Home
Manual - WISE Data Acquisition Controllers
Contents
1. Module amp Channel Channel 0 Figure 6 6 DI counter condition setting page http 7www icpdas com 26 ICP DAS WISE User Manual Follow the following steps Select the channel that you are going to use the value as evaluation criteria for IF condition statement Specify the channel from the dropdown list of channel field in Module amp Channel section 11 Set up the expression statement for this counter value Select an e 99 99 599 99 99 99 L operator from gt gt ce 99 99S 99 99 2099 99 gt lt Or lt an siete value has to be specified or Change If the operator is if ie DI counter value match the evaluation criteria the result of this condition evaluation will be true If the operator is Change the condition will be true when there is a change in the counter value The action will be executed only once and only at the moment when DO Counter experience a change lll Click Save button to save the settings This popup window will be closed and return to Rule settings page 6 1 4 DO counter DO counter value can be used as evaluation criteria for IF condition statement the editing page for DO counter Condition Setting 1s shown as follow DO Counter Condition Setting Figure 6 7 DO counter condition setting page Follow the following steps Select the channel that you are going to use the value as evaluation criteria for IF conditio
2. Follow the following steps i Specify the channel you are going to configure by selecting channel index from the dropdown list of channel field in Module amp Channel section ll You can set the initial value of the AO channel in the Initial Value field The hardware device will output this value when is power on The default initial value is 0 lil Repeat steps i ii After all AO Channel settings are completed click Save button to save the changes http 7www icpdas com 19 ICP DAS WISE User Manual 5 5 Internal Register Setting WISE provides 48 Internal Registers they can be used to hold temporary variables and to read write data via Modbus address The configuration page 1s shown as below Internal Register Setting Page No 01 No 02 No 03 No 04 No 05 No 06 No 07 No 08 JNo 09 No 10 L No 11 L No 12 No 13 No 14 No 15 No 16 C No 17 CI No 18 C No 19 C No 20 No 21 No 22 No 23 No 24 JNo 25 No 26 JNo 27 JNo 28 No 29 No 30 No 31 No 32 No 33 No 34 CINo 35 CI No 36 No 37 No 38 No 39 No 40 No 41 No 42 No 43 No 44 No 45 No 46 No 47 No 48 Figure 5 5 Internal Register setting page Follow the following steps i A checkbox appears for each Internal Register check the checkbox to enable the Internal Register You can also enter a default value for the Internal Register li After you finish selecting the Internal Registers y
3. http 7www icpdas com 25 ICP DAS WISE User Manual lll Click Save button to save the settings The popup window will be closed and return to Rule settings page 6 1 2 Di DI channel value can be used as evaluation criteria for IF condition statement the editing page for DI Condition Setting 1s shown as below DI Condition Setting Module amp Channel WISE 7026 Channel Channel Value Figure 6 5 DI condition setting page Follow the following steps i Select the channel that you are going to use the value as evaluation criteria for IF condition statement Specify the channel from the dropdown list of channel field in Module amp Channel section ll Define the evaluation criteria of the status in IF statement to be OFF ON ON to OFF OFF to ON or Change If the change of DI channel value matches the evaluation criteria the result of this condition evaluation will be true Please note If the statement involves state transitions ON to OFF OFF to ON and Change the action will be executed only once and only at the moment when the state transition occurs lll Click Save button to save the settings This popup window will be closed and return to Rule settings page 6 1 3 DI counter DI counter value can be used as evaluation criteria for IF condition statement the editing page for DI counter Condition Setting is shown as follow
4. 150 mV 150 mV x 150 mV 150 mV 150 mV 150 mV x 150 mV 150 mV AI8 AI9 AI10 Ani 150 mV 150 mV x 150 mV 150 mV AI12 AI13 AI14 AI15 Al16 All7 All18 AI19 Figure 4 3 WISE 70xx 71xx Al DO module setting page http 7www icpdas com 14 ICP DAS WISE User Manual 9 AI AO Module Analog I O module WISE 7026 7126 module These modules equip with both AI and AO channel therefore the voltage range or current range for each AI AO channel must be defined The setting page 1s shown as below Module Setting Page AO Voltage amp Current Input AOO AOl 5V 5V x 5V 5V_ y AI Voltage amp Current Input AIQ All AI AB 5V 5V Y 5V 5V v 5V 5V v 5V 5V x AI4 AI5 5V 5V 5V 5V l Figure 4 4 WISE 70xx 71xx Al AO module setting page 4 3 Password Setting Password Setting allows users to change the password and password hint for upload access control of logic rules The Password Setting page 1s as follow Password Setting Page Old Password Confirm New Password Figure 4 5 Password setting page The default password for upload access control is set as wise To avoid unauthorized access and altering of data it is required for users to input password before they start to upload control logic to the controllers Password Setting page allows users to modify the password and password hint Password length is limited to 16 characters and the
5. ON or to be OFF when the hardware device is power on Select the value from the dropdown list of Power On Value field The default value is OFF iii You can set the trigger criteria for triggering the counter to count http 7www icpdas com 18 ICP DAS WISE User Manual There are three criteria HI to LOW LOW to HI and Status Change This field cannot be None if you want to use the counter function of this channel You can also specify the initial value of the counter in the Initial Value field This counter will start counting from the initial count value The default initial value is 0 iv If you check the Enable pulse output checkbox it will allow this DO channel to perform pulse output In Pulse Output mode the selected DO channel will generate a square wave according to specified parameters Pulse High and Pulse Low Pulse High and Pulse Low are required and has to be entered in multiples of 10ms Pulse High indicates the ON time duration and Pulse Low indicates the OFF time duration in a periodic Pulse cycle vV Repeat steps 1 iv After all DO Channel settings are completed click Save button to save the changes 5 4 AO attribute Setting AO Attribute Setting page allows to set up initial value of the AO channel The configuration page is shown as below AO Attribute Setting Page Module amp Channel Channel Initial Value Figure 5 4 AO Attribute setting page
6. Please note the Timer you select has to be enabled in Advanced Setting li Specify you want to Stop or Start this Timer when this THEN ELSE Action statement is executed lil Click Save button to save the settings The popup window will be closed and return to Rule settings page 6 2 7 Email You can send a message to an Email group when executing a THEN ELSE Action statement the editing page 1s shown as below http 7www icpdas com 33 ICP DAS WISE User Manual Email Action Setting gm Email Information Subject Warning Email 1 1st Receiver Email Teg Address michael_lai icpdas com 2nd Receiver Email Address 3rd Receiver Email Address 4th Receiver Email Address 5th Receiver Email Address Figure 6 16 Email action page Follow the following steps Select the pre set Email group from the dropdown list of Index field The Email group information will be displayed for you to verify if this is the Email group you are going to send the message to ll Click Save button to save the settings The popup window will be closed and return to Rule settings page http 7www icpdas com 34 ICP DAS WISE User Manual 6 3 Summary of the Rules After you finish editing all IF condition and THEN ELSE action statements for a rule return to the Rules Setting page and click Save to save all settings of this rule Please note if you want to clear previous sett
7. WISE Firmware Uploader Setup exe O Double click the setup file to install the file you will see a window pop up as below click Next to continue 5 WISE Firmware Uploader version 1 01 Setup Welcome to the WISE Firmware Uploader version 1 01 Setup Wizard This wizard will guide you through the installation of WISE e Uploader version 1 01 is recommended that you close all other applications ore starting Setup This will make it possible to update want system files without having to reboot your ter WARNING Before you install backup you customized Files because they will be overwritten Click Next to continue Figure 10 1 Install WISE Firmware Uploader http 7www icpdas com 43 ICP DAS WISE User Manual O Choose the installation location to install WISE Firmware Uploader Click Install to start the installation 5 WISE Firmware Uploader version 1 01 Setup Choose Install Location Setup will install WISE Firmware Uploader version 1 01 in the Following Folder To install in a different Folder click Browse and select another folder Click Install to start the installation Destination Folder ANNAN Firmware Uploader Space required 338 0KB Space available 1 6GB 110 15 at EF 09 50 18 Figure 10 2 Select installation directory O The installation progress will be shown as below please wait till the installation 1s completed gt WISE Firmware Uploader version 1 01 Setup I
8. buttons to move the selected rule to the desired location and then click Save to save the settings 9 Swap Exchange the Rule content of a pair of rules Click Swap button a window as shown below will pop up Rule Swap Swap Figure 6 23 Rule Swap setting page From the left side drop down list select the first rule has to be previously edited and select the second rule from the right side drop down list the rule content can be blank click Save to swap the rule content http 7www icpdas com 39 ICP DAS WISE User Manual 7 Upload to Module Upload button allows you to upload edited rules from Web UI to hardware devices Click the Upload to Module button a popup window will appear for user to input the password Please enter the password Password Figure 7 1 Please enter the password If the password is incorrect the upload will not be processed the upload process will be started only when the correct password is entered Current upload progress will be displayed as below Saving Do not close this window 50 Figure 7 2 Upload to Module status page When the upload is finished the popup window will notify the saving process 1s completed The saving process is completed 100 Figure 7 3 The informing message when successfully Upload to Module Close the popup window and go back to the Rules Setting window About 3 seconds after the upload is completed th
9. 14 Figure 4 3 WISE 70xx 71xx AI DO module setting page ccccccooooonncnnnnnnnnnnnnannnnnss 14 Figure 4 4 WISE 70xx 71xx AI AO module setting page ccccccoooooncccnnnnnnnnnnninnnnnos 15 Frcure 4 5 PassWord setine Pase iio 15 Prone 9 1 5 Timer sete Pare a 16 Figure 5 2 DIAttribute Setting pafe ni ici iii 17 Figure 5 3 DO Attriblte setting Parcial dia 18 Figure 5 4 AQ Atribute Setin Ss PA io 19 Figure 5 5 Internal Register setting pase ad 20 Pistre 5 6 Ema Sete pace cara 21 Fistite 0 1 R les setine Pas 6 aia ai na a 23 Figure 6 2 Enable rules edit rules and status display cccccoooooooccncnnnnnnnnnnnonos 23 Proute 6 5 Rule SEMIN S Pase iio 24 Ficure 6 4 gt AT COnGitiOn setne PALO siii is 29 Figure 6 3 DI Condition setting pag iiiciiini idas 26 Figure 6 6 DI counter condition setting page occcccccccnonnnonnnnnnnnonononanannnnnnnnnnnnnnninnnnss 26 Figure 6 7 DO counter condition setting page seeesssssseseererssssssssseeressssssseeeeees ZT Figure 6 8 Internal register condition Setting page cccccccononncnnnnnnnnnnnnonanannnnnnnnnnnnnnnns 28 Figure 6 9 Timer Condition Setting Page ccccccocooonccnnnnncnnnnnnnnnnnnnnnnnnononanannnnnnnnnnnnnanos 28 ProureG 10 ACACIA pa iia 30 Proune 65 I DO vacio Par o adr 31 Frisure 6 12 D coUnter ACTION PATO ira iii 31 Figure 6 13 gt DO Counter action Pa Se iia a a aa 32 Figure 6 14 Internal Register action Page ccoooooooonccnn
10. A ei ey wa os ea oa oa wa wa ws we Wea wE o o o o o o o o o o 0 9 e Channel Figure 9 1 Channel Status page The Channel Status page will show the values of DI DO AI AO channel DI DI counter and the Internal Register This page will be updated once every 10 seconds showing the latest data of the controllers http 7www icpdas com A ICP DAS WISE User Manual 10 Firmware Update 10 1 Introduction WISE Firmware Uploader is a software tool provides a user friendly interface to easily update WISE firmware that runs on WISE hardware devices With a few clicks users could upload the latest WISE firmware to the hardware System Requirements O Operating System Windows Server 2003 Windows Server 2008 Windows Vista Windows XP O Make sure you have installed Microsoft NET Framework Version 2 0 or later E You can download Microsoft Net Framework Version 2 0 from the link below http www microsoft com downloads details aspx Fam1 l y D 0 89beacb 4362 4b0d 8edd aab1 5cde04f5 amp D1splayLang en E You can download Microsoft Net Framework Version 3 5 from the link below http www microsoft com downloads details aspx fami lyid 3 33325FD AE52 4E35 B531 508D977D32A6 amp display lang en 10 2 Install Uninstall WISE Firmware Uploader 10 2 1 Install WISE Firmware Uploader Follow the steps below to install WISE Firmware Uploader O Obtain the WISE Firmware Uploader setup file
11. AEA Cree LD Figure 10 15 Reset the device ttp www icpdas com 4 8 ICP DAS WISE User Manual Appendix Modbus Address Table WISE allows you to retrieve data on hardware devices via Modbus TCP Register addresses are specified according to Modbus register mapping tables as follows 00000 AGCGTES 1annels E E anne a 10000 30000 Firmware Version 65535 65535 E E channel value 65535 65535 B http 7www icpdas com 49 ICP DAS WISE User Manual 40000 0 65535 0 65535 Rw RW CRW AO channel value 65535 65535 li ares E Internal Register 65535 65535 A Ii OO a http 7www icpdas com 50
12. DO Action Setting Module amp Channel WISE 7026 Channel 0 Channel Value Figure 6 11 DO action page Follow the following steps Select the DO channel to execute actions from the dropdown list of channel field in Module amp Channel section ll Specify the output value of DO Channel from the dropdown list of the Channel Value field The output value can be OFF ON or Pulse Output Please note to make Pulse Output option available here you have to enable Pulse Output in Advanced Setting before editing Rules Setting lll Click Save button to save the settings The popup window will be closed and return to Rule settings page 6 2 3 DI counter You can reset DI counter in THEN ELSE Action statement the editing page for DI counter Action is shown as follow DI Counter Action Setting Module amp Channel WISE 7026 w Channel 0 Counter Res Figure 6 12 DI counter action page http 7www icpdas com 3 ICP DAS WISE User Manual Follow the following steps Select the DI channel to reset DI counter from the dropdown list of channel field in Module amp Channel section ll Click Save button to save the settings The popup window will be closed and return to Rule settings page 6 2 4 DO counter You can reset DO counter in THEN ELSE Action statement the editing page for DO counter Action is shown as below DO Counter Action S
13. Please use IE or Firefox browser to connect to Web server on WISE controller In order to get a better operation experience 1280x1024 resolution is recommended The main page of WISE controller Web page 1s shown as below i A Welcome to ICP DAS WISE web inside smart Engine Web configuration page WISE Engine Version 1 00 OS Version 2 02 10 Module Name WISE 7026 DI channels 2 DO channels o VA Al channels AO channels Configuration Procedure Basic Setting Set up Time Ethernet and Module type Advanced Setting Configure channel attributes and additional features Rules Setting Edit IF THEN ELSE logic rules Upload to Module Upload the settings to the hardware device Figure 3 1 Main page of WISE Web UI Six buttons will appear on the upper part of the Web page Basic Setting Advanced Setting Rules Setting Channel Status Download to PC Upload to Module The main page will display the WISE firmware version information current controller hardware that runs WISE information and general operating procedures hitp 7www icpdas com 11 ICP DAS WISE User Manual The procedures are as follows Basic Setting Advanced Setting Rules Setting Upload to Module Figure 3 2 WISE Web Ul Operation Procedures Please note DO NOT refresh the Web page when you are editing the pages otherwise the contents of all previous settings will be gone And please remember all
14. installation is needed on the target PC Support various hardware controllers that are with different I O types The wide range of I O function modules ICP DAS provided allows users to find best solutions that meet their requirements Please refer to the following table for modules and functions Functions ep ear AAA Without Display With Display Without Display With Display Analog Input Modules Multi Function I O WISE 70xx WISE 71xx Digital VO Series Series Relay Output amp Digital Input I O Expansion Boards WISE 7801 WISE 7801D WISE 7901 WISE 7901D FRnet Remote I O WISE 7802 WISE 7802D WISE 7902 WISE 7902D Modules SMS amp Data Logger WISE 4000 WISE 4000D 2 Figure 1 2 WISE Series Product ttp www icpdas com 7 ICP DAS WISE User Manual Provide Timer and Schedule operation WISE features two kind of timing functions Timer and Schedule It allows user to schedule specific date or time for control logic execution or perform specific tasks such as time delay Real time remote monitoring and alarm via SMS or Email WISE supports SMS and Email functions SMS and Email functions are important functions for real time message communication The sending action can be added to the logic edition as part of logic control to provide real time message transmission function Real time monitoring system status of controllers WISE supports Modbus TCP Protocol for users to perform real time monitorin
15. settings will be effective only when they are uploaded to Modules if you close the Web page before finish Upload to Module all settings will be disappeared as well More detail information of each button will be given in the following parts http www icpdas com 12 ICP DAS WISE User Manual 4 Basic Setting Under the Basic Setting section 1t allows to perform Ethernet Setting Module Setting and Password Setting The Module Setting section allows users to set up configuration of AI AO channels on Analog I O Module such as voltage range current range or operation modes 4 1 Ethernet Setting Ethernet Setting allows you to perform network configuration on hardware devices The following figure illustrates the configuration interface Ethernet Setting Page MER CT If Figure 4 1 Ethernet setting page Each time when you enter this page it will display current network configuration automatically read from hardware devices You can modify IP Mask Gateway configuration of the hardware devices in this section After you finish modification click Save and then all changes will be saved and written back to the hardware Please note 1f you make any modification to the network configuration the hardware device will reboot itself automatically So if there are changes to IP please use the new IP to re connect to the web page 4 2 Module Setting On the module configuration page it allows users to set up con
16. 16 ICP DAS WISE User Manual Follow the following steps il Timer Amount field is required Select the total number of timer you are going to use from the dropdown list li Assign an index number to the time from the dropdown list of the Index field lil Period field is required for each timer please input the period interval in units of seconds iv You can specify the initial status of each timer from the dropdown list of the Initial Status field Select Start indicates the timer will start to count as soon as the hardware device 1s power up Stop indicates the Timer will remain off when the hardware device is power up it will not be activated until being triggered under certain conditions The default setting of initial Status 1s Stop vV Repeat steps 11 iv After all timer settings are completed click Save button to save the changes 5 2 Dl attribute Setting DI Attribute setting page allows to set up detail DI channel counter configuration The configuration page is shown as below DI Attribute Setting Page Module amp Channel Channel Figure 5 2 DI Attribute setting page Follow the following steps Specify the channel you are going to configure by selecting channel index from the dropdown list of channel field in Module amp Channel section li Input the time interval in the Filter field if you want to implement counter function of this channel
17. 8 or later http ftp icpdas com pub cd 8000cd napdos minios7 utility minios7_utility On toolbar select Connection gt Search shown as below A MiniOS7 Scan window will pop up and automatically start searching controllers in the network ta MiniOS Utility Ferion 3 1 8 3 35 File ls Connection de Command New connection EZ Look in MEN LastConnection AIHF2 Disconnect Ctl ES Hame italia goes Cd 71800 Search F12 Figure 2 2 Select Search function on MiniOS7 Utility http 7www icpdas com 9 ICP DAS WISE User Manual After finish searching find the target controller and click TCP Broadcast and then click IP Setting button on the toolbar as shown below ca MiniOS7 Scan search Uptions Connect Clear ra Exit Type IP Port g TCP BroadCast 192 165 255 1 WwISE 7060 Figure 2 3 IP Setting button on MiniOS7 Scan Click IP Setting button a network settings window will pop up Input the information and click the Set button to complete the settings 2 IP Setting ota Recommend Settings IF 192 168 255 1 Mask 255 255 0 0 Gateway 192 168 0 1 Alias DHEP Disable Enable Cancel Figure 2 4 Network Settings page 9 After finish Network settings reboot the controller for the changes to take effect http 7www icpdas com 10 ICP DAS WISE User Manual 3 Website Overview
18. 814000900 Select the component for Action statement from the combo box and then click the right side H button a window will pop up for you to edit detail information The THEN Action statement will be executed only when the result of IF condition statement 1s found true otherwise the ELSE Action statement will be executed The Actions involve with AO DO ON and OFF or Internal Register will be executed over and over again as long as the conditions remain unchanged On the other hand other Actions will be executed only once and only at the moment when their corresponding IF Conditions are satisfied 6 2 1 AO You can execute an action in AO channel in THEN ELSE Action statement the editing page for AO Action 1s shown as follow AO Action Setting Module amp Channel Channel Figure 6 10 AO action page Follow the following steps 1 From the dropdown list of the Module amp Channel field select the AO channel index to execute actions li Specify the AO channel value in Channel Value field The AO http 7www icpdas com 30 ICP DAS WISE User Manual channel value will be changed into this value when executing Action under specific condition ii Click Save button to save the settings The popup window will be closed and will return to the rule setting page 6 2 2 DO You can execute an action in DO channel in THEN ELSE Action statement the editing page for DO Action is shown as follow
19. ICP DAS WISE User Manual for WISE 70xx 71 xx Series Version 1 0 AP ICP DAS CO LTD S MBF A RA ICP DAS WISE User Manual Warning ICP DAS Inc LTD assumes no liability for damages consequent to the use of this product ICP DAS Inc LTD reserves the right to change this manual at any time without notice The information furnished by ICP DAS Inc is believed to be accurate and reliable However no responsibility is assumed by ICP DAS Inc LTD for its use or for any infringements of patents or other rights of third parties resulting from its use Copyright and Trademark Information Copyright 2009 by ICP DAS Inc LTD All rights reserved worldwide Trademark of Other Companies The names used for identification only maybe registered trademarks of their respective companies License The user can use modify and backup this software on a single machine The user may not reproduce transfer or distribute this software or any copy in whole or in part http 7www icpdas com gt ICP DAS WISE User Manual Table of Contents L AMOO CHO Malal 6 DZ Beror COM COM aid 9 X Website e aii 11 A BASIC MINO discos 13 4 1 Ethernet cta o 13 az 1 016 LEN Kao cla road 13 4 3 Password SEUNS a denen r E iaacbanisnnosunsieacstanmencuenss 15 XO AVES a a as osesicaa iba datos 16 5 1 Ean e AA UE E E eee pa EE E A E eee 16 22 DEDE AAA a 17 5 3 DOatribute SeN esra ON 18 DA ADU SEMN S eiaa dio iia 19 5 5 Internal Resis
20. S product web site or contact ICP DAS service to obtain the latest version of the WISE firmware program Copy the file to the computer that you previously installed WISE Firmware Uploader O Connect the hardware device that you are going to update WISE firmware to the network Please verify and make a note of the hardware device IP address you will need it later in the process 10 3 2 Execute WISE Firmware Uploader O Taking Windows XP as an example click Start gt Al Programs gt ICPDAS gt WISE and then click WISE Firmware Uploader under the WISE category to start the program OEA Accessories Startup d 2 Internet Explorer w Faint SS Feview Ewe axes i e PIso Ps400 hb E MavIs mS PISO PS400 ar a g j 5 ET M8194H af Mr WISE Firmware Liploa iui All Programs fan ICPDAS Figure 10 9 Launch WISE Firmware Uploader http 7www icpdas com 46 ICP DAS WISE User Manual 10 3 3 Set up Hardware IP Enter the IP address of the hardware device that you are going to update WISE firmware as shown in the following figure WISE Fimware Uploader version 1 01 CIP 192 168 100 257 ES About WISE Figure 10 10 Assign IP address 10 3 4 Select WISE firmware file Click Select File button browse the file through File Dialog Box to select the appropriate WISE firmware version As shown in the following figure Select
21. The time interval for filter is the minimum duration a signal has to present to make a change to the counter The value must be multiples of 10ms for example a setting http 7www icpdas com 17 ICP DAS WISE User Manual of 20 would mean a 200 ms filter 20 x10 ms iii Please set the trigger criteria for triggering the counter to count There are three criteria HI to LOW LOW to HI and Status Change This field cannot be None if you want to run the counter of this channel iv You can set the initial value of the counter in the Initial Value field This counter will start counting from the initial count value The default initial value is 0 v Repeat steps 1 iv After all DI counter settings are completed click Save button to save the changes 5 3 DO attribute Setting DO Attribute Setting page allows to set up detail configuration of DO channel including Power On value Counter and Pulse Output You don t need to finish all configurations configure the one s according to your needs The configuration page is shown as below DO Attribute Setting Page Module amp Channel Grana Power On Value E Enable Pulse Output Figure 5 3 DO Attribute setting page Follow the following steps i Specify the channel you are going to configure by selecting channel index from the dropdown list of channel field in Module amp Channel section ll You can specify the initial status to be
22. a HEX file is User_Files D Look in 5 EBC573_AUDIO P5400_Setup_23F P5400_ 31RevI WISE 706 e O aa z f My Recent 4 Select File Documents Hi WISE 7060 HEX L Desktop E y File name WISE 7060 E J Hex Files hex My Network Files of type Figure 10 11 Select the WISE firmware 10 3 5 Upload WISE firmware program Click Upload File button to start update WISE firmware to the hardware device WISE Firmware Uploader version 1 01 IP 197 168 100 251 About WISE CAWISE 7060 HEX 2 CEP Figure 10 12 Upload firmware ttp www icpdas com 4 d ICP DAS WISE User Manual The status of WISE firmware update progress will be shown as below Uploading Progress Firmware Uploading Please Wait Uploading Progress Package Installation Status Installing File lc t DO htm LLL LLL LLL LLL LLL LLL LLL LLL LLL Figure 10 13 Display firmware update progress When completing update of the WISE firmware a pop up window will appear to inform the user Close the window to finish firmware upload Information gt lt Firmware Upload Successful Figure 10 14 Complete firmware update 10 3 6 Reset hardware Click Reset button to reset the hardware device The new updated firmware will take effect after resetting the hardware WISE Firmware Uploader version 1 01 IP 192 168 100 251 About WISE CMAISE FOGO
23. ct an operator from gt lt gt or lt and then specify the evaluation value If this Internal Register value match the evaluation criteria the result of this condition evaluation will be true lll Click Save button to save the settings The popup window will be closed and return to Rule settings page 6 1 6 Timer Timer condition can be used as evaluation criteria for IF condition statement the editing page for timer condition setting 1s shown as follow Time Condition Setting Not Timeout Figure 6 9 Timer condition setting page http 7www icpdas com 28 ICP DAS WISE User Manual Follow the following steps 1 Select the timer that you are going to use its status as evaluation criteria for IF condition statement Specify the timer index from the dropdown list of Index field li Define the evaluation criteria of the timer status in IF statement to be Not timeout or Timeout If the timer status match the evaluation criteria the result of this condition evaluation will be true ili Click Save button to save the settings The popup window will be closed and return to the Rule settings page http 7www icpdas com 29 ICP DAS WISE User Manual 6 2 THEN ELSE Action You may use the following values or status as evaluation criteria 1n THEN ELSE Action statement AO DO DI counter DO counter Internal Register Timer Email 91
24. e hardware device will automatically reboot and start to run the rules that have been uploaded At this time you can still edit or modify the content of the rules http 7www icpdas com 40 ICP DAS WISE User Manual 8 Download to PC Download button allows you to retrieve Rules Setting information from the hardware devices and edit them at this Rules Setting page Click Download to PC the following window showing the download progress will pop up The download process is completed 100 Figure 8 1 The informing message when successfully download to PC Click close to close the download process window to finish download Now the rules have been downloaded from hardware devices to Web page you can modify and upload the edited rules to hardware devices later again http 7www icpdas com 41 ICP DAS WISE User Manual 9 Channel Status Channel Status function offers an easy to view monitoring page that allows users to view important controller information in real time without SCADA software The Channel Status page is shown as below OFF OFF cho chi OFF OFF 2 49 2 49 2 49 2 49 AO Channel cho cnt 2 49 0 _Noo1r No02 Noo3 No04 noos Noo6 Noo7 Noos noo9 No10 No11 No12 _ 9 9 o o o o o o o o o o _ _ _ _ o Pg NONE TT o o o 0 0 IO O A A O E es ME es A O A A A A AA A A
25. etting Module amp Channel Channel 0 Counter Rese Figure 6 13 DO counter action page Follow the following steps Select the DO channel to reset DO counter from the dropdown list of channel field in Module amp Channel section ll Click Save button to save the settings The popup window will be closed and return to Rule settings page 6 2 5 Internal Register You can modify the value of Internal Register in THEN ELSE Action statement the editing page for Internal Register Action Setting is shown as below Internal Register Action Setting a Figure 6 14 Internal Register action page Follow the following steps i Select the pre defined Internal Register from the dropdown list of Index field Please note the Internal Register you select has to be http 7www icpdas com 32 ICP DAS WISE User Manual enabled in Advanced Setting li Input the value you want to set to this Internal Register when the THEN ELSE Action is executed lll Click Save button to save the settings The popup window will be closed and return to Rule settings page 6 2 6 Timer You can change Timer status to stop or to start the Timer in the THEN ELSE Action statement the editing page for Timer Action Setting 1s shown as below Timer Action Setting Figure 6 15 Timer action page Follow the following steps i Select the pre defined Timer from the dropdown list of Index field
26. figuration of AVAO channels on Analog I O Module such as voltage range current range or operation modes The hardware module will be automatically detected and will appear on the drop down list The Module Setting page allows users to set up the following three types of module different modules may equip with different I O http 7www icpdas com 13 ICP DAS WISE User Manual DI DO Module Digital I O module includes WISE 7042 gt WISE 7044 7144 WISE 7050 WISE 7051 7151 gt WISE 7052 7152 WISE 7053 WISE 7060 7160 WISE 7065 7165 gt WISE 7066 and WISE 7067 7167 modules Please note these modules contains DI DO channels only therefore no need to set up configuration for channel operation The setting page 1s shown as below Module Setting Page ocu E Figure 4 2 WISE 70xx 71xx DI DO module setting page 9 AI DO Module Analog Input module includes WISE 7005 7105 gt WISE 7015 7115 gt WISE 7017 7117 gt WISE 7017 10 gt WISE 7018Z 7118Z and WISE 7019 7119 modules These modules contains Al channel therefore the voltage range current range or operation mode such as RTD or Thermocouple of each Al channel must be defined The setting page is shown as below Module Setting Page AI Voltage amp Current Input Cl Enable Single ended AIO All AI2 AB 150 mV 150 mV x 150 mV 150 mV x 150 mV 150 mV x 150 mV 150 mV x Al4 Al5 Al6 Al7
27. g and control of the controllers Please refer to Appendix 1 for the mapping table of controller system information and Modbus TCP protocol Address In addition WISE provides an easy to view HMI web interface for real time monitoring It allows users to get important real time system information even without SCADA software Password protection for upload access control for logic rules WISE HMI web page offers password protection it allows users to modify the password for upload access control of the logic rules This document is intended to give you a full range instruction to WISE 70xx and WISE 71xx controllers You will be able to learn how to edit logic of the rules and how to upload the rules to the controllers for conditional execution http 7www icpdas com 8 ICP DAS WISE User Manual 2 Before Connection Before connecting to WISE Web HMI pages please complete the following steps for network configuration The network configuration of the controllers has to be set up for users to connect to Web server on WISE controllers Please make sure the Init Normal switch on the controller has been switched to Normal position Connect the controller to power supply and to the network The Init Normal switch position 1s shown as below Figure 2 1 The location of the switch on the controller Install and execute MiniOS7 Utility MiniOS7 Utility can be downloaded from the following link please download version v31
28. ill be set up to manage and deploy rules for controllers The Rule Engine will check whether the rules are valid or not and determine the execution of actions under specific conditions for examples setting up I O channel values perform scheduled tasks sending Email or sending SMS message under a specific condition In addition through the Modbus TCP Protocol it enables to control and monitor I O channel or system status on controllers in real time http 7www icpdas com 6 ICP DAS WISE User Manual WISE system features 4 IF THEN ELSE logic rules execution ability WISE controller equips with an IF THEN ELSE logic Rule Engine it offers up to 36 IF THEN ELSE rules for users to set up the logic content After completing rule edition and uploading rules to the WISE controller the Rule Engine will loop execute the rules in accordance with the execute order under specific conditions No programming is required to implement logic content on controllers WISE provides user friendly Web UI pages for editing control logic on the controllers It enables to implement logic edition by a few clicks on the mouse to set up and deploy logic rules without writing a single line of code No extra software tool is required all operations can be done through the Web browsers WISE HMI interface runs on regular Web browsers To edit control logic it only requires a browser to connect to the Web server on WISE controller No extra software tool
29. ings after you click Clear button you have to click Save to make sure this Clear status is saved Rules Setting page is shown as below Rules Setting Page iption Condition al i y z z icounier v 2 Time a mema eaae e 2 mD ls m m Figure 6 17 Clear Save Rules Each time you finish editing a Rule will go back to the Rules Setting main page All statements of edited Rules will be displayed Rules Setting main page is shown as below PR Overview Rule 1 Enable lt IF gt Timer1 Timeout lt THEN gt WISE 7026 DOO Pulse output Emaili Send Enable No Edit Status lull lt o a S g a 7 s 7 of E s a Edit O Rule Edit O Rulez Ed O Rules Y scription O Rue9 T RN iot O Rule 10 lt gt O Rule 11 Edit ti O Rule 12 O Rule 13 O Rule 14 O Rule 15 O Rule 16 O Rule 17 E cy in O Rule 18 Rule 5 Enable m Rule 19 Edit vl Description Figure 6 18 Rule setting main page http 7www icpdas com 35 ICP DAS WISE User Manual Click Rules Setting button to display detail rules description Rules can be uploaded to the hardware device immediately after you successfully set up one or more rule s http 7www icpdas com 36 ICP DAS WISE User Manual 6 4 Rule Manager The Rule Manager allows easy modification and deployment with existing rules By a few simple s
30. ll Welcome to the WISE Firmware Uploader version 1 01 Uninstall This wizard will quide you through the uninstallation of WISE Firmware Uploader version 1 01 Before starting the uninstallation make sure WISE Firmware Uploader version 1 01 is not running Click Next to continue Cancel Figure 10 6 Remove WISE Firmware Uploader 1 O Click Uninstall to uninstall the program WISE Firmware Uploader Uninstall Uninstall WISE Firmware Uploader version 1 01 Remove WISE Firmware Uploader version 1 01 from your computer WISE Firmware Uploader version 1 01 will be uninstalled From the Following Folder Click Uninstall to start the uninstallation Uninstalling From C ICPDAS WISE WISE Firmware Uploader WISE Firmware Uploader Installer built on 2009 10 15 at EF 09 50 18 Figure 10 7 Remove WISE Firmware Uploader 2 http 7www icpdas com 45 ICP DAS WISE User Manual Oo When the uninstall process is completed click Finish to finish the uninstallation WISE Firmware Uploader Uninstall Completing the WISE Firmware Uploader version 1 01 Uninstall WISE Firmware Uploader version 1 01 has been uninstalled From your computer Click Finish to close this wizard Figure 10 8 Complete uninstalling WISE Firmware Uploader 10 3 Update WISE firmware Please follow the six steps below to update the WISE firmware program on the hardware devices 10 3 1 Before update O Please visit ICP DA
31. loader 2 oooonccnnncccncnnnnnccnnnnnnnnnnnnnnos 45 Figure 10 8 Complete uninstalling WISE Firmware Uploader cccccccccnnnnnnnnn 46 Figure 10 9 Launch WISE Firmware Uploader oooooooonnnnncncccnnnonnnnncnnnnnnnnnnnnnnnos 46 Proure 1021 0 Assien IP addres nic 4 Figure O LI Selecttho WISE Firmware ula iia 4 Fitur 10 12 Upload tw Ale odos 4 Figure 10 13 Display firmware update progress ccccccocooocccnnnnnnonononannnnnnnnnnnonananinanss 48 Figure 10 14 Complete firmware update ooooonncnnnncccnonononnnnnnnnnnnnnnnnannncnnnnnnnnnnnannnnss 48 Fig re 10 153 Reset Ne devices 48 http 7www icpdas com 5 ICP DAS WISE User Manual 1 Introduction WISE Web Inside Smart Engine is a product series developed by ICP DAS that functions as control units for use in remote logic control and monitoring in various industrial applications WISE offers a user friendly and intuitive HMI interface that allows users to implement control logic on controllers just a few clicks away no programming is required With this powerful and easy to use software it will minimize the learning curve shorten time to market and dramatically reduce the effort and cost spent on system development WISE system architecture 1s shown as below Figure 1 1 WISE system architecture Through Web browser users can access Web Server on ICP DAS WISE controllers to perform tasks such as logic edition and upload A Rule Engine w
32. n statement Specify the channel from the dropdown list of channel field in Module amp Channel section ll Set up the expression statement for this counter value Select an ee 99 99 099 99 99 99 66 operator from gt lt D ce 99 99 99 99 99 99 gt lt D Or sii value has to be specified lt or change If the operator is if ds DO counter value match the evaluation criteria the result of this condition evaluation will be true If the operator 1s Change the condition will be true when there is a change of the counter value The action will be executed only once and only at the moment when http 7www icpdas com 27 ICP DAS WISE User Manual DO Counter experience a change lll Click Save button to save the settings This popup window will be closed and return to Rule settings page 6 1 5 Internal Register Internal Register value can be used as evaluation criteria for IF condition statement the editing page for Internal Register Condition Setting 1s shown as follow Internal Register Condition Setting nex Figure 6 8 Internal register condition setting page Follow the following steps i Select the Internal Register that you are going to use the value as evaluation criteria for IF condition statement Specify the Internal Register Index from the dropdown list of Index field ll Setup the expression statement for this Internal Register value Sele
33. nce to avoid possible error ix Enter the email subject in the Subject field http 7www icpdas com 21 ICP DAS WISE User Manual x Enter the content in the Content field xi Repeat steps 11 x After all email groups settings are completed click Save button to save the changes http 7www icpdas com 22 ICP DAS WISE User Manual 6 Rules Setting After finish all Advanced Setting configuration the user can start to edit IF THEN ELSE rules Click the Rules Setting button a Rule Manager table will appear and the list of rules will be displayed on the left side of the page At the left side of the page the status of each rule will be displayed And at the right side of the page will show detail content of each rule that was previously defined by the users The rule setting page 1s shown as below Rule Manager Enable No Edit Status Rulez Ea Rule8 Edit Rule 10 Rule 11 Rule 12 Rule 13 Rule 14 Rule 15 Rule 16 Rule 17 Rule 18 Rule 19 Edit wl oono2r2000002002 0 OCE E a Figure 6 1 Rules setting page On the left side of the page a Rule Manager table will appear at the top of the page More detail information for Rule Manager will follow Below the Rule Manager table the list of rule contains four items Enable No Figure 6 2 Enable rules edit rules and status display http 7www icpdas com 23 ICP DAS WISE User Manual 9 Enable A checkbo
34. nncnononinnonnnnnnnnnnnnonannnnnnnnnnnnnnnnos DZ Proure 6 15 Timer action paraiso iaa 33 http www Icpdas com 4 ICP DAS WISE User Manual Fiare 6216 Email Acton Pat aa 34 Furco Cleat ave RUS ida 35 Fig re 6 18 R le setine Man Parita ptas 35 Figure 6 19 Rule Manager Setting Page ccccccncncnnnnncnononononnnnnnnncnnccnnnnnnnnnnnnnnnnnnnnnnnnns 3l Figure 6 20 Rule Copy seting pafe A JT Preure 652 1 Rule Reset setini Pluna 38 Pisure 6 22 Rule Reorder Serum Pare anita ds 38 Fig re 0 237 R Swap seting palese ei 39 Ersure Le PIGasesenter the pass Word reesen ncevatedaschareiaeersiacheckaeieveeteieaes 40 Figure 7 2 Upload to Module status Par n r nutes aasaas 40 Figure 7 3 The informing message when successfully Upload to Module 40 Figure 8 1 The informing message when successfully download to PC 41 Freure 921 Nannel Status Paro ia 42 Figure 10 1 Install WISE Firmware Uploader oooooooooonnnncnncnccccnnnnnnnonononononananonos 43 Figure 10 2 Select installation directory iaa iii dla 44 Figure 10 3 Display installation PrOgresS ooooocccccccccnonononnnnnnnnnnononanonnnnnnnnnnnnnnnannnnss 44 Figure 10 4 Complete theanstallation da 44 Figure 10 5 Start to remove WISE Firmware Uploader oocccccccccncnnnnnnnnnononnnnooo 45 Figure 10 6 Remove WISE Firmware Uploader 1 oooccccccccnnnnnncncnnnnncnnnonnnnos 45 Figure 10 7 Remove WISE Firmware Up
35. nstalling Please wait while WISE Firmware Uploader version 1 01 is being installed Create shortcut C Documents and Settings AnYing Lee WISE Firmware Uploader Ink PEE EEEEELEEELELELELEELELE LEE EL EEE E EEL ELE LEE L EEE EEL EL ELL LL Figure 10 3 Display installation progress Oo When the installation is completed click Finish to close the process gt WISE Firmware Uploader version 1 01 Setup Completing the WISE Firmware Uploader version 1 01 Setup Wizard WISE Firmware Uploader version 1 01 has been installed on your computer Click Finish to close this wizard Figure 10 4 Complete the installation http 7www icpdas com 44 ICP DAS WISE User Manual 10 2 2 Uninstall WISE Firmware Uploader Follow the steps below to uninstall WISE Firmware Uploader O Click Start gt All Programs gt ICPDAS gt WISE and then click Uninstall under the WISE category BE CLS Lar eontror panes x Br W Paint mm E EZView EZuirw A Accessories Startup 2 Internet Explorer lA Piso Ps400 E Mavis E PIiso Ps400 oe Log FF a Til O E ET Ms194H fay WISE Firmware Uploader mi E rare Upe ar et ai gt a SAUER ASR EA E enn F a k All Programs fag ICPDAS E El Uninstall Mr WISE Firmware Upos Figure 10 5 Start to remove WISE Firmware Uploader O You will see a window pop up as below click Next to continue WISE Firmware Uploader Uninsta
36. ou want to use click Save button to save the settings 5 6 Email Setting WISE supports up to 12 Email messages This function allows sending pre input Email message s to pre set Email receiver s under certain conditions The configuration page is shown as below http 7www icpdas com 20 ICP DAS WISE User Manual E mail Setting Page oe ndes SMTP Server ler N 1st Receiver Email Address 2nd Receiver Email Address 3rd Receiver Email Address 4th Receiver Email Address 5th Receiver Email Address Content Note The length of the message cannot exceed 160 characters Figure 5 6 Email setting page Follow the following steps 1 Specify the numbers of email messages you want to set up from the dropdown list of the E mail Amount field ll Specify the email group number from the dropdown list of the Index field 11 Enter the SMTP server IP in the SMTP Server IP field 1v Enter the SMTP server login ID in the Login ID field v Enter the SMTP server password in the Password field vi Enter the sender s name in the Sender Name field vil Enter the sender s email address in the Sender Email Address field viii Enter the receiver s email address in the 1 5 Receiver Email address field Please note you can input up to 5 receivers at least one email address has to be entered Please enter the email address in seque
37. password hint length is limited to 20 characters http 7www icpdas com 15 ICP DAS WISE User Manual 5 Advanced Setting Advanced Setting provides additional features and allows you to perform channel configuration on hardware devices Click the Advanced Setting button a row of buttons will appear on the left of the page Timer Setting 9 DI Attribute Setting DO Attribute Setting 9 AO Attribute Setting 4 Internal Register Setting Email Setting Please note In order to avoid possible error when performing rule definition IF THEN ELSE please always finish configuration in Advanced Setting before start to define Rules Also avoid unnecessary change in Advanced Setting after you finish rule definition Unexpected errors might occur 1f you violate this sequence Advanced Setting gt Rule Setting please double check your settings and Rules definition if you make any modification In addition because each module may carry different I O channels if the related DI Attribute Setting DO Attribute Setting and AO Attribute Setting does not apply to the selected module the corresponding buttons will appear Disable The following sections will describe more detail information for these configurations 5 1 Timer Setting WISE provides 12 groups Timer for timing functions The Timer setting interface 1s shown as below Timer Setting Page MM Figure 5 1 Timer setting page http 7www icpdas com
38. sting rules Click Reorder button a window as shown below will pop up Rule Reorder Select Rule Content a ly Rule 1 Rule Content 1 Rule 13 None Rule 25 None Rule 2 Rule Content 2 Rule 14 None Rule 26 None R Rule 3 Rule Content 3 Rule 15 None Ru le 27 None R Rule 4 Rule Content 4 Rule 16 None Rule 28 None R Rule 5 None Rule 17 None Rule 29 None R Rule 6 None Rule 18 None Rule 30 None R Rule 7 None Rule 19 None Rule 31 None R Rule 8 None Rule 20 None Rule 32 None R Rule 9 None Rule 21 None Rule 33 None R Rule 10 None Rule 22 None Rule 34 None R Rule 11 None Rule 23 None Rule 35 None R Rule 12 None Rule 24 None Rule 36 None Figure 6 22 Rule Reorder setting page A menu will appear at the top of the page 1t contains a drop down list for selecting the target rule and a pair of Move Up Move Down buttons to move target rule to the desired location All rule locations will be listed http 7www icpdas com 38 ICP DAS WISE User Manual in sequence currently support 36 rule locations If the rule content of a specific rule location has been previously edited Rule Content X X rule sequence index will appear If the rule content of the rule location is blank 1t will be specified as None To reorder a rule select the target rule from the dropdown list the corresponding Rule content X font will turn to blue from its usual black Click on Move Up Move Down
39. teps users can easily change the rule orders or make modification with previously edited rules The Rule Manager table is shown as below Rule Manager Figure 6 19 Rule Manager setting page Rule Manager offers 4 functions Copy Copy the content of previously edited rule to another rule Click Copy button a window as shown below will pop up Rule Copy 1Rule1 ORulee2 Rule3 Rule a Rues C Rule6 Rulez Rule 8 OJrules Rul 10 Rule 11 Rule 12 O Rule 13 Rule 14 Rule15 Rule 16 Co Rule 1 iv E Cl Rule 17 Rule 18 Rule19 Rule 20 C Rue 21 Rule 22 Rule23 Rule 24 Ci Rue 25 Rule 26 Rule 27 Rule 28 C Rue 29 Rule 30 Rule 31 Rule 32 Rue 33 Rue 34 Rule 35 Rule 36 Figure 6 20 Rule Copy setting page Select the source rule from the first field and then select the destination s from the second fields multiple rule destinations is allowed Click Save button to copy the content of the source rule to all destination rules http 7www icpdas com 37 ICP DAS WISE User Manual Reset allows to clear rule content of previously edited rules Click Reset button a wndow as shown below will pop up Rulereser Due DRue2 Rues DRue4 Figure 6 21 Rule Reset setting page Rules that are previously edited will be listed on the page select the rule to be cleared and then click Save button the rule you select will be reset Reorder reorder exi
40. ter SeNi ia id dd 20 NO EMS E eee delo aa 20 O Rules Senia deiata ian aie a a aie este 23 6 1 ECONO a a 29 62 THENELSEACHOM ae dy Socem neuen asteatdencentadeniiadieSadses 30 6 3 Summary Or The RUS vs ca reese a ti 35 OA Rule Mana sn 37 Uploadto Modul sessar O 40 Download 10 PE aE 41 CO are Us SANS ao pri odo tiernos 42 TO Firmware Updalesara nia iio 43 O CU CHOM niaatt heen a tae nade hana ee col Acareheatneioh ee 43 10 2 Install Uninstall WISE Firmware Uploader ooocccccccccccononocnnnos 43 O Update WISE TINI O is 46 Appendix I Modbus Address Table ooocccocccccocooncccnnnccnnnoconnnccnnoccnonoconnaccnnnss 49 http 7www icpdas com 2 ICP DAS WISE User Manual List of Figures igure tel WISE y stem architecture iS a E EE 6 Feire 22 W ISE Ones Product adin 7 Figure 2 1 The location of the switch on the controller oooccoccccnnnnnnnnmmmmmmm 9 Figure 2 2 Select Search function on MiniOS7 Utility ooccccccnnncnnnnnnnnnnnnnnnm 9 Figure 2 3 IP Setting button on MiniOS7 Scan ccococccnnnnnnnoonnnnnnnnncnnnnnnnononononononnnnnnnos 10 PISUTE 2 4 INCtWOrk Senas DADO aso elas 10 Figure 3 1 Main page of WISE Web UL sintomas 11 Figure 3 2 WISE Web UI Operation Procedures ooooooooooconccnnccnnnnnnnnnnnnnnnonononanananos 12 Facute del Ethemet setini Pai E 13 Figure 4 2 WISE 70xx 71xx DI DO module setting page ccccooooonncccnnnnnnnnnnnnnnnnss
41. will follow http 7www icpdas com 24 ICP DAS WISE User Manual 6 1 IF Condition You may use the following values or their status as evaluation criteria in IF Condition statement Al DI DI counter DO counter Internal Register Timer 91 010 010 From the list above Al and DI channel will automatically appear 1f there 1s a corresponding hardware The other subjects have to be pre defined in Advanced Setting first The subjects that already being defined in Advanced Setting will appear in the dropdown list of IF Condition Select the subject you want to define and then click right side button a window will pop up for you to edit detail information 6 1 1 Al AI channel value can be used as evaluation criteria for IF condition statement the editing page for AI Condition Setting 1s shown as below Al Condition Setting Module amp Channel Channel Figure 6 4 Al condition setting page Follow the following steps i Select the channel that you are going to use the value as evaluation criteria for IF condition statement Specify the channel from the dropdown list of channel field in Module amp Channel section li Set up the expression statement for this channel value Select an operator from gt lt gt or lt and then specify the evaluation value If this AI channel value match the evaluation criteria the result of this condition evaluation will be true
42. x appears before each rule check the checkbox to enable the rule and this rule will be executed after being uploaded otherwise 1t will only be stored temporarily No Indicates the identification number of the rule To avoid possible error it is recommended to assign the identification number in sequence Edit Click the Edit button to edit detail logic content of the rule 9 Status OK indicates this rule is successfully defined Error indicates there is error occurs Please note if you make modification in Advanced Setting after finish defining the rules it might cause unexpected error due to the changes some variables may no longer exist Click the Edit button the Rules Setting page will appear THEN None v a NS z el Operator aqua Figure 6 3 Rule setting page The rule number will be displayed at the top of the page The Description field provides a space for users to make a brief description of this Rule An IF THEN ELSE Rule setting table will appear Each Rule offer 3 IF conditions The user could dynamically create IF condition statements by selecting appropriate operator AND OR from the dropdown list In order to avoid possible errors the design of this table is foolproof The user has to finish setting up Condition before moving on Condition2 and so on Each Rule also offers 3 THEN actions and 3 ELSE actions More detail information