Home

power + sa 10 kva double conversion ups

image

Contents

1. 4 Press Ent to change the automatic restart status Power SA User Guide rel 3 0 55 56 AUTO RESTART AFTER COMPLETE DISCHARGE IS ENABLED TO CHANGE PRESS ENTER TO EXIT PRESS ESC 5 new automatic restart status is displayed Press Esc to return to the Main Screen AUTO RESTART AFTER COMPLETE BATT DISCHARGE IS NOW DISABLED TO EXLT PRESS ESC Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 11 MISCELLANEOUS FUNCTIONS This section describes infrequently used but important features 11 1 Manually entering or leaving bypass mode When the AC input power is normal it is handled by the UPS in one of two ways e The input AC power is sent to the inverter where it is regulated and passed on to the load This is called normal mode or inverter mode e he input AC power bypasses the inverter entirely and goes directly to the load with no regulation This is called Bypass Mode Usually only a technician will need to manually switch the UPS to Bypass mode THERE ARE TWO WAYS TO MANUALLY ENTER OR LEAVE BYPASS MODE eUsing the manual bypass switch on the UPS rear panel eUsing the system console 11 1 1 Entering bypass mode via the manual bypass switch Note the Manual Bypass Switch is OPTIONAL EQUIPMENT not standard If the customer desires a Manual Bypass Switch it must be specifically ordered as a separate item The manual bypass switch on
2. SA User Guide rel 3 0 If Bypass Mode was invoked manually the message Manual Bypass appears ALARM LED LIT 59 12 IN THE EVENT AN AC POWER OUTAGE If a power outage occurs The Alarm LED lights up and the audible alarm sounds The UPS continues operating drawing its power from the batteries The POWER SA console looks like this BATTERY LED LIT ACINPUT NORMAL BATTERY BYPASS UPS ON BATTERY MODE L1 50 L2 50 13 571 ALARM LED LIT The Alarm and Battery LEDs are lit As the battery discharges the number of stripes in the battery icon on the screen decreases BATTERY LED LIT ACINPUT NORMAL BATTERY BYPASS UPS ON BATTERY MODE L1 50 L2 50 L3 51 8 O us LED LIT 60 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD When the BATTERY LOW message appears there are only a few seconds before the battery is exhausted Now is the time to shut down any computers connected to the UPS if you have not already done so BATTERY LED LIT ACINPUT NORMAL BATTERY BYPASS BATTERY UPS ON LOW BATTERY LOW L1 50 L2 50 L3 51 ALARM LED LIT When the UPS battery is exhausted the UPS does one of two things depending on the setting of Auto restart mode If Auto restart is DISABLED the UPS shuts off and remains off even when AC power is restored When AC power is restored you must press the OFF ON button twice to t
3. Ph Gnd L1 L2 L3 Battery input 4 10 mm 10 mm 2 5 mm Use the 1 5 meter long battery cable supplied by Gamatronic 2 Using a screwdriver remove the cable cover from the rear of the POWER SA The uncovered rear panel for the 3 1 configuration is shown in the next illustrations A Power SA User Guide rel 3 0 43 TERMINAL CONNECTIONS AC OUTPUT t BYPASS AC INPUT RECTIFIER AC INPUT BATTERY gt 44 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 3 Connect the cables for Ac Input Bypass Input Output and the Battery cables to the terminals on the rear panel of the UPS Ensure the cables are not live before you begin For the Bypass input use the phase for the Phase connection Use wires of the proper diameter as given on page 43 When you have finished the rear panel should resemble the following diagram 4 i i i 4 i i i i i i i i i i i 4 i HM j i i i TOTE ee ee 1 08 4 Use the supplied battery cable to connect the battery to the UPS 5 Recheck the connections before continuing 6 To protect and conceal the cables and terminals replace the outside cover on the rear of the UPS Power SA User Guide rel 3 0 45 8 1 4 Cable Connections for 1 1 Usage Only an authorized electrician may wire the UPS power connections Do not attempt to wire any of the power connections o
4. 79 Figure 15 Accessing the dip switches 2 79 Figure 16 Location of the dip 80 Figure 17 Components of the terminal assembly e eeeeeeee 84 Figure 18 Reconfiguring from 3 3 to 9 1 eere eere eren nennen nnn nnn nnn nnns 85 Figure 19 Remove the four screws from the rear panel eee 86 Figure 20 Accessing the dip switches 1 enne enne nnne n nnn 86 Figure 21 Accessing the dip switches 2 87 Figure 22 Location Of the dID SWIICRGS 87 Figure 23 Components of the terminal 92 Figure 24 Reconfiguring from 3 3 to 92 Figure 25 Remove the four screws from the rear 93 Figure 26 Accessing the dipswitches 1 ccccsssssecessssssseeeseeensseeeseeensseeeseoeenseseesoeenseesseoeenseessoos 93 Figure 27 Accessing th
5. 52 9 4 Fine tune the output Voltage eot or ores ts eue Des eva se 53 Power SA User Guide rel 3 0 10 11 12 13 14 15 16 17 18 19 20 21 22 23 atn Ow dc eu c aa ch uil a vou e du 55 10 1 Determining the current automatic restart 0 55 10 2 Changing the automatic restart status enne 55 MISCELLANEOUS FUNCTIONS a uc os cect ve Pate a a tua aegre D 57 11 1 Manually entering or leaving bypass 57 11 1 1 Entering bypass mode via the manual bypass switch 57 11 1 2 Entering bypass mode via the system 58 IN THE EVENT OF AN AC POWER OUTAGE enne enn a nhau ausu Deas asas asas s osea asas auus nr ranas 60 USING THE UPS WITH A GENERATOR reinen mean na e sanas e ees aa Iesus e oaa a arr nnna 63 13 1 The Automatic Transfer Switch nennen nennen 63 TROUBLESHOOTING 65 14 1 Alarm sounds and or Alarm LED lights up sese 65 14 2 Electricity returned but UPS remains in Battery 65
6. bee Lies S Dc equ 34 ke Manual Dattery eie bite 34 FIRS T SETUP e 35 Gel Hable COMME te M TT 35 8 1 1 Cable connections for 3 3 usage NO manual bypass 36 8 1 2 Cable connections for 3 3 usage WITH manual bypass 39 8 1 3 Cable Connections for 3 1 43 8 1 4 Cable Connections for 1 1 46 8 2 Installation and Start Up Sequence nennen nnns 49 saint e E etim LM tU UE 49 8 2 2 Verify proper number of input and output 49 9 2 9 SSL TIE WOUNOUT VOlldUg scnmeetieciuo condo und edad iouis ee dcos Sape Stunde Dass 49 9 2 4 SEE UIC SV cielos rnm 49 8 2 5 Modify the screen contrast 50 8 2 6 Set Automatic Restart mode 50 BZ ODE AU ON E Um T mE 50 SETTING SYSTEM PARAMETERS aaia 51 QA Seung tie ClO CK uuo eoe otto use e I sua oe ertet ador that te o tuc hot 51 9 OCUN Sreem CONI IS vani Listar mas ndm ati a 52 9 3 Changing the nominal output voltage
7. Attaching the POWER Stand Alone to its base viii Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 1 SAFETY PRECAUTIONS The POWER SA UPS system is designed for industrial applications and harsh environments Nevertheless the POWER SA UPS system is a sophisticated power system and should be handled with appropriate care following these guidelines 1 1 WARNING HIGH TOUCH CURRENT EARTH CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY e Read this manual carefully before starting installation and operation of the UPS e Review the safety precautions described below to avoid injury to users and damage to the equipment e This UPS is intended for installation in a temperature controlled indoor area that is free from conductive contaminants e All power connections must be completed by a licensed electrician who is experienced in wiring this type of equipment and who is familiar with the local electrical codes and regulations Improper wiring may cause injury to personnel or death or damage to the equipment e Ensure all power is disconnected before performing installation or maintenance e Leave atleast 20 cm of clearance space between the ventilation openings of the UPS and other objects or walls e he UPS must be well grounded to the building s grounding system with a conductor that has a current carrying capacity that matches the rating of the UPS e Battery installation battery mainten
8. IF YOU ARE SURE YOU WANT TO DO THE CHANGES PRESS ENTER ELSE PRESS ESC 76 Power SA User Guide rel 3 0 12 13 14 15 16 17 18 19 GAMATRONIC ELECTRONIC INDUSTRIES LTD The UPS screen informs you that the line configuration changes will be in effect only after all input and output voltages to the UPS have been disconnected and the wire connections and the dipswitches have been adjusted CHANGES WILL BE IMPLEMENTED ONLY AFTER COMPLETE DISCONNECTION OF ALL VOLTAGES AND CHANGING WIRE CONNECTIONS AND DIP SWITCH Disconnect the UPS from all voltages by turning OFF the circuit breakers for AC Input Bypass Input Output and Battery Disconnect the battery cable from the UPS Use a screwdriver to remove the external protective cover from the rear of the UPS refer to Figure 12 Before continuing verify with a multimeter that there is no voltage on any of the cables attached to the terminals For clarity s sake the electrical cables are not shown in Figure 12 Disconnect the cables from the terminal panel the screws from the right side of the internal protective cover the terminal assembly from the UPS refer to Figure 12 The terminal assembly consists of 3 parts the terminal panel the black metal internal protective cover behind it and green connector plugs The terminal assembly should be removed as a single unit there is no need to disassemble into its
9. Mains Mains UPS reconnects failure ada to mains power returns g i UPS fed T1 Time delay for irem maine l Sal normal source absent power confirmation i P T2 Time for ower return p normal source returned confirmed b confirmation Mains failure confirmed T b Mains disconnection from normal source and connection to T3 Load shedding time between reserve source Generator i begins Generator feeding UPS 4 disconnects from UP T4 Time between Generator stops running disconnection of UPS pois or from generator and Starts 8 2 NIS 4 reconnection to mains running Tp UPS fed from Y generator T5 Generator operating time T5 after UPS reconnect to normal source Time Se a ce Pe ce a T6 UPS in battery mode T1 T3 T2 T4 Lf a T6 T6 Figure 8 Timing variables when using a generator and an ATS Power SA User Guide rel 3 0 Figure 9 is an example of the control panel of an ATS The upper part of the control panel consists of a mimic diagram showing the control flow NS 0 means the normal source is not available NS 1 means the normal source is available R is the reserve source The timing variables T1 through T5 are described in Figure 8 The knob at the botto
10. 92 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 19 On the rear panel of the UPS remove the screws that secure the internal UPS body to its external shell See Figure 25 Note the number and position of the screws may differ from that shown in Figure 25 AE inpur j Figure 25 Remove the four screws from the rear panel 20 Grasp the top of the rear panel and pull the UPS body firmly so that it is most of the way out of the external shell see Figure 26 and Figure 27 Figure 26 Accessing the dipswitches 1 Power SA User Guide rel 3 0 93 21 REAR OF UPS 22 94 Figure 27 Accessing the dipswitches 2 On the top front of the UPS body there is a set of three small dipswitches as shown in the diagram When looking at the dipswitches from the front of the UPS the rightmost dipswitch controls the output line configuration For three phase output the rightmost dipswitch should be switched towards the back of the UPS Refer to the diagram J phase output 60Hz dipswitches 1 phase output 0 2 Slave Do not modify Figure 28 Location of the dipswitches FRONT OF UPS Push the UPS body back into the UPS shell and refasten the screws that you removed earlier from the UPS rear panel Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 23 Plug in the 1 1 terminal assembly which you should hav
11. BYPASS x Lr Ps T Fx UPS ON NORMAL MODE L1 7696 L2 82 L3 77 SA Ok POWER In the event of a battery test failure an icon indicating this appears in the lower right quadrant of the screen the alarm LED lights and the audible alarm sounds LEDs lit AC INPUT NORMAL BATTERY BYPASS sly aly 1 px px UPS ON NORMAL MODE L1 76 12 82 Battery test failure 77 Alarm ent A lt LED iit Power SA User Guide rel 3 0 13 In the event of an overload condition an icon indicating this appears in the lower right quadrant of the Main Screen the alarm LED ligits and the audible alarm sounds LEDs lit ACINPUT NORMAL BATTERY BYPASS VL p O 0 PTA UPS ON NORMAL MODE L1 76 L2 82 Overload 539 72 Alarm e A LED iit 14 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 4 2 1 2 BATTERY MODE When the UPS is operating in battery mode the Main Screen first displays the message UPS ON BATTERY MODE BATTERY LED lit ACIMPUT NORMAL BATTERY BYPASS why UPS ON BATTERY MODE S d Battery icon indicates approximate L3 17 battery charge Alarm LED lit battery full battery 1 4 discharged battery 1 2 discharged l battery almost fully discharged As the battery discharges the number of stripes on the ba
12. HH MM SS e The fourth lines shows the date of the log entry DD MM YY e The last line prompts you to scroll up or down to see later or earlier entries 6 2 3 Resetting the event log To erase the current contents of the event log 1 From the Main Screen press the Ent button to display the Main Menu 2 Onthe Main Menu select Advanced Options gt Technicians Menu gt Reset Event Log 9 Press Ent 30 Power SA User Guide rel 3 0 AC INPUT FAIL AC OUTPUT FAULT BATTERY LOW BATTERY TEST FAIL BYPASS NOT READY GAMATRONIC ELECTRONIC INDUSTRIES LTD Table 1 Outstanding alarm messages ALARM MESSAGE Explanation Meaning The voltage of one or more of the input ac phases is out of range or there is no ac input at all The UPS is now in Battery Mode Additional indications The alarm LED lights up and the audible alarm sounds The symbol X appears on the Ac Input screen Action If there is a power outage it is advisable to save any critical open files you are working on before the UPS battery is exhausted See In the event of an ac power outage on page 57 If there is not a power outage check the circuit breaker for the line supplying the UPS with power The circuit breaker may be off Meaning The voltage of at least one of the output ac phases is out of range Additional indications The alarm LED lights up and the audible alarm sounds The symbol X appears on the Ac Output screen Action After
13. INPUT OUTPUT DESIGNATION 3 PHASES 400V EA 3 PHASES 400 EA 3 3 3 PHASES 400V EA 1 PHASE OF 230V 3 1 1 PHASE OF 230V 1 PHASE OF 230V 1 1 Your POWER SA UPS was probably already set at the factory or by your dealer to operate with the number of input and output phases appropriate for your requirements 8 1 Cable connections The cable connections for your POWER SA UPS vary depending on which line configuration is used Refer to the appropriate section below The cable connections on your unit may have a slightly different appearance from those shown in the diagrams in this section The following sections describe installation of the Power in the following configurations e 3 3 using an adaptor without a manual bypass switch section 8 1 1 page 36 e 3 3 using an adaptor that includes a manual bypass switch section 8 1 2 on page 39 e 3 1 section 8 1 3 on page 43 e 1 1 section 8 1 4 on page 46 Power SA User Guide rel 3 0 35 8 1 1 Cable connections for 3 3 usage NO manual bypass This section describes cable connections for using the Power SA in 3 3 configuration using the rear panel adapter that DOES NOT HAVE a manual bypass switch For connections when using the adapter with a manual bypass switch see section 8 1 2 on page 39 Only an authorized electrician may wire the UPS power connections arg Do not attempt to wire any of the power connections on your own To connect the required cables to the UPS f
14. Main Screen displays the message UPS ON BYPASS MODE The ac INPUT BYPASS and ALARM LEDs are lit After 60 seconds in Bypass Mode the audible alarm sounds The UPS goes into bypass mode automatically in the case of an overload or if there is an inverter fault Bypass mode can also be invoked manually If the UPS was put in Bypass mode manually the message Manual Bypass appears on the screen AC INPUT BYPASS LED LIT LED LIT ACINPUT NORMAL BATTERY BYPASS BYPASS MODE If Bypass Mode was invoked L1 76 MANUAL manually the L2 76 BYPASS message Manual L3 76 Bypass appears ALARM LED LIT When an overload condition occurs the UPS moves to Bypass mode until the overload is resolved AC INPUT BYPASS LED LIT LED LIT ACINPUT NORMAL BATTERY BYPASS UPS ON BYPASS MODE E pos OVER OVERLOAD 2 6 condition L3 103 RE o UE ALARM e ets f the UPS went to bypass mode due to a failure of the ac input and the bypass input is still live the ac Input LED will not be lit at this time 18 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 4 2 1 4 UPS OFF OFF mode is invoked by pressing the On Off button twice when the UPS is operating The OFF screen displays the message UPS OFF NO OUTPUT AC INPUT LED LIT ACINPUT NORMAL BATTERY BYPASS UPS OFF NO OUTPUT sp 096 L2 096 0 OFF mode can also be invoked automatically the event of extended ac power o
15. You can continue to adjust another phase or press Esc to return to the main screen OUTPUT VOLTAGE WAS ADJUSTED FOR ANOTHER ADJUSTMENT PRESS ENTER ELSE PRESS ESC Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 10 AUTOMATIC RESTART In the event of a prolonged power outage the UPS turns itself off automatically after the batteries have been exhausted You can instruct the POWER SA to start up automatically so that it will supply current to the load devices when the AC power is restored This feature is called automatic restart If you do not use the automatic restart procedure when the AC power returns the recharging process begins automatically but no power is supplied to the load 10 1 Determining the current automatic restart setting To determine if the automatic restart mode is on or off go to the PROFILE screen To see the UPS Profile screen from the Main Screen press the Down button once UPS PROFILE DATE 05 12 2008 TIME 20 03 08 OUTPUT VOLT 230V OUTPUT FREQ 50HZ AUTO RESTART ON The Profile screen shows the current Automatic Restart status 10 2 Changing the automatic restart status 1 From the Main Screen press the Ent button to display the Main Menu 2 Onthe MAIN MENU select ADVANCED MENU and press Ent On the ADVANCED MENU select AUTOMATIC RESTART and press ENT ADVANCED MENU AUTOMATIC START TRANSFER LOAD SCREEN CONTRAST HAIN MENU
16. and terminals replace the outside cover on the rear of the UPS Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 8 2 Installation and Start Up Sequence 8 2 1 To start the UPS 1 Attach the load device if desired but do not turn it on until you have set the UPS output voltage as described below 2 Turnon the circuit breakers for the AC input the Bypass input and the Battery The UPS performs a self test this takes about a minute Afterwards you should see the following screen ACINPUT NORMAL BATTERY BYPASS UPS OFF NO OUTPUT LI 0 0 ES 0 e 7 ITED 8 2 2 Verify proper number of input and output phases Before turning the UPS on for the first time verify that the UPS s setting for number of input and output phases is correct for your requirements The phase setting can be seen on the second page of the Profile screen shown here with the phase setting highlighted UPS PROFILE POWER 10 CONTRAST 144 LINES CONFIG 3 5 VERSION 701 37 VERSION 705 6 See page 18 for instructions on how to display the Profile screen 8 2 3 Set the output voltage Before turning the UPS on you must set the UPS nominal output voltage if needed See Changing the nominal output voltage on page 52 8 2 4 Set the system clock Now set the system clock to the correct date and time See Setting the system clock on page 51 Power SA User Guide rel 3 0 49 8 2 5 Mod
17. arrangement you need switching to 3 3 operation section 19 4 on page 75 switching to 3 1 operation section 19 5 on page 81 or switching to 1 1 operation section 19 6 on page 89 Note Gamatronic highly recommends that you enlist the services of a trained electrician if you need to reconfigure the number of input and or output phases of your UPS 74 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 19 4 Switching to 3 3 operation This section explains how to reconfigure your Power SA UPS for use with 3x400 V input and 3x400 V output Note that at any point in the UPS console procedure you can exit by pressing the ESC key 1 Verify that you have obtained from Gamatronic three green connector plugs which will be needed later in the process 2 Turn the UPS off by pressing the On Off button twice The screen should read UPS OFF NO OUTPUT From the Main Menu select Advanced Options and press Ent Select Technician Menu and press Ent On the Technician Menu choose Number of Phases The UPS states the present line configuration THE PRESENT LINE CONFIGURATION Is 1 1 IF YOU WANT TO CHANGE IT PRESS ENTER ELSE PRESS ESC To continue the process of changing the current configuration press Ent 6 The UPS screen warns that attempting to change the input and output line configuration can damage the UPS if you are not a properly qualified technician If you are a properly qu
18. either express or implied Gamatronic s standard limited Warranty which accompanies its sales contract or order confirmation form is the only warranty offered by Gamatronic Electronic Industries Ltd in relation thereto Gamatronic Electronic Industries Ltd Gamatronic warrants the products it manufactures to be free from defect for a period of one calendar year from the date of invoice including the date of invoice Gamatronic s liability is limited to repairing or replacing any defective parts in the equipment under warranty Gamatronic reserves the right to determine whether the repair work shall be performed at Gamatronic s factory at the customer s premises or at an alternate site The customer must obtain authorization from Gamatronic before returning any parts or equipment to Gamatronic for repair or replacement Any items returned to Gamatronic must be sent freight prepaid Gamatronic s liability and warranty to the product are according and subject to the fulfilment and implementation by the customer of all the terms and instructions in connection with preventive maintenance and service and repair as further detailed in the user guide which 15 attached to the product and forms an integral part of it Gamatronic is not responsible for any damage to the product due to unauthorized repair work misuse or abuse of the product or force majeure If the product is delivered without batteries Gamatronic is not responsible for a
19. provides clean power to your loads e Has an overall efficiency of up to 96 and backup efficiency of 98 e 5 relatively light and small e Can operate in any of three line configurations 3 3 3 1 or 1 1 see chapter 8 beginning on page 35 and chapter 19 beginning on page 72 POWER SA requires little attention or intervention during normal operation however you should read and understand the procedures described in this manual to ensure trouble free operation 1 IEC 62040 3 is a standard for UPSs authored by the International Electrotechnical Commission IEC The IEC is the leading global organization that prepares and publishes international standards for all electrical electronic and related technologies These serve as a basis for national standardization and as references when drafting international tenders and contracts 4 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 2 1 Major Parts of the POWER SA The POWER SA includes the following sub assemblies Figure 1 The POWER SA CONTROL PANEL The POWER SA control panel allows the user to e manage and control the POWER SA e monitor the parameters of all sections of the POWER SA CHARGER The UPS includes a 3 phase charger with PFC PFC is a feature included that reduces the amount of generated reactive power Reactive power operates at right angles to true power and energizes the magnetic field Reactive power has no real val
20. reliable However no responsibility is assumed by Gamatronic for the use thereof nor for the rights of third parties which may be affected in any way by the use thereof This document may contain flaws omissions or typesetting errors no warranty is granted nor liability assumed in relation thereto unless specifically undertaken in Gamatronic Electronic Industries Ltd standard limited Warranty Information contained herein is periodically updated and changes will be incorporated into subsequent editions If you have encountered an error please notify Gamatronic Electronic Industries Ltd All specifications are subject to change without prior notice The product described in this document may cause interference with radio communications if not installed and used according to the user guide and or installation guide Be aware that the product is intended for use in a commercial or industrial setting Operation of the product in a residential area may cause harmful interference in which case the user will be required to correct the interference at his own expense ii Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD TABLE OF CONTENTS SAFETY PRECAUTIONS E duce SER dessus 1 EE IOS enean dva cud o Doe to Deo Lo Dc e nu coa svo to eae DM 1 a ttt ol M S EDU NEC M Ld 2 INTRODUCTION TO THE POWER SA eee L e Lee rc renes eee n e eaae uasa e re seas aaa re
21. this VOLTAGE IS ADJUSTED PLEASE WAIT TO ADJUST OUTPUT VOLTAGE THE UPS MUST BE OFF 9 The UPS fans may stop working for a moment They will start up again by themselves after the voltage adjustment is complete 10 Press Esc to return to the Main screen 9 4 Fine tune the output voltage You have the ability to fine tune the UPS output voltage You can adjust each phase of the output voltage up and down by one or more volts if needed To change the nominal output voltage 1 From the Main Screen press the Ent button to display the Main Menu On the Main Menu choose ADVANCED OPTIONS and press Ent In the ADVANCED MENU select TECHNICIAN MENU In the TECHNICIAN MENU select CHANGE VOLTAGE You are prompted to choose the type of voltage to change Select OUTPUT VOLTAGE 6 Youare prompted to choose a change to the nominal value or an adjustment fine tuning Choose DO ADJUSTMENT 7 You are prompted to choose the phase to be adjusted Choose a phase Gr de T9 J9 CHOOSE PHASE FOR ADJUSTMENT PHASE R PHASE S PHASE T Power SA User Guide rel 3 0 53 9 54 Use the UP and DOWN buttons to specify the voltage adjustment value The voltage can be adjusted up or down by up to 7 volts CHOOSE VALUE FOR ADJUSTMENT BY PRESSING ON THE UP DOWN The adjustment amount BUTTONS is displayed here SOV The phase voltage can be adjusted up or down y up to 7 volts THEN PRESS ENTER
22. 89 or according to local electrical codes 9 Run the batteries cable through the cable holder labeled Batteries in Figure 5 Connect the cable to the ac input terminals also shown in Figure 5 Use the appropriate grade of wire as specified in Table 5 on page 39 or according to local electrical codes 10 Tighten all cable holders so that the cables are fastened securely Power SA User Guide rel 3 0 41 11 Connect the PE Ground cable to the PE Ground pin shown in Figure 5 Bypass command connector Manual bypass switch Battery JJ connection Manual bypass switch Bypass command connector l f Battery connection Figure 6 Additional views of the UPS rear panel 42 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 8 1 3 Cable Connections for 3 1 Usage 1 Only an authorized electrician may wire the UPS power connections Do not attempt erg wire any of the power connections on your own To connect the required cables to the UPS 1 Ensure that the lines coming into the UPS are equipped with circuit breakers of the following capacity UPS output 50 A Class C Bypass output 50 A Class C AC input 3x16 A Class C The following table gives the required cable diameters that must be used when connecting the UPS The table states the cable diameters in mm Table 6 Wiring requirements for 3 1 configuration AC output Bypass input AC input Ph
23. E WITHOUT A NEUTRAL NULL CONDUCTOR FAILURE TO USE A NEUTRAL CONDUCTOR MAY CAUSE PERMANENT DAMAGE TO THE SYSTEM 2 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD RECYCLING INFORMATION CAUTION Do not discard waste electrical or electronic equipment WEEE or used batteries in the trash For proper disposal contact your local recycling or hazardous waste center Power SA User Guide rel 3 0 2 INTRODUCTION TO THE POWER SA Thank you for purchasing a POWER SA UPS system POWER SA is one of the most sophisticated UPSs on the market today In general an Uninterruptible Power Supply UPS provides backup power for use when the utility ac electric power mains fail or drop to an unacceptable voltage level POWER SA answers this critical need and more POWER SA is designed to protect your data and equipment and minimize downtime and other adverse effects normally incurred by power irregularities and failures POWER SA continually eliminates surges spikes and sags that are inherent in commercial utility power Over time these irregularities shorten the life of equipment and components The efficiency of POWER SA thus helps to extend the life of your equipment even during normal use when the input power is constant and continuous POWER SA IS UNIQUE BECAUSE IT e satrue on line battery design according to IEC 62040 31 e green power solution thanks to THD of 5 at the input and
24. ECTRONIC INDUSTRIES LTD 3 3 Bypass Mode In bypass mode the load receives power directly from the ac input via the static switch Whenever the inverters cannot provide power to the load for example due to an overload or a short circuit in the load the UPS supplies the load directly from the ac input bypassing the inverter As soon as the problem is corrected the load is transferred back to the inverter automatically AC INPUT BYPASS LED LIT LED LIT ACINPUT NORMAL BATTERY BYPASS UPS ON BYPASS MODE If Bypass Mode 1 76 was invoked 5 7 6 MANUAL manually the 29 BYPASS message Manual L3 76 ALARM amp er ets Bypass Mode display Power SA User Guide rel 3 0 4 USER INTERFACE This section describes the buttons and indicators used to operate the POWER SA 4 1 Control Panel The POWER SA Control Panel includes an LCD display control buttons and LED indicators The control panel has three principle functions e Shows the current operating mode e Lets you display other current readings e Lets you modify UPS settings and operating mode The control panel is for use by the end user and the service technician Indicator lights ACINPUT NORMAL BATTERY BYPASS ON OFF buttton LCD screen ENTER DS button p UP DOWN ESCAPE button scrolling button Also silences the audible alarm The POWER SA control panel 10 Power SA Use
25. GURES Figure T The POWER 4 oiii ie eiectus euet ie io ee die eoe cec esta du dd 5 Figure 2 Block diagram of the POWER 6 Figure 3 Connections at the rear of the 38 Figure 4 UPS rear panel with protective cover 40 Figure 5 UPS rear panel view with protective cover removed 41 Figure 6 Additional views of the UPS rear panel 42 Figure 7 The manual bypass switch on the rear panel eee esses 57 Figure 8 Timing variables when using a generator and an ATS 63 Figure 9 Example of an ATS control 64 Figure 10 Block diagram of major components and connections 66 Figure 11 Pin numbers D9 connectors 67 Figure 12 Reconfiguring from 1 1 or 3 1 to 3 3 Lesser eere eren enne enne nnns 77 Figure 13 Remove the four screws from the rear panel eese 78 Figure 14 Accessing the dip switches 1
26. ILE POWER 10 CONTRAST 144 LINES CONEIG 3 3 VERSION 701 37 VERSION 705 6 See section 4 2 2 1 on page 21 for instructions on how to display the Profile screen Power SA User Guide rel 3 0 73 19 3 A Summary Before Changing the Line Configuration Regardless of whether you are converting the UPS to 3 3 3 1 or 1 1 operation the procedure is basically the same for all three options as summarized in the following points If reconfiguring to 3 1 or 1 1 obtain from Gamatronic the appropriate terminal assembly for the desired new configuration If reconfiguring to 3 3 obtain from Gamatronic 3 green terminal connector plugs Turn the UPS off by pressing the On Off button twice The console should read UPS OFF NO OUTPUT Change the phase setting through the UPS console Deactivate the UPS completely by switching off the circuit breakers for Ac Input Bypass Input Battery Input and Ac Output Disconnect all ac cables and the battery cable from the UPS Change the phases dipswitch if appropriate Attach the input and output wiring to the UPS as required for the new phase arrangement This includes the replacement of the current terminal assembly or for 3 3 3 green connector plugs with a new terminal assembly or for 3 8 3 green connector plugs Also reattach the battery cable Turn the UPS on At the time of the switch be sure to follow the procedure below that is specific to the particular
27. LEVEL 110 4 Press the UP button repeatedly to make the screen greener Press the DOWN button repeatedly to make the screen darker blacker 9 3 Changing the nominal output voltage Do not change the output voltage unless you are sure that this is required by your load devices and you are sure that the new output voltage will not damage the load devices To change the nominal output voltage 1 If the POWER SA is not already in off mode press the ON OFF button twice to turn the UPS off 2 From the Main Screen press the Ent button to display the Main Menu 3 On the Main Menu choose ADVANCED OPTIONS and press Ent 4 Inthe ADVANCED MENU select TECHNICIAN MENU 5 Inthe TECHNICIAN MENU select CHANGE VOLTAGE TECHNICIAN MENU COLD START NUMBER OF PHASES CHANGE VOLTAGE RESET EVENT LOG BYP ACTIVATION 6 You are prompted to choose the type of voltage to change Select OUTPUT VOLTAGE 52 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 7 You are prompted to choose a change to the nominal value or an adjustment fine tuning Choose NOMINAL VALUE 8 Use the UP DOWN button to change the output voltage You can adjust it in a range from 220 to 240V Press Ent to apply the change TO CHANGE THE NOMINAL VOLTAGE THE UPS MUST The current nominal BE OFF voltage is displayed FOR CHANGING here PRESS UP DOWN 2 30V AND THEN ENTER After pressing Ent the screen looks like
28. ONS POWER SA Main Menu The Main Menu options are described elsewhere in this book The event log displays current alarm conditions and lists a Event EOY history of significant events See chapter 6 Set Clock 1 Sets the date and time used by the UPS See section 8 Select Language This feature not applicable for this model Battery Test Shows you when the next automatic battery test is scheduled to Advanced Options 26 occur lets you perform a manual battery test See page 31 A sub menu See page 52 for an image of the Advanced sub menu Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 5 DAILY OPERATION 5 1 Power SA Start up This section explains how to start up the Power SA after a shutdown You are beginning the process from the UPS OFF NO OUTPUT screen ACINPUT NORMAL BATTERY BYPASS UPS OFF NO OUTPUT 0 2 0 t3 096 1 Press the ON OFF button twice The BYPASS and ALARM LEDs light up for about 40 seconds 2 After a short time the screen reads UPS ON NORMAL MODE The ac INPUT and NORMAL LEDs are lit ACINPUT NORMAL BATTERY BYPASS UPS ON NORMAL MODE L1 50 L2 50 L3 51 e US 3 You can now turn on the computers or other equipment connected to the UPS POWER SA start up is now complete Power SA User Guide rel 3 0 27 5 2 POWER SA Shutdown This section describes the shutdown procedures for the UPS if you want to shu
29. R SA The connection allows the user to read data from the UPS and to control it as well There are two types of UPS connections e Directly to a host computer with dedicated software e Remote control through a SNMP WEB management programs for communication with a computer network optional In order to use the RS232 connection to a computer monitoring software must be installed on the user s PC The monitoring software can be ordered from Gamatronic The PIN assignment for this 9 pin connector is shown in the diagram below See also the column labeled Pins for dry contacts in Table 8 The communication is half duplex 9600 baud rate no parity 1 stop bit Rx Tx and COM lines no flow control neither h w nor s w COM TX RS232 Connector Power SA User Guide rel 3 0 69 17 SNMP AGENT OPTIONAL The SNMP agent enables monitoring management control and orderly shutdown of the UPS via the Internet protocol SNMP There are two types of SNMP agents e External Adaptor e Internal Card The SNMP agent communicates with the RS232 interface of the UPS which e Supports standard UPS RFC1628 e Supports the SNMP commands Trap Set and Get e Transfers UPS indicators such as voltage frequency and current via the Internet browser or any management system NMS Use of an SNMP agent disables the RS232 interface of the UPS Options INTERNAL CARDS EXTERNAL ADAPTOR POWER PSM AC lets you monitor an
30. S the connections before continuing pU CO NS To conceal and protect the cables and terminals replace the outside cover on the rear of the UPS 38 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 8 1 2 Cable connections for 3 3 usage WITH manual bypass Note the Manual Bypass Switch is OPTIONAL EQUIPMENT not standard If the customer desires a Manual Bypass Switch it must be specifically ordered as a separate item This section describes cable connections for using the Power SA in 3 3 configuration using the rear panel adapter that HAS A MANUAL BYPASS SWITCH The rear panel adaptor provides single feed input meaning that the bypass input is taken from the rectifier input lines For 3 3 connections for the adapter without a manual bypass switch see section 8 1 1 on page 36 To install the UPS and prepare it for initial start up 1 Verify that the external circuit breaker in the mains electrical cabinet for UPS input is OFF No voltage should be present in the cables 2 Verify that the battery cabinet circuit breaker is OFF 3 Ensure that the lines coming into the UPS are equipped with circuit breakers of the following capacity UPS output 3x16A Class C AC bypass input 3x16 A Class 4 The following table gives the required cable diameters that must be used when connecting the UPS The table states the cable diameters in mm Table 5 Wiring requirements for 3 3 conf
31. T LINE CONFIGURATION CAN BE DONE ONLY IN OFF STATE TO CONTINUE PRESS ENTER ELSE ESC Power SA User Guide rel 3 0 81 ra The UPS prompts you to choose the new line configuration Make your selection and press Ent IF THE UPS IS OFF YOU CAN CHOOSE ONE OF THE FOLLOWING OPTIONS INPUT 3 OUTPUT 3 INPUT 3 OUTPUT 1 INPUT 1 OUTPUT 1 8 The UPS screen advises that to work with a line configuration of 3 1 the UPS Input Output and Bypass connections must be properly fitted This will be done below after the UPS is disconnected from the input mains Press Ent to continue IN ORDER TO WORK WITH 3 1 MODE THE INPUT OUTPUT AND INPUT BYPASS CONNECTIONS MUST BE FITTED TO THE PROPER VOLTAGES PRESS ENTER 9 The UPS screen instructs you to refer to this user manual for specific instructions Press Ent to continue REFER TO THE USER MANUAL FOR SPECIFIC INSTRUCTIONS ON WIRES AND DIP SWITCH CONFIGURATIONS PRESS ENTER 10 The UPS screen prompts you once again to press Ent if you want to continue Press Ent to continue IF YOU ARE SURE YOU WANT TO DO THE CHANGES PRESS ENTER ELSE PRESS ESG 82 Power SA User Guide rel 3 0 11 12 13 14 19 16 17 18 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD The UPS screen informs you that the line configuration changes will be in effect only after all input and output voltages to the UPS have been
32. This user guide is for product numbers 101 011 10155041 and 10155061 CA GAMATRONIC Our Power Your Confidence POWER SA 10 KVA DOUBLE CONVERSION UPS WITH TRUE ON LINE BATTERY User configurable input and output voltage options INPUT OUTPUT 3 x 400V 3 x 400V 3 x 400V 1x230V 1x230V 1x230V User Guide Release 3 0 August 2015 GAMATRONIC ELECTRONIC INDUSTRIES LTD 17 Hartom St P O B 45029 Jerusalem 9777517 Israel Tel 972 2 588 8222 Fax 972 2 582 8875 Email info gamatronic co il Website www gamatronic com 2MUM PPSA 2 GAMATRONIC ELECTRONIC INDUSTRIES LTD Har Hotzvim Industrial Park 17 Hartom St P O B 45029 Jerusalem 9777517 Israel Tel 972 2 588 8222 Fax 972 2 582 8875 Email info gamatronic co il Website www gamatronic com The equipment described in this document is not intended to be used in connection with any application requiring fail safe performance unless the application design includes appropriate redundancy This exclusion includes but is not limited to the direct operation of any life support system or any other system whose failure could lead to serious injury death environmental damage or mass destruction Copyright 2015 by Gamatronic Electronic Industries Ltd All rights reserved worldwide Any representations in this document concerning the performance of Gamatronic s product s are for informational purposes only and are not warranties of future performance
33. a power outage this message can be ignored This message could also be the result of an overload Reduce the load on the UPS this may resolve the problem If not contact Technical Support Meaning The battery will soon be fully discharged Additional indications The alarm LED lights up and the audible alarm sounds The symbol appears on the Main Screen Action Shut down your computer or other equipment connected to the UPS Meaning The most recent battery test has failed Additional indications The alarm LED lights up and the audible alarm sounds The symbol appears on the Main Screen Action It is possible that the most recent battery test occurred after a power outage and before the battery had fully recharged Wait until two hours have elapsed from the most recent battery test and perform a manual battery test See Manual battery test on page 31 Meaning The voltage of at least one of the Bypass phases is out of range and a transfer to Bypass mode cannot be made at this time Additional indications The alarm LED lights up and the audible alarm sounds The symbol X appears on the Bypass screen Action This alarm can be the result of a power outage in which case it can be ignored Otherwise check the circuit breaker for the line supplying the Bypass voltage The circuit breaker may be off Power SA User Guide rel 3 0 31 Meaning The batteries have been exhausted and the UPS has turned itself off Addit
34. a screens that can be shown on the POWER SA display screen 4 2 1 The Main Screen The POWER SA Main Screen is the default display on the POWER SA screen From any other screen if the keyboard is not used for 45 seconds the POWER SA returns to the Main Screen The Main Screen shows the UPS s current operating mode and other critical data Other screens describing current operating conditions can be seen by navigating upwards or downward with the UP DOWN key The first line of the Main Screen shows whether the UPS is currently on or off The second line tells you the most important information about the UPS s current status Most of the time it will read NORMAL MODE The UPS can also automatically transfer to e BATTERY MODE e BYPASS MODE e UPS OFF The L1 L2 and L3 numbers in the Main Screen show the current load rate as a percent of maximal ac load at each phase UPS ON UPS OFF NORMAL MODE BATTERY MODE UPS ON Low BATTERY m a L1 76 Additional END OF DISCHARGE Kiss Meo NO OUTPUT 13 77 ALARM 12 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 4 2 1 1 NORMAL MODE In Normal mode the Main Screen displays the message UPS ON NORMAL MODE The ac INPUT and NORMAL LEDs are lit The following picture shows the Main Screen as you will see it most of the time in Normal Mode AC INPUT and NORMAL LEDs lit AC INPUT NORMAL BATTERY
35. alified technician press Ent to continue THIS ACTION CAN CAUSE DAMAGE IT MUST BE DONE BY A QUALIFIED TECHNICIAN TO CONFIRM AND CONTINUE PRESS ENTER ELSE ESC T The UPS screen warns that the unit must be off in order to change the line configuration If you turned off the UPS as instructed in step 1 above press Ent to continue CHANGING THE DEFINITION OF THE PRESENT LINE CONFIGURATION CAN BE DONE ONLY IN OFF STATE TO CONTINUE PRESS ENTER ELSE ESC 8 The UPS prompts you to choose the new line configuration Make your selection and press Ent Power SA User Guide rel 3 0 75 THE UPS IS OFF YOU CAN CHOOSE ONE OF THE FOLLOWING OPTIONS INPUT 3 OUTPUT 3 INPUT 3 OUTPUT 1 INPUT 1 OUTPUT 1 9 The UPS screen advises that to work with a line configuration of 3 3 the UPS Input Output and Bypass connections must be properly fitted This will be done below after the UPS is disconnected from the input mains Press Ent to continue IN ORDER TO WORK WITH 3 3 MODE THE INPUT OUTPUT AND INPUT BYPASS CONNECTIONS MUST BE FITTED TO 3 PHASES VOLTAGE PRESS ENTER 10 The UPS screen instructs you to refer to this user manual for specific instructions Press Ent to continue REFER TO THE USER MANUAL FOR SPECTEIC INSTRUCTIONS ON WIRES AND DIP SWITCH CONFIGURATIONS PRESS ENTER 11 UPS screen prompts you once again to press Ent if you want to continue Press Ent to continue
36. ance and battery replacement shall be performed only by authorized service personnel e Pay attention to all DANGER CAUTION and WARNING notices affixed to the inside and outside of the UPS e Keep the surroundings clean uncluttered and free from excess moisture e Keep the operating environment within the parameters stated in this document e Allow only qualified technicians to service the UPS There are no user serviceable components Do not try to repair it yourself e Use the UPS only for its intended purpose e The batteries should preferably be installed next to the UPS or as close to it as is practically possible WARNING ENERGIZED CIRCUITS DURING SERVICING The electronic boards and the control panel circuits remain energized during servicing procedures Take appropriate precautions CAUTION WARNING RISK OF LETHAL ELECTRIC SHOCK The battery drawer contains a series of 12 Volt batteries that provide high voltage and energy in the UPS body even when the UPS is not connected to the ac input Appropriate precautions should be taken during installation inspection and servicing Power SA User Guide rel 3 0 1 CAUTION WARNING RISK OF LETHAL ELECTRIC SHOCK The UPS receives power from more than one source Disconnection of all of the ac sources and the dc source is required to de energize this unit before servicing 1 2 Don ts e Do not open the cover of the UPS or the battery cabinets under any c
37. bbreviated 1 1 The configuration used by the UPS depends on the ac input supplied and on the UPS settings It follows that when displaying input or output voltages or currents the UPS s LCD display screen will show data for one or three phases depending on the UPS s current configuration The figures below show the UPS Main screen displaying output voltages in 3 phase and in 1 phase operation respectively UPS ON UPS ON NORMAL MODE NORMAL MODE L1 50 L1 45 L2 50 L3 51 UPS Main screen with 3 phase output UPS Main screen with 1 phase output In this user manual when illustrating a given UPS function that includes a voltage display both possible displays are usually not shown the single phase display and the 3 phase display For simplicity s sake usually only one of the two possible displays is shown The reader is asked to remember that the number of phases displayed on the screen of his UPS depends on the UPS settings and the actual ac input This manual contains diagrams which include images of the LCD display screen of the UPS Unless otherwise indicated the readings shown in the screen images are representational only and are not intended to match the readings on a specific system in a particular environment vi Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD This page left blank deliberately Power SA User Guide rel 3 0 vii ATTACHING THE POWER SA TO ITS BASE
38. ble connector plugs from the rear of the UPS See Figure 18 83 84 INTERNAL PROTECTIVE COVER TERMINAL PANEL EXIERNAL PROTECTIVE COVER GREEN CABLE CONNECTOR PLUGS L L L L L L L a LJ a a E L i 8 k L LI Figure 17 Components of the terminal assembly Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD GREEN CABLE CONNECTORS CABLE COVER D 3 N Figure 18 Reconfiguring from 3 3 to 3 1 19 Onthe rear panel of the UPS remove the screws that secure the internal UPS body to its external shell See Figure 19 Note the number and position of the screws may differ from that show in Figure 19 Power SA User Guide rel 3 0 85 SCREW 2911 979 NNI oe POP T et as M BATTERY Figure 19 Remove the four screws from the rear panel 20 Grasp the top of the rear panel and pull the UPS body firmly so that it is most of the way out of the external shell see Figure 20 and Figure 21 below Figure 20 Accessing the dip switches 1 86 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD Figure 21 Accessing the dip switches 2 21 On the top front of the UPS body there is a set of three small dipswitches as shown in the diagram When looking at the dipswitches from the front of the UPS the right
39. ble for ensuring that the preventive maintenance inspections take place This is done by contacting Gamatronic s service department and arranging a mutually convenient time for a technician to perform the inspection It is important that the UPS owner continue to arrange regular preventive maintenance inspections even after the expiration of the initial warrantee period Gamatronic bears no liability for damage caused to the UPS due to improper maintenance by third parties in particular after the expiration of the warrantee or service agreement It is the responsibility of the UPS owner to uphold his responsibilities according to the warrantee or service agreement This includes ensuring that the UPS s environment meets requirements 21 SERVICE AND REPAIRS Gamatronic maintains a team of service technicians repair laboratories and an ample inventory of spare parts dedicated to the service and repair of our products When service is required it will be performed either at the customer s site or in one of our laboratories according to the judgment of our technician and the specifics of the service agreement between the customer and Gamatronic In regards to service oral agreements have no standing Service shall be provided gratis during the warrantee period on the condition that the UPS has been properly maintained and a written record has been kept of any maintenance performed on the system The initial warrantee period can be extended b
40. d control your POWER SA UPS 70 Power SA User Guide rel 3 0 18 GAMATRONIC ELECTRONIC INDUSTRIES LTD WIRELESS CONTROL OPTIONAL The POWER SA system includes an option for wireless control and management using the Gamatronic WING The WING enables real time detection of power system faults and immediately notifies selected recipients control center technician etc detailing the faults The WING includes the following elements WING board SIM board antenna D9 D9 cable for RS232 connection between the POWER SA and the WING ac dc power adapter For more information request a copy of the Wing user guide Power SA User Guide rel 3 0 71 19 CHANGING THE UPS LINE CONFIGURATION Your POWER SA UPS is capable of operating with one or three phase input and can supply one or three phase output depending on the AC input and on the UPS settings The possible phase settings are shown in the following table Table 9 UPS line configuration options SHORTHAND INPUT OUTPUT DESIGNATION 3x400V 3x400V 3 3 3x400V gt 1x230V 3 1 1x230V 1x230V 1 1 Your POWER SA UPS was probably already set at the factory or by your dealer to operate with the number of input and output phases appropriate for your requirements If your requirements change the POWER SA UPS can be adjusted to handle any of the combination of input and output voltages listed above Gamatronic highly recommends that you en
41. disconnected and the wire connections and the dip switches have been adjusted as required CHANGES WILL BE IMPLEMENTED ONLY AFTER COMPLETE DISCONNECTION OF ALL VOLTAGES AND CHANGING WIRE CONNECTIONS AND DIP SWITCH Disconnect the UPS from all voltages by turning OFF the circuit breakers for AC Input Bypass Input Output and Battery Disconnect the battery cable from the UPS Use a screwdriver to remove the external protective cable cover on the rear of the UPS Refer to Figure 17 or Figure 18 below For clarity s sake the electrical cables are not shown in Figure 17 or Figure 18 Disconnect the battery cable from the rear of the UPS Before continuing verify with a multimeter that there is no voltage on any of the cables attached to the terminals If you are reconfiguring from 1 1 to 3 1 e Disconnect the cables from the terminal assembly e Remove the screws from the right side of the terminal assembly e Remove the terminal assembly from the UPS refer to Figure 17 The terminal assembly consists of 3 parts the terminal panel the black metal internal protective cover behind it and green connector plugs The terminal assembly should be removed as a single unit there is no need to disassemble it into its separate components Continue with step 0 on page 88 If you are reconfiguring from 3 3 to 3 1 e Remove the protective cover that protects the green terminal plugs see Figure 18 on page 85 eUnplug the green ca
42. e ONE PHASE FAULT Additional indications The alarm LED lights up and the audible alarm sounds Action This is likely to be due to a problem with the input ac supply Meaning There is an overload condition Additional indications The alarm LED lights up and the audible alarm sounds If the output current is between 104 117 for 10 minutes or between 117 13196 for one minute or above 13196 for 20 msec the UPS shuts down The OVERLOAD symbol EORR appears on the Main Screen Action Reduce the load to the UPS quickly or the UPS will automatically move to Bypass mode 32 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD Table 2 Log messages LOG ENTRY EXPLANATION AC LINE FAULT No input voltage to charger AC LINE OK Input voltage to charger has been restored BATT TEST FAIL The last battery test failed BATT TEST OK The last battery test was successful following a failed battery test END OF BACKUP Battery has been completely discharged RECHARGING Mains power has returned and battery is recharging INVERTER OFF The inverter has been turned off INVERTER ON The inverter has been turned on OVERLOAD An overload condition exists LOAD IN RANGE The load has returned to normal range LOAD ON BYPASS The load is bypassing the inverter LOAD ON INVERTER The load has returned to the inverter UPS OFF The UPS was turned off UPS ON The UPS was turned on Power SA User Gu
43. e UPS off by pressing the On Off button twice The screen should read UPS OFF NO OUTPUT 2 From the Main Menu select Advanced Options and press Ent 3 Select Technician Menu and press Ent 4 Onthe Technician Menu choose Number of Phases The UPS states the present line configuration THE PRESENT LINE CONFIGURATION IS 3 3 IF YOU WANT TO CHANGE IT PRESS ENTER ELSE PRESS ESC To continue the process of changing the current configuration press Ent 5 he UPS screen warns that attempting to change the input and output line configuration can damage the UPS if you are not a properly qualified technician If you are a properly qualified technician press Ent to continue THIS ACTION CAN CAUSE DAMAGE IT MUST BE DONE BY A QUALIFIED TECHNICIAN TO CONFIRM AND CONTINUE PRESS ENTER ELSE ESC 6 The UPS screen warns that the unit must be off in order to change the line configuration If you turned off the UPS as instructed in step 1 above press Ent to continue CHANGING THE DEFINITION OF THE PRESENT LINE CONFIGURATION CAN BE DONE ONLY IN OFF STATE TO CONTINUE PRESS ENTER ELSE ESG The UPS prompts you to choose the new line configuration Make your selection and press Ent Power SA User Guide rel 3 0 89 IF THE UPS IS OFF YOU CAN CHOOSE ONE OF THE FOLLOWING OPTIONS INPUT 3 OUTPUT 3 INPUT 3 OUTPUT 2 INPUT 1 OUTPUT 1 8 The UPS screen advises that to work with a line configurat
44. e dipswitches 2 94 Figure 28 Location of the dipswitches ll 94 Figure 29 Flowchart of system functions e 98 LIST OF TABLES Table 1 Outstanding alarm MCSSaGeS 31 Table 2 Eod messages Eti eco coo veu 33 Table 3 Line configuration options 35 Table 4 Wiring requirements for 3 3 configuration eee eere eene 36 Table 5 Wiring requirements for 3 3 39 Table 6 Wiring requirements for 3 1 43 Table 7 Wiring requirements for 1 1 46 Table 8 Assignments for D9 connectors on rear of controller 67 Table 9 UPS line configuration options e c 72 Power SA User Guide rel 3 0 CONVENTIONS USED IN THIS BOOK The POWER SA UPS is capable of operating with any of three possible line configurations e 3 phase input 3 phase output abbreviated 3 3 e 3 phase input 1 phase output abbreviated 3 1 e 1 phase input 1 phase output a
45. e ordered and obtained beforehand and secure it by fastening the screws on its right side 24 The UPS must now be wired Follow the instructions in the section Cable Connections for 1 1 Usage then continue with the next step below 25 Turn the circuit breakers ON for AC Input Bypass Input Output You can now start up the UPS If the UPS does not start up it may be that the UPS s line configuration setting does not match the dipswitch line configuration setting In this case go to the Profile screen and check that the line configuration setting matches the setting for the line configuration dipswitch Power SA User Guide rel 3 0 95 20 PREVENTIVE MAINTENANCE Every Gamatronic UPS contains technologically advanced electronic systems These electronic systems are sensitive to environmental conditions It is important that the operating and storage environments of the UPS be clean and dust free free of dampness and excess humidity The system s batteries provide back up power to the UPS when needed An environmental temperature of 20 68 F is ideal for the batteries Significantly higher temperatures shorten the batteries lifespan The UPS and its batteries both require periodic preventive maintenance inspections At the least these inspections should include a visual inspection of the UPS and its batteries and the tightening of any screws and bolts that have over time become loosened The owner of the UPS is responsi
46. ective cable cover on the rear of the UPS Refer to Figure 23 or Figure 24 below For clarity s sake the electrical cables are not shown in Figure 23 or Figure 24 Disconnect the battery cable from the rear of the UPS Before continuing verify with a multimeter that there is no voltage on any of the cables attached to the terminals If you are reconfiguring from 3 1 to 1 1 Disconnect the cables from the terminal assembly the screws from the right side of the terminal assembly the terminal assembly from the UPS refer to Figure 23 below The terminal assembly consists of 3 parts the terminal panel the black metal internal protective cover behind it and green connector plugs The terminal assembly should be removed as a single unit there is no need to disassemble it into its separate components Continue with step 23 on page 95 If you are reconfiguring from 3 3 to 1 1 e Remove the protective cover that protects the green terminal plugs see Figure 24 below eUnplug the green cable connector plugs from the rear of the UPS See Figure 24 Power SA User Guide rel 3 0 91 INTERNAL PROTECTIVE LOVER TERMINAL PANEL EXIERNAL PROT ECT IVE COVER GREEN CABLE CONNECTOR PLUGS A a i L L 4 L a d L L L L L a k a L i a k L ii a E i L L GREEN CABLE CONNECTORS Figure 24 Reconfiguring from 3 3 to 3 1
47. example in the following illustration there are three active alarms END OF BACKUP 1 the battery has been exhausted AC INPUT FAIL and BYPASS NOT READY ACTIVE ALARMS END OF BACKUP AC INPUT FAIL Active alarms BYPASS NOT READY TO VIEW LOG PRESS ENTER A list of all possible alarms can be seen in Table 1 on page 31 If there are no active alarms the display indicates this NO ACTIVE ALARM TO VIEW LOG PRESS ENTER Power SA User Guide rel 3 0 29 6 2 2 Event log entries To see the latest entry in the Event Log from the Active Alarm display press Ent To scroll backwards to previous entries press the Down button To scroll forwards again to later entries press the Up button To exit the Event Log entirely and return to the Main Screen press ESC A list of all possible log entries can be seen in Table 2 on page 33 The event log has the capacity to record 200 events When this number is exceeded the logwriter wraps around to the beginning of the file so that the oldest events in the log are overwritten by the newest events The illustration shows a typical log entry EVEHT LOG 23 INVERTER OFF 16 17 54 05 07 2001 SCROLL UP DOWN e first line gives the number of the log entry This is the 23 log entry e The second line gives the log text in this case INVERTER OFF The log entry shows that the inverter was turned off e The third line show the time of the log entry
48. gure 11 Pin numbers in D9 connectors Table 8 Assignments for D9 connectors on rear of controller ALARM CONNECTOR RS232 PINS FOR CONNECTOR PINS FOR DRY CONTACTS REMOTE PANEL Input dry contact 5 AUX5 Not used Reserved TAn Receive data Output dry contact 2 Normally Open TXD Default value when closed is Hanni EA line failure can be reassigned COMMON Ground Not used Output dry contact 1 Normally Open GND Default value when closed is low battery can be reassigned ECEDERCENEES Power SA User Guide rel 3 0 67 The following figure is a schematic of the Dry Alarm Contacts The triangles represent pins the numerals in the triangles represent pin numbers Low battery alarm contacts closed when battery low V Line failure alarm contact closed when line fails V Reserved for Gamatronic Vi Low Line battery failure 4 z Common Isolated from chassis General fault alarm contact General fault closes when fault occurs Opto couplers 30v 100mA max Reserved for Gamatronic Reserved for Gamatronic Reserved for Gamatronic pt 68 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 16 RS232 INTERFACE The POWER SA may be connected to a computer or a modem using a shielded cable with an RS232 type 9 pin female connector The cable should not exceed15 meters The RS232 plug is located on the rear panel of the POWE
49. h the dipswitch line configuration setting In this case go to the Profile screen and check that the line configuration setting matches the setting for the line configuration dipswitch Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 19 5 Switching to 3 1 operation 3x400 V input 1x230 V output Note that at any point in the procedure you can exit by pressing the ESC key 1 Turn the UPS off by pressing the On Off button twice The screen should read UPS OFF NO OUTPUT From the Main Menu select Advanced Options and press Ent o Select Technician Menu and press Ent 4 On the Technician Menu choose Number of Phases The UPS states the present line configuration THE PRESENT LINE CONFIGURATION TS 1 1 IF YOU WANT TO CHANGE IT PRESS ENTER ELSE PRESS ESC To continue the process of changing the current configuration press Ent 5 The UPS screen warns that attempting to change the input and output line configuration can damage the UPS if you are not a properly qualified technician If you are a properly qualified technician press Ent to continue THIS ACTION CAN CAUSE DAMAGE IT MUST BE DONE BY A QUALIFIED TECHNICIAN TO CONFIRM AND CONTINUE PRESS ENTER ELSE ESG 6 The UPS screen warns that the unit must be off in order to change the line configuration If you turned off the UPS as instructed in step 1 above press Ent to continue CHANGING THE DEFINITION OF THE PRESEN
50. ide rel 3 0 33 7 BATTERY TESTS 7 1 Automatic battery test The POWER SA is programmed to perform a battery test automatically every two weeks 7 2 Manual battery test To perform a battery test outside of this schedule a manual battery test 1 From the Main Screen press the Ent button to display the Main Menu On the Main Menu select Battery Test and press Ent The resulting screen tells you the time until the next scheduled automatic battery test To perform a manual test press Ent again AUTOMAT IC TEST WILL BE IH 13 DAYS 22 HOURS TO ACTIVATE MANUAL TEST PRESS ENTER The battery test lasts for 60 seconds The screen shows a countdown of the time remaining in the test To end the test immediately press Ent again BATTERY TOTAL 42754 POSITIVE 212 21357 TIME LEFT 20 TO STOP MANUAL TEST PRESS ENTER If the POWER SA batteries fail a battery test the battery failure icon K appears on the POWER SA screen and remains there until a later battery test is passed 34 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 8 FIRST TIME SETUP Your POWER SA UPS is capable of operating with any of three possible line configurations The configuration used by the UPS depends on the AC input supplied and on the UPS settings The permitted line configurations are shown in the following table Table 3 Line configuration options SHORTHAND
51. ify the screen contrast optional You can modify the screen contrast if necessary See Setting screen contrast on page 52 8 2 6 Set Automatic Restart mode optional You can enable automatic restart mode at this time if desired See Automatic Restart on page 55 8 2 7 Operation To turn the UPS on press the ON OFF button twice and wait a few seconds The following screen is displayed AC INPUT and NORMAL LEDs lit ACINPUT NORMAL BATTERY BYPASS Viv Sly OO PTA Y UPS ON NORMAL MODE L1 76 L2 82 ine E e POWER SA The AC Input and Normal LEDs should be lit Turn on the AC output circuit breaker You can now operate the equipment attached to the POWER SA 50 Power SA User Guide rel 3 0 9 GAMATRONIC ELECTRONIC INDUSTRIES LTD SETTING SYSTEM PARAMETERS There are several system parameters that can be modified as needed In general you only need set these parameters once during the first time setup of the POWER SA 9 1 Setting the system clock The system clock is used in recording entries to the POWER event log The clock should be set to the correct time so that the log entries will reflect the true time of events To set the system clock ls 2 From the Main Screen press the Ent button to display the Main Menu On the Main Menu select SET CLOCK and press Ent This displays the CLOCK screen which shows the current time a
52. iguration AC output Bypass input AC input N L1 L2 L3 Gnd N L1 L2 L3 Gnd N L1 L2 L3 Battery input 4 mm 2 5 mm 2 5 mm 4 mm Use the 1 5 meter long battery cable supplied by Gamatronic the protective cover from the UPS rear panel Connect the UPS wiring according to the labeling on the unit shown in Figure 5 on page 41 Power SA User Guide rel 3 0 39 MANUAL ue BYPASS gt SWITCH REAR COVER PROTECTS THE ELECTRICAL TERMINALS POWER CABLE INLETS d JO 40 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD TERMINAL CONNECTIONS AC ouTPUT I L MANUAL BYPASS SWITCH RECTIFIER INPUT BATTERY PE GROUND PIN POWER CABLE CONDUITS IL IL JL JL RECTIFIER INPUT AC OUTPUT BATTERIES Figure 5 UPS rear panel view with protective cover removed 7 Run the ac output cable through the cable holder labeled ac output in Figure 5 Connect the cable to the ac output terminals also detailed in Figure 5 Use the appropriate grade of wire as specified in Table 5 on page 39 or according to local electrical codes 8 Run the ac input cable through cable holder labeled input in Figure 5 Connect the cable to the ac input terminals also shown in Figure 5 Use the appropriate grade of wire as specified in Table 5 on page 3
53. ile screen shows e he software version on card PC705 e he software version on card PC701 e Current contrast setting of the display screen see page 49 for information on the contrast setting To see the third UPS Profile screen press again The third UPS Profile screen shows e The status of the Bypass option ON or OFF e The phase shift between the output phases e Whether the current in the input phases is symmetric equal or unsymmetric unequal Power SA User Guide rel 3 0 21 UPS PROFILE UPS PROFILE DATE 05 12 2006 POWER LOKVA TIME 20 03 08 CONTRAST 144 OUTPUT VOLT 230V LINES CONFIG 2 2 OUTPUT FREQ 50HZ VERSION 701 37 AUTO RESTART ON VERSION 705 6 UPS Profile screen 1 UPS Profile screen 2 UPS PROFILE BYP OPTION ON PHASE SHIFT 180 INPUT NOT SYM UPS Profile screen 3 4 2 2 2 AC OUTPUT SCREEN To see the current status of the UPS s ac output from the Main Screen press V twice The checkmark indicates that the ac voltage of each output phase is within acceptable range otherwise an X is displayed instead of the checkmark The voltage and current for the three output phases is also displayed AC OUTPUT Voltage pe in range dn of range Volt d m E of each output phase 22 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 4 2 2 3 AC INPUT SCREEN To see the current status of the ac input to the UPS from the Main Screen press three time
54. ion of 3 1 the UPS Input Output and Bypass connections must be properly fitted This will be done below after the UPS is disconnected from the input mains Press Ent to continue IN ORDER TO WORK WITH 1 1 MODE THE INPUT OUTPUT AND INPUT BYPASS CONNECTIONS MUST BE FETTED TO l PHASE VOLTAGE PRESS ENTER 9 The UPS screen instructs you to refer to this user manual for specific instructions Press Ent to continue REFER TO THE USER MANUAL SPECIFIC INSTRUCTIONS ON WIRES AND DIP SWITCH CONFIGURATIONS PRESS ENTER 10 The UPS screen prompts you once again to press Ent if you want to continue Press Ent to continue IF YOU ARE SURE YOU WANT TO DO THE CHANGES PRESS ENTER ELSE PRESS ESC 11 The UPS screen informs you that the line configuration changes will be in effect only after all input and output voltages to the UPS have been disconnected and the wire connections and the dip switch has been adjusted as required 90 Power SA User Guide rel 3 0 12 13 14 19 16 17 17 1 17 2 17 3 17 4 18 GAMATRONIC ELECTRONIC INDUSTRIES LTD CHANGES WILL BE IMPLEMENTED ONLY AFTER COMPLETE DISCONNECTION OF ALL VOLTAGES AND CHANGING WIRE CONNECTIONS AND DIP SWITCH Disconnect the UPS from all voltages by turning OFF the circuit breakers for AC Input Bypass Input Output and Battery Disconnect the battery cable from the UPS Use a screwdriver to remove the external prot
55. ional indications The UPS has turned itself OFF END OF BACKUP 8kVA 208V model The symbol appears on the Screen 10kVA 400V model The UPS screen is blank Action Wait for ac power to return Then if the UPS is in Auto Restart mode it will start up automatically otherwise start the UPS manually by pressing the OFF ON button twice Meaning The Inverter is not synchronized with the Bypass voltages Additional indications The alarm LED lights up and the audible alarm sounds INV SYNC FAULT The symbol X appears on the Inverter screen Action Check the voltage readings on the Inverter screen If the readings are in range and the alarm persists contact Customer Support Meaning The voltage of one or more of the Inverter output phases is out of range INV VOLT FAULT Additional indications The alarm LED lights up and the audible alarm sounds The symbol X appears on the Inverter screen Action Contact Customer Support Meaning The output voltage is the Bypass voltage Additional indications Action If the UPS was set to Bypass mode manually Manual Bypass appears LOAD ON BYPASS on the Main Screen you can manually return it to inverter mode to end the alarm condition If the UPS moved to Bypass mode automatically an overload condition may have been the cause OVERLOAD appears on the Main Screen In this case try reducing the load on the UPS Meaning One or more of the ac phases into the Charger is out of rang
56. ircumstances All UPS panels and doors should be closed e Do not insert any objects through the ventilation holes e Do not put objects on the UPS e Do not move the UPS while it is operating e Do not use the UPS outdoors e Do not turn the UPS upside down during transportation e Do not connect or disconnect the cable to the battery cabinet before the battery circuit breaker is turned OFF e Donotturn ON the battery circuit breaker when the battery cabinet is disconnected from the UPS e Do not install the UPS next to gas or electrical heaters A restricted location is recommended in order to prevent access by unauthorized personnel CAUTION GROUND CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY Connect the UPS to ground before connecting it to the ac supply CAUTION WARNING RISK OF ELECTRIC SHOCK DO NOT REMOVE COVER Do not remove the UPS cover There are no user serviceable parts inside Refer servicing to qualified service personnel CAUTION WARNING RISK OF ELECTRIC SHOCK Attention service personnel Capacitors store hazardous energy Do not remove cover until 5 minutes after disconnecting all ac and dc sources of supply Do not remove the UPS cover There are no user serviceable parts inside Refer servicing to qualified service personnel WARNING RISK OF SEVERE DAMAGE TO THE UPS THIS SYSTEM USES THE NEUTRAL LINE FOR OPERATION THEREFORE IT IS STRICTLY FORBIDDEN TO CONNECT THIS SYSTEM TO THE AC POWER SOURC
57. list the services of a trained electrician if you need to adjust the number of input and or output phases of your UPS Changing the UPS settings for input and output phases is serious business that can result in damage to the UPS and to your load devices if you make a mistake 19 1 Note regarding battery connection on UPS The battery connection on your UPS may differ in appearance from that shown in the following procedures Regardless the procedures are still applicable Your UPS will have one of two possible types of battery connections e Aplastic and metal terminal block on the terminal panel of the terminal assembly see Figure 12 on page 77 In this case there will be four terminal blocks on the terminal panel the bottom terminal block is for the battery e Athree segment Anderson type connector on the UPS rear grille In this case there will be only three terminal blocks on the terminal assembly terminal panel There will be no terminal block for the battery instead the battery cable connects to the Anderson connectors on the UPS rear grille through an opening in the terminal assembly panel 72 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 19 2 Determining present phase setting The first step in changing the line configuration of the UPS is to verify its present line configuration The phase setting can be seen on the second page of the Profile screen shown here with the phase setting UPS PROF
58. m of the control panel controls the actions of the ATS e The ATS can be set to use the normal source 240 300 Ter os e The ATS can be set to use the reserve source f anaratar 120 480 2 5119 1 J I e duos ef 00 e The ATS can be set to automatic mode which will use the normal source and will automatically switch to the reserve source in the event of a failure of the normal source e he Stop setting opens the ATS s circuit breakers Stop Auto o Normal Reserve input input Figure 9 Example of an ATS control panel 64 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 14 TROUBLESHOOTING This section explains what to do in the event of an alarm condition or when any other out of the ordinary event occurs on the UPS 14 1 Alarm sounds and or Alarm LED lights up 1 Goto the Event Log and look at the Active Alarm Display to determine the nature of the alarm See Navigating to the event log and Active Alarm display on page 26 2 Look for the appropriate heading below according to the nature of the alarm and follow the instructions 14 2 Electricity returned but UPS remains in Battery Mode Check the external circuit breaker for the AC line The circuit breaker may be off 14 3 Battery Test failed It may be that an automatically scheduled battery test was executed shortly after the end of a power outage when the battery was still charging Wait until about two h
59. mensions H x W x D in cm Weight kc All specifications subject to change without notice O Power SA User Guide rel 3 0 FLOWCHART OF SYSTEM FUNCTIONS 23 z TT TT X O lt lt 2 Enter MAIN SCREEN UPS profile screen 1 gt o z EVENT LOG SET CLOCK SELECT LANGUAGE BATTERY TEST ADVANCED arrow keys OPTIONS UPS profile screen 2 Active alarms listed Press enter to view log UPS profile screen 3 Ac output screen Auto Restart Transfer Load Screen Contrast Tecnician Menu c Q TO CO E u o c L Ac input screen bypass and inverter Bypass screen screen Cold start Number of phases Change voltage Reset event log Bypass activation Battery screen Output voltage Input voltage Dc voltage Bypass voltage Change nominal value Adjust a phase up to 16 V Calibrate a phase s voltage Tune UPS input voltage setting to actual input voltage Tune inverter input voltage Tune UPS input voltage setting to actual input voltage Figure 29 Flowchart of system functions Power SA User Guide rel 3 0 98 GAMATRONIC ELECTRONIC INDUSTRIES LTD For a full company profile please visit out website at www gamatronic com Gamatronic Building Jerusalem Israel Gamatronic s product range UPS system
60. most dipswitch controls the output line configuration For three phase output the rightmost dipswitch should be switched towards the back of the UPS Refer to the diagram dipswitches J phase output 1 phase output tn i 60Hz 50Hz 5 te Master gt Slave q Do not Do not me modify modify Figure 22 Location of the dip switches Power SA User Guide rel 3 0 22 23 24 20 88 Push the UPS body back into the UPS shell and refasten the screws that you removed earlier from the UPS rear panel Plug in the 3 1 terminal assembly which you should have ordered and obtained beforehand and secure it by fastening the screws its right side The UPS must now be wired Follow the instructions in the section 8 1 3 Cable Connections for 3 1 Usage then continue with the next below Turn the circuit breakers ON for AC Input Bypass Input Output You can now start up the UPS If the UPS does not start up it may be that the UPS s line configuration setting does not match the dipswitch line configuration setting In this case go to the Profile screen and check that the line configuration setting matches the setting for the line configuration dipswitch Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 19 6 Switching to 1 1 operation 1x230 V input 1x230 V output Note that at any point in the procedure you can exit by pressing the ESC key 1 Turn th
61. n your own Note To connect the required cables to the UPS 1 Ensure that the lines coming into the UPS are equipped with circuit breakers of the following capacity UPS output 50A Class C Bypass output 50A Class C AC input 50A Class C The following table gives the required cable diameters that must be used when connecting the UPS The table states the cable diameters in mm Table 7 Wiring requirements for 1 1 configuration AC output Bypass input AC input Gnd N Ph Gnd N Ph Gnd N Ph Battery input 4 mm 10 mm 10 mm 10 mm Use the 1 5 meter long battery cable supplied by Gamatronic Using a screwdriver remove the cable cover from the rear of the POWER SA The uncovered rear panel is shown in the next illustration 46 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD AC OUTPUT TERMINAL CONNECTIONS AC OUTPUT gt BYPASS AC INPUT RECTIFIER AC INPUT BATTERY gt Power SA User Guide rel 3 0 47 3 4 48 Connect the AC Input Bypass Input and Output cables to the terminals on the rear panel of the UPS Ensure the cables are not live before you begin Use wires of the proper diameter as given on page 43 When you have finished the rear panel should resemble the following diagram Use the supplied battery cable to connect the battery to the UPS Recheck the connections before continuing To protect and conceal the cables
62. nd date according to the POWEH SA clock The information is displayed in the format HH MM SS DD MM YYYY To change the time and date press Ent At any time in the following process you can press Esc to exit to the Main Screen The changes you made before pressing Esc are saved The SET MINUTES screen is displayed Use the UP DOWN button to change the minutes setting Press Ent The SET HOUR screen is displayed Use the UP DOWN button to change the hours setting Press Ent The SET DAY screen is displayed Use the UP DOWN button to change the day setting Press Ent The SET MONTH screen is displayed Use the UP DOWN button to change the month setting Press Ent The SET YEAR screen is displayed Use the UP DOWN button to change the year setting Press Esc to exit to the Main Screen Power SA User Guide rel 3 0 51 9 2 Setting screen contrast The screen contrast function controls the visibity of the message text against the screen background The default setting of 144 is usually satisfactory but you can modify the default setting between the values of 0 and about 210 if needed To modify the console contrast 1 From the Main Screen press the Ent button to display the Main Menu 2 From the Main Menu select ADVANCED OPTIONS and press Ent 3 From the ADVANCED menu select SCREEN CONTRAST and press Ent The following screen is displayed MODIFY CONTRAST BY UP AND DOWN BUTTONS EXIT PRESS ESC CONTRAST
63. ny damage or malfunction due to incorrect wiring of the batteries Gamatronic is not liable for and the Purchaser waives any right of action it has or may have against amatronic for any consequential or special damages arising out of any breach of warranty and for any damages that the Purchaser may claim for damage to any property or injury or death to any person arising out of its purchase or the use operation or maintenance of the subject product This warranty includes parts and labor however Gamatronic shall not be responsible for any labor subcontracted or performed by the Purchaser to prepare the warranted item for return to Gamatronic or Gamatronic s agent The information contained in this document is proprietary and is subject to all relevant copyright patent and other laws protecting intellectual property as well as any specific agreement protecting Gamatronic s rights in the aforesaid information Neither this document nor the information contained herein may be published reproduced or disclosed to third parties in whole or in part without the express prior written permission of Gamatronic In addition any use of this document or the information contained herein for any purposes other than those for which it was disclosed is strictly forbidden Gamatronic reserves the right without prior notice or liability to make changes in equipment design or specifications Information supplied by Gamatronic is believed to be accurate and
64. or 3 3 usage 1 Ensure that the lines coming into the UPS are equipped with circuit breakers of the following capacity UPS output 3x16 A Class C Bypass input 3x16 A Class C AC input 3x16 A Class C The following table gives the required cable diameters that must be used when connecting the UPS The table states the cable diameters in mm Table 4 Wiring requirements for 3 3 configuration AC output Bypass input AC input Gnd N L1 L2 L3 Gnd N L1 L2 L3 Gnd N L1 L2 L3 Battery input 4 mm Use the 1 5 meter long battery cable supplied by Gamatronic 2 Using a screwdriver remove the cable cover from the rear of the POWER SA 36 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD The uncovered rear panel is shown in the next illustration Output terminal Bypass Input terminal AC Input terminal Battery terminal 3 Unplug the green plastic connectors and wire them as labelled Be sure the wires are not live before you begin Use wires of the proper diameter as given in Table 4 on page 36 Be sure to follow the proper phase order AC OUTPUT AC INPUT BYPASS AC INPUT EL SA User Guide rel 3 0 37 Battery Input Figure 3 Connections at the rear of the UPS Connect the wired connectors to the rear of the UPS Use the supplied battery cable to connect the battery to the UP
65. ours after the return of the AC power and perform a manual battery test This should clear the alarm 14 4 The UPS remains in Bypass mode The UPS may have been put in Bypass mode manually In such a case the lower left quadrant of the Main Screen says Manual Bypass To manually return the UPS to Normal mode see Manually entering or leaving bypass mode on page 57 14 5 Sync Fault Verify that the AC Input and the Bypass Input lines are connected to the UPS in proper phase sequence Verify that AC of the proper frequency Hz is being used See on page 72 Power SA User Guide rel 3 0 65 66 4 P P P4 5 P2 P3 P4 22 161 7 INVERTER BATTERY CONNECTION umo E S pie dodi ne P17 STATIC SWITCH 4 P8 P6 SIT TT L1 L2 L3 L1 L2 L3 L1 L2 L3 INPUT BYPASS OUTPUT 3X400VAC 3X400VAC 3X400VAC Figure 10 Block diagram of major components and connections Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 15 ALARM DRY CONTACTS The rear panel of the UPS contains a standard DB9 port labeled ALARM This port is an interface to the Alarm Dry Contacts The Alarm Dry Contact port is shown below The Alarm Dry Contacts can be used to notify a computer or another system when certain events take place on the POWER SA UPS system The dry contact circuits make use of opto couplers No more than 30 V and 100 mA should be applied to a dry contact Fi
66. pswitch should be switched towards the back of the UPS Refer to Figure 16 Location of the dip switches on page 80 Power SA User Guide rel 3 0 79 REAR OF UPS 23 24 25 26 27 80 dipswitches J phase output 1 phase output 60Hz 50Hz i o Master Slave E Do not Do not modify modify Figure 16 Location of the dip switches Push the UPS body back into the UPS shell and refasten the screws that you removed earlier from the UPS rear panel If you going to use the 3 3 rear panel adapter that includes a manual bypass switch bring the adapter near the UPS rear panel and plug the adaptor panel s bypass command connector see Figure 6 on page 42 into the rear panel of the UPS Plug in the 3 3 terminal assembly and secure it by fastening the screws on its right side The UPS must now be wired Depending on whether you are going to install the rear panel adaptor without the manual bypass switch or the rear panel adaptor with the bypass switch follow the instructions in e section 8 1 1 Cable connections for 3 3 usage NO manual bypass starting on page 36 OR e section 8 1 2 Cable connections for 3 3 usage WITH manual bypass starting on page 39 Then continue with the next step below Turn the circuit breakers ON for ac input bypass input and output You can now start up the UPS If the UPS does not start up it may be that the UPS s line configuration setting does not matc
67. r Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 4 1 1 On Off Button O d To turn the UPS on press the button twice To turn the UPS off press the button twice 4 1 2 Navigation Keypad The control panel s keypad consists of three buttons A v The UP DOWN key is used to navigate through screens and browse the Event Log Ene Ent Enter key is used to select an item or apply a change ee Esc Escape key returns you to the Main Screen During an active alarm condition pressing the Esc button from the Main Screen silences the audible alarm Indicators The top of the control panel contains four LCD indicators The status indicators show what 1 running and how the UPS is providing power to the load The table shows the color and meaning of the LCD status indicators when lit AC INPUT Green ac input is present and within normal range NORMAL Green The UPS is in normal mode BATTERY Yellow The UPS is in Battery mode BYPASS Yellow The UPS is in Bypass mode ALARM Red Indicates an alarm condition To determine the nature of the alarm From the Main Screen press Ent to display the main menu press Ent again to see the Alarm Status press Ent once more to see the Event Log Power SA User Guide rel 3 0 11 4 2 The POWER Display Screen The display screen on the POWER SA control panel shows the current operating mode and related critical data There are several distinct dat
68. s The checkmark indicates that the ac voltage of each input phase is within an acceptable range otherwise an is displayed instead of the checkmark The voltage and current for the three input phases is displayed AC INPUT Voltage P in range of range L1 228 V Volt d L1 229 v m umen L1 229 V 4 2 2 4 BYPASS SCREEN To see the current status of the Bypass from the Main Screen press V four times The checkmark indicates that the voltage of all three phases at the Bypass Switch is within an acceptable range If the voltage of any of the phases is out of range an X is displayed instead of the checkmark The voltage and current for the three Bypass phases is also displayed Voltage Voltage t in range of range L1 228 V L1 230 V Voltage and amperage of each bypass phase L1 229 V Power SA User Guide rel 3 0 23 4 2 2 5 INVERTER SCREEN To display the current status of the inverter from the Main Screen press V five times One of three possible messages describes the status of the bypass input voltage SYNC OK m The inverter output is phase synchronized with the bypass input SYNC ORD m The phase sequence of the bypass input is incorrect SYNC FLT m The bypass input and the inverter output are not in sync A checkmark indicates that the voltage of all three phases of the inverter output is within an acceptable range If the voltage of any of the phases is out of range an X i
69. s Power systems for the telecom industry Dc to ac inverters Dc to dc converters Frequency converters Battery chargers V VV VVNWvV V Power management solutions Headquarters and Factory 17 Hartom Street Har Hotzvim Industrial Park POB 45029 Jerusalem 9777517 Israel Gamatronic Singapore Sales Office email singapore gamatronic co il Gamatronic UK Ltd Gamatronic House Stephenson Court Priory Business Park Bedford MK44 3US United Kingdom Tel 44 0 1234 831111 Fax 44 0 1234 831114 email info gamatronic net Power SA User Guide rel 3 0 99
70. s and supplies ac electrical power to your equipment The POWER SA has three automatic modes of operation e Normal mode e Battery mode e Bypass mode 3 1 Normal Mode POWER SA almost always operates in normal mode In normal mode the load receives its power from the inverters that supply stabilized voltage protected from spikes and irregularities in the ac input The ac input system feeds the charger which supplies dc power to the inverter while concurrently charging the batteries ACINPUT NORMAL BATTERY BYPASS UPS ON NORMAL MODE L1 50 22 50 L3 51 e US Normal Mode display Power SA User Guide rel 3 0 7 3 2 Battery Mode If the input ac power fails or the voltage drops below an acceptable level the UPS operates in backup mode In backup mode the load continues to receive power from the inverters but the dc input to the inverter is taken from the batteries instead of from the rectifier The batteries are galvanically connected by dc link to the inverter and the charger The dc inherently remains constant when the ac input supply drops out without any switching devices The duration of the battery operation is determined by the load demand and battery capacity BATTERY LED LIT ACINPUT NORMAL BATTERY BYPASS UPS ON BATTERY MODE BATTERY L1 50 CHARGE L2 50 LEVEL L3 51 INDICATOR OAO ALARM v LED LIT Battery Mode display 8 Power SA User Guide rel 3 0 GAMATRONIC EL
71. s displayed instead of the checkmark The output voltage and current for each inverter phase is also displayed INVERTER Voltage SYNC OK Voltage in range 9 of range 230 V Voltage and amperage 2 3 0 V of each inverter phase 231 V SYNC FLT appears here 1f the inverter output 1s not synchronized with the bypass input SYNC ORD appears here 1f the bypass input phase order 1s improper 24 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 4 2 2 6 BATTERY SCREEN To see the current battery status and voltages from the Main Screen press six times The battery status can be e BATTERY OK e BATTERY LOW or e BATTERY FLT means the battery failed the latest battery test The battery s positive negative and total voltage is also displayed BATTERY BATTERY OK BATT E RY a P battery test failed TOTAL 663 V POSITIVE 432 V Battery voltage NEGATIVE 431 V Power SA User Guide rel 3 0 25 4 2 2 7 THE POWER SA MAIN MENU Through the use of the control panel buttons the user can Modify UPS settings Perform a manual battery test Move the UPS to bypass mode or back to inverter mode View current alarms View the event history The Main Menu is your point of access to a number of informational and control features To display the Main Menu from the Main Screen press Ent EVEHT LOG SET CLOCE SELECT LANGUAGE BATTERY TEST ADYANCED OPTI
72. seas aaa rre rna 4 2 1 Major Parts of the POWER 5 OPERATING MODES meer 7 Sal NonnabMode iugstesdiedtasissnte eot a iata eU Ran 7 S Balen MOOS c ET 8 3 9 Bypass aee o dde ee 9 USER INTERPAGCE ou Pos Due E ODIT ORE duo E Diu uU eR oue A 10 dp SCOR eb alls cumin pain nciht canc aliti Deters bit di Dot ccs ann duties tpa d rM ei ira 10 qo Omolb BD Oi eu iub oa 11 4 1 2 Navigation 11 MACO 11 4 2 The POWER Display SCIeer uia eode oen Con ace to e e that baee tuas oko rtu E DR 12 AO a cedit dut n ete ea 12 422 Salus Soles kun 21 DAILY OPERATION mt 27 zx ME Lo i o TETTE 27 o2 POWERS OA ee vado reo i a ee see 28 THE EVENT cer P mU 29 SM NUNN Romo 29 6 2 Navigating to the event log seessssesssesesseeeeenennnenne nennen mnn nnne nennen ns 29 6 2 1 Active Alarm 1 nennen nennen nnns 29 6 2 2 Event log entries wou ccsdleacetsteiwacsavavesasanaleucdyadaavedsberonsjaveuelaquralausiualsavetsPeiwaeeceleredaandys 30 6 2 3 Resetting the event log nennen nnne nennen nnns 30 BATERY TESTS tnn veto MY CENE e us C uu 34 TA A utomatc Dallery
73. separate components INTERNAL PROTECTIVE COVER TERMINAL PANEL EXTERNAL PROTECTIVE COVER GREEN CABLE CONNECTOR PLUGS D Figure 12 Reconfiguring from 1 1 or 3 1 to 3 3 Power SA User Guide rel 3 0 It 77 20 21 78 On the rear panel of the UPS remove the screws that secure the internal UPS body to its external shell See Figure 13 Note the number and location of the screws may differ from that shown in Figure 13 lt m 8 Pa 92 e i K 01 K ETIE TATUM m ee 94 Hitt mo es he EE D SE TE T 199 B OE 3 T R Ld Te 079 Fe i99 e ve ve ex vm ie WM UN o a 6 lt aae 4m lt 01601904 20 9 gt Ba ioka eas he E Figure 13 Remove the four screws from the rear panel Grasp the top of the rear panel and pull the UPS body firmly so that it is most of the way out of the external shell See Figure 14 and Figure 15 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD Figure 14 Accessing the dip switches 1 Figure 15 Accessing the dip switches 2 22 Onthe top front of the UPS body there is a set of three small dipswitches as shown in the diagram When looking at the dipswitches from the front of the UPS the rightmost dipswitch controls the output line configuration For three phase output the rightmost di
74. t it down for a period of time during which the load devices will not be operating Begin the process from the UPS ON NORMAL MODE screen ACINPUT NORMAL BATTERY BYPASS UPS ON NORMAL MODE Ire 550 L2 50 Ls 51 It is advisable to turn of all equipment connected to the POWER SA 2 Press the ON OFF button twice The ALARM LED lights up for a few seconds then the screen reads UPS OFF NO OUTPUT ACINPUT NORMAL BATTERY BYPASS UPS OFF NO OUTPUT EL 0 Il 0 L3 0 US The Power SA shutdown is now complete 28 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 6 THE EVENT LOG The Event Log is really a combination of two functions e display of active alarms e history of important events that occurred to the UPS 6 1 Alarms In the event of an alarm the audible alarm sounds or the red alarm light on the POWER SA console lights up go to the Event Log to determine the nature of the problem Pressing the Esc key from the Main Screen silences the audible alarm 6 2 Navigating to the event log To see the event log 1 From the Main Screen press the Ent button to display the Main Menu 2 Onthe Main Menu press Ent again 6 2 1 Active Alarm display The first thing you see upon entering the Event Log is the Active Alarm display If there are any active alarms a 1 line message is displayed for each alarm to indicate the nature of the alarm For
75. t43 Baten veu da epe repas ve vite neta aati Vei Peine Laud aide nei Ya cU DU da 65 14 4 The UPS remains in Bypass mode nnne nnn nnns anna nne 65 TA 65 ALARM DRY CONTACTS 67 69 SNMP AGENT OPHONAE eut OO e dv atu va tow Ee 70 WIRELESS CONTROL OPTIONAL i 71 CHANGING THE UPS LINE CONFIGURATION a rsen assa nennen mnnn 72 19 1 Note regarding battery connection on 72 19 2 Determining present phase setting 73 19 3 A Summary Before Changing the Line 74 19 4 Switching to 3 3 ODGratlOfi c stes edes reto esas ecciesia uc tud ae 75 19 5 Switching to 3 1 operation 3x400 V input 1x230 V 81 19 6 Switching to 1 1 operation 1x230 V input 1x230 V 89 PREVENTIVE MAINTENANCE 515 ieu 96 SERVICE AND REPAIRS 96 POWERt SA SPECIFICATIONS 52 RN 97 FLOWCHART OF SYSTEM FUNCTIONS eene eene nnne nena nhau uuum seen asas asas aman Ioas assa aane esas asas asas nenne 98 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD LIST OF FI
76. the Power rear panel can be used to move the system to bypass mode Simply turn the switch from the UPS position to the BYPASS position The Bypass LED on the system console lights MANUAL BYPASS SWITCH 3 ERRORS e Figure 7 The manual bypass switch on the rear panel To end bypass mode and transfer the load back to the system inverter simply turn the manual bypass switch from the BYPASS position to the UPS position Power SA User Guide rel 3 0 57 11 1 2 Entering bypass mode via the system console 1 From the Main Screen press the Ent button to display the Main Menu 2 Onthe MAIN MENU select ADVANCED MENU and press Ent 3 On the ADVANCED MENU select TRANSFER LOAD and press Ent ADVAHCED MENU AUTOMATIC START TRAHSFER LOAD SCREEN CONTRAST MENU The TRANSFER LOAD screen tells you if the load is currently on the INVERTER or if the UPS is BYPASS MODE 4 Press Ent to switch the load LOAD ON INVERTER TO TRANSFER LOAD TO BYPASS PRESS ENTER TO EXIT PRESS ESC 58 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD On the Main Screen the message Manual Bypass appears in the lower right quadrant The audible alarm sounds after 60 seconds AC INPUT BYPASS LED LIT LED LIT ACINPUT NORMAL BATTERY BYPASS UPS ON BYPASS MODE L1 76 MANUAL L2 76 BYPASS L3 76 Ent Ee
77. ttery icon decreases Power SA User Guide rel 3 0 15 When the BATTERY LOW message appears there are only a few seconds before the battery is exhausted To avoid losing information you should at this time save your data and perform an orderly shutdown of any computers connected to the UPS if you have not already done so BATTERY LED lit ACINPUT NORMAL BATTERY BYPASS BATTERY LOW BATTERY LOW LI 17 D L2 17 L3 17 Oik ALARM LED lit When the UPS battery is exhausted the UPS does one of two things depending on the setting of auto restart mode e When auto restart is DISABLED the UPS shuts off and remains off even when ac power is restored When ac power is restored you must press the OFF ON button twice to turn on the UPS None of the top LEDs are lit ACINPUT NORMAL BATTERY BYPASS 3 UPS OFF at END OF BACKUP UPS OFF indicates Auto restart mode is END OF BACKUP OFF L1 0 L2 0 L3 0 ALARM LED lit 16 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD e When auto restart is ENABLED the Main Screen shows the UPS ON message When ac power is restored the UPS starts up automatically None of the top LEDs are lit ACINPUT NORMAL BATTERY BYPASS UPS ON at END OF BACKUP UPS ON indicates Auto restart mode is END OF BACKUP ON 1 0 L2 0 L3 0 ALARM LED lit Power SA User Guide rel 3 0 17 4 2 1 3 BYPASS MODE In Bypass mode the
78. ue for an electronic device but electric companies charge for both true and reactive power resulting in unnecessary charges In power factor correction the power factor represented as is the ratio of true power kwatts divided by reactive power kvar The power factor value is between 0 0 and 1 00 If the power factor is above 0 8 the device is using power efficiently A standard power supply has a power factor of 0 70 0 75 and a power supply with PFC has a power factor of 0 95 0 99 Power SA User Guide rel 3 0 5 INVERTER A 3 phase PWM inverter is connected to batteries by a classic dc link STATIC SWITCH ST SW The Static Switch enables an automatic transfer of the load from the output of the inverters to an alternate source whenever the inverter can no longer supply power to the load The static switch transfers current at high speed BATTERY The POWER SA battery bank is used as a backup in the event that the utility ac input fails The batteries are housed in an external cabinet next to the POWER SA cabinet Batteries are charged by the rectifier which supplies both the inverter and the battery charger AC INPUT STATIC SWITCH AC OUTPUT AC DC LINK INPUT CHARGER INVERTER Figure 2 Block diagram of the POWER SA 6 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 3 OPERATING MODES The POWER SA is installed between the power mains and your load device
79. urn on the UPS None of the top LEDs are lit ACINPUT NORMAL BATTERY BYPASS S m UPS OFF at END OF BACKUP UPS OFF indicates Auto restart mode is END OF BACKUP OFF L1 0 L2 096 Bea 0 SLz ALARM POWER 5A ALARM LED lit Power SA User Guide rel 3 0 61 62 If Auto restart is ENABLED the Main Screen shows the UPS ON message When AC power is restored the UPS starts up automatically None of the top LEDs are lit ACIMPUT NORMAL BATTERY BYPASS UPS ON at END OF BACKUP UPS ON indicates Auto restart mode is END OF BACKUP ON L1 0 2 096 L3 096 ALARM LED lit Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 13 USING THE UPS WITH A GENERATOR 13 1 The Automatic Transfer Switch ATS At many sites a generator is used as a reserve source for feeding the UPS during mains power failure In such cases the switching between the two sources the mains and the generator is performed by an Automatic Transfer Switch ATS Because these two sources are not usually synchronized switching between them requires an interval of at least 10 seconds Figure 8 illustrates the timing factors involved when using an ATS For proper functioning of the UPS the values used for T3 and T4 must be greater than 10 seconds The optimum delay times can be revealed with a little testing and may vary from site to site depending on the UPS on the loads and on the particular ATS being used
80. utage if auto restart is disabled None of the top LEDs are lit ACINPUT MORMAL BATTERY BYPASS UPS OFF END OF BACKUP UPS OFF at L1 0 END OF BACKUP L2 0 indicates Auto restart L3 0 mode is OFF ALARM LED LIT Power SA User Guide rel 3 0 19 20 OFF mode can also be invoked remotely through the RS232 data connection AC INPUT LED LIT ACINPUT NORMAL BATTERY BYPASS UPS OFF NO OUTPUT Li 0 RS232 RS232 L2 0 Shutdown Shutdown L3 0 gt E SA Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 4 2 2 Status Screens From the Main Screen by means of the V button you can access several screens that provide current UPS status information e UPS Profile screen e ac Output screen e ac Input screen e Bypass screen e Inverter screen e Battery screen 4 2 2 1 UPS PROFILE SCREENS To see the UPS Profile screens from the Main Screen press There are three UPS Profile screens The first UPS Profile screen shows e Current date according to the UPS s clock DD MM Y YY Y e Current time according to the UPS s clock HH MM SS See section 8 1 for instructions on setting the system clock e Nominal output voltage e Nominal output frequency e Auto restart status ON or OFF oee chapters 9 and 11 for information about the Auto Restart feature To see the second UPS Profile screen press again The second UPS Prof
81. y a written service agreement between Gamatronic and the customer Without a written agreement Gamatronic is under no obligation to provide service after expiration of the initial warrantee period Gamatronic will not be responsible for maintenance or changes to the UPS that are performed by an agent without written authorization from Gamatronic 96 Power SA User Guide rel 3 0 GAMATRONIC ELECTRONIC INDUSTRIES LTD 22 POWER SA SPECIFICATIONS POWER SA TECHNICAL DATA 230 3X400V True on line battery double conversion 10 kVa nominal Ac Ac efficiency nominal Voltage V 3x400 V 230 V 45 65 Hz Power walk in sec gt 60 Power factor THDI 96 5 Earth leakage current Output Regulation for unbalanced load 1 for 100 unbalanced load Inverter efficiency nominal 98 O Static Switch S O E Maximum power dissipation Po 8KW 384 W 1300 BTU Ambient temperature C 10 to 40 operating 20 to 70 storage Relative humidity Altitude m 1500 without derating Enclosure IP20 Cooling system Multi fan with speed control forced Acoustic noise full load at 1 5m distance M 250 000 Dimensions H x W x D cm Weight LCD displa UJ TI 2 Log events memory last 200 events M Design Safety IEC 62040 1 under LVD 2006 95 EC Low magnetic field radiation Type Number Voltage Backup time min 6 at 50 load Recharge time hrs Di

Download Pdf Manuals

image

Related Search

Related Contents

travelmate c300  1- Pair Port PoE (IEEE 802.3af) Mid-Span Power Supply  Conditions Générales d`Abonnement des offres de la gamme  DTR-T1000 Specification Brochure  Guide du Tri - Communauté de communes du sénonais  Rob_Papen_RG_Manual_German version 1.1  The Practical User Guide to DGOM-PlankTOM or: How to survive the  magicolor 5550/5570 - Printers  bibliographie élémentaire cartographie  LE MANDALA INTERACTIF Mode d`emploi  

Copyright © All rights reserved.
Failed to retrieve file