Home
1756-PM011 - Literature Library
Contents
1. Remote Data Tag Name or Instance Number RPI 20 0 ims 9 Do the following on the Consumed Tag Connection dialog box e Inthe Producer list choose the controller that produces the data If the drop down is empty you must first add a remote controller to the Controller Organizer I O Configuration folder This is the controller that is producing the data If you have only one controller configured it cannot be both the consumer and the producer The producing controller cannot consume its own data e Inthe Remote Data box type the name or instance number of the remote produced data If the producing controller is Then type or choose Logix5000 controller Tag name of the produced tag Rockwell Automation Publication 1756 PM011G EN P November 2015 17 Chapter 1 Produce and Consume a Tag If the producing controller is Then type or choose PLC 5C controller Message number from the ControlNet configuration of the PLC 5C controller e Inthe RPI field type or select the requested packet interval RPI for the connection Important Consuming controllers have additional setup to allow its consuming tags to use an RPI provided by a producing controller See Set RPI Limits Default for Producer Tag on page 21 for details 10 Click the Status tab to configure the status properties for the consumed tags a Tag Connection o Connection Status Connection Status Included
2. i Connection Status is included when the tags data type is a user defined data type whose first member is CONNECTION STATUS Data Type DINT iT O Connected to Producer O Producer in Run Mode 11 In the Data Type list click the data type that allows the connection status 12 Click OK Note Ifyou consume the tag over a ControlNet network use RSNetWorx for ControlNet software to schedule the network Additional steps for a PLC 5C controller If you are sharing data with a PLC 5C controller do the following Action Details If the PLC 5C This Then in RSNetWorx software controller In the ControlNet configuration of the PLC 5C controller schedule a message 18 Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce and Consume a Tag Chapter 1 Produces Integers In the ControlNet configuration of the PLC 5C controller insert a Send Scheduled Message Consumes Integers Do these steps in the ControlNet configuration of the PLC 5C controller Insert a Receive Scheduled Message In the Message size enter the number of integers in the produced tag REALs Do these steps in the ControlNet configuration of the PLC 5C controller Insert a Receive Scheduled Message In the Message size enter two times the number of REALs in the produced tag For example if the produced tag contains 10 REALs enter 20 for the Message size If the PLC 5C controller consumes REALS When you produce
3. dialog box to indicate that RPI limits are set to values other than what you entered Advanced Options Multicast Connection Options Use the following options to configure multicast connection behavior to this produced tag Minimum RPI 0 2 Us Effective Minimum RPI 4 ms Maximum RPI 536870 9 ms Y Effective Defsum RPI 2 ms V Provide Default RPI to Consumer for Out of Range Requests Defaut RPI 5 0 ms Unicast Connection Options Use the following options to configure unicast connection behavior to this produced tag Allow Unicast Consumer Connections ok Cancel Help 32 Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce and Consume a Tag Chapter 1 RPI 0 faults The following table provides a description of error messages for situations where an RPI is not accepted Scenario Description Software Version 1 0 Fault Message RPI of consumed tag is not within the range of the producer Producer does not Any Code 0111 Requested Packet Interval RPI out of range support RPI negotiation or is not configured to provide a default RPI to the consumer RPI of consumed tag is not within the range of the producer Producer is 18 and later Code 0112 Requested Packet Interval RPI out of range returning default RPI Consumer does not support negotiation or is not configured to accept RPI from producer 17 and earlier Code 0112 Unknown Error RPI of consumer is out of range
4. 5 Click Cancel to exit Produced and consumed The following scenarios explain how producing and consuming tags exchange RPI for controllers RPI scenarios Rockwell Automation Publication 1756 PM011G EN P November 2015 27 Chapter 1 Produce and Consume a Tag Scenario 1 The RPI is within range of the producing controller s RPI Limits There is no default RPI that is set up for the producing controller Produced Tag Minimum RPI 2ms Maximum RPI 8ms Default RPI ms Actual Packet Interval API 3 ms RPI 3 ms Version 17 and earlier The consuming controller is brought online with an RPI configured at 3 ms The producer accepts the RPI requested by the consuming tag All controllers on the multicast connection will be increased to 3 ms for the API which is the interval the data is actually being produced Version 18 and later The consuming controller is brought online with an RPI configured at 3 ms The producing controller verifies the requested RPI by the consumer is within the RPI limits set up for the producer Since the request is within the range the producing controller accepts the RPI of the consumer Tip If you use all the default settings of version 18 and later you have the same behavior as version 17 and earlier Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce and Consume a Tag Chapter 1 Scenario 2 The RPI is outside the range of the prod
5. November 2015 Chapter 1 Produce and Consume a Tag Introduction A Logix5000 controller lets you produce broadcast and consume receive system shared tags Controller_1 Controller_2 Consumed Tag Produced Tag Controller_3 Consumed Tag Controller 4 Consumed Tag Term Definition Produced tag A tag that a controller makes available for use by other controllers Multiple controllers can simultaneously consume receive the data A produced tag sends its data to one or more consumed tags consumers without using logic Consumed tag A tag that receives the data of a produced tag The data type of the consumed tag must match the data type including any array dimensions of the produced tag The RPI of the consumed tag determines the period at which the data updates Controllers and networks These combinations support produced and consumed tags that su pport This controller Can produce and consume tags over this network produced consumed tags EtherNet IP SLC 500 PLC 5 1769 CompactLogix X Rockwell Automation Publication 1756 PM011G EN P November 2015 9 Chapter 1 Produce and Consume a Tag Connection requirements of a produced or consumed tag 10 This controller Can produce and consume tags over this network Backplane EtherNet IP 1768 CompactLogix X ControlLogix X DriveLogix X SoftLogix5800 X For two controllers to share produced or consumed tags both controllers must be attached to
6. REALs 32 bit floating point values for a PLC 5C controller the PLC 5C controller stores the data in consecutive reconstruct the values 16 bit integers e The first integer contains the upper leftmost bits of the value e The second integer contains the lower rightmost bits of the value This pattern continues for each floating point value If the PLC 5C controller consumes REALs When you produce REALs 32 bit floating point values for a PLC 5C controller the PLC 5C controller stores the data in consecutive reconstruct the values 16 bit integers e The first integer contains the upper leftmost bits of the value e The second integer contains the lower rightmost bits of the value This pattern continues for each floating point value The following example shows how to reconstruct a REAL floating point value in the PLC 5C controller Example Reconstruct a floating point value The two MOV instructions reverse the order of the integers as the integers move to a new location Because the destination of the COP instruction is a floating point address it takes two consecutive integers for a total of 32 bits and converts them to a single floating point value RPI limitations and RPI limitations and negotiated behavior vary depending on the version of the Logix Designer application that is running on your controllers negotiated default Rockwell Automation Publication 1756 PM011G EN P November 201
7. United States Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the feedback form publication RA DU002 Rockwell Otomasyon Ticaret A Kar Plaza Is Merkezi E Blok Kat 6 34752 Icerenk y Istanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Auromarion NV Pegasus Park De Kleetlaan 12a 183 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberporr 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Rockwell Automation Publication 1756 PM011G EN P November 2015 Supercedes Publication 1756 PM011F EN P October 2014 Copyright 2015 Rockwell Automation Inc All rights reserved Printed in the U S A
8. and 1769 L3x controllers However ifan unsupported packet interval is entered then the Logix Designer Rockwell Automation Publication 1756 PM011G EN P November 2015 31 Chapter 1 Produce and Consume a Tag application may override the unsupported packet interval with a supported packet interval When this occurs the new effective value is displayed separately next to the unsupported value that was entered Similar to other controllers the 1769 L2x and 1769 L3x controllers will verify that the RPI of incoming connections are within the produced tag settings If the consuming tag s RPI falls outside the configured range a producing controller will reject the incoming RPI and then provide an RPI default to the consuming controller Important The producing and consuming controllers must be set up to allow the consumed tags to use an RPI provided by the producer See RPI Limitations and Negotiated Default on page 19 and Set Up the Consumer Tag on page 24 for procedures to set up the producer and consumer tags to accept a negotiated default RPI For the 1769 L2x and 1769 L3x controllers the Effective Minimum RPI when present is used to determine the fastest packet interval allowed by the tag When the Effective Default RPI is present it is the largest packet interval slowest rate at which negotiated connections will be produced for the tag The effective RPI limit values are presented with a flag on the Advanced Options
9. but producer provides a default RPI and 18 and later Code 0112 Requested Packet Interval RPI out of range consumer can accept default RPI Network path contains bridge that does not Producer provided RPI blocked by the network path support extended error information For 1 0 connectivity between two controllers such as consuming a tag from a producing controller both controllers must be attached to the same EtherNet IP subnet Two controllers cannot bridge produced or consumed tags over two subnets For more information on setting up your network refer to the following publication in the Rockwell Literature Library EtherNet IP Network Configuration User Manual ENET UM001 RPI of consumer is out of range but producer provides a default RPI and 18 and later Code 0112 Requested Packet Interval RPI out of range consumer can accept RPI provided by producer Network path contains Cannot use producer provided RPI over a path containing scheduled network update time NUT a scheduled network Prevent connection failures with 5x80 controllers Ifa consumer displays error code 0112 and fails to connect to a 5x80 controller that provides produce tags take the following steps to make sure consumers of produce tags can connect e For consumers running Logix Designer releases v17 and earlier that are consumers of a producer from a 5x80 controller e Verify that all multicast consumed tags of a produce tag are configured with the same RPI If
10. each packet carries 123 elements of data from the array as shown in the following Figure 1 Producer Consumer Data Elements Producer Consumer Array Array _ Packet Packet ait st onset 124 Acknowledge Acknowledge Rockwell Automation Publication 1756 PM011G EN P November 2015 35 Chapter 2 Produce a Large Array In addition the array must contain an extra 122 elements In other words it must be 122 elements greater than the greatest number of elements that you want to transfer e These elements serve as a buffer e Because each packet contains the same number of elements the buffer prevents the controller from copying beyond the boundaries of the array e Without the buffer this would occur if the last packet contained fewer than 123 elements of actual data Produce a large array Follow these steps to produce a large array 1 Inthe Controller Tags folder of the controller project that produces the array create these tags P Tag Name Type array_ack DINT 2 X array_packet DINT 125 2 Convert array_ack to a consumed tag For Specify Controller Name of the controller that is receiving the packet Remote Tag Name array_ack Both controllers use the same name for this data 3 In either the Controller Tags folder or the tags folder of the program that will contain the logic for the transfer create these tags Tag Name Type array DINT x where x equals
11. prevent an interruption to other controllers on the network Produced Tag Minimum RPI 2ms Maximum RPI 8 amp ms Default RPI 5ms Negotiation Disabled Version 17 and earlier The RPI requested by the consumed tag is not within the range of the producer The connection is rejected and a 0112 error is reported that the connection failed You must re enter an RPI that is within the range configured on the produced tag If a version 17 consumer is trying to connect with aversion 18 producer and the RPI is outside the range of the producer a 0112 error reports the connection failed Tip See RPI 1 0 Faults on page 33 for an explanation of the error messages Version 18 and later The RPI requested by the consumed tag is not within the RPI limitation range of the producer The producer is configured to provide an RPI default The producer sends the default RPI to the consumer but the consumer controller is not set up to accept a default RPI from the producer The negotiated RPI is disabled to prevent an interruption to the multicast connection A 0112 error message is reported and you must re enter an RPI within the range of the producer s limits 30 Rockwell Automation Publication 1756 PM011G EN P November 2015 1769 L2x and 1769 L3x RPI limits Produce and Consume a Tag Chapter 1 Scenario 4 The RPI is outside the range of the producing controller s RPI Limits A default RPI is set up for the producing c
12. the number of elements to transfer plus 122 elements array_offset DINT array_size DINT array_transfer_time DINT array_transfer_time_max DINT array_transfer_timer TIMER 4 In the array_size tag enter the number of elements of real data The value of x from step 3 minus the 122 elements of buffer 5 Create or open a routine for the logic that creates packets of data 36 Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce a Large Array Chapter 2 6 Enter this logic When the offset value in array_ack 0 is not equal to the current offset value but array_ack 1 equals 999 the consumer has begun to receive a new packet so the rung moves 999 into the last element of the packet The consumer waits until it receives the value 999 before it copies the packet to the array This guarantees that the consumer has new data NEQ EQU MOV Not Equal Equal Move Source A array_ack 0 Source A array_ack 1 Source 999 0 0 Source B array_packet 123 Source B 999 Dest array_packet 124 0 0 Rockwell Automation Publication 1756 PM011G EN P November 2015 37 Chapter 2 Produce a Large Array When the offset value in array_ack 0 is equal to the current offset value the consumer has copied the packet to the array so the rung checks for more data to transfer If the offset value plus 123 is less than the size of the array there is more data to transfer so the rung increases the offset by 123 Otherwise there is n
13. the same RPI If they are not some consumers will fail to connect e For multicast consumers running Logix Designer releases v18 to v27 e Verify that all multicast consumed tags of a produce tag are configured with the same RPI or e Verify that all multicast consumers are configured to Allow Consumed Tags To Use RPI Provided By Consumer 22 Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce and Consume a Tag Chapter 1 The following table describes the connection parameters Parameter Minimum RPI Maximum RPI Provide Default RPI to Consumer for Out of Range Requests Default RPI Allow Unicast Consumer Connections Description The smallest requested packet interval fastest rate at which consumers may consume data from the tag For ControlLogix controllers the minimum RPI is 0 2 ms For CompactLogix controllers the minimum RPI is 1 0 ms The Minimum RPI value must be less than or equal to the Maximum RPI value This field may be modified in offline mode The largest packet interval slowest rate at which consumers may consume data from the tag Rockwell recommends using the default setting of 536870 9 ms The Maximum RPI value must be greater than or equal to the Minimum RPI value This field may be modified in offline mode Enables a producing tag to provide an RPI to a consuming tag whenever a consuming tag has an RPI outside the range of the producer s Minimum and Maximum RP
14. they are not some consumers will fail to connect e For multicast consumers running Logix Designer releases v18 to v27 take one of these steps e Verify that all multicast consumed tags of a produce tag are configured with the same RPI or e Verify that all multicast consumers are configured to Allow Consumed Tags To Use RPI Provided By Consumer Rockwell Automation Publication 1756 PM011G EN P November 2015 33 Chapter 2 Introduction Produce a Large Array The Logix5000 controller can send as many as 500 bytes of data over a single scheduled connection This corresponds to 125 DINT or REAL elements of an array To transfer an array of more than 125 DINTs or REALs use a produced consumed tag of 125 elements to create a packet of data You can then use the packet to send the array piecemeal to another controller When you send a large array of data in smaller packets you must be sure that the transmission of a packet is complete before the data is moved into the destination array e Produced data over the ControlLogix backplane is sent in 50 byte segments e Data transmission occurs asynchronous to a program scan The logic that this section includes uses an acknowledge word to make sure that each packet contains new data before the data moves to the destination array The logic also uses an offset value to indicate the starting element of the packet within the array Because of the offset and acknowledge elements
15. use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss A ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequence Important Identifies information that is critical for successful application and understanding of the product Labels may also be on or inside the equipment to provide specific precautions SHOCK HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that dangerous voltage may be present temperatures ARC FLASH HAZARD Labels may be on or inside the equipment for example a motor control center to alert people to potential Arc Flash Arc Flash will cause severe injury or death Wear proper Personal Protective Equipment PPE
16. 00 enyironmen tanei i i E Ee 7 Additional Resotirees oS te testa Ee Co ao EEA tel ad ee 7 Chapter 1 Introd ctot enninu naian aa caseedinsa chess a 9 Controllers and networks that support produced consumed tags 9 Connection requirements of a produced or consumed tag sssssssssssssses seses 10 Considerations when migrating projects that contain multicast produce TASS nin a a a cite thts buna tal A a aint an 11 Organize tags for produced or consumed data ssss sssssssssssresserrssersessserersertesesress 12 Adjust for bandwidth limitations vassvivssdsenstecstinsdtisctaapsvestadsscedvaccyobeaitentete 13 Produced Lapa nanan natant a aa a aa aa e Rah 13 Crested CONSUME TAC isasi AEE PAEA ANRE 15 Additional steps for a PLC 5C controller ssssssssssssesssssesrsssssrsresssseeressssreses 18 RPI limitations and negotiated default vecc ccssscacassisvscsnvontcchsnvvcsesmisstonsceterte 19 Set RPI limits default for producer tag s sssssesssessssessrsssserssssressereesstsrssrerensereese 21 Unicast connection Options sssssssseesssssseeseeseessssstsereeeesessssstterereesssetstrereesesst 24 Set wip the consumer tag m sonesneisienniiiieneiiniaiiiiii niii 24 Verify consumed tag acceptance s essessssssttssesressertesstsrsssereessttessstrreeteesestesssnerrsn 25 Produced and consumed RPI scenarios sss ssssssssssssssssessssesresssstsresssstsressssesressssee 27 Scenario Lesiiiaciiiiiiiiiiainiiieiiniiiia anii 28 Sc nario Zissoun orii iiiu 29 Scenario Saniye ai A
17. 5 19 Chapter 1 20 Produce and Consume a Tag Behavior in releases v28 and later In releases v28 and later the first consumer of a produce tag determines the RPI at which data is produced All subsequent consumers must request the same RPI value as the first consumer or they fail to connect and display error code 0112 The first consumer of a produce tag is the device that sends the first consumer connection to the producing controller The first consumer request is based on the order in which the producer and consumer control system powers up so the first consumer can change if power is cycled to the system You cannot configure a device to be the first consumer There is no way to tell which consumer will send the first request to the producing controller so you must plan accordingly when configuring multicast produce tags See Considerations when migrating projects that contain multicast produce tags on page 11 for more information Tip The controller s backplane and Ethernet ports can support different RPls If multiple consumers need to connect to the controller at different RPls you can configure them to connect through the backplane or the Ethernet port See Connection requirements of a produced or consumed tag on page 10 for more information Behavior in releases v18 to v27 In versions 18 and earlier controllers can be programmed to enhance the requested packet interval RPI acceptance between producing and consum
18. Automation Publication 1756 PM011G EN P November 2015 Produce a Large Array Chapter 2 e Messages are unscheduled and are executed only during the system overhead portion of the Logix5550 execution Therefore messages can take a fairly long time to complete the data transfer e You can improve the transfer time by increasing the system overhead time slice but this diminishes the performance of the continuous task Rockwell Automation Publication 1756 PM011G EN P November 2015 41 adjust bandwidth limitations 13 array defining data packets 37 bandwidth adjust limitations 13 C communicate other controllers 9 connection produced or consumed tag 9 consumed tag connection requirements 9 consumer creatingtag 16 RPI scenarios 28 using producer RPI 25 verifying RPI 26 ControlNet bandwidth limits 13 create producedtag 14 default RPI 21 error messages RPI 34 l 1 0 faults 34 Index L L2x controller RPI limits 32 L3x controller RPI limits 32 limitations bandwidth 13 RPI 21 PLC 5C share data 19 produced tag connection requirements 9 create 14 producer creatingtag 14 RPI scenarios 28 R RPI 1 0 faults 34 limitations setting default 21 S scenarios RPl acceptance 28 tag array 38 consumer RPI verification 26 consumer using producer RPI 25 creating consumer 16 creating producer 14 produce 14 Rockwell Automation Publication 1756 PM011G EN P November 2015 43 Rockwe
19. Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment PPE AN BURN HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that surfaces may reach dangerous Allen Bradley Rockwell Software Rockwell Automation and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Summary of Changes This manual contains new and updated information This table contains the changes made to this revision Summary of Changes Topics Added Replacement Guidelines ControlLogix 5560 5570 Additional Resources on page 7 Controller to ControlLogix 5580 Controller to the list of Additional Resources Added considerations for multicast produce tags in release V28 Considerations when migrating projects that contain multicast produce tags and with 5x80 controllers on page 11 Organize tags for produced or consumed data on page 12 RPI limitations and negotiated default on page 19 Set RPI limits default for producer tag on page 21 Set up the consumer tag on page 24 Added information on communications paths to 5x80 Connection requirements of a produced or consumed tag on page 10 controllers Rockwell Automation Publication 1756 PM011G EN P November 2015 3 Preface Produce and Consume a Tag Produce a Large Array Index Table of contents Studio S0
20. I A consumer that supports negotiations then connects with the Default RPI provided by the producer This field may be modified in offline mode The value that the producer provides to the consumer when the consumer s RPI falls outside the range of the producer s Minimum and Maximum RPI This value must be within the minimum and maximum RPI range of the producer This field may be modified in offline mode and when the Provide Default RPI to Consumer for Out of Range Requests box is checked Important You must select Allow Consumed Tags to Use RPI Provided by Producer on the Controller Properties dialog box Advanced tab to allow negotiations to use the RPI provided by the producer Allows multiple Unicast consumers to consume from the produced tag This check box is selected by default This check box is enabled unless the safety controller is locked Tip Selecting Allow Unicast Consumer Connections results in additional producer resources being allocated for each potential consumer You should clear the check box if you are not using Unicast and you are running low on controller memory This field may be modified in offline mode 3 Click OK When the Produced Tag Connections dialog box appears click OK Important The RPI Limits configuration which is disabled when online must be within e Minimum RPI 0 2 ms for ControlLogix controllers and 1 0 ms for CompactLogix controllers e Maximum RPI 536870 911 ms e Default
21. Import Sample Project Release Notes rom Sample Project From Upload About Recent Projects B Pio_Destinstion2L75 Bf AppFrame_TestwareL75 sampleOnEventStopc The Studio 5000 environment is the foundation for the future of Rockwell Automation engineering design tools and capabilities The Studio 5000 environment is the one place for design engineers to develop all elements of their control system These documents contain additional information concerning related Rockwell Automation products Resource Description Replacement Guidelines ControlLogix 5560 5570 Controller Provides guidelines for migrating projects from to ControlLogix 5580 Controller publication 1756 RM100 5560 5570 controllers to 5x80 controllers Rockwell Automation Publication 1756 PM011G EN P November 2015 7 Preface Resource Description Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Provides general guidelines for installing a Rockwell Automation industrial system Product Certifications webpage available at http ab rockwellautomation com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative Rockwell Automation Publication 1756 PM011G EN P
22. Programming Manual Allen Bradley Logix 5000 Produced and Consumed Tags Catalog Number 1756 ControlLogix 1756 GuardLogix 1768 Compact GuardLogix 1769 CompactLogix 1789 SoftLogix PowerFlex with DriveLogix a si ad fae ss Allen Bradley Rockwell Software Automation Important user information Read this document and the documents listed in the additional resources section about installation configuration and operation of this equipment before you install configure operate or maintain this product Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes laws and standards Activities including installation adjustments putting into service use assembly disassembly and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual
23. RPI configurable within the minimum maximum range e 1769 L2x and 1769 L3x controllers see RPI Limits on page 19 for additional instructions The RPI limits apply only to multicast connections on unscheduled networks This functionality is not supported on the ControlNet network Rockwell Automation Publication 1756 PM011G EN P November 2015 23 Chapter 1 Produce and Consume a Tag Set up the consumer tag 24 Unicast connection options Unicast connections are point to point connections between a producing controller and consuming controller no multiple connections You do not have to enter a minimum or maximum RPI range or default value for this type of connection The Allow Unicast Consumer Connections check box at the bottom of the Advanced Options dialog box defaults with a check mark Click OK to complete setting up the producing tag The Consuming controller must be set up to allow its consumed tags to accept an RPI provided by the producer Follow these steps to access the Controller Properties dialog box Important For controllers running Logix Designer releases v17 or earlier that contain consumers of a producer from a 5x80 controller verify that all multicast consumed tags of a produce tag are configured with the same RPI If they are not some consumers will fail to connect See RPI limitations and negotiated default on page 19 for more information 1 Inthe Controller Organizer right click a controller th
24. The COP instructions copy the data from the packet to the destination array starting at the offset value e The offset value moves to array_ack 0 which signals that the copy is complete e Array_ack 1 resets to zero and waits to signal the arrival of a new packet If the last element of the packet is not equal to 999 the transfer of the packet to the controller may not be complete so 999 moves to array_ack 1 This signals the producer to return the value of 999 in the last element of the packet to verify the transmission of the packet NEQ EQU MOV Not Equal Equal Move Source A array_packet 123 Source A array_packet 124 Source array_packet 123 0 0 0 Source B array_ack 0 Source B 999 Dest array_offset 0 0 COP Copy File Source array_packet 0 Dest array array_offset Length 123 MOV Move Source array_packet 123 Dest array_ack 0 CLR Clear Dest array_ack 1 NEQ MOV Not Equal Move Source A array_packet 124 Source 999 Source B 999 Dest array_ack 1 0 Transferring a large array as smaller packets improves system performance over other methods of transferring the data e Fewer connections are used than if you broke the data into multiple arrays and sent each as a produced tag For example an array with 5000 elements would take 40 connections 5000 125 40 by using individual arrays e Faster transmission times are achieved than if you used a message instruction to send the entire array 40 Rockwell
25. a i A a A 29 EnEn SOR pssst A E EE oaltadaeatbuehheatabadoee 31 1769 L2x and 1769 L3x RPI limMits ssss ssssssssssstsrssssssssereresssssssseeersessssssesereeess 31 RPI O ails iscsi es cece iets nania 33 Chapter 2 Introductionis nsien i i i a e aeS 35 Prod ce a latge arrayasteirpiii e RTO E 36 Rockwell Automation Publication 1756 PM011G EN P November 2015 5 Studio 5000 environment Additional Resources Preface This manual details how with a Logix5000 controller to produce and consume system shared tags and produce a large array This manual is one of a set of related manuals that show common procedures for programming and operating Logix5000 controllers For a complete list of common procedures manuals refer to the Logix5000 Controllers Common Procedures Programming Manual publication 1756 PMOO1 The term Logix5000 controller refers to any controller that is based on the Logix5000 operating system The Studio 5000 Automation Engineering amp Design Environment combines engineering and design elements into a common environment The first element is the Studio 5000 Logix Designer application The Logix Designer application is the rebranding of RSLogix 5000 software and will continue to be the product to program Logix5000 controllers for discrete process batch motion safety and drive based solutions Rockwell Software Studio 5000 Create Open xplore New Project Existing Project Help rom
26. at has been set up with a consuming tag and choose Properties I Controller Ti Verify G Controller F Gi Power UpH Generate Report Tasks Print z 3 6 Motion Groups p f ngrouped The Controller Properties dialog box appears with the General tab as the default Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce and Consume a Tag Chapter 1 2 Click the Advanced tab Controller Properties Controtler_1 o amp General Major Fauks d 3 3 a Controller Faut Handler lt none gt Power Up Handler cnone gt System Overhead 2 Time Sice z During unused System Overhead Time Slice Run Continuous Task Reserve for System Tasks eg Communications Match Project to Controller Serial Number V Allow Consumed Tags to Use RPI Provided by Producer 3 Check Allow Consumed Tags to Use RPI Provided by Producer Important The check box that activates RPI Provided by Producer is disabled online This check box must be checked for the RPI negotiation to succeed If the check box is not checked the consuming controller does not accept the RPI provided by the producer if the consuming controller requests an RPI that is out of the producer s configured RPI range As a result an out of range RPI request results in a failed connection 4 Click OK Verify consumed tag When a consuming controller accepts a default RPI by a producing controller
27. d Consume a Tag 1 On the Produced Tag Connections dialog box click Advanced Advanced Options Multicast Connection Options Use the following options to configure multicast connection behavior to this produced tag Minimum RPI 0 2 Maximum RPI 536870 9 V Provide Default RPI to Consumer for Out of Range Requests Defaut RPI 5 0 ms Unicast Connection Options Use the following options to configure unicast connection behavior to this produced tag Allow Unicast Consumer Connections Important A unicast connection between a consumer and producer controller is the default on the Advanced Options dialog check box Multicast connections can be changed to a produced tag whether or not the box is checked The check box dictates only whether this produced tag can accept a unicast connection The consuming controller determines if the connection is unicast 2 Complete the Advanced Options dialog box to set up the multicast connection For 5x80 controllers the first consumer of a produce tag determines the RPI at which data is produced All subsequent consumers must request the same RPI value as the first consumer or they fail to connect Take the following steps to make sure consumers of produce tags can connect e For consumers running Logix Designer releases v17 and earlier that are consumers of a producer from a 5x80 controller e Verify that all multicast consumed tags of a produce tag are configured with
28. ducing controller The first consumer request is based on the order in which the producer and consumer control system powers up so the first consumer can change if power is cycled to the system You cannot configure a device to be the first consumer It can be difficult to tell which consumer will send the first request to the producing controller so you should plan accordingly when configuring multicast produce tags To make sure consumers of produce tags can connect to a 5x80 controller take the following steps e For consumers running releases v17 and earlier that are consumers of a producer from a 5x80 controller e Verify that all multicast consumed tags of a produce tag are configured with the same RPL If they are not some consumers will fail to connect e For multicast consumers running releases v18 to v27 take one of these steps e Verify that all multicast consumed tags of a produce tag are configured with the same RPI or e Verify that all multicast consumers are configured to Allow Consumed Tags To Use RPI Provided By Consumer For more information on migrating to a 5x80 controller refer to the following publication in the Rockwell Literature Library Replacement Guidelines ControlLogix 5560 5570 Controller to ControlLogix 5580 Controller 1756 RM 100 Rockwell Automation Publication 1756 PM011G EN P November 2015 11 Chapter 1 Produce and Consume a Tag Org anize tags for produ ced syou organize your
29. e and Consume a Tag Chapter 1 Adjust for bandwidth limitations When you share a tag over a ControlNet network the tag must fit within the bandwidth of the network e As the number of connections over a ControlNet network increases several connections including produced or consumed tags may need to share a network update time NUT e Since a ControlNet network can pass only 500 bytes in one NUT the data of each connection must be less than 500 bytes to fit into the NUT Depending on the size of your system you may not have enough bandwidth on your ControlNet network for a tag of 500 bytes If a tag is too large for your ControlNet network make one or more of these adjustments Adjustment Description Reduce your NUT Ata faster NUT less connections have to share an update slot Increase the requested packet interval RPI of your At higher RPls connections can take turns sending data during an update slot connections For a ControlNet bridge module CNB in a remote chassis Are most of the modules in the chassis non Then choose this communication format for the choose the most efficient communication format for that diagnostic digital 1 0 modules remote CNB module chassis Yes Rack Optimization The Rack Optimization format uses an additional 8 bytes for each slot in its chassis Analog modules or modules that are sending or getting diagnostic fuse timestamp or schedule data require direct connections and can
30. ed by the producer No default RPI is offered by the producing controller The packet intervals of existing connections from other consumers could be sped up on multicast connections The RPI limitations the range set on the produced tag and the default process applies only to multicast connections on unscheduled networks This feature is unavailable for controllers on the ControlNet network or unicast connections Scheduled bandwidths on the ControlNet network transmit critical data at pre determined intervals of time Important RPI limits and default values are not supported for safety tags and AXIS tags AXIS produced tags are produced at a rate equal to the Coarse Update Period of the associated motion group Safety produced tags are produced at a rate specified by the Safety Task Period If you have controllers running releases v17 or earlier that are consumers of a producer from a 5x80 controller take the following step to make sure consumers of produce tags can connect e Verify that all multicast consumed tags of a produce tag are configured with the same RPI If they are not some consumers will fail to connect Follow these steps to establish RPI limitations range and default values if you are setting up a producing tag for multicast connections See Unicast Connection Options on page 24 if you are setting up a unicast connection Rockwell Automation Publication 1756 PM011G EN P November 2015 21 Chapter 1 Produce an
31. ing tags within specified limitations for multicast connections A producing controller verifies that the RPI of incoming connections are within the produced tag settings If the consuming tag s RPI falls outside the configured range a producing controller will reject the incoming RPI and may provide an RPI default to the consuming controller This optional default RPI applies only if the consuming controller is set up to allow its consumed tags to use an RPI provided by the producer You can choose to not use the default value However you will have to manually change a rejected RPI to make the value within the limitation settings for the produced tag Tip 1769 L2x and 1769 L3x controllers have additional RPI information See 1769 L2x and 1769 L3x RPI Limits on page 31 for details If you have multicast consumers running Logix Designer releases v18 to v27 take the following steps to make sure consumers of produce tags can connect e Verify that all multicast consumed tags of a produce tag are configured with the same RPI or e Verify that all multicast consumers are configured to Allow Consumed Tags To Use RPI Provided By Consumer Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce and Consume a Tag Chapter 1 Set RPI limits default for producer tag Behavior in releases v17 and earlier When using releases v17 and earlier of the application an incoming RPI of a consuming controller will be accept
32. ll Automation support Rockwell Automation provides technical information on the web to assist you in using its products At hetp www rockwellautomation com support you can find technical and application notes sample code and links to software service packs You can also visit our Support Center at https rockwellautomation custhelp com for software updates support chats and forums technical information FAQs and to sign up for product notification updates In addition we offer multiple support programs for installation configuration and troubleshooting For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com services online phone Installation assistance If you experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running United States or Canada 1 440 646 3434 Outside United States or Canada Use the Worldwide Locator available at http www rockwellautomation com locations or contact your local Rockwell Automation representative New product satisfaction return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures
33. not take advantage of the rack optimized form Choosing None frees up the 8 bytes per slot for other uses such as produced or consumed tags Separate the tag into two or more smaller tags 1 Group the data according to similar update rates For example you could create one tag for data that is critical and another tag for data that is not as critical 2 Assign a different RPI to each tag Create logic to transfer the data in smaller sections See Produce a Large Array on page 36 packets Producea tag Follow these steps to create a producer tag 1 Open the Logix Designer application and choose a controller Important A controller can have both producing and consuming tags but a producer cannot consume its own data The local controller is the consumer and the remote controller is the producer 2 Inthe Controller Organizer right click the Controller Tags folder and click Edit Tags Rockwell Automation Publication 1756 PM011G EN P November 2015 13 Chapter 1 Produce and Consume a Tag You can produce only controller scoped tags J Controller Controller1 fg Controller Tags E Controller Fault Handler Power Up Handler 3 Inthe Tags Editor right click the tag that you want to be a producer and choose Edit name of tag Properties E Constant Open Parameter Connections 4 Inthe Tag Properties dialog box in the Name box type the name of the produced tag 5 From the Type li
34. nsfer_time_max Dest array_transfer_time_max 0 38 Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce a Large Array Chapter 2 7 Inthe Controller Tags folder of the controller project that consumes the array create these tags P Tag Name Type X array_ack DINT 2 array_packet DINT 125 8 Convert array_packet to a consumed tag For Specify Controller Name of the controller that is sending the packet Remote tag name array_packet Both controllers use the same name for this data 9 In either the Controller Tags folder or the tags folder of the program that will contain the logic for the transfer create these tags Tag Name Type array DINT x where x equals the number of elements to transfer plus 122 elements DINT array_offset 10 Create or open a routine for the logic that will move the data from the packets to the destination array 11 Enter this logic Rockwell Automation Publication 1756 PM011G EN P November 2015 39 Chapter 2 Produce a Large Array When the offset value in array_packet 123 is different than the offset value in array_ack 0 the controller has begun to receive a new packet of data so the rung checks for the value of 999 in the last element of the packet If the last element of the packet equals 999 the controller has received an entire packet of new data and begins the copy operation e The offset value moves from the packet to array_offset e
35. o more data to transfer so the rung resets the offset value logs the transfer time and resets the timer In either case the rung uses the new offset value to create a new packet of data appends the new offset value to the packet and clears the acknowledge element of the packet packet 124 TON Timer On Delay EN Timer array_transfer_limer Preset 10000000 ON Accum 0 TON Timer On Delay EN Timer array_transfer_timer Preset 10000000 ON Accum 0 NEQ EQU MOV Not Equal Equal Move Source A array_ack 0 Source A array_ack 1 Source 999 0 0 Source B array_packet 123 Source B 999 Dest array_packet 124 0 0 EQU CMP ADD Equal Compare Add Source A array_ack 0 Expression array_ack 0 123 lt array_size Source A array_packel 123 0 0 Source B array_packet 123 Source B 123 0 Dest array_offset 0 CMP CLR Compare Clear Expression array_ack 0 123 gt array_size Dest array_offset 0 MOV Move Source array_transfer_timer ACC 0 Dest array_transfer_time 0 array_transfer_timer RES COP MOV CLR Copy File Move Clear Source arraylarray_offset Source array_offset Dest array_packet 124 Dest array_packet 0 0 0 Length 123 Dest aray_packet 123 0 If the current transfer time is greater than the maximum transfer time update the maximum transfer time This maintains a record of the longest time to transfer data GRT MOV Greater Than A gt B Move Source A array_transfer_time Source array_transfer_time 0 0 Source B array_tra
36. ontroller The consumer is set up to accept the RPI provided by the producer Produced Tag Minimum RPI Maximum RPI Default RPI 2ms 8ms 5ms API 5ms Error 0112 Default RPI 5 ms RPI Tyas 5ms Negotiation Enabled Version 17 and earlier The RPI requested by the consumed tag is not within the range of the producer The connection is rejected and a 0112 error is reported that the connection failed You must re enter an RPI that is within the range configured on the produced tag If a version 17 consumer is trying to connect with aversion 18 producer and the RPI is outside the range of the producer a 0112 error reports the connection failed Version 18 and later The RPI requested by the consumed tag is not within the RPI limitation range of the producer The producer is configured to provide an RPI default The producer sends the default RPI to the consumer The consumer is set up to accept the RPI provided by the producer The connection is successful and the multicast connection accepts the new RPI of 5 ms All controllers with the exception of the CompactLogix 1769 L2x and 1769 L3x controllers produce data in packet intervals ranging from 0 196 536870 911 ms The 1769 L2x and 1769 L3x controllers produce only in packet intervals of 2 4 8 16 32 64 128 256 512 or 1024 ms You are not confined to entering these exact values when configuring an RPI limitation range and default RPI for the 1769 L2x
37. over a ControlNet network use a binary multiple of the ControlNet network update time NUT application For example if the NUT is 5 ms use an RPI of 5 10 20 40 ms and so forth Verify that 5x80 controller projects containing Take the following steps to make sure consumers of produce tags can connect multicast produce tags are configured correctly e For consumers running Logix Designer releases v17 and earlier that are consumers of a producer from a 5x80 controller e Verify that all multicast consumed tags of a produce tag are configured with the same RPI If they are not some consumers will fail to connect e For multicast consumers running Logix Designer releases v18 to v27 take one of these steps e Verify that all multicast consumed tags of a produce tag are configured with the same RPI or e Verify that all multicast consumers are configured to Allow Consumed Tags To Use RPI Provided By Consumer Combine data that goes to the same controller If you are producing several tags for the same controller group the data e Into one or more user defined data types This uses less connections than producing each tag separately e According to similar update intervals To conserve network bandwidth use a greater RPI for less critical data For example you could create one tag for data that is critical and another tag for data that is not as critical 12 Rockwell Automation Publication 1756 PM011G EN P November 2015 Produc
38. st click Produced 14 Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce and Consume a Tag Chapter 1 The Connection button becomes active when you choose either Produced or Consumed 6 Click Connection The Produced Tag Connection dialog box appears You can enter the number of controllers to consume receive the tag Produced Tag Connection Connection Status Max Consumers Advanced Send Data State Change Event To Consumer s 7 Inthe Max Consumers box enter a value Important The Advanced button on the right hand side of the Produced Tag Connection dialog box appears only for controllers using version 18 and later of the application This button opens the Advanced Options dialog box to set the RPI range limitation negotiated default or unicast connection See Additional Steps for a PLC 5C Controller on page 18 for details and procedures 8 Click OK Create a consumer tag Follow these steps to create a consumer tag 1 Open the Logix Designer application and choose a controller Important A controller can have both producing and consuming tags but a producer cannot consume its own data The local controller is the consumer and the remote controller is the producer 2 Inthe Controller Organizer I O Configuration folder add the controller that is producing the data the other Logix5000 controller or PLC 5C controller 3 Inthe Con
39. tags for produced or consumed data shared data follow these guidelines or consumed data Guideline Details Create the tags at the controller scope You can share only controller scoped tags Use one of these data types To share other data types create a user defined data type that contains the required data a Use the same data type for the produced tag and corresponding consumed tag or tags e REAL e Array of DINTs or REALs e User defined To share tags with a PLC 5C controller use a Then defined data type iii Produce Integers Create a user defined data type that contains an array of INTs with an even number of elements such as INT 2 When you produce INTs you must produce two or more Only one REAL Use the REAL data type value More than one Create a user defined data type that contains an array of REALs REAL value Consume Integers Create a user defined data type that contains these members Data Type Description DINT Status INT X where xis the output size of the data from the PLC 5C Data produced by a PLC 5C controller If you are consuming only one INT omit x controller Limit the size of the tag to 500 bytes If you must transfer more than 500 bytes create logic to transfer the data in packets If you produce the tag over a ControlNet network the tag may need to be less than 500 bytes See Adjust for Bandwidth Limitations on page 13 Use the highest permissible RPI for your If the controller consumes the tag
40. the 5x80 controller represent the 5x80 controller as a CompactLogix 5370 Controller such as the 1769 L36ERM in your consuming controller s I O configuration These controllers have a built in Ethernet port and therefore can be addressed using an EtherNet IP Address Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce and Consume a Tag Chapter 1 Considerations when migrating projects that contain multicast produce tags e Ifyou want to consume tags through the backplane port on the 5x80 Controller represent the 5x80 controller as a ControlLogix 5570 such as the 1756 L75 in your consuming controller s I O configuration This process allows connection using the backplane When you migrate projects from an earlier controller model to a 5x80 controller you need to verify that projects containing multicast produce tags are configured correctly In releases before v28 produce tags produce data at the requested packet interval RPI of the fastest requesting consumer This behavior allows multiple consumers with different RPI settings to successfully connect to a producer In releases v28 and later the first consumer of a produce tag determines the RPI at which data is produced All subsequent consumers must request the same RPI value as the first consumer or they fail to connect and display error code 0112 The first consumer of a produce tag is the device that sends the first consumer connection to the pro
41. the same network such as a ControlNet or Ethernet IP network You cannot bridge produced and consumed tags over two networks Produced and consumed tags each require connections As you increase the number of controllers that can consume a produced tag you also reduce the number of connections the controller has available for other operations like communication and I O Important If a consumed tag connection fails all of the other tags being consumed from that remote controller stop receiving new data Each produced or consumed tag uses the following connections This Type of Tag Uses This Many Connections Produced tag number_of_consumers 1 Consumed tag 1 Example Connection Requirements of a Produced or Consumed Tag e A ControlLogix controller producing 4 tags for 1 controller uses 8 connections e Each tag uses 2 connections 1 consumer 1 2 e 2 connections per tag x 4 tags 8 connections e Consuming 4 tags from a controller uses 4 connections 1 connection per tag x 4 tags 4 connections Communication Paths to 5x80 controllers Ifa controller running release v24 or earlier is to consume tag data from a 5x80 controller it must have a target device in its I O configuration for the connection However releases v24 and earlier do not have profiles for 5x80 controllers so a substitute must be used Rockwell recommends the following substitutes e Ifyou want to consume tags through the embedded Ethernet port on
42. troller Organizer right click the Controller Tags folder and click Edit Tags Rockwell Automation Publication 1756 PM011G EN P November 2015 15 Chapter 1 Produce and Consume a Tag You can produce only controller scoped tags J Controller Controller 14 B Controller Tags Controller Fault Handler Power Up Handler 4 Inthe Tag Editor window right click the tag that will consume the data and then choose Edit name of tag Properties lt controfler gt Base Alias Produced a fa Controller_1 Read Write Sye E Constant Open Parameter Connections 5 Inthe Name box type the name of the consumed tag 6 From the Type list click Consumed 16 Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce and Consume a Tag Chapter 1 The Connection button becomes active when either Consumed or Produced is chosen as the Type 7 Specify the data type If the producing controller Then the data type should be is Logix5000 controller Same data type as the produced tag PLC 5C controller User defined data type with these members Data type Description DINT Status INT X where x is the output size of the data from the PLC 5C controller Data produced by a PLC 5C controller If you are consuming only one INT omit x 8 Click Connection to define the consumed tag m Consumed Tag Connection Connection Status Producer fi
43. ucing controller s RPI Limits There is no default RPI that is set up for the producing controller Produced Tag Minimum RPI 2ms Maximum RPI 8ms Default RPI ms Error 0111 RPI 1 ms y Version 17 and earlier The RPI requested by the consumed tag is not within the range of the producer The connection is rejected and a 0111 error is reported that the connection failed You must re enter an RPI that is within the range configured on the produced tag If a version 17 consumer is trying to connect with a version 18 producer and the RPI is outside the range of the producer and there is no default set up a 0111 error reports the connection failed Tip See RPI 1 0 Faults on page 33 for an explanation of the error messages Version 18 and later The RPI requested by the consumed tag is not within the RPI limitation range of the producer The producer is not set up to provide a default RPI so a 0111 error message is reported that the connection failed You must re enter an RPI that is within the range configured for the producer because there is no RPI default negotiation with the consumer Scenario 3 The RPI is outside the range of the producing controller s RPI Limits A default RPI is set up for the producing controller But the network path contains a bridge Rockwell Automation Publication 1756 PM011G EN P November 2015 29 Chapter 1 Produce and Consume a Tag that blocks the negotiated RPI to
44. you can verify the acceptance and the RPI value on the Consumed Tag Connection dialog box You must be online to complete the following procedures acceptance 1 Open the Logix Designer application and choose a controller that is set up with a consuming tag 2 Inthe Controller Organizer right click the Controller Tags folder and choose Edit Tags 3 Inthe Controller Tags window right click a consuming tag and choose Edit name of tag Properties Rockwell Automation Publication 1756 PM011G EN P November 2015 25 Chapter 1 Produce and Consume a Tag The Tag Properties dialog box appears a 4 Click Connection at the right hand side of the Type box 26 Rockwell Automation Publication 1756 PM011G EN P November 2015 Produce and Consume a Tag Chapter 1 The Consumed Tag Connection dialog box appears with a flag to the right of the RPI box to indicate the consuming controller has accepted an RPI provider by the producer The time interval of the RPI also is indicated Consumed Tag Connection Connection Status Producer second_mod Remote Data Tag Name or Instance Number RPI 20 0 lms Y RPI provided by producer 8 37 ms V Use Unicast Connection over EtherNet IP The RPI that had been requested by the consuming controller is dimmed This lets you view the time interval the consuming controller had requested and the RPI provided by the producing controller
Download Pdf Manuals
Related Search
Related Contents
MANUAL SHAFT - Alignment Supplies, Inc. Reprenez le contrôle avec Linux ! - Systèmes d`exploitation - Barr - Better Biometry notes Termozeta Mixer 380 Clarion DB456MC User's Manual Lire l`article - sofiabensouda manuale d`uso - VERDE SABINA SRL WFT-E3 & E3A Instruction Manual for Use With EOS 50D (F) お使いください。 また、この取扱説明書はお手元に大切に保管 Copyright © All rights reserved.
Failed to retrieve file