Home

APS: Modbus Protocol User Guide

image

Contents

1. Security Settings Select 7 to configure the Device Server s security setting parameters 7 Security Settings SNMP a aa Rte due Enabled Modbus Protocol User Guide 17 3 Configuring Modbus SNMP Community Name public Telnet Setup i e s gv Enabled Download ess sus ass Enabled PORC MEME ace ame esse Enabled Web Server use end se Enabled Web Setup sss netenka see Enabled Enhanced Password Disabled Port AIO asser Seca Enabled CAUTION Disabling both Telnet Setup and Port 77FE will prevent users from accessing the setup menu from the network Below are the security features supported in Modbus IAP SNMP We can enable or disable SNMP By default it is enabled Disable SNMP N SNMP community The SNMP Community Name is a required field for NMS to read or write to a device Enter a string of 1 to 13 characters SNMP Community Name public __ The default entry is public The current value is displayed in parentheses Telnet Setup This setting defaults to the N No option The Y Yes option disables access to Setup Mode by Telnet port 9999 It only allows access locally using the web pages and the serial port of the unit Disable Telnet Setup N Note If you choose to disable this option keep in mind that disabling Telnet Setup will prevent users from accessing the setup
2. 00050msec 05000msec 7 Security Settings SNMP L4 x3 en ranger trees Enabled SNMP Community Name public Telnet Setup assume xum Enabled TETP Download i s Enabled Port TIPER laxe es es xe Enabled Web SERVER Enabled Enhanced Password Disabled D efault settings S ave Q uit without save Select Command or parameter set 1 7 to change Modbus Protocol User Guide 27 9 Factory Defaults with Reset Pin Default Pin xPico Factory Defaults To restore the factory default configuration of the device server press the reset pin and then press the default pin for 3 to 5 seconds Device server will load the factory default configuration and reboot again xDirect Factory Defaults To restore the factory default configuration press and hold the reset pin for more than 10 seconds After 10 seconds release the reset pin The device server will load the factory default configuration If the user presses the reset button for 0 2 seconds then the unit simply reboots Note With factory default configuration IP address Gateway and Netmask are set to 0 0 0 0 Micro125 Factory Defaults To restore the factory default configuration of the device server press the reset pin for 3 to 5 seconds Device server will load the factory default configuration and reboot again Modbus Protocol User Guide 28 10 Troubleshooting and Technical Support Using the IAP Device Server firmware i
3. hit space to toggle RS485 2 Wire Select Invert active low Y After all the configurable pins have been assigned the standard modem control settings can be entered if applicable DTR Mode 1 Fixed 2 Variable 1 RTS CTS Mode 1 Fixed 2 Variable 1 The setting for each configurable pin is displayed in the setup menu Modbus TCP to RTU Bridge Setup 1 Network IP Settings IP AddEGSSS scm ses 0 0 0 0 DHCP BOOTP AutoIP Default Gateway not set NeUtmask xe err ERR ens not set 2 Serial amp Mode Settings Protocol 444848 Modbus RTU Slave s attached Serial Interface 9600 8 N 1 RS232 CH1 3 Modem Configurable Pin Settings CP1 GPIO In CP2 GPIO Out CP3 DCD IN Channel 1 CP4 DTR Out Channel 1 CP5 Channel 1 Status LED CP6 Channel 2 Status LED CP7 RS485 Select CP8 RS485 2 Wire Selec DIR OUtDUE Sadek eee Fixed High Active RES OU DULG sise Fixed High Active 4 Advanced Modbus Protocol settings Slave Addr Unit Id Source Modbus TCP header Modbus Serial Broadcasts Disabled Id 0 auto mapped to 1 MB TCP Exception Codes Yes return 00AH and OOBH Char Message Timeout 00050msec 05000msec 7 Security Settings SNMP Soe stele RR siens 8 Enabled SNMP Community Name public Telnet Setup see ws Enabled TETP Download s Res Enabled P
4. The options are as follows CP1 Function 1 Unused 2 Status LED Output 3 RTS Output 4 RS485 Output Enable The Status LED Output function for CP1 is an active low output for controlling the device server s Status LED LED1 in the XPort Integration Guide Selecting RTS Output for CP1 prompts for additional options related to controlling a Request to Send RTS signal and performing flow control see Modem Control Settings on page 13 Select Wait for CTS from these options to auto configure CP3 for CTS Input Use the RS485 Output Enable function to control an external RS485 line driver when in RS485 2 wire mode This output is configurable for active high default or active low CP2 Function 1 Unused 2 DTR Output 3 RS485 Output Enable Select DTR Output for CP2 prompts for additional options for controlling a Data Terminal Ready DTR signal see Modem Control Settings on page 13 RS485 Output Enable function controls an external RS485 line driver when in RS485 2 wire mode This output is configurable for active high default or active low Function 1 2Unused 2 Diagnostic LED Output 3 CTS Input The Diagnostic LED Output function for CP3 is an active low output for controlling the device server s Diagnostic LED LED3 in the XPort Integration Guide Select Y es on the Wait for CTS option under the CP1 function menu for RTS Output to automatically select the CTS Input function
5. Unit ID is 0 Note In the current software version for IAP Device Server a true Modbus broadcast is only supported when a serial slave device is attached A Modbus broadcast from a serial master device is discarded regardless of this parameter setting Use MB TCP 0x0B 0x0A Exception Responses 1 No 2 Yes Traditional serial Modbus uses silence to signal some errors While this works well with direct serial lines it causes serious problems on a TCP IP wide area network where delays are not so predictable See 2 Modbus for more information Setting this parameter to 1 No causes the IAP Device Server to behave like a traditional Modbus serial slave it answers timeouts unconfigured slave addresses and CRC errors with silence Setting this to 2 Yes causes the IAP Device Server to return 1 of 2 new exception codes defined in Modbus TCP Consider exception hex 0A PATH UNAVAILABLE a hard error where a retry is not likely to succeed It is returned Modbus Protocol User Guide 14 3 Configuring Modbus lfslave attached currently never However future firmware may allow the user to define the range of valid slave addresses If master attached if a Modbus request has a slave address that is not configured in the Unit ID to IP mapping table If master attached if the TCP socket failed to open This is really a soft hard error as the reason the TCP socket failed to open may be transient or a hard configu
6. GPIO You may want to disable this capability for security purposes The default setting is the N No option which enables GPIO control The Y Yes option disables the GPIO control interface Disable Port 77F0h Note XPress DH xDirect UDS1100 and Micro125 will not support this security feature Default Security Settings All the security features are enabled by default except the Enhanced Password feature Table 3 1 Default Security Settings Disable SNMP No SNMP community name public Disable Telnet setup No Disable TFTP Firmware Update No Disable Port 77FEh No Disable Web Server No Enable Enhanced Password No Disable Port 77F0h No Modbus Protocol User Guide 19 Monitor Mode and Firmware UpgradeThe easiest way to upgrade your protocol firmware or reflash is to use our Devicelnstaller utility Devicelnstaller is a free utility program provided by Lantronix that discovers configures upgrades and manages Lantronix Device Servers It can be downloaded from the Lantronix website at www lantronix com support downloads For instructions on using Devicelnstaller to configure the IP address and related settings or for more advanced features see the Devicelnstaller Online Help The User Guide for the Device Server explains two other ways to reflash You can do it serially with HyperTerminal or directly by Ethernet with a Trivial File Transfer Protocol or TFTP Client The T
7. Monitor Mode and Firmware 20 5 WiPort and WiBox Implementation 21 6 XPort Implementation 24 7 xPico Implementation 25 8 Micro125 Implementation 27 9 Factory Defaults with Reset Pin Default Pin 28 Modbus Protocol User Guide 4 xPico Factory Defaults Table of Contents 28 xDirect Factory Defaults 28 Micro125 Factory Defaults 28 10 Troubleshooting and Technical Support How fast can poll 29 29 cannot get a slave response 30 Only Slave ID 1 can be polled 31 Every 2 poll seems to fail 31 Technical Support 33 Figures Tables Figure 2 1 Extended Modbus System Example Figure 3 1 Setup Configuration Mode Screen 11 Figure 3 2 Unit ID to IP Address Lookup Table 16 Figure 3 3 Unit ID to Address Lookup Table Example 16 Table 3 1 Default Security Settings 19 Table 9 1 Baud Rate 29 Modbus Protocol User Guide 1 Introduction This protocol manual is for use with Lantronix Industrial Automation Protocol IAP Device Servers such as the XPress DR IAP UDS1100 IAP and xDirect IAP In addition to our IAP Device Servers the Modbus protocol is supported on various embedded products including versions of the XPort WiPort xPico and Micro Micro125 The default protocol in new IAP Device Servers is the Standard Tunneling protocol a serial protocol used to connect thousands of intelligent devices to the Ethernet The user g
8. Serial amp Mode Settings menu option Note Channel 1 on WiBox only supports RS 232 while Channel 2 supports RS 232 and RS 422 RS 485 2 4 wire modes Use serial connector 1 2CH1 2 CH2 1 The menu option for Modem Control Settings is replaced with Modem Configurable Pin Settings on the WiPort The options are CPO Function hit space to toggl GPIO In CPO Function hit space to toggl GPIO Out CPO Function hit space to toggl DTR Out CPO Function hit space to toggl Diag LED Status LED G Status LED Y RS485 Select RS485 2 Wire RS485 4 Wire Defaults In CPO Function CPO Function CPO Function CPO Function CPO Function CPO Function hit space to toggl hit space to toggl hit space to toggl hit space to toggl hit space to toggl hit space to toggl 0000000000 The assignment for each configurable pin is set by cycling through the menu options by entering a space or any key other than Enter GPIO assigns the pin as a general purpose input or output The GPIOs can be written and read via Modbus TCP when in slave attached mode is the Modem Control Output signal for Data Terminal Ready Diag LED Status LED G and Status LED Y are the outputs for diagnostic LED red green status LED and the yellow status LED RS485 Select is an output made active when configuring the serial channel for RS422 485 operat
9. Transmitting 0 1275 ms 5 ms increments Only asked if RTS CTS mode is variable After the IAP Device Server completes transmission it delays from 0 to 1275 msec before dropping the RTS CTS output Advanced Modbus Protocol Settings Changing these parameters takes a bit of thought and planning Slave Address 0 for auto or 1 255 fixed otherwise Modbus TCP includes a Unit ID field which is used to address multiple Modbus slaves at a single IP address Unfortunately some first generation software drivers assumed a single slave at each IP and always set the Unit ID field to 0 This causes the IAP Device Server problems because it requires the Unit ID for the Modbus RTU Slave Address To support these older applications the IAP Device Server allows you to force a fixed address for Modbus RTU and Modbus ASCII but note that this restricts you to a single serial slave device per IAP Device Server Setting this value to 0 causes the IAP Device Server to use the Modbus TCP Unit ID as received Setting it to any other address causes the IAP Device Server to always use the set value as a fixed address Allow Modbus Broadcasts 1 Yes 2 No This relates to the previous issue The default is 2 No in which case the IAP Device Server always assumes a Modbus TCP Unit ID of 0 really means Modbus slave address 1 Answering No here is like setting a fixed address of 1 parameter above except the fixed address is only used if the Modbus TCP
10. a pure MB TCP to MB TCP network would suffer from this problem if the poll cycle approached the average response time Any Modbus TCP network going through WAN will discover this Ideally all Modbus TCP master applications must implement the sequence number and gracefully handle receipt of stale responses with unexpected sequence numbers Unfortunately the Modbus TCP specification says that this sequence number is optional and can be used by a master to match responses to requests however it can usually be just left as zero The Modbus TCP slave just echoes this back in the response So most Modbus TCP OPC servers today do not implement the sequence number Fortunately a second generation of Modbus TCP masters is starting to come that understands the issues of dealing with an IAP Device Server to serial So what is your solution if your Modbus TCP master is first generation Slow down your poll rate You have to consider the worst case response time assume all polls timeout If you have five slaves that normally answer in less than 100 msec each but you must use a 250 msec message timeout then polling each of the five 1 25 sec is the only promised safe rate f you are only polling a single slave or poll one slave at a time then you can try the Disable Pipeline option in the IAP Device Server firmware This will either help or make Modbus Protocol User Guide 32 10 Troubleshooting and Technical Support things hopelessly w
11. as it looks in the receive buffer yet this is stale Response B received before poll C was even issued If the master does not implement Modbus TCP sequence numbers then it accepts the response B as satisfying poll C Imagine if the master is putting out 300 polls per minute 5 polls per second but the IAP Device Server can only process on average 290 of those per minute and some carry over After 10 minutes you may have up to 100 stale responses waiting in your master s TCP buffer This makes it appear as though there is now a 20 second lag in data reaching the master Here is the source of your data taking longer and longer to propagate to Master Client problem However if the master does implement Modbus TCP sequence numbers then the stale responses are rejected If the master is smart enough to resynchronize itself Response B does not kill poll C but master waits more then this resynchronization will manifest itself as the slaves going off line and back on line intermittently If the master is not smart enough to resynchronize once this out of sync behavior occurs your slaves go permanently off line As you can see this Modbus TCP master is out of sync and the only cure may be to either restart the master or power cycle the IAP Device Server Both actions close the socket and purge the backlogged messages Our Network to Serial product brings out this shortcoming in master client Modbus TCP designs but even
12. firmware only expects Modbus TCP from the network Some applications just pack Modbus RTU raw in TCP this is not supported Your slave is set for 2 stop bits and your UDS 10 IAP does not support 2 stop bits Moabus Protocol User Guide 30 10 Troubleshooting and Technical Support Only Slave ID 1 can be polled Your application is setting the Modbus TCP Unit ID field to 0 This causes the IAP Device Server firmware to automatically map this to 1 Every 2 poll seems to fail Most likely you are using RS485 but regardless your device probably cannot accept a new poll as fast as the IAP Device Server firmware is sending it TCP IP is a full duplex channel and since you can have up to 8 active sockets it is very easy to have a new request already waiting as your last response is being returned The only solution to this is to slow down your Modbus TCP masters so they never poll before the last response has been seen This manually creates the time delay between polls your device expects My IAP Device Server runs fine for about 10 minutes and then my applications start reporting slaves going off line My IAP Device Server runs fine until a slave goes off line then tend to lose all the slaves or they all poll only intermittently Sometimes my IAP Device Server returns the wrong data from the wrong slave After a while the IAP Device Server seems to take longer and longer to answer after a few hours it ta
13. for Modbus Protocol User Guide 24 7 xPico Implementation The Modbus master slave functionality of xPico is similar to the Modbus implementation on other platforms such as the UDS1100 or XPress DR The difference is the configurable pins on the xPico CP1 CP8 The xPico has 2 serial ports Choose the serial port hence the firmware uses for sending and receiving Modbus RTU or Modbus ASCII serial data under the Serial amp Mode Settings menu option Note Channel 1 on xPico supports RS 232 and RS 422 RS 485 2 4 wire modes while Channel 2 only supports RS 232 Use serial connector 1 2CH1 2 CH2 1 The menu option for Modem Control Settings has been replaced with Modem Configurable Pin Settings on the xPico CP1 Function hit space to toggle GPIO In CP2 Function hit space to toggle GPIO Out CP3 Function hit space to toggle DCD IN Channel 1 CP4 Function hit space to toggle DTR Out Channel 1 CP5 Function hit space to toggle Channel 1 Status LED CP6 Function hit space to toggle Channel 2 Status LED CP7 Function hit space to toggle RS485 Select CP8 Function hit space to toggle RS485 2 Wire Select The assignment for each configurable pin is set by cycling through the menu options by entering a space or any key other than Enter GPIO assigns the pin as a general purpose input or output The GPIOs can be written and read via Modbus TCP when in slave attached
14. mode is the Modem Control Output signal for Data Terminal Ready DCD is the Modem Control input MCI signal for Data set Ready Channel 1 and Channel 2 status LED show the activity of Modbus packet transactions happening in the device server RS485 Select is an output made active when configuring the serial channel for RS422 485 operation RTS is the out pin for channel 2 for hardware flow control CTS is the input for channel 2 for hardware flow control After assigning the applicable function by pressing Enter you are then asked if the pin is inverted active low Moabus Protocol User Guide 25 7 xPico Implementation CP1 Function hit space to toggle GPIO In Invert active low Y A function should be assigned to each configurable pin GPIO Input should be the default for all unused or unassigned pins CP1 Function hit space to toggle GPIO In Invert active low 2 i Function hit space to toggle GPIO Out Invert active low 2 mud v nstion hit space to toggle DCD IN Channel 1 Invert active low 2 bi Function hit space to toggle DTR Out Channel 1 Invert active low 9 bun Function hit space to toggle Channel 1 Status LED Invert active low 2 a Function hit space to toggle Channel 2 Status LED Invert active low 2 a Hot hit space to toggle RS485 Select Invert active low 9 a
15. space to toggle GPIO Out Invert active low N After all the configurable pins have been assigned the standard modem control settings can be entered if applicable RTS CTS Mode 1 Fixed 2 Variable 1 The setting for each configurable pin is displayed in the setup menu Modbus TCP to RTU Bridge Setup 1 Network IP Settings Network mode Wired Only IP Address iens gens 0 0 0 0 DHCP BOOTP AutoIP Default Gateway not set Netmask 24899 eed RR not set 2 Serial amp Mode Settings Protocol Lis es Fax Modbus RTU Slave s attached Serial Interface 9600 8 N 1 RS232 CH1 3 Modem Configurable Pin Settings CP0 RS485 Select CP1 RS485 2 Wire CP2 GPIO In CP3 GPIO In CP4 GPIO In CP5 Diag LED CP6 Status LED G CP7 Status LED Y CP8 GPIO In CP9 GPIO In CP10 GPIO Out RTS OUDDUEP Lies Fixed High Active 4 Advanced Modbus Protocol settings Slave Addr Unit Id Source fixed to 136 Modbus Serial Broadcasts Disabled Id 0 auto mapped to 1 MB TCP Exception Codes Yes return 00AH and OOBH Char Message Timeout 00050msec 05000msec 6 WLAN Settings WEAN e mee Disabled network MSYS TOPOLOGY a dud ad ae Ore US UAR RA Infrastructure Country US SeCUEr2Uy esti y dre c ry HE os Authentication PSK Encryption TKIP IX Data alzare ss 54 Mbps auto fallback Power management Disabled Soft A
16. FTP method takes just a few seconds much faster than the 5 plus minutes required serially With all protocol firmware use the TFTP destination filename of ROM in caps There are important differences between the industrial protocol firmware files and the standard Lantronix firmware files Although the hardware may be the same you will not be able to download a standard Lantronix firmware such as the standard or the older Modbus versions 1 0 1 1 or 1 2 These firmware files are rejected with the error Sorry that firmware not supported And although you can download any industrial firmware to Lantronix Device Servers they will not function When started an industrial firmware on the wrong hardware will blink the red LED and you will see the error message Sorry this firmware is not supported from the serial port The industrial firmware also has blocked the SF command within the Monitor Modbus Protocol User Guide 20 5 WiPort and WiBox Implementation The Modbus master slave functionality on the WiPort and WiBox is similar to the Modbus implementation on other platforms such as the UDS1100 or XPress DR The difference is the configurable pins on the WiPort CPO CP10 and the WiFi settings on the WiPort and WiBox are configurable from the Setup Menu The WiPort and WiBox have 2 serial ports Choose the serial port the firmware uses for sending and receiving Modbus RTU or Modbus ASCII serial data under the
17. LANT ONIX Modbus Protocol User Guide Part Number 900 271 Revision June 2013 Copyright and Trademark 2013 Lantronix Inc All rights reserved No part of the contents of this book may be transmitted or reproduced in any form or by any means without the written permission of Lantronix Lantronix8 WiBox and WiPort are registered trademarks of Lantronix Inc xPico and xDirect are trademarks of Lantronix Inc Windows and Internet Explorer are registered trademarks of Microsoft Corporation Mozilla and Firefox are registered trademarks of the Mozilla Foundation Chrome is a trademark of Google Inc All other trademarks and trade names are the property of their respective holders Contacts Lantronix Corporate Headquarters 167 Technology Irvine CA 92618 USA Toll Free 800 526 8766 Phone 949 453 3990 Fax 949 450 3995 Technical Support Online www lantronix com support Sales Offices For a current list of our domestic and international sales offices go to the Lantronix web site at www lantronix com about contact Disclaimer The information in this guide may change without notice The manufacturer assumes no responsibility for any errors that may appear in this guide Revision History June 2001 A B Preliminary Release 6 01 Reformat Added notes PN August 2004 ID Reformat Added two advanced settings Added content for WiPort and WiBox September 2005 Added content fo
18. P Roaming are vice see 9 Disabled WLAN Max failed packets 6 7 Security Settings SNME e wea pie oi Enabled SNMP Community Name public Telnet Setup 4 99 ge Enabled TETE Download sise ssh Enabled Port TIEBED ane Shan se Enabled Web S EVe recekan ert ses Enabled Web Setup cedex Yers Enabled Enhanced Password Disabled Port 7T7E0BR eee RR xe Enabled The menu option for WLAN Settings has been added to configure the WiFi parameters of the WiPort WiBox Modbus Protocol User Guide 22 5 WiPort and WiBox Implementation Two new parameters were added under the menu option Advanced Modbus Protocol Settings on WiPort The Modbus slave address and starting offset parameters are used to direct Read Coil Status Read Input Status Force Single Coil and Force Multiple Coils Modbus commands to the WiPort s GPIO Other commands or unmatched addressing are directed to the serial port Local slave address for GPIO 0 to disable or 1 255 0 3 Starting offset 0x 1x0001 9999 1 100 Modbus Protocol User Guide 23 XPort Implementation The Modbus Master Slave functionality on the XPort is similar to the Modbus implementation on other platforms such as the UDS1100 or XPress DR A notable difference is the configurable pins on the XPort CP1 3 are configurable from the setup menu The menu option for Modem Control Settings has been replaced with Modem Configurable Pin Settings on the XPort
19. TCP IP network requires 32 bit IP addresses the IAP Device Server uses this table to map an 8 bit address into an IP Unit ID combination The 8 bit address is used to select the desired IP and as the Unit ID sent The table holds 8 entries and any Modbus slave address not found in the table returns an exception response to the master if enabled The example below is of adding an entry Select 5 to edit view settings Figure 3 3 Unit ID to Address Lookup Table Example Close Idle TCP sockets after 1 60 sec O leave open 00010 Redundant entry retries after 15 60 sec O disable feature 00000 Set 4th octet to 0 to use Slave Address as part of IP Jess 001 100 192 168 000 000 SLV 2 101 199 192 168 000 150 A dd D elete E xit select function A Modbus addr from 102 Modbus addr to 102 255 Modbus Protocol User Guide 16 3 Configuring Modbus Slave IP address 192 172 168 16 000 123 000 sl 001 100 192 168 000 000 SLV 2 101 199 192 168 000 050 3 200 255 172 016 123 000 SLV A dd D elete E xit select function Close Idle TCP sockets after 3 60 sec 0 leave open Unlike earlier versions of the Lantronix Modbus firmware that tried to hold 8 sockets open forever this version only holds sockets open as required Entering a 0 holds a single socket open to the last remote Modbus TCP slave accessed Otherwise enter values 3 to 60 to automatically close the last soc
20. annot work with a direct RS232 cable as each end only asserts its RTS control signal to power up intermediate transmitters The XPress DR IAP has a DTE style RS232 port so RTS is an output and CTS is an input The UDS 10 IAP and CoBox FL IAP have a DCE style RS232 port so RTS is an input and CTS is an output Delay after Output of RTS 0 1275 ms 5ms increments Only asked if RTS CTS mode is variable After the IAP Device Server asserts the RTS CTS signal it delays from 0 to 1275 ms before continuing Normally this is set to 0 Only set a value here if your device modem or cable is non standard Wait for CTS to Go Active N Y Only asked if RTS CTS mode is variable Answering N causes the IAP Device Server to ignore the RTS CTS response from the modem Answering Y causes the IAP Device Server to wait for the RTS CTS response from the modem Do not answer Y unless you know that the cable is wired properly to support this signal Moabus Protocol User Guide 13 3 Configuring Modbus Delay after CTS Going Active 0 1275 ms 5ms increments Only asked if RTS CTS mode is variable and set to wait for CTS to go active After the IAP Device Server sees the modem assert an RTS CTS response input it delays from 0 to 1275 msec before transmitting If the IAP Device Server waits without seeing a valid response from the modem it will return the Modbus exception response 0x0B hex to the Modbus TCP requesting master Delay Dropping RTS after
21. assword The Telnet configuration password can be set to disable unauthorized access to the setup menu via a Telnet connection to port 9999 To access the setup menu through the serial port you do not need to enter the password Serial and Mode Settings Select 2 to change the basic serial parameters The following values can be set or changed Attached Device 1 Slave 2 Master As mentioned in the introduction Modbus RTU devices are defined as either slave or master devices Type 1 if the attached device is a slave such as controller or PLC or 2 if the attached device is a master such as a computer running graphical human machine interface HMI software Serial Protocol 12Modbus RTU 2 Modbus ASCII Serial Modbus comes in two forms Modbus RTU uses 8 bit data bytes to send binary information However some devices cannot handle 8 bit data bytes so Modbus ASCII is used Modbus ASCII is a slower protocol where each 8 bit data byte is converted to 2 ASCII characters Since the IAP Device Server converts both to and from Modbus TCP fully you can mix any combination of RTU and ASCII devices on a Modbus TCP network So a Modbus RTU Modbus Protocol User Guide 12 3 Configuring Modbus master attached to one IAP Device Server can remotely access a Modbus ASCII slave attached to another IAP Device Server Interface Type 1 RS232 2 RS422 RS485 4 wire 3 RS485 2 wire This allows the IAP Device Server to deal with the software relat
22. ces with four Modbus TCP devices Extended Modbus System Example Figure 2 1 Extended Modbus System Example Modbus TCP over Ethernet Token Ring Routers WAN etc CoBox CoBox Modbus E Modbus Modbus RTU or Modbus ASCII CoBox Modbus Figure 2 1 Extended Modbus System Example Figure 2 1 Extended Modbus System Example shows four specific styles of Modbus operations Modbus RTU devices are traditionally split into two groups CoBox Modbus refers to an IAP Device Server Modbus slave devices generally are the workhorse devices They perform their tasks 24 hours a day 365 days a year for example tasks such as flow metering temperature control batch loading or even running entire automated assembly lines The slave devices are not called slaves because they work all the time they are called slaves because as far as the data communications is concerned they function as passive servers Modbus slave devices passively sit and wait for a remote Modbus master device to ask them to report existing data values Read or accept new data values Write Moabus Protocol User Guide 7 2 Modbus Modbus master devices generally are higher level computers devices in which data and software are very important The most common examples of Modbus master devices are the Human Machine Interface HMI computers which allow human operators to monitor adjust and maintain the operations of the field dev
23. data This feature is useful for Modicon I O scanners Unit ID to IP Address Lookup Table Figure 3 2 Unit ID to IP Address Lookup Table These parameters only apply when Modbus Master is selected for the Serial Protocol The new menu appears like this Network IP Settings IP Address ado wy desc we L92 168 100 77 Default Gateway not set Netmask s e ox ox 0 a not set 2 Serial amp Mode Settings Protocol Modbus RTU Master s attached Serial Interface 9600 8 N 1 RS232 3 Modem Control Settings RES Output d e k amp 099 Fixed High Active 4 Advanced Modbus Protocol settings MB TCP Exception Codes Yes return Ox0A and 0xO0B Char Message Timeout 00050msec 05000msec 5 Unit ID IP Address Table Close Idle Sockets 10sec Redundant Entry Retry Feature Disabled 7 Security Settings SNMP 4o ww de 9 ce Enabl d SNMP Community Name public Telnet Setup Enabled TFTP Download Enabled Port TTEER 2 x Enabled Web Server Enabled Web Setup e s Enabled Enhanced Password Disabled Port 77FOh Enabled D efault settings S ave Q uit without save Select Command or parameter set 1 7 to change Since serial Modbus uses 8 bit slave addresses and a
24. e D appear on the Modbus TCP network as a full Modbus TCP slave device All Modbus TCP enabled devices A B E and F can actively share access to slave device D A limitation in traditional Modbus RTU implementation expects devices to be dedicated as either master or slave devices so device D can only act as a Modbus slave Devices G and are different from device D They share a single RS485 multi drop line that strictly limits them to act as slaves to a single Modbus RTU master However a little of the new Modbus TCP and IAP Device Server magic still applies all Modbus TCP enabled devices A B E and F can actively share access to both slave devices G and H IAP Device Server manages and coordinates the shared access In fact the IAP Device Server allows up to eight concurrent Modbus masters to share access to the slaves Modbus RTU Serial Master Talking to Modbus TCP Slave Device C is a traditional Modbus RTU master device Yet the IAP Device Server makes device C appear to the TCP IP network as a Modbus TCP master plus all of the Modbus TCP slaves on the TCP IP network A B D E F G and H appear as traditional Modbus RTU slave devices The only limitation is the traditional Modbus RTU assumption that device C is dedicated as a master only Therefore Modbus TCP master devices A B E and F cannot treat device C as a Modbus TCP slave Modbus RTU Serial Master Talking to Modbus RTU Serial Slave Finally master device C ca
25. econds Table 9 1 Baud Rate 900 ao 3999953 asssssss 8533 333333 600 feo 1 666667 16666067 4266 666667 2133 333333 2400 240 0416667 41666867 1066 666667 4800 ago 0208399 2083939 533 333333 9600 990 1041667 266 666667 o 30 240 480 1920 1 3 333333 66 666667 44 444444 22 222222 The overall time it takes to poll is the combined sum of these delays a Delay for master client to recognize need for poll Modbus Protocol User Guide 29 10 Troubleshooting and Technical Support Delay to issue and get the poll onto the Ethernet Delay for the poll to cross Ethernet and arrive error free at the IAP Device Server device may include retries and contention Delay for IAP Device Server to process and queue Modbus RTU poll Delay for the serial link to be free remember other master clients may be actively polling Physical delay to shift poll bit by bit across the serial link Delay in the device to recognize process and start reply Physical delay to shift response bit by bit across the serial link Delay for IAP Device Server to process and queue Modbus TCP response Delay for the response to cross Ethernet and arrive error free at the master client may include retries and contention Delay for master client to recognize need for poll Delays a and k are defined by your OPC or DDE driver For example a driver that runs only once each 55 msec us
26. ed details of using RS232 RS422 and RS485 With the XPress DR IAP you still must set the external red RS232 RS485 switch appropriately With the UDS 10 IAP or CoBox FL IAP you must still select the correct pins for RS232 or the shared RS422 485 pins Enter Serial Parameters B D P S Enter the baud rate 300 600 1200 2400 4800 9600 19 200 or 38 400 data bits 7 8 parity N O E and stop bits 1 2 in the classic DOS Mode Command style Examples are 9600 8 E 1 or 1200 7 O 2 These settings must match the settings on the attached Modbus device These settings are valid with the XPress DR IAP only The UDS 10 IAP and CoBox FL IAP also support baud rates 57 600 and 115 200 The UDS 10 IAP supports only 1 stop bit If you try to set an unsupported combination of settings a warning displays Note Regardless of these settings IAP Device Server configuration is always done on CH1 with RS232 and a setting of 9600 8 N 1 Modem Control Settings When using RS232 the IAP Device Server has a number of user definable Modem Control parameters to manage RTS CTS handshaking for half duplex radio modems RTS CTS Mode 1 Fixed 2 Variable Answer 1 and the IAP Device Server output is fixed to high Answer 2 to enable modem handshaking The RTS CTS output is active when the device server is transmitting on the serial port This setting is very different from the hardware or RTS CTS flow control used with printers This mode c
27. ettings Slave Addr Unit Id Soutce Modbus TCP header Modbus Serial Broadcasts Disabled Id 0 auto mapped to 1 odbus TCP pipeline Enabled new MB TCP requests queued in FIFO B TCP Exception Codes Yes return 0x0A and OxO0B Char Message Timeout 00050msec 05000msec 7 Security Settings SNMP s s s 99 a we BDabled SNMP Community Name public Telnet Setup Enabled TFTP Download a a Enabled Port 13 e gt s es Enabled Web Server Enabled Web Setup s s Enabled Enhanced Password Disabled Port 77FOh Enabled D efault settings S ave Q uit without save Select Command or parameter set 1 7 to change Basic Commands D S Q Figure 3 1 Setup Configuration Mode Screen shows the main IAP Device Server configuration menu The IAP Device Server offers three basic options Default Settings D Entering D resets all parameters to the factory default as shown above Only the IP address does not change Although not required selecting this option immediately after reloading the firmware and saving it ensures that the unit resets Save S Entering S saves the currently displayed parameter settings into non volatile memory and exits configuration mode This option triggers a reset Quit Without Saving Q Entering Q cancels any parameter changes you have made and
28. exits configuration mode This option triggers a reset Moabus Protocol User Guide 11 3 Configuring Modbus Network IP Settings Select 1 to configure the Device Server s network parameters The following values can be set or changed To understand and select the appropriate values consult one of the many TCP IP books available today and your network administrator IP Address The IP address must be set to a unique value on your network If you are not familiar with IP addressing on your network please consult your network administrator Please refer to the IAP User Guide for your Device Server for more details about IP addresses If the IAP Device Server is set to an address already in use it displays an error code with the LEDs and will not operate properly If you plan to use DHCP set the IP to 0 0 0 0 to activate DHCP Set Gateway IP Address Y N Most users could select N for this case You only need to choose Y if the IAP Device Server must communicate to remote TCP IP networks through a router or gateway If you select Y you must also enter the IP address of the default gateway within your local network Set Netmask N for default Most users could select N which causes the IAP Device Server to automatically use the standard netmask appropriate for the IP address entered Users who want a non standard netmask need to enter the new subnet mask in the traditional form for example 255 255 248 000 Telnet Configuration P
29. ices Modbus master devices are clients that actively go out and read from and or write to remote Modbus slave devices to monitor or adjust slave behavior Modbus TCP Master Talking to Modbus TCP Slave Devices A B E and F are all new Modbus TCP devices which are improved over Modbus RTU see more about Modbus RTU limitations below All four devices can function concurrently as both Modbus master and Modbus slave Both computers A and B can treat controller E as a slave polling data in real time Yet controller E can also act as a master and poll data from controller F which can in turn also act as a master to write alarm data directly up to computers A and B to alert the operators to the alarm condition Traditional Modbus RTU requires slave devices even with life threatening alarm conditions to sit patiently and wait for a remote master to poll the specific data that caused the alarm condition It is revolutionary for such a simple and flexible protocol as Modbus to offer such functionality Therefore Modbus TCP offers exciting new design options for industrial users which the Lantronix IAP Device Servers extend to traditional Modbus RTU serial devices Modbus TCP Master Talking to Modbus RTU Serial Slave Devices D G and H are traditional Modbus RTU slave devices Device D uses a point to point electrical interface like RS232 This allows only a single Modbus RTU master to talk to device D However the IAP Device Server makes devic
30. ime out but complex devices have various interrupts that can cause 5 to 10 character pauses during transmission A safe value for general use with Modbus is 50 msec Note Setting this value lower than 50 msec will not improve performance and may even make performance worse The IAP Device Server uses an intelligent length predicting algorithm to detect end of message in Modbus RTU This character timeout is only used with user defined or non standard Modbus functions Message Timeout 200 65000 msec This sets the timeout for a response from a connected slave both serially and by TCP IP Serial TX delay after RX 0 1275 msec 0 This feature inserts a delay between the Modbus TCP master requests The first request is sent out of the serial port of the IAP Device Server to the Modbus slave When the slave s response enters the serial port of the IAP Device Server it triggers this timer After the specified delay is reached the next master request is allowed to pass through the serial port of the IAP Device Server and the timer is reset This feature is particularly useful when using RS485 2 wired serial protocol The delay gives ample time for the RS485 slave devices to turn their transmitters off and their receivers back on Moabus Protocol User Guide 15 3 Configuring Modbus Swap 4x 0x to get 3x x 1y This setting allows the MBF to convert input resistor data to holding resistor data It also converts coil and contact
31. ing the old DOS timer slice can have a variable delay here of between 0 to 110 msec Delays c and i are defined by the complexity and load of your TCP IP network For example if you are going through radio or satellite links these delays routinely amount to 1000 msec 1 sec or more per poll and another 1000 msec for a response Delays f and h are defined by the baud rate Assuming an 8 bytes poll and 255 byte response at 9600 baud this is at least 275 msec while at 1200 baud this is at least 2200 msec 2 2 sec Delay g is defined by the device Oddly enough the simpler the device the faster it tends to reply Some controllers only allocate fixed time slices to process a response from shared memory for example once each 100 msec Delays d e and i are defined by the load on the IAP Device Server If other master client are polling the queuing delay for e can be large the sum of delays f g and h for each earlier poll waiting cannot get a slave response Besides the obvious wrong baud rate there are many possible causes of this Is your cable set up correctly for RS232 or RS485 On the XPress DR IAP is the external red switch set correctly For RS485 you need to short the TX to the RX and TX to the RX externally The XPress DR IAP has a floating ground that is fully isolated from the power supply An external Signal Ground connection is often required between the IAP and your device The IAP Device Server
32. ion RS485 2 Wire and 4 Wire are outputs made active when configuring RS422 485 2 Wire or 4 Wire operation respectively Defaults is an input read at startup that tells the firmware to reset configuration to factory defaults After assigning the applicable function by pressing Enter you are then asked if the pin is inverted active low CPO Function hit space to toggle GPIO In Invert active low Y A function should be assigned to each configurable pin GPIO Input should be the default for all unused or unassigned pins Moabus Protocol User Guide 21 5 WiPort and WiBox Implementation CPO Function hit space to toggle RS485 Select Invert active low Y CP1 Function hit space to toggle RS485 2 Wire Invert active low Y CP2 Function hit space to toggle GPIO In Invert active low N CP3 Function hit space to toggle GPIO In Invert active low N CP4 Function hit space to toggle GPIO In Invert active low N CP5 Function hit space to toggle Diag LED Invert active low N CP6 Function hit space to toggle Status LED G Invert active low N CP7 Function hit space to toggle Status LED Y Invert active low N CP8 Function hit space to toggle GPIO In Invert active low N CP9 Function hit space to toggle GPIO In Invert active low N CP10 Function hit
33. kes 10 minutes or more for systems changes to propagate up to the master client All these relate to the same issue a mismatch in queuing behavior and expectation by the master client to the new realities of Ethernet It is not the IAP Device Server behaving poorly Resetting the IAP Device Server fixes the problem flushes the bloated TCP queues full of stale requests The core problem is that the master client is using the old RS485 serial assumption that no answer means poll was lost However in the IAP Device Server case it could also mean the IAP Device Server has not had time to answer is being overworked Also remember that TCP is reliable the IAP Device Server receives all polls sent without error The result is that the master client retries which makes it harder for the IAP Device Server to catch up Here is the scenario that is causing the problem 1 Master sends out MB TCP Poll 4A with a timeout of 1000 msec 2 AP Device Server receives the poll but the serial link is busy so it waits possibly another MB TCP master is being serviced or timeouts waiting on off line stations are creating a backlog of new requests 3 After approximately 850 msec the serial link is now free and the IAP Device Server forwards the MB RTU request 4 The IAP Device Server receives the response and since the timeout on the IAP Device Server and master are not inherently synchronized the IAP Device Server sends the MB TCP response in
34. ket after 3 to 60 seconds of idle time Redundant Entry Retries after 15 60 sec O disable feature Enter the time in seconds for redundant entry retries or set to 0 to disable the feature A dd D elete E xit Select Function You can either add or delete entries in the IP address table They are automatically sorted into increasing order Enter E when you are satisfied with the table to return to the main menu Modbus Address From To This is the minimum maximum Modbus slave address inclusive to forward to this IP address Slave IP Address This is the IP address of the remote Modbus TCP slave Note the two different ways these IP are interpreted In the configuration example above you see the following results Polls to Slave 12 will go to IP 192 168 0 12 with Unit ID 12 Polls to Slave 70 will go to IP 192 168 0 70 with Unit ID 70 Polls to Slave 112 will go to IP 192 168 0 50 with Unit ID 112 Polls to Slave 155 will go to IP 192 168 0 50 with Unit ID 155 Polls to Slave 201 will go to IP 172 16 123 201 with Unit ID 201 Polls to Slave 244 will go to IP 172 16 123 244 with Unit ID 244 Setting the last 4th IP octet to zero is interpreted as a signal to use the Slave ID as part of the IP This allows a Modbus RTU master to access up to 255 remote Modbus TCP slaves Setting the last 4th octet of the IP to 1 254 causes all slave polls in this group to be sent to the same IP 255 is not accepted as the last 4th IP octet
35. menu from the network TFTP Download This setting defaults to the N No option The Y Yes option disables the use of TFTP to perform network firmware upgrades With this option you can download firmware upgrades over the serial port using Devicelnstaller s Recover Firmware procedure Disable TFTP Firmware Update N Port 77FEh Port 77FE is a setting that allows Devicelnstaller custom program to locate and configure the unit remotely You may wish to disable this capability for security purposes Disable Port 77FEh N Note If you choose to disable this option keep in mind that disabling both Telnet Setup and Port 77FE will prevent users from accessing the setup menu from the network Moabus Protocol User Guide 18 3 Configuring Modbus Web Server This setting defaults to the N option The Y Yes option disables the web server Disable Web Server N Enable Enhanced Password This setting defaults to the N No option which allows you to set a 4 character password that protects Setup Mode by means of Telnet and web pages The Y Yes option allows you to set an extended security password of 16 characters for protecting Telnet and Web Page access Enable Enhanced Password N Y Port 77F0 Hex Port 77F0 is a setting that allows a custom application to query or set the eight xPico configurable pins when they are functioning as general purpose I O
36. n poll traditional Modbus RTU slave devices D G and H as if they were directly multi dropped on an attached RS485 line The IAP Device Server transparently bridges traditional Modbus RTU devices across any TCP IP network This means users can start implementing for Modbus TCP long before all of their required products exist with Modbus TCP and network interfaces Modbus Protocol User Guide 8 3 Configuring Modbus Network Protocols The IAP Device Server uses TCP IP protocols for network communication The supported standards are ARP UDP TCP ICMP Telnet TFTP DHCP and SNMP For transparent connections TCP IP binary stream or Telnet protocols are used Firmware upgrades can be made with the TFTP protocol The IP protocol defines addressing routing and data block handling over the network The TCP transmission control protocol assures that no data is lost or duplicated and that everything sent into the connection on one side arrives at the target exactly as it was sent For typical datagram applications in which devices interact with others without maintaining a point to point connection UDP datagram is used Packing Algorithm Traditional Modbus RTU requires a character timeout to signal the end of a Modbus RTU packet This stretches out the overall response cycle Fortunately the IAP Device Server uses an intelligent length predictive algorithm to detect the end of standard Modbus messages This allows better performance a
37. nd the IAP Device Server falls back to using a user definable character time out to manage non standard or user defined Modbus functions IP Address Every device connected to the TCP IP network including the IAP Device Server must have a unique IP address When multiple Modbus devices share a single IP then Modbus TCP includes an additional address called the Unit ID See the product user guide for your specific IAP Device Server for a complete description of IP Addressing When the IAP Device Server is receiving Modbus TCP messages from remote masters the Unit ID is converted to use in the Modbus RTU message as the slave address When the IAP Device Server is receiving Modbus RTU messages from local serial masters a user defined lookup table is used to match the 8 bit Modbus slave address to a remote IP address The Modbus slave address received is used as the Unit ID Configuration Methods The IAP Device Server can be configured using remote or local methods Either use an ASCII terminal or a terminal emulation program to locally access the serial port or use a Telnet connection to port 9999 to configure the unit over the network See the product user guide for your IAP Device Server The IAP Device Server configuration is stored in nonvolatile memory and is retained without power The configuration can be changed any time The IAP Device Server performs a reset after the configuration has been changed and stored Modbus Protocol Use
38. orse If your OPC server or host application relies on pipelining to send more than one outstanding poll at once then disabling the pipeline will essentially stop all data communication In which case you can just turn the pipeline back on The ideal solution the 2nd generation solution is for your Modbus TCP master client to not only support the Sequence Number but also support the receipt of the OxOA and 0x0B extended Modbus TCP exception response Then the master client never needs to do retries for each poll it will receive either a value Modbus TCP response or a Modbus TCP exception that the slave is unreachable or timed out This prevents the master client from sending more polls than the IAP Device Server can process and building the TCP buffer queue up in the first place Technical Support If you are experiencing an error that is not described in this chapter or if you are unable to fix the error you have the following options Technical Support US Check our online knowledge base or send a question to Technical Support at http www lantronix com support Phone 800 422 7044 US Only 949 453 7198 Technical Support Europe Middle East and Africa Phone 33 0 1 39 30 41 72 49 0 180 500 13 53 Germany Only Email eu techsupp lantronix com or eu_support lantronix com Firmware downloads FAQs and the most up to date documentation are available at www lantronix com support When you report a problem
39. ort 7 FER ane Enabled Web SERVER i e s ue dre Enabled Enhanced Password Disabled Port TOM qu eov aa ee due Enabled D efault settings S ave Q uit without save Select Command or parameter set 1 7 to change Modbus Protocol User Guide 26 Micro125 Implementation The Modbus master slave functionality on the Micro125 is similar to the Modbus implementation on other platforms such as the xPico IAP and xDirect IAP The Micro125 product does not support configurable pins so they are not applicable in the Setup Menu The Micro125 has 1 serial port In this serial port hence the firmware uses for sending and receiving Modbus RTU or Modbus ASCII serial data under the Serial amp Mode Settings menu option The setting for each configuration option is displayed in the setup menu Modbus TCP to RTU Bridge Setup 1 Network IP Settings IP Address xxx Eh 0 0 0 0 DHCP BOOTP AutoIP Default Gateway not set Netmasle 192 se siemens not set 2 Serial amp Mode Settings POOgbDOOUDl A3 verha n qo dents Modbus RTU Slave s attached Serial Interface 9600 8 N 1 RS232 CH1 3 Modem Configurable Pin Settings RES Lette Fixed High Active 4 Advanced Modbus Protocol settings Slave Addr Unit Id Source Modbus TCP header Modbus Serial Broadcasts Disabled Id 0 auto mapped to 1 MB TCP Exception Codes Yes return 00AH and OOBH Char Message Timeout
40. ou reset all of the parameters to the factory defaults 3 Toreset the parameters to the factory defaults type D on the command line and press Enter The default parameters display 4 Select an option on the menu 1 7 by typing the number of the option 5 To enter a value for a parameter type the value and press Enter or to confirm a default value press Enter 6 Review your entries 7 You have the following options save the configuration and exit type S on the command line and press Enter This saves the parameters to EEPROM Caution DO NOT POWER CYCLE the unit too fast after doing this Allow the unit to reboot naturally one time first To quit without saving type on the command line and press Enter The unit reboots the default values type D on the command line and press Enter Modbus Protocol User Guide 10 3 Configuring Modbus Figure 3 1 Setup Configuration Mode Screen Model Device Server Plus Firmware Code AM Modbus TCP to RTU Bridge Setup 1 Network IP Settings IP Address s 0 0 0 0 DHCP BOOTP AutoIP Default Gateway not set etmask S Xe a Se not set 2 Serial amp Mode Settings Protocol Modbus RTU Slave s attached Serial Interface 9600 8 N 1 RS232 3 Modem Control Settings RTS Output Fixed High Active 4 Advanced Modbus Protocol s
41. please provide the following information Your name and your company name address and phone number Lantronix model number and serial number Software version on the first screen shown when you Telnet to port 9999 Description of the problem Debug report stack dump if applicable 60 Status of the unit when the problem occurred please try to include information on user and network activity at the time of the problem Modbus Protocol User Guide 33
42. r Guide 9 3 Configuring Modbus IAP Device Server s IP Address The IAP Device Server is shipped with a default IP address of 0 0 0 0 which automatically enables DHCP within the IAP Device Server With a DHCP enabled IAP Device Server if there is a DHCP server to respond to IAP Device Server s request when it is booting up the IAP Device Server will then get an IP address a gateway address and a subnet mask from the DHCP server These addresses will not be shown in the IAP Device Server s Setup configuration screens you will still see 0 0 0 0 however if you enter the Monitor Mode and from 0 prompt type NC upper case the IP configuration of the IAP Device Server will display See 4 Monitor Mode and Firmware for more information Using the Setup Mode Screen 1 From the Devicelnstaller configuration utility click the Telnet rere button to open a Telnet connection to the IAP Device Server The IAP Device Server s Ethernet hardware address or HW MAC displays Lantronix Inc Modbus Bridge MAC address 00204A8bEEA49 Software version V3 3 0 2RC1 121211 Press Enter to go into Setup Mode wait to close 2 Within 5 seconds press Enter to display the Setup configuration Mode screen Here you can change the parameters that define how the IAP Device Server does its job Note When you set up a new unit and especially if you just reflashed the unit with a new firmware type we recommend that y
43. r XPort CS Updated network protocol and platform information April 2013 Added content for xDirect and xPico Updated security settings available on IAP June 2013 _ Added content for Micro125 For the latest revision of this product document please check our online documentation at www lantronix com support documentation If you use a previous version of the firmware go to the Lantronix FTP site at ftp ftp lantronix com pub to find the earlier documentation Modbus Protocol User Guide 2 Table of Contents Copyright and Trademark 2 Contacts 2 Disclaimer 2 Revision History 2 Figures 5 Tables 5 1 Introduction 6 2 Modbus 7 Extended Modbus System Example 7 Modbus TCP Master Talking to Modbus TCP Slave 8 Modbus TCP Master Talking to Modbus RTU Serial Slave 8 Modbus RTU Serial Master Talking to Modbus TCP Slave 8 Modbus RTU Serial Master Talking to Modbus RTU Serial Slave 8 3 Configuring Modbus 9 Network Protocols 9 Packing Algorithm 9 IP Address 9 Configuration Methods 9 IAP Device Server s IP Address 10 Using the Setup Mode Screen 10 Basic Commands D S Q 11 Default Settings D 11 Save S 11 Quit Without Saving Q 11 Network IP Settings 12 IP Address 12 Set Gateway IP Address Y N 12 Set Netmask N for default 12 Telnet Configuration Password 12 Serial and Mode Settings 12 Attached Device 1 Slave 2 Master 12 Serial Protocol 12Modbus RTU 2 Modbus ASCIl 12 Inte
44. ration error Consider exception hex TARGET DEVICE FAILED TO RESPOND a soft error where a retry may succeed It is returned fslave attached if the slave didn t answer or the answer contained a CRC error f master attached if a TCP socket is open but no response was received in the defined message timeout f master attached if a TCP socket is open but the remote Modbus TCP slave server returned exception OxOB Disable Modbus TCP pipeline 1 No 2 Yes While the Modbus TCP standard specification requires Modbus TCP masters clients to only issue one poll at a time the full duplex flow controlled nature of TCP IP allows them to issue more than one at a time and the TCP socket will buffer them The IAP Device Server will fetch them one at a time and answer each in turn See 4 Monitor Mode and Firmware for more information Setting this to 1 No causes the IAP Device Server to allow this queuing or pipeline behavior This is the safest default setting only change this to disable if you are having problems Setting this to 2 Yes causes the IAP Device Server to always fetch the newest request from the TCP buffer all older requests are discarded This allows a Modbus TCP master client to retry old requests without risking building up a stale queue of waiting requests Character Timeout 10 7050 msec This sets the timeout between characters received Official Modbus RTU defines a 3 5 character t
45. rface Type 1 RS232 2 RS422 RS485 4 wire 3 RS485 2 wire 13 Enter Serial Parameters B D P S 13 Modem Control Settings 13 Modbus Protocol User Guide 3 Table of Contents RTS CTS Mode 1 Fixed 2 Variable 13 Delay after Output of RTS 0 1275 ms 5ms increments 13 Wait for CTS to Go Active N Y 13 Delay after CTS Going Active 0 1275 ms 5ms increments 14 Delay Dropping RTS after Transmitting 0 1275 ms 5 ms increments 14 Advanced Modbus Protocol Settings 14 Slave Address 0 for auto or 1 255 fixed otherwise 14 Allow Modbus Broadcasts 12 Yes 2 No 14 Use MB TCP 0x0B 0x0A Exception Responses 1 No 2 Yes 14 Disable Modbus TCP pipeline 1 No 2 Yes 15 Character Timeout 10 7050 msec 15 Message Timeout 200 65000 msec 15 Serial TX delay after RX 0 1275 msec 0 15 Swap 4x 0x to get 3x x 1y 16 Unit ID to IP Address Lookup Table 16 Close Idle TCP sockets after 3 60 sec O0 leave open 17 Redundant Entry Retries after 15 60 sec 0 disable feature 17 D elete E xit Select Function 17 Modbus Address From To 17 Slave IP Address 17 Security Settings 17 SNMP 18 SNMP community 18 Telnet Setup 18 TFTP Download 18 Port 77FEh 18 Web Server 19 Enable Enhanced Password 19 Port 77F0 Hex 19 Default Security Settings 19 4
46. s normally easy However if a problem occurs it is difficult to troubleshoot without an in depth knowledge of Modbus and the system dynamics of polling Some general guidelines for troubleshooting Start polling slowly and increase speed gradually Cabling is the most common problem with device networking If you have created a custom cable make sure your pinout is correct Ideally you should have the ability to watch the serial line communications Most host applications do a poor job of explaining errors In many situations the host application declares No response when in fact the device did respond and the application did not understand the response How fast can I poll First remember that you still have the serial link in there and therefore cannot expect to poll any faster than you could by a direct serial link In fact since you are adding a number of queuing systems between your application and device you may even lose a bit of performance For example some download tests showed remote download by Modbus TCP bridged to Modbus RTU ran about 20 percent slower than direct download by Modbus RTU Above all remember that the serial speed or baud rate consumes the largest amount of time see the table below Suppose you issue a Modbus poll for 125 registers This requires a 255 byte response which at 19 2kbps requires over 133 msec just to physically shift across the wire while at 300 baud it takes nearly 10 s
47. to the TCP socket 5 Inthe best of times it may take 5 10 msec for this response to actually go down the IAP Device Server s TCP stack across the wire and up the master s TCP stack If a WAN or satellite is involved it could take 750 msec or longer 6 Meanwhile before the master receives the Response A it gives up and makes the Modbus RTU assumption that the request must have been lost The master sends out a new MB TCP Poll 2B Modbus Protocol User Guide 31 10 Troubleshooting and Technical Support 7 Afew msec later there is a response that looks like a good Response B but really is Response A If the master does not use a sequence number which many do not and has forgotten about pending poll A it wrongly assumes this is response B possibly with catastrophic results if Poll B was the same size but different register range Here is the source of the problem IAP Device Server returns the wrong data for wrong slave 8 The master is idle and has no outstanding polls Yet the IAP Device Server has received Poll B by TCP IP It sends this out to Modbus RTU slave and gets an answer The IAP Device Server is doing its job 9 The IAP Device Server returns Response B to the master if the socket is still open and there it sits in its TCP IP buffer The master is not expecting more responses so it neither receives nor purges the extra response 10 Master sends Poll C and magically finds a response waiting as soon
48. uide for your IAP Device Server provides detailed information for installing and operating the IAP Device Server using Standard Tunnel protocol Changing that protocol to one of the industrial protocols changes the configuration menus and dialogs This User Guide provides Modbus protocol specific information for the embedded and external products listed above Modbus Protocol User Guide 2 Modbus When it comes to planning data communication for open multi vendor industrial control systems Modbus is the first choice of end users and integrators alike The Modbus RTU protocol defines how a master device polls one or more slave devices to read and write data in real time by means of RS232 RS422 or RS485 serial data communication Although not the most powerful protocol available its rare simplicity allows not only rapid implementation but also enough flexibility to apply in virtually all industrial situations Modbus TCP an extension of Modbus RTU defines how Modbus RTU and Modbus ASCII messages are encoded within and transported over TCP IP based networks Modbus TCP is just as simple to implement and flexible to apply as the original Modbus RTU You can find the specification for both online at www telemecanique com The IAP Device Server allows users to integrate new and existing Modbus RTU and Modbus ASCII serial devices with newer TCP IP network based devices The next chapter describes a system that integrates four Modbus RTU devi

Download Pdf Manuals

image

Related Search

Related Contents

Targus 15.4” Ultra-Lite Corporate Traveler  体重体組成計 EX 画  GB KERN 572/573/KB/DS/FKB/FCB    ドレッシングスツール 取扱説明書  MANUAL DE INSTRUÇÕES ARCA HORIZONTAL    

Copyright © All rights reserved.
Failed to retrieve file