1. Rx 1 Finally a Force standby Inter AXE Link failed event would be recorded and the standby would refresh 7 The master would record a Forced other railbus mismatch event and the standby would refresh This issue is corrected in this release Handling of differences Simplex In previous releases under heavy communication load or rarely between RTC and CPU Duplex under normal load a controller could abort with a log event date time indicating TmrPIT FIT Interrupt rate This was due to an incorrect diagnostic check in the controller and has now been corrected RTOS did not manage the Simplex In previous releases a rollover of an internal clock could result in rollover of time slice Duplex a controller aborting The event log would indicate Abort due to up counter correctly SpvTaskTimeout for either a UDP or TCP task The clock rollover occurs at approximately 13 months from the last reset or power cycle Strategy download caused Projects containing Safe ISaGRAF strategies and with several Task Timeout thousand tags mapped into the Discrete Control Interface were failing during the Strategy download due to task timeouts The building of the Register Protection Table RPT was changed to better handle these projects The following error message appeared in the controller event log Abort due to SpvTaskTimeout ISaGRAF debugger Simplex The ISaGRAF debugger did not reliably connect to the
2. controller sometimes failed to start Duplex In these cases no log message was generated in the controller correctly log and the ISaGRAF debugger indicated a failure or a connection was not obtained PAC8000 8851 LC MT SafetyNet Logic Controller 3 Restrictions and Open Issues GFK 2569B Subject Configuration Description 8811 Module driver Simplex Duplex For channels configured to output single pulses multiple output pulses can be seen if the pulse length is set below the time of the execution cycle of the controller RECOVERY None The pulse duration should normally be substantially longer than the execution cycle A technical note that recommends appropriate values is available on the Support website www ge ip com support SpvTaskTimeout during sporadic Peer to Peer communications Duplex The SpvTask Timeout may occur on a duplex controller with peer to peer communications starting and stopping and while creating ISaGRAF TCP socket after firmware download and clean flash The controller event log may contain errors such as the following 00349 0000464 329 00B Abort due to SpvTaskTimeout task EXEC 0x27 RECOVERY Controller returns to healthy master after the reset due to the abort Debugger locking up Simplex Duplex The ISaGRAF debugger locks up under certain conditions To avoid this problem only use the ISaGRAF debugger in Config mode Stop the ISaGRAF deb
3. slave The issue occurs only for discrete Modbus registers This issue occurs on the standard controller with firmware v2 x RTU with firmware v2 11 and safety controller with firmware 1 1x and above RECOVERY To avoid this issue select the No Packing option on the Map Remote Device Points dialog in the WorkBench This would ensure that the issue is not encountered For complete information on this issue refer to Field Service Bulletin 100929 Insertion of standby controller causes master abort Duplex On rare occasions inserting an unpowered standby controller into a carrier with an operating master may cause the master to abort and go into failsafe If this occurs the master will record an Abort due to SpvTaskTimeout task in the event log RECOVERY If this occurs power cycle the controller to cause the master to exit failsafe and resume normal operation The master can also be commanded to exit failsafe via software tools such as the IO or Network Configurator After the master is healthy power can be applied to the standby controller Removing power to one controller may cause the second controller to abort Duplex On rare occasions in duplex systems removing power to either the master or standby controller may cause the master to abort and go into failsafe If this occurs the controller in failsafe will record an Abort due to PiReadStateFlags Unstable in the event log This issue occurs
4. PAC8000 8851 LC MT GFK 2569B SafetyNet Logic Controller December 2010 The 8851 LC MT PAC8000 SafetyNet Logic Controller is used for logic control applications in an SIL2 environment It provides Subset of IEC 61131 3 languages Redundancy with bumpless transfer for higher availability Dual redundant high speed Ethernet connections Peer to peer communications between controllers On line configuration Product Documentation PAC8000 Safety Manual 3 3 8000 System Specification Data Sheet PAC8000 SafetyNet Data Sheet 8000 I O 2 2 I O Modules General Purpose and 2 2 Applications Including SafetyNet Instruction Manual INM8100 8000 I O 2x I O Modules 2 1 applications Instruction Manual INM8200 System Specifier s Guide SSG8002 Product documentation can be downloaded from www ge ip com support Release Information PAC8000 8851 firmware release 1 26 for PAC8000 8851 LC MT SafetyNet Controller adds the following features Update for Modbus read load balancing Update for the Register Protection Table For details see Problems Resolved by Release 1 26 on page 2 Updates Existing versions of the 8851 LC MT Controller can be upgraded to version 1 26 using upgrade kit 82A1744 MS10 000 A0 Upgrade kits can be downloaded from the Support website www ge ip com support The upgrade kit is published as a SIM for the PAC8000 Workbench programming package After installing the SIM firmware
5. for the PAC8000 8811 IO DC module ATEX II 3 G Ex nL IIC T4 for the PAC8000 8851 Controller e CSA Class 1 Div 2 Groups A B C D hazardous locations with Temperature Code T4 Refer to Control Drawings SCI 702 and SCI 1005 for the PAC8000 8811 IO DC module Refer to Control Drawings SCI 702 and SCI 957 for the PAC8000 8851 Controller Functional Safety e TUV Rheinland Safety Related Programmable Electronic System suitable for safety related applications up to SIL 2 Applicable Standards e FM Approvals FM 3600 FM 3611 FM 3810 e ATEX Approvals EN 60079 15 2005 e CSA Approvals C22 2 No 0 M91 C22 2 No 142 M1987 C22 2 No 213 M1987 e TUV Rheinland IEC 61508 IEC 61511 EN 50156 1 NFPA 85 EN 61131 2 EN 61010 1 IEC 61326 1 EN 54 2 NFPA 72
6. on units with a date code of 11 3 10 or later RECOVERY If this occurs power cycle the controller to cause the master to exit failsafe and resume normal operation The master can also be commanded to exit failsafe via software tools such as the IO or Network Configurator PAC8000 8851 LC MT SafetyNet Logic Controller 5 GFK 2569B Operational Notes Subject Configuration Description Abort after strategy Simplex Duplex Abort due to SpvTaskTimeout task may occur after strategy download download of a project with a long execution cycle time The controller event log may contain errors such as the following 01835 0000507 07000B 08 14 53 01836 0000507 070 00 B Abort due to SpvTaskTimeout task EXEC 0x27 01837 0000507 07000B 08 14 53 01838 0000507 070 00B Exec 1st control package HISR SYSTEM H 01839 0000507 070 00B Active Task EXEC RECOVERY Download a new strategy with shorter execution cycle time 6 PAC8000 8851 LC MT SafetyNet Logic Controller GFK 2569B Compliance Information For detailed installation and operating procedures refer to the user manual for the module Hazardous Locations e Factory Mutual Class 1 Div 2 Groups A B C D hazardous locations with Temperature Code T4 Refer to Control Drawings SCI 701 and SCI 1004 for the PAC8000 8811 IO DC module Refer to Control Drawings SCI 701 and SCI 956 for the PAC8000 8851 Controller e ATEXII3G Ex nA nL IIC T4
7. ugger when going to Safe mode and do not attempt a connection while the controller is in safe mode RECOVERY Power cycle the controller s Controller aborts during Register Mapping Table download Simplex Duplex While downloading the Register Mapping Table or the Reg Init Values the controller aborts with message Abort due to RtosAlloc NU_Allocate_Memory NU_INVALID_ MEMORY RECOVERY Controller successfully resets after the abort and returns to healthy master or request standby depending on its partner controller s state Downloaded rejected with a CSC_CORRUPT error on peer to peer table Simplex Duplex Strategy download may be abandoned while downloading the Peer to Peer Table with both master and standby offline PAC8000 Workbench logs the following error in the Microsoft Event Log Download Failure Request to AXE timed out Download failed for the following reason Load RIT CRC does not match The controller log also contains the message Download Peer to Peer Table CSC_CORRUPT RECOVERY Re download the strategy 4 GFK 2569B PAC8000 8851 LC MT SafetyNet Logic Controller Subject Configuration Description Invalid data when using packed discrete points in Modbus master Simplex Duplex When the PAC8000 controller is used as a Modbus Master and an option other than No Packing is selected from the WorkBench the controller could return erroneous Modbus values to the
8. upgrades can be done through the Firmware Downloader utility launched from PAC8000 Workbench from PAC8000 SafetyNet controllers 2 PAC8000 8851 LC MT SafetyNet Logic Controller GFK 2569B Compatibility This release replaces all previous versions of the 8851 LC MT Controller firmware PAC8000 Workbench To support all features of 01 26 Workbench 8 3 0 SP1 or later is required Version Requirements Upgrading From Previous Version 1 x PAC8000 SafetyNet controllers can be upgraded to release 1 26 Firmware Versions Downgrade To Previous Downgrading from release 1 26 to previous releases of 1 x is supported for PAC8000 Firmware Versions SafetyNet controllers Problems Resolved by Release 1 26 Subject Configuration Description A Clean Flash command Duplex A Clean Flash command was processed only by the master cleared only the Master controller This had no impact on operation Modbus read load Duplex In previous releases large numbers of Modbus reads could balancing on Duplex cause the master to abort or the standby to refresh in duplex SafetyNet systems This could exhibit in multiple ways The master would abort and record an Abort by other processor log event The standby would record an Abort master rendezvous timeout xx ms at lt xxxxxx gt event The master would record multiple Inter AXE Link Events such as IAL incomplete Rx standby diag 3 size 2 bytes and Inter AXE Link failed retries Tx 0

Download Pdf Manuals

image

Related Search

Related Contents

PRIMO - SABINA  Bose SoundTouch SA-4  Omnitron miConverter 10/100 Plus  NRL_Tecnico (standard-silenziata3)_01_EN.indd  Google Drive  los proyectos hacen los objetos eternos, las modas los  Matériels et conditions pour l`endoscopie en urgence  開講科目名 担当教員 開講区分 単位数 授業のテーマと目標 授業の概要  Verbatim DVD-R Dual Layer Inkjet Printable 12x    