Home
        Level Products User Manual - Adaptive Wireless Solutions
         Contents
1.                 43  Figure 7 5 Setting a 22 Point Curve for Pressure Using WIM                              43  Figure 8 1 Pressure Setting Using WIM                       ssseeeeeee 44  Figure 8 2 Gauge Level Mode                       sssssssssseeseeee enne 46  Figure 9 1 WI Battery Kit   O1                  sssseseeeeenenenenn nene 50  Figure 9 2 WI BAT Field Unit Battery                      seemm 51  Figure 9 3 Menu Map to Error Log  Error Counter  RF Statistics  and Log  Gl  aring  M                   M ie 52  Figure 9 4 Definitions of error codes                     essseseeee 53  Figure 9 5 Error counter definitions    54  Figure 9 6 RF Statistics code descriptions                          ssssseseees 55  Figure 10 1 WI SL XX Dimensioned Mechanical Drawing                                   58  Figure 10 1 WI GL I XX Dimensioned Mechanical Drawing                                 60  Figure 10 2 WI GL E XX Dimensioned Mechanical Drawing                               62  Figure 10 3 WI GL E Y6 XX Dimensioned Mechanical Drawing                          64    AWS Level Field Units User Guide Rev 1210 VI    1 1    Introduction    USING THIS MANUAL    This manual is designed to assist in installing  operating  and maintaining AWS Level  Field Units  The manual is broken into sections as follows     2 Quick Start   This section summarizes what must be done in order to get the device installed   configured  and in operation quickly  However  it does not provide detailed inform
2.     Input     oma   Volts  set tc  10       Upper Value Normal Lower Value    6 5 Volts set to 2 5 Volts    Abnormal Condition    B 4        Normal Condition       0 L 1 ool b ool L 3 oo     Time  min sec  f    Abnormal Condition        Figure 6 14 Normal Upper and Lower Value Example    The Normal Upper Value would be an indication that the analog input is    high    and the  Normal Lower Value would be an indication that analog input is    low     Thus  the normal    operating condition for the analog input application would be found in between the two  Normal Values     The Time Deadband refers to the number of seconds that the measured reading must  stay in a certain condition before the Field Unit will actually switch to that condition  To  select a proper Time Deadband  consider the example in Figure 6 15     Input   Volts   Abnormal Condition Abnormal Condition Abnormal Condition Abnormal Condition  10    l  ix By Z gt   gt  lt  LA cM LEN  44  2   Normal Upper Value Normal Condition    set to 7 5 Volts    T     T    0  1 00 2 00 3 00    Time  min sec     Figure 6 15 Condition  Chatter  Without Time Deadband    AWS Wireless Level Products Field Units   User Guide Rev 0307    Notice that the Field Unit continues to cycle from Normal to Abnormal Conditions due to  the fact that the input value is fluctuating around the 7 5 Volt Normal Upper Value  This is  undesired  Adding a delay of several seconds before the Field Unit switches conditions  eliminates this  chatter   as
3.     aD on ens     b       ENTER        NK TST JENTER CRF ID        XXX     JENTER  NORM XR            5 STARR    4 STARR  3 STARR  2 STARR  1 STARR  NO LINK    Figure 3 4 Base Radio Link Test    When enough messages have been observed  link strength will be shown on the display   5 STARR indicates the strongest link  while 1 STARR indicates the weakest link  The  Link Test will continue to be evaluated and the rating on the screen may adjust itself   Keep in mind that the longer the Link Test runs the more data the Field Unit will have to  evaluate     The Field Unit installation site should strive to place the Field Unit in a location where it  receives the highest number possible  A stronger link means less data re transmits and  longer battery life     Conducting a Link Test from WIM    To conduct a Link Test from WIM  make sure that WIM is running on the PC attached to  the Base Radio  Then go to the Field Unit view and right click on the Field Unit you want  to test Received data transmission from  Figure 3 5      AWS Wireless Level Products Field Units   User Guide Rev 0307    12    VZ Accutech Wireless Instrumentation Manager  Connected     File View Help acm  Field Units       C Al Fek Unts Total Field Units  1  O Alarming Field Units otal Field Units  1  E A    Alarming Field Units  0  2 Peter Field Units Warning Field Units  1  ield Unit Groups    Base Radios     Ba i Selected Field Unit       Field Unit Types    Accutech Dual 4 20 m   Input    All Field Units    Mo
4.    To configure the abnormal transmission rate from the field unit  follow the menu map  below     Note Once WIM has been used to configure the Field Unit  this menu option will be  disabled on the Field Unit LCD menu  See Section 4 1 for more details     NEXT  ENTER     NEXT    NEXT    CABRA enter 1 5 SEC  10 SEC  15 SEC  20 SEC  40 SEC  60 SEC    Figure 6 8 Menu Map to Abnormal Transmission Rate Setting    30 AWS Wireless Level Products Field Units   User Guide Rev 0307    6 3 2 Configure the Abnormal Transmission Rate Using WIM  1  Open the configuration dialog box  See Appendix A      2  In the configuration dialog box  click the Sampling Rates tab to display the  sampling rate information as shown below     Gauge Level Pressure Properties    14 10     General   Range     peration Mode   Sensor Offset    Sampling Rates   Sampling Bands   Alarms    Update Rates    Normal Transmit Rate  j  Sec _ vl    Normal Sampling   Abnormal Sampling       Smart Smoothing    The Smart Smoothing feature rejects noise and glitches by averaging  samples within the deadband and ignoring the first sample outside the  deadband     I Enable Smart Smoothing    1 255 Seconds  Psi      SmartRate    The SmartRate feature causes the field unit to transmit its data  immediately any time the primary value changes by the amount set       Enable SmartRate    Load from File      Save to File    Cancel       Figure 6 9 Sampling Rates Tab    3  Select one of the time periods from the Abnormal Transmit Rate
5.    User Guide Rev 1210       Table of Contents    TABLE OF CONTENTS          erento anA Osan tete eee esee dress IV  TABLE  OF FIGURES               Ore bee Peace euer ainaani abiit nainii VI  1  INTRODUCTION             eerie teneo rene retento AAR TARA nene ceder 1  1 1  USING THS MAN UA   eee iere tte pete P re eget 1  1 2 ABOUT THE DEVICE    nenne 2  1 37   UNPACKING hri de tee ree tito e rb eroe 2  1 4 SOFTWARE COMPATIBILITY                   sse 2  QUICK START  2222265222620066 Idee teiteiddeseeccee rei idit creieniedoe 3  INSTALLATION i  roiie anaana                      setae 5  3 1 MECHANICAL INSTALLATION 9 5 bites pas Sua iiic ciii MuR 00000000 5  3 1 1 Field Unit Positioning    eec ttes 5  3 2    TESTING COMMUNICATIONS at tiet cutie  auatcata athe  it le abiti 8  3 2 1 Field Unit RSSI Diagnostic                       eene 8  SEL 081 5 111 eii  P PM ND 9  4 GENERAL CONFIGURATION                      eeeeeeeeeeneeen nennen nnn nnn nnne nnne nain 14  4 1 NAVIGATING USER MENU    entire te tene ret rib toe np 14  4 2 FIELD UNIT DISPLAYED MESSAGES                   sesenta 14  4 2   The Read Only Sequence                          sess 15  4 3 OVERALL CONFIGURATION MENU MAP       ccccccc cici i ciii eiii 16  4 4 SETTING THE FIELD UNIT TAG NAME                   eren 16  4 5 SETTING A USER PASSWORD             isssseseeeeneneeneeerenenne nnns 17  4 6 RESETTING ALL FIELD UNIT SETTINGS                    eene 19  5 CONFIGURING THE RF COMMUNICATIONS                           
6.   4  Enter the Value and Time Deadband for the limit    5  Type a message in the LCD Message box to be displayed on the Field Unit  when the value is beyond your set limit    6  Repeat steps 3 5 for the Lower Limit    7  Click OK to save and download the configuration changes to the Field Unit     39 AWS Wireless Level Products Field Units   User Guide Rev 0307    Gl    40    Configuring the Process Variable    This section helps you to select the engineering units and discusses the setting of a  measurement offset and the trimming of the process measurement  The subsections are  as follows     7 1 Zeroing the Sensor   7 2 Setting a Measurement Offset  7 3 Trimming the Measurement  7 4 Entering a 22  Point Curve    Zeroing the Sensor    Zeroing the sensor can only be performed from the Field Unit  You will need to check the     position zero     P ZERO  reading on the transmitter  The Level Field Unit is a sensitive  device  Its elevation and its orientation in the field may be different from the orientation in  the factory where it received its last configuration  To compensate for position changes   you may need to perform a sensor position adjustment once the unit is installed     If you have a Field Unit pressure reading of    zero      that is  the Field Unit reading is within  the specified accuracy of  0 1  of the full scale value when zero pressure is applied    there is no need to zero the sensor  If your    zero    reading is outside of this value  you will  need to
7.   The type of battery can be identified from the battery label on the field  unit     Be certain that you replace the battery with the battery specified on the battery  label as the battery contains protective components and must be replaced with  an identical kind to maintain the safety features of the product     To identify the type of battery in the individual field unit  first find the battery label  on the outside housing  If you see the note  Contains Battery Pack WI   BATTERY KIT     01  on the battery label  then you must replace the field unit  battery with AWS Battery Pack Part Number WI BATTERY KIT   01  These  battery packs  with AWS Part Number  WI Battery Kit  01     are available directly  from AWS and may be ordered by calling 800 879 6576     The AWS Battery Pack WI BATTERY KIT   01 is a battery replacement kit  The  kit contains a battery encapsulated with electronic safety components along with  two battery tie down clips     2  If you do not see the battery pack identification labels noted in item 1 above  your  field unit contains the following battery   TADIRAN    Lithium Inorganic Battery  non rechargeable  size    C        3 6Volts  s TL 2200 8     These replacement batteries  with AWS Part Number    WI BAT     are available  directly from AWS and may be ordered by calling 800 879 6576     3  To replace the battery or the battery pack  first power down the Field Unit by    pressing and holding the NEXT and ENTER buttons simultaneously for a few  momen
8.   eren 20  5 17  JRE  CHANNEL  SELECTIONS  3  p iie iE tee tie iere dts 20  5 2 RF BAUD RATE SELECTION            essent 21  5 3 RF IDENTIFICATION  RF ID  SELECTION                    eee 22  6 CONFIGURING THE SAMPLING AND TRANSMISSION RATES               23  6 1 SELECTING THE NORMAL TRANSMISSION RATE                  enne 23  6 1 1 Configure the Normal Transmission Rate from the  Field Ot RE T CETUR 24  6 1 2 Configure the Normal Transmission Rate Using  WIM eT 25  6 2 SELECTING THE NORMAL SAMPLING RATE    25  6 2 1 Configure the Normal Sampling Rate from the Field  KE A EN E ei apscaveasemcas cs ecc Dico refert nes 27  6 2 2 Configure the Normal Sampling Rate with WIM      28  6 3 SELECTING THE ABNORMAL TRANSMISSION RATE                    ene 29  6 3 1 Configure the Abnormal Transmission Rate from the  Feld LU mi cnn etn a eu etel Nera 30  6 3 2 Configure the Abnormal Transmission Rate Using  WIM p        ns 31  6 4 SELECTING THE ABNORMAL SAMPLING RATE                   eene 32    AWS Level Field Units User Guide Rev 1210 IV    6 4 1 Configure the Abnormal Sampling Rate from the    Field Unico  Garet ode eben 33  6 4 2 Configure the Abnormal Sampling Rate  Using WIM eere tanon RBS QUO ERAN Duae RR UE 34  6 5 SETTING THE SMART RATE THRESHOLD                 sese 35  6 5 1 Configure the Smart Rate from the Field Unit          35  6 5 2 Configure the Smart Rate Using WIM                      36  6 6 SELECTING THE NORMAL UPPER AND LOWER VALUES                      87  6 6 1 Co
9.  95     grams per milliliter     KGPerLiter   96     kilograms per liter     GramsPerLiter   97     grams per liter     PoundsPerCuln   98     pounds per cubic inch     ShTonPerCuYard   99     short tons per cubic yard     DegTwad   100     degrees twaddell     DegBaumHeavy   102     degrees baume heavy     DegBaumLight   103     degrees baume light     DegAPI   104     degrees API      MicroGMPerLiter  146     micrograms per liter     MicroGMPerCuMeter  147    micrograms per cubic meter     PercentConsistency   148    percent consistency          Viscosity Units     Centistokes   54     centistokes     Centipoise   55     centipoise          Angular Velocity Units      DegPerSec   117     degrees per second     RPS   118     revolutions per second     RPM   119     revolutions per minute          Energy  Work  Units      NM   69     newton meter     DekaTherm   89     deka therm     FtLbForce   126     foot pound force     KWH   128     kilo watt hour      MCal   162     mega calorie      MJ   164     mega joule      BTU   165     british thermal unit          Force Units     Newton   68     newton          Power Units      KW   127     kilo watt      HP   129     horsepower      MCalPerHr   140     mega calorie per hour     MJPerHr   141     mega joule per hour     BTUPerHr   142     british thermal unit per hour          Frequency Units     Hertz   38     hertz          Analytical Units      Percent   57     percent      PH   59     pH      PerSteamQuality  150     percent
10.  D E F amp G  Class  I II  Division 2  Groups A B C D F amp G    59 AWS Wireless Level Products Field Units   User Guide Rev 0307                1 2  NPT  M ALE          Figure 10 2 WI GL I XX Dimensioned Mechanical Drawing    60 AWS Wireless Level Products Field Units   User Guide Rev 0307    10 3 WI GL E XX    Accuracy  e t0 1 96 of sensor URL over temperature    Stability  e Combined zero and span stability  Less than   0 1  of sensor URL per year at 70  F    RF Characteristics   e 902 MHz   928 MHz Frequency Hopping Spread Spectrum  FCC certified ISM  license free band   e Up to 3000    range from Base Radio with clear line of sight  500    to 1000    range with  obstructions   e The RF module in each field unit is individually tested and calibrated over the full  temperature range to ensure reliable wireless operation    Operating Temperature Range   e  40 F to  250  F   40  C to  121   C  process temperature  steady state   40 F to  185  F   40  C to  85  C  ambient temperature sensor    40 F to  185  F   40  C to  85  C  electronics    4F to  158  F   20  C to  70  C  display  full visibility     40 F to  185  F   40  C to  85  C  display  with reduced visibility     Physical Characteristics   e Type 316 Stainless Steel Base and Diaphragm  e Standard 77  MNPT  Other Options Available   e GE Lexan   cover  V O rating and UV stable    Operating Vibration and Shock Characteristics  e Certified per IEC ENOOO0668 2  6  vibration  and 2 27  shock     Random Vibration Charact
11.  Field Units maintain their synchronization with  their Base Radio by simply assigning each of the two Field Units to talk to a different  Base Radio     Either way  following this process will keep the Base Radio and Field Units properly  synchronized for long term communication     AWS Wireless Level Products Field Units   User Guide Rev 0307    3 2    3 2 1    Testing Communications    Remember that proper placement of the Field Unit will optimize your RF communication  range and capabilities  Perhaps the best test to perform before mechanically mounting  the unit is a quick hand held test  There are two types of tests you can conduct  the RSSI   Received Signal Strength Indicator  Diagnostic and the Link Test  The RSSI Diagnostic  measures the strength of the signal at the Field Unit  The Link Test measures the  throughput of data sent to and from the Field Unit  The Link Test may be conducted from  the Field Unit  Base Radio  or through WIM     The RSSI Diagnostic should be conducted first to determine if the Base Radio is  communicating with the Field Unit  Then the Link Test may be performed to test the  validity of the installation     To perform these tests  you should have a good idea of where the Base Radio will be  placed  for more information  see Section 3 of the Base Radio User Manual   Place the  Base Radio in the desired area and power on  Make sure that the Base Radio and Field  Unit are on the same RF Channel and Baud Rate  See Section 5   You may also have
12.  above 105  of the  range of the Analog Input sensor  If the measurement goes above 15096 of the full range  the unit  will go into Sensor Fault mode  In over range mode  the measurement is continually displayed   with the  OVERRNG  message to remind you that the specified range of the sensor and the  calibrated range of the device are being exceeded     Fatal error messages will replace the normal cycling message sequence and will flash  A fatal  message indicates the Field Unit is no longer operating normally and requires repair  These are   RF ERR   fatal error within RF communications   SEN ERR fatal error within the sensor electronics   SYS ERR fatal error within the microprocessor system   RF CAL  fatal error within the RF calibration system    66 AWS Wireless Level Products Field Units   User Guide Rev 0307    Appendix C Field Unit Menu Map    67    Both buttons must be    depressed for 1 second  to turn on the Field Unit         r    se T a 5 BR AMNEM    USER PROMPTED FOR    USER PROMPTED FOR    USER PROMPTED FOR  Factory passwords will be hard    I ke   coded  User password will be  LDENOBUS I es Cumt eiie 0000 from factory    NTER    O  RF CHAN  enter     RF CHT6   RF OFF is Defauit    N    EXT  ENTER NEXT  Lie NEXT Default of 19 2K    NEXT NEXT    Default of 000    NEXT AT ANY TIME    NEXT z       RF STATU NO   Note  If a menu is left  unchanged for 2 minutes  then the Field Unit will  retum to the Operations r            rs     Sequence   OPERATIONS SEQUENCE    US
13.  develops  produces and supports  partner specific  high value industrial measurement and process  solutions that enable our end users to increase efficiency   through put and environmental compliance     AWS customers include large national companies in the oil and  gas  chemicals  pharmaceutical  food and beverage  primary  materials processing  and energy industries  In addition to the  wireless product line  AWS also offers a traditional wired line of  temperature  pressure and differential pressure instrumentation     In the process control field  where quality is taken for granted  and new technology is announced daily  we have deliberately  concentrated our efforts on the development of instrumentation  that makes business sense  The result is a product range that is  rugged  secure  and reliable and works in even the most  hazardous environments  We give companies the tools to  reduce   costs  save time  enhance safety  improve  environmental performance and cut waste     The next industrial revolution is right now  Let AWS show you  how to realize gains in operating efficiency     Visit us at  www adaptive wireless com  Or call us at  1  978  875  6000    Specifications subject to change without notice  Printed in USA  Copyright 2010 Adaptive Wireless Solutions    Adaptive Wireless Solutions Inc   577 Main St Phone   978  875 6000   Hudson  Ma 01749 Fax   978  568 9085  www adaptive wireless com    
14.  drop down list  box   4  Click OK to save and download the configuration changes to the Field Unit     31 AWS Wireless Level Products Field Units User Guide Rev 0307    32    Selecting the Abnormal Sampling Rate    Note If the device is not configured to check for abnormal process conditions using the  Sampling Bands  section 6 6 2   the Abnormal Sampling rate is not used and this section  can be ignored     The Abnormal Sampling Rate is identical to the Normal Sampling Rate with one  exception  The Abnormal Sampling Rate only applies while the Field Unit is in an  abnormal condition  see 6 6 Selecting the Normal Upper and Lower Values   This allows  an increase or decrease of the frequency of information you receive depending on the  operating conditions of the process being monitored     In order to properly set the Abnormal Sampling Rate  determine how often updates are  needed from the Field Unit when the process being monitored is operating under normal  conditions  The Field Unit has a selectable range of 1 5  10  15  20  40 seconds  and 1  minute  Figure 6 10 is an example of how the device switches sampling methods from  Normal Sampling Rates to Abnormal Sampling Rates  Note how the first abnormal  sample is taken a few seconds after the Normal Upper Value set point is exceeded  The  next sample will then follow this sample by five seconds  or whatever the Abnormal  Sampling Rate is set to   These samples will continue at this interval until the process  value drops 
15.  execute the position zero adjustment     When P ZERO is selected  the sensor is zeroed  however  the displayed value is  calculated relative to the offset point  The unit will display an amount equal to the keypad   configured offset added to the WIM configured level offset  if applicable  If the intent is to  have the unit display  0   the offsets must be zero before applying P ZERO     For example  if 3 PSI of pressure is applied to a sensor  an offset of 5 PSI is entered into  the keypad  and P ZERO is applied  the unit will display 5 PSI  If the pressure is then  raised by 1 PSI to 4 PSI  the unit will display 6 PSI     To set position zero  power on the unit and apply zero pressure  Be sure that the unit is    installed in its final location or that it is oriented exactly as it will be in its final installation   Then follow the menu map shown in Figure 7 1     AWS Wireless Level Products Field Units   User Guide Rev 0307    CSET  WIS      UE ci Em LE M    iu  cse    NEXT   SAMPLING    Lum  XT      Kee zo   ENTER        Figure 7 1 Menu Map to Pressure Zero Setting            If  ENTER  is pressed while YES is being displayed the value is  saved  If  ENTER  is pressed while NO is being displayed the value  is NOT saved  When YES is selected  the new displayed value  will be equal to the offset        7 2 Setting a Measurement Offset    For various applications  you may wish to display an offset value rather than the actual  value  To enter an offset  navigate to the OFFS
16.  installer of this radio equipment must ensure that the antenna is located or  pointed such that it does not emit RF field in excess of Health Canada limits for the  general population  consult Safety Code 6  obtainable from Health Canada s website  www hc sc gc ca rpb     FCC Certification    e This product is a frequency hopping RF transceiver module for the 900MHz ISM  band  designed to meet FCC 15 247  and is used in industrial control and monitoring  applications     e The antenna is factory installed and MUST NOT be removed or modified by the  user     Adaptive Wireless Solutions reserves the right to update or change this user guide at  anytime  For the most recent version of the user guide  please check our website     www adaptive wireless com       Adaptive Wireless Solutions  2010   Printed in the USA       AWS Level Field Units User Guide Rev 1210 ll                                        Rev Date Notes Initials  1 58 3 7 2005 Release TH  0605 6 24 2005 Reformatted TH  0206 2 2006 TH  0406 4 9 2006 Release CW  1206 1 9 2007 Edited grammar and AK  readability  0307 03 20 2007 Added a    Debugging AK  the Field Unit    section  under    Maintaining the  Field Unit     Merge Submersible  and Level product  manuals  Battery changing  supplement  1210 12 07 2010 AWS MJ       Adaptive Wireless Solutions  577 Main Street   Hudson  MA 01749 USA    TEL   978  875 6000    Email  techsupport adaptive wireless com    Web  www adaptive wireless com       AWS Level Field Units 
17.  minutes     Sec   51     seconds     Hr   52     hours     Day   53     days          Mass Units      Gram   60     grams      KG   61     kilograms     MetricTon   62     metric tons     Pound   63     pounds     ShortTon   64     short tons     LongTon   65     long tons     Ounce   125     ounce          Mass Flow Units      GramPerSec   70     grams per second     GramPerMin   71     grams per minute     GramPerHr   72     grams per hour     KGPerSec   73     kilograms per second     KGPerMin   74     kilograms per minute     KGPerHr   75     kilograms per hour     KGPerDay   76     kilograms per day     MetTonPerMin   77     metric tons per minute     MetTonPerHr   78     metric tons per hour     MetTonPerDay   79     metric tons per day     PoundsPerSec   80     pounds per second     PoundsPerMin   81     pounds per minute     PoundsPerHr   82     pounds per hour     PoundsPerDay   83     pounds per day     ShTonPerMin   84     short tons per minute     ShTonPerHr   85     short tons per hour     ShTonPerDay   86     short tons per day     LongTonPerHr   87     long tons per hour     LongTonPerDay   88     long tons per day          Density Units       SGU   90     specific gravity units     GramPerCuCm   91     grams per cubic centimeter       AWS Wireless Level Products Field Units   User Guide Rev 0307    72    KGPerCuMeter   92     kilograms per cubic meter     PoundsPerGal   93     pounds per gallon     PoundsPerCuFt   94     pounds per cubic foot     GramsPerML  
18.  records recent errors that have occurred in a log  Using the following  debugging tools  you will be able to keep track of all errors and RF communication  problems that have occurred  There is also the option to clear the logs of these records  for debugging purposes    9 2 1 Error Log   9 2 2 Error Counts   9 2 3 RF Statistics   9 2 4 Clear Logs    To use the above tools  follow the Field Unit menu map shown in Figure 9 3 on the  following page     AWS Wireless Level Products Field Units   User Guide Rev 0307    9 2 1    52       OPERATIONS SEQUENCE                   L NEXT                  CONFIG     NExr       DIAGNSE  T  ENTER                         USER PROMPTED FOR  PASSWORD  UF                 RSSI          INK TST  BATVOLT                 amp      ERR LOG          Y  ERR CNT         RF STAT    LOG CLR        EXIT 1  Figure 9 3 Menu Map to Error Log  Error Counter  RF Statistics  and Log Clearing                         Error Log    The error log holds information about the six most recent errors that have occurred within  the firmware of the Field Unit  Some errors are not fatal  and can occur automatically as a  result of the field unit s design  However  other errors indicate a potentially fatal condition  and should be dealt with accordingly by using the table of errors in Figure 9 4     Navigate to the Error Log using the NEXT and ENTER buttons and Figure 9 3 as a guide   When the display shows ERR LOG  press Enter to enter the Error Log  An error number  and a
19.  seen in Figure 6 16     Input   Volts   10        8          p Cl  4    2   ashton Up a Ve Normal Condition    set to 7 Volts     0    g T T   T l  1 00 2 00 3 00    Time  min sec   Figure 6 16 Condition    Chatter    Elimination Due to Time Deadband    6 6 1 Configure the Upper and Lower Limits from the Field Unit    The Upper and Lower Limits cannot be configured on Level Field Units  The Upper and  Lower Limits can only be enabled using WIM     38 AWS Wireless Level Products Field Units   User Guide Rev 0307    6 6 2 Configure the Upper and Lower Limits Using WIM  1  Open the configuration dialog box  See Appendix A      2  Click the Sampling Bands tab to display the sampling bands information as  shown below     Gauge Level Pressure Properties    14 10     General ange Operation Mode   Sensor Offset    Samet Sampling Bands Alarms      Apper Limits  V Use Input 1 Limit    Value  50 0 Psi    Time Deadband   5 0 Seconds  LCD Message  BAND1      Lower Limits  J   Use Input 1 Limit    Value  5 0 Psi  Time Deadband   5 0 Seconds  LCD Message  BAND2    This tab allows the user to set the  Sampling Bands  of the field unit   The unit uses Normal sampling transmission rates when the primary  values are within the bands  When the value is outside of the bands  it  is considered Abnormal and Abnormal rates are used     Load from File      Save to File    Cancel       Figure 6 17 Normal Upper and Lower Value    3  Enable the Upper Limit by selecting the Use Input 1 Limit check box  
20.  sleep  mode to save power during the operations  sequence  This mode turns off most of the electronics on the unit  with the exception of  the LCD  in order to preserve battery life  The Field Unit will then    wake up    every Normal  Sampling Period and take the necessary process value readings  The Field Unit will  then transmit these readings to the Base Radio on an interval determined by the Normal  Transmission Rate     Notice that the fastest update rate of the Normal Transmission Rate is dependent on  the baud rate setting you selected earlier  see Section 5 2   The transmission rates  cannot update data faster than their communication speed allows  Thus  if you selected  the 19 2K Baud Rate setting  your fastest transmission rate will be five seconds  The  Field Unit automatically determines these settings and adjusts the menu options  accordingly  A complete table of these parameters is shown in Section 6 2     In order to properly set the Normal Transmission Rate  you must first determine how  often you need updates from the Field Unit  You have a selectable range of 1 5  10  15   20  40 seconds  and 1 minute  The factory default is 10 seconds     If all of the data does not get through  the data is resent the following second  This  prevents data from being lost  However  if the Transmission Rate is set to the maximum   one second  76 8K baud   then the data cannot be resent the following second because  the next set of data must be sent in order to meet the Tran
21.  sooner than the normal or abnormal rate that you specify  This feature is used to  construct a more accurate graph of the measured process value vs  time than is possible  with the fixed transmission rates  while using less battery power     If the process value changes by more than the entered Smart Rate amount within the  normal or abnormal sampling rate  whichever is active   then the process variable is  transmitted immediately  The normal abnormal transmit clock is then reset upon this  transmission  If the Smart Rate amount is not exceeded in the next normal abnormal  sample  then the next transmission will be the normal abnormal transmit rate period     The amount entered is in the same units as you selected to be displayed on the Field  Unit  If the measured process value does not change by more than the entered Smart  Rate amount within the time between the sampling rates  whichever is active   then the  process value is transmitted on the next transmit rate     If changes in the process value  which exceed the Smart Rate Amount  continue to occur   the process value is transmitted repeatedly     Configure the Smart Rate from the Field Unit    The Smart Rate cannot be configured on Level Field Units  The Smart Rate can only be  enabled using WIM     AWS Wireless Level Products Field Units   User Guide Rev 0307    6 5 2 Configure the Smart Rate Using WIM  1  Open the configuration dialog box  See Appendix A      2  Click on the Sampling Rates tab to display the sampl
22.  square inch absolute     KGPerSqMeter   176     kilograms per square meter     FtH2OAt4C   177     feet of water at 4 degC     FtH2OAt60F   178     feet of water at 60 degF     MetHgAtOC   179     meters of mercury at 0 degC     MegaPascals   237     megapascals      InH2OAt4C   238     inches of water at 4 degC     MMH20OAt4C   239     millimeters of water at 4 degC          Volumetric Flow Units      CuFtPerMin   15     cubic feet per minute      GalPerMin   16     gallons per minute      LiterPerMin   17     liters per minute      ImpGalPerMin   18     imperial gallons per minute      CuMeterPerHr   19     cubic meter per hour      GalPerSec   22     gallons per second      MillionGalPerDay   23     million gallons per day      LiterPerSec   24     liters per second      MillionLiterPerDay   25    million liters per day      CuFeetPerSec   26     cubic feet per second      CuFeetPerDay   27     cubic feet per day      CuMeterPerSec   28     cubic meters per second      CuMeterPerDay   29     cubic meters per day      ImpGalPerHr   30     imperial gallons per hour      ImpGalPerDay   31     imperial gallons per day      NormCuMeterPerHr   121    normal cubic meter per hour   MKS System     NormLiterPerHr   122     normal liter per hour   MKS System     StdCuFtPerMin   123     standard cubic feet per minute   US System     CuFeetPerHour   130     cubic feet per hour      CuMeterPerMin   131     cubic meters per minute      BarrelPerSec   132     barrels per second   1 Barre
23.  steam quality     PercentPlato   160     percent plato      PerLowExpLevel   161     percent lower explosion level          Capacitance Units     PF   153     picofarads          EMF Units     MilliVolts   36     millivolts     Volts   58     volts          Current Units     MA   39     milliamperes          Resistance Units     Ohms   37     ohms     KOhms   163     kilo ohms          Angle Units     Deg   143     degrees       AWS Wireless Level Products Field Units   User Guide Rev 0307    73    Rad   144     radians          Conductance Units      MicroSiemens   56     micro siemens     MilliSiemensPerCM  66     milli siemens per centimeter     MicroSiemensPerCM  67     micro siemens per centimeter          Volume per Volume Units      VolumePercent   149     volume percent     MilliLitersPerLiterz 154    milli liters per liter     MicroLitersPerLiter  155    micro liters per liter          Volume per Mass Units     DegBalling 2 107     degrees balling     CuFtPerLb   152     cubic feet per pound          Concentration Units      DegBrix   101     degrees brix      PerSolidsPerWt   105     percent solids per weight     PerSolidsPerVol  106     percent solids per volume     PfPerVol   108     proof per volume      PfPerMass   109     proof per mass      PPM   139     parts per million      PPB   169     parts per billion          Special Units     SpecialUnits   253    AWS Wireless Level Products Field Units    User Guide Rev 0307    ABOUTUS    Adaptive Wireless Solutions
24.  to  increment the number of Field Units with which the Base Radio is communicating  See  the Base Radio User Manual Section 4 3      Once both the Base Radio and Field Unit are set up to be on the same network  make  sure communication is established by looking at the Field Unit LCD for the  RF OK   message in the Read Only Sequence  see Section 4 2 1      After communications have been established  go to Section 3 2 1 for the RSSI Diagnostic  or Section 3 2 2 for the Link Test     Field Unit RSSI Diagnostic    The Field Unit should be placed in RSSI Diagnostic mode to determine the signal  strength at the location of the equipment to be monitored     The RSSI Diagnostic  located in the Field Unit s diagnostic menu  displays the RF signal  strength in one of seven ranges  The signal strength is displayed on the LCD using a  combination of     gt     and    _    characters  Full signal strength is displayed as     gt   gt   gt   gt   gt   gt   gt       while minimum signal strength is displayed as     gt  _ _ _ _ _ _    If the field unit is not    communicating with the Base Radio  i e  NO RF   all underscore characters will be  displayed     _ _____          The RSSI is measured every time the Field Unit receives a message from the Base  Radio  The signal strength of the received message from the Base Radio is calculated  during this time  The actual signal strength in dBm for each range is shown below         gt   gt   gt   gt   gt   gt   gt     Less than Between Between Be
25.  will not reset the TRIM    D or OFFSET values     i 1      OPERATIONS SEQUENCE I  l    D es                I     1      USER PROMPTED FOR      PASSWORD  UF  I           a       E CN  NEXT   SAMPLING     NEXT    NEXT    Figure 4 5 Menu Map to Reset All Field Unit Settings    19 AWS Wireless Level Products Field Units   User Guide Rev 0307    5 1    20    Configuring the RF Communications    In order for the Field Unit and the Base Radio to communicate  they must be on the same  RF Channel and must be transmitting at the same Baud Rate  While all Field Units and  Base Radios are set to default configurations at the factory  if any configuration  differences are present  the Base Radio will not be able to communicate with the Field  Units  The subsections are as follows     5 1 RF Channel Selection  5 2 RF Baud Rate Selection  5 3 RF Identification  RF ID  Selection    Warning  If the Field Units have been running for an extended period of  time with no signal from the Base Radio  the Base Radio is off or not  present   the Field Units will only search for the Base Radio every one  hour or so  Turning the Field Units off and back on will cause them to  begin searching immediately     RF Channel Selection    The RF Channel defines a set of frequencies on which communication takes place  between the Base Radio and the Field Unit  Each RF Channel has a different set of  frequencies  thus allowing you to have multiple different wireless networks co existing  throughout the same fac
26. 1  of sensor URL per year at 60 F    RF Characteristics   e 902 MHz   928 MHz Frequency Hopping Spread Spectrum  FCC certified ISM  license free band   e Up to 3000    range from Base Radio with clear line of sight  500    to 1000    range with  obstructions   e The RF module in each field unit is individually tested and calibrated over the full  temperature range to ensure reliable wireless operation    Operating Temperature Range   e  4 to  140  F   20  C to  60  C  process temperature  steady state  e  4   to  140   20 C to  60  C  electronics   e  A F to  140   20  C to  60  C  display  full visibility     Physical Characteristics  e Type titanium base and diaphragm  e GE Lexan   cover  V 0 rating and UV stable    Operating Vibration and Shock Characteristics  e Certified per IEC ENOOO0668 2  6  vibration  and 2 27  shock     Random Vibration Characteristics  e Certified to withstand 6 g s  15 minutes per Axis from 9     500 Hz    Electromagnetic Compatibility  CE Compliance    e Operates within specification in fields from 80 to 1 000 MHz with Field strengths to 30  V m  Meets EN 50082 1 general immunity standard and EN 55011 compatibility  emissions standard    Industrial Certification     For ordinary locations only    57 AWS Wireless Level Products Field Units User Guide Rev 0307       SO Ft Cable    Figure 10 1 WI SL XX Dimensioned Mechanical Drawing    58 AWS Wireless Level Products Field Units   User Guide Rev 0307    10 2 WI GL I XX    Accuracy  e t0 1 96 of senso
27. 65 AWS Wireless Level Products Field Units   User Guide Rev 0307    Appendix B Field Unit Displayed Message  Definitions    This section covers the various messages  displayed on the Field Unit LCD  that occur  during operation of the device     Operations Sequence    RF Link Status   RF OK      Field Unit and Base Radio are communicating properly   RF SYNC Field Unit and Base Radio are attempting to synchronize communications  RF OFF Field Unit s RF Channel is set to RF OFF   NO RF Field Unit and Base Radio are not communicating    Gauge Level Input Level     XX XX Currently measured differential input level    Error Messages  If an error is detected with the operation of the Field Unit  a message will be displayed on the  Field Unit LCD  a corresponding message may also appear on the Base Radio LCD      There are several types of error messages  both warnings and fatal errors  Warning messages  are displayed as part of the normal cycling message sequence  These are    LOW BAT battery should be replaced as soon as possible   NO RF can not detect Base Radio   S FAULT there is an open sensor or excitation wire detected  Also displayed if a sensor value  goes above below logical limits  The unit will display 9999 99 for measurement  sensor fault  mode   but will continue sampling and recover if the problem desists    OVERRNG   the device is measuring a value above below sensor dependent bound values  For  example  the Analog Input device will report over range if measurement is
28. EE  Rev 1210  A d    WIRELESS SOLUTIONS    Level Products  User Manual       User Guide Rev 1210  Adaptive Wireless Solutions Inc  577 Main St Phone   978  875 6000  Hudson  Ma 01749 www adaptive wireless com    AWS Level Field Units   User Guide Rev 1210    Level Field Units  Models  WI SL xx WI GL I xx WI GL E xx  WI GL E Y6 XX    Versions 1 70 or later    Important Information for the User    e Changes or modifications not expressly approved by Adaptive Wireless Solutions  may void the user s authority to operate the equipment     e This device complies with Part 15 of the FCC Rules  Operation is subject to the  following two conditions     1 This device may not cause harmful interference     2 This device must accept any interference received  including  interference that may cause undesired operation     e This device is for mobile and fixed use only  not portable or body worn   A  separation distance of 20cm must be maintained at all times between the antenna  and the body of the user and bodies of nearby persons     e This device has been designed to operate with an antenna having a maximum gain  of 9 dBd  Antenna having a higher gain is strictly prohibited per regulations of  Industry Canada  The required antenna impedance is 50 ohms     e To reduce potential radio interference to other users  the antenna type and its gain  should be so chosen that the EIRP  Equivalent Isotropically Radiated Power  is not  more than that required for successful communication     e The
29. EQUENCE Next CONFIG  gt  ENTE SELECTED  NEW  qu TEN 4 ENTER TRIM IS SAVED   RE k MES   IF  NO  IS  i USER i  NEW TRIM   TRIM Enter    SELECTED  TRIM    PROMPTED     POINT IS    FOR   NEXT DISCARDED   iPASSWORD   4  225 IF  YES  IS  RESET   enter ENTER    PRESSED  TRIM IS  SET RF ENTER      RESET   da d  IF  NO  IS  E PRESSED  NEW  mE Lex    pe mis    CANCELLED   NEXT                TRIM fenter INPUT 1 F       NEXT    INPUT 2    NEXT         Figure 7 3 Menu Map to Trim Setting    Entering a 22  Point Curve   If you are running WIM  a 22 point sensor offset curve may be entered for the Field Unit   To do so  open the configuration dialog box  See Appendix A   Once in the configuration  dialog box  click the Sensor Offset tab to bring up the offset information as shown for  Level in Figure 7 4 and for Pressure in Figure 7 5     Note For Gauge Level  a 22 point curve table must be filled out for correct operation     AWS Wireless Level Products Field Units   User Guide Rev 0307    Gauge Level ure Properties    14 10        Figure 7 4 Setting a 22 Point Curve for Level Using WIM    Gauge Level Pressure Properties    14 10       Sam       Figure 7 5 Setting a 22 Point Curve for Pressure Using WIM    43 AWS Wireless Level Products Field Units   User Guide Rev 0307    8 1    44    Selecting and Configuring Operation  Modes    In this section  the two operation modes  Pressure and Gauge Level  are discussed in  order to aid you in selecting the right mode for your application and prop
30. ER PRO  ea pee el 3       I  b  _ PASSWORD  UF  R       Field Unit Menu Map  page 1     AWS Wireless Level Products Field Units   User Guide Rev 0307    NEXT  L User will be  locked out  of the following menus if WIM is available      from last page     r    LSET PWD geENTER  gt C XXXX   Default of 0000 Note  The Baud Rate determines the maximum    speed of the Transmission Rates  NEXT    aame CAIXA ENTER   gt  XXXXXXO EVTER  a b c    NEXT    NEXT  NEXT  NEXT  NEXT  C EXT     Field Unit Menu Map  page 2     68 AWS Wireless Level Products Field Units   User Guide Rev 0307    T GL Field Unit User Interface Spec     from last page     eer PST        NEXT  NEXT  NEXT  NEXT  NEXT  NEXT  NEXT  Allows specific gravities greater than  ENTER   gt  SP GRAV J ENTER    XX XXXXX       and less than 100  with 5 decimal  NEXT places of precision   NEXT    lt OTHER   OTHER menu will be the current user  units  if not in the list  This will be  NEXT skipped if it isn t necessary   If  ENTER  is pressed while YES is being displayed the value is  saved  If  ENTER  is pressed while NO is being displayed the value is  NOT saved  When YES is selected  the new displayed value will  NEXT be equal to the offset   Mera INPUT T   The user must apply  the POINT 1  amp  POINT  NEXT 2 to the sensor  then    NEXT rb select YES  To save  the point     NTER NeR  NEW TRIT eN ese APPLY enter    NEXT NEXT ARES R au va aio E d           LCHIERT J gt  0000700  enren gt   APPLY enr  NEXT r  NEXT  CERTZ    pA    Y 
31. ET command  as shown in Figure 7 2   Then enter the offset to be added or subtracted from the actual measured value        Ti 1  i OPERATIONS SEQUENCE HNEXT      USER PROMPTED FOR      PASSWORD       NEXT  SET Pwo   NEXT  ISETTAS    NEXT   SRH  LRG    NEXT  NEXT   OFFSET Jens  CINPUTT  NEXT     ext    Figure 7 2 Menu Map to Offset Setting    41 AWS Wireless Level Products Field Units User Guide Rev 0307    7 3    7 4    42    Trimming the Measurement    The Field Unit interface allows you to set a two point correction curve for the sensor  This  process is often called    trimming    because the displayed value is trimmed up or down to  reflect the actual value being applied     To set a trim point  take the Field Unit offline  navigate to the TRIM menu as shown in  Figure 7 3  select the input to be trimmed  and then select the point you wish to enter   After selecting the point  you will have the option to trim the device or reset the trim  If  NEW TRIM is selected  you will be prompted to enter the lower point first  Type the value  and press ENTER  The Field Unit will prompt you to apply the indicated process value to  the Field Unit  Apply the process value and press ENTER  Repeat the process for the  higher point  After both points have been trimmed  you can choose to save or discard the  new trim     LO PNT 0000 00 FENTER gt   APPLY NTER     I       ENTER      HIPNT      gt   0000 00  ewem  APPLY Jenter                                     kL   IF  YES  IS  OPERATIONS S
32. I GL I XX is a Gauge Level Field Unit with an integrated sensor     e   WI GL E XX is a Gauge Level Field Unit with an extended sensor  This Field Unit is  for locations where the sensor is too close to the ground  a dike  or additional  obstructions  It allows you to position the Field Unit transmitter in a location for  optimal communication with the Base Radio     e   WI GL E Y6 XX is a Gauge Level Field Unit with an extended sensor and a high  gain directional Yagi antenna  This Field Unit has all of the benefits of the WI GL E   XX plus the high gain antenna to increase the transmission distance between the  Field Unit and Base Radio     e  WI SL XX is a Submersible Level Field Unit with a cable mounted sensor     Mechanical Installation    In this section  mechanical installation instructions are discussed for the various setup  capabilities of the Level Field Units     Each AWS Level Field Unit is a rugged device  but it provides much better performance if  installed with careful consideration  as noted in this manual  It may be utilized in any  Level measurement application so long as care is exercised to prevent exposing the  sensing elements to excess stress or temperature  Installation practices greatly impact  these service parameters and the life that you can expect from your AWS Level Field  Units     Carefully consider the environment in which you will install your instrument  Avoid  installations that expose the device to excess temperature  high vibration  co
33. RF Baud Rate Selection    The RF Baud Rate refers to the speed at which the Base Radio and Field Units  communicate  The RF baud rate for the Base Radio and the Field Unit must be the same  in order for them to communicate successfully  There are three selectable settings with  the fastest update times and ranges listed below     e 48K     Rate of 4 8K baud  Update every 20 seconds       Range of 3000ft  Line of Sight     e 19 2K     Rate of 19 2K baud  Update every 5 seconds       Range of 2000ft to 2500ft  Line of Sight     e  76 8K     Rate of 76 8K baud  Update every 1 second       Range of 500ft to 750ft  Line of Sight     A faster RF Baud Rate allows you to transmit more information in a given period of time   but it will also limit the Field Unit s range  If you need more distance out of your Field  Units or are encountering difficulties by frequently losing communications  then select a  slower baud rate     Follow the Base Radio menu map shown in Figure 5 2 to configure the RF Baud Rate   The factory default is the 19 2K Baud Rate       USER PROMPTED FOR    A meg m oe FEE 1  PASSWORD       ENTER    NEXT    ENTER NEXT  NEXT Default of 19 2K    Figure 5 2 Menu Map to Baud Rate Setting    Note If you change the baud rate of a Field Unit  you must also change the baud rate of  the Base Radio and all other Field Units that are communicating with that Base Radio     21 AWS Wireless Level Products Field Units   User Guide Rev 0307    5 3    22    RF Identification  RF ID  S
34. SPLAYED MESSAGE DEFINITIONS                66  APPENDIX C FIELD UNIT MENU MAP                             eene 67  APPENDIX D MODBUS REGISTER DEFINITIONS                                         70    AWS Level Field Units User Guide Rev 1210    Table of Figures    Figure 3 1 Examples of Incorrect Field Unit Positioning                                   sssss 6  Figure 3 2 Menu Map to RSSI Mode                     sse 9  Figure 3 3 Field Unit Link Test                            esee 10  Figure 3 4 Base Radio Link Test                      sssseseeeee 11  Figure 3 5 WIM Field Unit View                    esseeeem mm 12  Figure 3 6 Wireless Data Loss Test                    ssseseee 12  Figure 4 1 Field Unit Power Up and Operations LCD Sequences                       15  Figure 4 2 The Read Only Sequence                      sse 15  Figure 4 3 Overall Configuration Menu Map                    eseeeneee 16  Figure 4 4 Setting a User Password                cccccciiciiiiiiiiiiiiiiiiiiiciiiii iini niii 18  Figure 4 5 Menu Map to Reset All Field Unit Settings                                 sssssse 19  Figure 5 1 Menu Map to RF Channel Setting    20  Figure 5 2 Menu Map to Baud Rate Setting                          sss 21  Figure 5 3 Menu Map to RF ID Setting                      ssssssseeeeem 22  Figure 6 1 Menu Map to Normal Transmission Rate Setting                                24  Figure 6 2 Sampling Rates Tab                    ssssssssssseeeeeen nene 25  Figure 6 3 Incorrec
35. al MPASCAL  Millibar MBAR  Millimeters of Mercury MM HG  Millimeters of Water MM H20  Mm water   4  C MMH204C  Pascals PASCALS  Percent     PER FS  Pounds per in2  PSI  PSI  Special SPECIAL  Torr TORR                Once you select the engineering units  you have the option of enabling a 22 point sensor  offset curve  it is disabled upon delivery from the factory   For additional information on a  22 point sensor curve  see Section 7 4     Gauge Level    This mode will calculate the level and display it in the units of your choice  In this mode   you have the option of entering the density of the material or the full tank pressure  Also   you must enter tank height and tank volume  Finally  you must select level units  which  can be in units of height  volume  or mass  The entered information is used to make level  calculations in the units you selected  For non uniform tanks  you must also fill out the 22   point curve table indicating the relationship between height and volume     To set the Field Unit to this operation mode  you must go to the configuration dialog box  in WIM  For further instructions on opening the configuration dialog box  see Appendix A     AWS Wireless Level Products Field Units   User Guide Rev 0307    Once you have opened the configuration dialog box  select the Operation Mode tab at  the top of the dialog box and then select Fluid Level in the Mode drop down list box  You  will then see a dialog box like the one shown in Figure 8 2     Gauge Level P
36. and  removing the contents  save the packing material and the carton     1 4 SOFTWARE COMPATIBILITY    Software for AWS is revised periodically  Internal device software may contain portions  that are not compatible with previous versions of WIM  Wireless Instrumentation Manager  software      To ensure software compatibility  WIM version 1 70 138 or later must be used  If you  believe you are experiencing software compatibility issues please call Adaptive Wireless  Solutions Technical Support at  978  875 6000 or email techsupport adaptive   wireless com      AWS Wireless Level Products Field Units   User Guide Rev 0307    Quick Start    This section summarizes what must be done in order to get the device installed   configured  and in operation quickly  However  it does not provide detailed or step by   step instructions explaining how to perform the tasks outlined     1     2     9     10     Install the Field Unit in the desired location of operation     Turn on the Field Unit by simultaneously pressing and holding the ENTER and  NEXT buttons until the unit powers up     Hit the NEXT button until the CONFIG message appears then hit ENTER   Enter the default password 0000 to enter the CONFIG menu    Enter the SET RF menu    Set the RF CHAN setting equal to the Base Radio s RF Channel    Set the BAUD RT setting equal to the Base Radio s RF Baud Rate    Set the RF ID number to be a unique value between 1 and 100    Zero the sensor     Trim and Offset the measurement  if appr
37. ar point  you may want to try a slower baud rate setting for an increased range     Note While using a slower baud rate increases communication distance  it also increases  the minimum transmit time  See Section 5 2 for a list of the fastest transmit rates for each  baud rate  This may not be suitable for your application     One final solution is to reposition the AWS Base Radio  However  this may affect  communications with previously installed Field Units  and if so  may require the use of a  second Base Radio for your application  To select a better spot for the Base Radio  see  Section 3 1 1 of the Base Radio User Manual     Link Test    The Link Test measures the wireless link performance of a Field Unit running in its  normal operating mode  Messages are sent from the Field Unit to the Base Radio at a  predefined interval called the Transmit Rate  see Section 6 1   Each message contains  data for the previous time period  since the last transmit   The Link Test looks at the  wireless performance going in both directions  from the Field Unit to the Base Radio and  vice versa  and comes up with a rating  The result that appears on the display shows the  determined link strength     In order to perform this test  the Field Unit must be communicating on the same channel  and baud rate as the Base Radio  See Section 5 to configure communications     The Link Test may be conducted from the Field Unit  Base Radio  or through WIM   Running the Link Test from WIM is ideal for t
38. ation or  step by step instructions explaining how to perform the tasks outlined     3 Installation   This section covers general considerations regarding correctly commissioning the Field  Unit as well as unique applications such as flow service commissioning  Also covered in  this section are mechanical installation considerations  such as Field Unit placement     4 General Configuration   In this section  general configuration options such as password protection and selecting a  user password are discussed  Also covered is the setting of a Field Unit tag name   resetting of all Field Unit settings  and a discussion of the various messages that are  displayed on the Field Unit LCD     5 Configuring the RF Communications   This section covers the setup of the Field Unit RF Communications that allow the Field  Unit to achieve communication with the Base Radio  Parameters discussed are the Field  Unit RF ID  the RF channel setting  and Baud Rate     6 Configuring the Sampling and Transmission Rates   This section aids you in selecting the amount of time between each sample of the  process  and the time between each transmission of this sample to the Base Radio  Also  discussed  is the use of setting an abnormal threshold in which sampling and  transmission times may change during a period when the process variable is within the  abnormal region     7 Configuring the Process Variable  This section helps you to zero the sensor and discusses setting a measurement offset  and trim
39. below the Normal Upper Value set point     Input   Volts   10            a    Abnormal Condition    Abnormal  Sample    Normal Upper  Value          Normal Sampling Rate of 15 Sec  Abnormal Sampling Rate of 5 Sec  Normal Upper Value of 2 5    Figure 6 10 Example of Abnormal Sampling Rate Setting    Once the process value drops below this set point  the sampling rate will return to the  Normal Sampling Rate  Also  the Abnormal Sampling must be equal to or faster than  the Abnormal Transmission Rate     You should also note that the transmission time depends on the sample rate  and when  the process variable is sampled  If the Normal Sampling Rate is 30 seconds  then the  process variable may be above the Normal Upper Value for up to 29 seconds before  abnormal condition is detected  This means that the transmission could be as late as 29  seconds after the process variable exceeded the Normal Upper Value     AWS Wireless Level Products Field Units   User Guide Rev 0307    Once you have decided the proper time for the Abnormal Sampling Rate  select this  setting from the Field Unit or through WIM     6 4 4 Configure the Abnormal Sampling Rate from the Field Unit    To configure the abnormal sampling rate from the field unit  follow the menu map below     Note Once WIM has been used to configure the Field Unit  this menu option will be  disabled on the Field Unit LCD Menu     NEXT  ENTER     NEXT    NEXT       NEXT  Cx sg en 1 5 SEC  10 SEC  15 SEC  20 SEC  30 SEC  60 SEC    Fig
40. counters that keep track of the number of  times each particular error has occurred  Each counter is associated with a different error  type  all of which are outlined in Figure 9 5   Navigate to the Error Counts using the NEXT and ENTER buttons and Figure 9 3 as a  guide  When the display shows ERR CNT  press Enter to enter the Error Counts menu   C1 is displayed on the Field Unit followed by a number that shows the value of the  counter  For example   C1 5  indicates that the error specified by C1 has occurred five  times since the last time the log was cleared  for the Clear Logs tool  see section 9 2 4    53 AWS Wireless Level Products Field Units User Guide Rev 0307       9 2 3    54    Pressing the NEXT button while the Field Unit is displaying an error count will show the  NEXT logged entry  Once the unit has cycled through all error counts  C1 C6  the unit will  return to C1 the next time you press the NEXT button     Cold Resets   Indicates the  number of times the device has  been restarted cold  This means  that a source of power  such as  a battery  was removed     Warm Resets   Indicates the  number of times the firmware of  the device has reset itself     Watchdog Resets   Indicates the  number of times the embedded  C CPU has crashed  The  watchdog module physically  resets the CPU if it crashes     Oscillator Faults   Indicates the  number of times the onboard  oscillator has failed to run    properly     4  2  3  4  Stack Overflows   Indicates the  number of 
41. e is not followed  the communication range of the Field Units will be significantly  reduced and the Field Units may eventually lose communication with the Base Radio  entirely  This procedure is easy to implement  but please read carefully for a full  understanding     The AWS Base Radio synchronizes with the Field Units in Synch Groups of seven   organized by their RFID numbers  If you want to place two Field Units closer than six  feet  make sure that you have set them in different groups  Note that this only applies to  Field Units that are communicating with the same Base Radio  The groups are defined in  the following table                                                        Group   RFID Range  1 1 7  2 8 14  3 15 21  4 22 28  5 29 35  6 36 42  7 43 49  8 50 56  9 57 63   10 64 70  11 71 77  12 78 84  13 85 91   14 92 98  15 99 100             For example  if two Field Units are placed one foot apart and the first Field Unit has an  RFID number of 027  it is in the 4  group  22 28   The second Field Unit must have an  RFID number that is in another group  less than 22 or greater than 28   Setting the RFIDs  of two closely spaced Field Units so that the RFID numbers are greater than seven apart  ensures that the Field Units are in different Base Radio sync groups  This allows the  closely spaced Field Units to properly receive their synchronization signal from the Base  Radio and maintain their proper communication and range     You can also ensure that closely spaced
42. ed trying to send the message    Figure 9 6 RF Statistics code descriptions    For debugging purposes  you may wish to reset the values of all error or condition  counters to determine how many errors or conditions will occur within a given time period   In order to do this  the Clear Logs feature can be utilized  This tool will clear all logs   including the Error Log  the Error Counts  and the RF Statistics counters     Navigate to the Clear Logs menu using the NEXT and ENTER buttons and Figure 9 3 as  a guide  When the display shows LOG CLR  press Enter to enter the Clear Logs menu     55 AWS Wireless Level Products Field Units   User Guide Rev 0307    56    The Field Unit will display    NO     on the screen and wait for your input  Pressing the  ENTER button while    NO     is displayed will cause the Field Unit to return to the  diagnostic menu and no changes will be made to the logs  Pressing the NEXT button  while    NO     is displayed will cause the Field Unit to display  YES    Pressing the ENTER  button while  YES   is displayed will cause the Error Log  the Error Counts  and the RF  Statistics counters to be reset to zero  To ensure that the operation is complete  make  sure    OK    is displayed on the screen after clearing the logs     AWS Wireless Level Products Field Units   User Guide Rev 0307    10 Technical Specifications    10 1 WI SL XX    Accuracy  e  t0 1 96 of sensor URL over temperature    Stability  e Combined zero and span stability  Less than   0 
43. educed by the amount of RF Noise  present  obstructions  and the material properties of the obstructions     e Only place the Field Unit in ambient operating temperatures of  40  F to 185  F    40 C to 85  C      Figure 3 1  shown below  gives examples of incorrect setups according to the previously  mentioned parameters            Outside  Base Radio         x                             Um   f range  9 Os  Field Units too  hp S009 close together  l 957 See Section3 1 1 1  A9  Qu    TAE  r             T    Base Radio       Bottom  aimed at  Base Radio         Behind too  great of an  obstacle         Obstruction       Figure 3 1 Examples of Incorrect Field Unit Positioning    Because there are so many setup possibilities  we cannot cover them all  A correct setup  would make sure that the above warnings are heeded  and that the Field Unit and Base  Radio are capable of communicating  The Testing Communications section will help you  to determine if you have selected the correct installation points and orientations for your  application     AWS Wireless Level Products Field Units   User Guide Rev 0307    3 1 1 1    Warning  During installation  do not apply force to the instrument housing  or antenna  Use a proper wrench for all installations  Failure to use correct  installation procedures can cause damage to the Field Unit     Technique for Close Positioning of Field Units    Field Units may be placed closely together by carefully following this procedure  If this  procedur
44. eld Unit on  press and hold both the NEXT and ENTER buttons  simultaneously for a few seconds  Upon power up  the Field Unit will display the Power     AWS Wireless Level Products Field Units   User Guide Rev 0307    Up Sequence  and then go into the Operations Sequence  These sequences are shown  in Figure 4 1     SL  amp  GL Field Unit User Interface Spec    POWER L ENCE   WES TAG NO    Powe ra pia    venxx H ranae    Both buttons must be  depressed for 1 second  to turn on the Field Unit                          r    OPERATIONS SEQUENCE   E    am au     an an an a a a               Figure 4 1 Field Unit Power Up and Operations LCD Sequences    Note During configuration and testing  keep Field Units at least six feet from the Base  Radio and other Field Units     4 2 4 The Read Only Sequence    Once the Field Unit is in the Operations Sequence  you may access the Read Only  Sequence without a password by simply pressing the ENTER button at any time  The  Read Only Sequence  as shown in Figure 4 2  displays extra information about the  current settings of the Field Unit that is not seen during the Operations Sequence  but  does not allow any changes to be made to these settings           ERROR  MSG    RF ERR  SEN ERR  LOW BAT   RF OFF  NO RF                Figure 4 2 The Read Only Sequence    15 AWS Wireless Level Products Field Units User Guide Rev 0307    4 3 Overall Configuration Menu Map    A complete Field Unit Menu Map is shown in Appendix C  Below is an overall view o
45. election    Each Field Unit is identified by the Base Radio and WIM according to the RF ID given to  that particular unit  Two Field Units on the same RF Channel CANNOT have the same  RF ID  if you do not know the RF Channel  see section 5 1   When the Field Unit is in the  Operations Sequence  pressing the ENTER button displays the Read Only Sequence on  the LCD  The RF of that unit will be displayed in the format  ID 3     All Field Units in your system are set to a default RF ID number upon shipment  For  example  if you have ordered a Base Radio and three Field Units  the Field Units will be  configured to ID s 0  0  and 0  You must set these units to three different RF IDs between  1 and 100  The Field Units in this example could be set to RF IDs 1  2  and 3     First determine the RF ID s you d like to give each unit  Then follow the menu map shown  in Figure 5 3 to configure the RF ID  The factory default is RF ID 0  which disables the RF  communication of the unit        42 1    NEXT    NEXT  C R  I feter Mer Default of 000    Figure 5 3 Menu Map to RF ID Setting    Once you have selected the RF ID you wish to use for this particular Field Unit  exit the  menus and return to the Operations Sequence     The Field Unit should now be successfully configured to the Base Radio  To check this   press ENTER while the Field Unit is in the Operations Sequence for the Read Only  Sequence to be displayed  You may see an RF SYNC message displayed on the Field  Unit LCD  This mean
46. eristics  e Certified to withstand 6 g s  15 minutes per Axis from 9     500 Hz    Electromagnetic Compatibility  CE Compliance    e Operates within specification in fields from 80 to 1 000 MHz with Field strengths to 30  V m  Meets EN 50082 1 general immunity standard and EN 55011 compatibility  emissions standard    Industrial Certification   e Rated for industrial use  40  F to 185  F   40  C to 85  C    e FM NEMA 4 weather proof housing   e FM rated intrinsically safe for Class I I IIIl  Division 1  Groups A B C D E F amp G  Class  MI  Division 2  Groups A B C D F amp G    61 AWS Wireless Level Products Field Units   User Guide Rev 0307    62                W2 HPT  Process Ating       Figure 10 3 WI GL E XX Dimensioned Mechanical Drawing    AWS Wireless Level Products Field Units   User Guide Rev 0307    10 4 WI GL E Y6 XX    Accuracy  e  t0 1 96 of sensor URL over temperature    Stability  e Combined zero and span stability  Less than   0 1  of sensor URL per year at 70  F    RF Characteristics   e 902 MHz   928 MHz Frequency Hopping Spread Spectrum  FCC certified ISM  license free band   e Up to 3000    range from Base Radio with clear line of sight   e The RF module in each field unit is individually tested and calibrated over the full  temperature range to ensure reliable wireless operation    Operating Temperature Range   e  40 F to  250  F   40  C to  121   C  process temperature  steady state   40 F to  185  F   40  C to  85  C  ambient temperature sensor    40 F t
47. erly configuring  the Field Unit  The subsections are as follows     8 1 Pressure  8 2 Gauge Level    Pressure    This mode simply calculates and displays the Pressure value from the Gauge Level  sensor  To set the Field Unit to this operation mode  you must go to the configuration  dialog box in WIM  For further instructions on opening the configuration dialog box  see  Appendix A     Once you have opened the configuration dialog box  select the Operation Mode tab at  the top of the dialog box  You should then see a dialog box like the one shown below     Gauge Level Pressure Properties    14 10     Sampling Rates   Sampling Bands   Alarms  General   Range Operation Mode   Sensor Offset          Mode    Pressure in       Pressure Units  Psi             Load from File      Save to File       Figure 8 1 Pressure Setting Using WIM    To select the Pressure mode  select Pressure in the Mode drop down list box  This will  display the Pressure Units drop down list box  which will allow the selection of Pressure  engineering units  You should select the units that are appropriate for your application  All  possible units are listed on the next page     AWS Wireless Level Products Field Units   User Guide Rev 0307    8 2    45                                                          Atmospheres ATMS   Bar BAR   Feet of Water FT H20  Grams   cm2 GM SQCM  Inches of Mercury IN HG  Inches of Water IN H2O  Inches water   4  C INH204C  Kilograms   cm2 KG SQCM  Kilopascal KPASCAL  Megapasc
48. esting communications for an installation  with remote Field Units or those that are hard to reach  To conduct the Link Test from a  Base Radio  see Section 3 2 2 2  To conduct the Link Test from WIM  see Section  3 2 2 3     AWS Wireless Level Products Field Units   User Guide Rev 0307    3 2 2 1    Conducting a Link Test from the Field Unit  The Link Test is located in the Field Unit s diagnostic menu  see Figure 3 3              OPERATIONS SEQUENCE      3 2 2 2    10    dm  ENTER  5 STARR    4 STARR    3 STARR  2 STARR    1 STARR  NO LINK       Figure 3 3 Field Unit Link Test    Using the NEXT and ENTER buttons  navigate to Link Test and press the ENTER button  to begin the test  The Field Unit will begin to test the link in both directions  to and from  the Base Radio   During this time  the word TEST will appear on the LCD display  When  the test is complete  the Field Unit will display the quality of the link  Be aware that the  Field Unit uses the configured Baud Rate and transmission rate to perform this test  The  length of time it will take to perform this test depends on the device   s normal transmitting  rate     When enough messages have been observed  link strength will be shown on the display   5 STARR indicates the strongest link  while 1 STARR indicates the weakest link  The  Link Test will continue to be evaluated and the rating on the screen may adjust itself   Keep in mind that the longer the Link Test runs  the more data the Field Unit will have to  eval
49. f the  configuration menu to aid you in setting up the Field Unit for proper operation        T  NEXT  NEXT NEXT       DIAGNSE   NEXT    FACTORY     NEXT EXIT       USER PROMPTED FOR          PASSWORD  UF     CSTAS   NEXT   SAMPLING   NEXT    NEXT       Figure 4 3 Overall Configuration Menu Map    Note You must enter a four digit password to enter the CONFIG and DIAGNSE menus   The FACTORY menu is for factory use only  The default user password is 0000  For  more information about the password  see Section 4 5     4 4 Setting the Field Unit Tag Name    Note Once WIM has been used to configure the Field Unit  this menu option will be  disabled on the Field Unit LCD menu  See Section 4 1 for more details     Each Field Unit has a user settable Field Unit Tag Name  This Tag Name is displayed  upon Field Unit power up  and when the Read Only Sequence is selected  The Tag  Name is a 21 character string that is displayed in three separate 7 character flashes on  the Field Unit LCD     16 AWS Wireless Level Products Field Units   User Guide Rev 0307    17    You may choose from A Z  0 9  a dash            and an underscore     _      The underscore  has a special meaning to the software inside the Field Unit  For example  if you have a  Tag Name that is only five characters long  then you may not want to wait for the  remaining 16 characters to be displayed on the LCD  So if your Tag Name was    TANK1     you would want to enter the Tag Name like this     TANK1       The Tag Name ca
50. here is a small detent in the connector which must be fully depressed to  remove the battery wiring connector  Once the detent is sufficiently depressed   the connector sections are easily disengaged  If the connector sections do not  disengage easily  you have not depressed the detent sufficiently  Do not apply a  large amount of force to separate the connection sections and do not pry the  connector apart     b  Cut the plastic tie wraps that hold the battery pack in place   c  Remove the battery pack and the plastic tie wraps     d  Slide the new plastic tie wraps included in the replacement kit through the  mounting holders on the circuit board     e  Place the new battery pack on the mounting holders and fasten the two tie  wraps     f  Plug the connector into the battery connector on the circuit board  Note that  the connector has a specific mating orientation and is intended to only engage  in one orientation  Do not force the connectors together  If it does not fit  easily  check to see if the battery connector is backwards and try to plug the  connector in again     6  If the battery looks like that shown in Figure 9 2 on page 51  then replace it by  following steps 6 a through 6b and then proceed to Step 7    49 AWS Wireless Level Products Field Units   User Guide Rev 0307       Figure 9 1 WI Battery Kit   01    a  Look carefully at the battery in the unit and identify the positive     end and  the Negative     end  The positive and negative terminals are marked on 
51. ility     All Base Radios and Field Units can be set to one of 16 different RF channels  The only  Field Units recognized by a particular Base Radio are the units that are on the same RF  Channel as that Base Radio  This allows you to decide which Field Units communicate  with each Base Radio     The RF Channel idea is analogous to a set of walkie talkies  If both walkie talkies are on  channel one  they can communicate  If a walkie talkie is on channel one and the other is  on channel two  they cannot communicate  Likewise  if two walkie talkies are on channel  one  and two other walkie talkies are on channel two  the walkie talkies on channel one  cannot hear what is being transmitted by the walkie talkies on channel two     Each Field Unit comes from the factory with the RF Channel set to OFF  This means the  Field Unit will not communicate with any Base Radio  To set the Field Unit for  communication  first determine the channel that you want to use  Then follow the Field  Unit menu map shown in Figure 5 1 to configure the RF Channel     quom   gt      a a             ENTER     RF CHAN  enter  gt  _RF CH16   Default of RF OFF       Figure 5 1 Menu Map to RF Channel Setting    AWS Wireless Level Products Field Units   User Guide Rev 0307    Once in the RF Channel menu  increment it by pressing the NEXT button  When  selecting this value  do not choose an RF Channel that is currently being used by other  AWS Wireless Systems as this can cause communication problems     5 2 
52. ing rate information as  shown below     Gauge Level Pressure Properties    14 10   General   Range   Operation Mode   Sensor Offset    Sampling Rates   Sampling Bands   Alarms      Update Rates    Normal Transmit Rate   i0Sec       Abnormal Transmit Rate   sec  gt    Normal S ampling   se    Abnormal S ampling   ise  gt        Smart Smoothing    The Smart Smoothing feature rejects noise and glitches by averaging  samples within the deadband and ignoring the first sample outside the  deadband       Enable Smart Smoothing      1 255 Seconds    Psi    SmartRate    The SmartRate feature causes the field unit to transmit its data  immediately any time the primary value changes b    Enable SmartR ate    Load from File      Save to File    Cancel       Figure 6 13 Smart Rate Configuration Using WIM  3  Select the Enable SmartRate check box     4  Enter the amount the process value needs to change  in order to trigger a  transmission to be sent     5  Click OK to save and download the configuration changes to the Field Unit     36 AWS Wireless Level Products Field Units User Guide Rev 0307    6 6    37    Selecting the Normal Upper and Lower Values    Each Field Unit is equipped with an upper and lower value for the analog input level  As  the analog input is measured  it is compared to a set threshold value  Depending upon  the setting of that value  whether it is enabled or not  and what the Time Deadband is  the  Field Unit will enter an Abnormal condition as seen in Figure 6 14 
53. l   42 US gallons     BarrelPerMin   133     barrels per minute      BarrelPerHr   134     barrels per hour      BarrelPerDay   135     barrels per day      GalPerHr   136     gallons per hour      ImpGalPerSec   137     imperial gallons per hour      LiterPerHr   138     liters per hour          Velocity Units       AWS Wireless Level Products Field Units   User Guide Rev 0307    71    FtPerSec   20     feet per second     MetersPerSec   21     meters per second     InPerSec   114     inches per second     InPerMin   115     inches per minute     FtPerMin   116     feet per minute     MetersPerHr   120     meters per hour          Volume Units      Gallons   40     gallons      Liters   41     liters      ImpGallons   42     imperial gallons      CuMeters   43     cubic meters      Barrels   46     barrels      Bushels   110     bushels      CuYard   111     cubic yards      CuFeet   112     cubic feet      Culnch   113     cubic inches      BarrelsLiquid   124     liquid barrels   1 bbl liq   31 5 US gallons     NormalCuMeter   166     normal cubic meter   MKS System     NormalLiter   167     normal liter   MKS System      StdCuFeet   168     standard cubic feet   US System     HectoLiter   236     hectoliters          Length Units      Feet   44     feet      Meters   45     meters      Inches   47     inches      CM   48     centimeters      MM   49     millimeters      FtInSixteenths   151     see Note 1 in HART document HCF_SPEC 183          Time Units      Min   50    
54. l x  C EXIT7_     SELECTED  NEW  TRIM IS SAVED  IF    ENTER NO Tate  NO  IS SELECTED   TRIM POINT IS  DISCARDED           IF  YES  IS  ER gt   PRESSED  TRIM IS  NEXT RESET  IF  NO  IS  PRESSED  NEW    Wee RESET  el NOTES    NEXT NTER     TRIM IS  CANCELLED    Field Unit Menu Map  page 3     69 AWS Wireless Level Products Field Units User Guide Rev 0307    Appendix D Modbus Register Definitions    70       Temperature Units      DegC   32     Degrees Celcius     DegF   33     Degrees Fahrenheit     DegR   34     Degrees Rankine     DegK   35     Kelvin          Pressure Units      InH2OAt68F   1     inches of water at 68 degF     InHgAtOC   2     inches of mercury at 0 degC     FtH2OAt68F   3     feet of water at 68 degF     MMH2OAt68F   4     millimeters of water at 68 degF     MMHgAtOC   5     millimeters of mercury at 0 degF     PSI   6     pounds per square inch      BAR   7     bars      MilliBAR   8     millibars      GMPerSqCm   9     grams per square centimeter     KGPerSqCm   10    kilograms per square centimeter     Pascals   11     pascals      KiloPascals   12     kilopascals      Torr   13     torricellis      Atmospheres   14     atmospheres      InH2OAt60F   145     inches of water at 60 degF     CmH2OAt4C   170     centimeters of water at 4 degC     MetH2OAt4C   171     meters of water at 4 degC     CmHgAtOC   172     centimeters of mercury at 0 degC     PSF   173     pounds per square foot      HectoPascals   174     hectopascals      PSIA   175     pounds per
55. le      Save to File       Figure 6 2 Sampling Rates Tab  3  Select one of the time periods from the Normal Transmit Rate drop down list box     4  Click OK to save and download the configuration changes to the Field Unit     Selecting the Normal Sampling Rate    The Normal Sampling Rate is the interval in which the Field Unit reads the monitored  process value  As previously mentioned  the Field Unit is in  sleep  mode to save power  during the operations sequence  This mode turns off most of the electronics on the unit   with the exception of the LCD  in order to preserve battery life  The Field Unit will then   wake up  for every Normal Sampling Period and take the necessary process value  readings     AWS Wireless Level Products Field Units   User Guide Rev 0307    Notice that the minimum speed of the Normal Sampling Rate depends on the Normal  Transmission Rate setting selected  see Section 6 1   The Sampling Rate cannot be  slower than the Normal Sampling Rate  Thus  if you selected the Normal Transmit Rate  setting to be 10 Seconds  the Normal Sampling Rate must be set to 10 Seconds or  faster  A complete table of these parameters is shown below              Baud Rate 76 8K 19 2K 4 8K   communication range  500 750 feet 2000 2500 feet 3000 feet   speed of updates  1 Second 5 Seconds 20 Seconds       Normal and Abnormal       1 Second or Greater 5 Seconds or Greater 20 Seconds or Greater  Transmit Rates          Normal and Abnormal Equal to Transmit Equal to Transmit Ra
56. le      Save to File    Cancel       Figure 6 6 Sampling Rates Tab  3  Select one of the time periods from the Normal Sampling drop down list box     4  Click OK to save and download the configuration changes to the Field Unit     28 AWS Wireless Level Products Field Units User Guide Rev 0307    29    Selecting the Abnormal Transmission Rate    Note If the device is not configured to check for abnormal process conditions using the  Sampling Bands  section 6 6 2   the Abnormal Transmission Rate is not used and this  section can be ignored     The Abnormal Transmission Rate is identical to the Normal Transmission Rate with  one exception  The Abnormal Transmission Rate only applies while the Field Unit is in  an abnormal condition  see Section 6 6 Selecting the Normal Upper and Lower Values    This allows an increase or decrease in the frequency of information you receive  depending on the operating conditions of the process being monitored     In order to properly set the Abnormal Transmission Rate  determine how often updates  are needed from the Field Unit when the process being monitored is operating under  normal conditions  The Field Unit has a selectable range of 1 5  10  15  20  40 seconds   and 1 minute  Figure 6 7 is an example of how the device switches transmission rates  from Normal Transmission Rate to Abnormal Transmission Rate  Note how the first  abnormal transmission is sent immediately when the Normal Upper Value set point is  exceeded  The next transmission 
57. ming the process measurement     8 Selecting and Configuring Operation Modes  In this section  the two operation modes  Pressure and Gauge Level  of the Level Field  Units are discussed in order to aid you in selecting the right mode for your application     9 Maintaining the Field Unit  This section explains how the Field Unit should be cared for once it has been placed into  service and how to change the battery     10 Technical Specifications    This section explains the technical specifications that are associated with this device   such as power characteristics  accuracy  and operating characteristics     AWS Wireless Level Products Field Units   User Guide Rev 0307    1 2 ABOUT THE DEVICE    Each AWS Level Field Unit is a reliable RF  Radio Frequency  transceiver coupled with a  Gauge Level sensor that can be used in two different modes  to monitor submerged  pressure or tank level  Tank level calculations can be performed using any of the  following methodologies  height  volume  or mass     The time and expense of running wires often makes it difficult to measure parameters  that have an economic impact on your plant operation  but the Level Field Units allow you  to quickly and accurately monitor those devices at a fraction of the cost  This gives you  bigger and faster returns on your instrumentation investments     The Field Units communicate in a secure  digital protocol over a band of frequencies from  902MHz to 928MHz  This data communication technique has been 
58. n also be entered via WIM  To do so  when the software is in the Field  Unit view  See Appendix A   right click the Field Unit icon  select Rename  and then enter  the Tag Name you wish the Field Unit to have     This Tag Name will then be uploaded to the Field Unit and can be displayed by pressing  the ENTER button when the unit is in the Operations Sequence  See Section 4 2 1 of this  manual      Setting a User Password    Note Once WIM has been used to configure the Field Unit  this menu option will be  disabled on the Field Unit LCD menu  See Section 4 1 for more details     Each Field Unit has a password that will lock out undesired users from making changes  to the Field Unit  Any user may still view some of the Field Unit settings by pressing the  ENTER key during the Operations Sequence and viewing the Read Only Sequence     The password consists of four digits  The factory default is 0000  If you wish to select a  different password  one may be entered via WIM  To do so  enter the configuration dialog  box  See Appendix A   From the configuration dialog box  click on the General tab to  bring up the general information as shown in Figure 4 4     AWS Wireless Level Products Field Units   User Guide Rev 0307    18    Gauge Level Pressure Properties    14 10     Sampling Rates   Sampling Bands   Alarms    General   Range   OperationMode     Sensor  ffset      Description    Location     Date Installed       Comments       General    Monitored Equipment     Field Unit Pa
59. n error code will then be displayed in the format    Error  Error Code      After three  seconds  the display will flash and show a number followed by the letter  H   this  represents the register location in the Field Unit s firmware where the error occurred  The  display will continue to flash  alternating between the error number and code and the  register location until you press enter to return to the diagnostic menu     For example  the display may show    E5 23  and then    10H    after flashing  The number  after the letter  E  indicates that the error is the fifth most recent  In the example  the code  of the error is 23  Use Figure 9 4 to determine the meaning of the error codes     Pressing the NEXT button while the Field Unit is displaying a logged error will show the  next available entry  After the Field Unit has cycled through all six error messages  E1   E6  E1 will be displayed the next time you press the NEXT button     The table in Figure 9 4 on the following page shows the possible error codes and their  definitions     AWS Wireless Level Products Field Units   User Guide Rev 0307                                                                                              Code   Description  1   generic or unspecified error  2   watchdog timeout  causes automatic reset through hardware   3   oscillator fault error  causes automatic reset   4   internal RAM error  5   undefined interrupt vector error  6   false spurious interrupt trigger error  20   any of 
60. nfigure the Upper and Lower Limits from the  Field United monne c et cce crop aute  38  6 6 2 Configure the Upper and Lower Limits  Usimg  WM 222224 302256 S ee eet qeu 39  7 CONFIGURING THE PROCESS VARIABLE                            enne 40  ZV    ZEROING THE SENSOR       5 texere tinte contd itunes 40  7 2 SETTING A MEASUREMENT OFFSET    41  7 3 TRIMMING THE MEASUREMENT         ccccececeeeeeeceeeceeeeeeaeeeetarenetererereters 42  7 4 ENTERING A 22  POINT CURVE  secet trond boe te iet 42  8 SELECTING AND CONFIGURING OPERATION MODES                           44   amp T  PRESSURE soa saco nen otc n cached Cte ecd oio er 44  8 2    GAUGE LEVEL iei inniti e eer Dee AGI Pr taedet n tee eed Te cand 45  9 MAINTAINING THE FIELD UNIT                              eere nennen 48  9 1 CHANGING THE BATTERY              eseeeeeeeeeeeenen entente ettet tnnt 48  9 2 DEBUGGING THE FIELD UNIT    eene 51  9 2  T   Error LOS uiii ipie eee etaed 52  92 2 Error COUMIS 265 iode eor Sie 53  072 3  JEESStAUSHIESC a ore D ee eee us 54  9 244  Clear LOS jcc nanugainusiaddcununianmuoudad  55  10 TECHNICAL SPECIFICATIONS                             eere nnne nnn 57  TOI WESESXOC  ui B pepper pretend deh nand oda 57  10 2  WIEGLZ  XXL iiid idee eite dise dr ti riego 59  10 3  WEGLSEPXX   adii preise re e Heo Organ deno 61  10 4 WI GL E Y6 XX ooo cece cece eeee ee esten enne nre nennen resins entren nene 63  APPENDIX A OPENING THE CONFIGURATION BOX IN WIM                      65  APPENDIX B FIELD UNIT DI
61. nitored Equipment      ID      DeviceType   Status   Primary  amp  Secondary Values  000 14 041 Dual 4 20 mA Input 1N1 35 00 m    51 0    Tasks    View Field Unit Data     Configuration       Export Data       Wireless Link Test       4 24 2006 10 34 38 AM  Device  RF Channel   14  ONLINE  4 24 2006 10 34 38 AM  Field unit 14 041 ONLINE  4 24 2006 10 34 50 AM  Device discovery completed       new devices found  0 devices removed          1 Total Field Unit   D Alarming Field Units  Figure 3 5 WIM Field Unit View  Select Wireless Link Test    from the popup menu     The Wireless Data Loss Test window appears  Figure 3 6   The name of the Field Unit  being tested appears in the title bar in parentheses     Wireless Link Test  Unit 14041          Configure Test    Hours Minutes Seconds          r Progress    Logging data    00 04 57 left                Figure 3 6 Wireless Data Loss Test    AWS Wireless Level Products Field Units   User Guide Rev 0307    13    In the top of the window  you can configure the test to run for a specified amount of time   The longer the test  the more data the test will have to do an evaluation  Type the length  of time that you want to run the test and click Begin to start  Once the test starts  WIM  will reconfigure the Field Unit s Transmit Rate to the fastest possible for the selected  Baud Rate  These rates are listed in Section 5 2  After the test has completed  it will  restore the previously configured Transmit Rate     During the test  the c
62. nsiderable  shock  or to dripping condensate or corrosive materials  Also avoid installing the device in  an unserviceable location     Most often these problems can be avoided with some thought at the time of installation   The practices noted below are generally recommended  but they can only act as a  guideline and cannot cover all possible variations  The final installation must be made at  the discretion and approval of the user  The user must be the judge of the actual  installation     Dimensioned mechanical drawings for aid in mechanical installation are located in  Section 10 Technical Specifications     Field Unit Positioning    Correct positioning of the Field Unit will ensure the best performance of the device  When  planning the positioning of the Field Units  there are a few parameters that must be paid  attention to     e The top of the Field Unit should point in an upward fashion  The bottom of the Field    Unit should NOT point directly at the Base Radio and the Field Unit LCD should  point away from the Base Radio     AWS Wireless Level Products Field Units   User Guide Rev 0307    e All Field Units should maintain an approximate spacing of at least six feet apart from  one another  Should you need to put Field Units closer than six feet  please see  Section 3 1 1 1 entitled  Technique for Close Positioning of Field Units      e The line of sight range between a Field Unit and Base Radio is 2000 feet at the  19 2K baud rate setting  Note that this range is r
63. o  185  F   40  C to  85  C  electronics    4F to  158  F   20  C to  70  C  display  full visibility     40 F to  185  F   40  C to  85  C  display  with reduced visibility     Physical Characteristics   e Type 316 Stainless Steel Base and Diaphragm  e Standard 77  MNPT  Other Options Available   e GELexanQ cover  V O rating and UV stable    Operating Vibration and Shock Characteristics  e Certified per IEC ENOOO0668 2  6  vibration  and 2 27  shock     Random Vibration Characteristics  e Certified to withstand 6 g s  15 minutes per Axis from 9     500 Hz    Electromagnetic Compatibility  CE Compliance    e Operates within specification in fields from 80 to 1 000 MHz with Field strengths to 30  V m  Meets EN 50082 1 general immunity standard and EN 55011 compatibility  emissions standard    Industrial Certification   e Rated for industrial use  40  F to 185  F   40  C to 85  C    e FM NEMA 4 weather proof housing   e FM rated intrinsically safe for Class I II  Division 1  Groups A B C D E F amp G  Class  MII  Division 2  Groups A B C D F amp G    63 AWS Wireless Level Products Field Units   User Guide Rev 0307    64    W2 HPT  Process fitting                   Figure 10 4 WI GL E Y6 XX Dimensioned Mechanical Drawing    AWS Wireless Level Products Field Units   User Guide Rev 0307       Appendix A Opening the Configuration  box in WIM    In WIM  go to the Field Unit View  This view shows the Field Unit information and allows  you to configure and view individual Field Unit da
64. oes back to the normal display mode     If you enter a sub menu that requires a numerical input  such as 001  the leftmost zero  will be blinking  This indicates that pressing the NEXT button will increment this value  with each press from 0 to 9  Pressing the NEXT button when the value is at 9 causes it to  reset back to 0  Pressing the ENTER button will move to the next available value  If the  last value is blinking  pressing ENTER will save the entered values and return from the  sub menu     If both the NEXT and ENTER buttons are depressed at the same time while the unit is  turned on  a message on the LCD displaying OFF  will appear  If both buttons are  released upon appearance of this message  you will be returned to the scrolling main  screen  If both buttons are not released for the duration of the OFF  message  you will be  prompted for the password  Upon entering the correct password  the unit will power down  and turn off     Note If the unit is turned off while entering values in a sub menu  those values will NOT  be saved     Note There are several menu options that will automatically turn off if you are using WIM   All changes to these Field Unit menu options should then be made through WIM instead   This is to prevent simultaneous changes from taking place  If you wish to discontinue use  of the software and want these menus re instated  you must contact your Adaptive  Wireless Solutions Sales Representative     Field Unit Displayed Messages    To turn the Fi
65. om the factory   Enable the offset curve by selecting the Sensor  Offset tab within the configuration dialog box  For additional information on a 22 point  sensor curve  see Section 7 4     AWS Wireless Level Products Field Units   User Guide Rev 0307    9 1    48    Maintaining the Field Unit    The Level Field Units are extremely easy to maintain in that they require no periodic  calibration or system checks  Each Level Field Unit has a self diagnostic that is  constantly checking the internal system  If the field unit finds any errors  they are reported  via the LCD or in the WIM software  A simple yearly visual inspection for the following is  all that is needed     e   sthe Field Unit still securely fastened to the equipment being monitored   e Are there any visible corrosions  cracks  or residue build ups on the unit     e Has anything about the application changed from the original intended use     Changing the Battery    The battery will need to be changed within one month of seeing a    LOW BAT    message  on either the Field Unit or in the Wireless Instrumentation Manager  Changing the battery  is a simple process  but you need to carefully follow the guidelines as the battery is a  safety component of the Wireless Field Unit and needs to be changed in accordance with  this procedure to maintain the safety of the device     1  Make sure you have the correct replacement battery   There are two types of batteries depending on the date of manufacture of the  field unit
66. ommunications reliability is evaluated while the Field Unit is running  under normal operating conditions  As the test runs  link strength is shown in the lower  right hand corner of the window  5 STARR indicates the strongest link  while 1 STARR  indicates the weakest link  The Link Test continues to be evaluated and the rating on the  screen adjusts itself for the specified amount of time     AWS Wireless Level Products Field Units   User Guide Rev 0307    4 1    4 2    14    General Configuration    This section discusses general configuration of the Field Unit via the NEXT and ENTER  buttons  The subsections are as follows     4 1 Navigating User Menus   4 2 Field Unit Displayed Messages  4 3 Overall Configuration Menu Map  4 4 Setting the Field Unit Tag Name  4 5 Setting a User Password   4 6 Resetting All Field Unit Settings    Navigating User Menus    Pressing either the NEXT or ENTER buttons located on the front of the Field Unit or Base  Radio just below the LCD screen is all that is needed to navigate the respective menus   Pressing both of these buttons simultaneously for one second will turn the unit on     Pressing the NEXT button at any time while the Field Unit is cycling through the normal  messages causes the Field Unit to enter the setup mode  The NEXT button is then used  to step through menu options  and the ENTER button is used to enter a sub menu of  what is displayed on the LCD at that time  If no button is pressed within a 30 second  period  the unit g
67. opriate      Perform the following via WIM     Select a mode of operation    Select the appropriate engineering units   Enter the appropriate calculation parameters   Select the normal transmission rate    Select the normal sampling rate    Select the abnormal transmission rate   Select the abnormal sampling rate     Set the normal upper and lower values     If the  RF OFF  message is being displayed on the Field Unit LCD  perform the  following     Set the RF CHAN setting equal to the Base Radio s RF Channel     If  NO RF  is being displayed on the Field Unit LCD  check the following     Is the Field Unit set to the above listed settings     AWS Wireless Level Products Field Units   User Guide Rev 0307    Is the Base Radio on     Do the Field Unit and Base Radio settings match   See Section 5 of the Field Unit  and Base Radio User Manuals     Are the Base Radio and Field Units unable to communicate due to obstructions or  distance   See Section 3 1 1 Field Unit Positioning      Have you run the RSSI Diagnostics   See Section 3 2 1 Field Unit RSSI Diagnostic     Warning  If the Field Units have been running for an extended period of  time with no signal from the Base Radio  the Base Radio is off or not  present   the Field Units will only search for the Base Radio every one  hour or so  Turning the Field Units off and back on will cause them to  begin searching immediately     AWS Wireless Level Products Field Units   User Guide Rev 0307    3 1    3 1 1    Installation    e W
68. r URL over temperature    Stability  e Combined zero and span stability  Less than   0 1  of sensor URL per year at 70  F    RF Characteristics   e 902 MHz   928 MHz Frequency Hopping Spread Spectrum  FCC certified ISM  license free band   e Up to 3000    range from Base Radio with clear line of sight   e The RF module in each field unit is individually tested and calibrated over the full  temperature range to ensure reliable wireless operation    Operating Temperature Range   e  40  F to  185  F   40  C to  85  C  electronics   e  A F to  158  F   20  C to  70  C  display  full visibility    e  40 F to  185  F   40  C to  85  C  display  with reduced visibility     Physical Characteristics   e Type 316 Stainless Steel Base and Diaphragm  e Standard 77  MNPT  Other Options Available   e GELexanQ cover  V O rating and UV stable    Operating Vibration and Shock Characteristics  e Certified per IEC ENOOO0668 2  6  vibration  and 2 27  shock     Random Vibration Characteristics  e Certified to withstand 6 g s  15 minutes per Axis from 9     500 Hz    Electromagnetic Compatibility  CE Compliance    e Operates within specification in fields from 80 to 1 000 MHz with Field strengths to 30  V m  Meets EN 50082 1 general immunity standard and EN 55011 compatibility  emissions standard    Industrial Certification   e Rated for industrial use  40  F to 185  F   40  C to 85  C    e FM NEMA 4 weather proof housing   e FM rated intrinsically safe for Class I I III  Division 1  Groups A B C
69. ressure Properties    14 10          Sampling Rates  General   Range    Sampling Bands  Operation Mode    Alarms    l               Sensor Offset       Mode    Fluid Level            Level          Density      Specific Gravity Units v        C Ful Tank Pressure                Tank Height      Feet       Tank Volume      Cubic Feet       Level Offset        Level Units     Load from File      Save to File       Feet             Feet       Cancel       Figure 8 2 Gauge Level Mode    You should select the units that are appropriate for your application  Note that the units  differ based on calculations by density and by Full Tank Pressure  For pressure units   see Section 8 1  Density and Height units are listed below and on the next page                                            Degrees API degAPI  Degrees Baume heavy degBaum hv  Degrees Baume light degBaum It  Degrees Twaddell degTwad  Grams   liter G L   Grams   cubic centimeter   GM CUCM  Grams   milliliter GM ML  Kilograms   cubic meter KG CM  Kilograms   liter KG L  Pounds   cubic foot LB CUFT  Pounds   cubic inch LB CUIN  Pounds   gallon LB GAL  Specific Gravity Units SGU   Short tons   cubic yard STON CUYD             AWS Wireless Level Products Field Units    User Guide Rev 0307                      Centimeters CM   Feet FEET  Inches INCHES  Meters METERS  Millimeters MM  Percent  96  PER FS                Once you select the engineering  you MUST enable a 22 point sensor offset curve  it is  disabled upon delivery fr
70. romthe Base Radio   This increments when a bit error 1s detected by the Field Unit during  the start of frarne message it is receiving from the Base Radio  after the    _ pattern match     Not implemented  Not implemented      Incremented if Field Unit ever wakes up in the wrong timeslot     This increments when it wakes up and doesn   t receive the start of  frame message from the Base Radio at all  If a pattern match is  received and then the error occurs  C is incremented instead    This increments if the Field Unit is told to receive an Asyne message   but does not receive the message for whatever reason  it becomes  corrupt  the base radio fails to send it  etc        Debug    Number of synchronous messages sent fromthe Field Unit to the Base    Radio    After three failed attempts to receive a start of frame message from the    Base Radio  the message buffer flushes  the field unit tries to re   synchronize its clock with the Base Radio  and this number gets  incremented      Not implemented    Not implemented    Number of times the Field Unit successfully re synchronized itself   with the Base Radio     Number of times the Field Unit attempted to re synchronize itself with  the Base Radio    Debug    Number of times the RF driver has attempted the 2    synchronous data  re transmission    Number of times the RF driver has attempted the 3  synchronous data      re transmission __ A  Number oftimes the RF driver has failed to transmit a synchronous  message and has stopp
71. s that the Field Unit and Base Radio are attempting to synchronize  communications  If this is successful  the RF Status will display an RF OK message  If  this is unsuccessful  the RF Status will display a NO RF message     Also notice the two small arrows on either side of the LCD  if they are fluctuating up and  down  that indicates the Field Unit and Base Radio are successfully communicating  If  only one or none of the arrows are moving  then they are not communicating  successfully     AWS Wireless Level Products Field Units   User Guide Rev 0307    6 1    Configuring the Sampling and  Transmission Rates    The Level Field Units are very versatile with many programmable features and can be  used in numerous different applications  Because no two applications are the same   some configuration is required for each unit  This section will walk you through the initial  configuration of the Sample and Transmit settings  Each section includes instructions for  configuring the rates from the Field Unit and with WIM  The subsections are as follows     6 1 Selecting the Normal Transmission Rate   6 2 Selecting the Normal Sampling Rate   6 3 Selecting the Abnormal Transmission Rate  6 4 Selecting the Abnormal Sampling Rate   6 5 Setting the Smart Rate Threshold   6 6 Selecting the Normal Upper and Lower Values    Selecting the Normal Transmission Rate    The Normal Transmission Rate is the interval in which the Field Unit transmits data to  the Base Radio  The Field Unit is in a 
72. several possible errors that should never happen in the kernel but are checked just  in case  21   kernel configuration error   number of defined tasks does not match what is actually in the  task data table  22   maximum number of preemptive scheduler instances has exceeded the allowed limit  23   kernel interrupt occurred without the appropriate status flags being set  24   task is in an error state  25   runaway task timer   i e  the current timeout value is greater than the beginning periodic  value  26   apreemptive task that is already active has been attempted to be executed a second time  30   semaphore is already owned by another task  40   stack overflow or underflow error  41   checksum error for calibration data  42   checksum error for program Flash  43   invalid value for one of the Chiplet s nonvolatile memory configuration parameters   i e   update rate  contrast etc   50   external A D converter error  51   broken sensor lead s  error  60   ALL parameters were reloaded to their defaults  100   the SmartWatch module is not responding to sample and or communications wakeup  attempts  101   the Xemics transceiver failed at least one write readback test  102   the Xemics  clock output should be enabled  103   problem with EEPROM communication  no sensor board or bad EEPROM  104   problem initializing or communicating with the Aic Sensor ADC or no sensor board  Figure 9 4 Definitions of error codes  9 2 2 Error Counts  The Error Counts menu contains a list of six 
73. smission Rate     AWS Wireless Level Products Field Units   User Guide Rev 0307    6 1 1 Configure the Normal Transmission Rate from the Field Unit    To configure the normal transmission rate  follow the menu map below     Note Once WIM has been used to configure the Field Unit  this menu option will be  disabled on the Field Unit LCD Menu              N EE    Default of 10 Seconds  NEXT     SAMPING ENER  NORM XR ENTER   1  5 10 SEC  15 SEC  20 SEC  40 SEC  1 MIN    Figure 6 1 Menu Map to Normal Transmission Rate Setting    24 AWS Wireless Level Products Field Units User Guide Rev 0307    6 1 2    6 2    25    Configure the Normal Transmission Rate Using WIM  1  Open the configuration dialog box  See Appendix A      2  In the configuration dialog box  click the Sampling Rates tab to display the  sampling rate information as shown below     Gauge Level Pressure Properties    14 10     General   Range   Operation Mode   Sensor Offset    Sampling Rates   Sampling Bands   Alarms      Update Rates   Abnormal Transmit Rate   5Sec Q Z Q  Normal Sampling    Abnormal Sampling     Smart Smoothing    The Smart Smoothing feature rejects noise and glitches by averaging  samples within the deadband and ignoring the first sample outside the  deadband       Enable Smart Smoothing    1 255 Seconds  Psi    SmartR ate    The SmartRate feature causes the field unit to transmit its data  immediately any time the primary value changes by the amount set       Enable SmartRate          Load from Fi
74. ssword   0000    NOTE  Device is in Pressure mode and units are in Psi     Load from File      Save to File          Figure 4 4 Setting a User Password    You can set the Field Unit password for this device by entering a four digit number in the  Field Unit Password field  Once a password is entered  click OK to save and download  the password to the Field Unit     Please note that the password only protects the Field Unit from unauthorized  configuration via the NEXT and ENTER buttons  WIM requires a user login password to  gain access to all configuration parameters  However  user accounts are available and  can be set with different access levels and restrictions  For more information on user  accounts see the WIM User Manual Section 8 4      AWS Wireless Level Products Field Units   User Guide Rev 0307    4 6 Resetting All Field Unit Settings    To reset all Field Unit settings to their default state  you must navigate to the DEFAULT  menu option in the CONFIG menu via the keypad     on the LCD  which asks you to confirm the reset operation  You will then be prompted  with  NO  on the LCD  Pressing the ENTER button while  NO  is being displayed will NOT  reset the device  Pressing the NEXT button will display  YES  on the LCD  If you press  the ENTER button while    YES    is being displayed  the device will be reset     D Note Once at the default menu option  pressing the ENTER button will display  RESET      Note Resetting the Field Unit by using the DEFAULT menu option
75. t Sampling Rate                        sssssssseeeeene 26  Figure 6 4 Correct Sampling Rate                           ciiciiciiiiiiiiciiiciiiic iini siiis 27  Figure 6 5 Menu Map to Normal Sampling Rate Setting                                      27  Figure 6 6 Sampling Rates Tab                     ssssssssseeeeenneenen 28  Figure 6 7 Example of Abnormal Transmission Rate Setting                               29  Figure 6 8 Menu Map to Abnormal Transmission Rate Setting                            30  Figure 6 9 Sampling Rates Tab                    ssssssssssee eene 31  Figure 6 10 Example of Abnormal Sampling Rate Setting                                   32  Figure 6 11 Menu Map to Abnormal Sampling Rate Setting                                33  Figure 6 12 Sampling Rates Tab                      sssssssseeeeeennene 34  Figure 6 13 Smart Rate Configuration Using WIM                           eene 36  Figure 6 14 Normal Upper and Lower Value Example                               ssesss 37  Figure 6 15 Condition  Chatter  Without Time Deadband                                   37  Figure 6 16 Condition  Chatter  Elimination Due to Time Deadband                   38  Figure 6 17 Normal Upper and Lower Value                           eee 39  Figure 7 1 Menu Map to Pressure Zero Setting    41  Figure 7 2 Menu Map to Offset Setting                      sss 41  Figure 7 3 Menu Map to Trim Setting    42  Figure 7 4 Setting a 22 Point Curve for Level Using WIM                    
76. ta  This view can be accessed at any  time by clicking on the Field Units icon in the Views pane  The Field Unit View is shown  below  More information is found in Sections 8 and 9 of the WIM User Guide     VZ Accutech Wireless Instrumentation Manager  Connected     Ele View Help    Field Units      ico RETE      O  Alarming Field Units Total Field Units  1    Alarming Field Units  0    O Unconfigured Field Units 7   Warning Field Units  0  2    Field Unit Groups Field Unit Tree r    O Base Radios    Connection   A   y All Field Units        Field Unit Types Contains all field units    registered in the system                   Field Units All Field Units    d  TagName   Monitored Equipment   ID__  DeviceType   Status    DK    00013007 13 07 Gauge Level Pressure IN1 0 00 Psi    Base  amp  Output    Devices  SS Field Unit Pane  es    Accounts 2 17 2005 5 49 29 PM  Device discovery completed       new devices found     devices removed  2 17 2005 5 50 23 PM  Field unit 13 07 ONLINE  2 17 2005 5 50 24 PM  Field unit 13 07 name resolved to  00013007     Events Chat  1 Total Field Unit la Alarming Field Units          Figure A  1 WIM with All Field Units view    The Field Units are displayed in the Field Unit Pane based on the selection in the Field  Unit Tree     To open the Configuration dialog box  right mouse click a Field Unit and select  Configuration from the Right Mouse Button menu     Rename  Tasks  gt     View Field Unit Data     Configuration           Export Data       
77. te   Equal to Transmit Rate  Sampling Rates Rate or Less or Less or Less                   26    In order to properly set the Normal Sampling Rate  determine how often updates are  needed from the Field Unit when the process being monitored is operating under normal  conditions  The Field Unit has a selectable range of 1 5  10  15  20  30  and 60 seconds  depending on the Normal Transmission Rate  The factory default is one second   However  the more frequently the Field Unit wakes up to check the monitored device  the  less battery life you can expect from the Field Unit     Figure 6 3 is an example of what happens when the Normal Sampling Rate is too slow  for the process being monitored  Notice how the rise in the voltage level falls between  two normal samples  and thus goes completely undetected     Input   Volts   10       6 lt  Normal  Sample    if          0 1 00 2 00  Time  min   With a Normal  Sampling Rate of 30 Seconds    Figure 6 3 Incorrect Sampling Rate  Figure 6 4 is an example of what happens when the Normal Sampling Rate is correctly    set for the device that is being monitored  Notice how this setting makes it possible to  sample the rise in the voltage level     AWS Wireless Level Products Field Units   User Guide Rev 0307    Input   Volts   10       6     Normal  Sample                0 1 00 2 00  Time  min   With a Normal  Sampling Rate of 15 Seconds    Figure 6 4 Correct Sampling Rate    Once you have decided on the proper Normal Sampling Rate  select 
78. the  battery and on the circuit board     b  Remove the old battery and replace it with AWS Part Number  WI BAT    Be extremely careful to put the positive     end of the battery in the proper  location  Plugging the battery in backwards will cause a safety component on  the circuit board to trip and the unit will need to be returned to the factory for  safety component replacement     f  Now you are ready to replace the cover  You will note that the cover gasket has a  thin coating of gasket lubrication  Use a cotton swab to wipe around the gasket to  spread the lubrication  and then replace the housing  When replacing the housing   make sure that the flexible ribbon cable folds properly  If the ribbon cable seats next  to the antenna  the RF operating distance can be reduced  Also check to be certain  that the cover tether is not sandwiched between the cover and the cover gasket     8  Tighten the four cover screws and torque them to 18 inch pounds  1 5 ft Ibs      9  Dispose of the old battery properly in accordance with your local regulations     50 AWS Wireless Level Products Field Units   User Guide Rev 0307    9 2    51       Figure 9 2 AWS WI BAT Field Unit Battery    Warning  When removing the housing  do not twist or bend the green flex  cable  Doing so may cause the tether to improperly seat next to the  antenna and greatly reduce operable RF distances  Do not allow the  housing to flop around while hanging by the tether     Debugging the Field Unit  The field unit
79. the backbone of the  military s secure communications protocols for many years  These devices require no  wires  permits  or licenses  and they are easily set up and installed right out of the box     You can use this device for long term monitoring in remote locations  for short term data  gathering on process conditions  or for quickly testing the economic viability of a new  installation     The purpose of this manual is to help you install and maintain your AWS Level Field Unit   BEFORE setting up and installing the Field Unit please setup and configure the Base  Radio     1 3 UNPACKING    Remove the Packing List and check off the actual equipment received  If you have any  questions about your shipment  please call your Adaptive Wireless Solutions  Representative  Upon receipt of the shipment  inspect the container for any signs of  damage in transit  Especially take note of any evidence of rough handling  Report any  apparent damage immediately to the shipping agent     Please note that sometimes units are assembled with accessories when shipped  Inspect  the shipment carefully if you think that something is missing  This is rare  as we take  considerable care to pack units for shipment  but it does sometimes happen  Please give  us a call and we may be able to resolve this matter quickly over the phone     Note The carrier will not honor any claims for damage unless all shipping materials are  saved for their examination  If you find any damage while you are examining 
80. this setting from  the Field Unit or through WIM     6 2 1 Configure the Normal Sampling Rate from the Field Unit  To configure the normal sampling rate from the field unit  follow the menu map below     Note Once the WIM has been used to configure the Field Unit  this menu option will be  disabled on the Field Unit LCD Menu        l    OPERATIONS SEQUENCE  NEXT      n m a a an qu    a a a ab    NEXT    NEXT     NOR SR  enter 1 5 SEC  10 SEC  15 SEC  20 SEC  30 SEC  60 SEC    Figure 6 5 Menu Map to Normal Sampling Rate Setting    27 AWS Wireless Level Products Field Units User Guide Rev 0307    6 2 2 Configure the Normal Sampling Rate with WIM  1  Open the configuration dialog box  See Appendix A      2  In the configuration dialog box  click the Sampling Rates tab to display the  sampling rate information as shown below     Gauge Level Pressure Properties    14 10     General   Range   Operation Mode   Sensor Offset    Sampling Rates   Sampling Bands   Alarms      Update Rates  Normal Transmit Rate  10 Sec  Abnormal Transmit Rate   Norral Sampling   Abnormal Sampling       Smart Smoothing    The Smart Smoothing feature rejects noise and glitches by averaging  samples within the deadband and ignoring the first sample outside the  deadband       Enable Smart Smoothing    1 255 Seconds    Psi      SmartR ate    The SmartRate feature causes the field unit to transmit its data  immediately any time the primary value changes by the amount set       Enable SmartRate    Load from Fi
81. times the stack  a   5 temporary storage area the CPU  uses in the RAM of the unit  has  run out of space    Minimum Free Stack   Number   C6 of bytes free in stack    Figure 9 5 Error counter definitions       RF Statistics    The RF Statistics menu contains a list of 19 counters  each of which indicates the number  of times a particular condition has occurred  These conditions and their definitions are  listed in Figure 9 6  This menu allows for simplifying the task of solving communications  problems     Navigate to the RF Statistics using the NEXT and ENTER buttons and Figure 9 3 as a  guide  When the display shows RF STAT  press Enter to enter the RF Statistics menu     AWS Wireless Level Products Field Units   User Guide Rev 0307    Field Unit RF Statistics    Code   Name  A   Rx Frame Start Msgs  B   Rx In Frame Msgs  C Rx Errors  D Rx USART Errors  E   Rx Recover Errors  F Rx Wrong Slot Error  Missing Frame Start  G   Msgs  H Missing In Frame Msg  I Rx Buffer Overflow  J Tx Msgs  K   TxFailed  L Tx Lost Acks  M   Tx Retransmits  N Sync Success  i9    Syne Attempts  P RF Driver Restarts  Q 2 Sync Attempts  R   33 Sync Attempts  5 Sync Failure    9 2 4 Clear Logs    Description   Number of start of frame messages received fromthe Base Radio    The start of frame message is sent by the Base Radio at the beginning  of each set synchronous messages  If the Field Unit does not receive  this message  it cannot send its synch data    Number of asynchronous messages received f
82. ts  You should see the display ask for the PASSWORD  Enter the    AWS Wireless Level Products Field Units   User Guide Rev 0307    correct password to power down the unit  The factory default password is     0000        4  Next  remove the four cover screws on the sides of the Field Unit housing with a  standard screwdriver  Remove the housing cover  It may be a bit difficult to  separate the housing cover from the gasket  Be very careful  if you need to pry  the cover off the gasket  not to damage the gasket  When removing the cover   you will notice a flexible cable that connects the instrument cover to the  electronic circuit boards  Note the position of this cable as well as the tether  which restrains the movement of the cover  The ribbon cable is easily damaged  and must be carefully folded back into place when you replace the cover     5  Locate the battery or the battery pack and identify which type of battery you  have  The battery pack  AWS Part Number  WI BATTERY KIT     01   is shown in  Figure 9 1 on the following page  To replace this battery pack  follow steps 5a  through 5d and then proceed to Step 7  Otherwise follow steps 6a through 6b  and then proceed to Step 7    Caution  The positive end of the battery clip is the end with the red wire   Putting the battery in backwards will blow a fuse     a  If your unit contains the battery pack AWS Part Number WI BATTERY KIT    01  carefully unplug the connector that connects the battery pack to the circuit  board  T
83. tween Between Between Greater  than           105 dBm    105dBm  amp     100 dBm  amp     95 dBm  amp     90 dBm  amp     85 dBm  amp    100 dBm  95 dBm  90 dBm  85 dBm  80 dBm  80 dBm                               To place the Field Unit in RSSI Diagnostic mode  follow the menu map shown in Figure  3 2  Note that the RSSI menu is under the DIAGNSE menu and not the CONFIG menu     AWS Wireless Level Products Field Units   User Guide Rev 0307    3 2 2       T 1  I      NEXT  NEXT NExT M DIAGNSE  Next     FACTORY    wexr    EXIT       USER PROMPTED FOR  I PASSWORD  UF       Figure 3 2 Menu Map to RSSI Mode    Now that the Field Unit is in the RSSI mode  bring the Field Unit close to the equipment  you wish to monitor  Look at the LCD  notice the     gt     will constantly fluctuate  One should  estimate an average value based on these fluctuations  The ideal signal integrity is seven  arrows     Once you have verified that you are receiving a signal  you should check to make sure  the Field Unit is communicating properly with the Base Radio  To do so  exit the RSSI by  pressing ENTER  and then navigate to EXIT  of the diagnostic menu and return to the  Operations Sequence shown in Figure 4 1 in Section 4 2     If you see a NO RF message  then you do not have satisfactory RF communication with  the Base Radio  If your application allows  move the Field Unit to a different position and  check again for communications  If your application only allows you to mount at this  particul
84. uate     The Field Unit installation site should strive to place the Field Unit in a location where it  receives the highest number possible  A stronger link means less data re transmits and  longer battery life     Conducting a Link Test from the Base Radio    When the Link Test is conducted from a Base Radio  it measures the link strength  between a selected Field Unit and the Base Radio  The Link Test data must be  configured to match the communication parameters of the Field Unit from which you want  to test  The Link Test is located in the Base Radio s diagnostic menu  see Figure 3 4      To conduct a Link Test from the Base Radio  Navigate to Link Test and press the Enter  button  Next  enter the RF ID for the Field Unit that you want to test  Then select the  Normal Transmit rate that matches that of the Field Unit  If the Field Unit is transmitting  at a different rate than the one you select in this menu  your results will be invalid     Once the Normal Transmit Rate is selected  the Link Test will immediately start  The    Base Radio will begin to test the link from the Field Unit  During this time  the word TEST  will appear on the LCD display  When the test is complete  the Base Radio will display    AWS Wireless Level Products Field Units   User Guide Rev 0307    the quality of the link  Be aware that the length of time it takes to perform this test  depends on the device s normal transmitting rate        OPERATIONS SEQUENCE      l  l  berm asw    3 2 2 3    11  
85. ure 6 11 Menu Map to Abnormal Sampling Rate Setting    33 AWS Wireless Level Products Field Units   User Guide Rev 0307    6 4 2 Configure the Abnormal Sampling Rate Using WIM  1  Open the configuration dialog box  See Appendix A      2  In the configuration dialog box  click the Sampling Rates tab to display the  sampling rate information as shown below     Gauge Level Pressure Properties    14 10     General   Range   Operation Mode   Sensor Offset    Sampling Rates   Sampling Bands   Alarms    Update Rates    Normal Transmit Rate  10 Sec v    Abnormal Transmit Rate   5 Sec       Normal Sampling    rmal Sampling       Smart Smoothing    The Smart Smoothing feature rejects noise and glitches by averaging  samples within the deadband and ignoring the first sample outside the  deadband       Enable Smart Smoothing    1 255 Seconds      SmartRate    The SmartRate feature causes the field unit to transmit its data  immediately any time the primary value changes by the amount set       Enable SmartRate    when primary value      H    Load from File      Save to File    Cancel       Figure 6 12 Sampling Rates Tab  3  Select one of the time periods from the Abnormal Sampling drop down list box     4  Click OK to save and download the configuration changes to the Field Unit     34 AWS Wireless Level Products Field Units User Guide Rev 0307    6 5    6 5 1    35    Setting the Smart Rate Threshold    The Smart Rate is a feature used to trigger radio transmission of the measured data 
86. will then follow this immediate transmission by 10  seconds  or whatever the Abnormal Transmission Rate is set to   The transmissions will  continue at this interval until the process value drops below the Normal Upper Value set  point     Input   Volts   10            I     Abnormal Condition       Abnormal  Transmission        Normal  Transmission    Normal Upper       Normal Transmit Rate of 1 Min  Abnormal Transmit Rate of 10 Sec  Normal Upper Value of 2 5    Figure 6 7 Example of Abnormal Transmission Rate Setting    Once the process value drops below this set point  another transmission is sent to the  Base Radio  The transmissions will then be sent at the Normal Transmission Rate of one  minute  the current setting for the Normal Transmission Rate  from the time of the last  abnormal transmission     You should also note that the transmission time depends on the sampling rate  and when    the process value is sampled  If the Normal Sampling Rate is 30 seconds  then the  process value may be above the Normal Upper Value for up to 29 seconds before an    AWS Wireless Level Products Field Units   User Guide Rev 0307    abnormal condition is detected  This means that the transmission could be as late as 29  seconds after the process value exceeded the Normal Upper Value     Once you have decided the proper time for the Abnormal Transmission Rate  select  this setting from the Field Unit or through WIM     6 3 14 Configure the Abnormal Transmission Rate from the Field Unit 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
speed-link black hawk force joystick  DODGE JOURNEY  Geotagger Pro 2 manual  UI BULLETIN #53  1-ブロモプロパンによる労働災害防止について  TE-M80 - Support  Peavey PR 603 User's Manual  H-ft ft-a H-ft ft-ft ft-H ` H-ft ft-H H-ft ft-a H-ft ft-ft ft-H H-ft ft-ft  Classic A27 ISDN Mode d`emploi  golden embers gas fired masonry ovens installation and operating    Copyright © All rights reserved. 
   Failed to retrieve file