Installation Guidelines for Power Drive Systems
Contents
1. Mains Mains side Frequency filter converter Screened RCD motor line Motor Mains side Frequency I Motor side i filter converter filter RCD Motor r Due to the currents flowing off through the filters designated the sum of currents through the RCD is not exactly zero which causes unwanted tripping Figure 11 Interference paths for RCD operation The likelihood of such problems depends to some extent on the frequency response of the particular RCD In cases where the RCD can be set at over 300mA problems are less likely with lower power drives unless very long motor cables are being used or considerable numbers of drives are connected to the same RCD If RCDs are specifically required some drive suppliers offer low leakage RFI filters as an option This solution generally only works with short motor cables alternatively it may be necessary to use an isolation transformer at the drive input It should also be noted that an a c VSD also incorporates large capacitors in the d c link which store charge also if a high inertia load is connected substantial kinetic energy may be available to regenerate into the drive This means that even if an RCD feeding the drive trips this does not remove all sources of electrical charge and this may induce a false sense of safety in the user For this reason it is best to avoid RCDs where possible and to rely on conventional protective
2. insulation monitoring device detects insulation faults at an early stage as they are developing and provides a signal that can be used to trigger visual and audible alarms when the insulation level drops below its set point The insulation resistance can generally be monitored over a period 4 2 3 EARTH LEAKAGE PROTECTION Earth leakage protection using a Residual Current Device RCD or similar is predominately used for the protection of personnel and requires special attention with an a c VSD for the following reasons i The drive contains a rectifier which could cause a smooth d c earth current For this reason only a type B RCD can be used with a VSD Note A type A RCD must never be used up stream of an a c VSD It could become disabled by the presence of smooth d c residual current and fail to provide protection for other loads Some manufacturers offer a range of RCDs specifically designed for use with frequency converters ii The majority of drives have a significant residual current both at the supply frequency because of the presence of RFI filter capacitors between lines and earth and at frequencies related to the PWM because of the effect of the capacitance from the motor circuit to earth This can cause nuisance tripping of the RCD iii Further details on the selection of RCDs for a drive are given in IEC 61800 5 1 Annex E Page 27 of 41 Installation Guide for Power Drive Systems
3. design which also precludes running at critical speeds below the nominal speed The advice of the manufacturer should be sought especially before e running any motor above its base speed e running any 2 pole unit constructed motor at variable speed e running any motors which include self lubricated sleeve bearings Q What is the likely effect on reliability of including a drive within my system A Frequency converters have been available in the market place for over 30 years and have improved in reliability over this time Subject to satisfactory installation and routine maintenance including removal of dust cleaning cooling surfaces and regular replacement of limited lifetime parts such as cooling fans and capacitors together with regular driven equipment and motor bearing lubrication and maintenance a modern drive system should have a long and satisfactory life Current manufacturers experience shows the MTBF for the electronics increasing Currently it is around 15 years to 30 years depending on size and installation Q I need to install an isolator local to the motor for safety purposes what do have to consider A The isolator housing must continue the Faraday Cage screening the inverter output and must be connected to the cable screen armour Every junction in a cable will also be a substantial change in impedance which can cause voltage transients As a rule of thumb each junction can be considered t
4. Ground terminals that may also be provided Cables should be connected as in Figure 8 EQUIPMENT 1 EQUIPMENT 2 D OUT IN SIGNAL IN GNDJ SCREEN SCREEN Figure 8 Control cable connection Page 24 of 41 Installation Guide for Power Drive Systems An example of bad practice is shown in Figure 9 Figure 9 Incorrect control cable connection Here the negative input has been connected to a local 0 Volt connection instead of the negative output of the signal source This results in the input being susceptible to common mode noise If the signal source is single ended the IN input should be connected to the 0 V reference of the signal source 3 15 2 DIGITAL SIGNALS Always separate digital and analogue signals Never mix 110 230 V digital signals in the same cable as 24 V DC signals A conventional screened or armoured cable can be used for 110 230 V signals 3 15 3 SERIAL COMMUNICATION SIGNALS The appropriate cable will depend on the carrier medium be it RS 232 RS 485 Ethernet etc Follow the system recommendations 3 15 4 ENCODER CABLES Pulse encoders may be galvanically connected to the motor rotor it is important that any bearing insulation is not bridged The recommendations of the encoder and drive supplier should always be strictly followed The correct cable type is also essential It is also preferable to ensure that the cable run from the encoder is a continuous length and not interr
5. The practical implementation of these issues needs to be resolved for each case but the examples in Section 5 9 give guidance 5 4 MOTORS As previously stated motors are essentially benign unless fed from a converter In this case the motor becomes a part of the Faraday Cage which restricts radiated emissions As the voltage received by the motor will consist of a high frequency pulse train with a common mode voltage it becomes a prospective emissions source For this purpose all separate parts of the motor frame and terminal box must be adequately bonded and joints may need to be filled with conductive gaskets This bonding needs to be connected by a low impedance path back to the converter 5 5 CONVERTERS The converter is the main source of electromagnetic noise potential radiated emissions must be contained within a Faraday Cage which may well include the motor and cables Conducted emissions are generally controlled by filtering see Section 5 7 5 6 TRANSFORMERS Transformers are again benign components which will not generate disturbances however if a new transformer is being specified consideration should always be given to fitting an earthed screen between primary and secondary windings which has a substantial filtering effect on high frequency conducted emissions The use of an earthed screen is mandatory when feeding an ungrounded IT network 5 7 CABLES Correct cable selection is essential to achieve g
6. Whatever couplings are used they should be aligned very carefully in all three planes The shaft centres should be correctly aligned when in normal use so that they are coincident The value of good alignment cannot be over estimated Poor alignment can be a major source of noise and vibrations It may damage bearings possibly shear a shaft and quickly ruin a flexible coupling To ensure correct alignment the manufacturers instructions must be followed Allowance must always be made for shaft end float and thermal expansion in both axial and radial directions Page 8 of 41 Installation Guide for Power Drive Systems Figure 3 Belt driven fan assembly Spline or gear type couplings generally should be aligned by procedures similar to that of solid couplings Coupling hubs should be heated in an oil bath or oven prior to fitting gas torches must never be used Belt drives have the motor mounted on slide rails or an adjustable base to permit re tensioning of the belt by moving the machine Whether it is flat belt drive or V belt drive any limitation on pulley ratio and bearing radial loading must be strictly observed Never overtension a drive belt Careful attention to the design of belt drives in highly dynamic applications is always required 2 3 2 2 BEARINGS It is normal practice for motors to be ready to run when despatched from the works and there should be no need for the bearings to be greased In the case of non shield
7. afforded by the converter will only see the group of motors Great care must be taken in selecting suitable protection as many protection devices do not function satisfactorily in an inverter output When considering the maximum cable lengths permitted the sum of all the cables fitted in the inverter must be considered Q How frequently should the mains supply of a Frequency Converter drive be switched off A This will depend on the individual manufacture However typically a gap of at least three minutes will be required otherwise the internal inrush current limitation could be overloaded Normally a drive should be started and stopped by the control electronics Frequent opening for example of safety interlocks may require output switching or the use of a PDS SR with Safe Torque Off Q How should a power supply cable shield be connected A Supply cable shields must always be grounded at the supply source end usually the converter end will be grounded at the converter Cables should always be properly terminated using the appropriate glands to give 360 shield termination However with single cores the shield must always be left unconnected and isolated at the converter end to prevent circulating currents Q For most motors the thermal loadability drops as the speed reduces how do we protect the motor A Basically a conventional motor thermal overcurrent relay would allow a motor to draw too high a current a
8. automatically This arrangement works effectively for lightly loaded circuits powering lighting and older motors but must not be used to feed converters which require a constant d c voltage or for modern high and premium efficiency motors 3 4 POWER CABLE TYPES 3 4 1 DRIVE SUPPLY CABLE There are no special considerations for the selection of input cable types when using a PDS unless advised by the manufacturer The cable should be chosen to suit the installation 3 4 1 1 FAULT CURRENT CONTRIBUTION AND CABLE SIZING Unlike a motor directly connected to a network a diode rectifier fed drive will not produce any contribution to a fault in the supply network A regenerative drive will only feed a current equal to its rating while the control is energised 3 4 2 DRIVE MOTOR CABLE Drive output cables should always be multicore types and the use of single core cables is to be deprecated Where a single cable is inadequate for the current rating parallel multicore cables should always be used The following additional issues must be considered Page 15 of 41 Installation Guide for Power Drive Systems 3 4 2 1 CABLE CAPACITANCE The drive has to provide charging current for the cable capacitance at every PWM pulse edge and this forms an additional current load on the drive which can if excessive cause it to trip or invoke a premature current limit The drive supplier should specify a maximum cable length with an indication
9. be considered when specifying and installing a power drive system Supplies considered are low voltage up to 690 V a c The installation procedures detailed are specifically oriented to current United Kingdom practice For the application of a power drive system incorporating Ex motors refer to the motor manufacturer for confirmation of their suitability and certification SUMMARY Satisfactory operation of a drive system is dependent on a satisfactory installation Not only must the motor and converter be mounted in accordance with the manufacturer s requirements but they must also be adequately cooled effectively cabled and earthed Compliance with the appropriate EU Directives and with local regulations is also a legal requirement Specific sections in this report cover the requirements for the various parts of a power drive system to assist specifiers and purchasers of drive systems from the specification phase to the installation and final commissioning CONTENTS FOREWORD SCOPE SUMMARY Section 1 INTRODUCTION 1 1 1 2 1 3 1 4 1 5 THE POWER DRIVE SYSTEM THE MOTOR AC VARIABLE SPEED DRIVES THE TRANSFORMER THE CABLES Section 2 THE MECHANICAL INSTALLATION 2 1 2 2 2 3 2 4 2 5 THE MACHINERY DIRECTIVE SAFETY ENVIRONMENT 2 3 1 MOTOR 2 3 2 MOTOR INSTALLATION 2 3 3 CONVERTER 2 3 4 TRANSFORMERS CABLES EQUIPMENT SITING 2 5 1 MOTOR 2 5 2 CONVERTER 2 5 3 COOLING REQUIREMENTS Section 3
10. be energised when the motor is de energised The operation of any auxiliary device should be checked Motors on their own when operated direct from the public electricity supply network are benign in respect of electro magnetic interference both in terms of immunity and emissions although they are designed for a Total Voltage Harmonic Distortion THDy of only 2 and may require de rating for higher levels When used in conjunction with inverters they become part of the power drive system and therefore can no longer be considered benign More information is provided in Sections 4 amp 5 Finally recommendations for insulation and bearing requirements are given in GAMBICA REMA Technical Reports 1 and 2 3 2 1 2 CONVERTERS It is of paramount importance that the manufacturers instructions and diagrams with regard to wiring are adhered to Connecting a mains supply to the converter motor terminals can cause serious damage to the installation 3 3 THE TRANSFORMER In general the electrical installation of a drive dedicated transformer is no different to any other distribution or power transformer The transformer cables should follow the Page 14 of 41 Installation Guide for Power Drive Systems guidelines given for drive input cables unless the manufacturer makes a specific recommendation for example where a 12 pulse rectifier is utilised Most distribution transformers are fitted with tappings and care should always be taken
11. differential K A Surface area in m k constant typically 5 5 W Km for painted sheet steel Details on the selection principles for secondary enclosures can be found in the GAMBICA Technical Guide General Purpose Enclosures Section 3 THE ELECTRICAL INSTALLATION 3 1 THE LOW VOLTAGE DIRECTIVE Any electrical equipment supplied in the European Union or European Economic Area except those in a hazardous area utilising voltages below 1000 V or 1500 V must comply with the EU Low Voltage Directive which is designed to ensure electrical safety The ATEX directive covers safety in hazardous areas The Low Voltage Directive 2006 95 EC is implemented in a similar manner to the Machinery Directive as previously described 3 2 BASIC REQUIREMENTS The electrical installation of the equipment covers aspects such as e Insulation e Provision for isolation e Cable selection e Overload and fault protection e Earthing Page 13 of 41 Installation Guide for Power Drive Systems All of these aspects must be undertaken correctly to ensure a safe and satisfactory installation Any installation must be undertaken in accordance with the appropriate National Regulations Requirements that are specific to a power drive system are considered in detail in the following sections 3 2 1 GENERAL REQUIREMENTS With regard to the electrical installation the equipment suppliers instructions must be observed Before any
12. leaving the drive unprotected Where drives are mounted on a wall this should preferably be of brick or block construction Larger power drives can have their discharge ducted to outside air where extreme care must be taken to avoid condensation forming in the ductwork Consideration may also be given to water cooling This may be by utilising a proprietary water cooled drive system or by installing water air coolers in the control room This type of cooling system should always be provided with anti freeze and corrosion inhibitors Where the air flow through the main heat sinks is ducted outside the control room or where water cooling is used there will still be some heat dissipation into the control room e g due to cabling and the control electronics The drive manufacturer will advise on the magnitude of this dissipation 2 5 3 COOLING REQUIREMENTS The majority of drives are designed for a maximum ambient temperature of 40 C which means that the inlet cooling air must not exceed that value This in turn suggests that to maintain an acceptable room temperature a suitable level of airflow will be needed The basic formula to determine an airflow in cubic metres per hour is to multiply the heat loss in Watts x a constant 3 1 for air at sea level and divide by the temperature differential in K These requirements are equally valid for drives installed in secondary enclosures In the event of manufacturers figures being unav
13. that any coolant leakage is restricted The most common coolant is mineral insulating oil which is closely related to diesel oil It is a potential carcinogen and is also flammable Other coolants include less flammable materials such as silicone oils midel and others including water miscible types The manufacturers recommendations regarding the nature of the hazards for these products must be followed Containment in case of any leakage will probably be required It follows therefore that a COSHH review should be implemented before installing this equipment 5 Control of Substances Hazardous to Health Page 10 of 41 Installation Guide for Power Drive Systems 2 3 4 2 DRY TYPE TRANSFORMERS Dry type transformers are of two basic types Low voltage windings are usually resin impregnated in the same manner as motor windings but many high voltage windings are resin encapsulated either in an autoclave or by wrapping techniques Dry type transformers may be installed in hostile environments and a number of classes exist Typically a cast coil transformer will meet Class C2 which requires a thermal shock to be applied Class E2 which requires the equipment to operate satisfactorily in high humidity and F1 which determines the fire retardant capability 6 In either case the transformer will require cooling and as a guide each kilowatt of losses requires at least 4 m min air circulation 2 4 CABLES It is important to plan
14. the cable installation carefully The installation may require bottom cable entry for the cables running in trenches or top entry from cables on tray work It is important with either arrangement to ensure the segregation detailed later is maintained It is also of primary importance to ensure that the equipment is suited to cable entry from the direction required and to ensure that water and foreign matter cannot enter through the cable entry or cable gland plate Many armoured power cables are extremely intractable and difficult to bend therefore allowing adequate bending radii is always important In drive installations the armouring also forms an essential part of the electrical screening and the minimum bending radii detailed by the manufacturer must always be observed to prevent the wire armour spreading thus leaving slots to radiate HF emissions 2 5 EQUIPMENT SITING 2 5 1 MOTOR Motor siting has been discussed in 2 3 1 However the availability of free access to the cable boxes for installation and maintenance must be considered as should the access to bearing greasing points when provided generally in motors gt 75 kW It is advisable to install the motor with adequate access for routine maintenance A minimum clearance at the fan inlet is necessary to ensure free airflow this can vary from 50 mm for low power lt 11 kW to 150 mm or more for a high power motor Ensure that there is no obstruction to the cooling airflow and that
15. to set the transformer on the correct voltage tapping It should also be noted that European practice is to label the transformer with it s no load ratio in other words when the transformer is loaded the secondary volts will drop Throughout Europe including the UK the majority of low voltage drives operate on a mains voltage of 400 V prescribed by EN 50160 This means that a typical distribution transformer should be designed for a no load ratio of 11000V 2 x 2 5 420 V The vector group and impedance should be agreed between the drive manufacturer and the transformer manufacturer The conventional winding arrangement for a distribution transformer is Dyn11 and a 3 winding transformer for 12 pulse bridge is Dy11d0 The electrical protection of a transformer requires care and must always be carefully considered Protection is normally required for over current and over temperature as a minimum It is usual for the over current protection to include the primary and secondary cables Dry type transformers will normally have resistance temperature detectors RTDs that must be monitored Liquid cooled transformers have contact thermometers or RTDs plus monitoring for the coolant pressure and condition In either case the primary must be disconnected rapidly in the event of a problem 3 3 1 POWER CONDITIONERS Some areas where there are old networks use power conditioners in the circuit these devices monitor the load and reduce the voltage
16. with a direct on line started induction motor The intelligent control of even the simplest drives limits the starting current in the motor circuit to typically 150 of the full load rating This provides a starting torque that is not affected by voltage drop in the input cable and can be optimised to allow for the voltage drop in the output cable The cable voltage drop does affect the available torque at maximum speed and especially for drives that operate beyond the motor base speed field weakening For applications where this is an important consideration this aspect must be given attention Even then many drives offer slip compensation that can maintain the torque at the expense of an increased motor current When standard design codes are used for cable selection they should be configured for resistive loads and not for motor loads otherwise unnecessary cost may be incurred in allowing for the starting current 3 6 SUPPLY CABLE e Co ordination with the protection device fuse or circuit breaker This device provides protection to both the drive and the cable so the cable must be selected appropriately When using standard industrial fuses such as the BS EN 60269 gG range including the former BS 88 which are designed for co ordinated protection of cables against faults and overloading the cable rating must simply equal or exceed the fuse rating allowing for ambient temperature The disconnection time of the protection device
17. C which are largely governed by local regulations They are a site specific requirement and within the UK are governed by the Energy Networks Association Engineering Recommendation G5 4 1 No PDS can in itself meet G5 4 1 only the entire client s site at the point of common coupling can comply For information on compliance the GAMBICA Guide to G5 4 1 is available Note Where active harmonic filtering is employed this will inject anti phase harmonic currents into a network and the comments of Section 3 14 regarding de tuned power factor correction are of importance 5 12 RESPONSIBILITIES All parties in the chain of supply have responsibilities to meet the requirements of the EMC directive and all other relevant directives 5 12 1 MANUFACTURER The manufacturer has a duty to design products in a way that enables the EMC requirements to be met with realistic installation procedures The manufacturer must also give detailed instructions in the installation guidelines which are a pre requisite to meeting the EMC directive Further the manufacturer should be able to recommend the appropriate conducted EMC filters to be able to meet EMC mitigation levels gt normally specified as class A or class filters The manufacturer should also be able to provide estimates of harmonic currents 5 12 2 PANEL BUILDER The panel builder MCC manufacturer must follow the manufacturer s installation instructions to achiev
18. GAMBICA REMA Technical Guide Variable Speed Drives amp Motors Installation Guidelines for Power Drive Systems l N amp AUTOMATION ROTATING LECTRI ICAL Fourth Edition 2012 INSTRUMENTATION amp CO LABORATORY TECHNOLOGY NES ASSOCIATION NTROL Installation Guide for Power Drive Systems Fourth Edition GAMBICA REMA 2012 FOREWORD This Technical Report has been produced to meet a demand for an authoritative guide on best practice for the installation of Power Drive Systems It is the result of a study carried out by GAMBICA and REMA taking note of well established fundamental theory technical papers and carrying out specific investigations The information given while it can be applied to motors and inverters in general is specific to current generation products of member companies The Technical Report principally considers the aspects of safe mechanical and electrical installation and the avoidance of EMC problems This report covers motors and inverters installed with a separate cabling system connecting the components together it is not wholly applicable to inverters integrated into a motor design which are now generally available up to 7 5 kW The references together with a useful list of further reading are included in the final section of this report SCOPE This report provides information on the basic principles that require to
19. NSTALLATIONS Very often problem installations are not immediately apparent as can be seen from the following examples Terminal box has no conductive gasket Junction in earth conductor should go to moto then cross bond to fan bed AND fan volute Instrument cable mounted on same racking a main motor conductors Figure 14 Problem Example No 1 Page 35 of 41 Installation Guide for Power Drive Systems Unscreened Plastic enclosed local isolator Breaks earth plane Motor cable in common harness with other cables allows cross interference Page 36 of 41 TERM OR ABBREVIATION Armour ATEX BDM BSI CE Mark CENELEC CISPR COSHH d c Earth Earthing ELCB EMC EMI EN Ethernet EU Faraday Cage G5 4 1 IEC Page 37 of 41 Installation Guide for Power Drive Systems GLOSSARY OF TERMS DESCRIPTION Alternating current A sheath fitted around a cable to provide mechanical protection Atmosph res Explosible European Directive using French acronym covering the essential health and safety requirements for products used in potentially explosive atmospheres Basic Drive Module British Standards Institution responsible for the preparation of UK National Standards prefixed BS and publication of harmonised standards prefixed BS EN Indication of compliance with EU Directives European Committee for the Electrotechnical Standardisation respo
20. THE ELECTRICAL INSTALLATION 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 THE LOW VOLTAGE DIRECTIVE BASIC REQUIREMENTS 3 2 1 GENERAL REQUIREMENTS THE TRANSFORMER 3 3 1 POWER CONDITIONERS POWER CABLE TYPES 3 4 1 DRIVE SUPPLY CABLE 3 4 2 DRIVE MOTOR CABLE CABLE RATINGS 3 5 1 SUPPLY AND MOTOR CABLES SUPPLY CABLE MOTOR CABLE CIRCUIT PROTECTION HIGH POWERS CURRENTS 3 10 CABLE CONNECTION POINT 3 11 LOCAL TO MOTOR ISOLATION AR NN O O O O O Q Q N PO ND HM HH SH 0 N NN O O O Q O Q Q N ND 3 12 3 13 3 14 3 15 OUTPUT CIRCUIT SWITCHING CABLE GLANDING POWER FACTOR CORRECTION CONTROL CONNECTIONS 3 15 1 ANALOGUE SIGNALS 3 15 2 DIGITAL SIGNALS 3 15 3 SERIAL COMMUNICATION SIGNALS 3 15 4 ENCODER CABLES 3 15 5 SEGREGATION Section 4 EARTHING 4 1 4 2 4 3 SUPPLY CONNECTIONS 4 1 1 EARTHED SECONDARY TN C TN S 4 1 2 UNEARTHED SECONDARY IT EARTH FAULT PROTECTION 4 2 1 SUMMATION PROTECTION 4 2 2 INSULATION MONITORING 4 2 3 EARTH LEAKAGE PROTECTION EARTH LOOP IMPEDANCE TESTING Section 5 EMC ISSUES 5 1 5 2 5 3 5 4 5 5 5 6 5 7 5 8 5 9 5 10 5 11 THE EMC DIRECTIVE STANDARDS MOTORS CONVERTERS TRANSFORMERS CABLES FILTERS EARTH CONDUCTORS PRACTICAL EXAMPLES OF EMC AND PRODUCT SELECTION HARMONICS RESPONSIBILITIES 5 11 1 MANUFACTURER 5 11 2 PANEL BUILDER 5 11 3 S
21. YSTEM INTEGRATOR INSTALLER 5 11 4 USER Section 6 PROBLEM INSTALLATIONS Section 7 REFERENCES AND ACKNOWLEDGEMENTS 22 22 23 23 23 25 25 25 25 26 26 26 26 27 27 27 27 28 28 28 30 31 31 31 31 32 32 32 34 34 34 34 34 34 35 41 Installation Guide for Power Drive Systems Section 1 INTRODUCTION 1 1 THE POWER DRIVE SYSTEM A power drive system PDS is a concept used by a number of standards It consists of a Complete Drive Module CDM and a motor together with its interconnections it does not include driven load In turn the CDM consists of a Basic Drive Module BDM and its possible extensions such as the feeding section or some auxiliaries for example ventilation The BDM contains the electronic power converter control and self protection functions Figure 1 shows the boundary between the PDS and the rest of the installation and or manufacturing process Installation or part of Power Drive System CDM Complete Drive Module System control and sequencing BDM Basic Drive Module Control Converter and Protection Feeding section Field supply Dynamic braking Auxiliaries others Motor and sensors Driven equipment Figure 1 The Power Drive System 1 IEC 61800 part 1 2 and 4 give details for these definitions Page 4 of 41 Installation Guide for Power Drive Systems For the purpose of this guide the cabling from the supply is also cons
22. ailable the loss can be assumed to be 2 5 of the controlled motor power for each inverter If transformers are installed in the same room a similar allowance should be made for each transformer Page 12 of 41 Installation Guide for Power Drive Systems As a typical example a standard 6 pulse drive rated at 75 kW with the converter mounted in a switch room with an ambient temperature of 30 C and an anticipated temperature differential of 10K will require 0 025 x 75000 x 3 1 10 581 These values in addition to those for dissipating losses from cables switch and control gear The maximum surface temperature of any parts that may be touched must also be considered In multiple drive installations the diversity of loading should be considered since this may offer savings in the cooling requirements The airflow must be arranged to ensure that no recirculation of the heated exhaust air occurs It must also be remembered that warmed air expands therefore if free ventilation is required the outlet should be at least 20 greater cross sectional area than the inlet In addition to cooling the equipment adequately the prevention of condensation is also critically important For effective prevention a dry transformer motor or converter enclosure should be kept at least 10K warmer than the surroundings Generally heaters are sized according to the formula H AtxAxk Where H Heater Power Watts At Temperature
23. and having relatively low switching losses The nature of the voltage generated by such an inverter incorporates a certain degree of high frequency noise which can lead to problems with Electromagnetic Compatibility EMC The rectifier also presents harmonic currents back to the network which must be taken into account when designing a system Page 5 of 41 Installation Guide for Power Drive Systems 1 4 THE TRANSFORMER While most power drive systems are fed at low voltage from a supply shared with other equipment there is occasionally a requirement to utilise a dedicated transformer in association with the drive 1 5 THE CABLES Cabling is one of the most critical areas of a good installation Section 2 THE MECHANICAL INSTALLATION 2 1 THE MACHINERY DIRECTIVE Any installation in Europe must comply with the EU Machinery Safety Directive which is designed to ensure safety for any user or operative EU Directives do not have the force of law in themselves In the event of any problem in the UK it is only the appropriate Statutory Instrument passed by the UK Parliament which has force of law The Machinery Directive is known by the number 2006 42 EC under which it was published in the Official Journal of the EU The UK national legislation which implements it is in the form of Statutory Instruments The Directive defines a machine as an assembly fitted with or intended to be fitted with a drive system other than dir
24. ation of output filters can reduce this requirement Page 17 of 41 Installation Guide for Power Drive Systems Po Separate protective S 525 O F wire Fe armour Frequency converter Frequency converter UV w Factory main grounding bus Factory main grounding bus Factory main rounding bus Factory main z grounding bus Separate protective 2 conductor Protective Conductor Figure 4 Typical Converter Motor Cables 3 4 2 5 VOLTAGE RATING Standard 600 1000V mains rated cables are suitable for this application It has sometimes been suggested that because of the repetitive voltage transients caused by pulse reflections in the cable special cable with additional insulation should be used This may be the case for large drives operating at voltages above 690V but for applications at or below 690V there is no requirement for special insulation 3 4 2 6 INCLUSION OF OTHER CABLES No other cables neither power cables nor data signal cables should be included within the motor cable screen Very high levels of electrical noise will be induced into such cables Although it is possible to accommodate this by careful management it is not recommended for general use 3 5 CABLE RATINGS The cable rating should primarily be based on the electrical safety and wiring regulations ap
25. bonding to ensure electrical safety 4 3 EARTH LOOP IMPEDANCE TESTING In principle the drive terminals are the end of a subcircuit feeding the PDS and earth loop impedance tests should be only conducted to this point For security it is normally recommended to conduct a further test with the drive input terminals directly connected to its output and therefore including the motor in the loop Section 5 ISSUES 5 1 THE EMC DIRECTIVE The EMC Directive is administered in the same way as the Machinery Directive and the Low Voltage Directive The EMC Directive 2004 108 EC requires that electrical electronic equipment must function satisfactorily in its electromagnetic environment without introducing intolerable electromagnetic disturbances to other equipment in that environment In Page 28 of 41 Installation Guide for Power Drive Systems essence no piece of equipment may emit undue electromagnetic emissions or be unduly susceptible to external emissions Electromagnetic disturbances can arise from both conducted emissions and radiated emissions ElectroMagnetic Compatibility EMC is a balance of the emissions from a particular apparatus and the immunity of that apparatus from disturbances caused due to emissions from external sources and these requirements are enshrined as the essential protection requirements of the EMCD Disturbance VICTIM W Immunity limit Compatibility margin Immunity margin Com
26. d care must be taken to ensure that lubricant films are established and maintained as soon as possible after starting Frequently manufacturers fit insulated bearings to the non drive end of the motor for protection against the effects of variable speed drive operation It is essential if replacing these bearings that a compatible type of bearing is fitted 2 3 2 3 MAXIMUM EXTERNAL LOADS A full list of limits for both radial and axial forces can normally be found in motor manufacturers catalogues For a long and trouble free bearing life it is important that these values are abided by at the time of installation 4 GAMBICA REMA Technical Report No 2 gives recommendations Page 9 of 41 Installation Guide for Power Drive Systems 2 3 3 CONVERTER Frequency converters use power electronic devices which are relatively robust However the control electronics are generally assembled onto printed circuit cards with very close component spacing They are therefore potentially vulnerable to contamination Specifically condensation can have a disastrous effect by allowing tracking across the surfaces of main semiconductors and of control cards so it is of prime importance to prevent condensation within the converter enclosure especially while the equipment is switched off This also includes the effects of frost when a converter is installed in an unheated switch room during the winter Means must always be installed to ensure that c
27. d on the prospective fault level To operate as a protective conductor the shield conductance must be at least 50 of that of the phase conductor If a separate protective conductor is required then it must comply with one of the following options e entirely outside the cable screen e entirely inside the cable screen and terminated by a very short connection at the same place as the screen at both ends of the cable Any other arrangement will reduce or remove the screening benefit of the cable Recommended connections for earthing connections are shown in Figure 4 3 4 2 4 SYMMETRY Very large numbers of successful installations have been undertaken with 4 core shielded or armoured cables however there is some evidence to suggest that for larger cables gt 16 mm a symmetrical construction will give an improved performance i e either there should be no internal protective conductor or else there should be three internal protective conductors symmetrically arranged with respect to the phase conductors as shown in Figure 4 items B and C The object of the symmetry is to achieve an even field within the cable screen which will reduce the induced voltages on the protective conductor and therefore limit any potential difference applied to a motor frame which will induce shaft voltages and potentially cause motor bearing damage This effect becomes more apparent with increase in size and cable run while the applic
28. e a reliable and compliant system The installation instructions will cover basic safety issues EMC mitigation measures and general installation issues such as cooling etc 5 12 3 SYSTEM INTEGRATOR INSTALLER The system integrator or installer should ensure that the correct products have been selected with appropriate measures for the intended electromagnetic environment and installed in a rigorous way Aspects such as earthing grounding and shielding require particular attention 5 12 4 USER The equipment selection is dependent on the final use e g domestic industrial see examples above For industrial use the end customer should specify the necessary site conditions and should also oversee the installer to ensure that the complete system is appropriate for the intended use Page 34 of 41 Installation Guide for Power Drive Systems For any given industrial application the potential implications of installing the new equipment should be considered Analysing the four criteria given in Section 5 2 above will form the basis of the site EMC plan and will therefore determine the required level of mitigation Ideally the assessment will be done consideration of the basic data supplied from the manufacturer Guidance is given within EN 61800 3 The user will also have a responsibility to ensure that the equipment is maintained in accordance with the manufacturer s instructions Section 6 PROBLEM I
29. ectly applied human or animal effort consisting of linked parts or components at least one of which moves and which are joined together for a specific application The Power Drive System is clearly therefore a part of a Machine The Directive also uses the concept of a safety component and certain Power Drive Systems may have safety related features and are termed Safety Related Power Drive Systems or PDS SR specific GAMBICA Guide to the application of these has been published 2 To implement the Directive a number of standards are published well over 400 are currently listed on the EU website CE Marking is the method used within the EU to indicate compliance with the appropriate directives for a particular item offered for sale the presence of a CE Mark generally means that the equipment meets the relevant requirements general purpose PDS is not a complete machine so it cannot carry a CE mark under the Machinery Directive It should however be delivered with appropriate declarations showing the standards that have been met A drive with safety functions i e a PDS SR does require a CE mark under the Machinery Directive The GAMBICA Guide to CE Marking provides further information on the application of the appropriate regulations 3 2 2 SAFETY A framework of standards regarding safety exists and the machinery manufacturer must identify the hazards associated with his specific equipment together with the corresponding
30. ed bearings re greasing facilities are provided as standard Shielded bearings have sufficient grease to last over two years in normal operation However the manufacturer s instructions should always be consulted before putting a motor into operation and when establishing the motor s service schedule If any motor has been stored for a long period it may be necessary to rotate the shaft in accordance with the manufacturer s recommendations It may be necessary to re grease the bearings with compatible grease before it is commissioned and this should be done in accordance with the manufacturer s instructions Re lubrication intervals are load and temperature dependent and they are available on request from motor manufacturers When replenishing it is important that a right type of lubricant is used Preferably it should be the same as the one given on the motor nameplate Using incompatible lubricants could lead to premature failure of bearings When motors are inverter fed the bearings may be subjected to damaging electrical discharges due to high frequency common mode voltages It is therefore important that correct precautions are taken 4 In some circumstances such as highly dynamic systems or high ambient temperatures converter fed motors should be provided with high temperature grease this is not usually miscible with standard grease Sleeve or white metal bearings are only normally encountered in special or large motors an
31. electrical connections are made check there is no foreign matter present and if there is any surface dust or dirt ensure it is removed 3 2 1 1 MOTOR To make electrical connections a connection diagram which is normally provided in the terminal box of the motor must be carefully followed The connecting links must be correctly set for the appropriate voltage Cabling practice is described in the following paragraphs If a motor is fitted with a feedback device such as a digital tachometer commonly referred to as an encoder or a resolver ensure pin connections are correctly made The terminal connections must be made with utmost care ensuring that there is sufficient clearance and creepage distances between the adjacent terminals The cable end lugs must be properly secured to the studs of the anti tracking terminal block using washers and nuts provided but excessive torque to the terminals must be avoided as this can result in damage to them When auxiliary devices such as Resistance Temperature Detectors RTDs thermistors or thermostats are located in the stator winding they must be connected to a suitable control circuit in the inverter cabinet to give an alarm or trip the drive at a predetermined temperature Where anti condensation heaters are fitted on to the stator windings they must be connected to a suitable supply and control must be arranged such that they are disconnected whilst the motor is energised They should only
32. etic Interference Power Drive System Protective Earth Pulse Width Modulated Residual current detecting device form of earth leakage protection Standards for serial communications interfaces Root mean square Resistance temperature detector An electromagnetic barrier Statutory Instrument Earthed neutral networks Underwriters Laboratories American inspection and certification organisation Technique to reduce harmonics 3 6 3 15 4 1 2 2 1 4 1 1 See GAMBICA Guide to G5 4 1 Installation Guide for Power Drive Systems FREQUENTLY ASKED QUESTIONS Q If have several motors to run at the same speed how do l select frequency converter A In multi motor configuration where a number of motors are fed from a single inverter the sum of the motor currents must be less than the rated current of the inverter If the motors are started simultaneously the total acceleration current must be less than the overload current of the inverter When motors are started sequentially at any frequency as the direct on line DOL starting current typically 5 to 8 times full load current flows into the motor this peak current must be accounted for and the maximum current must not exceed the overload current rating of the inverter The sum of the rated motor currents after completion of the start must be less than the rated inverter output current Each motor will require individual protection as the integral protection
33. g environments To acquire the greatest benefit from them in terms of trouble free operation and long life it is very important that utmost attention is paid to all aspects of their installation This becomes even more vital if motors are to be driven from an inverter supply the nature of which could lead to unforeseen problems such as excessive vibrations noise bearing failures insulation damage mechanical damage electrical or thermal overloading etc if due care is not exercised There are many ways of mounting motors They can be foot or flange mounted and mounting position can be horizontal or vertical with shaft up or down or inclined The mounting method and orientation must be specified to the motor manufacturer Normally the motors are mounted on foundations which must be solid rigid and level Slide rails sunken bolts and metallic base plates may be used to secure them to the foundations Direct coupled motors can be mounted on bedplates or soleplates grouted in the foundations or on pads or rods in special applications When transmission is via belts it is normal to use slide rails or an adjustable base which permits the belt to be Page 7 of 41 Installation Guide for Power Drive Systems tensioned by moving the motor Avoid the types of belt that are likely to become electro statically charged Usually the location of the driven load will govern the location of the motor and in general a wide range of motor enclos
34. idered as the selection of suitable cables is often a problem especially when dedicated feeding transformers are installed 1 2 THE MOTOR The vast majority of motors sold today are squirrel cage induction motors they are widely available robust and efficient When installed in accordance with the simple guidelines given they can be used in conjunction with a voltage source PWM drive to give a highly satisfactory variable speed drive system Specific requirements for motors are detailed in GAMBICA REMA Technical Reports 1 and 2 which discuss winding insulation and bearing currents 1 3 AC VARIABLE SPEED DRIVES Variable speed a c drive systems as illustrated below are used in ever increasing numbers because of their well known benefits for energy efficiency and flexible control of processes and machinery using low cost maintenance free a c motors Virtually all a c drives use power switching techniques and generate high rates of change of voltage Supply Feeding Supply Frequency Transformer Equipment Cable Converter Motor Cable SS SS a Motor Rectifier DC Link Inverter l l l l Motor Control Cables auxiliaries Factory Earth Figure 2 Power Drive System Most modern a c drives incorporate a Basic Drive Module based on a voltage source PWM inverter with very fast switching power semiconductor devices such as Insulated Gate Bipolar Transistors IGBT which have the advantage of being very robust
35. ight be expected the upstream protective device will not trip due to a first fault It is possible for the equipment to continue to function in the event of a single earth fault Earth leakage monitoring is a mandatory requirement to alarm in the event of a first earth fault and allow safe disconnection before a second earth fault EN 61800 3 recommends that EMC filters should not be used in un earthed networks 8 GAMBICA REMA Technical Report No 2 covering Bearing Currents gives further information on the requirement for potential equalising Page 26 of 41 Installation Guide for Power Drive Systems High levels of common mode voltage can occur in IT systems such as those used with 12 pulse drives which will share the electrical stresses on the motor windings with the input circuit and transformer This is not a potential problem with l v networks however the manufacturers recommendations for cable insulation levels for higher voltage systems should be sought 4 2 EARTH FAULT PROTECTION 4 2 1 SUMMATION PROTECTION A current summing core balance transformer is normally used to detect an earth fault current in an earthed network In case of an earth fault the current imbalance produces an earth fault warning or trip depending on the requirements 4 2 2 INSULATION MONITORING The high reliability of an IT system including an isolated 12 pulse system is assured by continuously monitoring the insulation level of the system
36. is of critical importance and should be checked when planning the installation Typically this should be less than 500 ms or as advised by the drive manufacturer e Effects of inrush current A frequency converter will have an inrush current on charging that is LESS than its full load current therefore no provision in cable sizing is needed to cover this aspect If a transformer is installed a substantial inrush of very short duration is to be anticipated e Effects of harmonic currents Page 19 of 41 Installation Guide for Power Drive Systems Most drive rectifiers generate harmonic currents back to the network these tend to increase the overall r m s current flowing between the drive and the supply Line reactors in the a c or d c link chokes will provide some harmonic mitigation and reduce the effective r m s current Typically the total r m s input current of a 3 phase 6 pulse drive at full load is very similar to the rated output current For single phase input drives this assumption cannot be made and the manufacturer s listed input current must be used for dimensioning Skin effect Another factor influencing the cable carrying capacity is skin effect which causes an increase in cable losses due to high frequency currents These relative losses increase with increasing conductor size Typically the cable de rating factor for a 6 pulse rectifier due to skin effect will vary from negligible levels
37. n the market or put into use The employer is then responsible for the safety of any work equipment machine apparatus tool or installation used at work throughout the life of the equipment The obligations of the employer are specified in the national regulations on the use of work equipment that implement the provisions of Directive 2009 104 EC Minimum safety and health requirements for the use of work equipment by workers at work 5 3 STANDARDS Firstly we consider Generic standards which apply generally except where specific product standards apply Generic standards which may be relevant include e 61000 6 parts 1 amp 2 Immunity e EN 61000 6 parts 3 amp 4 Emissions For variable speed drives however there is a product specific standard EN61800 3 Adjustable speed electrical power drive systems Part 3 EMC requirements and specific test methods The standard contains conformity assessment requirements as well as recommended engineering practice The requirements of the product specific standard supersede the requirements of the generic standards unless the PDS is built into another product e g a lift for which there is another specific product standard EN 61800 3 covers two environments e First environment where the point of coupling with domestic users of the public electricity supply is at low voltage or e Second environment where the point of coupling is above 1000V a c The sta
38. ndard also covers four categories of intended use e Category C1 PDS of rated voltage less than 1000V intended to be used in the First environment and therefore likely to be available to the general public e Category C2 PDS of rated voltage less than 1000V which is neither a plug in device nor a moveable device and when used in the first environment is intended to be installed and commissioned only by a professional e Category C3 PDS of rated voltage less than 1000V intended to be used in the Second environment and not intended to be used in the First environment e Category C4 PDS of rated voltage equal to or above 1000V or rated current more than 400 A or intended for use in complex systems in the Second environment Page 30 of 41 Installation Guide for Power Drive Systems This allows for differing levels of communication between supplier and vendor for standard and purpose built equipment The definition of actual use will predominantly affect the requirements for both emissions and immunity The overriding requirement is always to meet the essential protection requirements of the EMC directive Practically the specific requirements of a particular VSD installation may be established by considering the following points 1 The intended environment for the equipment use 2 The installation category 3 The risk of interference with low immunity equipment 4 The consequences of interference
39. ndustrial CISPR 11 environments G 1 Category C1 Not applicable Applicable Category C2 Applicable Not applicable G 2 i Category C3 2 Applicable Not applicable Category C4 Not applicable Not applicable Not applicable Table 1 Comparison of class and environment terminology in the EMC emissions standards 5 9 EARTH CONDUCTORS In general good EMC requires low impedance bonding between the different parts of the PDS The minimum size of the protective earthing conductor is given in BS 7671 The IET Wiring Regulations However due to the application of PWM waveforms to the stray capacitance of the motor cable the protective conductor current may be higher than 10 mA Therefore in cases where the phase conductor cross section is less than 10 mm the protective earthing conductor size should be increased to 10 mm or one of the other measures in BS 7671 section 543 7 should be applied Multi stranded cables and braids provide better high frequency conductance 5 10 PRACTICAL EXAMPLES OF EMC AND PRODUCT SELECTION e An0O 55kW PDS used for automatic garage door opening 9 Emission levels defined in CISPR 11 Page 32 of 41 Installation Guide for Power Drive Systems As this unit is intended to be used in a domestic environment connected to the public low voltage supply it is clearly in the first environment Category C1 In this case a class type filter to meet the generic residential emis
40. ngineering Recommendation G5 4 1 GAMBICA Guide to CE Marking and Technical Standardisation GAMBICA Guide to Variable Speed Drives and Functional Safety of Machinery GAMBICA REMA Guide to Application of the ATEX Directives to Power Drive Systems NEMA Application Guide for AC Adjustable Speed Drive Systems Page 41 of 41 GAMBICA REMA Technical Guide Copyright GAMBICA REMA 2012 AUTOMATION INSTRUMENTATION amp CONTROL LABORATORY TECHNOLOGY ROTATING ELECTRICAL MACHINES ASSOCIATION The GAMBICA Association Ltd Broadwall House 21 Broadwall SE1 SPE Tel 44 0 20 7642 8080 Fax 44 0 20 7642 8096 Email assoc gambica org uk www gambica org uk REMA A BEAMA Association Westminster Tower 3 Albert Embankment SE1 7SL Tel 44 0 20 7793 3006 Email jparsons beama org uk http www beama org uk en other associations rema1
41. nsible for the preparation of harmonised EN standards Commit International Sp cial des Perturbations Radio lectriques English International Special Committee on Radio Interference Prefix for standards prepared by this organisation Published by the IEC q v Control of Substances Hazardous to Health UK Statutory requirements See SI 2002 2677 etc Direct Current Ground Grounding Terms used interchangeably Earth Leakage Circuit Breaker Electromagnetic compatibility Electromagnetic Interference EuroNorm Standard issued by CENELEC normally prefixed by the national issuing body e g BS EN Standards for serial communications interfaces European Union Term for an electromagnetic screen UK requirements for harmonics International Electrotechnical Commission International Standardisation Body Prefix for standards prepared by this organisation SECTION 2 4 et seq Specifically excluded from this Guide 1 1 2 1 5 7 2 3 4 1 4 2 3 IEEE 519 MCC MCCB noise PDS PE PWM RCD RS 232 485 r m s RTD Screen Sl TN TN C TN S UL 12 pulse Page 38 of 41 Installation Guide for Power Drive Systems American Standard IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems Input Output connections Ungrounded network Miniature circuit breaker Motor Control Centre Moulded case circuit breaker Electromagn
42. o halve the maximum cable run approved by the drive manufacturer The editors invite further questions to be passed by e mail to assoc gambica org uk for inclusion in subsequent editions Page 40 of 41 Installation Guide for Power Drive Systems Section 7 REFERENCES AND ACKNOWLEDGEMENTS 1 2 3 4 5 6 7 8 8 9 10 11 12 13 14 5 60034 17 Cage induction motors when fed from converters Application guide 5 60034 25 Guidance for the design and performance of a c motors specifically designed for converter supply IEC 60034 30 Efficiency classes of single speed three phase cage induction motors IEC TS 60034 31Selection of energy efficient motors including variable speed applications IEC 61800 3 Adjustable speed electric power drive systems EMC requirements and specific test methods IEC 61800 5 1 Adjustable speed electrical power drive systems Part 5 1 Safety requirements Electrical thermal and energy IEC 61800 5 2 Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functional GAMBICA REMA Technical Report No 1 Motor Insulation Voltage Stresses under PWM Inverter Operation GAMBICA REMA Technical Report No 2 Motor Shaft Voltages and Bearing Currents under PWM Inverter Operation GAMBICA Technical Guide General Purpose Enclosures GAMBICA Technical Guide Managing Harmonics A guide to ENA E
43. o be effective the screen must have good electrical continuity along the cable length The braided or helical construction must be such that current can easily pass from turn to turn along the length The screen coverage must be as close as possible to 100 and the resistance must be low especially at high frequencies The following are less suitable for their screening capabilities e Galvanised steel spiral tape e Screwed steel conduit e Cables with thin foil screens e Cables with open woven braids 3 4 2 3 PROTECTIVE CONDUCTOR EARTH CONNECTION To meet the EMC and availability requirements only shielded multicore cables should be used Some exceptions to this rule are given in the product specific manuals Page 16 of 41 Installation Guide for Power Drive Systems To be effective at high frequency the shield conductance shall be at least 1 10 of the phase conductor conductance One way of evaluating the effectiveness of the shield is the shield inductance which must be low and only slightly dependent on the frequency These requirements are easily met with a copper or aluminium shield armour The cross section of a steel shield has to be ample and the shield helix of low gradient Galvanizing will increase the high frequency conductivity The question of whether the cable screen can be used as the protective earth conductor depends on the safety regulations being applied on its resistance relative to the phase conductors an
44. of 41 Installation Guide for Power Drive Systems Protection against drive or motor overload and against a short circuit at the output is provided in the drive The drive suppliers recommendations must be followed This is essential for the safety of the installation and to maintain the validity of safety markings such as the CE mark UL approval etc Most small drives can be protected by standard industrial power fuses such as the IEC 60269 gG range or by a corresponding MCB or MCCB For some designs it may be necessary to use special fast acting semiconductor fuses to prevent serious damage to the drive following an internal fault In this case it will generally not be possible to use a MCCB In all cases where MCBs or MCCBs are intended to be utilised the initial let through values should be checked as some MCBs have a relatively slow initial action while giving the desired let through characteristic Where high speed fuses are used to protect the PDS it is often possible to use lower RMS rating slow fuses to protect the cables feeding the PDS and as in all installations the overall discrimination needs careful assessment 3 9 HIGH POWERS CURRENTS When high powers are involved and it is not possible to obtain an adequately rated single three core cable or the physical installation of such a cable is too difficult the installation should be made in parallel three core cables not in single core cables This is to prevent circ
45. of the type of cable used It is usually possible to extend the limit by the use of output chokes or du dt filters at the drive terminals The use of output devices will result in a voltage drop which should be taken into account when selecting the motor Some types of cable have exceptionally high capacitance and in these cases reduced limits may apply The drive supplier should be consulted Some examples of cables with high capacitance are e Mineral insulated copper clad cable e Screened cable where the screen is laid directly on the phase cores with no intervening insulating jacket The maximum cable length will vary with the drive rating and whether input or output filtering is installed and will generally increase with increasing power As a general guide in the absence of special filtering considerations if the cable length exceeds 50m then the drive supplier should be consulted 3 4 2 2 CABLE SCREENING It is strongly recommended that the cable be screened This is essential in order to meet many of the relevant EMC standards and is recommended in any case to reduce the risk of interference to other equipment The screen will have to carry relatively high amplitude current pulses therefore its RF impedance and connection method at each end are critical Effective forms of screen are e Copper braid e Copper tape e Close wound galvanised steel wire armour e Aluminium tape armour e Steel braid e Solid copper cladding T
46. ondensation is cleared away before energising Other sources of potential problems are corrosive gaseous contaminants such as hydrogen sulphide which can even attack the alloys used for heat sinks The majority of commercially available drives are designed to operate when rigidly mounted and are not designed to withstand high and repeated levels of vibration Where high levels of mechanical vibration are likely to be encountered the use of vibration damping mounts should be considered 2 3 4 TRANSFORMERS Some higher power drives use isolating transformers or phase shifting transformers for 12 or more pulse rectifiers to reduce harmonic distortion or limit common mode voltage propagation There are two basic types of transformer liquid cooled and dry type All transformers have losses both standing and load related and must be installed in a situation where adequate cooling is available Contrary to the practice used for drives and motors the transformer rating is specified in IEC standards on the basis of a maximum 40 C being reached occasionally a monthly average of 30 C and a yearly average of 20 C They are not designed for continuous operation at sustained high ambient If this is required then the manufacturer needs to be consulted and a de rating must be applied 2 3 4 1 LIQUID COOLED TRANSFORMERS Liquid cooled transformers are generally designed for use outdoors It is also usual to provide containment to ensure
47. ood EMC performance especially to attenuate radiated emissions If screened cables are not practical in a particular installation the use of a sinusoidal output filter should be considered Page 31 of 41 Installation Guide for Power Drive Systems 5 8 FILTERS Conducted emissions filters are sometimes referred to as RFI filters or EMC filters These are always fitted to the supply side of a converter Many manufacturers will offer integrated or footprint designs which minimise the installation dimensions Typically filters are available to meet so called Class A and Class B limits The level of conducted emissions fed back into the supply will be dependent on the shielded motor cable lengths and the limits and B 9 will be met only with limited cable lengths as specified by the suppliers Suppliers have an obligation to identify suitable filters Basic emission test methods and levels are given in CISPR standards CISPR 11 also published as EN 55011 and CISPR 22 EN 55022 The generic and PDS standards are based on these but use different terminology for their specific purposes The following table shows how they correspond EN 61800 3 EN 55011 EN 61000 6 4 EN 61000 6 3 Product Product family Generic Generic Standard standard for emission emission industrial standard for standard for scientific and industrial residential medical ISM environments commercial and equipment light i
48. patibility limit Emission margin Emission limit Emission level EMITTER Independent variable Frequency Figure 12 Aspects of EMC Distribution Network Supply Network Conducted Emissions electromagnetic Immunity noise a ee Power Drive System Converter Emissions Immunity lt Radiated electromagnetic Motor noise Figure 13 EMC aspects of a power drive system Drive manufacturers take extensive design precautions which both minimise the emissions of electromagnetic disturbances and maximise the immunity to externally generated noise However irrespective of the rigorous design parameters implemented by manufacturers the integrity of the overall system is fundamentally dependent on the installation techniques adopted Immunity to external disturbances is achieved by the basic design in combination with high integrity high frequency earthing systems Protection from radiated emissions is dependent on containment within the system using an effective shielding system particularly in VSD output cables that carry the pwm waveform Over and above the filtration included in standard drives additional mitigation of the conducted noise may be specified using optional filtering Page 29 of 41 Installation Guide for Power Drive Systems 5 2 USE OF WORK EQUIPMENT DIRECTIVE 2009 104 EC The Machinery LVD and EMC Directives apply when the equipment is placed o
49. plicable in the end product or the intended place of use of the installation This must take account of the ambient temperature and the mounting arrangement for the cable in so far as it affects the cooling capability In the UK cables are normally rated in accordance with BS 7671 The IET Wiring Regulations and IEC 60287 However the specific manufacturer s rating tables should be applied as these take into account the specific cable construction The worst case method of installation must also be taken into account For example where a cable is installed for the most part on a tray in air it may also pass through a restricted transit In this case this transit must be considered as the installation method in order to avoid hot spots and thermal problems Page 18 of 41 Installation Guide for Power Drive Systems The following additional issues must be considered 3 5 1 SUPPLY AND MOTOR CABLES e Continuous r m s input supply and motor output current ratings of the drive Note that the short term overload rating of the drive is typically for too short a duration e g 1 min to affect the cable rating directly However it may have an indirect effect by determining the rating of the protective device e Voltage drop For long cable runs it may be necessary to increase the cable rating beyond the requirement for safety in order to restrict the cable voltage drop However the effect of voltage drop is much less severe with a VSD than
50. rrent generating devices are also present Care should also be taken to avoid a leading power factor Power factor correction equipment can provide a valuable means of attenuating low order 7 In addition group power factor correction batteries can lead to high switching transient voltages which must be limited by restricting the maximum reactive power switched in one stage to Qm Sn 2 5xZk Where Qm Maximum permissible capacitor reactive power kVAr Sn Rated power of supply transformer kVA Zk Short circuit impedance of supply transformer 3 15 CONTROL CONNECTIONS The control interfaces to a PDS are at least as important as the power connections 3 15 1 ANALOGUE SIGNALS Analogue and very low voltage digital I O signals should always be made in twisted pairs with the twist carried as close as possible to the appropriate terminals If possible avoid the use of acommon return for different analogue signals Double shielded cables will give the best performance 7 See Section 5 10 Page 23 of 41 Installation Guide for Power Drive Systems Figure 7 Double screened twisted pairs Unless otherwise stated in the installation instructions for the particular equipment the cable screen should be bonded at both ends The cable screen should be bonded at the screen termination points provided by the equipment manufacturer These should not be confused with the O Volt or Signal
51. safety requirements he alone is in a position to do so 2 GAMBICA Technical Guide Variable Speed Drives and Functional Safety of Machinery 3 GAMBICA Technical Guide CE Marking and Technical Standardisation Guidelines for application to Electrical Power Drive Systems Page 6 of 41 Installation Guide for Power Drive Systems The principle is to ensure that the risk associated with the system is acceptable by undertaking risk analysis on the machine to identify potential hazards throughout its life cycle and where necessary to minimise them The basic standards require that the PDS must be capable of being isolated whilst other hazards may require emergency stopping of the drive system either by freewheeling to a stop on removal of power or by active braking The location and type of any safety related requirements such as emergency stopping must be defined at the outset of the project In addition to these purely mechanical considerations for safety the electrical safety of the system must also be considered See Section 3 2 3 ENVIRONMENT The location of the parts of the power drive system must be considered including Altitude e Ambient Temperature e Humidity e Possibility of condensation e Ventilation e Access e Vibration e Airborne contamination e Noise e Electrical Power Quality 2 3 1 MOTOR Induction motors are very widely used around the world as prime movers in industrial domestic and buildin
52. sion requirements would be included e A1000kW PDS in a Steel Rolling Mill A steel mill would invariably take its incoming power supply at high voltage and have local dedicated HV LV transformers to obtain the site low voltage supply The mill is a complex installation in the second environment and the PDS would be supplied according to a specific contract In this case there are likely to be many other electrical amp electronic loads and the equipment used would be intended for such environments e g would have a high immunity This is clearly a second environment Category C4 installation By considering the effects of the new equipment on the installation a site specific EMC plan would be developed Typically this would conclude that no additional conducted EMC filtering is required and standard unfiltered drives may be selected possibly with earthed screen between the dedicated transformer windings e One booster pump drive in a water pipeline A small pumping station may well be supplied from an HV LV transformer which also feeds residential properties in the vicinity This is therefore a Category C2 first environment PDS supplied only to professional installers Considering these criteria a VSD with filtering at least to class A would be recommended e Sixty Drives in a Supermarket for HVAC Duties Typically the building would contain integral HV LV transformers and may therefore be considered Ca
53. t low speed and is therefore unreliable An embedded thermal device is always one method of obtaining protection thermostats PTC thermistors or RTD devices may all be used with an appropriate external relay Some drives will also integrate thermistor monitoring Page 39 of 41 Installation Guide for Power Drive Systems As the inverter controls the speed and monitors the motor current it can also provide motor protection based on the load and speed and compensate for reduced loadability at reduced speed Some more sophisticated drives offer both over and under load protection which allows monitoring of coupling failure or possibly low flow Q What limits a motor maximum speed motor is not limited to its mains supply frequency synchronous speed it can be both reduced and increased Beyond base speed the torque available will drop as the inverter cannot increase its output voltage and the motor becomes progressively under fluxed This is known as field weakening There is a specific maximum output speed for any motor based on two factors e The mechanical maximum speed these are normally limited by the bearings and peripheral velocities and values are obtainable from the manufacturer e The electrical maximum speed which is due to the reduction in flux causing the available maximum torque to reduce as the square of the increase in frequency For larger 2 pole motors it is common to design with a flexible shaft
54. tegory C3 second environment However an EMC plan may determine that within the building there will be numerous items of electronic apparatus such as computers Point of Sale equipment environmental monitoring instruments etc connected to the same LV supply Considering the criteria VSDs with filtering at least to class A would typically be recommended e Sixty Drives To Be Installed In a Hospital For HVAC Duties Again the building would normally be supplied via a local HV LV transformer and might therefore be considered as a Category C3 second environment However there are obviously considerable quantities of potentially susceptible medical apparatus with the severe consequences of failure Therefore a cautious approach should be implemented and VSDs with class B filtering would be recommended As some supplies in a hospital environment will be IT care must be taken to ensure that the filtered drives are connected to a TN network The majority of RF Filters do not function in IT networks Page 33 of 41 Installation Guide for Power Drive Systems Notes In each of the above examples the correct installation techniques remain a fundamental pre requisite For each installation the specific local conditions should be assessed within an EMC plan In each case the essential protection requirements of the EMC directive must be observed 5 11 HARMONICS Harmonic emissions are an aspect of EM
55. tem to radiate noise it is essential that all the parts share a common potential Because of the high frequencies involved this means that the conductors connecting them must have very low inductances For this reason the conductors required from the safety point of view are often inadequate Sizing of earth and PE conductors is discussed in the EMC issues It is also important that both the motor and driven machine share a common earth potential and that the drive and its controls share a common potential 4 1 SUPPLY CONNECTIONS 4 1 1 EARTHED SECONDARY TN C 5 In these network connections the neutral is earthed at the point of supply normal drives with EMC conducted emissions filters can be used A TN C network uses a common earth and neutral conductor which is not recommended a TN S system should always be utilised to ensure a single earth neutral bond 4 1 2 UNEARTHED SECONDARY IT These networks are commonly found in hospitals in certain crude oil pumping installations and in the secondary connections of 12 pulse drives An isolation transformer or other separately derived source normally supplies the unearthed system A particular feature of this system is the absence of a direct connection between the phase and neutral if present conductors and earth As a result the fault current is relatively low in the event of an insulation fault In fact its magnitude is primarily limited by the system leakage capacitance As m
56. the inlet and outlet apertures are clear Motor bearings also require occasional replacement typically after 20 000 to 35 000 operating hours and the suitability of the site for removal and refitting the motor should be considered Any motors that are mounted vertically must be protected from rain snow and falling objects entering the fan housing 6 60726 Page 11 of 41 Installation Guide for Power Drive Systems 2 5 2 CONVERTER With the exception of some motor mounted converters sometimes referred to as integral motors the converter is designed for indoor installation The preferred solution is always to mount drives in custom plant or control rooms both for safety by restricting access and to ensure an optimum operational regime Drive losses have to be dissipated This is generally to the ambient air in the control room therefore the largest possible room volume is helpful The majority of converters are fitted with cooling fans to circulate cooling air across the heat sinks Any restriction to this air path reduces the efficiency of the cooling system Smaller power drives associated with specific items of plant or machines installed indoors may be mounted locally to the machine provided that adequate protection is possible Enclosure ingress protection should be selected as the minimum level commensurate with safety Filtering cooling air involves maintenance and in time the filter mats are often discarded
57. to clear the arc and the inverter switching should be inhibited before allowing the contacts to open It is always good practice to inhibit the inverter before output switching 3 13 CABLE GLANDING Whenever screened cables are used it is essential that they are properly glanded and terminated that the screen armour makes contact through 360 to the gland and also that the gland is circumferentially grounded to the gland plate and to the main earth terminations tails Should be as short As possible Cable armour Each strand must be Effectively grounded within the Cable gland Cable Gland General view SWA Cable Cable Gland Typical section Figure 6 Typical Cable and Gland Page 22 of 41 Installation Guide for Power Drive Systems 3 14 POWER FACTOR CORRECTION With a frequency converter power factor correction capacitors must never be installed in the motor circuit The inverter will always provide the reactive power Voltage source PWM type frequency converters have an inherently high fundamental network power factor due to the uncontrolled or active rectifier design and in general do not require power factor correction Where power factor correction is required for other equipment connected to the same bus care must be taken to avoid harmonics from the drives or other loads such as active filters damaging the capacitors and de tuning reactors should always be used in circuits where harmonic cu
58. ulating currents in the screens of single core cables as the screen must be terminated at both ends DC bus Figure 5 High Current Installation Page 21 of 41 Installation Guide for Power Drive Systems 3 10 CABLE CONNECTION POINT Even when a drive is mounted in a secondary enclosure the cable connecting points on the drive module should preferably be used and intermediate connections avoided 3 11 LOCAL TO MOTOR ISOLATION Where local to motor isolation is required for safety purposes it is essential that the switch enclosure should be conductive and form part of the Faraday Cage surrounding the entire PDS This means that the cable screens should be correctly bonded glanded to the enclosure In many cases the converter manufacturer will make recommendations regarding switching off the inverter prior to opening of the switch contacts 3 12 OUTPUT CIRCUIT SWITCHING The majority of PWM drives use a conventional control and it is generally possible to include a switch in the output of the inverter without causing damage Some converters use more sophisticated predictive control these include flux vector and Direct Torque Control DTC designs where the drive has an integrated software motor model and it is possible that opening the output circuit can cause the drive to attempt to force a higher voltage at its output to maintain the motor current In these circumstances it becomes difficult for the switch
59. up to 35 mm 1 with 50 mm increasing to 4 with 300 mm These figures may be very small but do indicate that cable sizing should not be skimped Some further guidance on cable de rating for harmonics is given IEEE519 and IEC 60092 352 Cables for Marine Installations while there are currently no European standards for industrial applications 3 7 MOTOR CABLE Co ordination with the protection provision The drive provides fast acting short circuit and earth fault protection which protects the motor cable and drive Overload protection of the motor is also provided usually within the drive but possibly by a separate device where multiple motors are connected to a single drive Provided this protection has been correctly arranged the cable rating needs only to match the motor continuous rating Effects of harmonic currents The inverter produces a series of voltage pulses in the output and this results in a virtually sinusoidal output current There is therefore no need for any special consideration Other factors Other factors detailed for input cables also need to be taken into account when selecting motor cables 3 8 CIRCUIT PROTECTION Most drive modules require circuit protective devices fuses or circuit breakers at the supply input Their purpose is to provide protection from a catastrophic failure within the drive which causes a fault between lines or to earth or rarely a sustained overload Page 20
60. upted by screw terminals 3 15 5 SEGREGATION Motor cable gt 300 mm gt 500 Right angle Mains Cable gt 200 mm ad Signal control cables 0 3 Figure 10 Recommended Segregation between cables Page 25 of 41 Installation Guide for Power Drive Systems Many installers are reluctant to bond a cable screen at both ends due to a fear of circulating currents Drive manufacturers are well aware of this but have tested their products to meet the most stringent operating conditions They include instructions for appropriate mitigation measures such as potential equalisation conductors in parallel with the screened cables The screen termination may only be omitted at one end if the signal at that end is galvanically isolated and the manufacturer of the equipment specifically approves of this style of connection Section 4 EARTHING Primarily the purpose of earthing is personnel safety Irrespective of any other instructions all the conducting parts of the PDS frames must be earthed ensuring that a safe touch voltage is not exceeded The requirements of BS 7671 The IET Wiring Regulations must always take precedence For electromagnetic compatibility it is also necessary to ensure that equipotential bonding is effective over a wide range of frequencies 8 Further information on Earth Bonding and Electronics is also contained in EN 60204 1 In order to limit the potential for a sys
61. ures are available to cope with the range of environments to be encountered The correct level of ingress protection should be selected by reference to the appropriate standards Special attention should be paid to areas with particularly high gt 40 C and low lt 10 C ambient temperatures when special consideration may be required to ensure adequate cooling lubrication etc Attention should also be paid to installations where considerable levels of water spray are present such as in cooling towers to prevent ingress through the bearing seals In all these cases the motor manufacturer should be consulted to enable a suitable solution to be selected 2 3 2 MOTOR INSTALLATION 2 3 2 1 COUPLING The transmission of power from the motor shaft to the driven equipment is achieved in a number of ways broadly classed as solid and flexible Solid couplings lock the two shafts together allowing no relative motion between them some axial adjustment is possible at assembly They are used when accuracy and fidelity of torque transmission are of paramount importance for instance when the phase relationship between driver and driven equipment must be accurately maintained Flexible couplings depending on their individual design can absorb a degree of axial angular parallel and torsional misalignment between the shafts It is nevertheless important that during setting up of alignment the manufacturer s instructions are strictly followed
Download Pdf Manuals
Related Search
Related Contents
Electrolux WT830EM User's Manual MD20D Nov 12 07 Samsung DCB-H360 User Manual Bedienungshinweise - Askari jagd-shop LS-3000 1 - Sulky Burel Lotus Domino for AS/400 R5 Implementation 194 05 00 Rev2 Folheto de Instruções Secador Super Liss Kenroy Home 32175CH Instructions / Assembly User Manual Copyright © All rights reserved.