Home

System bit and Register reference

image

Contents

1. 9130 Language control word Use this to change the displayed language Ver 2 5 state for all labels The range is 0 3 read write 9135 Li Battery Voltage in millivolts Only displayed after download Not available Ver 2 6 0 in Simulation modes Hardware Version 4 5 Note This is not the PLC s battery It is the jonly The range is 0 1228 which is scaled touchscreen s internal battery from 0 3V If the LW9135 lt 1126 2 75V change the Li battery read only 9136 CF card download status read only Ver 2 7 0 O inactive 1 download in progress 2 download complete 3 download failed Retentive memory The HMI units have 64K of battery backed RAM This memory is accessed by using the following data types RB accesses the first 2047 registers as 16 bit groups The bit is designated as a hexadecimal number i e accessing bit 10 of word 63 would be Device type RB Device address 63A RBI accesses the first 2047 register s bits and sets the index pointer to that bit LW9000 is used in conjunction with the RBI value to give an offset value for Recipe Transfer parts i e If RBI is set to device address 20 and LW9000 has a value of 5 in it then bit downloads and saves would begin at RB25 RBI20 5 RW accesses the retentive registers as words The full range 0 to 65535 is available but registers above 60000 are reserved for system use See below RWI Reads the register and sets the index pointer to the value in that regis
2. bit to indicate when a recipe _ ver 1 2 Set ON when downloading download is in progress read write Set OFF when download done 9011 Recipe upload indicator it is Use this bit to indicate when a recipe _ ver 1 2 Set ON when uploading upload is in progress read write Set OFF when upload done 9012 Recipe download upload indicator it is Use this bit to indicate when any recipe ver 1 2 Set ON when transferring data transfer is in progress read write Set OFF when transfer done 9013 Task bar Touch Indicator pressed bit it is This bit does not return the state of the Ver 1 4 Set ON when Touch Indicator is pressed touch indicator read write LB Address Description NOTE Version 9014 Task bar CPU Indicator pressed bit it is This bit does not return the state of the Ver 1 4 Set ON when CPU Indicator is pressed CPU indicator read write 9015 Task bar Alarm Indicator pressed bit it is This bit does not return the state of the Ver 1 4 Set ON when Alarm Indicator is pressed alarm indicator read write 9016 Print Error indicator Use to trigger an alarm or event to let Ver 1 4 Changes to 1 when printing fails the user know there is a problem with printing read only 9017 Printer enable bit The user Setting in System Parameters must Ver 1 4 Sets ON to disable print functions have a printer selected for this Bit to Sets OFF to enable print functions have an
3. effect read write 9020 Pen enable bit The user Positive edge trigger Message board Ver 1 4 Sets ON to enable pen functions use read write 9021 Brush Eraser enable bit The user Positive edge trigger Message board Ver 1 4 Sets ON to enable brush functions use read write 9022 Clipping enable bit The user Positive edge trigger Message board Ver 1 4 Sets ON to enable clip functions use read write 9030 Pen width to 1 pixel enable bit The user Positive edge trigger Message board Ver 1 4 Sets ON to set pen width to 1 pixel use read write 9031 Pen width to 2 pixels enable bit The user Positive edge trigger Message board Ver 1 4 Sets ON to set pen width to 2 pixels use read write 9032 Pen width to 3 pixels enable bit The user Positive edge trigger Message board Ver 1 4 Sets ON to set pen width to 3 pixels use read write 9040 Fast Selection window enable bit The user This bit overrides the System Ver 1 4 Sets ON to hide Fast Selection window Parameter Task Bar setting Sets OFF to show pop up Fast Selection read write window 9041 Task Bar enable bit The user Task Bar control read write Ver 1 4 Sets ON to hide the Task Bar Sets OFF to show pop up the Task Bar 9042 Task Buttons enable bit The user Task Bar control read write Ver 1 4 Sets ON to hide the two Task Buttons Sets OFF to show pop up the two Task Buttons 9043 Hide Show Task Items Fast Selection screen Task When enabled all items ap
4. 1 this value from the data read write 9057 EventLog DataBase Item size Management Use when storing the Event Log in retentive Ver 2 1 information the size of every item memory read only 9058 9059 EventLog DataBase size Use when storing the Event Log in retentive Ver 2 1 Management information the size of the memory DataBase the size includes management read only information total_item item_size management_info_size 9060 9075 Holds Numeric and ASCII Input input data read write Ver 1 4 9075 holds the least significant digits LW Address Description NOTE Version 9080 9085 Project name Use ASCII Data to show project name Ver 1 5 It occupies 12 bytes read only 9086 9087 Project size in bytes Use Numeric Data to show In Decimal Ver 1 5 read only 9088 9089 Project size in K bytes Use Numeric Data to show In Decimal Ver 1 5 read only 9090 9091 Compiler version ID Use Numeric Data to show In Decimal Ver 1 5 read only 9092 Project Compile Date Year Use Numeric Data to show In Decimal Ver 1 5 read only 9093 Project Compile Date Month Use Numeric Data to show In Decimal Ver 1 5 read only 9094 Project Compile Date Day Use Numeric Data to show In Decimal Ver 1 5 read only 9100 Indirect Addressing For external PLC 9100 indirect window number Ver 1 6 only 9101 Indirect Addressing For external PLC 9101 indirect offset Ver 1 6 only
5. 1 Keypad control bit bottom side See note for 9060 read only Ver 2 0 Risht and To Le5e66 T g LE9S065 Reserved Local Words LW Address Description NOTE Version 9000 Retentive memory Index base RBI and RWI use this as an index offset when Ver 1 2 accessing retentive data read write 9002 9003 Set to Numeric Input Maximum value Numeric Input loads its maximum value when Ver 1 4 when numeric input gets the focus activated When Numeric Input loses the focus it is set to zero read only 9004 9005 Set to Numeric Input Minimum value Numeric Input loads its minimum value when Ver 1 4 when numeric input gets the focus activated When Numeric Input loses the focus it is set to zero read only 9006 Message board mode Message board use Ver 1 4 0 pen read 1 brush 2 clipping 9007 Pen width Message board use Ver 1 4 0 1 pixel read 1 2 pixel 2 3 pixel 9008 Pen color Message board use Ver 1 4 0 255 read write 9010 Local second BCD code valid values 0 59 Ver 1 2 read write allow 9011 Local minute BCD code valid values 0 59 Ver 1 2 read write allow 9012 Local hour BCD code valid values 0 23 Ver 1 2 read write allow 9013 Local day BCD code valid values 1 31 Ver 1 2 read write allow 9014 Local month BCD code valid values 1 12 Ver 1 2 read write allow 9015 Local year BCD code valid values 0 9999 Ver 1 2 read write allow 9016 Loca
6. System Bit and Register Reference Local memory Local memory resides in DRAM and every value is initialized to zero at system start up The HMI is equipped with following local memory ranges LB 0000 9999 Bit devices Segmented in groups of 16 bits as follows LW 0000 9999 Word devices LWO LB 15 0 LWI1 LB 31 16 LW2 LB 47 32 LB 9983 9968 LW9998 LB 9999 9984 LW9999 Each LBnnnn is a 1 bit device and each LWnnnn is a 16 bit device These devices use separate memory areas and do not overlap i e LB0000 is not the first bit of LW0000 Changing LB0000 does not affect LW0000 Note The Local Bit and Word addresses above 8999 are reserved for system use Remote memory When using Master Slave hardware configurations the Slave HMIs can access the Master s Local memory Master local memory ranges Ms_LB 0000 9999 Bit devices and Ms_LW 0000 9999 Word devices Reserved Local Words Bits Some Local Words Local Bits and Recipe Words are reserved for special purposes Users should not use these areas except for their specified purposes Local Bits 9000 9999 are reserved Local Words 9000 9999 are reserved Reserved Local Bits LB Address Description NOTE Version 9000 9009 _ Initialized as ON Use these bits for objects that need an ver 1 2 initial setting of ON read write 9010 Recipe download indicator it is Use this
7. l day of the week BCD code valid values 1 7 Ver 1 2 read write allow 9020 Object queue status If a screens object queue exceeds 1000 then Ver 1 4 This holds the total number of objects of ithe HMI screen is too complex The HMI is in all the windows on the display danger of reporting a Severe System Error Each window can hold up to 500 due to low system resources objects 9034 9035 System time unit as 0 1 second Starts at 0 when project started read write Ver 1 4 9040 9041 Window Security password Double word Ver 1 6 This word must contain the password for write only access to secure windows 9042 Security level read only Ver 1 6 The current active security level 9043 Force security level A security level can only be forced to a lower Ver 1 6 Set to 0 Lowest or 1 Middle level than is active write only LW Address Description NOTE Version 9044 Touch process mode This modification is to resolve a software Ver 1 6 There are three operational modes to handle constraint in older versions momentary switches They are based on the current value of LW9044 Use a SET WORD When a momentary switch is pressed touch of Set on window open in the Common down the related bit is set ON window to configure the desired operation mode If there is any popup window that hides the 0 Window popup operation is enabled during momentary switch before it is released the bit touch down and up a
8. only valid values For example Seconds cannot be changed to 78 BCD if 78 BCD is entered the RTC continues counting 78 79 80 etc This causes unpredictable conditions to happen System Information System Parameter mapping to recipe card information When a project is downloaded to a unit and run for the first time System Parameters are stored in the System Reserved Memory area The following is a list of the mapping relationship Parameters from the General Tab RW System Parameter NOTE Version 60061 Back light saver 0 Disable Ver 2 1 1 255 second Enable 60064 Buzzer 0 None Ver 2 1 1 Yes Parameters from the Security Tab RW System Parameter NOTE Version 60071 Security Control 0 None 1 Yes Ver 2 1 60072 Password level 0 two words Ver 2 1 60074 Password level 1 two words Ver 2 60076 Password level 2 two words Ver 2
9. pear in their Ver 1 4 Bar and Task Buttons The user activated state Task Bar and Fast Sets ON to hide the Task Items Selection window are opened Sets OFF to show pop up the Task Items read write 9044 Enable changes made to System Parameters in Forcing this bit ON restores Security Ver 2 1 Retentive memory area The user Passwords Backlight and Buzzer Sets ON to make the Security Passwords system parameters from Reserved Backlight and Buzzer System Parameters Retentive word area active After restoration the system sets this OFF has no effect bit OFF read write 9045 Reset HMI The user Forcing this bit ON resets the HMI Ver 2 1 Sets ON to reset the HMI write 9046 Security level change event indicator Changes to when going from a lower Ver 2 1 security level to a higher security level read only LB Address Description NOTE Version 9050 Toshiba T C write enable bit The user When setting the Timer Counter s Ver 1 5 Sets ON to enable writing to T C bits ON amp device to ON use 01 for OFF use OFF 00 read write Sets OFF to disable T C writing T1 T1S user s manual NOTE When writing to Timer Counter registers the Timer Counter s device data should be added to the written data 2 bytes each corresponding to the Timer Counter s register 9051 Enable or Disable the touchscreen when the OFF is the default mode Ver 1 6 Backlight is turned OFF The
10. responding bit changes to 0 when communication times out Write to resume communications read write 9360 CF status read only Ver 2 7 0 OFF CF not installed ON CF installed 9361 Controls CF card Recipe download After recipe download LB9361 stays Ver 2 7 0 ON to OFF stops download action ON until CF card is unplugged OFF to ON starts recipe download from CF read write 9060 Keypad control bit left side of window User can use this bit to control a Ver 1 6 Bit forced ON whenever a user actives an input Direct window Keypad popup data object NI or Al Keypad window is closed if input Bit forced OFF when entering valid data or ESC succeeds key is pressed read only 9061 Keypad control bit left side See note for 9060 read only Ver 1 6 9062 Keypad control bit left and top side See note for 9060 read only Ver 1 6 9063 Keypad control bit left and bottom side See note for 9060 read only Ver 1 6 9064 Keypad control bit right side See note for 9060 read only Ver 1 6 9065 Keypad control bit right side See note for 9060 read only Ver 1 6 9066 Keypad control bit right and top side See note for 9060 read only Ver 1 6 9067 Keypad control bit right and bottom side See note for 9060 read only Ver 1 6 9068 Keypad control bit all side See note for 9060 read only Ver 1 6 9069 Keypad control bit all side See note for 9060 read only Ver 1 6 9080 Keypad control bit top side See note for 9060 read only Ver 2 0 908
11. s written to R because it creates an Valid range 0x00800000 to 0x7 FFFFFFF error 8388608 to 2147483647 decimal read write Invalid range OxFF799999 to 0x80000000 8388608 to 2147483648 decimal 9071 MITSUBISHI J2 S10 driver control read write Ver 1 6 Write options for R The user Sets bit ON to write to EPROM Sets bit OFF to write to RAM default 9090 Event Log Clear The user After the Event log is cleared this bit Ver 2 5 2 Sets bit ON to write to clear entries from the auto resets to OFF Event Log This includes entries stored in RW read write memory if enabled 9091 Adjusts contrast lighter one shade The user After the contrast is made lighter this Ver 2 6 0 Sets bit ON to activate bit auto resets to OFF Hardware Version 4 5 only read write 9092 Adjusts contrast darker one shade The user After the contrast is made darker this Ver 2 6 0 LB Address Description NOTE Version 9100 9227 PLC address node communication status These bits correspond to the PLC Ver 2 6 0 OFF Communications timed out Station Numbers 0 127 The ON Communications are good corresponding bit changes to 0 when communication times out Write to resume communications read write 9228 9355 AUX address node communication status These bits correspond to the AUX Ver 2 6 0 OFF Communications timed out Station Numbers 0 127 The ON Communications are good cor
12. t touch up the BIT remains ON even if released touch up previously set ON is set OFF even if a read write popup window hides the momentary switch default initial value 1 Window popup operation is disabled during touch down and up 2 Window popup operation is enabled during touch down and up Therefore if the momentary switch is hidden by a popup window on touch up the BIT is not reset 9050 Base Window Id Slave HMI can use this word to show the Ver 1 2 same screen as the Master 9051 Reserved for Base Window ID write back PLC control Change screen writes back to Ver 1 2 operations by a slave HMI See LW9050 9051 so it is reserved for that purpose 9054 Report printout option print out Use this to change the attributes of a PLC Ver 1 5 0 Text Meters and Trends Control Report printout assignment 1 Text Meters Trends and Shapes but not read write patterns 2 Text Meters Trends and Bitmaps 3 Text Meters Trends Bitmaps and Shapes but not patterns 4 All 9055 PLC Control word Offset Use this to offset window numbers coming _ Ver 1 6 There are two options in the PLC Control from the PLC object that use this local word Example Change window and Report printout A PLC Control Change window uses D10 The value in this word is added to the If LW9055 10 and D10 4 then the HMI controlling data as an offset changes to window 14 After changing the Before writing back the HMI subtracts HMI writes back 4 to D1
13. ter LW9000 is used in conjunction with the RWI value to give an offset value for Recipe Transfer parts See Recipe Transfer Part for an example of the RWI register is used The valid range of RWI types is 0 32767 Ms_RB and Ms_RW are used by Slave configured units for accessing retentive memory locations in a remote Master unit NOTE All retentive data types overlap in retentive memory i e changing RB0002 to ON changes the value of RW00001 This also affects RWI00001 and RBIO002 Some Retentive Words are reserved for special purposes Users should not use these areas except for their specified purposes Retentive Words 60000 65535 are reserved Reserved Retentive Word RW Address Description NOTE Version 60000 Real Time Clock second BCD code valid values 0 59 Ver 1 2 read write allow 60001 Real Time Clock minute BCD code valid values 0 59 Ver 1 2 read write allow 60002 Real Time Clock hour BCD code valid values 0 23 Ver 1 2 read write allow 60003 Real Time Clock day BCD code valid values 1 31 Ver 1 2 read write allow 60004 Real Time Clock month BCD code valid values 1 12 Ver 1 2 read write allow 60005 Real Time Clock year BCD code valid values 0 9999 Ver 1 2 read write allow 60006 Real Time Clock day of the week BCD code valid values 1 7 Ver 1 2 read write allow NOTE about RTC When using Objects to display and change system time the user must take care to enter
14. user read write Sets ON to disable touchscreen when Backlight is turned OFF Sets OFF to keep touchscreen enabled when Backlight is turned OFF 9052 Write back enable PLC Control Change window This applies to Change Window Ver 1 6 The user control only Sets ON to disable write back to PLC read write Sets OFF to enable write back to PLC 9055 Disconnect action PLC communications The user When HMI is disconnected from the Ver 1 6 Sets ON to continuously retry any write to PLC PLC it acts according to the state of command this local bit 9055 Sets OFF to stop any write to PLC commands _ read write 9056 Disconnect action Touchscreen The user When HMI is disconnected from the Ver 1 6 Sets ON to enable touchscreen PLC it acts according to the content Sets OFF to disable touchscreen of this local bit 9056 read write Bits LB9060 9069 6080 and 6081 are used for detecting Numeric Input Extend and ASCII Input Extend presses See the following page for Touchscreen map Sets bit ON to activate bit auto resets to OFF Hardware Version 4 5 only read write 9070 MITSUBISHI J2 S10 driver control Due to the protocol limitation of J2 Ver 1 6 Effects local data being added to R or subtracted S100 for R registers A value from R between 0x00800000 and Set bit ON to disable add subtract operations OxFFFFFFFF inclusive cannot be Set bit OFF to enable add subtract operation