GFK-2785C, PACSystems* RXi Box IPC User`s Manual

image

Contents

1. GG Q Y 9 gt AQ 4 i Zz er O o Qe Qe h gt d 4 PACSystems RXi Box IPC GFK 2785C Introduction Power On Off Switch and Status Indicator Operation Power up the IPC Press and hold the button for at least second If powering up from a no power state the ring LED blinks blue while the IPC is booting and is solid green when the IPC is up and running For ICRXIBN7x000A CA or earlier only If the system has been shut down but power has not been cycled the ring LED immediately turns solid green For all other versions the ring LED blinks blue for 40 seconds before changing to solid green Shut down the IPC Press and hold the button briefly between 100ms and 4 seconds The ring LED stays green while the IPC is shutting down and then turns off when the IPC is powered down Sleep Mode The default BIOS settings when shipped from the factory are e Enable Hibernation is disabled e ACPI Sleep State is S1 CPU Stop Clock The default settings send IPC to sleep state S1 ICRXIBN7x000A The ring LED stays green while the IPC is in Sleep State S1 The ring LED turns off while the IPC is in Sleep State S3 ICRXIBN7x001A The ring LED stays green while the IPC is in Sleep State S1 The ring LED fades blue while the IPC is in Sleep State S3 Forced Shut down Caution Use this option only if the operating system is non responsive Press the button for at least 4 seconds The ring LED turns off
2. following dimensions the bottom Static Latches Top Spring loaded Latches Bottom Backplate Rear View 14 PACSystems RXi Box IPC GFK 2785C I Hardware Installation Install the IPC on the Backplate a Place the IPC and Backplate on a flat surface b Loosen the four captive screws on the IPC s front panel and remove the front panel GFK 2785C PACSystems RXi Box IPC 15 16 Hardware Installation Make sure the top of the IPC is positioned at the top of the Backplate static latches on top For Backplate orientation refer to page 14 Align the IPC s four mounting screws with the mounting holes in the Backplate Using the hex driver tighten the mounting screws der pui a bh a on oe si f Replace the front panel on the IPC and use the screwdriver to hand tighten the four captive screws to secure it a TEL TG l Er E o n ae As 5 e Ume E Una 09 ow dea m x Sk a PE pg D Lea ep lt Ta ov Pr 4 PACSystems RXi Box IPC GFK 2785C Hardware Installation 2 Install the unit on the DIN Rail a Start with the top of the unit rotated approximately 202 from the panel b Engage the spring loaded latches at the bottom of the black DIN rail clip attached to the adaptor on the DIN rail c Rotate the unit up and press it upward to engage the top static latches with the rail d Press the unit into place GFK 2785C
3. unit i stesskenomesmdenseg O Applies only to IPCs with solid state hard drive ICRXIBNxEOOxA For ambient temperatures greater than 50 C 122 F the unit must be installed in a restricted access area as defined below If the Box IPC is operating in ambient temperatures greater than 50 C 122 F its exterior temperatures may be too hot to touch safely To avoid burn hazards the unit must be installed in a restricted access area as defined by Access can only be gained by service persons or by users who have been instructed about the reasons for the restrictions applied to the location and about any precautions that shall be taken and Access is through the use of a tool or lock and key or other means of security and is controlled by the authority responsible for the location Pollution Degree 2 A Pollution Degree 2 environment as defined by UL60950 1 Pollution Degree 2 applies where there is only non conductive pollution that might temporarily become conductive due to occasional condensation Note For additional product standards and agency approvals refer to Appendix A GFK 2785C PACSystems RXi Box IPC 3 Introduction RXi Box IPC User Features Power On Off Audio Indicators Switch and Status Connector Indicator SD Card Slot Blue blinking Booting Blue slow fade S3 Sleep Green solid Running Red solid Fault Connectors Di DI 24 VDC sie iu V COM A PA
4. are technically equivalent to the IEC 61000 4 x series GFK 2785C PACSystems RXi Box IPC ST Product Certifications and Installation Guidelines for Conformance Government Regulations The FCC requires the following note to be published according to FCC guidelines Note This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his or her own expense Note Changes or modifications to this unit that are not expressly approved by GE Intelligent Platforms could void the user s authority to operate the equipment Industry Canada requires the following note to be published Note This Class A digital apparatus complies with CAN ICES 3 A NMB 3 A 38 PACSystems RXi Box IPC GFK 2785C Index Air flow 11 Audio jack 28 Battery real time clock RTC 21 Clearances 13 Connectors audio jack 28 Ethernet 26 overview 4 power 8 25 SD card slot 28 se
5. of this manual Before you attempt to power up the IPC for the first time inspect the unit for loose or damaged components If damage is observed for example in the form of bent component leads or loose components contact GE Intelligent Platforms for additional instructions Depending on the severity of the damage it may be necessary to return the product to the factory for repair Do not apply power to the unit if it has visible damage Applying power to a unit with damaged components may cause additional damage GFK 2785C PACSystems RXi Box IPC Initial Startup Unpacking and Initial Startup You will need the following 24VDC 18 32V range 48W power supply Class 2 or LPS The product is supplied with a Phoenix Contact part number 1827716 or 1851245 spring loaded quick release power terminal block for use with a power supply The power supply used must be a UL Listed or equivalent Limited Power Source LPS or Class 2 power source Power cord with 28 AWG 16 AWG wires VGA compatible video monitor USB compatible keyboard USB compatible mouse optional Attach the power supply output to the IPC s DC power plug using 16 to 28 AWG 1 31 to 0 08mm For frame ground use shortest length 16 AWG 1 31mm wire to ground Recommended wire stripping length is 7mm 0 28 in Tighten the screws that hold the wires to a torque of FGND OV 24V 4 in Ib 0 452 Nm Insert the plug into the IPC s Input Po
6. page 25 28 PACSystems RXi Box IPC GFK 2785C Chapter System Recovery 5 Recovering from a Drive Failure ICRXIBN7x000x Models only To recover from a drive failure you will need to re install the operating system and the device drivers that are provided by GE Intelligent Platforms Windows Operating System To re install the Windows 7 Professional operating system refer to http windows microsoft com for instructions RXi Box IPC Device Drivers The drivers and the instructions for installing them are available on the GE Intelligent Platforms Support website http support ge ip com The drivers consist of Ethernet drivers two SD card reader driver VIA Graphics driver Note This improves resolution of the standard Windows graphics driver and is necessary to support sleep states but is not necessary for operation of a standard video monitor DT audio codec driver Custom GE IP drivers six GFK 2785C PACSystems RXi Box IPC 29 System Recovery Recovering from a Drive Failure ICRXIBN7x001x Models only A USB Drive is shipped along with the Windows Embedded Standard 7IPC unit Retain it ina secure location Use this drive to recover in the event of drive failure The procedure is as follows 1 Power down the RXi system 2 Insert the USB recovery Flash Drive in any available USB port 3 Power on system a As soon as the system turns on press the lt F7 gt key to display the boot device
7. powering off using the On Off switch by changing the setting of SW1 1 located on the underside of the IPC s front panel This prevents unplanned shutdowns caused by accidentally pressing the On Off switch The disabled setting affects only the ability to power down the unit You can still use the On Off switch to power on the unit You will need the following One flat or large Phillips screwdriver 1 Turn off or remove the power supplying the IPC 2 Loosen the four captive screws on the IPC s front panel and remove the front panel 3 Move the SW1 1 switch from the default Off position to the On position Seis ae TO Sr cme os A beeete ON CEK SDA04 o LEEI PREG SI 14 gt e een oa 3 f X SW1 1 Switch Shown in default Off position 4 Replace the front panel on the IPC and hand tighten the four captive screws to secure it GFK 2785C PACSystems RXi Box IPC 23 24 Hardware Installation PACSystems RXi Box IPC GFK 2785C Chapter Connectors and Cabling 4 This chapter describes the connector layout and cabling requirements on the RXi box IPC Power and communication connectors are described in this section All connectors are provided on the bottom panel of the IPC Summary of Cabled Ports Port Name Usage Maximum Cable Length Shielding Required Revo Femanent amst we cavia remanen 76 mas CITE COTTI N auto Maintenance ams fm Shielding
8. without first shutting down Windows This provides some protection against unplanned shutdowns caused by accidentally pressing the switch To totally disable power off you can use the hardware switch setting as noted below If a hard shutdown is acceptable you can change the OFF button to a 4 second press time through Windows 7 settings as follows 1 D RD Note 10 Start the Windows 7 Control Panel Select Hardware and Sound section if displayed Select Power Options Select Choose what the power buttons do Change the When I press the power button selection to Do Nothing Save the changes To totally disable power off you can set a switch that is located on the underside of the front panel This disables the ability to shut down the IPC using the On Off switch and prevents unplanned shutdowns caused by accidentally pressing the On Off switch For more information see Disabling the Off Switch in chapter 3 PACSystems RXi Box IPC GFK 2785C Hardware Installation Chapter 3 This chapter describes the procedures for the safe location and securing of the RXi Box IPC Note The proper method for removing power from the unit is to switch off power at the circuit breaker Installation Guidelines The RXi Box IPC can be mounted on a DIN rail using the optional Backplate ICRXIACCBPL or directly onto a panel Mounting methods are described on pages 14 through 19 m The IPC must be mounted with its cooling fi
9. EE RE E T E 12 Mounting MN ee 12 Dimensions and Clearances for Installation 13 MP 14 Mounting the IPC DNR Mu 4pvvvs iaia 14 Mounting the IPC on a Panel Using a Backplate 18 Mounting the IPC Directly on a Panella 19 FTBS 21 DENS 23 oe TL Jr 25 Duri 25 Ethernet Communication Portssizzonini iaia pioneer prati 26 NS 27 VER 21 VIGGO OUUTE OTE eraka EEE NE ENE EN 28 SD Gecure Digital Card Ne andel 28 UO OR AO E NE EE EE A 28 IRON coil a 29 Recovering from a Drive Failure ICRXIBN7x000x Models OnlyY rr 29 Recovering from a Drive Failure ICRXIBN7x001x Models only rr 30 Recovering from an Overtemperature Shutdown All Models 33 Product Certifications and Installation Guidelines for Conformance cccccceeeeeeeeeeeeeeeeeeeeeees 35 ATNA a 36 Standards OE GA W ssa SEN E 37 EMC Emissions and Immunity Specifications 37 G vemment Regulations Leke 38 O AA 39 GFK 2785C PACSystems RXi Box IPC iii Chapter 1 Introduction The PACSystems RXi family of industrial computers provides an advanced high performance control and computing platform The PACSystems RXi Box IPC delivers the flexibility of a PC with the industrial ruggedness of traditional automation controllers Built with an open and scalable architecture the RXi platform enables easy connectivity and allows you to maximize applica
10. GE Intelligent Platforms Industrial Computer Products PACSystems RAI BOX IPC User s Manual GFK 2785C May 2014 GFL 002 Warnings Cautions and Notes GFK 2785C as Used in this Publication Warning notices are used in this publication to emphasize that hazardous voltages currents temperatures or other conditions that could cause personal injury exist in this equipment or may be associated with its use In situations where inattention could cause either personal injury or damage to equipment a Warning notice is used Caution notices are used where equipment might be damaged if care is not taken Note Notes merely call attention to information that is especially significant to understanding and operating the equipment This document is based on information available at the time of its publication While efforts have been made to be accurate the information contained herein does not purport to cover all details or variations in hardware or software nor to provide for every possible contingency in connection with installation operation or maintenance Features may be described herein which are not present in all hardware and software systems GE Intelligent Platforms assumes no obligation of notice to holders of this document with respect to changes subsequently made GE Intelligent Platforms makes no representation or warranty expressed implied or statutory with respect to and assumes no responsibility for the acc
11. PACSystems RXi Box IPC I7 Hardware Installation Mounting the IPC on a Panel Using a Backplate You will need the following Four machine screws with maximum thread size 20 standard or M6 metric Driver for selected machine screws One ICRXIACCBPL Backplate 1 Install the IPC on the Backplate See step 1 on page 14 2 Drill four holes in the panel based on screw selection using the spacing shown in the following drawing if holes are tapped recommended minimum panel thickness should be equal to thread diameter Drilling Pattern for Panel Mounting Using a Backplate pm o e 119 4mm 4 7 3 Using the four mounting screws attach the IPC Backplate assembly to the panel 18 PACSystems RXi Box IPC GFK 2785C Hardware Installation Mounting the IPC Directly on a Panel You will need the following One flathead or large Phillips screwdriver One 2 5mm hex driver included with the RXi IPC 29 0 116 drill bit and M4x0 7 tap The IPC has four captive machine screws in its base for attaching the unit to the panel 1 Drill four mounting holes using the spacing shown in the following drawing and tap M4x0 7 thru Drilling Pattern for Direct Panel Mounting 1 1 mm 6 76 M4 Thru CT 95 5mm 3 76 2 Place the IPC on a flat surface 3 Loosen the four captive screws on the IPC s front panel and remove the front panel GFK 2785C PACSystems RXi Box IPC 19 Hardware Installation 4 Align
12. Port connector is mapped as follows ICRXIBN7x000A CA ICRXIBN7x000A CA versions and earlier and ICRXIBN7x000A CA versions and earlier om o COM1 ICRXIBN7x001A Two ports are provided for connection of USB 2 0 compatible devices such as a keyboard mouse serial Communications or data storage device For maximum cable length refer to page 25 Double shielded cable that complies with USB 2 0 must be used Note These USB ports are defined as maintenance ports and are intended to be used only as temporary connections USB Pin Assignments Current Limited 5VDC Pin 1 GFK 2785C PACSystems RXi Box IPC e7 Connectors and Cabling Video Output Port Video monitor output is provided on the standard 15 pin VGA connector The pin assignments are shown in the following table Shielded cable is required For maximum cable length refer to page 25 Video Pin Assignments GND pe RedGND gt ei ae There is a 1 1A self resetting fuse on the 5V signal pin 9 SD Secure Digital Card Slot Audio Jack The IPC accommodates a user supplied SD card for auxiliary storage Note The SD card slot is defined as a maintenance port and is intended to be used only asa temporary connection The IPC provides an Audio out Microphone in 3 5mm four pin TRRS combo jack Note The Audio jack is defined as a maintenance port and is intended to be used only as a temporary connection For maximum cable length refer to
13. The ring LED displays solid red to indicate a fault including Overtemp condition IPC Status Indicators Operation SATA Drive Status White blinking Read write access on SATA drive Overtemp Red solid The IPC s internal temperature has exceeded the maximum allowable value To recover let the IPC cool then press the Power On Off switch Ethernet Port LEDs Operation Each Ethernet port has two LED indicators ACTIVITY and LINK ACTIVITY D Blinking Green Traffic is detected at the port GFK 2785C PACSystems RXi Box IPC 5 Introduction Resume Power Mode Operation after Power loss press the button Start the unit Last state The chipset remembers the last state After restoring power A clean Win7 shutdown requires user to press the button to start the unit The unit will restart without the button press if power is cycled without a clean Win7 shutdown For ICRXIBN7x000A CA or earlier unit always operates in Last state despite UEFI setting Sleep Mode Setting Options and Ring LED Status Indicator Operation UEFI UEFI Start gt Power Timeout to Recovers by Hibernation Sleep State Shutdown gt Button to Sleep pressing Setting Setting Sleep Sleep Disabled S3 Suspend to RAM Solid Green Solid Green Blue Fade Keyboard button Enabled S3 Suspend to RAM Blue Fade Blue Fade Blue Fade Keyboard button Enabled S1 CPU Stop Clock Solid Green Solid Green Solid Green Keyboard button Default UEFI settings are Hi
14. bernation Disabled and Sleep State to S1 6 PACSystems RXi Box IPC GFK 2785C Chapter Unpacking and Initial Startup 2 This chapter contains information you need to perform a pre installation check of your RXi Box IPC Before installing and using the IPC the following steps should be completed Unpacking and Inspection Initial Startup Configuring Ethernet Communications Unpacking and Inspection Upon receiving your RXi Box IPC carefully inspect all shipping containers for damage If any part of the system is damaged notify the carrier immediately The damaged shipping container should be saved as evidence for inspection by the carrier As the consignee it is your responsibility to register a claim with the carrier for damage incurred during shipment However we will fully cooperate with you should such action be necessary After unpacking the Box IPC record all serial numbers Serial numbers are required if you need to contact Customer Care during the warranty period All shipping containers and all packing material should be saved should it be necessary to transport or ship any part of the system Verify that all components of the system have been received and that they agree with your order If the system received does not agree with your order contact Customer Care If you need technical help contact Technical Support For phone numbers and email addresses see the Contact Information page in the front
15. down recovery 33 storage 3 Unpacking and inspection 7 USB ports 27 Vibration 3 Video output 28 Weight 2 GFK 2785C PACSystems RXi Box IPC 39
16. e For Ethernet port and cabling information refer to chapter 4 Pinging TCP IP Ethernet Interfaces on the Network PING is the name of a program used on TCP IP networks to test reachability of destinations by sending them an ICMP echo request message and waiting for a reply Most nodes on TCP IP networks including the PACSystems Ethernet Interface implement a PING command You should ping each installed Ethernet device When the Ethernet device responds to the ping it verifies that the device is operational and configured properly Pinging the Ethernet Interface from a UNIX Host or Computer Running TCP IP Software A ping command can be executed from a UNIX host or computer running TCP IP most TCP IP communications software provides a ping command or from another Ethernet device When using a computer or UNIX host you can refer to the documentation for the ping command but in general all that is required is the IP address of the remote host as a parameter to the ping command For example at the command prompt type ping 10 0 0 1 Determining if an IP Address is Already Being Used Note This method does not guarantee that an IP address is not duplicated It will not detect a device that is configured with the same IP address if it is temporarily off the network It is very important not to duplicate IP addresses To determine if another node on the network is using the same IP address GFK 2785C PACSystems RXi Box IPC 9 Unpackin
17. g and Initial Startup Disconnect your industrial computer from the LAN Ping the disconnected industrial computer s IP address If you get an answer to the ping the chosen IP address is already in use by another node You must correct this situation by assigning a unique IP address Shutting Down the Computer For ICRXIBN7xxxxx Models to avoid damaging files always shut down Windows software before removing power from the IPC For ICRXIBN7xxxxx Models do not disconnect external devices such as a flash drive or external DVD drive without first using the Windows Safely Remove Hardware feature to eject the device Failure to observe this precaution could result in damage to data To shut down the IPC press the Power On Off switch briefly between 100ms and 4 seconds or select Shut Down from the Windows Start menu This provides a controlled shutdown of the operating system before removing power from the system The status indicator stays solid green while the IPC is shutting down and then turns off when the IPC has finished powering down To completely shut down the IPC turn off or remove the power supplying the IPC Disabling Operating System Shutdown ICRXIBN7xxxxx Models The current On Off button operation requires only a 100ms press to begin a controlled Windows shutdown You can change this setting in Windows to require pressing the On Off switch for 4 seconds to immediately perform a hard shutdown that forces the unit off
18. he power cable 2 Loosen the four captive screws on the IPC s front panel and remove the front panel 3 Remove the IPC from its mounting location and place it on a static safe surface 4 Remove the four Phillips head screws that secure the interior lid to the IPC chassis then lift off the interior lid GFK 2785C PACSystems RXi Box IPC 21 Hardware Installation 5 Remove the RTC battery from the retaining clip being careful to not bend the positive terminal clip RTC Battery f en Topi o O A Aa Use of a different type of battery than that specified here may present a risk of fire or explosion Battery may explode if mistreated Do not recharge disassemble heat above 100 C 212 F or incinerate Note For proper disposal refer to Battery Disposal document 82A1540 MDOL 6 Install the new battery in the retaining clip The replacement battery must be IC690ACC001 from GE Intelligent Platforms Install the battery with the positive side up That is with the side away from the circuit board The coin cell must be inserted at an angle to go under the positive terminal clip and then slid into the carrier and snapped into place 7 Replace and secure the interior lid with four Phillips head screws 8 Replace the front panel on the IPC and hand tighten the four screws to secure it 22 PACSystems RXi Box IPC GFK 2785C Hardware Installation Disabling the Off Switch You can disable
19. hen shutdown occurred If you initiate a complete power cycle instead of restarting immediately the Box IPC performs the normal power up cycle GFK 2785C PACSystems RXi Box IPC DI 34 System Recovery PACSystems RXi Box IPC GFK 2785C Appendix product Certifications and Installation A Guidelines for Conformance This appendix describes the compliance markings that appear on PACSystems RXi industrial computer products and the corresponding standards to which the products have been certified GFK 2785C PACSystems RXi Box IPC tia Product Certifications and Installation Guidelines for Conformance Agency Approvals Agency Description Standard or Comments Marking N A Safety for Information Technology Certification by Underwriter s Laboratories to UL Equipment C US LISTED 60950 1and CSA 60950 1 Low Voltage Directive C E Self Declaration in accordance with European European Safety for Industrial Control Directives Refer to Declaration of Conformity Equipment found at http www ge ip com for a complete list of approved products Electromagnetic Compatibility Self Declaration in accordance with European Directive Directives Refer to Declaration of Conformity European EMC for Industrial Control found at http www ge ip com for a complete Equipment list of approved products Note The agency approvals listed above and on the Declaration of Conformities are believed to be accurate however a product s agency ap
20. i is required to be in compliance with the standards identified in Appendix A Can be permanently connected while the system is running Intended only for temporary connection Input Power The IPC requires 24VDC 18 32V range 48W power supply Class 2 or LPS The IPC is supplied with a Phoenix Contact part number 1827716 or 1851245 spring loaded quick release power terminal block for use with a power supply The power supply used must be a UL Listed or equivalent Limited Power Source LPS or Class 2 power source FGND OV 24V Power cord with 28 AWG 16 AWG wires To connect the DC power supply refer to Initial Startup in chapter 2 Note There are no user serviceable fuses in the IPC GFK 2785C PACSystems RXi Box IPC 25 Connectors and Cabling Ethernet Communication Ports ACTIVITY LINK The IPC provides two RJ 45 Ethernet network port LED LED connectors that support 10BASE T 100BASE TX and 1000BASE T communications Either or both of these ports may be attached to other Ethernet devices Each port automatically senses the data rate 10 100 or 1000Mbps duplex half duplex or full duplex and cabling arrangement straight through or crossover of the attached link The two ports on the Ethernet Interface must not be connected directly or indirectly to the same device The hub or switch connections in an Ethernet network must form a tree otherwise duplication of packets
21. l SAN dd NN Ill LN ina m m HALEN AL i i HM NCR Da _ M WES7 Recovery Exit the Program Click OK to continue the recovery and image the system hard drive The drive will be reformatted in the process GFK 2785C PACSystems RXi Box IPC si System Recovery 7 The image load process will be displayed as follows BD tsa y DA ve Gujrat 8 When the image load completes the system will prompt to remove the USB drive IMOgination at work RXi Recovery Solution se 5 This program will recover Windows Embedded Standard 7 on your Rxi computer ring this process ALL DATA stored on your Hard Disk will be DELETED Please backup necessary files before starting to recover he Recovery Process USB Recovery Solution x Please remove the USB Stick and Press OK The System will reboot Start WES7 Recovery Exit the Program 9 Remove the USB drive and click OK The system will reboot as a new factory install 37 PACSystems RXi Box IPC GFK 2785C System Recovery Recovering from an Overtemperature Shutdown All Models If the Box IPC overheats it will shut down to protect critical components When this happens the Overtemp LED will blink on red and then shut off quickly while the entire unit shuts down The Power On Off LED turns off at the same time To recover let the Box IPC cool and then press the Power On Off button to restart The Box IPC will return immediately to what it was doing w
22. may result Ethernet Media The IPC can operate on 10BASE T 100BASE TX or 1000BASE T media via its network ports All three arrangements can use up to 100m of twisted pair cable between each node and a switch hub or repeater Note For all three types shielded twisted pair STP cable is required to maintain CE compliance 10BASE T Two pairs of wire are used one for transmission and the other for receive 100BASE TX Two pairs of wire are used one for transmission and the other for receive 1000BASE T Four pairs of wire are used for simultaneous transmission and receive in both directions Ethernet Port Pin Assignments RO RecemeData ere Bidirectional pare Note Pin assignments are provided for diagnostic purposes only Ethernet cables are readily available from commercial distributors We recommend purchasing rather than making cables The operation of the Ethernet port LED indicators ACTIVITY and LINK is described in chapter 1 26 PACSystems RXi Box IPC GFK 2785C Connectors and Cabling Serial Communication Port USB Ports The serial port provides RS 232 communications through a standard RJ 45 female connector with the following pin assignments For maximum cable length refer to page 25 RS 232 Serial Port Pin Assignments No connection o a Re Tie Notes The RJ 45 connector shell provides frame ground To reduce interference shielded cables are required The Serial Communication
23. mm ea x 5 39 in x 0 47 in IPC without IPC without Backplate _ 1 814 Kg 1 814 Kg 4lbs Ibs Backplate 0 454 Kg 1 Ib 1 0 GHz VIA Eden dual core processor Non volatile storage 32GB mSATA SSD or 250GB SATA drive Non volatile storage NVS can retain data indefinitely without loss of data integrity Time of day clock RTC Maximum drift of 2 seconds day at 25 C accuracy Elapsed time clock internal 0 01 maximum timing accuracy Video wooo ports Standard 15 pin VGA connector Two Type A USB 2 0 SD standard card slot Dual function Audio out Microphone in jack 3 5mm four pin TRRS Power requirements 1 8 A at 24 VDC 18 32 VDC LPS or Class 2 power supply required Serial Communications One RS 232 RJ 45 port ICRXIBN7x000A CA versions and earlier COM2 ICRXIBN7x001A COMI Two Ethernet 10 100 1000 Mbit s RJ 45 ports Intended only for temporary connection PACSystems RXi Box IPC GFK 2785C Introduction Environmental Specifications Note The Box IPC shall be installed in a location that is not exposed to corrosive gases or liquids rain or direct sunlight and that meets the environmental specifications listed below Vibration IEC60068 2 6 10 57 Hz 0 006 in displacement peak peak 57 500 Hz 1 0 g acceleration Ambient Operating Temperature ICRXIBNXEOOXA 25 C to 65 C inlet 13 F to 149 F ICRXIBNXMOOXA 0 C to 40 C inlet 32 F to 104 F Sorge Tenersi oosa OO
24. ns vertical to ensure adequate airflow m The panel should be capable of supporting the weight of the industrial computer without distortion to the panel m Adequate airflow around the exterior of the unit is essential to maintain safe interior temperature of the unit Inlets and outlets must not be obstructed For details see page 13 m You may need to allow more space for installation of cables and connectors than what is required for heat dissipation To avoid impacting mechanical reliability and signal quality cable installation must comply with the minimum bend radius specified by the cable manufacturer GFK 2785C PACSystems RXi Box IPC 11 Hardware Installation Grounding Note These grounding connections serve as a path for reducing noise interference and radiated emissions and are required for the IPC to comply with the standards identified in Appendix A The DIN rail or panel the IPC is mounted on must have a safety ground connection to protective earth This ground wire must be at least 16 AWG 1 31mm and should be as short as possible If using the ICRXIACCBPL to mount the Box IPC add a ground wire from the M8 threaded hole on the metal DIN Backplate M8 screw included to protective earth The frame ground connection on the power plug must be a 16 to 28 AWG 1 31to 0 08mm wire with shortest possible length It is recommended that these ground wires terminate in a star wiring pattern at the same grounding poin
25. p by following the on screen prompts The Windows 7 product key is printed on the Microsoft Certificate of Authenticity label located on the right side of the IPC PACSystems RXi Box IPC GFK 2785C Unpacking and Initial Startup 8 To activate the operating system online you will need to first configure the IPC s Ethernet settings for operation on your network Note The ICRXIBNOE000A and ICRXIBNOMOOOA models come with two hard drive options a blank 32GB mSATA solid state drive or a blank 250GB SATA magnetic hard drive You will need to load the desired operating system and associated drivers to fully utilize the I O interfaces Configuring Ethernet Network Communications Before configuring your industrial computer for operation on a network consult your network administrator Duplicate TCP IP addresses and duplicate computer names on the same network can cause network problems Default Factory settings are to obtain an IP address automatically 1 For both ports if necessary use the operating system s network configuration tool to change the IP address and subnet mask from the factory settings to the correct settings for your network If your network s IP addresses are controlled by a DHCP server the setting should be Obtain an IP address automatically Port Network Adapter Name VIA Velocity Intel 82574L 2 When prompted by the operating system restart the IPC 3 Connect the IPC to your Ethernet network Not
26. pport Email support cn ip ge com China support jp ip ge com Japan support in ip ge com remaining Asia customers Customer Care Email customercare apo ip ge com customercare cn ip ge com China li PACSystems RXi Box IPC GFK 2785C Contents Contents EM OCG 11 OO EE estensnceeet l DLE Shia E E E E E EA E E O E N 2 NNN 2 Environmental Specifications ui 3 RXi Bog IPC User EE a aaraa esarri 4 Power On Off Switch and Status Indicator Operation rrrrrrnnrrvnnvnnnvvrrnnnnnnnnnnnennrrrrrrnnnnrrrrnnnnnn 5 IPC Status Indicators Operation 5 Ethernet Port LEDs Ope ram ws cicsccscsasssesasasinsdesengencdgatasoneterseanunasneadesansansdbehanenebaaunseatanoaidesensienets 5 Resume Power Mode Operation cccccccccccccccceessssseseeeeececeeeeeeeeeeeanaesseeseeseeeeceeeeeeeeeaeaaaaeeaenses 6 Sleep Mode Setting Options and Ring LED Status Indicator Operation 6 Unpacking and Initial Startup ii 7 Unpacking atid IRSPeeHof acala ire n 7 ESE FIR RS EE 8 Configuring Ethernet Network Communications 9 Pinging TCP IP Ethernet Interfaces on the Network 9 SMU Chine Deyn OK ila 10 Disabling Operating System Shutdown ICRXIBN7xxxxx Models rrrrrvvrvrvrrvvvrrrrrrrrsrsrrrsrsnene 10 Hardware TG CANARIO RARE SAR RR RC RS ER 1 Wiis ENG LS icona EE EE RE 1 CHOU 110 1 EE
27. provals should be verified by the marking on the unit itself 36 PACSystems RXi Box IPC GFK 2785C Product Certifications and Installation Guidelines for Conformance Standards Overview For environmental specifications refer to chapter 1 EMC Emissions and Immunity Specifications EMC EMISSIONS Emissions CISPR 11 EN 55011 30 1000 MHz radiated Group 1 Class A EN55016 2 3 FCC 47CFR15 30 7500 MHz radiated Class A CISPR 22 EN55022 30 6000 MHz radiated Class A EMC IMMUNITY EN55024 CISPR 24 RF Susceptibility EN 61000 4 3 1kHz sine wave 80 AM 10 V m 80 1000 MHz 3 V m 1 0 2 0 GHz 1 V m 2 0 2 7 GHz Fast Transient EN 61000 4 4 DC Input 2 kV 33 nF direct Video and Ethernet ports shielded 1 1 kV capacitive clamp RS 232 port unshielded 1 1 kV capacitive clamp Surge EN 61000 4 5 DC Input 0 5 kV 12 ohms CM 0 5 kV 2 ohms DM Ethernet port shielded 1 0 kV 2 ohms CM Conducted RF Immunity EN 61000 4 6 DC Input 10 V CDN Video and Ethernet ports shielded 10 V current clamp RS 232 port unshielded 10 V current clamp Magnetic Field Immunity EN61000 4 8 50 and 60 Hz 30 A m Damped Oscillatory Wave EN 61000 4 18 DC Input 2 5kV 1 MHz CM DM Video and Ethernet ports shielded 2 5 kV 1 MHz CM RS 232 port unshielded 2 5 kV 1 MHz CM 1 Applies only to IPCs with magnetic hard drive ICRXIBNxMOOxA 2 EN 61000 4 x series of tests
28. rial 27 USB 27 video 28 Declaration of Conformities 36 Determining if an IP address has been used 9 Dimensions 2 mounting 13 Disabling controlled shutdown of OS 10 Disabling the Off Switch 23 Drivers re installing 29 30 Environmental specifications 3 Ethernet ports configuring 9 connectors 26 FCC notice 38 Features 4 Grounding 12 Humidity 3 Indicators Ethernet 5 26 IPC status 5 module 4 power 5 6 Initial startup 8 Installation directly on a panel 19 guidelines 11 ona DIN rail 14 space required 13 IP address Determining if already used 9 LEDs Ethernet port 5 26 IPC status 5 module 4 power 5 6 Mounting dimensions 13 DIN rail 14 orientation 12 panel direct 19 panel with a Backplate 18 space required 13 Network communications configuration 9 Part numbers 2 Pinging the TCP IP interfaces on the network 9 Ports audio jack 28 Ethernet 26 overview 4 SD card slot 28 serial 27 USB 27 video 28 Power connecting 8 25 disabling the Off switch 23 requirements 2 Recovery drive failure models with Windows operating system 29 30 overtemperature shutdown 33 RFI standards 38 RTC battery replacing 21 SD card slot 28 Serial ports 27 Shock 3 Shutting down the computer 10 disabling controlled shutdown of OS 10 Specifications 2 SW1 1 23 Technical Support ii Temperature Ambient Operating 3 overtemperature LED 5 overtemperature shut
29. select menu Please select boot device JN ADATA SP800 TOSHIBA MSFT NORB lt Enter Setup t and 4 to move selection ENTER to select boot device ESC to boot using defaults b Use the arrow keys TN too select TOSHIBA MSFT NORB press lt Enter gt to select 30 PACSystems RXi Box IPC GFK 2785C System Recovery 4 The RXi will boot to the Window PE WinPE on the USB drive This will take a minute Wait for the RXi recovery screen to appear ROG Recovery Solution This program will recover Windows Embedded Standard 7 on your Rxi computer During this process ALL DATA stored on your Hard Disk will be DELETED Please backup necessary files before starting to recover Please do not remove the USB Drive from your Computer after starting the Recovery Process A tako v 5 Click the Start WES7 Recovery button Note clicking the Exit the Program button will abort the recovery and reboot the RXi computer 6 A warning message will be displayed RX Recovery Solution ogram will recover Windows Embedded Standard 7 on your Rad compi ALL DATA stored on your Hard Disk will be DELETED Please backu before starting to recover di eee s retrerte fosti es weratrenizrrd mer MESSER md ganske pori bebe id ecesas aap Pep ind IMI POZZI ZAN U4 ert INA IH ASI DTT odd HHEH AHHAA LEA LEN rbt oso DAA OA ARE Danby ob BRAD BA P miti Solution sure you want to continue ALL DATA ON DRIVE C wu Eos a Aa ae He i
30. t Mounting Orientation The cooling fins on the back of the IPC must be vertical However the unit can be mounted with the front panel connectors oriented either up or down Correct Incorrect 12 PACSystems RXi Box IPC GFK 2785C Hardware Installation Dimensions and Clearances for Installation Dimensions IPC 191 8 mm x 115 6 mm x 81 3 mm 7 55 in x 4 55 in x 3 2 in Backplate 226 mm x 137 mm x 12 mm 8 90 in x 5 39 in x 0 47 in Minimum clearances for heat dissipation Each side 51mm 2 inches Top and bottom 127mm 5 inches 51 mm 191 8 mm 51 mm lt q A n 2 7 55 gt 2 137 mm 5 39 127 mm 226 mm 5 8 90 GFK 2785C PACSystems RXi Box IPC 153 Hardware Installation Mounting Procedures Using the optional ICRXIACCBPL Backplate the IPC can be mounted on a DIN rail or a panel You can also mount the IPC directly onto a panel without using a Backplate The IPC has four captive machine screws in its base for attaching the unit to the Backplate or panel Mounting the IPC ona DIN Rail You will need the following One 2 5mm hex driver included with the RXi IPC One flathead or large Phillips screwdriver One Backplate ICRXIACCBPL When installed on the Backplate the IPC mounts to a standard EN 50022 DIN rail with the 35 oo ro 75 Backplate Orientation The Backplate should be installed with the static latches on top and the spring loaded latches at
31. the IPC s four mounting screws with the mounting holes in the panel 5 Using the hex driver hand tighten the mounting screws 2 LA 7 6 Replace the front panel on the IPC and hand tighten the four screws to secure it 20 PACSystems RXi Box IPC GFK 2785C Hardware Installation Replacing the RTC Battery The real time clock is backed up by a lithium coin cell battery IC690ACC001 The RTC battery has an estimated life of 5 years and must be replaced every 5 years on a regular maintenance schedule There are no diagnostics or indicators to monitor RTC battery status If the RTC battery fails the CPU date and time is reset to 12 00 AM 01 01 2008 at startup The CPU operates with a failed or missing RTC battery however the initial CPU TOD clock information will be incorrect Caution To avoid damage from electrostatic discharge adhere to the following precautions when opening the IPC enclosure e Wear a properly functioning antistatic strap and be sure that you are fully grounded Never touch any components inside the IPC unless you are wearing an antistatic strap e The IPC should be placed on a static safe surface facilitated by antistatic mats e Extra caution should be taken in cold dry weather when static charges can easily build up You will need the following One flat or large Phillips screwdriver One small Phillips screwdriver IC690ACC001 battery 1 Remove power from the IPC by disconnecting t
32. tion reusability supporting your current and future needs for business growth These small form factor industrial PCs provide a number of features to support computing applications in demanding environments m Dual core 1 0 GHz VIA processor m Multiple Gigabit Ethernet interfaces provide network implementation flexibility m Built in Data Storage Internal disks provide highly reliable local long term data retention m USB and SD Card interfaces enable program loading serial communications and removable data storage via standard devices GFK 2785C PACSystems RXi Box IPC Specifications Part numbers ICRXIBN7EQOOA ICRXIBN7EOO1A ICRXIBN7MO000A ICRXIBN7MOOTA ICRXIBNOEOOOA ICRXIBNOMO00A ICRXIACCBPL IC690ACC001 General Specifications Dimensions Weight Processor Introduction RXi Box IPC with Embedded 32GB mSATA SSD and Windows 7 Professional SP1 or later operating system RXi Box IPC with Embedded 32GB mSATA SSD and Windows Embedded Standard 7 RXi Box IPC with 250GB Magnetic SATA Hard Drive and Windows 7 Professional SP1 or later operating system RXi Box IPC with 250GB Magnetic SATA Hard Drive and Windows Embedded Standard 7 RXi Box IPC with Embedded 32GB mSATA SSD RXi Box IPC with 250GB Magnetic SATA Hard Drive Optional Backplate for DIN rail mounting Real Time Clock RTC battery included with IPC IPC 191 8mm x 115 6mm x 81 3mm 7 55 in x 4 55 in x 3 2 in Backplate 226 mm x 137 mm x 12
33. uracy completeness sufficiency or usefulness of the information contained herein No warranties of merchantability or fitness for purpose Shall apply indicates a trademark of GE Intelligent Platforms Inc and or its affiliates All other trademarks are the property of their respective owners Copyright 2014 GE Intelligent Platforms Inc All Rights Reserved PACSystems RXi Box IPC Contact Information If you purchased this product through an Authorized Channel Partner please contact the seller directly General Contact Information Online technical support and GlobalCare p support ge ip com i htt Additional information http www ge ip com Solution Provider solutionprovider ip ge com Technical Support If you have technical problems that cannot be resolved with the information in this guide please contact us by telephone or email or on the web at http support ge ip com Americas Europe the Middle East and Africa Online Technical Support http support ge ip com EMEA Direct Dial 420 23 901 5850 if toll free 800 option is unavailable or dialing from a mobile telephone Technical Support Email support emea ip ge com Customer Care Email customercare emea ip ge com Primary languages of support English French German Italian Czech Spanish Asia Pacific Online Technical Support http support ge ip com tt Phone 86 400 820 8208 86 21 3217 4826 India Indonesia and Pakistan Technical Su
34. wer connector and securely tighten the attaching screws The torque range for the attaching screws is 1 95 2 21 in lb 0 22 0 25 Nm Connect a VGA compatible video monitor and tighten down its attaching screws Also attach a USB compatible keyboard and if desired a USB compatible mouse Power up the unit and check whether any concealed damage has been caused by incorrect transportation operating storage conditions or handling For ICRXIBN7x000A CA or earlier units only to power up the unit press the Power On Off switch for at least second ICRXIBN7x001A will start up once power is applied without the need to depress the On Off switch If you notice any damage remove power from the unit immediately and secure it against unintentional use During normal power up and operation the Power On Off status indicator display is Blinking blue while the IPC is starting up Solid green when the IPC has completed startup and is running Solid green when the IPC is restarted without a loss of power Models that include the Windows 7 operating system ICRXIBN7xxxxx 5 The Windows 7 operating system starts in accordance with the BIOS settings During power up you should see the normal operating system starting displays on the monitor ICRXIBN7x001x models contain Windows Embedded Standard 7and do not require license activation For ICRXIBN7x000x activate the Windows 7 Professional operating system license during initial power u