Home
DCM 5 Installation - ProMinent Fluid Controls, Inc.
Contents
1. 24 VDC maximum on internal card surfaces Installation Services The OP driver measures ORP and pH sensors The Controller powers the OP card using its internal 12VDC supply and measures pH on the C input and ORP on the D input The DCM5 only allows the pH ORP configuration although other configurations of the OP driver are possible Up to two dual sensor OP drivers may be installed in a DCM5 controller The second OP driver would be installed in the E and F slot Pool 2 pH is then assigned to E and Pool 2 ORP to F Faster Response Lower Temperature The OP responds immediately to pH changes The extremely high sensor input impedance of the OP supports water pH measurement below 40 F 5 C Fie Solution Ground Required The faster response and improved low temperature performance makes the pH sensor more sensitive to electrical noise and requires a solution ground for both operation and calibration Do not calibrate the pH sensor on line or in a buffer solution unless the solution ground is connected and immersed in the same sample as the pH sensor CETRA Static Discharge The faster response and improved low temperature performance also makes the OP_Ext driver sensitive to static discharge at the sensor connection terminals If you accidentally touch or contact the sensor terminals with the OP Ext power ON static discharge may lock up the sensor input You ll experience the lock up up as a pH mea
2. If the site 4mA Level amp 20mA Level are known Gain Multiplier 20 0 mA_Level 4 0 mA_Level 800 Offset Adjust 200 x Gain Multiplier Example 4mA_Level 0 ppm amp 20mA_Level 10 0 ppm Gain Multiplier 10 800 0 0125 Offset Adjust 200 x 0 0125 2 5 Check At 4mA we ll measure 200 mV and display 200 x 0 0125 2 5 0 ppm At 20mA we ll measure 1000 mV and display 1000 x 0 0125 2 5 10 0 ppm Page 57 DCM 5 Installation 7 2 8 Specifications Resolution 0 0125 of span 2uA Most current loop sources are 10 bit resolution typically 0 1 of span In this case the source of the current loop or loop powered sensor constrains overall accuracy and resolution Accuracy 05 of span Accuracy stated after calibration correct for GAIN error through the DC isolator Max Input Input is polarity protected to 50VDC and Voltage thermally fused at 50mA 0 MA if loop polarity incorrect Terminated Loop Green LED ON at loop Visual indication of correct loop wiring Indicator currents greater than polarity and active loop power 3 5MA Dual Isolated 21MA O 24VDC 4 Dual 24VDC supply powered by controller 24VDC Supplies 75mV P P noise unregulated supply 85C Max DC Isolation 50VDC maximum DC supplies rated 1000VDC 60 Sec PCB sets isolation voltage limit Notes Resolution Example If 4 20mA represents 0 100 0 ppm and the current transmitter has 10 bit resolution then residual displayed woul
3. 3 it out 3 Use the wall bracket as a drilling template to mark the posi tions of four drill holes 4 Drill the holes 6 mm d 50 mm Page 9 DCM 5 Installation Fig 7 Fitting the wall bracket 9 Screw the wall bracket into position using the washers see Fig 7 6 Hook the bottom of the DXC housing 1 into the wall bracket 7 p Lightly press the DXC housing at the top 2 against the wall bracket 8 p Then checkthat the DXC housing is hooked in at the top and press down 3 until it audibly engages Page 10 DCM 5 Installation 2 2 1 Sample Connections Modular Sensor Housing DGMa e Mount white acrylic mounting plate within 60 of the DCM5 controller and allow at least 18 clearance above the top of the mounting plate e Using the typical installation drawings on the following pages connect sample tubing to the DGMa modular sensor housing and the main recirculation lines using the fittings supplied Note that the default mounting of the modular housing is to flow from left to right If preferred the modular housing is reversible by removing the assembled modules from the black upper snap clips o First disconnect the spacer standoff brackets and pull the module assembly to unsnap it from the upper clips Once it is loose simply flip the assembled modules so that the molded arrows on the modules are pointing right to left o Then reconnect it to the standoff brackets and
4. DCM 5 Installation 6 7 6 8 Technical Pump Freguency Stroke Controls 1 Gallon 3785 mL Set pump frequency control to External amp Stroke to 100 GPH Gallons per hour GPD Gallons per day Pump Defaults User Adjustment Range amp Resolution Pump default mL stroke is set for a 25psi head typical for chemical injection piping The user mL stroke adjust is limited to 25 and 70 for ProMinent pumps The user mL stroke adjust is limited to 0 01mL stroke and 10ml stroke for Other type pumps In both cases the adjust resolution is 0 01mL Other type Pump SPM rates are limited to a minimum of 50 SPM and a maximum of 400 SPM Maximum Feed Rate A pump s maximum feed rated is it s rated maximum strokes minute x mL stroke Example A ProMinent Beta 1602 pump is rated 180 SPM with a default of 0 24 mL stroke rated backpressure The maximum feed rate for this pump 180 x 0 24 x 60 2592 ml hour 0 685 GPH 15 44 GPD At the 70 minimum user adjust 0 78 L hour 0 2 GPH At the 25 maximum user adjust 3 24 L hour 0 856 GPH Minimum Feed Rate or Turn Down The minimum pump freguency is set to 0 1 SPM a turn down of 1800 1 for a 180 SPM pump and 2400 1 for a 240 SPM pump The 0 1 SPM limit turns the pump drive LED ON for 5 minutes and OFF for five minutes a maximum for an observer visually verifying that a pump is stroking Minimum feed rate only applies to pumps that are controlled by analog sensors pH O
5. 5 has a Flow Monitor device on its output that provides a contact closure every time the pump strokes We re going to use it to verify that we re actually feeding flocculent We ve enabled unused meter input U and named it Flocc Verify We ve configured Flocc Verify U with Compensation Feed Verify and Verify Output 5 flocculent We ve left the Wait to Verify at the default 30 seconds Each time the Flocculant Pump turns ON the controller verifies that a contact closure is measured by Flocc Verify U every 30 seconds or less 30 seconds ensures that even at a low stroke rate we ll see a contact closure every 30 seconds unless we ve lost prime emptied the drum blocked a feed etc If Flocc Verify U does not measure a contact closure every 30 seconds while the flocculent Pump 5 is ON U will alarm 6 6 Frequency Controlled Pumps Feed Rate Setting Page 39 DCM 5 Installation The controller knows the pump s mL stroke and maximum stroke rate Maximum SPM based on the ProMinent pump model entered or the values you entered for Other Once you select the pump feed method or control mode the controller sets the optimum Pump Speed Modes UserSets Pump Speed pH Acid Sensor TurnOFF As the pool or spa chemistry changes from swimmers or Controlled pHor ORP setpoint Chlorine feed the pH rises The acid pump is OFF at pH lt TurnOFF pH 100 ON The pump speed increases linearly between TurnOFF pH or ORP setpo
6. 6 10 7 Temperatures Temperature default units are set by the Metric US Units software choice for each input which measures a temperature and is then used for each sensor which may be temperature compensated Default offsets amp gains for thermal sensors are set to the defaults corresponding to the Metric US Units switch US Units Temperature units F Metric Temperature units C CETRA Remember that even if you change the default units on a temperature input the controller internally applies the units set by the Metric US Units switch ProMinent strongly recommends that you do not change the default units on any temperature used for control or for temperature compensation of conductivity or pH Errors in both temperature calibration and tracking over temperature for conductivity and or temperature compensated pH will result Page 46 DCM 5 Installation 6 10 8 User Assigned Units User assigned units have no effect on controller volumes inventory ppm and temperature compensation calculations You are free to assign whatever units you wish and to mix unit types in any one controller bearing in mind how the controller handles unit conversions in Metric amp US Units modes If you need to override the units on any input you can edit the OFFSET amp GAIN that s applied to the target input 7 Sensor Driver Manuals and Drawings 71 OP Driver Card ORP pH Safety 1 VDC maximum on field wiring terminals
7. CAUTION Fractional horsepower chemical feed pumps cannot be directly powered by the controller Use the controller 120VAC control output to switch a small relay with a 120VAC coil for these type pumps or feeders Page 14 DCM 5 Installation Sensor Wiring Analog sensors pH ORP conductivity corrosion rate temperature 4 20MA contact sets water meters and flow switches may be cabled in a common conduit without causing operational problems Do not mix AC Line 120 VAC wiring with any sensor or communications cable in a common conduit Grounded metallic conduit is preferred in areas where variable freguency drives operate Sensor cables with the exception of pH or ORP sensors may be extended in paired AWG22 0 25mm cable Ensure that cabling splices are accessible in conduit fittings or junction boxes Verify that the shields on contact head water meters are also extended when meter cables are extended Ground cable shields to the internal frame grounding screw at one end only Ethernet LAN Cabling CAT5 LAN cabling is limited to a maximum of 300ft 100m from controller to access hub or router Do not exceed this limit Controller Enclosure Wiring If shipped with the controller pre mounted to an acrylic back panel the controller has already been wired to the sensors you purchased with the controller Unless reguested otherwise the controller has also been fitted with a 120 VAC power cord Refer to sections below for p
8. DCM 5 Installation 2 3 4 Flow switches Contact Sets and Water Meters Water meters flow switches and dry contact sets are connected to input terminals O through V and a ground terminal 5VDC limited by 10KQ puts 1 2mA through a closed contact set Input O is reserved for the sample flow switch function and cannot be changed Paddlewheel and Turbine water meters Hall Effect types are powered by the 15 22VDC controller power supply thermally fused at 100mA Connecting Meters amp Flowswitches Upper Measure Card a Conductivity Red Ak WotGm 420mA DC Pow Meter Contact Set Inputs S1S2T Gt opt OP QRH ST UV NDOSOD SORBYVDOSODEDOSODS DGMa Sample W Flow Switch N O Remote connections are terminals 2 amp 3 E In most default ra configurations the remote stop contact T is enabled Black Red Signal Silver Shield Lai noi Sensor connected to digital inputs O through V Controllers are defaulted to input O as Sample stream flowswitch interlock T as the remote disable contact and P as the main reciculation paddlewheel flow meter and will stop chemical feed relays from feeding Either Jumper T to ground as shown or remove all interlocks with T signet Blue Cap type Turbine Flow Meter Flow Switches interlock contacts flow meter pulsed inputs tank low level switches or other dry contact inputs are Connect cabling shields
9. Page 3 DCM 5 Installation Contents 6 9 System Alarms amp Indicating LEDs 6 10 Units for Volumes amp Temperatures 6 10 1 Metric US Units Selection 6 10 2 Water Meter Volumes 6 10 3 Rate to Volume 6 10 4 Copy Volume to 6 10 5 Pump Volumes 6 10 6 mL Pulse Meters 6 10 7 Temperatures 6 10 8 User Assigned Units 7 Sensor Driver Manuals and Drawings 7 1 OP Driver ORP pH 7 2 Cll Driver Dual 4 20mA Current Input Isolated 8 Spare Parts Page 4 DCM 5 Installation 1 Overview 1 1 All ProMinent DCM5 controllers have an integral web server with a CAT5 Ethernet connection ready to communicate with any internet ready computer regardless of operating system This makes the ProMinent DCM5 one of the easiest Aquatic controllers to allow you to network and remotely monitor and control your pool and spa chemistry parameters 1 2 DCM5 controllers are optimized for Aquatic water disinfection control applications These controllers use sensors to measure water quality and then control chemical feeders UV systems recirculation pumps heaters and more to maintain a safe and comfortable aquatic environment 1 3 The built in conventional and complex control configurations are easily field selectable for most any custom control needs 1 4 Many additional sensors and capabilities are easily added in the field to meet your changing needs 1 5 AC powered pumps and solenoids for ON OFF Time Modulated and PID control
10. ProMinent pH types pH Sensor Aguatics 7500441 25mm cell or Dulcotest PH electrode PHES 112 SE 150702 13 5mm cell or PHE 112 SE 305054 13 5mm cell ProMinent ORP types ORP Sensor Aguatics 7500442 25mm cell RHES Pt SE 150703 13 5mm cell RHEP Au SE 1003875 13 5mm cell CETTE Do not install pH sensors without installing and connecting a solution ground Unstable drifting pH readings will occur if the solution ground is disconnected SETTIMA Turn OFF the controller before connecting or disconnecting pH sensors Do not install sensor cabling in the same conduit as AC power cabling Page 48 DCM 5 Installation Sensor Wiring Solution Ground not needed here if connected on Measure card Cf Center of Coax to 4 sesso Outside of Coax to ee ee ee Lee Coen L N eee TT Lt Real aN KS KN KKK NINNIN ISIS III IZZO LIZA NINNIN IZZO III III NNN OLIO III MIEI VIZZINI MARIO SITE 9 NINA ee T a aaeeea eee a ee ee MZ NINNIN MILZA IZZO MILIONI NNN IZZO IZZO IZZO NINNIN TIT TA MIN Be ee LIAN DODOCOOLOCR TELE REOCOCCOCOCOSCOO AKO RIPOLI COLOURED ann OR POSSONO NS SONNIN MN 101 0 13 LUIN MN Lk ta ISIN N a a e IZZO IZZO VIZZINI j DA fsi DA NNN INSSI IZZO III PEYYYYYTYYYTYYTYTYYYTYYTYTYYYTTYYTIY TITTI TUTTI KKK MKKMKKKKIKKKKKKKKKKKKKKNIKKIKKIKIKIKIK Doe ada ea IT ITE ITE TANKIN a a LON EEI 1 YTYTYY TYDS SS n JUU JUU NINNIN EGO J UL QU UNI NIINAN TI
11. at the controller ends of the cable only to any ground terminal either on the Measure Card or on the bottom center of the aluminum frame backplate Page 22 DCM 5 Installation 2 3 5 Sensors pH and ORP Sensor Wiring DCMS controllers normally have the cables Copper Center pins are for the pH and ORP sensors pre wired and Il Metal Shield is marked on the cables for the appropriate _ 7 KK a OOOH jossa a sensor lf replacing these cables connect the center pins on coaxial cables to the EFSA N a pomarin BME 1 pt positive terminal and the metallic shield Toi N wy pResidual cu is connected to negative A solution M i ee ground reference is reguired for proper th es Brio operation An SGT sensor has a solution si De reference Green and temperature sensor VEE S W h sa n White Even if the temperature sensor is ri in a not being used the solution reference must be connected to the ground terminal NOTE For the second pool in a 2 pool system the second temperature input is located on the optional expansion PCB Conduct vity t Meter amp Contact Set nputi Ru d tr Whe Or 6 20nA SENET I oc Pow ar pu uput cree a se e is required for proper operation 941 S27 she 4 ese Pr Minent i Page 23 DCM 5 Installation Residual Sensors Controller Powered 4 20 mA Current Loops Loop Powered Sensor 1 Free or Total Chlorine Controller 24VDC pow
12. in high ambient temperature locations with both loops powered by the Card and 20MA Do not install more than one Cll card in a DCM5 Controller 7 2 2 Application Use the CII when you need to DC isolate the 4 20mA current loop and the current loop power supply from the controller and electrical ground such as the Residual Chlorine and bromine sensors used in aguatic applications Wiring connection detail for each of the three typical applications is depicted in Section 2 3 Applications Detail Loop powered oxidant sensors Splitting or sharing a 4 20mA current loop Isolating powered 4 20mA current loops ProMinent s loop powered oxidant sensors reguire both a 24VDC supply and DC isolation form electrical ground The Cll card can power and measure two of these loop powered sensors Since the CII card is used exclusively in the DCM5 for residual sensor inputs splitting the 4 20mA signal is not advised or supported by the DCM5 software This is the least common application since most uses of the CII card use the power supplied by the CII card and ProMinent residual sensors In other applications the current loop is powered externally to the DCM5 by the sensor or measuring eguipment and DC isolated at the DCM5 controller input by the CII card Page 52 DCM 5 Installation 7 2 3 Installation 7 2 4 Services The Cll driver DC isolates and measures two 4 20mA current loops Each current loop may be
13. new device appears automatically in all of the selection and configuration menus Data Logging Each enabled input and output is logged by the controller as a user set interval from 5 to 1440 minutes The default rate for all data is 60 minutes with a 600 sample log size Range is 2 to 600 days Default maximum is therefore 25 days of information Sensors log minimum maximum and average Water meters log volume Contact sets log time ON Power Relays controlling pumps and valves log ON time in seconds Freguency controlled pumps log volume pumped in mL in each log period Alarms are time amp date stamped The last 25 controller activities are time and date stamped with the user ID Note Data logging of relay ON time continues when AC fuse fails but a relay can t power ON a pump valve or solenoid so the ON time may be lower by the amount of time the power is off to the relays 5 0 Control Configuration 5 3 1 Control Method Relays 1 to 5 ON OFF Controls The distance between the Turn ON and Turn OFF setpoints sets the deadband hysteresis response of an ON OFF relay controlled by sensors A N Not applicable to relays controlled by volume meters or contact sets O Z Method Function Examples amp Rising Setpoint ON Sensor gt Turn ON Setpoint Acid Feed Feed Down OFF Sensor lt Turn OFF Setpoint Falling Setpoint ON Sensor lt Turn ON Setpoint Oxidant Feed Feed Up OFF Sensor gt Turn O
14. remount onto the backpanel o Next use the typical installation drawing below as a guide and connect the sample supply and return tubing using the selection of fittings supplied NOTE Sensor Sample should always be from downstream of the filter but up stream of the heater and any chemical injection Discharge sample into the line returning to the pool or spa as close to the pool as possible to get the most pressure drop Using the pressure drop created by other devices like heaters or UV system works best CAUTION Never plumb the sensor sample from unfiltered water as this may introduce hair or other debris into the flow switch and sample cell Never return sample to the suction side of the circulation pump as this will cause a negative pressure vacuum on the sensors Sensors under vacuum vill cause erroneous readings poor disinfection control and a prolonged vacuum vill also cause non warranty damage to the sensors AN Typical Vacuum Filter Arrangement DCM 5 Installation Sensor Sample Return Surge Tank i BREE ProMinent Sensor Sample Supply ACID Page 12 DCM 5 Installation 2 2 2 Sensor Installation Total Chlorine Free Chlorine pH sensor ORP sensor 12 5 GPH Sample Valve Aguatic Sensor Placement in DGMa Modular Sensor Housing e Check that all fittings of the assembly have O rings installed and fittings are secure Adjust flow switch shaft so the to
15. the controlling sensor approaches the Turn OFF setpoint Typically used for pH control reducing acid feed rate as the Turn OFF setpoint is approached Use if you can t use a variable pulse frequency controlled pump Setup User selects a relay amp selects Time Modulation in Special Control User sets Period in seconds minimum 60 recommended Default is currently at 120Seconds maximum is 600 seconds Operation Relay ON 100 of Time Period when Control is beyond Turn ON setpoint Relay ON time Control Turn OFF Setpoint Deadband x Period where Deadband Turn ON Turn OFF setpoints Relay is OFF when Control is beyond Turn OFF setpoint Example Acid Pumps Turn ON 7 70 pH and Turn OFF 7 50 pH Period 120 seconds At pH gt 7 70 Pump ON for 120 seconds in every 120 seconds 100 of Period At pH 7 65 Pump ON for 90 seconds in every 120 seconds 75 At pH 7 60 Pump ON for 60 seconds in every 120 seconds 50 At pH 7 55 Pump ON for 30 seconds in every 120 seconds 25 At pH lt 7 50 Pump OFF 0 Notes Time Modulation control is not advisable when the system response time is faster than 5x the Period In the previous Example If the measured pH moves from 7 70 to Page 35 DCM 5 Installation 7 50 in less than 300 seconds Time Modulation may not improve control hold pH more stable Process buffering pump setting feed point and system volume all affect the response to chemical feed Time modu
16. turned on after card install User selected Reset to Factory loads the GAIN OFFSET set from the following table Sensor Type Input Factory Factory Fault Driver Gain Offset MAX yP Conductivity GAIN GAIN Range gt 100uS l 10 2 5 Range lt 100uS 0 55 0 25 None None ORP pH OFFSET OFFSET Type pH 6 Type ORP 50 Temperature OFFSET OFFSET US units i l 430 590 Metric units 253 293 Water meter Contact Head None None Turbine 3 3 pH ORP Conductivity and Temperature Sensor Accuracy The accuracy of all the sensors is published in the table above and all that is required to meet that accuracy for non residual sensors is a representative sample and a solution ground connection Proper sampling and testing technique is of course essential as is an accurate calibration standard test kit thermometer etc to achieve the accuracies above Refer to your testing standards for more details on the accuracy of your standard and proper sample testing 3 4 DCMS Residual Sensor Accuracy The same sampling and testing technique issues apply to residual calibration with added flow sensitivity thrown in The purpose of this section is to review a number of items that can affect residual measurement and accuracy and offer tips on how to improve the calibration and tracking of ProMinent residual sensors Items discussed are e DPD Tests and amperometric residual sensor accuracy e Combined chlorine readings and how they are affect
17. DCM5 controllers include a USB port which is only used for factory diagnostics and is not an option for remote monitoring and control functions Configuration View sets DCM5 Controllers are loaded with at least 4 View Configurations more coming soon One of these is selected when the controller is manufactured to be the as shipped view configuration Installed View Configurations represent typical uses of the controller that allow loading a configuration that closely fits the intended use of the DCM5 For example residual chlorine sensors and all associated options related to them can be eliminated for an installation with pH and ORP only Configurations and Views are preloaded to support various options Additional expanded capabilities and their associated standard views are planned Page 33 DCM 5 Installation 5 2 4 Field Upgrades As additional capabilities are available for the DCM5 sensor driver cards can be added by powering OFF the controller installing the upgrade card and powering ON The controller will recognize the new supported hardware and auto configure modifying the LCD display to add the new sensor inputs and sub menus The diagnostic browser view will auto enable the new sensors and displays their current values No additional hardware is reguired to connect a water meter flow or level switch Wire the switch or pulsed output flow meter to the DCM5 as shown in the above wiring section Then enable the input and the
18. FF Setpoint Caustic Feed Between Setpoints ON Sensor lt Turn ON Setpoint Blocking Controls or Not normally used in pools amp Sensor gt Turn OFF Setpoint Level Controls and spas OFF Sensor gt Turn ON Setpoint Sensor lt Turn OFF Setpoint Event Rising Rising Setpoint Operates only during Caustic Feed or Not normally used in Timed Events Dechlorination Aquatic applications Page 34 DCM 5 Installation Event Falling Falling Setpoint Oxidant alternate setpoint Operates only during Timed Events Event Between Between Setpoints Blocking seguencing Not normally used in Operates only during Timed Events controls Aquatic applications Frequency Controlled Pumps Contacts 6 to 9 Sets the variable freguency control range for pumps controlled by sensors A N Not applicable to pumps controlled by volume meters or contact sets O Z Freguency varies proportional to Proportional acid or oxidant sensor value when value between controls Turn ON and Turn OFF setpoints Substitutes for more expensive 4 20mA controlled pumps Can also select PID control functions in addition to strictly proportional control During Events Control active during events until Periodic flocculent feed event volume pumped during a timed feed event 5 3 2 Special Control Responses Multiple Types of Control For Standard Relays Time Modulation Relays 1 5 Application Cycles a chemical feed pump ON OFF decreasing the ON time as
19. If the CII card is installed in the CD controller slot the IN2 shows up as Sensor D IN1 If the CII card is installed in the CD controller slot the IN1 shows up as Sensor C Mixing Sensor amp Controller Power Controller powered and sensor powered current loops may be connected to the same Note CII card one loop to each input DCM 500 controllers are limted to 1 CII used in Controller Powered sensor mode Sensor powered 4 20mA Current Loops Powered Sensor 1 Powered Sensor 2 Sensor powered by its power supply Sensor powered by its power supply 4 20mA Return 4 20mA Output 4 20mA Output 4 20mA Return IN2 If the CII card is installed in the CD controller slot the IN2 shows up as Sensor D IN1 If the CII card is installed in the CD controller slot the IN1 shows up as Sensor C Mix Sensor amp Controller Powered 4 20mA Controller powered and Sensor powered current loops may be connected to the same CII card one loop to each input Page 54 DCM 5 Installation Driver Card Wiring cont Sharing a 4 20mA Current Loop Powered Sensor 1 Sensor powered by its power supply 4 20mA Return 4 20mA Output IN1 If the CII card is installed in the CD controller slot the IN1 shows up as Sensor C Loop Compliance Inserting the CII into an existing current loop uses a maximum 2VDC of loop driving voltage at 20mA Page 55 Distributed Con
20. N D depsonsvoercseseesoessvoececoo n AZ a T MYYTY on 0 B MIO a e ZA DI RT INAN 8 LL ROTTI nua Fi SSN e I eee ee sos aus ee eee P Dual ORP a Jumper 20 w pH amp ORP 25 _ Jumper PO 7500441 pH 7500442 ORP Page 49 DCM 5 Installation Controller Wiring All internal wiring connections are made through the Driver card connector in slot C D so there are no other connections to make Configuration Operation Be sure jumper J2 on the Driver card is on the PO pins All other configuration is performed automatically by the DCM5 internal software Specifications Input Range 1000mV 0 14 pH Resolution ORP 0 1mV PH 0 01 pH Accuracy Input Impedance gt 500 MOhm Fully differential 10M ohm power OFF input resistance DC Power 8 VDC minimum to 25 VDC maximum 20MA Controller to OP Cabling Coaxial cabling with Do not exceed 10ft from Sensors to SN6 connectors OP module Notes 1 Accuracy stated after sensor calibration Requires installed solution ground immersed in the common stream with the pH sensor Page 50 DCM 5 Installation 7 2 Cll Driver Dual 4 20mA Current Input Isolated CII Driver Card ur a4 Te al cE J BE EH fo Cel e Page 51 DCM 5 Installation 7 2 1 Safety Electrical 30 VDC maximum on field wiring terminals 24 VDC maximum on internal card surfaces 7 2 1 1 Thermal Driver card surfaces may exceed 70C 160F When installed
21. Once the user set time limit for an increase in volume expires a Fail to Feed alarm occurs Any water meter s measured volume can be directed to any analog sensor input H through N and used to calculate tank inventory Volume Meters Verify Feed ProMinent Pumps may have a Metering Monitor on the pump output to verify feed Or others may have a switch on the pump outlet that provides a contact closure every time the pump strokes to verify pump operation Water Meters Verify Bleed Blowdown Drawdown Make up Contact head or turbine type water meters may be installed on fill piping to verify that the valve or solenoid has operated or opened and flow is not blocked or valved off Tank Inventory The volume measured by any water meter input P through V or calculated for any frequency controlled pump 6 through 9 is subtracted from the input used to display amp log tank volume When you add liquid to the tank you tell the controller the new tank volume by Calibrating the sensor input H through N used as an Inventory target Any sensor input or inputs H through N may be used to calculate volume If more than one pump is drawing from the same tank 1 Use the same Inventory sensor location for each pump amp measuring meter 2 Referto the previous Copy_Volume application note 6 5 Typical Feed Verify Applications Verifying a Filter Aid Feed Example The flocculent pump controlled by Relay
22. ProMinent Installation Guide ProMinent DCM 5 series Aquatic Water Quality Controller ProMinent Fluid Controls 136 Industry Drive Pittsburgh PA USA 15275 1014 DCM 5 Installation Guide 12 12 p n 7500582 DCM 5 Installation This page intentionally left blank Page 2 DCM 5 Installation Contents 1 Overview 2 Installation Commissioning 2 1 Safety 2 2 Mounting 2 2 1 Sample Connections 2 2 2 Sensor Installation 2 3 Wiring 2 3 1 Line Power Wiring 2 3 2 120 VAC Feeders 2 3 3 Pulse Controlled Pumps 2 3 4 Flow switches Contact Sets and Water Meters 2 3 5 Sensors 3 Calibrations 3 1 Single Point Calibrations 3 2 Two Point Calibrations 4 Password Security 4 1 Overview 4 2 Password Level Activities 4 3 Browser Passwords amp Lockout 4 4 LCD Passwords 4 5 Passwords Reset 5 Application Notes 5 1 Sensor Inputs amp Control Outputs 5 2 Communications 5 2 1 Ethernet 5 2 2 USB Services 5 2 3 Configuration View sets 5 2 4 Field Upgrades 5 2 5 Data Logging 5 3 Control Configuration 5 3 1 Control Method 5 3 2 Special Control Responses 6 Sensors 6 1 Compensation 6 2 Digital Input Sensors O Z 6 3 Contact Sets Flow Switches O Z 6 4 Feed Verify amp Inventory 6 5 Typical Feed Verify Applications 6 6 Frequency Controlled Pumps 6 7 Technical Pump Frequency Stroke Controls 6 8 Relay amp Frequency Controls Comparison 6 8 1 ON OFF Controls 6 8 2 Frequency Controls
23. RP temperature flow rate Other pump controls operate at either the user set mL minute or MAX SPM so minimum feed rate is not applicable Control Resolution Control resolution 1mS 1mS defines the precision of pulsed output variable frequency control The DCM5 controller calculates pulsed output strokes per minute to the nearest 1000 of a second 1mS based on deviation from setpoint and other factors like PID control calculations Example At 180 SPM the pump pulses 3 times per second At 179 strokes per minute the pump strokes 2 983 times per second The number of times per minute to the nearest 1mS control resolution is 667 feed rates between 179 and 180 SPM At 10 SPM with 1mS control resolution up to 6000 calculated feed rates are possible As the example clarifies control resolution is more important at high pump speeds and much more control precision than Time Modulated control Relay amp Freguency Controls Comparison 6 8 1 ON OFF Controls Relays R1 to R5 are used for ON OFF controls The relay switches 120 VAC ON or OFF powering pumps solenoids and motorized valves Page 41 DCM 5 Installation 6 8 2 Freguency Controls P6 to P9 pulse outputs control pump freguency The pump is always plugged into an AC supply and the pumping rate is set by the frequency of pulses from the controller Modes o Frequency Controls ON OFF Controls Sensors Control Range Setpoints are TurnOFF amp 100 ON Proportio
24. an be performed e Turn off the chemical feeders so that they do not change the water chemistry during the calibration process e Temperature and pH sensors are used to compensate other readings so they should always be checked and calibrated first if necessary A common mistake is calibrating the pH last or after a pH compensated sensor has been calibrated which then shifts the pH compensated sensor e Test samples should be taken from the petcock at the sensor cell Samples from the side of the pool are not the same homogenous sample from the main drain and the skimmers the sensors are using for control e Write down the readings on the controller for all parameters before taking water samples e Observe that the sensor readings do not change significantly when the petcock is opened to take your samples If the readings change noticeably you are drawing too much water from the flow cell during your sample extraction e Follow the test kit instructions to the letter including proper order of chemical introduction accurate sample volumes and reagent reaction times e Make 1 point calibrations on Temperature followed by Conductivity pH Free Cl2 then Total Chlorine Keypad Calibration Step by Step Calibrations can be done from the keypad or the Browser interface but are most conveniently done from the DCM5 keypad or a connected iPad tablet computer while close to the controller during testing Avoid waiting until you can get to a remote c
25. and damage to equipment may result from improper operate chemical application feeders and other devices that may pump Unplug or turn OFF the AC power to the controller if you have hazardous corrosive any concerns regarding safety or incorrect controller operation and toxic chemicals and notify supervisory staff Page 5 DCM 5 Installation Flow Switch Function NEVER OVERRIDEA FLOW SWITCH Uncontrolled feeding of concentrated chemicals can result in personal injury or death Sample and recirculation flow switches are critical safety devices which prevent uncontrolled chemical feed Follow Instructions Carefully Flow switches are provided with all ProMagua pool controllers and are an integral safety device to prevent the uncontrolled feed of chemicals which could cause personal injury or death This critical safety device must always be available to protect the swimmers and others near the pool Flow switches should NEVER be bypassed even temporarily The DCM5 has the capability to assign a low flow lockout for a turbine or paddlewheel flow meter The above precaution pertains to those low flow lockouts If disabled or bypassed the sensor would not be able to sense a hazardous situation and turn of the chemical feed pumps to prevent uncontrolled chemical feed Test Flow Switch Function If flow switch float does not drop to the bottom and remain there during backwash no flow or very low flow conditions the contro
26. and potentially PRECAUTIONS REGARDING toxic chemicals Please CHEMICALS USED use extreme caution and comply with all national IT IS THE RESPONSIBILITY OF THE USER OF THE EQUIPMENT TO OBTAIN state and local AND FOLLOW THE SAFETY regulations and lampaat kit E recommendations for the MANUFACTURER OF THE HAZARDOUS MATERIAL INCLUDING ALL PERSONAL handling and storage of PROTECTION EOUIPMENT these chemicals Page 7 DCM 5 Installation 2 2 Mounting Fully Assembled System on Acrylic Backpanel ei a D a W EA la ED JH la wm Overall System Mounting e locateanareaona flat wall large enough to accommodate the full size of the 18 x 30 system panel with enough extra room to accommodate flexible sample tubing The controller is shipped with a 3 ft power cord already installed for easy connection to a close wall receptacle Alternatively you may choose or be required to install conduit into the bottom of the controller enclosure Refer to Section 4 4 for enclosure opening sizes and locations e Refer to dimensional drawings in appendix section for location and spacing of pre drilled mounting holes measure and mark these locations on the wall e Approximate weight of the assembled system with water flowing may be in excess of 30 Ibs so take care to choose adequately sized mounting hardware Page 8 DCM 5 Installation Individual Components DCM5 Control
27. at ae devices surge PC Board CT protection is always recommended for connections to the AC relay controlled output devices and the AC power line Relay 3 N O Booster Pu Relay 4 N O bottom of backpanel a G QD 2 Probe Wash All Earth Grounds connect at Sm Page 20 DCM 5 Installation 2 3 3 Pulse Controlled Pumps Pulsed controlled pumps can be connected to give more precise control options like PID control and use low voltage wiring to convey pumping signals to the feeders These control options are built into all DCM5 controllers as a standard feature Use the diagram below for connections to ProMinent pump universal control cable and similar cables for other pumps To Measure Card Line Voltage Select Relay Fuse 5 Power Relay 4 Pump ON OFF Freguency Controls 1 You ple Controls AC RELAYS 1 33 AC RELAYS 4 5 FREQUENCY CONTROLS RUN R1 R2 R3 R4 R5 P6 P7 P8 P9 AC POWER EN NONCNONCNO NCNONCNWOVl AB AB AB AB LUMNN NEUTRALS n O 1 CI OD Ka POSQOSSDISDSOSSIOSS For Beta Pumps with universal control cable Black and Brown wires must be connected together and White wire is used to pulse ee Oxidant Pump 3 Pulse outputs connect to Acid Pump External Control input requiring a low current DC switch closure For Concept Plus and other pumps connect the 2 pulse trigger conductors to the A and B terminals of the desired pulsing output Page 21
28. culated Values such as Ryznar s and Langelier s SI indexes or Combined Chlorine level Users can also change the default names of sensors pumps and valves to more meaningful site specific names For example although you may name controller meter input O to Flow Switch O identifies where the meter is connected and the letter O is used to represent the Flow Switch input in hardware connections and data logging Most inputs may be used to control almost any output with some logical aquatic application exceptions VOPoint Sensor A n Ea conductivity sensor HEITIT ms for ProMinent CT conductivity sensors input All controllers have at least one conductivity sensor input Sensor B Fixed thermal sensor Support for the ProMinent SGT 10mV K temperature input sensors and CT sensor Thermal compensation for the A conductivity and pH sensors Sensors C D There are two sensor card The input card is the interface between the analog sensor slots In the DCM5 C D and the digital microprocessor It is a separate card to make slot is always used for the field repairs easier and less expensive if needed C is pH ORP input card assigned to pH and D is assigned to ORP Sensors E F There are two sensor card The input card is the interface between the analog sensor slots In the DCM5 E F and the digital microprocessor It is a separate card to make slot is used for the Dual field upgrades and repai
29. d change in increments of 0 0125 ppm Page 58 DCM 5 Installation 8 Spare Parts DCM5 SPARE PARTS Part Number Description 7500441 pH sensor Aguatic Industrial Grade 38 9mL Inorganic gel 25mm with SN6 connector ORP Sensor Aguatic Industrial Grade 38 9mL Inorganic gel with proprietary Platinum tip design 7500442 SN6 connector Sensor Accessories and Rebuild Parts 1024611 741277 Accessory set for CTE 1 0 5 ppm 2 membrane caps 50mL electrolyte 740048 Accessory set for CGE 2 CTE 1 2 5 10 ppm and BRE 1 2 membrane caps 50mL electrolyte 790488 Membrane cap for types CLE 2 2 CLE 3 CDE 1 2 CDE 2 OZE 2 and OZE 3 792862 Membrane cap for CGE CTE 1 2 5 10 ppm and BRE 1 741274 Membrane cap CTE 1 0 5 ppm CBR 1 1035197 Sensor cap for CLO 1 1035191 CLO 1 Electrolyte 100ml 506270 CLE Electrolyte 100mL all CLE chlorine sensors 792892 CTE Electrolyte 50mL for sensor types CGE CTE BRE 1010380 791635 1004739 987356 791634 1023973 Flow expansion module with scale in gph Accessories and Replacement Parts 7500539 Pulse Flow sensor for 1 2 to 4 pipe with direct connection to DCM5 Saddle ordered separately 7500540 Pulse Flow sensor for 5 to 8 pipe with direct connection to DCM5 Saddle ordered separately 7500541 Pulse Flow sensor for 10 and greater pipe with direct connection to DCM5 Saddle ordered separately 7500542 PVC Saddle 2 PVC Page 59 DCM 5 Ins
30. e A pump running at 10 SPM would have it s indicating LED on for 3 Seconds and OFF 3 Seconds since 10 Strokes Minute is a 6 second period If it is a 180 SPM rated ProMinent pump that would be 5 5 of its rated output Behind LCD Display ON when the controller is AC powered and its internal 5VDC Backlight supply is near 5VDC Page 44 DCM 5 Installation 6 10 Units for Volumes amp Temperatures 6 10 1 Metric US Units Selection Controller units are selected by the Metric US Units keypad and or browser choice Although the increasing use of ppm controls and freguency controlled pumps moves more sites to Metric units the familiarity with GPH GPD and GPM recirculation rates indicates that sites will continue to use both unit systems This application note details how the controller applies the Metric US Units switch setting EMMA Sensor values meter and pumped volumes are logged with the units applicable at the time of log entry Typically the Metric US Units switch is set once when the controller is commissioned since changing units causes problems with interpreting data logs amp adjusting feed timeout and alarm setpoints 6 10 2 Water Meter Volumes The measured and displayed water meter volumes volume per contact K Factor and the high and low alarms are all in the units set by the Metric US Units switch Although the user set units for each volume meter and sensor input are ignored you may mix volume units as
31. e if all the errors of both the Free and Total Chlorine residual are added the error for the combined chlorine reading may differ as much as 0 16 ppm By definition Free Chlorine cannot exceed Total Chlorine but measuring accuracy limits can cause this Another phenomenon seen with real time residual readings is the chemical and sensor reaction times which occur faster with Free chlorine than Total This can be seen immediately after chlorine feed events especially dry chlorine products when Free residual readings temporarily register higher than Total residual readings The Total residual species reactions are completed and Total residual sensor readings catch up in a few minutes and the readings then return to normal This is another good reason to not attempt hasty calibrations while chemistry is changing Conditions that cause DPD test inaccuracy Your DPD tester will have instructions for how to e Humaneyeascolor comparator properly use and maintain your instrument to obtain e Poorcleanliness of sample vial optimum results Read these instructions carefully and e Inadequate rinsing of sample vial between samples follow them to the letter including the newest e Variable total chlorine reaction times seguences of reagent first then water sample e Varying sample volumes introduction vial cleaning reagent storage and shelf life e Varying reagent metering e Aging reagents e Contaminated reagents e Aging or dirty comparator e Colori
32. ed by accuracy e DPD testing conditions that reduce accuracy Page 28 DCM 5 Installation Accuracy of DPD tests and Amperometric Sensors The published accuracy of ProMinent residual amperometric sensors is approximately the same as the published accuracy of the residual test being used to calibrate them 0 04 ppm for typical DPD colorimeter Essentially you can only be as accurate as the tool used to calibrate the instrument That means under perfect conditions for both measurements if they each have an error of 0 04 ppm the next reading after a perfect DPD calibration could still have as much as 0 08 ppm difference If the DPD test is not using an electronic colorimeter the errors can be as much as 0 2 or higher using the human eye as the color comparator Accuracy Effects on Combined Chlorine Readings We ve all see the situation especially during UV operation where the DPD Total Chlorine measurement is less than the Free Chlorine measurement with a perfectly calibrated DPD tester and reagents When seen on a DPD test kit it is either shrugged off or a retest is done to get a better reading If this is seen on the DCMS the typical assumption an operator makes is that there is some sort of sensor error Keep in mind that the DCMS uses the same simple formula to calculate the combined chlorine residual Total Cl Free Cl Combined Cl and cannot be more accurate than the standard used to calibrate it Using the accuracy example abov
33. efine other users as Operator or Configure Cannot view other users passwords Can edit own password default AAAA Cannot edit Admin user id DCM 5 Installation 4 3 Browser Passwords amp Lockout After 5 unsuccessful attempts to log on the controller locks out both Ethernet and modem access Locked out users will see an Alarmed status message in place of Password Incorrect Browser amp modem resets at 7 00AM or when AC power OFF ON Therefore the maximum lockout time is 24 hours and the minimum is less than a minute This feature blocks scripting attacks on controllers and cannot be disabled There is no limit on the number of keypad password attempts Changing all passwords from their default values is strongly recommended for Ethernet and modem connected controllers Passwords can be reset to the factory default by logging on as the Reset Pswrds user Refer to Section 4 4 L CD Passwords Passwords are defaulted OFF for keypad users The System Password menu item does not display unless System Configure has turned passwords ON Once passwords are turned ON only the administrator can access System Configure to turn Passwords OFF If passwords are ON you are prompted with the required password level Admin Configure Operate when you attempt to execute a command which reconfigures the controller Passwords are not required to view the current state Default Passwords amp User IDs Password Operator Operatori O
34. epending on the Metric US Units switch setting Page 45 DCM 5 Installation 6 10 5 Pump Volumes Frequency controlled pump volumes are measured in mL The Metric US Units switch selects the display units for volumes greater than 100mL Frequency controlled pumps are specified in mL stroke with mL stroke calibration limits enforced by the controller Unit Conversion ML to Gallons multiply mL x 0 0002642 Liters to Gallons multiply L x 0 2642 6 10 6 mL Pulse Meters In addition to the ProMinent mL pulse flow monitors there are a number of other devices which provide a contact closure or pulse on pumped volume In all cases the controller assumes that the volume represented by the pulse or contact closure is measured in mL Set the Volume contact for the ProMinent flow monitor or other volume measuring device to the correct mL value The controller will make the correct assumptions The mL assumption is reguired for two controller sensor compensations amp not reguired for type of control 1 Inventory The drum or tote volume is reduced as the volume meter measures 2 ppm The volume of prodfuct pumped in mL can be used to calculate ppm using the volume of make up in Gallons or Liters Warning Do not sum volume meters with different units The result is meaningless For example you can sum make up meters and you can sum feed verify meters but you cannot sum a Make up meter Gallons or Liters and a Feed Verify meter mL
35. ers and are case sensitive The controller blocks the use of HTML delimiter characters by limiting password content to letters and numbers only The controller blocks duplicate passwords since the password identifies the user on keypad log in 4 2 Password Level Activities Password Level Activities Notes OO Public 1 per DCM5 Operator 4 per DCM5 Operator1 4 Configure 3 per DCM5 5 7 Administrator 1 per DCM5 Views current state and clears alarms select System or Diagnostic view Cannot adjust or edit Calibrate sensors Prime Pumps Set 4 amp 20MA levels Changes setpoints and feed rates Can view but not edit all controller configure level settings Configure controls interlocks and blocking Sets sensor compensation feed alarms amp limits Sets biocide timing Prebleed Lockout amp cycle days Zeroes water meters All Operator Activities Set IP address and network parameters All Operator amp Configure Activities Page 30 Password not required for keypad or browser use Browser access to controller wide alarm reset only Can edit own user ID amp password Keypad users password only editing Controller fixed user ID is Operator1 thru Operator4 with default passwords 1 4 Can edit own user ID amp password Keypad users password only editing Controller default user ID is Configure5 thru Configure7 with default passwords 5 7 Browser Can d
36. ers sensor Loop Powered Sensor 2 Total Chlorine Controller 24VDC powers sensor o Q WEA 24 IN1 24 IN2 N a a Part Cll The factory supplied The factory supplied cable connects the EKA Ma aN cable connects the 24VDC to terminal 1 Isolated 24VDC to terminal 1 of the sensor IN1 is of the sensor IN2 is connected to terminal 2 connected to terminal 2 of the sensor Shield of the sensor Shield is connected to ground is connected to ground connector_ _ connector IN1 E IN2 F The DCM 500 CII card is The DCM 500 CII card is installed in the E F slot installed in the E F slot IN1 shows up as Input E IN2 shows up as input F Page 24 DCM 5 Installation N 1 pali Kata 1 Powerit e465 Expanilon Running Pi Control Mond ole wt it Hy Optional Ethernet Jack Conductvity Pad Bix Vat Grr dA DC Bower Matr amp Contact Sat Nputi Output fe ES LaPeer eee ee ey li SGT sensor green solution ground wire must always be connected If CT and SGT are both installed additional white temp sensor wire on SGT should not be connected E CT Sensor SGT Solution Ground Temperature and CT Conductivity Temperature Sensor connections Page 25 DCM 5 Installation 3 Calibrations 3 1 Single Point Calibration One Point or Standardization All inputs A Z have single point calibrations Calibration of digital contact set inputs is blocked SENSORS A N Co
37. es connect to the ground screws at the bottom of the aluminum controller frame NOTE Like most modern microprocessor devices surge protection is always recommended for connections to the N 3 7 power line and relay controlled output devices A CAUTION BASIC SAFETY PRACTICES AND MOST LOCAL ELECTRICAL CODES REQUIRE THIS CONTROLLER S ELECTRICAL POWER TO BE PROTECTED BY A GROUND FAULT CIRCUIT INTERRUPTER GFCI Page 19 DCM 5 Installation 2 3 2 120VAC Feeders NEVER CONNECT FEEDER DIRECTLY TO POWER SOURCE If the chemical feeders are connected to a wall outlet the safety devices integral to your ProMagua controller and to the safe feeding of chemicals will be bypassed It is very important that the chemical feeders be connected to the controller and never directly to a wall outlet If the chemical feeders are connected to a wall outlet and feeding continuously when the flow of water to the pool stops due to filter backwash the circulation pump losing prime or other causes potentially hazardous concentrations of chemicals can be fed into a pool or spa Follow Instructions carefully to insure safe operation To Measure Card Line Voltage Select Relay Fuse 5 Power Relay 4 Pump 115V ON OFF Freguency 3 Controls Ac Dc Controls AC RELAYS 1 3 AC RELAYS 4 5 FREQUENCY CONTROLS RUN R1 R2 R3 R4 R5 AC POWER EN NONCNONCNO NCNO NC NO LLMNN NEUTRALS II a EN Cu NOTE Like most modern microprocessor re
38. et correctly measures 200 0mV 4mA x 50 ohms and calculates OFFSET and GAIN to convert the user calibration input to a displayed value Two Point Calibration 1 Configure the device or sensor controlling the current loop to operate at 4mA 2 Select Sensors Calibrate and Enter first value key the 4 0 mA level in site units For example if your current loop was spanned 0 0 10 0 ppm 4 20mA you would key 0 amp Enter Configure the device or sensor controlling the current loop to operate at 20mA Key the 20mA level the Enter second Value prompt In our example you would key 10 0 amp Enter The controller will then calculate the Offset amp Gain required to convert the measured current to user units ppm AI Any two loop currents may be used to calibrate The previous 4mA amp 20mA example is the optimum Accuracy improves as the difference between the two calibration currents increase Calculating Offset amp Gain 1 The input Offset Adjust and Gain Multiplier may be manually set using Sensors Configuration 2 This method to convert a measured current to a user value may be used if it s not easy to drive the current loop between 4 0 amp 20 0 mA At 4 0 mA the 50 ohm loop terminating resistor measures 200mV 50 x 0 004 At 20 0 mA the 50 ohm loop terminating resistor measures 1000mV 50 x 0 020 As the current loop varies from 4 20mA the controller measures a mV change from 200 to 1000mV an 800mV change
39. from Contact Set to Water Meter clears the log on the switched input Type Setup Ntes I Contact Head User set volume contact not typical in Aquatic applications Contact Head compensation turns ON software de bouncing Volume counts on contact closure Contact opening ignored Not normally used in Pools and Spas Turbine or User set K factor pulses unit Counts pulse on falling edge 400Hz max Paddlewheel volume Ignores rising edge Typical pool and spa circulation flow meter sensors must be powered type sensors Contact Sets Flow Switches O Z Switching from Water Meter to Contact Set clears log Type Setup NNN IINA Contact Set User selects Contact Set Contact sets are ON when closed and OFF when open ON time is logged typical Aguatic uses Contact sets used for interlocking prevent relays are sensor flow from turning ON when contact set is OFF or open switch main recirculation flow Contact sets may be configured as inverted to act and display as ON when they are OFF switch auto fill switch or low chemical level alarm Contact sets may be configured to mirror a controlled relay or frequency controlled pump acting amp displaying as ON when the relay or pump is ON Page 37 DCM 5 Installation Page 38 DCM 5 Installation 6 4 Feed Verify amp Inventory Methods Any water meter input may be used to verify flow while a pump solenoid or valve is ON
40. int and 100 TurnON setpoints ORP Oxidant As the pool or spa operates contaminants are introduced Chlorine is consumed and the ORP falls Proportional control The hypochlorite pump is OFF at ORP gt TurnOFF The pump speed increases linearly between TurnOFF and 100 ON setpoints Measure The Water meter measures volume Water Meter Volume measured on meter The controller turns ON the pump at Maximum SPM ppm adding the volume reguired to meet the ppm setpoint Controlled Feed Example Measure 250 Gallons Feed 1 5 ppm opm of product to feed Rarely used in Pool and Spa operations mL minute setpoint Additional Acid Pump ON when Fill Solenoid ON Especially useful where high pH makeup water feeds into balance tanks and temporarily upsets the pH chemistry Base Pump feeds at user set rate unless flow switch interlocks Feed mL minute setpoint turns OFF feed Not normally used in pool and spa applications Pumps user set volume at maximum SPM Probe Wash Events Feed Volume Timed User sets cycle period in Pumps user set volume 1mL to 10L at maximum SPM Cycling minutes and ON volume in mL atthe start every user set period if above TurnON setpoint Not typically used in Pool and Spas Contact Set TurnON seconds TurnON user set seconds after contacts close amp Controls TurnOFF seconds display ON Turn OFF user set seconds after TurnON Fed at maximum SPM Not normally used in Aquatics Page 40
41. ion line and no anti siphon device is installed on the chemical feeders potentially hazardous concentrations of chemicals can be drawn into pool or spa Always use injection check valves and anti siphon valves in the chemical feed lines to prevent this situation from occurring Electrical Surges ELECTRICAL SURGES CAN DAMAGE YOUR CONTROLLER Uncontrolled feeding of chemicals can result in injury or death A damaged controller could feed chemicals in an uncontrolled manner If you suspect your ProMagua controller is not operating properly disconnect it from the chemical feeders until the problem has been corrected ProMinent controllers like all modern electronic devices can be damaged by severe electrical spikes and surges like lightning Every effort has been made to harden your controller against such surges but no precautions are 100 effective Additional surge protection can be installed at time of installation but even that is not a guarantee that surge damage will not occur If surge damage occurs chemicals could be fed to your pool or spa continuously with no safety controls If you inspect your ProMinent controller after a possibly damaging power surge thunderstorm or power outage and suspect the controller is not operating properly disconnect the chemical feeders at once and contact your ProMinent dealer for service Water disinfection control involves irritating corrosive READ AND FOLLOW ALL MSDS caustic
42. lation works on both Rising or Falling Setpoints PID Time Modulation Relays 1 5 Application Time Modulation applications where additional variable loading control is needed like extremely variable bather loading Setup User selects a relay amp selects Special Control PID Control User sets Relay Period in seconds as in Time Modulated control minimum 60 recommended default 120 maximum is 600 seconds User sets Kp Proportional factor for correction to deviation from setpoint User Sets Ki Integral factor for correction for loading User Sets Ki updated time for how often checks are made for loading correction User Sets Kd Differential factor for corrections due to guick sensor changes User Sets Kd updated time for how often checks are made for guick sensor changes Operation See PID Appendix for detailed setup explanation 6 Sensors 6 1 Compensation Analog Sensors A N Type Thermal User selected thermal sensor Applied to conductivity sensors Conductivity A N Zero at 70 F or 20 C dependent on metric units User set degree switch setting compensation The defaults are 0 97 F or 1 746 C Thermal User selected thermal sensor Applied to pH sensors pH A N Zero compensation at 7 pH Compensation adjusts sensor gain slope 0 00467 above 25 C amp 0 0058 below 25 pH thermal compensation can only be applied to directly connected pH sensors and not to 4 20MA inputs which may represent pH Ra
43. ler Enclosure Mounting e Locate an area on a vertical wall where the controller can me mounted at approximately eye level and have enough clearance to allow the DGMa modular sensor housing to be installed near and below the controller The location of the sensor housing must have about 18 of clearance above it to allow removal of the sensors and about 12 inches below for removal of a conductivity sensor if installed a oR i NOTE a common mistake made at installation is not allowing enough space above the sensor housing to accommodate easy sensor maintenance e Individual DCM5 controllers are shipped with mounting bracket and mounting screws to assist with wall mount installation Install bracket using the machine screws provided and fasten securely to the back of the enclosure as shown e Install the enclosure on a vertical wall at approximately eye level within 3ft of the nearest 120 VAC power outlet Alternatively mount near a power disconnect and wire the power directly to the controller through electrical conduit Refer to local and national electrical codes for wet locations e After controller is mounted time is best used mounting the DGMa modular sensor housing to allow sensors to equilibrate while the remainder of the installation and wiring is performed 1 Pull the two snap hooks 1 outwards gt The wall brackets snaps slightly downwards 2 Push the wall bracket downwards 2 from the DXC housing and fold
44. ller cannot prevent the uncontrolled feed of chemicals which could cause personal injury or death Testing of the flow switch installation is essential to assure the flow switch stops remains stopped and controller shows SensorFlow ALARM within 20 seconds whenever filter is in backwash or circulation flow stops If the flow switch does not fully drop plumbing corrections or the installation of additional safeguards will be necessary to avoid uncontrolled chemical feed Chemical Feeders NEVER CONNECT FEEDER DIRECTLY TO POWER SOURCE If the chemical feeders are connected to a wall outlet the safety devices integral to your ProMaqua controller and to the safe feeding of chemicals will be bypassed It is very important that the chemical feeders be connected to the controller and never directly to a wall outlet If the chemical feeders are connected to a wall outlet and feeding continuously when the flow of water to the pool stops due to filter backwash the circulation pump losing prime or other causes potentially hazardous concentrations of chemicals can be fed into a pool or spa Follow Instructions carefully to insure safe operation Page 6 DCM 5 Installation ALWAYS USE ANTI SYPHON DEVICES Uncontrolled feeding of chemicals can result in injury or death Anti Syphon devices must be installed on chemical feeders to prevent uncontrolled feed of concentrated chemicals If a vacuum is created in the water circulat
45. long as you don t combine volumes measured with different units US Units All volumes measured in Gallons Metric All volumes in Liters Zeroing a Water Meter Switching a water meter to a contact set and then back to a water meter will zero the meter and set the default units to L or Gal depending on the Metric US Units switch 6 10 3 Rate to Volume The rate displaying on the sensor input converts to a volume based only on the Rate Minute Rate Hour switch setting If you are measuring rate in GPM or LPM then the volume logged by the target water is in Gallons or Liters respectively Note that in both examples the volume units are set by the measured rate units and not by the Metric US Units switch Example1 A stream demand meter measuring 1200 Ibs hour would increase the volume on the target meter by 20 lbs per minute 28 800lbs day Set the units on the target meter to lbs Example2 An RO waste meter measuring 10 GPM would increase the volume on the target meter by 10 gallons per minute 600 gallons for every hour Set the units on the target meter to gal 6 10 4 Copy Volume to Copying between water meters uses the units set by the Metric US Units switch Copying a volume from a frequency controlled pump to a water meter converts mL to Gallons if the Metric US Units switch is set to US Units Copying a volume from a freguency controlled pump to an Inventory sensor input converts pump mL to either Liters or Gallons d
46. may be mixed with pulse signal frequency controlled pumps 2 Installation Commissioning 2 1 Safety Before we talk about any installation or configuration we need to talk about safety for you and your co workers customers and swimmers Please read and follow the caution and warning statements below to familiarize yourself with the hazards associated with installation and operation of the equipment covered in this manual Electrical Shock Hazards Opening the controller enclosure with the controller A BY NN e power turned on or plugged in may expose the user to AC line voltages on the controller circuit boards Hazardous voltages cause severe injury or death Ground the controller AC power to the ground screw Disconnect all sources of located on the bottom of the aluminum back plate power before servicing A 120VAC plug and receptacle socket cables may CREE eae ete De provided with controllers installed in North of power may be present America All must be grounded to the ground screws located on the bottom of the aluminum back plate For personal safety a clear acrylic cover is provided over the power connections and must be replaced after all wiring connections or changes are completed and before power is reapplied Do not discard this important safety device Configuration Hazards Fully understand the implications of the control setpoints interlocks and alarms that you select Aguatic Water Treatment Controllers Injury
47. meter calibration alignment Amperometric Sensor High Residual Exposure Limits Exposure of any duration to residuals above 18 ppm will alter the chemistry of the gel in the CTE CGE and CBR sensors and may damage the membrane If sensors may have been exposed to high residuals and are not tracking properly suspect the electrolyte and membrane have been damaged and replace them When using high chlorine residuals for shocking or performing a fecal incident response procedure always isolate the sensors by closing the lab valves to the DGMA flow cell before the high residuals are introduced Keep sensors isolated until the residual in the pool is well below the 18 ppm threshold for electrolyte and membrane damage If you have an application that requires higher residuals ProMinent offers sensors made for concentrations as high as 200 ppm Consult your Regional Sales Manager for more information Page 29 DCM 5 Installation 4 Password Security 4 1 Overview DCM5 controllers use 4 levels of password for controller access and to stamp the activity log Public Operator Configuration and Administrator Refer to Section for default user IDs and passwords Passwords are defaulted OFF for keypad users and ON for Browser users Passwords cannot be turned OFF for browser users There are 7 user assignable passwords which are distributed between Operators amp those allowed to Configure Passwords are a maximum of 9 letters and numb
48. nal variable frequency control Meters Setpoints are ppm amp volume Control Setpoints Contact Sets See Notes 1 Setpoints are seconds amp feed volume In mL 100 ON O user set seconds after contacts close then feed setpoint volume Sensors Control Range Setpoints are TurnOFF amp TurnON Relay is OFF or ON Meters Setpoints are volume amp ON time Contact Sets See Notes 1 Setpoints are seconds TurnON user set seconds after contacts close Turn OFF user set seconds after ON Events Event ends on volume fed Event ends when time elapsed Logging Limit Volume per Feed MAX SPM Limits Limit Volume Day Notes 2 A water meter input must measure a count to Feed every user set seconds at any non zero control frequency Notes 3 oR Method OR During Events Up to 4 Relay or Frequency controls may block Blocking not typical in pools and spas Blocks on any Relay ON or any Frequency at a non zero SPM Limit Time ON per actuation Limit Time ON Day Notes 2 A watermeter input must measure a count within a user set seconds of turning on the control relay Notes 3 Rising Falling amp Between setpoints Rising Falling amp Between during events Up to 4 Relay or Freguency controls may block Blocks on any Relay ON or any Freguency at a non zero SPM Flow Switches Contact Sets may be ORed or ANDed Contact Sets may be ORed or ANDed Modulation approaches TurnOFF setp
49. nductivity Calculated Sensor GAIN is adjusted so that the sensor value matches the user s calibration value Temperature pH Cl ppm Sensor OFFSET is adjusted so the sensor value amp Corrosion Rate matches the user s calibration value ORP is a factory only calibration Ryzner and Langelier s index Hardness Alkalinity and Conductivity values are entered for index calculations Inventory Manual Sensor OFFSET is set so the sensor value matches the user s calibration value Since the GAIN on these inputs is zero the OFFSET is the input value for control and logging During calibration users have the option to Reset to Factory which resets the sensor GAIN amp OFFSET to default values If the calibration OFFSET or GAIN is outside fault limits users are offered the option to OVERRIDE OFFSET or GAIN outside of the fault limits typically indicates a sensor cabling or driver fault Users also have the option to manually enter OFFSET and GAIN by selecting Sensor then Configure The value of a sensor Measured Level mV x GAIN OFFSET This value may be modified by sensor compensation Compensation Temperature Rate Volume Corrosion Rate is applied after GAIN amp OFFSET WATER METERS P Z The user calibration value is Volume contact for contact head meters and K factor Pulses per unit volume gallon for turbine and paddlewheel meters General Calibration Instructions Typical calibrations involve taking a wate
50. ntroller 15 20VDC While alarmed sensors meters and current loops DC Power Output supply powered by the 15VDC supply will not operate Internal 2 5V Out of Range Used to auto calibrate all sensor measurements to Sensor meter or contact set wring remove power supply drift error error or driver card fault All sensor measurements stop auto calibration Power on fault Controls Removed The pump or solenoid controlled by the removed One or both sensor driver cards have sensor turns OFF Re configure the control been removed or type changed Indicating LEDs Name Location Function I OK Screen Orange Screen ALARM Green Front Measure board ON when the controlling processor on the upper measure circuit Running Right side center board is communicating with processor that measures water meters and contact sets and supports a USB connection Back Power board ON when the controlling processor on the upper measure circuit above the NEUTRALS board is communicating with the lower power control processor wiring block ON when the AC line fuse powering R1 to R5 is NOT open Lower Power board ON whenever the Relay is ON Above Relay1 to Relay5 ON when the NO wiring terminal is at the AC power voltage AC wiring terminals Lower Power board ON for 50 of the pump frequency period Above P6 to P9 control Mirrors the time that the electronic contact set pulsing the pump terminal is closed Exampl
51. oint Verification Notes 3 Notes 3 Pump Type Selection User selects Pump Type which sets default mL stroke amp Max SPM Other type allow user to set MAX SPM All types allow user to modify mL stroke Checks that existing feed rates are possible when user changes pumps or set to MAX SPM and alarm message if feed rate modified Pump changes update the event log Copy Sums to water meters Volume to Subtracts from Sensors Inventory Notes 4 Page 42 Not applicable Not applicable DCM 5 Installation 6 8 Relay amp Freguency Controls Comparison cont Contact Sets Runs once per controlling contact closure In addition to being able to use Contact sets to turn ON amp OFF relays and freguency controls contact sets can have the following compensation Mirror Contact set Closed when user set output ON and OPEN when output OFF May be used with phantom contact sets U to Z If used with inputs O to T the physical input is ignored by the controller Invert ON OFF Switches the logical sense of the contact set so you can control on contacts opening and if you also select Mirror a relay turning OFF Applications Allows a control only when relay changes state Flushing or priming feed headers Day tank fill drain filter backwash or mixer seguence controls Neutralization timing controls Feed Limits Users may set OFF on Alarm turning OFF a Relay or Freguency on limit Users may also
52. omputer to make calibration changes To change a calibration of any of the above sensors the keypad procedure is the same as the pH calibration example use in the Quick Start Guide that came with your DCM5 controller 1 Performa pH test and NOTE the results 2 Press 2 times e Oxidant e pH Sensor_C 3 Press 4 3 times e Editing lt or Exit e Calibrate e Enter Value 4 Press t 4 9to adjust displayed value to match the tested value then press lt to accept the change 5 Press BACK to return to the main status screen Browser Calibration Step by Step From Section 4 of the Browser Manual e Log in to the controller using your Configure level password e Choose the sensor to calibrate then select the link under the sensor value e Atthe top right of the screen pull down the Diagnostic menu selecting Calibrate e Make sure the 1 Point Calib Button is showing Yes e Type in the samples tested value in the Enter Value box e Pressthe SUBMIT button e Move to the next sensor to calibrate and repeat until all calibrations have been performed Refer to the DCM5 Browser manual for more information Page 27 DCM 5 Installation 3 2 Two Point Calibration Two point calibration is limited to pH sensors There are no fault limits on GAIN or OFFSET for Cll ppm inputs Reset to Factory Newly installed sensor driver cards amp reconfigured water meters are Reset to Factory Default calibrations when controller Power is first
53. operates as an HTML micro server for command amp control using Microsoft Internet Explorer Apple Safari and Mozilla s amp Firefox and other internet browsers available on most computers Logged data is served as an XML file in response to an HTML request This feature makes configuration easy using common Ethernet network browsers already installed on most computers and easily supported by local IT departments This port also supports the ProMinent Trackster download auto poll analysis and report software package USB Services Contact sets are flow and level switches They are used to interlock and to initiate feeds Input O is defaulted as the Sensor Flow Switch safety interlock and should not be changed Meter volume inputs calculate flow rates using turbine paddlewheel K factors display flow rate totalize volume today and this year Example A Paddlewheel Turbine pulse GPM input on P may be converted to a minimum recirculation flow switch on XK Controller powered outputs switch 120 VAC pumps valves amp solenoids ON OFF Log time ON Relay 1 is SPST only Relays 2 5 are SPDT for motorized valves reguiring power OPEN amp power CLOSE if needed Outputs can alarm on runtime per actuation and per day Variable speed pulse output feeds with presets for popular ProMinent and other pump ml stroke and maximum rates Calculates amp logs volume fed Use volume fed to calculate ppm amp inventory All
54. operations staff and swimmers The DCM5 controller is provided with a clear acrylic safety cover over the high voltage terminal that must be removed before and replaced after any wiring is performed on the back Power circuit board Wiring Guidelines AC Controller Power Power the controller using a dedicated separate breaker in the local lighting distribution panel Do not route the controller AC power in common conduit with variable freguency pump drives Like most modern electronic microprocessor devices controllers are affected by dirty line power and voltage surges and spikes AC Power to Valves amp Solenoids Controller ON OFF relays switch and power the AC line to valves solenoids and solenoid pumps Ensure that each valve amp solenoid has a dedicated neutral cable between the controller and the valve or solenoid Do not share a common neutral to multiple valves or solenoids Inductive loads like solenoids and small pump motors should also have additional surge protection Fractional Horsepower Chemical Feed Pumps The controller ON OFF relays 1 through 5 are fused at 5 amps total which will power multiple solenoid driven chemical feed pumps and solenoid coils Fractional horsepower feed pumps gt 1 8 HP are commonly used in high pressure chemical feed applications and large volume Sodium Hypochlorite pumps Typically the motor inrush current reguires a dedicated breaker and separate AC feed from the controller AC power breaker N
55. p Offset after ID Level correction Gain Multiplier 3 1250 Calibration adjusts Gain Displayed Value Measured Level x Gain Multiplier Offset Adjust Both single and two point calibrations recalculate Gain Both single and two point calibrations recalculate Offset 2209 mV Design level 2216mvV 12mA Driver Verification Test 12mA is 50 of a 4 20MA loop 16mA span Connect a 2K ohm Optionally use 2 x 1K 5 1 4W resistor between CII card 24 VDC terminal amp adjacent IN1 or IN2 terminal OR Connect the output of a 4 20mA calibrator and set the 4 20mA output to 50 12 0 mA Diagnostic Displayed Value will be nominally 570mV at Factory Default GAIN 1 amp OFFSET 0 0 The actual test current in mA is the DC voltage across the test resistor divided by 2000 The measured voltage is 50 ohm x the DC voltage in mV Page 56 DCM 5 Installation Calibration Current loops require two point calibrations to convert the measured current into end user units If 4 0 mA represents zero sensor value single point calibration may be used The current loop may be calibrated using either the Keypad or the Browser It s also possible to calculate the input OFFSET amp GAIN to convert a 4 20mA signal to its equivalent sensor value Single Point Calibration Many current loops use 4 0 mA to represent 0 0 ppm as in the DCM5 These loops can use single point calibration The controller assumes that the 4 0 mA level is s
56. p of the ring at the bottom of the shaft is at or above the 12 5 gph mark and tighten the compression nut to keep the shaft from leaking and secure the flow switch shaft in place e When you are ready to open up the sample water valves remove the protective caps from the pH and ORP sensors and clean both sensors with Isopropyl alcohol followed by a mild acid using a soft bristled toothbrush e IMPORTANT If you are installing a chlorine residual sensor refer to the sensor manuals and charge the sensor with electrolyte before beginning sample flow e Nowopen the supply and return valves fully to evacuate all the air from the modular sensor housing e Onceallair has been evacuated reduce flow through the assembly to 11 13 GPH for optimum residual sensor performance If only pH and ORP sensors are being used flow can be between 11 and 25 GPH as long as it is stable e Allow sensors to equilibrate while you complete the wiring of the controller ProMinent Page 13 DCM 5 Installation 2 3 Wiring A DANGER Hazardous voltages cause severe injury or death Disconnect all sources of power before servicing Multiple and or remote sources of power may be present Before beginning controller wiring be sure power has been removed locked out and tagged as under repair before proceeding Observe all national and local electrical codes during wiring and installation to best assure your safety and the safety of the pool
57. perator2 Operator3 Operator4 Configure Configure5 Configure6 Configure7 Keypad LCD access cannot change User Type or ID MOULA If you are going to use keypad passwords your first action after turning passwords ON should be to change the admin and all other passwords since leaving any password at it s default value bypasses password protection NYS Only the admin user can load a new controller view configuration Page 31 DCM 5 Installation 4 5 Passwords Reset Contact ProMinent Technical Department with the controller serial number to obtain a reset password which resets all passwords to the factory defaults shown above Proof of controller ownership is understandably required DCM5 controllers have no backdoor or super user password If you forget the password this is the only way to recover controller access 5 Application Notes 5 1 Sensor Inputs amp Control Outputs The controller uses the letters A thru Z to identify input sensors like pH ORP Chlorine Residual Flow Switch Surge Level Recirc water flow meter and other analog or Digital signals The numbers 1 to 9 identify the five 5 AC power switching relays and four 4 pulse frequency outputs A to G and O to V exist as terminal blocks where inputs are connected Sensor inputs H to N and meter contact set inputs W to Z are used to implement more complex control and monitoring functions like cal
58. powered by a DC isolated 24VDC supply included on the Cll card The Cll driver terminates each current loop with 50 ohms Each 4 20mA input is polarity and thermally protected Driver Card Installation Turn OFF the controller AC power A CII driver may be installed in only card slot E amp F After installing the CII Driver turn the controller ON and the DCM5 will auto configure displaying both inputs as millivolt levels 200mV 4mA to 1000mV 20mA Driver Card Wiring AWG22 0 25 mm current loop cabling may be extended several hundred feet or meters without causing measurement errors The maximum cable length is determined by the open loop voltage and the cable gauge Do not install current loop cabling in the same conduit as AC power cabling Current loop cabling may share a common conduit with other sensors water meter and contact set cabling DC Isolation Each 24VDC Input amp common is electrically isolated from the other and from the controller power supply Loop Active LED When IN1 loop current is gt 3 5MA this green LED is ON Loop Active LED When IN2 loop current is gt 3 5MA this green LED is ON Page 53 DCM 5 Installation Driver Card Wiring cont Controller Powered 4 20mA Current Loops Loop Powered Sensor 1 Loop Powered Sensor 2 Controller 24VDC powers sensor Controller 24VDC powers sensor Return Output 24VDC Input 24VDC Input Return Output IN2
59. r sample performing chemical tests on the sample and adjusting the controller s corresponding sensor readings to the values tested Following some basic guidelines below will minimize your effort while maximizing your calibration accuracy with the first test e Thebesttime to make adjustments to sensor calibrations is typically in the morning when the water has been unloaded for the longest period of the day e Make sure any feed of makeup water or any chemical has not happened for at least 30 minutes and all of the readings to be calibrated are stable on the controller display e Make sure all the sensors have been in the normal sample flow for as long as possible before the calibration but at least 30 minutes since the flow was last stopped or changed a measurable amount This means you should do your backwashing or sensor maintenance after the time you choose to calibrate the sensors or several hours before Page 26 DCM 5 Installation e Verify the flow on the flowcell is at and does not exceed the 11 13 gph recommended for the residual sensors or between 11 and 25 gph and stable if no residual sensors are installed e Slowly open the sample petcock on the flow manifold and check that there is a small positive pressure not a vacuum on the flowcell avoid opening the petcock wide open to dramatically change the flow rate across the sensors as this will cause an additional 30 45 minute re equilibration period before an accurate calibration c
60. re lid is open AC Line power may still be present if the controller is not unplugged or has power removed with a lock out device Controllers may be supplied prewired with either 120VAC receptacle cords or ready to be installed with conduit and individual wiring Page 17 DCM 5 Installation Enclosure Entries Remove the controller frame assembly prior to drilling any additional enclosure entries to prevent damage to wiring and circuit boards The frame assembly is secured by 6 Phillips screws Do not put conduit entries in the top of the enclosure Resulting conduit condensation and failure to seal may damage controller circuit boards Sensor wiring in the same conduit with AC power will cause measurement errors and measurement instability 1 Plan which threaded holes shall be broken out mark the desired threaded holes CAUTION When breaking open the threaded holes avoid pushing the screwdriver deep into the housing Parts inside the device could be damaged Fig 10 Breaking out threaded holes 2 To break out the threaded holes punch the slit in the middle of the threaded holes using a screwdriver tip width 3 5 4 mm see Fig 10 and lever the material out 3 De burr the resulting edges NOTE Enclosure threaded holes are metric sizes M20 P11 and P7 2 3 1 Line Power Wiring The factory pre wired your controller with a power cord and two 120VAC receptacle cords unless you requested otherwi
61. roper wiring of power Individual sensors and feeders 5 5 E I la m m OC in im Li DCM 5 Installation Controller Wiring Terminals Controllers consist of two main circuit boards a left Measure circuit board and a right Power board The left Measure circuit board supports 7 analog sensor inputs and 8 digital Inputs It is connected to a single 2 line x 16 character LCD display an Ethernet jack and a control module Measure Left Card Diagram with General Arrangement of Sensor Connections MN Ta Interior of DCM5 controller POWBT Elparnslon Control Module Ath Ostion zi latini Jack Sl d en A nt Mats amp contet Setnputi 21521 lt 6 ouput OP ORE ST UY SDAOSAT OK ECOSOC DOD Sensors Sensor R J45 Turbine ontact Heal A amp B a Ethana Curent amp Turbine Meters Conductivity Jack Loop Flow amp Leve Switches Tanperature Power sensor Page 16 DCM 5 Installation Controller Wiring Terminals cont The right Power circuit board has 5 ON OFF Line Power Relays 4 DC low voltage or pulse outputs and the controller power supply Power Right Card Diagram with General Arrangement of Power and Feeder Connections AC Power cabling to optional 3 door mounted ON OFF DVOVIOSOOD OCDVAOSOD FOVEYVIOSOOD AC Power AC Power to econ IN amp fused Solenoids oe y Auxiliary Power Valves amp Pumps tia OUT er vtggie When blue enclosu
62. rs easier and less expensive E and Isolated 4 20 mA input F inputs are not available if the residual sensor or Second card used for ProMinent Pool option is not installed chlorine residual sensors It is also used for an additional OP card for pH and ORP on a second pool or spa G Fixed 4 20mA ae I Support for loop powered and isolated 4 20mA inputs like PR am sensor or surge tank level The default is UV sensor huusi H to N If the expansion board is Inputs used to for calculated and manually entered values not installed these virtual like Calculated Langelier s and Ryznar s Indexes Combined sensor inputs have no Chlorine and inventory tank levels Manually entered drop physical connection and count chemical test results are used for calculated Page 32 DCM 5 Installation Meter Contacts O to V Phantom or Virtual Contact Inputs W to Z Relays 1 to 5 Freguency Outputs 6 to 9 logging and control The optional expansion board uses these as its hardware inputs H I K L M and N Eight digital inputs individually configurable as meter volume or contact set inputs Phantom digital inputs used for logging and control AC Line powered outputs ON OFF controls DC isolated non mechanical 0 to 400Hz 4 2 Communications Ethernet LAN TCP IP The DCM5 controller contains a 10 Base T RJ45 Ethernet port that can use a fixed or Dynamic IP address assigned by your network server The controller
63. se For conduit wiring configurations remove the cords supplied and replace the cord wiring with the individual wires from the conduit The same terminals are used and are shown in the diagram below for reference Page 18 Fig 11 Fitting the threaded cable glands Blanking plug Union nut Multiple seal insert Lock nut 2 2 3 4 Threaded cable gland a 4 Screw in the appropriate threaded cable glands 4 using suitable lock nuts 5 and tighten firmly Insert multiple seal inserts 3 depending on the cable diam eter being used Guide the cables into the threaded cable glands Further steps are contained in Chapter 5 1 4 Connect the coaxial cable on page 34 and Chapter 5 1 5 Connecting the terminals on page 34 Tighten the union nuts 2 of the threaded cable glands so that they are properly sealed Place the front part on the rear part Manually tighten the four housing screws DCM 5 Installation I To Measure Card Line Voltage Select Relay Fuse 5 Power Relay 4 Pump ON OFF Freguency 8 115V Controls AC I DC Controls AC RELAYS 1 3 AC RELAYS 4 5 FREQUENCY CONTROLS RUN R1 R2 R3 R4 R5 P6 P7 P8 P9 AC POWER EM NONCNONCNO NCNONCNWOV AB AB AB AB LLMNN NEUTRALS psosfpszo 2600 SES For individual wires fed from conduit connections are the same as shown here 120VAC Line Black or Red to Terminal marked L Neutral wires White tie to any terminal marked N All Earth Ground wir
64. set Midnite Reset to reset a feed limited output at midnight Feed Verify Users may set Feed Verify compensation on any water meter by selecting the Relay or Freguency output and the Wait to Verify delay to alarm in seconds Allowing a variable delay to alarm widens applications and supports very low feed rates User selects Verify Output pump valve or solenoid User selects optional Inventory Location and fed volume is subtracted from the tank volume Copy Volume to Users may copy the volume pumped to any water meter input summing the pumped volume with the meter measured volume Meters may also be copied to other meters Inventory Users may also copy the pump volume to a sensor input where the volume pumped is subtracted from the tank volume More than one freguency controlled pump volume may be subtracted from a single tank Page 43 DCM 5 Installation 6 9 System Alarms amp Indicating LEDs System Alarms Alarms are not specific to any sensor or control Name Alarm Message amp Cause Relay 1 5 Fuse Fuse opens 120VAC Pumps solenoids amp valves OFF Data AC line Fuse faults opens logging on R1 to R5 shows zero ON time 5 Amps to the solenoids valves amp Variable frequency controls continue to operate pumps powered by Relays 1 to 5 15VDC External Low Alarm Correct wiring Remove defective sensor Wiring errors or a fault on any sensor 15VDC thermal fuse auto recovers powered by the co
65. surement that does not change as the process pH changes Turn the controller power OFF ON to reset sensor input Page 47 DCM 5 Installation Driver Card Installation 1 2 6 T 8 9 The OP card is normally installed at the factory so field installation is not normally needed If replacement becomes necessary remember that ESD precautions are needed to prevent damage to the OP Driver card and follow these steps 3 Turn OFF the controller AC power 4 5 Disconnect the pH and ORP sensor wires and the solution ground from the OP Driver wiring OP Driver card is always installed in the C D slot at the upper left of the Measure Card terminals at the top of the Driver card Remove existing OP Driver by unscrewing the Phillips screw at the bottom of the Driver Card and carefully pulling on the card until the connector at the top of the card is disengaged from the connector on the Measure Board Replace the OP card with the new OP card by carefully plugging in the connector at the top and securing with the screw previously removed Reconnect the pH and ORP sensor wiring and solution ground to the OP Driver wiring terminals Be sure Jumper J2 atthe bottom of the OP Driver card is in the PO position before restoring power to the DCM5 10 After installing amp cabling the OP Driver return power to the controller 11 The DCM5 will auto configure when it recognizes the OP Driver Card has been installed Sensor Types
66. tallation DCMS5 SPARE PARTS Continued Accessories and Replacement Parts Continued PVC Saddle 3 PVC PVC Saddle 12 PVC o Documents gt Page 60
67. te to Volume User selected water meter Typically a 4 20mA input proportional to gpm rate is O Z displays and logs converted to volume to feed ON OFF based on resulting volume volume amp time setpoints User selected rate minute Freguency controlled pumps can be controlled or rate hour directly by the 4 20MA level Corrosion Rate User set alloy number default Controller sets alloy to default and conductivity 1 00 Carbon Steel sensor to none on CR driver installation User selected conductivity Conductivity sensor optional sensor A N corrects corrosion Remove driver to remove compensation rate for conductivity Manual Entry Logs the results of hardness ppm testing or any analog value Any analog input without a driver card may be used for Manual Entry for virtual phantom inputs H to N Page 36 DCM 5 Installation Remove by setting compensation to none ppm log Sensors Oxidant Chlorine Combined Chlorine Total Clo Free Clo Combined Cl Inventory Feed Verification calculated Remove by setting to none in Feed Verify control tank volume log Pumped volume may also be copied to an Inventory input reducing the tank volume by the volume pumped Note pH thermal compensation is seldom used in pools and spas since the pH is typically between 7 amp 8 and the temperature fairly stable so the effect or thermal compensation is limited to the third decimal place Digital Input Sensors O Z Switching
68. trol System 4 20MA monitoring input 4 20mA Return 4 20mA Input N Typically a DCS input is grounded and the sensor current loop output is floating Sharing or Splitting a Current Loop Controller powered or Sensor powered current loops may be shared with the controller and another monitoring or control system without creating a ground loop The Cll card can share two 4 20MA current loops Warning DCM 500 controllers are limited to 1 CII used in Controller Powered sensor mode There is no limit on CII used in sensor powered mode DCM 5 Installation 7 2 7 Configuration Operation Diagnostics Parameter Browser Value Use Display Sensor Location C Installation slot LCD displays slot letter on screen Input Sensor ction Type 4 20mA Input verifies driver card type Current State Operational Alarmed Displayed Value OK 1836 gpm Current measured value with user set units default Displayed with user set resolution Period Maximum 1920 gpm Data from current log interval Used to assess controls Bei nian OK evn gprs Period Average OK fak Sample Size OK 1110 Samples in Period Max Min amp Average Current Period OK 46minutes Elapsed time in current log period Log Period OK _ 60 minutes User set log period 5 to 1440 minutes None Rate to Volume Measured Level OK OK 787 5 mV Raw sensor level in mV before Gain am
Download Pdf Manuals
Related Search
Related Contents
Infos/recos - Entretien des housses de matelas SUN-PVS 太陽光発電ストリング監視システム the Forte Ultrasound La page CONCOURS Manual - Thiim A/S Water Kettle KWK170 1 Introduction - USC - University of Southern California MV-374 / MV-378 VoIP GSM Gateway User Manual PORTech Beko 32WLA530HID User's Manual Copyright © All rights reserved.
Failed to retrieve file