Guide to the MVI56-BSAPS User Manual
Contents
1. Page 22 of 83 ProSoft Technology Inc September 22 2008 Module Configuration MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Select the 1756 Module Generic 1756 Module from the list and click OK The following dialog box is displayed fl Module Properties Local 1 1756 MODULE 1 1 x General Connection Module Info Backplane Type 1756 MODULE Generic 1756 Module Parent Local p Connection Parameters Assembly 5 Instance Size Name MYVI Input 1 250 j 16 bit Description MVIS6 BSAPS a Output Ro pe 4 Eb mme Configuration pooo p a 8 bit Comm Format Daan ES Slot fi ae EET Status Offline Cancel Apply Help Fill in the dialog boxes as shown adjusting the Name Description and Slot options for your application You must select the Comm Format as Data INT in the dialog box Failure to set the Assembly Instance and Size values correctly will result in a module that will not communicate over the backplane of the ControlLogix rack Click Next to display the next dialog box Module Properties Local 2 1756 MODULE 1 1 d i x Requested Packet Interval API Solms 0 2 750 0 ms I Inhibit Module I Major Fault On Controller If Connection Fails While in Run Mode Module Fault Cancel lt Back Next gt Help Select the Request Packet Interval value for scanning the I O on the module This value r
2. 3 write command types Immediate Response Mode 5 2 3 General Concepts The following discussion explains several concepts that are important for understanding the operation of the MVI56 BSAPS module Module Power Up On power up the module begins performing the following logical functions 1 2 3 4 5 Initialize hardware components Initialize ControlLogix backplane driver o Test and clear all RAM o Initialize the serial communication ports Read module configuration Initialize module register space Enable slave driver on selected ports After the module has received the configuration the module begins receiving and transmitting messages with BSAP devices on the network Page 58 of 83 ProSoft Technology Inc September 22 2008 Reference MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Main Logic Loop Upon completing the power up configuration process the module enters an infinite loop that performs the functions shown in the following diagram From P ower Up Logic Call VO Handler Call VO Handler Transfers data between the module and processor user status etc Call CFG DEBUG Port Call Serial Port Driver Rx and Tx buffer routines are interrupt driven Call to serial port routines check to see if there is any data in the buffer and depending on the value will either service the buffer or wait for more characters Driver Call Network Call Network Slave
3. Pentium Il 450 MHz minimum Pentium III 733 MHz or better recommended Supported operating systems o Microsoft Windows XP Professional with Service Pack 1 or 2 o Microsoft Windows 2000 Professional with Service Pack 1 2 or 3 o Microsoft Windows Server 2003 128 Mbytes of RAM minimum 256 Mbytes of RAM recommended ProSoft Technology Inc Page 9 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Start Here 100 Mbytes of free hard disk space or more based on application requirements 256 color VGA graphics adapter 800 x 600 minimum resolution True Color 1024 x 768 recommended CD ROM drive ProSoft Configuration Builder HyperTerminal or other terminal emulator program Note You can install the module in a local or remote rack For remote rack installation the module requires EtherNet IP or ControlNet communication with the processor 12 Package Contents The following components are included with your MVI56 BSAPS module and are all reguired for installation and configuration Important Before beginning the installation please verify that all of the following items are present Qty Part Name Part Number Part Description 1 MVI56 MVI56 BSAPS Bristol Babcock Serial Slave Module BSAPS Module 1 Cable Cable 15 RS232 For RS232 Connection to the CFG Port Null Modem 3 Cable Cable 14 RJ45 to For DB9 Connection to
4. Storage Temperature 40 to 85 C 40 to 185 F Shock 30g Operational 50g non operational Vibration 5 g from 10 to 150 Hz Relative Humidity 5 to 95 non condensing All phase conductor sizes must be at least 1 3 mm squared and all earth ground conductors must be at least 4mm squared Markings Ex II 3 G OC lt Ta lt 60C EEx nA IIC T4 DEMKO 07ATEX0710717X Battery Life Advisory All modules in the MVI series use a rechargeable Lithium Vanadium Pentoxide battery to backup the 512K SRAM memory real time clock and CMOS The battery should last for the life of the module The module must be powered for approximately twenty hours before it becomes fully charged After it is fully charged the battery provides backup power for the CMOS setup and configuration data the real time clock and the 512K SRAM memory for approximately 21 days Before you remove a module from its power source ensure that the battery within the module is fully charged A fully charged battery will hold the BIOS settings after being removed from its power source for a limited number of days When the battery is fully discharged the module will revert to the default BIOS settings Note The battery is not user replaceable ProSoft Product Documentation In an effort to conserve paper ProSoft Technology no longer includes printed manuals with our product shipments User Manuals Datasheets Sample Ladder Files and Configuration Files are provided on
5. P Package Contents e 10 Parity 32 Pass Through Control Block Examples 63 Pass Through Control Blocks e 62 Pass Through Time Synchronization 62 Pinouts e 2 12 65 70 Please Read This Notice e 2 Printing a Configuration File 28 Procedures for Return of Units Out of Warranty e 75 Procedures for Return of Units Under Warranty e 75 Product Specifications e 7 55 ProSoft Configuration Builder 25 ProSoft Product Documentation e 3 Protocol Overview 57 Protocol Serial BSAP Menu e 51 Purchasing Warranty Extension 75 R Read Block 61 Read Register Count es 29 Read Register Start 29 Reading Status Data from the Module e 43 Receiving the Configuration File 47 Redisplaying the Menu e 50 51 Reference 7 55 Required Hardware 43 Required pin assignments 34 Resetting diagnostic data e 47 Return Material Authorization RMA Policies and Conditions 74 Returning to the Main Menu 50 51 RS 232 e 67 Modem Connection e 67 Null Modem Connection Hardware Handshaking 68 Null Modem Connection No Hardware Handshaking 68 RS 232 Configuration Debug Port 65 RS 422 69 RS 485 e 69 RS 485 and RS 422 Tip 69 RTS Off 33 RTS On 33 Index S Select the Slot Number for the Module e 16 Sending the Configuration File 47 Set Module Parameters e 21 27 Set Up the Project es 25 Setting Jumpers e 12 SFirmware Enable e 30 Signal Addr e 31 Signal Descriptor 32
6. a A replacement module will be shipped and invoiced A purchase order will b 6 2 3 a b c be required Credit for a product under warranty will be issued upon receipt of authorized product by ProSoft at designated location referenced on the Return Material Authorization Procedures for Return of Units Out of Warranty Customer sends unit in for evaluation If no defect is found Customer will be charged the equivalent of 100 USD plus freight charges duties and taxes as applicable A new purchase order will be required If unit is repaired charge to Customer will be 30 of current list price USD plus freight charges duties and taxes as applicable A new purchase order will be required or authorization to use the purchase order submitted for evaluation fee The following is a list of non repairable units Or OO BO OF BOD OO OD 6 2 4 a 3150 All 3750 3600 All 3700 3170 All 3250 1560 Can be repaired only if defect is the power supply 1550 Can be repaired only if defect is the power supply 3350 3300 1500 All Purchasing Warranty Extension ProSoft s standard warranty period is three 3 years from the date of shipment as detailed in Limited Warranty page 76 The Warranty Period may be extended at the time of equipment purchase for an additional charge as follows e Additional 1 year 10 of list price e Additional 2 years 20 of list price e Additional 3 years
7. 209 to 210 Revision level as ASCII This register contains the product version for the current string software 211 to 212 Operating system level as This register contains the month and year values for the ASCII string program operating system 213 to 214 Run number as ASCII This register contains the run number value for the string Current software 215 Number of requests Port Contains the number of port messages sent out of the 1 port 216 Number of responses Contains the total number of messages received on the Port 1 port 217 Number of errors sent Contains the total number of message errors sent out of Port 1 the port 218 Number of errors received Contains the total number of message errors received Port 1 on the port 219 Number of requests Port Contains the total number of messages sent out the 2 port Page 70 of 83 ProSoft Technology Inc September 22 2008 Reference MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Offset Content Description 220 Number of responses Contains the total number of messages received on the Port 2 port 221 Number of errors sent Contains the total number of message errors sent out Port 2 the port 222 Number of errors received Contains the total number of message errors received Port 2 on the port 223 Backplane Transfer Writes Contains the total number of write blocks transferred from the proces
8. Name PCB_2 0 12 13 0054 exe Type Application 17 3MB From www prosoft technology com Bun se JE While files from the Intemet can be useful this file type can P potentially ham your computer if you do not trust the source do not un or save this software What s the risk 4 Make a note of the location where you saved the file for example Desktop or My Documents so you can start the installation program 5 When the download is complete locate and open the file and then follow the instructions on your screen to install the program If you do not have access to the Internet you can install ProSoft Configuration Builder from the ProSoft Solutions CD ROM included in the package with your MVI56 BSAPS module To install ProSoft Configuration Builder from the CD ROM 1 Insert the ProSoft Solutions CD ROM into the CD drive of your PC Wait for the startup screen to appear 2 On the startup screen click Product Documentation This action opens an explorer window ProSoft Technology Inc Page 11 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Start Here Bristol Babcock Serial Slave Module 3 Click to open the Utilities folder This folder contains all of the applications and files you will need to set up and configure your module 4 Double click the ProSoft Configuration Builder Setup program and follow the instructions on your screen to install the software on your PC Note
9. object is shown in the following example Data Type BSAPBIkStat E SAPBIKStat This object is used to store the block Iransfer statistics for the MVI56 BSAP module Decimal Total number of read block transfers Decimal Total number of write block transfers Decimal Total number of blocks parsed Decimal Total number of block transfer errors Cancel Apple Help ProSoft Technology Inc Page 39 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Ladder Logic Bristol Babcock Serial Slave Module Additionally the status object contains a structure for each of the servers in the module The structure used for each server is shown in the following example Data Type BSAPPortErrors BSAPPortE mors This object is used to store the port statistics for an MYI56 BSAP port Reguests oe a number of requests for port Responses 4 Decimal Total number of responses for port EnSent Decimal _ Total number of errors sent EnRec ji IT Decimal Total number of errors received Cancel Apply Refer to MVI56 BSAPS Status Data Area for a complete listing of the data stored in status object 3 2 BSAP Message Data This module s program includes the pass through mode In this mode write messages sent to a slave port are passed directly through to the processor It is the responsibility of the ladder logic to process the message received using this
10. 6 Support Service amp Warranty In This Chapter 4 How to Contact Us Technical SUDDOF ees esse ee ee ee ee ee ee ee 73 Return Material Authorization RMA Policies and Conditions 74 4 LIMITED WARRANTY ee ee ee ee ee ee ee ee Re ee Ee ee ee ee ee Re ee ee ee 76 ProSoft Technology Inc ProSoft is committed to providing the most efficient and effective support possible Before calling please gather the following information to assist in expediting this process 1 Product Version Number 2 System architecture 3 Network details If the issue is hardware related we will also need information regarding 1 Module configuration and contents of file o Module Operation o Configuration Debug status information o LED patterns 2 Information about the processor and user data files as viewed through and LED patterns on the processor 3 Details about the serial devices interfaced if any 6 1 How to Contact Us Technical Support Internet Web Site http www prosoft technology com support http www prosoft technology com support E mail address support prosoft technology com mailto support prosoft technology com Asia Pacific 603 7724 2080 support asia prosoft technology com mailto support asia prosoft technology com Languages spoken include Chinese English Europe location in Toulouse France 33 0 5 34 36 87 20 support EMEA prosoft technology com mailto support emea prosoft
11. Drivers Slave Drivers Respond to messages received ControlLogix Processor Not in Run Whenever the module detects that the processor has gone out of the Run mode that is Fault or PGM the BSAP ports can be shut down as prescribed in the user configuration When the processor is returned to a running state the module resumes communications on the network Backplane Data Transfer The MVI56 BSAPS module communicates directly over the ControlLogix backplane Data is paged between the module and the ControlLogix processor across the backplane using the module s input and output images The update frequency of the images is determined by the scheduled scan rate defined the user for the module and the communication load on the module Typical updates are in the range of 2 to 10 milliseconds This bi directional transference of data is accomplished by the module filling in data in the module s input image to send to the processor Data in the input image is placed in the controller tags in the processor by the ladder logic The input image for the module is set to 250 words This large data area permits fast throughput of data between the module and the processor The processor inserts data to the module s output image to transfer to the module The module s program extracts the data and places it in the module s internal database The output image for the module is set to 248 words This large data area permits fast throughput of data fro
12. Platform Module Configuration Bristol Babcock Serial Slave Module First define the module to the system Right click the mouse button on the I O Configuration option in the Controller Organization window to display a pop up menu Select the New Module option from the I O Configuration menu E Controller A Controller Tags 3 Controller Fault Handler 3 Power Up Handler E Tasks Sa MainT ask E8 MainProgram E Program Tags E MainRoutine 23 Unscheduled Programs E3 Trends 3 Data Types ER User Defined Ej oe Predetined 8 Module Defined Ga New Module eat Copy aste Pritt This action opens the following dialog box Select Module Type xj Type Major Revision 1756 MODULE fi 7 Description 1756 M32 A 32 Point 10 30 DC Input Source 1756 L1 ControlLogix5550 Controller 1 756 L53 ControlLogix5553 Controller 1 756 L55 ControlLogix5555 Controller 1 756 MO24E 2 Axis Analog Encoder Servo Generic 1756 Module 1756 0416 16 Point ZAV 265V AC Output 1756 04161 16 Point ZAV 265V AC Isolated Output a 1756 048 8 Point 74V 265V AC Output 1 756 048D 8 Point 74 132 AC Diagnostic Output 1 756 048E 8 Point 74V 132v AC Electronically Fused Output 1756 0B16D 16 Point 19 2V 30 DC Diagnostic Output xl Show Vendor Al 7 V Other IV Specialty 1 0 Select All M Analog WM Digital V Communication V Motion Controller Clear All Cancel Help
13. RD 2 _ _ 9 TxD TXD 3 _ _ 4 RXD GND 5 5 RTS 6 cTs GND Page 34 of 83 ProSoft Technology Inc September 22 2008 Module Configuration MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module The DPC 3330 supports command types SEND POLL AND POLL SEND The ProSoft BSAPS driver ONLY supports SEND and POLL A POLL SEND will not work The DPC 3330 Inlist must match the ProSoft BSAPS Data Element list For the DPC 3330 to read and write to the ProSoft BSAPS enabled device both a Master Module Mode 0 Poll AND Mode 1 Send must be defined within ACCOL Workbench The following illustration shows an example of the ACCOL Workbench defining both a Master Module Mode 0 Poll AND Mode 1 Send ACCOL Workbench Dc ACC lt Code for Task 4 gt BAX E Eile Edit View Actions Modules Setup Window Help xX oea rek L ee Ti REMOTE 15 0000000 POINT 00 OI 1 00000 HODE 0 INTYPE 0 0000000 OUTTYPE 0 0000000 INLIST 115 0000000 OUTLIST 215 0000000 STATUS_1 R15 STAT1 DONE STATUS_2 R1S STAT2 ERR 730 C 740 C R15 CAMERON HILL BCBS BS AB ProSoft 750 C EE EE EE EE EE EE EE EE EE EE EE EE EE EE 760 MASTER REMOTE 15 0000000 POINT 1 0000000 MODE 1 INTYPE 0 0000000 OUTTYPE 0 0000000 INLIST 115 0000000 OUTLIST 15 00
14. Viewing Backplane Diagnostic Information Press D to view Backplane Diagnostic information Use this command to display the configuration and statistics of the backplane data transfer operations between the module and the processor The information on this screen can help determine if there are communication problems between the processor and the module Tip Repeat this command at one second intervals to determine the number of blocks transferred each second 4 1 6 Protocol Serial BSAP Menu Press 0 or 1 to view protocol serial information for ports 1 and 2 respectively Use this command to view a variety of error and status screens for the port Press to view a list of commands available on this menu M Main Menu 0 4 Protocol Serial Menu Display Menu Redisplays refreshes this menu Y Version Information x Displays version information sereen pomm ays configuration information C Configuration Information pensthe Master Command List See Master Command List Menu L Master Command List menu section Serial Port Opensthe Serial Port menu See Serial Port Menu section E Error Status Information Opens the Command List menu See Command List Menu section Redisplaying the Menu Press to display the current menu Use this command when you are looking at a screen of data and want to view the menu choices availabl
15. ee ee ee ee ee ke ee ee 34 This section contains the setup procedure data and ladder logic requirements for successful application of the MVI56 BSAPS module Each step in the setup procedure is defined in order to simplify the use of the module The section also contains a discussion of the data object defined for the module This single object completely encapsulates all the data required for module operation It is important to understand each element of the object for proper application of the module The ladder logic requirement section defines the minimum ladder logic required to apply the module in a user application The logic is simple to understand and implement 2 1 installing and Configuring the Module The configuration process consists of the following steps 1 Download the sample program to the processor Note For most applications the sample program will work without modification We strongly recommend setting up the module first with the sample program before attempting to add the module to an existing application or create a custom application Modify the module s configuration files to meet the needs of your application and copy the updated configuration to the module Example configuration files are provided on the CD ROM Refer to Modifying the Configuration File page 27 for more information on the configuration files ProSoft Technology Inc Page 21 of 83 September 22 2008 MVI56 BSAPS ControlLogix
16. feature This information is passed from the module to the processor using block identification codes of 9001 for Time Synchronization TS NRT The following topics explain the data objects involved Page 40 of 83 ProSoft Technology Inc September 22 2008 Ladder Logic MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 3 2 1 BSAP Time Synchronization BSAPDateAndTime These objects hold data transferred from the MVI56 BSAPS module The object shown in the example is updated each time a read block number of 9001 is received by the processor Data Type BSAPDateandTime BSAPDateandTime Date and Time E Data Type Size 20 byte s Day Decimal Month Decimal Year Decimal Hour Decimal Minute Decimal Second Decimal JulianD ay Decimal Juliandsec Decimal Julian20sec Decimal Cancel Apply Help ProSoft Technology Inc Page 41 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Ladder Logic Bristol Babcock Serial Slave Module Page 42 of 83 ProSoft Technology Inc September 22 2008 Diagnostics and Troubleshooting MVI56 BSAPS ControlLogix Platform 4 1 Bristol Babcock Serial Slave Module Diagnostics and Troubleshooting In This Chapter Reading Status Data from the Module ccccccceeceeeeeeeeeeesenteeeeees 43 LED Status Indicators esse sesse ee ee se ee ee teers ee ee ke ee ee ee ee ee e
17. ke ee ee 34 EA se _s__BHa ze wqg a q __ 3 1 Module Data Object BSAPModuleDef iese ee se ee ee ee ee Re ee ke ee ee ee 37 3 2 BSAF Message Dalane sa ee se DE ee Re ge ee aiden i eke Ee Ee ee OA ee 40 4 Diagnostics and Troubleshooting 43 4 1 Reading Status Data from the Module se ee ee ee ee Ge RR ee Re ee ee 43 4 2 LED Status MICAS acs RE EE OE EE EE EE ME N 52 S Reference OB 5 1 Product SpecificationS see ee ee ee ER AA Ge GR ER Re Re ee ee ee ee GR ee Re Re ee ee ee ee ee ee Re de ee ee ee 55 ProSoft Technology Inc Page 5 of 83 September 22 2008 Contents MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 5 2 Functional Overview ccccccceceeceeeeccececeeeeeeeeeeaeceeeeeeeesageaeeeeeeeeeseeneaeeeeeeeeneeees 57 5 3 Cable Connections ie ee ee EA EA ee 65 5 4 MVI56 BSAPS Status Data Area ees ee se se ee cece cece GR Ee Re RA ee ee ee ee ee ee Re Re ee ee ee ee ee ent 70 6 Support Service amp Warranty 73 6 1 How to Contact Us Technical SuDpOF see ese se ER Re Re ee ee ee ee AR Ge ee ee ee ee ee ee 73 6 2 Return Material Authorization RMA Policies and ConditioNS esse ee ee 74 6 3 LIMITED WARRANT Yi ie Ee reacts ee es n ee se se ee cee ee EE Ee ast Es kke ek sats ooh 76 Index 81 Page 6 of 83 ProSoft Technology Inc September 22 2008 Start Here MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Guide to the MV
18. on the RS 485 network unless you are experiencing communication problems that can be attributed to signal echoes or reflections In this case install a 120 ohm terminating resistor on the RS 485 line RS 485 and RS 422 Tip If communication in the RS 422 RS 485 mode does not work at first despite all attempts try switching termination polarities Some manufacturers interpret and A B polarities differently ProSoft Technology Inc Page 69 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Reference 5 3 5 DB9 to RJ45 Adaptor Cable 14 Cable Assembly J1 J2 o og og og O RS 232 RS 485 RS 422 J1 Vv DAR Vv J2 LA DCD TXD 7 2 EE RXD RXD i j iS f TXD j i i j DTR j bes i GND GND GND i i GE i DSR RXD i i 2 EE RTS i 2 Q i j CTS TXRXD TXD 2 NIC T MT j Wiring Diagram 5 4 MVI56 BSAPS Status Data Area This section contains a listing of the data contained in the lt ModelNumber status data object Offset Content Description 202 Program cycle counter This value is incremented each time a complete program cycle occurs in the module 203 to 206 Product Name 207 to 208 Product Code as ASCII This register contains the product code of BSAP string
19. point 5 2 4 Data Flow Between the MVI56 BSAPS Module and the ControlLogix Processor The following section describes the flow of data between the two pieces of hardware ControlLogix processor and MVI56 BSAPS module Each port on the module is configured to emulate a BSAP RTU slave device The operation of each port is dependent on this configuration Slave Driver The Slave Driver Mode allows the MVI56 BSAPS module to respond to data read and write commands issued by a master on the BSAP network The following flowchart describes the flow of data into and out of the module The Module Setup section provides a list of the parameters that must be defined for a slave port All write requests will be placed in the database The following illustration shows the data flow for a slave port Processor Memory Backplane Interface BS APS Module Contollogle FEB va Controller Tagi Addrei ie 1 tite Functions oa Ela va Mode Drvar Status from Mod ule Page 64 of 83 ProSoft Technology Inc September 22 2008 Reference MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 5 3 Cable Connections The application ports on the MVI56 BSAPS module support RS 232 RS 422 and RS 485 interfaces Please inspect the module to ensure that the jumpers are set correctly to correspond with the type of interface you are using Note When using RS 232 with radio modem applications some radios or mode
20. rate selected depends on a variety of application dependent factors BSAP has been designed and implemented according to the functional layers of the International Standards Organization ISO model Because each layer is independent of its adjacent layers both synchronous and asynchronous transmission modes can be supported MVI56 BSAPS supports only asynchronous transmission mode 5 2 2 Protocol Overview Variable message length to 253 bytes Analog Floating point 4 bytes Logical data 1 byte Packed logical data 8 bits byte Alarm time stamp 5 bytes Alarm data 6 10 bytes ProSoft Technology Inc September 22 2008 MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Page 57 of 83 MVI56 BSAPS ControlLogix Platform Reference Bristol Babcock Serial Slave Module Local addressing 127 nodes from each node at a level Communication modes peer to peer remote database access RDB polled report by exception RBE Automatic alarm handling 16 bit CRC CCITT Asynchronous communications RS 232 RS 422 RS 423 RS 485 multi drop RDB requires data address lookup function 4 types of poll messages Each node maintains transaction statistics more than MVI std Each transaction is serialized ACK handshaking Message priority levels Data types signal by address or name data arrays array number row column select signal data matches criteria Physical memory N A input ports N A
21. the processor OK LED remains red The program has halted or a critical error has occurred Connect to the Configuration Debug port to see if the module is running If the program has halted turn off power to the rack remove the card from the rack and re insert the card in the rack and then restore power to the rack Page 54 of 83 ProSoft Technology Inc September 22 2008 Reference MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 5 Reference In This Chapter 4 Product SpecificatiOnS iese ee ee ee ee Re Re AA AR AA Re AA AA AA AA AA 55 dt Functional Overvi W ees sesse ee es see ee Ee ee ee AE Ge Ge AE Ee Ee ee ee Ke Geek AR ee 57 Cable Connections ee ee ee ee Ea d GR Re ee Re AR ee ee Re ee ee ee 65 MVI56 BSAPS Status Data Area sesse ees se ee ee ee ee ek ee ee Ge Re ee ee ee 70 5 1 Product Specifications The MVI56 Bristol Babcock Serial Slave Module allows ControlLogix VO compatible processors to interface easily with Bristol Babcock Serial communication devices 5 1 1 Features and Benefits The MVI56 BSAPS module acts as an input output module between the BSAP network and the ControlLogix backplane The module acts as a slave receiving commands from a BSAP master device The data transfer from the ControlLogix processor is asynchronous from the actions on the BSAP network An internal database in the module exchanges data between the processor and the BSAP netwo
22. 00000 STATUS_1 R15 STAT15 DONE STATUS_2 R15 STAT2S ERR v Line 239 Col 1 ProSoft Technology Inc Page 35 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Module Configuration Bristol Babcock Serial Slave Module Page 36 of 83 ProSoft Technology Inc September 22 2008 Ladder Logic MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 3 Ladder Logic In This Chapter Module Data Object BSAPModuleDef BSAP Message Data ees se ee ee ee ee ee ee Re ee ee Ee ee ee ee ee Ge Re ee ee ee 40 Ladder logic is required for application of the MVI56 BSAPS module Tasks that must be handled by the ladder logic are module data transfer special block handling and status data receipt Additionally a power up handler may be needed to handle the initialization of the module s data and to clear any processor fault conditions The sample ladder logic on the ProSoft Solutions CD ROM is extensively commented to provide information on the purpose and function of each rung For most applications the sample ladder will work without modification 3 1 Module Data Object BSAPModuleDef All data related to the MVI56 BSAPS is stored in a user defined data type An instance of the data type is required before the module can be used This is done by declaring a variable of the data type in the Controller Tags Edit Tags dialog box The object has the following structure M Data Type BSAPModuledef lo
23. 30 of list price ProSoft Technology Inc Page 75 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Support Service amp Warranty Bristol Babcock Serial Slave Module 6 3 LIMITED WARRANTY This Limited Warranty Warranty governs all sales of hardware software and other products collectively Product manufactured and or offered for sale by ProSoft and all related services provided by ProSoft including maintenance repair warranty exchange and service programs collectively Services By purchasing or using the Product or Services the individual or entity purchasing or using the Product or Services Customer agrees to all of the terms and provisions collectively the Terms of this Limited Warranty All sales of software or other intellectual property are in addition subject to any license agreement accompanying such software or other intellectual property 6 3 1 What Is Covered By This Warranty a Warranty On New Products ProSoft warrants to the original purchaser that the Product that is the subject of the sale will 1 conform to and perform in accordance with published specifications prepared approved and issued by ProSoft and 2 will be free from defects in material or workmanship provided these warranties only cover Product that is sold as new This Warranty expires three years from the date of shipment the Warranty Period If the Customer discovers within the Warranty Period a failur
24. 7 Back 5 Pages P Previous Page Skip 5 Pages ab T N Next Page D Decimal Display H Hexadecimal Display a pi pi EN Displays data in floating point format 4 ASCII Display Displays data in test format M Main Menu TA Goes up one level to main menu Page 48 of 83 ProSoft Technology Inc September 22 2008 Diagnostics and Troubleshooting MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Viewing Register Pages To view sets of register pages use the keys described below Command Description 0 Display registers 0 to 99 1 Display registers 1000 to 1099 2 Display registers 2000 to 2099 And so on The total number of register pages available to view depends on your module s configuration Displaying the Current Page of Registers Again DATABASE DISPLAY TO 99 DECIMAL 164 i i 182 4 11 12 1 14 EA A TATATEE Beeageqraqc u Seqgreerees Beggar biiinn 5 5 B B i 4 a a a a This screen displays the current page of 100 registers in the database Moving Back Through 5 Pages of Registers Press from the Database View menu to skip back to the previous 500 registers of data Viewing the Previous 100 Registers of Data Press P from the Database View menu to display the previous 100 registers of data Skipping 500 Registers of Data Hold down Shift and press to skip
25. AX number of a range from 1 to MAX Only one list can be setup 2 5 3 Array Element Row Data Array Element Row Row Column lt Number of Signal Value 2 5 4 Array Element Column Data Array Element Column Row Column lt Number of Signal Value 2 5 5 SFirmware Enable 0 Disable 1 Enable This parameter enables the slave for longer messages on specific BSAP Master devices 2 5 6 Immediate Response Mode 0 Disable 1 Enable This parameter enables slave immediate response Page 30 of 83 ProSoft Technology Inc September 22 2008 Module Configuration MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 2 6 BSAP Data Element This section defines the database structure for the BSAP Data Element 2 6 1 Signal Type 0 Analog 1 Logical 2 String 4 Analog w Alarm 5 Logical w Alarm 2 6 2 Version No Version number is the version of each element that can be read by a master 2 6 3 Signal Addr The Signal Address indicates the local address of each element that can be used to read or write the signal by the local address 2 6 4 HiDB High Deadband Also use for logical signal to indicate change of alarm state 0 or 1 2 6 5 LoDB Low Deadband 2 6 6 Hi AL High Alarm Limit 2 6 7 Lo AL Low Alarm Limit 2 6 8 HHAL High High Alarm Limit 2 6 9 LLAL Low Low Alarm Limit 2 6 10 Base Name Max char of Base Name 8 2 6 11 Extension Name Max char of
26. At least one UART hardware based serial communications port available USB based virtual UART systems USB to serial port adapters often do not function reliably especially during binary file transfers such as when uploading downloading configuration files or module firmware upgrades A null modem serial cable ProSoft Technology Inc Page 43 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Diagnostics and Troubleshooting Bristol Babcock Serial Slave Module 4 1 2 The Configuration Debug Menu The Configuration and Debug menu for this module is arranged as a tree structure with the Main Menu at the top of the tree and one or more sub menus for each menu command The first menu you see when you connect to the module is the Main menu Because this is a text based menu system you enter commands by typing the command letter from your computer keyboard in the diagnostic window in ProSoft Configuration Builder PCB The module does not respond to mouse movements or clicks The command executes as soon as you press the command letter you do not need to press Enter When you type a command letter a new screen will be displayed in your terminal application Using the Diagnostic Window in ProSoft Configuration Builder To connect to the module s Configuration Debug serial port 1 Start PCB program with the application file to be tested Right click over the module icon Default Project La Default Location RA
27. ControlLogix Platform Bristol Babcock Serial Slave Module 3 1 3 Status Data This object views the status of the module The BSAPInStat object shown is updated each time a read block is received by the processor Use this data to monitor the state of the module at a real time rate Data Type BSAPInStat JBSAPInstat This status data is returned on each read block and can be used to detect proper module operation aie ae cycle counter NE ASCII Product Name INT 2 ASCII INT 2 ASCII Revision Level Number INT 2 ASCII Operating Level Numb INT 2 ASCII Run Number PrtEtrs BSAPPortE rrors 2 Port error statistics Requests INT Decimal Total number of reques Responses INT Decimal Total number of respon INT Decimal Total number of errors s INT Decimal Total number of errors r h BlkEns BSAPBIkStat Block transfer statistics Decimal Total number of read bl Decimal Total number of write bl Decimal Total number of blocks Decimal Total number of block t Port CurE rr Decimal Current error index for Port LErr Decimal Last error index for Port Port2CurE tr Decimal Current error index for Port2LErr Decimal Last error index for Port Cancel Apply Help This object contains a structure that includes the status information for the data transfer operations between the processor and the module The structure of this
28. Extension Name 6 ProSoft Technology Inc Page 31 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Module Configuration Bristol Babcock Serial Slave Module 2 6 12 Attribute Name Max char of Attribute Name 4 2 6 13 Signal Descriptor Max char of Signal Descriptor 64 2 7 BSAP Port x This section is used to define the port configuration for the BSAPS device simulated on network port 27 1 Enable Enable Yes No Port Disabled Yes Port Enabled This parameter defines if the port will be used If the parameter is set to No the port is disabled A value of Yes enables the port 2 7 2 Baud Rate Baudrate 1200 Baudrate for port 110 to 115 2K This is the baud rate to be used for the port Enter the baud rate as a value Baud rate entries are 110 150 300 600 1200 2400 4800 9600 19200 28800 57600 115200 2 7 3 Parity None Odd Even Mark Space Parity is a simple error checking algorithm used in serial communication This parameter specifies the type of parity checking to use All devices communicating through this port must use the same parity setting 2 7 4 Data Bits 5 6 7 or 8 This parameter sets the number of data bits for each word used by the protocol 2 7 5 Stop Bits 1or2 Stop bits signal the end of a character in the data stream For most applications use one stop bit For slower devices that require more time to resynchronize use two stop bits All devices
29. I56 BSAPS User Manual Function Section to Read Details Introduction Start Here page 9 This Section introduces the customer to the Must Do module Included are package contents system requirements hardware installation and basic configuration Verify Communication Diagnostic and Troubleshooting Verifying Communication page 52 Diagnostics and Troubleshooting page 43 This section describes how to verify communications with the network Diagnostic and Troubleshooting procedures Reference Product Specifications Functional Overview Glossary Reference page 55 Functional Overview page 57 Product Specifications page 55 These sections contain general references associated with this product Specifications and the Functional Overview Support Service and Warranty Index Support Service and Warranty page 73 This section contains Support Service and Warranty information Index of chapters ProSoft Technology Inc September 22 2008 Page 7 of 83 MVI56 BSAPS ControlLogix Platform Start Here Bristol Babcock Serial Slave Module Page 8 of 83 ProSoft Technology Inc September 22 2008 Start Here MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 1 Start Here In This Chapter System Requirement ii ee se ee ee AR ee AR Re ee ee ee ee ee ee ee Re ee e
30. Many of the configuration and maintenance procedures use files and other utilities on the CD ROM You may wish to copy the files from the Utilities folder on the CD ROM to a convenient location on your hard drive 1 4 Setting Jumpers If you use an interface other than RS 232 default you must change the jumper configuration to match the interface There are three jumpers located at the bottom of the module The following illustration shows the MVI56 BSAPS jumper configuration CMOS RUN CLA SETUP f PRT2 PRT3 EET SETUP NOT JUMPERE 1 Setthe PRT 2 for application port 1 and PRT 3 for application port 2 jumpers for RS232 RS422 or RS485 to match the wiring needed for your application The default jumper setting for both application ports is RS 232 2 The Setup Jumper acts as write protection for the module s flash memory In write protected mode the Setup pins are not connected and the module s firmware cannot be overwritten Do not jumper the Setup pins together unless you are directed to do so by ProSoft Technical Support Page 12 of 83 ProSoft Technology Inc September 22 2008 Start Here MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 1 5 Install the Module in the Rack If you have not already installed and configured your ControlLogix processor and power supply please do so before installing the MVI56 BSAPS module Refer to your Rockwell Autom
31. Module s Port DB9 Male Adapter cable 2 Adapter 1454 9F Two Adapters DB9 Female to Screw Terminal For RS422 or RS485 Connections to Port 1 and 2 of the Module 1 ProSoft Contains sample programs utilities and Solutions CD documentation for the MVI56 BSAPS module If any of these components are missing please contact ProSoft Technology Support for replacement parts Page 10 of 83 ProSoft Technology Inc September 22 2008 Start Here MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 13 Install ProSoft Configuration Builder Software You must install the ProSoft Configuration Builder PCB software in order to configure the MVI56 BSAPS module You can always get the newest version of ProSoft Configuration Builder from the ProSoft Technology web site To install ProSoft Configuration Builder from the ProSoft Web Site 1 Open your web browser and navigate to http www prosoft technology com pcb 2 Click the Download Here link to download the latest version of ProSoft Configuration Builder 3 Choose Save or Save File when prompted The following illustrations show the file download prompt for two of the most common web browsers Opening PCB_2 0 12 13 0054 exe xi You have chosen to open E PCB_2 0 12 13 0054 exe which is a Application from http www prosoft technology com Would you like to save this file File Download Security Warning xi Do you want to run or save this file
32. Signal List Number 30 Signal Type 31 Skipping 500 Registers of Data e 49 Slave Driver e 64 Slave ID 33 Start Here e 7 9 Status Data 39 Stop Bits 32 Support Service amp Warranty 7 73 System Requirements e 9 T The Configuration Debug Menu e 44 Time Limit for Bringing Suit 79 To Determine the Firmware Version of your Processor 015 Troubleshooting 54 Use CTS Line 33 User Data Objects e 38 Using the Diagnostic Window in ProSoft Configuration Builder 44 V Version No e 31 Viewing Backplane Diagnostic Information e 51 Viewing Configuration Information 50 52 Viewing Data in ASCII Text Format e 50 Viewing Data in Decimal Format e 49 Viewing Data in Floating Point Format e 49 Viewing Data in Hexadecimal Format 49 Viewing Error and Status Data 52 Viewing Register Pages e 49 Viewing the Next 100 Registers of Data 49 Viewing the Previous 100 Registers of Data e 49 Viewing Version Information 46 50 51 WwW Warm Boot 62 Warm Booting the Module 47 Warnings 2 What Is Covered By This Warranty e 76 78 What Is Not Covered By This Warranty e 76 Write Block 62 Write Register Start e 29 Y Your Feedback Please 3 Page 82 of 83 ProSoft Technology Inc September 22 2008 Index MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module ProSoft Technology Inc Page 83 of 83 September 22 2008
33. T Decimal Index of last write block BH BlockIndex INT Decimal Computed block offset f 3 1 2 User Data Objects These objects hold data to be transferred between the processor and the MVI56 BSAPS module The user data is the read and write data transferred between the processor and the module as pages of data up to 200 words long ReadData INT 800 Decimal E __WriteData INT 800 _ Decimal The read data ReadData is an array containing values that are read from module database For ease of use this array should be dimensioned as an even increment of 200 words This data is paged up to 200 words at a time from the module to the processor The ReadData task is responsible for placing the data received into the proper position in the read data array Use this data for status and control in the ladder logic of the processor The write data WriteData is an array contain value that is written into the module database For ease of use this array should be dimensioned as even increments of 200 words This data is paged up to 200 words at a time from the processor to the module The WriteData task is responsible for placing the write data into the output image for transfer to the module This data is passed from the processor to the module for status and control information for use in other nodes on the network Page 38 of 83 ProSoft Technology Inc September 22 2008 Ladder Logic MVI56 BSAPS
34. TECHNOLOGY Where Automation Connects INRAS MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module September 22 2008 USER MANUAL Please Read This Notice Successful application of this module requires a reasonable working knowledge of the Rockwell Automation ControlLogix hardware the MVI56 BSAPS Module and the application in which the combination is to be used For this reason it is important that those responsible for implementation satisfy themselves that the combination will meet the needs of the application without exposing personnel or equipment to unsafe or inappropriate working conditions This manual is provided to assist the user Every attempt has been made to ensure that the information provided is accurate and a true reflection of the product s installation requirements In order to ensure a complete understanding of the operation of the product the user should read all applicable Rockwell Automation documentation on the operation of the Rockwell Automation hardware Under no conditions will ProSoft Technology be responsible or liable for indirect or consequential damages resulting from the use or application of the product Reproduction of the contents of this manual in whole or in part without written permission from ProSoft Technology is prohibited Information in this manual is subject to change without notice and does not represent a commitment on the part of ProSoft Technology Imp
35. ULE 1 1 x General Connection Module Info Backplane Type 1756 MODULE Generic 1756 Module Parent Local Connection Parameters Assembly r Instance Size Name Miss Input 1 250 16 bit Description a Output 2 248 mm 16 bit Configuration 4 jo 8 bit Comm Format Data INT z Status Input Slot f er Status Output Status Offline Cancel Kopi Help Page 16 of 83 ProSoft Technology Inc September 22 2008 Start Here MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 3 In the Slot field use the spinners on the right side of the field to select the slot number where the module will reside in the rack and then click OK RSLogix will automatically apply the slot number change to all tags variables and ladder logic rungs that use the MVI56 BSAPS slot number for computation 1 7 3 Configuring RSLinx If RSLogix is unable to establish communication with the processor follow these steps 1 Open RSLinx 2 Open the Communications menu and choose Configure Drivers Communications Station DDELOPC RSWho Configure Drivers Configure Shortcuts Configure Client Applications Configure CIP Options Driver Diagnostics CIP Diagnostics This action opens the Configure Drivers dialog box Available Driver Types Cose RS 232 DF1 Devices 7 Add New es Help Configured Drivers Name and Description Status AB
36. _DF1 1 DH Sta 0 COM1 RUNNING Configure Startup Start Stop Delete Note If the list of configured drivers is blank you must first choose and configure a driver from the Available Driver Types list The recommended driver type to choose for serial communication with the processor is RS 232 DF1 Devices ProSoft Technology Inc Page 17 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Start Here Bristol Babcock Serial Slave Module 3 Click to select the driver and then click Configure This action opens the Configure Allen Bradley DF1 Communications Device dialog box Configure Allen Bradley DF1 Communications Device Device Name AB_DF1 1 Comm Port com pa Device Logix 5550 Serial Port 7 Baud Rate 13200 7 oe ns fo ctal Parity None Error Checking crc Stop Bits fi X Protocol Full Duplex Auto Configure I Use Modem Dialer Cancel Delete Help 4 Click the Auto Configure button RSLinx will attempt to configure your serial port to work with the selected driver 5 When you see the message Auto Configuration Successful click the OK button to dismiss the dialog box Note If the auto configuration procedure fails verify that the cables are connected correctly between the processor and the serial port on your computer and then try again If you are still unable to auto configure the port refer to your RSLinx documentation for further troubl
37. and the configuration pane changed when you added the MVI56 BSAPS module to the project 8 Untitled_ppf ProSoft Configuration Builder File Edit View Project Tools Help Er Default Project Name Stats tnformation SSS E Default Location New Module Please Select Module Type FgNew Module Unknown Product Line 1 Last Change Last Download Module Information ersion 2 1 0 Build 9 Module Configuration Module Module Type Module Name New Module Updating data from new database At this time you may wish to rename the Default Project and Default Location folders in the tree view To rename an object 1 Select the object and then click the right mouse button to open a shortcut menu From the shortcut menu choose Rename 2 Type the name to assign to the object 3 Click away from the object to save the new name ProSoft Technology Inc Page 27 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Module Configuration Bristol Babcock Serial Slave Module Module Entries To configure module parameters 1 Click on the plus sign next to the icon comment to expand module information 2 Double click the 8 Module comment icon to open the Edit dialog box 3 To edit a parameter select the parameter in the left pane and make your changes in the right pane 4 Click OK to save your changes Comment Entries To add comments to your configuration file 1 Click the plus sign to the l
38. anies to the extent based on a claim that any Product made to Buyer specifications infringed intellectual property rights of another party ProSoft makes no warranty that the product is or will be delivered free of any person s claiming of patent trademark or similar infringement The Buyer assumes all risks including the risk of suit that the product or any use of the product will infringe existing or subsequently issued patents trademarks or copyrights ProSoft Technology Inc Page 77 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Support Service amp Warranty Bristol Babcock Serial Slave Module a Any documentation included with Product purchased from ProSoft is protected by copyright and may not be duplicated or reproduced in any form without prior written consent from ProSoft b ProSoft s technical specifications and documentation that are included with the Product are subject to editing and modification without notice c Transfer of title shall not operate to convey to Customer any right to make or have made any Product supplied by ProSoft d Customer is granted no right or license to use any software or other intellectual property in any manner or for any purpose not expressly permitted by any license agreement accompanying such software or other intellectual property e Customer agrees that it shall not and shall not authorize others to copy software provided by ProSoft except as expressly permitted i
39. ansferred from the module to the processor Valid range for this parameter is 0 to 3999 2 4 2 Read Register Count 0 to 4000 The Read Register Count parameter defines the size of the module s input database up to a maximum value of 4000 words 2 4 3 Write Register Start 0 to 3999 This parameter specifies the starting register in the module where the data will be transferred from the processor to the module 2 4 4 Read Register Count 0 to 4000 The Read Register Count parameter defines the size of the module s input database up to a maximum value of 4000 words 2 4 5 Backplane Fail Count 0 to 65535 This parameter specifies the number of consecutive backplane transfer failures that can occur before communications should be halted ProSoft Technology Inc Page 29 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Module Configuration Bristol Babcock Serial Slave Module 2 5 2 4 6 Error Status Block Pointer 1 to 7000 The Error Status Block Pointer parameter is used to specify the range of database registers to use for error and status data The value should be no lower than 700 to avoid overwriting data and no higher than 6970 to allow sufficient space for the error status block BSAPS Config This section is used to define the BSAPS configuration for the BSAPS device simulated on network port 2 5 1 Number of Signal Value 0 to 255 2 5 2 Signal List Number 1 to 300 List Number is the M
40. as Shift Also take care to distinguish capital letter I from lower case letter I L and number 1 likewise for capital letter O and number 0 Although these characters look nearly the same on the screen they perform different actions on the module 4 13 Main Menu When you first connect to the module from your computer your terminal screen will be blank To activate the main menu press the key on your computer s keyboard If the module is connected properly the following menu will appear on your terminal screen MUIS6 BSAP MENU Display Menu U Uersion Information D Datahase Menu G Glear diagnostic data R Rackplane Menn Protocol Serial BSAP 1 1 Protocol Serial BSAP 2 Transfer Configuration from Unit to PC R Transfer Configuration from PC to Unit W Warm Boot Module Esc Exit Program Caution Some of the commands available to you from this menu are designed for advanced debugging and system testing only and can cause the module to stop communicating with the processor or with other devices resulting in potential data loss or other failures Only use these commands if you are specifically directed to do so by ProSoft Technology Technical Support staff Some of these command keys are not listed on the menu but are active nevertheless Please be careful when pressing keys so that you do not accidentally execute an unwanted command Viewing Version Information Press V to view Version informat
41. ation product documentation for installation instructions Warning You must follow all safety instructions when installing this or any other electronic devices Failure to follow safety procedures could result in damage to hardware or data or even serious injury or death to personnel Refer to the documentation for each device you plan to connect to verify that suitable safety procedures are in place before installing or servicing the device After you have checked the placement of the jumpers insert MVI56 BSAPS into the ControlLogix chassis Use the same technique recommended by Rockwell Automation to remove and install ControlLogix modules Warning When you insert or remove the module while backplane power is on an electrical arc can occur This could cause an explosion in hazardous location installations Verify that power is removed or the area is non hazardous before proceeding Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector Worn contacts may create electrical resistance that can affect module operation 1 Turn power OFF 2 Align the module with the top and bottom guides and slide it into the rack until the module is firmly against the backplane connector Slot 1 3 With a firm but steady push snap the module into place ProSoft Technology Inc Page 13 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Start Here Bristo
42. communicating through this port must use the same number of stop bits Page 32 of 83 ProSoft Technology Inc September 22 2008 Module Configuration MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 2 7 6 RTS On 0 to 65535 milliseconds This parameter sets the number of milliseconds to delay after RTS is asserted before the data will be transmitted 2 7 7 RTS Off 0 to 65535 milliseconds This parameter sets the number of milliseconds to delay after the last byte of data is sent before the RTS modem signal will be set low 2 7 8 Use CTS Line Yes or No This parameter specifies if the CTS modem control line is to be used If the parameter is set to No the CTS line will not be monitored If the parameter is set to Yes the CTS line will be monitored and must be high before the module will send data Normally this parameter is required when half duplex modems are used for communication 2 wire 2 7 9 Slave ID Slave ID 1 1 255 Modbus Node Address Slave Slave address used by the host to access this port Valid values are 0 to 255 2 8 Download the Project to the Module In order for the module to use the settings you configured you must download copy the updated Project file from your PC to the module To Download the Project File 1 Inthe tree view in ProSoft Configuration Builder click once to select the MVI56 BSAPS module 2 Open the Project menu and then choose Module Download T
43. e ee 9 OG He slee SE N N EE OE OR EEE 10 Install ProSoft Configuration Builder Software sees ees se ke ee ee 11 4 Setting Jumpers see ee Re Re Re AA Re Re AA ee ee Ee Re ee ee ee 12 Install the Module in the Rack iese ee ee Re ee Ee GR ee ee Re ee ee 13 Connect your PC to the ProceSSOF ese ee se ee ee ee ee ek ee ee Re ee ee ee 14 Open the Sample Ladder LogiC ee ee ee ee AR ee ee Re ee ee 15 4 Download the Sample Program to the ProceSSOF iese se se ee ee ee 19 Connect your PC to the Module ese ee se ee ee ek ee ee Re ee ee 20 Installing the MVI56 BSAPS module requires a reasonable working knowledge of the Rockwell Automation hardware the MVI56 BSAPS Module and the application in which they will be used AA It is important that those responsible for implementation can complete the application without exposing personnel or equipment to unsafe or inappropriate working conditions Safety quality and experience are key factors in a successful installation 11 System Requirements The MVI56 BSAPS module requires the following minimum hardware and software components Rockwell Automation ControlLogix processor with compatible power supply and one free slot in the rack for the MVI56 BSAPS module The module requires 800mA of available power Rockwell Automation RSLogix 5000 programming software version 2 51 or higher Rockwell Automation RSLinx communication software
44. e ee ee ke ee ee 52 The module provides information on diagnostics and troubleshooting in the following forms Status data values are transferred from the module to the processor Data contained in the module can be viewed through the Configuration Debug port attached to a terminal emulator LED status indicators on the front of the module provide information on the module s status Reading Status Data from the Module The MVI56 BSAPS module returns a 22 word Status Data Block that may be used to determine the module s operating status This data is located in the module s database at the location specified in the configuration This data is transferred to the ControlLogix processor continuously with each read block The Configuration Debug port provides the following functionality Full view of the module s configuration data View of the module s status data Complete display of the module s internal database registers 0 to 8999 Version Information Control over the module warm boot cold boot transfer configuration 4 1 1 Required Hardware You can connect directly from your computer s serial port to the serial port on the module to view configuration information perform maintenance and send upload or receive download configuration files ProSoft Technology recommends the following minimum hardware to connect your computer to the module 80486 based processor Pentium preferred 1 megabyte of memory
45. e error ProSoft Technology Inc Page 19 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Start Here Bristol Babcock Serial Slave Module 1 9 Connect your PC to the Module With the module securely mounted connect your PC to the Configuration Debug port using an RJ45 DB 9 Serial Adapter Cable and a Null Modem Cable 1 Attach both cables as shown 2 Insert the RJ45 cable connector into the Configuration Debug port of the module 3 Attach the other end to the serial port on your PC or laptop RJ45 to DBS Pigtail Cable OF Vi Page 20 of 83 ProSoft Technology Inc September 22 2008 Module Configuration MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 2 Module Configuration In This Chapter 4 Installing and Configuring the Module iese se se ee ee ee Ee Re ee ee 21 4 ProSoft Configuration Builder ie se ee ee AR Ee Re AE ee ee Ge Re Re ee ee ee 25 e Module EE ae eaten Site ee es de ED Re N ee ae Ng Ee 29 se Backplane 56 2 52 22 BEER MERE ER heck Ee PERE EKG SR GER ER hee Me Re ie ees 29 e BSAPS GONfIG EE EE Re N ae Ge ae Ee ee Res Ke Ge ee ee ae ee ee ese 30 BSAP Data Element iese se se ee ee AA ee Ge AA ee Ee Re ee ee Ge ke ee ee 31 N De EE EE AE N EE EE N EE 32 4 Download the Project to the Module iese ee ee se ee Ee ee Ge Re Re ee ee ee 33 Configuring a BSAP Master ees see ee ee ee ee ke ee ee Re
46. e of the Product to conform to specifications or a defect in material or workmanship of the Product the Customer must promptly notify ProSoft by fax email or telephone In no event may that notification be received by ProSoft later than 39 months Within a reasonable time after notification ProSoft will correct any failure of the Product to conform to specifications or any defect in material or workmanship of the Product with either new or used replacement parts Such repair including both parts and labor will be performed at ProSoft s expense All warranty service will be performed at service centers designated by ProSoft b Warranty On Services Materials and labor performed by ProSoft to repair a verified malfunction or defect are warranteed in the terms specified above for new Product provided said warranty will be for the period remaining on the original new equipment warranty or if the original warranty is no longer in effect for a period of 90 days from the date of repair 6 3 2 What Is Not Covered By This Warranty a ProSoft makes no representation or warranty expressed or implied that the operation of software purchased from ProSoft will be uninterrupted or error free or that the functions contained in the software will meet or satisfy the purchaser s intended use or requirements the Customer assumes complete responsibility for decisions made or actions taken based on information obtained using ProSoft software Page 76 o
47. e to you Viewing Version Information Press V to view Version information for the module Use this command to view the current version of the software for the module as well as other important values You may be asked to provide this information when calling for technical support on the product Values at the bottom of the display are important in determining module operation The Program Scan Counter value is incremented each time a module s program cycle is complete Tip Repeat this command at one second intervals to determine the frequency of program execution Returning to the Main Menu Press M to return to the Main Menu ProSoft Technology Inc Page 51 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Diagnostics and Troubleshooting Bristol Babcock Serial Slave Module Viewing Configuration Information Press C to view configuration information for the selected port protocol driver or device Opening the Command List Menu Press L to open the Command List menu Use this command to view the configured command list for the module Opening the Serial Port Menu Press S to open the Serial Port menu Use this command to view and change additional serial port driver settings Viewing Error and Status Data Press E to display the error status data for the module 4 2 LED Status Indicators The LEDs indicate the module s operating status as follows P
48. ed port This information can be useful for trouble shooting communication problems Sending the Configuration File Press S to upload send an updated configuration file to the module For more information on receiving and sending configuration files please see Uploading and Downloading the Configuration File Receiving the Configuration File Press R to download receive the current configuration file from the module For more information on receiving and sending configuration files please see Uploading and Downloading the Configuration File Warm Booting the Module Caution Some of the commands available to you from this menu are designed for advanced debugging and system testing only and can cause the module to stop communicating with the processor or with other devices resulting in potential data loss or other failures Only use these commands if you are specifically directed to do so by ProSoft Technology Technical Support staff Some of these command keys are not listed on the menu but are active nevertheless Please be careful when pressing keys so that you do not accidentally execute an unwanted command ProSoft Technology Inc Page 47 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Diagnostics and Troubleshooting Bristol Babcock Serial Slave Module Press W from the Main Menu to warm boot restart the module This command will cause the program to exit and reload refreshing configuration parameter
49. eed 10 1 3 Install ProSoft Configuration Builder Software oo sesse ee de ee ee ee ee ee ee ee ee 11 1 4 getting JUMPS EE EES RE ER nina EE DE ee GE N GEE dd ere dee 12 1 5 Install the Module in the Rack iese ee ee ee ee ee Ee AA ee ee ee ee Re ee ee ee 13 1 6 Connect your PC to the ProceSSOF ees ees ee ee ee ee ke ee ee ee ke ee ee ee ke ee ee ee Re ee ee ee be ee 14 1 7 Open the Sample Ladder Logic i ie sk ee ee Re Re AE ee Ge AA ee ee ee ee 15 1 8 Download the Sample Program to the ProcesSOF ee se ee ee ee ee ke ee ee ee 19 1 9 Connect your PC to the Module sosse rnein ke ee ee Re ee Ge Re ee ee Re ee ee ee ke ee 20 2 Module Configuration 21 2 1 Installing and Configuring the Module ese ee de ee ee AA ee Re ee ee ee ee ee 21 2 2 ProSoft Configuration Builder sisean iaeiaiai oradan ee Re raa aa ee ee Re ee ee ee 25 2 3 Mod le es ste EE ME RE ra id cht RD gad Seid ned ae sea n shit asides ga es eed 29 2 4 Backplane BOS REKE Sorte scenes ane vets tai tests a ER don waned nee Ee ee 29 2 5 IBSAPS CONTIG Es Es tok ates i Sede edit ae So SEE eb eer deine aati ed 30 2 6 IBSAP Data Element iss es Se inate RENE EE Ee eek cde De en ER Veg cet ge 31 2 7 BSAP POX it EE RE ME ee Ee te ee ee RE het EE ve ee PG Ee ee TE ND EED Ad 32 2 8 Download the Project to the Module ie ee se ee ee Re ee ee ee ke ee ee ee 33 2 9 Configuring a BSAP Master sarcen ee ees ee ee ee ee ke a ek ke ee ee ee eiaei ee ke ee E ee Re ee ee
50. eft of the comment icon to expand the Module Comments 2 Double click the Modiecomment icon The Edit Module Comment dialog appears Comment Put Comment Here Definition Reset Tag Reset All OK Cancel 3 Enter your comment and click OK to save your changes Printing a Configuration File To print a confiquration file 1 Select the Module icon and then click the right mouse button to open a shortcut menu 2 On the shortcut menu choose View Configuration This action opens the View Configuration window 3 On the View Configuration window open the File menu and choose Print This action opens the Print dialog box 4 On the Print dialog box choose the printer to use from the dropdown list select printing options and then click OK Page 28 of 83 ProSoft Technology Inc September 22 2008 Module Configuration MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 2 3 Module This section is used to define the configuration for the Module level data 2 3 1 Module Type The part number for the module for example MVI56 BSAPS 2 3 2 Module Name O to 80 characters This parameter assigns a name to the module that can be viewed using the configuration debug port Use this parameter to identify the module and the configuration file 24 Backplane 56 2 4 1 Read Register Start Range 0 to 3999 This parameter specifies the starting register in the module where data will be tr
51. epresents the minimum frequency the module will handle scheduled events This value should not be set to less than 1 millisecond Values between 1 and 10 milliseconds should work with most applications ProSoft Technology Inc Page 23 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Module Configuration Bristol Babcock Serial Slave Module After completing the module setup the Controller Organization window will display the module s presence The data required for the module will be defined to the application and objects will be allocated in the Controller Tags data area The following example shows the Controller Organization window B Controller MVISEBSAPS A Controller Tags Controller Fault Handler 21 Power Up Handler Tasks Le MainTask Unscheduled Programs 5 Trends wE Data Types 8 6 HO Configuration 1 1756 MODULE mvi Next define the User Defined Data Types to be used with the module Copy these data types from the example ladder logic if you are not using the example They will be defined if you are starting from the example ladder logic The Controller Organization window should display the User Defined Data Types shown in the following example Controller MVISGBSAP Tasks amp Motion Groups Ungrouped Axes Trends es I i H En User Defined M BSAPAnalogData M BSAPBackplane R BSAPBIkStat M BSAPCommandBits M BSAPDateandTime M BSAPINStat M BSAPl
52. er logic must handle the receipt of this function code to the processor The structure of the pass through control block is shown in the following table Block 9001 Offset Description Length 0 0 1 9001 2 Date 1 3 Month 1 Page 62 of 83 ProSoft Technology Inc September 22 2008 Reference MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Offset Description Length 4 Year 1 5 Hour 1 6 Minute 1 7 Second 1 8 Julian Day 1 9 Julian 4 Second 1 10 Julian 20 Second 1 11 to 248 Spare 238 249 9001 1 Formatted Pass Through Control Block If the configuration parameter pass through for either Port 1 or Port 2 is enabled the module will pass blocks with identification code of 9500 for Port 1 or 9501 for Port 2 for each received write command Any BSAP Command Remote Database Access CRDB AO FUN Function Code 80H write signal via MSD address or FUN Function Code 84H write signal via name will be passed from the port to the processor using this block ID number Ladder must be written to handle the receipt of these BSAP write functions to the processor and to respond as expected to commands issued by the remote BSAP Master device The structure of the formatted pass through control block is shown in the following table Offset Description Length 0 9500 or 9501 Port 1 or Port 2 1 1 Last Read Block 1 2 Total register building
53. eshooting steps Page 18 of 83 ProSoft Technology Inc September 22 2008 Start Here MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 18 Download the Sample Program to the Processor Note The key switch on the front of the ControlLogix module must be in the REM position To download the sample program from RSLogix 5000 to the ControlLogix processor 1 If you are not already online to the processor open the Communications menu and then choose Download RSLogix will establish communication with the processor 2 When communication is established RSLogix will open a confirmation dialog box Click the Download button to transfer the sample program to the processor Download Eg f Download to the controller N Name Controller Type 1756 L5574 17EB M13 A ControlLogix5555 Controller Path AB_DF1 1 Security lt None gt Ay The controller is in Remote Run mode The mode will be changed to Remote Program prior to download Cancel Help 3 RSLogix will compile the program and transfer it to the processor This process may take a few minutes 4 When the download is complete RSLogix will open another confirmation dialog box Click OK to switch the processor from Program mode to Run mode RSLogix 5000 t Done downloading Change controller mode back to Remote Run e Note If you receive an error message during these steps refer to your RSLogix documentation to interpret and correct th
54. f 83 ProSoft Technology Inc September 22 2008 Support Service amp Warranty MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module b This Warranty does not cover the failure of the Product to perform specified functions or any other non conformance defects losses or damages caused by or attributable to any of the following i shipping ii improper installation or other failure of Customer to adhere to ProSoft s specifications or instructions iii unauthorized repair or maintenance iv attachments equipment options parts software or user created programming including but not limited to programs developed with any IEC 61131 3 C or any variant of C programming languages not furnished by ProSoft v use of the Product for purposes other than those for which it was designed vi any other abuse misapplication neglect or misuse by the Customer vii accident improper testing or causes external to the Product such as but not limited to exposure to extremes of temperature or humidity power failure or power surges or viii disasters such as fire flood earthquake wind and lightning c The information in this Agreement is subject to change without notice ProSoft shall not be liable for technical or editorial errors or omissions made herein nor for incidental or consequential damages resulting from the furnishing performance or use of this material The user guide included with your original pr
55. forward to the next 500 registers of data Viewing the Next 100 Registers of Data Press N from the Database View menu to select and display the next 100 registers of data Viewing Data in Decimal Format Press D to display the data on the current page in decimal format Viewing Data in Hexadecimal Format Press H to display the data on the current page in hexadecimal format Viewing Data in Floating Point Format Press F from the Database View menu Use this command to display the data on the current page in floating point format The program assumes that the values are aligned on even register boundaries If floating point values are not aligned as such they are not displayed properly ProSoft Technology Inc Page 49 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Diagnostics and Troubleshooting Bristol Babcock Serial Slave Module Viewing Data in ASCII Text Format Press A to display the data on the current page in ASCII format This is useful for regions of the database that contain ASCII data Returning to the Main Menu Press M to return to the Main Menu 4 1 5 Backplane Menu Press B from the Main Menu to view the Backplane Data Exchange List Use this command to display the configuration and statistics of the backplane data transfer operations Press to view a list of commands available on this menu ED Main Menu B Backplane Menu Display Menu DI Red
56. g Demo Module 2 On the shortcut menu choose Diagnostics Default Project 6 Default Location Delete Rename Copy Paste Choose Module Type Gonfigure Verify View Configuration Write to Gompact Flash Export Configuration File s Load Config File 4dd External File Download from PC to Device Upload from Device to PC Page 44 of 83 ProSoft Technology Inc September 22 2008 Diagnostics and Troubleshooting MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 3 This action opens the Diagnostics dialog box Press to display the Main Menu Time 11 58 39 MODULE MENU Display Menu B Block Transfer Statistics C Module Configuration D Database View R Transfer Configuration from PC to Unit S Transfer Configuration from Unit to PC U Reset diagnostic data V Version Information w Warm Boot Module Network Menu Esc Ex1t Program Com 1 w Connection DownLoad Config Log ToFile Email Log to Support I ClearFile Close Important The illustrations of configuration debug menus in this section are intended as a general guide and may not exactly match the configuration debug menus in your own module If there is no response from the module follow these steps 1 Verify that the null modem cable is connected properly between your computer s serial port and the module A regular serial cable will not work 2 On computers with more than one serial
57. gnostics and Troubleshooting MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module During module configuration the OK LED will be red and the APP and BP ACT LEDs will be on If the LEDs are latched in this mode for a long period of time look at the configuration error words in the configuration request block The structure of the block is shown in the following table Offset Description Length 0 Reserved 1 1 9000 1 2 Module Configuration Errors 1 3 Port 1 Configuration Errors 1 4 Port 2 Configuration Errors 1 5 to 248 Spare 244 249 2 or 3 1 If the APP BP ACT and OK LEDs blink at a rate of every one second this indicates a serious problem with the module Call ProSoft Technology support to arrange for repairs 4 2 1 Clearing a Fault Condition Typically if the OK LED on the front of the module turns red for more than ten seconds a hardware problem has been detected in the module or the program has exited To clear the condition follow these steps Turn off power to the rack Remove the card from the rack Verify that all jumpers are set correctly If the module requires a Compact Flash card verify that the card is installed correctly Re insert the card in the rack and turn the power back on Verify the configuration data being transferred to the module from the ControlLogix processor khOND mk oo If the module s OK LED does not turn green verify that the module is in
58. he program will scan your PC for a valid com port this may take a few seconds When PCB has found a valid com port the following dialog box will open _ _ Step 1 Select Port Com 1 fal Js Default I Address Abort Step 2 Transfer Files Download em Pas ER ProSoft Technology Inc Page 33 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Module Configuration Bristol Babcock Serial Slave Module 3 Choose the com port to use from the dropdown list and then click the Download button The module will perform a platform check to read and load its new settings When the platform check is complete the status bar in ProSoft Configuration Builder will be updated with the message Module Running Download files from PC to module Ea Module Running LSS Step 1 Select Port Com 1 X Use Default IP Address Abort Step 2 Transfer Files D abot Gance 2 9 Configuring a BSAP Master This section describes a few required steps for setting up a BSAP enabled master a Bristol Babcock DPC 3330 in this example device to communicate with ProSoft Technology s BSAPS enabled products You should have a general understanding of the Bristol Babcock ACCOL Workbench software 2 9 1 BSAP Protocol In order for the Bristol Babcock DPC 3330 and ProSoft Technology s BSAPS enabled products to communicate please review the following information 2 9 2 Required pin assignments ProSoft BB DPC 3330
59. ion for the module Use this command to view the current version of the software for the module as well as other important values You may be asked to provide this information when calling for technical support on the product Values at the bottom of the display are important in determining module operation The Program Scan Counter value is incremented each time a module s program cycle is complete Page 46 of 83 ProSoft Technology Inc September 22 2008 Diagnostics and Troubleshooting MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Tip Repeat this command at one second intervals to determine the frequency of program execution Opening the Database Menu Press D to open the Database View menu Use this menu command to view the current contents of the module s database Resetting diagnostic data Press U to reset the status counters for the client and or servers in the module Opening the Backplane Menu Press B from the Main Menu to view the Backplane Data Exchange List Use this command to display the configuration and statistics of the backplane data transfer operations Tip Repeat this command at one second intervals to determine the number of blocks transferred each second Opening the Protocol Serial BSAP Menu Press 0 or 1 from the Main Menu to open the Protocol Serial BSAP menu for BSAP Ports 1 and 2 Use this command to view communication status and statistics for the select
60. is used when the device connected to the module requires hardware handshaking control and monitoring of modem signal lines RS 232 Application Port Cable Hardware Handshaking DB 9 Male RS 232 Device TxD RxD CTS RTS Signal Signal Common Common RS 232 Null Modem Connection No Hardware Handshakin This type of connection can be used to connect the module to a computer or field device communication port RS 232 Application Port Cable No Handshaking DB 9 Male RS 232 Device RTS RTS CTS jumper must be installed if CTS line CTS se monitoring enabled Signal Signal Common Common Note If the port is configured with the Use CTS Line set to Y then a jumper is required between the RTS and the CTS line on the module connection Page 68 of 83 ProSoft Technology Inc September 22 2008 Reference MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 5 3 3 RS 422 RS 422 Application Port Cable DB 9 Male RS 422 Device TxD ro TxD s ro Signal Signal Common Common RxD 2 ro RxD s H ro 5 3 4 RS 485 The RS 485 interface requires a single two or three wire cable The Common connection is optional and dependent on the RS 485 network The cable required for this interface is shown below RS 485 Application Port Cable DB 9 Male RS 485 Device TxD RxD TxD RxD TxD RxD s HK TxD RxD Signal 5 Signal Common Common Note Terminating resistors are generally not required
61. isplays refreshes this menu Version Information Pens version information screen a Main Menu ee up one level to main menu y lt Oo Coniguration Information Displays configuration screen N o Diagnostic Information isplays backplane diagnostic infomation Redisplaying the Menu Press to display the current menu Use this command when you are looking at a screen of data and want to view the menu choices available to you Viewing Version Information Press V to view Version information for the module Use this command to view the current version of the software for the module as well as other important values You may be asked to provide this information when calling for technical support on the product Values at the bottom of the display are important in determining module operation The Program Scan Counter value is incremented each time a module s program cycle is complete Tip Repeat this command at one second intervals to determine the frequency of program execution Returning to the Main Menu Press M to return to the Main Menu Viewing Configuration Information Press C to view configuration information for the selected port protocol driver or device Page 50 of 83 ProSoft Technology Inc September 22 2008 Diagnostics and Troubleshooting MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module
62. l Babcock Serial Slave Module 4 Check that the holding clips on the top and bottom of the module are securely in the locking holes of the rack 5 Make a note of the slot location You will need to identify the slot in which the module is installed in order for the sample program to work correctly Slot numbers are identified on the green circuit board backplane of the ControlLogix rack 6 Turn power ON Note If you insert the module improperly the system may stop working or may behave unpredictably Note If you are installing MVI56 BSAPS with other modules connected to the PCI bus the peripheral modules will not have holding clips Make sure all of the modules are aligned with their respective slots before you snap them into place 1 6 Connect your PC to the Processor 1 Connect the right angle connector end of the cable to your controller at the communications port Communications Port BATTERY DATE 2 Connect the straight connector end of the cable to the serial port on your computer Page 14 of 83 ProSoft Technology Inc September 22 2008 Start Here MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 1 7 Open the Sample Ladder Logic The sample program for your MVI56 BSAPS module includes custom tags data types and ladder logic for data I O and status monitoring For most applications you can run the sample ladder program witho
63. l x Warning This structure is being referenced Modifications will result in loss of data Name BSAPModuledef Description BSAP Module Data Structure a Members Data Type Size 6020 Name Data Type Style F Backplane BSAPBackplane Statistics BSAPInStat ReadData INT 800 Decimal WriteData INT 800 Decimal H DateAndTime BSAPDateandT ime E m m m Ww AnalogData BSAPAnalogD ata El ad LogicalData BSAPlogicalData CommandBits BSAPCommandBits String BSAPSting Cancel Apply Help This object contains objects that define user data status and command control data related to the module Each of these object types is discussed in the following topics of the document ProSoft Technology Inc Page 37 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Ladder Logic Bristol Babcock Serial Slave Module 3 1 1 Backplane Control Object This data object stores the variables required for the data transfer between the processor and the MVI56 BSAPS module The structure of the object is shown in the following example M Data Type BSAPBackplane lolx Name BSaPB ackplane Description Values used by program for data transfer operation a between the module and the processor a Members Data Type Size 8 byte s Name Datatype Style Description LastRead INT Decimal Index of last read block Lastwrite IN
64. late a BSAP slave RTU Peer to Peer communication for Local BSAP formatted messages slave to master only Page 56 of 83 ProSoft Technology Inc September 22 2008 Reference 5 2 Configurable parameters include Parameter Value Analog Input Count 0 to 255 Logical Input Count 0 to 255 String Count 0 to 30 Slave Address 1 to 255 Baud Rate 110 to 115 200 Parity None Odd Even Data Bits 5 to 8 Stop Bits 1or2 RTS On and Off Timing 0 to 65535 milliseconds Minimum Response Delay 0 to 65535 milliseconds Use of CTS Modem Line Yes or No Functional Overview This section provides an overview of how the MVI56 BSAPS module transfers data using the BSAP protocol You should understand the important concepts in this chapter before you begin installing and configuring the module 5 2 1 Introduction The Bristol Babcock Asynchronous Communication Protocol BSAP is the foundation for a proprietary network that has a tree structured topology This open ended topology supports a variety of configurations which may include one or more nodes at each of up to six levels Messages can be sent between nodes on the same level or on different levels Each message is uniquely identified and has an error checking code associated with it MVI56 BSAPS supports only bottom level one to one communication BSAP operates in a polled environment Each link in the network supports a different poll rate The
65. le s program Up to 248 words of data can be transferred from the module to the processor at a time Up to 247 words of data per backplane scan can be transferred from the processor to the module Each image has a defined structure depending on the data content and the function of the data transfer described in the following topics Page 60 of 83 ProSoft Technology Inc September 22 2008 Reference MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Normal Data Transfer Normal data transfer includes the paging of the user data found in the module s internal database in registers 0 to 2740 and the status data These data are transferred through read blocks input image Write blocks output image transfer data into module s internal database in register 3000 to 5740 These data are gathered in a response command to a master The Module Setup section provides a description of the data objects used with the blocks and the ladder logic required The structure and function of each block is described in the following topics Read Block These blocks of data transfer information from the module to the ControlLogix processor The structure of the input image used to transfer this data is shown in the following table Offset Description Length 0 Reserved 1 1 Write Block ID 1 2 to 201 Read Data 200 202 Program Scan Counter 1 203 to 204 Product Code 2 205 to 206 Product Ve
66. ll C PLXSK C PTQ MVI 56 C MVI71 PLX4K PLX6K CO MVI 46 C MVI 69 C MVI 94 Search Module Type STEP 1 Select Module Type Module Definition z MVIS6 BSAPS Action Required cancel _ 3 In the Product Line Filter area of the dialog box select MVI56 In the Select Module Type dropdown list select MVI56 BSAPS and then click OK to save your settings and return to the ProSoft Configuration Builder window The next task is to set the module parameters Adding a Project To add a project to an existing project file 1 Select the Default Project icon 2 Choose Project from the Project menu then choose Add Project A new project folder appears Adding a Module To add a module to your project 1 Double click the Default Module icon to open the Choose Module Type dialog box 2 On the Choose Module Type dialog box select the module type Or 1 Open the Project menu and choose Location 2 On the Location menu choose Add Module Page 26 of 83 ProSoft Technology Inc September 22 2008 Module Configuration MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module To add a module to a different location 1 Right click the Location folder and choose Add Module A new module icon appears Or 1 Select the Location icon 2 From the Project menu select Location then select Add Module 2 2 2 Set Module Parameters Notice that the contents of the information pane
67. m the processor to the module ProSoft Technology Inc Page 59 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Reference Bristol Babcock Serial Slave Module The following illustration shows the data transfer method used to move data between the ControlLogix processor the MVI56 BSAPS module and the BSAP network Control Logix Processor MUISE BSAP Module CantrolLoglE Prozat ier Controller Tagi Module s In temal Bits Ladder Datangi Raad Data Logio Tran cfare Cata tram module sinput Image b data amas In the nmo car Inputimage Ladder Logio Bpeolal Cantal Tran sbre Booka Cats tram Cu tpu timage Pmoscar data ama n toouhutimage Jang aue dHoeg As shown in the diagram all data transferred between the module and the processor over the backplane is through the input and output images Ladder logic must be written in the ControlLogix processor to interface the input and output image data with data defined in the controller tags All data used by the module is stored in its internal database MVI56 BSAPS Fixed Database Map Start Address End Address Data 0 509 Input Analog Data 510 638 Input Logical Data 640 2740 Input String Data 3000 3509 Output Analog Data 3510 3638 Output Logical Data 3640 5740 Output String Data Data contained in this database is paged through the input and output images by coordination of the ControlLogix ladder logic and the MVI56 BSAPS modu
68. ms require hardware handshaking control and monitoring of modem signal lines Enable this in the configuration of the module by setting the UseCTS parameter to 1 5 3 1 RS 232 Configuration Debug Port This port is physically an RJ45 connection An RJ45 to DB 9 adapter cable is included with the module This port permits a PC based terminal emulation program to view configuration and status data in the module and to control the module The cable for communications on this port is shown in the following diagram RS 232 Config Debug Port Cable DB 9 Male Config Debug Port Ro 2 R To 3 ro COM s COM Disabling the RSLinx Driver for the Com Port on the PC The communication port driver in RSLinx can occasionally prevent other applications from using the PC s COM port If you are not able to connect to the module s configuration debug port using ProSoft Configuration Builder PCB HyperTerminal or another terminal emulator follow these steps to disable the RSLinx Driver 1 Open RSLinx and go to Communications gt RSWho 2 Make sure that you are not actively browsing using the driver that you wish to stop The following shows an actively browsed network EiRSwho 1 5 x IV Autobrowse o Browsing node 10 found ET ders 1 01 0 DF1 COM1 UNTITLED Workstation PS5FT YAIO 1 as Linx Gateways Ethernet HZ AB DF1 1 DH 485 E g 01 SLC 5 05 UNTITLED 10 Workstation DF1 COM1 ProSoft Technolog
69. n any license agreement accompanying such software transfer software to a third party separately from the Product modify alter translate decode decompile disassemble reverse engineer or otherwise attempt to derive the source code of the software or create derivative works based on the software export the software or underlying technology in contravention of applicable US and international export laws and regulations or use the software other than as authorized in connection with use of Product f Additional Restrictions Relating To Software And Other Intellectual Property In addition to compliance with the Terms of this Warranty Customers purchasing software or other intellectual property shall comply with any license agreement accompanying such software or other intellectual property Failure to do so may void this Warranty with respect to such software and or other intellectual property 6 3 5 Disclaimer of all Other Warranties The Warranty set forth in What Is Covered By This Warranty page 76 are in lieu of all other warranties express or implied including but not limited to the implied warranties of merchantability and fitness for a particular purpose 6 3 6 Limitation of Remedies In no event will ProSoft or its Dealer be liable for any special incidental or consequential damages based on breach of warranty breach of contract negligence strict tort or any other legal theory Damages that ProSoft or its Dealer will
70. not be responsible for included but are not limited to Loss of profits loss of savings or revenue loss of use of the product or any associated equipment loss of data cost of capital cost of any substitute equipment facilities or services downtime the claims of third parties including customers of the Purchaser and injury to property Some areas do not allow time limitations on an implied warranty or allow the exclusion or limitation of incidental or consequential damages In such areas the above limitations may not apply This Warranty gives you specific legal rights and you may also have other rights which vary from place to place Page 78 of 83 ProSoft Technology Inc September 22 2008 Support Service amp Warranty MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 6 3 7 Time Limit for Bringing Suit Any action for breach of warranty must be commenced within 39 months following shipment of the Product 6 3 8 No Other Warranties Unless modified in writing and signed by both parties this Warranty is understood to be the complete and exclusive agreement between the parties suspending all oral or written prior agreements and all other communications between the parties relating to the subject matter of this Warranty including statements made by salesperson No employee of ProSoft or any other party is authorized to make any warranty in addition to those made in this Warranty The Customer is
71. oduct purchase from ProSoft contains information protected by copyright No part of the guide may be duplicated or reproduced in any form without prior written consent from ProSoft 6 3 3 Disclaimer Regarding High Risk Activities Product manufactured or supplied by ProSoft is not fault tolerant and is not designed manufactured or intended for use in hazardous environments requiring fail safe performance including and without limitation the operation of nuclear facilities aircraft navigation of communication systems air traffic control direct life support machines or weapons systems in which the failure of the product could lead directly or indirectly to death personal injury or severe physical or environmental damage collectively high risk activities ProSoft specifically disclaims any express or implied warranty of fitness for high risk activities 6 3 4 Intellectual Property Indemnity Buyer shall indemnify and hold harmless ProSoft and its employees from and against all liabilities losses claims costs and expenses including attorney s fees and expenses related to any claim investigation litigation or proceeding whether or not ProSoft is a party which arises or is alleged to arise from Buyer s acts or omissions under these Terms or in any way with respect to the Products Without limiting the foregoing Buyer at its own expense shall indemnify and hold harmless ProSoft and defend or settle any action brought against such Comp
72. odule 26 Adding a Project e 26 All Product Returns e 74 Allocation of Risks 79 Array Element Column e 30 Array Element Row e 30 Attribute Name e 32 Backplane Control Object 38 Backplane Data Transfer e 59 Backplane Fail Count e 29 Backplane Menu 50 Base Name 31 Battery Life Advisory 3 Baud Rate 32 BSAP Message Data e 40 BSAP Protocol 34 BSAP Time Synchronization BSAPDateAndTime e 41 C Cable Connections 65 Clearing a Fault Condition 53 Cold Boot 62 Comment Entries 28 Configuring a BSAP Master 34 Configuring RSLinx e 17 Connect your PC to the Module e 20 Connect your PC to the Processor e 14 Controlling Law and Severability s 79 ControlLogix Processor Not in Run 59 D Data Bits e 32 Data Flow Between the MVI56 BSAPS Module and the ControlLogix Processor e 64 Database View Menu 48 DB9 to RJ45 Adaptor Cable 14 70 Diagnostics and Troubleshooting e 7 43 Disabling the RSLinx Driver for the Com Port on the PC ee 65 Disclaimer of all Other Warranties 78 Disclaimer Regarding High Risk Activities e 77 Displaying the Current Page of Registers Again 49 MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Download the Project to the Module e 33 Download the Sample Program to the Processor e 19 E Enable es 32 Error Status Block Pointer 30 Exiting the Program 48 Extension Name 31 F Features and Benefits 55 Fo
73. ogicalData M BSAPModuledef Ei BSAPPortErrors M BSAPString1 R al Strings i STRING a Predefined m C Module Defined BE 1 0 Configuration f 1 1756 MODULE mvi Next define the data to be used to interface with the module and the ladder logic Open the Controller Tags Edit Tags dialog box and enter the values required for the application You can set the tag name to any valid tag name you desire If you are using the example ladder logic this step has already been performed The last step in the module setup is to add the ladder logic If you are using the example ladder logic adjust the ladder to fit your application If you are not using the ladder example copy the ladder logic shown in the Controller Organization window below to your application Page 24 of 83 ProSoft Technology Inc September 22 2008 Module Configuration MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 2 2 ProSoft Configuration Builder ProSoft Configuration Builder PCB provides a quick and easy way to manage module configuration files customized to meet your application needs PCB is not only a powerful solution for new configuration files but also allows you to import information from previously installed known working configurations to new projects 2 2 1 Set Up the Project To begin start ProSoft Configuration Builder If you have used other Windows configuration tools before you will find the screen lay
74. ogy Inc September 22 2008 Reference MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module 6 Upon seeing this you may now use that com port to connect to the debug port of the module Note You may need to shut down and restart your PC before it will allow you to stop the driver usually only on Windows NT machines If you have followed all of the above steps and it will not stop the driver then make sure you do not have RSLogix open If RSLogix is not open and you still cannot stop the driver then reboot your PC 5 3 2 RS 232 When the RS 232 interface is selected the use of hardware handshaking control and monitoring of modem signal lines is user definable If no hardware handshaking will be used the cable to connect to the port is as shown below RS 232 Application Port Cable No Handshaking DB 9 Male RS 232 Device RS 232 Modem Connection This type of connection is required between the module and a modem or other communication device RS 232 Application Port Cable Modem Connection DB 9 Male RS 232 Device mw m Signal Signal Common Common DTR DTR The Use CTS Line parameter for the port configuration should be set to Y for most modem applications ProSoft Technology Inc Page 67 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Reference Bristol Babcock Serial Slave Module RS 232 Null Modem Connection Hardware Handshaking This type of connection
75. ollowing table Offset Description Length 0 Write Block ID 1 1 to 200 Write Data 200 201 to 247 Spare 47 The Write Block ID is an index value used to determine the location in the module s database where the data will be placed Each transfer can move up to 200 words block offsets 1 to 200 of data Warm Boot This block is sent from the ControlLogix processor to the module output image when the module is required to perform a warm boot software reset operation This block is commonly sent to the module any time configuration data modifications are made in the controller tags data area This will force the module to read the new configuration information and to restart The structure of the control block is shown in the following table Offset Description Length 0 9998 1 1 to 247 Spare 247 Cold Boot This block is sent from the ControlLogix processor to the module output image when the module is required to perform the cold boot hardware reset operation This block is sent to the module when a hardware problem is detected by the ladder logic that requires a hardware reset The structure of the control block is shown in the following table Offset Description Length 0 9999 1 1 to 247 Spare 247 Pass Through Control Blocks Pass Through Time Synchronization The module will pass blocks with identification codes of 9001 to the processor for function 88h command time synchronization Ladd
76. out familiar ProSoft Configuration Builder s window consists of a tree view on the left an information pane and a configuration pane on the right side of the window When you first start ProSoft Configuration Builder the tree view consists of folders for Default Project and Default Location with a Default Module in the Default Location folder The following illustration shows the ProSoft Configuration Builder window with a new project Untitled ProSoft Configuration Builder OF x File Edit View Project Tools Help EI Default Project Name Stats information E G Default Location Default Module Please Select Module Type A Default Module Unknown Product Line 1 Last Change Never Last Download Never Module Information dress ConfigEdit version 2 0 13 Build 18 Module configuration Module Module Type N Module Name Default Module Updating data from new database Your first task is to add the MVI56 BSAPS module to the project 1 Use the mouse to select Default Module in the tree view and then click the right mouse button to open a shortcut menu ProSoft Technology Inc Page 25 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Module Configuration Bristol Babcock Serial Slave Module 2 On the shortcut menu choose Choose Module Type This action opens the Choose Module Type dialog box Choose Module Type x Product Line Filter C A
77. pass through block 1 3 Number of Element 1 4 First Element Address 1 5 First Element Type 0 Analog 1 Logical 1 6 First Data two words for Analog or one word for Logical 1 or 2 M 2 Nth Element Address 1 M 1 Nth Element Type 0 Analog 1 Logical 1 M Nth Data two words for Analog or one word for Logical 1 or 2 249 9500 or 9501 Port 1 or Port 2 1 Pass Through Control Block Examples First example host sends logical Off to Port 2 for address 11 The block will look like this 9051 Passthrough block for Port 2 x Previous read block number prior to pass through block was sent 5 5 registers count from this register to the last register of the last element 1 1 element is written by thehost 11 address 11 is configured in the configuration 1 type logical 0 set to Off ProSoft Technology Inc Page 63 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Reference Bristol Babcock Serial Slave Module Second example host sends Analog 775 to Port 1 for address 14 The block will look like this 9050 Passthrough block for Port 2 x Previous read block number prior to pass through block was sent 6 6 registers count from this register to the last register of the last element 1 1 element is written by the host 14 address 14 is configured in the configuration 0 type analog 16834 first register for analog floating point 17473 second register for analog floating
78. port verify that your communication program is connected to the same port that is connected to the module If you are still not able to establish a connection contact ProSoft Technology for assistance Navigation All of the sub menus for this module contain commands to redisplay the menu or return to the previous menu You can always return from a sub menu to the next higher menu by pressing M on your keyboard The organization of the menu structure is represented in simplified form in the following illustration Main Menu Child Menu A Child Menu B Child Menu C Child Sub Menu 1 Child Sub Menu 2 Child Sub Menu 1 Child Sub Menu 2 Child Sub Menu 3 Child Sub Menu 1 ProSoft Technology Inc Page 45 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Diagnostics and Troubleshooting Bristol Babcock Serial Slave Module The remainder of this section shows you the menus available for this module and briefly discusses the commands available to you Keystrokes The keyboard commands on these menus are almost always non case sensitive You can enter most commands in lower case or capital letters The menus use a few special characters that must be entered exactly as shown Some of these characters will require you to use the Shift Ctrl or Alt keys to enter them correctly For example on US English keyboards enter the command
79. r Comm Path AB_DF1 1 Security lt None gt Offline Project ProSoft Technology Inc Page 15 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Start Here Bristol Babcock Serial Slave Module 5 On the Connected To Go Online dialog box click the General tab This tab shows information about the processor including the Revision firmware version In the following illustration the firmware version is 11 32 Minor Faults Redundancy Nonvolatile Memory Options General Date Time Major Faults Vendor Allen Bradley Type 1756 L55 A 1756 M13 A ControlLogix5555 Controller Revision 11 32 Name Fetole tt ti sS s S SCS Description Chassis Type Slot Select File Cancel Help 1 7 2 Select the Slot Number for the Module The sample application is for a module installed in Slot 1 in a ControlLogix rack The ladder logic uses the slot number to identify the module If you are installing the module in a different slot you must update the ladder logic so that program tags and variables are correct and do not conflict with other modules in the rack To change the slot number 1 Inthe Controller Organization list select the module 1 1756 MODULE MVI56 and then click the right mouse button to open a shortcut menu 2 On the shortcut menu choose Properties This action opens the Module Properties dialog box W Module Properties Locak1 1756 MOD
80. rial Activity Debug Configuration port CFG CFG Port CFG RJ45 DB 9M with supplied cable RS 232 only Application ports PRT1 amp PRT2 Full hardware handshaking control providing radio modem and multi drop support Software configurable communication Baud rate 110 to 115 200 baud depending on protocol parameters RS 232 485 and 422 Parity none odd or even Data bits 5 6 7 or 8 Stop bits 1 or 2 RTS on off delay 0 to 65535 milliseconds App Ports P1 P2 Serial modules RJ45 DB 9M with supplied cable RS 232 handshaking configurable 500V Optical isolation from backplane Shipped with Unit RJ45 to DB 9M cables for each port 6 foot RS 232 configuration cable 5 1 4 Functional Specifications The Bristol Babcock Synchronous Asynchronous Communication Protocol BSAP is the foundation for a proprietary network that has a tree structured topology This open ended topology supports a variety of configurations which may include one or more nodes at each of up to six levels Messages can be sent between nodes on the same level or on different levels Messages can be sent between nodes local message only Each message is uniquely identified and has an error checking code associated with it Some of the general specifications include Slave implementation Support for the storage and transfer of internal database registers to from the ControlLogix processor s controller tags Two ports to emu
81. rk BSAP operates in a polled environment Each link in the network supports a different poll rate The rate selected depends on a variety of application dependent factors BSAP has been designed and implemented according to the functional layers of the International Standards Organization ISO model Because each layer is independent of its adjacent layers both synchronous and asynchronous transmission modes can be supported 5 1 2 General Specifications Single Slot 1756 backplane compatible The module is recognized as an Input Output module and has access to processor memory for data transfer between processor and module Ladder Logic is used for data transfer between module and processor Sample ladder file included Configuration data obtained from configuration text file downloaded to module Sample configuration file included Local or remote rack ProSoft Technology Inc Page 55 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Reference Bristol Babcock Serial Slave Module 5 1 3 Hardware Specifications Specification Description Backplane Current Load 800 mA 5 V DC 3mA 24V DC Operating Temperature 0 to 60 C 32 to 140 F Storage Temperature 40 to 85 C 40 to 185 F Shock 30g Operational 50g non operational Vibration 5 g from 10 to 150 Hz Relative Humidity 5 to 95 non condensing LED Indicators Module Status Backplane Transfer Status Application Status Se
82. rmatted Pass Through Control Block e 63 Functional Overview 7 57 Functional Specifications 56 G General Concepts 58 General Specifications 55 Guide to the MVI56 BSAPS User Manual e 7 H Hardware Specifications es 56 HH AL e 31 Hi AL e 31 Hi DB ee 31 How to Contact Us Technical Support 73 74 Immediate Response Mode 30 Install ProSoft Configuration Builder Software e 11 Install the Module in the Rack e 13 Installing and Configuring the Module e 21 Intellectual Property Indemnity 77 Introduction 57 K Keystrokes 46 L Ladder Logic e 37 LED Status Indicators 7 52 Limitation of Remedies e 78 LIMITED WARRANTY e 75 76 LL AL 31 Lo AL e 31 Lo DB 31 Main Logic Loop 59 Main Menu 46 Module Configuration e 21 Module Data Object BSAPModuleDef e 37 Module Entries 28 Module Name e 29 Module Power Up 58 Module Type 29 Moving Back Through 5 Pages of Registers e 49 ProSoft Technology Inc September 22 2008 Page 81 of 83 MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module MVI56 BSAPS Status Data Area 70 N Navigation 45 No Other Warranties e 79 Normal Data Transfer e 61 Number of Signal Value 30 O Open the Sample Ladder Logic e 15 Opening the Backplane Menu e 47 Opening the Command List Menu 52 Opening the Database Menu 47 Opening the Protocol_Serial_BSAP Menu 47 Opening the Serial Port Menu e 52
83. roSoft Color Status Indication Module CFG Green On Data is being transferred between the module and a remote terminal using the Configuration Debug port Off No data is being transferred on the Configuration Debug port P1 Green On Data being transferred between master and port 1 Off No data P2 Green On Data being transferred between master and port 2 Off No data APP Amber Off The MVI56 BSAPS is working normally Status On The MVI56 BSAPS module program has recognized a communication error BP ACT Amber On The LED is on when the module is performing a write operation on the backplane Off The LED is off when the module is performing a read operation on the backplane Under normal operation the LED should blink rapidly on and off OK Red Off The card is not receiving any power and is not securely Green plugged into the rack Green The module is operating normally Red The program has detected an error or is being configured If the LED remains red for over 10 seconds the program has probably halted Remove the card from the rack and re insert the card to restart the module s program BAT Red Off The battery voltage is OK and functioning On The battery voltage is low or battery is not present Allow battery to charge by keeping module plugged into rack for 24 hours If BAT LED still does not go off contact ProSoft Technology as this is not a user serviceable item Page 52 of 83 ProSoft Technology Inc September 22 2008 Dia
84. rovements and or changes in this manual or the product may be made at any time These changes will be made periodically to correct technical inaccuracies or typographical errors Warnings UL Warnings A Warning Explosion Hazard Substitution of components may impair suitability for Class Division 2 B Warning Explosion Hazard When in Hazardous Locations turn off power before replacing or rewiring modules Warning Explosion Hazard Do not disconnect equipment unless power has been switched off or the area is known to be nonhazardous C Suitable for use in Class division 2 Groups A B C and D Hazardous Locations or Non Hazardous Locations ATEX Warnings and Conditions of Safe Usage Power Input and Output VO wiring must be in accordance with the authority having jurisdiction A Warning Explosion Hazard When in hazardous locations turn off power before replacing or wiring modules B Warning Explosion Hazard Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous C These products are intended to be mounted in an IP54 enclosure The devices shall provide external means to prevent the rated voltage being exceeded by transient disturbances of more than 40 This device must be used only with ATEX certified backplanes D DO NOT OPEN WHEN ENERGIZED Electrical Ratings Backplane Current Load 800 mA 5 V DC 3mA 24V DC Operating Temperature 0 to 60 C 32 to 140 F
85. rsion 2 207 to 208 Operating System 2 209 to 210 Run Number 2 211 to 214 Port 1 Error Status 4 215 to 218 Port 2 Error Status 4 219 to 224 Data Transfer Status 6 225 Port 1 Current Error Index 1 226 Port 1 Last Error Index 1 227 Port 2 Current Error Index 1 228 Port 2 Last Error Index 1 229 to 248 Spare 20 249 Read Block ID 1 The Read Block ID is an index value used to determine the location of where the data will be placed in the ControlLogix processor controller tag array of module read data Each transfer can move up to 200 words block offsets 2 to 201 of data In addition to moving user data the block also contains status data for the module This last set of data is transferred with each new block of data and is used for high speed data movement The Write Block ID associated with the block requests data from the ControlLogix processor Under normal program operation the module sequentially sends read blocks and requests write blocks For example if three read and two write blocks are used with the application the sequence is as follows R1W1 gt R2W2 gt R3W1 gt R1W2 gt R2W1 gt R3W2 gt R1W1 ProSoft Technology Inc Page 61 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Reference Bristol Babcock Serial Slave Module Write Block These blocks of data transfer information from the ControlLogix processor to the module The structure of the output image used to transfer this data is shown in the f
86. s that must be set on program initialization Only use this command if you must force the module to re boot Exiting the Program Caution Some of the commands available to you from this menu are designed for advanced debugging and system testing only and can cause the module to stop communicating with the processor or with other devices resulting in potential data loss or other failures Only use these commands if you are specifically directed to do so by ProSoft Technology Technical Support staff Some of these command keys are not listed on the menu but are active nevertheless Please be careful when pressing keys so that you do not accidentally execute an unwanted command Press Esc to restart the module and force all drivers to be loaded The module will use the configuration stored in the module s Flash ROM to configure the module 4 1 4 Database View Menu Press D from the Main Menu to open the Database View menu Use this menu command to view the current contents of the module s database Press to view a list of commands available on this menu i D Database Menu Display Menu Redisplays refre shes this menu EIE FY Selects page 0 1000 2000 or 3000 S Show Again TA Redisplays last selected page of data Goes hack five pages of data Goes back one page of data Goes fornard five pages of data Goes fonnard one page of data Displays data in decimal format Displays data in hexformat
87. serted completely into the rack If this does not cure the problem contact ProSoft Technology Support ProSoft Technology Inc Page 53 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Diagnostics and Troubleshooting Bristol Babcock Serial Slave Module 4 2 2 Troubleshooting Use the following troubleshooting steps if you encounter problems when the module is powered up If these steps do not resolve your problem please contact ProSoft Technology Technical Support Processor Errors Problem Description Steps to take Processor Fault Verify that the module is plugged into the slot that has been configured for the module Verify that the slot in the rack configuration has been set up correctly in the ladder logic Processor I O LED flashes This indicates a problem with backplane communications Verify that all modules in the rack are configured in the ladder logic Module Errors Problem Description BP ACT LED remains off or blinks slowly Steps to take This indicates that backplane transfer operations are failing Connect to the module s Configuration Debug port to check this To establish backplane communications verify the following items The processor is in Run mode The backplane driver is loaded in the module The module is configured for read and write block data transfer The ladder logic handles all read and write block situations The module is configured in
88. sor to the module 224 Backplane Transfer Reads Contains the total number of read blocks transferred from the module to the processor 225 Backplane Blocks Parsed 226 Backplane Transfer Errors Contains the total number of block errors recognized by the module 227 Current Error Port 1 For a slave port this field contains the value of the current error code returned For a master port this field contains the index of the currently executing command 228 Last Error Port 1 For a slave port this field contains the value of the last error code returned For a master port this field contains the index of the command with the error 229 Current Error Port 2 For a slave port this field contains the value of the current error code returned For a master port this field contains the index of the current executing command 230 Last Error Port 2 For a slave port this field contains the value of the last error code returned For a master port this field contains the index of the command with an error A data file should be allocated in the ladder logic to hold this block of data The size of the block of data is 35 words ProSoft Technology Inc September 22 2008 Page 71 of 83 MVI56 BSAPS ControlLogix Platform Reference Bristol Babcock Serial Slave Module Page 72 of 83 ProSoft Technology Inc September 22 2008 Support Service amp Warranty MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module
89. t that the Customer experiences a problem with the Product for any reason Customer should contact ProSoft Technical Support at one of the telephone numbers listed above page 73 A Technical Support Engineer will request that you perform several tests in an attempt to isolate the problem If after completing these tests the Product is found to be the source of the problem we will issue an RMA c All returned Products must be shipped freight prepaid in the original shipping container or equivalent to the location specified by ProSoft and be accompanied by proof of purchase and receipt date The RMA number is to be prominently marked on the outside of the shipping box Customer agrees to insure the Product or assume the risk of loss or damage in transit Products shipped to ProSoft using a shipment method other than that specified by ProSoft or shipped without an RMA number will be returned to the Customer freight collect Contact ProSoft Technical Support for further information d A 10 restocking fee applies to all warranty credit returns whereby a Customer has an application change ordered too many does not need etc Page 74 of 83 ProSoft Technology Inc September 22 2008 Support Service amp Warranty MVI56 BSAPS ControlLogix Platform 6 2 2 Bristol Babcock Serial Slave Module Procedures for Return of Units Under Warranty A Technical Support Engineer must approve the return of Product under ProSoft s Warranty
90. technology com Languages spoken include French English ProSoft Technology Inc Page 73 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Support Service amp Warranty Bristol Babcock Serial Slave Module 6 2 North America Latin America excluding Brasil location in California 1 661 716 5100 support prosoft technology com mailto support prosoft technology com Languages spoken include English Spanish For technical support calls within the United States an after hours answering system allows pager access to one of our qualified technical and or application support engineers at any time to answer your questions Brasil location in Sao Paulo 55 11 5084 5178 eduardo prosoft technology com mailto eduardo prosoft technology com Languages spoken include Portuguese English Return Material Authorization RMA Policies and Conditions The following RMA Policies and Conditions collectively RMA Policies apply to any returned Product These RMA Policies are subject to change by ProSoft without notice For warranty information see Limited Warranty In the event of any inconsistency between the RMA Policies and the Warranty the Warranty shall govern 6 2 1 All Product Returns a In order to return a Product for repair exchange or otherwise the Customer must obtain a Returned Material Authorization RMA number from ProSoft and comply with ProSoft shipping instructions b In the even
91. the enclosed CD and are available at no charge from our web site http www prosoft technology com Printed documentation is available for purchase Contact ProSoft Technology for pricing and availability Asia Pacific 603 7724 2080 Europe Middle East Africa 33 5 34 36 87 20 Latin America 1 281 298 9109 North America 1 661 716 5100 Your Feedback Please We always want you to feel that you made the right decision to use our products If you have suggestions comments compliments or complaints about the product documentation or support please write or call us ProSoft Technology 1675 Chester Avenue Fourth Floor Bakersfield CA 93301 1 661 716 5100 1 661 716 5101 Fax http www prosoft technology com Copyright ProSoft Technology Inc 2000 2008 All Rights Reserved MVI56 BSAPS User Manual September 22 2008 ProSoft Technology ProLinx inRAx ProTalk and RadioLinx are Registered Trademarks of ProSoft Technology Inc Contents MVI56 BSAPS ControlLogix Platform Bristol Babcock Serial Slave Module Contents Please Read This Notice 2 EER RE OE EE N OR EE ER RE A 2 Battery RT ie RA EE EE RE 3 Prosoft Product Documentation is sistiese e AE Ge Ke OGE ERA e ek AE ee Fa AE 3 det gelee dl ENE EE HOE ON EE EE RE RE 3 Guide to the MVI56 BSAPS User Manual 7 1 Start Here 9 1 1 System Requirements sista itr a ain ida alae ine are it ee 9 1 2 Package Contents EE dal eden aed ein tines d
92. ut modification or for advanced applications you can incorporate the sample program into your existing application The inRAx Solutions CD provides one or more versions of the sample ladder logic The version number appended to the file name corresponds with the firmware version number of your ControlLogix processor The firmware version and sample program version must match 1 7 1 To Determine the Firmware Version of your Processor Important The RSLinx service must be installed and running on your computer in order for RSLogix to communicate with the processor Refer to your RSLinx and RSLogix documentation for help configuring and troubleshooting these applications 1 Connect an RS 232 serial cable from the COM serial port on your PC to the communication port on the front of the processor 2 Start RSLogix 5000 and close any existing project that may be loaded 3 Open the Communications menu and choose Go Online RSLogix will establish communication with the processor This may take a few moments 4 When RSLogix has established communication with the processor the Connected To Go Online dialog box will open Connected To Go Online xi Minor Faults Redundancy Nonvolatile Memory Options General Date Time Major Faults Condition The project file Controller ACD was not found in your project directory Connected Controller Controller Name Controller Controller Type 1756 L55 A 1756 M13 A ControlLogix5555 Controlle
93. warned therefore to check this Warranty carefully to see that it correctly reflects those terms that are important to the Customer 6 3 9 Allocation of Risks This Warranty allocates the risk of product failure between ProSoft and the Customer This allocation is recognized by both parties and is reflected in the price of the goods The Customer acknowledges that it has read this Warranty understands it and is bound by its Terms 6 3 10 Controlling Law and Severability This Warranty shall be governed by and construed in accordance with the laws of the United States and the domestic laws of the State of California without reference to its conflicts of law provisions If for any reason a court of competent jurisdiction finds any provisions of this Warranty or a portion thereof to be unenforceable that provision shall be enforced to the maximum extent permissible and the remainder of this Warranty shall remain in full force and effect Any cause of action with respect to the Product or Services must be instituted in a court of competent jurisdiction in the State of California ProSoft Technology Inc Page 79 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Support Service amp Warranty Bristol Babcock Serial Slave Module Page 80 of 83 ProSoft Technology Inc September 22 2008 Index Index Backplane 56 29 BSAP Data Element e 31 BSAP Port x 32 BSAPS Config 30 Module 29 Adding a M
94. y Inc Page 65 of 83 September 22 2008 MVI56 BSAPS ControlLogix Platform Reference Bristol Babcock Serial Slave Module 3 Notice how the DF1 driver is opened and the driver is looking for a processor on node 1 If the network is being browsed then you will not be able to stop this driver To stop the driver your RSWho screen should look like this IV Autobrowse Not Browsing je fresh Ad Workstation PSFT VAIO 1 Hes Linx Gateways Ethernet we ae es AB_DF1 1 DH 485 ie AB DF1 1 Gatew DH 485 Branches are displayed or hidden by clicking on the or the icons Hs AB_DF1 1 DH 485 4 When you have verified that the driver is not being browsed go to Communications gt Configure Drivers You may see something like this Configure Drivers Available Driver Types 7 m Configured Drivers Status Running Name and Description AB DF1 1 DH485 Sta 10 COM1 RUNNING If you see the status as running you will not be able to use this com port for anything other than communication to the processor To stop the driver press the Stop on the side of the window Configure Startup Start Stop Delete 5 After you have stopped the driver you will see the following Configure Drivers gt Driver Types z Configured Drivers Name and Description Status AB_DF1 1 DH485 Sta 10 COM1 STOPPED Stopped Page 66 of 83 ProSoft Technol
Download Pdf Manuals
Related Search
Related Contents
お店用・業務用掃除機 Philips HDR3700 User's Manual Application Note CMX-Micronet for 78K0 Family Application manu comté mes nuits sans robert suzy raconte Polycom CX 300 User Guide ESTUDIO DE PORTABICICLETAS 2005 VIDEOWALL & PUBLIC INFORMATION ヤマザキマザック株式会社 parte 2 - MCZ GROUP SpA Copyright © All rights reserved.