switching the OV terminal to the input terminal via a normally open switch or contact These inputs require a very low switching current therefore the contact or switch used should be suitable for switching currents as low as 0 1mA see fig 4 Note These functions may not be used to provide any options with requirements as specified in EN54 2 and could leave the panel in a non compliant state 11 1 FLT Fault The fault input can be used to indicate a fault at an associated system e g extinguishant release control panel and when operated will display Remote Fault on the LCD The input is non latching and when active will light the Common Fault LED and sound the fault tone on the buzzer The f
41. tion Commissioning and Operating Manual Page 2 of 30 3 INSTALLATION Installation of the panel should be carried out by qualified personnel only The electronic components within the panel are vulnerable to physical damage and damage by electrostatic discharges It is advisable to wear a wrist strap designed to prevent the buildup of static charges within the body before handling any electronic circuit boards Never insert or remove boards or components with the power on Mounting the Cabinet The site chosen for the location of the panel should be clean and dry and not subject to shock or vibration The temperature should be in the range 5 to 35 the humidity should not exceed 95 Open the cover using the key provided Using the chassis as a template mark the position of the fixing holes ensuring that the wall is flat at the chosen location Drill and plug the wall then fix the cabinet using all fixings The polarity of the battery connection should be carefully checked before proceeding 4 CABLING Cables should be brought into the cabinet using the knockouts provided and using couplers to maximise the space within the enclosure Inlet bushings or cable glands should be used to maintain insulation The screen or drain wires should be bonded to the earth terminals provided The maximum size of cable which can be terminated is 2 5 mm The communications protocol is highly immune to noise but sensible segregation from
42. utton will perform a lamp test to allow the user to check that all of the lamps are working If there is more than one event of any type on the panel indicated by 002 002 or similar on the right of the display and the More Events LED then these can be viewed by pressing the More Events button to advance through them SOLO Single Loop Addressable Fire Control Panel Installation Commissioning and Operating Manual Page 22 of 30 18 0 OPERATION Continued Operation of the enable control keyswitch puts the panel into access level 2 It is at this access level that the proper functions of the controls are available Operation of the Evacuate button will now sound all sounders continuously whether connected to the control panel loop or to field mounted bell controllers Operation of the silence button in the event of a fire will 1 Change the tone of the fire buzzer from rapid pips to one beep every 7 seconds ii Change the flashing zonal fire indicator to continuous Silence all sounders connected to the control panel and field mounted bell controllers iv Iluminate the Alarm Silenced LED Operation of the silence button in the event of a fault will 1 Change the tone of the buzzer from continuous to one every 7 seconds ii Illuminate the Buzzer Silenced LED Operation of the Reset Button has no effect without prior operation of the Silence Button following a fire or evacuate condition Following

Download Pdf Manuals

image

Related Search

Related Contents

CFW11 - DeviceNet Manual  Instructions d`utilisation support InFlow751  3 - EV-Power  Globalsat Technology GH-615B/GH  Graco ISPP025AA User's Manual  Sony VAIO VPCEE21FX  Cooler Master CRC-U01  Polti Flash  RV-722 Voltage Divider User and Service Manual    

Copyright © All rights reserved.
Failed to retrieve file