1. M 13 PolyGard is a registered trademark of MSR Electronic GmbH GAADT531193 E 1011 d relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual INEL Specifications subject to change without notice USA 160104 Page 30f 13 CONTROLS Electrochemical Chlorine Transmitter 1 Intended Use The PolyGard I analog digital gas transmitter AT 1193 with digital processing of the measuring values and temperature compensation is used for the continuous monitoring of the ambient air to detect the presence of Chlorine gas Main application ranges are waterworks sewage plants swimming pools etc The intended sites are all areas being directly connected to the public low voltage supply e g residential commercial and industrial ranges as well as small enterprises according to EN50 082 The PolyGard Cl analog digital transmitter must not be used in potentially explosive atmospheres The transmitter must only be employed in areas within the environmental conditions as specified in the Technical Data 2 Functional Description 2 1 Control Mode The analog output can be selected as current signal with 0 4 20 mA or as voltage signal 0 2 10 V In the 4 20 mA mode and without any supplementary options the AT 1193 also works in the 2 wire technique 2 2 Sensor The sensor portion of the tr
2. The following parameters are factory set Alarm threshold 1 Relay 1 5 ppm Alarm threshold 2 Relay 2 8 ppm Switching hysteresis 1 ppm 6 Inspection and Service Inspection service and calibration of the transmitters should be done by trained technicians and executed at regular intervals We therefore recommend concluding a service contract with INTEC Controls or one of their authorized partners According to EN 45544 4 inspection and service has to be executed at regular intervals The maximum intervals have to be determined by the person responsible for the gas warning system according to the legal requirements INTEC Controls recommends checking the PolyGard Transmitter every three months and maintaining it every 12 months If different intervals are indicated always consider the shortest interval Inspections and services must be documented The date for the next maintenance has to be affixed to the transmitter 6 1 Inspection The PolyGard Transmitter should be checked regularly by a competent person The following has to be checked in particular e Maintenance calibration interval not exceeded e Visual inspection of the transmitter including cable for damage etc e Remove dust deposits especially at the gas inlet 6 2 Service and Calibration When performing the maintenance you have to do the calibration and the functional test in addition to the inspection e Calibration See section 5 e Functional test Ch
3. Carbon monoxide CO Hydrogen H2 300 0 0 Nitrogen dioxide NOz Nitrogen monoxide NO Sulphur dioxide SO 20 35 5 Power supply Power consumption without options Analog mode Output signal Analog output signal Selectable Current tension Starting point 0 20 18 28 VDC AC reverse polarity protected 2 wire mode only VDC 22 mA max 0 6 VA 0 4 20 mA load x 500 Q 0 2 10 V load 2 50k Q proportional overload and short circuit proof 1 The table doesn t claim to be complete Other gases too can have an influence on the sensitivity The mentioned cross sensitivity data are only reference values valid for new sensors Y relevant 12700 Stowe Drive Suite 100 P CONTROLS AT 1193 UserManual INEC cifications subject to change without notice Physical o O Enclosure stainless steel Type 5 Stainless steel V2A Enclosure colour Natural brushed Dimensions W x H x D 113 x 135 x 45 mm 5 35 x 4 5 x 1 8 in Weight Approx 0 5 kg 1 1 Ib Protection class IP55 Mounting Wall mounting pillar mounting Enclosure Plastic Type A Polycarbonate Flammability UL 94 V2 Enclosure colour Light grey RAL 7032 Dimensions W x H x D 94 x 130 x 57 mm 3 7 x 5 12 x 2 24 in Weight Approx 0 3 kg 0 6 Ib Protection class IP 65 Mounting Wall mounting Cable entry Standard 1 x M 20 Wire connection Screw type terminal 0 25 to 2 5 mm 24 to 14 AWG Wi
4. IVISR ELECTRONIC MEL CONTROLS PolyGard AT 1193 Electrochemical Chlorine Transmitter Serial No AT03 005 User Manual October 2011 January 04 2016 Revision PolyGard is a registered trademark of MSR Electronic GmbH GAADT531193 E 1011 a relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual INEL Specifications subject to change without notice USA 160104 Page 20f 13 CONTROLS 1 Intended Se iiie aana aa aaae ae a A EAE a REAA e TE aaa aS EAA aA EAKR EA SEA aa ENARA SiS EANES REA REDRAR 3 2 Functional Descriptioh cecinere etre eto rk Enn aaa aaraa raaa a eaaa a FRA ER VAR ERR Nonne RE 3 A EEEe vici ms 3 IMEEM E 3 EMEMNIICIrilm 4 3 1 Mounting Instr ctlornis ide ieee tto eei ef dn e e ee ecd n lh Pear ned a eae 4 SM uw 4 4 Electrical ConnectIOl orto nee ERERERRR3R RAP KR KRNERRXER RRRARREKRARKRFEXRRARRRAEKRRR AXERRERRRRRRKRARRRRERKRARRRARKRRRKRERERERRRAR 4 4 1 Wiring Connection rccte cea edi boc ec eee ned eee 5 ME OUI eem 5 5 1 Correction of the Zero point at the Analog Output Signal seeee 5 5 2 Calibration eee 6 5 2 1 Zero point m 6 Do Aa ED 6 5 3 3 Calculation of Control Voltage sss
5. Installation Note Avoid any force e g by thumb on the sensor element during operation or installation Electronics can be destroyed by static electricity Therefore do not touch the equipment without a wrist strap connected to ground or without standing on a conductive floor acc to DIN EN100015 3 1 Mounting Instructions When choosing the mounting site please pay attention to the following The specific weight of Chlorine CL is higher than that of air factor 2 4 Recommended mounting height is 0 2 m 0 7 ft to 0 3 m 1 ft above floor Choose mounting location of the sensor according to the local regulations Consider the ventilation conditions Do not mount the transmitter in the center of the airflow air passages suction holes Mount the transmitter at a location with minimum vibration and minimum variation in temperature avoid direct sunlight Avoid locations where water oil etc may influence proper operation and where mechanical damage might be possible Provide adequate space around the sensor for maintenance and calibration work Duct mounting Mount only in a straight section of duct with minimum air vortex Keep a minimum distance of 1 m 3 5 feet from any curve or obstacle Mount only in a duct system with a maximum air velocity of 10 m s 2000 ft min or less Mounting must be performed so that the probe openings are in line with the airflow 3 2 Installation Open the cover Unplug basic PCB car
6. connect 24 VAC at pin 2 and pin 4 or 24 VDC at pin 2 and 0 VDC at pin 4 Short circuit R 10 Ohm burns up Analog_Ou 0 VAC DC Transmitter AT 1193 PolyGard is a registered trademark of MSR Electronic GmbH GAADT531193 E 1011 a relevant 12700 stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols art93 UserManual NE Specifications subject to change without notice USA 160104 Page 120f 13 CONTROLS PCB Terminal block Fig 3 Anal Output Start Point E 20 Manual Calibration Function Relay R2 a fF WN gt N U A AONI e a eo a A A X5 Anal Output EN V DC mA Selection analog output signal Fig 4 Jumper 0 20 Jumper V A Output signal Calibration adapter Fig 5 Type CONKIT E CH AT PolyGard is a registered trademark of MSR Electronic GmbH GAADT531193_E_1011 r relevant 12700 Stowe Drive Suite 100 Poway CA 92064 I Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual INEL Specifications subject to change without notice USA 160104 Page 130f 13 CONTROLS 11 Part Disposal Since August 2005 there are EC wide directives defined in the EC Directive 2002 96 EC and in national codes concerning the waste electrical and electronic equipment and also regarding this device For private households there are specia
7. installation techniques and with codes standards and proper safety procedures for control installations and the latest edition of the National Electrical Code ANSI NFPA70 It is also essential to follow strictly all instructions as provided in the user manual 12 3 Maintenance It is recommended to check the PolyGard transmitter regularly Due to regular maintenance any performance deviations may easily be corrected Re calibration and part replacement in the field may be implemented by a qualified technician and with the appropriate tools Alternatively the easily removable plug in transmitter card with the sensor may be returned for service to INTEC Controls 12 4 Limited Warranty MSR Electronic GmbH and INTEC Controls warrants the PolyGard transmitters for a period of 2 years from the date of shipment against defects in material or workmanship and 12 months normal exposure for sensor element Should any evidence of defects in material or workmanship occur during the warranty period INTEC Controls will repair or replace the product at their own discretion without charge This warranty does not apply to units that have been altered had attempted repair or been subject to abuse accidental or otherwise The warranty also does not apply to units in which the sensor element has been overexposed or gas poisoned The above warranty is in lieu of all other express warranties obligations or liabilities This warranty applies only to the Pol
8. pin 4 can destroy the transmitter 5 Commissioning Consider commissioning instructions at any exchange of the sensor element as well Only trained technicians should perform the following e Check mounting location e Select output signal form Current or voltage and starting point 0 or 20 See fig 4 e Check power voltage e Check PCB ATO3 for correct mounting at X4 and X5 Required instruments for commissioning calibration of the transmitter e Test gas bottle with synthetic air 20 O2 80 96 N or chlorine free ambient air e Test gas bottle with Cl ppm in the range of 30 70 96 of the measuring range Rest is synthetic air e Gas pressure regulator with flow meter to control the gas flow to 150 ml min e Calibration adapter with tube Calibration set CONKIT E CH AT See fig 5 e Digital voltmeter with range 0 300 mV accuracy 1 e Small screwdriver Note Prior to calibration the sensor must be connected to the power supply and fully stabilized for at least 6 hours without interruption Please observe proper handling procedures for test gas bottles Attention CL calibration gas is toxic never inhale the gas Symptoms Chemical burn dizziness headache and nausea Procedure if exposed Take the victim into fresh air at once call a doctor 5 1 Correction of the Zero point at the Analog Output Signal The analog output signal is factory set to the zero point If necessary a manual adaptation of the analo
9. ange Cl ppm Signal start 0 V 0 mA Control voltage mV 200 mV x test gas concentration Cl ppm measuring range Cl ppm Example Measuring range 20 ppm Test gas concentration 10 ppm Cl Control voltage Signal start 2 V 4 mA 120 mV Control voltage Signal start 0 V 0 mA 100 mV Signal start 2 V 4 mA Signal start 0 V 0 mA 160 mV x 10 ppm 40 mVY 120mV 200 mV x10 ppm 100 mV 20 ppm 20 ppm PolyGard is a registered trademark of MSR Electronic GmbH GAADT531193 E 1011 d relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual INEL Specifications subject to change without notice USA 160104 Page 7 0f 13 CONTROLS 5 4 Option Relay Output The two relays are activated in dependence of the gas concentration If the gas concentration exceeds the adjusted alarm threshold the corresponding relay switches on If the gas concentration falls below the threshold minus hysteresis the relay switches off again The contact function for relay 2 NC normally closed or NO normally open can be selected via the jumper NO NC See fig 1 and 3 Relay 1 is equipped with a change over contact Via the ModBus interface the two alarm thresholds and the hysteresis are freely adjustable at the PC within the measuring range The procedure can be read from the user manual ModBus Software
10. ansmitter is a sealed electro chemical cell with three electrodes sensing counter and reference The ambient air to be monitored diffuses through a membrane filter into the liquid electrolyte of the sensor The chemical process of the measurement is one of reduction where one molecule of the target gas is exchanged for one molecule of oxygen The reaction drives the oxygen molecule to the counter electrode generating a DC microampere signal between the sensing and reference electrodes This signal is linear to the volume concentration of the sensed gas The signal is evaluated by the connected amplifier and transformed into a linear output signal Electrochemical processes always lead by and by to a loss of sensitivity Therefore regular calibration of zero point and gain is obligatory See also section 6 Caution There is a small quantity of corrosive liquid in the sensor element If in case of damage persons or objects touch the liquid you have to clean the affected areas as fast and carefully as possible with tap water Out of use sensors must be disposed in the same way as batteries PolyGard is a registered trademark of MSR Electronic GmbH GAADT531193 E 1011 d relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual INEL Specifications subject to change without notice USA 160104 Page 40f 13 CONTROLS 3
11. e tension at X4 in spite of gas concentration Signal Pin 4 not wired correctly Check the wiring 8 Cross sensitivity Data The cross sensitivity can be read from the table Technical Data see section 9 The table doesn t claim to be complete Other gases can have an influence on the sensitivity too The indicated sensitivity data are only standard values referring to new sensor elements ard is a registered trademark of MSR Electronic GmbH GAADT531193 E 1011 a relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual IMEL 9 Technical Data 104 Page 9 of 1 lt CONTROLS General sensor performances pu Chlorine Cl2 Gas type Sensor element Measuring range Electrochemical diffusion 0 10 ppm factory set 0 20 ppm optional Temperature range 10 C to 45 C 14 F to 113 F Atmosphere 15 Humidity 15 95 RH non condensing Storage temperature range 5 C to 30 C 41 F to 86 F Storage time Mounting height Max 6 months 0 2m 0 7ft Stability amp resolution 0 1 ppm Repeatability 2 of reading Long term output drift lt 2 signal loss year too lt 90 sec Response time Life expectancy Cross sensitivity Concentration ppm gt 2 years normal operating environment Reaction ppm Cl 300
12. eck the output signal at the test pins during calibration PolyGard is a registered trademark of MSR Electronic GmbH GAADT531193 E 1011 d relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual INEL Specifications subject to change without notice USA 160104 Page 80f 13 CONTROLS 6 3 Exchange of Sensor Element Consider static electricity See point 3 Sensor should always be installed without power applied Unplug basic PCB ATO3 carefully from the bottom part Unplug old sensor element from the PCB Take the new sensor out of the original packing Plug the sensor element in the PCB Replug the PCB ATO3 in the terminal blocks X4 X5 carefully Calibrate according to section 5 7 Troubleshooting 7 1 Analog Mode Output signal lt 3 mA 1 5 V Jumper 0 20 not set Check jumper position and or control voltage 30 mV only for starting signal 2V 4 mA Measure tension at X4 Power voltage not applied Two wire Pin 1 and 4 Three wire Pin 1 and 2 PCB ATO3 not plugged in correctly at X4 Replug PCB correctly and X5 Output signal gt 22 mA 220 mV Short circuit Check the wiring Control voltage does not reach Sensor element not calibrated Calibrate sensor element the calculated value Replace sensor element No reaction of the output signal Power voltage not applied Measur
13. efully from the bottom part Fix bottom part by screws vertically to the wall terminal blocks to the ground Replug the basic PCB at X4 and X5 with care Replace the cover 4 Electrical Connection Consider static electricity See 3 Mounting Installation of the electrical wiring should only be executed by a trained specialist according to the connection diagram without any power applied to conductors and according to the corresponding regulations Avoid any influence of external interference by using shielded cables for the signal line but do not connect the shield Recommended cable for analog mode J Y St Y 2x2x0 8 LG 20 AWG max loop resistance 73 O km 20 8 Q 1000 ft It is important to ensure that the wire shields or any bare wires do not short the mounted PCB PolyGard is a registered trademark of MSR Electronic GmbH GAADT531193 E 1011 d relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual INEL Specifications subject to change without notice USA 160104 Page 50f 13 CONTROLS 4 1 Wiring Connection e Open the cover Unplug basic PCB carefully from terminal blocks X4 and X5 e Insert the cable and connect cable leads to terminal blocks See fig 1 e Replug the PCB in the terminal blocks X4 X5 with care Replace the cover Note The connection of the power supply at the output signal X4
14. g signal is possible within 10 sec after having applied the supply voltage e Jumper 0 20 for signal start has to be set 4 mA or 2 V e Connect digital voltmeter 300 mV at test pint Test measuring signal 40 mV 4 0 mA e Switch on the operating voltage e Each pressing on the Zero push button increases the signal by 0 5 mV 0 05 mA Press the button repeatedly until the measuring signal reaches 40 0 2 mV After 44mV the signal starts again at 36 mV The correction is only possible within the 10 seconds after having switched on the power supply An impulse pause of more than 10 sec cancels the release of the correction function PolyGard is a registered trademark of MSR Electronic GmbH GAADT531193 E 1011 d relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual INEL Specifications subject to change without notice USA 160104 Page 6 0f 13 CONTROLS 5 2 Calibration Manual calibration is only possible if the transmitter is equipped with the push button Zero and the potentiometer Gain version for manual calibration 5 2 1 Zero point e Connect digital voltmeter to pin Test e Connect calibration adapter carefully to the sensor element e Apply synthetic air 150 ml min 1 Bar 14 5 psi 10 or Chlorine Cl2 free ambient air e Wait 2 minutes u
15. l collecting and recycling possibilities For this device isn t registered for the use in private households it mustn t be disposed this way You can send it back to your national sales organization for disposal If there are any questions concerning disposal please contact your national sales organization Outside the EC you have to consider the corresponding directives 12 Notes and General Information It is important to read this user manual thoroughly and clearly in order to understand the information and instructions The PolyGard transmitters must be used within product specification capabilities The appropriate operating and maintenance instructions and recommendations must be followed Due to on going product development MSR and INTEC Controls reserve the right to change specifications without notice The information contained herein is based upon data considered to be accurate However no guarantee is expressed or implied regarding the accuracy of this data 12 1 Intended Product Application The PolyGard Cl transmitters are designed and manufactured for control applications and air quality compliance in commercial buildings and manufacturing plants 12 2 Installers Responsibilities It is the installers responsibility to ensure that all PolyGard transmitters are installed in compliance with all national and local codes and OSHA requirements Installation should be implemented only by technicians familiar with proper
16. ntil the signal is stable push button Zero for 5 seconds After successful calibration the measuring signal is corrected automatically Depending on the selected signal starting point the measuring signal shows the following values Signal start at 2 V or 4 mA 40 mV 0 ppm Signal start at O V or 0 mA OmV 0 ppm If the zero point is out of the admissible range gt 20 mV at starting point 0 gt 60 mV at starting point 20 before calibration there is no correction of the measuring signal The sensor has to be replaced e Remove calibration adapter carefully by turning lightly Check the sensor for correct mounting 5 3 2 Gain e Connect digital voltmeter to pin Test e Connect calibration adapter carefully to the sensor element e Apply calibration test gas Cl 150 ml min 1 Bar 14 5 psi 10 e Wait three minutes until the signal is stable adjust control voltage with potentiometer Gain until the signal corresponds to the calculated value 2 mV see 5 3 3 Calculation of Control Voltage e Remove calibration adapter with a careful light turn Check the sensor for correct mounting By limiting the gain factor calibration will not be possible any more when the sensitivity of the sensor reaches a residual sensitivity of 30 Then the sensor has to be replaced 5 3 3 Calculation of Control Voltage Signal start 2 V 4 mA Control voltage mV 160 mV x test gas concentration Cl ppm 40 mV measuring r
17. re distance Current signal ca 500 m 1500 ft Voltage signal ca 200 m 500 ft Guidelines EMCDirective2004 108 EEC CE SOS Approvals NEM Warranty Two years material and workmanship 12 months normal exposure for sensor element Options Relay output o o 30 VAC DC 0 5 A potential free SPDT Heating ojo r relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual IMEC Specifications subject to change without notice USA 160104 Page 110f13 CONTROLS 10 Figures Application Analog mode Fig 1 7 Bus B Controller 6 Bus A 5 4 20 mA Inp 1 4 20 mA 4 Analog Out 2 24V 3 24 VDC Out 3 OV 20V 4 1 24 VDC 5 X4 X5 Transmitter AT 1193 Two wire connection 4 20 mA output signal without options Le Do not connect power supply at this pin 0 VDC 24 VAC or OVAC will destroy the transmitter 7 Bus B Option Controller 6 Bus A Relay 5 4 20mA Inp g4 4 20 mA 4 Analog Out r2 24 V 3 24 V Out 3 OV 20V mooo 124VAC IDC N Piz 5 X4 _ R2 eo X5 Transmitter AT 1193 Three wire connection VDC output signal 0 20 mA output signal Relay output LCD display Heating Do not
18. sssesseene nennen mener 6 54 Option Relay OUtpUL iieri nte iaai ERER E NER RRUR E RR checnensaaies danhadeaccsassanaccattadccdes 7 6 Inspection and Service 4 iuieiiieeeeeceeii erneuten cen pn danni era E ceeuedtecedesouedseeeaceecedeaieentesstedeedeeeces 7 SUME ei T ME 7 0 2 Service and Calibration odore iere itte a be de enar EUR E ERU EP Re Fe cH EU aee EORR ERE a 7 6 3 Exchange of Sensor Element aiiis nies tek E abe Add te ku dd db La ac 8 7 Troubleshooting E 8 GCA Analog MOGe coii eet ed ERI end eee ate Uv Hae Mete s 8 8 Cross sernsitivity Data initiiert EE IRE nie Ex meni ERA AAR 8 9 Technical Data iier RRRERREXRREARMRRRIRRER RAREBEREEAXARRRRRRRERRERAR ERAS RRSARERARE MK PERRRRARARRAR SERE EXE ERRRXRRNR AREER iaia 9 LEM JP 11 11 Part Disposal iR ER ERRRAREEEERRERERRRKRERENEER E aa aaa a AKA EARN aaa Eaa NEE a ENa 13 12 Notes and General Information ccccesseeeeeeseeceeeenee cee seeeeeeeseaeeeeeeeeaee sens eaeeseeseaeeesaseeaeeeenseeneeenees 13 12 1 Intended Product Application ccccccceccececeeeeeeeneaeceeeeeeeeseceacaeceeeeeeeesesecaueaeeseeeesesseesenaeees 13 12 2 Installers Responsibilities eoo etna rent hne Lue nee ee nnno o n ehe nire eue 13 12 3 M intenaNCe EH H ER 13 12 4 IBhcoRiaco
19. yGard transmitter MSR Electronic GmbH and INTEC Controls shall not be liable for any incidental or consequential damages arising out of or related to the use of the PolyGard transmitters If the PolyGard transmitter needs to be returned to INTEC Controls for service an RMA number must be obtained prior to sending PolyGard is a registered trademark of MSR Electronic GmbH GAADT531193 E 1011 d relevant 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 amp 888 GO INTEC relevantsolutions com inteccontrols

Download Pdf Manuals

image

Related Search

Related Contents

Manual de funcionamiento  取扱説明書 - ビデオトロン  Video Surveillance Management Software NVClient V5  Übersetzung Rückfahrsystem R7-Funk  ATV-571D 取扱説明書  Targus Getta Backpack  Samsung AW08N0AF User Manual  Sharkoon Rush Headset  cuisson sv-31 • sv-41 - Сервисный центр Деловая Русь. Ремонт  PowerStream SA High Pressre Coolant Service Manual  