MV/LV substations remote monitoring DNP 3.0 Communication

image

Contents

1. Description Index Default Static Default Event Variation Point Name hex dec Variation Obj Var Desc Obj Var Class Desc Analog Input 0 0 30 2 16 Bit 32 4 1 16 Bit Phase current I1 With Time Analog Input 1 1 30 2 16 Bit 32 4 1 16 Bit Phase current I2 With Time Analog Input 2 2 30 2 16 Bit 32 4 1 16 Bit Phase current 3 With Time Analog Input 3 3 30 2 16 Bit 32 4 1 16 Bit Homopolar current IO With Time Analog Input 4 4 30 2 16 Bit 32 4 1 16 Average current Imean With Time Analog Input 5 5 30 2 16 Bit Power factory Analog Input 6 6 30 2 16 Bit Frequency Description Index Default Static Default Event Variation Point Name hex dec Variation Obj Var Desc Obj Var Class Desc Analog Input 7 7 30 1 32 Bit Voltage phase 1 Analog Input 8 8 30 32 Active power Analog Input 9 9 30 32 Reactive power Analog Input A 10 30 32 Bit Apparent power Description Index Default Static Default Event Variation Point Name hex dec Variation Obj Var Desc Obj Var Class Desc Binary counter 0 0 20 1 32 Bit Energy Description Index WRITE READ Point Name hex dec Obj Var Desc Obj Var Class Desc Analog Output 0 0 41 132 40 1 1 32 Bit Cyclic dial up period Without Time Analog Output 1 1 41 32 Bit 40 1 1 32 Bit Energy preset value Without Time Analog Output 2 2 41 1 32 bit 40 1 1 32 Bit F200C IP address Without GPRS ve
2. F200C DNP 3 0 Communication Analog output 5 to 11 Parameter of measurements range Power off threshold e Poweron threshold Imax threshold 8 10 threshold 9 Reset fault time Imax fault ack time 10 fault ack time Analog output 12 and 13 F200C and SCADA ports for GPRS only F200C port local port on which F200C is listening to incoming connections only if local parameter listen mode is lt ON gt SCADA port remote port on which the SCADA is listening to incoming connections from F200C Possible values 1 to 65535 Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Special considerations Internal INdications Control center time synchronization Bit 4 of first IIN byte is set when F200C starts up This bit is cleared when the SCADA sends its first clock synchronization message Then F200C sets it again regularly every hour to ensure the SCADA is answering it on a regular basis This clock synchronization is required to ensure a proper accuracy of time stamping process Should F200C not receive a new synchronization message from the master within an hour after the last one the bit is set Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc 22 Schneider Electric SA 64 70 avenue Jean Baptiste Cl ment F 92646 Boulogne Billancourt Cedex Tel 33 0 1 46 99 70 00 NT00138EN
3. Addition to Highest DNP Levels Supported 7 RESPONSE TO THIS REQUEST IS OBJECT UNKNOWN Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Description Index Default Static Variation Default Event Variation Point Name hex dec Obj Var Desc Obj Var Class Desc Control Relay 0 0 12 1 Digital Output 1 Ouput Block Control Relay 1 1 12 1 Digital Output 2 Ouput Block Control Relay 2 2 12 1 Preset energy Ouput Block Control Relay 3 3 12 1 Reset of Fault Passage Ouput Block Indicator Control relay output block 0 and 1 Command of digital output 1 and 2 2 Loading of the meter Energy with the preset energy value 32 bits on closing order 3 Fault passage indicator reset on closing order Description Index Default Static Default Event Variation Point Name hex dec Variation Obj Var Desc Obj Var Class Desc Binary Input 0 0 I 1 NoStatus 2 2 1 With Time Digital Input 1 Binary Input 1 1 1 1 NoStatus 2 2 I With Time Digital Input 2 Binary Input 2 2 1 1 NoStatus 2 2 1 With Time Digital Input 3 Binary Input 3 3 1 1 NoStatus 2 2 1 With Time Digital Input 4 Binary Input 4 4 1 1 NoStatus 2 2 1 With Time Digital Input 5 Binary Input 5 5 1 __ No Status 2 2 1 With Time Digit
4. keys simultaneously Specific messages When the configuration software is started up several types of message may appear on the screen Unidentified Equipment connected the serial link between the configuration computer and the equipment to be configured is not valid check the connection cord and the connection location at the computer end Fault messages related to a configuration loss or internal problem Software configuration Pressing the F10 key accesses the software configuration menu The menu is used to modify display colors the serial port used Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Main menu RTU address e May take every value between 0 and 65534 e Default value is 0 SCADA address e take every value between 0 and 65534 e Default value is 0 Parameters Displays the configuration screen of protocol dedicated parameters Modem type e Defines the communication medium Possible values Direct R8232 Hayes GSM GPRS e In this exemple default value is Direct RS232 Communication Parameters RS232 Hayes and GSM only Displays the communication medium parameters setup screen according to the medium selected GPRS modem version GPRS Parameters GPRS only Displays the configuration screen of GPRS dedicated parameters TCP IP Parameters GPRS only Di
5. d listening to incoming connection Local Port TCP IP connect delay Enter the port number you want F200C to Time to send an alarm configured with delayed option listen to incoming TCP connection Value is from 1 to 65535 e first attempt adjustable from 0 to 1min per steps of 1s ye Setting it to 70 selects a random time between 0 and 1 min Max transmission time this is mandatory to prevent all equipment calling the SCADA Maximum duration of a TCP IP connection at the same time On time out expiry the TCP IP connection is closed second attempt configurable from 0 to 5min per steps of Each time the F200C receives a request 1min Setting it to 0 selects a random time between 0 and 5 the timer is re armed min Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication e third attempt configurable from 0 to 10 min in steps of 1 min Setting it to 0 selects a random time between 0 and 10 min Note The 2nd and 3rd emissions are only used by the equipment if the preceding one did not manage to send the frame DNP3 Parameters Idle line delay It s the minimum line idle interval between two consecutive frames Values are from 10 to 100 ms e 10 ms is the default value Requires Data Link Layer Confirm e Select yes if you want User Data to be sent using a SEND CONFIRM expected frame type by the Link Layer Selecting no conf
6. 01 doc Edition 09 2006 Fax 33 0 1 46 99 71 00 http www schneider electric fr Due to changes in standards and equipment the characteristics mentioned in the texts and images of this document cannot be considered as binding unless confirmed by our services Publication Schneider Electric Industries SA Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc 23
7. 1 0 at start 99 x 31 is faulty Modem state comments Modem Init G200 is configuring the modem Entering code pin Code pin error Wrong code pin Network registration IMSI registration GPRS registration PDP Init Open a PDP session PDP Closing Close the PDP session PDP Status Check the PDP status PDP Connected Stand bye state when listen mode is not activated Closing TCP listened Close the listen port TCP Closing Disconnection from the SCADA TCP Listening Opening the listen port TCP Listened Stand bye state when listen mode is activated TCP Connecting Try to connect to the SCADA TCP Connected Connected to the SCADA Modem failure GSM registration denied IMSI registration is refused by the operator check your SIM card right with your provider GPRS registration denied GPRS registration or PDP activation is refused by the operator check your SIM card right with your provider MERLIN GERIN Co 31 43 16 522 22 05 64 55 52 99 lt 9515989500 esd 05 64 55 55 09 Gio 139 5 erster 05 64 55 57 20 lt SS gu A fb cutie se dus 05 64 55 57 69 OS L7 18 ou e ee eis 05 64 Pause nfiguration and Diagnostic ALT F4 Exit 81 90 00 01 01 00 00 17 07 0
8. 2 00 1E 01 00 00 01 00 00 01 00 00 01 00 00 18 FC 01 86 13 1E 01 00 07 01 F6 02 00 16 82 01 00 F2 60 08 00 73 B9 01 3C 02 06 3C 03 06 3C 04 06 95 9D 81 90 00 01 01 00 00 17 07 02 00 1E 01 98 04 01 88 04 01 8F 04 01 92 05 5E 01 01 8A 13 1E 01 00 07 OA 01 DA 02 00 9A D4 01 8F 49 2A 08 00 CO 17 Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Device Profile Document DNP V3 00 DEVICE PROFILE DOCUMENT Vendor Name SCHNEIDER ELECTRIC Device Name F200 C DNP3 1 00 Highest DNP Level Supported Device Function For Requests L1 Master Slave For Responses L1 Notable objects functions and or qualifiers supported in addition to the Highest DNP Levels Supported the complete list is described in the attached table e Binary input All Variations Read all points e Binary counter Variations Read all points e Analog input All Variations Read all points e Analog output All Variations Read all points Maximum Data Link Frame Size octets Maximum Application Fragment Size octets Transmitted 292 Transmitted 1369 0 Received 498 Received must be 292 Maximum Data Link Re tries Maximum Application Layer Re tries None None Fixed at Fixed at Configurable range 1 to 10 Configurable range 1 to 10 Enables an applicatio
9. 5 min in increments of 1 min e Default value 1mn The value 0 corresponds to a random delay between 1 and 5 min 3 attempt In the event that the second call fails time lag before the third call to the SCADA e Configurable from 0 to 10 min in increments of 1 min e Default value 2 mn The value 0 corresponds to a random delay between 1 and 5 min Maximum transmission time Maximum lasting time of a call After this time systematic call break e Configurable from 1 to 30 min in increments of 1 min e Default value 10 min Short Message System SMS SMS activated e Yes No enables SMS s to be sent or not e Default value is no SMS service center phone number Phone number of the SMS server refer to the notice with the SIM card e This field is empty in default settings SMS user phone number e Mobile phone number of the recipient of the SMS s e This field is empty in default settings Schneider Electric Easergy FLAIR 200 DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication GPRS Parameters GPRS version only MERLIN GERIN Configuration and Diagnostic ALT F4 Exit GPRS Parameters PIN code a o o o o Setting of the PIN code into the SIM card GPRS COMMUNICATION PARAMETERS default value IS 0000 APN Server Max 30 Digits internet entreprise In case of wrong PIN code SIM card 3 failure appears in the screen Equipment states Time betwe
10. Imn Transmission of currents on changes yes Deadband value 10 Escape Exit 4 Delay before emission To avoid collision when spontaneously emitting on a half duplex link F200C will wait a T delay after seeing the link is no more busy using CD If at this moment CD is still not present F200C will send the message If present it will wait another T delay T delay is the sum of Delay before emission and a random value Configured values are from 0 to 10 s e Default value is O s Transmission of currents on changes e You can permit or inhibit transmission of currents measurements on changes by selecting respectively yes or no e Default value is yes Deadband value e It s the difference there must be between last reported value and current value to have a Change Event generated Range is from 1 to 10 000 in increments of 1 e Default value is 10 Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Equipment State The equipment states menu is used to display the information linked to the state of the F200C Fault passage indicator Faults are indicated in reverse video Equipment States Current states are indicated in reverse video Digital Outputs Use the S select confirm and A cAncel keys to control the relay outputs Digital Inputs Inputs in logical state 1 are indicated in reverse vide
11. MV Network management MV LV substations remote monitoring Merlin Gerin Easergy Range Easergy FLAIR 200C DNP 3 0 Communication User s Manual F200C DNP 3 0 Communication Summary Epi 3 SOFTWARE CONFIGURATION eere 4 P 4 MAIN 6 ALARM PARAMETERS eee eene 7 COMMUNICATION PARAMETERS 7 GPRS PARAMETERS eene 10 TCP IP 6 000040000 10 DNP3 PARAMETERS eene 11 EQUIPMENT 12 DNP3 eee eeemememenenenen eren 12 DEVICE PROFILE DOCUMENT nenne 13 IMPLEMENTATION TABLE eren 16 F200C DNP 3 0 Communication Software Configuration General Local configuration Configuration and diagnosis of the Flair 200C is performed by connecting a laptop PC This software can be used to Change the Flair 200C configuration communication parameters alarms etc Read the equipment state of the Flair 200C Read the recordings made by the Flair 200C Reset the time of the Flair 200C Requisite equipment The equipment is configured using a PC provided with MS DOS Metal part and 5 Metal part Connector on Connector on o Flair 200 Configuration and diagnostic software computer end F200C end Connection cable Running the configuration progra
12. S0 2 Factory modem init Escape Exit 2 attempt In the event that the first call fails time lag before the second call to the SCADA e Configurable from 0 to 5 min in increments of 1 min e Default value 1mn The value 0 corresponds to a random delay between 1 and 5 min In the event that the second call fails time lag before the third call to the SCADA e Configurable from 0 to 10 min in increments of 1 min e Default value 2 mn The value 0 corresponds to a random delay between 1 and 5 min Maximum transmission time Maximum lasting time of a call After this time systematic call break e Configurable from 1 to 30 min in increments of 1 min e Default value 10 min Modem init e Hayes modem initialization chain AT command e Default settings EOQ0V1 amp C1 amp D2S0 2 Factory modem init Restores the factory initialization chain Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication GSM Host baud rate e This is the transmission speed between the SCADA and theRTU The available values are 200 300 600 1200 2400 4800 and 9600 bauds e The default value is set to 9600 bauds PIN code PIN code of the SIM card e Default value 0000 In the event of an incorrect PIN code PIN code error appears in the Equipment states menu Important after three incorrect attempts the SIM card becomes invalid To ma
13. able Latch On O Never Always O Sometimes Configurable Latch Off O Never Always O Sometimes Configurable Queue Never Always Sometimes Configurable Clear Queue Never Always Sometimes Configurable Local configuration with a PC Executes as it has been received Always executes a Pulse On with on time 3 s Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Reports Binary Input Change Events when no specific variation requested Never Only time tagged Only non time tagged Configurable to send both one or the other attach explanation Reports time tagged Binary Input Change Events when no specific variation requested Never Binary Input Change With Time Binary Input Change With Relative Time Configurable attach explanation Sends Unsolicited Responses Never MConfigurable attach explanation Only certain objects Sometimes attach explanation ENABLE DISABLE UNSOLICITED Function codes supported Sends Static Data in Unsolicited Responses Never When Device Restarts When Status Flags Change No other options permitted Default Counter Object Variation No Counters Reported Configurable attach explanation Default Object 20 Default Variation 01 Point by point list attached Counters Ro
14. al Input 6 Binary Input 6 6 1 1 NoStatus 2 2 1 With Time Reserved Binary Input 7 7 1 Status 2 2 1 With Time Reserved Binary Input 8 8 1 1 NoStatus 2 2 I With Time Flair 200C fault Binary Input 9 9 I 1 NoStatus 2 2 I With Time Local configuration Binary Input A 10 1 1 No Status 2 2 1 With Time Remote configuration Binary Input 11 1 1 NoStatus 2 2 1 With Time Reserved Binary Input C 12 1 1 NoStatus 2 2 I With Time Configuration fault Binary Input D 13 1 1 NoStatus 2 2 I With Time Stack 80 Binary Input E 14 1 1 No Status 2 2 1 With Time Event loss Binary Input F 15 1 1 NoStatus 2 2 I With Time Reserved Binary Input 10 16 1 __ No Status 2 2 1 With Time Earth fault Binary Input 11 17 1 __ No Status 2 2 1 With Time Fugitive earth fault Binary Input 12 18 1 NoStatus 2 2 1 With Time AC supply off phase 1 Binary Input 13 19 1 1 NoStatus 2 2 1 With Time Phase fault Binary Input 14 20 1 1 NoStatus 2 2 1 With Time Fast phase fault Binary Input 15 21 1 1 NoStatus 2 2 I With Time Reserved Binary Input 16 22 1 1 No Status 2 2 1 With Time Reserved Binary Input 17 23 1 1 NoStatus 2 2 1 With Time Reserved Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication
15. en connection attempt 5mn Important after three incorrect attempts the SIM card becomes invalid To make it valid a mobile phone must be used The Flair 200C cannot do this Please consult the user guide of the SIM Card to return to an available status Escape Exit APN Server gt Enter the APN Access Point Name which you obtain from your GPRS provider Time between connection attempt APN Login and Password Delay time between 2 failed connection attempts to the IP network Enter the login and the password provided with your GPRS account Note In major case no login and password are required for GPRS access TCP IP Parameters GPRS version only MERLIN GERIN Configuration and Diagnostic ALT F4 Exit TCP IP parameters F200C Parameters F200C PARAMETERS Host address Host address 0 0 0 0 if dynamic 0 0 0 0 1 d The address of the F200C is currently E allocated dynamically 0 0 0 0 corresponds Max transmission time l0mn to dynamic allocation The allocated TCP connect delay 1st try TET address is readable in Equipment State i c dd menu This field should be writable in SCADA PARAMETERS IP address 2 192 168 1 13 future use Socket type TOP Remote port 1 65535 E 2404 Listen Mode Select yes if you want F200C to listen to incoming TCP connection When the equipment is in alarm mode F200C stops Escape Exit
16. igures Link Layer to use a SEND NO REPLY expected frame type for User Data transmission Notice that in the case where SEND NO REPLY expected frame type is used F200C will never send RESET of remote link frames It will work strictly as a slave e Default is yes Maximum Data Link Re tries Defines the number of re tries by the Link Layer when the RTU doesn t receive any CONFIRM frame ACK or NACK to a frame using a SEND CONFIRM expected frame type When the Maximum Data Link Re tries is reached without confirmation Link Layer will perform RESET of remote link to re initialise the link Default value is 3 Time out e It s the delay Link Layer will wait for a CONFIRM frame after sending SEND CONFIRM expected frame Values are from 1 to 10 s e Default value is 5 s SCADA Parameters address Enter the Ip address of the SCADA Socket type Not implemented for future use Remote port Enter the port number the SCADA listens to incoming connection MERLIN GERIN Configuration and Diagnostic 4 DNP3 Parameters LINK LAYER Idle line delay 10ms Requires Data Link Confirm no Maximum Data Link Re tries 2 23 Time out 58 Delay before emission 108 APPLICATION LAYER Handle requested object s unknown bit yes Sends Unsolicited Responses no Wait delay 100ms Requires Application Confirm no Maximum Application Re tries 2 23 Time out
17. ke it valid a mobile phone must be used The Flair 200C cannot do this Please consult the user guide of the SIM Card to return to an available status Alarm Parameters Host tel number main Phone number of the control station maximum 15 digits e This field is empty in default settings Host tel number standby e Standby number od the control station if the main number is unavailable station maximum 15 digits e This field is empty in default settings Dial up delay time Time lag between the occurrence of an alarm and the call to the SCADA rsi 1 attempt e Configurable from 0 to 60 s in increments of 1 s e Default value 1s The value 0 corresponds to a random time lag between 1 and 60 s to avoid all the equipment calling the SCADA at the same time MERLIN GERIN Configuration and Diagnostic ALT F4 Exit Communication Parameters Modem GSM Host baud rate PIN code 0000 9600 bauds Alarm parameters Host tel number main 1 Host tel number standby Dial up delay time first attempt 15 Os random value second attempt lmn third attempt 2mn Max transmission time 10mn Short Message System SMS Short Message System enabled no SMS service center phone number SMS user phone number Escape Exit 2 attempt In the event that the first call fails time lag before the second call to the SCADA e Configurable from 0 to
18. ll Over at O No Counters Reported Configurable attach explanation 16 Bits 32 Bits Other Value Point by point list attached Sends Multi Fragment Responses V Yes O Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Implementation Table OBJECT REQUEST RESPONSE Notes slave must parse master must parse Obj Var Description Func Qual Func Qual Codes Codes Codes Codes dec hex dec hex 1 0 Binary Input Variations 1 06 1 1 Binary Input 129 00 1 2 Binary Input with Status 129 00 2 2 Binary Input Change with Time 129 17 Echo of 12 I Control Relay Ouput Block 5 6 17 28 129 request 20 0 Binary Counter All Variations 1 06 20 1 32 Bit Binary Counter 129 00 30 0 Analog Input Variations 1 06 30 1 32 Bit Analog Input 129 00 30 2 16 Bit Analog Input 129 00 32 4 16 Bit Analog Change Event with Time 129 17 40 0 Analog Output Status All Variations I 06 41 2 16 Analog Output Block 5 6 17 28 41 1 32 Bit Analog Output Block 5 6 17 28 50 1 Time and Date 2 see 07 where 4 14 quantity 1 60 1 Class 0 Data 1 06 60 2 Class 1 Data 1 06 07 08 60 3 Class2 Data 1 06 07 08 m 60 4 Class3 Data 1 06 07 08 o 80 1 Internal Indications 2 00 index 7 No object 13 No object 23 see 4 14
19. m Connect the cable to serial port 1 COM1 of the computer and to the serial connector of FLAIR 200C Start the PC under Windows and insert the Easergy CD Rom The configuration program is run Select the start menu The main menu appears Comments concerning use of the software Following modifications the configuration data are only acknowledged by the equipment after validation in the OK zone During modifications and before the validation operation the equipment runs with the previous data which are therefore at least partially different from the data momentarily displayed on the Screen Action in the Cancel zone displays the old parameters again The zone in which the cursor is positioned is highlighted To move between zones data input fields or function title the arrow keys or tabulation key are used To select a highlighted zone the Enter or Space keys are used Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc EN F200C DNP 3 0 Communication Parameter values are modified using o the or Space keys to increase the value o the key to reduce the value When parameter value is at its maximum pressing or Space key changes the value to its minimum Pressing the key changes it back to the maximum To exit a sub menu the user presses the Escape key m To exit the main menu the user presses the Alt and F4
20. mmunication Description Index WRITE READ Point Name hex dec Obj Var Desc Obj Var Class Desc Analog Output 4 4 41 2 16 Bit 40 2 1 16 Bit Alarms on TSS Without Time Analog Output 5 5 41 2 16 Bit 40 2 1 16 Bit Powert off threshold Without Time Analog Output 6 6 41 2 16 Bit 40 2 1 16 Bit Power on threshold Without Time Analog Output 7 7 41 2 16 Bit 40 2 1 16 Imax threshold Without Time Analog Output 8 8 41 2 16 Bit 40 2 1 16 Bit 10 threshold Without Time Analog Output 9 9 41 2 16 Bit 40 2 1 16 Bit Reset fault time Without Time Analog Output A 10 41 2 16 Bit 40 2 1 16 Bit Imax fault ack time Without Time Analog Output B 11 41 2 16 Bit 40 1 1 16 Bit 10 fault ack time Without Time Analog Output C 12 41 2 16 Bit 40 1 1 16 Bit Flair 200C port Without Time GPRS only Analog Output D 13 41 2 16 40 1 1 16 SCADA port Without Time GPRS only Analog output 4 Alarms on TSS 1 Alarm is ON if the TSS is ON 0 Alarm is not used Analog output 4 alarms on TSS Digital input 1 Digital input 2 Digital input 3 Digital input 4 Digital input 5 Digital input 6 Flair 200C fault Test alarm Short message system enabled Reserved AC supply off Phase fault Earth fault Alarm message set up Reserved Reserved Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc 20
21. n fragment to contain all class 0 data including expansion future use and reserved points and 100 event objects corresponding to event buffer capacity Local configuration with a PC Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Requires Data Link Layer Confirmation Never Always Sometimes Configurable Requires Application Layer Confirmation Never Always not recommended When reporting Event Data Slave devices only O When sending multi fragment responses Slave devices only Sometimes If Sometimes when Configurable Timeouts while waiting for Data Link Confirm O None Fixed at O Variable Configurable Complete Appl Fragment None Fixed at O Variable Configurable Application Confirm O None Fixed at O Variable Configurable Complete Appl Response None Fixed at O Variable Configurable Others Sends Executes Control Operations WRITE Binary Outputs Never Always Sometimes Configurable SELECT OPERATE Never O Always O Sometimes Configurable DIRECT OPERATE O Never Always O Sometimes Configurable DIRECT OPERATE O Never M Always O Sometimes Configurable Count gt 1 Never Always O Sometimes Configurable Pulse On Never Always O Sometimes Configurable Pulse Off Never Always O Sometimes Configur
22. o Modem not identified F200C was unable to communicate with the modem used GSM SIM card failure F200C has detected the embedded GSM modem card but cannot read the SIM card address GPRS only Indicates the current Ip address of the F200C GSM signal quality Specific to the GSM modem the barchart indicates the quality of the reception signal DNP3 Analyser This analyser shows the different frames recognised with some complementary information such as the direction of the frame Host gt F200C or F200C gt Host possibly the error detected character framing error overflow checksum bad length bad control character In case of multiple errors it s the first one that is indicated Each correct frame is shown one block per line 10 bytes for the first one 18 bytes for next ones last one may be shorter MERLIN GERIN Co Fault passage indicator Phase fault Earth fault Equipment state Flair 200C fault Local conf Remote conf Config fault Alarm processing AC supply off Communication state Modem not identified SIM card failure GSM signal quality The signal must be betwe 0 received signal 0 E Escape Exit nfiguration and Diagnostic ALT F4 Exit Equipment state Digital outputs DO Controle Select Confirm command cAncel command Digital inputs DE 1 DI 2 Modem state DI 3 TCP Connected DI 4 Ip address D 5 193 249 197 190 DI 6 en 17 and 3
23. rm on phase fault detection no Alarm on earth fault detection no Escape Exit Cyclic dial up e The yes option causes cyclic dial up to the control station e Default value is no Starting time min amp hour e Starting time in the following 24 hours of the cyclic dial up e Default value is midnight Period Time interval between two consecutive cyclic dial ups from 0 to 255h e Default value is 24 hours MERLIN GERIN Configuration and Diagnostic ALT F4 Exit Communication Parameters Modem Direct RS 232 Host baud rate 9600 bauds Handle DSR no Handle DCD no Handle CTS CTS delay 20ms RTS or CTS to message delay 20ms Message to RTS delay 20ms Escape Exit Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Handle DCD e Select yes if you want F200C to control reception with DCD e Default value is no Handle CTS e Select yes if you want F200C to wait for CTS after asserting RTS before sending the message e Default value is no CTS Delay 5 the delay F200C will wait for CTS if handled Value is from 20 to 500 ms e Default value is 20 ms Hayes Host baud rate e This is the transmission speed between the SCADA and the RTU The available values are 200 300 600 1200 2400 4800 and 9600 bauds The default value is set to 9600 ba
24. rsion only Time read only for future use Analog Output 3 3 41 32 bit 40 1 1 32 Bit SCADA IP address Without GPRS version only Time Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Analog output 0 Cyclic dial period The Flair 200C may periodically dial up This function can be used to check if the equipment is still running and to download measurements The parameters of the cyclic dial up are coded as follows Most significant byte Set 0 0 i ji nue di B15 B8 B7 BO Set 1 Cyclic dial up process is on only if alarms are activated Set 0 Cyclic dial up process is off Hour and Minute stand for the starting time of the process in the current day Least significant byte i 15 B8 B7 BO Period stands for the number of hours between two automatic calls Analog output 2 and 3 IP addresses for GPRS only F200C IP address IP address of the F200C must be 0 0 0 0 if dynamic allocation is used SCADA IP address IP address of the SCADA Each byte can be 0 byte 255 For instance 193 251 9 68 is coded as 68 0x44 byte 1 9 0x09 byte 2 251 byte 193 0 1 byte 4 Schneider Electric Easergy FLAIR 200C DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Co
25. splays the configuration screen of TCP IP dedicated parameters MERLIN GERIN Configuration and Diagnostic ALT F4 Exit Easergy Flair 200C DNP3 PROM v1 00 PIC v2 08 Type A PARAMETERS SETUP Equipment name f200c DNP3 Setup RTU address 0 SCADA address 0 DNP3 Parameters Modem Type Direct RS 23 Communication Parameters SAVE CONFIGURATION Cancel DIAGNOSIS Display events Display analog Equipment states Measurement and fault detection Alarm Parameters Setup Time Energy Preset 2 Erase events DNP3 Analyser Alarm Parameters Displays the alarm con DNP3 Analyser figuration screen Displays the trace of exchanges between the equipment and the control station MERLIN GERIN Configuration and Diagnostic ALT F4 Exit Easergy Flair 200C DNP3 PROM v1 00 PIC v0 00 Type A PARAMETERS SETUP Equipment name f200c DNP3 Setup RTU address H 0 SCADA address 0 DNP3 Parameters Modem Type GPRS GPRS Parameters TCP IP parameters SAVE CONFIGURATION Cancel DIAGNOSIS Display events Display analog Equipment state Measurement and fault detection Alarm Parameters Setup Time Energy Preset Default Config Erase events DNP3 Analyser Schneider Electric Easergy FLAIR 200 DNP 3 0 Communication NT00138EN 01 doc F200C DNP 3 0 Communication Alarm Parameters Digital Input For each Digital Input the
26. uds Dialing type e Tone pulse or none e The default value is tone Host tel number main Phone number of the control station maximum 15 digits e This field is empty in default settings Host tel number standby Standby number od the control station if the main number is unavailable station maximum 15 digits e This field is empty in default settings Dial up delay time Time lag between the occurrence of an alarm and the call to the SCADA 15 attempt e Configurable from 0 to 60 s in increments of 1 s e Default value 1s The value 0 corresponds to a random time lag between 1 and 60 s to avoid all the equipment calling the SCADA at the same time RTS or CTS to message delay e It s the delay F200C will wait after RTS or CTS if handled before sending the message Value is from 0 to 500 ms e Default value is 20 ms Message to RTS delay e t s the delay F200C will wait after the end of the message before asserting RTS low Value is from 0 to 500 ms e Default value is 20 ms MERLIN GERIN Configuration and Diagnostic ALT F4 Exit Communication Parameters Modem Hayes Host baud rate 9600 bauds Dialing type Tone Host tel number main 0478574532 Host tel number standby 0478574532 Dial up delay time first attempt 18 Os random value second attempt lmn third attempt 2mn Max transmission time 10mn Modem init E0QOV1 amp C1 amp D2
27. yes option causes sending of an alarm on each change of state of the input e Default value is no Alarm on e The yes option causes sending of an alarm upon occurrence of the fault e Default value is no Alarm message enabled e yes option activates alarm transmission e Default value is no Note Alarm call to the control station and SMS sending can be enabled at the same time The SMS message is sent first Dial up test e yes option allows a test to be performed on alarm transmission to the control station The Flair 200C is calling the supervisor after recording of the configuration e Default value is no Communication Parameters RS232 Hayes or GSM modem type Direct RS 232 Host baud rate e This is the transmission speed between the SCADA and the RTU The available values are 200 300 600 1200 2400 4800 and 9600 bauds e The default value is set to 9600 bauds Handle DSR e Select yes if you want F200C to detect connection using DSR e Default value is no MERLIN GERIN Configuration and Diagnostic ALT F4 Exit Alarm Parameters Digital input Digital input Digital input Digital input no Cyclic dial up no T no Alarm message enabled no 2 3 4 Digital input 5 6 Dt no Dial up test no Starting time min 0 Digital input no hour 0 Flair 200C fau no Period hours 24 Alarm on AC supply off detection no Ala