1. 9292202922 INCOMING POWER CONTROL RELAYS 8 fo t0 11 12 13 44 18 tel 17 18 tof 20 izle fr miese afe SENSORS P1 P2 TERMINAL BLOCKS PRIMEX 3 331 SV User Manual 8 Firmly tighten all fittings on control panel or junction box if required 9 In the control panel insert the appropriate overload modules in the motor starter These overload modules must be ordered separately The control panel will not operate without over load modules a Adjust the dials to match motor full load amps b Turn motor starter switch to the ON position CAUTION Resetting the motor starter with power applied may cause the pump to run unexpectedly OVERLOAD MODULE ORDERED SEPARATELY LUCAOSFU 1 25 5 0 FLA LUCA18FU 4 25 18 0 FLA LUCA32FU 18 0 32 0 FLA 10 Connect pump wires to terminal blocks as indicated on the provided electrical schematics NOTE Three phase motors will run in either direction Check for proper rotation of the pump prior to final instal lation To reverse the rotation swap pump cable connections on any two terminals T1 T2 T3 11 Connect incoming power 208 230 460 VAC 3 phase to the 3 position terminal block as indicated on the provided electrical schematics Verify that the appropriate voltage tap on the transformer primary matches the incoming voltage PRIMEX 33
2. AA User Manual THREE PHASE DUPLEX LUFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER I Lr NN DL Ashland OH 800 363 5842 WWW PRIMEXCONTROLS COM A WARNING ELECTRICAL SHOCK HAZARD Warranty void if panel is modified Disconnect all power sources before Call factory with servicing Failure to do so could result servicing questions in serious injury or death This control panel must be installed and serviced by a licensed electrician in accordance with the National Electric Code NFPA 70 state and local electrical codes All conduit running from the sump or tank to the control panel must be sealed with conduit sealant to pre vent moisture or gases from entering the panel NEMA 4X enclosures are for indoor or outdoor use primarily to provide a degree of protection against corrosion windblown dust and rain splashing water and hose directed water Cable connectors must be liquid tight in NEMA 4X enclosures Check the incoming power voltage amperage and phase to meet requirements of the pump motor being installed Always check the pump nameplate for electrical requirements SEAL FAIL LIGHTS RED ALARM LIGHT CUTOUT IN INNER DOOR TAEST N FOR MOTOR STARTER STATION VIEW CONTROLLER 20 H O A SWITHCES PRIMEX 2 331 SV User Manual INSTALLATION INSTRUCTIONS MOUNTING THE CONTROL PANEL Determine mounting location for panel If distance exceeds the length of either the level sensor
3. L3 a N in p O rv Oona lt ow N gO DD mO O t ui E u Oa N O I I N m Cc w Fo gt 0O 4A CN 5 lu 7 o 9 oO X c5 Ow uo NE lt Ia a LQ a gt Ta SOmo of FW Egz u re SR 7 Al gt gt Oot 1 o x LL Cc IT 8 a U Img Lu cS I ul lt In m oO u iuf L TRANSDUCER OPERATION IN AUTO MODE As the liquid level rises above the STOP set point the pumps will remain inactive As the level rises above the LEAD start set point the lead pump will start and remain ON until the level drops below the STOP level If the level con tinues to rise past the start LEAD and above the start LAG start set point the second pump will start and both pumps will remain ON until the level drops below the STOP set point BACK UP FLOAT IN AUTO MODE If the level drops below the back up LOW LEVEL float switch pumps will stop As the level rises above the LOW LEVEL Float the pumps will remain inactive until the the level rises above the LEAD start set point If the level rises above the back up HIGH LEVEL float switch both pumps will start and both pumps will remain ON until the level drops below the back up LOW LEVEL float switch ALARM LEVELS The alarm beacon and the horn will active on the following level conditions If the level rises above the back up HIGH LEVEL float switch If the level rises above the HIGH LEVEL set point transducer If the level drops below the back up LOW LEVEL float switch
4. PRIMEX 8 331 SV User Manual TRANSDUCER INSTALLATION SENSOR CABLES PUMP CABLES CONDUIT CONDUIT IN FLOW nm DISCHARGE BACK UP FLOAT HIGH LEVEL BACK UP FLOAT LOW LEVEL LEVEL TRANSDUCER WITH CABLE WEIGHT Typical transducer with float back up setup for a duplex lift station WARNING Keep sensors clear of pumps pipes and motor cables Ensure that floats cannot reach pump suction Do not run pump and float cables in the same conduit PRIMEX 9 331 SV User Manual ALARM OPERATION The alarm will activate and remain ON only if the alarm float is tipped to the ON close position ALARM SYSTEM HORN AND BEACON When an alarm condition occurs a red light and a horn will be activated If the silence push button is pressed the horn will be silenced When the alarm condition is cleared the alarm system is reset The alarm system can be tested by pressing the same push button HOA SWITCH A HAND OFF AUTO switch is provided for each pump In the HAND mode the pump will run regardless of the float switch It will stop only if manually stopped and or an overload trip or motor thermal cutoff condition has occurred In the OFF position the pumps will not RUN In the AUTO position the pumps will only run if the float switches are activated in the correct sequence MOTOR PROTECTIVE SWITCH MOTOR STARTER A motor protective switch is supplied for each pump to provide motor overload protection branch circuit pro
5. 1 SV User Manual CAUTION The transformer is wired from the factory for 460VAC If incoming power is 230VAC or 208VAC the wire connections to the transformer must be changed for proper operation Not doing so could result in damage VERIFY CORRECT OPERATION OF CONTROL PANEL AFTER INSTALLATION IS COMPLETE i Lal A A Al 2j E B BB E 208V 230V 460V H1 H2 H3 4 208 T 230 460 amp x2 115V xi I ii P FIGURE 2 Transformer INSTALLATION OF LEVEL SENSORS CAUTION If the level sensors are not mounted correctly the pump system will not function properly WARNING Turn off all power before installing level sensors in wet well Failure to do so could result in serious or fatal electrical shock 1 Use label kit to identify level sensors cables stop lead lag alarm etc See control panel schematic for level sensor connections 2 Determine your normal operating level 3 Mountlevel sensors at appropriate levels Be sure that floats have free range of motion without touching each other or other equipment in the basin 4 Ensure that the level transducers cannot reach the pump PRIMEX 5 331 SV User Manual OPERATIONS FLOAT FLOAT SWITCH CONNECTIONS lip ra CONTROL TERMINALS BEEEE EB EN FRSE Ld a I I I MEN I Pot pop l P Zi ey Eum dod d des F is M h D Pot ee A O52 OND lt bot 4 N 2 E A cao v xO a I tue Do zH uj Seya wa g
6. Disconnect all power sources before servicing Failure to do so could result in serious injury or death FLOAT CONTROLS Check the floats through their entire range of operation Clean adjust or replace damaged floats Checking the float resistance The float resistance can be measured to determine if the float is operating cor rectly or is defective Use the following procedure to measure the float resistance 1 Isolate the float by disconnecting one or both of the float leads from the float terminals 2 Place one ohmmeter lead on one of the float wires and the other ohmmeter lead on the other float wire 3 Place the ohmmeter dial to read ohms and place on the R X 1 scale With the float in the off position the scale should read infinity high resistance Replace the float if you do not get this reading With the float in the ON position the scale should read nearly zero very low resistance Replace the float if you do not get this reading NOTE Readings may vary depending on the length of wire and accuracy of the measuring device FUSES Check the continuity of the fuse Pull the fuse out of the fuse block With the ohmmeter on the R X 1 scale mea sure resistance A reading of infinity indicates a blown fuse and must be replaced Replace fuse with same type voltage and amp rating TRANSFORMER The 331 panel can be configured to operate at 208VAC 230VAC or 460VAC It is factory set for 460VAC opera tion Check the
7. available incoming supply voltage to the 331 control panel prior to installation Verify that the connections on the transformer are correct and will match the available incoming voltage Measure the voltage between terminals 27 and 28 with a voltmeter It must read 115VAC 15 for proper operation PUMPS AMPS DISPLAY If the pump amps do not display correctly check the following 1 Check that the jumper setting on the current transducer is correct 2 Current monitoring is enabled in the Station View Controller PRIMEX 11 331 SV User Manual a I 1 DD rmm NN C Ashland OH 800 363 5842 MUNICIPAL WATER CONTROL SOLUTIONS WWW PRIMEXCONTROLS COM PN 1038887B 2013 SJE Rhombus Rev 01 14 PRIMEX is a trademark of SJE Rhombus amp
8. cables or the pump power cables splicing will be required For outdoor or wet installation we recommend the use of a Nema 4X Junction box with liquid tight connectors to make required connections You must use conduit seal ant to prevent moisture or gases from entering the panel Do not mount the junction box in the wet well Determine conduit entrance locations on control panel Drill proper size holes for type of connectors being used NOTE If using conduit be sure that it is of adequate size to pull the pump and sensor cables through Attach cable connectors and or conduit connectors to control panel FOR INSTALLATION WITHOUT A SPLICE GO TO STEP 8 FOR INSTALLATION REQUIRING A SPLICE FOLLOW STEPS 6 7 Determine location for mounting junction box according to state and local code requirements Mount the junc tion box to proper support Run conduit to control panel or to junction box if required Drill proper size holes for the type of conduit used Use one conduit for float switch cables and a separate one for pump cables Do not run pump and float cables in the same conduits Identify and label each wire before pulling through conduit into control panel and junction box Make wire splice connections at junction box if necessary CONTROL TRANSFORMER CURRENT TRANSDUCER INTEGRATED MOTOR STARTER POWER SUPPLY EN 22228222 eooooooeooooo
9. t o aut gt n La o a 0 40 eh zu o ot O _ xO lt gt ol E gt I gt __ uz I s di gt di Es uU Il cc 2 I z U a LLI LL muse Y I T x JA C O lt LL Un The 331 panels are designed to operate with four floats for pump sequencing The standard float functions are common pump stop lead pump start lag pump start and alarm float FLOAT SWITCH OPERATION IN AUTO MODE As the liquid level rises above the STOP float the pumps will remain inactive As the level rises above the LEAD start float the lead pump will start and remain ON until the level drops below the STOP level If the level continues to rise past the start LEAD float and above the start LAG float the second pump will start and both pumps will remain ON until the level drops below the STOP float PRIMEX 6 331 SV User Manual FLOAT INSTALLATION FLOAT CABLES PUMP CABLES CONDUIT f CONDUIT IN FLOW DISCHARGE HIGH LEVEL LAG FLOAT START FLOAT STOP FLOAT Typical float setup for a duplex lift station WARNING Keep floats clear of pumps pipes and motor cables Ensure that floats cannot reac pump suction Do not run pump and float cables in the same conduit PRIMEX 7 331 SV User Manual OPERATIONS TRANSDUCER LEVEL TRANSDUCER CONNECTIONS tt Fa 7 CONTROL TERMINALS I x LI db p w tb d d 4 ay 4 d d ML LOEO gd dog dod Pod d abo Ya ME d BEN d al INH I
10. tec tion and a means to disconnect the pump The overload dial on the starter must be set to match the motor Full Load Amps FLA In the event of an overload trip the motor protective switch must be reset by first turning the selector handle counterclockwise to the OFF position and then turning the handle clockwise to the ON position DRY AUXILIARY CONTACTS Normally open Contacts are open under normal conditions and closed when alarm condition is present Au tomatically reset once alarm condition is cleared SEAL FAILURE CIRCUIT AND INDICATOR LIGHT The seal fail circuit is resistance sensitive and will sense the presence of water in the pump seal chamber When water is sensed the control circuit will illuminate the appropriate indicator light on the control panel If a seal fail occurs turn off the pump and consult the pump manufacture for proper repair or maintenance THERMAL CUTOUT The thermal cutout is wired in series with the magnetic contactor coil If the pump s thermal switch opens on high temperature the contactor will turn off and stop the pump When the thermal switch cools and closes the magnetic contactor will turn on if the pump is called to run If the pumps are not supplied with a thermal sensor jumper wires must be placed on the terminal block from I1 to l2 and I5 to l6 Not doing so will result in the pumps not operating PRIMEX 10 331 SV User Manual TROUBLESHOOTING A WARNING ELECTRICAL SHOCK HAZARD