1. 20 50V continuous reinforced insulation type I O to DeviceNet network 1 0 to power and power to DeviceNet network Tested at 750V DC for 60s Publication 1732DS INOO1D EN P September 2009 20 ArmorBlock Guard I O DeviceNet Safety Modules General Specifications 1732DS IB8XOBV4 1732DS IB8 Attribute 1732DS IB8XOBVA 1732DS IB8 Product temperature versus current derating BA 7A 6A 20 C 40 C 50 C 60 C 1 44199 Product Temperature Versus Current Derating combined current from both input and output supplies 1 on signal ports Wiring category 1 on power ports 2 on communication ports Weight approx 640 g 1 41 Ib Dimensions HxWxD 69 x 179 x 70 mm 2 7 x 7 0 x 2 8 in approx 0 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Publication 1732DS IN001D EN P September 2009 ArmorBlock Guard I O DeviceNet Safetv Modules 21 Environmental Specifications 1732DS IB8XOBV4 1732DS IB8 Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1732DS IB8XOBVA 1732DS IB8 20 60 C 4 140 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat 45 85 C l
2. feedback purposes use devices with contacts capable of switching micro loads of 24V DC 5 mA Bulletin 700S 100S Other devices Evaluate whether devices used are appropriate to satisfy requirements of safety category levels None Publication 1732DS IN001D EN P September 2009 10 ArmorBlock Guard I O DeviceNet Safety Modules Install the Module Read this section for installation related information Set MAC ID Set the MAC ID by using the rotary switches The MAC ID is set to 63 by default Wiring the Module Follow these guidelines when wiring the module e Do not share communication input ot output lines with high voltage referring to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 e Wire correctly after confirming the signal names of all terminals e Follow wiring and installation guidelines for DeviceNet networks and be sure that you e do not exceed a drop length of 5 7 m 19 ft e note that the total drop length budget for the network is reduced by 0 30 m 1 ft for each 1732DS module Publication 1732DS IN001D EN P September 2009 ArmorBlock Guard I O DeviceNet Safety Modules 11 Working with 1 0 Connectors See the figure that shows connectors The modules have M12 female I O connectors Input and Output Configuration Input Configuration Output Configuration B 1732DS IBBXOBVA Pin Signal Q lid 1 m
3. 49 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp 5 95 noncondensing IEC 60068 2 27 Test Ea Unpackaged Shock Heat Vibration 5g 10 500 Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g Emissions Group 1 Class A CISPR 11 ESD immunity 6 kV contact discharge IEC 61000 4 2 8 kV air discharge Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM at 900 MHz 10V m with 200 Hz 50 Pulse 100 AM at 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz Publication 1732DS IN001D EN P September 2009 22 ArmorBlock Guard I O DeviceNet Safety Modules Environmental Specifications 1732DS IB8XOBV4 1732DS IB8 Attribute Conducted RF immunity 1732DS IB8XOBVA 1732DS IB8 10V rms with 1 kHz sine wave 8096 AM from IEC 61000 4 6 150 kHz 80 MHz EFT B immunitv 4 kV at 5 kHz on power ports IEC 61000 4 4 3 kV at 5 kHz on signal ports 2 kV at 5 kHz on communication ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 1 kV line line DM and 2 kV line earth CM on signal ports 2 kV line earth CM on communication ports Reaction Time Input reaction time max 16 2 ms set values of ON OFF delays Outp
4. Description Recommended Action Off Safety input The safety input is off or the Turn the safety input on or off or module module is being configured wait for the module to be being configured configured Solid Safety input The safety input is on None yellow on Solid red Fault detected A fault in the external wiring Check configuration field or input circuit detected wiring and devices If no problem found replace module Flashing Partner fault A fault in the partner input Check the field wiring and red detected circuit of a dual input verify your configuration for configuration detected Publication 1732DS IN001D EN P September 2009 the partner circuit If no problem found replace module ArmorBlock Guard I O DeviceNet Safety Modules 17 Safety Output Status Indicator 1732DS IB8XOBV4 module only State Status Description Recommended Action Off Safety output The safety output is off Turn the safety output on or wait off or module or the module is being for the module to be configured being configured configured Solid Safety output The safety output is on None yellow on Solid red Fault detected A fault in the output Check the circuit wiring and end circuit was detected device If no problem found replace module Both tags in a dual Make sure logic is driving tag channel circuit do not values to the same state off or have the same value on Flashing Partner fau
5. compliant with the following safetv extra low voltage SELV or protected extra low voltage PELV Publication 1732DS IN001D EN P September 2009 ArmorBlock Guard I O DeviceNet Safetv Modules 5 Before Vou Begin Before installing and operating the product read these installation instructions to learn important installation related information and the precautions to follow as you install and operate the product Keep these instructions for future reference Concerning suitability for use note that we are not responsible for conformity with any standards codes or regulations that apply to the combination of the products in your application or use of the product Take all necessary steps to determine the suitability of the product for the systems machines and equipment with which it will be used Know and observe all prohibitions of use applicable to this product Never use the products for an application involving serious risk to life or property without first verifying that the system as a whole has been designed to address the risks and that the Rockwell Automation product is properly rated and installed for the intended use within the overall equipment or system Module Identification and Dimensions See the table for identification information and figures for module dimensions Module Identification Cat No Name Safety Test Safety Outputs Inputs Outputs 1732DS IB8 Safetv input module 8 8 173
6. in which the module is incorporated noting that incorrect wiring can lead to loss of safety function Do not apply DC voltages exceeding rated voltages to the module Apply properly specified voltages to the module inputs Note that applying inappropriate voltages causes the module to fail to perform its specified function which leads to loss of safety functions or damage to the module Do not use test outputs as any safety output Test outputs are not safety outputs Be sure that qualified personnel confirm installation and conduct test operations and maintenance after installation of the module Be sure that personnel familiar with machinery where the module is to be installed should conduct and verify installation Do not dismantle repair or modify the module This can lead to loss of its safety function Publication 1732DS INOO1D EN P September 2009 8 ArmorBlock Guard I O DeviceNet Safety Modules e Use only appropriate components or devices complying with relevant safety standards corresponding to the required level of safety categories safety integrity level Conformity to requirements of safety category safety integrity level is determined as an entire system We recommend you consult a certification body regarding assessment of conformity to required safety level e You are responsible for compliance with applicable standards for the entire system e Disconnect the module from the power supply when wiring Saf
7. 2DS IBBXOBVA Safety 1 0 module with 8 8 4 bipolar pairs solid state outputs Each test output can be set to function as a pulse test output or a standard output pulse Test outputs are used in combination with a safety input Broken wires in an external indicator can be detected for terminal T3 and T7 only Publication 1732DS INOO1D EN P September 2009 6 ArmorBlock Guard I O DeviceNet Safety Modules 1732DS IB8XOBVA Module Dimensions 68 7 mm 168 6 mm 6 64 in 2 71 in 70 mm 2 76 in 1732DS IB8 Module Dimensions 68 7 mm 168 6 mm 6 64 in gt 2 71 in 70 mm 2 76 in 179 mm 7 05 in 31627 Publication 1732DS INO01D EN P September 2009 ArmorBlock Guard I O DeviceNet Safety Modules 7 Observing Precautions for Correct Use Read this for information related to operating directions after reading the Guard I O DeviceNet Safety User Manual publication 1791DS UMO001 Do not use the unit in locations subject to the following Direct sunlight Temperatures or humidity beyond the ranges noted in the Specifications section Corrosive or flammable gases Shock or vibration beyond the range noted in the Specifications section Observing Precautions for Safe Use Read this list of precautions for safe use Wire conductors correctly and verify operation of the module before commissioning the system
8. Installation Instructions ArmorBlock Guard I 0 DeviceNet Safety Modules Catalog Numbers 1732DS IBBXOBVA 1732DS IB8 Topic Page Important User Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 4 Before You Begin 5 Module Identification and Dimensions 5 Observing Precautions for Correct Use 7 Observing Precautions for Safe Use 7 Install the Module 10 Set MAC ID 0 Wiring the Module 0 Working with I O Connectors 11 Terminal Positions 12 Interpret the Status Indicators 4 Specifications 8 Additional Resources 23 ALLEN BRA DLEY Rockwell e ROCKWELL SOFTWARE Automation 2 ArmorBlock Guard I O DeviceNet Safety Modules Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls Publication SGI 1 1 available from your local Rockwell Automation sales office or online at http www rockwellautomation com literature describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable n no event will Rockwell Aut
9. at which fault indication is generated when used as a muted lamp output Safety Output 1732DS IB8XOBV4 module only Output types Current sourcing current sinking bipolar pair Output current rating 2 A max per point 8 A total module 40 C 104 F 6 A total module 60 C 140 F On state voltage drop 0 6V Leakage current 1 0 mA Publication 1732DS IN001D EN P September 2009 ArmorBlock Guard I O DeviceNet Safety Modules 19 Technical Specifications 1732DS IB8XOBV4 1732DS IB8 Attribute 1732DS IB8XOBVA 1732DS IB8 Internal resistance from P to M terminal 3 25 KQ Short circuit detection Yes short high and low and cross circuit fault detect Short circuit protection Electronic Aggregate current of 8 A 40 C 104 F outputs per module 6 A 60 C 140 F Pilot duty rating DC 14 Pilot Duty 1732DS IB8XOBV4 module only Number of outputs 1 4 dual channel Includes the presence of a single P stuck high or M stuck low short General Specifications 1732DS IB8XOBV4 1732DS IB8 Attribute Meets IP64 65 66 67 69K when product is marked Enclosure type rating 1732DS IB8XOBVA 1732DS IB8 Communication power supplv voltage 11 25V DC supplied from communication power supply Communication current consumption 85 mA at 24V DC Operating voltage range Isolation voltage 19 2 28 8V DC 24V DC 20
10. e a drive or motor to alert AN people that dangerous voltage may be present BURN HAZARD Labels may be on or inside the equipment for example a drive or motor to alert AN people that surfaces may reach dangerous temperatures Publication 1732DS IN001D EN P September 2009 ArmorBlock Guard I O DeviceNet Safety Modules 3 Environment and Enclosure This equipment is intended for use in overvoltage Category ll applications as defined in IEC 60664 1 at altitudes up to 2000 m 6562 ft without derating This equipment is considered Group 1 Class A industrial equipment according to IEC CISPR Publication 11 Without appropriate precautions there may be potential difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances This equipment is supplied as enclosed equipment It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings beyond what this product provides that are required to comply with certain product safety certifications In addition to this publication see e Industrial Automation Wiring and Grounding Guidelines for additional installation requirements publication 1770 4 1 explanations of the d
11. egrees of protection provided by different e NEMA Standards 250 and IEC 60529 as applicable for types of enclosure Publication 1732DS INOO1D EN P September 2009 4 ArmorBlock Guard I O DeviceNet Safety Modules Preventing Electrostatic Discharge ATTENTION A This equipment is sensitive to electrostatic discharge which can cause internal damage and affect normal operation Follow these guidelines when you handle this equipment Touch a grounded object to discharge potential static Wear an approved grounding wriststrap Do not touch connectors or pins on component boards Do not touch circuit components inside the equipment Use a static safe workstation if available Store the equipment in appropriate static safe packaging when not in use ATTENTION A Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type equirements Personnel responsible for the application of safety related Programmable Electronic Systems PES shall be aware of the safety requirements in the application of the system and shall be trained in using the system If the devices sensors connected to the input connections require Class 2 power to operate the auxiliarv power connections of this equipment must be powered bv a Class 2 source To comply with the CE low voltage directive LVD this equipment and all connected I O must be powered from a source
12. ety state of the module and its data is defined as off state A Serious injury can occur due to breakdown of safety outputs Do not connect loads beyond the rated value of the safety outputs Serious injury can occur due to loss of required safety functions Wire the module properly so that supply voltages or voltages for loads do not touch the safety outputs accidentally or unintentionally As serious injury can occur due to loss of safety functions use appropriate devices as shown in the Controlling Devices Sample Requirements table Publication 1732DS INO01D EN P September 2009 ArmorBlock Guard I O DeviceNet Safety Modules 9 Controlling Devices Sample Requirements Device Requirement Allen Bradley Bulletin Safety Components Emergency Use approved devices with direct opening Bulletin 800F 800T stop switch mechanism complying with IEC EN 60947 5 1 Door Use approved devices with direct opening Bulletin 440K 440G or interlocking mechanism complying with IEC EN 440H for interlock switch switch 60947 5 1 and capable of switching Bulletin 440P or 802T for limit switch microloads of 24V DC 5 mA limit switch Safety sensor Use approved devices complying with the relevant product standards regulations and rules in the country where used Any Allen Bradley Guardmaster product Relay with forcibly guided contacts Use approved devices with forcibly guided contacts complying with EN 50205 For
13. evisions Additional Resources For safe and correct use of the product read these publications e DeviceNet Modules in Logix5000 Control Systems User Manual publication DNET UM004 e Guard I O DeviceNet Safety Modules User Manual publication 1791DS UM001 You can view or download publications at http literature rockwellautomation com To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative Publication 1732DS INOO1D EN P September 2009 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www tockwellautomation com support you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect support programs For more information contact your local distributor or Rockwell Automation representative or visit http www tockwellautomation com support Installation Assistance If you experience a problem within the first 24 hours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting yo
14. g Device in self test The module is performing its ed and power cycle diagnostic tests green U For recommended action refer to the user manual that covers these modules Network Status Indicator State Status Description Off Module not online orno The module is not online with the network power Flashing Module online with no The module identified the communication rate of green connections in the network but no connections are established established state Solid Module online with The module is operating normally green connections in established state Publication 1732DS INOO1D EN P September 2009 16 ArmorBlock Guard I O DeviceNet Safety Modules Network Status Indicator State Status Description Flashing One or more I O The module detected a recoverable network fault red connections in or user initiated firmware update is in progress timed out state or user initiated firmware update in progress Solid red Critical link failure The module detected an error that prevents it from communicating on the network Flashing Communication faulted The module detected a network access error and is redand module in communication faulted state The module green received and accepted an Identity Communication Faulted Request long protocol message 1 For recommended action refer to the user manual that covers these modules Safety Input Status Indicator State Status
15. l Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1732DS IN001D EN P September 2009 PN 46668 Supersedes Publication 1732DS IN001C EN P April 2009 Copyright 2009 Rockwell Automation Inc All rights reserved Printed in the U S A
16. lt A fault in the partner of Check the circuit wiring and end red detected a dual output circuit device of the partner If no was detected Configuration Lock Indicator problem found replace module State Status Description Recommended Action off No configuration nvalid configuration data None Solid Locked Valid configuration locked None yellow by a network configuration ool such as RSNetWorx or DeviceNet software Flashing Not locked Valid configuration owned None yellow by a network configuration ool such as RSNetWorx or DeviceNet software Not applicable if owned by a GuardLogix controller Publication 1732DS INOO1D EN P September 2009 18 ArmorBlock Guard I O DeviceNet Safety Modules Specifications Technical Specifications 1732DS IB8XOBV4 1732DS IB8 Attribute 1732DS IB8XOBVA 1732DS IB8 Safetv Input Input tvpe Current sinking Voltage on state input min 11V DC Current on state input min 3 3 mA Voltage off state input max 5V DC Current off state max 1 3mA IEC 61131 2 input type Type 3 Pulse Test Output Output type Current sourcing Pulse test output current 07A Residual voltage max 1 2V Output leakage current max 0 1 mA Short circuit protection Yes Current max 25 mA Current max to avoid fault when used as a muted lamp output Current min 5 mA Current min
17. odule oniv 1 Test Output n 1 X o Pin Signal 2 Safe Input n 1 744042 1 Output 24V DC Power 3 Input Common 7 Output n 1 4 Safe Input n Sinking Switch 24V DC Common 5 Test Output n 3 Output Power Common 4 Output n Sourcing Switch 24V DC 5 Output Power Common Publication 1732DS INOO1D EN P September 2009 12 ArmorBlock Guard I O DeviceNet Safety Modules The modules have mini sealed DeviceNet In male and DeviceNet Out female connectors for daisy chaining and a mini sealed Power Output male connector DeviceNet and Power Configuration Male Male l l ZE DeviceNet Male and Power Configuration Female Configuration Pin Signal Pin Signal AT e a 44040 O 44044 1 Output 24V DC Power 1 Drain femal 4 2 Input 424V DC Power emale 2 V4 EE 3 Input Power Common 3 V 4 Output Power Common 4 CAN H j ie 5 CANL 1732DS IBBXOBVA module only Terminal Positions See the figure and table that show terminal positions A B c D 44121 Publication 1732DS IN001D EN P September 2009 ArmorBlock Guard I O DeviceNet Safety Modules 13 Terminal Positions 1732DS IB8XOBV4 and 1732DS IB8XOBV4 Module Only 1732DS IB8 Modules A 1 Test Output E1 Jsa zav DC A 2 Safety Input 1 E 2 Safety Output 11 Switch 24V DC Comm
18. omation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment he examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations WARNING Identifies information about practices or circumstances that can cause an explosion in N a hazardous environment which may lead to personal injury or death property damage or economic loss MPE identifies information that is critical for successful application and understanding of the product ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequences SHOCK HAZARD Me l i Labels may be on or inside the equipment for exampl
19. on A 3 InputCommon JE 3 JL 24V DC Common A 4 Safety InputO E 4 Safety Output 02 Switch 24V DC A 5 Test Output 0 E 5 L 24V DC Common B 1 Test Output3 F 1 sy av DC B 2 Safety Input3 JF 2 Safety Output 312 Switch 24V DC Common B 3 Input Common F 3 L 24V DC Common B 4 Safety Input2 F 4 Safety Output 22 Switch 24V DC B 5 Test Output 2 F 5 L 24V DC Common C 1 Test Outputs G 1 f54 24v DC C 2 Safety Input5 6 2 Safety Output 5 Switch 24V DC Common C 3 Input Common G 3 L 24V DC Common C 4 Safety Input 4 G 4 Safety Output 412 Switch 24V DC C 5 Test Output 4 G 5 L 24V DC Common D 1 Test Output H 1 J syaav DC D 2 Safety Input 7 H 2 Safety Output 7 2 Switch 24V DC Common D 3 Input Common JH 3 JL 24V DC Common D 4 Safety Input6 H 4 Safety Output 62 Switch 24V DC D 5 Test Output 6 H 5 L 24V DC Common 1 2 3 S denotes output return 24V DC Safety outputs can be used only as pairs Safety outputs 0 1 2 3 4 5 and 6 7 must be controlled as a pair L denotes output return common Publication 1732DS INOO1D EN P September 2009 14 ArmorBlock Guard I O DeviceNet Safety Modules Interpret the Status Indicators See the tables for information about how to interpret status indicators 24V DC Input Power Indicator State Status Description Recommended Action Off No power No power is applied A
20. pply power to this section Solid Normal The applied voltage is None green operation within specifications Solid Input power The input power is out of Check your configuration yellow out of specification wiring and voltages and apply specification the changes 24V DC Output Power Indicator 1732DS IB8XOBV4 module only State Status Description Recommended Action Off No power No power is applied Apply power to this section Solid Normal The applied voltage is None green operation within specifications Solid Output power The output power is out Check your configuration yellow out of of specification wiring and voltages and specification apply the changes Module Status Indicator State Status Description Off No power or autobauding No power is applied to the DeviceNet connector Solid Normal operation The module is operating normally green Solid red Unrecoverable fault The module detected an unrecoverable fault Publication 1732DS IN001D EN P September 2009 ArmorBlock Guard I O DeviceNet Safety Modules 15 Module Status Indicatoril State Status Description Flashing odule needs commissioning due to Module is unconfigured green missing incomplete or incorrect configuration Flashing Recoverable fault or user initiated The module has detected a ed irmware update in progress recoverable fault or user initiated firmware update is in progress Flashin
21. ur product up and running United States 1 440 646 3434 Monday Friday 8 a m 5 p m EST Outside United States Please contact your local Rockwell Automation representative for any technical support issues New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Allen Bradley ArmorBlock Guard I O GuardLogix GuardMaster Logix5000 Rockwell Automation TechConnect Rockwell Software and RSNetWorx for DeviceNet are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation Vorstlaan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwel
22. ut reaction time max 6 2 ms 20 ms relay response time 1732DS IBBXOBVA module Signal Sequence Typ 600 ms y Typ 700 ps 44072 While safetv outputs are in an on state the signal sequence shown in the figure is output continuously for fault diagnosis when output pulse testing is enabled Confirm response time of device connected to safety outputs so the device does not malfunction due to off pulse Publication 1732DS IN001D EN P September 2009 ArmorBlock Guard I O DeviceNet Safety Modules 23 Certifications 1732DS IBBXOBVA 1732DS IB8 Certification when 1732DS IB8XOBVA 1732DS IB8 product is marked c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E65584 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions ODVA ODVA conformance tested to DeviceNet specifications TUV TUV Certified for Functional Safetv up to and including Categorv 4 and SIL 3 2 See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details 2 When used with specified firmware r