BI series temperature controller user manual 1.Ordering code 2

image

Contents

1. BI series temperature controller user manual Features 3 digit dual display SV value set by key one key for one digit Easy operation and long use life Fuzzy PID control output Economic for simple control 1 Ordering code BI 7 R K Input signal K Ktype P PT100 Q SSR output Output R relay output Dimension 4 48H 48W 6 96H 48W 7 2H 72W 9 9 96H 96W BI series intelligent temperature controller 2 Technical parameters c K K Type input range 0 600 C P PT100 Type input range 0 600 C E E Type input range 0 400 C J J Type input range 0 600 C Cu Cu50 Type input range 0 150 C Resolution Input type Display range Digiti Control mode PID control or ON OFF control set by key Control Relay AC250V3A output SSR DC8 15V Ambient temperature 9 9 100 240VAC DC Customized 45 89 No freezing 3 Mounting dimensions mm FH Foxit PDF Editor Sas REAG c by Foxit 4 2003 2010 lt gt E RAFFE W i som 4 Panel instructions Measure value Set value OUT indicate lamp AT indicate lamp Set Confirm key SET Increase key QaQSeoOWO 5 Operating instructions A SV value setting process Temperature setting Press one of DG keys one of SV digit flashing each press the value keep increasing Stop pressing when you set the value as you want after 4 flashings the new SV set down Remarks If the control temper
2. ature is not good please start AT autotuning function Press SET and No 3 key at the same time AT lamp will be on PV value should not more than 80 of SV vaiue otherwise autotuning run error For example when the SV is100 the PV should less than 80 B Autotuning function Autotuning starts by press SET and No 3 key AT lamp on And finished AT lamp off All parameters can be modified only after autotuning finished C Parameters setting In the measuring estate Press and hold SET key for 5 seconds enter parameter setting area oc om ooo Press SET Press SET 7400 Previous measured value ooe LCK key lock Press 1 2 3 key to modify the mumber then press SET key to confirm The factory setting is 55 When LCK 51 all the parameters are locked except SV and LCK value WHen LCK 55 all the parameters can be modified When LCK not 51 55 all the parameters are locked except LCK value Proportional Band Press 1 2 3 key to modify the mumber then press SET key to confirm Factory set is 0 Range is 0 600 P 0 means it is the position controll ON OFF The larger the proportional band is the slower the system heats Under this condition the time to reach SV is longer f the proportion temperature is too low it will cause oscillation Integral Time Press 1 2 3 key to modify the mumber then press SET key to confirm Factory set is 240 Range is 0 600 l 0 means that it is PD heating system The smaller the integral time
3. ce to avoid interference 3 Attention to Min Max of the input T C Wrong connect probably cause burning out H Foxit PDF Editor Sap REPA c by Foxit 45 2003 2010 RAT Terminal connection Note Please refer w uie prouuci vuinievuuin Ulawiliy AC220V K Remarks 1 Relay capacity AC 3A 250V 2 5SR DC8 15V Max 30mA 7 Caution 1 Installed in the following environments A Atmospheric pressure 86 106Kpa Ambient temperature 0 50 degree Humidity 35 85 no freeze B Dramtic changes in the ambient temperature may cause condensation corrosive flammable gases the main structure of direct vibration or shock water oil chemicals smoke or steam excessive dust pollution salt or metal powders air confitioning blowing straight direct sun thermal radiation accumulation place C Instrument should be stored in dry and ventilated non corrosive gas application with the case of complete package 2 Warranty A Meter sold within one year from the data of billing failure due to manufacturing quality full warranty by the factory responsible for damager caused by improper use of the repair costs from the factory charge a fee 3 About Error A lf the PV display Err or HHH it means it is out of range or TC RTD does not work B If the parameters can not be changed please chec if the LCK value is 55 C The PV value display abnormal fluctuations please increase the parameter FT value
4. is the stronger the integral action is And better for eliminating the bias between it and the setting value f the integral time is too short it may cause oscillation Integral Time Press 1 2 3 key to modify the mumber then press SET key to confirm Factory set is 60 Range is 0 600 D 0 means that it is PI heating system To decrease the derivative time to a proper value can prevent the system from oscillation The bigger the D is the derivative action is Hysteresis value Press 1 2 3 key to modify the mumber then press SET key to confirm Factory set is 3 Range is 1 50 If P not 3 it is unvalid When P 0 HYS 3 and SV IS 100 While the PV 100 it will stop heating lower than 96 it will begin heating Control cycle Press 1 2 3 key to modify the mumber then press SET key to confirm Factory set is 20 Range is 1 255 Relay output T 20 SSR output or SCR output T 1 PV bias amend Press 1 2 3 key to modify the mumber then press SET key to confirm Factory set is 0 Range is 50 50 PV bias applied to amend the bias caused by TC and compensation lead during the measuring process FT filter constant Press 1 2 3 key to modify the mumber then press SET key to confirm Factory set is 100 Range is 0 200 The smaller the filter is the quicker response but it caused fluctuations 6 Connection drawing Connection Caution 1 When input TC should use the corresponding compensation lead 2 Input signal wire should be far alway from other noice sour

Download Pdf Manuals

image

Related Search

Related Contents

Melissa 753-087 User's Manual  LevelOne WAB-3000A  MAGNUM OPERATORS MANUAL - Refurbished Floor Cleaning  impression 12 impression 15 impression 215  Terra 400 / Oceana 400 User Manual - E-SAT  Philips SCF334/12 Data Sheet  VGATonic Guide in Progress - Don`t Quit Your Day Job  B767-200/-300 Manual  Jenn-Air 8.34E+12 Refrigerator User Manual  DNX7280BT DNX5280BT DNX4280BT DNX5580BT  

Copyright © All rights reserved.
Failed to retrieve file