Home
        026-1102 - Emerson Climate Technologies
         Contents
1.                                                          est          8 1  8 1  SUPERHEAT CONTROL  LIQUID SIDE CONTROL     1            2            4   2  2100000000000000000000000000000000000000000 nennen nenne 8 1  6 2  TEMPERATURE                         ee subse Bere eie reto eoe dae E ette Eie E RESP Ee E EIER enda 8 1  8 3  VALVE CONTROL  5 edt EO PO RR E UR DR ORO RIPE FO PD RET P PEDES    PAPE 8 2  8 4  DEFROST  CONTROL 1    et                esee Ie epe e aedem          cete e b cR A testi             8 4  8 92  SYSTEM START UP    irr ER OR EREMO EU PH HERD E OR ERU          RD t DP ERE 8 4  8 6  SYSTEM RECOVERY  MODE                                                      a a 8 4  8 4   FAN CONTROL c              AERE E      SO o EIFE E DOE rhe SEE E 8 5  8 9  EIGHT CONTROL  ee TA et e Re e Nee TRE noi Ene eae ER eR EAE IAE UNSERE                      8 5  8 9   WASH MODE  inn nc rrr FER UR ERE ERIE DR PERRO PUR P EP FOIE REO UR ERO Ee DRE CE EPA 8 5  8 10   FAIL SAFE MODE  LIQUID SIDE CONTROL     1                  2 2 2 220   0000000000000000000000000000000000000050       8 6  8 10 1  Evaporator Control During Temperature Sensor Failure                 eese eene 6 6  9 SOFTWARE OVERVIEW e            M 9 1  9 15 PID  CONTROL                   RA e ERR tit 9 1  9 2  PROGRAMMING PID                                                                Chee DEEP PRI  9 1  9 3  HOW PID  CONTROL    OPERATES  aine eet ree br t ede Ee UE        oco ei                              
2.                                         T PREV                If the Sensor Type chosen in Section 11 5 1   Setup   was set to  IRLDS   this version of the Sensor Setpoints  screen will appear  All other sensor types use the Sensor  Setpoints screen as shown in Section 11 5 2  or Section  11 5 2     The Sensor Setpoints IRLDS Input screen allows users  to calibrate an IRLDS input and to specify cut on and cut   Off set points for the sensor control output     The current DC voltage from the IRLDS output is  shown in the Curr VDC field  Beside this value is the Curr  PPM value  which will always be equal to the Curr VDC  multiplied by the gain added to the offset     Gain   999   999   250     The RMCC multiplies the actual DC voltage from the  IRLDS with the number in the Gain field  The gain neces     11 48   Sensor Control       sary for proper IRLDS to RMCC communication  250  ppm V  is entered by default  If no adjustments to the gain  are needed  leave this value at 250     Offset   9999   9999   0     If the IRLDS s output is known to send a voltage that is  higher or lower than it should be  an offset may be speci   fied  The number of millivolts entered in the Offset field is  added to the voltage received from the IRLDS times the  gain  The result of this addition is entered in the Curr PPM  field     Cut ON Cut OFF Setpoints   9990   9990 PPM   0  PPM     The Cut ON and Cut OFF set points may be defined as  specific PPM values  The Cut ON set point is the PPM val   
3.                                     J00  Steps per Sec   10  Maximum Steps Open  250         gt  5                 If the EEV is    stepper valve  the stepper functions may  be configured in this screen  Refer to Valve Types on Sec   tion Valve Types for all recommended settings for case  control valves     Valve Type  Bipolar  Unipolar     Users must specify whether the valve is unipolar or bi   polar in the Valve Type field     11 4 39 Manual Defrost    Refer to the description of Manual Defrost on Section  11 4 13  Manual Defrost     RMCC I amp O Manual       Hysteresis  0   255     The hysteresis value is the number of steps required by  the valve to change direction  When a stepper valve is clos   ing and receives a command to open  or when a valve is  opening and receives a command to close  the valve must  continue to close or open for the number of steps equal to  the valve s hysteresis value     Steps per Second  1   100     The maximum steps per second rate of a stepper valve  is defined in the Steps per Second field     Maximum Steps  50   6553     The Maximum Steps value is the number of steps it  takes for a stepper valve to travel from closed  096  to open   100       System Navigation     11 37    11 4 40 Logs Graphs    Refer to the description of Logging and Graphing in  Section 12 1 4   Standard Circuit Log            26     11 4 41                   Refer to the description of the Summary screens on  Section 11 4 56  Circuit Summary                  11 4 42 
4.                                  Normal sensor operation may be bypassed with Sensor  Alarm Overrides  When the RMCC receives closure from  the selected Alarm Override Input defined at the Input Def   initions screens  see Section 11 8 1   Input Definitions   the  associated sensor will not perform an alarm sequence and  if desired  will relay OFF to the controlled output  The  Alarm Override Input and override settings are defined at  the Alarm Overrides screen  Normal sensor operation is  also manually bypassed at this screen     No     Selecting the Alarm Overrides command activates a  sensor selection screen where users select the appropriate  sensor number to be defined  The selected sensor number  is then displayed at the Alarm Overrides screen in the No   field     Digital Override Input  0   8     Normal sensor operation is bypassed when the RMCC  receives closure from an Alarm Override Input defined at  the Input Definitions screens  Up to eight override inputs  may be defined at the Input Definitions screens  Section    14 2   Alarm Overrides       To define sensor alarm set points and time delays  enter  the appropriate High and Low set points and time delays in  the appropriate High and Low fields  To generate an alarm  when the control value exceeds the alarm set points  define  the set points in the Alarms fields  To generate a notice  when the control value exceeds the alarm set points  define  the set points in the Notices fields  Sensor alarm set points  may 
5.                                  REFLECS PROCESSOR  BOARD       4800 19200 38400                        N N          b                  J Barg       26501045       Figure 4 11   Baud Rate Dip Switch Settings  4 14 1  Case Controllers    If using case controllers  the baud rate setting for COM  A and D must be set to 19 200 since the baud rate for the case  controller is hard coded at 19 200  Refer to Section 4 12    Baud Rate Dip Switches  COM A and D only   for more in   formation     4 14 2  8lO    Baud rate settings for the 8IO board are automatically  adjusted by the board based on the baud rate setting of the  RMCC  The 8IO and ARTC can communicate at baud rates  between 4800 and 38 400 baud     4 14 3  COMB    The COM B baud rate is preset on the RMCC and 485  Alarm Panel dip switch S1 at 4800 baud since the 485 alarm  panel can only communicate at 4800 baud     RMCC I amp O Manual          4 14 4  COMC    The COM C baud rate setting is established within the  remote communications screens in the RMCC and is related  to the speed of the modem being used at the store  The  RMCC can communicate at 300  1200  2400  and 9600  baud  It is recommended that a baud rate of 9600 be used for  remote communication        ASE CONTROL  COM A AND D   BAUD RATE      STANDARD CIRCUIT    COM A AND D   BAUD RATE 7                             AND 8RO FC   SWITCH 51   16     SWITCH 53     nui    REFLECS PROCESSOR  BOARD                                              Figure 4 12 Baud Rate Dip
6.                        Name Type Eng  Unit    T PREV 4 NEXT   gt  SET DATA       Selecting the Alarms command activates a sensor se   lection screen where users select the appropriate sensor  number to be defined  The selected sensor number  name     RMCC I amp O Manual System Navigation     14 1    type  and associated engineering unit are displayed at the  Sensor Alarm Setpoints screen in the 4  Name  Type  and  Eng  Unit fields respectively     Alarms Notices   N one  O pen   C losed     When control values are received by the RMCC from  the specified sensors  they may be compared to the user de   fined High and Low alarm set points to determine if the  RMCC should generate an alarm or notice  A notice creates  an entry in the RMCC Alarm Log and initiates no other sig   nal  An alarm is a high level warning that will appear in the  RMCC Alarm Log and may be accompanied by a contact  closure for on site operation of a bell  light  horn  etc  An  alarm may also initiate an alarm dialout sequence and or  the activation of the 485 Alarm Annunciator Panel     Time Delays  0   240 minutes     When the RMCC generates an alarm or a notice  it must  wait the specified time delay before activating the alarm se   quence     14 5  Alarm Overrides    J         ce 59    OVERR DE SETPO NTS  1       ALARM  No    Digital Override nput    Turn Sensor Relay OFF  Type   FF Duration     Manual Override   NORM  Leave a Notice in Alarm Logs      T PREV 4 NE T   gt  SET DATA                      
7.                      Sea RS 11 52  LET A  Demand Set Points              DR DI pP dte ree opui y rere rade 11 52  1128  lt                            ttt penam eeiam he tien eO NO 11 52  ISe Input Definiti  nsiss ai                         E visa sales                                  11 53  1H 5 2  Output Definitions  iie v    Uie iM e d p edt RR ge aed ee eee eS 11 54  11 8 3    System Information    ote resi eere ER ER EE aere rte pep de He ri ER              11 55  FISA             Options iiie eR ERE SD EGRE QURE                   AERA ER davis Eoo neds VE    quie Lees     11 56  1 8 5  System  Information                        ree i rhe HR RH RR ER RR Ree ne                11 57  71 6 6  Send 10 485 Alarm P  nel       c ec c e a d e etes e b        eye v o pen 11 57  11 947  System UNIS 5i in      e                   ON                        GNE MU RES asad 11 58  11 6 6    Dialout Set  p  siio eee oe RU E REN E LSE               11 58  11 6 9  FoggingJSetup  ue                                        OD aO pn iae eben 11 59  11 8 10    Communications Setup  i i iv e ER er ied dieit dea eive            e ever            11 59  11 8 11  Modem Iitialization        eoe etuer quiere der ir ageres 11 60  11 8 12   Transducer Offsets    asus dir E ER RO TR EGER o RS E EO QUIE          11 61  LL813   Oil Pressure Transducer Offsets       eet tre I Pet t trit peer gts 11 61  1 8 14    TransducerSSetupz  iade at      n eade estela A bier erepti 11 61  TLS AS  Host Network    ip
8.                     O MENU      gt  SET DATA    After suction pressure groups are defined at the Pres   sure Groups Setup screen  see Section 11 2 6  Compressor  Setup   the compressors within each group are defined and   or edited at the Group   Setup screen  use the down arrow  to access the Group 2  3  and 4 setup screens      Type CMP   C omp   V S or  U nldr   X  Clear   C     Compressor stages are defined in the Type CMP fields   A variable speed compressor    V    may be defined as the  first stage in each compressor group  An unloader    U    may  be defined for any stage immediately following a compres   sor stage           Unused stages within a group should always  be cleared    X        Run Time   0  Clear Runtime     The Run Time field displays the total hours of operation  for the selected compressor stage     Oil Sens   P ress                           N one   N    An Oil monitoring sensor is defined in the Oil Sens  field  If the compressor is equipped with an oil sensor  it  may be defined as either a pressure transducer or a contact     If a pressure transducer is indicated  the RMCC will termi   nate compressor stages when the net oil pressure read by    11 2 8  Pressure Setup    SETUP                mp On During Defr   During Reclaim                        Always Remain On             Grp2      T PREV                            Grp3     gt  SET DATA                11 6   Main Menu          Each compressor group may contain a single variable  speed compress
9.                    cud eR eee        aet erbe ere 14 3  1258  SAEARMS        EGER OR IRSE EE HERR RE SERRE NU SR EUER CRGO TORRE RUEDAS ERE tenian 14 4  15 HAND HELD TERMINAL SCREENS wisssscsssscssesssccscsnssesnsssonsssnsesessensvensevsncsvensendecesesdosdesasebscecdsseszesosssoassesaveess 15 1  15 1  LIQUID  PULSE  HHT SCREENS ii exerce Sends sac E ERU EN E eren Ree      e        ans d tUe tats 15 2  15 2  LIQUID STEPPER HHT SCREENS           cccssscccceceesscecceceessaececcsesenececeseneseececeseasseeccecessaaeccecessaaeceececsaaececeeeesaeeeseeeeenees 15 4    RMCC 1 amp 0 Manual Table of Contents     ix    15 3  CPC SUCTION STEPPER                5  005  4                                        seco e e oe                                              15 7    15 4  HUSSMANN SUCTION STEPPER HHT 5          6        00 0 0 202  0 0 000 00000000000                   15 9  APPENDIX A  ADVANCED PRESSURE CONTROL  RMCT 2 10                            cere eee eere ee een eee teen ee enne seen seta A 1  APPENDIX B  SENSOR HARDWARE SOFTWARE SETUP                                  1 1  1 7 1                                                       B 1  APPENDIX C  PRESSURE VOLTAGE AND TEMPERATURE RESISTANCE CHARTS FOR ECLIPSE   TRANSDUCERS  amp  CPC TEMP SENSORS    oso rosse edes oaa bu eoo oo voe Ua eee eV no           ep so      ed eeu pe rob bU pU ND co e Uwe        C 1  APPENDIX D  SYSTEM NAVIGATION SCREEN G            sssccssssssssssccesssccsssscccsssscscsscccsssccccsscecscsscecescc
10.                    ea ae ena ee 5 1  5 1     WAIRING SPECIFIGATIONS 2 533                                rU ne E A EO                           5 1           AND D WIRING             tete edocet et tuit etate e 5 1  25 3 COM  B WIRING             ette EORR BERE EUR UR EIE E 5 1  3S4 COM CCWIRING                         oe epe tieni                                           5 2  2 29   BINCORG  INVERTER  WIRING                              5 2  5 6  SENSOR AND TRANSDUCER WIRING      scsssccscesssssecececssssceececeeseceecsensaeseeceeeasseseseessececesesaeeecesesaesececessaaeeeeceneseaeecs 5 3  5 7  POWER CONNECTION WIRING            eere reete teneor eie                             aeree es eo          see o                                          eee iren                                             rae uh 5 7  5 70  Power Transformers  aq      gi o E PER EET dee a Remus 5 7  5 7 1 1  Wiring the 16AI  8RO  4AO  or 8 DOn                                       ROA E E           ertet trennen ersten nnns 5 8  5 71 2  Wiring th   8IO  Board    ueber tede ee a neve tr            t eee edet ete 5 8  3 5  NEDLWORK SETTINGS  uere          deis eei datam eed ute uide deis e PUN  DEST           AGATESS             IM EE eA deme RES AS t                9 61  DIp SWItC 6S  c treo neat OV        ERE OE fe tetra otic coat nhs etna a  5 8 1 2  LED Indicator Lights  5 9  FAIL SAFE AND RELAY DIP SWITCH SETTINGG        ccccccccccesssssceceeesescecescsessecccesessecccecessaaeccecesssaeceecsessus
11.               T PREV               gt  5              O MENU    The circuit Refrigeration  Defrost  and Master Liquid  Line Solenoid outputs are configured at the Circuit Output  Setup screen  This screen will display only those outputs  defined at the Circuit Setup screens and only applicable  fields will be active     11 30   Circuit Defrost Control          The RMCC uses this address to locate the selected sen   sor     Log Interval  00 00 00   24 00 00     The RMCC periodically records the values received  from the defined sensors and stores the information in the  RMCC Log  The Logging Interval defines when the data  received from the sensors are recorded     Bypass   50   99   N one   O pen   C losed     A fixed bypass may be assigned to the defined sensors  in the Bypass field  A fixed bypass will override the actual  sensor reading with a user defined value until the bypass is  deactivated at this screen  Users may bypass the current  sensor reading with a numerical value  or with an open or  closed status  To activate the fixed bypass  enter a numeri   cal value                or    C    losed in the Bypass field     Sensor Type   T emp   6 450   D igital   T     If the circuit has been configured with the default val   ues for the type of case within the circuit  the appropriate  sensor type for the selected sensor will be displayed in the  Sensor Type  Users may change the sensor type to either a  temperature sensor or a digital sensor by entering the ap   propriat
12.               ce 2 5  2 5  4855                                                                                2 5  20  HAND HELD TERMINAL                                                                                               E PTUS EE RETE VEEREC EAE VE CR 2 6  2 7   REMOTE COMMUNICATION ss      te RR EU                                                             e    2 6  2 7 1  RS232                                                            eese ge dee tete et eges 2 6  2 727                                                                                     2     22723  UI CIAM ce 2 6  3 HARD WARE MOUNTING e           3 1  3 1  REFRIGERATION MONITOR AND CASE CONTROL         cscssscscsesssscececesesssesecesesseaeececescasecececsauececcecesasseseeeseneseseeesentaeees 3 1  3 2  I O BOARDS  AND  ENCLOSURES      detect eeetceee eee tec                                    ER UE VR Rev UY 3 1  22   485                      nere tono reel cabectos eu evi eee                              3 4  3 4   RS232  BUS                EDI EUR UTE ERE UR 3 5  35                                                                             3 5  3 0  PRESSURE TRANSDUCERS      ier RAE IECUR AREE ERE RRE NER ES REESE EUER A E EG              ENS               3 5  3 7     TEMPERATURE SENSORS    e      tes iut erteilt eto                       ipee    de Edere 3 6  3 7 1  Outside  Ambient  Temperature Sensor              eese eene teeth ettet nnen tenente ee terere tenen nent enne enne 3 6  3
13.              THE SWITCH SETTING SHOWN CER 2  IS SPECIFICALLY FOR UNLOADERS      N O 1  C       THE SWITCH CLOSES THE RELAY        4  LOSS OF COMMUNICATION  THE JUMP       ER OPENS THE RELAY ON LOSS OF                                              D  POWER  n c                 S2 FAILSAFE       JUS  26501031    Figure 4 13   8RO Board Fail Safe Dip Switch and Jumper  Settings    The ARTC  8      and 8RO FC have a dip switch  S2   which indicates the state of the relay  NC or NO   When the  relay is set normally closed  the appropriate LED relay indi   cator  one through eight  is illuminated  Dip switch rockers  one through eight should be set to the up position if the relay  is wired normally closed and down if the relay is wired nor   mally open     The REFLECS Networks     4 5    5 Communication and  Power Connections    This section describes how to wire the CPC refrigera   tion control system  Information is provided for the RE   FLECS and all sensors  alarm panels  modems  loads  and  output functions          wiring schemes shown in this section conform to  the requirements outlined in Section 5 1   Wiring Specifi   cations     5 1     All CPC I O and host bus communication components   COM A and D  and COM B  have been designed to con   form to RS485 standards  Remote communication compo   nents  COM C  have been designed to conform to RS232  standards  When wiring CPC components together  it is  necessary to follow the rules and requirements specified in  this section 
14.             CABLE SHIELD      335 3151  DD  a     DISCHARGE AIR 1  CASE  n  CONTROLLER   iL BLUE s 2      DISCHARGE AIR 2  G BLUE  OHE  919  2  DISCHARGE AIR 3         RED GG  G  CREEN          GREEN   B  0  DISCHARGE AIR 4  G  PURPLE     PURPLE OKD                   So    amau  BLUEMHITE       EP        EXTRA TEMP 2  43    REDWHITE 210   ORANGE         5 e   DEFROST TERMINATION   15  eR SUCTION VALVE OUTPUT         OUS SUCTION VALVE OUTPUT RETURN     RS485    Gg  HE  Gg    BLACK C  09                   26513018    Appendix F   F 1    Index    Numerics    16AI Analog Input Board  defined 2 2  features 2 2  mounting in enclosure 3 1  mounting without enclosure 3 3  power requirements 5 7  software setup 11 63    485 Alarm Panel  alarm filtering 11 57  14 3  defined 2 5  disabling alarm resets 11 57  features 2 5  location 3 4  mounting 3 4  power requirements 5 7  sending notices to 11 56  11 57    4     Analog Output Board  defined 2 4  features 2 4  mounting in enclosure 3 1  mounting without enclosures 3 4  power requirements 5 7  software setup 11 63    8DO Digital Output Board  definition 2 4  max number of boards 2 4  power requirements 5 7  software setup 11 63    8IO Combination Input Output Board  Baud Rate Dip Switch Settings    defined 2 4   features 2 4   Limitations on Transformer Wir   ing 5 7   max number of boards 2 4   mounting in enclosure 3 1   mounting in weather resistant  enclosure 3 2   mounting without enclosure 3 4   power requirements 5 7   software s
15.             COIL 2 OUT                   DEFROST TERMINATION                  GO        GO  eg  GO          SUCTION VALVE OUTPUT  SUCTION VALVE OUTPUT RETURN  RS485                  RS485        CABLE SHIELD                                                                  26513021    Figure 7 3   Input Cable Harness  335 3151  Schematic  Diagram    7 6 2  Output Cables  Full Output Cables    CPC s case controller full output cable harness without  connectors  335 3156  and with connectors  335 3158  are  designed for use with either a pulse or stepper valve case  controller  The connector is constructed with 18 AWG col   or coded wire with a 16 pin  male end connector for con   nection to the case controller  The 335 3156 output cable is  supplied with wire leads for connection to non CPC power  modules  while the 335 3158 cable is supplied with an 8   pin  male end connector for connection to the CPC power    RMCC I amp O Manual        module  The schematic diagrams for these cables are  shown in Figure 7 4 and Figure 7 5     CASE  CONTROLLER  BLUE  GREEN  ORANGE  BLACK  BROWN  BLACK  RED  BLACK  PURPLE  BLACK  WHITE  WHITE  BLACK  YELLOW  PURPLE RED  BLACK  YELLOW        PULSE VALVE 1 OR STEPPER MOTOR 1  PULSE VALVE 1 OR STEPPER MOTOR 2  LIGHTS CONTROL   LIGHTS CONTROL RETURN   FANS CONTROL   FANS CONTROL RETURN   DEFROST CONTROL   DEFROST CONTROL RETURN  ANTI SWEATS CONTROL                                  ANTI SWEATS CONTROL RETURN   24 VAC 1   24      2   OPTIONAL VALVE 
16.             __             ESEN   gt  SET DATA _ 0              L NEXT   gt  SET DATA O MENU 0          0            gt  SET DATA  SYSTEM OPTIONS   12 00  MODEM INITIALIZATION STRING  12 00      DIL PRESSURE TRANDUCER OFFSETS 12 00     Host Net State   ON 1 0 Bus State   ON 12 00  Addi tional Delay After Defrost 000 m Curren 01 02 05 04 05 06 07 08 Number Offline   D Number Offline  0  Notice on Defrost Timeout ATRFE OS O 1 8 2x08W 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 1234567890123456  Patterns  Number to Copy    gt     09 10 1i 12  13  1   15 15 RMCC 2        3     485A 1 8809  Power Fail Alarm Notice D Hayes 3  P P  24008A v42bis 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 1 GAIs  Record             NO  Powcrup Self Test  Y 11Multi tech 21 pip  96008A   42  16 1  18 19 20 21 23 AOs  2 P P  24005A 5  Generic 00 0 00 0 00 0 00 0 00 0 00 0 CCBS Total O   Online 0             gt  SET DATA _O MENU i J 0 T PREV L NEXT   gt  SET DATA  SYSTEM INFORMATION 12 00 TRANSDUCER SETUP 12 00     Host Bus DEVICES 12 00      170 BOARD DEVICE NUMBERS 12 00  Send Notices to 485 Alarm DN Disch  Pressure This Controller is Device   1    Disable Alarm Reset by 485 Alm   N Sucti  n Pressur Alarm If Another Device Fails  N   Number 8RO Boards MAX 16  NOW D   Delay Before Alarm Dial Out   000 m Gri Gre GR3 GR4 Test Host Net for New Devices  N   DAYLIGHT SAVINGS MODE  AUTOMATIC  USA 100 lb     100 tb 100 Lb 100 Lb Number 16AI Boards Max 8  NOW 0   DST MANUAL SET START   04 05 92 Oil Pressure  200 lb Nu
17.          ier        T PREV               gt  SET DATA    When the Demand Defrost feature is activated  the  RMCC will only activate defrost when a contact closure is  received from the installed Demand Defrost sensors or  when the system reaches the demand fail safe time  For  more information about the Demand Defrost feature  see  Section 3  Software Overview  This feature is optional  within the RMCC  therefore  default values will not apply  to this screen       Demand Sensors  0   2     The number of Demand Sensors installed within each  circuit is defined in the   Demand Sensors field  If two De     11 4 21 Circuit Set Points 4       Dabok E     CIRCUIT SETPOINTS   Z1             Case Pump Down Delay          Dual Tmp Alarm Set Point Shift   Dual Temp Shift Input                  T PREV               gt  SET DATA    Circuit settings for the Pump Down Delay and Dual  Temp Case features are defined at the Circuit Set Points 4  screen     Case Pump Down Delay  0   240 seconds   0     Defrost performance is improved by specifying a dura   tion during which the system empties or    pumps down    re   frigerant from the evaporator coil  This procedure ensures  that residual refrigerant in the coil will not work against the  defrost cycle  When the delay is activated within a Stan   dard Circuit  the refrigeration solenoid is closed for the de   fined delay before the defrost cycle begins  During this    RMCC I amp O Manual          mand Sensors are used  the RMCC must receive 
18.          t tee et e          e ies 9 9  9 9 12     Module Inputs and Outputs      oe e E E ete ER Ee eee ueste te ae          9 9   9 9 2  RMCC VO  Module Descriptions    Lii wiih todas          d esa Rebel edid e e               E      9 9  9 92  T    An  log  Input Module    err en tere E eee ee        t eee tien eee e eie e cade ERE        9 9  90 20 22 Digital Output  Module ec                                                                                                      9 12  9 9 2 3  Analog Output Module nseni rer ten                                                                                9 14   10 SYSTEM CONFIGURATION GUIDE                                           eee          setatis tosta sessanta sensns theta ss so sesta tns en sens 10 1       GENERAL T                                                                            10 1  10 22    SETUP COMPRESSORS 5    ubere omoibus auper ende EP ae miii 10 1  10 3    SETUP  CONDENSERS  sri ee eei idein EG t n te dc rte yi bti ie 10 1  10 4   SETUP STANDARD  CIRCUITS  ertet E ER IRE eR GERIT Ute eee tiae 10 2  10 5       SETUP CASE CONTROL                     E E UE INE ESE 10 2  10 6   SETUP SENSORS oni RI eae eei adiutorem e bcp             IRE 10 2   MOr                                                       11 1  1121           tie CUP Ie ro te CERE E                            11 2         MENU                        BU QOO BI ee e RN UNI E he 11 2   TTE  Pressure Control iet e tt tette tetro eer e SEHR
19.         Circuit  SummbaEy     a t Re RR PERLE        13 4  13 23  Anti Sweat  Status               eerte ettet teta tede aS i ades 13 4  13 3 4  Anti Sweat Dewpoint Status Screen             eese               SOSSE SE OEK                   13 4  13 3 5  Anti Sweat Output Status    iie vedere dee devon      eve ee                                    13 5  13 4   CASE CONTROL STATUS          reete bi EE e ER e E FU d eT 13 5  13 4  L   Case Control Circuit Status c SE E a EN ee me        13 5  13 4 2  CCB Status 1  Liquid Pulse and Stepper Only               sese enne etre rennen rene 13 5  13 4 3  CCB Status  1  Suction Stepper Only     ette etr ret ee               EUR siete 13 6  13 4 4  CCB Status 2  Liquid Pulse and Stepper Only               esses                 13 7  13 4 5  CCB Status 2  Suction Stepper Only         e ee bere e ie ee o e bp etre Eye Dues 13 7  13  4 6   CCB  Status 3  Liquid  Pulse Only          entente he ee i i radere 13 8  13 4 7  CCB Status 4  Liquid Pulse and Stepper Only              sese eese eerte trennen etre trennen rene 13 8  13 5  SENSORS 2t eR                 RINT                                13 8  13 2  D SensorSStatls So SESE EEA EONS metn I 13 8  13 6  ALARMS  reete or t e RR ODER RENI                                           13 9  75 26  Alarm Oyerride  Status   e et ERU I RN SUI IB He RR 13 9  13 7  oINPUT QUTPUT  MODULES      5    eter Nee SEU EHE ERE RI Ee TO RARE VAR TS RSSEEPEEKFO FERRO ELE REPE EFE 13 9  13 72 Analog  Input Mo
20.         Valve Type Jumper  JU5        Output Cable Connector  Lights  12 VDC  170 Ma max    Fan  12 VDC  170 Ma max    Anti Sweat  12 VDC  170 Ma max    Defrost  12 VDC  170 Ma max    Pulse Valve 1  24 VAC     26502022       Figure 6 2   Stepper EEV Case Controller    Full installation of the case control kit requires five    standard components     1  Case Controller    Applicable Temperature Sensors    2   3  Input Cable  4  Output Cable  5    Power Module    Items 1 and 2 are supplied as a single kit  The input and  output cables must be ordered separately depending on the  power modules being used     Case Control Hardware Overview     6 1    Table 6 1 lists the different case controller types and  their part numbers  Table 6 2 lists the available input and  output cable configurations and their part numbers     Description Part  Number  Liquid Pulse EEV Case Controller Kit  810 3140    Liquid Pulse EEV Case Controller  no sensors  810 3141  Liquid Stepper EEV Case Controller Kit  810 3150    Liquid Stepper EEV Case Controller  no sen  810 3151  SOrS    Suction Stepper EEPR Case Controller Kit 810 3152   Hussmann      Suction Stepper EEPR Case Controller  Hus  810 3153  smann   no sensors    Suction Stepper EEPR Case Controller Kit 810 3154   CPC      Suction Stepper EEPR Case Controller  CPC  810 3155   no sensors     Second Valve Kit  pulse only   Includes  510 3130  Coil Inlet Temperature Sensor  Blue Leads  501 1125  Coil Outlet Temperature Sensor  Red Leads  501 1126
21.        12 00       12 00                 STA  Case Te  Status   Disch     Disch     Disch     Disch A       TUS         01801   01            mp   NONE Setpoint    On Last Term       OPEN Valve Koo        OPEN Humidity X       OPEN Antisw  X       ir    12 00   25 0    0 0  30 0  NONE   100 0    ODMENU           SETPOINTS CCB    Asw Lo Limit  Frost Sensor    t PREV J NEXT   gt     Asw Hi Limit  060 0  204        01 SDIC O1c 12 00   Revision  6 0B2L              CCB STA    TUS CCB 015DIC 01c    SHORT Fan Relay    0 0 Lights  Off   OPEN    OPEN    12 00    On  On       O MENU          ALARMS  CCB   Extra  Imp  YES  Extra2 Tmp  YES    T PREV               gt        NO    SET DATA   O1 80IC 01c 12 00  Refr Leak   NO  Leak Alm Lvl  1000  Leak Alm Diy   010m    Door Alm Delay  015m     SET          T PREV 4 NEXT          OFFSETS  008 01 501   01   12 00  Case Offset   Q D Extra          0 0  Discharge   1  0 0 Extra2 Tmp  0 0  Discharge   0 0 Refr Leak   0000  Discharge   0 0  Discharge   0 0                         STPTS         Valve Type  Hysteresis  Steps per Sec  Maximum Steps Op       301 8DIC Olc 12 00  UniPolar Stepper  005   gt  100  en  2500             D 4   RMCC Front Panel Screens    026 1102 Rev 4 08 12 99       SENSOR CONTROL 12 00    1 Status 5 Logs  2 Setup 6 Alarm Overrides  3 Setpoints 7                  Status                 amp  Shut off Sched     9 1 0 Control Modules  SELECT NUMBER          ENU                                     SENSOR STATUS 12 00   SELECT
22.        NOTE  There is no additional setup  NO     if you select  T PREV J NEXT       gt  SET DATA O MENU    11 4 25 Advanced Defrost Options  Hot Gas                       e Es      CIRCUIT SETUP    ADVANCED DEFROST OPTIONS  Host Compressor Group                                             gt  SET DATA    O MENU    Hussmann PROTOCOL   Advanced Defrost set points  for Advanced Hot Gas Defrost are defined at the Advanced  Defrost Options screen  If controlling with an Electric De   frost System  see Section 11 4 26  Advanced Defrost Op   tions  Electric      Host Compressor Group    1   4 Group Number    0  Disable   0     The Host Compressor Group   field ties a specific com   pressor group to the circuit  To define the compressor  group  enter the appropriate Compressor Group Number   or Suction Group Number  in the Host Compressor Group    field  Group numbers are defined at the Compressor Set   up screen  see Section 11 2 6  Compressor Setup      Hot Gas Defrost Type   S tandard   R everse Cy   cle   S     There are two types of Advanced Hot Gas Defrost Sys   tems  Users may choose from the following types     RMCC I amp O Manual          system settings with a user defined ON or OFF value until  the bypass is deactivated at this screen     Run Time   0  Clear Run Time   0     A real time clock within the RMCC records the cumu   lative runtimes of each output  The cumulative runtime is  the total number of hours each output has been activated for  the duration the RMCC has 
23.        exo NEU                    o RENE 26513034    Figure 5 2   COM B Network Connections    Communication and Power Connections     5 1                  Connect the three wire COM C network cable to the  REFLECS controllers and modem as shown in Figure 5 3     TO POWER    TOPHONEJACK N      DB25 TO REFLECS    CONTROLLER CABLE V   PN 535 1015       REFLECS POWER  INTERFACE BOARD    TB1 RS485 TB2 RS485 TB3 RS232                  A OV  A   COMA COMB    SHIELD       26513047    Figure 5 3   COM C Network Connection                       5   Fincor  Inverter Wiring    Fincor  brand inverters may be used to power variable   speed compressors  The following sections show how to    set up a Fincor  inverter to work with REFLECS I O  boards     Wiring is as shown in Figure 5 4  The terminal strips  shown in the bottom of Figure 5 4 diagram correspond to  the terminal strips in the lower right corner of the inverter s          control board  Consult the Fincor  user   s manual for more    information about these terminals     RMCCB8RO   RMCC8RO   RMCC8RO 4AO OUTPUT  EMERGENCY INV x  RESET              VS COMP  x   STOP  N C   RELAY  N C   RELAY  N O          16AI INPUT   JUMPER TERMINALS oe 69 9          INVALM  IF E STOP IS NOT i5    TO BE USED   e     Lx X 3                                          DAOC        a    7     DOOK   X    ANON    EXTERNAL    JUMPER FAULT    26513073    Figure 5 4   Fincor Inverter Control Wiring    Fincor   Inverter Wiring Procedure    1  E STOP   Termi
24.      Power Connection Wiring    Center  Center   tapped tapped    ano   459A    800           Center  Center   tapped tapped    Table 5 2   Power Requirements    5 7 1     Transformers for powering the input and output boards  should be wired according to Figure 5 7 and Figure 5 8  depending on the number and type of boards being pow   ered     Power Transformers    To select a power transformer for a board or a series of  boards     1  Determine what the total VA is for the boards  that will be powered by the transformer     EX  Two 8105  18 0 VA each   and one 4AO   10 0 VA  boards are to be powered by one  transformer     2 x 18VA     1 x I0VA    46VA    2  Usea transformer that has a power rating  higher than the total calculated VA  see Fig   ure 5 6      EX  Three board transformer  56 VA  is suf   ficient    56 VA is greater than 46 VA    RMCC I amp O Manual       Three  Six Board Ten   Board Board    640 0043 640 0045   640 0048   0048    ELM 56      100 VA LM VA  Rating    Figure 5 6 Power Ratings for CPC Transformers       FOR 208 VAC POWER SOURCE  26513001    FOR 110 VAC POWER SOURCE    Figure 5 7   Wiring for 640 0043  Three Board  and 640 0045   Six Board Transformer    Communication and Power Connections     5 7    PINOUT    24 VAC OUTPUT  CENTER           FOR 208 230 VAC POWER SOURCE    120 VAC    24 VAC OUTPUT  CENTER           FOR 120 VAC POWER SOURCE 26513002       Figure 5 8   Wiring for 640 0048  Ten Board Transformer  5 7 1 1  Wiring the 16Al  8RO  4AO   
25.      Supht 1   the superheat of coil 1    Setpt   the superheat set point for coil 1    Valve 1    the current valve opening percentage   Case dF   the case temperature in degrees Fahrenheit     Coil 1 In   the coil 1 in temperature    Offset   the coil 1 in temp sensor offset  This may be changed with the HHT   Coil 1 Out   the coil 1 out temperature    Offset   the coil 1 out temp sensor offset  This may be changed with the HHT     This screen is identical to Screen 3  except it applies to valve 2 and coil 2  if applicable      This screen is identical to Screen 4  except it applies to valve 2 and coil 2  if applicable      Defr   When in defrost  this field shows the number of minutes and seconds the circuit has  been in defrost  This number will be equal to the fail safe time when not in defrost     Failsafe   the maximum number of minutes and seconds defrost mode will remain active   Term   the termination temperature sensor reading   Setpt   the termination temperature set point     Defr  1 Defr  4   the first four scheduled defrost times     Defr  5 Defr  6   the fifth and sixth scheduled defrost times     Drip   When in drain mode  this field shows the number of minutes and seconds the circuit has  been draining  This number will be equal to the set time when not in drip mode     Set Time   the amount of time moisture on the coil is allowed to drain after defrost        026 1102 Rev 4 08 12 99    Humidity   the humidity sensor reading           1    the percentage at 
26.      To define the defrost termination strategy  enter the let   ter corresponding to the desired strategy in the Defrost Ter   mination field     Defrost Termination Type   N ormal   P ulsed     The Termination Type is also defined in the Defrost  Termination field  This type determines the status of the  system after defrost is terminated  Users may choose from  the following Termination Types        N ormal   the RMCC will return to normal refrig   eration operation        P ulsed   the circuit will remain in defrost mode for  the defined Defrost Duration  If during this time a  termination is called for by either the Stat  Inl  Dsch   Out  or Rtrn Termination strategies  the RMCC will  remain in defrost and pulse the defrost heat on and  off in an effort to keep the termination temperature  reading equal to the Termination Temperature Set   point  See Section 11 4 46  Circuit Set Points 1   Add Edit Circuit      The Termination Temperature has a fixed 2  dead  band value for case control circuits  The RMCC will  shut off defrost heat when the case temperature ex   ceeds the Termination Temperature and reactivate  if the temperature falls 2  below the Termination  Temperature     When the defrost duration is over  the RMCC will  prevent refrigerant from entering the coil for the du   ration specified in the Drain Time field  see Section  11 4 46  Circuit Set Points 1  Add Edit Circuit     The RMCC will then return to normal refrigeration  operation     Valve Control Strate
27.     11 56   Configuration       access to the RMCC  A detailed description of each access  level is given in Table 11 1 on Section 11 1  Log On  To  change the passwords  enter the desired password in each  password level field  After a new password is defined  it  may be used to log into the system at the corresponding lev   el access     ation of a bell  light  horn  etc  An alarm may also initiate  an alarm dialout sequence and or the activation of the 485  Alarm Annunciator Panel     Record Logons   Y es   N o   N     The Record Logons feature configures the RMCC to  record the password level of users logging into the control   ler  When Record Logons is activated  the RMCC will send  a notice to the RMCC Alarm Log each time a users logs  onto the RMCC from the front panel or through a remote  connection  Included in the log entry is the date  time  and  password level     Powerup Self Test   Y es   N o   Y     Itis recommended that the CRC test be enabled to pro   vide a method for ensuring that the controller operat   ing program has not been corrupted     A power up self test   also called a Cyclic Redundancy  Check  CRC    is a self diagnostic the controller performs  during system startup  This test validates that the program  running in the REFLECS controller has not been corrupted   The CRC test searches the entire operating program and  validates that the current values are the same as were orig   inally uploaded  This test takes approximately one minute  to compl
28.     800    The 16AL 8RO  4AO  and 8DO all require the use of a  center tap  The number of boards that need power will de   termine the transformer size that is required   see Section  5 7 1   Power Transformers   It is important that the trans   former size match the board s power requirement     Figure 5 9 diagrams the wiring for three 16AIs  SROs   4AOs  or 8DOs  or any combination of the four board  types  These boards all use a center tap configuration for  grounding     5 8   Power Connection Wiring    16AI 8RO   4AO 8DO  POWER  TRANSFORMER    SECONDARY             CENTERTAP     ___       16AI 8RO   4AO 8DO                8IO ARTC  NON CENTER            0V terminal connected      to Earth ground        GROUND 26513093       Figure 5 9 Wiring for Three 16AIs  SROs  4AOs  or 8DOs or  Any Combination of    5 7 1 2  Wiring the 8     Board    The 8IO board can be wired for power in three different  ways     1  By itself with one transformer for power   Figure 5 10     2  Incombination with a or multiple 16AI  8RO           or 8DO boards Figure 5 11     3  Ona 24 V AC line with the ground in the sys     026 1102 Rev 4 08 12 99    tem on either side of the power line or with no  ground in the system at all  Figure 5 12     16AI 8RO   4A0 8DO    POWER  TRANSFORMER  SECONDARY    POWER  TRANSFORMER  SECONDARY         EARTH GROUND 26513095       Figure 5 10 Single 810 Board Wired to One Transformer    When the 8IO board is used by itself  it is satisfactory  to wire the board with 
29.     Digital Value Combiner  DVCombiner     The DVCombiner cell   s function is to read up to four  digital input signals  combine these signals into one value   based on the combination strategy   and send the com   bined value to the Schedif cell     Two different combination strategies may be specified  by the user  a primary combination strategy and an alter   nate combination strategy  The primary combination strat   egy will be used whenever the Alt Combiner input is LOW   When the Alt Combiner input is HIGH  the alternate com   bination will be used  If an alternate combination strategy  is not desired  only the primary combination strategy needs  to be defined     Schedule Interface Combiner  Schedif     The Schedif cell gives users a method of modifying the  combined value of the Digital Inputs based upon the occu   pied or unoccupied state of the building  Using a user de   fined strategy  the Schedif cell combines the input value    RMCC I amp O Manual    from the DVCombiner cell with the Occup input  The re   sult is then sent to the Min On Off cell     While the Schedif cell   s function is similar to the DV   Combiner cell   s function  their combination strategies are  not similar  The Schedif cell   s combination strategies are  specially made for occupancy driven control  and are not as  logic based as the DVCombiner strategies     Two different combination strategies may be specified  by the user  a primary combination strategy and an alter   nate combination
30.     gt  SET DATA  12 00  Electric  Stat NORMAL  Temp Temp  Disch Air  No          CIRCUIT SETPOINTS  1  Drain Time 000  fist Defrost             End Defrost           Brd Defrost NONE           1             SDIC     Otc    befr Duration 000 Control Temp  Fan  amp  ASW Off  Terminate Temp 000 0 D R Weighting   4th Defrost  Sth Defrost  6th Defrost      gt  5                 12 00  000 0  000 0                                               CIRCUIT SETPOINTS  1           Lights Strategy           Pump Down Delay    lanti Sweat Control    Dual Temp Shift Input              L7NEXT    SDIC     Shut Down 1f Suction Grp Fail  Dual Tmp Alarm Set Point Shif    01             gt  SET DATA        CIRCUIT SETPOINTS  1  Demand Defrost      Demand Fail safe Time   Alarm Time      FCIRCUIT SETPOINTS  1  Cleaning Override Switc  Cleaning Switch Type   Cleaning Notice Enabled    T PREV L NEXT    SDIC   OFF    000 h  000 h    h  NO  Sw  No    He    rs  rs      gt  SET DATA    NE  itched      gt  SET DATA       12 00  oooh          Input Name  Case  Location    Log Interval  00 00 0  Bypass    Sensor Type    Offset     T PREV 1             0    CIRCUIT INPUTS SETUP SDIC 10c      gt  SET DATA    12 00          CIRCUIT OUTPUTS SETUP    Output Name         Location 00 00  Log Interval 00 00   Bypass Norm          Time 00000m    T PREV L NEXT    00    Dfr  00 00  00 00  Norm  00000      gt  SET DATA    12 00    00    s          ALARM SETPOINTS    Case Temp ALARM  Hi Alarm  NONE  Hi Delay 0000  Lo A
31.    550 2500 KW Transducer   16AI  E 02 and 4 20 mA Output to Input Board  550 2550 Above  Any LINE VOLTAGE   Available Point INPUT GONNECTIONS      oon   16AIs Below v  RES EN              E 02 Pulse        YA            EET   Accumulator   Must be Con  m   nected to Point 1 pu   8            Avail    able Input Point   ARTC AnAux      BATI     Input PHASE LOSS MEME                            Wire positive transducer terminal to positive 24VDC supply   Wire negative transducer terminal to odd numbered input terminal   Wire negative 24VDC supply to even numbered input terminal     Place 2500 resistor across odd and even numbered input terminals     Ue uec PE    Set input dip switch down        Pulse Accumulator Output to Input Board    1  Ifthe input board is an 8IO or a 16AI version E 02  or greater  connect the two KWH terminals to the  input point  polarity insensitive    2  Ifthe input board is a 16AI version less than E 02   connect the KWH terminals to board point 1  Set    input switch  1 DOWN  and set network switch TO INPUT  BOARD  318 UP                  3  Setinput dip switch down  2 OW VOLTS  PHASE LOSS       28513086       Table 5 1   Sensor Wiring    5 6  Sensor and Transducer Wiring 026 1102 Rev 4 08 12 99    5 7     Power Requirements    Each board used with the RMCC has specific power re   quirements  These requirements determine how many  boards may be wired to each transformer  Power require   ments for each board on the RMCC network are listed in  Table 5 2
32.    Output number on IRLDS to even  number on 16AI    Common on IRLDS to odd num   ber on 16AI    NOTE  Individual commons  MUST be wired for each point   Gain 1000  Offset 0  Alarm at 4960 mV    Output number on IRLDS to even  number on 16AI    Common on IRLDS to odd num   ber on 16AI    NOTE  Individual commons  MUST be wired for each point   Black to  12V on 16AI  PWR   Green to odd no  on input  GND   Yellow and red to even no  on in   put  SIG    Red to  12V on 16AI  PWR   Black to odd no  on input  GND   Green to even no  on input  SIG     Gain 175  Offset 0  On   20  Off   30    Alarm   15  with  delay of 30 minutes       Appendix     B 1    Voltage  to Typical  P N Sensor Type Settings  207 1000 Refrigerant Lev   L inear Gain 20 Red to  12V on 16AI  PWR   el Transducer Offset 0 Black to odd no  on input  GND    Hansen Probe  Alarm   10  with   Green to even no  on input  SIG   delay of 30 minutes  508 2000 N A Alarm    150 with   Two blk  wires to ACI and AC2  delay of 30 minutes   Two gray wires to input  polarity  insensitive     809 1550 Refrigerant Linear Gain 200 Red to  12V on 16AI  PWR   Xducer Offset 0 Black and Green to odd no  on in   Alarm   250 ppm   put  GND    White to even no  on input  SIG   NOTE  A 16AI board may only  power one Refrigerant Transduc   er  Multiple transducers may be  on one 16AI if external power  source is used     800 1100 Pressure Trans   1 00  Alarm at 20 lbs Red to  5V on 16AI  PWR   800 1200 ducers  Eclipse   2 00  or   above set
33.    Similar to the I O network loop  the host network   shown in Figure 4 2  also uses an open loop configuration   The primary function of the Host Network Loop is to allow  single or multiple REFLECS Controllers to be connected  together to one common 485 Alarm Panel  The Host Net   work is always labeled as COM B on the REFLECS  Input  and output boards cannot be connected directly to the host  network         NETWORK WITH     CPC PES                RUE                 Dv ALARM    PANEL    HOST NETWORK  COM B  26513040    Figure 4 2   RS485 Host Communication Network  COM        4 3  RS232 Remote Communica     tion Network  COM C     The RS232 Remote Communication Network connects  single or multiple REFLECS Controllers to a modem to  provide remote access using a remote communication soft   ware package  In some configurations  an RS232 Bus Am   plifier may be installed to improve transmission rates and    The REFLECS Networks   4 1    overall data quality  Like the host network  input and out   put boards cannot be connected directly to the remote com   munication network  Figure 4 3 shows a typical remote  communication network layout                                REMOTE COMMUNICATIONS  NETWORK  COM C     26513045    Figure 4 3   RS232 Remote Communication Network  COM        m         4 4 1     All CPC I O and host bus communication components   COM A and D  and COM B  have been designed to con   form to RS485 standards  Remote communication compo   nents  COM C  have 
34.    off  or    ON    on   Run Time   The accumulated run time hours of each compressor are    shown in the Run Time field  This value may be cleared at  the Group 1 4 Setup screens     Oil Pres    The net oil pressure  oil pressure reading   suction pres   sure reading  is displayed in the Oil Pres field     H  Power    The horsepower rating of each compressor is displayed  as defined at the Group 1 4 Setup screens     Proof    If a proof input is defined under Input Definitions  Sec   tion 11 8 1   Input Definitions  the Proof field will display              If the compressor proof contact remains open for an  amount of time equal to the Proof Delay  defined in Sec   tion 11 2 3   Group 1 Pressure Alarms Setup   the field will  read    FAIL        System Navigation     13 11    14 Alarms    14 1  Alarm Set Points          ALARM SETPO NTS  Tmp1  i Alarm              i Delay  Lo Alarm  Lo Delay                                    gt  5                 Alarms Notices   99   100   N one   N   Delays  0   999   0     Alarm Control within the RMCC includes the genera        set points  an alarm or notice will be generated  A notice is  a low level warning that creates an entry in the RMCC  Alarm Log and initiates no other signal  An alarm is a high   level warning that will appear in the RMCC Alarm Log and  may be accompanied by a contact closure for on site oper   ation of a bell  light  horn  etc  An alarm may also initiate  an alarm dialout sequence and or the activation of the 4
35.   9 1                                                                                                                                          9 2  94 1   Control Strategies    tod ee ROS ERE        ere eie per                9 2  94 11  t Normal   PID             cero deh eed Pe er Ende Deer tiae cedat ite 9 2  9 412   Fixed Steps                       ee De umen Il ai eg et        E t te had 9 2  94 2  Variable Speed Compressors    eee ote ir o tr e e e I OR ETE ERU RH HOS      bag eet 9 2  9 421    Normal  Strate By  oio odere ette eee tent ne      ee m He                  ie ire      erede de 9 2  9 4 2 2   Alternate  Strategy   ciere etr he ete me oe erbe e                                  gana 9 3  9492 Bloating Set            eet lyon Bee ei eee denter 9 4  9 5   CONDENSER CONTROL    te aca ae ipe oia                                   ee PR HN 9 4  9545  Control StFate BIOS  ei che tte ttt t suede t t ee ttn 9 4  9 5  1 1    Air ClooledCondensetsz   shu et ete e be bt t n e e te d ete e bete al e ette 9 4  975 12  Evaporative  COndensets     eed e deeem oe gene dude ue nee                           9 4  9 5 2                                                          E A ar aa er E E e                 9 4  9 5 2  T   Sinple Speed           eee ee Oe aree reete eo ir              9 5            Ewo  Speed            es riesce             9 5  9 5 2 31  Variabl   Speed  Fans enn e        ERN ERU PIER                 9 5  9 5 3  Operation During                  tiep ee Ide
36.   Black  Yellow  Purple  14 White White White  Red    Table 7 4   Valve Cable Wire Colors    7 7  Power Modules  ize  The case controller power module measures 16 25  inches long by 3 inches wide by approximately 3 25 inches  deep  The base plate has one 0 218 inch mounting hole lo   cated at each corner     Power    The case controller power module should be connected  to a 120 VAC single phase power source  Complete wiring  of the case controller power module is diagrammed in Fig   ure 7 7  Follow all local  NEC  and UL wiring practices    026 1102 Rev 4 08 12 99    DEFROST HOT        DEFROST HOT     j  DEFROST HOT          DEFROST OUT  DEFROST OUT  DEFROST OUT    ANTI SWEAT HOT       ANTI SWEAT OUT       FANS HOT      FANS OUT  NC or NO                 LIGHTS HOT    4 LIGHTS OUT  NC or NO           HOT       LINE  NEUTRAL                OUTPUT CABLE          EARTH GROUND       26513067    Figure 7 7   Case Controller and Defrost Power Module Wiring  Schematic    7 8   7 8 1     Sensor Location    Discharge Air Sensor  Green  Leads     In general  the discharge air sensor should be located in  the air stream leaving the evaporator coil  but just before  the air stream enters the food compartment of the refriger   ated display case     7 8 2  Coil Inlet Sensor  Blue Leads     Proper location of the coil inlet sensor is critical since  valve control is dependent upon accurate measurement of  changes to evaporator liquid temperature  The coil inlet  sensor should be located on
37.   C3        2   1  Dad DOM Cen   used in conjunction with a temperature sensor  If the dew   DEWPOINT HUMIDITY OFFSETS   point cell or relative humidity sensor is known to read high  Dewpoint Offset  000    or low  offsets may be specified in the Dewpoint Offset and  Humidity Offset  000   Humidity Offset fields to correctly calibrate the sensors   Users may enter a value from  20  to 20  or from  20  to  20                T PREV   lt     gt  SET       RMCC I amp O Manual System Navigation     11 21    11 4 9  Anti Sweat Outputs Setup                       2           ANTI SWEAT OUTPUTS SETUP  ON OFF Interval  010 sec                      lt     gt  SET    Heater zone names and the on off interval of the anti   sweat circuit are set up in this screen     11 4 10 Anti Sweat Circuit Setpoints     9  CIRCUIT SETPOINTS    ALL OFF  ALL ON                            during ALL OFF  ALL ON            Anti sweat circuits are controlled by comparing a mea   sured or calculated dewpoint value to a range of dewpoints  defined in the Anti Sweat Circuit Setpoints screen  See  Section 3 5   Anti Sweat Control  for a complete explana   tion of anti sweat control     11 4 11 Anti Sweat Overrides    ANTI SWEAT OVERRIDES  Screen  Override          Name                                                           PREV               lt     gt  SET    Manual and external anti sweat heater bypasses         configured at the Anti Sweat Overrides screen     11 22  Circuit Defrost Control             Al
38.   Circuit  Set Points 2   The field will display either OPN  open  or  CLSD  closed     Demand    The current status of the Demand Defrost Input is dis   played in the Demand field if a Demand Defrost Sensor is  defined at the Circuit Set Points 3 screen  see Section  11 4 20  Circuit Set Points 3   The field will display either  ON or OFF     The Circuit Statistics screen displays daily status infor   mation for both the refrigeration and defrost outputs     Cycl    The total numbers of refrigeration and defrost cycles  initiated during the past seven days are displayed in the  Cycl fields     Run    The total runtimes of refrigeration and defrost cycles  for the past seven days are displayed in the Run fields     see Section 11 4 18  Circuit Set Points 1 through Section  11 4 21  Circuit Set Points 4         1 2     026 1102 Rev 4 08 12 99    11 4 5  Anti Sweat Control Menu     tem   Description      Page         BEC   ANTI SWEAT CONTROL               1 Status 4 Daily Logs s  asad 5 0verrides Daily Logs    Set int    SELECT NUMBER       11 4 6  Anti Sweat Status Menu               1      1             Description Page  2 0utput Status Output Status       SELECT NUMBER       11 4 7  Anti Sweat Setup    2 0utput Setup       SELECT NUMBER       11 4 8  Dewpoint Humidity Offsets    Anti sweat circuits are controlled by dewpoint  Dew   point in an anti sweat circuit   s area may be determined ei               EE EE E ther by a dewpoint cell or by a relative humidity sensor      
39.   Fan Off Delay   B sec       Fast Rec Fan On Delay   sec  Fast Rec Fan Off Delay   sec                   T PREV               gt  SET DATA O MENU    Fan On Delay  0   3600 sec    30 sec      Before the RMCC turns on a condenser fan  it will wait  a number of seconds equal to the Fan On Delay  Enter the  desired value in this field     Fan Off Delay  0   3600 sec    30 sec      Before the RMCC turns off a condenser fan  it will wait  a number of seconds equal to the Fan Off Delay  Enter the  desired value in this field     Fast Rec Fan On Delay  0   3600 sec    6 sec      When the condenser is switched from normal to fast re   covery mode  the RMCC will wait a number of seconds  equal to the Fast Rec Fan On Delay before activating all  condenser fans  Enter the desired value in this field     Fast Rec Fan Off Delay  0   3600 sec    6 sec      When the condenser is switched from fast recovery to  normal mode  the RMCC will wait a number of seconds  equal to the Fast Rec Fan Off Delay before returning the  condenser to normal operation  Enter the desired value in  this field     11 3 5 2  Single Speed Setup Screen 2       CONDENSER SINGLE SPEED FAN SETUP 12 00       Split Enable             Split Type   NE  Force Split in Reclaim    Unsplit to Split Delay    Equalize Runtimes    T PREV                                         gt  SET DATA    Split Enable   Y ES   N O   N     The Condenser Split feature allows the RMCC to re   duce or expand the condensing capabilities of the con
40.   Log Interval 00 00  00  Bypass Norm   Run Time 00000m                            gt  SET DATA    CPC SUCTION STEPPER SCREENS    STATUS    CASE SET POINTS             Case   01 01  Status On   Temp 007 0  Term 000 0    ENT Next tk  Circuit  lt   gt    Board O MENU    12 00   SELECT ITEM   12 00  Circuit number   1   01 SDIC 01c  Enter Item   CIRCUIT  01 STATUS SDIC O1c 12 00   SELECT ITEM   12 00  01 Case Boards O1 cCB O1          Enter Item                    STATUS CCB O1SDIC O1c 12 00  Case Temp NONE Setpoint  25 0  Status on Last Term   0 0  bisch Air OPEN Valve X 30 0  Disch Air OPEN Humidity NONE  Disch Air OPEN Antisw  X 100 0  Disch Air 4  OPEN    ENT Next  lt   gt           t CCLRIE        SETPOINTS CCBH O1 SDIC O1c 12 00  Revision  6 0B2L  Sensitivity   004  Update Rate   006    Asw Hi Limit  060 0  Asw Lo Limit   40 0  Frost Sensor   NO    EV J NEXT       SET DATA                 STATUS CCB O1SDIC O1c 12 00    Frost   SHORT  Refr Leak   0 0  Door Switch  Off   Extra 1         OPEN  Extra 2 Tmp  OPEN    Fan Relay   On  Lights i On                   ALARMS  CCB  OT SDIC O1c 12 00  Refr Leak    NO  Leak Alm Lvl   1000  Leak Alm Dly   010m    Extra          YES  Extra2         YES  Door Alm Delay  015m    4          J NEXT   gt  SET DATA                OFFSETS     8401 5010 01   12 00  Case Offset   0 0 Extra  Imp  0 0  Discharge  1  0 0 Extra2 Tmp  0 0  bischarge 42  0 0 Refr Leak   0000  bischarge 43  0 0  Discharge  4  0 0    EV 4 NEXT   gt  SET DATA               
41.   Manual Override   N ormal   O n   O ff     Normal sensor operation may also be bypassed manu   ally regardless of the Alarm Override Input status  A man   ual override is a fixed ON or OFF override and is activated  in the Manual Override field  To activate a manual over   ride  enter the desired override value in the Manual Over   ride field  The selected sensor will remain in override mode  until the user returns to this field and enters Normal     026 1102 Rev 4 08 12 99    Leave a Notice in Alarm Logs    Y es   N o     The RMCC will record the date and time of each over   ride to the Alarm Log when    Y    is entered in the Leave     Notice in Alarm Logs  field     14 6  Alarm Override Status         Sensor Name  1 LIQUID LEVEL    2 REFR LEAK  3 AMBIENT  4    5    T PREV                The status of all defined Sensor Alarm Overrides         displayed at the Alarm Override Status screen  Alarm  Override Inputs are defined at the Input Definitions screens   see Section 11 8 1   Input Definitions  and are assigned to  a sensor at the Alarm Overrides screen  see Section 14 5   Alarm Overrides   Users may view the Sensor Name that  contains the displayed override  the associated Alarm  Override Input assigned to the sensor  the status of the  override  the type of override defined to the displayed sen   sor  and if currently in override mode  the time remaining  in the override duration     14 7  Send to 485 Alarm Panel    remi    SEND TO 485 ALARM PANEL             YES  CH
42.   Pressing    U    begins the Update command  The update  command is similar to the Initialization command in that it  scans the network for all boards connected to the circuit   However  the update command retains all information that  has already been received and only brings in new informa   tion      S end    Pressing    S    begins the Send command  The RMCC  monitors case controllers and updates its information with  that of the case  Therefore  the set points at the case should  match with the set points at the RMCC  If these set points  do not correspond to each other  users may manually send  the RMCC set points to the case controller by selecting the  Send command     Circuit Assignment    After initialization of the boards  the boards must be as   signed to a circuit by entering the desired circuit number in  the CKT field  When the circuit is defined  the circuit name  and type are automatically displayed in the Ckt Name and  Ckt Type fields  The total number of cases defined to the  circuit is displayed in the  CCB field     Set points defined for each Case Controller Board are  backed up  restored  and copied at the Utilities screen     Backup    Activating the backup feature retrieves the current set  points and setup configuration of one or all Case Control   lers within the circuit  This information is stored within the  RMCC and may be restored to any case with the Restore  feature  To backup a Case Controller  enter the ID Number  of the case to be backed u
43.   Solid State Relay 221 7000  75 VA Transformer 140 0050    Second Valve Kit  without 75 VA Transformer 510 3125      Includes   Discharge Air Sensor  Green Leads  501 1122  Coil Inlet Temperature Sensor  Blue Leads  501 1125  Coil Outlet Temperature Sensor  Red Leads  501 1126       Includes   Discharge Air Sensor  Green Leads  501 1122       Table 6 1   Case Controller Part Numbers    6 2 2  Input and Output Cables    CPC produces a single input cable harness  and three  different output cable harnesses depending on the power  module or valve type being used     The input cable harness  335 3151  is supplied with a  connector for connection to the case controller  and con   nector ends which mate to the temperature sensors supplied  with the case controllers     The output cable harness may be any of three types  The  full output cable harness is supplied without connectors   335 3156  for connection to non CPC power modules  or  with connectors  335 3158  for connection to CPC power  modules  which are supplied with female connectors  A  third output cable harness  335 3159  is provided if a  Sporlan suction stepper unipolar valve is being used     6 2   Hardware Description    Table 6 2 lists the harness configurations and their part  numbers     Description Part  Number    Input Cable   Includes coil in and coil out for 335 3151  one valve  discharge air  defrost termination    suction valve  and network I O communica    tion     Output Cable   Includes lights  fans  ant
44.   The   and Name fields display the sensor number and  the sensor name     Status    If the sensor is controlling an output  and if the output  board and point location is specified at the Output Defini   tions screen   see Section 11 8 2   Output Definitions   the  status of the controlled output  either ON or OFF  will be  displayed in the Status field     13 6  Alarms  13 6 1  Alarm Override Status       ALARM OVERRIDE STATUS    Sensor Name d  LIQUID LEVEL   REFR LEAK    r  0  0  AMBIENT 0  0  0    1  2  3  4  5   P    T PREV                The status of all defined Sensor Alarm Overrides         displayed at the Alarm Override Status screen  Alarm  Override Inputs are defined at the Input Definitions screens   see Section 11 8 1   Input Definitions  and are assigned to  a sensor at the Alarm Overrides screen  see Section 14 5    Alarm Overrides   Users may view the Sensor Name that  contains the displayed override  the associated Alarm  Override Input assigned to the sensor  the status of the  override  the type of override defined to the displayed sen     13 7  Input Output Modules  13 7 1  Analog Input Module Status          29      ANALOG INPUT MODULE  Name        INPUT 01  Command  NONE     NONE     NONE     NONE       1 STATUS    Value  Alarm  Count  Count Tripped NONE  T PREV                Notice  NONE    Users may view the real time status of an Analog Input  Module   s outputs in the Analog Input Module Status  screen  The Value and Count outputs will appear as a
45.   The  kW peak is displayed in the Peak field and the time of the  occurrence is displayed in the Time field     12 1 8  Daily Demand Log          The Daily Demand Log displays a summary of the kW  usage during the previous 24 hour periods  KW usage for  up to 48 days may be logged in the Daily Demand Log  The  date and total kW hours used in the window during the 24  hour period are listed     Peak    The peak power is the highest value of kW measured by  the kW transducer during a specified period of time     Time   The time of the occurrence of the peak power is dis   played in the Time field   Demand    The Demand field displays the cumulative number of  hours the RMCC was in demand during the specified 24  hours     026 1102 Rev 4 08 12 99    12 2  Graphs       12 2 1  Graph Control Screen             12 00    ntimes    ntimes    SE ECT NU BE    Users may view RMCC log data in graphical format  from the Graphs screens  The Graphs menu characterizes  all system logs in six different categories     e Suction Groups   all logs related to pressure control   including suction and discharge and compressor op   eration  but excluding compressor and fan runtimes   see below      e Sensors   the input values for sensors 41 48   e Circuits   all logs for refrigeration circuits 1 48     CCB   all logs for case control boards     e Comp  Runtimes   bar graph of runtimes for all de   fined compressors     e Fans Runtimes   bar graph of runtimes for all de   fined condenser fans     O
46.   boards that are the same type are  numbered together  For example  if a segment contains  four 16AI boards and five 8RO boards  the 16AIs are num              one  two  three  and four  and the 8ROs are numbered  one  two  three  four  and five  Figure 4 9 provides a graph   ic representation of board numbering  Actual dip switch  and rotary dial setup is described fully in Section 5 8 1 1    Dip Switches     BOARD NUMBER  BOARD TYPE    3    4  16AI 8RO   4 5   80                                                                   A NETWOR  COM D NETWOR   26501054    Figure 4 9   Network Device Numbering        12  Baud Hate Dip Switches   COM A and D only          networks  COM A  B  C  D  have specific baud rate  requirements  however  only COM A and COM D require  manual setting of the baud rate dip switch  Currently  the  baud rate dip switch in network components may be set at  either 4800  9600  19 200  and 38 400  Setting of the baud  rate is accomplished using switch S1 on the REFLECS pro   cessor board  the RS485 alarm panel board  and 4AO  8RO   and 8RO FC output boards  and switch 53 on the 16AT in   put board  The COM B baud rate is preset on the REFLECS  and 485 Alarm Panel dip switch S1 at 4800  The 8IO board  automatically adjusts to the required baud rate  Actual baud    4 4   Network Dip Switches and Rotary Dials  COM A and D only        rate setup is described fully in Section 4 14   Baud Rate  Settings     4 13  Network Settings    For all boards  except 8I
47.   how to wire both kinds of liquid level sensors to a 16AI     026 1102 Rev 4 08 12 99    When setting up the probe in the RMCC system soft   ware  specify the probe as a linear sensor with a gain of 20  and an offset of zero  See Section 7 6 2   Setup and Section  7 6 4   Set Points  for Linear sensor types only  for specif   ic software setup instructions     3 9  Leak Detectors    CPC supplies both a refrigerant transducer  809 1550   and Checkit refrigeration system monitor  508 2000  for  monitoring refrigerant leaks  Each is installed by the refrig   eration and equipment manufacturer  If a replacement  transducer or Checkit must be installed in the field  com   plete installation and operation instructions are available in  either 026 1302  Refrigerant Transducer Installation and  Operation Manual  or 026 1303  Checkit Refrigeration  System Monitor Installation and Operation Manual     3 10  Power Monitoring    The current transformer  watt hour transducer  and  transducer power supply are all required to perform power  monitoring  CPC uses standard off the shelf configurations  of each of these products  Installation instructions supplied  with the units should be used for both the watt hour trans   ducer and the transducer power supply  A single current  transformer should be located on each phase of the incom   ing power supply of the motor room     3 11  Transformers    Transformers are required for all input and output com   munication boards and case controllers 
48.   level  the RMCC will turn off all heat producing loads  in   cluding the fans and the anti sweat heaters  This level is de   fined in the Fan  amp  ASW Off field  The 99 default value  disables this feature     Terminate Temp   99     994    The Termination Temperature set point is the tempera   ture at which defrost should terminate if a certain strategy  is chosen     D R Weighting  0   100  0          If the Mixed Air strategy is chosen as the Circuit Tem   perature Control strategy at the Circuit Setup 2 screen  see  Section 11 4 45  Circuit Setup 2  Add Edit Circuit    the  discharge to return air percentage is defined in the D R  Weighting field  Enter in the D R Weighting field the per   centage of Discharge Air to be mixed with the remaining  percentage of Return Air     1st   6th Defrost  Circuit Defrost Times   00 00    23 59     RMCC software version 1 05 will not allow defrost to  begin within 60 minutes after the conclusion of the  previous defrost event     Circuit defrost start times are established in the 1st 6th  Defrost fields  Defrost begins within the selected circuit at  the times defined in these fields  Up to six defrost times  may be defined for each circuit     When programming defrost start times  note that the  RMCC will allow overlapping of defrost times within cir   cuits  Overlapping defrost times may not be appropriate   especially when running hot gas defrost systems     026 1102 Rev 4 08 12 99    11 4 47 Circuit Set Points 2  Add Edit Circui
49.   ulating a sensor value or providing a control command to a  physical relay are grouped together within a Module  A  module may be used alone or combined with other mod   ules  Unlike cells  modules may be connected in many dif   ferent ways depending on the needs of the user     Figure 9 8 provides an example of the relationship be   tween set points  cells  and modules  Set points   such as  the limiting  cut in  and cut out set points shown   are or   ganized into cells  These cells use their set points  along  with the cell   s inputs  to perform certain functions that gen   erate output values  These cells  along with other cells  fit  into the fixed structure of a module  where each cells    func   tions work together  The module may then be connected  via its inputs and outputs to other sensors  output devices   and I O modules in a variety of control applications     026 1102 Rev 4 08 12 99    SET POINTS                Occ  Cut In   30  Occ  Cut Out 20                High Limit 2 150                   Low Limit  0                     Unoc  Cut In   25  Unoc  Cut Out 15    v    ae CELLS  Limiter Cut In Cut Out    High Limit   150      Occ  Cut In   30  Low Limit   0 Occ  Cut Out   20  Unoc  Cut In   25  Unoc  Cut Out   15                                              V    MODULES  Analog Input Module  AVCombiner          Inputs                   Alt Comb       Override                   Limiter     gt                          Filter                   Counter          S
50.  11 2   TI  2 2  Bypass  aoa a EE etre e RS Pe s e EY USERS UM UE E UE OERS 11 3   41 23     Group I Pressure Al  rmsSetup i usc Rot A Hove tatu ed ese eodd 11 3   11 2 4  Pressure Alarms Notices Setup            esee E EE a E EEK EEEE ET EEE EEE oan OE aS 11 5   11 23  CHECKIE Sensor Setup eia oH WEN bae ttg n RI ERREUR 11 5   11 26   Compressor Setup ais isa e t ert                                                               11 5   TIAS Group T SCLup ios fic cares egere ee      qp e nec 11 6   11 26  Pressure Setup nnen          ege ete eet ee e Re trees 11 6   74 29  TWO  Stage System Setup SE ette tte Pre Ee dee 11 7   11 2 10  Group 1 Pressure Set Points    esee nni iet ee               e e rb e pepe esce Ide eee dores 11 7   TE2 M Group  1  Variable S peed  Set Points  set eee rete me rr ee 11 8   11 2 12    Group 1 Floating Suction          eei ise eee detiene pine lettere hee lace iae dere eoe bd eese ees 11 9   11 20137 Group T Strategy Setup  aie ee e UR PUER e EPIRI be ett da 11 9   11 35 CONDENSER CONTROL                    RE E COR GN RITU tI IER            11 10   ALS UL   Condens  r Setups asso er dH t so ter RP RU St 11 10   11 3 2  Condenser Pressure Inputs Setup  Air Cooled  amp  Temp Diff Strategies Only                    cesse 11 11   11 3 3  Condenser Evaporative Inputs Setup              eese eee nene ener nhe entretenir tre enne          11 12   11 3 4  Condenser Fan Delays Setup Jessie tiber ete ie ee Ue teure        Seg          va crecen e 11 12  
51.  11 2 6  Compressor Setup       PRESSURE GROUPS SETUP          Name   Name   Name   Name      Comps   Comps   Comps   Comps                                       gt  5                                                          The RMCC is capable of simultaneously controlling up  to four compressor groups with a total of 16 compressor    RMCC I amp O Manual             cates abnormal system conditions  An alarm is always sent  to the RS485 Alarm Panel and to the Alarm Log  A notice  is a low level warning that also indicates abnormal system  conditions  A notice is sent to the Alarm Log and may be   sent to the 485 Alarm Panel if the RMCC is configured to  do so     To specify which type of alarm is to be generated when  alarm conditions are met  select the desired alarm type for  each suction group at the Pressure Alarms Notices Setup  screen  Different alarm types may be selected for different  groups as well as for different types of alarm conditions   The Pump Down alarm feature defined at the Pressure  Alarms Setup screen  see Section 11 2 3  Group 1 Pressure  Alarms Setup  may also be disabled at this screen     uid levels within the system  The RMCC may be  configured to generate an alarm and or a notice when the  measured Checkit temperature rises to a defined value     The value at which an alarm will be generated is de   fined in the Alarm Setpoint field  The value at which a no   tice will be generated is defined in the Notice Setpoint  field  Delays are defined for 
52.  11 4 20    Circuit Set Poinis 3  iie petere eer RR ERE Rede apt          11 29  1154221  Circuit Set Points F                   CO ERO TIE OR Ute ERR EE CE c Vd 11 29  11 4 22   Circuit Inputs  Setup  ise te om tH tet re te RR Pe ORE Ee eee s 11 30  11 423  Circuit Output Setup    ee eee e aa i ees Ha eta ore ed discos ai pest t e tes 11 30  11 4 24    Advanced Defrost rira egeat ee rto almo oper ei re egeta 11 31  11 4 25  Advanced Defrost Options  Hot Gas                                      erret rennen entente nennen 11 31  11 4 26  Advanced Defrost Options  Electric                                                  eere n enne trennen tenens 11 32  14 4 27   C  se  Controls sine aae             A eU Re ECRIRE BEER ERA ioe 11 32  11 4 28    Circuit Set Points 5    neu eae pedea e rte mH OH OO RT Ree      11 32  11 4 29  CCB Set Point Screen 1  Liquid Pulse and Stepper            11 33  11 4 30  CCB Set Points Screen 1  CPC Suction Stepper            11 33  11 4 31         Set Points Screen 1  Hussmann Suction Stepper Only                 eese 11 34  11 4 32         Set Point Screen 2  Liquid Pulse and Stepper     1                      11 34  11 4 33         Set Points Screen 2  Suction Stepper Only               esses nennen enne           11 35  11 4 34         Set Point Screen 3  Liquid Pulse and Stepper            11 36  11 4 35  CCB Set Points Screen 3  Suction Stepper     1                  eene nennen enne neen nennen 11 36  11 4 36  CCB Set Point Screen 4  Liquid 
53.  16  Unoccupied Setpoint 9   15  9 16  output when in failure 9 16  overriding 9 16  PWM  pulse width modula   tion  9 17  defined 9 8  Digital Output Module 9 12 9   14    cells 9 13  Counter 9 14  Digital Value Combiner  Minimum On Off 9 13  One Shot 9 13  Override 9 13  Proof 9 14  Schedule Interface 9 13  Select 9 14   inputs 9 12  Alt Combiner 9 13  Alt Schedule 9 13  Digital Inputs 9 12    Index    1 4    Occupied 9 13   Proof 9 13  9 14   Reset Count 9 12  9 14   Suspend Count 9 12  9   14    Use Alternate Logic  Combination  9 13  modules  inputs and outputs 9 9    Input Definitions 11 53    Inverter  condenser fan  reset count 11 16  reset delay 11 16  Fincor wiring 5 2  IRLDS  hardware software settings B 1    J    Jumpers    Fail Safe Settings on 8RO 4 5   fail safe settings on 8RO 5 11   lights and fans on case controller  7 2   Terminating Resistance Settings  4 3  4 5   terminating resistance settings 5   12    valve type on case controller 7 2    L    LED Indicator Lights 4 5  5 11  Legs  See Wiring  Legs and Segments     Liquid Line Solenoid  control of 9 6    Logging On 11 2    Logs  anti sweat 12 1  CCB Logging Times 12 2  daily demand 12 2  hourly 11 59  hourly demand 12 2  logging setup 11 59  pressure control 12 1  sensor 12 2  standard circuit 12 1    Low Pressure Hysteresis Cutoff Set   point Removed from Con   denser Setpoints Screen 2  11 17    Manual Defrost  standard circuits 11 23    Modems  initialization strings 11 60  parity data bits 11 60  set
54.  17  Circuit Setup  2   the Control Temperature is the temperature that should  be maintained within the circuit  Degree units are deter   mined by the unit selected at the System Units screen  see  Section 11 8 7  System Units      System Navigation     11 27    Drain Time  0   240 minutes   0     Immediately following defrost  an unacceptable  amount of moisture may still be present on the evaporator  coils  When refrigeration begins  this moisture may freeze  and reduce system performance     Dead Band  0   10   0     A dead band may be established around the Control  Temperature and the Terminate Temperature set points   The dead band is a value equally above and below the Con   trol Temperature set point within which the temperature  level is considered to be acceptable  Establishing a dead  band helps alleviate short cycling of the case expansion  valves during refrigeration and  for certain types of defrost   alleviates short cycling of the defrost heat     Terminate Temp   99     99    0     The Termination Temperature set point is the tempera   ture at which defrost should terminate if Temp is chosen as  the Defrost Termination Strategy at the Circuit Setup 2    11 4 19 Circuit Set Points 2    Eo E        Selected circuits are overridden OFF for cleaning pur   poses based on the configuration defined at the Circuit Set  Points 2 screen  This feature is optional within the RMCC   therefore  default values will not apply to this screen     Cleaning Override Switch   N 
55.  2 6  Com   pressor Setup      Contr  by   T emperature   P ressure   P     Select  Temperature or    P   ressure to determine the  method by which the RMCC will control the suction group  in the Contr  by field     Setpoint   999   999   22 0     The Suction Pressure set point establishes the pressure  or temperature the compressors within the suction group  will maintain during normal operation     Deadband  0   99   0 2     The dead band is the value equally above and below the  set point within which the pressure or temperature level is  considered to be acceptable  This value should be based on  the suction set point to reduce short cycling of the com   pressors     Delays    Changing the compressor delays affects how quickly  changes determined by the PID algorithm are used to  control the compressors and unloaders  It is recom   mended that the delays be set to the default values  3  and 3 for the compressor  and 5 and 5 for the unload   er      Time delays are specified measurements of time the  RMCC must wait before activating or deactivating system  components when a command is received for activation or  deactivation     System Navigation     11 7    Comp  0   240 seconds   3     The Comp Delay is the duration   in seconds   the  compressors will remain off or continue to run when     command is received from the RMCC     Unldr  0   240 seconds   5     The Unldr Delay is the duration   in seconds   the  unloader will delay before turning on or turning off de   pend
56.  5 7   Standard circuit systems control  by dewpoint only  however  this may be supplied either by  a dewpoint probe or by an automatic calculation from tem   perature and relative humidity sensor values  The circuit s  dewpoint temperature is compared to two user defined val   ues  the      Off and      On values     If the circuit s dewpoint is lower than the      Off set  point  all the anti sweat heaters will remain off  If the cir   cuit s dewpoint is higher than the      On set point  all the  anti sweat heaters will be 100  on  If the dewpoint falls  between the      Off and      On set points  the anti sweat  heaters will pulse on and off for a percentage of a user de   fined time window  1 999 seconds   The percentage of  time in which the heaters will be on depends upon where  the circuit s dewpoint falls between the range of dewpoints  formed by the      Off and      On set points  The percent   age is figured by using the following equation     Figure 9 7 illustrates the operation of an anti sweat cir   cuit with a time window of 10 seconds  an All Off dewpoint  of 20  F  and an      On dewpoint of 70  F  If a dewpoint of  45  F is measured in the circuit  the anti sweat heaters will  operate at 5096  This is because the 45 F dewpoint is direct   ly between the      On and      Off set point  The heaters   therefore  will be on for five seconds and off for five sec   onds  A measured dewpoint of 30 F will result in the heat   ers being on 20  of the time     TALL 
57.  50  however  would  open only half of that distance at the end of the control  loop   from 50  to 5596  Similarly  an EEV with a valve  filter value of 25 would open to 52 596     from 50  to 60   an EEV with a valve filter rating of 100    Type Default Min Max Description  Value    Case Temp From    a a   a Method of calculating case temperature  disch Air  return air   mixed      Mix  Dsch 0    100  The weight given to the discharge air if    mixed    is selected     Dead band 0 1  F   10 0  F Dead band around case temp set point   Case   Case Offset      99  F  99  F   99  F Varies a   Varies a single case temp from the circuit case temp set point    case temp   Varies a single case temp from the circuit case temp set point    the circuit case temp set point     E Rate Set point EM 255 Determines how fast the valve will close when the case tem   perature set point is reached    Valve Filter 10096 0    100  Reduces the valve opening value supplied by the PID algo   rithm     Table 8 2   Liquid Side Temperature Control Parameters       Suction Side Control controlled  The case temperature is being monitored  and  the suction valve percentage is controlled via a suction al   gorithm to maintain the set point  The suction side param     eters are shown in Table 8 3     The case controller controls case temperature from the  suction side of the evaporator by controlling the valve  opening percentage of the suction valve to regulate the suc   tion pressure  In suction side cont
58.  7 2  Refrigeration System Temperature Probes        Sensors             eee eene ener nennen nene 3 6  3 8  PUD EVEL  SENSORS  sU ERE ETUR EY GU ER RERO Te ER ERE A EE KE EET ERE              3 6  3 9                              iere tec Eco             e ven eive rie cere cv eec vies terres 3 7  3 10   POWER  MONITORING a        yn sete loves snl ck petite pe                          a e RE           EXER Ne Ux 3 7  3 11    ZTRANSFORMERS    etit nene                3 7  4 THE REFLECS                        eei coo aorta eoo datar to bas ee sonia boe apos Ia panini ena ea Dua osos sona deoa a enun ten eios aes us eoe snos pn             4 1  41  RS485 INPUT OUTPUT  I O  NETWORK  COM    AND                              000200000000000000000000000000000000000 enn nennen 4 1  4 2  RS485 HOST                                                                           n e deed eed ee eec    ees 4 1  4 3  RS232 REMOTE COMMUNICATION NETWORK                                                         4 1  AAs WIRING 2                        diee ie pter                                   EE bed 4 2                                                            4 2  4 5   EBGS AND SEGMENTS                                                                                te dee 4 2  4 6  LEG AND SEGMENT WIRE LENGTH           ccsssssssccossssccccessnsncccecensnneccececenneesccecenneeecesceeneeecescesseeseesesssseeesescsenseesecesenee 4 2  4 7  NUMBER OF DEVICES PER SEGMENT         ccccsssscccesesss
59.  75    40 0     When the Anti Sweat feature is activated in the selected  circuit at the Circuit Setpoints 2 screen  see Section    11 4 47  Circuit Set Points 2  Add Edit Circuit    the anti   sweat heater range for each case is defined in the Asw Hi  and Lo Limit fields  If the humidity is higher than the ASW  Hi Limit  the anti sweat heaters will remain on at all times   If the humidity is lower than the Asw Lo Limit  the anti   sweat heaters will remain off at all times  Between these set  points  the anti sweat heaters will cycle in a six second win   dow according to the humidity level     Frost Sensor   Y es   N o   N     If a Demand Defrost Sensor is installed at the selected  case  enter  Y es in the Frost Sensor field  Demand Defrost  set points may then be defined at the Circuit Setpoints 3  screen  see Section 11 4 48  Circuit Set Points 3  Add Edit  Circuit       11 4 31 CCB Set Points Screen 1  Hussmann Suction Stepper Only                                   CCB SETPOINTS CCB 01 SDIC O1c  Revision  6                 Asw Hi Limit               Asw Lo Limit    Frost Sensor            T PREV J NEXT   gt  5                 Asw Hi Limit  25   100   60 0  Asw Lo Limit  0   75    40 0     When the Anti Sweat feature is activated in the selected  circuit at the Circuit Setpoints 2 screen  see Section       11 4 47  Circuit Set Points 2  Add Edit Circuit    the anti   sweat heater range for each case is defined in the Asw Hi  and Lo Limit fields  If the humidity is higher
60.  8 1         put Definitions     Sensor Open An open circuit has been detected at a sensor input connection  SENSO1   SENS48   see Section  11 8 1   Input Definitions      Table 14 1   RMCC Alarm Log Notice and Alarm Messages       RMCC I amp O Manual System Navigation     14 7    15 Hand Held Terminal  Screens    The operational status and settings of a Case Control  Board may be viewed or changed by using a CPC hand   held terminal  HHT   When an HHT is plugged into a  CCB  users may access a series of screens that display de   frost  anti sweat  case light  override  door switch  and  valve status information  Certain control parameters  such  as offsets  set points  and dead bands  may also be changed  in these screens  The HHT may also be used to initiate  manual defrost overrides and to manually bypass case  lights     The UP and DOWN keys on the HHT keypad are used  to scroll through the screens  The DOWN key scrolls for   ward through the screens  and the UP key scrolls backward   The screens wrap around  therefore  users may jump from    RMCC 1 amp 0 Manual    the last screen to the first screen by pressing DOWN  or  from the first screen to the last screen by pressing UP     Some screens will have fields that may be changed us   ing the HHT  To change the value in a field  press the  RIGHT arrow key  A cursor will appear in the screen next  to the first changeable field in the display  Use the UP and  DOWN arrow keys to move the cursor to the desired field   and ent
61.  AC Power Input Connection        Network Connection   LED Power Indicator   Termination Resistance Jumpers  Address and Baud Rate Dip Switch    Fail Safe Dip Switch   Output Connection  8 places   Relay Fuses  8 places    LED Relay Indicators  8 places                       26501017    Figure 2 5   SRO FC Relay Output Board with Form C Contacts    Hardware Overview     2 3    2 3 3  4     Analog Output Board    Three 4AOs may be connected to an           through the RS485 COM A and D networks     The 4     Analog Output Board  Figure 2 6   is config   ured with four analog output connections that provide a  variable voltage signal to any of four variable speed devic   es that may be controlled by a single REFLECS           L    LJ        4  2                 eg    DOO       AC Power Input Connection   I O Network Connection   LED Power Indicator  Terminating Resistance Jumpers    Address and Baud Rate Dip Switch  Analog Outputs  4 places   Divider Circuits  4 places                    Figure 2 6   4     Analog Output Board  2 3 4  8DO Digital Output Board    Up to two 8DOs may be connected to an RMCC  through the RS485 COM A and D networks     The 8DO digital output board  Figure 2 7  is similar to  the SRO board  except that instead of a relay that closes on  and off  each output generates either a high  12VDC  or  low  OVDC  signal  The 8DO has eight outputs which may  pulse up to 150mA at 12VDC  The 8DO s primary func   tions are to control anti sweat heaters     2 4   Sp
62.  Alarm Panel is not con   nected to the RMCC through the COM B Host Net   work     The host network is  by default  not active within the            If one or more RMCCs are connected to a 485  Alarm Panel  then the host network should be reset ON at  the Reset screen   1  Off   2  Reset On   1      026 1102 Rev 4 08 12 99    To reset the host network ON within the current RM   CC  select    2    for Reset ON at the Reset screen     11 8 19 Host Inputs    K J    7  8      HOST NETWORK       12 00    Send all CCB Leak Detector Input data    on the Host Bus  N                11 8 20 1    Board Setup       1 0 BOARD MENU    1 ONLINE Status  2 Set Device   s    3 Reset       Each CCB has a single input that may be connected to  a leak detector  If desired  CCBs can send data from the  leak detectors to the RMCC over the Host Bus Network  To  enable this feature  enter a  Y  in this field     Tem           Description         ase        11 8 21 Set Device Numbers       1 0 BOARD DEVICE NUMBERS    Number 8  0 Boards MAX    Number 16AI Boards MAX    Number         Boards MAX  Number 8  0 Boards MAX    T PREV              gt  5        Each RMCC supports up to 16 8     Boards  up to eight  16AI Boards  up to three 4AO Boards  and up to two 8DO  Boards  To define the number of boards connected to the  RMCC  enter this number in the corresponding fields at the  Set Device Numbers screen  Defining these numbers al     RMCC I amp O Manual       lows the RMCC to calculate the number of boa
63.  Circuit  lt     The first Case Controlled Circuit Status screen displays  the current number of CCBs within the circuit  the selected  case number  the current case status  the current case tem   perature  and the last recorded termination temperature     Case Boards    The number of CCBs within the selected circuit is dis   played in the Case Boards field     Case      The assigned case number of the selected case is dis   played in the Case   field  The number lists first the circuit  number followed by the case number     Status    The status of the selected board is displayed in the Sta   tus field  One of the following conditions will be displayed     e On      selected board is calling for a stage of re   frigeration     e Off  the selected board is not calling for a stage of  refrigeration     RMCC I amp O Manual             dewpoint value to the anti sweat set points  and pulsing the  heaters on and off for a percentage of the on off interval   defined in Section 11 4 9   Anti Sweat Outputs Setup  The  fields in the Anti Sweat Status Screen show the current sta   tus of the pulse  either ON or OFF  and the time remaining  before the next status switch     For example  if a heater is operating at 5096 during an  interval of four seconds  the Status field for that heater will  show ON for two seconds and OFF for two seconds  Every  time the Status field changes  the Time Left field will reset  to two seconds and count down to zero     If a heater is being overridden ON
64.  DOWN arrow key scrolls through the daily  logs in reverse chronological order  pressing the UP arrow  key scrolls through the daily logs in chronological order              The average daily ON time percentage for the anti   sweat circuit is shown in the  ON field     Max Min  DP     The highest and lowest daily dewpoint values for the  anti sweat circuit is shown in the Max Min  DP  fields     12 1 4  Standard Circuit Log           fa  ce         99    IT LO S  00           DFJ 01 TR       The RMCC continuously logs circuit information ac   cording to circuit input and output logging intervals and  stores the information in the Standard Circuit Log  This log  and all options for generating graphs from the logged infor   mation is displayed at the Logs Graphs screen  When  9    Graph is selected  the logging information is displayed in  graphical form  For information on navigating through and  using the graph screens in the RMCC  see Section 12 2   Graphs     System Navigation     12 1    12 1 5  CCB Log Interval          015                                The RMCC periodically records sensor readings and  stores the information in the CCB Logs for each sensor   The Logging Interval defines how often the data for each  sensor are recorded  The interval range is between 0 and  99 99 99 and is entered at the CCB Logging Times screen   There is a limited amount of memory for logging  there   fore  the smaller the logging interval  the faster the logs will  be overwritten  The 
65.  ITEM   12 00   SELECT ITEM   12 00    SELECT ITEM   12 00   SELECT            12 00  ALARM OVERRIDE STATUS 12 00 SHUT OFF SCHEDULE 12 00 ANALOG INPUT MODULE 1 STATUS 12 00    Name Status Value CI co 01 SENSO 06 SENSO6 SENSO1 01 SENSO1 06 SENSO6 01 SENSO1 06 SENSO6   Sensor Name Ovrd St_ Type Time SHUT OFF TIME Name        INPUT 01   0 LIQUID LEVEL OFF OPEN o 0 02 SENSO2 07 SENSO  SENSO 02 SENSO 07 SENSO  02 SENSO2 07 SENSO  1 LIQUID LEVEL oO OFF FIX 00 00 FROM UNTIL Command  NONE   P          LEAK OFF 004    0 03 SENSO3 08 SENSO8 SENSO3 03 SENSOS 08 SENSO8 03 SENSO3 08 SENSO8 2 REFR LEAK 00 OFF FIX 00 00 day time day time Value NONE   D AMBIENT OFF 56 7 31 0 65 0 04 SENSO4 09 SENSO SENSO4 04 SENSO4 09       509 04 SENSO4 09 SENSO  3 AMBIENT 00 OFF FIX 00 00     00 00     00 00 Alarm NONE Notice   NONE   d 05 SENSOS 10 SENS10 SENSOS 05 SENSOS 10 SENS10 05 SENSOS 10 SENS10 4 00 OFF FIX 00 00       00 00 Count _              5 Enter Item  5 00 OFF FIX H   Count Tripped NONE       Arrows to Move  ENT PREV         EXT MEN                                                             SENSOR SETUP 12 00   SENSOR SETPOINTS 72 00   BENSOR ALARM SETPOINTS 12 00  SENSOR LOGS 72 00  ALARM OVERRIDE SETPOINTS 12 00  ANALOG OUTPUT MODULE 1 STATUS 12 00  3 01 Status OFF Name    01           Temp Eng Unit  No  03_           AMBIENT DATE TIME     TEMP   3 AMBIENT No   01 Name zAV OUTPUT 01  Type  Temp Control Using Diff of D1 700      00 Type  Temp Eng  Unit dF 07 18 13 50 85 7 106  O OF 682 Di
66.  LUE          GREEN  ORANGE          POWER  MODULE    24 VAC 1   ANTI SWEATS CONTROL  LIGHTS CONTROL   CCB GROUND   24      2   DEFROST CONTROL  FANS CONTROL       BROWN                RED                PURPLE                         WHITE   WHITE  BLACK YELLOW  PURPLE RED  BLACK        2099oo39o             S        ER  zo       mm             STEPPER MOTOR 2  STEPPER MOTOR 1  STEPPER MOTOR 4  STEPPER MOTOR 3                      QOOOOOOOOCOQOQOOOOOA                          09060          26513024    Figure 7 6   Sporlan Stepper Valve Output Cable Harness  335   3159  Schematic Diagram    Full Output Cable for Alco ESR Valve    The CCB is designed to use the 24 V version of the  Alco ESR Valve  The 24 V version of the valve has   24VDC appended to the part number  The ESR valve har   ness from Alco comes in two versions  with an in line  molex connector  the CPC harness  P N 335 3159  can be  used  If the valve is purchased with the in line molex  the  CPC Output Cable Harness with Quick Connects  335   3158  must be used  The connector must be cut off of the  harness and the valve wired according to specifications in  Table 7 4     Table 7 4 shows the relationship between the CPC out   put cable colors and the associated valve cable colors     7 4  Power Modules       Sporlan  ALCO SEI  ESV Liquid  Liquid Stepper  Stepper  S EEV     S EEV  CDS  CPC Unipo  EEPR  Wire lar Bipolar  Color  24V   12V     Ew      me  me     _                  Bu  Gren    Black  13 Black Black  
67.  Manual Defr  Manual Term  Ovrd Ac   tive  Ovrrd  Phase Fail  Phase Restored  Power  Failed  Power Restored  Proof Fan  lt 99 gt   Proof  Failure  Pump Down  RM Level  lt 999 gt  Login  Re   set  Run Proof  Sensor Open  Sensor Short  Set   points Corrupted  Setpoint Restore Error  Xducer  Open  Xducer Short  alarms     The Miscellaneous alarm type also includes all Hi  and Lo alarms generated by Analog Input Modules     Temperature Unit  Deg C  Deg F   Deg F     Temperature units may be shown in degrees Celsius or  degrees Fahrenheit  For degrees Fahrenheit enter an            For degrees Celsius enter a              Pressure Unit   P  PSI   B  BAR   P     Pressure units may be shown in PSI or Bars  Pressing           while in the Pressure Unit field will display pressures  in PSI  Pressing          while in the Pressure Unit field will  display pressures in Bars     Date Format   0  Month Day   1  Day Month   0     To display dates in the month day year format press    0     while in the Date Format field  To display dates in the day   month year format press    1    while in the Date Format  field     Change Baud Rate when dial to   3 00   1 200    2 400   9 600   9     The baud rate of the dialout modem is specified in the  Communications Setup screen shown on Section 11 8 10   Communications Setup  The baud rate specified in the  Communications Setup screen is the default baud rate used  when the RMCC dials out  If the device receiving the dia   lout cannot read data at t
68.  O Network Status screen displays the total num   ber of CCBs connected to the network  and the number of  these boards that are on line  Refer to Board Circuit As   signment on Section 11 4 52   Board to Circuit Assignment  for detailed network status information     13 2 5  Host Network Status    n     ost Net State   ON  Number Offline   O       RMCC 2          3 485A 1             The Host Network Status screen displays the status of  the Host Network  No modifications to the network may be  made from this screen     Host Net State    The Host Network Status screen will not display the  status of the controller currently being used     The status of the host network is displayed in the Host  Net State field  If the network is defined properly on each  controller  this field should read OK  If the network is im   properly configured  this field will read Reconfigure  Fi   nally  if the network is reset OFF  the field will read OFF     If the field reads Reconfigure  there is a problem with  the configuration of the hardware  For more information  about hardware configuration  see Section 5  Hardware  Overview     System Navigation     13 3    13 3  Circuits  13 3 1  Circuit Status       CIRCUIT STATUS 01  Refr Defr  Stats OFF OFF       Status  Refr    LstChg 00 00 00 00  0 0    1              1      The first Circuit Status Screen displays the circuit  cir   cuit status  sensor input information  and output status in   formation     Stats    The current Refrigeration and D
69.  Off  D R Weighting  4th Defrost                            Terminate Tem  1st Defrost  2nd Defrost  3rd Defrost                         5th Defrost  6th Defrost      gt  SET DATA                            T PREV                Set points for controlling each refrigeration circuit are  defined at the Circuit Setpoints screens  All case controls  assigned to the selected circuit will be controlled by these  defined set points     Defr Duration  0   240 minutes     The Defrost Duration is the maximum amount of time  the selected circuit should remain in defrost  If no Termina   tion Type is defined or if termination conditions are not  met  the circuit will remain in defrost until the defined De   frost Duration is complete     Control Temp   99     99       The Control Temperature is the temperature that should  be maintained within the circuit  Degree units are deter   mined by the unit selected at the System Units screen  see  Section 11 8 7  System Units      Drain Time  0   240 minutes     Immediately following defrost  moisture may still be  present on the evaporator coils  When refrigeration begins   this moisture may freeze and reduce system performance   To establish a drain time  which is the duration after defrost  the system sits idle before returning to refrigeration  enter  a value between 0 and 999 seconds      the Drain Time field     11 40  Circuit Defrost Control       Fan  amp  ASW        50     99       When the temperature within the case exceeds a certain
70.  PAGE    Continuslly try to Clear FailurezNO  Num Clear At       CONDENSER 2 5         FAN FAIL SETUP 12 00    Try Other Speed On Fan Fail NO    tempts                Delay Between Clear Attempts  0030       i Continually try to Clear Failure no  H t            RMCC I amp O Manual Appendix D   0 1       CIRCUIT CONTROL 12 00    Standard Circuit    2  Case Control       3  Circuit Summary  SELECT NUMBER       ENU       CIRCUIT CONTROL 12 00  1 Status 6 Logs Graphs  2 8et Points f Summary  3 Anti Sweat BlLight Schedules   amp iAlarm Set Points 9 Setup  5 Manual Defrost                                                                         12 00 12 00   RNTI SWEAT CONTROL 12 00 MANUAL MODES 12 00 12 00 IRCUITS STATUS 12 00  Std Circuit number  1  Std Circuit number  1  Std Circuit number  1  01        02 Rfr Std Circuit number   1  NAME STATUS TMP Lite Group number   1  Std Circuit number  1   1 Status    Daily Logs 03        04 Rfr     2 8etup 5 0verrides 05 Rtr 06 Rfr  3 5etpoints 07        07  09 Rfr 10  11        12                              as ENT                                CIRCUIT STATUS 01 12 00 FCIRCUIT SETPOINTS    1 12 00 ALARM SETPOINTS 12 00   SELECT ITEM 12 00 SCHEDULE 1  CIRCUIT SETUP   1 1  Refr Defr Defr Duration 000 Control Temp 000 0 ALARM NOTICE 01 MDF J 01 TR From Until Event  Stats OFF OFF Status  Refr Drain Time 000 Dead Band 000 0 Hi Alarm  NONE NONE loz MDF J O2 TR 00 00 00 00 Case Type   000      SPARE  LstChg 00 00 00 00 Terminate Temp 000 0 Hi 
71.  PID percentage is recalculated at a constant rate  called the  update rate  usually every 2 6 seconds      9 2     In order to set up a system that uses PID control  several  constants and parameters must be specified  However   most of these constants are pre configured with default val   ues that do not need to be adjusted  The two values that  must be set up for all PID systems are the PID set point and  the throttling range     Programming PID    The PID set point is the desired value of the control in   put  PID control constantly changes the PID output per   centage in an effort to make the control input equal to the  PID set point     Throttling range  sometimes called the    throttle range    is a band of values surrounding the PID set point  The pro   portional part of the PID output is determined by where the  PID input falls within the throttle range  a more detailed  explanation is given below in Section 9 3   How PID Con   trol Operates      RMCC I amp O Manual       9 3     Most of the PID output percentage is determined by the  proportional part of PID control  which is determined by  comparing the input to the set point and throttling range  A  simplified illustration showing how proportional mode  works is given in Figure 9 1     How PID Control Operates    THROTTLING  RAN    OUTPUT AT    SETPOINT     shown here as 50            26512028    Figure 9 1   PID Proportional Mode Diagram    When the control input is equal to the PID set point  the  proportional p
72.  PL    16Al 8RO 8BDO BOARD    WEIGHT  0 50 LB     26501055    Figure 3 6   16AI 8RO 8DO Mounting Dimensions  8RO Form C Boards Without Enclosures Mountin       The 8RO Form C board is slightly larger than the 16AI  and 8RO boards  and is not supplied with a snap track  If  the SRO FC is supplied without an enclosure it is supplied  with 500 inch long metal stand off dowels which are    Hardware Mounting     3 3    pressed into the mounting holes in the board  Figure 3 7  shows the mounting dimensions for the 8                 i M2 0 156   i  TYP6PL    8RO FC BOARD    WEIGHT  0 50 LB     26501019       Figure 3 7   SRO FC Mounting Dimensions  8lOs Without Enclosures Mounting    810 boards not supplied with an enclosure are supplied  with 500 inch long metal stand off dowels that are pressed  into the mounting holes in the board  Figure 3 8 shows the  mounting dimensions for the 8IO Board        Figure 3 8   SIO ARTC Mounting Dimensions  4AO Boards Without Enclosures Mounting    4     boards not supplied with an enclosure are supplied  with a snap track for easy installation  The insulation sheet  and I O board must be removed from the track  and the  track mounted using the 1875 inch mounting slots  Figure  3 5 shows this installation procedure for 16AI and 8RO  boards  Installation for the 4AO board is identical  Figure  3 9 provides mounting dimensions for the 4AO board     3 4     485 Alarm Panel       TYP 4 PL    4AO BOARD  WEIGHT  0 50 LB     26501009    Figure 3 9   4AO 
73.  Pressure Set Points    21116     GROUP 1 PRESSURE SETPTSCENA LED   CONTROLLED Y   PRESSURE  SETPOINT   22 0  DEAD AND    00 2 T  MIN TIME   ON OFF T D   COMP 000 5  0005     UNLD  0005  0005    T PREV                                        DISCHARGE  P                                 5                        gt  SET DATA O MENU    Variable Speed Set Points       GROUPS VARIABLE SPEED SETPOINTS    Off on  Failure  N    N  N    12 00    band                                                                         Variable speed compressors for RMCT suction groups  are configured using this screen     Deadband  0   99   5 0     The Deadband value is subtracted from a group s Suc   tion Setpoint to determine the pressure below which all  compressors will be shut off  For example  if the Suction  Setpoint is 25 and the Deadband is 5 0  all compressors will  shut off when the suction pressure goes below 20  Off de   lays will still be applied     RMCC I amp O Manual          This screen is similar to the RMCC Group 1 Pressure  Setpoints screen shown in Section 7 3 13  However  the  Strategy field is not present  since the RMCT uses only the  Normal strategy     Also  RMCT suction groups have no ON and OFF de   lays  instead  the RMCT uses minimum ON and OFF  times  The Min Time Off and Min Time On fields are in the  lower left corner of the screen  0   240 sec   0 sec         compressors and unloaders in the group must remain on for  the Minimum Time On duration and must remain off
74.  RED                    C99 02          C9                          EARTH GROUND  7          DEFROST TERMINATION                                             9    O        90  OG  OY   90       eo                         SUCTION VALVE OUTPUT  SUCTION VALVE OUTPUT RETURN  RS485                  PULSE EEV     gt  lt   422 BLACK    YELLOW                2000000000000009                             CABLE SHIELD         OOODODODOOOOOQOOQOOO                         RMCC I amp O Manual Appendix E   E 1    Appendix F  Wiring for Case Controller  Power Module  Defrost Module  and Sporlan EEPR Valve                                                                         335 3159      BLUE          GREEN       ORANGE          BROWN                RED                PURPLE                      DEFROST HOT an DEFROST OUT  DEFROST HOT    DEFROST OUT  DEFROST HOT n DEFROST OUT  ANTI SWEAT HOT    ANTI SWEAT OUT  FANS HOT a  eee FANS OUT  NC or NO   LIGHTS HOT 7v mc LIGHTS OUT  NC or NO   OO  Qe  HOT      n 3E       NEUTRAL              8          8    8     EARTH GROUND                      RMCC I amp O Manual    WHITE          WHITE       BLACK YELLOW       PURPLE RED                       BLACK                   SPORLAN EEPR GREEN   BIPOLAR  RED  WHITE   BLACK          OOO       OOO                                                                                                                                                                                                                    
75.  RMCC  Status screens available before logon include the  following     e Suction Group Status  Section 13 9 2   Suction  Group Status       Condenser Status  Section 13 1 1   Condenser Sta   tus       Sensor Status  Section 13 5 1   Sensor Status       Circuits Status  Section 13 3 1   Circuit Status  or  Section 13 4 1   Case Control Circuit Status     A complete explanation of what information is avail   able at each status screen is available in the applicable sec   tion     13 1 1  Condenser Status                CONDENSER STATUS   Discharge  Current    Setpoint 200   Reclaim  OFF       12 00  PRESSURE    Ambient  Ki  F1 F2 F3 F4    The Condenser Status screen displays the current status  of each defined condenser fan  In addition to each condens     RMCC I amp O Manual       er fan s ON or OFF status  users may view the current dis   charge temperature or pressure reading  the current  discharge temperature or pressure set point  and the current  reclaim status     Discharge    The Discharge field displays the discharge sensor s  current reading  the defined discharge set point  and wheth   er the discharge is being controlled by temperature or pres   sure  If any of these values are undefined  a line of periods  will be shown in the field     Ambient    The Ambient field displays the current outside temper   ature reading  If the RMCC receives no reading from an  outside temperature sensor  a line of periods will be shown  in the field     Reclaim    The Reclaim field 
76.  SETPTS      8 07 5010 01   12 00  Valve Multplier   100  Combine Type           Derivative Gain   0 0      gt  5                       STEPPER STPTS CCB 01 SDIC O1c 12 00        Valve Type UniPolar Stepper  Hysteresis   005  Steps per Sec   100    Maximum Steps Open  2500             LIQUID STEPPER SCREENS    STATUS    CASE S    ET POINTS       Circui    t numbenr  1     a                  12 00      SELECT ITEM    01 SDIC 01c    Enter Item        12 00       CIRCUIT  01 Cas  Case    Status  Temp  Term                       01 STATUS SDIC O1c  e Boards   01 01   On   007 0   000 0    t                       lt   gt                  12 00    O MENU                 STA    Case Te  Status   Coil In  Super H  Humidit    ENT Nex    TUS CCB 018DIC 01c       mp 007 0 Setpoint  on Last Term    005  Valve X   eat  008 0 Setpoint   y X           Antisw  X    1  lt   gt                12 00     025   000 0  100 0  008 0  100 0       T PREV 1             ICCB SETPOINTS CCB O1SDIC O1c 12 00  Supht Setpnt   8 0 Revision  6 082  Sensitivity 4   Recovery   070   Max Revy Time  000   Asw Hi Limit  060 0          Lo Limit   40 0 Frost Sensor  NO                 STA    Disch     Return                  Coil In  Coil Ou    TUS CCBHOTSDIC O1c              007 0 Setpoint   Air OPEN Valve  amp    at   008 0 Setpoint    005       003 0    ENG a    12 00    epe yy  100 0  008 0          ALARMS   0  Coil 1 In    Coil 1 Out  Cort A Im     Coil 2 Out        T PREV 1                       SET DATA Q MEN
77.  Set Points 1 screen  see Section 11 4 46   Circuit Set Points  1  Add Edit Circuit   and is the temperature the RMCC will  maintain in the circuit     Status    The status of the selected CCB is displayed in the Status  field  One of the following conditions will be displayed     e On  the selected case board is calling for a stage of  refrigeration     e Off  the selected case board is not calling for a stage  of refrigeration     e Def the selected case board is calling for a stage of  defrost       Lost   the selected case board cannot be found with   in the defined circuit     Last Term    The temperature at which defrost was last terminated  within the selected case is displayed in the Term field     Coil In    The current Coil In Temperature of the selected case is  displayed in the Coil In field     Valve      When operating an Electronic Expansion Valve  EEV    the current valve percentage is displayed in the Valve    field     Super Heat    The current superheat calculation for the selected case  is displayed in the Super Heat field  The term    superheat     is referring to the temperature differential across the evap   orator coil  coil outlet   coil inlet      Setpoint    The current Superheat Set Point defined for the selected  case is displayed in the Setpoint field  This set point is de   fined at the CCB Setpoints screen  see Section 11 4 29    CCB Set Point Screen I  Liquid Pulse and Stepper Only     The Superheat Set Point is the superheat value the RMCC  w
78.  Support in the Dual Temp  Shift Input field if a dual temperature case is defined within  the circuit     System Navigation     11 29    11 4 22 Circuit Inputs Setup                  9  a        CIRCUIT INPUTS SETUP  Input Name   Location                                Log Interval   Bypass   Sensor Type   Offset                                         T PREV               gt  SET DATA O MENU    All Temperature Control  Defrost Termination  Clean   ing Switch  Extra  or Dual Temp   and Demand Sensor in   puts defined within the RMCC are configured at the Circuit  Inputs Setup screen  This screen will display only those  sensors defined at the Circuit Setup screens and only appli   cable fields will be active     Input Name    The name of the defined sensor to be configured is dis   played in the Input Name field     Location  BB PP  BB   Board  PP   Point     The board and point number on the 16AI board where  the selected sensor is located is defined in the Location  field  The network address of the 16AI board is defined by  a network dip switch on the board  Enter this number in the  first Location field  Each defined sensor is physically con   nected to a specific point on the 16AI board  This number  is printed on the board above the input connection  Enter  this number in the second Location field     11 4 23 Circuit Output Setup    ror ml    CIRCUIT OUTPUTS SETUP  Output Name  Location                                  Log Interval  Bypass  Run Time                    
79.  Switch Settings    4 15  Fail Safe Dip Switch Settings    CPC uses two fail safe devices on its output boards  a  dip switch and jumpers  These two devices are used to pro   vide fail safe operation of equipment in the event of either  power loss or network communication loss  The use of these  devices differs depending on the board or controller     Boards using Form C contacts do not have fail safe de   vices  since the contacts are wired for the position required  during power loss  but have a dip switch which illuminates  the LED relay indicator depending on the contact position     The 8RO has both a fail safe dip switch  S2  to force the  contacts open or closed if the network fails  and a jumper for  each output  JU4 through      1  that forces the contact open  or closed during a power loss  Figure 4 13 shows the possi   ble settings for the dip switch and jumpers     SWITCH 1 AND JUMPER JU4 FOR RELAY 1          THE SWITCH SETTING SHOWN  ALLOWS THE RELAY TO CLOSE ON       LOSS OF COMMUNICATION  THE 1  JUMPER SETTING ALLOWS THE RELAY    TO CLOSE ON A POWER LOSS                          oh EINER                                                    S2 FAILSAFE Noo           2  THE SWITCH SETTING SHOWN DEG NEUEN    ALLOWS THE RELAY TO OPEN ON N   N O  T       SWITCH 2 AND JUMPER JUS FOR RELAY             LOSS OF COMMUNICATION  THE    JUMPER SETTING ALLOWS THE RELAY                  OPEN ON A POWER LOSS     S2 FAILSAFE NCD  JUS                      SWITCH 3 ANI U6 FOR RELAY
80.  TTI3 5  Condenser Single Speed Setup SCreelis                   ER a E Eee pt repe terere gera 11 12  11 3 5 1  Single Speed Setup Screen 1      E    11 3 5 2  Single Speed Setup Screen 2      es ae ee  11 3 5 3   Condenser Fan  Fail Setup    iet tere eee e ere Ed em  11 3 6  Condenser Two Speed Fan Setup               sese eee nennen Sea Ee entes nete nene eene 11 14  11 3 6 1  Two Speed Setup Screen 1  11 3 6 2  Two Speed Setup Screen 2 m  11 3 6 3  Condenser Fan Fail Setup                           11 3 6 4  Condenser Two Speed Fan Fail Setup  11 3 7  Variable Speed Set  p Screens    e e o      e                        XO E Ve e ones  11 3 7 1  Condenser VS Fan Setup  11 3 7 2  Condenser Fan Fail Setup  11 3 7 3  Condenser VS Fan Fail Setup  11 3 6     Condenser Setpoints Screen 1 4 3  sape a seite e a sl ee EUN                       11 3 9   Cond  nser Setpoints Screen 2    esu esas eror arte pepe derer              11 3 10     Condenser  Split Setpoints      cid ea en e E ORE GE ES ERE HERR QURE HR DO NIE                        H3 Run Pimes a E           EE    ERR                                       vi     Table of Contents 026 1102 Rev 4 08 12 99    LE 3 12    Bypass eias Hap ee kel e et ey e e ak ea id e ego era deep eve e i a ee ae p t ees tee 11 19    11 4    CIRCUIT                               5                                                                                                  11 19  HA  Standard Circuit  eoo e eR GE                   bn exu eder 
81.  The current temperature readings of discharge sensors  one through four are shown in the Disch Air 1   Disch Air  4 fields     Valve 96    When operating an Electronic Expansion Valve  EEV    the current valve percentage is displayed in the Valve 96  field   Humidity 96    When the CCB s Anti Sweat feature is active  the cur   rent status of the selected humidity probe is displayed in the  Humidity   field     Antisw 96    The Anti Sweat percentage is displayed in the Antisw     field  This percentage is the cycle rate of voltage pulsing  to the case s anti sweat heaters     13 4 4  CCB Status 2  Liquid Pulse and  Stepper Only        CCB 01SDIC O1c       CCB STATUS  Setpoint    Valve X  Setpoint    For liquid pulse and liquid stepper circuits  this status  screen displays the current sensor readings and set points of  the values important to controlling the EEV     Disch Air    The current Discharge Air Temperature within the se   lected case is displayed in the Disch Air field     Setpoint    The current Discharge Air Temperature Set Point de   fined for the selected case is displayed in the Setpoint field     Return Air    The current Return Air Temperature within the selected  case is displayed in the Return Air field     Valve      When operating an Electronic Expansion Valve  EEV    the current valve percentage is displayed in the Valve    field  A case may be controlled with up to two expansion  valves  Status information about the second valve is dis   played at the C
82.  The transformer  should be located within 10 feet of the board itis powering   preferably within the board enclosure  CPC supplies four  types of transformers for standard refrigeration applica   tions  three board transformer  six board transformer  10  board transformer  and SIO ARTC transformer  The multi   ple board transformers may not be used to power      8IO or  ARTC     RMCC I amp O Manual    Hardware Mounting     3 7    4 The REFLECS Net   works    The REFLECS uses four separate networks     1  The RS485 Input Output  I O  Network  COM  A  connects the controller to the input and output  communication boards     2  The RS485 Host Bus Network  COM B  connects  multiple controllers to a 485 alarm panel     3  The RS232 Remote Communication Network   COM C  connects multiple controllers to a modem   thus allowing remote communication     4  The RS485 Input Output  I O  Network  COM  D  is an additional I O network that connects the  controller to the input and output communication  boards     The following sections provide an overview of the ba   sic network components and their function  Wiring require   ments for each of the networks is provided in Section 4 4    Wiring     4 1   RS485 Input Output  I O  Net     work  COM A and D     The   5485 Input Output  I O  network connects all in   put and output communication boards together in an open  communication loop  This loop connects the REFLECS to  multiple input and output communication boards  and ter   minates at
83.  VARIABLE SPEED SETPOINTS 12 00          FLOATING SUCTION 12 00     TYPE  amp  f  01 02 00  C01 NORM COS NORM C11 NORM High Suct 45 0 Dly 060m Dchg Alm     4  Group 1 L Contr  by PRESSURE Float on off   OFF P IAEN  STENE  STRATERY TENN         STATUS   02 NORM C    NORM  12 NORM Low Suct 01 0 bly 060m Proof Dly 030  2  Group 2  1  Name  4Comps 00 DISCHARGE VS MINIMUM SPEED  0900 rpm INTERVAL M   15 1 GROUP 1  RUN TIM 605 NORM   OS NORM  15 NORM Pump Down 00 5 Dly 010s  3  Group 3  2  Name               00 Trip Point 350 0 VS  MAXIMUM SPEED  1800 rpm        SUCTION 030 0 MIN SUCTION 020 0 D EROUP  gt   OIL PRE   0  NORM C09 NORM C15 NORM Automatic Oil Reset  NO  4  Group 4  3  Name               00 Trip Delay 005 MAX INCREASE RATE  2000 rpm minute Use Circuit  01 S EROUP 5  H  POWE C05 NORM   10 NORM  15 NORM Copeland Oil System     Window 010 sec 63 Log Interval  5  Name               00 s    Autoreset  050 0 MAX DECREASE RATE  2000 rpm minute Delay Floating After Defrost  10 min A 6ROUP 4  PROOF s      Below Trip Point  Altern  Strategy     OFF on Failure  N Extern  Shift  000 0    z i UU     8ET DAT     gt  SET DATA O MENU                            gt  SET DATA T PREV 4            gt  SET DATA  GROUP2 STATUS 12 00 COMPRESSOR BYPASS 12 00         PRESSURE ALARMS SETUP 12 00   GROUPT SETUP 12 00         VARIABLE SPEED SETPOINTS 12 00 ION 12 00  FGROUPT STRATEGY SETUP 12 00  TYPE  amp  01 02 03 04 05 High Suct 45 0 Dly 060m Dchg Alm Y TYPE CMP 01 02 03 04 05 ST      HP  STATU
84.  VS COMP 4  in the system software  see  Section 7 9 2   Output Definitions      6  External Fault   Place a jumper across termi   nals 25 and 26     7  Fault Input   The Fincor  inverter sends a  signal to a 16AI when an inverter fault oc   curs  Wire the 16AI point to terminals 30 and  32 on the inverter  The 16AI board and point  address must be set up as an inverter alarm   VS INVALM  input in the system software   see Section 7 9 1   Input Definitions      Dip Switches    Figure 5 5 shows how dip switches JD and JE on the  inverter control board must be set  Jumper JD must be set  to the ENABLE position to allow the RMCC to control the  inverter  Jumper JE must be set to the DISABLE position    026 1102 Rev 4 08 12 99    to disable the FWD  REV  and JOG keys on the inverter  keypad     DISABLE ENABLE ENABLE          JE                8            DISABLE    26513070       Figure 5 5   Fincor Inverter Dip Switch Settings    Various    Temp Sensors  and Probes    Connect to  Input Point  by Board    Type    16AI Any  Available Point  8            Avail   able Input Point  ARTC Any  Temp or Aux  Input    5 6  Sensor and Transducer Wir   ing  Table 5 1 shows some typical sensor and transducer  connections     For a complete list of hardware and software setup in   structions  refer to Appendix B  Sensor Hardware Soft   ware Setup Table                 ODD   EVEN    TERMINAL TERMINAL    1  Connect one lead to the odd numbered terminal and the other lead to the even numbered  
85.  Valves       eae D 7 _    Case Type   the four letter case type code  See Section 11 4 16   Circuit Setup 1 for a complete  table of codes     Rev   the software revision number     Status   the system is operating in either of five modes  refrigeration on  On   refrigeration off   Off   defrost on  MDfr   recovery mode  Rcvy   or override mode  Ovrd      Time   the current time  in 24 hour format      Setpt   the current control temperature set point  This may be changed using the HHT     CaseOffset   the sensor offset for the control temperature  This may be changed using the  HHT     Valve 1     the current opening percentage of the valve   Ctrl Temp   the current calculated control temperature reading     Disch 1   Disch 4   the current readings of discharge air temperature sensors one through four     Defr   the defined defrost duration    Failsafe   this shows the demand defrost fail safe time   Term   the termination temperature sensor reading   Setpt   the termination temperature set point     Humidity   the humidity sensor reading    Aswt    the percentage at which the anti sweat heaters are operating    Max   the humidity above which the anti sweat heater will remain on at all times   Min   the humidity below which the anti sweat heater will remain off at all times       Lights   the current status of the case lights  Pressing RIGHT followed by one of the com   T gh    mands below allows users to bypass the case lights     Turn 1 Auto   Pressing 1 will return the c
86.  WITH A 10 HP RATING  AND A HIGH FAN WITH A 40 HP RATING              FAN OFF     HIGH FAN ON    ____LOW FAN ON    Condenser PID Output     from 0  to 100   y      0  100                    25  Cut on Cut off Value  10 HP 40 HP    lt _ lt  iE    Condenser PID Output     _BOTH   HIGH FAN OFF  from 100  to 0      FANS LOW FAN ON  OFF    Figure 9 5   Diagram of Two Speed Condenser Operation    Two speed fan operation may be further fine tuned by  specifying on off delays  low to high and high to low tran   sition delays  specified start speeds and durations  and min   imum on off durations     9 5 2 3  Variable Speed Fans    Variable speed fan control simply interprets the 0    100  PID output given by the condenser control algorithm  as 0  100  of the fan s maximum output  The percentage  at which the fan cuts on and off is determined by the fan s  maximum and minimum RPM  The RMCC divides the  minimum RPM by the maximum RPM to yield a percent   age  any PID output above this value means the fan will be  on  and any PID output below this value means the fan will  be off     An example of how variable speed condenser control  works is shown in Figure 9 6  In this example  the Mini   mum Fan RPM is set to 900  and the Maximum Fan RPM  is set to 1800  As the PID output rises from 0  to above the  cut on cut off value  Minimum   Maximum RPM  or  50    the fan activates and begins operating at 900 RPM   the fan s defined Minimum Speed   When the PID output  is between the cut on cut
87.  a condenser that has either a  single set of fans that may operate at two different speeds  or two sets of single speed fans with different horsepower  ratings  Generally  two speed condenser control cycles the  fans from off to low and from low to high as the PID output  goes from 0  to 100   Likewise  fans cycle from high to  low and from low to off as the PID output goes from 10096  to 096     Single Speed Fans    Two speed condenser fans change speeds at three dif   ferent PID output values  0   the cut on   cut off value  de   termined by taking the ratio of the low speed fans     horsepower vs  the high speed fans  horsepower   and  100      For example  if the low fan s horsepower rating is 10  and the high fan s horsepower rating is 40  the cut on cut   off value would be 25   10   40   see Figure 9 5      If the fan is currently off  096  and the condenser calls  for 10  of the fan  the low fan will not come on until the  condenser calls for 25  of the fan     At a call for 2596  the low fan will come on and remain  on until the condenser calls for 100  fan  At the call for  100  fan  the high fan will turn on and the low fan will turn  off     If the condenser calls for 80  fan  the high fan will re   main on even though the percentage is lower than 100    The high fan will continue to run until the condenser calls  for 2596 fan  At a call for 2596 fan  the low fan will turn on  and the high fan will turn off     RMCC I amp O Manual       TRIP DIAGRAM FOR A LOW FAN
88.  a defrost  cycle within a selected circuit  enter    1    in the appropriate  circuit field     RMCC I amp O Manual       whichever is greater  Enter the minimum amount of time  the heater will remain OFF in this field     Anti sweat override inputs must be configured in the  Input Definition screen  see Section 11 8 1  Input Defini   tions   They are listed in the Input Definitions screen as in   puts ASC 1           through ASC 8 OVRD     Standard Circuit Control Alarm Set Point screens are  also accessed by selecting the Setup Command from the  Standard Circuit Control Menu  For descriptions of these  screens  see Section 14 1   Alarm Set Points     End    Both manual and scheduled defrost cycles may be man   ually deactivated at the Manual Defrost screen  When de   frost is manually deactivated  the circuit is returned to  normal refrigeration after the programmed termination  drain time is completed  To manually deactivate a defrost  cycle within a selected circuit  enter    2    in the appropriate  circuit field     Start Override    In addition to the activation and deactivation of defrost   circuits may also be manually overridden OFF at the Man   ual Defrost screen  When a manual override is activated   the selected circuit will shut down until the override is de   activated at this screen  To activate a manual override with   in a selected circuit  enter    3    in the appropriate circuit  field     Emergency Defrost    Pressing    4    initiates an emergency defro
89.  accomplished using either a pulse type  valve using pulse width modulation or a stepper valve     The superheat control algorithm is identical for either  valve type  Once a valve percentage has been determined   this value is fed to the valve output algorithm  The valve  output algorithm converts the valve percentage into the ap   propriate control value depending on the valve type being  used  For a pulse valve  the control value is a duration the  valve will be fully open within a fixed period of time  For  a stepper valve  the valve is the number of steps the valve  opening must be adjusted to move from the current opening  to the new required opening  Control of the coil   s superheat  applies to liquid side valve control only     Type Default Min Max Description  Value   50 0  F   120 F   Current coil inlet temperature    ColOu                 50 0  F   120  F   Current coil outlet temperature     Desired Superheat  Speo         1  F     FF 19F      Valve Multiplier 10096 1046   100       Set point   point   Setpoint  4     0   9  16   255 Sets throttling range and integral gain       Sensitivity      Target coil differential     Multiplier applied to output    Used to support overcapacity  valves     Vave    Output        0    100  Calculated valve   required to reach maintain set point     Table 8 1   Superheat Control Parameters    8 2     Liquid Side Control    The case controller controls case temperature from the  liquid side of the evaporator through simple ther
90.  content of the setup screens that follow the first  screen are largely dependent upon the Control Strategy and  Condenser Fan Type settings chosen in the first screen     The condenser fans are set up at the Output Definitions  screen  see Section 11 8 2  Output Definitions      Control Strategy   A ir Cooled   T emp Diff   E va   porative   A     The method of determining the control value used by  the condenser   s PID control algorithm is specified in the    026 1102 Rev 4 08 12 99    Control Strategy field  There are three strategies to choose  from       Air Cooled   The control value is read directly from  the control source chosen in the Control Source  field  see below      e Temp Diff   The RMCC takes a pressure value from  the control source chosen in the Control Source  field  see below  and converts this pressure value to  a temperature value based on the selected Refriger   ant Type  see below      e Evaporative   The RMCC uses a combination of  pressure or temperature values from up to five  sources  The method the RMCC will use to combine  the values must be entered in the Control Using  field  see below   Note that when this strategy is se   lected              Inputs  becomes locked in as the de   fault value for the Control Source field     Control Source   D ischarge   I nlet   O utlet   D     The temperature sensor or pressure transducer used to  control the condenser fans may be mounted in either of  three places  on the condenser s discharge line  on th
91.  either sent to the proper 8RO  relay  or an existing signal is discontinued  Through the use  of this relay signal  refrigeration control functions that can  be properly maintained by a simple contact closure se   quence are effectively operated by the REFLECS     Like the 16AI input board  the 8RO board is easily in   stalled and operated within the CPC network environment    RMCC I amp O Manual          because of its straightforward design  Several of these fea   tures are shown in Figure 2 4        AC Power Input Connection      Network Connection   LED Power Indicator   Termination Resistance Jumpers  Address and Baud Rate Dip Switch    Fail Safe Dip Switch   Output Connection  8 places   Fail Safe Jumpers  8 places   Relay Fuses  8 places                       Figure 2 4   8RO Relay Output Board  2 3 2  8RO Form C Board    A maximum of sixteen SROs and SRO FCs may be  connected to an          through the RS485 COM A and  D networks     The 8RO Relay Output Board with Form C contacts   Figure 2 5  is identical in function to the standard 8RO  Relay Output Board  except that it uses relays with form C  contacts and does not use fail safe jumpers  wiring the con   tacts as either normally open or normally closed creates the  fail safe condition   The 8RO FC is slightly larger than the  standard 8      therefore  specific mounting instructions for  the SRO FC provided in Section 3 2     O Boards and En   closures  should be used     Kick    UCU  sga leget ea    eT         
92.  either the first or second pass  through the evaporator  Preferably  the sensor should be  placed six inches into the evaporator on the first pass     Place the coil inlet sensor with the curved surface  against the pipe and secure with a Panduit low temperature  cable tie number PLT2S M120 or equivalent  The tie  should be positioned in the groove on the top surface of the  sensor  A second tie should be used to secure the lead to the  pipe for additional support     Sensors located on refrigerant tubing should be insulat   ed to eliminate the influence of the surrounding air  A self   adhering insulation that will not absorb moisture is recom   mended to prevent ice accumulating at the sensor location   For orientation of the sensor on the coil  see Figure 7 8     RMCC I amp O Manual       7 8 3  Coil Outlet Sensor  Red Leads     Proper location of the coil outlet sensor is critical since  valve control is dependent upon accurate measurement of  changes to evaporator discharge gas temperature  The coil  outlet sensor should be located on a horizontal section of  the suction line  near the evaporator outlet  Follow the  mounting instructions listed for the coil inlet sensor  For  orientation of the sensor on the coil  see Figure 7 8        26509022    Figure 7 8  Sensor Location    7 9     Complete wiring of the Case Controller  Case Control   ler Power Module  and optional Defrost Power Module is  shown in Appendix E  Wiring for Case Controller   Power Module  Defrost Modu
93.  field     Termination Sensors Strategy  Min  Max  Avg    Avg     If all termination sensors are digital sensors  defrost  will terminate when all sensors are CLOSED     The Termination Sensors Strategy field determines  how multiple termination sensors will be combined into a  single termination control value  Users may choose from  the following strategies     e Avg  the average of the temperature sensor readings  is used to control termination     e Max  the highest temperature sensor reading is  used to control termination     e Min   the lowest temperature sensor reading is used  to control termination     Temperature Strategy   F ull   E PR Valve          The Temperature Strategy field determines how the re   frigeration solenoid will operate within this circuit  Users  may choose from the following two strategies     11 4 18 Circuit Set Points 1       T PREV L NEXT      gt  SET DATA    Set points for controlling each Standard Circuit are de   fined at the Circuit Setpoints screens     RMCC I amp O Manual           Full   the refrigeration solenoid is being used to  control refrigeration in this circuit  When Full is se   lected  this solenoid will open and close in an effort  to maintain the Control Temperature within the cir   cuit  The Control Temperature is defined at the Cir   cuit Setpoints   screen  see Section 11 4 18  Circuit  Set Points 1          EPR Valve   a mechanical EPR or other regulating  device is being used to control refrigeration in this  circuit  
94.  field     The real time clock within each RMCC records the cu   mulative runtimes of each condenser fan  These runtimes  are displayed at the Condenser Runtimes screen  The cu   mulative runtime is the total number of hours each fan has  been activated for the duration the RMCC has been con   nected or since the last clear runtimes command     The clear runtimes command clears the cumulative  runtimes for each fan  To reset the runtimes for any fan   move the cursor to the desired fan runtimes and press the  blue key then the    R    key     026 1102 Rev 4 08 12 99    11 3 12 Bypass    Any defined condenser fan may be bypassed for a fixed  duration at the Condenser Bypass screen  A fixed bypass  overrides the system condenser fan settings with a user de   CONDENSER BYPASS    fined ON or OFF setting until the bypass command is re     F1 F2 F5 turned to normal at the Condenser Bypass screen   NORM  NORM   NORM             7  8 9      To activate a condenser bypass  specify  O n or           NORM NORM  NORM for each defined condenser fan to be bypassed  To deacti   vate a condenser bypass  change the On or Off status to the  Normal command and the selected condenser fan will re    sume controlling with its original settings                                                 gt  SET DATA       11 4  Circuit Defrost Control    Cem       Desorption  Page       CIRCUIT CONTROL    1  Standard Circuit       2  Case Control    5  Circuit Summary  SELECT NUMBER       11 4 1  Standard Circ
95.  fields  The RMCC will  automatically set the Day for the entered Date     System Navigation     11 55    Passwords  6 Character Limit     Choose a different password for each level of access   If all passwords are defined the same  users will only  be able to log in at 100 level access     The RMCC system requires a password for all users to  enter into and modify the system  There are four levels of    11 8 4  System Options                    Additional Delay After Defrost  0   240 minutes   0     When the RMCC exits a stage of defrost  the RMCC  will wait a specified Defrost Delay before reactivating  alarms     Notice on Defrost Timeout   Y es   N o   N     Some circuits may be set up with defrost termination  strategies that cause them to exit defrost when a certain  Termination Temperature is exceeded within the case  Re   gardless of strategy or termination temperature  a circuit  will operate in defrost mode no longer than the defined De   frost Duration     Power Fail Alarm Notice   A larm   N otice   N     The RMCC will generate a notice or an alarm when  there is a power failure within the system  A notice is a low   level warning that alerts users of abnormal facility or con   trol system conditions     notice creates an entry in the  RMCC Alarm Log  An alarm is a high level warning that  also alerts users of abnormal facility or control system con   ditions  An alarm will appear in the RMCC Alarm Log and  may be accompanied by a contact closure for on site oper 
96.  for  the Minimum Time Off duration     Off on Failure  Y or N   N     See the description of Off on Failure given in the  RMCC Variable Speed Set Points screen on Section 7 3 14   Group 1 Variable Speed Set Points     Max Speed  0   9999 rpm   1800 rpm     The maximum rpm of the variable speed compressor  must be entered in the Max Speed field     Note that unlike the RMCC Variable Speed Set Points  screen on Section 7 3 14  Group 1 Variable Speed Set  Points  there is no Minimum Speed field  The RMCT auto   matically assumes that the minimum speed of the variable   speed compressor is 50  of the maximum speed  therefore   when the Max Speed is 1800 rpm  the minimum speed will  be 900 rpm  Users may not alter the value of minimum  speed     Also  note that unlike the RMCC  there are no fields in  which to insert maximum speed increase and decrease  rates  In the RMCT  increase rates are determined by the in   verters driving the compressors     Appendix A   A 3    Appendix B  Sensor Hardware Software Setup Table    How to Use This Table    Table B 1 lists all sensors commonly used in an RMCC  setup by both name and part number  The table divides sen   sor setup for each sensor into five different steps  each of  which is represented by a column in the table  The columns  are as follows       Input Dip Switch   the position of the 16AI or 8IO  dip switch rocker that corresponds to the input point  to which the sensor will be connected  Refer to Sec   tion 5 12   Input Type Di
97.  ging and graphing features that allow the user to view  accurate real time information about system conditions     The RMCC may be configured to control a refrigera   tion system using traditional pressure control of up to four  suction groups and as many as 22 compressors  orit may be  used to interact with CPC s case controller for complete  control of refrigerated case valves  superheat  fans  lights   defrost  and anti sweat heaters     All other refrigeration system components must be con   nected to the RMCC for proper monitoring and control of  the system  The RMCC has connections for I O  host  and  remote communication components  Compressors  con   densers  refrigerated cases  and sensors and transducers   while not directly connected to the RMCC  are accessed by  the controller through the communication boards described  below     Installation of the RMCC consists of mounting the unit  in an easily accessible location       communication boards   additional RMCCS  alarms panels  and remote communica   tion equipment must be wired to the RMCC  Network  switches must be set to give the RMCC a relative address  on the I O network  A 120 208 volt power supply is re   quired to provide power to the unit  Finally  the RMCC  must be configured based on the refrigeration components  to be controlled     The RMCC consists of a rugged steel enclosure con   taining a processor board and Power Interface Board  PIB    The Processor Board  Figure 2 1  contains the LCD  screen  
98.  gt  SET DATA O MENU    Setpoint   99   999   200 0     The Setpoint value is the discharge pressure or temper   ature  or temperature differential  as is the case with TD  condensers  the RMCC will attempt to maintain during  condenser control  See Section 3 3   Condenser Control   for more information about condenser control     Throttle Range  0   99   4 0     The Throttle Range value forms an operational range  for the condenser fans that is equally above and below the    11 16   Condenser Control             11 3 7 3  Condenser VS Fan Fail Setup       CONDENSER VS SPEED FAN FAIL SETUP 12 00       Inverter Reset Count  0035                   Inverter Reset Delay  0030         gt  SET DATA 0              Inverter Reset Count  0   240 attempts   3 at   tempts     In order for the RMCC to automatically reset failed  inverters  an inverter reset output must be defined in  the Output Definitions screen on Section 11 8 2  Out   put Definitions     When an inverter failure is detected on the condenser  fans  inverter alarm input  see Input Definitions on Section  11 8 1  Input Definitions   the RMCC will attempt to reset  the inverter  The Inverter Reset Count is the number of re   set attempts the RMCC will make before bypassing the  failed compressor off     Inverter Reset Delay  0   3600 sec    30 sec      When the RMCC is set up to make multiple attempts to  reset failed inverters  the Inverter Reset Delay is the num   ber of seconds between each inverter reset attempt     S
99.  manual bypass by entering ON or  OFF in the heater   s Screen Override field  When bypassed  in this manner  the anti sweat heater will remain ON or  OFF until a user terminates the bypass by entering NORM  in the heater   s Screen Override field     026 1102 Rev 4 08 12 99    Input OVR Time Min  0   240 min    0 min      Anti sweat heaters may also be overridden OFF by  closing an external input  When this input is closed  the  heater will remain OFF for as long as the output is closed  or for an amount of time equal to the Input OVR Time Min     11 4 12 Alarm Set Points    11 4 13 Manual Defrost    T PREV                  gt  SET DATA    In the Manual Modes screens  the status of circuits 1 48  are shown in the field to the right of the number  Rfr for re   frigeration  Dfr for defrost  etc   Defrost for each defined  circuit within the RMCC may be manually activated or de   activated by entering a command in the circuit   s field   1 Defrost  2 End  3 Start Override  4 Emergency  Defrost   Rfr      Defrost    When defrost is manually activated  defrost will run  within the selected circuit for the defrost duration defined  at the Circuit Set Points 1 screen  see Section 11 4 18  Cir   cuit Set Points 1   Defrost termination strategies defined at  the Circuit Setup 2 screen  see Section 11 4 17  Circuit  Setup 2  are ignored  After the defrost duration has been  completed  the circuit will return to normal refrigeration af   ter the defined Drain Time  To manually activate
100.  multiplied by the filter ratio  which is a percentage  between 0  and 100   The result of this multiplication is  the filtered output value  Note that if the filter ratio is at  100   or if the Filter cell is disabled  the input is not mod   ified by the Filter cell     The Filter output value is the final Analog Input Mod   ule Value  This value is also sent to the Process Alarm cell  and the Cut In Cut Out cell for use in alarm generation and  digital output control     Process Alarm    The Process Alarm cell reads the Analog Input Module  Value from the Filter cell and compares it to the notice and  alarm set points defined by the user  When an alarm condi   tion is detected  the Process Alarm cell sends digital values  tothe Alarm or Notice outputs and sends an alarm message  to the RMCC Alarm Log     RMCC I amp O Manual    Different set points may be specified for occupied or  unoccupied building states  The Process Alarm cell reads  the digital state of the Occup input to determine which set  of set points to use  HIGH occupied  LOW unoccupied      If the input exceeds a high set point or falls below a low  set point for an amount of time greater than the specified  delay period  the corresponding Alarm or Notice Output  will turn ON     The Alarm Disable and Notice Disable inputs  when  HIGH  force the Alarm and Notice Outputs OFF     Cut In Cut Out    The Cut In Cut Out cell   s function is to read the Analog  Input Module Value from the Filter cell  compare it to a 
101.  of a 100 HP compressor rack were called for   one or more compressors totalling 15 HP would be activat   ed     The normal control strategy varies both the number of  compressors and run duration to achieve proper system  performance  To initiate the normal control strategy  the  user provides the RMCC with the number of compressor  stages within the group  the stage type  compressor  vari   able speed  unloader   and the horsepower of the stage     9 2  Pressure Control       9 4 1 2  Fixed Steps    As an alternative to the normal suction pressure control  strategy  the RMCC allows the user to build a specific con   trol method for a pressure group using fixed steps     To initiate the fixed steps strategy  a matrix is built by  the user that tells the RMCC when each compressor should  be cycled on or off  Because the RMCC can only cycle the  compressors based on that matrix  the ability to match  available compressor capacity to the refrigeration needs of  the system is greatly reduced     If the fixed steps strategy is selected  only 10 compres   sor stages may be defined per group     9 4 2  Variable Speed Compressors    Each of the four suction groups may have one variable   speed compressor  The chief advantage of having a vari   able speed compressor in a compressor rack is that a vari   able speed compressor can operate at a wide range of  horsepowers  whereas a standard compressor may only op   erate at 10096 or 096 capacity  Variable speed compressors  thus allow t
102.  off value and 100   the fan op   erates at a percentage of the Maximum Fan RPM dictated  by the PID output value  i e  65  of Maximum RPM when  the output is 65   maximum RPM when the PID is 100    etc    The fan continues to operate in this manner until the  PID output drops below the cut on cut off percentage  at  which time the fan deactivates     Software Overview     9 5       Figure 9 6   Diagram of Variable Speed Condenser Operation    To fine tune condenser fan operation  users may speci   fy on off delays  minimum ON OFF times  and maximum  RPM increase and decrease rates for variable speed con   denser fans     9 5 3  Operation During Reclaim    During heat reclaim  it may be preferable to raise  or  shift  the condenser set point to increase the temperature of  the refrigerant in the system  The RMCC provides a user   definable shift value that may be added to the condenser set  point  This change is made when the RMCC receives a sig   nal from the RMCC s defined Reclaim input that heat re   claim has been initiated     9 5 4  Condenser Split  Single Speed  Fans Only     In cold conditions it may be preferable to reduce the op   erational capacity of the condenser by either limiting the  number of fans that maybe activated or by activating a  valve which reduces the effective condensing area of the  coil  The RMCC provides a user defined set point at which     signal is sent to the condenser to initiate split  A different  set point is definable for heat reclaim  
103.  offset value may be entered at the CCB Offsets screen to  calibrate selected sensors to actual conditions     To offset a displayed sensor  enter an offset value be   tween  9   and 9    or between 0 ppm and 99 ppm for the re   frigerant leak sensor  in the appropriate fields     11 4 35 CCB Set Points Screen 3  Suction Stepper Only        TEETAN     CCB OFFSETS CCB 01 SDIC O1c  Case Offset   2 Extra1 Tmp   Discharge  1  Extra2 Tmp   Discharge  2  Refr Leak    Discharge  3   Discharge  4                                                     T PREV 4 NEXT   gt  SET DATA       At times  a sensor may provide a reading that reads low   er or higher than the known condition being monitored  An  offset value may be entered at the CCB Offsets screen to  calibrate selected sensors to actual conditions     To offset a displayed sensor  enter an offset value be   tween  9   and 9   or between 0 and 99 ppm in the appropri   ate fields     11 4 36 CCB Set Point Screen 4  Liquid Pulse and Stepper Only          gt  SET DATA       Case Deadband  0     12 7   0 6     The Case Dead Band is a value equally above and be   low the Control Temperature Set Point defined at the Cir   cuit Set Points screen  see Section 11 4 46  Circuit Set  Points 1  Add Edit Circuit    When the case temperature  exceeds the dead band  refrigeration will be activated with   in the case  When the case temperature falls below the dead  band  the refrigeration valve closes according to the Close  Rate Percentage define
104.  or OFF by a manual  or external bypass  an asterisk will appear to the right of the  Status field  The Time Left field will display    BPSS    for  manual bypasses and the time left in minutes for external  bypasses     e Def   the selected board is calling for a stage of de   frost         Lost the selected board cannot be found within the  defined circuit     Temp    The current case temperature is displayed in the Temp  field  This temperature is calculated according to the Tem   perature Control Strategy defined at the Circuit Setup 2  screen  see Section 11 4 45   Circuit Setup 2  Add Edit Cir   cuit       Term    The current Termination Temperature sensor reading is  displayed in the Term field     13 4 2  CCB Status 1  Liquid Pulse and  Stepper Only              22   4                     STATUS       01SD C 01            Setpoint  ast Term   Val eX    Setpoint  Antisw  X     eat   umidity       For liquid pulse and liquid stepper CCBs  this status  screen displays current information about case sensor read   ings and set points     System Navigation     13 5    Case Temp    The current temperature in the selected case is dis   played in the Case Temp field  This temperature is calcu   lated according to the Temperature Control Strategy  defined at the Circuit Setup 2 screen  see Section 11 4 45    Circuit Setup 2  Add Edit Circuit       Setpoint    The current Control Temperature Set Point is displayed  in the Setpoint field  This set point is defined at the Circuit 
105.  speed compressors 11 6   variable speed  Alternate strategy 9 3  VS HP on Edge 9 3  Normal strategy 9 2  flowchart 9 2  variable speed compressors 9 2    Processor Board  features 2 2  Pulse Valves  EEVs   See Case Con   trol  valve control     Pulse Width Modulation    analog output modules 9 17  anti sweat control 9 7    R    Reclaim    condenser operation during 9 6  condenser set point shift 11 16    Recovery mode 8 4    REFLECS  defined 2 1    RMCC I amp O Manual    functions of 2 1   list of controllers 2 1   standard components 2 1  REFLECS Networks    Baud Rate Dip Switch Settings  4 5  Fail Safe and Relay Dip Switch  Settings  Output Boards 4 5  RS232 Remote Communication  Network  Terminating Resistance  Jumpers 4 3  Refrigeration Circuits  See Circuit  Control     Refrigeration Monitor and Case Con   trol  number of compressor groups  controlled by 11 5  number of compressor stages  controlled by 11 5  Refrigeration Monitor and Case Con   trol  See RMCC     Remote Communication Network   See RS232 Remote Commu   nication Network     RMCC  mounting 3 1  RMCC  functions of 2 1    RMCT A 1  differences between RMCC and  RMCT A 1  PIDA control    1  variable speed operation A 1  variable speed setup A 3  Rotary Dials  network  board numbering 4 4  function of 4 4  Settings for 8IO 4 4  settings for 8IO 5 11  RS232 Bus Amplifier  defined 2 6  features 2 6  location 3 5  mounting 3 5  RS232 Remote Communication Net   work 4 1  defined 4 1  wiring 4 1  5 2  RS485 Host Bu
106.  strategy  The primary combination strat   egy will be used whenever the Use Alt Comb input is  LOW  When the Use Alt Comb input is HIGH  the alter   nate combination will be used  If an alternate combination  strategy is not desired  only the primary combination strat   egy needs to be defined     Min On Off    The Min On Off cell gives users a method of assuring  that the Digital Output Module   s Command Output re   mains ON for a minimum amount of time and or OFF for a  minimum amount of time   regardless of the input value  read from the Schedif cell     Every time a change of state is detected in the input val   ue  the Min On Off cell begins to actively measure the  length of time the input remains in its current state  If the  input switches from ON to OFF before a user specified  Minimum On duration is reached  the output signal being  sent from the Min On Off cell will not reflect the input   s  change of state  it will remain ON until the Minimum On  duration has passed  If the input is still OFF when the dura   tion is over  the output will switch OFF     The reverse is true with the Minimum Off duration  If  the input signal switches ON before the Minimum Off du   ration is reached  the output signal from the Min On Off  cell will remain OFF until the duration has passed     One Shot    Some applications for the Digital Output Module re   quire digital pulses instead of ON OFF logic  The One Shot  cell  when enabled  reads the ON OFF output from the Min  On Off c
107.  than the ASW  Hi Limit  the anti sweat heaters will remain on at all times   If the humidity is lower than the Asw Lo Limit  the anti   sweat heaters will remain off at all times  Between these set  points  the anti sweat heaters will cycle in a six second  window according to the humidity level     Frost Sensor   Y es   N o   N     If a Demand Defrost Sensor is installed at the selected  case  enter  Y es in the Frost Sensor field  Demand Defrost  set points may then be defined at the Circuit Setpoints 3  screen  see Section 11 4 48  Circuit Set Points 3  Add Edit  Circuit       11 4 32 CCB Set Point Screen 2  Liquid Pulse and Stepper Only        CCB ALARMS  CCB 01SDIC O1c  Refr Leak  Leak Alm Lvl  Leak Alm Dly                                        Coil 2 Out           Bypassed Vlv     Door Alm Delay         SET DATA                T PREV                Case alarm control includes the generation of alarms  when the RMCC detects coil in or coil out sensor failures  or when it detects a refrigerant leak  An alarm is a high lev   el warning that creates an entry in the RMCC Alarm Log  and may be accompanied by a contact closure for on site  operation of a bell  light  horn  etc  An alarm may also ini   tiate an alarm dialout sequence and or the activation of the  485 Alarm Panel     11 34   Circuit Defrost Control       The alarm configuration for each case is defined at the  CCB Alarms screen     Coil 1 In   Y es   N o   Y     To generate an alarm when the RMCC detects a Coi
108.  the  RMCC must wait before shutting down the compres   sors after the Trip Point is reached     Autoreset  2   99 Ib    50 0     After the trip point has been reached and the RMCC  has shut down all compressors  the compressors are au   tomatically reset when the discharge pressure falls to an  acceptable level  This reduction in pressure is defined  in the Autoreset field  This value must be lower than the  Trip Point  Therefore  if the trip point is set to 350  pounds and the autoreset value is 50 pounds  the com   pressors will reset at 300 pounds     Max Decrease Rate  0   9999   2000     The Maximum Decrease Rate is the maximum rate at  which the speed of the compressor may be decreased     Altern  Strategy   Y es   N o   N     Normal compressor operation dictates that a variable  speed compressor be the first compressor on and the last  compressor off in a compressor group  Users may define an  alternative strategy to bring on whichever compressor is  most closely matched to the current system suction pres   sure demanded by entering    Y    for Yes in the Altern  Strat   egy field     Off on Failure   Y es   N o   N     The Off on Failure feature allows the user to define the  compressor status when an inverter failure is detected with   in the system  When an inverter failure is detected by the  inverter alarm input defined at the Input Definitions  screens  see Section 11 8 1  Input Definitions   the RMCC  will attempt to reset the inverter three times  Note that fo
109.  the EEV to a fixed valve  percentage  This percentage is the Bypassed Valve Per   centage  The fail safe function maintains an adequate de   gree of refrigeration during alarm situations     Door Alm Delay  0   120 minutes   15     If a Door Switch is defined at the Circuit Set Points 4  screen  see Section 11 4 49  Circuit Set Points 4  Add Edit  Circuit    the Door Alarm Delay may be defined in the  Door Alm Delay field  The Door Switch disables refriger   ation  turns off fans  and turns on all lights within the walk   in cooler  When switched again  any calls for refrigeration  and fans are reactivated and all lights are turned off  How   ever  if the switch is not switched back after the designated  Door Alarm Delay  an Open Door Alarm will be generated  and the cooler will return to normal operation     11 4 33 CCB Set Points Screen 2  Suction Stepper Only     CCB ALARMS             01 501   01    Refr Leak  Leak Alm Lvl  Leak Alm Dly                         Extra1 Tmp   YES  Extra2         YES                            Door Alm Delay        T PREV J NEXT      gt  SET DATA    Refr Leak   Y es   N o   N     To activate an alarm when a defined amount of refrig   erant is detected by a leak sensor  enter  Y es in the Refr  Leak field     Leak Alm Lvl  1   100   100     The Leak Alarm Level is an amount of refrigerant that   when detected by a leak sensor  activates an alarm  Enter  the Leak Alarm Level  in parts per million  in the Leak Alm  Lvl field     RMCC I amp O Ma
110.  the actual kW and send a voltage range defined  by a minimum and maximum voltage     Maximum and Minimum Voltage  0   12     Enter the minimum and maximum voltage sent by the  kW transducer in the appropriate fields     Power at Maximum  0   3200     To translate the voltage reading into a kW reading cor   rectly  the RMCC requires the kW reading when the maxi   mum voltage is being supplied  Enter the kW value in the  maximum voltage in the Power at Maximum field  The  RMCC assumes the minimum voltage represents a value of  Zero     Cem       Besipion                                                                           Wwe wes                       026 1102 Rev 4 08 12 99    11 8 1  Input Definitions    rotary dials on the 8IO board  The number entered in the  Board Number field is used by the RMCC in conjunction             Er  E 4  with the Point address defined below to locate the selected  INPUT DEFINITION Sensor   0 Pt  1   16                 Each input sensor is physically connected to a specific  point on an input communication board  The point numbers  T PREV J NEXT   gt  SET DATA are printed on the board above the input connections  This  point address is used by the RMCC in conjunction with the  board address to locate the selected sensor                                0  0  0  0                All inputs connected to the 16AI or 8IO boards        con   figured at the Input Definitions screen  Each input is iden   tified according to its board and point addre
111.  the defrost time     If an input is configured as a demand defrost input  the  CCB will check the demand defrost state before entering  the defrost state  If no demand defrost is present  the CCB  will not enter the defrost state unless overridden by an  emergency defrost command     Defrost control is configured through the RMCC  Refer  to Section 7  System Navigation     8 4   Defrost Control       8 5     When the CCB is powered up  either for the first time  or after a power failure  it sits idle for a period of 72 sec   onds before beginning case control  During this time  the  CCB waits for communication with an RMCC to begin  If  communication with the RMCC is begun  the CCB starts  normal case control at that time  If  after 72 seconds  no  communication is established with the RMCC  the CCB as   sumes that no RMCC is available and begins control on its  own  If the CCB is controlling a stepper valve  the valve is  fully closed during start up to ensure that the position of the  valve is known when normal control is reestablished  After  start up  recovery is initiated     System Start Up    8 6  System Recovery Mode     The CCB may exit recovery mode early and begin  normal superheat control if  after 24 seconds  super   heat is greater than 150 percent of the superheat set  point     Recovery occurs when the valve has been fully closed  because either the temperature set point was satisfied or be   cause of defrost or system start up     recovery sequence is  neces
112.  the last input or output board on the network   The term    daisy chain    is sometimes applied to this open  loop arrangement     The REFLECS is configured to monitor and control  two separate RS485 input output communication net   works  These two networks are labeled as either COM A or  COM D  Each network is capable of supporting up to 31  separate input or output boards  plus the single REFLECS  controller  This means that a single REFLECS can monitor  or control up to sixty two individual input or output boards   Figure 4 1 shows the I O network configurations     The concept of a loop is critical to operation of the I O  network  The REFLECS cannot properly interact with the  input and output boards unless the boards are connected  and identified within the confines of the loop  The I O net   work is always identified as COM A or COM D on the con   troller  Input and output communication boards are  configured with a RS485 network connection only  which  can be used to connect the board to either COM A or COM  D     In addition to the primary loop arrangement  a single  star configuration may be connected to the loop  A more in     RMCC I amp O Manual          depth explanation of CPC network wiring practices is pro   vided in Section 4 4   Wiring          NETWORK   COM A or D                       CPC                    input OR OUTPUT  BOARD                            26513041    Figure 4 1   Network Loop Wiring Configurations    4 2   RS485 Host Network  COM    B  
113.  the type  network modem used with the remote network  Refer to the  modem user s manual for specific baud rate information     Parity   N one   O dd   E ven  N   Data Bits  7 or 8    8     The following two fields represent the Parity and Data  Bits values  The RMCC automatically calculates the appro   priate settings required for the remote network to commu   nicate properly according to the specified baud rate  settings  Refer to the modem user s manual for specific  Parity and Data Bits information     Initialization String  Enter String     Modems are initiated by receiving an attention code  followed by the appropriate command or set of commands  the modem should implement  This command set  or ini   tialization string  is different for most modem vendors  The    11 8 11 Modem Initialization                            CPC supplies a standard 9600 baud modem for use with  the RMCC RS232 COM C network  however  most stan   dard modems with a baud rate of at least 9600 are suffi   cient  The RMCC stores communication settings for    11 60   Configuration    initialization string for the modem operating within the re   mote network is defined in the Initialization String field     The RMCC stores modem settings for several frequent   ly used types of modems  Initialization strings for these  modems may be copied to the Initialization String field at  the Modem Initialization screen  see Section 11 8 11  Mo   dem Initialization      Send Now   Y es   N o   N  Response    To 
114.  types supported 8 4  demand defrost operation 8 4  early recovery based on super   heat 8 4  fail safe conditions 8 6  fail safe operation 8 6  fan control 8 5  fan operation during defrost 8 4  light control 8 5  for walk in boxes 8 5  liquid side temperature control 8   recovery mode 8 4  sensor failure  calculation of coil inlet tem   perature 8 6  coil inlet 8 6  coil inlet and coil outlet 8 6  coil outlet 8 6  discharge air 8 6  evaporator control during 8     Sporlan valve settings 8 3  start up mode 8 4  suction side temperature control  8 2  superheat control 8 1  valve control 8 2   8 4  pulse valve 8 3  stepper valve 8 3 8 4  wash mode control 8 5    Case Controller   case controller power module  features 6 2 6 3   differences between pulse and  stepper 6 1   dimensions of 7 1   input cable harness 6 2   mounting 7 1   optional inputs and outputs 7 2   output cable harness 6 2   power module types 6 2   power requirements 7 1   prohibition against use of center  tap 7 1   pulse type features 6 1   standard components 6 1   stepper type features 6 1   valve control capabilities 8 3    Case Lights    light schedules  standard circuit 11 24  light strategy 11 41    CCBs  See Case Controller   Checkit Sensor    Index     1 1    hardware software settings B 2  set points 11 5  setup 11 5    Circuits  Case Control 11 32    alarms  CPC suction stepper  extra temp 11 35  leak alarm delay 11 35  leak alarm level 11 35  refrigerant leak 11 35  liquid pulse stepper  coil sen
115. 0    on the  dial     5 8 1 2  LED Indicator Lights    Each board contains a LED Power Indicator Light  This  light indicates if the board is receiving power  It also indi   cates if the board is on line with the network by sending a  pulsing signal     5 9   Fail Safe and Relay Dip    Switch Settings    CPC uses two fail safe devices on its output boards  a  dip switch and jumpers  These two devices are used to pro   vide fail safe operation of equipment in the event of either  power loss or network communication loss  The use of  these devices differs depending on the board or controller     Boards using Form C contacts do not have fail safe de   vices  since the contacts are wired for the position required  during power loss  but have a dip switch which illuminates  the LED relay indicator depending on the contact position     5 9 1  8RO    The 8RO has both a fail safe dip switch  S2  to force  the contacts open or closed if the network fails  and a jump   er for each output  JU4 through JU11  that forces the con   tact open or closed during a power loss  Figure 5 14 shows  the possible settings for the dip switch and jumpers     SWITCH 1 AND JUMPER JU4 FOR RELAY 1       THE SWITCH SETTING SHOWN   ALLOWS THE RELAY TO CLOSE ON  LOSS OF COMMUNICATION  THE     JUMPER SETTING ALLOWS THE RELAY H H  TO CLOSE ON A POWER LOSS                                              JUS FOR RELAY 2    THE SWITCH SETTING SHOWN     2 7 8  ALLOWS THE RELAY TO OPEN ON No   4           LOSS OF COMM
116. 0   Network Address Settings for Dip Switch S1 or S3  on I O Boards    Numbering 810 Boards    The 8IO board uses rotary dials to set the network ad   dress instead of dip switches  The rotary dial S1 is used to  define the output portion of the board  Therefore  the board  may only be defined as board 1 through 9  Likewise  dial    026 1102 Rev 4 08 12 99    S2 is used to define the input portion of the board and may  be set from 1 to 9     LED Indicator Lights    Each board contains a green LED Power Indicator Light   This light indicates whether or not the board is receiving  power  It is also a good indication if the board is on line  when the LED pulses     4 14  Baud Rate Settings    The COM A and D networks may be set to either 4800   9600  19 200  or 38 400 baud  Positions one and two of the  dip switch located on the processor board of the RMCC are  used to set the baud rate  A different baud rate setting may  not be set for the COM A and D networks     Positions six and seven on dip switch S1 of the 4AO   8RO  and 8RO FC  and switch S3 of the 16AI  are used to  set the baud rate for the communication boards  This baud  rate should match the setting for the RMCC  Figure 4 11  shows the possible baud rate settings and dip switch posi   tions for the COM A and D networks     COM B    COM AAND D BAUD RATE  BAUD RAE  PRESET AT 4800     COM AAND D    BAUD EN    ERR                   dut            8RO  AND 8RO FC   SWITCH S1  16     SWITCH  3                 7 8          
117. 000 0 Power at Maximu 0500 0 KW 00 00 00000 00000 00 00                                                                                                                                                 CONFIGURATION 12 00  ll  Input Definitions 5 Xducer Setup  B Output Definitions 6 Host Network  B System Information 7 1 0 Brd Setup   Remote Communication 8 8      Comm   INPUT DEFINITIONS 72 00   OUTPUT DEFINITIONS 72 00   SYSTEM INFORMATION 12 00  COMMUNICATIONS SETUP  72 00   TRANSDUCER OFFSETS 12 00 HOST NETWORK MENU   12 00 170 BOARD MENU   12 00  SATELLITE COMMUNICATION  12 00  Input Bd Pt Input Bd Pt Output Bd Pt Output Bd Pt Unit Name  REFRIG MOINTOR  amp  CONTROL knit fs 01 Baud Rate 9600 N    1 ONLINE Status 3 Reset 1 ONLINE Status 3 Reset         prs 00 00        tme 00 00       01 00 OG       02 00 00 Date  01 10 96 Time  05 20         WED nitialization String  Group 1 Suction  00 0 2 Set Device   s 2 Set Device   s Enable Satellite Mode  N  DSCH PRESS 00 OO DsScH TEMP 00 00 CMPO3 00 00       04 00 00                    ab axbeW Group 2 Suction  00 0  SPARE 00 00 SPARE 00 00       05 00 00  lt     06 00 00 Passwords   1  100  3  300  For Help Go To the Next Screen  Group 3 Suction  00 0 Disconnect Message NO CARRIER  SPARE 00 00            00 00 CMPOT DO 00         8 00 00  2  200  4  400 Send Now  NO Reset at Midnight     Group 4 Suction  00 0  Response  Discharge Press  00 0  EPREV   NEXT   gt  SET DATA __                      gt  SET DATA 0 H PREV I NEXT   gt     
118. 0000 00000 00000 00000 08000 00000 NORM NORM NORM NORM NORM NORM Inlet Pres Offset 00 0 Inlet Pres Offset 00 0 Curr  Ambient       Reclaim  OFF Control Source  DISCH  RGE Throttle Range   0005 Outlet Pres Offset 00 0 Outlet Pres Of fset 00 0 Curr   FANS Control Type  PRESSURE Shift During Reclaim 000 0 ni 18 9 4200  12    7  8    8 10       12  10 2 3  46 7 8 29 10 11 12 Condenser Fan s  Type  SINGLE SPEED 80000 00000 00000 00000 00000 00000 NORM NORM NORM NORM NORM NORM       T PREV               gt  5          gt  SET DATA   gt  SET DATA    T PREV 1            gt  SET DATA T PREV        gt  SET DATA                    CONDENSER PRESSURE INPUTS SETUP  CONDENSER SETPOINTS 12 00  CONDENSER FAN DELAYS SETUP 18 00  CONDENSER FAN DELAYS SETUP 12 00    Inlet Pres Offset 00 0 Curr          hi Fast Recovery Setpoint  NONE Fan Minimum On Time  000 Fan Minimum Qn Time  000  Outlet Pres Offset 00 0 Curr  E      5 Fast Recovery Hystersis 002 0 Fan Minimum Off Time  000 Fan Minimum Off Time  000    Low Pressure Cutoff Setpoint  Low Pressure Cutoff Hystersi       T PREV 4 NEXT   gt  SET DATA T PREV                    SET DATA    4          1            gt  5                                                       T PREV 1            gt  5              T PREV J NEXT   gt  SET DATA       CONDENSER FAN DELAYS SETUP 12 00 i  CONDENSER SETPOINTS SINC LE CONDENSER 2 SPEED FAN SETUP 12 00  CONDENSER VS FAN SETUP 12 00  Fan Minimum Qn Time 00 1   Unsplit Setpoint Fan High Output 2 pd Relay 2 VS Min
119. 026 1102 Rev 4 08 12 99    Refrigeration Monitor and  Case Control Installation  and Operation Manual       E Q                  CLL    COMPUTER PROCESS CONTROLS  1640 Airport Road  Suite 104  Kennesaw  GA 31044    Phone   770  425 2724  Fax   770  425 9319    ALL RIGHTS RESERVED     The information contained in this manual has been carefully checked and is believed to be accurate  However  Com   puter Process Controls  Inc  assumes no responsibility for any inaccuracies that may be contained herein  In no event will  Computer Process Controls  Inc  be liable for any direct  indirect  special  incidental  or consequential damages resulting  from any defect or omission in this manual  even if advised of the possibility of such damages  In the interest of continued  product development  Computer Process Controls  Inc  reserves the right to make improvements to this manual  and the  products described herein  at any time without notice or obligation     THIS PRODUCT IS AN FCC CLASS A DIGITAL DEVICE     This equipment has been tested and found to comply with the limits for a Class A digital device  pursuant to Part 15 of  the FCC Rules  These limits are designed to provide reasonable protection against harmful interference when the equip   ment is operated in a commercial environment  This equipment generates  uses  and can radiate radio frequency energy   and   if not installed and used in accordance with this instruction manual   may cause harmful interference to radio com   mu
120. 05      Input Output  or I O Control  is a method of controlling  refrigeration and building control using user configured  modules that both interpret and manipulate data from input  components  and monitor and control mechanical equip   ment     The traditional approach to component control is  through the use of applications  Applications are boiler   plate programs that provide the user with a fill in the blank  method of controlling common building functions  Such  systems are flexible only in that the existing inputs  out   puts  settings  and set points are configured by the user  the  ability to manipulate and customize the control framework  is nonexistent when using the applications approach     Most standard refrigeration circuit control  condenser  control  and lighting schedule control functions still use the  applications approach  These common control functions  require the ability to simultaneously control many compo   nents with similar or different set points     While applications are a quick  easy to understand way  to control conditions within a building  they do suffer from  a lack of flexibility  Many of today   s refrigeration control  environments require a greater degree of latitude that al   lows for complex overriding and scheduling features not  available with the traditional applications approach     9 8   Sensor Control    I O Control  while sacrificing the boilerplate ease of ap   plications  provides the user with the ability to completely  cu
121. 1   Wash Mode Parameters    8 10  Fail Safe Mode  Liquid Side    Control Only     Under the following conditions  the CCB will enter fail   safe mode     1  Corruption detected in case and circuit set points   The CCB will revert to the default settings as de   scribed in the tables within this section     2  Unrecoverable sensor failure s   The CCB will cal   culate a sensor value or use a default setting as de   scribed below     8 10 1  Evaporator Control During Tem   perature Sensor Failure    During a temperature sensor failure  the case controller  must compensate for the lost data by either performing a  calculation to define an alternate value or using data al   ready defined at an alternate source  The case controller is  designed to compensate for several sensor failures  coil in   let  coil outlet  both coil inlet and outlet  and discharge air     Coil Inlet Sensor Failure    If the coil inlet reads open or short  or if the coil inlet  temperature reading is 20 F above the control set point for  10 minutes  the case controller will go into sensor bypass   During sensor bypass  the case controller calculates the coil  inlet temperature as follows     Coil Inlet   Coil Outlet   Control Set Point   12  Example     8 6  Fail Safe Mode  Liquid Side Control Only        Case Set Point   20   Coil Inlet   Open or Short  bypass    Coil Outlet   15   15   20   12  7  calculated inlet temperature     Coil Outlet Sensor Failure    If the coil outlet reads open or short  or if 
122. 102 Rev 4 08 12 99       CIRCUIT CONTROL 12 00    1  Standard Circuit    2  Case Control    SELECT NUMBER O MENU             CIRCUIT CONTROL 12 00  1 Circuit Status 6 Logs Graphs  2 Circuit Set Points 7 Summary   31         Set Points BlLight Schedules   amp iRlarm Set Points 9 Setup    5 Manual Defrost  SELECT NUMBER                                                      12 00 12 00 ELECT ITEM 12 00 12 00 ANUAL MODES 12 00 FCIRCUIT STATUS  1 12 00 BET UP MENU 12 00  Circuit number  1  Circuit number   1  501   01   Circuit number   1  SDIC O1c Circuit number  1             STATUS        TERM Lite Group numbe  1 Refr    0 0 1 Add Edit Circuit 4 Bd Pt Assignment  2 Refr    0 0 2 Board Cct Assgn 5 0111         3 Refr   0 0 3 CCB Logging Times    Anti Sweat Setup  4 Refr   0 0  Enter Item  5 Refr       0 0   CLROEsC  CIRCUIT  01 STATUS SDIC O1c 12 00 FCIRCUIT SETPOINTS  1 SDIC O1c 12 00   SELECT ITEM   12 00 ALARM SETPOINTS 5010 01   12 00   SELECT ITEM   12 00 SCHEDULE 1 OFF 12 00  01 Case Boards befr Duration 000 Control Temp 000 0  01 CCB 01 Case Temp ALARM NOTICE  1 8010 01        From until Event o Bath Event SEE FOLLOWING PAGE  Case   01 01 rain Time an   Hi Alarm  NONE NONE i       Status On Terminate Temp 000 0 D R Weighting N A Hi Delay 0000 0000 00 00 00 00 0 00 00 SETUP SCREENS  Temp 007 0  8  Defrost          4th Defrost Lo Alarm NONE NONE 00 00 00 00 0 00 00  Term 000 0        Defrost NONE 5th Defrost Lo Delay 0000 0000 00 00 00 00 0 00 00  3rd Defrost          6th De
123. 10s OIL SENS 1800 rpm  Automatic Oil Reset  NO OIL PRES 2000 rpm minute             5 2000 rpm minute  PROOF OFF on Failur N i  P REV   NEXT   gt  SET DATA  PREV   gt  5                gt  5                gt  SET DATA                     0 of Q 12 00            SUCT DCHG SETPOINT FLOAT T  Suction             NONE NONE          NONE  Discharg A     A NONE NONE NONE NONE  Pump Dow A A A A NONE NONE NONE NONE  Qil Fail             NONE NONE NONE NONE  Phase   N       NONE NONE          NONE  T PREY 1 NEXT      8ET A   gt  SET DATA   CheckIt SENSOR SETUP  12 00    PRESSURE LOGGING INTERVAL 12 00  PRESSURE SETUP 12 00  Alarm Setpoints  150 Delay  030 m Phase  Y  Notice Setpoint  135 belay  030 m Force Comp On During Defr  Y  Disabled During Hot Gas N Delay  000 m ALL Groups  00 03 00 Run Comp During Reclaim   Y    Disabled During Reclaim N                One Comp Always Remain 00        1  Grp2  N Grp3  N                 gt  5                gt                 T PREV 4 NEXT   gt  SET DATA          TWO STAGE SYSTEM SETUP 12 00    Low Suction Group  0  High Suction Group  0      gt  SET DATA          oe eB TWO SPEED VARIABLE SPEE  SETUP SCREENS SETUP SCREENS                           TU CONDENSER SETUP CONDENSER SETPOINTS  CONDENSER RUNTIMES Te  00  CONDENSER BYPASS Te  00 CONDENSER PRESSURE INPUTS SETUP 12 00  CONDENSER PRESSURE INPUTS SETUP 12 00  Control  Value sas  PRESSURE           Ei      Fo r6    Fe F3 F4 F5 F6  Setpoint 200 0 Control Strategy  AIR COOLED Setpoint   800 0 0
124. 11 14   Condenser Control       attempt is unsuccessful  the RMCC shuts off the fan  After  a specified number of attempts are made to clear the fan   see below   the fan will be considered    failed    and will be  bypassed OFF     Num Clear Attempts  0   240   0     The number of clear attempts the RMCC will make be   fore considering a fan to be failed is entered in this field     Delay Between Clear Attempts  0   3600 sec    30  sec      The Delay Between Clear Attempts value is the number  of seconds the RMCC will wait between clear attempts       No Relays   Neither relay will be closed during  high speed operation     Relays  1 and  2 must be defined as    C1 2S REL 1     and         25 REL 2  in the Output Definitions section  see  Section 11 8 2  Output Definitions      Fan Low Output   1  2Spd Relay 1   2  2Spd Relay  2   0  Both Relays   N o Relays   1     The relay or relays chosen in the Fan Low Output field  are closed when the RMCC calls for low speed output on  the condenser fans  Options for this field are the same as for  the Fan High Output field above  except the default setting  is    2 Spd Relay  1        Fan Off Output   1  2Spd Relay 1   2  2Spd Relay  2   0  Both Relays   N o Relays   N     The relay or relays chosen in the Fan Off Output field  are closed when the RMCC calls for the condenser fans to  be turned off  Options for this field are the same as for the  Fan High Output field above  except the default setting is     No Relays      Start Spee
125. 11 2  Main Menu       MAIN MENU 12 00       1 Pressure Control  2 Condenser Control  3 Circ Defr Control  4 Sensor Control    5 Status  6 Power Monitor  7 Configuration  8 Graphs  9 Alarms    SELECT NUMBER ENT LOGOFF    11 2 1  Pressure Control       PRESSURE MENU 12 00    1 Status ress Setpts  Speed Setpts  Setpts  ixed Steps    trategy Setup    6 P  2 Bypass 7 V  3 Alarms 8 Float  4 Logs 9 F  5 Comp Setup S    SELECT NUMBER    11 2     Log On    hovel   password   Actions Alowed    Level   Password Actions Allowed  1   100   Manual Defrost    Acknowledge and Reset  Alarms    Bypass Compressors and Fans  2   200 Level 100  plus    Adjust Set Points    Clear Alarm Logs    3   300 Level 200  plus    Perform Setup Functions    4   400 Level 300  plus    Unit Configuration    Edit System Information    Edit Communication Informa   tion    Table 11 1   Password Levels and Available Tasks       Cem       Besson   Pave                                                dC                                    Page         026 1102 Rev 4 08 12 99     tem   Desorption     Pase   Compressor Setup                    Variable Speed Compressor Set Points    8 Floating Suction Set Points   09 Fixed Steps Strategy Setup       11 2 2  Bypass                COMPRESSOR BYPASS    01 NORM  CO6 NORM  NORM             1  C02 NORM  c03  c04  c05                                                    T PREV               gt  SET DATA    The bypass commands for compressors are retained  by the RMCC even if pow
126. 13 1  13 2  power demand status 13 10  pressure control 13 11  sensor 13 8  override 13 9  14 3  standard circuit 13 4  inputs 11 20  statistics 11 20  summary 13 4  variable speed compressors 13 3  Stepper Valve Control  See Case    Control  valve control    Suction Groups  See Pressure Con   trol   Superheat Control 8 1  System Configuration Guide 10 1  Define Inputs 10 2    System Settings  date  time  and day 11 55    T    Terminating Resistance Jumpers 4 3  Transducers  Discharge Pressure  setup 11 61    Transducers  Oil Pressure    offsets 11 61  setup 11 61    Transducers  Pressure  See Sensors   Pressure Transducers    Index    1 6    Transducers  Refrigerant  See Sen   sors  refrigerant transduc   ers     Transformers  Wiring Six Board 5 7  Wiring Ten Board 5 8  Wiring Three Board 5 7  wiring to case controller 7 2    U    UltraSite    defined 2 6  list of user guides 2 7    Units  Engineering 11 57  11 58    Unloaders  See Compressors  unload   ers     W    Wiring 4 2  legs and segments 4 2  number of devices per seg   ment 4 2  wire lengths 4 2  Power Connections  Transformers 5 7  power requirements for I O  boards 5 7  Specifications 5 1  Transformers 5 7    026 1102 Rev 4 08 12 99    
127. 2 00     PEWPOINT HUMIDITY OFFSETS 12 00 CIRCUIT INPUTS SETUP 12 00  Input Name  Tmp1 Irmi  bewpt      F CALL ON 65 0 ALL OFF 25 0  Dewpoint Offset  00 0 F Location  00 00 00 00  Percent ON during ALL OFF   0 Humidity Offset  00 0 X Log Interval  00 00 00 00 00 00  ALL ON   100 Bypass  NONE NONE  Current   Today Sensor Type  Temp Digit    ON Time  100 0 Offset 0000 0 0000 0  4                       MENU MEN T PREV 4            ANTI SWEAT OUTPUTS STATUS 72 00  ff  ANTI SWEAT OUTPUTS SETUP 12 00 CIRCUIT OUTPUTS SETUP 12 00  Override ON OFF Interval  010 sec Output Name        Dfr    Name Status Time Left   Name Location 00 00 00 00  1  000  n  Log Interval 00 00 00 00 00 00  2  000  2               Norm Norm  E 000 5  Run Time 00000 00000  4  000  ae  REV            f          ALARM SETPOINTS 12 00        1 ALARM NOTICE   Hi Alarm  NONE NONE   Hi Delay 0000 0000   Lo Alarm NONE NONE   Lo Delay 0000 0000      gt  SET DATA           ADVANCED DEFROST  1 12 00  Setup Advanced Defrost Options  NO    NOTE  There is no additional setup  if you select NO                    1            gt  SET DATA O MENU   CIRCUIT SETUP       1 12 00  ADVANCED DEFROST OPTIONS  Host Compressor Group    0  Hot Gas Defrost Type Standard  Compressor Start Delay 02  Defrost Suction Setpt 10 0      gt  SET DATA           CIRCUIT SETUP   1 12 00    DEFROST LOAD SHEDDING OPTIONS  Host Compressor Group    0  Electric defrost Amps   0000               gt  5                   D 2   RMCC Front Panel Screens 026 1
128. 2 00    5 Reset    Host Inputs    11 8 16 0n Line Status    Refer to the description of the Host Network State in  Section 13 2 5   Host Network Status     2716112     HOST BUS DEVICES   This Controller is Device   1  Alarm If Another Device Fails  N   Test Host Net for New Devices  N                    This Controller is Device    1   16   1     Each RMCC must have a defined device number when  more than one RMCC is being used  No two RMCCs may  have the same device number  If other non RMCC RE   FLECS controllers are connected to the host network  each    11 8 18 Reset                   11 62  Configuration    Cie                             Pase     Presta              must be identified as well  Device numbering for each RE   FLECS type always begins with the number 1     To define a device number for the current RMCC  enter  the appropriate device number in the Device   field   RMCC unit numbers should be assigned in numerical order  starting with one     Alarm If Another Device Fails   Y es   N o   N     To activate an alarm if a controller stops communicat   ing  select    Y   es in the Alarm If Another Device Fails  field     Test Host Net for New Devices   Y es   N o   N     The RMCC is capable of searching for any new device  defined to the host network  To activate this feature  select   Y es in the Test Host Net for New Devices field  After all  REFLECS controllers have been wired and configured  test  each host net for new devices     Do not select Reset if a 485
129. 4 29 CCB Set Point Screen 1  Liquid Pulse and Stepper Only     25   zu  Hla j r 2J       CS       gt  5                    The Electronic Expansion Valve  EEV  is an electroni   cally controlled expansion valve that is cycled via pulse  width modulation  PWM   The EEV regulates the opera   tion of the evaporator based on superheat measurements  from two sensors located at the inlet and outlet of the evap   orator  Set points for the control of the evaporator are de   fined at the CCB Set Points screen     Superheat Set Point  Supht Setpnt   3     247   8 0     The term    superheat    refers to the temperature differen   tial across the evaporator coil  coil outlet   coil inlet   The  Superheat Set Point is the superheat temperature the  RMCC will maintain within the selected case  Degree units  are determined by the unit selected at the System Units  screen  see Section 11 8 7  System Units      Revision    The current CCB software revision is automatically  displayed in the Revision field     Sensitivity  0   9   4     Sensitivity is a value that either increases or decreases  the reaction of the EEV to superheat changes  The lower  the sensitivity  the slower the reaction time  the higher the  sensitivity  the faster the reaction time  For a more detailed  explanation of sensitivity  see Section 5 3 1 3   Valve Con   trol     Recovery    10  100   70     System Recovery mode occurs when the valve has been  fully closed because either the temperature set point was  satisfie
130. 5 3 1 3   Valve Control     Network   whether the host network is ON or OFF     Sensitivity   the valve s sensitivity value  This may be changed using the HHT  See Section  5 3 1 3   Valve Control for a complete definition of sensitivity    Kd x10   the derivative gain value for the valve multiplied by ten  See Section 11 4 37   CCB  Set Points Screen 4  CPC Suction Stepper Only  for a complete definition of derivative gain    UpdateRate   the valve s update rate  See Section 5 3 1 2   Temperature Control for more in    formation     Ctrl Type   the method the CCB uses to combine the discharge air sensors into a control tem   perature value  Pressing RIGHT followed by a 0  1  or 2 will define the combination strat   egy     0  AVG   The control temperature is the average of all the discharge sensor readings      1  MIN   The control temperature is the lowest of all the discharge sensor readings      2  MAX   The control temperature is the highest of all the discharge sensor readings     Case Type   the case type number  See Section 11 4 16   Circuit Setup 1 for a complete list of  case types and their corresponding numbers  This may be changed using the HHT     Case     the CCB number        15 8   Hand Held Terminal Screens 026 1102 Rev 4 08 12 99    15 4  Hussmann Suction Stepper  HHT Screens    Case Type   the four letter case type code  See Section 11 4 16   Circuit Setup 1 for a complete  table of codes     Rev   the software revision number     Status   the system is op
131. 6 2 1     The RMCC may be configured to wait a specified time  period before reentering refrigeration to allow the evapora   tor coil to dry     Drain Time    9 6 2 2  Pump Down Delay    The RMCC may be configured to pump down the evap   orator coil for a specified period to ensure that refrigerant  is not present in the coil when defrost begins     9 6 2 3  Demand Defrost    The RMCC may be configured to monitor a Demand  defrost optical sensor  When the RMCC reaches a sched   uled defrost time  it first determines if the sensor has detect   ed frost buildup on the coil  If no frost is detected  the  defrost time is skipped  At each subsequent defrost time   the sensor is checked and the same determination is made  by the RMCC     A fail safe time may be entered to ensure that defrost is  initiated if the sensor is malfunctioning     9 7     In a case controlled refrigeration system  each Case  Control Board is capable of operating a single anti sweat  heater  Independent of the Case Controllers  however  the  RMCC is also capable of controlling a single circuit of up  to eight heaters  which may be used in standard refrigera   tion circuits or for other applications  Anti sweat control in    Anti Sweat Control    RMCC I amp O Manual       non case controlled RMCC networks requires a Pulse  Modulating Anti Sweat Control panel  P N 809 1105      Case controlled anti sweat may control the case heaters  using either the humidity or dewpoint value  see Anti   Sweat Control  page
132. 7  Set Floating Suction Set Points  Groups 1 4 are Accessible from this Screen    Section 11 2 12   Group 1  Floating Suction    8  Define Group Control Strategy  Groups 1 4 are Accessible from this Screen    Section 11 2 13   Group 1  Strategy Setup    10 3  Setup Condensers    1  Condenser Setup   Section 11 3 1   Condenser Setup    2  Define Condenser Input  amp  Output Pressure   Section 11 3 2   Condenser Pressure Inputs Setup  Air Cooled   amp  Temp Diff Strategies Only     3  Define Condenser Fan Delays   Section 11 3 4   Condenser Fan Delays Setup    4  Setup Condenser Fan  Single Speed Condenser Fan   Section 11 3 5   Condenser Single Speed Setup Screens  Two Speed Condenser Fan   Section 11 3 6   Condenser Two Speed Fan Setup  Variable Speed Condenser Fan   Section 11 3 7   Variable Speed Setup Screens    5  Define Condenser Fan Fail  For Single Speed Fans   Section 11 3 5 3   Condenser Fan Fail Setup  For Two Speed Fans   Section 11 3 6 3   Condenser Fan Fail Setup    6  Define Condenser Split Setpoints  Single Speed Condenser Fans Only    Section 11 3 10   Condenser Split  Setpoints    RMCC I amp O Manual System Configuration Guide     10 1    10 4  Setup Standard Circuits    1  Setup Standard Circuit  Screen 1    Section 11 4 16   Circuit Setup 1  Screen 2    Section 11 4 17   Circuit Setup 2    2  Define Standard Circuit Set Points  Screen 1   Section 11 4 18   Circuit Set Points 1  Screen 2   Section 11 4 19   Circuit Set Points 2  Screen 3   Section 11 4 20   
133. 85  Alarm Panel     Sensor alarm set points are defined at the Alarm Set   points screen  This screen will display only those sensors  defined at the Circuit Setup screens  Alarm delays are also  defined at this screen  When the RMCC generates an alarm  or a notice  it must wait the specified time delay before ac   tivating the alarm sequence     Pressing the down arrow key will allow users to specify    tion of alarms or notices when specific control values ex   ceed HI and LO alarm set points  When the current input  sensor reading exceeds the user defined HI and LO alarm    alarm and notice set points for other sensors     14 2  Case Control Alarm Set Points    Refer to the description of Alarm Set Points in Section 14 1   Alarm Set Points           14 3  Case Control Alarm Set Points  Add Edit Circuit     Refer to the description of Alarm Set Points on Section 14 1  Alarm Set Points     DAMM a i     14 4  Sensor Alarm Setpoints          Alarm Control within the RMCC includes the genera   tion of alarms or notices when specific control values ex   ceed HI and LO alarm set points  When the current sensor  reading exceeds the user defined HI and LO alarm set  points  an alarm or notice will be generated  These Sensor  Alarm Set Points are defined at the Sensor Alarm Setpoints  screen        S  44  4  AENT    SENSOR ALARM SETPOINTS  No   03 Name AMBIENT  Type  Temp Eng  Unit dF    0100 Low  0055  NONE Low NONE                Alarms  HI  Notices HI       GH  GH                
134. 99     At times  a sensor may provide a reading that reads low   er or higher than the known condition being monitored  An  offset value may be entered in the Offset field to calibrate  the sensor to actual conditions  When an offset is made to  a sensor  that value is then displayed in all status screens  and the actual or raw value will no longer appear     11 5 3  Set Points  for Linear sensor types only     n          T    SENSOR SETPOINTS LINEAR INPUT  4 01 Status ON Name   Stay ON        000  min Eng    i f 01 00                                  Using Diff  Of  0 of 0 0  Offset                                        Gain  0  ON  D pLy  10000     gt  5           OFF 0                   T PREV J NEXT    If the Sensor Type chosen in Section 11 5 1   Setup   was set to    IRLDS     this version of the Sensor Setpoints  screen will appear  All other sensor types use the Sensor  Setpoints screen as shown in Section 11 5 4  or Section  11 5 2     The Sensor Setpoints Linear Input screen allows users  to set up a generic linear sensor by specifying a gain  an off   set  and cut on cut off set points     Stay ON for  0   240 min    0 min      The number entered in the Stay ON For field is the min   imum number of minutes the sensor s output must remain  on after the ON set point is reached     Eng  Unit  5 characters max     The RMCC reads a signal from the sensor and com   pares the signal to the sensor type to determine the correct  analog value  Therefore  units of measure ar
135. Alarms Notices Setup      The RMCC will generate an alarm and shut down all  compressors when the measured suction pressure falls to a  specified Pump Down set point  Compressors will remain  shut down until the suction pressure rises to the Suction  Pressure Set Point defined at the Group 1 4 Pressure Set  Points screens  see Section 11 2 10  Group 1 Pressure Set  Points   Define the Pump Down Suction Pressure set point  in the Pump Down field     Dly  0   240 seconds   10    The Pump Down Delay is the specified duration the  measured suction pressure must remain below the  Pump Down set point before the RMCC will generate  an alarm     Automatic Oil Reset   Y es   N o   N     In screw compressor applications where low oil condi   tions are common  it may be advantageous to provide an  automatic reset whenever a low oil condition is recognized  through a digital sensor closure  When a low oil condition  occurs  the associated compressor will be shut down for 20  seconds  After 20 seconds  the RMCC will read the digital  sensor relay again  If the low oil condition remains  the as   sociated compressor will be turned on for 20 seconds  The  RMCC will run this oil pressure safety cycle three times   On the third low oil pressure occurrence  the RMCC yields  alarm and safety control to the mechanical safety device in   stalled on the compressor and turns the compressor off     If at any time during the pressure safety cycle the  RMCC finds normal oil pressure  the associated co
136. Bad Message A problem has been detected on the I O Network     Check System Now The alarm set point for a sensor defined as a Checkit monitor has been exceeded for the user defined  delay duration  see Section 11 2 5   Checkit Sensor Setup      Check System Soon The notice set point for a sensor defined as a Checkit monitor has been exceeded for the user defined  delay duration  see Section 11 2 5   Checkit Sensor Setup      Coil In A coil inlet sensor value is being generated by one of the sensor failure conditions described in Sec   tion 5 3 1 10   Fail Safe Mode  Liquid Side Control Only      Coil Out A coil outlet sensor value is being generated by one of the sensor failure conditions described in Sec   tion 5 3 1 10   Fail Safe Mode  Liquid Side Control Only      Coil2 In A coil 2 inlet sensor value is being generated by one of the sensor failure conditions described in Sec   tion 5 3 1 10   Fail Safe Mode  Liquid Side Control Only      Coil2 Out A coil 2 outlet sensor value is being generated by one of the sensor failure conditions described in  Section 5 3 1 10   Fail Safe Mode  Liquid Side Control Only      Condenser VS Fan Proof A failure has been detected in a variable speed condenser fan proof   Condenser VS Inv Fail A failure has been detected in the inverter of a variable speed condenser     Defr Timed A defrost event has timed out based on the defrost duration set point  see Section 11 4 17   Circuit  Setup 2  or Section 11 4 46   Circuit Set Points 1  Add Edit 
137. CB Status 3 screen     RMCC I amp O Manual       Super Heat    The current superheat calculation for the selected case  is displayed in the Super Heat field  The term    superheat     refers to the temperature differential across the evaporator  coil  coil outlet   coil inlet      Setpoint    The current Superheat Set Point defined for the selected  case is displayed in the Setpoint field  This set point is de   fined at the CCB Setpoints screen  see Section 11 4 49    Circuit Set Points 4  Add Edit Circuit    The Superheat Set  Point is the superheat value the RMCC will maintain within  the selected case     Coil In    The current Coil In Temperature within the selected  case is displayed in the Coil In field     Coil Out    The current Coil Out temperature within the selected  case is displayed in the Coil Out field   13 4 5  CCB Status 2  Suction Stepper  Only        Esta  E  e fo     STATUS       01SD C 01            12 00    Fan Relay   On  ights   On       For suction stepper CCBs  this status screen displays  the current status of the demand defrost sensor s   refriger   ant leak sensor  door switch  extra temperature sensors  fan  relay  and case lights     Frost    When the Demand Defrost feature is activated at the  Circuit Set Points 3 screen  see Section 11 4 48   Circuit  Set Points 3  Add Edit Circuit    the current status of the  Demand Defrost Sensor is displayed in the Frost field     Refr Leak    The current reading from the refrigerant leak sensor is  displ
138. Circuit       Demand Time Out The duration since the last defrost event has exceeded the Demand Defrost alarm time  see Section  11 4 20  Circuit Set Points 3  or Section 11 4 48   Circuit Set Points 3  Add Edit Circuit       Device ONLINE A defined communication board that was previously not responding has come back on line   Dialout Unsuccessful A user defined dialout sequence has failed     Dig  Alarm Override ON A contact closure has been detected at an input configured as a digital override input  see Section  14 5  Alarm Overrides      Discharge Tripped The discharge pressure has exceeded the user defined discharge trip point for a duration exceeding  the trip delay  see Section 11 2 10   Group 1 Pressure Set Points      Fan   99   Proof A failure has been detected in a single speed condenser fan proof   FP Level   999   Login User has logged into the system at the front panel at the 100 through 400 level     Hi Humidity The high alarm value for a sensor defined as type          has been exceeded for the user defined alarm  delay duration  see Section 14 4  Sensor Alarm Setpoints      Hi   I O Module   A high alarm set point for an Analog Input Module has been exceeded  Refer to P N 026 1002  Ultr   aSite RMCC Supplement  Section 21 1  Viewing Alarms     High Avg Temp The average temperature of all cases within a CCB case circuit is high  See Section 14 1  Alarm Set  Points     High Speed Proof A failure has been detected in the high speed fan proof of a double speed co
139. Circuit Set Points 3  Screen 4   Section 11 4 21   Circuit Set Points 4    Define Circuit Inputs   Section 11 4 22   Circuit Inputs Setup  Define Circuit Outputs    Section 11 4 23   Circuit Output Setup  Setup Advanced Defrost   Section 11 4 24   Advanced Defrost    abr      oa  ede    Setup Advanced Defrost Option  Hot Gas   Section 11 4 25   Advanced Defrost Options  Hot Gas   Electric    Section 11 4 26   Advanced Defrost Options  Electric     10 5  Setup Case Control    1  Define CCB Set Points Screen 1  Liquid Pulse and Stepper Only    Section 11 4 29   CCB Set Point Screen 1  Liquid Pulse and Step   per Only   CPC Suction Stepper Only   Section 11 4 30   CCB Set Points Screen I  CPC Suction Stepper Only   Hussmann Suction Stepper Only   Section 11 4 31   CCB Set Points Screen I  Hussmann Suction  Stepper Only     2  Define CCB Set Points Screen 2  Liquid Pulse and Stepper Only   Section 11 4 32   CCB Set Point Screen 2  Liquid Pulse and Step   per Only   Suction Stepper Only   Section 11 4 33   CCB Set Points Screen 2  Suction Stepper Only     3  Define CCB Set Points Screen 3  Liquid Pulse and Stepper Only   Section 11 4 34   CCB Set Point Screen 3  Liquid Pulse and Step   per Only   Suction Stepper Only   Section 11 4 35   CCB Set Points Screen 3  Suction Stepper Only     4  Define CCB Set Points Screen 4  Liquid Pulse and Stepper Only   Section 11 4 37   CCB Set Points Screen 4  CPC Suction Stepper  Only   Stepper Only   Section 11 4 38   CCB Stepper Set Points Scre
140. Command Output turns ON  The initial  value of the Count output is entered by the user  as well as  the amount the Count output is incremented every time an  ON is detected     If desired  the Count cell may also be configured to turn  on a digital output whenever the Count value exceeds a  user specified Trip Setpoint  This digital output  called the  Count Tripped output  may be connected to a relay on an  alarming device  or it may be used as an input for another  I O Module     The Count output value is reset by sending a signal to  the Reset Count input  The user specifies whether the count  will be reset when the Reset Count is ON  OFF  or transi   tioning from ON to OFF  When the appropriate type of sig   nal is read from the Reset Count output  the Count output  reverts to the initial value specified by the user     Counting may be suspended via the Suspend Count in   put  While this input is ON  the Counter will not increment  the Count output regardless of the state of the Command  output     Select    The Select cell s primary function is to send either of  two values to the Proof cell  the output value from the Min  On Off cell  or the final Command Output value from the  Override cell     In most cases  the final Command Output value would  be used for proof checking  since this Output will be mir   roring the Proof input  However  for relays or modules that  are controlled by digital pulses  supplied by the One Shot  cell   the pulse from the output will not mat
141. Ct HERO Od reef        12 1  12 1 5  CCB  Log Interval is sinrin aioir tete tese ERE Ue           SUN e Ee ENE eet saepe Ea vede et ote 12 2  12 1 6  Sensor O98  ease Een po p Rp intere 12 2  127  Hourly Demand              ea ve ER Ped RR Re e OE ee EORR        12 2  12 1 8   Daily Demand                 ter              per pO PU I t E      RH Pe E e a RR ER eed 12 2    viii   Table of Contents 026 1102 Rev 4 08 12 99    ADD                           E EE                                                     12 3    12 2 1 Graph Control Screen    eate oe eo ape iren seine ERI a          12 3  12 2 2    Graph View  eed eio etr mde ER d ve ie m           R E 12 3  LEE EM NBI LEO  D ESTE 13 1  13  T  MAIN STATUS SCREEN  tete rtr x CR        PERDU EEUU RE REOR REFUND LEE aE E 13 1  TILT     CONDENS CP SIGHS css RE da an gena ui a 13 1  13 2  STATUS  MENU ji   erri ee ERIS PU ER CEP Ee EDAD        EDEN RR SEEN RUE HERR eS          13 2  13 2  L   MIM Status   ose ent tete uerit quita bie tete ite cte au      hte 13 2  132222          Status                   ftre ett ordre ger eae ERE ERO N        13 3  13 2 3  Variable Speed Status  eec OPERE I SERE ERE doves             Foe rede 13 3  13 2 4  I O Network Status  I O Board Status              eese eene nennen        13 3  13 2 5                                               t taie RATA NEA ERAS 13 3  13 3   CIRCUDITSA          nti RE RO DERE E E RE ERU UE EROR RR 13 4                                        d MI Bu 13 4  132322   
142. Delay  0000 0000 00 00 00 00   Enter Defaults  No   ist Defrost          4th Defrost NONE Lo Alarm  NONE NONE       Circuit             Temp    0 0  0 0 End Defrost          Sth Defrost NONE Lo Delay  0000 0000 Master 114 Line Solenoid  None  Term C   3rd Defrost          6th Defrost NONE Enter Ite  a EE              1            gt  SET DATA O MENU O MENU O MENU T PREV 1            gt  SET DATA O MENU  CIRCUIT INPUTS 01 12 00 FCIRCUIT SETPOINTS  1 12 00 12 00 HOLIDAY SCHEDULE 12 00   CIRCUIT SETUP     1 12 00  Temp  Cleaning Override Switch  None NONE 0 682 Date Defrost Type   Hot Gas  Term  Cleaning Switch Type Switched 000h NONE 1  00 00 Defrost Termination Type  Stat NORMAL  Wash Switch  Cleaning Notice Enabled   No NONE 3  00 00   Termination Sensors 0  Demand  NONE 5  00 00 Temperature Strategy Full  NONE 7  00 00     Temp Sensors Strategy   0 Avg  NONE Fans On During Defrost   No                                                                                                                                     4            gt  SET DATA 1          4            gt  SET DATA 1          4            gt  SET DATA O MENU  CIRCUIT STATISTICS 12 00 FCIRCUIT SETPOINTS  1 12 00 GRAPH CONTROLS FCIRCUIT SETPOINTS    1 12 00  CYCL Su Mo      We Th Fr Sa befr Duration 000 Control Temp 000 0  R  r o 0 o 0 o 0 o   Demand Sensors   0   gt   lt   Scroll brain Time 000 Dead Band 000 0  Dir 0 0 0 0 0 0 0 Demand Fail safe Time  000 hrs      Go to current                    Temp 000 0  RUN A
143. ECKIT  iYES  SENS LO            COMP PRES                      YES  MISC      gt  5                                                     T PREV J NEXT    If a Send Notices to 485 Alarm Panel field is set to    YES  both alarms and notices for the alarm types with   in the category will be filtered  Users may keep notices  from being sent to the panel by setting the Send Notic   es field in Section 11 8 3  to    N        Using the Send to 485 Alarm Panel screen  users may  choose which alarm types to send to the 485 Alarm Panel   Alarm types within a category marked with a YES will be    RMCC I amp O Manual            Name    The   and Name fields display the sensor number and  the sensor name respectively     Ovrd    The Ovrd field displays the number of the alarm over   ride input assigned to each sensor     St    The St field displays the operational status  either ON  or OFF  of the alarm override for each sensor     Type   The Type field shows whether the alarm override is  fixed or timed for each sensor   Time    For timed overrides  the amount of time remaining in  the override duration is shown in the Time field     sent to the 485 Alarm Panel  alarm types within a category  marked with a NO will not be sent to the alarm panel     The ten different alarm filter categories and the alarm  types within each category are listed below  For additional  information on alarm types  see Table 14 1 on page 5     e Ckt Hi  Circuit High    This alarm type includes the  Hi Temp and 
144. G    RANGE    o m         Hom  DOD  I           5 5                     26512007    Figure 9 2   Typical PID Control      SITE        The RMCC controls temperature within the cases of a  circuit by varying the suction pressure of a compressor  group based on a user defined suction set point  The suc   tion pressure is adjusted by cycling compressors on or off   or  in the case of variable speed compressors  adjusting the  speed of the compressor     The RMCC is capable of simultaneously controlling up  to four compressor groups with a total of 16 compressor  stages designated for any single group  However  no more  than 22 compressor stages may be defined for a single RM            Each compressor group may contain a single variable  speed compressor  and the RMCC is capable of controlling  multiple stages of unloading within each group     9 4 1  Control Strategies    The RMCC provides two methods for controlling suc   tion pressure  normal and fixed steps  CPC recommends  using normal control whenever possible since it provides a  greater degree of control over the suction group     9 4 1 1  Normal  PID Control     The normal control strategy is a method of managing  the suction group using PID control  Normal control mea   sures the suction pressure  compares it to the suction pres   sure set point  and generates a PID output percentage from  0 100   This percentage corresponds to the percentage of  total compressor horsepower that will be activated  For ex   ample  if 15 
145. HP     In this field  enter the horsepower of the fan  or the total  horsepower  if more than one fan  that is active when the  condenser is operating at low speed     11 3 7  Variable Speed Setup Screens    The following screens are accessible only if the Con   denser Fan s  Type field is set to    Variable Speed        Single   and two speed setup screens are described in the Condens   er Single Speed Fan Setup and the Condenser Two Speed  Fan Setup sections  on Section 11 3 5  Condenser Single   Speed Setup Screens and Section 11 3 6  Condenser Two   Speed Fan Setup  respectively      RMCC I amp O Manual             High Speed HP  0   240 HP   100 HP     In this field  enter the horsepower of the fan  or the total  horsepower  if more than one fan  that is active when the  condenser is operating at high speed     11 3 6 3  Condenser Fan Fail Setup                   CONDENSER FAN FAIL SETUP  Fan Fail Enable         Fan Fail Delay       10005     Continually try to Clear Failure      0   Num Clear Attempts    Delay Between Clear Attempts 0030 sec    T PREV              gt  SET DATA                   Refer to Condenser Fan Fail Setup on Section 11 3 5 3   Condenser Fan Fail Setup     11 3 6 4  Condenser Two Speed Fan Fail Setup         C2  Es      CONDENSER 2 SPEED FAN FAIL SETUP       12 00             Try Other Speed On Fan Fail  NO         gt  SET DATA O MENU    Try Other Speed On Fan Fail   Y es   N o   N     The Try Other Speed On Fan Fail feature allows the  RMCC to com
146. Hi Avg Temp alarms     e Checkit  This alarm type includes the Check Sys   tem Now and Check System Soon alarms     e Sens Hi  Sensor High    This alarm type includes  the Hi Sens and Hi X Ducer alarms generated by  Sensor Control       Sens Lo  Sensor Low    This alarm type includes the  Lo Sens and Low Avg Temp alarms generated by  sensor control       Sens Fail  Sensor Fail    This alarm type includes  the IRLDS Fault  Sensor Fail  Sensor Short  Sensor  Open  Xducer Short  and Xducer Open alarms     System Navigation     14 3    e Comp Pres  Compressor Pressure Alarms    This  alarm type includes the Auto Reset  Discharge  Tripped  Hi Suction  and Oil Pressure alarms     e Refr Leak  Refrigerant Leak    This alarm type in   cludes the Leak alarm         CCB Sens  CCB Sensors    This alarm type includes  the Coil In  Coil Out  Coil2 In  and Coil2 Out  alarms     e Network   This alarm type includes the Bad Check   sum  Bad Message  Device ONLINE  Host Bus  Network Down  Missed Token  and No Response  alarms       Miscellaneous   This alarm type includes all other  alarm messages not covered in the first nine catego   ries  These include the Condenser VS Fan Proof     14 8  Alarms               129  Description                  7ack 9reset Rclear  switch Omenu       The RMCC Alarm Log is similar to other RMCC Logs  in that it records specific occurrences within the RMCC ac   cording to the user defined logging interval and stores the  information for later review  Specifical
147. IMES  F1 F2 F3  00000  00000  00000                                                  7  8  9  1  00000  00000   00000       11 18   Condenser Control          Ambient Split Temp   50   99     N one   50     The Ambient Split Temperature is the temperature at  which the condensing capabilities of the condenser are re   duced   or split   either by limiting the number of fans that  may be operated or by activating a valve which reduces the  effective cooling area of the coil     Configuration of condensers during split operation is  defined at the Condenser Setup screen  see Section 11 3 1   Condenser Setup      Ambient Split Temp During Reclaim   50   99      N one   N     When heat is being reclaimed  it may be desirable to  have the condenser split at an ambient temperature higher  than the Ambient Split Temperature set point  Degree units  are determined by the unit selected at the System Units  screen  see Section 11 8 7  System Units      Ambient Split Temp Deadband  0   99     N one    4 0     The dead band is a value equally above and below both  the Ambient Split Temperature and the Reclaim Ambient  Split Temperature set points within which the ambient out   side temperature is considered to be acceptable  This value  ensures the condenser does not drop in and out of split  mode when the ambient outside temperature hovers around  the split temperature set point  To define an ambient split  temperature dead band  enter a value between 0  and 99 F  in the first Dead Band
148. INSTALLATION 5 2 eerie err                                                         7 1      CASECONTROLEER iiie cse uer ete teer eee ves belt eee eedem      eee doe pre cue 7 1  74                                                                    E                            7 1  7 2 SPOWER                     E EE                                      7 1  T3    JUMPER SETTINGS  5 acer RI RETINERI DORUM GI ee        7 2                                                                          7 2  7 5     OPTIONAL INPUTS AND OUTPUTS             les reae                          veedeesueel desessunettedes 7 2  TOs  CABLE HARNESSES 5 exces IER                                                        7 3  7 6 1    Input Cable      esis eene ladite ente e tite eel eerie eta 7 3    iv     Table of Contents 026 1102 Rev 4 08 12 99    46 2  Output Cables   di d tae ra e io e tire gie a toe ep etae Rp hd 7 3    7 37     POWER                   noui IT e HERR EREMO EGER RR HERR EFLENT 7 4  797 SENSOR LOCATION                     e AO aae reete cui aee mp EE eee 7 5  7 8 1  Discharge Air Sensor  Green Leads                         7 5  7 6 2   Coil  Inlet Sensor  Blue Leads  3 eed aede ban a e ei EG i ite t 7 5  7 6 3  Coil Outlet Sensor  Red Leads                esee seen entere enne ennt ener senten sosie nre                        7 5  RI A dem E 7 5  8 CASE CONTROL SOFTWARE OVERVIEW                                     1                                                      sta       
149. INV4 RESET  SCHEDULE 1   SCHEDULE 4  GRPI LLS   GRP4 LLS  CRCTO1 DFR   CRCT48 DFR  CRCTO1 RFR   CRCT48         CRCTO1 FAN   CRCT48 FAN  ASW 1   ASW 8   VS COMP 1   VS COMP 4   C1 VS FAN        VS ALM   C1INV RST   C1 FAN CON   C1 2S RELI   C1 2S REL2    Contacts close when an inverter fault condition occurs  see Section 11 2 11  Group 1 Vari   able Speed Set Points         Table 11 6   List of Outputs Configurable at the Output Definitions Screens    11 8 3  System Information    01 10 96 05 20    100        gt   lt 5                 T PREV                             General information such as defining          identifi   ers  the power up self test  summer and winter start dates   and user passwords is defined at the RMCC System Infor   mation screens  The System Information screen is the first  of six screens where such information is entered     RMCC I amp O Manual       Unit Name  25 Character Limit     The Unit Name is a user defined identifier that is used  to identify the specific RMCC on modification and status    screens within UltraSite    Enter    unique name in the Unit  Name field     Date Time Day  01 01 00   12 31 99   00 00   24 00     The RMCC contains a real time clock that is used when  logging information to the various logging screens  It is im   portant that the system date and time be accurate  Many  RMCC applications use the system date and time to record  important information  To set this clock  enter the current  date and time in the Date and Time
150. Light Schedules    Refer to the description of Lighting Schedules on Sec   tion 11 4 14  Light Schedules     13 2118     11 4 43 Setup                  7e                  1 Add Edit Circuit 4 Bd Pt Assignment  2 Board Cct Assgn 5 Utilites CCB Logging Times  3 CCB Logging Times 6 Anti Sweat Setup Board Point Assi 1143  oard Point Assignment    6  Anti Sweat Setup 11 44       11 4 44 Circuit Setup 1  Add Edit Circuit     Refer to the description of Circuit Setup 1 on Section  11 4 16  Circuit Setup 1           2      1  eee       11 38  Circuit Defrost Control 026 1102 Rev 4 08 12 99    11 4 45 Circuit Setup 2  Add Edit Circuit           G2    9   1           s       CIRCUIT SETUP     1  Defrost Type    Defrost Termination Type                            Termination Sensors  Temperature Strategy      Temp Sensors Strategy    Fans On During Defrost    T PREV LzNEXT                                       case control circuits are set up at the Circuit Setup  screens  Each defined circuit is set up separately at these  screens  If the Enter Defaults feature is activated at the First  Circuit Setup screen  see Section 11 4 16  Circuit Setup 1    the default settings for the defined case type should be dis   played in all fields at the Circuit Setup 2 screen     Defrost Type   H ot Gas   E lectric   R everse Air    T imed     The defrost type for the selected circuit is defined in the  Defrost Type field and should be defined according to the  case type  Enter one of the following d
151. Liquid  Level    Connect to  Input Point  by Board    Type    16AI Any   Available Point  8IO Any Avail   able Input Point                Connect RED power    wire to  12VDC TO  12V  source on input ON BOARD  board  A   Connect BLACK  ground wire to odd  numbered terminal   Connect GREEN sig   nal wire to even num   bered terminal        Set input dip switch  down     v  ODD    TERMINAL TERMINAL       207 1000 Refrigerant  Level Trans   ducer  Hansen  Probe     16AI Any   Available Point  8IO Any Avail   able Input Point       Wire BLACK  ground wire from     GND    sensor ter   minal to odd num   bered board    terminal  TOODD  TOEVEN   Wire GREEN sig  TERMINAL TERMINAL  nal wire from    SIG    NAL    sensor   terminal to even   numbered board ter      lt   minal  TO  12 VDC  Wire RED power ON BOARD  wire from     POWER    sensor  terminal to 12VDC  terminal on board     GREEN  SIGNAL     Set input dip switch  down        203 1902 Dew Point  Probe    Table 5 1   Sensor Wiring    RMCC 1 amp 0 Manual    16AI Any  Available Point    8            Avail   able Input Point    ARTC An Aux  Input    Connect the WHITE and GREEN wires  to ACI and AC2 power terminals     Connect BLACK ground wire to odd  numbered board terminal     Connect RED signal wire to even num   bered board terminal     Set input dip switch up        Communication and Power Connections     5 5    Connect to  Input Point    P N                                                                         by Board  Type
152. Mounting Dimensions    3 3     Location    485 Alarm Panel    The 485 Alarm Panel is used to alert store personnel to  system problems that require immediate attention  there   fore  it is important to mount the panel where it will be vis   ible and easily accessible     Mounting    The 485 Alarm Panel is supplied with four mounting  holes in the rear panel of the enclosure  These holes are ac   cessible without removal of any boards inside the enclo   sure  Figure 3 10 shows the enclosure dimensions and  weight     026 1102 Rev 4 08 12 99    i 485 ALARM PANEL i     REAR OF ENCLOSURE     WEIGHT  4 LB           26509004       Figure 3 10   485 Alarm Panel Mounting Dimensions    3 4     Location    RS232 Bus Amplifier    Although there are no specific location requirements  for installation of the RS232 Bus Amplifier  it is recom   mended that the amplifier be located close to the bussed  CPC controllers to prevent data loss over long cable  lengths  It is also recommended that the bus amplifier be lo   cated adjacent to the modem and  if present  the local com   puter terminal to provide easy access to all components  necessary for building control     In some cases  location of the modem and local termi   nal will not allow location of the bus amplifier to both the  modem and local terminal and the CPC controllers  Since  data loss is possible when multiple CPC controllers trans   mit data over long cable lengths  it may be necessary to  connect the CPC controllers to a remot
153. NALOG OUTPUT MODULE 01 BYPASS  Name        OUTPUT 01                Enable        Value  Time    000            NORMAL  10005 minutes             Ov State UNKNOWN Time Left 00000 sec  T PREV j4 NEXT   gt  5        The Value output of the Analog Output Module may be  overridden using this screen     Name  15 characters max   AV OUTPUT  module  number      If desired  enter a name for the analog output module in  the Name field     Enable  Yes  No   N     The Enable field allows users to turn an individual An   alog Output Module on or off without having to use Ultra   Site  Entering Yes in this field enables the current module   entering No in this field turns off the module     Value  0   100   0     The value to which the Value output will be overridden  is entered in the Command field     11 50   Sensor Control       e Timed   The output will be overridden to the value  chosen in the Command field for the amount of time  entered in the Time field  see below   This override  may also be terminated by selecting    Normal    in  the Command field     Time  0   68 minutes   5 minutes     The value entered in the Time field will be the number  of minutes a timed override will last     Ov State    The Ov State is a read only field that shows the current  state of the Command override  either Fixed  Timed  or  Normal      Time Left    The Time Left field is a read only field showing the  amount of time left in a timed override  When no timed  override is being carried out  the Tim
154. O boards  the network dip  switch labeled S1  or S3 for the 16AI board  is used to set  the unique board number of the unit and the baud rate  The  8IO uses rotary dials to set the board number of the unit     4 13 1  Network Addresses    Board numbering is accomplished using the first five  rockers on dip switch S3 on the 16AI board  the first five  rockers on dip switch S1 on the SRO and 8RO FC boards   and two rotary dials on the 8IO board     Dip Switches    Each of the first five rockers of either S1 or 53 is given  a value which is twice as large as the value for the rocker to  the left of it  The first rocker is given a value of one  With  these five rockers  a board may be given any value between  1 and 31  however  network restrictions limit the actual  number of boards that may reside on both the COM A and  COM D networks at one time  These restrictions are given  in Section 4 7   Number of Devices per Segment  Use Fig   ure 4 10 to determine the switch settings for 16   1  8RO   and 8RO FC boards     If a pulse type input is connected to a 16AI Board with  software older than version E 02  the input must be con   nected to point one  and rocker number eight on the board   s  network dip switch and must be configured to the ON or up  position                                                                                                                                                                                                                          Figure 4 1
155. ON SETPT  80 DEG F    50      DEWPOINT  45 DEG F  OFF     ALL OFF SETPT                                  20 DEG F    Osec 5 sec 10 sec       T ALL ON SETPT  80 DEG F    DEWPOINT    30 DEG F         ALL OFF SETPT    20 DEG F    Osec sec 10 sec  26512014    Figure 9 7   Illustration of Anti Sweat Control    Each anti sweat heater output may be configured to  override OFF when a defined contact closure is detected     Software Overview     9 7    Anti sweat heaters may also be overridden manually from  the RMCC front panel or by using UltraSite         ensor contro    The RMCC can monitor a total of 48 generic sensors  configured by the user     Section 7 6   Sensor Control  provides the set points  and setup functions necessary to customize a generic  sensor input  Users may select from several sensor types  and may make adjustments to gain and offset to ensure  accurate values are read by the RMCC  On  off  and delay  values  entered at the sensor set points screen Section  7 6 5   determine when a generic output will be activated     A generic sensor input is tied to a generic sensor output  by defining a board and point for the sensor output under  Section 7 9 2   Output Definitions     m                 RMCC Input and Output Modules are not program   mable from the RMCC front panel  I O Modules may  only be programmed using UltraSite version 1 31 or  greater  For specific I O Module programming instruc   tions  see the UltraSite User   s Guide RMCC Supple   ment  P N 026 10
156. POWER OR STEPPER MOTOR 3  OPTIONAL VALVE POWER OR STEPPER MOTOR 4  CCB GROUND   STEPPER MOTOR 5                   QOOOOQOOOOQOQOOOOOD                 26513022    Figure 7 4   Output Cable Harness Without Quick Connects   335 3156  Schematic Diagram    CASE  CONTROLLER  BLUE    GREEN  ORANGE          POWER  MODULE    24 VAC 1    BROWN  ANTI SWEATS CONTROL  LIGHTS CONTROL     RED  CCB GROUND  24 VAC 2 177 PURPLE  DEFROST CONTROL  FANS CONTROL f                9        WHITE  WHITE  BLACK YELLOW  PURPLE RED  PULSE VALVE 1 OR STEPPER MOTOR 1 BLACK  PULSE VALVE 1 OR STEPPER MOTOR 2 YELLOW  OPTIONAL VALVE POWER OR STEPPER MOTOR 3  OPTIONAL VALVE POWER OR STEPPER MOTOR 4  STEPPER MOTOR 5                                QOQOOOOQOOOOQOQOOHOOOD                    26513023    Figure 7 5   Output Cable Harness With Quick Connects  335   3158  Schematic Diagram    Case Control Installation   7 3    Full Output Cable for Sporlan Suction Stepper Bipolar  Valve    CPC s case controller full output cable harness  335   3159  is designed for use with a stepper valve case control   ler controlling a Sporlan suction stepper bipolar valve  The  connector is constructed with 18 AWG color coded wire  with a 16 pin  male end connector for connection to the  case controller  an 8 pin  male end connector for connec   tion to a CPC power module  and a 4 pin female end con   nector for connection to the Sporlan valve     The schematic diagram for this cable is shown in Fig   ure 7 6     CASE  CONTROLLER 
157. Points    Case Control Circuit set points are also accessed by se   lecting the Setup command from the Case Circuit Control    11 32   Circuit Defrost Control       The RMCC assumes that power wiring is designed for  a maximum load equal to all compressors running at the  same time  When defrost is initiated  the defrost output is  delayed for one minute  During this time  a compressor  control algorithm determines how many amps are available  to run the defrost output and interlocks one or more com   pressors  if required  to make more current available for de   frost     Compressors bypasses take priority over load shedding   if a compressor is bypassed ON  it will not be deactivated  by this feature  Also  if the One Compressor Always Re   main On feature is enabled for the compressor group  see  Section 11 2 8  Pressure Setup   one compressor will re   main on even if the Advanced Defrost calls for all compres   sors to be deactivated     Enter the circuit   s compressor group or suction group  number in the Host Compressor Group   field  or enter a  zero to disable the feature   1   4  Group Number   0  Dis   able   Enter the number of amps being drawn by the defrost  heaters in the Electric Defrost Amps field   999   999       em                Pese        e tesGehs          Summary      8   Light Schedules  Lx    Setup    Menu  For descriptions of these screens  see Section  11 4 46  Circuit Set Points 1  Add Edit Circuit                  026 1102 Rev 4 08 12 99    11 
158. Pulse and Stepper Only                 seen 11 36  11 4 37  CCB Set Points Screen 4  CPC Suction Stepper                    11 37  11 4 38  CCB Stepper Set Points Screen  Stepper Only                 essere nennen enne eene      11 37  11 4 39   Manual Defrost i a eret a eee hee sas b          e e           11 37  11 440                        bis marier n OPE ete d e n ederet tea                   11 38  JURE UENIT dg ERE                            11 38  71  4 42  Light Schedul  s      eme aa ERR Deae e p ep           PED 11 38  IU RT M                                                  11 38  11 4 44  Circuit Setup 1  Add Edit Circuit                            11 36  114 45    Circuit Setup 2   Add Edit Circuit     iere p te Rt EXER ERG TELS          DR XE ERE NR AES 11 39  11 4 46  Circuit Set Points 1  Add Edit Circuit                                   11 40  11 4 47  Circuit Set Points 2  Add Edit Circuit               eee eese esee nennen nennen tenete nere      11 41  11 4 48  Circuit Set Points 3  Add Edit Circuit              eee eese seen nennen nennen nennen enne enne 11 42  11 4 49  Circuit Set Points 4  Add Edit Circuit  receret anaE E E EER AES EE EES        11 42  11 4 50  Circuit Inputs Setup 1  Add Edit Circuit                   esee eterne nennen nennen nennen      11 42  11 4 51  Circuit Outputs Setup  Add Edit Circuit                     eese eee enne entree nnne tnter 11 42  11 4 52                 Circuit Assignment    sime p dr eer Her RR det ERR e E se
159. RES  YES  CCB SENS   YES  MISC      gt  lt 5                                         T PREV                If a Send Notices to 485 Alarm Panel field is set to    YES  both alarms and notices for the alarm types with   in the category will be filtered  Users may keep notices  from being sent to the panel by setting the Send Notic   es field in Section 11 8 5  to    N        Using the Send to 485 Alarm Panel screen  users may  choose which alarm types to send to the 485 Alarm Panel     RMCC I amp O Manual          DAYLIGHT SAVINGS MODE   1  Auto   2  Manual    3  None   Auto     The RMCC contains a real time clock that is used when  logging information to the various logging screens  When  the current time changes to standard time or to daylight  saving time  the RMCC s clock should be modified accord   ingly  Time changes occur twice a year in most areas   Methods for defining how the system will change its set   tings for daylight savings time are defined in the DAY   LIGHT SAVINGS MODE field     The clock may be configured to change according to the  standard USA Daylight Savings Time dates  according to a  user defined date  or for areas that do not participate in day   light savings time  the clock will not be modified     DST MANUAL SET START  01 01 00   12 31 99    04 05   DST MANUAL SET END  01 01 00   12 31   99   10 25     If the Manual method is chosen in the DAYLIGHT  SAVINGS MODE field  the RMCC will modify the sys   tem time on the specified dates  RMCC system se
160. RM OVDI   ALARM OVD8   see Section 11 8 1   Input Definitions and Section 14 5   Alarm Overrides      Ovrrd A contact closure has been detected at an input defined as a clean switch  CLEANSW   see Section  11 2 8   Pressure Setup  and Section 11 8 1   Input Definitions      Table 14 1   RMCC Alarm Log Notice and Alarm Messages       14 6   Alarms 026 1102 Rev 4 08 12 99    Notice Alarm Description  Message  Phase Fail A contact closure has been detected at an input defined as a phase loss device  PHASE LOSS   see  Section 11 2 8   Pressure Setup  and Section 11 8 1   Input Definitions    Phase Restored A open contact has been detected at an input defined as a phase loss device  PHASE LOSS   see Sec   tion 11 2 8   Pressure Setup  and Section 11 8 1   Input Definitions    Power Failed Power loss detected at the unit     Pump Down The measured suction pressure has fallen below the user defined Pump Down set point  see Section  11 2 3   Group 1 Pressure Alarms Setup      RM Level   999   Login User has logged into the system from a remote location at the 100 through 400 level     RMCC has been reset without a power loss     Run Proof A contact closure has been detected   within the proof delay duration   at an input defined as a com   pressor proof device        01 PRF   CMP22 PRF   see Section 11 8 1   Input Definitions  and Sec   tion 11 2 3   Group 1 Pressure Alarms Setup     Sensor Short A short has been detected at a sensor input connection  SENSO1   SENS48   see Section 11
161. RMCC will use the Minimum Condensing  Setpoint as the control set point     Evaporative condensers may use a combination of one  or more sensor values as a control value  Some of the com   bination strategies used in evaporative condenser control     namely Average  AVG  and Minimum  MIN    may not  yield appropriate control values for use in Fast Recovery   because a high pressure in one sensor might have little or  no effect on the control value  Since the Fast Recovery fea   ture is designed to keep discharge pressure from going too  high  it might be a better option to use the maximum sensor  value as the control value for Fast Recovery     To use the highest sensor value as the Fast Recovery  control value  select Max in this field  To use the same con   trol value that is used in condenser fan control  select Ctl  Value     Low Pressure Cutoff Setpoint   99   999 or NONE    NONE     The Low Pressure Cutoff Setpoint is the lowest con   denser control input value at which the condenser control  fans will be allowed to operate  If the condenser control  value falls below this set point  all condenser fans will be  deactivated EXCEPT those in bypass     The RMCC uses a Low Pressure Cutoff Hysteresis de   fault value of 2 0 to determine the control input value above  which the RMCC will exit recovery mode  The Low Pres   sure Cutoff Hysteresis is added to the Low Pressure Cutoff  Setpoint For example  if a condenser s discharge pressure  is 49 psi when the Low Pressure Cutof
162. Rev 4 08 12 99    2 39  Output Communication    Boards    When a REFLECS receives data from the 16AI board   it interprets that information based on current stored set  points  System changes required as a result of this exami   nation are then made through one of several output commu   nication boards  CPC offers four different output boards for  refrigeration system control  1  8RO  Relay Output Board   2  8RO FC  Form C Relay Output Board  3  4AO  Analog  Output Board and 4  8DO  Digital Output Board     2 3 1  8RO Board    The 8RO Relay Board is a general purpose board capa   ble of supplying an output signal through any of eight stan     dard contact relays     A maximum of sixteen SROs and SRO FCs        be  connected to an RMCC through the RS485 COM A and  D networks     To function  the 8     board must be connected through  the RS485 I O network to the REFLECS  When properly  installed  the 8RO receives an electrical impulse from the  REFLECS  which either opens or closes any of eight con   tact relays  Output definitions within the REFLECS soft   ware allow the user to configure the 8RO board to interact  with any refrigeration system component     The 8RO board is the direct link between the REFLECS  and refrigeration system component operation  Information  gathered by the controller from the 16AI board or 810  board is checked against current stored set points  If differ   ences in the received input data and the set point informa   tion are detected  a signal is
163. S C16 NORM C20 NORM Low Suct 01 0 DLy 060m RUN TIME VS MINIMUM SPEED  0900 rpm O1   0  RUN         17 NORM C21 NORM Pump Down 00 5  DLy 010s OIL SENS VS MAXIMUM SPEED  1800 rpm MIN SUCTION 020 0 02   0  OIL PRE C18 NORM C92 NORM Automatic Oil Reset  NO OIL PRES MAX INCREASE RATE  2000 rpm minute bs   0  H  POWE  19 NORM HPIAMPs s MAX DECREASE RATE  2000 rpm minute er Defrost  10 0    0  PROOF PROOF s Altern  Strategy  N OFF on Fai lur N 0 05   0  EV g NEXT   gt  SET DATA  PREV   gt  SET DATA Press  H  for Help  lt             GRP3 PRESSURE ALARMS 12 00 GROUP2 SE    VARI SETPOINTS 12 00 12 00 9 0  To Toggle Compr  12 00   High Suc 5 0 Dly  Dchg Alm    TYPE CMP 01 02 03 04 Contr  by      xit  Prev    Hest   Low Suct 01 0      RUN TIME VS MINIMUM SPEED  0900 rpm  cLRI   Clear Step     Last Step   Pump Down 00 5 DULY OIL SENS VS MAXIMUM SPEED  1800 rpm MIN SUCTION 020 0  D Insert Step  D  Delete Step   Automatic Oil Reset OIL PRES MAX INCREASE RATE  2000 rpm minute   HPIAMPS MAX DECREASE RATE  2000 rpm minute er Defrost  10 min Max Number of Steps for This group  20  PROOF 1 8 y  N OFF on Failur  0  REV 4 NEXT       ET DATA  PREV   gt  SET DATA T PREV 4 NEXT   gt  SET DATA                                                                GRP4 PRESSURE ALARMS SETUP 12 00 GROUPS SETUP SETPTSCENABLED  12 00          SETPOINTS 12 00 12 00  High Suct 45 0 01   060   Dchg Alm Y TYPE CMP  01 02 03 04 L Contr  by PRESSURE  Low Suct 01 0 Dly 060m RUN T  ME  vs 0900 rpm  Pump Down 00 5  Dly 0
164. S may be accessed through UltraSite using pop up  dialog boxes that duplicate information displayed on the  screen of the controller  Changes made to set points in the  dialog boxes are immediately transferred to the unit  Con   trol of the system using the new parameters is instanta   neous     026 1102 Rev 4 08 12 99    Although most users will make alterations to the system  using the front panel of the REFLECS  individuals who  have access to a laptop computer may find it easier to enter  data   especially during start up   using UltraSite  A list of  the available UltraSite user guides are listed below     Pato   Desorption          026 1002 UltraSite User s Guide    026 1003 UltraSite User s Guide BEC Supplement  026 1004 UltraSite User s Guide BCU Supplement  026 1005 UltraSite User s Guide RMCC Supplement    Table 2 1   UltraSite User s Guides       RMCC I amp O Manual    Hardware Overview     2 7    3 Hardware Mounting    Hardware Mounting provides all information necessary  to assemble a refrigeration system control network     3 1  Refrigeration Monitor and    Case Control    Location    The operating environment of the          is  20  F    28 9  C  to 120  F  48 9  C   and 0  to 95  humidity     non condensing     The Refrigeration Monitor and Case Control  RMCC   is the main controller of the CPC refrigeration control net   work  As such  it is the component most accessed by store  managers and service technicians  The RMCC should be  located in an easily access
165. TE signal  wire to even numbered  terminal     Connect BLACK ground  wire to odd numbered  terminal     Connect the bare  SHIELD wire to odd  numbered terminal   Set input dip switch  down        WHITE TO   gt  EVEN 4 TERM       BLACK TO  ODD   TERM                      SHIELD  BARE  WIRE     TO ODD   TERMINAL                            STANDARD  TRANSDUCER                               203 5750    Relative Humid   ity Sensor    16AI Any   Available Point  8IO Any Avail   able Input Point    ARTC An Aux  Input    SHIELD 7  CONNECTED     TO GND  _ la    TO ODD    TERMINAL                                        CONNECT    SHIELD JUMPER    POWER    ITO  12VDC    TO EVEN    TERMINAL    Wire the    P    sensor terminal to 12VDC supply on board     Wire the    GND    sensor terminal to odd numbered terminal     Wire the  OUT  sensor terminal to even numbered terminal     Jumper sensor terminal           to sensor terminal    GND        Set input dip switch down        206 0002    Light Level    Table 5 1   Sensor Wiring    16AI Any   Available Point  8IO Any Avail   able Input Point    ARTC An Aux  Input    5 4   Sensor and Transducer Wiring    Wire GREEN  ground wire to odd  numbered termi   nal    Wire YELLOW  and RED signal  wires to even  numbered termi   nal    Wire the POWER  wire to a  12VDC  source on input    Set input dip  switch down     TO ODD     board  TERMINAL         v vs    TO EVEN    TERMINAL    TO  12VDC  ON BOARD       026 1102 Rev 4 08 12 99    207 0100 Analog 
166. U  18DIC   lc 12 00  Refr Leak 1 NO  Leak Alm Lvl 1000  Leak Alm Diy   010m    Bypassed Vlv 1  030  Door Alm Delay  015m       CCB STA    Disch     Return                  Coil In  Coil Ou    ENT Nex    TUS CCBHOTSDIC O1c              007 0 Setpoint  Air  OPEN Valve 2   at2  008 0 Setpoint  27   005   t2   003 0    1  lt   gt          12 00   OE Sa     100 0  008 0    ODMENU    ICCB OFFSETS CCB    Case Offset  0 0  Discharge          Return   0 0  Coil 1 In 0 0  Coil 1 Out 0 0       1                             STA    Frost  Refr Le  Door Sw  Fan Rel  Lights                        TUS CCB O1SDIC O1c       OPEN  ak 100 0  itchi OFF  ay ON   ON    t  lt   gt    B    12 00          ICCB SETPTS  CCB    Case Deadband  Valv Multplier  Close Rate    Differential Gain  Coil Out Fan Lock    EERETS            gt  5             O MENU  01801   01   12 00  Coil 2 In 0 0  Coil 2 Ou 0 0  Refr Leak 0 0    gt  5             O MENU  01801   01   12 00  0 0  100  000   FOR  xh  out  0100       STEPPER STPTS CCBH  Valve Type  Hysteresis  Steps per Sec  Maximum Steps Ope       T DATA  OTSP IC Olc 12 00  UniPolar Stepper   005    100  n  2500                    T DATA    HUSSMANN SUCTION STEPPER SCREENS  CASE SET POINTS    STATUS       Circui    t numbenr  1     a           12 00      SELECT ITEM    01 SDIC 01c    Enter Item        12 00       CIRCUIT  01 Cas  Case    Status  Temp  Term    ENT Nex     01 STATUS SDIC O1c  e Boards   01 01   On   007 0   000 0    t                      lt   gt    
167. UNICATION  THE     JUMPER SETTING ALLOWS THE RELAY   TO OPEN ON A POWER LOSS              Nc      FAILSAFE  5 JUS    ITCH 3 ANI JUG FOR RELAY 3       THE SWITCH SETTING SHOWN          8    IS SPECIFICALLY FOR UNLOADERS      lox         WITCH 4  L         CLOSES THE RELAY ON  5 OF COMMUNICATION  THE JUMP   ER OPENS THE RELAY ON LOSS OF                                                       S2 FAILSAFE       26501031       Figure 5 14   8RO Board Fail Safe Dip Switch and Jumper  Settings    5 9 2  8     and 8RO FC    The 8IO and 8RO FC have a dip switch  52  which in   dicates the state of the relay  NC or NO   When the relay is    RMCC I amp O Manual       set normally closed  the appropriate LED relay indicator   one through eight  is illuminated  Dip switch rockers one  through eight should be set to the up position if the relay is  wired normally closed and down if the relay is wired nor   mally open     5 10  Baud Rate Dip Switch  Settings    The ARTC  8      and 8RO FC have    dip switch  S2   which indicates the state of the relay  NC or NO   When the  relay is set normally closed  the appropriate LED relay in   dicator  one through eight  is illuminated  Dip switch rock   ers one through eight should be set to the up position if the  relay is wired normally closed and down if the relay is  wired normally open     5 10 1  COM A and D Networks    The COM A and D networks may be set to either 4800   9600  19 200  or 38 400 baud  Positions one and two of the  dip switch loca
168. When EPR is selected  the refrigeration so   lenoid will only be used to activate or deactivate re   frigerant flow during calls for defrost       Temp Sensors  0   6   0     Enter the number of case temperature sensors within  the selected circuit in the   Temp Sensors field     Temp Strategy   0  Average   1  Max   2  Min   0     When multiple temperature sensors are being used to  measure case temperature  the RMCC must be told how to  calculate the controlling temperature reading from the dif   ferent sensors  Users may choose from the following strat   egies        0  Average   the average of the temperature sensor  readings is used to control case temperature        1  Maximum   the highest temperature sensor read   ing is used to control case temperature        2  Minimum   the lowest temperature sensor read   ing is used to control case temperature     Fans On During Defrost   Y es   N o   N     To continue normal operation of fans during defrost   enter    Y   es in the Fans On During Defrost field  Enter     N   o to shut off all fans during defrost     Defr Duration  0   240 minutes   0     The Defrost Duration is the maximum amount of time  the circuit should remain in defrost  If no Termination Type  is defined  or when termination temperature is not met  the  circuit will exit defrost when the defined Defrost Duration  is complete     Control Temp   99    99     0     When controlling the selected circuit based on the Full  Temperature Strategy  see Section 11 4
169. a Reha        11 43    RMCC I amp O Manual Table of Contents     vii    11 4 53   Board Point Assignment  oe e o n lee Te ok P edet d e d retos ren 11 43  14 94  Utiliti  S                       emer eene eom 11 43  71 45  CANES WAL Setup    ise ett etn E                   ATENE KTE EET E eS 11 44  11 4 56  Circuit SUMM  TY iiis aie tete tap re Rr Dr a iere go                           11 44  I1 SENSOR CONTROL s                                                           etos teret E ql        11 45  LTDA                                                              o p nae one pU neg IRR 11 45  11 5 2  Set Points  all sensor types except IRLDS and Linear               eese eee      11 46  11 5 3  Set Points  for Linear sensor types                   11 47  11 5 4  Set Points  for IRLDS sensor type                                                     E N 11 48  11559  Shut Off Schedule    one euni ei rr RO P Pre n ep               11 49  715 06  Shut Off Schedule 2    I oe t tte oe E RE UIS            11 49  H 5 7  Input Output Control    sie ee Rt e PR Epp retreat 11 49  115 8  Analog Input Module Bypass    ec e ee Gn e e pesci e tb e te NER ee Y eee                11 49  11 5 9  Analog Output Module Bypass    asi ete te rte etant i geri e de ri           11 50  11 5 10    Digital Output Module  Byp  ss     ec dette e                                  e Reed 11 51  E176  x MAIN S TATUS                               nM EI      PLAT IUE IINE AUT 11 51  7 POWER  MONTOR iiie enc t   
170. ace  field will add logging points to other logs generated within  the RMCC  as shown in Table 11 7  If the Hourly Log is  deactivated  the RMCC Demand Control Hourly Log will  not be generated     Used    The percentage of log space currently being used within  the RMCC is displayed in the Used field  Users may not ex   ceed 100      The remote communication capability within the  RMCC allows the user to communicate with a site from a  remote location  Remote communication with a site con   trolled by the RMCC is accomplished using UltraSite      CPC s remote communication software package  To use  this RMCC function  the communication network must be  connected to a modem  some systems may require that a  RS232 Bus Amplifier be installed before the modem in the  communication line      Remote communication network settings are defined at  the Communications Setup screen     System Navigation     11 59    Unit    1   38     The Unit Number for each RMCC is the number Ultra   Site uses to determine the specific RMCC controller from  which information is being received  No two REFLECS  controllers may have the same Unit number     Forthe specified RMCC to communicate properly with  the remote communication software  the Unit Number  must be entered in the Unit   field     Baud Rate   3 00   1 200   2 400   9 600   9     Most standard Hayes compatible modems with a baud  rate of at least 9600 will operate properly with the RMCC  network  The baud rate should be set according to
171. alarm pan   el can only communicate at 4800 baud     5 10 3  COM C Network    The COM C baud rate setting is established within the  remote communications screens in the RMCC and is relat   ed to the speed of the modem being used at the supermar   ket  The RMCC can communicate at 300  1200  2400  and  9600 baud  It is recommended that a baud rate of 9600 be  used for remote communication     S p     ian    Jumper Settings    Each device on the network has a set of three terminat   ing resistance jumpers  JU1  JU2  JU3   These jumpers are  critical to network operation  If a device is at the beginning  or end of the COM A or COM D network  or if the device  is at the hub of a star  the terminating resistance jumpers  must be set to the up position  If the device is any where  else on the network  set the jumpers down  Refer to Section  4 10   Terminating Resistance Jumpers  COM A  COM B   and COM D Only  for more information          m             Settings    The 16AI and 8IO Boards have input type dip switches  that are used to establish the type of inputs connected to the  board  On the 16AL switches S2 and S1 contain all the  rockers that correspond to each of the 16 inputs  shown in  Figure 5 16   On the 8IO  switch 54 contains eight rockers  that represent inputs one through eight     If asensor requires voltage to operate  the input type dip  switch rocker must be set to the DOWN position  Sensors  that require no voltage must have their input type dip  switch rockers se
172. alarm value for a sensor defined as either    1        2     or     5    for the user defined alarm delay duration  see Section 14 4   Sensor Alarm Setpoints     Low Humidity The sensor reading has fallen below the low alarm value for a sensor defined as type          for the user   defined alarm delay duration  see Section 14 4   Sensor Alarm Setpoints     Low Temp The circuit control temperature has fallen below the low alarm value for an input defined as a circuit  temperature sensor  01 TEMP     48 TEMP     see Section 11 8 1   Input Definitions  for the user   defined alarm delay duration  see Section 14 1   Alarm Set Points     Low Term The circuit control temperature has fallen below the low alarm value for an input defined as a circuit  defrost termination sensor  01 TEMP     48 TEMP     see Section 11 8 1   Input Definitions  for the  user defined alarm delay duration  see Section 14 1   Alarm Set Points     Manual Defr A manual defrost has been initiated at the Manual Defrost screen  see Section 11 4 13   Manual De   frost  or Section 11 4 39   Manual Defrost     A defrost event has been terminated at the Manual Defrost screen  see Section 11 4 13   Manual De   frost      A defined communication board cannot be located     Oil Pressure The oil pressure in a compressor has risen above the oil pressure defined at the group setup screen   see Section 11 2 7   Group 1 Setup     OVRD ACTIVE A contact closure has been detected at an input defined as an alarm override  ALA
173. alarms  0   240 minutes   30   and for notices  0   240 minutes   30  in the Delay fields     Disabled During Hot Gas Disabled During Re   claim   Y es   N o   N     The Checkit sensor monitors the system for all temper   ature increases  regardless of cause  Therefore  Checkit  may detect normal flash gas occurrences as a result of hot  gas defrosts or heat reclamation     When the Checkit sensor is disabled during Hot Gas de   frost  the RMCC must wait a specified amount of time after  the completion of the defrost before accurate measure   ments of the liquid level can be made     stages designated for any single group when using standard  control  However  no more than 22 compressor stages may  be defined for a single RMCC  When using the Fixed Step  Strategy activated at the Group 1 4 Pressure Set Point   screen  see Section 11 2 10  Group 1 Pressure Set Points    up to 10 compressors may be assigned to a suction group     To establish a suction pressure group  enter the desired  name in the Name field  Each pressure group name may be  no more than 15 characters long  The number of compres   sors within the defined group is entered in        Comps  field  The RMCC is capable of simultaneously controlling  up to 16 compressor stages designated within any single    System Navigation     11 5    group  However  no more than 22 compressor stages may  be defined for a single RMCC     11 2 7  Group 1 Setup    GROUP1 SETUP                                                        
174. an ON sta   tus from both sensors to activate Demand Defrost  If either  of the two sensors relay OFF  Demand Defrost will not be  activated     Demand Fail safe Time  0   240 hours     The Demand Fail safe is the maximum duration the  RMCC will keep the circuit out of defrost when a contact  closure is not received from the Demand Defrost sensor in   stalled in the case  This time should be the maximum dura   tion in hours the case should remain in normal refrigeration  mode without a stage of defrost  When controlling defrost  using defrost times set within the RMCC  defrost will occur  at the defined defrost time following the demand fail safe  time     Alarm Time  0   240 hours     The RMCC will activate an alarm in the Alarm Log  when defrost has not occurred in the selected circuit for the  defined Alarm Time     delay  the Defrost and Master Liquid Line Valves are also  closed     Dual Tmp Alarm Set Point Shift   99    99     0     This setting does not change the temperature set point  within the case  it only offsets the alarm set point by  the amount specified in the field     The Dual Temperature Alarm Shift Set Point is the val   ue added to the defined Circuit Alarm Temperature Set  Points when a contact closure is detected from the Extra in   put  The Circuit Alarm Temperature Set Points are defined  atthe Alarm Set Points screen  see Section 14 1   Alarm Set  Points      Dual Temp Shift Input   0  None   1  Dual Temp  Support   0     Enter    1    for Dual Temp
175. and a dead band may  also be established     9 5 5  Fail Safes  9 5 5 1     Under certain conditions the system pressure may in   crease too quickly above the condenser set point to be re   duced effectively by normal condenser control  The RMCC  provides a user definable fast recovery rate set point at  which the condenser fans are cycled on to reduce system  pressure     Fast Recovery for Air Cooled and Temp Diff Con   denser Strategies    When an Air Cooled or a Temperature Differential con   denser control strategy is being used   see Section 9 5 1    Control Strategies   the RMCC uses the discharge pressure  transducer as the input source for Fast Recovery  In other  words  Fast Recovery will initiate whenever the discharge  temperature rises above the Fast Recovery set point     Fast Recovery    9 6   Circuit Control    Fast Recovery for Evaporative Condensers    Unlike Air Cooled or Temperature Differential con   densers  the Evaporative strategy does not use the dis   charge pressure transducer in Fast Recovery  Evaporative  condensers use the same combination of up to five sensors  that is used in condenser fan control  However  users have  the option of using the Maximum sensor combination strat   egy in place of the combination strategy used in condenser  fan control     When the Average or Minimum sensor combination  strategy is being used in condenser fan control  see Section  9 5 1 2   Evaporative Condensers   a single high sensor  value will either be averaged 
176. andard compressors    026 1102 Rev 4 08 12 99    to activate  Some of the criteria for determining the most  appropriate combination are       Best match to desired horsepower      Staging on a compressor before its unloader     Matching the minimum on and off times  and    Equalizing compressor run times     When the RMCC has activated enough standard com   pressors to satisfy the HP requirement and the suction pres   sure begins to decrease below the suction set point  the  RMCC will begin decreasing the active compressor HP by  first decreasing the RPM ofthe variable speed compressor   During this stage of operation  the VS compressor is again  the primary pressure control device  and it will be increased  and decreased as necessary to maintain the set point  If dur   ing this phase the VS compressor reaches 10046 capacity  and the RMCC requires more HP  the RMCC will again  look for a standard compressor combination to activate     Ifthe VS compressor reaches its minimum capacity and  the RMCC still requires less HP  the RMCC will begin to  deactivate standard compressors  If there are no standard  compressors left to deactivate  the VS compressor will turn  off     The above description of the Normal strategy is only  the basic framework of how compressor control works   Other settings in the RMCC may slightly alter the way in  which the rack operates  such as       Compressor ON and OFF delays     Unloader ON and OFF delays      nverter alarming  and      Specialized se
177. are configured at the Alarm Overrides screen  see  Section 14 5   Alarm Overrides      The override schedule defined at the Shut Off Schedule    screen is activated when assigned to selected sensors at  the Shut Off Schedule 2 screen     To activate the schedule within selected sensors  find  the desired Sensor Numbers and enter            in the corre   sponding fields     em  Desorption   Pee        The Command output of the Analog Input Module may  be overridden using this screen     Name  15 characters max   AV INPUT  module  number      If desired  enter a name for the analog input module in  the Name field     System Navigation     11 49    Enable  Yes  No   N     The Enable field allows users to turn an individual An   alog Input Module on or off without having to use Ultra   Site  Entering Yes in this field enables the current module   entering No in this field turns off the module     Command  OFF  ON  NONE   OFF     The value to which the Command output will be over   ridden is entered in the Command field     Type  Fixed  Timed  Normal   Normal     In the Type field  users may choose the type of over   ride  There are three override types to choose from       Normal   Choosing    Normal    in the Type field ends  a fixed or timed override already in progress     e Fixed   The output will be overridden to the value  chosen in the Command field until the user returns  to this field and selects    Normal        11 5 9  Analog Output Module Bypass          29  08     A
178. arge 0 0 Coil 2 Out  0 0  Refr Leak   100 0 Return   0 0 Refr Leak 0 0  Door Switch  OFF Coil 1 In 0 0  Fan Relay   ON Coil 1 Qut 0 0  Lights   ON 0                                                                                                                                                       NEXT   gt  SET DATA    O MENU 15 05 11  int 0 03  15703 12 00             SEE FOLLOWING PAGE CCB                   CCS  OTSDIC OIc 12 00  FOR SCREENS FOR QN i gi  ADDITIONAL VALVE TYPES Coil Out Fan Lockout  0100     LIQUID PULSE SHOWN              SEE FOLLOWING PAGE  FOR SCREENS FOR  ADDITIONAL VALVE TYPES   LIQUID PULSE SHOWN        RMCC I amp O Manual Appendix D   0 3       CIRCUIT CONTROL 12 00    1  Standard Circuit    Case Control             IRCUIT CONTROL 1       1 Circuit Status 6 Logs Graphs  g Circuit Set Points 7                    ase Set Points Light Schedules   Alarm Set Points  2  Setup    5  Manual Defrost    SELECT BE                       UP MENU 1       0       1 Add Edit Circuit 4 Bd Pt Assignment   Board Cct Assgn 5 Utilites  3 CCB Logging Times 6 Anti Sweat Setup          Circuit number  1     12 00                          SETUP   1    Case            001  Enter Defaults  No   Circuit Name   801   01  Master Liq Line Soleno    REV                                       SETUP     1  Defrost Type   Defrost Termination  Valve Control Strategy  Temp Control Strategy  Fans On During Defrost    T PREV L NEXT         gt  SET DATA    12 00     gt  SbIC  c  d  Grp  LLS
179. arm Temperature Set  Points when a contact closure is detected from an Extra in   put  The Circuit Alarm Temperature Set Points are defined  atthe Alarm Set Points screen  see Section 14 1   Alarm Set  Points      Dual Temp Shift Input   0  None   1  Dual Temp  Support     Enter    1    for Dual Temp Support in the Dual Temp  Shift Input field if a dual temperature case is defined within  the circuit     System Navigation     11 41    11 4 48 Circuit Set Points 3  Add Edit Circuit                  4  899   v       CIRCUIT SETPOINTS  81  Demand Defrost                   Demand Fail safe Time   Alarm Time                   O MENU    T PREV                 gt  SET DATA       When the Demand Defrost feature is activated  the  RMCC will only activate defrost when a contact closure is  received from the installed demand sensor or when the sys   tem reaches the demand fail safe time  For more informa   tion about the Demand Defrost feature  see Section 4   Software Overview  This feature is optional within the  RMCC  therefore  default values will not apply to this  screen        Demand Defrost   O n  O F f    To activate the Demand Defrost Feature  enter  O n in  the Demand Defrost field  To deactivate Demand Defrost   enter               Demand Fail safe Time  0   240 hours     The Demand Fail safe is the maximum duration the  RMCC will keep the circuit out of defrost when a contact  closure is not received from the Demand Defrost sensor in   stalled in the case  This time should 
180. art of the PID output will be 50   or  in  some cases  whatever value the user specifies as the Output  at Setpoint value   The proportional part of PID moves pro   portionately as the output moves within the throttling  range  that is  the output is at 100  when the input is at the  top of the throttling range  and the output is at 0  when the  input is at the bottom of the throttling range     The integral part of PID control makes adjustments to  the output based on the error that has existed over time  The  integral mode is necessary because the proportional mode  alone cannot force the control input to match the PID set  point  it can only stabilize the control input at a value which  may be higher or lower than the set point  The integral  mode    grabs    the value and brings it towards the set point     Finally  the derivative part of PID control observes the  rate of change of the input and makes slight adjustments  based on the predicted future values of the input  This al   lows PID control to    catch    arapidly changing input before  it gets too far away from the set point     A diagram showing the operation of all three modes is  shown in Figure 9 2     Software Overview     9 1       ACTUAL READING       P  MAKES INITIAL   ADJUSTMENT TO THE  PID PERCENTAGE           TRACKS THE ERROR AND  AND    ERROR DURATION    MAKES AN ADDITIONAL       ADJUSTMENT    a     D  NOTES ANY LARGE RATES  SET FONT OF CHANGES AND ADJUSTS THE    PERCENTAGE AS NECESSARY       THROTTLIN
181. ase lights to automatic operation   Turn    2 Turn Off   Pressing 2 will bypass the case lights off    3 Turn On   Pressing 3 will bypass the case lights on    Status   the operational status of the refrigeration and defrost modes  Pressing RIGHT fol   Status Ovrd lowed by one of the commands below allows users to manually override the case    1 Man Dfr   Pressing 1 initiates manual defrost    2 OV OFF   Pressing 2 overrides both refrigeration and defrost OFF    3 End Dfr OV   Pressing 3 will terminate defrost mode     Disch 1   the current reading of discharge air temperature sensor one   Offset   the offset for discharge air sensor one  This may be changed using the HHT   Disch 2   the current reading of discharge air temperature sensor two   Offset   the offset for discharge air sensor two  This may be changed using the HHT     Disch 3   the current reading of discharge air temperature sensor three    Offset   the offset for discharge air sensor three  This may be changed using the HHT   Disch 4   the current reading of discharge air temperature sensor four    Offset   the offset for discharge air sensor four  This may be changed using the HHT        RMCC I amp O Manual System Navigation     15 7    Extra 1 Tmp   the current reading of extra temperature sensor one   Offset   the offset for extra temperature sensor one   Extra 2 Tmp   the current reading of extra temperature sensor two   Offset   the offset for extra temperature sensor two     Door   the current status of t
182. ate system  information  CPC provides this information to the RE   FLECS through a series of input communication boards   Except for boards designed to supply both input and output  functions  the 16AI Communication Board is the only input  board used by CPC     2 2 1  16     Board    The 16AI Analog Input Board is a general purpose in   put board capable of receiving an input signal through any  of 16 two wire input connections  To function  the 16AI  must be connected through the RS485 I O network to the  REFLECS  When properly installed  the board receives ei   ther digital or analog data from sensors wired to any of the  16 input connections located on the board  Input definition  screens within the REFLECS allow the user to define each  input for refrigeration control     A maximum of sixteen 16AIs may be connected to  an RMCC through the RS485 COM A and D networks     Within a refrigeration system  the 16AI may be con   nected to temperature  humidity  or dew point sensors and  pressure transducers  liquid level indicators  and refrigerant  leak transducers     The 16AI Board is designed with several features that  make it easy to install  wire  and configure  These main  user interface features are shown in Figure 2 3     LEGEND  Address and Baud Rate Dip Switch  Input Connections       AC Input Power Connection        Network Connection   LED Power Indicator  Termination Resistance Jumpers                   26501001    Figure 2 3   16AI Analog Input Board    026 1102 
183. ayed in the Refr Leak field  This sensor calculates the  parts per million rating of escaped refrigerant     Door Switch    When a Door Switch is configured at the Circuit Set   points 4 screen  see Section 11 4 49   Circuit Set Points 4   Add Edit Circuit    the current status of the Door Switch is  displayed in the Door Switch field     System Navigation     13 7    Extra Temp    The current temperature readings of the Extra 1 Tmp  and Extra 2 Temp sensors are displayed in the Extra 1  Temp and Extra 2 Temp fields  The extra temp sensors may  be used to monitor temperature only     Fan Relay    The current status of the Fan Relay is displayed in the  Fan Relay field     Lights    The current status of the case lights is displayed in the  Lights field     13 4 6  CCB Status 3  Liquid Pulse Only     SISSE           CCB STATUS CCB 01SDIC O1c          Setpoint    Valve 2     Setpoint      A Liquid Pulse CCB may control up to two liquid pulse  valves  if a second pulse valve is connected to the CCB   status information about the second EEV may be viewed in  Status Screen 3  To access this screen from Status Screen  2  press ENTER     13 5  Sensors  13 5 1  Sensor Status           SENSOR STATUS      Name   LIQUID LEVEL  REFR LEAK  AMBIENT       Status Value CI    1  2  3  4  5  T     PREV                13 8   Sensors          13 4 7  CCB Status 4  Liquid Pulse and  Stepper Only     DEM sm              For liquid pulse and liquid stepper CCBs  this status  screen displays the cur
184. be defined as specific values for analog sensor inputs  or simply as contact closed or contact open for digital input  sensors     Fault Alarm  IRLDS only   Enabled Disabled   En   abled     When the Fault Alarm is enabled  the RMCC generates  a fault alarm whenever the input being monitored goes to  5Vdc  a sign that a flow fault has occurred in the corre   sponding IRLDS zone      11 8 1   Input Definitions   The Alarm Override Input that  should control the override status of the selected sensor is  chosen in the Digital Override Input field  To select an  override input  enter the appropriate override number in the  Digital Override Input field     Turn Sensor Relay OFF   Y es   N o     To deactivate the sensor relay to the controlled output  when an Alarm Override is activated  enter  Y es in the  Turn Sensor Relay OFF field     Type   F ixed   T imed     There are three types of overrides  timed  fixed  and  scheduled  A timed override bypasses the normal sensor  operation for a specified period of time  A fixed override  bypasses the normal sensor operation until the user returns  to this screen and disables the override  A scheduled over   ride bypasses the normal sensor operation according to a  schedule configured at the Shut Off Schedule 1 screen  see  Section 11 5 5   Shut Off Schedule 1      Duration  00 00   99 99     The Override Duration is the specified measure of time  the sensor will remain in override mode if the override is  defined as a timed override   
185. be the maximum dura   tion in hours the case should remain in normal refrigeration  mode without a stage of defrost  When controlling defrost  using defrost times set within the RMCC  defrost will occur  at the defined defrost time following the demand fail safe  time     Alarm Time  0   240 hours     The RMCC will activate an alarm in the Alarm Log  when defrost has not occurred in the selected circuit for the  defined Alarm Time  This Alarm Time is defined in the  Alarm Time field     11 4 49 Circuit Set Points 4  Add Edit Circuit     Refer to the description of Circuit Set Points 2 on Sec   tion 11 4 19  Circuit Set Points 2              11 4 50 Circuit Inputs Setup 1  Add Edit Circuit     Refer to the description of Circuit Inputs Setup on Sec   tion 11 4 22  Circuit Inputs Setup        Dam mm        11 4 51 Circuit Outputs Setup  Add Edit Circuit     Refer to the description of Circuit Outputs Setup on  Section 11 4 23  Circuit Output Setup              11 42   Circuit Defrost Control    026 1102 Rev 4 08 12 99    11 4 52 Board to Circuit Assignment          BOARD CIRCUIT ASSIGNMENT    1  Board Ckt  01         1  01            Ckt Type       SDIC    Ckt Name  SDIC O1c  Undefined  Undefined          02 SPARE  00  05 SPARE  00  O4 SPARE  00 Undefined  05 SPARE  00 Undefined    T PREV              1                    5         O MENU                      After Case Control Circuits are programmed and the  cases are installed and have a board ID number  the boards  must be 
186. been connected or since the last  Clear Runtime command  This calculation is displayed and  may be reset in the Run Time field     When using Hussmann Refrigeration    s PROTOCOL     the RMCC   s Advanced Defrost Feature is available  There  are three types of advanced defrost systems available  Ad   vanced Hot Gas Defrost  Advanced Reversed Cycle Hot  Gas Defrost  and Advanced Electric Defrost  To activate  the Advanced Defrost Feature  enter  Y es in the Setup  Advanced Defrost Options field  Selecting  Y es will acti   vate the appropriate Advanced Defrost Options screen ac   cording to the type of defrost system defined  From this  screen  Advanced Defrost Set Points are defined        S tandard   all compressors within the host group  are shut down during the defrost duration and return  to normal operation when the defrost duration is  complete     e  R everse Cycle   all compressors within the host  group are shut down for the Compressor Start Delay  defined below and are then cycled to maintain the  programmed Defrost Suction Set Point also defined  below  Defrost is terminated and compressors re   turn to normal operation based on the selected ter   mination strategy     To define the Hot Gas Defrost Type  enter the letter cor   responding to the desired type in the Hot Gas Defrost Type  field     Compressor Start Delay  0   60 minutes   2     When the Reverse Cycle Hot Gas Defrost Type is cho   sen  all compressors within the host group are shut down  for the Compre
187. been designed to conform to RS232  standards  When wiring CPC components together  it is  necessary to follow the rules and requirements specified in  this section to ensure proper communication between net   work devices and effective control of refrigeration control  equipment  Unless noted  all information in this section  pertains to COM A  B  C  and D networks  Information  provided in Section 3  Hardware Mounting  conforms to  these requirements     pa um QI aa    A leg is defined as a cable running between two devices  such as two communication boards  or a REFLECS unit  and a communication board  A segment is defined as the to   tal combined length of all legs connected to one REFLECS  power interface board output connection such as the COM    Overview    4 2   Wiring       A or COM D connections  Figure 4 4 demonstrates the re   lationship between legs and segments     INPUT OR OUTPUT  BOARD      NETWORK                or D         CONTROLLER                         START OF  SEGMENT   COM A or D  CONNECTION     26513042    um OF SEGMENT     LAST BOARD     Figure 4 4   Relationship Between Legs and a Segment    4 6  Legand Segment Wire    Length    A single segment connected to COM A  B  or D may  not exceed 4000 feet  Therefore  the combined length of all  legs in a single segment may not exceed 4000 feet  This  length restriction includes the length of legs in a single star  configuration described in Section 4 9   Star Configura   tions     A single segment connec
188. c                      GRAPH CONTROLS 0       mn 0 GRAPH CONTROLS GRAPH CONTROLS    gt      Scroll   gt   lt   Scroll   gt   lt   Scroll        Go to current      Go to current      Go to current   Z   Zoom out  Zoom in 2  m out  Zoom in 7   Zoom out  Zoom in        Menu 0  Me      Menu      PLEASE WAIT    0    PLEASE WAIT       PLEASE WAIT     5705 11 57 int 0 03 00 15 03 12 00                     0                                        ate                       15 03 12700 ae    210 DIN     00 15703 1    2 00                                  0 6     RMCC Front Panel Screens 026 1102 Rev 4 08 12 99    Appendix E  Wiring for Case Controller  Power Module  Defrost Module  and Pulse EEV Valve        335 3151  335 3158                DEFROST      DEFROST OUT  DEFROST H   DEFROST OUT  DEFROST H   DEFROST OUT CASE   CONTROLLER       COIL INLET                                     COIL OUTLET                                  ANTI SWEAT H   ANTI SWEAT OUT    RED   RED   GREEN  GREEN  PURPLE  PURPLE  BLUE WHITE  BLUE WHITE  RED WHITE  RED WHITE  ORANGE  ORANGE  GRAY  GRAY BLACK  RED             DISCHARGE AIR          FANS          FANS OUT  NC                                                LIGHTS H       LIGHTS OUT  NC or NO                    RETURN AIR                                              HOT COIL 2 INLET                            LINE                PURPLE                NEUTRAL       COIL 2 OUTLET                                        WHITE   WHITE  BLACK YELLOW  PURPLE
189. ch the Proof in   put  In these cases  the logical signal from the Min On Off  cell may be used as the Proof value     9 14   Input Output Control       Proof       The Proof cell compares the Select cell   s output value  to an external digital input and turns on the Proof Fail Out   put when the two inputs are not the same for a specified  amount of time  The most common application of this cell  is to connect the Proof input to the external device being  controlled by the Command Output  so that the Proof Fail  Output may be used as an indicator of device failure     In order for the Proof Fail Output to be activated  the  two inputs must be different for an amount of time equal to  the user specified delay     9 9 2 3  Analog Output Module    The Analog Output Module s main function is to read  the value of an analog input  compare the value to a set  point  and generate a single analog output value  This out   put value is represented in three different forms  a single  analog value from 0  to 100   up to eight digital stage  outputs  and a digital pulse width modulation output     The output value s  are generated by a PID Control cell   which takes into account both the input s instantaneous  value and its rate and direction of change  In many ways   the PID Control algorithm is similar to the PID algorithm  used by Pressure Control  except the Analog Output Mod   ule is designed to be used in a wider array of applications   Refer to Section 9 4 1 1   Normal  PID Contr
190. ciation can be set to either pulsed or  continuous mode    E  1         x  E     t  t  v     2  t    e Interfaces with existing facility alarm system  e 25 pin parallel printer interface port     Wiring of the alarm panel to the REFLECS is discussed  in Section 5 3   COM B Wiring        Termination Resistance Jumpers Output Connections  8 places   LED Power Indicator Input Connections       Network Connection Analog Outputs   Fail Safe Dip Switch Input Type Dip Switch   LED Output Indicators Power Output Connection  Network Address Rotary Dials AC Power Input Connection  Relay Output Fuses  under cover        Enable Jumper  JU4                            26501010       Figure 2 8   8IO Combination Input Output Communication  Board    2 4 2  Case Controller    CPC offers a variety of case controllers depending on  the valve control approach being used  Because of this va                      riety  and the multiple power modules that are available     Screen Scroll Buttons LCD Alarm Screen      B       Al R Bi i  complete overview of case control is provided in Section 5  UTR LED Alarm Indicator  Case Control     LEGEND                   26509002       Figure 2 9   485 Alarm Panel    2 5  485 Alarm Panel    One of the most important requirements of any network  environment is its ability to notify personnel of system fail   ures or possible problems  The REFLECS is designed with  sophisticated logging  graphing  notification  and alarming  features that put system data at the 
191. closed     RMCC I amp O Manual       Shut Down if Suction Grp Fails  1   4 Group Num   ber   0  Disable     The Shut Down if Suction Group Fails option will close  all EEVs within a circuit under certain failure conditions  If  a proof fail is received for all compressors in a group  along  with a suction pressure reading above the high suction pres   sure set point  Section 11 2 3  Group 1 Pressure Alarms  Setup   all case controllers associated with the group are  put into wait mode and    WAIT    is displayed in the status  field of the circuit setup screen  In addition  in the event of  phase loss or a pressure reading above the discharge pres   sure trip point  Section 11 2 10  Group 1 Pressure Set  Points   all case controllers associated with all defined suc   tion groups are put into wait mode  When the failure con   dition has been corrected  the          will stage the case  controllers back on by bringing the first 16  on right away   and 16  every minute until all case controllers are back on  and functioning     Anti Sweat Control   Y es   N o     To activate anti sweat heater control  enter  Y es in the  Anti Sweat Control field  To deactivate control  enter                  Dual        Alarm Set Point Shift   99    99       This setting does not change the temperature set point  within the case  it only offsets the alarm set point by  the amount specified in the field     The Dual Temperature Alarm Shift Set Point is the val   ue added to the defined Circuit Al
192. co ESR  Bipolar   24 V  Only     Unipolar    Unipolar   24V     Set Unipolar  Jumpers  For    Table 7 2   Valve Type Jumper Settings    See Section 8 3   Valve Control  for valve types avail   able     Lights and Fans Output Jumpers  JU7 and JUS     If the lights and fans are wired to the NC connection  of the power module relays  then the relays are de rated  to 10 amps     Jumpers JU7 for lights and JU8 for fans define whether  the relay is normally open or normally closed when 12  VDC power is applied  Set the jumpers up for normally  open or down for normally closed  The case controller is  supplied in the normally open configuration and should be  wired to the case controller power module as shown in Fig   ure 5 13 and Figure 5 14  If JU7 and JUS are set in the    7 2  Jumper Settings        down position  wire the fans and lights to the NC connec   tion on the power module relays  See Table 7 3     Jumper Indicator Load  Position Light    Table 7 3   JU7 and JU8 setting result       T 4  Baud Rate    The CCB baud rate is hard coded at 19 200 and cannot  be changed  For networks with case controllers attached   the baud rate setting for COM A and D on the RMCC  should be set to 19 200  See Section 4 12   Baud Rate Dip  Switches  COM A and D only      7 5     The case controller is configured with optional inputs  for a leak detector  optical frost sensor  and clean door  switch  non voltage contact change of state   One optional  output for a second 24 VAC  pulse electro
193. ctive lo      Table 8 10   Light Level Parameters    8 9  Wash Mode    Wash mode is initiated by activation of the cleaning  switch or through the hand held terminal  During wash  mode  refrigerant flow is stopped  the fan and anti sweat  outputs are turned off  and the lights are turned on  Wash  mode may end by either a time out condition  or by the  cleaning switch     When a time out condition is detected  the case control   ler automatically ends wash mode and enters recovery  mode     If manual deactivation of the cleaning switch is detect   ed  the CCB will end wash mode and enter recovery mode   The wash mode set points are shown in Table 8 11     Case Control Software Overview     8 5    Itis possible to define a cleaning switch input at both a  16AI and the case controller  When this is done  the 16AI  takes priority over the case controller cleaning switch in   puts  That is  when a circuit is in clean mode because of a  contact closure at the 16AI input  a single case cannot be  brought out of clean mode through the cleaning switch con   nected to the case controller  However  if a contact closure  is not received from the 16      a single case may be put into  wash mode using the local cleaning switch     Type Min  Descrip   Max tion  Cleaning Input   NA NA Contact clo   Switch sure   Wash De  Set NA Timed or  point manual deac   tivate     activate    Type    Wash Time   Set 0 120 Time to stay  point minutes   in wash  mode  Time  deactivate  only      Table 8 1
194. d         keys  There are 10 different  types to choose from     e R502  e R22  e R401A    e R401B    e R402A  e R402B  e R408A  e RI34A  e R404A  e R507    Temp Press Input Offset   999   999   0     If necessary  a temperature sensor or pressure transduc   er may be given an offset value that is applied before the  temp to pressure or pressure to temp conversion takes  place  This input offset is entered in the Temp Input Offset  or Pres Input Offset field     Logging Interval  00 00 00   24 00 00   00 03 00     The RMCC periodically records the values received  from the defined sensors and stores the information in the  RMCC Sensor Log  see Section 12 1 6   Sensor Logs   The  Logging Interval defines when the data received from the  sensors are recorded  The RMCC will store a number of  readings for each input equal to the amount of logs speci   fied in Logging Setup  See Section 11 8 9  Logging Setup     11 5 2  Set Points  all sensor types except IRLDS and Linear     d  ENT                SENSOR SETPOINTS  84 01 Type  Temp                                           Control Using Diff  of  0 0                CUT ON  Delay   Min time ON   000                                                    Sensor set points are control parameters stored within  the RMCC that are compared to sensor readings to deter   mine the controlled output function  These set points are  only defined when the selected sensor is controlling an out   put       Type    Selecting the Setpoints command ac
195. d   O ff   H igh   L ow   O     The Start Speed is the speed at which the condenser  must begin to operate when activated from an OFF state   The condenser must begin operation at either Off  High  or  Low speed until the defined Start Duration has passed  at  which point the condenser operates at the speed required by  the RMCC     The Start Duration is defined in Two Speed Setup  Screen 2  see below      026 1102 Rev 4 08 12 99    11 3 6 2  Two Speed Setup Screen 2       CONDENSER 2 SPEED FAN SETUP    Start Duration 10000       High to Low Delay 0030   Low to High           0000   Low Speed HP  050    High Speed HP   100             T PREV              gt  SET DATA O MENU    Start Duration  0   3600 sec    0 sec      Before the condenser can be activated from an OFF  state  it must undergo a    start duration   During this time   the condenser operates at a fixed  user defined speed until  the end of the start duration  After the start duration is com   plete  the condenser will operate at the speed called for by  the RMCC     The Start Speed is defined in Two Speed Setup Screen  1  see above      High to Low Delay  0   3600 sec    30 sec      The High to Low Delay is the number of seconds the  RMCC must wait before switching a condenser s fan speed  from High to Low     Low to High Delay  0   3600 sec    0 sec      The Low to High Delay is the number of seconds the  RMCC must wait before switching a condenser s fan speed  from Low to High     Low Speed HP  0   240 HP   50 
196. d below     Valv Multiplier  25   100   100     The Valve Multiplier is a value that allows the capacity  of the EEV to be reduced  This value should only be adjust   ed in special applications where the valve appears to be  oversized     11 36   Circuit Defrost Control    Close Rate    15    255    255     When 255  is defined as the Close Rate  the EEV will  close immediately     When refrigeration is deactivated within the case  the  EEV closes according to the Close Rate Percentage  The  EEV will close the defined percentage within one minute of  the call for the deactivation of refrigeration within the case     Derivative Gain  0   25     The derivative gain is a multiplier used by CCBs that  are operating valves using PID control  The larger the de   rivative gain  the greater the size of the Derivative mode   s  reaction to rapid changes in the PID input  See Section  3 1 1   Programming PID  for more information on the de   rivative mode     Coil Out Fan Lockout   99   99   100     To disable the Coil Out Fan Lockout feature  enter a  temperature set point of 99     If desired  the evaporator fan may be disabled when the  coil outlet temperature climbs above the temperature set  point defined in the Coil Out Fan Lockout  To activate this  feature  specify a temperature set point in the Coil Out Fan  Lockout field     026 1102 Rev 4 08 12 99    11 4 37 CCB Set Points Screen 4  CPC Suction Stepper Only       2  8       cen  n      CCB SETPTS  CCB 01 SDIC O1c          Va
197. d on the combination strategy   and send the com   bined value to the Limiter cell     Two different combination strategies may be specified  by the user  a primary combination strategy and an alter   nate combination strategy  The primary combination strat   egy will be used whenever the Use Alt Comb input is OFF   When the Use Alt Comb input is HIGH  the alternate com   bination will be used  If an alternate combination strategy  is not desired  only the primary combination strategy needs  to be defined     Limiter    The Limiter cell simply applies a user defined set of  high and low limits to the value leaving the AV Combiner  cell  If the combined value is greater than the specified high  limit value  the Limiter cell will block the combined value  from the rest of the module and replace it with the high lim   it value  Likewise  when the combined value is lower than  the low limit value  the low limit value will be substituted   This limited analog value is passed on to the Filter cell     The Limiter cell also commands a digital output  called  the Limiting output  This output is ON when the Limiter  cell is enabled and OFF when the Limiter cell is disabled     Filter    The Filter cell s primary function is to slow the rate of  change of the combined input  The filter reads the differ   ence between the current input value and the input s value  x seconds ago  where x   a user specified amount of time   called the  period    The difference between these two  values is
198. d or because of defrost  To reactivate superheat con   trol  a recovery sequence is necessary since  in both of  these instances  the coil is empty  To refill the coil and re   establish superheat  the valve is opened a certain percent   age for a fixed period of time  See Section 5 3 1 6   System  Recovery Mode  for more information     The EEV will open between 10 and 100   based      a  six second control window  to achieve the Superheat Set  Point     Max Recy Time  1   60     Unless the coil achieves superheat and exits recovery  mode early  recovery mode will terminate after the Max  Recy Time has passed     Asw Hi Limit  25   100   60 0  Asw Lo Limit  0   75    40 0     When the Anti Sweat feature is activated in the selected  circuit at the Circuit Setpoints 2 screen  see Section  11 4 47  Circuit Set Points 2  Add Edit Circuit    the anti   sweat heater range for each case is defined in the Asw Hi  and Lo Limit fields  If the humidity is higher than the ASW  Hi Limit  the anti sweat heaters will remain on at all times   If the humidity is lower than the Asw Lo Limit  the anti   sweat heaters will remain off at all times  Between these set  points  the anti sweat heaters will cycle in a six second win   dow according to the humidity level     Frost Sensor   Y es   N o   N     If a Demand Defrost Sensor is installed at the selected  case  enter  Y es in the Frost Sensor field  Demand Defrost  set points may then be defined at the Circuit Setpoints 3  screen  see Sectio
199. d the Output  Time is 10 minutes  the PWM output would be ON for six  minutes and OFF for four minutes  After the Output Time  has passed  the PWM starts over again with the new PID  percentage     RMCC 1 amp 0 Manual       Software Overview     9 17    10 System Configuration Guide    This guide can be used for the general configuration of an RMCC system  The System Configuration Guide pre   sents the steps for general configuration of an RMCC  Some steps of this guide can be skipped if the RMCC is not to per   form the functions defined  Before attempting to program the RMCC  decide what functions the RMCC will perform and  then identify what sections are pertinent to the configuration     10 1  General    1  Make      Network and Power Connections    2  Define Board Types and Numbers    Section 11 8 21   Set Device Numbers    10 2  Setup Compressors    Name Pressure Groups and Define the Number of Compressors Used    Section 11 2 6   Compressor Setup  Setup Pressure Group  Groups 1 4 are Accessible from this Screen     Section 11 2 7   Group 1 Setup    1   2   3  Define Pressure Options   Section 11 2 8   Pressure Setup   4  Define Two Stage System Setup    Section 11 2 9   Two Stage System Setup  5    Set Pressure Setpoints for the Group  Groups 1 4 are Accessible from this Screen     Section 11 2 10   Group  1 Pressure Set Points    6  Define Variable Speed Set Points  Groups 1 4 are Accessible from this Screen     Section 11 2 11   Group 1  Variable Speed Set Points    
200. d the valve may open or close   Max Steps   the number of steps in between closed  0   and open  100       Control   whether the valve is an EEV or and EEPR   Valve Type   whether the valve is a pulse or stepper     Valve Jmpr   whether the CCB   s valve jumper is set for unipolar  UniP  or bipolar  BiPo  op   eration  See Section 5 3 1 3   Valve Control     Network   whether the host network is ON or OFF    Case Type   the case type number  See Section 11 4 16   Circuit Setup 1 for a complete list of  case types and their corresponding numbers  This may be changed using the HHT    Case     the CCB number        15 10   Hand Held Terminal Screens 026 1102 Rev 4 08 12 99    Appendix A  Advanced Pressure Control  RMCT 2 10     CPC manufactures a companion version of the RMCC  v  2 10 software that incorporates the advanced pressure  control system developed by Tyler Refrigeration  This soft   ware is designated as RMCT 2 10  The two versions are  identical except for a few aspects of pressure control     RMCC RMCT  Maximum of 4 suction Maximum of 3 suction  groups groups  Maximum of 16 compressors   Maximum of 10 compressors  per group per group    Normal strategy uses PID Normal strategy uses PIDA  control control  see PIDA Control   below     Variable speed compressors   Variable speed compressor  optional required for each group    Fixed Steps strategy and Al   ternate variable speed strate    strategy is used   no Fixed  gies available Steps strategy is available    Compres
201. dens   er when the outside ambient temperature is appropriate  To  enable Condenser Split  enter a  Y  in this field     Split Type   N ONE   E VEN   O DD   1 ST HALF    2 ND HALF   N     When the Condenser Split feature is active and the  RMCC calls for the condenser fans to be split  selected fans    RMCC I amp O Manual          will be disabled  These fans are chosen in the Split Fans  field     The Condenser Split feature uses the addresses of the  fans    8RO board connections  Choosing    O   dd disables all  odd numbered fan outputs  e g       FAN  01       FAN  03        FAN  05  etc    Choosing    E   ven disables all even  numbered fan inputs  Choosing  1 st Half disables fan in   puts      FAN  01 through      FAN  06  Choosing  2 nd  Half disables fan inputs      FAN  07 through      FAN  12   Choosing  N  None leaves all fans operational on a call for  a condenser split     If    N    None is chosen  be sure to identify an output re   lay at the Output Definitions screens to control operation of  a condenser split valve  otherwise  regardless of any split  settings defined  condenser operation will remain un   changed     Force Split in Reclaim   Y ES   N O   N     To activate the split configuration when the RMCC de   tects a closure on the Reclaim input  enter  Y es in the  Force Split in Reclaim field     Unsplit Split Delay  0   240 minutes   2     The Unsplit Split Delay is the specified measurement  of time the RMCC must wait before reactivating the split  
202. dialout sequence and or activation of the 485  Alarm Annunciator Panel     Unacknowledged alarms  alarms indicated by an aster   isk     in the RMCC Alarm Log  are active and must be ar   chived  acknowledged  or reset to silence         When alarms are acknowledged  all alarm dialouts  are discontinued and the alarms are maintained  within the Alarm Log as acknowledged alarms   These alarms are signified by a dash         in the  RMCC Alarm Log  If an alarm is acknowledged   the same alarm will not be generated or logged  again       When alarms are archived  all alarm dialouts are  discontinued and the alarms are maintained within  the RMCC Alarm Log as archived alarms  These  alarms are signified by a space in the log  If an alarm  is archived  the same alarm will generate if the  problem occurs again       When alarms are reset  all alarm dialouts are discon   tinued and all alarm records are cleared in the  RMCC Alarm Log     026 1102 Rev 4 08 12 99    To acknowledge  archive  or reset the activated alarms  within the RMCC Alarm Log  select the appropriate com   mand at the RMCC Alarms screen     Notice Alarm Description  Message    Auto Reset The discharge pressure has fallen within an acceptable range as defined by the Autoreset set point   see Section 11 2 10   Group 1 Pressure Set Points      Bad Checksum The RMCC has received three invalid messages from a case controller  This alarm may be due to im   proper network wiring  see Section 5 2   COM A and D Wiring      
203. dule    Status  i  iuh aee ides he ee e Dh e eto uat qe do ee Pee Re seed ie does 13 9  13 7 2   Analog Output Module Status         iem rt aper e per e eite E                            13 9  13 7 3    Digital Output Module Status    i itae teet net crt et eU Y re ea E ducere      13 10  13 8  DEMAND           ro ERA P EU ERU                    ARRIERE EE treten bei 13 10        Demand Status  iiio A S ee Ie Ie en e tee E uui 13 10  13 9   VO POAR D S aiite eh E FE re ORO ERREUR P                        13 11  DS OT  O        RR ERU QUAE SERERE NN n MIU EN 13 11  13 9 2   Suction Group Status eie eee eae oe a ex        Pere a ea e E Eee to RS 13 11  14  ALARMS 2                                                                        14 1  TAI  ALARM SET POINTS     eto eR ect                    ee en Ee ET RE RE            eX e Wee Rege ege eR 14 1  14 2    CASE GONTROL ALARM SET         iere P EE EE E               ERE NU      EE RT VE      RU ee PERI 14 1  14 3  CASE CONTROL ALARM SET POINTS  ADD EDIT CIRCUIT                  sees 000000000000       14 1  144     SENSOR ALARM SETPOINTS                                                                                                                               14 1  14 37 ALARM OVERRIDES    ie ge                                    Tie EE PUE ERA ATI cus e eure SEHR RUE CREDERE ERR 14 2  14 6  ALARM OVERRIDE  STATUS sce pie ito tie eere                 EE EU ERR RUE LEE Er             ERT 14 3  14 7  SEND TO A85 ALARM PANEL   
204. e  Ye                   240 VAC 1 Phase  Full Configuration  8163310   Yes  Yes    Ye          Table 6 3   Power Module Part Numbers       Power Module Output Ratings    Normally  Volts Normally Closed  Open    Anti Sweat 120 V 15A  Defrost 120V   30A  1 or2 pole   25 A  3 pole   240V   30A  1 or2 pole   25 A  3 pole     Table 6 4   Power Module Output Ratings       RMCC I amp O Manual Case Control Hardware Overview     6 3    7 Case Control Installa   tion    7 1     Generally  the case controller will be mounted within  the raceway or on top of the case  If a controller must be    Valve Type Case Control Probe Types In    CPC Case Control    Manufacturer   Valve Description Type cluded Board Required         Second Valve Kit  Pulse Only     Case Controller    Generic    Second Valve Kit  Pulse Only  W out 75 VA    Transformer    Stepper    replaced or installed in the field  it should be located based  on the specific design of the case  however  the following  guidelines are provided to help ensure proper installa   tion  Use Table 7 1 to help ensure that the correct CPC case  control board is being installed     W  Probes  P N 810 3140    W  High Humidity P N 810 3142  Probes    W  Coil Inlet Tempera    P N 510 3130  ture Sensor  Coil Outlet   Sensor  Solid State Re    lay   amp  75 VA Trans    former    W  Coil Inlet Tempera   ture Sensor  Coil Outlet  Sensor  Solid State Re   lay    P N 510 3125    Liquid Stepper ESV P N 810 3151  Valve    W  Probes  P N 810 3150    Hus
205. e Left field will dis   play a row of dashes     Type  Fixed  Timed  Normal   Normal     In the Type field  users may choose the type of over   ride  There are three override types to choose from       Normal   Choosing    Normal    in the Type field ends  a fixed or timed override already in progress     e Fixed   The output will be overridden to the value  chosen in the Value field until the user returns to  this field and selects    Normal        e Timed   The output will be overridden to the value  chosen in the Value field for the amount of time en   tered in the Time field  see below   This override  may also be terminated by selecting    Normal          the Command field     Time  0   68 minutes   5 minutes     The value entered in the Time field will be the number  of minutes a timed override will last     Ov State    The Ov State is a read only field that shows the current  state of the Value override  either Fixed  Timed  or Nor   mal      Time Left    The Time Left field is a read only field showing the  amount of time left in a timed override  When no timed  override is being carried out  the Time Left field will dis   play a row of dashes     026 1102 Rev 4 08 12 99    11 5 10 Digital Output Module Bypass    aei    DIGITAL OUTPUT MODULE 01 BYPASS   DV OUTPUT 01  NOJ       12 00             Command OFF             NORMAL  Time 10005 minutes    Time Left 00000 sec    gt  SET                      Ov State UNKNOWN  T PREV J NEXT    The Value output of the Analog Outp
206. e RMCC Alarm  Log     026 1102 Rev 4 08 12 99    11 5  Sensor Control       SENSOR CONTROL    1 Status  2 Setup  3 Setpoints  4 Alarms    5 Logs   6 Alarm Overrides  7 Override Status  8 Shut off Sched   9 1 0 Control Modules    SELECT NUMBER    11 5 1  Setup       SENSOR SETUP    01 Status OFF  Type   Temp          Name                          00 03 00  O MENU    Logging Interval  HH MM SS            T PREV J NEXT   gt  SET DATA    RMCC sensors and all identification set points and  commands associated with each sensor are defined at the  Sensor Setup screen  Up to 48 sensors may be defined with   in the RMCC       Status    Selecting the Setup command activates a sensor selec   tion screen where users select the appropriate sensor num   ber to be defined  The selected sensor number and the  current status of the selected sensor are displayed at the  Sensor Setup screen in the   and Status fields respectively     Name  15 Character Limit     The Sensor Name is a user defined name that corre   sponds to the Sensor Number  While the RMCC uses vari   ous set points to determine the type and location of a  particular sensor  the Sensor Name provides a convenient   easily recognized description of the sensor for the user     RMCC I amp O Manual           em                                                            L o                         135        Type  See Table   Temp     A complete list of common CPC sensor types and their  software setup instructions is given in Append
207. e amplifier adjacent  to the controllers  and then connect the remote amplifier to  a main amplifier connected to the modem and local termi   nal  For complete information on operation of the RS232  Bus Amplifier  refer to 026 1401  RS232 Bus Amplifier In   stallation and Operation Manual     Mounting  To mount the RS232 Bus Amplifier   1  Remove the four front panel screws     2  Remove the front panel  with circuit board at   tached      3  Mount the empty amplifier body  with the power  connection cut out down     RMCC I amp O Manual       4  Replace the front panel     Figure 3 11 shows the enclosure dimensions and  weight        RS232 BUS AMPLIFIER ENCLOSURE   REAR OF ENCLOSURE        26509001    Figure 3 11   RS232 Bus Amplifier Mounting Dimensions    3 5     For information regarding locating and mounting case  controllers  refer to Section 5  Case Control     Case Controller    3 6  Pressure Transducers    CPC uses Eclipse  pressure transducers as pressure  sensing devices  These transducers convert pressure read   ings to proportional electrical signals between 0 5 and 4 5  volts  The transducer is designed with a 1 8 inch male fine  pipe thread fitting for connection to a standard access fit   ting  If the fitting is configured with a Schrader valve  this  fitting will have to be removed and replaced with a 1 8 inch  female fitting  Each pressure transducer is supplied with 20  feet of cable for connection to a 16AI input board     Location    CPC supplies three pre
208. e con   denser s inlet  or on the condenser s outlet  Enter the loca   tion of the sensor or transducer in this field     Control Type   T emperature   P ressure   P     Condenser fans are controlled by either temperature or  pressure  This control type is defined in the Control Type  field  The method entered in this field will determine the  units used when defining condenser set points  see    Set   points  on Section 11 3 8  Condenser Setpoints Screen 1      Condenser Fan s  Type   S ingle Speed   D ouble  Speed   V ariable Speed   S     Condenser fans may be either single speed  double  or  two speed  or variable speed     Refrigerant Type  options   R502     When    Temp Diff  is selected as the control strategy in  the Control Strategy field  this field will become visible at  the bottom of the screen  The refrigerant type used in the  refrigerant system must be entered in this field  The             uses the refrigerant type to determine the refrigerant tem   perature based on the refrigerant pressure     Use the period         and dash           keys to scroll through  the possible refrigerant types  There are ten different refrig   erant types to choose from     e R22   e R401A  e R401B  e R402A  e R402B      R408A  e R134A  e R404A  e R507   e R502    Control Using   O NE   A VG  MI N   MA X    O     When    Evaporative    is selected as the control strategy  in the Control Strategy field  this field will become visible  at the bottom of the screen  The discharge p
209. e esee      ee dene oper            elo E Dee        9 6  9 5 4  Condenser Split  Single Speed Fans Only                 esee eese eterne nennen etre nennen nennen 9 6  9 5 5  TOUS APES r iiie nde ee e deed d d e e eee er eet ed 9 6         Bast  RecoVety   ete edes    re ae ie e We Een ene ioter eee dee iter vrbe eR TO E ERE  9 5 5 2  Discharge Unsplit  Single Speed Fans only  244 ss        aes  95 5 3  Discharge           Rep eee ta e ce avid eden dte dd ied esr obe               9 6  CIRCUIT CONTROL 3                                               A E E                    9 6 1  Refriger  ti  n     icto een ede reed E E Pe Ep e         e E etre site eret uri  9 6 2                Gar eS dee nadie tpe      OM ed      Cet Ue     96 2  1  s DrainzEimes o see Eon E RC On ne t eee E ra ce RR E eS ETUR  9 0 2 2   PUMP Down Delay    eere er EE ee RU Ee EO            e Per fr HUE HR OE re  9 623  Demand DIE         aer eei e votes erem ret bn        ln On oen etes mese      ANTES WEAT  CONTROL a ER TENERE QR SERE EUER a EE ERE RAE ERR EN               9 8        5                        cime ru eI ELA                           sub ea                     rU ee BRE E TECH       RMCC I amp O Manual Table of Contents     v    9 0  INP OUTPUT CONTROL             a             sven du        into Peer oe a pedes eee tbo          9 8    DOT     Cells and               aai e rt Ge v        iR ETIN FG                        9 8  9 0 1 1   Programming Cells and Modules 5 neue eerte          
210. e established at  the Pressure Setpoints screens  Each compressor pressure  group must be defined separately at these screens  Screens  for Group 2  3  and 4 are accessed by pressing the down ar   TOW     Strategy   N ormal   F ixed Steps   N     The compressor strategy determines the cycling of  compressors to maintain the appropriate suction pressure   A complete overview of these strategies may be found in  Section 3  Software Overview  Users may choose from the  following strategies       Normal   the RMCC cycles compressors to main   tain suction pressure based on HP Amps defined at  the Group 1 4 Setup screens  see Section 11 2 7   Group 1 Setup  using PID control algorithms       Fixed Steps   the RMCC cycles compressors to  maintain suction pressure based the sequence of op   eration defined by the user at the Fixed Steps Strat   egy Setup screens  see Section 11 2 13  Group 1  Strategy Setup      RMCC I amp O Manual          One Comp Always Remain On   Y es   N o   N     To ensure one compressor is always on within a select   ed suction group regardless of the suction pressure reading   select  Y   Yes  in the appropriate Grp fields     When a two stage rack is to be controlled  the user must  specify which pressure suction group is high  and which is  low  This choice will ensure a high stage compressor is run   ning when the low stage is running  1   4 Group Number    0  Disable   0   Group numbers are determined at the  Pressure Groups Setup screen  see Section 11
211. e letter in the Sensor Type field     Offset   99   99   0     At times  a sensor may provide a reading that reads low   er or higher than the known condition being monitored  An  offset value may be entered in the Offset field to calibrate  the sensor to actual conditions     Output Name    The name of the defined output to be configured is dis   played in the Output Name field     Location  BB PP  BB   Board  PP   Point     The board and point number on the 8RO board where  the selected output is located is defined in the Location  field  The network address of the 8RO board is defined by  a network dip switch on the board  Enter this number in the  first Location field  Each defined output is physically con   nected to a specific point on the SRO board  This number  is printed on the board above the output connection  Enter  this number in the second Location field     The RMCC uses this address to locate the selected out   put     026 1102 Rev 4 08 12 99    Log Interval  00 00 00   24 00 00     The RMCC periodically records the status of the de   fined outputs and stores the information in the RMCC Log   The Logging Interval defines when the data received from  the outputs are recorded     Bypass   N ormal   O n  O F f   N     A fixed bypass may be assigned to the defined outputs  in the Bypass field  A fixed bypass will override the normal    11 4 24 Advanced Defrost                  TON     ADVANCED DEFROST   71       12 00       Setup Advanced Defrost Options   0      
212. e network ON  enter    2    for  Reset ON at the Reset screen   1  Off   2  Reset On   1      The RMCC has the ability to communicate via satellite   The RMCC s Satellite Communication feature is config   ured at the Satellite Communication screen     To enable the RMCC Satellite Communication feature   enter  Y es in the Enable Satellite Mode field  If the satel   lite feature is activated  users may enter the appropriate dis   connect message in the Disconnect Message field     The RMCC is capable of accepting inputs from both  standard and Eclipse pressure transducers  The RMCC as   sumes by default that all transducers set up in the RMCC  software are Eclipse transducers  If any standard transduc   ers are being used  the transducer type must be changed in  this screen     The Pressure Transducer Type screen lists all transduc   er inputs currently set up in the RMCC  along with their  board and point numbers  To change the transducer types   scroll through the list using the arrow keys until the desired  input is shown  Using the RIGHT arrow key  move the cur   sor to the input   s Type field and select the desired transduc   er type   0    Standard   1    Eclipse   1      026 1102 Rev 4 08 12 99    12 System Logs and Graphs    12 1     12 1 1  Suction Pressure Log Interval    Logs       PRESSURE LOGGING INTERVAL       ALL Groups   00 03 00                           gt  lt 5                 The Logging Interval defines how often the data within    all suction groups are 
213. e not important  to the RMCC  As a convenience to the user  a Units field is  provided so that analog values displayed on the RMCC  screen are easily interpreted  Enter the corresponding units    RMCC I amp O Manual       of measure for a specified sensor type in the Eng  Unit  field     Control Using   D ifferential or 1st Only   A vg   Ma X   Mi N    D     The control method defined in the Control Using field  determines how to combine the values from up to four sen   sors  This combined or control value is then compared to  defined set points and commands to determine the opera   tional status of an output  Users may choose from the fol   lowing four control methods     e      or Ist Only   The RMCC calculates the dif   ferential of two sensors or uses the primary sensor  value as the control value     e  A VG   The          calculates the control value us   ing the average reading of one or more sensors     e MA X   The          calculates the control value us   ing the maximum sensor reading of one or more  sensors     e MI N    The          calculates the control value us   ing the minimum sensor reading of one or more sen   sors     Up to three sensors may be combined with the current  sensor  Enter the sensor number of the desired sensors to be  combined in the three fields following the field displaying  the current sensor number  The current status of the select   ed sensors are then displayed in the fields directly below  the sensor number fields  The current calcu
214. e set in the up position       other devices in  a segment should have their jumpers set to the down posi   tion  No segment shall have more than two devices with the  terminating resistance jumpers in the up position     DAISY CHAIN CONFIGURATION  SET TERMINATING JUMPERS                          DOWN    J16 J17     9  DAISY CHAIN  1 TERMINATION  ojl  JUMPER SETTINGS                      26513088    Figure 4 7 Terminating Jumpers for a  Daisy Chain   Configuration    STAR CONFIGURATION  SET TERMINATING JUMPERS     P HUB OF STAR                               7    LONGEST LEG       26513089    Figure 4 8 Jumper Settings for Star Network    The REFLECS Networks     4 3    n   mm                        Rotary Dials  COM A and D  only     Each device that may be connected to a segment has ei   ther a network dip switch or rotary dials that provide a  unique identifier for each device on the network  Devices  on a segment may numbered in any order  however  gaps  or omissions in the numbering sequence are not permitted   As an example  if a segment contains four devices  then  board addresses one  two  three  and four must be used   one  two  three  and five would not be permitted     In addition  when setting network dip switches and di   als  both COM A  COM B  and COM D must be considered  together  If the last device on COM A is numbered five   then the first device on COM D must be numbered six     The REFLECS automatically identifies the board types  on the network  therefore
215. e turned on   If a VS HP On Edge is not entered  the RMCC establishes  the value at 50 percent of the maximum horsepower rating  of the compressor     The RMCC will not cycle the variable speed compres   sor on until a horsepower value above the VS HP On Edge  value is called for  Before that time  the RMCC will cycle  the lower capacity standard compressors to try and match  system demand  When the variable speed compressor is cy   cled  it will be brought on at the minimum horsepower rat     Software Overview     9 3    ing  not the On Edge value  and will increase in capacity  until the suction pressure requirement is fulfilled     Once the VS compressor is ON  the compressor rack  operates and deactivates in the same manner as the Normal  strategy described above     9 4 3  Floating Set Point    The RMCC is capable of using the average  maxi   mum  or minimum value of the four temperature sen   sors  or a single value from one of the temperature  sensors  as the float temperature     The Floating Set Point strategy within the RMCC pro   vides a method for varying the suction set point of the  group based on the temperature within a circuit  When ac   tivated  the Floating Set Point strategy monitors up to four  temperature sensors within a circuit and makes adjustments  to the suction pressure when the temperature is too low or  too high     The user establishes a range outside of which the  RMCC is instructed to make a one pound adjustment to the  suction pressure set po
216. each defined transducer at the Transducer Offsets screen to  calibrate the sensor to actual conditions   99   99 Ib    0      Pressure transducers within the RMCC measure the  current suction pressure  discharge pressure  and or oil  pressure within each suction group  Transducer configura   tions are defined at the Transducer Setup screens     Oil pressure transducers monitor the oil pressure within  each of the twenty two available compressor stages  At  times  transducers within the RMCC may provide readings  that read lower or higher than the known condition being  monitored  An offset value may be entered for each defined  oil pressure transducer within each compressor stage at the  Oil Pressure Transducer Offset screen to calibrate the sen   sor to actual conditions   99   99 Ib    0      Discharge Pressure   2 00   5 00 Ib    5     The transducer type defined within the RMCC to mon   itor discharge pressure is selected in the Discharge Pressure  field     Suction Pressure   1 00   2 00   5 00 Ib    1     Suction transducers may be set up for each suction  group defined within the RMCC  The transducer type de   fined to monitor suction pressure is selected in the Suction  Pressure Group fields     Oil Pressure   2 00   5 00 Ib    2     The transducer type defined within the RMCC to mon   itor oil pressure is selected in the Oil Pressure field     System Navigation     11 61    11 8 15 Host Network            HOST NETWORK MENU    1 0NLINE Status  2 Set Device Z s       1
217. ececesessscececesescecececessaaeccecesaaececcecsaaececcscesseaececceesaeseecsensaeeeeeeenes 4 2  4 8  DAISY                Onmeda Deni e e RUE 4 2  240                                                       ode decessor      eene Pe pe eet eec dtes eerta eet veo eee cue prevede 4 3  4 10  TERMINATING RESISTANCE JUMPERS  COM A  COM B  AND COM D ONLY                eese enne 4 3    RMCC I amp O Manual Table of Contents   iii    4 11  NETWORK DIP SWITCHES AND ROTARY DIALS  COM    AND D ONLY               esee enne 4 4          4 12  BAUD RATE DIP SWITCHES  COM    AND D                            enne enne ener entren tense          nnne            nennen nnne 4 4  3  NETWORK SETTINGS         etel ivt Re eR                     4 4  43 1     Network AddEFessess  ae                              eene der              4 4  4 14    BAUDRATESELTIINGS  an Ace ome eni aucaantau us Gh acc coc Coa Noes asd iu ir d 4 5  414 1    Case Controllers  ssa nti epe dete eee certe be ces thesis ti cre             4 5                                   aedium OEE EUM a NN 4 5                 S                    net                  PEOR 4 5             COMI niece nao altes                        aaro ed ee            4 5  4 15  FAIL SAFE DIP SWITCH SETTINGS         ccccccccccecsssscecceceesececeecsescececesensecececeseaseececeseaseaeccecesusaeececessauececeeessaeeeeeeesenees 4 5  5 COMMUNICATION AND POWER CONNECTIONS                  eere seen eee                                         sete setae ee
218. ecial Purpose Communication Boards          Figure 2 7   8DO Digital Output Board    2 4  Special Purpose    Communication Boards    Special purpose communication boards are boards that  either possess greater capabilities than standard input and  output boards  or combine the features of both input and  output boards into a single package     2 4 1  8     Board    When programming the REFLECS  the 81O must  be listed as one 16AI board and one 8RO board     The 8IO combination input and output board is a com   munication board designed to provide input and output  functions within the same board when space restrictions do  not allow for installation of dedicated boards  Like the  16AI and the 8RO  the 8IO must be connected to the RE   FLECS to perform input retrieval and output transmission  functions  The 8IO has input and form C relay output con   nections for monitoring of sensors and control of loads   Since the 8IO has no memory capability  the hand held ter   minal jack is removed from the board  The 8IO is shown in  Figure 2 8     026 1102 Rev 4 08 12 99    system reading falling outside of these set points is detected  by the REFLECS  a signal is sent to the alarm panel  which  in turn emits an alarm signal and displays the alarm infor   mation on the notification screen  Other features of the  alarm panel provide the user with additional information  and capabilities       Alarm reset    Date and time adjustment    Storage of twenty separate alarms      Audible annun
219. ecsssesessseeees D 1  APPENDIX E  WIRING FOR CASE CONTROLLER  POWER MODULE  DEFROST MODULE  AND PULSE   IU ACETATE                                1  APPENDIX     WIRING FOR CASE CONTROLLER  POWER MODULE  DEFROST MODULE  AND   SPORLAN EEPR UE IS Op F 1         0     C                                               T I 1    x   Table of Contents 026 1102 Rev 4 08 12 99    1 RMCC Introduction    The Refrigeration Monitor and Case Control  RMCC   PN 827 1000  is a microprocessor based controller designed to  provide complete control of all refrigeration systems  The RMCC is the controlling component of a three network config   uration  I O  Host  Remote Communication  that includes case controllers  input and output communication boards  remote  communication software  and a variety of sensors  probes  and transducers     RMCC I amp O Manual RMCC Introduction     1 1    2 Hardware Overview    Computer Process Controls uses both an RS485 host  network  I O network  and an RS232 remote communica   tion network to monitor and manage all aspects of  refrigeration control     Within the framework of each of these networks vari   ous components are required to monitor system perfor   mance  control system operation  and interact with remote  communication packages  In general  a standard refrigera   tion control network will consist of the following compo   nents     1  RMCC   2  Various input and output communication boards  3  485 Alarm Panel   4  RS232 Bus Amplifier   5  Remote commu
220. ed Status Time  0005 minutes  Ov State UNKNOWN     Time Left   sec              SELECT NUMBER             MAIN STATUS 12 00 MARIABLE SPEED STATUS 12 00 1 0 Bus State ON Host Net State         1 Group 1 Number Offline   0 Number Offline   0  2 Group 2 GRP1 GRP2 GRP3 GRP4 1234567890123456  3 Group 3                        00 BROs RMCC 2 RMCC 3     485A 1  4 Group 4 0 0 0 0       1    8 8 8 8 4405  C CBs Total D   Online 0                          12 00  OX a    rpm  9  07                act TX       GRP2 STATU 12 00  SUCT     22 2 0 VS          0 rpm  DSCH   20 00 9 Ambient     22  0  03   04 05 06 07 Da                eye              GRP3 STATU 12 00  SuCT   22 2 0  Vey         0 rpm  DSCH   200 200 9 Ambient  0   C 03 0  05 06 07 Da                     8  9  10  11  12    MENU  12 00  VS  OX a    rpm  Ambient  0  05 06 07 08                             RMCC I amp O Manual Appendix D   0 5                  POWER MONITORING 12 00    1 Demand Status 3 Hourly Logs  2 Demand Setpoints    amp  Daily Logs    SELECT NUMBER           DEMAND STATUS                            12 0 DEMAND SETPOINTS  01 of 48 12 00  Demand OFF Timer  00 00           350KW KWHRS EAK TIME DEMAND  Demand Setpoint 5 0350 KW 00 00 00000 00000 00 00 00 00  Current Power Usage  0000 Kw KW TRANSDUCER 00700 00000 00000 00 00 00 00  Peak Power Today 0         00 00 Minimum Voltage 1 000 v 00700 00000 00000 00 00 3  KWHs Used This Mount 00000 05 Maximum Voltage 05 000 v 00700 00000 00000 00 00  Total KWHs Toda   00
221. ee Section 11 4 13   Manual De   frost  or Section 11 4 44   Circuit Setup 1  Add Edit Circuit      Inverter Fail A contact closure has been detected from an input defined as a compressor inverter fail alarm  VS1  INVALM VS4 INVALM   see Section 11 8 1   Input Definitions     IRLDS Fault A system fault alarm has been detected on an IRLDS unit  See Section 14 4   Sensor Alarm Setpoints    Leak An analog signal read from the optional leak sensor input on a CCB has exceeded the leak alarm level  set point for the duration specified in the leak alarm delay field  see Section 11 4 32   CCB Set Point  Screen 2  Liquid Pulse and Stepper Only      Lo Avg Temp The average temperature of all cases in a CCB circuit is low  See Section 14 1   Alarm Set Points    Lo   I O Module   A low alarm set point for an Analog Input Module has been exceeded  Refer to P N 026 1002  Ultr   aSite RMCC Supplement  Section 21 1  Viewing Alarms    Lo Sens The sensor reading has fallen below the low alarm value for a sensor defined as any type other than     1        2     or    5    for the user defined alarm delay duration  see Section 14 8   Alarms     Lo Suction The measured suction pressure has fallen below the user defined low Suction set point for a duration  exceeding the low suction delay  see Section 11 2 3   Group 1 Pressure Alarms Setup     Low Speed Proof A failure has been detected in the low speed fan proof of a double speed condenser    Lo Xducer The sensor reading has fallen below the low 
222. eecceenaeeeees 5 11  RUNE dU T                                                                  5 11  2 027  361Q and  SRO PO ier ette a                   aeree qu ARLE eye tase es eco ete        5 11  5 10  BAUD RATE DIP SWITCH SETTINGS                                                                    5 11  DAO   COM A  and DNetWOrks                            EESE n 5 11           Case Conttollets       Ree see e NE                                     OAD cd d 5 11  5 10 1 2  8IO Baud Rates  23 10 27 COM B                                                    BG        tee iie enia  9 10 32                                                   tete                                       tte Eee       ede           5 11  TERMINATING RESISTANCE JUMPER SETTINGS       cccccccccssssssceceecsesceceseseueeeecesesssecececesaaeccecessaeceeceessueseceeesaeeeees 5 12  8 12  INPUT TYPE  DIP S WITGH SETTINGS eee icio yr ett ore                                       5 12  6 CASE CONTROL HARDWARE OVERVIEW                ee eeeee eee coetu se eoa seen 1 22 5111  51 sese            eto see            sese en eee so etae eene         6 1  6 1   INTRODUCTION 5 eee RR RUN D EH EI IHRE                        6 1  62     HARDWARE DESGRIPTION                                           ro ERO E RECEPTOR ee ne Ee Te RENE          6 1  6 21  Case Controllers  iussi esent iin edet eu 6 1  0 2 2   Input and Output Cabless    tte nre hp ed IO RE HERE QR 6 2  623 P0210 7A cat C0121 711 HT I 6 2  7 CASE CONTROL 
223. eed compressor  operating within its middle range of speeds  around 55   90    When the variable speed is 100   the RMCT will  cycle on enough standard compressors to both fulfill the  HP requirement and to allow the variable speed compres   sor to lower its speed  By keeping the variable speed in its  middle range of speeds  it is in a better position to apply  slight corrections to the PID output to compensate for small  fluctuations in the suction pressure     The RMCT also has a    dead band  feature that cycles  off compressors when the suction pressure drops too low   This feature is described in detail in the System Navigation  section below     RMCT v2 10 System Navigation Screens  Advanced Pressure Menu     The following pages contain all of the screens under the  RMCT s Advanced Pressure Menu that are different from  the RMCC Pressure Menu  Most of the descriptions of  these screens will refer to the RMCC screens in Section 7  of this manual  with only a brief description of the differ   ences between RMCT and RMCC  The RMCT screens that  are identical to the RMCC screens will not be shown in this  appendix     RMCC I amp O Manual          ADVANCED PRESSURE MENU 12 00  1 Status ess  2 Bypass  3 Alarms oat    Setpts  peed Setpts  Setpts    4 Logs  5 Comp Setup    SELECT NUMBER    Appendix        1    Grp 1 3 Pressure Alarms Setup    The Pressure Alarms Setup screens are identical to the  RMCC screens shown in Section 7 3 4  However  since  only three groups may be de
224. een graphics     Data Ranges and Default Settings    Data ranges for data fields   the information supplied  in the help prompt lines   are displayed in brackets and  bold type   99    99    either at the heading for the particu   lar field description  or   when a heading does not exist     within the body of the description  Suggested or default  values for a particular entry are always shown in brackets  and bold type immediately following the data range   99      997    15 5      Alternate Screen Entries    Alternate screens are displayed for Standard and Case  Control Circuit setup as well as for the multiple case con   trol types  If a screen description does not match the screen  on the RMCC front panel  ensure that the description is not  for a different hardware or setup function     System Navigation     11 1       RMCC  Password          Password required to change setpoints   Press ENT for viewing only       10 02 96    Enter Your Password  up to 6 digits     The RMCC requires a password for users to log on and  modify the system  This ensures security of system set   tings  Passwords also determine the access level of the user     New passwords may be added to replace the default  passwords at the System Information screen  see Section  11 8 3  System Information      To view the Log On screen  press the Enter key  To log  on to the system  enter the appropriate password in the  Password field and press Enter  Default passwords are dis   played in Table 11 1     
225. efrost Output status in   formation is displayed in the Stats fields  These fields will  display either OFF or ON  Also displayed is the circuit sta   tus  which will display Refr during refrigeration mode   Defr during defrost mode  Ovrd during manual override  mode  or Drip if the RMCC is in the drain time period im   mediately after defrost termination     LstChg    The times  in 24 hour format  that the refrigeration or  defrost outputs were last activated are displayed in the  LstChg field under the Refr and Defr columns     Temp    The current Control Temperature set point is shown in  parenthesis in the Temp field  Beside this number is the  current circuit temperature reading     Term    The current Termination Temperature set point is  shown in parenthesis in the Term field  Beside this number  is the current termination sensor reading  If the termination  sensors are digital  no value will appear in parenthesis  and  the termination sensor reading will display either a         for  CLOSED or a         for OPEN  If no termination strategy is  defined for this circuit  NONE will appear in the Termina   tion Temperature field     13 3 2  Standard Circuit Summary    uw       13 4     Circuits       Circuit summaries        also accessible from the main  Circuit Control menu  For a description of these screens   see Section 13 2 4         Network Status  I O Board Status      13 3 3  Anti Sweat Status Menu       ANTI SWEAT STATUS         1 Dewpoint Status  2 0utput Statu
226. efrost times may not be appropriate   especially when running hot gas defrost systems     If Door is selected as the Cleaning Override Switch   only the refrigeration output will be turned off when the  cleaning switch input is closed  If a defrost is active  the de   frost output remains energized and the defrost continues as  normal     Cleaning Switch Type   1  Timed   2  Switched   2     Cleaning Switches perform cleaning overrides accord   ing to the strategy defined in the Cleaning Switch Type  field  Users may choose from two cleaning override strate   gies       1  Timed   momentary switch that overrides the cir   cuit OFF for a defined period of time  When select   ed  the override duration should be entered in the  second Cleaning Switch Type field        2 Switched   manual switch that when closed acti   vates the override and when open deactivates the  override     Cleaning Notice Enabled   Y es   N o     To generate a notice in the RMCC Alarm Log when a  Cleaning Override is activated  enter            in the Cleaning  Notice Enabled field     Minimum Defrost Duration Percentage  0 100      The minimum defrost duration percentage is the mini   mum percentage of time a circuit will be in defrost  If the  Defrost Duration is set to 30 minutes  Section 11 4 18    Circuit Set Points 1  and the Minimum Defrost Duration  Percent is defined as 5096  the circuit will be in defrost at  least 15 minutes     026 1102 Rev 4 08 12 99    11 4 20 Circuit Set Points 3           
227. efrost types     Defrost Termination   S tat          D sch   N one    R trn     The strategy the RMCC uses to terminate defrost within  the selected case control circuit is defined in the Defrost  Termination field  Users may choose from the following  strategies        S tat  the          will terminate defrost when it de   tects a change of state from a dry contact        I nl   the          will terminate defrost when the  Coil Inlet Sensor temperature reading exceeds the  defined Termination Temperature set point  This set  point is defined at the Circuit Setpoints 1 screen  see  Section 11 4 46  Circuit Set Points 1  Add Edit Cir   cuit       e  D sch  the          will terminate defrost when the  Discharge Air Sensor temperature reading exceeds  the defined Termination Temperature set point   This set point is defined at the Circuit Setpoints 1  screen     e  O ut   the          will terminate defrost when the  Coil Outlet Sensor temperature reading exceeds the  defined Termination Temperature set point  This set  point is defined at the Circuit Setpoints 1 screen        N one   the          will terminate defrost when de   frost has occurred for the defined Defrost Duration   This duration is defined at the Circuit Setpoints 1  screen     RMCC I amp O Manual          R trn   the RMCC will terminate defrost when the  Return Air Sensor temperature reading exceeds the  defined Termination Temperature set point  This set  point is defined at the Circuit Setpoints 1 screen
228. ell and sends a digital pulse whenever a user de   fined transition type is detected  The pulse width of the One  Shot cell   s pulse is defined by the user  as is whether the  pulse is a Momentary OFF  Momentary ON  or Change of  State pulse     If the One Shot cell is not enabled  the output value will  pass the input value on to the Override cell without modi   fication     Override    The primary purpose of the Override cell is to provide  a method of overriding the Digital Output Module Output  to a user specified value instead of the value dictated by the  One Shot cell  Unlike other Digital Output Module cells   the Override cell may be accessed from the RMCC front    Software Overview     9 13    panel without using UltraSite  The RMCC s Digital Output  Module Bypass screen is shown below        DIGITAL OUTPUT MODULE O1 BYPASS  Name V OUTPUT 01   Enable   Command   Type NORMAL   0005 minutes    Time    Ov State UNKNOWN  T PREV  lt     gt  SET    Time Left 0000 sec    Figure 9 12   Digital Output Module Bypass Screen    The Override cell may override the Digital Command  output to ON  OFF  or NONE  The override may be either  fixed or timed  A fixed override remains overridden until  the user deactivates the override using the Digital Output  Module Bypass Screen  A timed override remains in effect  until a user specified time period elapses or until the user  cancels the override     Counter    The Count cell simply increments the Count output val   ue every time the 
229. en  Stepper Only     10 6  Setup Sensors    1  Define Sensors   Section 11 5 1   Setup    2  Define Sensor Setpoints  All Sensor Types Except IRLDS and Linear   Section 11 5 2   Set Points  all sensor types except  IRLDS and Linear   Linear Sensor Types   Section 11 5 3   Set Points  for Linear sensor types only   IRLDS Sensor Types   Section 11 5 4   Set Points  for IRLDS sensor type only     10 2   System Configuration Guide 026 1102 Rev 4 08 12 99    11 System Setup    Section 11  System Setup  provides a system descrip   tion for every screen programmed in the RMCC  With over  150 accessible screens  navigation through the RMCC can  be complex  The following descriptions provide informa   tion necessary to access any screen  what data entries are  required  how those data are entered  what data ranges are  acceptable for each field  and any default settings when ap   plicable  The screens and instructions were prepared for  RMCC software versions 2 0 and above  therefore  some of  these instructions may not apply to earlier software ver   sions     An overall layout of the RMCC screens is provided in  the foldouts in this section     To help ease the use of this section  the general layout  of the section and the icons used are described below     Page Layout    A main heading entry is provided for each screen found  in the RMCC  For Menu Screens such as the Main or Pres   sure Control menu screens  the screen graphic is accompa   nied by a quick reference table that prov
230. ennen 11 48  REV        CONDENSER STATUS SCREEN NOW DISPLAYS  PHASE LOSS  IF PHASE FAILURE OCCURS                  13 1    RMCC I amp O Manual Table of Revisions     i    Table of Contents    t RMCCINTRODUCTION       T 1 1  2                                          55                                           A 2 1  2  T    REFLECS  CONTROLLERS ener eee idee het reped                                      2 1  2 1 1  Refrigeration Monitor and Case Control  RMCC               esses ener netten eese 2 1  2 2  INPUT COMMUNICATION BOARDS S                                                   ete           2 2  2 21     J6AI Board    ie d dee dein tice iie e eie een ate ued eeu iiie o RI IR 2 2  2 3  OuTPUT COMMUNICATION BOARDG        ccssssccececssssceececessececescsesscececcsensnececesesaeeececessassececesenssecececessaaeececessaaececceenaaecs 2 3  224                                                   aha stn A aia Baa A PBI i RIE 2 3  2 3 2  SRO Eorm C Boards                   SE te        ie Sty        2 3  2 3 3  4AO Analog Output Board    ecelesie edi iet ertt ete EE eerte eere        2 4  2 3 4   8DO  Digital Output Board                         e eet p PE OI Re HERE RE 2 4  2 4  SPECIAL PURPOSE COMMUNICATION BOARDS         ssccssesssseseeceessceseeceenececesensaseececesessececeseassecececessaaeceecesuauececeeensaeas 2 4  Zu  T   OIOvBOGFd    seiten aee eec eite vec val E E eU        2 4  24422  lt                                                                                
231. eparate temperature or  pressure values as the control value  These inputs may be  used to control the fan based on sump temperature or con   denser pressure values     The Evaporative strategy activates the fan in order to  keep the sump temperature or the combined pressure value  below the set point  see Section 9 5 2   Fan Control  for de   tails      9 5 2  Fan Control     The Output at Setpoint for Condenser Control de   faults to 0   NOT 50  as is the case with most other  PID controlled systems  In other words  proportional  mode begins at 0  when the input is equal to the set  point and ends at 100  when the input is equal to the  set point plus the throttling range     Regardless of the control strategy used  condenser fans  are controlled using PID control  see Section 9 1    The    026 1102 Rev 4 08 12 99    control value  determined by the control strategy  is com   pared to the condenser set point and throttling range  and  the resulting 0 100  output is used to activate the corre   sponding percentage of fan capacity  The percentage is  used differently based on whether the fans are single   two     or variable speed     9 5 2 1     For single speed fan stages  the percentage corresponds  to the number of fan stages  A 7596 output in a 12 stage  condenser  for example  would activate nine fans  Single   speed fan operation may be further fine tuned by specify   ing on off delays and minimum on off durations     9 5 2 2  Two Speed Fans    A two speed condenser is
232. eps second  e Hysteresis     steps    e Valve Type  4 phase unipolar    Alco ESR 12  bipolar     Full Travel  500 steps    Maximum Step Rate  50 steps second  e Hysteresis     steps    e Valve Type  2 phase PM 2 coil bipolar    Case Control Software Overview     8 3    Alco ESR 20  bipolar     Full Travel  800 steps      Maximum Step Rate  50 steps second     Name   Type   Default_  Mia  Description  Max Step Rate 1 100 The maximum number of steps per second the valve will support     e Hysteresis     steps    e Valve Type  2 phase PM 2 coil bipolar    0   100 Number of steps required for valve to change direction   Full Travel 0   6553 Number of step at which the valve is open 100         Table 8 6   Stepper Valve Parameters    4  eirost Contro    There are three types of defrost supported by the case  controller  hot gas  electric off cycle  also called timed    and reverse air  For hot gas  a suction valve must be wired  to the optional suction valve terminal of the case controller   See Figure 7 2 in Section 7 5   Optional Inputs and Out   puts  This suction valve closes during hot gas defrost  The  state of the outputs during defrost is shown below in Table    8 7   Suction  Valve    Start De  OFF ON OFF  frost  pump  down     ON    Table 8 7   Output State During Defrost    Drip    The fan may be configured to be ON or OFF during de   frost     Termination of the defrost may be via  1  termination temperature reached   2  defrost termination input  or   3  expiration of
233. er the desired value using the numeric keypad   When finished  use the UP and DOWN arrow keys to move  the cursor off the screen     The F1 and F2 keys are defined as shortcut keys  When  F1 is pressed  the display jumps to Screen 1  showing the  case type  the software revision  the system status  and the  time  When F2 is pressed  the display jumps to the override  screen  where users may initiate manual defrost  terminate  defrost mode  or override the system off     The following sections show the HHT screens for all  CCB types currently available     System Navigation     15 1    15 1     Liquid Pulse HHT Screens    15 2   Hand Held Terminal Screens    Supht 1  Setpt  Valve 1 2  Case dF    Setpoint  Valve 2 X  Case dF    Defr 00 00  Failsafe 00 00  Term 0   Setpt    Defr  5 NONE  Defr  6 NONE  Drip 00 00  Set Time 00 00    Case Type   the four letter case type code  See Section 11 4 16   Circuit Setup 1 for a complete  table of codes     Rev   the software revision number     Status   the system is operating in either of five modes  refrigeration on  On   refrigeration off   Off   defrost on  MDfr   recovery mode  Rcvy   or override mode  Ovrd      Time   the current time  in 24 hour format      Disch Air   the current discharge air temperature reading    Setpt   the discharge air set point  This may be changed with the HHT    Case dF   the current case temperature in degrees Fahrenheit    Case Offset   the case temperature sensor offset  This may be changed with the HHT
234. er to the RMCC is lost     11 2 3  Group 1 Pressure Alarms Setup       UP 12 00  m Dchg Alm   m  s                            Proof DLly  050                RE A  High Suct 45 0  Low Suct 01 0  Pump Down  00 5  Automatic Oil Res  Copeland Oil Syste                               Window Om  sec       T PREV Y NEXT   5 SET DATA    The RMCC sends an alarm to the RS485 Alarm Panel  and writes an alarm to the alarm log when specific control  values exceed HI and LO alarm set points  Compressor  alarm set points are defined at the Group 1 4 Pressure  Alarms Setup screens  The Group 2  3  and 4 screens are  accessed by pressing the down arrow     High Suct   20   999 Ib    45 0     The RMCC will generate an alarm when the measured  suction pressure rises to the High Suction Pressure set  point     Dly  0   240 minutes   60    The High Suction Time Delay is the duration the  RMCC must wait before generating an alarm when the  High Suction set point is reached     RMCC I amp O Manual          Any compressor may be manually bypassed at the  Compressor Bypass screen  The bypass overrides the sys   tem compressor settings until          is entered at the Com   pressor Bypass screen  However  in the event of phase loss   or if the high discharge trip point is reached  the compres   sor will be shut down regardless of the bypass condition     The RMCC displays the compressors as defined under  Output Definitions  page 54   but does not differentiate be   tween groups     To bypass a compres
235. erating in either of five modes  refrigeration on  On   refrigeration off   Off   defrost on  MDfr   recovery mode  Rcvy   or override mode  Ovrd      Time   the current time  in 24 hour format      Setpt   the current control temperature set point  This may be changed using the HHT     CaseOffset   the sensor offset for the control temperature  This may be changed using the  HHT     Valve 1 96   the current opening percentage of the valve   Disch Avg   the average of the discharge air sensor readings     Disch 1   Disch 4   the current readings of discharge air temperature sensors one through four     Defr   When in defrost  this field shows the number of minutes and seconds the circuit has  been in defrost  This number will be equal to the fail safe time when not in defrost     Failsafe   the maximum number of minutes and seconds defrost mode will remain active   Term   the termination temperature sensor reading   Setpt   the termination temperature set point     Defr  1 Defr  4   the first four scheduled defrost times     Defr  5 Defr  6   the fifth and sixth scheduled defrost times     Drip   When in drain mode  this field shows the number of minutes and seconds the circuit has  been draining  This number will be equal to the set time when not in drip mode     Set Time   the amount of time moisture on the coil is allowed to drain after defrost     Humidity   The humidity sensor reading     Aswt    The percentage at which the anti sweat heaters are operating     Max   The 
236. ete     Should the CRC test fail  contact the CPC Service De   partment for further information     Enhanced Phase Loss Processing  Y es   N o   N     This is a special application in the RMCC and should  not be activated unless you call CPC     026 1102 Rev 4 08 12 99    11 8 5  System Information       SYSTEM INFORMATION  Send Notices to 485 Alarm     Disable Alarm Reset by 485 Alm            Delay Before Alarm Dial Out    DAYLIGHT SAVINGS MODE   AUTOMATIC  DST MANUAL SET START    04 05   DST MANUAL SET END 10 25 92    T PREV 4            gt  5                                                   Send Notices to 485 Alarm   Y es   N o   N     To send generated notices to the 485 Alarm Panel in ad   dition to generated alarms  enter  Y es in the Send Notices  to 485 Alarm Panel field     Disable Alarm Reset by 485 Alm   Y es   N o   N     To deactivate this feature  enter  Y es in the Disable  Alarm Reset by 485 Alm field     Delay Before Alarm Dial Out  0   240 minutes   0     RMCC alarms are usually accompanied by an alarm di   alout sequence  The time delay for the dialout is defined in  the Delay Before Alarm Dial Out field  The Dialout Time  Delay is the amount of time in minutes the unit must wait  before activating the call out sequence  The delay allows  an on site user to acknowledge the alarm  thereby cancel   ling the dialout     11 8 6  Send to 485 Alarm Panel    K B            2  SEND TO 485 ALARM PANEL  CHECKIT                         YES  SENS LO       5   COMP P
237. etpoint value  See Section 3 3   Condenser Control  for  more information about throttle ranges     If the condenser is being controlled by pressure  be sure  to set the Throttle Range to 60  At the same time  the PID  Output as Setpoint should be set to 50  set the PID Output  as Setpoint on the Condenser PID Parameters screen      Shift During Reclaim   99   999   0     During reclaim  it may be preferable to increase the  pressure at which the fans begin to operate in order to in   crease the temperature of the refrigerant in the system  The  Shift During Reclaim set point shifts the First Fan set point  pressure by the number entered  All subsequent fan set  points are adjusted accordingly     For example  if the Setpoint is 175  the Throttle Range  is 25  and the Shift During Reclaim set point is 25  the first  condenser fan set point will be shifted to 200 and the last  condenser fan will be activated at 225 when a call for re   claim is received from an environmental control system     026 1102 Rev 4 08 12 99    Minimum Condensing Setpt  Temp Diff Strategy  Only   0   999   50 0     This field appears at the bottom of the Condenser Set  Points screen only if the Temperature Differential strategy    is specified in the Condenser Setup screen  see Section  11 3 1       11 3 9  Condenser Setpoints Screen 2       CONDENSER SETPOINTS       Fast Recovery Setpoint                           Low Pressure Cutoff Setpoint               T PREV              gt  5        Fast Recove
238. etup 11 63    8RO Form C Relay Output Board  Baud Rate Dip Switch Settings    defined 2 3   features 2 3   max number of boards 2 3  mounting in enclosure 3 1  mounting without enclosure 3 3  software setup 11 63    8RO Relay Output Board  defined 2 3    RMCC I amp O Manual    features 2 3   max number of boards 2 3  mounting in enclosure 3 1  mounting without enclosure 3 3  power requirements 5 7  software setup 11 63    A    Alarm Dial Out  changing baud rate 11 58  day phones 11 58  defining dial out delay 11 57  night phones 11 58  setting baud rate 11 60    Alarm Panel  See 485 Alarm Panel     Alarms  defining dial out delay 11 57  filtering to 485 Alarm Panel 11   57  14 3  RMCC alarm logs 14 4  RMCC alarm types 14 5    Alarms  Power Failure 11 56    Analog Input Module  See I O Con   trol  Analog Input Module    Analog Output Module  See I O Con   trol  Analog Output Module     Anti Sweat  Case Control Circuits 8   5 9 7   enabling 11 41   example of 9 7   high low limits  CPC suction  stepper 11 34   high low limits  liquid pulse   stepper 11 33   high low limits  suction stepper    set points 9 7  Anti Sweat  Standard Circuits 9 7    example of 9 7   logs 12 1   offsets 11 21  overrides 11 22   set points 9 7  11 22  setup 11 22    B    Baud Rate Settings    SIO ARTC 4 5  COM B 4 5  COM C 4 5    Bus Amplifier  See RS232 Bus Ampli   fier           Case Control  Alco valve settings 8 4  anti sweat heater control 8 5  control algorithms 8 1  defrost control 8 4  defrost
239. evaporative 9 4  evaporative strategy 11 10  fan run times 11 13  fast recovery 9 6  fast recovery for evaporative  condensers 9 6  set points  ambient split temp 11 18  ambient temp dead band 11   18    ambient temp during reclaim  11 18  discharge dead band 11 18  discharge unsplit 11 18  fan set point 11 16  fast recovery 11 17  fast recovery control type  shift during reclaim 11 16  throttle range 11 16  setup 11 10  11 16  control source 11 11  control strategy 11 10  air cooled 11 11  temperature differential  11 11  control type 11 11  evaporative 11 11  evaporative inputs  offsets 11 12  type 11 12  evaporative sensor combina   tion 11 11  inlet pressure offset 11 11  outlet pressure offset 11 11  refrigerant type 11 11    026 1102 Rev 4 08 12 99    split  ambient dead band 11 18  ambient temp 11 18  ambient temp during reclaim  unsplit pressure 11 18  split operation 9 6  unsplit set point 9 6  strategy setup 11 10  temp diff strategy 11 10  specifying refrigerant type  11 11    throttling range 11 16    Condenser Fans    bypass 11 18  bypassing 11 19  clearing run times 11 18  min off time 11 12  min on time 11 12  PID Control 9 4  run times 11 18  setup  control types 11 11  single speed 9 5  11 12 11 14  clearing failures 11 14  delay between clear attempts  enabling fan fail 11 13  equalize runtimes 11 13  fan fail delay 11 14  fan off delay 11 13  fan on delay 11 13  fast recovery off delay 11 13  fast recovery on delay 11 13  force split in reclaim 11 13  numbe
240. evels specified correspond to preset  values of the throttling range and the integral gain  as    026 1102 Rev 4 08 12 99    shown in Table 8 4 and Table 8 5  Throttling range deter   mines the range of inputs that will result in a 0 100  pro   portional reaction  therefore  the higher the sensitivity  rating  the lower the throttling range  The integral gain is  simply a multiplier that adjusts the size of the integral part  of PID  therefore  greater integral gains result in higher  sensitivity        Table 8 4   Relationship of Sensitivity to Throttling Range  TR   and Integral Gain  K   for Suction Side Control     Sewwy  3      S RE 8                            Table 8 5   Relationship of Sensitivity to Throttling Range  TR   and Integral Gain  K   for Liquid Side Control       Throttling ranges and integral gains not shown in the ta   bles may also be used  To determine the sensitivity number  for a custom combination  use the following formula     Sensitivity   16 x  TR 2     5x Kj     Sensitivity calculated with this formula will not corre   spond with the sensitivities listed in Table 8 4 and Table 8   5  The formula listed above is used to calculate custom sen   sitivities only     RMCC I amp O Manual    Pulse Valve Control    Pulse valve control is used by the liquid algorithm to  control superheat  The coil control algorithm calculates an  output percentage and passes this value to the valve control  algorithm  The valve control algorithm pulses the valve on  and 
241. f set point is 50  the  RMCC begins Low Pressure Cutoff mode  The RMCC will  continue low pressure cutoff mode until the pressure rises  above 52 psi  50   2 0      System Navigation     11 17    11 3 10 Condenser Split Setpoints    G2    3  Cs      CONDENSER SPLIT SETPOINTS          Discharge Unsplit Press       Discharge Unsplit Press Deadband   Ambient Split Temp   Ambient Split Temp During Recl  Ambient Split Temp Deadband      gt  SET DATA                Discharge Unsplit Pressure  0   999 Ib    N one   N     In some instances  unacceptable pressure levels within  the refrigeration system require that a condenser be brought  out of split mode  When the discharge pressure level reach   es the Discharge Unsplit Pressure Set Point  the selected  condenser will be brought out of split mode and the con   denser fans will return to normal operation  To activate the  Discharge Unsplit Pressure feature  enter a value in pounds  in the Discharge Unsplit Pressure field  A    NONE    in this  field disables this feature     Discharge Unsplit Press Deadband  0   50 Ib    10     The Discharge Unsplit Pressure Dead Band is a value  equally above and below the Discharge Unsplit Pressure  set point within which the pressure level in the refrigeration  system is considered to be acceptable  This value ensures  the condenser does not drop in and out of split mode when  the discharge pressure hovers around the Discharge Unsplit  Pressure set point     11 3 11 Run Times       CONDENSER RUNT
242. f this  value is HIGH  the Select cell sends the Occ SP analog sig   nal to the Setpt Reset cell  If the Occup value is LOW  the  Select cell sends the Unoc SP analog signal to the Setpt  Float cell     Because the Occ SP and Unoc SP values may be sup   plied by external analog signals   and because the Analog  Output Module requires a set point value to function cor   rectly   the Select value may be programmed with    fall   back  set points  which are used if the set point values  become corrupted     As an added safety measure  the Analog Output Module  may be programmed to supply a fixed numerical value that  will be used as the PID Output in case the set point or con   trol input s  become corrupted     Setpt Float    The Setpt Float cell provides users with a method of  raising and lowering the PID Setpoint based on the value of  the Float Control input  This cell is primarily designed for  heating and cooling applications  such as modifying space  temperature set points based on outside air temperature  sensor values     To set up the Setpt Float cell  users must supply three  set point values  a High Float Value  a Low Float Value   and an Output Range     The Output Range is the maximum amount that the PID  Setpoint may vary  An Output Range of 4  for example   means that the PID Setpoint input being read from the Se   lect cell may only be increased by 2 or decreased by 2     The High Float Value and Low Float Value form a  range of values that determines what port
243. failures  The Digital  Output Module is shown in Figure 9 11     Command    Input Value DVCombiner One Shot Override          1 4    In 2 Out  In 3  In 4       In 1 Trigger Out In                Command          on  off  normal   Type              timed  fixed   OV time                     Combiner Pulse Width           Timer      gt  Use Alt Comb    Comb            Alt Comb    Invert Output                 Suspend  Count        00    Reset Count    OR    d el    Schedif  Occupied Logic In        vy Sched In Out  Alt Schedule        m Use Alt Sch    Comb Type  Alt Comb  Invert Output  inn                         Counter Increment                    Counter       In    Suspend    Reset                Initial Count    Trip SP   Reset Type             Select Proof       Min On Off Int       In In2          Desired Proof Output    Faila am    Actual                   Min On Off Times          Min On Off Delays       Proof Input           Figure 9 11   Digital Output Module  Inputs  Input Value 1   4  In1 In4     Up to four digital inputs may be combined in a Digital  Output Module     9 12   Input Output Control                   Delay     Latch Time     26512021    Suspend Count and Reset Count    The Digital Input Module has a cell  called the Counter  cell  that counts the number of times the Output goes from  OFF to ON  There are two inputs that manipulate the mod     026 1102 Rev 4 08 12 99    ule s Counter cell  The Suspend Count input  while ON   prevents the Counter cell 
244. fined in the RMCT  there is no             PRESSU 12 00 Group 4 setup screen   High Suct   0   Dchg            Low Suct        Proof        030   Pump Down      Automatic Oil    Copeland Oil   Window 010                                                          T PREV               gt  SET DATA    The Pressure Alarms Notices Setup screen is nearly  identical to the RMCC screen shown in Section 7 3 5   ex   cept there is no GP4 column           Suction    Discharge   Pump Down   Oil Fail  Phase   T PREV J NEXT                                     The Pressure Groups Setup screen is similar to the  Compressor Setup screen shown in Section 7 3 9  Howev   er  only three groups may be defined  and no more than ten  PRESSURE GROUPS SETUP compressors may be defined in a single group            1  Name   Comps   2  Name   Comps   3  Name   Comps                                      4            gt  SET DATA       Groups 1 3 Setup    The Groups 1 3 Setup screens are similar to the RMCC  Group Setup screens as shown in Section 7 3 10  However   the first compressor in the group is always  V ariable   speed  and its type may not be altered        GROUP1 SETUP  a      T t    E 2 06000 p Also  since there are only three suction groups  there is  OIL SENS           no Group 4 Setup screen   OIL PRES   00 0  HP AMPs   015  PROOF   NO    T PREV                gt                                                                                  2   Appendix    026 1102 Rev 4 08 12 99    Group 1 3
245. fingertips of the service  technician or store manager  However  no network is com   plete without the basic ability to provide annunciated  alarms in the event of serious system problems     CPC uses the 485 Alarm Panel  Figure 2 9  to accom   plish this task  The 485 Alarm Panel is linked to all RE   FLECS Controllers through the   5485 COM B Host  Network  Although the alarm panel has many features that  make it a powerful notification tool  the primary and most  important function of the alarm panel is to receive signals  from the REFLECS and deliver an alarm annunciation     The REFLECS constantly compares real time system  conditions against user defined alarm set points  When a    RMCC I amp O Manual Hardware Overview     2 5     0  and ne ermina    The Hand Held Terminal  HHT   shown in Figure 2   10  connects directly to the RJ11 jack on a case controller  and is used to make set point and setup adjustments during  system start up or for routine or emergency maintenance   The HHT displays several screens for viewing refrigeration  system status  making control set point adjustments  and  bypassing loads on or off  Set point changes made through  the HHT are transferred to the RMCC by the case control   ler and overwrite any existing set points     7   S  v       LEGEND    LCD Display 3  RJ11 Jack  Numeric Keypad                            26509010    Figure 2 10   Hand Held Terminal       af  emote Communication    2 7 1  RS232 Bus Amplifier    The RS232 Bus Amplifie
246. for  the day     Demand    The Demand field will read ON when the energy being  used exceeds the Demand Set Point defined on Section  11 7 1   Demand Set Points  Otherwise  the Demand field  will read OFF     13 10   Demand       13 7 3  Digital Output Module Status       DIGITAL OUTPUT MODULE 1 STATUS    OUTPUT 01      NONE  Tripped NONE       Users may view the real time status of a Digital Output  Module s outputs in the Digital Output Module Status  screen  The Command  Proof  and Count Tripped output  values will appear as either ON  OFF  or NONE  The Count  value will appear as an analog value     To view the status of other Digital Output Module Sta   tus screens  press the UP and DOWN arrow keys     Timer    A timer within the RMCC calculates the number of  hours and minutes the current power usage has exceeded  the defined Demand Set Point during the last 24 hour time  period  The timer resets every night at midnight and the cu   mulative demand time is cleared     Set Point    The defined Demand Set Point is displayed in the Set  Point field  This is the desired level of energy consumption  within the system     Current Power Usage    The current kW reading provided by the kW transducer  or watt hour transducer is displayed in the Current Power  Usage field     Peak Power Today    The peak power is the highest value of KW measured by  the kW or watt hour transducer during a specified period of  time  The peak power for the day is displayed in the Peak  Power Today f
247. from counting ON transitions   The Reset Count input supplies a digital signal that resets  the Counter cell to its user specified initial value     Occupied  Occup     The state of this input tells the Digital Output Module  that the building is either occupied  ON  or unoccupied   OFF      Alt Combiner  Use Alt Comb     The Digital Output Module allows for a user to specify  two different input combination strategies  a primary com   bination type and an alternate combination type  The mod   ule reads the state of the Alt Combiner input to determine  which combination method to use     Alt Schedule  Use Alt Sched Comb     After the module   s Digital Inputs are combined in the  DVCombiner  the Digital Input Module allows the user the  option of combining the resulting value with the value of  the Occupied  Occup  input  Two different combination  strategies may be chosen  a primary combination type  and  an alternate combination type  The module reads the state  of the Alt Schedule input to determine which combination  method to use     Proof Input    The Digital Output Module issues a command  called a  proof failure command  as a result of comparing the final  control value issued by the module with a digital value  called the Proof Input  The Proof Input is most often  hooked to the physical device being controlled by the Dig   ital Output Module   s Output  so that the RMCC has a  means of assuring that the device is being properly activat   ed and deactivated     Cells
248. frost Enter Item  00 00 00 00 0 00 00  ENT Next ti  Circuit  lt   gt    Board             4            gt  SET DATA   gt  SET DATA         STATUS CCBHOTSDIC O1c 12 00 FCIRCUIT SETPOINTS  1 501   01   12 00       SETPOINTS CCBHOISDIC O1c 12 00   ase Lights Strategy   On Supht Setpnt   8 0 Revision  6 082  Case Temp   007 0 Setpoint    025  Case Pump Down Delay   000 sec Sensitivity   4  Status    On Last Term  000 0 Shut Down 1f Suction Grp Fails  0 Recovery     O70  Coil In 2  005  Valve      100 0 Anti Sweat Control   No Max Rcvy Time  000  Super Heat  008 0 Setpoint   008 0 Dual Tmp Alarm Set Point Shift  000 0 Asw Hi Limit  060 0  Humidity X           Antisw     100 0 Dual Temp Shift Input   None Asw Lo Limit   40 0 Frost Sensor  NO              Board T PREV 1            gt  SET DATA T PREV 4            gt  SET DATA       T PREV 4                                                          CCB STATUS CCB 01SDIC 01c 12 00       ALARMS  CCB 01SDIC 01c GRAPH CONTROLS  Coil 1 In   YES Refr Leak  Disch Air   007 0 Setpoint    025  Coil 1 Out  YES Leak Alm Lvl   gt   lt   Scroll  Return Air  OPEN Valve     100 0 Coil 2 In   YES Leak Alm Dly      Go to current  Superheat 008 0 Setpoint   008 0 Coil 2 Out  YES 7   Zoom out  Zoom in  Coil In  005  Bypassed Vlv    030      Menu  Coil Out 003 0 Door Alm Dela PLEASE WAIT  1          S NEXT   gt  SET DATA         STATUS CCB O1SDIC O1c 12 00       OFFSETS  CCBHOISDIC Olc 12 00 0 xo mn 0  Case Offset  0 0 Coil 2 In   0 0  Frost   OPEN Disch
249. gital Override Input   00 PID Output  NONE  0 0 of 0 0 0 0 0 0 0 0 07 18 13 47 85 6 TuPn Sensor Relay OFF   N PID Setpt   NONE  CUT ON 8000 0        OFF 8000 0 Alarms  HIGH 0100 Low 0035  Dly   05   07 18 13 44 85 4            FIX Duration   00 00 PWM Output  NONE  Delay  00005 Delay  0000 Notices HIGH NONE        NONE Dly   00    07 18 13 31 85 6 Manual Override   NORM  Logging Interval  HH MM SS   00 03 00 Min time ON  ODOmin Offset  000 0 07 18 13 28 8515 Leave a Notice in Alarm Logs   NO Stages  T PREV L NEXT   gt  SET DATA T PREV   NEXT                                gt  SET DATA T PREV 4            gt  SET DATA    gt  SET DAT T PREV J NEXT  OR DIGITAL OUTPUT MODULE 1 STATUS 17 00  Name  DV OUTPUT 01  SENSOR ALARM SETPOINTS 12 00 gennana  NONE  No   01 Name  IRLDS OUTRE E NONE  Type  Temp Eng  Unit PPM EQUI               NONE  Alarms  High NONE Delay 000 m  Notices High NONE Delay O00 m P  Fault Alarm   ENABLED    ANALOG INPUT MODULE 01 BYPASS 12 00  Name  AV INPUT 01  Enable   NO  Command  0FF Type NORMAL  Time  0005 minutes    Ov State NORMAL Time Left          sec                                       ANALOG OUTPUT MODULE O1 BYPASS 12 00  Name  AV OUTPUT 01  Enable   NO  Value  000 0 Type NORMAL  Time  0005 minutes  Ov State UNKNOWN     Time Left    sec  T PREV   gt  SET O MENU  STATUS MENU 12 00 DIGITAL OUTPUT MODULE 01 BYPASS 12 00  Name  DV OUTPUT 01   l Main Status 4 1 0 Network Enable   NO  B Input Status 5         Network Command  0FF Type NORMAL  B Variable Spe
250. gy   T emp Temp  T X V     The strategy used to control refrigerant flow is defined  in the Valve Control Strategy field  Users may choose from  the following strategies        T emp Temp   the refrigerant flow is being metered  by an EEV controlled by superheat  coil inlet tem   perature   coil outlet temperature   When refrigera   tion is called for  the EEV opens to a percentage  determined by the control algorithm     e T X V   the RMCC does not pulse 24 VAC  but  turns refrigerant flow ON or OFF base on the case  temperature     System Navigation     11 39    Temp Control Strategy   D ischarge Air   M ixed     The strategy used to calculate the Control Temperature  from the discharge and return air sensors is entered in the  Temperature Control Strategy field  Users may choose  from the following strategies       Discharge Air   the RMCC will use the discharge  air sensor as the Control Temperature       Mixed Air   the RMCC will use a mixture of the dis   charge air and the return air to control the circuit  temperature  Percentages are defined on Section  11 4 46  Circuit Set Points 1  Add Edit Circuit      Fans On During Defrost   Y es   N o     To continue normal operation of fans during defrost   enter  Y es in the Fans On During Defrost field  Enter     N   o to shut off all fans during defrost     11 4 46 Circuit Set Points 1  Add Edit Circuit         alfa        a      CIRCUIT SETPOINTS 4Z1  Defr Duration  Drain Time          SDIC O1c  Control Temp  Fan  amp  ASW
251. he RMCC to supply the exact horsepower nec   essary to maintain the set point     Variable speed pressure control may follow either of  two strategies in the RMCC pressure control software  the  Normal strategy or the Alternate strategy     9 4 2 1     The Normal strategy is the default pressure control  strategy used by the RMCC  This strategy dictates that if  there is a variable speed compressor in a suction group   then it will be treated as the primary pressure controlling  device  and any other standard compressors in the rack are  secondary devices used only if the VS compressor is unable  to fully handle the required horsepower  The variable   speed compressor will therefore always be the first com   pressor on and the last compressor off when the Normal  strategy is used     Normal Strategy    A flowchart of the Normal strategy s control scheme is  shown in Figure 9 3  When an inactive compressor rack  receives a call from the RMCC to activate  the variable   speed compressor turns on  The RMCC attempts to operate  the VS compressor at the percentage of its maximum horse   power necessary to bring the suction pressure back down   Note  however  that the rate of change is limited by the VS  compressor   s maximum RPM increase and decrease rates   defined by the user      If the VS compressor reaches 10046 capacity and the  RMCC still demands more horsepower  the RMCC will  look at the standard compressors available and determine  the most appropriate combination of st
252. he default baud rate  select the  baud rate used by the modem being dialed and select  Y  es  in the toggle field     Day Phones Night Phones  Enter Number   T  for  Tone Dial     Phone numbers to be called when an alarm is generated  are defined in the Day and Night Phones fields  Phone  numbers for daytime dialouts as well as nighttime dialouts    026 1102 Rev 4 08 12 99    must be defined in these fields to activate the remote dia   lout function     When an alarm is generated  and after the dialout delay   the dialout sequence begins  If the remote line is busy or  there is no answer  the system will dial the first number six  times  waiting five minutes before each attempt  until a  connection is made  If no connection is made  the system  will dial the Day or Night Phones Two number six times   waiting five minutes before each attempt  If there is still no    11 8 9  Logging Setup    12 00                0                     5               i 0   points   if No Hourly    6    10  12          0 X      gt  SET DATA 0                 The RMCC periodically records data to          Logs  according to Input and Output Logging Intervals defined  within the RMCC  These logs are configured at the Log   ging Setup screen     Select Configuration Type  See Table   0     There is a limited amount of logging space within the            therefore  the available number of logging points  is determined by the number of logs the RMCC is config   ured to generate  Each Input or Output L
253. he door switch   Frost   the demand defrost sensor status                           Refr Leak   the ppm concentration of refrigerant currently being detected by the leak sensor   Offset   the leak sensor offset  This value may be changed using the HHT     Step Deflt   By pressing RIGHT and selecting one of the options below  the hysteresis  max  step rate  and maximum steps values are automatically programmed with appropriate de   fault parameters for Alco EEVs or Sporlan EEPRs  These values may also be reset     1 Alco EEV   Hysteresis is set at 0  Max Step Rate at 33  and Max Steps at 384    2 Sporlan EEPR   Hysteresis is set at 10  Max Step Rate at 100  and Max Steps at 2500    3 Reset   Hysteresis is set at 0  Max Step Rate at 100  and Max Steps at 0    If a default setting was chosen using Screen 12  the default values will be displayed in this  screen  They may be changed at this screen using the HHT     Step Hyst   the hysteresis value  See Section 11 4 38   CCB Stepper Set Points Screen  Stepper  Only  for a definition of hysteresis     Step Hz   the maximum number of steps per second the valve may open or close    Max Steps   the number of steps in between closed  0   and open  100      Control   the valve control type  This should read EEPR  electronic evaporator pressure reg   ulator     Valve Type   the valve type  This should read Step  stepper      Valve Jmpr   whether the CCB s valve jumper is set for unipolar  UniP  or bipolar  BiPo  op   eration  See Section 
254. his value may then be sent to other modules or  physical devices  and it may also be compared to cut in cut  out set points to generate a digital signal  Secondarily  the  Analog Input Module generates alarms and notices  and    Software Overview     9 9    processes override commands     diagram of the Analog In     put Module is shown in Figure 9 9     Analog Input Module    AVCombiner  In 1  In 2  In 3  In 4       Out    Alt Combiner        p   Use Alt Comb             Comb            Alt Comb      w  Limiter  In nr       1          Filter                                 High Low Limits                      Ratio        Period        Suspend  Count            OV     Reset Count         vp         NET  Process Alarm  Input Alarm    Disable Alarm  Disable Notice    Alarm   Notice       Notice  Occup    Occ Setpts  Unocc Setpts                   Occupied                   Figure 9 9   Analog Input Module    Inputs  Input Value 1 4  In1 In4     Up to four analog inputs may combined in an Analog  Input Module     Alt Combiner  Use Alt Comb     The Analog Input Module allows for a user to specify  two different input combination strategies  a primary com   bination type  and an alternate combination type  The mod   ule reads the state of the Alt Combiner input to determine  which combination method to use     Suspend Count and Reset Count    The Analog Input Module has a cell  called the Counter  cell  that counts the number of times the Digital Command    9 10   Input Output Co
255. humidity above which the anti sweat heater will remain on at all times   Min   The humidity below which the anti sweat heater will remain off at all times     Lights   the current status of the case lights  Pressing RIGHT followed by one of the com   mands below allows users to bypass the case lights     1 Auto   Pressing 1 will return the case lights to automatic operation    2 Turn Off   Pressing 2 will bypass the case lights off    3 Turn On   Pressing 3 will bypass the case lights on    Status   the operational status of the refrigeration and defrost modes  Pressing RIGHT fol   lowed by one of the commands below allows users to manually override the case    1 Man Dfr   Pressing 1 initiates manual defrost    2 OV OFF   Pressing 2 overrides both refrigeration and defrost OFF    3 End Dfr OV   Pressing 3 will terminate defrost mode        RMCC I amp O Manual System Navigation     15 9    Disch 1   the current reading of discharge air temperature sensor one   Offset   the offset for discharge air sensor one  This may be changed using the HHT   Disch 2   the current reading of discharge air temperature sensor two   Offset   the offset for discharge air sensor two  This may be changed using the HHT     Disch 3   the current reading of discharge air temperature sensor three    Offset   the offset for discharge air sensor three  This may be changed using the HHT   Disch 4   the current reading of discharge air temperature sensor four    Offset   the offset for discharge air senso
256. i  335 3156  sweat  defrost  For use with non CPC power  modules  without connectors      Output Cable   For use with CPC power mod  335 3158  ules  with connectors     Output Cable   For Sporlan SEI and CDS 335 3159  valves     Table 6 2  Case Controller Cable Harness Part Numbers       6 2 3  Power Modules    In addition to the case controllers  CPC manufactures a  power module for distribution of incoming power to the  controller and electric defrost circuits  The power module  is available with or without circuit protection  See Figure  6 3 and Figure 6 4  The CPC power module configura   tions and part numbers are listed in Table 6 3  The electri   cal ratings for the power modules are shown in Table 6 4     The case controllers may also be installed within the  case in conjunction with an OEM designed power module        Figure 6 3   Case Controller Power Module    026 1102 Rev 4 08 12 99    LEGEND  Class 2  24 VAC  50 VA  Transformer 4  Solid State Relay  Anti Sweat   Mechanical Relay  Lights  5  Three Pole Defrost Relay  Mechanical Relay  Fans                    26510003       Figure 6 4   Case Controller Power Module Without Fuse  Protection    Part  Description Number Lights    120 VAC 1 Phase 240 VAC 3 Phase Defrost  Full Con  Siesoo Ys Yo   Hus  ve      ve  Ye pe  120 VAC 1 Phase 240 VAC 3 Phase Defrost  No Fuses    816 3100 p                  Hess  re pre  re e  120 VAC 1 Phase 240 VAC 3 Phase Defrost  No Fuses                                       Hum  ve      v
257. ible area  but away from custom   ers and most supermarket employees  Generally  the  RMCC is mounted on the rack by the rack manufacturer     For information on setting up all components of a stan   dard refrigeration system control network  see Section 10   System Configuration Guide     Mounting    The REFLECS is supplied with four mounting holes in  the rear panel of the enclosure  These holes are accessible    RMCC 1 amp 0 Manual    without removal of any boards inside the enclosure  Figure    3 1 shows the enclosure dimensions and weight        RMCC   REAR OF ENCLOSURE     WEIGHT  7 LB        26502020       Figure 3 1   RMCC Mounting Dimensions    3 2     Location    The 16AI Input Board  SRO  8RO FC  8DO  and 4AO  Output Boards  and 8IO Combination Input Output Board  are usually installed within the refrigeration rack or the  condenser by the equipment manufacturer  Therefore  the  installer need only make the necessary connections be   tween the REFLECS  the condenser boards  and the refrig   erated cases     l O Boards and Enclosures    In some instances  an installer may be required to  mount an I O board  There are no restrictions on the loca   tion of these boards  however  for ease of network config   uration  it is recommended that the boards be located  adjacent to the REFLECS  If the boards are not located near  the REFLECS  ensure the leg and segment length restric   tions described in Section 4 6  are followed  The I O  boards may be mounted without an encl
258. ides page numbers  for the options listed at that menu screen     In addition to the screen graphic  key graphics are pro   vided that show the exact key sequence necessary to access  a particular screen  Although most of these buttons are self   explanatory  several require further discussion     cU   Data Entry  The Data Entry button means that  data  such as circuit numbers  may be required before    pressing the button  These data vary from screen to  screen and a description of the data is provided when nec   essary     04     Follow On Keystroke  When    subscripted num   ber appears next to a key graphic  it means that the key    RMCC I amp O Manual    should be pressed that number of times to reach the desired  screen  In some instances  a subscripted number may be    followed by a   symbol  24     This means that the key    may need to be pressed an additional time to reach the de   sired screen     Help Prompt Lines    Most RMCC screens contain a help prompt line at the  bottom of the screen that provides the user with informa   tion about navigation and field data ranges  Within this sec   tion  the help prompt line shown is always the line that is  displayed when the cursor is off the screen  Generally  the  prompt line changes when the cursor is moved to a data en   try field  For information on what data are displayed see  Section Data Ranges and Default Settings below     Data Fields    Data fields where entry is required by the RMCC user  are shaded on the scr
259. ield along with the time of its occurrence   This measurement may help determine the time of day to  minimize active loads to help reduce power consumption     KWHs Used This Hour    The kW measurement for the previous hour is dis   played in the KWHs Used This Hour field     Total KWHs Today    The total kW usage for the day is displayed in the Total  KWHs Today field     026 1102 Rev 4 08 12 99    13 9          Boards       13 9 1  On Line Status             Description  Pave    Refer to the description of the I O Bus State in Section 13 2 4    O Network Status  I O Board Status         T PREV               The Pressure Status screens display the current status of  each compressor defined using the Output Definitions  screens  Section 11 8 2   Output Definitions   The com   pressors are grouped and displayed according to how many  compressors have been defined for Groups One through  Four at the Pressure Groups Setup screen  Section 11 2 8    Pressure Setup   If more than five compressors are defined  for a group  pressing the down arrow will display the addi   tional compressors     Type  amp       The Type  amp    field shows the compressor type   C om   pressor   V ariable speed compressor  or  U nloader  These  types are defined at the Group 1 4 Setup screens  Section  11 2 7   Group I Setup   The compressor number is shown  as defined under Output Definitions     RMCC I amp O Manual       Status   The current operational status of the each compressor is  given as      
260. ill maintain within the selected case     13 6   Case Control Status    Humidity      When the CCB   s Anti Sweat feature is active  the cur   rent status of the selected humidity sensor is displayed in  the Humidity   field     Antisw      The Anti Sweat percentage is displayed in the Antisw     field  This percentage is the cycle rate of voltage pulsing  to the case   s anti sweat heaters     13 4 3  CCB Status 1  Suction Stepper  Only                  CCB STATUS CCB 01SDIC O1c    NONE Setpoint          Case Temp  Last Term    Valve   X i  Humidity     Antisw  2        For suction stepper circuits  this status screen displays  current information about case sensor readings and set  points     Case Temp    The current case temperature sensor reading is dis   played in the Case Temp field     Setpoint    The defined case temperature set point is displayed in  the Setpoint field     Status    The status of the selected CCB is displayed in the Status  field  One of the following conditions will be displayed     e On  the selected case board is calling for a stage of  refrigeration     e Off  the selected case board is not calling for a stage  of refrigeration     e Def   the selected case board is calling for a stage of  defrost       Lost   the selected case board cannot be found with   in the defined circuit     Last Term    The temperature at which defrost was last terminated  within the selected case is displayed in the Term field     026 1102 Rev 4 08 12 99    Disch Air   
261. imum Speed  0900 rpm  Fan Minimum Off Time 2000 i  Onsplit Deodband Fan Loy Qutput        Relay T VS Maximum Speed  1800 rpm   i  Ambient Split Temp Fan Off Output  No Relays VS Increase Rate  2000 rpm  minute      Ambient Split Temp During Reel V  Decrease Rate  2000 rpm minute      Ambient Split Temp                 Start Speed off                CONDENSER SINGLE SPEED FAN SETUP 12 00 CONDENSER 2 SPEED FAN SETUP 12 00 CONDENSER        FAIL SETUP 12 00  Fan Fail Enable  NO   Fan      Delay 0030 Start Duration      0000 Fan Fail Delay 10005   Fan Off Belay 10050 fitgh to Low             0020   Fast Rec Fan      Delay  0006 Low to High Delay 0000 Continually try to Clear Failure NO   Fast Rec Fan Off Delay  0006 Low Speed HP 50 Num Clear Attempts     SINGLE SPEEI   High Speed HP 88 Delay Between Clear Attempts 0030   T PREV 4 NEXT   gt  SET DATA 1                      gt  551  T PREV 4 NEXT   gt  SET DATA             CONDENSER SINGLE SPEED FAN SETUP 12 00 SHOWN      CONDENSER FAN FAIL SETUP T2 00  CONDENSER VS FAN FAIL SETUP 12 00  Fan Fail Enable  NO  Split Enable Fan Fail Delay  0005 Inverter Reset Count 003        Split Type                  SEE TWO  AND    Unsplit to Split Delay               VARIABLE SPEED    T PREV J NEXT      S8ET D    Inverter Reset Delay  0030    Num Clear Attempts    Delay Between Clear Attempts  0030  T PREV 4 NEXT      SET DATA     SET DATA                      CONDENSER FAN FAIL SETUP 18 00 5 REENS N  Fan Fail Enable  NO  Fan Fail Delay 10005 THIS
262. ing for the Floating Set Point Strategy  therefore   the strategy is disabled during defrost  After defrost  there  is a period of time that the system must wait before reacti   vating the Floating Set Point Strategy  This duration is the  Floating After Defrost Delay and is defined in the Delay  Floating After Defrost field     Extern  Shift   99   99   0     In certain instances  users may wish to increase suction  pressure during hours when refrigeration demand is greatly  reduced  This shift to the Suction set point is achieved by  entering a value in the External Shift field  On a contact  closure  defined as a sensor input under Input Definitions   Section 11 8 1  Input Definitions   the RMCC adds the Ex   ternal Shift value to the Suction Pressure set point and con   trols compressor operation based on the new increased  value     Press  1   9 0  To Toggle Compr      gt  lt      Exit  Prev  Next       12 00     CLR  Clear Step     Last Step     I  Insert Step  D  Delete Step  Max Number of Steps for This group  20             When the Fixed Step Strategy is activated at the Group  Pressure Set Points screen  see Section 11 2 10  Group 1    System Navigation     11 9    Pressure Set Points   the RMCC cycles compressors within  the selected group according to a sequence of operation de   fined by the user at the Fixed Step Strategy Set Up screens   Each suction group may have its own strategy  Options for  defining this sequence of operation for each suction group  are d
263. ing on the current operation     Discharge    Trip Point  5   499 Ib    350 0     On rare occasions  a fan motor fails or a condenser  becomes blocked  causing the discharge pressure to rise  to an unacceptable level  thus endangering the entire re     11 2 11 Group 1 Variable Speed Set Points          GRP1 VARIABLE SPEED       SETPOINTS       VS MINIMUM SPEED   VS MAXIMUM SPEED   MAX INCREASE RATE     rpm  rpm  rpm                      MAX DECREASE RATE   Altern  Strategy     T PREV              gt  5                          rpm    on Failure                      set points for variable speed compressor operation  are established in the Variable Speed Setpoints screens   The default settings are appropriate for most common com   pressors  To verify variable speed set points  refer to the  compressor user s manual  Screens for Groups 2  3  and 4  are accessed by pressing the down arrow     VS Minimum Speed  0   9999   0900     The VS Minimum Speed is the minimum rated speed at  which the compressor may operate     VS Maximum Speed  0   9999   1800     The VS Maximum Speed is the maximum rated speed  at which the compressor may operate     Max Increase Rate  0   9999   2000     The Maximum Increase Rate is the maximum rate at  which the speed of the compressor may be increased     11 8   Main Menu    frigeration system  The Trip Point is the pressure at  which all compressors are shut down     Trip Delay  0   240 seconds   5     The Trip Delay is the specified measure of time
264. initialized into the system at the Board Circuit As   signment screen  After initialization  boards are assigned to  a Case Control Circuit at the Board Circuit Assignment  screen   0   48      Initialization    Pressing          from this screen starts the Initialization  command  The Initialization command scans the network  for all boards connected to the circuit  The status of all  boards found is returned to the Board Circuit Assignment  screen  An asterisk         indicates the board was found and  it is currently on line  A dash         indicates the board is lost   When a board is lost  the system knows it is connected   however  the board cannot be located  If there is no indica   tion next to the board  the board is not connected  If a board  is lost or is not connected  confirm that the boards have  been set up properly     11 4 53 Board Point Assignment    Refer to the description of Circuit Inputs Setup on Sec   tion 11 4 22  Circuit Inputs Setup or Circuit Outputs Setup  on Section 11 4 23  Circuit Output Setup       USER FUNCTIONS     Backup          001 Setpoints   Restore           001 Setpoints   Copy CCB  8001 Setpts to  8001   Copy         4001 Logpts to  ALL              ALL Circuits   CCBs                                                                     gt  SET DATA    RMCC I amp O Manual          To cancel the initialization command  press any key   The RMCC will return all information gathered prior to the  cancellation of the command      U pdate  
265. int to either reduce or increase the  case temperature  If the temperature continues to remain  outside of the range for a user defined period of time  the  RMCC continues to make pressure set point adjustments  until the temperature is within the established range     By varying the suction pressure set point to match the  temperature requirements of the circuit  the RMCC is able  to ensure product integrity while achieving maximum rack  efficiency          nu mE    The RMCC is capable of controlling up to 12 condenser  fan stages including changes to normal condenser opera   tion based on abnormal system conditions or special sys   tem requirements  The RMCC can control both air cooled  and evaporative condensers with either single   two   or  variable speed fans     9 5 1  Control Strategies    9 5 1 1  Air Cooled Condensers    The RMCC may employ either of two strategies to con   trol air cooled condensers  the Air Cooled strategy or the  Temperature Differential strategy     Air Cooled Strategy    The Air Cooled strategy simply controls condenser fan  operation based on a single pressure or temperature value  from either the condenser inlet  the condenser outlet  or the  discharge line  The Air Cooled strategy activates fans in or   der to keep this pressure or temperature below the set point   see Section 9 5 2   Fan Control  for details      9 4   Condenser Control       Temp Differential Strategy    The Temperature Differential strategy attempts to keep  a maximum dis
266. into the other sensor values or  ignored entirely  In either case  Fast Recovery would not  properly react to high pressures  If either of these strategies  are being used  it is recommended that the Maximum strat   egy be used for the Fast Recovery strategy     9 5 5 2  Discharge Unsplit  Single Speed Fans  only     The RMCC will bring a condenser out of split if the sys   tem pressure rises to a user definable unsplit pressure set  point     9 5 5 3  Discharge Trip    If the system pressure continues to rise after all other  failsafes have been initiated  the RMCC will shut down all  compressors when the user definable discharge trip set  point is reached     9 6     The RMCC provides standard defrost and refrigeration  control of up to 48 separate circuits  Information on circuit  control using case controllers may be found in Section 5   Case Control     9 6 1  Refrigeration    Refrigeration control of a standard circuit involves ac   tuation of the refrigeration liquid line solenoid  The RMCC  provides two methods for controlling the solenoid  full and  EPR     Circuit Control    When Full control is selected  the          pulses  opens  and closes  the solenoid based on whether the temperature  within the circuit is above or below the circuit set point  In  addition  the RMCC closes the liquid line solenoid when   ever defrost is initiated     When EPR control is selected  the RMCC opens the  valve when the system is not in defrost  This allows the  temperature in the c
267. ion     Drain Time 9 7    Drip Time  See Drain Time    EPR 9 6    F    Fast Recovery Hysteresis Setpoint  Removed From Condenser  Setpoints Screen 2 11 17    Fast Recovery  See Condenser  fast  recovery     Fincor Inverters    dip switches 5 2  wiring 5 2    G    Graphs 12 3    Guide for System Configuration 10 1  Define Inputs 10 2    H    Hand Held Terminal  defined 2 6  features 2 6  programming 15 1 15 10  CPC suction stepper 15 7   15 8  Hussmann suction stepper  15 9 15 10  liquid pulse 15 2 15 4  liquid stepper 15 4 15 6  Heat Reclaim  See Reclaim   HHT  See Hand Held Terminal     Host Network  See   5485 Host Bus  Network     Hussmann 15 9    Hussmann PROTOCOL      advanced defrost 11 31  electric 11 32  hot gas 11 31  defining compressor amp ratings    l       Control 9 8   9 17    Index     1 3    Analog Input Module 9 9 9 12  cells 9 11  Analog Value Combin   er 9 11  Counter 9 11  Cut In Cut Out 9 11  Filter 9 11  Limiter 9 11  Override 9 11  Process Alarm 9 11  inputs 9 10  Alarm Disable 9 10  9         Alt Combiner 9 10  9   11   Notice Disable 9 10  9   11    Occupied 9 11   Reset Count 9 10  9 12   Suspend Count 9 10  9   12    overriding 9 11  Analog Output Module 9 14   9   17    cells 9 15  Filter 9 16  Override 9 16  PID Control 9 16  Select 9 15  Sequencer 9 17  Setpoint Float 9 16  fallback set points 9 16  floating set points 9 16  inputs 9 15  Control Value 9 15  9   16    Direct Acting 9 15  Float 9 15  9 16  Occupied 9 15  Occupied Setpoint 9   15  9
268. ion Type field  This type determines the status of the  system after defrost is terminated  Users may choose from  the following Termination Types        N ormal   when defrost is terminated  the RMCC  will prevent refrigerant from entering the coil for  the duration specified in the Drain Time field  see  Section 11 4 18  Circuit Set Points 1   The RMCC  will then resume refrigeration        P ulsed   the circuit will remain in defrost mode for  the defined Defrost Duration  If during this time a  termination is called for by either the Stat or Temp  Termination strategies  the RMCC will remain in  defrost and pulse the defrost heat on and off in an ef   fort to keep the case temperature within the range of  the Termination Temperature s dead band  defined  in Section 11 4 18  Circuit Set Points 1   The  RMCC will shut off defrost heat when the case tem   perature exceeds the defined Termination Tempera     026 1102 Rev 4 08 12 99    ture s dead band and reactivate if the temperature  falls below the Termination Temperature dead  band     When the defrost duration is over  the RMCC will  prevent refrigerant from entering the coil for the du   ration specified in the Drain Time field  see Section  11 4 18  Circuit Set Points 1   The RMCC will then  resume normal refrigeration       Termination Sensors  0   6   0     Each standard circuit may be configured with up to six  Termination Sensors  Enter the number of sensors within  the selected circuit in the   Termination Sensors
269. ion of the Output  Range is applied to the final PID Setpoint  For the example  shown in Figure 9 14  a Setpt Float cell is set with a High  Float Value of 100  a Low Float Value of 0  and an Output  Range of 4  Consequently  when the Float Control input is  at 100  the PID Setpoint is modified by  2  When the Float  Control is 0  the PID set point is modified  2  For all Float    9 16   Input Output Control       Control values in between the Low and High values  the  PID set point modification varies linearly     Float PID  Control Setpoint  100 E gt   2       Occ Unoc SP   from Select cell     PID Setpoint    Float Control                High Float Value 100__        Low Float Value 0             Output Range 4       Figure 9 14   Example of a Setpt Float cell    The output value of the Setpt Float cell is the final PID  Setpoint value that will be used by the PID Control cell     PID Control    The PID Control cell uses a PID algorithm  see Section  9 1   PID Control  to compare the Control Value with the  PID Setpoint values  From this comparison  an analog out   put representing a 0    100  data range is generated  The  PID control cell repeats this command sequence in a con   stant loop every few seconds     The 0    100  output from the PID Control cell is  passed along to the Filter cell  Users have the option of by   passing PID altogether  in which case the Control Value is  passed unaltered to the Filter cell     Filter    The Filter cell   s primary function is t
270. ional compressor status line  Condenser fan  status must then be viewed at the condenser status screen     The operating status of each defined compressor is  shown directly below the appropriate number  Four differ   ent operating states may be displayed in these fields     ON   The compressor is currently on   4     The compressor is currently off     e           The compressor is on because of a manual  bypass     e       The compressor is off because of a manual by   pass     Fans    The bottom two lines of the display show the operating  status of the condenser fans  When a fan is has been config   ured in the output definitions screens  an    F    appears next  to the fan number on the RMCC Group Status screen  Ei   ther of four operating states may be displayed below the fan  numbers       ON   The fan is currently on   e     The fan is currently off   e   ON   The fan is on because of a manual bypass     e      The fan is off because of a manual bypass     026 1102 Rev 4 08 12 99    13 2 2  Input Status       NPUT STATUS  1 SUC PRES    The Input Status screen displays the current status of all  inputs connected to the 16AI or 8IO board and pro   grammed within the RMCC  Each status display is based  on the sensor type  For linear sensors  the status screen dis   plays the actual or raw value of the sensor in millivolts re   gardless of any offsets that may be in place     13 2 3  Variable Speed Status       E SPEED STATUS  RP1 RP   coo coo   0 0  0    The status of al
271. ircuit to be maintained by a mechanical  EPR valve or other regulating device  The RMCC closes  the liquid line solenoid whenever defrost is initiated     026 1102 Rev 4 08 12 99    9 6 2     The RMCC provides control for four defrost types  hot  gas  off cycle  electric  and reverse air  If hot gas defrost is  configured  the RMCC closes the liquid line solenoid   switches the master liquid line solenoid to divert hot gas  from the condenser to the circuit  and opens a defrost sole   noid which allows hot gas to flow through the evaporator   If electric defrost is selected  the RMCC closes the liquid  line solenoid  and energizes a relay for electric heat  If off   cycle or reverse air defrost is selected  the RMCC only  closes the liquid line solenoid     Defrost    For each defrost type  the RMCC uses a user defined  defrost schedule to determine when to shift the system from  refrigeration to defrost  This schedule is defined at the Cir   cuit Set points screen  see Section 7 5 24   Circuit Set  Points 1      When a defrost time is reached  the          closes the  liquid line solenoid valve and either opens a defrost sole   noid valve  activates a relay  or sits idle for a specified pe   riod depending on the defrost option selected by the user   Defrost may be ended by either defrost duration  termina   tion temperature  contact closure  or change of state from a  thermostat  All options are user configurable  Defrost may  also be ended by bypassing the system on     9 
272. isplayed in the Fixed Steps Strategy Menu     The Fixed Step Strategy for each suction group is con   figured at the Group 1   4 Strategy Setup screens  The  Fixed Step Strategy must be defined at the Group 1   4  Pressure Set Points screens  see Section 11 2 10  Group 1  Pressure Set Points  for the RMCC to cycle the compres   sors according to the strategy configured at the Strategy  Setup screens     Displayed across the top of the screen are the defined  compressors and unloaders within the suction group  Dis   played down the left hand side of the screen are all of the  possible stages the group may have according to the avail   able combinations of compressors and unloaders  This cal   culated amount is also displayed in the Max Number of  Steps for This group field at the Help Screen     It is recommended that all compressors be configured  OFF in the first stage of the strategy  For the remaining  stages  select the appropriate compressors or unloaders to  be activated by entering their appropriate compressor or  unloader number in the stage fields     11 3  Condenser Control       CONDENSER MENU    1 Status    4 Run Times                5 Bypass    p  3 Setpoints    SELECT NUMBER    11 3 1  Condenser Setup       CONDENSER SETUP       Control Strategy  AIR COOLED             Control Source  DISCHARGE              PRESSURE  SINGLE SPEED             Input Type  Condenser Fan Type             T PREV               gt  SET DATA O MENU    Condenser characteristics that dete
273. ix B     The Sensor Type is the specific type of sensor to be read  by the RMCC  There are 17 sensor types available  The  sensor type should be defined according to the physical in   put connected to the 16AT board  To assign a type to a spec   ified sensor  choose the appropriate type by scrolling    through the list of types using the         and         keys  The sen   sor types listed in Table 11 4     input Type    LiqLvl Float Type Liquid Level Transducer  does  NOT include liquid level probe   this must  be set up as a linear sensor   see Appendix  B     Digit    RelHum Humidity Sensor    Non voltage Digital Sensor    Linear  KWatt  DewPnt  6450Tm    Table 11 4   Input Types    System Navigation     11 45    IRLDS Infrared Leak Detector    Temp2Press Refrigerant temperature converted to pres   sure    Pres2Temp 100 Ib  refrigerant pressure transducer con   verted to temperature     2Pres2Temp 200 Ib  refrigerant pressure transducer con   verted to temperature   5Pres2Temp 500 Ib  refrigerant pressure transducer con   verted to temperature    Table 11 4   Input Types       Refrigerant Type  options   R502     When the Temp2Press  1 Pres2Temp  2Pres2Temp  and  5Pres2Temp sensor types are chosen  the Refrigerant Type  field appears  These sensor types require a refrigerant type  to be specified so that the RMCC can convert refrigerant  temperatures to pressures or vice versa     To select a refrigerant type  scroll through the list of re   frigerants using the         an
274. k   the coil out fan lockout temperature set point  See Section 11 4 36   CCB Set  Point Screen 4  Liquid Pulse and Stepper Only  for more information     Valve Filt   the valve filter percentage  See Section 5 3 1 2   Temperature Control  for more  information     Case Type   the case type number  See Section 11 4 16   Circuit Setup 1 for a complete list of         55 ype case types and their corresponding numbers  This may be changed using the HHT     Valve Mul Case     the CCB number     Bypass Viva Vlv Mul   the valve multiplier  See Section 11 4 37   CCB Set Points Screen 4  CPC Suction    Stepper Only  for more information   Byp Viv    the percentage at which the EEV will remain open during fail safe mode     Case Type   the four letter case type code  See Section 11 4 16   Circuit Setup 1 for a complete  table of codes     Rev   the software revision number     Status   the system is operating in either of five modes  refrigeration on  On   refrigeration off   Off   defrost on  MDfr   recovery mode  Rcvy   or override mode  Ovrd      Time   the current time  in 24 hour format      Disch Air   the current discharge air temperature reading    Setpt   the discharge air set point  This may be changed with the HHT    Case dF   the current case temperature in degrees Fahrenheit    Case Offset   the case temperature sensor offset  This may be changed with the HHT     Supht 1   the superheat of coil 1    Setpt   the superheat set point for coil 1    Valve 196   the current val
275. l 1  In sensor failure  enter  Y es in the Coil 1 In field     Coil 1 Out   Y es   N o   Y     To generate an alarm when the RMCC detects a Coil 1  Out sensor failure  enter  Y es in the Coil 1 Out field     Coil 2 In   Y es   N o   Y     To generate an alarm when the RMCC detects a Coil 2  In sensor failure  enter   Y es in the Coil 2 In field     Coil 2 Out   Y es   N o   Y     To generate an alarm when the RMCC detects a Coil 2  Out sensor failure  enter  Y es in the Coil 2 Out field     026 1102 Rev 4 08 12 99    Refr Leak   Y es   N o   N     To activate an alarm when a defined amount of refrig   erant is detected by a leak sensor  enter              in the Refr  Leak field     Leak Alm Lvl  0   100 ppm   100     The Leak Alarm Level is an amount of refrigerant that  when detected by a leak sensor activates an alarm  The  Leak Alarm Level is defined in parts per million     Leak Alm Dly  0   120 minutes   10     The Leak Alarm Delay is the specified measurement of  time the RMCC must wait before generating a Refrigerant  Leak Alarm after the specified amount of refrigerant has  been detected by a leak sensor     Bypassed Viv    0   100   30     The Bypassed Valve Percentage set point is defaulted    in the          to 30   It may be necessary to find the  optimum percentage by simulating a failure to test the  case s reaction     When the selected case is in a fail safe mode  see Sec   tion 5 3 1 10   Fail Safe Mode  Liquid Side Control  Only    the case controller opens
276. l anti sweat heaters connected to the PMAC   s 8DO  must be given board and point addresses in the Input  Definition screen  Section 11 8 1       ON OFF Interval  1   240 sec    10 sec      The 8DO on the PMAC panel pulses heaters ON for a  percentage of a defined time interval  This interval is en   tered in the ON OFF Interval field     Name  15 characters max     In the field to the right of the anti sweat heater number   a name may be entered     Dewpoint All OFF All ON   20     99     25   65       The Dewpoint      OFF set point is the minimum dew   point below which the anti sweat circuit s heaters will re   main OFF at all times  The Dewpoint All ON set point is  the maximum dewpoint above which the anti sweat cir   cuit s heaters will remain ON at all times  Between these  dewpoint values  the anti sweat circuit will pulse ON and  OFF for a percentage of the time interval defined in Sec   tion 11 5 1   Setup     Percent On During All OFF  0   30    0      By default  anti sweat circuits operate at 0  when the  dewpoint is below the Dewpoint All OFF set point  If de   sired  a lower value for All OFF may be specified     Percent On During All ON  70   100    100    By default  anti sweat circuits operate at 100  when    the dewpoint is above the Dewpoint All ON set point  If de   sired  a lower value for All ON may be specified     Name    The name defined for the anti sweat heater is shown in  the Name field next to the number     Screen Override    Users may order a
277. l variable speed compressors defined  within the RMCC are displayed at the Variable Speed Sta   tus screen  The first compressor within each suction group  may be defined as a variable speed compressor  If the dis   played suction group contains a variable speed compressor   the variable speed percentage and the current rpm reading  is displayed for that compressor in the Speed and RPM  fields respectively     13 2 4        Network Status  I O Board Sta   tus      5   04        0 Bus State   ON  Number O Line   O  123456789 012535456       8ROs  16AIs  4A0s  8DOs  CCBs    Total 0  Online 0             RMCC I amp O Manual             The I O Network Status screen displays the status of the  I O Network  No modifications to the network may be  made at this screen          Bus State    The status of the I O Network is displayed in the I O  Bus State field  This field reflects if the network is ON or  OFF  Modifications to this status may be made at the Reset  screen  see Section 11 8 22   Reset      Number Offline    The status of all boards connected to the I O Network  are displayed in the Number Off line field  A 1  under the  specified board indicates the board is on line  A period          under the specified board indicates the board is off line  A  space under the specified board indicates the board is not  defined within the system  The RMCC calculates the num   ber of defined boards currently off line and displays this  calculation in the Number Off line field     The I
278. larm NONE  Lo Delay 0000            gt  SET DATA    NOTICE  NONE  0000            0000    12 00                                    CUIT ASSIGNMENT 12 00 SELECT ITEM NCTIONS 12 00 CIRCUIT INPUTS SETUP SDIC O1c 12 00  Board          Ckt Name  Ckt Iype  CCB   01 81   01   Circuit number  1  1  CCB  001 Setpoints No Input Name  Humid    Ol ccB 1 01 901   01   SDIC 01 B Restore         001 Setpoints No Location  00 00    O2 SPARE 00 Undefined   99 Bicopy         001 Setpts to  001 No Log Interval  00 00 00  O3 SPARE 00 Undefined   99 E copy CCB  001 Logpts to ALL No Bypass  NONE  04 5         00 Undefined A 99 5           ALL Circuits CCBs No Sensor Type  RelHum  O5 SPARE 00 Undefined   99  Enter Item  Offset  0000 0    T PREV 4                      nit  U pd  S end                 Arrows to Move  ENT ac               SELECT ITEM    01           1    Enter Item   Arrows to Move                   12 00       CIRCUIT INPUTS SETUP SDIC 10c 12 00  Input Name  Case   Location    Log Interval  00 00 00  Bypass    Sensor Type    Offset    T PREV   NEXT    O MENU              LOGGING CCB O1SDIC O1c       Dischg Air 00 00 00  Return Air 00 00 00  Case Temp 00 00   Superheat 00   Valve Pent 00        T PREV J NEXT    SET DATA          Coil Out  Coil In             T PREV 4 NEXT   gt SET DATA    12 00       coi L oure      11     2   Superht 2  Valve Pct2               Refr Leak  T PREV 1              SET DATA    12 00       CIRCUIT OUTPUTS SETUP            Output Name         Location 00 00
279. larm Time 1 O00 hrs 7   Zoom out  Zoom in  ist Defrost NONE 4th Defrost NONE       Menu        Defrost NONE Sth Defrost           PLEASE WAIT Brd Defrost NONE 6th Defrost                    LSNEXT      gt  SET DATA          RXCGEDTIENENILHIS  FCIRCUIT SETPOINTS  1 12 00 o      0 mn 0 FCIRCUIT SETPOINTS  1 12 00   leaning Override Switch  None  Case Pump Down Delay   000 sec Cleaning Switch Type   Switched         Dual Tmp ALarm Set Point Shift  000 0 Cleaning Notice Enabled   No  Dual Temp Shift Input   None  lo         T PREV             gt  5              12 05 11 57 int 0 03 00     15 05 12 00 T PREV 1            gt  SET DATA  FCIRCUIT SETPOINTS  1 12 00    Demand Sensors   0  Demand Fail safe Time  000 hrs  Alarm Time   O00 hrs              4            gt  SET DATA   ANTI SWEAT STATUS 12 00  ANTI SWEAT SETUP 12 00    ANTI SWEAT SETPOINTS 12 00    ANTI SWEAT DAILY LOGS  0 of 48 12 00    ANTI SWEAT OVERRIDES 12 00  CIRCUIT SETPOINTS  1 12 00  DATE XON MAX D MIN DP Screen   Input         1 Dewpoint Status 1 Dewpoint Humidity Offsets Dewpoint   ALL OFF   25 0 00 00 000 00 0 00 0   Name Override   Time min case Pump Down Delay   000 sec  2 0utput Status 2 0utput Setup ALL ON   65 0 00 00 000 00 0 00 0 1  NORM   000 Dual Tmp Alarm Set Point Shift  000 0  00 00 000 00 0 00 0 2  NORM   000 Dual Temp Shift Input   None  Percent ON during ALL OFF   000 0 00 000 00 0 00 0 B  NORM   000  ALL ON   100 00 00 000 00 0 00 0 NORM 2 000  LECT NUMBE MBE   gt  SET DATA   ANTI SWEAT STATUS 7
280. lated control  value is displayed in the field directly below the Control  Using field     System Navigation     11 47    Gain   999   999   0     The value entered in the Gain field is multiplied with  the voltage from the sensor input to determine the sensor  control value  The correct gain for the IRLDS sensor is 1     Offset   9999   9999   0     If necessary  an offset may be applied to the sensor val   ue by entering a number in the Offset field  The number in  the Offset field will be added to the sensor value     Cut On Cut Off   999   999   N one   O pen    C losed     Sensor Cut On and Cut Off set points may be defined  as specific values for analog input sensors or simply as con     tact closed or contact open for digital input sensors in the  Cut On and Cut Off fields respectively  The Cut In set  point is the value at which the controlled output will turn on  and the Cut Out set point is the value at which the con   trolled output will turn off  There is a 1  dead band around  each set point     Cut On Cut Off Delay  0   9999 seconds     The Cut On and Cut Off Delays are specified measure   ments of time the RMCC must wait before activating or de   activating the controlled output     11 5 4  Set Points  for IRLDS sensor type only     IO               SENSOR SETPOINTS  4 01 Status OFF       IRLDS INPUT  Name   Eng Unit PPM  Curr        0  Offset  00000 mv         0000 s        10000 s     gt  SET    Curr VDC  O V  Gain    Cut ON  0  Cut OFF   0 PPM               
281. lay    Refr    when the circuit is op     11 44   Circuit Defrost Control       nally  enter              in the third Copy Set Points field to per   form the copy     Copy Log Points    Logging Intervals defined for one Case Controller are  copied to another or all Case Controller when the Copy Set  Points feature is activated  To activate this feature  enter the  ID Number of the source case in the first Copy Set Points  field and the ID Number of the target case in the second  Fi   nally  enter              in the third Copy Set Points field to per   form the copy     Make All Circuits CCBs    When this option is selected  all standard circuits are  designated as case control circuits     at the Anti Sweat Setup screen  Refer to the description of  Circuit Inputs Setup on Section 11 4 22  Circuit Inputs Set   up for information on the data fields     erating in refrigeration mode               when the circuit is  operating in defrost mode     Ovrd    when the circuit is being  manually overridden  or    Drip    when the circuit is in the  drain time period immediately following defrost termina   tion     Tmp    The average of all discharge air sensors in the circuit is  displayed in the Tmp field     Term    The current termination temperature sensor reading is  displayed in the Term field     A  Alarms     If there are any sensor  rack  or bypass failure alarms in   volving this circuit  the A field will display an asterisk  De   tails about the alarms may be found in th
282. le  and Pulse EEV Valve  and Appendix F  Wiring for Case Controller  Power  Module  Defrost Module  and Sporlan EEPR Valve     Wiring    Case Control Installation     7 5    8 Case Control Software  Overview    CPC s case controller supports both liquid side pulse  and stepper valves  and suction side stepper valves     The fundamental control algorithms and their associat   ed set points may be segregated into the following parts     1  Superheat control   control of the temperature dif   ferential of the coil  only applicable to liquid side  control   The CCB is capable of supporting two  pulse valves independently     2  Temperature control   regulation of the temperature  in the controlled space by monitoring either dis   charge or return air  This may be either liquid side  or suction side control     3  Pulse and stepper valve control     4  Defrost operation including pump down  drip  and  wait     5  Defrost recovery and system start up   6  Anti sweat control     7  Fan control     8  Light control   9  Wash mode     The following sections describe each of the control  components and their associated set points     8 1  Superheat Control  Liquid    Side Control Only     The case controller determines the valve percentage  opening by monitoring the temperature differential be   tween the coil inlet and outlet sensors and comparing that  value to the superheat set point  The set points necessary  for superheat control are shown in Table 8 1  Refrigerant  control may be
283. losure     The weather resistant enclosure is supplied with four  mounting holes on flanges at the top and bottom of the en   closure  These holes are accessible without access to the in   side of the enclosure  Figure 3 4 shows the enclosure  dimensions and weight  Figure 3 8 provides mounting di   mensions for the 8IO     026 1102 Rev 4 08 12 99           ENCLOSURE   REAR OF ENCLOSURE     WEIGHT  11 4 LB           26501012  Figure 3 4   Weather Resistant Enclosure    16Al  8RO  and 8DO Boards Without Enclosures  Mounting    16AL 8RO  and 8DO boards not supplied with an en   closure are supplied with a snap track for easy installation   The insulation sheet and I O board must be removed from  the track  and the track mounted using the 1875 inch  mounting slots  Figure 3 5 shows this installation proce     dure  Figure 3 6 provides mounting dimensions for the  16AI and 8RO board     RMCC I amp O Manual             1  REMOVE THE 16    OR 8RO BOARD  AND THE INSULATOR FROM THE  SNAP TRACK                 2  MOUNT THE SNAP TRACK USING  THE  1875  SLOTS PROVIDED                                            acoge repr PIS NUR             ages TOUS MAY AD  TENOR         NAY CAUSE SERIOUS  OMMAGE TO THE BOARD       3  REINSTALL THE INSULATOR  IN THE SNAP TRACK           4  REINSTALL THE 16    OR 8RO BOARD  IN THE SLOTS IN THE SNAP TRACK        26501040    Figure 3 5   4      8RO  or 16  1 Snap Track Installation                 10 00       4 75      T _TYP2PL   _          0 218   TYP 6
284. lowed by one of the com   mands below allows users to bypass the case lights     1 Auto   Pressing 1 will return the case lights to automatic operation   2 Turn Off   Pressing 2 will bypass the case lights off   3 Turn On   Pressing 3 will bypass the case lights on     Supht SP   the current superheat set point  This value may be changed using the HHT     Sens   the valve s sensitivity value  This may be changed using the HHT  See Section 5 3 1 3    Valve Control for a complete definition of sensitivity     RcvyLevel   This number is equal to the recovery valve percentage  see Section 11 4 29   CCB  Set Point Screen 1  Liquid Pulse and Stepper Only   divided by 10  This may be changed  using the HHT     MaxRcvy Sec   the maximum number of seconds the CCB will operate in recovery mode  This  number may be changed using the HHT    Disch Air   the current discharge air temperature reading    Offset   the discharge air temperature sensor offset  This may be changed with the HHT    Ret Air   the current return air temperature reading    Offset   the return air temperature sensor offset  This may be changed with the HHT     Status   the operational status of the refrigeration and defrost modes  Pressing RIGHT fol   lowed by one of the commands below allows users to manually override the case     1 Man Dfr   Pressing 1 initiates manual defrost   2 OV OFF   Pressing 2 overrides both refrigeration and defrost OFF   3 End Dfr OV   Pressing 3 will terminate defrost mode        RMCC I am
285. lues will be displayed in this  screen  They may be changed at this screen using the HHT     Step Hyst   the hysteresis value  See Section 11 4 38   CCB Stepper Set Points Screen  Stepper  Only  for a definition of hysteresis     Step Hz   the maximum number of steps per second the valve may open or close   Max Steps   the number of steps in between closed  0   and open  100       Control   the valve control type  This should read EEV  electronic expansion valve    Valve Type   the valve type  This should read Step  stepper      Valve Jmpr   whether the CCB s valve jumper is set for unipolar  UniP  or bipolar  BiPo  op   eration  See Section 5 3 1 3   Valve Control     Network   whether the host network is ON or OFF     CO Fan Lock   the coil out fan lockout temperature set point  See Section 11 4 36   CCB Set  Point Screen 4  Liquid Pulse and Stepper Only  for more information     Valve Filt   the valve filter percentage  See Section 5 3 1 2   Temperature Control  for more  information     Case Type   the case type number  See Section 11 4 16   Circuit Setup 1 for a complete list of  case types and their corresponding numbers  This may be changed using the HHT     Case     the CCB number     Vlv Mul   the valve multiplier  See Section 11 4 37   CCB Set Points Screen 4  CPC Suction  Stepper Only                Viv    the percentage at which the EEV will remain open during fail safe mode     15 6   Hand Held Terminal Screens 026 1102 Rev 4 08 12 99    15 3  CPC Suction Stepper
286. lve Multplier       Combine Type  Derivative Gain                  gt  SET DATA    Valv Multiplier  25   100   100     The Valve Multiplier is a value that allows the capacity  of the EEV to be reduced  The default setting is 100  and  should only be adjusted in special applications where the  valve appears to be oversized  To adjust the Valve Multi   plier  enter a value between 25 and 100  in the Valv Mul   tiplier field        Combine Type   A vg   M in  Ma X    A     The suction stepper uses four temperature sensors to  measure discharge air temperature  The RMCC must be  told how to combine these values into a single discharge air  temperature reading  Users may choose three different  combining methods        A VG   The RMCC uses the average of the sensors  to calculate discharge air temperature     e MKN           RMCC uses the lowest sensor reading  as the discharge air temperature     e MA X   The          uses the highest sensor reading  as the discharge air temperature     Derivative Gain  0   25   0     The derivative gain is a multiplier used by CCBs that  are operating valves using PID control  The larger the de   rivative gain  the greater the size of the Derivative mode s  reaction to rapid changes in the PID input  See Section  3 1 1   Programming PID  for more information on the de   rivative mode     11 4 38 CCB Stepper Set Points Screen  Stepper Only     23 22  3 85  Bien        STEPPER STPTS CCBH O1SDIC O1c 12 00    Valve Type UniPolar Stepper  Hysteresis
287. ly  the RMCC  Alarm Log displays all problems occurring in the RMCC at  any given time     The RMCC Alarm Log displays all notices and alarms  generated within the RMCC  Alarms are displayed in order  of occurrence with the most current alarm at the top of the  first page  A notice is a low level warning that signifies an  abnormal facility or control system condition  A notice cre   ates an entry in the RMCC Alarm Log and initiates no other  signal       alarm is a high level warning that also signifies  abnormal facility or control system conditions  An alarm  appears in the RMCC Alarm Log and may be accompanied    14 4   Alarms    Condenser VS Inv Fail  Defr Timed  Demand Tim   eOut  Dialout Unsuccessful  Dig  Alarm Override  ON  Fan Proof  FP Level   999   Login  High Speed  Proof  Hi Humidity  Hi Term  In Override  Inverter  Fail  Lo Suction  Lo Xducer  Low Humidity  Low  Speed Proof  Low Temp  Low Term  Manual Alarm  Ovrride ON  Manual Defr  Manual Term  Ovrd Ac   tive  Ovrrd  Phase Fail  Phase Restored  Power  Failed  Power Restored  Proof Fan   99    Proof  Failure  Pump Down  RM Level   999   Login  Re   set  Run Proof  Sensor Open  Sensor Short  Set   points Corrupted  Setpoint Restore Error  Xducer  Open  Xducer Short  alarms     The Miscellaneous alarm type also includes all Hi  and Lo alarms generated by Analog Input Modules     by a contact closure for on site operation of a bell  light  or  other notification device  Alarms may also be accompanied  by an alarm 
288. mber 4A0 Boards MAX 1  NOW 0   DST MANUAL SET END 10 25 92    gt  SET DATA  SYSTEM UNITS 12 00 12 00 12 00  Temperature Unit  Deg F HOST NETWORK 1 0 BOARD NETWORK  Pressure Unit PSI 1  OFF 2  Reset CON  1  OFF 2  Reset CON  Date Format Month Day  1 PREV_J NEXT   gt  SET DATA     DIALOUT SETUP    12 00  Change Baud Rate when dial to 9600  NO  Day Phones  di  21  Night Phones 1   Use From NONE to NONE   Sat N  Sun N  H PREV 1            gt  SET DATA    LOGGING SETUP   12 00  F Select Configuration Type  D  Fuse Hourly Log Space        logs points   i No Hourly  0  1365  1  0920 819 10  2   256   682 12  UsediO 7  H PREV I NEXT   gt  SET DATA  GRAPHS 72 00  1 Suction Groups 5 Comp  Runtimes  2 Sensors 6 Fans  Runtimes  3 Circuits  2 6  SELECT NUMBE    SELECT            12 00   SELECT ITEM   12 00   SELECT ITEM 12 00 q SELECT            12 00 1 1 ALARMS   1 of 129 12 00   71 DISCHARGE D1 AMBIENT TEMP      MbFJ 01 lo1 CCB  01 H   Date Time Description  D2 GROUP  1 2 E 007 0       GROUP 42 E    00 0  8 8  pa 2 B  Enter Item  Enter Item  Enter Item  of 01 D  CLR EERDE NEED                1234567891011 12 135 14 15 1234567891011 12 13 14 15 HEPUNSIPEDESUPDTS    SELECT            12 00 GRAPH CONTROLS   SELECT ITEM   12 00   SELECT            12 00  D1 G1 SUC PRS 01 MDFJ 01 TMP D1 OTCCBOTDschAir      61 SUC TMP   gt   lt   Scroll 02 MDFJ 01 CSW 02 OTCCBOTRtrnAir       Go to current  Z   Zoom out  Zoom            Menu  PLEASE WAIT    a aE ows 10 accept  CLR Escape ows to Move t  CLR  Es
289. mode after reaching the Discharge Unsplit Pressure     Equalize Runtimes   Y es   N o   N     The real time clock within the RMCC records the cu   mulative runtimes of each condenser fan  The RMCC may  be configured to select condenser fans for operation based  on which fans have the fewest operational hours by select   ing    Y     for Yes in the Equalize Runtimes field     To prevent condenser damage  condenser manufactur   ers recommend that condenser fan cycles should be config   ured so that the fans closest to the condenser manifold  always cycle on first  These fans will not always cycle on  first when runtimes are equalized     11 3 5 3  Condenser Fan Fail Setup    62 021      CONDENSER FAN FAIL SETUP  Fan Fail Enable   NO   Fan Fail Delay 10005           Continually try to Clear                    0  Num Clear Attempts    Delay Between Clear Attempts 0030 sec                T PREV 4            gt  SET DATA    Fan Fail Enable   Y es   N o   N     When the Fan Fail Enable field is set to YES  the  RMCC will check for condenser fan failure by monitoring    System Navigation     11 13    the condenser fan proof inputs  see Input Definitions on  Section 11 8 1  Input Definitions      Fan Fail Delay  0   3600 sec    5 sec      If a fan proof indicates a fan failure for a duration equal  to the Fan Fail Delay  the RMCC will consider that fan to  have failed     Continually try to Clear Failure   Y es   N o   N     When this field is set to YES  the RMCC will automat   icall
290. mostatic  control of refrigerant supply to the coil  If the case temper   ature is satisfied  no refrigerant is allowed to flow  If the  case temperature is too high  refrigerant is allowed to flow   and is then regulated by the superheat control algorithm     Temperature Control    The method of determining case temperature is selected  as a set point  and may be supplied by a single sensor or a    RMCC I amp O Manual       combination of the return air and discharge air sensors us   ing the            Dsch  set point shown in Table 8 2     Liquid side control uses superheat control  discussed  earlier  while refrigerant is being supplied  If the case tem   perature is greater than the desired set point    gt  dead band  the coil control algorithm is invoked and refrigerant is al   lowed to flow  The refrigerant flow will be stopped when  the case temperature is less than the desired set point   1   2  dead band     Valve Filter    At times  the EEV may react too quickly to the control  commands supplied by the CCB  To compensate  the CCB  may be programmed with a valve filter value  The change    Case Control Software Overview   8 1    in valve opening or closing called for by the RMCC during  each six second control loop is automatically multiplied by  the valve filter percentage  resulting in a smaller adjust   ment to the EEV     For example  if the RMCC ordered an EEV to open    would open to 60  at the end of the six second control  loop  An EEV with a filter rating of
291. mpres   sor will return to normal operation     Copeland Oil System   Y es   N o   N     Enabling the Copeland Oil System for a compressor    group disables Oil Sensor monitoring that may be set  up for individual compressors  see Section 11 2 7    Group 1 Setup      The Copeland Oil System allows the RMCC to take  samples of oil input from a compressor and determine low    11 4   Main Menu    oil levels by building a percentage of good versus bad read   ings     The Copeland Oil System takes a number of pressure  readings during a user defined time window  0   120 sec     If during this window the oil readings are 10096 good  the  compressor operates as normal  If the readings are below  100  good  the          sets up a    time out period     the  length of which is dependent on the percentage value  low   er percentages generate a smaller time out period than  higher percentages   If the percentage of bad oil readings  continues throughout the length of the time out period  the  compressor will bypass OFF and an alarm will be written  to the RMCC Alarm Log  Table 11 2 shows the percentag   es and their corresponding time out periods    If the percentage of good readings changes during a  time out  the time out period will change  and the percent   age of time elapsed will be applied to the new time out pe   riod  For example  if a compressor had 6096 good readings   the time out period would be twelve minutes  Six minutes  into the time period  the percentage of good readi
292. n  A timed override remains in effect until a  user specified time period elapses or until the user cancels  the override     The output from the Override cell is the final Analog  PID PWM Loop Output  This value is also sent to the Se   quencer and PWM cells     Sequencer    The Sequencer cell simply activates a certain percent   age of the Digital Stage 1 8 Outputs based on the percent   age of the PID output  For example  if the PID output is  50   the Sequencer cell will activate 50  of the total de   fined outputs  The Sequencer cell always rounds the PID  value down  in other words  if there are four stages defined  in a Sequencer cell and the output is 74   the Sequencer  cell will treat the output value as 50  and only activate two  stages  If the output then climbed above 75   however  a  third stage would come on     If desired  delays may be specified for stage activation  and deactivation  Also  the definitions of ON and OFF may  be defined as either ON  OFF  or NONE  In other words   when the Sequencer cell calls for an output to be ON or  OFF  the actual output can be configured to be NONE   OFF  ON NONE  or even OFF ON     PWM    The PWM cell  short for Pulse Width Modulation  con   verts the PID output percentage to a periodic ON pulse  The  period of time over which the pulse takes place is called the  Output Time  The PWM cell turns the PWM output ON for  a percentage of the Output Time equal to the PID percent   age  For example  if the PID output is 60  an
293. n 11 4 48  Circuit Set Points 3  Add Edit  Circuit       11 4 30 CCB Set Points Screen 1  CPC Suction Stepper Only        D E    ESI 52  NS E we                       CCB SETPOINTS CCB 01 SDIC O1c  Revision  6        Sensitivity  Update Rate  Asw Hi Limit    Asw Lo Limit    Frost Sensor      T PREV J NEXT                                 gt  SET DATA    RMCC I amp O Manual       Using this screen  users may set up valve sensitivity   update rate  anti sweat heaters  and demand defrost sensors  for suction stepper CCBs     Sensitivity  0   9   4     Sensitivity is a value that either increases or decreases  the reaction of the suction stepper to case temperature  changes  The lower the sensitivity  the slower the reaction  time  the higher the sensitivity  the faster the reaction time   For a more detailed explanation of sensitivity  see Section  6  Case Control     System Navigation     11 33    Update Rate  1   60   6     The Update Rate is the number of seconds it takes for  the suction valve to complete a single control loop  Lower  update rate values will cause the valve to react faster to case  temperature changes  while high update rate values will  slow the valve s reaction time  The default value  six sec   onds  should be a sufficient update rate for nearly all cases   however  if the case temperature is fluctuating because the  valve is overreacting to temperature changes  a higher up   date rate might be necessary     Asw Hi Limit  25   100   60 0  Asw Lo Limit  0  
294. n any value between  24 V AC OM FM  POWER 1 and 31  however  network restrictions limit the actual  SUPPLY number of boards that may reside on both the COM A and    COM D networks at one time  These restrictions are given  in Section 4 7   Number of Devices per Segment  Use Fig   ure 5 13 to determine the switch settings for 16AI  8RO   and 8RO FC boards                    If a pulse type input is connected to a 16AI Board with  software older than version E 02  it must be connected to  input one and rocker number eight on the board   s network    dip switch must be configured ON or in the up position   EARTH GROUND    OR    24 VAC  POWER  SUPPLY                                                                                                                                                                                                                                        EARTH GROUND 26513097       Figure 5 13   Network Address Settings for Dip Switch S1 or S3  on I O Boards    Figure 5 12 One 8IO Wired to a 24 V AC Line with a Ground on  Either Side    5 10  Network Settings 026 1102 Rev 4 08 12 99    Rotary Dials on 810 Board    The 8IO board uses rotary dials to set the network ad   dress in lieu of dip switches  The rotary dial S1 is used to  define the output portion of the board  Therefore  the board  may only be defined as board one through nine Likewise   dial S2 is used to define the input portion of the board and  may be set from one to nine  Do not select the    
295. nalog    RMCC I amp O Manual          Value    The current sensor reading is shown in the Value field                The      and CO fields display the cut in and cut out set  points respectively  When the sensor value rises above the  cut in value  the sensor s controlled output will activate   When the sensor value falls below the cut out value  the  controlled output will deactivate     sor  and if currently in override mode  the time remaining  in the override duration       Name    The   and Name fields display the sensor number and  the sensor name respectively     Ovrd    The Ovrd field displays the number of the alarm over   ride input assigned to each sensor     St  The St field displays the operational status  either ON    or OFF  of the alarm override for each sensor   Type  The Type field shows whether the alarm override is  fixed or timed for each sensor   Time    For timed overrides  the amount of time remaining in  the override duration is shown in the Time field     values  while the Command  Alarm  Notice  and Count  Tripped inputs will appear as either OFF  ON  or NONE     To view the status of other Analog Input Modules   press the UP and DOWN arrow keys     13 7 2  Analog Output Module Status    ANALOG OUTPUT MODULE  Name        INPUT  PID Output     PID Setpt   PWM Output         1 STATUS  01    Stages          T PREV                 System Navigation     13 9    Users may view the real time status of an Analog Out   put Module s outputs in the Analog Out
296. nals 1 and 2 are the invert   er s emergency stop  E STOP  contacts   When this connection is open  the inverter  will be overridden off  If desired  terminals 1  and 2 may be wired to a normally closed 8RO  relay so that the RMCC may be configured to  stop the inverter when necessary  Otherwise   place a jumper between these terminals     5 2   COM C Wiring          2  Jumper 3 to 9   Place a jumper between ter   minals 3 and 9     3  Inverter Reset Setup        allow the RMCC to  automatically reset the inverter  connect ter   minal 9 to one contact of the defined INV x   RESET relay  where X equals the group  number of the compressor   Connect the oth   er contact to the compressor relay  see step  4   The INV RESET relay must be set up in  the system software  see Section 7 9 2   Out   put Definitions      4  Compressor Relay   Connect terminals 7 and  12 to one contact of the defined CMP xx  re   lay  where XX equals the compressor num   ber   Connect the other contact of the relay to  the VS Alarm relay  see step 4   The CMP re   lay must be set up in the system software  see  Section 7 9 2   Output Definitions      5  4     Analog Output      0 10 VDC signal  from a 4AO board determines the RPM of the  variable speed compressor  Wire the positive  terminal of this 4AO point to terminal 27 on  the inverter s contact strips  Wire the nega   tive terminal to terminal 24  The 4AO board  and point address must be set up as a vari   able speed compressor output  VS COMP 1   
297. nce a category has been selected  the user must also  specify an instance for graphing within the category  Select  a category from the menu and then select the instance from  the list     RMCC I amp O Manual       GRAPH CONTROLS      gt   lt   Scroll        Go to current   Z   Zoom out  Zoom in  0   Menu      PLEASE WAIT       Make Selection       The Control Screen is displayed while a graph is com   piling  The screen displays the controls for viewing a graph  such as scrolling  zooming  and exiting to the main menu     12 2 2  Graph View             int 0 03 00    5 0 0             The View Graph screen displays the requested com   piled graph  Viewing controls such as scrolling  zooming   and exiting to the main menu are active in this screen     System Navigation     12 3    13 Status Screens    Status screens display current information about the RMCC and Case Control system  Users may view information such  as the status of alarms  inputs outputs  and board communication     13 1  Main Status Screen       12 00  0  0           05 06 07 08      3  4  5  6  7  8  9  10  11  12    ENT LogOn   lt   gt Scroll         1 2 10       The Main Status screen may be accessed without log   ging into the system  After the unit is turned on  the unit  goes through a software check  then the main status screen  is displayed  From this screen  the arrow keys allow users  to scroll through additional RMCC status screens to view  current information about specific components within the 
298. ndenser     Hi Sens The high alarm value for a sensor defined as any type other than    1        2        5     or  H  has been ex   ceeded for the user defined alarm delay duration  see Section 14 4  Sensor Alarm Setpoints      Hi Suction The measured suction pressure has risen above the user defined High Suction set point for a duration  exceeding the high suction delay  see Section 11 2 3   Group 1 Pressure Alarms Setup         Table 14 1   RMCC Alarm Log Notice and Alarm Messages    RMCC I amp O Manual System Navigation     14 5    Notice Alarm Description  Message   Hi Temp The high alarm value for an input defined as a circuit temperature sensor  01 TEMP     48 TEMP     see Section 11 8 1   Input Definitions  has been exceeded for the user defined alarm delay duration   see Section 11 4 12   Alarm Set Points    Hi Term The high alarm value for an input defined as a circuit defrost termination sensor  01 TEMP     48  TEMP    see Section 11 8 1   Input Definitions  has been exceeded for the user defined alarm delay  duration see Section 11 4 12   Alarm Set Points    Hi Xducer The high alarm value for a sensor defined as either    1        2     or    5    has been exceeded for the user   defined alarm delay duration  see Section 14 4   Sensor Alarm Setpoints     Host Bus Network Down The RMCC cannot connect to the 485 Alarm box or to other REFLECS controllers on the Host Bus  COM B network    In Override A manual override has been initiated at the Manual Defrost screen  s
299. ngs drops  to 3096  This immediately changes the time out period  from 12 minutes to 5 minutes  Since six of the twelve min   utes in the previous time out period  i e  50  of the time   had already passed  the RMCC continues with the new  time out period as if 2 5 minutes  50  of the new period   has already elapsed     Table 11 2   Copeland Oil Time Out Periods vs  Percentages       026 1102 Rev 4 08 12 99    11 2 4  Pressure Alarms Notices Setup                        PRESSURE ALARMS NOTICES SETUP  GP1 GP2 GP3       Suction A A  Discharge  A    Pump Down  A A  A    N                                 Oil Fail  Phase  T PREV J NEXT                 gt  SET DATA    The RMCC may be configured to generate either an  alarm or notice when user defined Alarm set point condi   tions are met  An alarm is a high level warning that indi     11 2 5  Checkit Sensor Setup     CheckIt SENSOR SETUP   Alarm Setpoints  150  Notice Setpoint  155  Disabled During Hot Gas   Disabled During Reclaim                                                       gt  SET DATA    If a Checkit sensor is defined as an input at the Input  Definitions screen  see Section 11 8 1  Input Definitions    the RMCC may be configured to generate an alarm when  the input senses a low liquid level within the system at the  Checkit Sensor Setup screen     Alarm Setpoint Notice Setpoint  0   240   150 135     The Checkit sensor continuously monitors the refriger   ation system for a temperature increase indicating low liq    
300. nic expansion  valve is provided  If a second valve is used  a valve relay  must be installed as shown in Figure 6 1         10  Wiring  for these connections is shown in Figure 7 2     Optional Inputs and Outputs    PULSE CASE CONTROLLER   BASE PLATE REMOVED     DOOR   FROST SENSOR  SWITCH 2 9     gt   o m     2    EE    CHANGE TODEMAND 1 2 3 4  OF SENSOR TO SENSOR  STATE ELEMENT    DETAIL       LEAK SENSOR TO SECOND   5 VALVE  24              E       ap   SOS      1  AC1     2  VALVE 2                D        o  1       DETAIL     26502004    Figure 7 2   Case Controller Optional Inputs and Outputs  Wiring    026 1102 Rev 4 08 12 99    7 6     7 6 1     CPC s case controller input cable harness  335 3151  is  designed for use with either a pulse or stepper valve case  controller  The connector is constructed with 18 AWG col   or coded wire with a male end  20 pin connector for con   nection to the case controller  Female connectors are  supplied for each of the sensors and wire leads are supplied  for an optional suction valve and the RS485 network  The  schematic diagram for the cable is shown in Figure 7 3     Cable Harnesses  Input Cable          COIL IN             CASE  CONTROLLER  BLUE  BLUE             COIL OUT                                  DISCHARGE AIR          GREEN  GREEN  PURPLE  PURPLE  BLUE WHITE  BLUE WHITE  RED WHITE  RED WHITE  ORANGE  ORANGE  GRAY  GRAY BLACK  RED   WHITE  BLACK                RETURN AIR                               COIL 2 IN          
301. nication modem   6  Network wiring  7  Sensors and loads    The following sections provide an overview of the  function of each of these components  A more detailed ex   amination of the installation and configuration of these  components for actual in store operation is provided in  Section 3  Hardware Mounting     2 1  REFLECS Controllers    The    brain    of any CPC network is the REFLECS con   troller  REFLECS is an acronym for  REF rigeration    L ighting  and  E nvironmental  C ontrol  S ystem  The  following list categorizes the current REFLECS line of  controllers     Refrigeration Control         Refrigeration Monitor and Control  RMC     Refrigeration Monitor and Case Control  RMCC     Environmental Control         Refrigeration Monitor and Case Control  RMCC     Building Control Unit  BCU      Building Environmental Control  BEC      Store Environmental Control  SEC    Data Logging      ntelligent Data Logger  IDL     CPC REFLECS controllers are designed to perform  three specific tasks  system control  system monitoring   and data storage  Each controller    depending      its soft     RMCC I amp O Manual    ware package   is tailored to perform one or all of these  three tasks     2 1 1  Refrigeration Monitor and Case  Control  RMCC     The Refrigeration Monitor and Case Control primarily  interacts with refrigeration system components including  compressors  condensers  and refrigerated cases  In addi   tion  the RMCC provides extensive sensor control and log  
302. nications  Operation of this equipment in a residential area is likely to cause harmful interference in which case correc   tion of the interference will be at the user   s expense     827 1005  RMCC CE VERSION  CONFORMS TO CE STANDARD BSEN 50082 1 AND BSEN 50081 1     Table of Revisions       Revision Description Page  REV 4                   CHANGED MAXIMUM NUMBER OF 81   BOARDS FROM TEN TO                      5 11  REV        NEW        PART NUMBER ADDED FOR USE WITH SPORLAN SEI VALVES                eese 7 1  REV 3    nue VALVE TYPE JUMPER SETTINGS FOR CCBS ARE NOW  12V  AND             7 2  REV  3 osse ADDED DEFAULT FAST RECOVERY HYSTERESIS FOR CONDENSER                                                    11 17  REV      ADDED DEFAULT LOW PRESSURE CUTOFF HYSTERESIS FOR CONDENSER                                        11 17  REV          ADDED HELP LINE TO CONDENSER RUNTIMES 5                       2  0   0                  11 18  REV 4                   ADDED THAT          DEFAULTS CASE          TO  0   SPARE             esses enne enne 11 25  REV 4                   CASE TYPE 38  POBX  CHANGED FROM PRODUCE BOX TO POULTRY                                            11 25  REV 3    THREE TYPES OF CLEANING SWITCHES ARE AVAILABLE NONE  CLEAN  DOOR                              11 28  REV 3s ADDED USER OPTION TO DEFINE MINIMUM DEFROST                                         11 28  REV          CORRECT GAIN FOR IRLDS SENSOR          DEFINED               eese eene enne nennen n
303. nitiates a pull down  valve open 100  until case  temperature meets the case temperature set point   After  pull down is complete  the case controller will return to  normal control     026 1102 Rev 4 08 12 99    9 Software Overview    The following section will discuss the frequently used  control functions within the RMCC  For specific screen de   scriptions  please refer to the related screens in Section 7   System Navigation     9 1  PID Control    Before going into detail about the RMCC   s system soft   ware  it may be helpful to first talk about the primary meth   od used by the RMCC to control systems such as pressure  control  condenser control  case control  and Analog Out   put Modules     PID Control is a method of control that attempts to  make an input equal to a set point by changing a single out   put value  PID control is made up of three parts  propor   tional  integral  and derivative  PID   The proportional part  of PID checks the difference between the input and the set  point  called the error   the integral part measures the error  that has existed over time  and the derivative part predicts  what the future error will be based on previous rates of  change     The result of the three PID comparisons is an output in  the form of a percentage  0 100906   This percentage is used  differently in RMCC systems  in pressure control  for ex   ample  this percentage corresponds to a percentage of total  rack horsepower  For all systems that use PID control  the 
304. no grounding on either side of the 24  V AC power supply                 EARTH GROUND    26513094       Figure 5 11 810 Board Wired in Combination with    or Multiple  16AI  8RO  4AO  8DO    When the 81   board is wired in conjunction with other  boards  the 8IO board is not grounded through the other  board s center tap  A separate Earth ground should be run  off of the 8IO     RMCC I amp O Manual Communication and Power Connections     5 9    When the 8IO is wired alone  either or neither side of  the power supply may be grounded however  a separate  Earth ground should be made off of the center terminal   power connection      5 8  Network Settings    For all boards  except 8IO boards  the network dip  switch labeled S1  or S3 for the 16AI board  is used to set  the unique board number of the unit and the baud rate  The  810 uses rotary dials to set the board number of the unit and  the baud rate is set internally at 9600     5 8 1  Network Address    Board numbering is accomplished using the first five  rockers on dip switch S3 on the 16AI board  the first five    24 V AC  POWER  SUPPLY                             EARTH GROUND rockers on dip switch 51 on the 8RO and 8RO FC boards   and two rotary dials on the 8IO board   OR 5 8 1 1  Dip Switches    Each of the first five rockers of either 51 or 53 is given  a value which is twice as large as the value for the rocker to  the left of it  The first rocker is given a value of one  With  these five rockers  a board may be give
305. nto reclaim can be programmed to force condenser split  or to raise the discharge pressure set point        Table 11 5   List of Inputs Configurable at the Input Definitions Screens    RMCC I amp O Manual System Navigation     11 53    Input Description    SUCT SETUP   DEFR INH 1 DEFR INH 4  CHECK IT   HUMIDITY    C1 F1 PRF   C1 F12 PRF    OIL PRESO1 OIL PRES22        01 PRF CMP22         SENSO1 SENS48    A contact closure from contacts on fans 1   12 will prove the fans are working     Oil pressure transducer inputs OR Copeland Oil System inputs for compressors 1   22  A contact closure from contacts on compressors 1   22 will prove the compressors are working   Inputs for sensors 1   48     VS1 INVALM VS4 INVALM   A contact closure from an inverter signifies an inverter fault     ALARM OVDI ALARM OVD S  A contact closure activates a sensor alarm override for either a fixed or timed duration     ALL SCH ON  ALL SCH OFF  SCH 1 OVRD SCH 4 OVRD    A contact closure activates all lighting schedules   A contact closure deactivates all lighting schedules   A contact closure bypasses schedules 1  2  3  and or 4     01 CLEANSW 48 CLEANSW   Clean switches for circuits 01   48     01 EXTRA   48 EXTRA    01 TEMP      48 TEMP      01 TERM     48 TERM      Also known as the Dual Temp input  a contact closure from this input may be used to raise the  case temperature alarm set point for a dual temp case   Case temperature sensors 1 6 for circuits 01   48     Termination temperature sensor
306. ntrol    Cut In Cut Out          Input    Occup    Out          Occ Setpts     Unocc Setpts                      verride                                    Command           on  off  normal   Type   timed  fixed   OV time          Limiting    Analog Input  Value    17  es                   Counter       In       Suspend    Reset    Count         Count Tripped    Trip  o          Initial Count             Trip Set Point  Reset Type   Count Increment                   26512020    output goes from OFF to ON  There are two inputs that ma   nipulate the module s Counter cell  The Suspend Count in   put  while ON  prevents the Counter cell from counting ON  transitions  The Reset Count input supplies a digital signal   that resets the Counter cell to its user specified initial val    ue     Alarm Disable and Notice Disable    The Alarm Disable and Notice Disable inputs affect the  Analog Input Module s ability to generate alarms and no   tices  When the alarm disable input is HIGH  the Analog  Input Module s Process Alarm cell will not be able to acti   vate the alarm output  Likewise  when Notice Disable is  high  the Notice output will not be allowed to activate     026 1102 Rev 4 08 12 99    Occupied  Occup     The state of this input tells the Analog Input Module  that the building is either occupied or unoccupied     Cells    Analog Value Combiner  AVCombiner     The AVCombiner cell s function is to read up to four  input values  combine these values into a single value   base
307. nual       Leak Alm Dly  0   120 minutes   10     The Leak Alarm Delay is the amount of time the  RMCC must wait before generating a Refrigerant Leak  Alarm after the specified amount of refrigerant has been  detected by a leak sensor     Extra Tmp   Y es   N o   Y     If desired  the RMCC will generate an alarm if one or  both of the extra temperature sensors fail     Door Alm Delay  0   120 minutes   15     If a Door Switch is defined at the Circuit Set Points 4  screen  see Section 11 4 49  Circuit Set Points 4  Add Edit  Circuit    the Door Alarm Delay may be defined in the  Door Alm Delay field  The Door Switch disables refriger   ation and walk in cooler fans  and turns on all cooler lights   When switched again  any calls for refrigeration and fans  are reactivated and all lights are turned off  However  if the  switch is not switched back after the designated Door  Alarm Delay  an Open Door Alarm will be generated and  the cooler will return to normal operation     System Navigation     11 35    11 4 34 CCB Set Point Screen 3  Liquid Pulse and Stepper Only     Er           89   Ul    clo            OFFSETS C  Case Offset   Discharge    BHO1SDIC O1c  Coil 2 In    Coil 2 Out     H  0  0  0 Refr Leak    0  0                                  Coil 1 In     Coil 1 Out         C  0  0  Return   0  0  0             T PREV               gt  SET DATA O MENU       At times  a sensor may provide a reading that reads low   er or higher than the known condition being monitored  An 
308. o slow the rate of  change of the PID cell   s output  The filter reads the differ   ence between the current value and the value x seconds ago   where x   a user specified amount of time  called the    pe   riod      The difference between these two values is multi   plied by the filter ratio  which is a percentage between 096  and 100   The result of this multiplication is the output  value  Note that if the filter ratio is at 100   or if the Filter  cell is disabled  the input is not modified by the Filter cell     The Filter output value is sent to the Override cell   Override    The primary purpose of the Override cell is to provide  a method of overriding the analog output going to the Se   quencer and PWM cells to a user specified value instead of  the value dictated by the Filter cell  Unlike other Analog  Output Module cells  the Override cell may be accessed  from the RMCC front panel without using UltraSite  The  RMCC s Analog Input Module Bypass screen is shown in  Figure 9 15     026 1102 Rev 4 08 12 99       ANALOG OUTPUT MODULE 01 BYPASS  Name        OUTPUT 01  Enable  YES  Value  000 0 Type NORMAL    Time  0005 minutes    Ov State NORMAL  T PREV              gt  5        Figure 9 15   Analog Output Module Bypass Screen    The Override cell may override the output to any value  between 0  and 100   The override may be either fixed or  timed  A fixed override remains overridden until the user  deactivates the override using the Analog Output Module  Bypass Scree
309. off  The period used to pulse the valve is fixed at six  seconds     When case temperature is satisfied  the valve control al   gorithm uses a close rate set point to determine the speed at  which the valve transitions to the closed position  The algo   rithm closes the valve at a rate of 1 10th the close rate set  point every six seconds until the fully closed position is  reached  The valve control algorithm also has a rapid close  rate function that multiplies the close rate set point by four  if the case temperature is two degrees cooler than the case  temperature set point     Stepper Valve Control    Stepper valve control is used by the liquid and suction  algorithms  Basically  in stepper valve control  the valve is  positioned at the   open as determined by the control algo   rithm  The control algorithm  liquid stepper or suction  de   termines the output   and passes this to the stepper valve  control algorithm  The valve control algorithm controls the  valve according to set points that define the number of  steps for full travel  the maximum rate  and hysteresis     Valve Types    The CCB is capable of controlling two types of valves   bipolar and unipolar  Representative characteristics for  both valve types are shown below     Sporlan EEPR or EEV  bipolar     Full Travel  2500 steps    Maximum Step Rate  100 steps second    Hysteresis  10 steps  e Valve Type  2 phase PM 2 coil bipolar    Alco EEV  unipolar       Full Travel  384 steps    Maximum Step Rate  33 st
310. ogging Interval de   fined within the RMCC represents a log  Select the  appropriate Log Configuration according to the number of  defined logs in the Select Configuration Type field  Users    11 8 10 Communications Setup          4      COMMUNICATIONS SETUP   Unit     01 Baud Rate  9600  Initialization String   AT amp FEOSO T amp D2X08W     6                                                  For Hel o To the Next Screen   Send Now  NO  Response     T PREV                                    Reset at Midnight          gt  SET DATA 0              RMCC I amp O Manual          connection  the system will generate an additional alarm in  the RMCC Alarm Log and cease dialout     Use From  00 00   23 59   N one   N     To specify when the RMCC should use defined Night  phone numbers instead of Day phone numbers  enter the  start and end night times in the Use From fields     Sat Sun   Y es   N o     To activate the RMCC   s alarm dialout feature on Satur   day and Sunday  enter  Y es in the Sat and Sun fields     may choose from the configuration types displayed in the  following table     Available  Logging  Points w o  Hourly  Log    Available    Logging  Points    Number  of RMCC  Logs    Configu   ration  Type    1365 1371    829  694    Table 11 7   Logging Strategies    Use Hourly Log Space   Y es   N o   N     To activate the RMCC Demand Control Hourly Log   enter              in the Use Hourly Log Space field  Deactivat   ing this log by entering  N o in the Use Hourly Log Sp
311. ol   for more  information about PID control     026 1102 Rev 4 08 12 99    A diagram of the Analog Output Module is shown in  Figure 9 13     Analog Output Module    Select          In 1          nalog PID PWM       In2    Ratio   Occupied Period    ys        p    Occup                Occ Fallback        Unoc Fallback   Output during Failure    mn          Setpt Float  SP In Out  m Float    Float Hi Lo           Output Range    DOD    PID  Setpoint  Control Value     gt  Input Out  Direct Acting       D                                    Direct Acting    PID Gains       Output   setpoint    Min Max Output             Figure 9 13   Analog Output Module    Inputs  Control Value    The Control In value is the primary signal the Analog  Output Module uses in PID control     Float    The Float Control input provides an analog value to the  Analog Output Module   s Setpoint Float cell  which is used  to adjust  or    float     the PID setpoint value     Occupied  Occup     The state of this input tells the Analog Output Module  that the building is either occupied or unoccupied     Occupied Setpoint Unoccupied Setpoint  Occ SP   Unoc SP     The Occ SP and Unoc SP values are the PID set point  values used during occupied and unoccupied building  times  These set points may be fixed values specified by the  user  or they may be inputs from sources within or outside  the RMCC     RMCC 1 amp 0 Manual       SW Override Loop Output  In                              on  off  normal     Ty
312. one   C lean   D oor    N     When the RMCC receives a contact closure from a  Clean Switch input defined at the Input Definitions screens   see Section 11 8 1  Input Definitions   the circuit    s refrig   eration valve  defrost valve  and fans will be overridden  OFF     None must be entered in the Cleaning Override Switch  field if no switch 1s to be used  If Clean is selected  the re   frigeration and defrost outputs will be turned off when the  cleaning switch input is closed  If a defrost was active  the  defrost timer will continue to run while the Clean switch is  closed  If the Clean switch is opened before the defrost time  has expired  the defrost output will energize and continue  until the defrost time does expire     11 28  Circuit Defrost Control       screen  see Section 11 4 17  Circuit Setup 2   Degree units  are determined by the unit selected at the System Units  screen  see Section 11 8 7  System Units      1st   6th Defrost  Circuit Defrost Times   00 00    23 59   N one   N     RMCC software version 1 05 will not allow defrost to  begin within 60 minutes after the conclusion of the  previous defrost event     Circuit defrost start times are established in the 1st 6th  Defrost fields  Defrost begins within the selected circuit at  the times defined in these fields  Up to six defrost times  may be defined for each circuit     When programming defrost start times  note that the  RMCC will allow overlapping of defrost times within cir   cuits  Overlapping d
313. or  and the RMCC is capable of controlling  multiple stages of unloading within each group     the transducer rises to the Oil Pressure set point defined in  the Oil Pres field  If a contact is indicated  the RMCC mon   itors the system for a contact change of state from a generic  mechanical oil sensor switch and terminates the compres    sor stage  If the compressor is not equipped with an oil sen   sor  select N  default  for None in the Oil Sens field     Cil Pres  0   999   15     If the oil sensor is defined as a pressure transducer in  the Oil Sens field  the net oil pressure that will cause the  compressor to terminate must be defined in the Oil Pres  field  This value is determined by the compressor manufac   turer  The RMCC calculates the net oil pressure based on  the actual oil pressure reading of the transducer minus the  suction pressure reading     HP AMPs  0   999   15     The RMCC will only accept horsepower in whole  number increments  Round all fractional horsepower  to the nearest whole number     Enter the Horse Power or BTU rating of the selected  compressor in the HP AMPs field  If using a Hussmann    PROTOCOL   system with the advanced defrost option   enter the amperage of the selected compressor in the  HP AMPs field  Make sure that either all compressors are  defined in HP or all compressors are defined in amps     Proof   Y es   N o   N     If a compressor proof input has been defined for the se   lected compressor stage at the Input Definitions sc
314. ore a one pound adjustment is made to the suction  pressure  When the current circuit temperature reading is  below the defined Circuit Temperature set point defined at  the Circuit Setpoints screen  see Section 11 4 28  Circuit  Set Points  for the defined Float Interval  the Suction Pres   sure set point is raised one pound  When the current circuit  temperature reading is above the defined Circuit Tempera   ture set point for the defined Float Interval  the Suction  Pressure set point is lowered one pound  The interval  counter is reset anytime the current circuit temperature is  within the circuit temperature set point range     11 2 13 Group 1 Strategy Setup    PONI     GROUPT STRATEGY SETUP  1       ST          for Help  lt  Exit       RMCC I amp O Manual          Max Suction   20   99 Ib    30 0     The Maximum Suction is the highest pressure the Suc   tion set point may be adjusted to when the Floating Strate   gy is enabled     Min Suction   20   99 Ib    20 0     The Minimum Suction is the lowest pressure the Suc   tion set point may be adjusted to when the Floating Strate   gy is enabled     Use Circuit  0   48   1     The RMCC monitors a specified circuit temperature  when utilizing the Floating Set Point Strategy  To define  the circuit to monitor for the selected suction group  enter  the appropriate circuit number in the Use Circuit field     Delay Floating After Defrost  0   60 minutes   10     During defrost  the circuit temperature is not an accu   rate read
315. osure  but should  be mounted in a location that is not easily accessible to  avoid tampering or damage     Mounting  Single Enclosure Mounting    The Single enclosure is supplied with four mounting  holes in the rear panel of the enclosure  These holes are ac     Hardware Mounting   3 1    cessible without removal of any boards inside the enclo   sure  Figure 3 2 shows the enclosure dimensions and  weight  Figure 3 6 shows mounting dimensions for the  8RO and 16      Figure 3 7 shows mounting dimensions for  the 8RO FC        0025  TYP 2 PL    00 50         2 PL    SINGLE ENCLOSURE     REAR OF ENCLOSURE   WEIGHT  12 LB     00 25  TYP2PL       Y    26501039       Figure 3 2   Single Enclosure Mounting Dimensions    Double Enclosure Mounting    The Double enclosure is supplied with four mounting  holes in the rear panel of the enclosure  These holes are ac   cessible without removal of any boards inside the enclo   sure  Figure 3 3 shows the enclosure dimensions and  weight  Figure 3 6 shows mounting dimensions for the    3 2   I O Boards and Enclosures    8RO and 16AL Figure 3 7 shows mounting dimensions for  the 8              13 00     4 25     00 25  TYP 2 PL    00 50        2           DOUBLE ENCLOSURE   REAR OF ENCLOSURE  ren    WEIGHT  15 LB        0 25  TYP 2 PL       26501033       Figure 3 3   Double Enclosure Mounting Dimensions    8     Weather Resistant Enclosure Mounting    The 8IO Combination Input Output Board is generally  supplied with a weather resistant enc
316. p  In addition to the sta   tus of each compressor within the suction group  users may  view the current suction and discharge pressure or temper   ature set points and status  the current variable speed com   pressor percentage and rpm value  and the status of all fans  within the group     Suct    The current suction pressure set point is shown in pa   renthesis in the Suct field  Beside this value  the current  suction pressure is shown     VS    If a variable speed compressor is present in this suction  group  the VS field will show the percentage and the RPMs  at which the compressor is operating     13 2  Status Menu          Dsch    The current discharge temperature or pressure set point  is shown in parenthesis in the Dsch field  Beside this value   the current discharge temperature or pressure is shown     Ambient    The Ambient field displays the current ambient temper   ature  If an ambient temperature sensor is not defined  this  field is not displayed     Compressors    The numbers 01 to 08 in the fourth row of the display  represent each compressor in the suction group  If the com   pressor has been previously defined in the system software   see Section 11 2 7   Group 1 Setup   a letter will appear  before the compressor   s number signifying whether it is a  compressor             a variable speed compressor              or  an unloader     U      If more than eight compressors are de   fined the line displaying the condenser fan status is re   placed an addit
317. p O Manual System Navigation     15 5    Door   the current status of the door switch    Frost   the demand defrost sensor status    Refr Leak   the ppm concentration of refrigerant currently being detected by the leak sensor   Offset   the leak sensor offset  This value may be changed using the HHT     Case Dbd   the dead band for the case temperature  This value may be changed using the HHT   Close Rate   the rate of closure for the valve  This value may be changed using the HHT     OV Type   the type of override currently being executed  Four different messages may appear  here     None    for no override     Timed    for timed override   Swtch  for door switch over   rides  and              for manual overrides     Kd x10   The derivative gain value for the valve multiplied by 10  See Section 11 4 37   CCB  Set Points Screen 4  CPC Suction Stepper Only  for a complete definition of derivative gain     Step Deflt   By pressing RIGHT and selecting one of the options below  the hysteresis  max  step rate  and maximum steps values are automatically programmed with appropriate de   fault parameters for Alco EEVs or Sporlan EEPRs  These values may also be reset     1 Alco EEV   Hysteresis is set at 0  Max Step Rate at 33  and Max Steps at 384    2 Sporlan EEPR   Hysteresis is set at 10  Max Step Rate at 100  and Max Steps at 2500    3 Reset   Hysteresis is set at 0         Step Rate at 100         Max Steps at 0    If a default setting was chosen using Screen 15  the default va
318. p Switch Settings     Voltage  to  Switch   Sensor    Dew Point Probe   Down 24 VAC  D ewpt  or  L in   ear    203 1902    Voltage to Sensor   the voltage  if any  required to  power the sensor     Type   the sensor type that must be selected when  setting up the sensor in the sensor software  Sensor  types are defined in Section 7 6 2   Setup     Typical Settings   This column contains typical  alarm set points  sensor cut on and cut off set  points  and alarm delay values for each sensor type   If the sensor type is linear  the Gain and Offset val   ues are also included in this column     Wiring   wiring instructions and specifications     Typical  Settings    Green to ACI   White to AC2   Black to odd number input  GND   Red to even number input  SIG     If set up as linear   Gain    58 4  Offset    1523     p D ii SET NENNEN   in ii Bem     sitive     809 1070  809 1072    LDS to          Down Supplied  by LDS  IRLDS to Down Supplied  DRLDS  RMCC by IRLDS or  L in   ear  IRLDS to Down Supplied  by IRLDS    809 1100  809 1101  809 1105  809 1106    809 1100  809 1101  809 1105  809 1106    RMCC  all vs   below RMCC  2 10  for faults    207 0100 Analog Liquid  Level    Table B 1   RMCC sensor setup    RMCC I amp O Manual    206 0002   Light Level 12 VDC  12 VDC L g Lvl     R efrLk   Alarm at 250 ppm   Shielded wire and Common on  LDS tied together to odd number  on 16AI  Analog Outputs to even numbers  on 16AI    If set up as linear   Gain 250  Offset 0   Alarm at 100 ppm 
319. p in the first Backup field and se   lect              in the second     System Navigation     11 43    Restore    The Restore option replaces the current case settings  with the saved backup settings  This option is only active  after the selected case has been backed up  To restore saved  settings to the Case Controller  enter the ID Number of the  target case in the first Restore field and select    Y      es in the  second     Copy Set Points    Case control set points defined for one Case Controller  are copied to another Case Controller when the Copy Set  Points feature is activated  To activate this feature  enter the  ID Number of the source case in the first Copy Set Points  field and the ID Number of the target case in the second  Fi     11 4 55 Anti Sweat Setup              If the          Anti Sweat feature is activated at the Cir   cuit Set Points 2 screen  see Section 11 4 47  Circuit Set  Points 2  Add Edit Circuit    the humidity or dewpoint sen   sor input that controls the anti sweat heaters is configured    11 4 56 Circuit Summary        CIRCUIT STATUS              STATUS T  1    MP  Refr 0   Refr 0   Refr 0   Refr 0   Refr 0    T PREV J NEXT    Basic summary information about all standard circuits  defined within the RMCC is listed at the Circuits Status  Summary screen        Name    The   and Name fields display the number and defined  name of the circuit     Status    The Status field displays the operating status of the cir   cuit  The status will disp
320. pe Anal   timed  fixed  a og    OV time PID Setpoint    He     PEN    Sequencer    Input Stage 1  Stage 2  Stage 3  Stage 4  Stage 5  Stage 6  Stage 7  Stage 8    Delays      _  Num Stages  Type                            Digital Stage  1 8 Output                         Digital PWM  Output  In                   2                              Period  Range              26512022    The Analog Output Module uses either the Occ SP or  the Unoc SP as the control set point based upon the status  of the Occup input  ON occupied  OFF unoccupied      Direct Acting    The Direct Acting input determines how the output of  the Analog Output Module changes in relation to the input   When the Direct Acting output is ON  the output value will  move in the same direction as the input value  in other  words  when the input value increases  the output value in   creases  When the Direct Acting input is OFF  the output  value will move in the opposite direction as the input value     The primary purpose of the Direct Acting input is to al   low a single Analog Output Module to control both cooling   typically requiring direct action  and heating  typically re   quiring reverse action  with a single input and output   Cells    Select    The Select       s primary function is to select either the  Occ SP or Unoc SP analog signals to be used as the Analog    Software Overview     9 15    Output Module s PID Setpoint  To perform this function   the Select cell reads the value of the Occup input  i
321. pensate for a fan failure by substituting the    11 3 7 1  Condenser VS Fan Setup           2  ks     CONDENSER VS FAN SETUP  0900 rpm          VS Minimum Speed        VS Maximum Speed   1800 rpm       VS Increase Rate   VS Decrease Rate           2000 rpm minute  2000  rpm minute             T PREV 4            gt  SET DATA O MENU    VS Minimum Speed  VS Maximum Speed  0    32000 rpm   0 rpm     When the RMCC calls for the variable speed condenser  fans to be on at 0   the fans will operate at the defined VS    System Navigation     11 15    Minimum Speed  Likewise  when the RMCC calls for the  fans to be on at 100   the fans will operate at the defined  VS Maximum Speed     VS Increase Rate  VS Decrease Rate  0   32000  rpm minute   0 rpm minute     The VS Increase Rate is the maximum rate at which the  speed of the condenser fan may be increased  The VS De   crease Rate is the maximum rate at which the speed of the  condenser fan may be decreased     11 3 7 2  Condenser Fan Fail Setup    G2  02  Es      CONDENSER FAN FAIL SETUP  Fan Fail Enable   NO   Fan Fail Delay 10005              Continually try to Clear Failure      0   Num Clear Attempts  00  Delay Between Clear Attempts 0030 sec                      T PREV               gt  SET DATA    Refer to Condenser Fan Fail Setup on Section 11 3 5 3   Condenser Fan Fail Setup     11 3 8  Condenser Setpoints Screen 1       CONDENSER SETPOINTS       Setpoint             Throttle Range  Shift During Reclaim       T PREV J NEXT  
322. percentage of log space used within the  system is displayed on the Logging Setup screen  see Sec   tion 11 8 9   Logging Setup      Information received from sensors with a logging in     terval of zero will not be recorded to the log     A typical logging interval may be defined for all sen   sors by using the copy feature described in Section  11 4 54   Utilities     Setup for Additional Logging Intervals    There are two additional screens where other logging  intervals for such values as refrigerant leak concentration   coil in temperature  and coil out temperature may be de   fined  To access these screens  press the DOWN arrow key     12 1 6  Sensor Logs       12 00  A BIENT  LO   0 OF 682    Sensor readings are logged to the Sensor Control Log   This historical data is recorded for any of the 48 defined  sensors according to user selected time intervals  Logging  Intervals are defined at the Sensor Setup screen  see Sec   tion 11 5 1   Setup   The RMCC will store as many read   ings as is specified in Logging Setup on Section 11 8 9    Logging Setup for each sensor     12 2   Logs       12 1 7  Hourly Demand Log          The Hourly Demand Log displays a summary of the  kW usage during the past hour  The date and time of each  log are also displayed     KW HRS    The total kW hours used within the selected hour is dis   played in the KW HRS field     Peak Time    The peak power is the highest value of kW measured by  akW or watt hour transducer during the selected hour
323. pointwith   Black and Shield to odd no  on in   800 1500  5 00 60 min delay put  GND     White to even number on input   SIG     NOTE  Transducer type must be  set to ECLIPSE under Transduc   er Setup     203 5750 Relative Humid  Red to  12V on 16AI  PWR   ity Black to odd number on input   GND   White to even number on input   SIG  marked    out    on sensor  Jumper N to G at sensor    Table B 1   RMCC sensor setup          2    Appendix B 026 1102 Rev 4 08 12 99    Appendix C  Pressure Voltage and Temperature Resis   tance Charts for Eclipse Transducers  amp  CPC Temp  Sensors    CPC Temperature Sensors    Eclipse Transducers  Pressure  PSI     Resistance  ohms  Temperature  F     336 450  234 170    5 40    30       D      5 20   0   0   70     ws        88998    Table 15 1   Temp Sensor Temperature Resistance Chart       RMCC 1 amp 0 Manual    100 Ib  200 Ib  500 Ib   xducer xducer xducer          N                  N                                     N                  o            1           Table 15 2   Eclipse Voltage to Pressure Chart    Appendix C   C 1    Appendix D  System Navigation Screens       PRESSURE MENU 12 00  1 Status   Press  Setpts  2 Bypass   VSpeed Setpts  3 Alarms B Float Setpts  4 Logs 9 Fixed Steps  5 Comp Setup Strategy Setup                                                                      GROUP1 STATUS COMPRESSOR BYPASS 12 00   RPT PRESSURE ALARMS SETUP 12 00  PRESSURE LOGS   2 0   PRESSURE GROUPS SETUP 12 00 SETPTSCENABLED  12 00         
324. program the modem  initialize the modem by send   ing the initialization string to the modem in the Send Now  field  The modem   s response will be displayed in the Re   sponse field  The modem should initialize within approxi   mately five seconds after the string is sent  An OK response  or a replica of the string is returned to the screen if the mo   dem is properly defined  If a No Response is returned   check the wiring  resend the string  then refer to the trou   bleshooting guide in the modem user   s manual for sugges   tions     Reset at Midnight   Y es   N o   N     To ensure the modem is properly programmed to per   form the RMCC   s remote communication functions  send  the string to program the modem on a regular basis  To au   tomatically send the string every night at midnight  select             in the Reset at Midnight field     Only one controller in the network chain should be con   figured to reset the modem at midnight  If more than one  controller is configured to reset the modem at midnight   communication errors can occur     modems frequently used with RMCC  The following mo   dem types are available    e Hayes   e Multitech   e Practical Peripheral 24008A   e Practical Peripheral 2400SA V42bis   e Practical Peripheral 9600SA V42bis   e Generic    To copy the stored initialization strings for one of the  listed modem types to the Communications Setup screen   enter the corresponding number in the Patterns  Number to  Copy field  Refer to the modem use
325. put Module Status  screen  The PID Output will appear as a value between 0   and 100   the PID Setpoint will appear as an analog value   and the PWM Output will appear as either ON  OFF  or  NONE  depending upon the current state     The Stages fields at the bottom of the screen show the  status of Stage 1 through Stage 8 of the Analog Output  Module   s Sequencer outputs  see    Sequencer    on Section  Sequencer   Each field will read either          for OFF or   ON  for ON  If a field is blinking  the stage is currently in  the interstage delay period between transition changes  see   Sequencer  on Section Sequencer      To view the status of other Analog Output Module Sta   tus screens  press the UP and DOWN arrow keys     13 8  Demand  13 8 1  Demand Status    Du    DEMAND STATUS  Demand OFF       12 00    Timer  00 00 Setpt  350KW    Current Power Usage  0000 KW    Peak Power Today   0 KW 9 00 00  KWHs Used This Hour  00000 0  Total KWHs Today   00000 0    The RMCC activates a demand relay when the energy  being used by the system exceeds the demand limit set  point  When this set point is exceeded  the RMCC is said to  be in Demand     The Demand Status screen displays the current status of  demand control within the RMCC  Information displayed  on this screen includes the ON OFF status of demand  a  summation of the times the RMCC has been in demand  the  demand limit set point  current power usage  peak power  usage  power used in the past hour  and total power used 
326. r   s manual to determine  the correct modem type  The stored initialization string for  the selected modem type is displayed in the Current field     026 1102 Rev 4 08 12 99    11 8 12  Transducer Offsets    ers     TRANSDUCER OFFSETS          Group 1 Suction        Group 2 Suction   Group 5 Suction   Group   Suction   Discharge Press     T PREV               gt  5                                                   11 8 13 01 Pressure Transducer Offsets       eres  bs   0       PRESSURE TRANDUCER OFFSETS   1   00 0  0    11  00 0  0  100 0  1 1    7 1  00 0   01  00 0                                                                                                  gt  5                              11 8 14 Transducer Setup       TRANSDUCER SETUP  Disch  Pressure    Suction Pressure           500 Lb          Gr1 Gr2 GR3                100 Lb  Oil Pressure           100 Lb  200 Lb       100 Lb                              gt  SET DATA    Discharge  suction  and oil pressure transducers moni   toring the RMCC are configured at the Transducer Setup  screen     RMCC I amp O Manual             Pressure transducers within the RMCC measure the  current suction pressure  discharge pressure  and or oil  pressure within each suction group  Transducer configura   tions are defined at the Transducer Setup screens     At times  transducers within suction groups may pro   vide readings that read lower or higher than the known con   dition being monitored  An offset value may be entered for  
327. r  If a device must  be added to the system  refer to the information supplied  with the device and consult the refrigeration equipment  manufacturer  Table 3 1 lists some typical sensor applica   tions and the sensor or probe most suited for that purpose   The use of these devices is not limited to these applications   however  Refer to Table 5 1 for wiring of these device    types     3 6   Temperature Sensors    Table 3 1   Sensor Application and Type       Mounting Bullet and Pipe Mount Sensors    Bullet or pipe mount sensors mounted on refrigerant  lines should be secured with a Panduit low temperature ca   ble tie  number PLT2S M120  or equivalent  For pipe  mount sensors  the curved surface should be placed against  the pipe and the tie should be positioned in the groove on  the top surface of the sensor     second tie should be used  to secure the lead to the pipe for additional support     Sensors located on refrigerant lines should be insulated  to eliminate the influence of the surrounding air  A self ad   hering insulation that will not absorb moisture is recom   mended to prevent ice logging at the sensor location     Depending on the size of the refrigeration line  the sen   sor should be positioned as shown in Figure 3 13        Figure 3 13   Sensor Orientation    3 8  Liquid Level Sensors    CPC supplies both a probe  207 1000  and float  207   0100  type liquid level sensor  Each is installed by the re   frigeration and equipment manufacturer  Table 5 1 shows
328. r  P N 812 1800   shown in  Figure 2 11  is used to connect CPC controllers together as  an integrated communication system  Communication  problems sometimes associated with large control sys   tems   such as limited cable lengths  data rate limitations   and terminal and modem communication interference   are  eliminated through the use of the RS232 Bus Amplifier     2 6   Hand Held Terminal          Figure 2 11   RS232 Bus Amplifier    2 7 2     To communicate with a site from a remote location  the  network must be connected to a modem directly  or through  the RS232 Bus Amplifier  CPC supplies a standard 14400  fax 9600 data modem  P N 370 9600  for use with the RE   FLECS network     The REFLECS and CPC s RS232 Remote Communi   cation Network are designed to connect to and be compat   ible with most modems in use today  Remote  communication screens allow the user to define modem  type  baud rate settings  automatic dial out functions  and  auto polling     2 73  UltraSite      Remote communication with a site controlled by the  REFLECS is accomplished using UltraSite  CPC s remote  communication software package  UltraSite is a    Modems    Microsoft  Windows    based program that uses animated  graphics  icon buttons  and tabular and graphical data to  display real time conditions of any site     UltraSite accesses any site controller through the on   site modem  and  if present  the RS232 Bus Amplifier  AII  commands available through the front panel of the RE   FLEC
329. r  the RMCC to reset the failed inverter  an output must be de   fined as an inverter reset at the Output Definitions screens   see Section 11 8 2  Output Definitions   After the third at   tempt to reset the inverter  the compressor will bypass Off  if the Off on Failure feature is activated  If the Off on Fail   ure feature is not active  the compressor will bypass On     026 1102 Rev 4 08 12 99    11 2 12 Group 1 Floating Suction    alke     GRP1 FLOATING S  Float on off   INTERVAL M    85   MAX SUCTION  03   0  g          CTION  F                                  U  0  0  1       Use Circuit   Delay Floating A  Extern  Shift   0                                                  T   F   0 MIN SUCTION   f   0       ter Defrost   10            gt  SET DATA O MENU    The Floating Set Point Strategy operates the compres   sor system at the highest possible suction pressure while  maintaining proper temperatures in the controlled cases  and coolers  This strategy adjusts suction pressure settings  as long as temperature conditions are acceptable  Floating  Set Point Strategy settings are defined at the Group 1 Float   ing Suction screens  Screens for Group 2  3  and 4 are ac   cessed by pressing the down arrow     Float On Off   O n  O f f   F     The Floating Set Point Strategy is activated in the Float  On Off field     Interval  0   60 minutes   15     The Interval is the duration the current circuit tempera   ture must be above or below the Circuit Temperature set  point bef
330. r Leak  Refrigerant Leak    This alarm type in   cludes the Leak alarm         CCB Sens  CCB Sensors    This alarm type includes  the Coil In  Coil Out  Coil2 In  and Coil2 Out  alarms     e Network   This alarm type includes the Bad Check   sum  Bad Message  Device ONLINE  Host Bus  Network Down  Missed Token  and No Response  alarms       Miscellaneous   This alarm type includes all other  alarm messages not covered in the first nine catego   ries  These include the Condenser VS Fan Proof     11 8 7  System Units    Er  15       SYSTEM UNITS       Temperature Unit  F             Pressure Unit  Date Format               Month Day         gt  SET DATA O MENU    Engineering units used throughout the RMCC are de   fined at the System Units screen     11 8 8  Dialout Setup                      DIALOUT SETUP     Change Baud Rate when dial to  Day Phones                                      2   Night Phones 1   2       Use From           to                                     gt  SET DATA O MENU    RMCC alarms  or high level warnings  are usually ac   companied by an alarm dialout sequence  This sequence is  setup at the Dialout Setup screen     11 58   Configuration          Condenser VS Inv Fail  Defr Timed  Demand Tim   eOut  Dialout Unsuccessful  Dig  Alarm Override  ON  Fan Proof  FP Level  lt 999 gt  Login  High Speed  Proof  Hi Humidity  Hi Term  In Override  Inverter  Fail  Lo Suction  Lo Xducer  Low Humidity  Low  Speed Proof  Low Temp  Low Term  Manual Alarm  Ovrride ON 
331. r four  This may be changed using the HHT     Extra 1 Tmp   the current reading of extra temperature sensor one     ee E    t          2 n Offset   the offset for extra temperature sensor one     BE         E 2 Tmp 0         Extra 2 Tmp   the current reading of extra temperature sensor two     Offset   the offset for extra temperature sensor two     Door   the current status of the door switch    Frost   the demand defrost sensor status    Refr Leak   the ppm concentration of refrigerant currently being detected by the leak sensor   Offset   the leak sensor offset  This value may be changed using the HHT     Step Deflt   By pressing RIGHT and selecting one of the options below  the hysteresis  max  step rate  and maximum steps values are automatically programmed with appropriate de   fault parameters for Alco EEVs or Sporlan EEPRs  These values may also be reset     1 Alco EEV   Hysteresis is set at 0  Max Step Rate at 33  and Max Steps at 384   2 Sporlan EEPR   Hysteresis is set at 10  Max Step Rate at 100  and Max Steps at 2500   3 Reset   Hysteresis is set at 0  Max Step Rate at 100  and Max Steps at 0     If a default setting was chosen using Screen 14  the default values will be displayed in this             hee t screen  They may be changed at this screen using the HHT     Max Steps Step Hyst   the hysteresis value  See Section 11 4 37   CCB Set Points Screen 4  CPC Suction  Stepper Only  for a definition of hysteresis     Step Hz   the maximum number of steps per secon
332. r of clear attempts 11   14  split type 11 13  unsplit split delay 11 13  two speed 9 5  11 14 11 15  defining fan relays 11 14  fan fail setup 11 15  high speed HP 11 15  high to low delay 11 15  low speed HP 11 15  low to high 11 15  start duration 11 15  start speed 11 14  variable speed 9 5  11 15  cut on cut off value 9 5  inverter reset count 11 16  min max speed 11 15  VS increase decrease rates  11 16    CRC Test  See Cyclic Redundancy  Check     Cyclic Redundancy Check 11 56    RMCC I amp O Manual    D  Daisy Chaining 4 1  4 2    Daylight Savings Time  setup 11 57    Defrost 9 7  alarm delay 11 56  case control  defining termination type  11 39  demand defrost enabling 11   42  demand fail safe time 11 42  scheduling defrost times 11   40  specifying defrost type 11   39    defrost duration 11 56  demand 9 7  demand fail safe time 9 7  drain time 9 7  electric 9 7  emergency 11 23  hot gas 9 7  pump down delay 9 7  standard circuits   manual defrost 11 23  termination methods 9 7    Demand Defrost 9 7  fail safe time 9 7    Digital Output Module  See       Con   trol  Digital Output Mod   ules     Digital States  definition of NONE 9 9    Dip Switches  16AT 81O input type settings 5   12    baud rate   settings 4 4  Baud Rate Settings 4 5  baud rate settings 5 11  fail safe settings 5 11  network   board numbering 4 4   function of 4 4  network settings 5 10  relay state on 810 and 8RO FC   5 11    Discharge Trip 9 6    Discharge Unsplit  See Condenser   split operat
333. rcuits  Standard 11 19    making all circuits CCBs 11 44  set points  alarms 14 1  case pump down delay 11   29    defining drain time 11 27   demand fail safe time 11 29   dual temp alarm shift 11 29  setup 11 24   circuit inputs 11 30   circuit outputs 11 30   clean switch 11 28   defrost schedules 11 28   defrost termination type 11    26    defrost type 11 26  demand defrost sensors 11     drain time 11 28  liquid line solenoid 11 24  temperature sensors 11 27  temperature strategy 11 27  termination sensors 11 27  Clean Switch  control of  See Wash  Mode   Clean Door Switch  wiring on case controller 7 2  COM A Network  See RS485 Input   Output Network    COM B Network  See RS485 Host  Bus Network     COM C Network  See RS232 Remote  Communication Network     COM D Network  See RS485 Input   Output Network    Compressor Groups  See Pressure  Control     Compressors    forcing ON during defrost 11 7  forcing one compressor ON 11 7    horsepower or amperage defini   tion 11 6  oil pressure fail safe set point 11     oil sensors 11 6  proofs 11 6  run times 11 6  running one compressor during  reclaim 11 7  specifying number of per group  11 5  standard  defining compressor as 11 6  unloaders  defining 11 6  variable speed  defining compressor as 11 6  function of 9 2  max RPM increase and de   crease 9 2  Normal strategy 9 2    Condenser 9 4   9 6  11 10    air cooled 9 4  strategy 9 4  temperature differential  strategy 9 4  air cooled strategy 11 10  discharge trip 9 6  
334. rds within  the system  By default  this screen will display the maxi   mum number of 8RO  16AI  4AO  and 8DO boards the  RMCC may hold  and it displays the current number of  boards defined     When setting up      8IO in this screen  count    8IO as         16AI                 and one 4AO board  If the 8IO s ana   log output functionality is not being used and the 4AO slot  is needed elsewhere on the I O network  users may remove     81078 functionality to free a 4AO slot  To achieve this   disable the 8IO s analog outputs by removing the jumper   JU4   see Section 2 4 1   SIO Board  on the 810  This  board must then be set up as one 8RO and one 16AI in this  screen     System Navigation     11 63    11 8 22 Reset    er Er es        NETWORK  Reset  ON              11 8 23 Satellite Communication    2r     11 8 24 Pressure Transducer Type       PRESSURE TRANSDUCER TYPE 12 00    Board Point Type  00  LIP                           gt  SET       Before a transducer type may be changed  the trans   ducer input s board and point address must be entered  in the Output Definitions screen  Section 11 8 2  Out   put Definitions      11 64  Configuration          The I O Board Network is disabled at the Reset screen   If this network is disabled  the RMCC may no longer con   trol functions associated with the unit  After the network is  reset OFF  it may also be reset ON at the Reset screen     To turn off the I O Board Network  enter    1    for OFF  at the Reset screen  To reset th
335. recorded to the Pressure Control logs     To define the logging interval for all suction group data   enter the time the suction group data should be logged at  the Pressure Logging Interval Screen  00 00 00    24 00 00   00 03 00   The number of available logging  points is determined by the Logging Configuration defined  at the Logging Setup screen  see Section 11 8 9   Logging  Setup      12 1 2  Suction Group 1 Logs    61  04   Group         0 of 0 12 00  SETPOINT FLOAT T    00 00  T PREV 4  NEXT    The RMCC continuously records occurrences within  each suction group and stores the information in the Pres   sure Logs  The RMCC records the date  time  and occur   rence data based on the logging interval defined at the Log  Interval screen  see Section 12 1 1   Suction Pressure Log  Interval      Occurrence data points displayed at the Group Logs  screens include the Suction Pressure reading  the Discharge  reading  the Float Temperature set point  and the Float  Temperature reading for each entry     The number of available logging points is determined  by the Logging Configuration defined at the Logging Setup  screen  see Section 12 1 1   Suction Pressure Log Inter   val      RMCC I amp O Manual       12 1 3  Anti Sweat Daily Logs          The RMCC keeps a record of anti sweat circuit opera   tion and displays the daily statistics in the Daily Logs  screen  Each record shows the average ON time percentage  and the highest and lowest dewpoints for each day     Pressing the
336. reens   see Section 11 8 1  Input Definitions   the RMCC must be  configured to look for a contact closure indicating the acti   vation of the compressor or unloader     Phase loss monitoring and special situation compressor  activation for all suction groups are defined at the Pressure  Setup screen     Phase   Y es   N o   Y     The RMCC is designed to monitor a phase loss device   non voltage contact closure   When phase loss is detected   the RMCC will shut down all compressors     phase loss  device must be setup at the Input Definitions screens  See  Section 11 8 1  Input Definitions     026 1102 Rev 4 08 12 99    Force Comp On During Defr Run Comp During  Reclaim   Y es   N o   Y     When suction pressure within a group has been satis   fied  the RMCC will terminate all compressor stages  A  single compressor may be forced on during hot gas defrost    and or during reclaim when all compressors are terminated     11 2 9  Two Stage System Setup    TWO STAGE SYSTEM SETUP       Low Suction Group                High Suction Group         gt  SET DATA O MENU    11 2 10 Group 1 Pressure Set Points    J     nj    GROUP 1 PRESSURE SETPTSCENABLED  12 00  STRATEGY NORMAL Contr  by PRESSURE  SETPOINT   22 0   DISCHARGE   00 2 Trip Point  3550 0   Trip Delay 005   Autoreset  50 0    Below Trip Point       gt  SET DATA O MENU             DEADBAND  DELAYS  _ON OFF  s  005  s  005                                              T PREV                Set points for compressor operation ar
337. rent operating status of the demand  defrost sensor s   refrigerant leak sensor  door switch  fan  relay  and case lights     Frost    When the Demand Defrost feature is activated at the  Circuit Set Points 3 screen  see Section 11 4 48   Circuit  Set Points 3  Add Edit Circuit    the current status of the  Demand Defrost Sensor is displayed in the Frost field     Refr Leak    The current reading from the refrigerant leak sensor is  displayed in the Refr Leak field  This sensor calculates the  parts per million rating of escaped refrigerant     Door Switch    When a Door Switch is configured at the Circuit Set   points 4 screen  see Section 11 4 49   Circuit Set Points 4   Add Edit Circuit    the current status of the Door Switch is  displayed in the Door Switch field     Fan Relay    The current status of the Fan Relay is displayed in the  Fan Relay field     Lights    The current status of the case lights is displayed in the  Lights field     The Sensor Control Status screen displays the current  status information about each defined RMCC sensor  Users  may view the sensor name  current controlled output status   if applicable   current sensor reading  and the defined cut   in and cut out set points if the displayed sensor is control   ling an output  No modifications to the sensor controls may  be made at these screens  Up to five sensors may be viewed  on the screen at one time  Use the up and down arrows to  view additional sensors     026 1102 Rev 4 08 12 99      Name  
338. ressure or tem   perature of an evaporative condenser may be controlled by  asingle temperature or pressure sensor or a combination of  up to five temperature or pressure sensors  The method  used to combine the multiple values into a single control  value must be specified in this field  There are four differ   ent refrigerant types to choose from     e  OJNE   Only one sensor will be used to determine  the control value     e  A VG   The average of all sensor values will be  used as the control value     e MI N   The lowest of all sensor values will be used  as the control value     e MA X    The highest of all sensor values will be  used as the control value     Sensors for evaporative condensers must be given  board and point addresses in the Input Definition screens   see Section 11 8 1  Input Definitions      11 3 2  Condenser Pressure Inputs Setup  Air Cooled  amp  Temp Diff Strategies Only        CONDENSER PRESSURE INPUTS SETUP    Inlet Pres Offset  000 0   000 0           Outlet Pres Offset     T PREV              gt  SET    RMCC I amp O Manual       This screen is present only if the Control Strategy field  in Section 11 3 1   Condenser Setup  is set to    Air Cooled     or    Temp Diff     If the Evaporative strategy is being used   this screen is replaced with the Condenser Evaporative In   puts Screen as shown in Section 11 3 3     The Condenser Pressure Inputs Setup screen allows us   ers to enter an offset value to correct the inlet and outlet  transducer value
339. rigeration and defrost modes  Pressing RIGHT fol         8       5 Pe lowed by one of the commands below allows users to manually override the case   2 0V OFF f 1 Man Dfr   Pressing 1 initiates manual defrost   S  End DECOY 2 OV OFF   Pressing 2 overrides both refrigeration and defrost OFF     3 End Dfr OV   Pressing 3 will terminate defrost mode        RMCC I amp O Manual System Navigation     15 3    Door   the current status of the door switch    Frost   the demand defrost sensor status    Refr Leak   the ppm concentration of refrigerant currently being detected by the leak sensor   Offset   the leak sensor offset  This value may be changed using the HHT     Case Dbd   the dead band for the case temperature  This value may be changed using the HHT     Close Rate   the rate of closure for the valve is shown in this field  This value may be changed  using the HHT     OV Type   the type of override currently being executed  Four different messages may appear  here     None    for no override     Timed    for timed override   Swtch  for door switch over   rides  and              for manual overrides     Kd x10   The derivative gain value for the valve multiplied by ten  See Section 11 4 36   CCB  Set Point Screen 4  Liquid Pulse and Stepper Only  for a complete definition of derivative  gain    Control   the valve control type  This should read EEV    Valve Type   the valve type  This should read Puls  pulse     Network   whether the control network is ON or OFF     CO Fan Loc
340. rmine the operation  of the fans during normal  split  and fast recovery modes  are specified in the Condenser Setup screens  The first    11 10   Condenser Control       The RMCC will activate the stages when the suction  pressure is above the suction pressure set point  The RMCC  will cycle through the defined stages until the pressure falls  to the set point  When the suction pressure set point is met   the RMCC will cycle backwards through the defined stages  until the first stage of the cycle is complete  or until the suc   tion pressure rises above the suction pressure set point   When a stage is activated or deactivated  the RMCC will  wait the defined ON or OFF delay defined for compressors  and unloaders at the Groups 1 4 Pressure Set Points screen  before activating or deactivating the stage     A dash must be inserted after the last step or the  RMCC will assume all unused stages are configured  and should be off     Stages not defined are configured by default as all com   pressors OFF because no compressors or unloaders are se   lected for the stage  Therefore  after the last stage is  defined  enter a dash         to indicate that the defined step is  the last step in the cycle     The total combined horsepower for each defined cycle  is automatically calculated by the RMCC and displayed in  the HP field      em           Pee        Condenser Setup screen is where the condenser   s control  strategy  input types and locations  and fan types are spec   ified  The
341. rol  superheat is not being    Type Default Min Max Description  Value   20 0  F   120 0  F Average of installed discharge air temp  sensors     Case Temp Combina   tion Type    Set point Determines how case temperature read   ing of installed sensors will be com   bined  avg  max  min      Update Rate Set Point 6 seconds 1 second   60 seconds Determines how often the algorithm  will update the valve position     Table 8 3   Suction Side Temperature Control Parameters     m  DE                             is capable of supporting two types of valves   pulse and stepper  A pulse valve controls flow by pulsing  fully open and fully closed within a fixed period of six sec   onds     stepper valve controls flow by adjusting the valve  opening from zero to 100 percent using a fixed number of  steps     Both valve types are controlled using PID control  PID  control is explained in depth in Section 3 1   PID Control   However  programming the PID parameters for case con     8 2   Valve Control       trol is slightly different than programming for other sys   tems  In case control  throttling range  TR  and a multiplier  called integral gain  K   are both set by specifying a single  value called sensitivity     Sensitivity determines the size of the PID output s reac   tion to changes in the input  Sensitivity is set by entering a  value from 0 to 9  Zero is the lowest sensitivity and thus  will have a lesser reaction to error  nine is the highest sen   sitivity    The sensitivity l
342. rouping of times that designates when  the lights in the circuit cases will be ON or OFF  Up to four  schedules may be defined for assignment the standard cir   cuits  These schedules are defined at the Light Schedules  screen     At this screen  users are first prompted to name the cur   rent schedule  15 Characters   Users may then configure  the schedule in the From and Until fields  Enter the time  when the lights will be turned on in the From field and the  time when the lights will be turned off in the Until field   00 00   24 00   For each time period  designate the day of  the week the time period will take effect in the Event field    S unday   M onday   T uesday   W ednesday   Thu R sday   F riday  S A turday  or  7  Days      Up to eight holiday dates may be entered into the RM   CC   s Holiday Schedule  All lighting schedules will be  overridden OFF during any of the defined holiday dates   01 01   12 31   00 00      the default values for circuit defrost be entered since this  action guarantees that all necessary set points are estab    lished  Each set point may then be reviewed  revised  or  cleared as necessary     Circuit Name  12 Character Limit     The Circuit Name is a user defined or default system   defined identifier for the selected circuit     Master Liquid Line Solenoid   M aster LLS   1   4   Group LLS   N one   N     All hot gas circuits contain a master liquid line sole   noid  When using a refrigeration system other than the  Hussmann PROTOCOL   
343. ry Setpoint   99   999 or NONE    NONE     The Fast Recovery feature within the RMCC attempts  to prevent the discharge pressure from reaching the Trip  Point defined at the Pressure Setpoints screen  see Section  11 2 10  Group 1 Pressure Set Points   The set point en   tered in the Fast Recovery Setpoint field is the discharge  pressure or temperature at which the RMCC bypasses the  normal fan operational settings and cycles on all fans to  bring the discharge pressure or temperature down to an ac   ceptable level     The RMCC uses a default Fast Recovery Hysteresis of  2 0  This value is subtracted from the Fast Recovery set  point to determine the control input value below which the  RMCC will exit recovery mode  For example  if a condens   er s discharge pressure is above 300 psi when the Fast Re   covery set point is 300 psi  the RMCC begins fast recovery  mode  The RMCC will continue fast recovery until the dis   charge pressure drops below 298 psi  300   2 0      Fast Recovery Control Type  Evaporative Only    Ctl Value Max   Ctl Value     This field only appears in this screen when the Control  Strategy field in the Condenser Setup screen  Section  11 3 1  Condenser Setup  is set to EVAPORATIVE     RMCC I amp O Manual       The Minimum Condensing Setpoint is the lowest pos   sible value of the condensing setpoint  If the ambient tem   perature plus the temperature differential entered in the  Setpoint field  above  falls below the Minimum Condens   ing Setpoint  the 
344. s     026 1102 Rev 4 08 12 99        MI N    The          calculates the control value us   ing the minimum sensor reading of one or more sen   sors     Up to three sensors may be combined with the current  sensor  Enter the sensor number of the desired sensors to be  combined in the three fields following the field displaying  the current sensor number  The current status of the select   ed sensors are then displayed in the fields directly below  the sensor number fields  The current calculated control  value is displayed in the field directly below the Control  Using field     Cut On Cut Off   999   999   N one   O pen    C losed     Sensor Cut On and Cut Off set points may be defined  as specific values for analog input sensors or simply as con   tact closed or contact open for digital input sensors in the  Cut On and Cut Off fields respectively  The Cut In set  point is the value at which the controlled output will turn on  and the Cut Out set point is the value at which the con     trolled output will turn off  There is a 1   dead band around  each set point     Cut On Cut Off Delay  0   9999 seconds     The Cut On and Cut Off Delays are specified measure   ments of time the RMCC must wait before activating or de   activating the controlled output     Min time ON  0   240 minutes     When the Cut In set point has been reached and the  controlled output is activated  the output must remain on  for the Minimum ON Time regardless of the Cut Out set  point     Offset   99   
345. s    SELECT NUMBER    tem Description   Page    13 3 4  Anti Sweat Dewpoint Status  Screen                          ANTI SWEAT STATUS  FCALL ON  65 0 ADE BERS 25 0           p  Percent ON during ALL OFF    ALL ON   100  Current   Today  100 0       Dewpoint    The current dewpoint sensor reading or calculation is  shown in the Dewpoint field  To the right of this value  the  All On and      Off set points  specified in Section 11 4 10    Anti Sweat Circuit Setpoints  are displayed     Percent ON during All OFF AII ON    The Percent ON During ALL OFF and Percent ON  During ALL ON set points  specified in Section 11 4 10    Anti Sweat Circuit Setpoints  are displayed in these two  fields      On Time    The current ON percentage at which the selected cir   cuit s anti sweat heaters are operating is displayed in the  Current field  The average ON time percentage for the anti     026 1102 Rev 4 08 12 99    sweat circuit during the entire day is displayed in the Today  field     13 3 5  Anti Sweat Output Status          1      1 2     ANTI SWEAT OUTPUTS STATUS  Override          12 00  Time Left    8 Name  1     2   5   4     T PREV    NEXT  The real time status of anti sweat heater operation is    shown in the Anti Sweat Output Status Screen  Anti sweat  heaters operate by measuring dewpoint  comparing the    13 4  Case Control Status  13 4 1  Case Control Circuit Status    C        T  01 STATUS SD C 01    oar S  01          7 0  0 0        0  0  0  0    1  n  0  0    ENT Ne t t 
346. s  The current transducer values are shown    System Navigation     11 11    in the Curr fields  Any offset value entered in the Offset  fields are added to the current values   99   99   0      An offset for the discharge pressure transducer may be  entered using the screen shown in Section 11 8 12   Trans   ducer Offsets     11 3 3  Condenser Evaporative Inputs Setup        2  2  ka   CONDENSER EVAP INPUTS    TEMP Offset   TEMP Offset                                Offset   Offset                       1   2   3  Offset   4   5           T PREV                This screen is present only if the Control Strategy field  in Section 11 3 1   Condenser Setup  is set to    Evapora   tive     If the Air Cooled or Temp Diff strategies are being  used  this screen is replaced with the Condenser Pressure  Inputs Setup screen as shown in Section 11 3 2     The Condenser Evaporative Inputs Setup screen allows  users to specify the sensor types used for the evaporative  inputs and to calibrate sensors by specifying offsets     11 3 4  Condenser Fan Delays Setup    G2         CONDENSER FAN DELAYS SETUP       Fan Minimum On Time                    Fan Minimum Off Time 1000       T PREV               gt  SET DATA O MENU          Input Types  options   Temp     The types of sensors used as evaporative inputs must be  specified in the Input Type fields  There are two different  sets of choices to choose from depending upon whether the  Control Type field in Section 11 3 1   Condenser Setup  i
347. s  set to Temperature or Pressure     Temperature     TEMP   Standard temperature sensor    e  6450Tm   Margaux 6450 temperature sensor    Pressure   e 100 LB   100 pound pressure transducer    e 200 LB   200 pound pressure transducer    e 500 LB   500 pound pressure transducer   Offset   99   99   0     Offset values may be entered in the Offset fields to cor   rect sensor or transducer values  The current values are  shown in the Curr fields  Any offset value entered in the  Offset fields are added to the current values     Fan Minimum On Time  0   240 min    0 min      When condenser fans activate  they must remain on for  an amount of time specified in the Fan Minimum On Delay  field     Fan Minimum Off Time  0   240 min    0 min      When condenser fans deactivate  they must remain off  for an amount of time specified in the Fan Minimum Off  Delay field     11 3 5  Condenser Single Speed Setup Screens    The Condenser Single Speed Fan Setup screens are ac     cessible only if the Condenser Fan s  Type field is set to   Single Speed   Double  and variable speed setup screens  are described in the Condenser Two Speed Fan Setup and    11 12   Condenser Control    the Condenser Variable Speed Fan Setup sections  on Sec   tion 11 3 6  Condenser Two Speed Fan Setup and Section  11 3 7  Variable Speed Setup Screens respectively      026 1102 Rev 4 08 12 99    11 3 5 1  Single Speed Setup Screen 1       CONDENSER SINGLE SPEED FAN SETUP 12 00       Fan      Delay   sec           
348. s 1   6 for circuits 01   48     01 DEMAND  48 DEMAND    Demand defrost sensors 1 and 2 for circuits 01   48     Table 11 5   List of Inputs Configurable at the Input Definitions Screens    11 8 2  Output Definitions       OUTPUT DEFINITIONS  Output Bd  CMPO1                CMPOS          5  CMPO7                                                gt  SET DATA O MENU    All outputs connected to the 8RO  8RO Form C  4AO   8DO or 8IO boards are configured at the Output Defini   tions screen  Each output is identified according to its  board and point address     11 54   Configuration          Bd  1   20     The network address of an output communication  board is defined by the network dip switch on the 8RO  boards or rotary dials on the 8IO board  The number en   tered in the Board Number field is used by the RMCC in  conjunction with the Point address defined below to locate  the selected output     Pt  1   8     Each output is physically connected to a specific point  on an output communication board  The point numbers are  printed on the board above the output connections  This  point address is used by the RMCC in conjunction with the  board address to locate the selected output     Table 11 6 shows the specific outputs as they appear in  the Output Definitions screens     026 1102 Rev 4 08 12 99    Output Name  CMPO0I   CMP22  ALARM  DEMAND  SUBCOOLER  MASTER LLS  C  FAN  01   C  FAN  12  CI SPLIT 1   CI SPLIT 2  SEN CTL 01   SEN CTL 48  VS1 ALARM   VS4 ALARM    INV1 RESET   
349. s Network 4 1  defined 4 1  wiring 4 1  5 1  RS485 Input Output Network 4 1  max number of boards 4 1    wiring 4 1  5 1  RTC    Baud Rate Dip Switch Settings  4 5    S    Satellite Mode 11 64    Segments  See Wiring  Legs and Seg   ments     Self Test 11 56    Sensor Control 9 8  11 45    alarms 14 1   overrides 14 2  set points 11 46   controlled outputs 11 47   setup 11 45   log interval 11 46   sensor type 11 45  shut off schedule 11 49    Sensor Failure  See Case Control   sensor failure     Sensors    bullet and pipe mount  mounting 3 6  settings B 1  Checkit  hardware software settings  dewpoint probe  hardware software settings  B 1  IRLDS  hardware software settings  B 1  LDS  hardware software settings  light level  hardware software settings  liquid level  hardware software settings  B 1  mounting 3 6  outside temperature  location 3 6  mounting 3 6  pressure transducers  choosing Eclipse or standard  Eclipse voltage to pressure  chart C 1  hardware software settings  location 3 5  refrigerant transducers    Index    1 5    hardware software settings  B 2  refrigeration system  location 3 6  relative humidity  hardware software settings  B 2  temperature  settings B 1  temp to resistance chart C 1  wiring to 16AI or 810 5 3    Star Configurations 4 1  4 3    Status Screens  Anti Sweat Status 11 21  13 4     13 5  case control 13 5  liquid pulse stepper 13 5  suction stepper 11 32  condenser 13 1  host network 11 61  13 3  I O Network 13 3  inputs 13 3  main screen 
350. sary since  in both of these instances  the coil is emp   ty  To refill the coil and reestablish superheat  the valve is  opened a certain percentage for a fixed period of time  Af   ter the recovery period is complete  normal superheat con   trol algorithms are used  Table 8 8 describes how the  recovery time is determined     026 1102 Rev 4 08 12 99     Name   we                           Description     Maximum Recov  Set point 0 seconds 30   255 seconds Maximum amount of time valve will be  ery time left open to establish superheat     7  7096  0   10  0    100   Amount to open valve during recovery        Table 8 8   Recovery Parameters    Anti Sweat Control    The anti sweat algorithm controls the pulsing of the  anti sweat output to control the heat applied to the heaters   Table 8 9 lists the set points used to control the anti sweat  algorithm  The anti sweat control algorithm compares a  value sent by the RMCC to the high and low anti sweat set  points  Based on that reading  the algorithm pulses the heat   ers ON for some fraction of six seconds depending on  where the humidity reading falls within the anti sweat set    point range  See Section 3 5   Anti Sweat Control  for a  complete explanation of the anti sweat algorithm     The value sent by the RMCC may be from either a dew  point probe or a relative humidity sensor  The anti sweat  algorithm does not differentiate between the two types  it  only reads the raw value and compares it to the high and  low anti s
351. see        11 19  LD AD    Circuitinputs  iie bo Step iba p ORIS tecto 11 20  11 433  Circuit Statistics  ii e Ne LR NAA We eee eet Pee n de ERR            sire d ius 11 20  14 44   Circuit Set Points  senio PIC p ae bees 11 20  ELAS  Anti Sweat Control Menu  a E ERU DEC MERE CER IRE                     Pep c ate 11 21  11 4 6  Anti Sweat Status Menu  da eee eee re              i Ptr ER epe te ER Gi e rto        11 21  7147  Anti Sweat Setup    ss e he Rom      HERR ea e eise Hag ete eee bes 11 21  11 4 8  Dewpoint Humidity           iade e perdete RE REO SE                 iro              11 21  17 4 9 Anti Sweat  Outputs  Setups ic  ss iin ie teet ee ee o Uk EE RUE git            a             11 22  1 4 10   Anti Sweat Circuit Setpoints esee b a reat e e PER        Pa                 11 22  41 4    Anti Sweat Overrides    aed ah RR R   E e reb               ue eeu              11 22  71 412  Alarm Set Points  eoe eie rere eH RP re egi ete 11 23  HAS    Manual Defrost 2c eer o gt o RUE RR EE ae Shab ova cea ER RU e            11 23  LD ATA  Light Schedul  s     eee a ene ERN Rab ee ERE 11 24  TIL                      Schedule 2 33  e eerta tete e i eee ra dee aee p sera es 11 24  11 4 16    Circuit Setup 1    iustae rete ro p E RUD UR ERE TRE erede 11 24  11 447  Circuit Setup 25  eic gea ae UR SOR RUE ir oa ban ecl or            11 26  11 418  Circuit Set Points l c aee ERR Dp eO ER es dp epe e 11 27  144 19  Circuit Set Points 2    v RARE Sp Ned e IR RN ee eb   nd 11 28 
352. set  of user specified cut in and cut out set points  and turn an  output ON or OFF based on the results of the set point com   parison     Users may specify different cut in and cut out set  points for occupied and unoccupied building states  The  cell uses the occupied set points when the Occupancy input  reads HIGH and the unoccupied set points when the Occu   pancy input reads LOW     The Cut In Cut Out cell s digital signal is sent to the  Override cell     Override    The primary purpose of the Override cell is to provide  a method of overriding the Digital Command output to a  user specified value instead of the value dictated by the Cut  In Cut Out cell  Unlike other Analog Input Module cells   the Override cell may be accessed from the RMCC front  panel without using UltraSite  The RMCC s Analog Input  Module Bypass screen is shown below        ANALOG INPUT MODULE 01 BYPASS         INPUT 01       5  Command  OFF Type NORMAL   0005 minutes    Time    Ov State NORMAL  T PREV              gt  5           Figure 9 10   Analog Input Module Bypass Screen    The Override cell may override the Digital Command  output ON  OFF  or NONE  The override may be either  fixed or timed  A fixed override remains overridden until  the user deactivates the override using the Analog Input  Module Bypass Screen  A timed override remains in effect  until a user specified time period elapses or until the user  cancels the override     Counter    The Count cell simply increments the Count ou
353. shows the reclaim status  If a reclaim  is being called for  the Reclaim field will read ON  other   wise  it will read OFF     Fans    The bottom two lines of the Condenser Status screen  show the status of the condenser fans  If a fan has been giv   en a board and point address on the Output Definitions  screen  an    F    will appear by the fan   s corresponding num   ber  Otherwise  a period will appear by the fan number   Note in the sample screen shown above that fans 1   6 are  defined  F1   F6  and fans 7   12 are not   7    12      The fields directly below the fan numbers display the  current state of the fans  A fan will be shown as either on     ON    or off           If a fan is on or off because of a user or   dered bypass  an asterisk will appear next to the fan s status     ON  for bypassed on            for bypassed off      Phase Loss    When a phase loss occurs  all of the condenser fans are  bypassed off  The Condenser Status screen will display   PHASE LOSS  on occurrence so that the user can verify  that the condenser fans are bypassed off due to the phase  loss and not another condition     System Navigation     13 1    13 2  Status Menu       STAT S MEN 00     Main Statu   In ut Statu  5  aria le S ee        0 Net ork  5 Ho t Net ork    Statu     em                  Pss      13 2 1  Main Status                                 1 STATUS     22        c02           The Main Status screen displays the current status with   in each defined RMCC suction grou
354. sman Suction P N 810 3157  CPC  Standard  Suc  PIN 810 3159    Sporlan Stepper    Hussman Suction P N 810 3153  Stepper CDS Valve    Uses t P N 810 3152    CPC  Standard          P N 810 3155  Liquid Stepper SEI P N 810 3139     Includes Discharge Air Sensor  Coil Inlet Temperature Sensor   amp  Coil Outlet Temperature Sensor                Table 7 1   Required CPC Case Control Boards based on Valve Type and Case Control Type    7 1 1     The case controller enclosure measures 14 375 inches  long by 3 inches wide by 1 875 inches deep  The cover is  secured to the base plate by two 6 32 lock nuts  The base  has one 0 218 inch mounting hole located at each corner     Size    RMCC I amp O Manual    7 2  Power    Do not use the center tap of any transformer to pow   er the CCB  Do not use a single transformer to power a  CCB and another I O board  16AI  8RO  etc       The case controller should only be used with a Class 2   24 VAC  50 VA  transformer with no center tap  Wiring of    Case Control Installation     7 1    the case controller to the transformer is diagrammed in  Figure 7 1        Figure 7 1   Case Controller to Transformer Wiring    m               Valve Type Jumper  JU5   Stepper EEV Only     Set the valve type jumper  JU5  UP for 24V valves  AI   co ESV  amp  ESR Liquid Stepper  and DOWN for 12V valves   Sporlan SEI Liquid Stepper   See Table 7 2       Sporlan  ALCO SEI  ESV Liquid  Liquid Stepper  Stepper  S EEV     S EEV  CDS EEPR  Bipolar   12V     Bipolar    Al
355. sor  enter  O   On  or  F   Off    To return a compressor to normal operation  enter  N  for  Normal     Dchg Alm   Y es   N o   Y     The Discharge Alarm is generated when the Discharge  Pressure Trip Point is met  The Discharge Pressure Trip  Point is defined at the Group 1 4 Pressure Set Points  screens  see 7      Low Suct   20   999 Ib    1 0     When the measured suction pressure equals the Low  Suction Pressure set point  the RMCC will generate an  alarm     Dly  0   240 minutes   60    The Low Suction Time Delay is the duration the  RMCC must wait before generating an alarm when the  Low Suction Pressure set point is met     Proof         0   240 seconds   30     If a compressor proof has been defined for any com   pressor  the RMCC may be configured to issue an alarm if  a proof signal closure is not received after a specified dura   tion following a call for a compressor stage to activate  The  RMCC will generate a run proof failure alarm while con   tinuing to call for the compressor  The RMCC will also dis   play    FAIL    in the Proof field of the Pressure Control  Status screen  Section 13 9 2   Suction Group Status      System Navigation     11 3    Pump Down   20   999 Ib    0 5     The Pump Down alarm has a default setting of 0 5 Ib     Changing the set point to zero does not disable the  Pump Down alarm  The Pump Down alarm must be  disabled by placing a          in the pump down field of  the Pressure Alarms Notices Setup screen  Section  11 2 4  Pressure 
356. sor failure 11 34  door alarm delay 11 35  leak alarm level 11 35  refrigerant leak 11 35  assigning CCBs to circuits 11 43  backing up CCB setpoints 12 2  case set points  CPC suction stepper 11 33  derivative gain 11 37  frost sensor 11 34  offsets 11 36  sensitivity 11 33  temp sensor strategy  11 37  update rate 11 34  valve multiplier 11 37  Hussmann suction stepper  demand sensor 11 34  liquid pulse stepper  anti sweat limits 11 33  case dead band 11 36  close rate percentage  11 36  coil out fan lockout 11   36  demand sensor 11 33  derivative gain 11 36  hysterisis 11 37  max number of steps  11 37  max step rate 11 37  offsets 11 36  recovery 11 33  sensitivity 11 33  superheat 11 33  valve bypass percentage  11 35  valve multiplier 11 36  valve type 11 37  copying CCB set points 11 44  copying log points 11 44  initializing CCBs 11 43  restoring CCB set points 11 44  sending CCB settings 11 43  set points  alarm time 11 42  case pump down delay 11   41    control temp 11 40   demand fail safe time 11 42   discharge return weighting  11 40    Index    1 2    drain time 11 40   fan and anti sweat off 11 40   termination temp 11 40   valve control strategy 11 40  setup   anti sweat control 11 41   defrost schedules 11 40   defrost termination 11 39   defrost type 11 39   demand defrost 11 42   dual temp shift 11 41   inputs 11 44   shut down if suction group   fails 11 41   temp control strategy 11 40   valve control strategy 11 39  updating CCB information 11 43    Ci
357. sors unloaders have   Compressors unloaders have  ON and OFF delays minimum ON and OFF times    Table A 1   Differences between RMCC and RMCT    Only Normal variable speed    PIDA Control    The RMCT s PIDA control is similar in most respects  to the RMCC s PID control  see Section 3 1   PID Con   trol   except that a fourth mode  called the acceleration  or     A   mode  is working along with the proportional  inte   gral  and derivative modes  The A mode is closely related  to the derivative mode  which attempts to compensate for  sudden changes in the control input  The acceleration mode       watches the derivative mode and  speeds up  the system  when necessary to help the derivative mode compensate  quicker     Variable Speed Control    RMCT compressor groups operate much the same as  RMCC compressor groups using Normal control  see Sec   tion 3 2 1 1   and Normal variable speed compressor con   trol  see Section 3 2 2 1    The Fixed steps strategy and  Alternate variable speed strategy may not be used in  RMCT groups     Like RMCC variable speed compressors  RMCT vari   able speed compressors are always the first on and the last  off in a group  and the RMCT only looks for new standard  compressor combinations when the compressor is either at  maximum  100   or minimum speed  The major differ   ence is in the way the RMCT selects compressor combina   tions and speeds     The RMCT attempts to stabilize the suction pressure at  the set point while keeping the variable sp
358. ss     Bd  1   20     Table 11 5 shows the specific inputs in the order they  appear within the Input Definitions screens     The network address of an input communication board  is defined by the network dip switch on the 16AI board or    Input Description  G1 SUC PRS   G1 SUC TMP   CI DIS PRS        DIS TMP   CI IN PRS        OUT PRS  ASW HUMID  ASW TEMP   G2 SUC PRS   G2 SUC TMP  ASW OVRD 1  4  G3 SUC PRS   G3 SUC TMP  ASW OVRD 5  8  G4 SUC PRS   G4 SUC TMP        EVAP 1 5   CI INV ALM  PHASE LOSS  KW ANALOG   C1 IN TMP        OUT TMP  AMBIENT   CI RCL STA    Group 1 Suction Pressure    Group 1 Suction Temperature    Condenser Discharge Pressure    Condenser Discharge Temperature    Condenser Inlet Pressure    Condenser Outlet Pressure    Anti Sweat Relative Humidity sensor    Anti Sweat Temperature sensor    Group 2 Suction Pressure    Group 2 Suction Temperature    Anti sweat override  1 through  4    Group 3 suction pressure    Group 3 suction temperature    Anti Sweat override  5 through  8    Group 4 suction pressure    Group 4 suction temperature    Condenser evaporative cooling sensor 1 through 5   Condenser inverter alarm    A contact closure from a phase monitor will cause the RMCC to turn off all loads   Kilowatt analog input from the watt hour transducer   Condenser inlet temperature    Condenser outlet temperature  used if temperature strategy is selected for condenser control      Ambient  outside  temperature input     A contact closure when the system goes i
359. ssor Start Delay defined in the Compressor  Start Delay field  This delay allows pressure equalization  within the system  To define the delay  enter a value be   tween 0 and 10 minutes in the Compressor Start Delay  field     Defrost Suction Set Point   999   999   10 0   After the compressors within the host group have been  shut down for the Compressor Start Delay  they are cycled    to maintain the Defrost Suction Set Point defined in the De   frost Suction Set Point field  To define the Defrost Suction    System Navigation     11 31    Set Point  enter a value between 1 and 50 psi in the Defrost  Suction Set Point field     11 4 26 Advanced Defrost Options  Electric        fa  falta  ae fa         CIRCUIT SETUP   Z 1             DEFROST LOAD SHEDDING OPTIONS       Host Compressor Group    Electric defrost Amps       0  0000               gt  5              O MENU       Hussmann PROTOCOL   Advanced Defrost Set Points  for Advanced Electric Defrost are defined at the Advanced  Defrost Options  Electric  screen  This feature analyzes the  number of amps drawn by each compressor within the cir   cuit   s suction group  defined in Section 11 2 7  Group 1  Setup   compares it to the load that will be drawn by de   frost  and interlocks one or more compressors in order to  shed enough load to compensate for defrost     11 4 27 Case Control       Case set points may not be viewed until a case control     ler is physically attached to the RMCC I O network     11 4 28 Circuit Set 
360. ssure transducers  0 100 Ib  for  suction pressure  0 200 16  for oil pressure  and 0 500 Ib   for discharge pressure  Each is generally installed on the  system by the equipment manufacturer  If a transducer  must be added to the system  consult the refrigeration  equipment manufacturer for proper location     Mounting    In high humidity environments  mount the transducer  so that the cable is at the bottom or side  This prevents cre   ating a moisture trap  However  if pressure media might  freeze  mount the transducer with the pressure port pointing  down     Hardware Mounting     3 5         pu m    3 7 1  Outside  Ambient  Temperature    Sensor  Location    The outside or ambient temperature sensor should be  located on the north side of the building  preferably under  an eave to prevent sun heated air from affecting the tem   perature at the sensor     Mounting    The temperature sensor may be mounted using any  standard tubing clamp  CPC also offers an aluminum cover  and clamp which may be mounted as shown in Figure 3 12   fasteners are not provided         Figure 3 12   Outside Temperature Sensor with Cover and  Clamp    3 7 2  Refrigeration System Tempera     ture Probes and Sensors    Location    CPC supplies several temperature monitoring devices  including bullet sensors  pipe mount sensors  immersion  probes  insertion probes  and sensors for high temperature  applications  Each of these sensors is generally installed on  the system by the equipment manufacture
361. st sequence   Emergency defrost is practically identical to the normal de   frost sequence initiated by pressing    1     except the emer   gency defrost ignores the values of termination sensors and  defrosts for the full defrost duration  defined in Section  11 4 18   Circuit Set Points 1   The only way an emergency  defrost may be terminated before the full defrost duration  is to select the End    2    option from the manual defrost  screen     System Navigation     11 23    11 4 14 Light Schedules    aum eee       11 4 15 Holiday Schedule       Him ou    HOLIDAY SCHEDULE  Date    1       00 00     00 00     00 00                                                                   11 4 16 Circuit Setup 1     CIRCUIT SETUP    1                      Case Type   1000    gt              Enter Defaults   No  Circuit Name    Master Liq Line Solenoid                                                     gt  SET DATA O MENU       All standard circuits defined within the controlled sys   tem are setup using the Circuit Setup screens     Case Type  0   64   0   The type of case controlled by the selected standard cir   cuit is defined in the Case Type field  Users may choose    from the case types displayed in Table 11 3  Select any key  to view a list of all available case types     Enter Defaults   Y es   N o   N     Default configuration information for all available case  types is stored within the RMCC  It is recommended that    11 24   Circuit Defrost Control    A schedule is a g
362. stomize control of mechanical components     9 9 1  Cells and Modules    I O Control is best defined as the process of reading a  sensor value  comparing the value to a set of user defined  set points  and activating or deactivating a load based on  the comparison  Unfortunately  control of large systems re   quires multiple layers of set points that have different pri   orities and control many loads  To simplify this complex  array of set points  the RMCC uses the concept of cells and  modules     Cells are groups of set points that share common func   tions or priorities  such as Override or Proof set points   While different types of cells perform different functions in  different applications  all cells are basically alike in their  operation     cell reads one or more input values  applies  these values to the cell s settings and set points  and exports  one or more resultant values as outputs  Depending upon  the set function of the cell  the cell   s outputs may then be  used as inputs for other cells or modules  or they may be  used to drive physical devices     The number of cells used within the RMCC s I O mod   ules is fixed and comprises the various controlling features  of the RMCC  such as Alarming  Logging  Overrides  By   passing  etc  The arrangement of these cells may not be  changed  The user may choose to use certain cells and not  others  but may not add  delete  or rearrange features in the  RMCC     Various cells that share a common bond such as manip 
363. system  there will be a single  master liquid line solenoid for all groups controlled by the  RMCC  enter    M   aster in the Liq Line Solenoid field   When using a Hussmann PROTOCOL   system  the group  supplying the circuit will have its own master liquid line  solenoid  enter the number of the suction group within  which the solenoid is located     If the selected circuit is not a hot gas circuit  enter     N    one in the Master Liq Line Solenoid field     026 1102 Rev 4 08 12 99    Defrost Type  High Low                                   Description Time   Time Time  Spare Spare for future use  RMCC defaults the case type to this set                               lcecreamfeezerbox       20  560   30 60  sno  2 45  2 60  7 60         Reacinfreezrjuce            i15  560   2015         1 45 veoj 1 60     9           Fwenfoodbo M   I12  560   2015  3718  3745  2 60  2 60    Table 11 3   Case Type Default Settings       RMCC I amp O Manual System Navigation     11 25                  Defrost Type    PIN    75 30    2 4    5  5    245  2 60       S0 PRPR  Produce preproom   35  eseoj 45 0 one  2 45  2 45  2590       Table 11 3   Case Type Default Settings    11 4 17 Circuit Setup 2       834419 ug      CIRCUIT SETUP     1  Defrost Type    Defrost Termination Type                            Termination Sensors  Temperature Strategy      Temp Sensors Strategy    Fans On During Defrost                                  T PREV               gt  SET DATA O MENU    All standard circ
364. t           2       a  Ran          CIRCUIT                      1  Case Lights Strategy  Case Pump Down Delay                            Shut Down if Sic ioh Grp Fails   Anti Sweat Control   Dual Tmp Alarm Set Point Shift   Dual Temp Shift Input                            T PREV              gt  SET DATA    Circuit set points for lighting  pump down  anti sweat   and dual temperature features are defined at the Circuit Set  Points 2 screen     Case Lights Strategy  Always  O n  Always O F f   Schedules  1  2  3  4      Lighting control within a case control circuit is deter   mined by the Case Lights Strategy  Users may choose from  the following Case Lights Strategies       Always  O n   lights in the case are always on  e Always O f f   lights in the case are always off       1234  Schedules   lights in the case cycle on and  off according to the selected schedule  Schedules  are configured at the Light Schedules screen  see  Section 11 4 42  Light Schedules      Case Pump Down Delay  0   240 seconds     Defrost performance is improved by specifying a dura   tion during which the system empties or    pumps down  re   frigerant from the evaporator coil  This procedure ensures  that residual refrigerant for the coil does not work against  the defrost cycle  When this delay is activated within a  Case Control Circuit  the Suction Valve is opened for the  defined delay before the defrost cycle begins  During this  delay  the Pulse Width Modulation and Defrost Valves are  also 
365. t to the UP position     5 12  Terminating Resistance Jumper Settings    S2                             45                   mm                                                                                 INPUTS 9 16           Set DOWN for  sensors requiring  voltage      SetUP for  sensors not requiring    voltage    26501070    Figure 5 16   Input Type Switches  S1 and 82     026 1102 Rev 4 08 12 99    6 Case Control Hardware  Overview    This section provides complete information for install   ing and programming all versions of CPC s case controller   Information is also given for both the CCB and defrost  power modules  which are designed to provide power with   in the space restrictions of the refrigerated case  The sec   tion should be used in conjunction with the other sections  within this manual to configure a complete refrigeration  control system  Information for controlling refrigerated  cases without case controllers is provided in Section 2   Hardware Overview  and Section 9  Software Overview     6 1  Introduction    A case controller is typically designed to control all re   frigerated case functions including lights  fans  defrost   anti sweat  and suction side or liquid side valve control     6 2  Hardware Description  6 2 1     CPC produces two different hardware versions of the  case controller to interact with either a pulse valve or step   per valve     Case Controllers    The pulse valve case controller  Figure 6 1  may be  configured with a second 
366. tance between the refrigerant temperature  and the ambient  outside  temperature  Refrigerant con   densing temperature is measured from the condenser inlet   condenser outlet  or discharge using a pressure transducer   The pressure value is automatically converted to tempera   ture based upon the refrigerant type defined in the system  software  The resulting temperature value is compared to  the ambient temperature value plus the condensing temper   ature differential value  specified by the user      MINIMUM    CONDENSING AMBIENT CONDENSER CONDENSING    TEMP   TEMP DIFF   SETPOINT  SETPOINT           Kk     Condensing    Setpoint will           go below this value        SETPOINT         CONTROL PRESSURE   converted to temperature     26512027    Figure 9 4   Temperature Differential Strategy    As shown in Figure 9 4  the PID set point is propor   tionally changing in the Temperature Differential strategy  based on the ambient temperature value  Therefore  to pre   vent the PID set point from dropping too low during cold  weather  a Minimum Condensing set point may be defined   If the combined total of the ambient temperature and the  condensing temperature differential is less than the Mini   mum Condensing set point  the Minimum Condensing set  point becomes the new PID set point     9 5 1 2  Evaporative Condensers    The RMCC uses a single strategy to control evaporative  condenser fans  This strategy uses either the average  the  highest  or the lowest of up to five s
367. ted on the processor board of the RMCC are  used to set the baud rate  A different baud rate setting may  not be set for the COM A and D networks     Positions six and seven on dip switch S1 of the 4       8RO  and 8RO FC  and switch S3 of the 16AI  are used to  set the baud rate for the communication boards  This baud  rate should match the setting for the RMCC  Figure 5 15  shows the possible baud rate settings and dip switch posi   tions for the COM A and D networks     COM A AND D  BAUD   RATE  BAUD WIN y  PRESET AT 4800               nm    COM A AND D     BAUD RATE NG  4AO  8RO  AND 8RO FC     SWITCH S1   16     SWITCH 53                                                           REFLECS PROCESSOR  BOARD    29600 4800 1 9200 38400                 26501045    Figure 5 15   Baud Rate Dip Switch Settings  5 10 1 1  Case Controllers    If using case controllers  the baud rate setting for COM  A and D must be set to 19 200 since the baud rate for the  case controller is hard coded at 19 200  Refer to Section  4 12   Baud Rate Dip Switches  COM A and D only   for  more information     5 10 1 2  8IO Baud Rates    Baud rate settings for the 8IO board are automatically  adjusted by the board based on the baud rate setting of the  RMCC  The 8IO can communicate at baud rate settings be   tween 4800 and 38 400     Communication and Power Connections     5 11    5 10 2  COM B Network    The COM B baud rate is preset on the RMCC and 485  Alarm Panel dip switch S1 at 4800 since the 485 
368. ted to COM C may not exceed  2500 feet     4 7  Number of Devices per Seg     ment    A single segment beginning with a REFLECS control   ler may have no more than 31 additional devices  A device  is considered to be any controller  board  or alarm panel   There are restrictions to the number of each board type that  may be connected to the COM A and D networks     No more than sixteen 8ROs or 8RO FCs  sixteen  16AIs  three 4AOs  and two 8DOs may be connected to  both the COM A and COM D networks at the same time   In addition  an 8IO board must be listed as one 16AI and  one 8RO     4 8     Except for the single star configuration described be   low  all devices in a segment must be connected in an open  loop or    daisy chain  configuration  A daisy chain must  start with the first device in the segment and continue to the  last device  Branching from a device in the middle of the  segment is prohibited  Figure 4 5 demonstrates correct and  incorrect daisy chain configurations     Daisy Chains    026 1102 Rev 4 08 12 99         BOARD      NETWORK                CPC  CONTROLLER                            END OF SEGMENT    CORRECT LOOP  CONFIGURATION    INCORRECT LOOP  CONFIGURATION    26513037    Figure 4 5   Correct and Incorrect Loop Configurations    4 9     Within a single segment  a single star branching from a  single device is allowable  A star is multiple devices con   nected to a single device within a segment  The device from  which the star extends is called the h
369. terminal  polarity insensitive      2  Set input dip switch up        Various    Digital Sensors   Klixons  Sail  Switches  etc      16AI Any   Available Point  8IO Any Avail   able Input Point    ARTC An Aux  Input       1 Connect one lead to the odd  numbered terminal and the other  lead to the even numbered termi   nal  polarity insensitive            2 Set input dip switch up        ODD    TERMINAL    EVEN    TERMINAL       800 1100  800 1200  800 1500    Pressure Trans   ducers  Eclipse   100  200  500  Ib  ratings    Table 5 1   Sensor Wiring    RMCC I amp O Manual    16AI Any   Available Point  8IO Any Avail   able Input Point    ARTC An Aux  Input      Connect RED power wire  to  5VDC supply on  input board        Connect WHITE signal EL  wire to even numbered      ae    1     terminal    SHIELD  BARE  WIRE    Connect BLACK ground     TO ODD   TERMINAL  wire to odd numbered ter   minal        WHITE TO   gt  EVEN   TERM       BLACK TO  ODD   TERM                                       Connect the bare  SHIELD wire to odd  numbered terminal        TRANSDUCER       ECLIPSE          Set input dip switch  down                       Communication and Power Connections     5 3    800 0100  800 0200  800 0500    Pressure Trans   ducers  Stan   dard  100  200   500 Ib  ratings    Connect to  Input Point  by Board    Type    16AI Any   Available Point  8            Avail   able Input Point    ARTC An Aux  Input    Connect RED wire to   12VDC source on input  board    Connect WHI
370. the coil outlet  temperature reading is 35  F above the control set point for  60 minutes  the case controller will go into sensor bypass   During sensor bypass  the case controller controls the valve  using the Default Valve Percentage defined under CCB Set  Points in the RMCC System Navigation     Coil Inlet and Coil Outlet Sensor Failure    If both the coil inlet and coil outlet read open or short  the case controller will go into sensor bypass  During sen   sor bypass  the case controller controls the valve using the  Default Valve Percentage defined under Case Set Points in  the RMCC  page 51     Discharge Air Sensor Failure  Liquid     If the discharge air sensor reads open or short  or if the  discharge air temperature reading is 15  F above the control  set point for 15 minutes  when not in defrost   the case con   troller initiates recovery mode  see Section 8 6   System  Recovery Mode    After the recovery sequence is complete   the case controller will return to normal control  The case  controller will wait another 15 minutes before repeating the  recovery sequence again     Discharge Air Sensor Failure  CPC Suction     If the discharge air sensor reads open or short  the  RMCC writes a case fail alarm to the Alarm log     Discharge Air Sensor Failure  Hussmann Suction     If the discharge air sensor reads open or short  or if the  discharge air temperature reading is 15  F above the control  set point for 15 minutes  when not in defrost   the case con   troller i
371. the main processor  and the memory chips that hold  all the code required to operate the RMCC and the data en   tered at the front panel or through UltraSite  The Processor  Board is mounted on the door of the enclosure and is con   nected to the PIB with a ribbon cable  The PIB  Figure 2   2  contains all power and network connections required to  power the RMCC and drive the network  and is attached to  the rear wall of the enclosure     Hardware Overview     2 1       LCD Screen Contrast Dial       Main Processor Chip    Ribbon Cable Connection to Power  Interface Board       Ribbon Cable Connection to Keypad    RAM Battery       Flash Memory Chips    Clock Battery       Manufacture Date    Network Baud Rate Dip Switch       RAM Chips          26502005       Figure 2 1   REFLECS Processor Board       Board    Remote Communication Network  Connection  COM C        COM B Termination Resistance  Jumpers         Network Connection  COM D        COM D Term  Resistance Jumpers                 Termination Resistance  Jumpers    LED Power Indicator       Power Switch       Network Status Lights  4 places     AC Power Input Connection            Network Connection  COM        AC Input Power Fuse          Host Network Connection  COM B        AC Voltage Jumpers  26502016       Figure 2 2   Power Interface Board    2 2  Input Communication Boards       2 2  Input Communication  Boards    To properly interact with any environmental control  system  the REFLECS requires constant  accur
372. timed override will last     Ov State    The Ov State is a read only field that shows the current  state of the Command override  either Fixed  Timed  or  Normal      Time Left    The Time Left field is a read only field showing the  amount of time left in a timed override  When no timed  override is being carried out  the Time Left field will dis   play a row of dashes     System Navigation     11 51    11 7  Power Monitor       POWER MONITORING 12 00    1 Demand Status  2 Demand Setpoints    3 Hourly Logs    4 Daily Logs    SELECT NUMBER    11 7 1  Demand Set Points       DEMAND SETPOINTS          Demand Setpoint   KW TRANSDUCER  Minimum Voltage  Maximum Voltage  Power at Maximum                          Demand Set Points are defined at the Demand Setpoints  screen     Demand Setpoint  0   9999     Enter the appropriate demand limit set point in kilo   watts in the Demand Setpoint field  If the power usage ex   ceeds this set point  the RMCC will activate a closure in the  demand relay  A demand relay must be configured at the    11 8  Configuration       CONFIGURATION 12 00  1 Input Definitions  2 Output Definitions  3 System Information  4 Remote Communication    5 Xducer Setup  6 Host Network  7 1 0        Setup  8 Sat  Comm     9 Xducer Types    SELECT NUMBER    11 52  Power Monitor        em           Pese         Output Definitions screen  see Section 11 8 2  Output Def   initions    kW Transducer   To calculate the current energy consumption  kW trans     ducers read
373. ting baud rate 11 60  setup initialization strings 11 60  types supplied 2 6   Modules  inputs and outputs 9 9    N    Network  searching for new devices 11 62  setting device numbers 11 62  Network  Host  reset 11 62  Network  IO Board  reset 11 64    NONE  digital state  9 9          Output Definitions 11 54    P    Passwords  access levels 11 2  entering 11 2  logging logons 11 56  setting 11 56   Phase Loss    shutting off compressors during  11 6    PIB  features 2 2    PID Control 9 1    analog output modules 9 16  case controllers 8 2  condenser fans 9 4   definition of 9 1   definition of throttle range 9 1  derivative 9 1   error 9 1   integral 9 1   pressure 9 2   proportional 9 1    026 1102 Rev 4 08 12 99    update rate 9 1  PIDA Control A 1    Power Monitoring 11 52  demand setup 11 52    Power up Self Test  See Cyclic Re   dundancy Check    Power up Self Test  See Cyclic Re   dundancy Check     Pressure Control 9 2 9 4  11 2  alarms setup 11 3  11 5  automatic oil reset 11 4  bypass 11 3  Copeland oil system 11 4  discharge trip 9 6  discharge trip point 11 8  fixed step strategy 11 7  11 9  Fixed Steps strategy 9 2  floating set point 9 4  forcing one compressor ON 11 7  forcing one compressor on dur    ing defrost 11 7  log interval 12 1  max number of compressors 9 2  PID Control 9 2  proofs 11 6  13 11  running one compressor during  reclaim 11 7  set points  variable speed 11 8  setup 11 5  11 6  setup  two stage system 11 7  unloaders 11 6  13 11  variable
374. tivates a sensor se   lection screen where users select  or may enter  the appro   priate sensor number  The selected sensor number and the  defined type of the selected sensor are displayed at the Sen   sor Set Points screen in the   and Type fields respectively     Eng  Unit  5 Character Limit     The RMCC reads a signal from the sensor and com   pares the signal to the sensor type to determine the correct    11 46   Sensor Control       analog value  Therefore  units of measure are not important  to the           As a convenience to the user  a Units field is  provided so that analog values displayed on the RMCC  screen are easily interpreted  Enter the corresponding units  of measure for a specified sensor type in the Eng  Unit  field     Control Using   D ifferential or 1st Only   A vg   Ma X   Mi N    D     The control method defined in the Control Using field  determines how to combine the values from up to four sen   sors  This combined or control value is then compared to  defined set points and commands to determine the opera   tional status of an output  Users may choose from the fol   lowing four control methods     e           Ist Only   The RMCC calculates the dif   ferential of two sensors or uses the primary sensor  value as the control value     e  A VG   The          calculates the control value us   ing the average reading of one or more sensors     e MA X   The          calculates the control value us   ing the maximum sensor reading of one or more  sensor
375. to ensure proper communication between net   work devices and effective control of refrigeration equip   ment  Unless noted  all information in this section pertains  to COM A  B  C  and D networks  Information provided in  Section 5  conform to these requirements     Wiring Specifications    Network wiring must meet or exceed the following  specifications   RS485  COM     B  and D     Shielded twisted pair  18   24 AWG wire    31 pf ft maximum capacity between signal wires    59 pf ft maximum capacity between signal and  shield    120   50 ohm nominal impedance    Belden part number 8641  for plenum installations   82641 or 88641     RS232  COM C     Shielded    22 AWG wire    23 pf ft max cap  between signal wires    41 pf ft max cap  between signal and shield    Belden part number 8771    RMCC I amp O Manual    5 2                    Wiring    Connect the three wire COM A or COM D network ca   ble to the REFLECS and I O board 485 network connec   tions as shown in Figure 5 1     POWER INTERFACE BOARD    TR PS       OMD    POWER  ON    e POWER  IN    eco  GND NEU HOT    TBI           SEXES       COMMUNICATION    OTHER PORT    BOARDS    26513032       Figure 5 1   COM A Network Connections    5 39  COMB Wiring    Connect the three wire COM B network cable to the  REFLECS controllers and 485 Alarm Panel as shown in  Figure 5 2              POWER INTERFACE BOARD  PIB  485 ALARM PANEL PIB             ON         D so   TBI RS485     2 RS485 A POWER ALARM   GOMA     0     comc   
376. tput val   ue every time the digital Command output turns ON  The  initial value of the Count output is entered by the user  as  well as the amount the Count output is incremented every  time an ON is detected     Software Overview     9 11    If desired  the Count cell may also be configured to turn  on a digital output whenever the Count value exceeds a  user specified Trip Setpoint  This digital output  called the  Count Tripped output  may be connected to a relay on an  alarming device  or it may be used as an input for another  I O Module     The Count output value is reset by sending a signal to  the Reset Count input  The user specifies whether the count  will be reset when the Reset Count is ON  OFF  or transi   tioning from ON to OFF  When the appropriate type of sig   nal is read from the Reset Count output  the Count output  reverts to the initial value specified by the user     Digital Output Module    Counting may be suspended via the Suspend Count in   put  While this input is ON  the Counter will not increment  the Count output regardless of the state of the Command  output     9 9 2 2  Digital Output Module    General Description    The primary purpose of a Digital Output Module is to  combine up to four digital values into a single digital value   which may drive a physical relay or be used as an input for  other modules  In addition  the Digital Output Module may  be configured to count the number of Output transitions   and it may be set up to detect proof 
377. ttings that keep one or more compres   sors on during defrost and reclaim modes     RMCC I amp O Manual    Requested  Horsepower   HP        Adjust Variable Speed  compressor RPM   Requested HP   Current  Rack HP     5  increase   decrease amount              Is an increase or  decrease necessary     Is the   5  at the  minimum     INCREASE             Are all standard  compressors  OFF     Is the VS  at maximum             Activate deactivate a standard  compressor combination  to satisfy the HP requirement                   Turn VS compressor off                    26512026             Figure 9 3   VS Compressor Control Flowchart  9 4 2 2  Alternate Strategy    The Alternate strategy is very similar to the Normal  strategy described above  except that the VS compressor is  not always the first compressor on  Instead  when the           calls for the first compressor s  to activate  it takes  into account the amount of HP needed and considers acti   vating a combination of standard compressors to meet the  requirement  For example  if 5 HP is needed and there is a  5 HP standard compressor in the group  the RMCC may ac   tivate the standard compressor rather than activate a 15 HP  variable speed compressor     In order to determine whether the first compressor on  will be variable speed or standard  the RMCC compares  the required HP amount to the VS HP On Edge set point   The VS HP On Edge set point is a horsepower value below  which the variable speed compressor will not b
378. ttings will  be changed to daylight savings time starting on the date de   fined in the DST MANUAL SET START field  and will re   turn to standard time on the date defined in the DST  MANUAL SET END field  System time changes at ap   proximately 2 00 a m on the dates specified     Because the defined dates are specific for each year  the  Date fields must be updated each year by the user     Alarm types within a category marked with a YES will be  sent to the 485 Alarm Panel  alarm types within a category  marked with a NO will not be sent to the alarm panel     The ten different alarm filter categories and the alarm  types within each category are listed below  For additional  information on alarm types  see Table 14 1 on page 5     e Ckt Hi  Circuit High    This alarm type includes the  Hi Temp and Hi Avg Temp alarms     e Checkit  This alarm type includes the Check Sys   tem Now and Check System Soon alarms       Sens Hi Sensor High    This alarm type includes  the Hi Sens and Hi X Ducer alarms generated by  Sensor Control       Sens Lo  Sensor Low    This alarm type includes the  Lo Sens and Low Avg Temp alarms generated by  sensor control       Sens Fail  Sensor Fail    This alarm type includes  the IRLDS Fault  Sensor Fail  Sensor Short  Sensor  Open  Xducer Short  and Xducer Open alarms     System Navigation     11 57    e Comp Pres  Compressor Pressure Alarms    This  alarm type includes the Auto Reset  Discharge  Tripped  Hi Suction  and Oil Pressure alarms     e Ref
379. u            inerte iP DR P ree res 11 62  116 16  On Eine St  tus   iia quee OG a EE ERROR                                      11 62  145 17  S  t Device Numbers        ER DR RE EPOR PR                   11 62  T4 8 15     Reset  ida RR eo p n tbe ate d ED    e                   11 62  11 86 19                                                                                       e rb Der OE ee rte          E 11 63  11 6 20  I O Bo  rd Setup    eer E E cO E RE pave RARE OR Feo steven DUREE X E 11 63  1 86 21    Set Device Numbers    en ed eee eret he ER gre e i esee Pi PP E ERR eti          11 63  74 68 20                                  ee eu e cone ER aie            b ten deo etie ecol piena 11 64  11 8 23  Satellite  Communication sisses duse eene t OH eerie e a        Hs ebrei 11 64  11 8 24    Pressure Transducer                           E ESES OT EE O 11 64  12 SYSTEM LOGS AND                            2      2   1 1 1  1                                                                                                                     12 1                       age                                        d UR 12 1  72 11  Suction  Pressure Log Interval          n sio e be Oi te ee DR RE SR                       12 1  12 1 2  Suction Group L Logs           Co d ER EXER i re E ERE                   12 1  12420  Anti Swe  t Daily Logs iive ise e d deem eva ese bu        e ete ae gere ee eve rd 12 1  12 1 4  Standard Circuit                                         er D 
380. ub  The legs within a  star may not exceed 100 feet  No more than one star in a  single segment is permitted  Star configurations are not  permitted on the COM B  Host  and COM C  Remote Com   munication  networks  Figure 4 6 shows correct and incor   rect star configurations     Star Configurations                                              ORRECT STAR  ONFIGURATION                                     INCORRECT STAR       CONFIGURATION    F                      CORRECT STAR  CONFIGURATION                26513049    Figure 4 6   Correct and Incorrect Star Configurations    4 10  Terminating Resistance  Jumpers  COM A  COM B   and COM D Only     Each device that may be connected to a network seg   ment has a set of terminating resistance jumpers  one jump   er for each wire lead   These jumpers are always labeled  JU1  JU2  and JU3 for COM A  COM B jumpers are al   ways labeled JU4  JU5  and JU6  COM D jumpers are al   ways labeled JU9  JU10  and JU11     RMCC I amp O Manual           The purpose of the jumpers is to indicate the two ends   or termination points  of the segment  If a segment contains  a star  the hub of the star must be one of the segment termi   nation points  The other termination point in the star con   figuration is the longest leg contained in the network     If a device is at either end of a segment in a daisy chain  configuration  Figure 4 7   or if the device is the hub of a  star configuration  Figure 4 8   the terminating resistance  jumpers must b
381. ue above which the controlled output will turn on  The Cut  OFF set point is the value below which the controlled out   put will turn off  There is a 1  dead band around each set  point     Cut On Cut Off Delay  0   9999 seconds     The Cut On and Cut Off Delays are specified measure   ments of time the RMCC must wait before activating or de   activating the controlled output     026 1102 Rev 4 08 12 99    11 5 5  Shut Off Schedule 1     8       SHUT OFF SCHEDULE  SHUT OFF TIME  FROM  day                                              T PREV                                                                                                    INPUT OUTPUT CONTROL   1  Analog In Status  Analog Out Status  Digital Out Status  Analog In Bypass  Analog Out Bypass  Digital Out Bypass    SELECT NUMBER    11 5 8  Analog Input Module Bypass    uw       ANALOG INPUT MODULE 01 BYPASS  Name        INPUT 01  Enable NO                               Command HOFF Type  NORMAL  Time 10005 minutes          Ov State NORMAL  T PREV J NEXT   gt  5        RMCC 1 amp 0 Manual       A Scheduled Override bypasses normal sensor opera   tions according to the schedule defined at the Shut Off  Schedule 1 screen  The defined override schedule is acti   vated when assigned to selected sensors at the Shut Off  Schedule 2 screen     To define the schedule override  enter the schedule start  day and time in the FROM field and the schedule stop day  and time in the UNTIL field  Fixed  timed  and manual  overrides 
382. uit               Description Page  CIRCUIT CONTROL 12 00    Status  Logs Graphs      Anti Sweat  Light Schedules      Alarm Set Points  Setup Alarm Set Points 11 23       6 fet togs ant apis       1                   1                        RMCC I amp O Manual System Navigation     11 19    11 4 2  Circuit Inputs          CIRCUIT INPUTS 01  Temp   Term     Wash Switch   Demand     ENT Next fi   Circuit    The Circuit Inputs Status screen displays the current  status information about selected inputs defined within the  selected circuit     Temp    The current Circuit Temperature is displayed in the  Temp field     11 4 3  Circuit Statistics       ts E Er  ege  o    CIRCUIT STATISTICS  Su Mo Tu We  0          0 0  0 0 0 0    Om Om Om Om Om  Dfr Om Om Om Om Om Om    th t Circuit    11 4 4  Circuit Set Points    Standard Circuit Control Set Point screens are also ac   cessed by selecting the Setup Command from the Standard  Circuit Control Menu  For descriptions of these screens     11 20   Circuit Defrost Control          Term    If the termination sensors were set up as analog temper   ature sensors  the current termination temperature reading  is displayed in the Term field  This field will display either  OPN  open  or CLSD  closed  if the termination sensors  were set up as digital sensors     Wash Switch    The current status of the Clean Switch Input is dis   played in the Wash Switch field if the switch is defined at  the Circuit Setpoints 2 screen  see Section 11 4 19
383. uits are set up at the Circuit Setup  screens  If the Enter Defaults feature was activated at the  first Circuit Setup screen  see Section 11 4 16  Circuit Set   up 1   the default settings for the defined case type should  be displayed in all fields at the Circuit Setup 2 screen     Defrost Type   H ot Gas   E lectric   R ev Air    T imed   H     The defrost type for the selected circuit is defined in the  Defrost Type field and should be defined according to the  case type     Defrost Termination   S tat   T emp   N one   S     The strategy the RMCC uses to terminate defrost within  the selected standard circuit is defined in the Defrost Ter   mination field  Users may enter one of the following strat   egies     e  S tat  the          will terminate defrost when it de   tects a change of state from a dry contact  non volt   age contact closure      11 26   Circuit Defrost Control          T emp   the RMCC will terminate defrost when the  temperature monitored by the defrost termination  sensor surpasses the defined Termination Tempera   ture set point  This set point is defined at the Circuit  Setpoints 1 screen  see Section 11 4 18  Circuit Set  Points 1         N one   the          will terminate defrost after the  defined Defrost Duration has elapsed  This duration  is defined at the Circuit Setpoints 1 screen  see Sec   tion 11 4 18  Circuit Set Points 1      Defrost Termination Type   N ormal   P ulsed   N     The Termination Type is defined in the Defrost Termi   nat
384. uspend  Count           t Tri d  Reset Count    ount Trippei    Alarm   Disabiers  gt                           5  gt                       Process Alarm   Alarm      Notice                            Occupied       V    CONTROL APPLICATIONS    AN INPUT 1 AV OUTPUT 1 DV OUTPUT 1                AV INPUT 2    26512029       Figure 9 8   Relationship Between Set Points  Cells  and  Modules    The RMCC uses three kinds of modules  Analog Out   put Modules  Analog Input Modules  and Digital Output    RMCC 1 amp 0 Manual    Modules  In general  the cells grouped within the Analog  Input and Digital Output Modules are those cells that are  necessary to combine several analog or digital values into  a single control value that may be used by physical devices  or other modules  The cells grouped within the Analog  Output Module are those cells that control an output using  a closed loop PID control method     9 9 1 1  Programming Cells and Modules    In UltraSite  set points for RMCC I O Modules are  grouped together in their respective cells  Modules  there   fore  may be easily programmed cell by cell     Up to 24 separate Analog Input Modules  16 separate  Digital Output Modules  and 8 Analog Output Modules  may be configured within the RMCC  Although the user  may not change which cells fall within the two types of  modules  users may often customize a module   s functions  by disabling certain cells     9 9 1 2  Module Inputs and Outputs    The inputs used to drive I O Modules ma
385. ut Module may be  overridden using this screen     Name  15 characters max   DV OUTPUT  module  number      If desired  enter a name for the digital output module in  the Name field     Enable  Yes  No   N     The Enable field allows users to turn an individual Dig   ital Output Module on or off without having to use Ultra   Site  Entering Yes in this field enables the current module   entering No in this field turns off the module     Command  OFF  ON  NONE   OFF     The value to which the Command output will be over   ridden is entered in the Command field     11 6  Main Status       12 00    4 1 0 Network  5 Host Network    STATUS MENU    1 Main Status    2 Input Status  5 Variable Speed Status    ELECT NUMBER    RMCC I amp O Manual          Type  Fixed  Timed  Normal   Normal     In the Type field  users may choose the type of over   ride  There are three override types to choose from       Normal   Choosing    Normal    in the Type field ends  a fixed or timed override already in progress     e Fixed   The output will be overridden to the value  chosen in the Value field until the user returns to  this field and selects    Normal        e Timed   The output will be overridden to the value  chosen in the Value field for the amount of time en   tered in the Time field  see below   This override  may also be terminated by selecting    Normal          the Type field     Time  0   68 minutes   5 minutes     The value entered in the Time field will be the number  of minutes a 
386. valve relay for simultaneous con   trol of two pulse valves  Control of two valves simulta   neously is intended for applications where two evaporators  are being used to refrigerate a single space such as a walk   in box cooler  A single pulse case controller is not capable  of controlling two separate cases  The stepper valve case  controller  Figure 6 2  does not have the second valve re     RMCC I amp O Manual    lay  and it has a jumper that is set based on whether the  valve is bipolar or unipolar        Network Address Rotary Dials    Valve Relay  Plug In        Leak Sensor Input    Fuse 250 V  5 A  AGC 5  or Equivalent       Frost Sensor Input       Door Switch Sensor Input    Valve Fuses 250 V  AGC 2 or  Equivalent       Hand Held Terminal Jack RJ11       Input Cable Connector       Termination Resistance Jumpers       Fan and Light Fail Safe Jumpers   JU7  JU8        Second Valve Output  24 VAC           Optional 2nd Valve Relay  Plug In       Output Cable Connector  Lights  12 VDC  170 Ma max    Fan  12 VDC  170 Ma max    Anti Sweat  12 VDC  170 Ma max    Defrost  12 VDC  170 Ma max    Pulse Valve 1  24 VAC     26502018       Network Address Rotary Dials    Fuse 250 V  5 A  AGC 5  or Equivalent       Leak Sensor Input       Frost Sensor Input       Door Switch Sensor Input       Hand Held Terminal Jack RJ11       Input Cable Connector       Termination Resistance Jumpers                                             Fan and Light Fail Safe Jumpers   JU7  JU8         
387. ve opening percentage   Case dF   the case temperature in degrees Fahrenheit        15 4   Hand Held Terminal Screens 026 1102 Rev 4 08 12 99    Coil 1 In   the coil 1 in temperature    Offset   the coil 1 in temp sensor offset  This may be changed with the HHT   Coil 1 Out   the coil 1 out temperature    Offset   the coil 1 out temp sensor offset This may be changed with the HHT     Defr   When in defrost  this field shows the number of minutes and seconds the circuit has  been in defrost  This number will be equal to the fail safe time when not in defrost     Failsafe   the maximum number of minutes and seconds defrost mode will remain active   Term   the termination temperature sensor reading   Setpt   the termination temperature set point     Defr  1 Defr  4   the first four scheduled defrost times     Defr  5 Defr  6   the fifth and sixth scheduled defrost times     Drip   When in drain mode  this field shows the number of minutes and seconds the circuit has  been draining  This number will be equal to the set time when not in drip mode     Set Time   the amount of time moisture on the coil is allowed to drain after defrost     Humidity   the humidity sensor reading   Aswt    the percentage at which the anti sweat heaters are operating   Max   the humidity above which the anti sweat heater will remain on at all times     Min   the humidity below which the anti sweat heater will remain off at all times     Lights   the current status of the case lights  Pressing RIGHT fol
388. weat set points     Type Min  Description  Max  Fixed 6seconds   None Number of seconds the anti sweat algorithm divides between time on  and time off   High anti sweat   Set point 60  0   Humidity level when heaters will be      100  of six seconds   set point 10096    Period    Low anti sweat  set point    Table 8 9   Anti Sweat Control Parameters    8 7     The fan control algorithm controls operation of the fan  output  The fans will be on while in normal operation  liq   uid control or suction control   When in defrost mode  the  fan status may be programmed to be either ON or OFF  If  the fan status is programmed OFF during defrost  a coil out  delay may be specified that forces the fan to continue to run  until the coil outlet temperature exceeds the delay set point   See Section 8 4   Defrost Control  for more information   For walk in box control  the fan will turn off when the door  switch is activated     Fan Control    8 8  Light Control    The case controller controls the light output as shown  below  The light control set point is shown in Table 8 10     1  The lights default to on     2  Forwalk in box control  when the door switch input  is activated  door open  the lights will turn on  The  lights turn off when the switch is deactivated     RMCC I amp O Manual       Humidity level when heaters will be on 10  of six seconds   10096     Name   Type   Default   Description        Set point Active hi Defines the active   on  level for the  lights  active hi or  a
389. which the anti sweat heaters are operating    Max   the humidity above which the anti sweat heater will remain on at all times   Min   the humidity below which the anti sweat heater will remain off at all times     Lights   the current status of the case lights  Pressing RIGHT followed by one of the com   mands below allows users to bypass the case lights    1 Auto   Pressing 1 will return the case lights to automatic operation    2 Turn Off   Pressing 2 will bypass the case lights off    3 Turn On   Pressing 3 will bypass the case lights on     Supht SP   the current superheat set point  This value may be changed using the HHT     Sens 3 Sens   the valve   s sensitivity value  This may be changed using the HHT  See Section 5 3 1 3      RcvyLevel Valve Control for a complete definition of sensitivity                  see RcvyLevel   This number is equal to the recovery valve percentage  see Section 11 4 29   CCB    Set Point Screen 1  Liquid Pulse and Stepper Only   divided by 10  This may be changed  using the HHT     MaxRcvy Sec   the maximum number of seconds the CCB will operate in recovery mode  This  number may be changed using the HHT     Disch Air   the current discharge air temperature reading     Offset   the discharge air temperature sensor offset  This may be changed with the HHT   Ret Air   the current return air temperature reading   Offset   the return air temperature sensor offset  This may be changed with the HHT     Status   the operational status of the ref
390. y attempt to clear fan proof failures  When a fan proof  is closed  the RMCC attempts to clear it by turning the fan  on  If the proof is successfully cleared after this attempt  the  fan shuts off and condenser control reverts to normal  If the    11 3 6  Condenser Two Speed Fan Setup    The following screens are accessible only if the Con   denser Fan s  Type field is set to    Two Speed   Single  and  variable speed setup screens are described in the Condens   er Two Speed Fan Setup and the Condenser Variable   Speed Fan Setup sections  on Section 11 3 5  Condenser  Single Speed Setup Screens and Section 11 3 7  Variable   Speed Setup Screens respectively      11 3 6 1  Two Speed Setup Screen 1    62  C2  C4      CONDENSER 2 SPEED FAN SETUP  Fan High Output  2Spd Relay 2                   Fan Low Output    125     Relay 1  Fan Off Output            Relays                            Start Speed   0 f f  T PREV                  gt  SET DATA          O MENU    Fan High Output   2  2Spd Relay 2   1  2Spd Relay  1   0  Both Relays   N o Relays   2   The relay or relays chosen in the Fan High Output field    are closed when the RMCC calls for high speed output on  the condenser fans  There are four options     e 2 Spd Relay I   Two speed relay  1 will be closed  during high speed operation    e 2Spd Relay 2  default    Two speed relay  2 will be  closed during high speed operation     e Both Relays   Both two speed relay  1 and  2 will  be active during high speed operation     
391. y come from  external I O board inputs and outputs  other I O Module  outputs  or a number of RMCC internal values  including   pressure control  sensor control  anti sweat control  case  control  and circuit control inputs  Most module inputs can  also be set up as constant analog or digital values     Digital inputs and outputs of I O modules may be any  of three states  OFF  ON  or NONE  The NONE state in  most respects is interpreted to be the same as OFF  except  NONE represents    don   t care  rather than  off   In certain  input combining strategies  a NONE input will be ignored   whereas an OFF input will be read as an input value     An example of this is the Analog Input Module s     First    strategy  which passes the first of four defined in   puts along to a module s output  If Input  1 of a module is  NONE  the First strategy will skip Input   1 and use the val   ue of Input  2  If Input  1 is zero or OFF  the First strategy  would use the value of Input  1     Some digital I O outputs may also be configured with  user specified definitions of ON and OFF  For example  in   stead of having an output be either ON or OFF  a user may  configure the output be ON NONE  NONE OFF  or even  OFF ON     9 9 2  RMCC I O Module Descriptions  9 9 2 1  Analog Input Module    General Description    The primary purpose of the Analog Input Module is to  combine up to four analog inputs  from either analog sen   sors or Analog Output Modules  into a single analog output  value  T
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
sistemi di gestione della sicurezza e della salute sul lavoro  Vtech VT 1932 900MHz Phone (VT  Service Manual  Ricoh Aficio MPc2051AD  Handbücher    K-Tech News Vol.11 No.2  Annexe 6  5in1 Mesoporation+LED Photon+Electroportion+EMS+  Descargar ficha de producto    Copyright © All rights reserved. 
   Failed to retrieve file