Manual trusa recuperare refrigerant RECO25
Contents
1. 7 CIRCUIT BREAKER 15 MOTOR 23 SOCKET 8 HP SWITCH 16 TUB 24 POWER SUPPLY CORD Optional 25 80 O F P SHUT OFF CORD for RECO25 O F P 26 OIL DRAIN VALVE for RECO25 O S 27 OIL SEPARATOR for RECO25 O S 28 LP SWITCH low pressure shut off function
2. off Output pressure is too high Failure in motor or in other electrical components MODE valve is in PURGE position Output valve is not open and high pressure activates Recovery tank valve is not open Head pressure too high Compressor seals are worn Connecting hoses are loose Leakage in unit ACTION Attach the power supply cord Check power supply at job site Press the button to reset Reduce pressure and then press the button of the High Pressure Switch Rotate INPUT valve and MODE valve to PURGE then rotate INPUT valve back to OPEN and MODE valve to RECOVER Factory service required Rotate MODE valve to RECOVER Rotate OUTPUT valve to OPEN Open recovery tank valve Reduce tank temperature with TANK COOLING PROCEDURE Factory service required Tighten the connecting hoses Factory service required WIRING DIAGRAM CIRCUIT BREAKER HIGH PRESSURE SWITCH SOCKE d COMPRESSOR POWER FAN SWITCH MOTOR MOTOR Wiring Diagram Standard CIRCUIT BREAKER Low HIGH PRESSURE PRESSURE SWITCH SWITCH SOCKE INDICATO j K F POWER SWITCH COMPRESSOR FAN MOTOR MOTOR Wiring Diagram Low pressure shut off function PARTS DIAGRAM 1 PLASTIC CASE 9 POWER SWITCH 17 TUB 2 CONTROL VALVE 10 DRYER FILTER 18 BASE 3 FRONT PANEL 11 HOSE 19 RUBBER FOOT 4 INPUT GAUGE 12 TUB 20 CONDENSER 5 OUTPUT 13 TUB 21 FAN 6 KNOB 14 COMPRESSOR 22 BACK PANEL
3. the compressor Slowly open the input port on the machine 1 If the compressor starts to knock slowly throttle back the input valve until the knocking stops 2 If the input valve was throttled back it should be fully opened once the liquid has been removed from the system the manifold gauge set vapor port should also be opened at this time Run until desired vacuum is achieved 1 Close the manifold gauge sets vapor and liquid ports 2 Turn off the machine 3 Close the unit s input port and proceed with the SELF PURGE PROCEDURE on the next page If the recovery machine fails to start rotate the INPUT valve and the MODE valve to purge position Then rotate the MODE valve back to recovery position and open the INPUT valve Caution Always purge the unit after each use Failure to purge the remaining refrigerant from the unit could result in the acidic degradation of internal components ultimately causing premature failure of the unit SELF PURGING PROCEDURE Procedure for purging remaining refrigerant from this machine 1 Close the ports of the system being serviced that are connected to the input port of the machine Turn off the recovery machine Turn the Input valve to the PURGE position Turn the MODE valve to the PURGE position Restart the machine Run until desired vacuum is achieved Close the ports on the recovery tank and the machine Turn the machine off Return the MODE valve to
4. 4a R 401C R 406A R 500 Cat IV R 22 R 401A R 401B R 402B R 407C R 407D R 408A R 409A R 411A R 411B R 412A R 502 R 509 Cat V R 402A R 404A R 407A R 407B R 410A R 507 Voltage 220 240VAC 50 60Hz 110 127 VAC 60Hz 100VAC 50 60Hz 110 220VAC 50 60Hz Compressor 1 2 HP Oil less Max current 4A 50Hz 8A 60Hz HP Shut off 38bar 550psi Recovery Rate Cat MI Cat IV Cat V Vapor 0 23kg min 0 25kg min 0 26kg min Liquid 1 57kg min 1 81kg min 1 85kg min Push Pull 4 64kg min 5 57kg min 6 22kg min LP Shut off Optional 80 Capacity Shut off Optional Operating Temp 0 40 C Case Blow Molded High Impact Polyethylene Dimensions 19 1 L x 8 7 W x 14 4 H 485mm x 220mm x 365mm Net Weight 33 lbs 15kg ONE SO WA AE er STANDARD LIQUID VAPOR RECOVERY PROCEDURE Make sure this recovery machine is in good operating condition Make sure all connections are correct and tight Open the liquid port of the storage tank Make sure the MODE valve is set on RECOVER Open the output port of the recovery machine Open the liquid port on your manifold gauge set opening the liquid port will remove the liquid from the system first After the liquid has been removed open the manifold vapor port to finish evacuating the system Manifold gauge set Note STANDARD LIQUID VAPOR RECOVERY PROCEDURE Connect the recovery unit to a right outlet See the nameplate on the machine Switch the power switch to the ON position to start
5. 6 Be sure that any room where you are working is thoroughly ventilated 7 Use ONLY authorized refillable refrigerant tanks It requires the use of recovering tanks with a minimum of 27 6 bar working pressure 8 Do not overfill the storage tank Tank is full at 80 volume There should be enough space for liquid expansion overfilling of the tank may cause a violent explosion A scale or a 80 O F P Kit must be used to avoid over filling the storage tank 9 Do not exceed the working pressure of Recovering Tank cylinder 10 Do not mix different refrigerants together in one tank or they could not be separated or used 11 Before recovering the refrigerant the tank should achieve the vacuum level 0 1 mpa which is for purging non condensable gases Each tank was full of nitrogen when it was manufactured in the factory thus the nitrogen should be evacuated before the first use 12 When the recovery machine is not used all the valves should be closed Because the air or the moisture of the air may harm the recovery result and shorten the service life of the recovery machine 13 When using an extension cord it should be a 14AWG minimum and no longer than 7 62 meters 25feet or it may make the voltage drop and damage the compressor GENERAL SAFETY GUIDELINES 14 A dry filter must always be used and should replaced frequently And each type of refrigerant must have its own filter For the sake of assuring the normal operation of the
6. USER MANUAL REFRIGERANT RECOVERY UNIT RECO25 SERIES TABLE OF CONTENTS GENERAL SAFETY GUIDELINES 1 ses see see se ee see see ees SPECIFICATIONS 3 SS US Bee EG Ve DES ee KERE Ge ee Gee ve ee STANDARD LIOUID VAPOR RECOVERY PROCEDURE SELF PURGE PROCEDURE eee se ese ese ese ee se ee ee see see ee LIQUID PUSH PULL PROCEDURE ees ses sees see se es ee see ees TANK COOLING PROCEDURE OPTIONAL ee ALTERNATIVE COOLING PROCEDURE OPTIONAL OIL SEPARATING PROCEDURE esse sees ses se ee ee ee ees ee TROUBLESHOOTING oeta ieir ee see see see se se ee na ee WIRING DIAGRAM ee se ee ee GR Re Ge ee ee ee ee PARTS DIAGRAM iese Ee SEE Ge ee Seep Ee gee ee SES eke be bee hee HE GENERAL SAFETY GUIDELINES 1 Read all safety operating guidelines and instructions before operating this recovery machine 2 Always think before acting familiarity breeds carelessness and carelessness can be harmful to your health or worse result in death 3 Only a qualified technician should operate this Recovery machine 4 Read all safety information regarding the safe handling of refrigerant and refrigerant oil including the Material Safety Data Sheet MSDS sheets can be obtained from your refrigerant supplier 5 Always wear safety goggles and protective gloves when working with refrigerants to protect your skins and eyes from refrigerant gases and refrigerant liquid Avoid getting in touch with causticity liquid or gas
7. the RECOVER position VO Oo HA OM BUL ND 10 Disconnect and store all hoses and dry filter Var A LIQUID PUSH PULL PROCEDURE Push pull procedure only works with large systems where the liquid refrigerant is no less than 6 8kg 151bs 1 put MODE valve knob on RECOVER 2 Open OUTPUT valve 3 Open INPUT valve 4 When the scale stops rising close all ports 5 Switch off the machine CAUTION When using the Push pull method a scale must be used to avoid over filling the storage tank once the siphon is started it can continue and overfill the storage tank even if the tank is equipped with a float level sensor The siphon can continue even when the machine is turned off You must manually close the valves on the tank and the unit to prevent overfilling of the recovery tank HYAC System TANK COOLING PROCEDURE OPTIONAL In order for this procedure you must have a minimum of 5 lbs 2 3kg of liquid refrigerant in the storage tank 1 Connect the hoses as shown 2 Turn the MODE valve to the Recover position 3 Open the Vapor and Liquid valve of the storage tank 4 Power on and start the compressor 5 Open the INPUT valve and OUTPUT valve of the machine 6 Throttle the OUTPUT valve of the machine so that the output pressure is 100psi greater than the input pressure but never more than 300psi 7 Run until tank is cold Vapor Liquid ALTERNATIVE COOLING PROCEDURE OPTIONAL Set up
8. unit please use the filter specified by our company High quality dry filters will bring high quality services 15 Special care should be taken when recovering from a burned out system Use two high acid capacity filters in series When you have finished recovering from the system flush the recovery machine with a small amount of clean refrigerant and refrigerant oil to purge off any foreign substances left in the machine 16 This recovery machine has a Pressure Shut Off Switch If the pressure inside the system should go above 38bars the system will automatically shut itself off The shut off switch must be manually reset 17 If the tank pressure exceeds 20 7bar use the TANK COOLING PROCEDURE to reduce the tank pressure 18 To maximize recovery rates use the shortest possible length of 3 8 or larger hose A hose no longer than 0 9 meter is recommended 19 When recovering large amounts of liquid use the LIQUID PUSH PULL PROCEDURE 20 After recovering make sure there s no refrigerant left in the machine Read the SELF PURGING PROCEDURE carefully Liquid refrigerant remained may be expanded and destroy the components 21 If this recovery machine is to be stored or not used for any length of time we recommend that it be completely evacuated of any residual refrigerant and purged with dry nitrogen 22 To reduce the risk of injury care should be taken when moving this machine SPECIFICATIONS Refrigerants Cat III R 12 R 13
9. your equipment as shown it is possible to cool the storage tank during the recovery procedure if necessary 1 Open the vapor valve of the storage tank it is closed while recovering 2 Close the two valves of the manifold gauge set 3 Follow the sixth and seventh items of the tank Cooling Procedure Manifald gauge set HVAC System Vapar Liquid OIL SEPARATING PROCEDURE This procedure is only for RECO25 O S Recovery amp Recycling 1 Make sure all connections are correct and tight 2 Make sure the port of drain valve is closed 3 Make sure the MODE valve on RECOVERY position 4 Open the liquid port of the storage tank 5 Open the output port of the unit and liquid port on the manifold gauge set 6 Turn the power switch to ON Open the input valve slowly to liquid position Run until the recovery is achieved 7 Turn the power switch to OFF Open the port of oil drain valve and drain the oil into a suitable container and then close the oil drain port 8 Disconnect all hoses Manifold Bauge sel TROUBLESHOOTING PROBLEM Fan does not run when Power Switch is in ON position Fan runs but compressor does not start Compressor starts but cuts off within a few minutes Recovery process too slow Recovery machine does not pull out a vacuum CAUSE Power supply cord not attached voltage is not right The circuit breaker has cut off The recovery machine is in high pressure shut