1. To make adjustments scroll each time wheel to adjust the month day year hour minutes seconds and AM PM selection Once all adjustments have been made press the Save button to set the system clock to the date and time entered 9 3 1 Time Options Select the Time Options tab to configure the time zone and national time server clock settings If nCompass is connected to the internet these settings can be used to have nCompass automatically synchronize its time with one of the nationally provided time servers Adjust Time Time Zone Eastern Standard Time a L NTP Server local Name IP 192 168 0 102 Current Time 9 19 2013 9 34 39 AM NTP Service Enable ON wem To enable the national time server select your time zone and which time server you wish to use from the drop down menu selections Turn on the NTP Service Enabled option and press the Save button nCompass will then synchronize its time with the selected national time server at 2 00AM each day lf nNCompass is not connected to the internet a local alarm message will be shown on the alarm screen NTP Failure Check cable and server to indicate that the time server could not be located Offline Setup FDC nCompass 9 5 f FUTUREDESICN N T R O nCompass i4 3 9 3 1 1 Local Time Server Settings If an active internet connection is not available or company policy prohi
2. activation in which the input must make the required transition state in order to activate the function When selected the input will put a running program into the hold state If a program is not currently running no action will occur This is a single shot activation in which the input must make the required transition state in order to activate the function When selected the input will put a program that is in hold into the run state Ifa program is not active or the program is not currently in hold no action will occur This is a single shot activation in which the input must make the required transition state in order to activate the function When selected the input will turn the program off This will also turn off all system events If a program is not running no action will occur and event status will not be affected This is a single shot activation in which the input must make the required transition state in order to activate the function When selected the input acts as a trigger for the program wait for digital input function The input can then be selected in the program to pause a step until the input is activated When selected the input will act as a switch that can be used to directly control a digital output of the nCompass control module In order to use the input as a switch for an output the digital output must be configured to use the input for control See Section 9 8 Digital Outputs for
3. If the analog output is being used to control the position of a cooling valve or SCR power controller of a heater bank for example it is important that the analog output supply only the signal for the proper heating or cooling range in order to properly control the amount of cooling or heating applied to a process nCompass provides the ability to supply only the heating output cooling output or a combination of heating and cooling outputs from its analog outputs For example if an FDC 300 series control is used setting an Out Min to Out Max range of 0 to 100 will result in an analog output of 0 10Vdc or 4 20mA for an output of 0 to 100 heating If a different model of controller is used that represents heating as 50 to 100 with cooling from 50 to 0 setting an Out Min to Out Max range of 50 to 100 will result in an analog output of 0 10Vdc or 4 20mA for an output of 0 to 100 of the heat output In order to retransmit a cooling percentage of output nNCompass allows the analog output range to be inverted relative to the value representing the cooling percentage of output This allows the positoner of a cooling valve for example to receive a 0 10Vdc or 4 20mA signal representing 0 full closed to 100 full open of cooling even if the cooling percentage represented by the controller is 50 no cooling output to 0 full cooling output For example if 0 to 100 represents no cooling to full cooling setting
4. Improper voltage or frequency Improper lead connection Ho operstion no damage Permanent damage may be caused Permanent damage may be caused FDC nCompass A 5 d FUTUREDESION c O N T R O nCompass i4 3 Main CPU Input Specifications DC Input Specifications CPU Module laput Points and Common Lines Terminal Arrangement Rated Input Voltage Input Voltage Range Rated Input Current Input Impedance Tara ON Time Turn OFF Time Isolation Input Type Extemal Load for 1 0 Interconnection Signal Determination Methel Effect of Improper Input Conmmection Cable Length Connector on Mother Board Connector Insertion Removal Durability Input Operating Range The input operating range of the Type 1 HEC 61131 2 input modu is shown balga Inputs IO 12 13 14 16 and I7 Ud Lei E KZ Input Gurmrerg im 4 5 6 0 Inputs 3 15 and ELO te Hi7 Inpu SD eee ie Lei FDC nCompass POSADIGRSL amp points in 1 commen line 24V DS sink source input signal 20 4 to 26 4V DC OH 3 l4 6 7 46 mA point 24V DO 12 16 10 to liT T m point 24 DC OH B la 16 FP 4 9 k i2 16 0 to liT 3d Ki OH aL I7 5 ue filter value 3 15 35 us filter value LO te liT 40 us filter value OH ae Ir 5 ue filter value 3 15 159 ps filter valus LO to liT 150 ps filter value Hot isolated Photecoupler isolated Between input terminals Internal circuit Type 1 EC 1131
5. 2 8 FDC nCompass Installation FUTUREDESION N T R O nCompass i4 3 fil 2 3 5 3 Digital Output Module The digital output card FC4A R081 or FC4A T08S1 provides 8 additional control outputs to the system EH Communications Connector Cover sticker Remove ONLY when attaching additional O modules 2 3 5 4 Analog I O Module Each nCompass analog I O card FC4A L03A1 provides two inputs and one output to the system lt Remove ONLY when attaching additional LOCH modules LUH Oooo oud Installation FDC nCompass 2 9 N T R O LS f FUTUREDESIGN nCompass i4 3 2 4 nCompass Control Module Installation Example The installation order of the control module expansion cards is important and should be installed from left to right in the following order 1 FC4A HPC3 RS485 Card 2 FC5A D16RS1 Main CPU 3 FC4A SIF4 User Communication Card 4 FC4A SIF2 Barcode Reader Communication card 5 FC4A N08B1 8 point 24 VDC Input Card 6 FC4A R081 8 point Relay Output Card 7 FC4A L03A1 Analog Input Output Card s User RS485 232 8 Relay Comm Cards Output CL CL ch O Bi P o TI E t dt 1 rAlS VSO LSU9 La WSO4 LasON WrO4 uEOtgb ETH N d Digital Analog Input Input Output Cards 2 10 FDC nCompass Installation nCompass ia3 ff eurupenesron 3 Wiring This section describes the methods and precautions for wiring the nCompass system components Before
6. DIP switch 9 is used to select the upscale or downscale value for sensor break detection A value of 32 768 is used to indicate upscale break and a value of 32 67 is used to indicate downscale break NOTE DIP switch 8 is not used with the RTD module so its position does not affect operation As there is no inter channel isolation isolated RTD s must be used in order to prevent ground loops and reading errors Input ta k input ta o i aW Input a d l Input 2b Input Ze Input 3a Input 3b Input Ze Se ce e on t ro os Lo RTD 7 2 Wire fe Lu lin Le Oooog Goooeereeer e DI 3 10 FDC nCompass Wiring FUTUREDESION c O N T R O nCompass i4 3 fil 3 6 Connecting to the nCompass Control Module lf output relays or transistors in the control module should fail outputs may remain on or off For outputs that may cause malfunction of equipment that could lead to property damage or injury monitoring and or safety circuits MUST be provided outside of the control module Depending on the load a protection circuit may be required for the relay outputs of the nCompass control module and optional output card Choose the appropriate protection circuit from A through D shown below according to the power source for the load For protection of transistor outputs connect protection circuit C shown below to the transistor output circuit Protection Circult A This pro
7. Do ll 1 II 1 Seng ae Communications FDC nCompass 10 7 f FuTUREDESIGN nCompass i4 3 N T R O 10 1 4 Using the VNC Server The nCompass VNC server allows a user to remotely monitor and control nCompass by directly viewing and manipulating the touch screen over the network You must use the assigned IP address and VNC port number to access nCompass The IP address is shown on the communications screen and is also included in the notifications list Write down the IP address and port number so you will have it to enter into your VNC viewer There are many VNC viewers available for both PC and tablet use Due to the ever changing market and availability of such applications it is not possible to test them all for compatibility or provide assistance for their use with nCompass It is the responsibility of the end user to test the chosen VNC client for compatibility with nCompass prior to putting the unit into service If the VNC client viewer has compatibility issues with nCompass it can cause the VNC server to stop responding and or shut down requiring power to be cycled to nCompass in order to reboot the system and restart the server Future Design Controls has tested and recommends the use of RealVNC s viewer It has been tested for compatibility with nCompass and a free version can be obtained from http www realvnc com for PC MAC use RealVNC does offer a version for the iPad that can be obtained through the App Store for a small fee
8. If you suspect that there is a problem with your nCompass controller if you are unable to change a loop set point contact your OEM and verify the configuration of your system to determine if the loop is operating under cascade control and how that interacts with your equipment 4 1 1 2 Calculated RH Loop Mode If a loop is configured as an RH wet bulb control loop it will appear as a normal control loop on nCompass however the reading on the nCompass display is a calculated relative humidity value while the reading on the process loop controller will be a temperature reading nCompass calculates humidity by using two temperature loops a dry bulb loop and a wet bulb loop as set in its configuration to calculate humidity When entering the humidity set point on nCompass the set point shown on the display of the process loop controller will not match that of the nCompass display because it is a calculated wet bulb temperature set point This set point value will change as the dry bulb temperature input varies in order to maintain the proper set point for maintaining the desired relative humidity If you suspect that there is a problem with your nCompass controller or a control loop does not seem to be operating properly contact your OEM and verify the configuration of your system to determine if the loop is operating under the calculated RH loop mode and how that applies to your equipment Basic Operation FDC nCompass 4 1 f FuTUReEDESIGN
9. It is accessed from the home View menu The screen allows manual set point entry for each loop by touching the respective set point entry field As on the Single Loop view screen the left and right scroll buttons allow you to cycle through each loop and monitor point available in the system 100 0 4 16 FDC nCompass Basic Operation f FuTUReEDESIGN N T R O nCompass i4 3 4 6 System Event Control Events are the switches used to turn the digital outputs of nCompass on and off These events can be manually turned on and off as well as programmed into automatic ramp soak programs so that they can be turned on and off at set time intervals NOTE Not all digital outputs of nCompass may be able to be controlled as event outputs Depending upon the configuration of nCompass some outputs may perform specific control or alarm functions The use of each output and what it controls is determined by the system designer Consult section 9 12 on Digital Outputs and how to program them as event outputs or any of the other available control functions The names of events are also determined by the system designer The screen shot below is an example showing factory default event names Consult section 8 5 on Event names in order to see how to change the names of events so that their description in the list matches their function to avoid operator confusion EYZ DO 2 EY DO 3 E 4 DO 4 E 6 DO EN DO 7 EYG DO To turn the
10. N T R O 4 2 Touch Screen interface The nCompass display is split into two sections the icon bar and main display area Main Display 100 0 o Manual Control BI Automatic Tune Single Loop View Screen nCompass i4 3 The menu icon will open the main menu for navigating to the different control and Leed monitoring screens Menu items will dynamically appear providing available options based on the system area the user is in Le security data logging setup etc ny The information help icon will display text based help associated with the current A screen Help is available in 28 languages based on the user selection in the offline ee setup of section of nCompass The home icon will return the user to the main view from anywhere in the nCompass application The main view is set by the OEM in the nCompass configuration and can be the single or dual loop chart alarm alarm history event or digital IO view The alarm icon will appear and flash when a new system alarm occurs Pressing the alarm icon will take the user directly to the alarm monitor screen in order to view and or The left and right navigation arrows will appear on screens that provide additional information that the user can scroll to such as the loop view screens charts or program entry screen in order to cycle through each step of a ramp soak program E Vi OH ig AA reset the active alarm condition The up and down navigation
11. No Dielectric Strength Between Input and Ground 2000 VAC 1 minute Insulation Resistance Batween Input amp Output Terminals 100 MO Min Operating Temperature 10to 6OPC 14 to 10 F Storage Temperature 25to 75 C 13 to 167 R Operating Humi ng Hun idity 20 to 90 relative humidi lity na ca no condensation no freezing Vibration Resistance Frequency 10 to 55Hz Amplitude 0 375mm Shock Resistance m s 3 times each In amp axas EMC EN61T204 3 EMI Class B EMS Industrial VO ENDIJS Approvals ENSO1TE 1997 UL 1604 UL 508 JL1310 PSER SC SDL c UL CSA 22 2 No 14 Harmonic Directive EN61000 3 2 N A Weight approx 285g Terminal Screw M3 5 slotted Phillips head screw screw terminal type IP protection _ IP20 fingersafe Dimensions H x W x D mm x 36x 108 Dimensions H x W x D inches 3 74 x 1 42 4 25 2 tBerween input and ouput 20002 I minute Behveen entput and ground SOORAC J minute APPENDIX FDC nCompass A 17 FUTUREDESIGN nCompass i4 3 P Power Supply Specifications page 2 of 2 Temperature Derating Curves PS5R SD Condition Natural Air Cooling Operating Tamperature means uly rature in surrounded e PS5A we HI Make sure of conva ction in SH consideration of sufficient heat Se radiation Do not block the A opening ofthe switching power Bon supply 20 Keep at laast mm clearance around the switching power 0 o 0 2 am 4 m a a supply except
12. The App Store also offers a free VNC client called Remotix for the iPad It has also been tested for compatibility with nCompass NOTE Contact your network administrator prior to enabling the VNC server of nCompass Company policy may prohibit the use of VNC servers and or viewers for security reasons Future Design is not responsible for the use of nor makes any claims as to the security of the VNC server interface over your network The use of the VNC server is the responsibility of the end user 10 1 4 1 Recommended VNC Viewer Settings PC MAC This section applies to setup of the recommended RealVNC viewer for PC MAC These settings have been tested and evaluated in order to provide the best performance and quickest response to user input when using the VNC viewer with nCompass After installing the VNC viewer software it is recommended that the following changes be made to the default viewer settings To begin start the VNC viewer Click on the Options button in order to open the VNC Viewer Options window VNC Viewer A VNC Server we Encryption Let VNC Server choose About Click on the Advanced button at the bottom left of the window in order to show the advanced setup options On the Display tab make sure the scaling is set to No scaling and the checkbox for Adapt to network speed recommended is checked 10 8 FDC nCompass Communications c O N T R O nCompa
13. digital output force and input monitor screens as well as the import export configuration utility FDC nCompass 4 11 N T R O f FuTUREDESIGN nCompass i4 3 4 3 5 Data Menu The data log menu is provided when the user selects Data from the main Data menu See section 7 on Data Logging for information on these settings and their use 4 3 5 1 Text Based Data Menu Wises Annotation Signature The View menu provides access to the data file Annotation and digital Signature screens The File menu provides functions for opening and deleting historical data log files View gt File d Open Delete The Data menu provides access to the main Data screen for starting and stopping data logging and to the log point Assignment screen where the user can select which items are to be logged to the history file Chart Utilities The Chart menu provides functions for viewing historical data files in graphical format Utilities Chart The Utilities menu provides access to the nCompass file management utilities including USB file transfer and FTP WAN back up 4 12 FDC nCompass Basic Operation nCompass i4 3 4 3 5 2 Icon Slide Page Based Data Menu ae Open b A Annotation Signature Memory Basic Operation f FUTUREDESICN N T R O Slide page 1 provides access to the main Data log screen and to the log point Assignment screen where the user can select whi
14. if the display does not come on within 2 seconds remove power The interface is reverse polarity protected Check wiring to insure proper connections and try to power up again An Internal fuse will prevent damage for over voltage conditions however it isnt guaranteed DC voltage sources should provide proper isolation from main AC power and similar hazards To 24Vdc Power Supply COM1 port DB9 male RS232C Signal Name Signal Ee RD ITD Transmit data Output Data terminal ready Output TD Signal Ground e Data set ready T Request to send Output Clear to send 3 4 FDC nCompass Wiring nCompass ia3 ff eurupenesron N T R O 3 3 1 Serial Communications to Control Module The nCompass interface is connected to the control module via a single cable with a 9pin connection on the interface end and an 8pin mini din connection at the CPU end Future Design Controls offers this cable as an option p n CA2011 8N The cable can also be manufactured according to the following diagram Mini DIN Connector Pinouts e raoa 3 e o ERC se signalGrond 7 J D sub 9 pin Female Connector Pinouts emn Description s se Signal Ground Wiring FDC nCompass S f FuTUReEDESIGN N T R O nCompass i4 3 3 4 Connecting to the nCompass Process Loop Controllers nCompass can support up to 3 individual control loops The controllers communicate with the nCompass control module using the RS485
15. nCompass provides this ability but there are considerations that must be taken by the end user to protect their equipment and investment Just like placing a personal computer on the internet opens it up to outside attack placing your nCompass on a network poses the same risk The first thing to remember is this The most likely cause of problems is not a hacker trying to sabotage your equipment but more often to be related to the ubiquity of PCs with Ethernet cards the ease with which your own co workers can hang stuff on the network and careless or nonexistent internal security measures Accidental problems are more common than deliberate ones Allowing anyone access to nCompass by placing it on the office LAN also opens the door for accidental shutdown damage to equipment loss of data lost time etc This is possible even by the most well intentioned co workers Thus there are several steps that should be taken to minimize this risk The first is to never mix your office LAN with your control LAN The control LAN should be a separate network that consists of your nCompass controller s and possibly any other equipment that you may have that is related to the operation of the system It should be separated from your office LAN by a firewall or at minimum a bridge or router A control network and a business network have two entirely different purposes and their interaction should be closely controlled It is also unwise to assume
16. only the high SP is used for high alarms low for all low alarms and both fields are used for Absolute Deviation A Out both alarm types J See the following section for information on setting the set point for a rate of change ROC alarm The Low set point defines the input value that will trigger a low side alarm It must be lower than the alarm high set point The High set point defines the input value that will trigger a high side alarm It must be higher than the alarm low set point The Differential often referred to as alarm hysteresis defines how far the input must return into the normal operating range before the alarm can be cleared High side Alarm Range filam High Set Point Mam Hysteresis Normal Operating Range Tempera re alarm Hysteresis Abm Low Set Point Low Side Alarm Range Tire 8 10 FDC nCompass Device Settings f FuTUReEDESIGN N T R O nCompass i4 3 The alarm on delay time Delay seconds can be used to delay the activation of the alarm If the input exceeds the alarm setting but then re enters the normal operating mode before the alarm delay time expires the alarm will not be activated The allowable time setting is from O 32 760 seconds A value of zero 0 disables the alarm delay and the alarm will activate immediately when the input exceeds the alarm settings The Start Delay seconds works in conjunction with the alarm start delay mode selection
17. or Status from the Program menu The menu provides all functions related to the creation editing and operation of programs See section 5 on Automatic Ramp Soak Program Operation for detailed information on how to create and run programs 4 3 2 1 Text Based Program Menu Status The View menu provides navigation to the program view screens These E include the Status Entry Guaranteed Soak limits and profile AutoStart niy screens Soak AutoStart The File menu provides functions needed to create open save and New delete automatic ramp soak programs Open Save Save As Delete The Step menu provides all of the functions needed to edit programs These include Insert Remove Copy and Paste step functions as well as the Clone event function which allows the user to transfer the current step Remove event selections to all following program steps with a single click to Copy simplify and speed program entry Insert Paste Clone The Program menu provides the program control selections for Start Hold Halt and Off The Adjust menu provides functions for adjusting the operation of a program while it is running These items are available when the program is placed in hold and include step Time and advance to the Next or Previous step Time Next Previous 4 6 FDC nCompass Basic Operation f FuTUReEDESIGN N T R O nCompass i4 3 4 3 2 2 Icon Slide Page Based Program Menu 6 28 2013 Slide page 1 prov
18. 10 1 4 2 Recommended VNC Viewer Settings for Tablets c cc ccccccccseceseeeeseeeeeeeseeeeseeeeseeeeaes 10 10 10 1 4 3 Accessing nCompass through a VNC Viewer 10 11 10 2 Gebees eege Ee 10 13 11 Alarm Codes and Troubleshooting cccccsccceeeeeeeeeeeeeeeceeseneeenseesecensseneeeesonesees 11 1 Appendix Component Specifications Order Matrix and Replacement Parts Software Versions Software License Software Usage Note Warranty Returns iv FDC nCompass Table of Contents f FuTUReEDESIGN N T R O nCompass i4 3 1 What is nCompass The nCompass system combines all of the features of typical loop controllers video chart recorders and data logging systems into a single intuitive device Email SMS text messaging FTP file transfer protocol for automated data backup and remote view control Web server VNC server are standard with nCompass and can be accessed via LAN WAN using a PC tablet or smart phone device Future Designs nCompass provides a 4 3 color touch screen interface with standard Smart Device user interface features for single and dual loop OEM control applications All loop configuration and runtime user access is configurable at the device with no PC software required OEM s have the ability to configure runtime features screens available menus etc to easily customize the system for their requirements These configurations can be imported exported to any nCompass device for setup f
19. 11 to complete RS232 settings For pre postamble settings see page 13 Scanner of the MS 120 Series Programming Manual Step 1 scan barcode at top of page 13 for enter group 5 Step 2 scan barcode D1 for terminator at top of page 14 and then scan the barcode for the number 3 on page 13 Step 3 scan barcode PP for preamble at bottom of page 14 and then scan the barcode for STX at top of page 30 2nd down on left Step A scan barcode OO for postamble at bottom of page 14 and then scan the barcode for ETX at top of page 30 2nd down on right Step 5 scan the barcode for exit on page 13 to complete settings Device Settings FDC nCompass 8 19 f FuTUReEDESIGN N T R O nCompass i4 3 8 9 2 Important Notes on Barcode Reader Use There are certain limitations of use for the barcode reader based on the mode of operation selected It is important that the user read and understand these to insure that the barcode reader operates as expected 8 9 2 1 Using the Barcode Reader to Start an Automatic Ramp Soak Program When using the barcode reader to start a program the scanned barcode data must match the ramp soak program name exactly in order for nCompass to load and prompt the user to start it Program names can be a maximum of 16 characters which also matches the maximum data that nCompass will accept from the barcode scanner However if a prefix is also used the overall name prefix scanned data can exceed the maximum all
20. 2 common lines 16 N contacts in 2 common lines 2A per point Makmum Load Curent TA Percommon line SA Percommon line Minimum Switching Load 2 1 m rO IV DE preference value inda Contact Resistance 30 mA maximum Ekka Life 100 000 operations minimum rated ad 1 600 operastion s hour Mechanical Up 20 0000 000 op rations minimum ino oad 18 000 operations houn ER 2400 AC h teslst Me load inductive ad cosa 2 4 SON DC 2A resistive load inductive logd L R 7 msi Between output and ord terminals 1 POUM AC 1 minute DetscHk Su ene Eetween output terminal and internal cimuit LSD AC 1 minute Eetween output terminals C DM sy L500W AC 1 minute MC 1 57 11 5 3 81BH MEL 6 106 3 81BK a EE E a al Phoenix Contact Phoenix Contact Connector Insertion Removal Durability 100 times minimum 20 MASY DE 45 mA TE DE A TE 40 mAt24V DC pm 24 D I Intemal Curent Draw Eeer BEE DI Dm OFF omar2avpCn OmA 24y DC Inema Power Consumption 1 1EM 2 10 at 24V DE while all outputs DN wagm 1458 Output Delay On CRF Command Cutput Relay Status CFF OFF della 10 ms matmum Chatter Gre matimum ON dela Eme retour A 14 FDC nCompass APPENDIX FUTUREDESION c O N T R O nCompass i4 3 fil RS232 485 Communications Card Specifications page 1 of 2 HPCS Loop Communications Adapter Type No FC4A HPCS Standards EIA R5485 Maximum Connectable Quantity Maximum Baud Rate 57 600 bps Maintenance Communication Pos
21. 3 fil 9 4 Language The Language screen is used to select the language for all of the online help menus and most static display fields Note that the keypad will remain in English so all user text entry will still be in the English language OA t4 OFF French OFF German Available language selections include Afrikaans Albanian Arabic Basque Belarusian Simplified Chinese Traditional Chinese Czech Danish Dutch English Finnish French German Greek Hebrew Hungarian Icelandic Italian Japanese Korean Norwegian Polish Portuguese Russian Spanish Swedish Turkish DISCLAIMER English is the default language for the nCompass control system All other language selections provided through internet translation of the English language FDC does not guarantee the accuracy or validity of alternative language selections and shall not be liable for any damages or losses whether direct indirect incidental special consequential or any other damages for misinterpretation of other languages FDC offers a free PC based application which allows the end user or OEM to create the translation files for the desired language selection The translation files can then be copied to the nCompass control system in order to provide a more accurate or desired translation for the online help files Offline Setup FDC nCompass 9 7 f FuTUReEDESIGN N T R O nCompass i4 3 9 5 Analog Inputs nCompass supports up to 4 analog inputs which ar
22. 4 FUTURE DESIONn O N T R O Orion nCompass CM i4 3 Multi loop Controller User Manual kd a my LOOP 1 100 0 Orion nCompass CM i4 3 Controller User Manual Rev C October 2013 V1 1 Supersedes Rev B June 2013 N T R O f FuTUREDESIGN nCompass i4 3 Safety Information in this Manual Notes cautions and warnings appear throughout this book to draw your attention to important operational and safety information A NOTE marks a short message to alert you to an important detail A CAUTION safety alert appears with information that is important for protecting your equipment and performance A WARNING safety alert appears with information that is important for protecting you others and equipment from damage Pay very close attention to all warnings that apply to your application A This symbol an exclamation point in a triangle precedes a general CAUTION or WARNING statement AN This symbol a lightning bolt in a lightning bolt in a triangle precedes an electric shock hazard CAUTION or WARNING safety statement Technical Assistance If you encounter a problem with your Orion nCompass controller review all of your configuration information to verify that your selections are consistent with your application inputs outputs alarms limits etc If the problem persists after checking the above you can get technical assistance by dialing 1 866 342 5332 or by faxing your request
23. 9 3 f FuTUREDESIGN nCompass i4 3 N T R O 9 2 Degrees C F Units Selection nCompass can display temperatures in either degrees Centigrade or Fahrenheit To change the temperature display units select Units from the offline Set menu Units Select units of measure for temperature readings Centigrade E Fahrenheit Press the button for the desired temperature units to make the selection The choices are mutually exclusive so when one selection is made the other will be de selected NOTE When changing display units ramp soak program set points will not be converted between units Separate programs are required for each temperature range Operating nCompass with programs that have been written using alternate units could cause property damage or personal injury The temperature units selection only effects control loops and monitor inputs configured as temperature i e controllers or monitor input cards with a temperature input device such as a thermocouple or RTD The units display for loop controls and monitor input cards configured with linear inputs mA or Vdc will not be effected by this selection 9 4 FDC nCompass Offline Setup N T R O nCompass i4 3 f FuTUREDESIGN 9 3 Clock Settings The system date and time is adjusted from the Adjust Time tab under the Set Clock menu The current date and time will be displayed in the thumb wheels as shown below Time Options Daylight
24. Address 00 0A 05 01 46 EB IF Address 192 168 0 12 Subnet Mask 755 255 755 0 Default Gateway 192 168 0 1 DHCP Server 192 168 0 1 Lease Obtained 9 16 2009 10 19 55 Lease Expires Of17 2009 10 19 55 DNS Servers 168 95 1 1 WINS Servers Communications FDC nCompass 10 3 f FuTUReEDESsIGN N T R O nCompass i4 3 The MAC address is displayed as the first item Physical Address Once the address has been recorded close the network information windows and cycle power to nCompass in order to restart the system and return to normal operation 10 1 2 2 Setting a Static IP Address In order to set a static IP address for nCompass on a network it requires you to exit the nCompass application and enter the Network and Dial up Connections settings of the CE operating system IMPORTANT It is recommended that only personnel charged with configuring and maintaining nCompass perform this procedure Do not alter change or delete any other files or settings of the system Doing so may render nCompass inoperable To begin you must exit the nCompass application To do so proceed to the Exit Application screen under the offline setup menu Press the Exit and start runtime on next power up button to exit the nCompass runtime application Follow the on screen prompts to stop the application and exit to the Windows CE desktop System Startup Please Wait From the desktop touch the narrow gray bar at the
25. Defeat button on the Alarm screen Defeat Group DIG OUT 1 DIG OUT Z2 DIG OUT 3 DIG OUT 4 Return DIG OUT 5 DIG OUT 6 DIG OUT 7 DIG OUT amp Select which outputs are to be turned off when the alarm is active by pressing the toggle switch associated with the desired output s and press the Return button when finished If more than eight outputs are configured in the system the Group button will be shown Pressing the button will toggle between the first group of eight inputs and the second group of up to eight inputs allowing the user to set all outputs configured in the system 8 12 FDC nCompass Device Settings f FuTUReEDESIGN N T R O nCompass i4 3 8 4 Limits The set point Limits screen allows for the adjustment of the minimum and maximum operating set points allowed to be entered for the control loops These limits can be used to prevent operators from entering a value that exceeds the survivability limits of equipment or product being manufactured reducing the risk of property damage Limits Lower Limit 100 Upper Limit 100 Enter the desired set point limits by touching the Lower Limit and Upper Limit entry fields and enter the desired values using the numeric keypad IMPORTANT The minimum and maximum values for the set point limits are defined by the OEM or equipment installer limits set in the nCompass configuration nCompass prevents the user from entering set
26. Hot needed State Both sinking and sourcing input signals can be connected If any input exceeding the rated value is applied permanent damage may be caused 3m 9 84 ft in compliance with electromagnetic immunity MOLE 130 3 81 BK Phoenia Contact LOO times minirmumi Input intemal Circuit inpute WO 11 13 HE 16 and I7 Inputs 12 15 and DO te LiT EL Input COR we Sg Je mi D E itana Cou LO Usage Limits When using the HERAT GK DS at an ambient tem perature of EX in the normal mounting direction limit the inputs and outputs respectively which tum on simultansoushy on esch connector along line 1 When using amp Ar all 1 0 on every Slim type CPU madue can be turned on sirmulteneously at 26 Ay DC as indicated with line 31 Inpak itage LO O D DI GO TO D LAO Sbnult reeus GA Ralo Fei Loo APPENDIX d FUTUREDESION c O N T R O nCompass i4 3 Main CPU Output Specifications Relay Output Specifications CPU Module Ne of Outputs Out put Points per Common Line Maximam Load Curent Minimum Switching Load Initial Contact Resistance Electrical Life Mechanical Life Rated Lowe Dielectric Strength Connector on Mother Board S eae Connector Insertion Removal Durability output Delay OH Command OFF OH Output Raay Status CF EU ee delay Chatter FC SA D1i6RS1 S pants including 2 transistor output paints 2 ponts transistor source output 3 N
27. O O O CO All dimensions are in mm Tolerance 1 mm Panel cutout 123 x 997 DB9 Male Not Used LAN Ethernet RJ45 SD slot DB25 Female USB port Power supply Installation FDC nCompass 2 3 f FuTUReEDESIGN N T R O nCompass i4 3 2 3 2 nCompass Process Loop Controllers nCompass requires one PID loop controller for each process control loop required in the system Since nCompass is capable of interfacing to more than one brand of controller refer to the part number matrix for the operating system provided Refer to the operating manual for the brand and model loop control being used for dimensions appropriate mounting and operating conditions NOTE For systems using dual loop controllers such as the Honeywell UDC3500 brand control each controller provides two loops of control Therefore only one controller can be used with nCompass providing a maximum of two loops of control For applications requiring several loops of control proper planning and arrangement of the process controllers prior to mounting is critical for optimum routing of the controller wiring For applications requiring frequent access to the process controllers panel mounting provides direct access to the controllers For applications where operator access to the controllers is not required or is desired to be kept at a minimum the controllers can be mounted directly inside of an enclosure This also reduces wiring concerns by eliminating the need
28. Once the selection is made press the Copy Delete button All related files will be copied to the USB memory stick and then deleted from nCompass with progress status displayed to user The Import file function allows automatic ramp soak program files to be copied from the USB memory device to nCompass A dialog box will appear listing the available program directories on the USB memory stick Program directory names exported from nCompass are in the format Profiles_mm_dd_yyyy hh_mm_ss NOTE The USB memory stick must be inserted into the USB port for any of the file utility operations to function It is recommended to only use memory sticks certified by Future Design Controls for use with nCompass Future Design Controls has tested and validated these memory devices for proper operation and performance Due to manufacturing variations in the USB memory sticks it may take from a few seconds up to 30 seconds for nCompass to recognize the device when it is plugged in Allow sufficient time for the device to be recognized before attempting any file utility operations or nCompass will indicate a file transfer memory stick error When files are being copied to the USB storage device a directory for each file type will be created to store the copied files The directory structure is as follows Program files directory Profiles_mm_dd_yyyy hh_mm_ss Alarm files directory Alarm Files_mm_dd_yyyy hh_mm_ss Audit files directory Audit Files_
29. Refer to the documentation provided by your OEM regarding any loop control and monitor point setup Note that prior to entering offline setup ramp soak program operation and data logging must be manually stopped When in offline mode all nCompass digital and analog outputs will be turned off To assist in setup and documentation of nCompass see the Orion M iSeries Configuration and Worksheets Excel file provided on the Future Design Controls website http www futuredesigncontrols com Orion M htm This document provides setup and configuration forms and templates for all nCompass features including those provided under Offline Setup The offline menu provides navigation to the following functions System Calibrate Language View J Settings View menu Settings Navigation back to the online settings menu Set i i SE l Service View output operational data cycles hours on Hardware OPtions Options Settings for system output maintenance data Calibrate System Set menu Units Setting for temperature units Clock Settings for system date and time Hardware Language Settings for menu and help language text View Analog Input Hardware menu Analog Output Analog Input Settings for optional analog input operation Set Dia Analog Output Settings for optional analog output operation Digital Input S e TEEI bicital Outout Digital Input Settings for digit
30. T R O nCompass i4 3 fil In order to connect the barcode scanner to nCompass an optional RS232 communications card FC4A SIF2 is required However this must be the second communications card on the control module The first communications card supports the optional user communications FC5A SIF2 or SIF4 The second card is assigned to support the barcode reader Thus if the optional user communications are not required the card must still be installed in order to use the barcode scanner A ial Ee ze eg A vs od ae DBS Male Connector to Barcode Scanner RS23 2 Interface Pl DDDDODEDDDOD User Communications Card Required for Scanner Use Barcode Scanner Communications Card D Sub 9 pin Male Gonnector Pinouts FC4A SIF2 Connector Terminals Description L Dn Terminal Description RXD Receve Data Clear to Send THO Send Data 3 e EEL Data RTS Regquestto Ge rid CTS Clear to Send RI Ring Indicato To connect to the RS232 interface of the barcode scanner a DB9 male connector must be wired as shown The connection only requires three of the 9 available pins on a standard DB9 connection NOTE Even though the barcode scanner is connected to nCompass if its communication parameters are not set properly the scanner will not operate correctly See Section 8 5 Barcode Scanner Setup Wiring FDC nCompass 3 15 P 3 6 4 Optional Digital Input Expansion Card Wiring FUTUREDESION c O N T R O
31. The IP Address field is a static field that provides the IP address of nCompass which is required for connecting over the VNC and web server interfaces For more information on Device IP and other LAN information refer to Section 10 Communications NOTE Any changes made to the above settings must be saved in order for them to take affect When changes are completed press the Save button and then cycle power to nCompass The new settings will only take affect when nCompass first boots up Device Settings FDC nCompass 8 17 f FuTUREDESIGN nCompass i4 3 N T R O 8 9 Barcode Reader The Barcode screen provides access to the settings for the optional barcode reader These include settings to turn the barcode reader on and off applying a prefix to scanned data and a test window for verifying proper operation Barcode Prefix Bar Code Test Scott Barcode reader operation is enabled through the Start the automatic program and Annotation on off buttons The selections are mutually exclusive i e only one can be enabled at a time When one option is turned on the other is automatically turned off When the Start the automatic program option is turned on if the scanned data matches the name of a ramp soak program stored in memory nCompass will automatically load the program and prompt the user to Start it If the user presses Yes to start the program it will be downloaded to the CM and will begin operation
32. There are internet sites with this information that cover most of the providers or when in doubt contact your service provider for the proper address format i SMS Address to use where 0123456789 is an Cell Phone Provider Maximum message length ee example for a 10 digit cell phone number AT amp T 160 characters 0123456789 txt att net Nextel now part of Sprint Nextel 140 characters 0123456789 messaging nextel com C 1 L zmgescs Device Settings FDC nCompass 8 21 f FuTUReEDESIGN N T R O nCompass i4 3 8 10 2 Email Addresses Selecting the Addresses tab allows the user to view the list of email addresses entered in nCompass Each entry will be shown with the notification method and address associated with it email SMS To delete a user touch the name of the user in the list box and press the Delete button This will permanently remove the user from the list Bill Smith Email On Alarm smithiroyconpany com SMS On Alarm 01234567890phone com 8 10 3 Email Settings The Settings tab provides access to the email server configuration which is how nCompass is able to connect and send email messages over its Ethernet connection Each field may have up to 50 characters New Addresses Settings Login Return Address nlompass mycompany com Password SMTP Address mailaimycompany Subject ncompass Alarm Message The Login field is used to enter the login name required b
33. This allows the analog input configuration to be maintained but disable its operation until it is required Select None to prevent the analog input from taking set point control over the selected loop Press the SP button to enable the analog input set point control override Once all settings have been made press the Save button to save the changes If you do not press the Save button all changes will be lost if you leave the screen or navigate to another analog input 9 5 1 Remote Set Point Operation Once an input is configured for loop set point control as the analog input signal is varied it will provide a linear set point change from the minimum to maximum value over the range of the input 2 10Vdc for voltage input and 4 20mA for current selection Signals below 2Vdc for the voltage input type and below 4mA for the current input type will disable remote set point control so that the loop set point can be changed manually at nCompass It also prevents the remote set point control from setting a false input if the signal wires are cut or the signal is lost from the remote set point source device NOTE When remote set point control is activated it will override the local set point as well as the ramp soak program set point if a program is running Once deactivated the loop set point will return to the previous local set point of the loop i e the value prior to the remote set point being activated and taking
34. and operator audit trial files File transfer via LAN features or USB flash memory Support View loop amp digital IO status force loop amp digital outputs and more LAN Remote Access amp touch screen operation VNC email SMS on alarm email historical alarm amp audit trail files on demand Web Page view only and FTP of alarm audit and historical data files automatically or on demand Data Acquisition Data log up to 3 control loops PV SP amp out and up to 15 optional Monitor Point PVs up to 18 PV inputs in all Log interval configurable 2 seconds to 31 minutes with configurable number of days to auto start amp name next file 1 to 31 days File Start Stop Configurable operator on demand on system boot automatic program start end or digital inputs File Interval Once started a data log file is configurable to auto end and start new file with the same name as previous file with an appended time date name Configurable time interval is from 1 to 31 days File name Operator entered file name batch amp lot number or if running an automatic program file name same as program name all file names appended with date time to file name Operator Comments Events Unlimited operator comments events linked to each file entered manually or via Bar Code Scanner Digital Signatures full support for user based digital signatures for each data file data encryption Historical Data File View
35. arrows will appear on screens that provide list views in E S order to scroll up and down through items of the list List views also provide touch sliding like other modern smart devices NOTE A single press of the left right or up down arrows will scroll list views to the next list item program steps to the next step or screens to the next available loop or chart Pressing and holding the arrow keys will continue the item scrolling until the end of the list is reached or the button is released 4 2 FDC nCompass nCompass ia3 ff eurupenesron N T R O IMPORTANT Do not use any sharp or metal objects on the touch screen as they may damage the surface Also be sure that hands and fingers are free from oils or chemicals which may mar the surface of the touch screen 4 3 Menu Navigation nCompass provides the user with the ability to select text based menu navigation much like the typical file menu system of a PC as well as an icon based navigation system like that of a smart device The user can switch back and forth between the two from the Setup menu Program Device gt alarm File Security vi Digital Data Events Touch and drag finger across screen to switch between menu pages Active Page Indicator 1 of 3 Icon Based Slide Page Navigation The available menu items are dependant upon the OEM configuration of nCompass Not all of the menu items shown may be available on your system The foll
36. as the enable point the process value must be equal to or below the defrost enable set point Once the user set interval has elapsed the defrost cycle begins When the defrost cycle starts the OEM configured output defeats will be activated This will turn off all outputs configured for defeat regardless of any other settings If a digital output is configured as a Defrost Output the output will be turned on for the duration of the defrost cycle Once the user set defrost duration has elapsed the defrost cycle will be terminated and the fan delay will be activated During the fan delay period the defrost output defeats are removed and the OEM configured precool output defeats are activated If a digital output is configured as a Defrost Precool Output the output will be turned on for the fan delay period Once the fan delay period has expired the precool output defeats are removed allowing all outputs to return to normal function The system will continue to run normally until the interval timer elapses once more and the cycle begins again If at any time the user presses the Demand Defrost button the interval timer will be reset and a single defrost cycle will be initiated Note that if defrost is configured for timed process pressing the Demand Defrost button will only initiate a defrost cycle if the OEM configured loop or monitor point is also below the enable set point that is entered in the nCompass configurator NOTE If redundant sys
37. back and forth according to the minutes of operation defined by this field Valid entry is in the range of 0 32767 minutes If a value of O is entered the alternating timer will not operate The interval must have a value of 1 32767 in order for alternate switching to take place Device Settings FDC nCompass 8 5 f FuTUReEDESIGN N T R O nCompass i4 3 8 2 1 Concurrent Redundancy Switching When redundancy is active OEM configured enable output s on any digital outputs configured for Redundant System 1 or Redundant System 2 that correspond with the selected primary system will be turned on The opposing system then becomes the backup system by default When the redundancy process alarm exists nCompass will run the backup system concurrently with the primary system until the minimum concurrent run timer expires or until the process alarm condition no longer exists If the redundancy alarm is set for latching the user must press the alarm reset button on the main alarm screen to acknowledge the alarm in order for it to clear The backup system will then shut down automatically after the minimum time period user defined expires if the process alarm no longer exists The user can switch from Auto to Manual at any time and select the primary system or run a single system in manual mode 8 2 2 Alternating Redundancy Switching When redundancy is active OEM configured enable output s on any digital output
38. backup to the FTP site Note that if data logging is currently active the active file will not be deleted Once all settings have been made press the Save button to save the settings so that on the next power up the entries will be maintained The Start button can be used at any time to perform a manual data backup If the files already exist on the FTP site they will be overwritten on each subsequent backup If the FTP site is down or nCompass is not connected to the network a local alarm message on the Alarm screen will indicate a transmission failure NOTE Typically FTP Server software uses case sensitive alpha numeric characters for the User name Password and Server directory Contact your network administrator for proper settings 7 6 Annotation The Annotation screen allows the user to add a messages to the running data file and view any messages currently associated with a loaded historical data file Annotation REMOVE BATCH 567 Lf1 f2013 1 38 PM User MARE LAMBERT ADD BATCH 568 1 17 2013 1 59 PM User MARK LAMBERT When a historical data file is loaded the Annotation screen will display any messages that were written to the file The date time user name and description of the data file annotation is shown Note that the currently running data log file can be opened as a historical data file and the current annotations for the running file will be shown To add an annotation to the running log fil
39. bottom of the screen to show the taskbar Before proceeding any further enable the CE keyboard so that it will be available to enter in the IP address If you do not enable it now you will not be able to access the taskbar later once in the Ethernet Drivers screen System Startup Please Wait Keyboard LargeKB ie 7 35 PM Keyboard Icon 10 4 FDC nCompass Communications FUTUREDESION N T R O nCompass i4 3 fil To enable the keyboard touch the keyboard icon at the lower right of the taskbar and select Keyboard from the menu This will make the keypad visible Next press the Windows Start button and select Settings and then Network and Dial up Connections to show the connections window System Startup Please Wait Make New DMOISA1 Connection e Programs d se Favorites d J E Documents DD STEET GEREIEIEEEENENENCHSESEH E Settings d Control Panel tl yluli folie Tab q wle ritlylulijolpi ti cun amp rik and Dialup Connections AE ECHT caPlalslalflalhlilkl11 Shift oi Taskbar and Start Menu ift z x c v bjn m F CED ET l OI ESE From the Connection window select the current network connection by double tapping the connection icon to enter its property window DO NOT create a new connection The Ethernet Drivers property window will allow you to set the IP address as well as name primary and secondary DNS and WINS servers from the Name Servers ta
40. communications port This allows all loop controls to be connected using one 2 wire link The controllers are wired in parallel with each one having a unique address from 1 to 3 corresponding to loop controllers 1 3 See the corresponding FDC Orion M controller configuration guide for the brand and model of loop control used Each loop control must be configured with the proper communications settings prior to use with nCompass NOTE Refer to loop control s operating manual for proper power communications and sensor connections it is important to keep the power control and sensor communications wiring separated from one another Relay and or high voltage outputs can interfere with the sensor and communication wiring as they cycle on and off which could erroneous sensor readings or communications errors 3 4 1 Communications Wiring Communications wiring must be run using a minimum of 24 AWG twisted pair copper conductors For short runs lt 50 feet total non shielded wiring can be used as long as proper separation from power control conductors is maintained For communications wiring where the total length will exceed 50 feet up to the maximum allowed length of 650 feet shielded twisted pair must be used When using shielded twisted pair be sure to ground only when end of the cable preferably at the control module Allowing any other portion of the cable shield to come in contact with ground or grounding both ends will Cause ground l
41. copy paste step USB Data Utilities USB allows USB memory stick to copy delete data alarm program amp audit trail files amp to import programs Event Names Device Settings Email Email Settings configure email settings and addresses Device Settings Email Message access to compose amp send email message Device Settings Offline access to Off Line menu system Service items amp Options Units set Clock Calibrate Touch Language Email Settings Email Message Offline Device Settings Set Event configure event tagnames seen in manual Events amp program step Events Exit To Application monitor Offset Configuration Analog Input amp Output Setup Digital Input amp Output Setup Digital Input Monitor amp Digital Output Force FTP WAN Data Utilities FTP WAN configure FTP client settings Device Settings Comms Comms configure web page Modbus address amp VNC settings Device Settings Comms Barcode applies to all barcode reader settings Defrost Device Settings View Defrost applies to defrost interval duration and fan delay time settings Start Thaw Device Settings View Defrost access to manually initiate a defrost cycle Defrost button Redundancy Device Settings View Redundancy applies to primary system selection redundancy operating mode and alternate concurrent time settings Load Timer Device Settings View Redundancy access to active redundancy product load timer Load Timer button Setpoint Limits Device Settin
42. damage or malfunction of the device When handling the nCompass B41 42 series loop control boards use proper ESD electro static discharge handling procedures to prevent damage to board components Locate nCompass and all related control components away from AC power motor wiring and sources of direct heat output such as transformers heaters or large capacity resistors 2 1 Enclosure Guidelines nCompass must be installed correctly for reliable operation The nCompass controller is designed for installation within a suitable enclosure Do not install nNCompass outside of an enclosure Care must be taken when locating components to ensure that AC power wiring contactors starters relays and other sources of electrical interference are properly located to minimize their impact on the nCompass control system Particular note should be taken to the position of variable speed drives and switching power supplies Their input and load cables should be screened and properly grounded to a central equipment grounding point to prevent radiated emissions from affecting nCompass operation Installation FDC nCompass 2 1 f FuTUREDESIGN nCompass ia3 N T R O 2 1 1 Locating the nCompass Touch Screen Interface It is recommended that the unit be mounted to the front panel of a steel enclosure through an appropriately sized opening Proper enclosure depth is required to insure that there is adequate spacing between the rear of the interface a
43. each When a file name is specified the file will be saved as FileName_mm_dd_yyyy_hh_mm_ss Data Data Lengthidays Secs 60 File Name IDF 1 7 2 FDC nCompass Data Logging nCompass ia3 ff eurupenesron N T R O The data logger also provides two entry fields ID 1 and ID 2 which allow the user to enter in information specific to the file such as a batch and or lot number to identify product that may be associated with the new data file These entries will be saved with the data log file for later identification The Length days field sets the length of a data file in number of days It can be set for 1 to 31 days Once the selected number of days has elapsed a new data file will be created and logging will continue in the new file The Interval secs field is used to set the rate at which points are written to the log file which equates to the sample rate in seconds When the Fixed Interval option is turned on the logging interval will be automatically set to record at minute intervals based on the number of days set for the file If the file is set for 1 day in length the logging rate will be at 1 minute intervals If the file is set for 7 days then the logging rate will be every 7 minutes This keeps the data file size manageable and able to be viewed by the nCompass data viewer The log interval can be manually set to any rate between 2 and 1860 seconds in any combination with the number of days befor
44. in ramp soak program operation When a process variable deviates from its set point by more than its soak limit value the program timer will stop until the process variable re enters the soak band These limits apply to every step in the program and only need to be set once LOOF 1 Soak SP OC LOOP 2 Soak SP 0 RH LOOP 3 Soak SP 0C To change a limit select the desired loop from the list and press the Edit button Enter the new limit setting on the numeric keypad and press Done when finished The new limit value will then be shown in the list view for the selected control loop NOTE If soak limit is set too tight i e a very small deviation value from set point it could prevent the program from operating as desired because the process may not be able to be controlled to such a tight limit setting Automatic Program Operation FDC nCompass 5 9 FUTUREDESIGN nCompass i4 3 P 5 2 Starting an Automatic Ramp Soak Program In order to start a ramp soak program it must first be loaded into the nCompass control module In order to do this you must select Start from the Program menu Cycle Count 0 Start ee Hold he aa Im The screen will automatically change to the Start screen By default a program will always start on step 1 If you wish to start the program on a different step press the start step field and enter the desired start step or use the left and right scroll buttons to adjus
45. in the event that the redundancy alarm was due to a frozen evaporator 8 2 3 2 After Defrost Switching After defrost operation provides equal run time switching based on the user defined alternating switch interval When OEM configured for After Defrost and no redundancy alarm condition exists a defrost cycle will be forced at each system switch time when timed defrost is configured If defrost is configured for timed process a defrost cycle will be forced at system switch only if required based on the condition of the loop or monitor point configured Normal defrost cycles will take place based on timed or timed process settings since the equal run time switching is typically longer than the system should run without a defrost cycle lf a defrost cycle is running and the equal run time switching timer has elapsed the defrost cycle will be completed then the primary systems will switch If a redundancy alarm condition exists process alarm system 1 2 fail defrost cycles will be performed under fail mode operation based on timed or timed process settings Pressing the demand Defrost button will perform a single defrost cycle based on defrost settings during normal switching or fail mode conditions Primary systems and actual system digital outputs 1 2 will only switch when no redundancy alarm conditions exist and concurrent operation is not active 8 2 4 System 1 2 Failure If a system 1 2 failure occurs on alternating o
46. more information When selected the input will cause digital outputs selected under Defeat to turn off The operation is similar to the alarm input function but no alarm message Is displayed FDC nCompass 9 13 Start Data Halt Setpoint Control Reset Alarm Defeat Input Halt Defrost Load Timer NOTE IMPORTANT 9 14 f FuTUREDESIGN nCompass i4 3 N T R O When selected the input will start and stop the data logging operation of nCompass When selected the input will disable set point communications from the nCompass control module to all loop controls attached to the system This allows for direct manual adjustment of the loop set point s on the process controllers The input acts as a manual override but still allows nCompass to gather process data for proper display and data logging purposes When activated the loop set point on nCompass will reflect the set point of the loop control as long as the loop is not under ramp soak program control If a change is made to the set point at the loop control the new set point will be updated on nCompass lf a ramp soak program is operating the set point indicated on nCompass will remain at the value as defined by the running program even though it is not being sent to the loop controller If the program is put into hold however the set point on nCompass will match that on the loop control since the loop set point change at nCompass is allowed
47. nCompass i4 3 NOTE The following information covers basic input connection information for the nCompass digital input expansion cards Since nCompass is a fully configurable control system the use of each input is dependant upon the application therefore the input control devices and real world connections are determined by the system designer FC4A NO8B1 8 point DC Input Module Screw Terminal Type Applicable Terminal Block FC4A PMT LP supplied with the input module Source Input Wiring Sink Input Wiring Sire Sensor Terminal No wire Sensor Terminal No kA S THE NPN T 24V DC pay De Two COM terminals are interconnected Slate tale teas E IE i ke ht FC4ANOS8A11 point AC Input Module Screw Terminal Type Applicable Terminal Block FC4A PMT11P supplied with the input module Temninal No Output E E CH X CoMo COMO Two COM terminals are nat interconnected Do not connect an external load to the input terminals 3 16 FDC nCompass Wiring f FUTUREDESICN N T R O nCompass i4 3 Expansion Digital Input Assignments 130 Digital Input 9 function determined by nCompass configuration 131 Digital Input 10 function determined by nCompass configuration 132 Digital Input 11 function determined by nCompass configuration 133 Digital Input 12 function determined by nCompass configuration 134 Digital Input 13 function determined b
48. navigate through the various operation monitor and setup screens and learn how to use them Subsequent sections of this manual are tailored to the special features and functions of nCompass Consult those sections of the manual for further information and specifics on how to set up and operate them 4 1 OEM Configuration Options The availability of certain menu items screens and the functionality of nCompass are determined by the configuration of the controller This manual covers all available options some of which may not be available on your system If there are questions or concerns about the operation and available options on your nCompass controller contact your OEM for further information Only your OEM can address equipment related issues 4 1 1 OEM Control Loop Configuration Options nCompass provides the OEM with special loop configuration options that can affect user interaction with the control loops It is important for the end user to note that these special loop modes exist in case they are present on your controller and understand their operation to avoid confusion when operating the equipment 4 1 1 1 Cascade Control Loop Mode lf a loop is configured for cascade control it may appear as a normal control loop on nCompass however this type of loop is operated by another control loop on nCompass The set point of the cascade loop can not be changed by the user It is a calculated set point generated by the other control loop
49. on a step the program will first execute the step as a normal step however once the step time is complete the program will jump to the specified jump step rather than continuing on to the next step After all of the programmed jumps have been completed the program will then continue to the next sequential step in the program without making any further jumps To program a jump enter the step number that you want the program to jump to when the step is complete along with the total number of times the jump is to be made A cycle count of zero on a step indicates that no jump will be made once the step is complete regardless of what the jump step number is set to Jump to Step Sets the step number that the program will jump to upon the completion of the step The jump will only occur if the cycle count is greater than zero The step number can be a previous step number in order to cycle back to a previous portion of the program or it can be set to make the program skips steps by jumping further ahead in the program Cycle Count Sets the number of jumps that will be made from the step Once all jumps have been made the program will continue on to the next step in sequential order Jumps are disabled on the step when the cycle count is zero nCompass will ignore the jump step so it does not have to be set It can be left at its default value of one NOTE The cycle count defines how many jumps will be made Thus if you wish to perform
50. password at any time even if aging is not used by selecting Password from the main security menu When enabled Verification requires that the logged in user must log in again before the process value will actually be changed Audit is a global setting that turns the audit trail on or off When the audit trail is turned on all user actions are written to a daily log Security is the global setting that turns the nCompass security system on or off The security system must be enabled for the audit trail to be enabled 6 6 FDC nCompass Security nCompass ia3 ff eurupenesron N T R O 6 5 Audit Trail The audit trail viewer is accessed by selecting Audit from the Security menu It displays all user actions that affected the system for any given day nCompass can store daily audit files for a period of a year or longer time based on storage usage for data history Each time a user take an action that affect the operation of the system changing a set point start stop data logging changes an alarm set point etc the action is written to a file Audit trail file names are listed as month_day_year The Open file button will display a dialog box where the user can select any audit file to view NOTE _ If no actions occurred on a given day an audit file will not be created for that day Audit File Interval secs From 60 To 7 Device Manager LfiFf2013 1 07 PM Data file start Device Manager LiF f2013 1 07 PM D
51. power p al Turn off after 1 minute of continuous idle time Advanced The brightness of the display during operation is set by adjusting the ON slider The default setting is 100 The OFF slider is used to adjust the brightness of the display during periods of inactivity The default setting is 10 Note that a setting of zero 0 does not completely turn off the backlight Timer ON 100 OFF 16 Ji Automatically tum off backlight To enable the backlight dimming function place a check in the Automatically turn off backlight checkbox and set the delay time using the drop down selection box The delay time can be set at fixed intervals from as little as 15 seconds to as long as 30 minutes Once all settings are complete press the OK button and then press the OK button at the top right of the Display Properties window to return to the nCompass application and begin normal operation 9 13 Configuration The Configuration utility allows the user to back up the entire configuration of NCompass and save it to a file for safe keeping in case of system damage due to a lightning strike etc The utility also allows nCompass to be configured with a push of a button by selecting from a list of preconfigured setups that could be created and saved on a USB memory device for loading a configuration to a new nCompass system IMPORTANT Do not import configuration files that are not inten
52. restart the system and return to normal operation with the new network settings NOTE The text System Startup Please Wait on the desktop is static and does not indicate that any application is going to start at this time It is used as a placeholder prior to the nCompass runtime or configuration application starting during normal power up sequences so that the user is informed that an action is taking place Communications FDC nCompass 10 5 f FuTUReEDESIGN N T R O nCompass i4 3 10 1 3 Using the Web Server The nCompass web server allows a user to remotely monitor operations anywhere via a PC s standard web browser When enabled the web server provides a detailed status page of the current operating conditions The web server can be enabled and disabled by pressing the Web Server button on the communications screen under the Comms setup menu You must use the assigned IP address to access nCompass The IP address is shown on the communications screen and is also included in the notifications list Write down the IP address so you will have it later to enter into your web browser Modbus Address YNE Address Pswrd None YC Device Name nCompass YNE Password IP Address 192 168 0 6 gemeng ST NOTE Contact your network administrator prior to enabling the web server of nCompass Company policy may prohibit the use of web servers for security reasons Future Design is not responsible fo
53. starts again Guaranteed soak is primarily used on soak steps to make sure that the process stays at the desired set point within the soak banad for the full time duration of the step 5 1 2 Setting Step Set Points and Ramp Rate Dwell Time Ramp Rate Option When the ramp rate configuration is selected the rate of change for the control loop set points is specified as a change in units hour A single set point is then entered which is applied to all control loops and is used as the target set point for the step i e the set point that each control loop will arrive at by the end of the step If the user enters a set point that matches the set point of the previous step the ramp rate field will be hidden and the dwell time fields for Hours and Minutes will be shown This allows the user to create a dwell step in which all loops will remain at set point for the time entered NOTE A ramp rate of zero can be entered for a step to implement an immediate set point change Step 1 is always a ramp step as there is no preceding step to compare the set point entry with S1 Step Data Reun Si Step Data Return o Rate Unit Hour Hour Minute o Control SP 25 Control SP OFF Meh OFF Soak OFF Soak Ramp Rate Step Entry Dwell Step Entry 5 1 3 Setting Step Events For each step of the program the user can select which events are to be on during the step To edit step events press the Events button on the program En
54. the Out Min field to 0 and the Out Max field to 100 will produce an analog output of 0 10Vdc or 4 20mA for an output of 0 to 100 cooling If a model of controller is used that represents cooling as 50 to 0 while heating is represented as 50 to 100 setting an Out Min to Out Max range of 50 to 0 will result in an analog output of 0 10Vdc or 4 20mA for an output of 0 to 100 of the cool output NOTE The analog outputs always treat the Out Min field as the OVdc or 4mA output value and the Out Max field as the 10Vdc or 20mA output value This allows any portion of a control loop s output range to be retransmitted and represented as a range of 0 to 100 of output or 100 to 0 of output Offline Setup FDC nCompass 9 11 f FuTUReEDESIGN N T R O nCompass i4 3 9 7 Digital Inputs nCompass provides eight digital inputs standard and is configurable up to 16 The inputs can be used as alarm inputs used to start and stop a ramp soak program start and stop data logging or even disable set point communications to the nCompass loop controllers The digital inputs can be configured to work on either a low to high transition or a high to low transition Upon seeing the selected transition the input will perform the action selected from the input function list Function Transition Delay seconds The left and right navigation buttons at the upper right of the screen allow the user to sc
55. the IP address for nCompass be assigned as a fixed static address This insures that the address will not change once it has been set This can be done in one of two ways The first is by setting up the control LAN router to assign the same IP address whenever it detects the nCompass device on the network via its own identifier its MAC address The other option is to configure nCompass to use a fixed IP address and disable the DHCP addressing function of its network interface When using this method it is important to make sure that the address being assigned to nCompass is not used by any other device on the network If another device is using the same address the VNC and web server interfaces will not function correctly It is recommended that this method of static IP assignment be used as it removes the IP address lease renewal process that would be performed by the control LAN router if DHCP was used The lease renewal process performed by the control LAN router can cause the VNC server in nCompass to shut down due to an issue in the renewal process It could be caused by something in the router firmware or configuration of the router itself Due to the numerous brands and models of routers available and the dynamic nature of their use attempting to resolve the issue is beyond the scope of this manual Therefore the use of static IP addressing removes this from the equation providing the most robust network solution 10 1 2 1 Obtaining the n
56. the chart plots a new point is based on the time period to be shown Each buffer can hold a total of 720 readings for each of the selected channels to plot The update rate can be calculated by the formula time period in minutes 60 720 Note that for time periods less than 72 minutes the update rate will be held to a minimum of 6 seconds Thus the update rate will vary from a minimum of 6 seconds for time periods of 72 minutes or less up to a maximum of 120 seconds for 1440 minutes 24 hours Chart 1 Sy Frges The Labels button allows the user to cycle through each of the configured plot channels to determine what each colored plot represents as well as view the current value without having to return to the Single or Dual view screens The left and right scroll buttons at the upper right of the screen allow the user to cycle through each of the four available charts The charts also allow you to zoom in on a particular area to have a more detailed look at current data By using your finger to select an area on the screen the chart will zoom in on that area To select a portion of the plot touch and hold the screen with your finger Drag your finger across the graph and a box will be drawn around the selected area Removing your finger from the screen will cause the chart to redraw with only the selected plot area To return to the normal view touch the X or Y axis and select zoom out to return to the previous zoom se
57. the control or erroneous network activity could cause connection problems over the VNC interface and result in the VNC server shutting down and requiring nCompass to be restarted in order to regain access NOTE Some viewers may also contain additional features for file transfer and other high level functions These functions are NOT compatible with nCompass Any attempt to use them may cause the nCompass VNC server to malfunction and require power to be cycled in order to reboot the system All viewers should be used ONLY to monitor and manipulate nCompass as if you were standing directly in front of it 10 12 FDC nCompass Communications nCompass ia3 ff eurupenesron N T R O 10 2 Serial Communications Option The nCompass optional serial interface uses Modbus RTU protocol Any device used to communicate with nCompass over the serial interface must use this protocol Modbus Address YNE Address Pswrd None YNE Device Name nCompass YNE Password IP Address 192 168 0 6 a VNC The nCompass communication address can be set on the communications screen All other communication settings are fixed The serial port settings of the device used to communicate with nCompass must be set to match in order for the communications to take place Address 1 31 user selectable Baud Rate 9600 Data Bits 8 Stop Bits 1 Parity Even Timeout 1 second The address is used to identify nCompass on the serial link When a multi drop connecti
58. the desired control loop and press the Return button to return to the Analog Output screen Source a OFF LOOP 2 OFF LOOP 3 9 10 FDC nCompass Offline Setup nCompass ia3 ff eurupenesron N T R O Choose which loop value is to be retransmitted for the loop by pressing the appropriate function select button PV SP or Out If None is selected the output will remain in the off state i e OVdc or 4mA depending upon the output type selection Enter the minimum and maximum values for which the output is to retransmit The output range is 32760 to 32760 for a decimal point resolution of zero 3276 0 to 3276 0 for a decimal point of one 327 60 to 327 60 for a decimal point of two and 32 760 to 32 760 for a decimal point resolution of three Once all settings have been made press the Save button to save the changes If you do not press the Save button all changes will be lost if you leave the screen or navigate to another analog output 9 6 1 Retransmitting Loop Percentage of Output Depending upon the loop control being used the percentage of output value for bimodal control heat cool is represented differently For example FDC 100 and 300 series controls represent heat output as a value from 0 to 100 while the cool output is represented as a value from 0 to 100 Other controls supported by nCompass may split the standard 0 to 100 range and use 50 to 100 for heating and 50 to 0 for cooling
59. the historical data file as well as select up to six channels of data to plot To edit the settings for the historical plot select Set from the Chart menu EE LOOP 1 SP Oon LOOP 1 Out Aale w IRCH Jent2en Any point from the data file can be selected along with the vertical axis to be used for each channel to be plotted Select channels from the list by turning them on or off and use the Left and Right axis buttons to assign the selected item to the left or right axis for the plot range To adjust the period of time to plot from the data file press the Time button File start end Return The start and end dates for the currently loaded file will be shown with time in hours minutes and seconds The File Date Start and File Date End sliders are used to select a time span for historical viewing Once the desired start and end times have been set press the Return button to return to the Chart Settings screen ZA FDC nCompass Data Logging FUTUREDESION c O N T R O nCompass i4 3 f 7 3 2 Plotting Historical Data The history Chart plots the data from the currently opened history file according to the selections made under chart setup If a file has not been opened or data points have not been assigned to a plot nCompass will alert the user to correct the problem The X and Y axis scales are set to auto scale based on current values for each plot channe
60. the loop and monitor inputs When an alarm condition occurs the alarm icon flashes in the nCompass icon bar to provide a visual indication of an alarm condition NOTE The alarm settings for digital inputs and loop monitor alarms are determined by the system designer For information on how to program digital inputs as alarms see section 9 11 on Digital Inputs For information on loop monitor alarm operation see Section 8 4 Alarm Settings 4 8 1 Alarm Monitor The Alarms screen is accessed from the home View menu It can also be displayed by pressing the alarm icon whenever a new alarm occurs It displays all current and or previously acknowledged alarms according to time and date of occurrence Once the alarm is reset the alarm icon will be hidden however the alarm condition may still be present The alarm will only leave the list when cleared by the operator by pressing the Clear button Only alarms that are not currently active in the system can be cleared from the alarm list Basic Operation FDC nCompass 4 21 f FUTUREDESICN N T R O nCompass i4 3 4 8 2 Alarm File The Alarm File screen is accessed from the home View menu It displays all alarms for any given day nCompass can store daily alarm files for a period of a year or longer time based on storage usage for data history Each time an alarm occurs on nCompass the alarm is written to a file Alarm file names are listed as month_day_year The O
61. the optional serial communications interface Valid addresses are 1 to 31 The VNC Address and Password set access rights to the nCompass VNC server Valid addresses are from 0 to 255 The VNC password selection defines the connection mode for the server The selections are None and VncAuth which requires users to enter the password when connecting to nCompass over the VNC interface IMPORTANT When multiple nCompass controllers are connected to a single router DHCP server it is imperative that each nCompass have a different VNC address If multiple nCompass controllers have the same VNC address network errors may result causing the VNC server to shut down or cause nCompass to lock up and become non responsive requiring the unit to be power cycled in order to return to normal operation The VNC Device Name field is used to enter a name up to 35 characters that can better identify nCompass to users logged into the VNC interface The name entered here will be used on the VNC header window on a PC so that if multiple VNC clients are open to different systems each one can be identified The VNC Password field is used to enter the password up to 20 characters that a user must enter for the VNC interface to connect to nCompass if the VNC password is enabled The Www web server pushbutton is used to enable or disable the web server interface The VNC server pushbutton is used to enable or disable the VNC server interface
62. to add up to 30 users to the system Select the type of user from the drop down list System User Supervisor or Administrator Press each field to add the user ID full name and password no spaces allowed 5 character minimum and 16 characters maximum Press the Create button to add the user to the system If the passwords do not match or the user ID is already used nCompass will alert the user and not accept the entry New Users Access Options User ID NWame MLAMBEF T MARK LAMBERT Password Contirm Password 6 2 Viewing Users The Users tab provides the administrator with the ability to view information on each user entered into the system Password information is not available The user can be deleted from this tab and a new password for each user can also be entered from this area New Users Access Options MARK LAMBERT MLAMBERT ser Updated Or 1 17 2013 GROSSMORE GROSSMORE Administrator Updated Or 1 17 2013 To delete a user select the user from the list and press the Delete button Likewise to change the password for a user select the user from the list and press the Password button 6 2 FDC nCompass Security f FuTUReEDESIGN N T R O nCompass i4 3 6 2 1 New Password Entry To change a password select the desired user by touching the User ID in the list box and press the New Password button Enter the new password and confirm the password Pres
63. user takes action Process must reach or exceed wait for setpoint The digital input selections are made by pressing Digital button on the Wait For screen When using the digital input wait for selection the digital input must be configured as a wait for event input If it is not configured as a wait for event input the program will ignore that input when the wait for step is executed and continue through the step as normal See section 9 11 on the offline setup of Digital Inputs for information on setting the digital input function 5 6 FDC nCompass Automatic Program Operation FUTUREDESION N T R O nCompass i4 3 Digital DIG IN 1 DIG IN 3 DIGINS DIG IN lf more than 8 digital inputs are configured in the system the Group button will be shown Pressing this button will toggle between the first 8 and second group of up to 8 inputs so that all available inputs can be edited for the step When all entries have been made press the Return button to return to the Entry screen NOTE If no digital inputs are configured in the system the Analog and Digital button selections will not be shown and the normal icon bar will be visible as there are no inputs available to select as a wait for condition Only the loop monitor selections will be provided 5 1 5 Setting Jump Steps This feature allows the program to jump between different steps within itself When a jump is programmed
64. when a program is in hold When selected the input will reset any active alarms on the alarm screen If a digital output is set to Remote Alarm NO the output will be turned off Note that the input will not clear any alarms from the list on the alarm screen and the alarm icon will continue flashing This is a single shot activation in which the input must make the required transition state in order to carry out the function Thus for each new alarm the input must be re activated to reset the new alarm Leaving the input in an activated state will not reset alarms when they occur When selected the input will disable the digital inputs selected under Defeat The selected inputs will not perform their function until the input defeat is deactivated When selected the input will terminate an active defrost cycle and the fan delay will begin If the input is active when a defrost cycle is to begin the cycle will be skipped and defrost will not take place See section 8 1 Defrost for more information regarding defrost operation When selected the input will active the redundancy product load timer If the load timer is already active the input will reset the timer See section 8 2 Redundancy for more information on redundant system operation For the input control functions listed with an asterisk CL the on state for the input is defined by the transition mode If high is selected the input is on when
65. 0 F 2 3 Mounting Dimensions This section provides mounting details and dimensional information for the various components that make up the nCompass control system Note that your system may not include some of these components and that quantities of certain components vary depending upon the application and options ordered Make sure that you have all components required for your application prior to installation 2 3 1 nCompass Touch Screen Interface The nCompass i4 3 interface is supplied with four mounting clips All clips must be installed and properly tightened to insure the IP65 protective rating from the front of the interface Failure to install all mounting clips may also affect touch screen operation Be sure to tighten each one evenly so as not to flex the case of the unit Mounting Clip Slot 4 total Mounting Clip Installed in Slot 2 2 FDC nCompass Installation nCompass i4 3 ff eurupenesron N T R O NOTE nCompass will not operate properly without the SD card installed into the SD card slot on the back of the unit The SD card has all software required loaded onto the card for Auto Boot operation The slot on the back of the interface is keyed so the card can only be installed in one direction The card is pre installed for your convenience If the card is removed take care when inserting the SD card and do not force it into the slot The card MUST be installed before powering on the unit 122 0
66. 00 times minimum Connector on Mother Board Isolation from Internal Circuit Transformer isolated Incorrect Wiring Malfunction may be caused Effect of Improper Input Connection Improper Voltage If any input exceeding the rated value is applied permanent damage may be caused Between communication terminals and internal circuit Dielectric Strength 500V AC 1 minute _ lt Expansion Connector __ 2 Module Label ___ 3 LED Indicator 4 Terminal Name _ 5 Cable Terminal A 16 FDC nCompass APPENDIX FUTUREDESION c O N T R O nCompass i4 3 fil Power Supply Specifications page 1 of 2 Part Number up output PSSA SD24 Output Capacity eu Input Voltage 65 to 264 VAC lsingla phase 2 wira 100 to 370 VOC s 1OOVAC 17A Input Current typical TAE Se Keser O inmush Current cold start 50A maximum at 2004 AC Leakage Current at no load D TE maximum Typical Efficiency am a FER E E E E e ES e re em Voltage Adjustment 10 IN ADJ control on front Output Holding Time ms minimum lat rated input and output Starting Time z Rise Time 100ms maximum tat rated input and output Line Regulation 04 maximum Load Regulation 1 5 maximum Temperature Regulation 0 05 degres C maximum Ripple Voltage 2 peak to paak maximum including noise Overcearreat Protection 105 or more auto raset Overvoltage Protection 120 min SHUTDOWN Parallel Operation
67. 10 cycles within a program your cycle count will be set to 9 10 minus the 1 you performed prior to reaching the jump step Automatic Program Operation FDC nCompass oa P FUTUREDESION N T R O nCompass i4 3 Example A process must cycle between 0 and 55 for 10 cycles during a portion of the program and then returned to its starting value for following steps Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Start at 25 Ramp to 55 BEE Eee soak at 55 LU LU LU LU LU E LU LU LU LU LU LU LU LU LU LU E ramp to 0 soak at 0 BR Ty Ramp to 25 o i A ge Set Jump to Step 2 Jump from step amp to 2 Set Cycle Count 9 LO E in With the jump programmed on step 6 the program will jump from step 6 back to step 1 after the ramp time has completed The program will then repeat steps 2 through 6 It will continue to do this until all 9 jumps have occurred Once all 9 jumps have been completed the program will continue on to step 7 after the final ramp to 25 Since 1 cycle is made prior to the first jump at the end of step 6 a total of 10 cycles are completed NOTE 5 1 6 Auto Start is a feature that can be used to start a ramp soak program on a specified date or day and time of a 24 hour clock The auto start settings are saved with the program Choose the desired auto start method by date or by day from the drop down menu and enter the start time settings The nCompass ramplsoak program
68. 11 O CH BO Input Voltage V AC 20 Input Current mA APPENDIX 45 12 7 15 16 9 FC4A NO8A11 8 points in 2 common lines 100 to 120V AC 50 60 Hz 85 to 132V AC 15 mA point 120V AC 60 Hz AC input Type 1 2 3 IEC 61131 2 0 8 kQ 60 Hz 25 msec 30 msec Between input terminals in the same common Not isolated Between input terminals in different commons Isolated Between input terminals and internal circuits Photocoupler isolated Not needed Static If any input exceeding the rated value is applied permanent damage may be caused MC1 5 11 G 3 81BK Phoenix Contact 100 times minimum 60 mA 5V DC O mA 24V DC 30 mA 5V DC O mA 24V DC 80g Input Internal Circuit FC4A NO8A11 Input oft L H COM wi 5 O E EN D pa Z ON Area Input Usage Limits When using the FC4A NO8A11 all inputs can be turned on simultaneously at 55 C input voltage Transition 132V AC Area OFF Area 132 120 102 Input Voltage V AC d 0 50 100 Input Simultaneous ON Ratio FDC nCompass A2 FUTURE DESIG c O N T R O N nCompass i4 3 Analog Input Output Card Specifications page 1 of 3 Analog 1 0 Module Specifications General Specific ations Type No Rated Power Voltage Allowable Voltage Range Terminal Arrangement Commector on Mother Board Connector Insertion Removal Durability Intermal Curent Draw External Current Draw Note W
69. 5 1A USB File Transier E 7 6 LC SN at A A LO eee oct esas tr ee ater ok tes tices pace fr snr atc seer E EE A 7 8 LO PAIN ten WE 7 9 7 f Add View Digital Signatures cccccccccsccccssceceeeceeccseecececeueesaueeseeseaceseusessueesseeecsueessusesseeesaeesaas 7 10 6 BI d et goo de ener nen ren nn ee ence ene ee E 8 1 EE wd EE 8 2 81 1 eet ETag 8 3 SSC e ee En tacts ce cn yn O gd de imc se dk pein At ind Secs ese desc ssc eee gs eee 8 4 8 2 1 Concurrent Redundancy ZSwttchumg A 8 6 8 2 2 Alternating Redundancy Switching cccsccccssccccssccceescnsusccseecsusensusensusensuseaseessusessusensusessussanssensass 8 6 8 2 3 Egu ual R n TIME Me EE 8 6 E Ga Belore Derost SWINGING ME 8 6 ee AE DEOS T WN lee 8 7 o2 E EE 8 7 ao AaS E 8 8 8 3 1 Set Points and Alarm Message 8 10 8 3 1 1 Rate of Change ROC Alarm Set bont 8 11 ore ay mmm OUT O 212 ee 8 12 OF EI EE 8 13 DEEN Eeer 8 14 8 6 h 6 2 2 E 8 14 Gr a 912 9 lt A 8 15 8 8 CommunicationS ee occ ene 8 17 8 9 Barcode Header 8 18 8 9 1 Barcode Reader Communication Zeftgs 8 19 8 9 1 1 Setting up the Unitech MS 120 2 Barcode Gcanmner 8 19 8 9 2 Important Notes on Barcode Reader Uee 8 20 8 9 2 1 Using the Barcode Reader to Start an Automatic Ramp Soak Hrogram 8 20 8 9 2 2 Using the Barcode Reader to Annotate a Datalogtie cece eececeeeeeeeeeeeeeeeeeeeaes 8 20 Za LAN un EU 8 21 Ot METI NO OS ENUY sects Scien eeben 8 21 ER e 8 22 OF Ee 8 22 OO EMA IVC e 8 23 Table
70. 5 1 2 Setting Step Set Points and Ramp Rate Dwell Time Ramp Rate Option ccccccccseeeceeeeeeeees 5 4 E Seling Step EE 5 4 5 1 4 Setting Wait For Conditions 5 5 EE 5 7 mei Ee de e tee Stall EE 5 8 5 1 7 Setting Guaranteed SOAK Limits cccccccscccssccccescnsuscnsusensueccsuecsusessusensusensuseaueessusessusensusessassaseesanass 5 9 5 2 Starting an Automatic Ramp Soak Program cccccccecccseececeeeceeeeseeeeaeeeseeeeseueeseeeeseeeesaueesaeeeseeetaes 5 10 5 2 1 Hold Resume Ramp Soak Program CUperaton 5 11 g2 AUSMO e EE 5 17 5 2 3 Advance PrevioUusS N Xt Sien 5 12 5 3 Monitoring Automated Ramp Soak Program Cpoeraton 5 12 5 4 Common Questions About Ramp Soak Program Operation 5 13 FDC nCompass Table of Contents FUTUREDESION nCompass i4 3 N T R O 2 E EE 6 1 CT Addni EE 6 2 Oa MONG USO cea swiss see T A E eee eee 6 2 02 1 NewfFassword ENUY EE 6 3 6 3 Setting Re 6 3 6 3 1 Security System User Access 6 4 GOA Setting Security ODTONS EE 6 6 Oa E Tel e E UE 6 7 ACO GIN E 7 1 7 1 Selecting Points f r LOGGING E 7 2 1 2 Sarung Stopping Data LOGGING EE 7 2 Teed GOlGUIAUINO Log d E 1 3 723 Reviewing Historical Data sik casceccccceseneduwedwsdscdeannieswnctwnndwsiecwinintinensecedahcwens abnenciesxnc esd eulnaenintenteaseateewendwesSesbnc 7 4 E FT Ee FOE SOE eE e ced eee elie E EEEE E EEEE E dette eee assis 1 4 fas ee deefe elle DA oasis ee at seated gag sin eae ee noel ven tenons delat ee ee cede EEEE 7
71. 5 Hz ER SES Operating extremes m pitude 0 5mm 10 ta 55 Hz l Shock Aas istance Damage lin its 500m Approx S06 24 AC type 1 AVA l Z OC 1 Oey GEIA G HEE T10 AC type 3 3 vA Powar 220 AC type TT VA Consumption 20 AC type 2 0 Ve Z OC type Du GEA T10 AC type 3 5 vYA 220 AC typa o0 yA Fach ical Fa TOO O00 operations minimum Gr full ated lad Mechanical Life TO OOO O00 operations min mum Opoatng Temperature 10 to HE iwithout frees ing Operating Humid gu 350 6 AA without freezing APPENDIX FDC nCompass A 19 P Power On Delay Relay Specifications page 2 of 2 FUTUREDESION nCompass i4 3 N T R O LS kem Terminal Number Operation set Time e Power z TISH Henie KE ANN Contact G G Er up POW ER Indicator OUT 6 Pin Screw Terminal SR2P 06 e smn 25 5 S aa Terminal ising By DIM Rail BAA Arrangement BO Peace Mounting gt Hole A 20 FDC nCompass APPENDIX c O N T R O nCompass i4 3 d FUTUREDESION How to Order nCompass CM is ordered as three components the 4 3 color touch screen firmware and the Control Module CM with its assorted options The loop controls must be ordered separately nCompass CM Sample Part Numbers minimum of 3 component part numbers is required 1 Display 2 Firmware and 3 Control Module Product Sample Part Number Description Display FDC 0450 1011 000BN 4 3 display CM software 11 36 VDC power input SD slot Ethernet standa
72. 7 Digital Output 8 function determined by nCompass configuration 3 12 FDC nCompass Wiring f FuTUReEDESIGN N T R O nCompass i4 3 3 6 2 Optional User Communications Card Wiring The RS485 communications card FC5A SIF4 allows multiple nCompass controllers to be connected to a single communications link The connection requires a single twisted pair cable that is daisy chained from one controller to the next Use of this card requires an RS485 connection on the host computer Since most computers do not provide this type of interface an RS232 to RS485 adapter is required Future Design recommends the use of the SNA10A or SNA10B network adapter S nCompass nloampass J Unit 2 C Unit 1 HDD oooaa RS 485 to RS 232 Xt El TX TAZ A TA rT network adaptor Di H CR Ce WS W NATO or OC 7 SNA1OB l I L z REARS P A TXI L Twisted Fair Wire d P KE Ke 3 7 NOTE When using shielded twisted pair cable be sure to ground only when end of the cable preferably at the RS232 to RS485 network adapter Allowing any other portion of the cable shield to come in contact with ground or grounding both ends will cause ground loop currents to flow in that section of the cable which can cause communication errors Wiring FDC nCompass 3 13 P 3 6 3 Optional Barcode Scanner Communications Card Wiring FUTUREDESIGN nCompass i4 3 c O N T R O Future Design recommends and supports the use of the Unitech M
73. C mpass Process LOOP COnNTOlN rS 0 0 ccccccccccsseccnseeccssecsuscnsusensusessusensusensuseseesausensusensuseasassaneess 2 4 2 3 3 NCompass Process Monitor Modules ccccccccsecccsseecsneccseeccseeecueessueessueesssesseessaeessusessueesaneessneess 2 4 234 NCOMDASS ee deele 2 5 2 3 4 1 Installing the RS485 Communication Module aanneannnannnnnnnnnnnnnnnnnnnnnnrnsnnnnrrsnnnenrnnrnnrrnnrennne 2 6 2 3 4 2 Installing the Control Module in a banel 2 2409 ICOMDASS Ee 2 8 2 3 9 1 User Communication Modules annnannnannannnnnnnnnnennnnnnrnrnnrrnnrnrrrnnrrsrrnnrrnrrrnrrnnrrnrrnnrrnrrenrrnnne 2 8 299 2 Digital Input WO le ET 2 8 29 99 ER Belle ef e le IT 2 9 2004 ANAI VO IO GUNG EE 2 9 2 4 nCompass Control Module Installation Example ccccccccccceececeeeeceeeeeeeeseeeeseeeeseeeeaeeesseeeeseeeeaes 2 10 KL e WEEN 3 1 3 1 PowerReguirements si cicessssace eeticei dc nivainste tite 0 ind aE A AAEE EE AEE OREN SEREEN 3 1 3 1 1 Installing the Power On Delay Relay A 3 2 3 2 Grounding ReguirementS wire dice niica dccwained sac ebinka sin unetnsiasaeeiin saieabdniawendtidaicdbisct OEE AEE a AEREE EAEan 3 3 3 2 1 Special Considerations for Low Voltage System Grounding cccccccceeeccseeccseeesneessneeseeessneessnsess 3 3 3 3 Connecting to the NCompass lntertace 3 4 3 3 1 Serial Communications to Control Module cccccscccsscccsseecsesceceeesseeessueeesueesseessaeessseeesseessneesaneess 3 5 3 4 Connecting to the nCom
74. Compass MAC Address The MAC address can be obtained from the network connections screen In order to access the screen you must exit the nCompass application To do so proceed to the Exit Application screen under the offline setup menu Press the Exit and start runtime on next power up button to exit the nCompass runtime application Follow the on screen prompts to stop the application and exit to the Windows CE desktop NOTE The text System Startup Please Wait on the desktop is static and does not indicate that any application is going to start at this time It is used as a placeholder prior to the nCompass runtime or configuration application starting during normal power up sequences so that the user is informed that an action is taking place 10 2 FDC nCompass Communications f FuTUReEDESIGN T R O 14 3 System Startup Please Wait From the desktop touch the narrow gray bar at the bottom of the screen to show the taskbar System Startup Please Wait Network Icon Le Te 720 PM Ile Start Next double click on the network connections icon to open the network connection information window Two tabs will be provided one for IP Information and the other for IPv6 Information To obtain the MAC address press the Details button on the IP information tab Dy e DM9ISAL IP I Network Connection Details Property Physical
75. DESICN N T R O nCompass i4 3 7 5 FTP Data Backup The FTP WAN screen allows the user to configure automatic back up of all data files contained in nCompass memory to a user designated FTP site When enabled nCompass will automatically back up all data log files alarm files and audit trail files at 2 00AM each day With the optional delete files selection nCompass will then automatically delete the files from its internal memory after back up This will maintain nCompass memory automatically so that continuous data logging can be performed without filling up the available memory space NOTE Setting up an FIP site on your network may require authorization and or assistance from your network administrator Contact your network administrator for proper settings and authorization from your network server if required to allow nCompass to connect to the designated FTP site FTP WAN ee gem IP Add 192 168 0 102 User PSWRD Server FTF Data Files User Name Pswd blank for anonymous logins OFF The IP Add field is used to enter the IP address of the FTP site that nCompass is to send the files to The User field allows you to enter a user name for FTP site access When nCompass connects to the FTP site to transfer files the user name will be used to identify the connection If a security login is required the proper user name will have to be entered in this field If security is not used this field can be left bla
76. E Z EL 8 b EF W APAID i e e e 8 e e Eje e e e e je le ago JA O40 T 5 6S WO LARS IEE PRTI PED i Outputs Q0 and Q1 are transistor source outputs others are relay outputs COM COM COM1 COM2 and COMS terminals are not interconnected COM terminals are interconnected Connect a fuse appropriate for the load a AR Main CPU Digital Input Assignments 24Vdc inputs Digital Input 1 function determined by nCompass configuration 1 Digital Input 2 function determined by nCompass configuration 2 Digital Input 3 function determined by nCompass configuration 3 Digital Input 4 function determined by nCompass configuration 4 Digital Input 5 function determined by nCompass configuration 5 Digital Input 6 function determined by nCompass configuration Digital Input 7 function determined by nCompass configuration Digital Input 8 function determined by nCompass configuration QO Digital Output 1 function determined by nCompass configuration Q1 Digital Output 2 function determined by nCompass configuration Q2 Digital Output 3 function determined by nCompass configuration Q3 Digital Output 4 function determined by nCompass configuration Q4 Digital Output 5 function determined by nCompass configuration Q5 Digital Output 6 function determined by nCompass configuration Q6 Digital Output 7 function determined by nCompass configuration Q
77. If the alarm start delay is enabled the start delay time can be used to set the maximum length of time the alarm can be inhibited For example if a process is started and the start delay is enabled what happens if the process never reaches its normal operating mode The process will operate indefinitely in an alarm condition unless an operator notices it because the alarm will not activate since it never entered the normal range By setting the start delay the alarm inhibit will be disabled once this time period is exceeded from the start up of the system The allowable time setting is from 0 32 760 seconds A value of zero 0 disables the alarm start delay timer so inhibit will be on indefinitely until the alarm input reaches normal operating range The Alarm Message is the text notification that appears on the Alarm screen when the alarm activates This message can be edited up to 25 characters maximum so that the alarm message more accurately describes what the alarm means 8 3 1 1 Rate of Change ROC Alarm Set Point When rate of change ROC is selected as the alarm type increasing decreasing or both the alarm set point is defined by an amount of change in the process value over a period of time in minutes Alann Settings Se Delta C 0 0 Time minute oi Differential C 0 0 Delay seconds 0 Start Delay seconds 0 Alarm Message ALMA 1 The Delta set point defines the allowable change of the selected l
78. O contacts 2 NO contacts 1 HO contact 24 per point SA per commen line A m A O 1V OC reference value 30 mi maxsimum 100 000 operations minimum rated load 1 800 operatians hour 20 000 000 operations minimum ne load 13 000 operations hour 240 ACs 2A resistive load inductie load cos a 0 4 SOV DCs 24 resistive load inductive load L R T mai Petasan output and a terminals 1 500 AC 1 minute Between output terminal and internal circuit 1 500 AC 1 minute Between output terminals COM 1 500 4C 1 minute MEL 6645 381 6K Phoenix Contact 100 tines minimum 10 me maxmur 6 ma maximum ON daar Gma maximum FDC nCompass A 7 c O N T R O d FUTUREDESION nCompass i4 3 Digital Input Card Specifications page 1 of 2 DC Input Module Specifications Type Mo FCIA NOBBL amp ponts ini Input Points and Conmn Lines comma lins Rated Input Voltage 24V DC sinks source input signal Input Voltage Range 20 4 to 28 8V DC Rated Input Current T maA point 24 Le Input Impedance 3 4 k Turn ON Time 24V DC 4 ms Turn OFF Time 24V DC 4 ms isolation Beta een input taminals Not isolated Inter real circuit Photecoupler isolated Extemal Load for 1 0 Interconnection Not needed Signal Determination Method Static 20 CG Both sinking and sourcing input signals can be connected H any input fect oF Ya pope tae Daai enceeding the rated value is applied permanent damage may be caused Cable Length 3m 9 84 ft i
79. Page Based Home Menu cess eesaeeseeeeseeeseeeeseeeeseeeeseeesseeess 4 5 4 3 2 Automatic Ramp SOak Program Menu 4 6 4 3 2 1 Text Based Program Menu cccccccsscccseecceeeceececaueeceeeceeeceueesaueesueeseueessusesseeessenseeeeseueess 4 6 4 3 2 2 Icon Slide Page Based Program Men 4 7 Aaa Re dee 4 8 4 3 3 1 Text Based Device Settings Men ccccccccsecccseeeceeeeceeeceuceceueeceueeceeeceueessueesseesseeessaeess 4 8 4 3 3 2 Icon Slide Page Based Device Settings Men 4 9 E OTIS IACI EE 4 10 4 3 4 1 Text Based Offline Men 4 10 4 3 4 2 Icon Slide Page Based Offline Men 4 11 E OR IV EE 4 12 BBO Text Based Data WCU ME 4 12 4 3 5 2 Icon Slide Page Based Data MeN cccccsscccseecceeeceuceceueeceeecueeseasesseeeseeeseueessueensass 4 13 AA INO UEC AON cece rA e a E E od settee tase ciated suid neiden E A EEE EE AA E et EEEE EE AE 4 14 4 5 Control Loops Single Set point Operaton 4 15 431 ONOS LOOD WE 4 15 Aa DULO VON EE 4 16 Ey un EVM CONVO err a a a E E E E T Ea 4 17 Al Process Monitoring eserse aaa iE EA AA A OaE a AA A aaa EEE 4 18 e E et 4 18 reng Ee See le EE 4 19 Bel LIQ et 4 20 AO SVS un RE EE 4 21 LoT PIT TORO E 4 21 EE 4 22 Automatic Ramp Soak Program Operation ccccescesseeeeeeeeeneeeeseneeneneeseneeeneones 5 1 5 1 Entering a ane Tee EA Progra EE 5 2 5 1 1 Setting Step Set Points and Time Ramp in Time Option ccccccccseccccseecseeecsesecseeesseesseeesseeesaess 5 3
80. S 120 2 barcode scanner with an RS232 interface and built in decoder The barcode scanner also requires a separate 5Vdc power supply which attaches to the decoder module Unitech model 101000 0150 110V power adapter SPECIFICATIONS OPTICAL Light Source BOM Red LED Resolution 5 mils 0 12mi Depth of field 0 04 OU Jm Scan Rate 2 fo inchesfsec 5 200 crvsech Gesang Angle Oto 45 Print Contrast Ratio 0 5 min Min Marrow Bar 0 12 mm when PCS 0 4 0 18 mm when PCS 0 5 INTERFACE Connector R232 DAY 4 ERMVIRON RENTAL a Cable Coiled cable Type A 2 prong plug Case Material Stainless Steel Output 5vDC DECODER 300mA Symbologies Code 39 Mul ASCII EAN 3 9 with add on code 2 1x5 5mm WIPC AIE with add on code Code 11 Code 93 Code 128 Positive inside Codabar MSlfPlessey Interleaved 2 of 5 Standard 2 of 5 China Cord Length 75 1 9M Postal Code Italian Pharmacy reversed label NOTE Other barcode scanners with built in decoders can be used with nCompass however due to the numerous types and models available Future Design can only provide support on models tested for use with nCompass The barcode scanner must be configured for use with nCompass prior to use or it will not communicate properly with the control module See Section 8 5 Barcode Reader Setup for information on the proper settings and use of the barcode scanner 3 14 FDC nCompass Wiring FUTUREDESION c O N
81. TE The OEM configuration of nCompass may allow the operator to change the loop set point activate manual mode and initiate an auto tune at the loop control itself If any of these permissions are active any change made at the loop control will be indicated on the loop view screens If these permissions are not enabled any change made at the loop control will be overridden by the setting from nCompass If in doubt about which permissions if any are allowed from the loop control contact the equipment manufacturer or consult the OEM configuration Any changes made at the loop controls are not logged or protected by nCompass security settings These changes will not appear in the audit trail If adjustments to control loop settings are to be made only by authorized users with the proper security access the loop permissions should be disabled in the nCompass configuration or other means are necessary to prevent unauthorized users from accessing the loop controls 4 5 1 Single Loop View The Single loop view display shows one control loop or process monitor input at a time It is accessed from the home View menu The screen provides special loop control functions not available on the Dual loop view screen These special functions are accessed by the Manual Mode and Auto Tune control buttons Loop Name LG Set Point Entry Field 100 0 Loop Units o Manual Control Ey Automatic Tune The left and right arrow buttons allow
82. TX 0x02 Postamble ETX 0x03 The preamble and postamble are the start of transmission and end of transmission characters that must be used to frame the barcode transmitted to nCompass so that it recognizes the beginning and end of the transmission All other terminator BCC ACK and or handshaking characters must be disabled 8 9 1 1 Setting up the Unitech MS 120 2 Barcode Scanner The following instructions are provided for the Future Design recommended Unitech MS 120 2 barcode scanner These instructions do not apply to other makes or models of scanner Consult the manufacturer s manual for other makes or models for information on how to set the proper communications settings NOTE The steps below are assuming manufacturer default settings are in place If the scanner settings are unknown restore the scanner to manufacturer defaults by scanning barcode enter group 1 on page 5 of the MS 120 Series Programming Manual and then scanning the factory defaults barcode at the bottom of page 5 Scan exit to complete the process For communication settings see page 11 RS232 Serial Setting of the MS 120 Series Programming Manual Step 1 scan barcode at top of page 11 for enter group A Step 2 scan barcode C2 for parity on page 12 and then scan the barcode for the number 0 on page 11 Step 3 scan barcode C3 for data bit on page 12 and then scan the barcode for number 0 on page 11 Step 4 scan the barcode for exit on page
83. UT 6 DIG OUT 7 DIG OUTS Input defeat selections are available for the Defeat Input function Any of the available nCompass control module inputs can be selected for defeat and multiple inputs can be selected for defeat when the input is activated Note that the current input can not be selected for defeat or the function would not be able to be activated If more than eight inputs are available in the system the Group button will be shown allowing the user to toggle between the first eight inputs and the second group of up to eight inputs 16 max Defeat Group Return EN DIG IN 1 al DIG IN 2 DIG IN 3 DIG IN 5 DIG IN Offline Setup FDC nCompass 9 15 f FuTUReEDESIGN N T R O nCompass i4 3 9 8 Digital Outputs nCompass provides eight digital outputs standard and is configurable up to 16 The outputs can be used as system event outputs alarm outputs or for other signaling needs Digital Output 1 wm emm Function Inactive Digital Input Select era ere Delay Start Seconds 0 0 Delay Stop seconds 0 0 Repeat seconds o Interval seconds 0 0 The left and right navigation buttons at the upper right of the screen allow the user to scroll through each available output To make changes to the output s configuration select the desired function of the output and set any necessary delay times Once all changes have been made press the Save button to save them If you do no
84. ailable for both the 1 32 and 1 16 DIN sizes The FD10 CM software also allows connection to the B41 board level control Information on these Series controllers may be found at the following links http www futuredesigncontrols com 300 HTM http www futuredesigncontrols com 100 HTM http www futuredesigncontrols com B41 HTM The FD42 CM software allows connection to Future Design Controls P Series DIN controllers and the B42 board level controller Information on these Series controllers may be found at the following links http www futuredesigncontrols com P_Series HTM http www futuredesigncontrols com B42 HTM CM software supporting Honeywell Watlow Danaher Eurotherm Yokagawa and other controller products are available Refer to the specific FDC brochure available for each control brand as there may be limitations depending upon control brand NOTES Serial Communications Serial connection to CM RS485 Modbus RTU slave and RS232 barcode input modules RS485 Modbus RTU input module The RS485 module allows 3rd party software hardware R W access to specific registers within the Control Module Contact Future Design Controls technical support for the register address listing for specific software versions RS232 Serial input for barcode readers The RS232 serial input option allows the nCompass to receive up to 16 characters from a standard compatible serial Barcode reader Data from the bar code reader will insert op
85. ailable on the system It also provides access to the input Monitor and output Force screens View Analog Output Set Digital Input BC Digital Output Calibrate Monitor System gt Force The Calibrate menu provides access for applying an offset to the monitor inputs if available on the system View Set Hardware gt Calibrate The System menu provides access to the nCompass Display settings import export Configuration utility About screen and Exit application screen View v Set gt Display Hardware l Configuration Calibrate D SE 4 10 FDC nCompass Basic Operation nCompass i4 3 4 3 4 2 Icon Slide Page Based Offline Menu re Clock Settings l About CX Service Analog Input Digital Output Configuration Basic Operation Exit Options a ch Analog Output Monitor Display CF Units ap k Pe K Language Digital Input f FuTUReEDESIGN N T R O Slide page 1 provides navigation back to the device settings menu temperature units selection NTS Clock Service items and Options touch screen calibration and language settings lt also provides access to the About and Exit application screens Slide page 2 provides configuration access to the nCompass digital and analog inputs and outputs if available on the system It also provides access to the monitor input offset screen
86. ait for condition of the step in order for the program to continue To enable a wait for condition in a step press the Wait For button on the Entry screen This displays the Wait For screen The process selections as shown below allow you to select which loops and or monitors if any will be used as a wait for condition If more than six loops and monitors are configured in the system the Group button will be shown to allow the user to cycle through all available inputs Automatic Program Operation FDC nCompass 5 5 f FuTUREDESIGN nCompass i4 3 N T R O Wait SFP The loop and monitor selections share a common Wait for Setpoint This set point is used as the trigger point for the wait for condition i e the value that each loop and or monitor must meet for the program to continue NOTE The set point entry for a wait for loop andlor monitor is critical in order for the step to operate correctly During the wait state each selected loop and or monitor input must arrive at or cross the wait set point in order for the program to resume operation Thus the previous step must insure that the process values will be moving towards the target wait for set point prior to the wait for step beginning If all selected loops and or monitors do not cross the wait for set point after the wait step has started the program will pause indefinitely on the step until the
87. al input operation r a Digital Output Settings for digital output operation Calibrate gt Monitor Monitor View current digital input status troubleshooting System Force Force Force digital outputs on troubleshooting View Set Hardware ltiema Offset System View Set gt Displa Hardware gt pier Calibrate Sat Exit Offline Setup Configuration Calibrate menu Offset System menu Display Configuration About Exit Settings for optional monitor offset calibration Access to display calibration and backlight settings Access to nCompass import export utility View current firmware software version numbers Exit nCompass application and access to the nCompass configurator FDC nCompass 9 1 f FuTUReEDESIGN N T R O nCompass i4 3 9 1 Service The service counters provide service interval alerts and life total service numbers for each of the digital outputs available on the nCompass control module The service intervals counter set points are adjustable and can be set to match service intervals for equipment operated by nCompass Service DIG OUT 1 Count 55 DIG OUT 2 Count 655 Exceeded Service Limit Two service alert set points are provided for each output of nNCompass One service alert is available for the number of times each output turns on and is adjustable from 0 to 4 000 000 000 cycles The second servic
88. amp print the data directly from the display auto scale on X amp Y axis with each channel selectable for right or left axis values from a PC after data is copied moved via LAN FTP or email or USB Flash Memory card provided NOTES Monitor Inputs Optional DIN Rail Mount w serial connection to CM Monitor Inputs The FDC IO modules are DIN rail mount 8 channel isolated thermocouple RTD 6 channel or 8 channel linear mA or Vdc input modules Each monitor point is configurable for Alarm setpoints and segment advance wait for logic SP logic amp loop Delta function 2 Monitor input cards may be specified nCompass system configuration allows up to 15 monitor points Information on the FDC IO modules may be found at the following Link http www futuredesigncontrols com FDC IO_Modules html NOTES Power Supply Standard DIN Rail Mount Power Capacity Required Watts A base system without options requires 30 watts of 24Vdc power The 60W power supply offered is sufficient to power all of the components and options including up to 3 24Vdc powered B42 loop control boards Note The power supply should be used to power nCompass components only and not OEM or other end user components or devices APPENDIX FUTUREDESION c O N T R O NOTES Configurable Control Logic Ramp Soak Programs Global program configurable as Time or Ramp Rate based The FDC nCompass provides for a virtually unlimited number
89. an be adjusted from the Options screen Service Options Count total Hours total Notification The count and hours selection buttons are used to choose what information will be shown for the digital outputs on the Service screen The selections are mutually exclusive so when one item is selected the other items will be de selected The Count and Hours are what generate the service alert when the set point is exceeded for the output These are the counters that must be cleared in order to remove the service alert from the alarm screen When either of these is selected the service screen will display the elapsed count or hours for each output The Count total and Hours total selections are for displaying the life total count and hours for each output These maintain separate count and hour values from the elapsed selections Note that these can also be cleared from the Service screen by pressing the Clear button if they are selected for view This allows life total operation to be tracked for external equipment and then reset when the external equipment is replaced with new The Notification button is used to turn the service alert option on and off Service alerts are turned off by default When the service alerts are turned off there will be no notification on the alarm screen when an output exceeds its service interval Offline Setup FDC nCompass
90. ass CM i4 3 Configuration Manual PS5R SD24 60W power supply USB Memory Stick Note DIN Rail mount 24VDC 60 watt power supply 2 5 amps to power the FDC 0450 control module CPU optional IO and FDC IO monitor input modules UDF115 2GB 2GB High Capacity USB Memory Stick 3VDC USB Cables amp Accessories IStick Panel USB Panel Mount Adapter System Reset Timer IStick 4X CVR USB Panel Mount Adapter Nema4x GE1A C10MA110 SR2P 06 Reset Timer and socket DIN Rail Note Timer is recommended for proper system restart due to momentary power interruptions lt 500ms which can cause false alarms and or erroneous operation DIN Rail Mounting Adapter for 1 16 DIN Loop Controls DRA 16 1 16 Din Rail Mounting Adapter APPENDIX FDC nCompass A 21 FUTUREDESION c O N T R O nCompass i4 3 Item 2 Loop Control Firmware Order Matrix Fixed characters SD CM SD card with CM Control Module Display Configuration and SD plugged into display Item 3 nCompass Control Module loop controls ordered separately em ui Order Matrix 1 2 3 4 5 6 7 1 Control Module CM Application Software loop control type 6 Optional Monitor Inputs serial connection to CM 0 FD42 CM software for FDC P41 B42 Series 0 None 1 FD10 CM software for FDC 100 B41 Series 1 10 8TCS 8 thermocouple input module isolated 2 FD30 CM software for FDC 300 Series note 1 2 10 6RTD 6 RTD input module 3 HWSL CM software
91. ata file end Device Manager 1 17 2013 1 08 PM Each action recorded to the file includes the date time it occurred as well as the user if logged in that made the change If no user is logged in the user will be listed as Device Manager which is the default user account for the nCompass system The send email icon Ee allows the user to send a copy of the currently opened audit trail file to any user configured in nCompass When the email icon is pressed an Add Recipients window will be displayed where the user can select recipients for the file from any of the email addresses configured under the nCompass email settings For information on how to add email recipients to nCompass see the section 8 9 Email IMPORTANT Functions performed via the digital inputs such as starting or stopping a ramp soak program are not logged to the audit trail These are external inputs to the control module and are not protected by security If a digital input is programmed for the Halt Setpoint Control function and the input is active any set point change entered by an operator for a control loop will be logged to the audit trail however the set point on the loop control will not change This will cause a discrepancy in the audit trail file as it will log the new set point entry even though the loop control is prevented from taking it Security FDC nCompass 6 7 f FuTUReEDESIGN N T R O nCompass i4 3 7 Data Logging The nC
92. ature allows the refrigeration system to pre cool the cooling coil before the fan is turned on after a defrost cycle This is adjusted to give a minimum amount of temperature rise after the defrost cycle has completed Defrost Defrost Status Interval hour Duration minute Fan delay seconds The defrost settings allow the user to set the interval duration and fan delay time for timed defrost sequences If nCompass is configured for timed defrost only defrost cycles will take place at the interval set by the user If the defrost function is configured for timed process the defrost interval for defrost will only be active when the OEM configured loop or monitor point is below the defrost enable set point that is entered in the nCompass configurator Consult your OEM configuration for the defrost type your system uses The Status field displays the current status of defrost operation Inactive Active or Fan Delay Active The defrost Interval field is used to set the defrost interval The time can be entered in hours from 0 999 If 0 is entered for the defrost interval defrost will not be initiated automatically The defrost interval must be set from 1 999 hours to activate defrost Setting the field to zero allows the user to disable automatic defrost operation for testing purposes or to require manual activation only via the demand Defrost button 8 2 FDC nCompass Device Settings nCompass ia3 ff eu
93. aw at the position shown in the diagram This is required when equipment containing the MicroSmart is destined for Europe Do not connect any wiring to unused terminals Before turn on the power make sure that wiring to the analog 0 module is correct If wiring is incorrect the analog 1 0 module may be damaged The analog expansion card must receive separate 24Vdc power from the nCompass power supply If power is not supplied to the and terminals the input output circuitry of the card will not operate The PWR indicator light on the card indicates bus power only and that it is properly connected to the nCompass CPU It does not indicate that the 24Vdc power source is present The analog inputs and outputs increase in sequential order as expansion cards are connected to the nCompass CPU from left to right For example the first analog expansion card is assigned inputs 1 and 2 and output 1 As the next analog expansion card is connected to the right of the first card it will be assigned inputs 3 and 4 and output 2 Expansion Card 1 Assignments OUT Analog Output 1 INO Analog Input 1 IN Analog Input 2 Expansion Card 2 Assignments OUT Analog Output 2 INO Analog Input 3 IN Analog Input 4 Wiring FDC nCompass 3 19 nCompass ia3 ff eurupenesron N T R O 4 Basic Operation This section is designed to help guide you through the nCompass touch screen interface and menu structure so that you can
94. b if necessary Select Specify an IP address and enter in the desired IP address subnet mask and default gateway You can move the keyboard around on the screen to position it as necessary to access the different fields Once complete close the Ethernet Drivers window by pressing the OK button located at the top right of the window Next close the Connection window by pressing the X button at the top right of the window Ei DM9000 Fast Ethernet Adapter Settings An IP address can be Obtain an IP address via DHCP automatically assigned to this computer If your network Gi Specify an IP address does not automatically assign IP Address 192 168 1 IP addresses ask your network administrator for an Se Subnet Mask ee ee Jeu Daten id Kl shift 2 x e v b n m LO aka AY SO CS Access the taskbar and hide the keyboard by pressing the keyboard button at the bottom right of the taskbar and select Hide Input Panel DO NOT cycle power to nCompass at this time Wait approximately 2 minutes before removing power This provides time to allow the Windows CE operating system to save the new network settings to the registry so that it uses the settings on the next reboot If power is cycled too soon the network settings will revert back to the previous settings on the next power up Once the 2 minute time period has elapsed since updating the network settings cycle power to nCompass in order to
95. beginning wiring be sure to read Safety Precautions in the beginning of this manual Turn off power to nCompass before starting installation removal wiring maintenance and inspection of the nCompass controller Failure to turn off power may cause electric shock create a fire hazard or cause damage to nCompass Emergency stop and interlocking circuits MUST be configured outside of the nCompass control system If such circuits are made through nCompass failure of the nCompass control system may cause uncontrollable operation damage to equipment or accidents This section presents recommended installation practices and procedures Since no two applications are identical these recommendations should be considered as guidelines The system designer should be aware that devices in control systems could fail and thereby create an unsafe condition Electrical interference in an operator interface can lead to equipment start up which could result in property damage and or physical injury to the equipment operator If the application requires an operator or attendant you should be aware that this potential safety hazard exists and take appropriate precautions Consult NEMA ICS 3 304 for more information regarding safety for the installation of solid state programmable control devices 3 1 Power Requirements The nCompass control system operates on a nominal 24Vdc supply voltage with an allowable range of 20 4 to 26 4Vdc Do not po
96. bits internet access nCompass can be configured to use a local time server instead of one of the national time servers To configure the use of a local time server select local from the NTP server list When selected the Name IP entry field will be shown The computer name or IP address of the computer running the local timer server on the LAN can then be entered nCompass will then contact the local computer in order to synchronize time NOTE The steps required to configure and provide NTP service from a computer on the LAN is outside the scope of this manual Contact your network administrator for assistance 9 3 2 Daylight Savings Select the Daylight tab to configure daylight saving time options The daylight savings time options allow the user to set the start date and end date for daylight savings time February 10 2012 October Daylight Savings Enable If your locale utilizes daylight savings time set the start and stop dates for daylight savings and turn on the Daylight Savings Enable option Press the Save button to store the settings nCompass will then automatically update its clock for daylight savings time NOTE If the NTS time server setting is enabled and the selected time zone uses daylight savings time daylight savings must be properly configured and enabled or the clock will not show the correct time 9 6 FDC nCompass Offline Setup FUTUREDESION c O N T R O nCompass i4
97. ccomplish another task and forgets to turn the output off NOTE Each time an output is turned on or off the output force delay timer is reset The automatic force disable time begins from the moment an output switch is pressed Offline Setup FDC nCompass 9 19 f FuTUReEDESIGN N T R O nCompass i4 3 9 11 Monitor Offset Calibration The monitor option provides up to 15 additional process inputs which can be configured from any combination of thermocouple analog and RTD inputs from the optional monitor input modules The monitor input option can also be configured to display the second input from compatible loop controllers attached to the system one from each available control loop The calibration range is fixed within the thermocouple analog and RTD monitor input cards however the user can input a linear offset in order to adjust for sensor tolerances and lead affects When the second input of a control loop is used for the monitor input the loop controller provides calibration range and input bias adjustments The input bias of the loop control can be used to set the linear offset for the input or the monitor offset calibration of nCompass can be used Offset e Current Value 29 9 Offset 0 0 The left and right navigation buttons at the upper right of the screen allow the user to scroll through each available monitor input To adjust the input reading enter the offset value in the Offset field and verify t
98. ce digital outputs on off Security View Security Configure applies to Security Setup Configuration Device Settings Offline System access to import export setup files of nNCompass Configuration Default Configuration Device Settings Offline System function to clear system configuration and reset all to Configuration Reset Default blank default state for reconfiguring Configuration button Exit run mode Device Settings Offline System Exit prevents nCompass application from being stopped Exit application automatic mode startup button Exit to Configurator Device Settings Offline System Exit prevents nCompass application from being stopped and Exit Application configuration mode access to the nCompass configurator application startup button Device Settings Offline Set Language Select help language Security FDC nCompass 6 5 f FuTUReEDESIGN N T R O nCompass i4 3 6 4 Setting Security Options The security Options tab provides the administrator the ability to set the global security options The Password Aging Days field is a global for all users Password aging starts from the day the user is entered into the system The value can be set from 0 to 365 days A value of zero disables password aging NOTE When using password aging and the password expires for a user the user will be required to change their password before access to the system is permitted A user can change their
99. ch items are to be logged Historical data file functions are provided for Opening and Deleting historical files and viewing setting data file Annotations and digital Signatures The plot Set and Chart icons provide access to the historical data viewer options Slide page 2 provides access to the FIP WAN back up settings and the memory check utility for viewing available system storage memory space FDC nCompass 4 13 f FuTUREDESIGN nCompass i4 3 N T R O 4 4 Notifications The notification window is a feature that can be accessed by pressing the date time field in the icon bar This window provides a snapshot of current nCompass activity The notification window can be closed by pressing the date time field again or is automatically closed if the Menu Home or an arrow icon is pressed D D D Kat left h pi E i a D LOOP 1 DV 11 5 SP 244 0 LOOP 2 DV 51 4 SP 0 0 LOOP 3 DV 54 8 SP OP Program Inactive Defrost Inactive K Manual Control A user can view all notifications by touching the screen and dragging their finger up or down on the list to scroll through all items like other lists in nCompass The notifications include the following e Loop PV and SP for each loop configured e Automatic program status including name of running program e Defrost operational status e Redundancy operational status e Active alarm status including the most recent alarm e Data logg
100. ch set of tools for control interaction and data analysis Views include system overviews trends alarms automatic programs as well as historical data alarm history and audit trail views The menu driven interface eliminates screen clutter by providing an easy to use Smart Device interface for interaction between the user and nCompass nCompass can store more than one year of data on its SD memory card Data logging can be enabled manually or automatically during automatic program operation Data backup is provided with the USB I Stick for plug and play transfer of files to any PC running Microsoft Windows XP operating systems and via the FTP back up utility nCompass protects system access with 4 level security user rights based audit trails that document all user activity and ensures data integrity by digitally signing all data files and audit trails to meet regulatory requirements The nCompass controller includes the following features e Single Dual loop controller models e Touch screen Smart Device user interface Ul e Email SMS FTP VNC and Web functionality standard e Remote View Control using PC Tablet or Smartphone e Detailed maintenance alarm monitoring and alarm history e User configurable data logging and historical data viewer e 4 level security with digitally signed audit trails and data files e National time server connectivity with daylight savings e Multi lingual user interface su
101. control of the loop s set point or the current program set point if a program is running If the minimum or maximum range exceeds the set point limits for the loop as set in the nCompass configuration nCompass will limit the set point to the minimum or maximum value as defined under the loop s configuration Offline Setup FDC nCompass 9 9 f FuTUReEDESIGN N T R O nCompass i4 3 9 6 Analog Outputs nCompass can support up to two analog outputs which can be used to retransmit set points process variables or percentage of output from the installed control loops Each of the available analog outputs can be configured from the Analog Output screen Analog output 1 Pe Minimum 0 0 Maximum Type Source mre Ce Function Oo The left and right navigation buttons at the upper right of the screen allow the user to scroll through each available output To make changes to the output s configuration select the desired output type by pressing the voltage Vdc or current mA button to select a 0 10V or a 4 20mA input signal NOTE If the analog output type is changed from voltage to current or vice versa power must be cycled to the nCompass controller in order for the output to switch types When nCompass is offline the outputs will go to their minimum output state 0OVdc or 4mA Select the desired source loop by pressing the Source select button to choose from the list of available control loops Select
102. control or the output will not operate When selected the output acts as a fail safe fault output When no alarm is present the output will be energized Any alarm in nCompass will de activate the output When the alarm Reset button is pressed on the Alarm screen the output will turn back on When used in conjunction with the repeat time setting the output will automatically turn back off after the repeat time period if any alarm condition is still present When selected the output will turn on during an active defrost cycle When defrost is inactive or the fan delay is active the output will be off See section 8 1 Defrost for more information on defrost operation When selected the output will turn on during the fan delay period after a defrost cycle When defrost is inactive or a defrost cycle is in progress the output will be off See section 8 1 Defrost for more information on defrost operation When selected the output will turn on when system 1 is selected for operation based on system redundancy settings See section 8 2 Redundancy for more information on redundant system operation When selected the output will turn on when system 2 is selected for operation based on system redundancy settings See section 8 2 Redundancy for more information on redundant system operation NOTE For the output control functions listed with an asterisk the output is not activated for failed FTP or email transmissions NTS cl
103. d in which case the menu for a specific user right may not be shown View Single Dual loop views applies to loop controls when not running an automatic ramp soak program does not apply to loop monitor alarms View Events applies to enable or disable manual events View Single enable or disable loop control Manual mode button View Single enable or disable loop control Automatic Tune button Program Start Hold Halt Off actions applies to all program control menu selections does not affect digital Inputs configured for same action Device Settings Set Recovery logic when running an automated ramp soak program Setpoint Edit Events Manual Control Auto Tune Program Operate Recovery when power lost amp recovery Off Hold Continue Restart or Resume View Alarm does not affect digital input alarm silence function View Alarm Clear button prevents alarm list view from being cleared Reset Alarms Clear Alarms Chart Settings View Chart affect digital input functions Annotation Data View Annotation Signature Data View Signature Open see description Save see description program save and save as note files may be copied from system with USB file transfer utilities Delete see description data files amp automatic programs note files may be deleted with File Utilities no data entry or access to Events or Step SP Time fields Program Edit Program Entry or GS Soak Limits Auto Start can t insert delete
104. data logging is running If the operator needs to back up or delete files from the system a large number of files could take considerable time to backup and delete from memory The file transfer screen will be locked during file transfer so plan the timing appropriately when access to other screen functions is not required When data logging is running the current data log file will not be copied or deleted while using the file transfer functions This protects the current file and makes sure that the data file is complete before being copied and cannot be deleted from memory while it is still in operation USB Export Type OFF OFF Note Memory stick must be inserted for file transfer To Copy files insert the USB memory stick into the USB port Select the file type you wish to copy from the Export Type drop down menu Available file selections are Program Alarm Audit and Data files Once the selection is made press the Copy button All related files will be copied to the USB memory stick with progress status displayed to user 7 6 FDC nCompass Data Logging nCompass ia3 ff eurupenesron N T R O To Copy Delete files from internal memory insert the USB memory stick into the USB port Select the file type you wish to copy and erase from nCompass internal memory by selecting it from the Export Type drop down menu Available file selections are Program files Alarm files Audit trail files and Data files
105. ded for use with the current hardware configuration of nCompass as unexpected operation may result Offline Setup FDC nCompass 9 23 f FuTUREDESIGN nCompass i4 3 N T R O Configuration Load Configuration Reset default configuration Import File Loaded When the Export button is pressed the nCompass configuration data will be written to the USB memory device The export file function will use the name entered in the text field to the right of the export button and create a directory on the memory stick with that name to contain the configuration data The filename can be entered with up to 10 characters which permits multiple configurations to be identified and saved for later retrieval The export file will be saved with a name format of cfg_filename_mm_dd_yy_hh_mm_ss to identify the configuration according to the date and time it was created This prevents multiple configuration files with the same name from overwriting previous files It also allows the user to identify a backup of nCompass so that it could be reconfigured to a previous date if multiple back ups are created The Import button is used to write the configuration data to nCompass from the currently loaded file To load a configuration file the USB memory device must first be inserted into the USB port When the Load Configuration button is pressed a list of available configuration files from the memory stick will be shown Select the desired file fr
106. dition until it is cleared and reactivates The repeat time can be set from 0 to 32 760 seconds The Digital Input Select is only available when the output is set for the Digital Input Control function The selected input will then act as the switch to turn the output on and off In order to use the input as a switch for the output the digital input must be set for the Alarm Input or Control Output function See Section 9 7 Digital Inputs for more information The digital output Function defines what condition causes the output to turn on and off 9 16 FDC nCompass Offline Setup nCompass ia3 ff eurupenesron N T R O The Output Function list is shown when the function selection button is pressed The output functions selections are mutually exclusive i e only one can be made at a time If Program is in Operation is currently selected for the output function and another function such as Program Paused is then selected as the output function the program in operation function will automatically be turned off An output can also be disabled by turning off all of the output functions Once the desired selection has been made press the Return Button to return to the Digital Output screen Function OFF Program is in Operation F OFF Program Paused OFF Step Change Event When selected the output is controlled directly from the corresponding event on the Events screen When the event is sel
107. dule options are packaged separately and like the FC AA Note Each I O card has qty 2 Remote Setpoint input and quantity 1 Retransmission HPC3 must be plugged into the FCSA D16RA1 bus as described in the manuals output configurable for PV SP or Percent Output The exception is the Monitor Card s which are not part of the FC5A D16RA1 bus and have separate power supply and RS485 communication wiring The Monitor Card serial RS485 is wired to the FC4A HPC32 board along with any loop controls A 22 FDC nCompass APPENDIX nCompass i4 3 NOTES SCADA Supervisory Control amp Data Acquisition FDC nCompass Series Graphic User Interface GUI touch screen provides a full SCADA feature set providing ease of use with either an icon menu system with finger navigation or traditional Menu bar data acquisition alarm manager operator audit trail multi level security with user rights LAN connections and more The GUI provides ease of configuration use amp support System Configuration for loop monitor point alarm digital input amp outputs assignment logic Help language selection and more all without an external device or PC Loop Views view Loop and or Monitor Points in single or dual View and also in Trend format Ramp Soak Programs Virtually unlimited number of programs with each program having up to 99 steps with up to 16 events File Management View print copy move Program Alarm Historical Data data log files
108. duwur Type Tt Ponts and Common Lines Rated Load Volare Opera dng Load Voltage Range Rated Load Current Makmim Load Curent at Zn DN LN voltage Drop ON Voltage Irguzi Curent Leakage Curent Camping Voltage Maximum Lamp Load Inductive Load Extema Current Dram laHa ton Conmachor on Mother board PC 4A TOBSL Transistor source output 6 points in 1 common line Z D 20 4 To ZEN D GSA IerOoutpUt point SA PE rOutput point 3A per common line 1y maximum VOLS between COM and output terminals when output is on LA Mae inn ur 1 mA maximum 20 IM Gw L R 10 ms 26 6 DC 1 He LOD mA maximum 24 DE power voltage at the v teminal Between output te miinal and internal cimuit Photocouper isolated Between Output te minals Mot isolated MCLBIIDS 3 EIER Phoenix Contact COnReECt Or Ins dog Removal Lara 100 times minimum imema Current Craw imema Power Com upton fat 24 OC while all Outputs OM ouput Diay Waem approx Output intemal Circult APPENDIX Source Out hitara Croat ALL OUR Of ALL OU OFF 10 mA tS DE 20 mA 24 DE B rr SC DC O mAtz4y DE CO PEW Tum cN time a US maximum TUM FF time a WS maximum es o a FDC nCompass FUTUREDESION A 13 FUTUREDESION c O N T R O nCompass i4 3 Digital Output Card Specifications page 2 of 2 Rebay Out out Module Speciicatlons Type Ao FC4A ROL FC44 R161 MT Ponts amdi Common Lines amp AO contacts in
109. e alerts is for on time and is adjustable from 0 0 to 400 000 000 0 hours To adjust a counter set point select the output from the list by touching its description The current set point for that output will be shown in the set point field at the bottom of the screen Enter the new set point by touching the set point field and press the Done button on the numeric keypad when finished NOTE To adjust the cycle counter you must be viewing the elapsed interval or life total counts for the outputs To adjust the set point for hours of operation you must be viewing the elapsed run or total life hours of the outputs See section 9 1 1 Service Options When a service interval is exceeded a service alert can be set to appear on the alarm screen This alert will notify the operator that service should be performed at the next available down period However the alert will not be able to be cleared from the alarm screen until the service counter that has been exceeded is reset In order to determine which service counter has been elapsed scan the list of outputs and look for the Exceeded description To clear the counter select the output from the list and press the Clear button This will clear the counter so that it can begin totalizing for the next service interval 9 2 FDC nCompass Offline Setup nCompass ia3 ff eurupenesron N T R O 9 1 1 Service Options The service display options as well as alert action c
110. e touch the Entry field at the bottom of the screen and enter the message up to 16 characters maximum Press the Add button and the message will be added to the current log file If the running log file was opened as the historical log file the annotation will be shown immediately on the screen as it is added If logging is not currently running the entry field will be disabled Data Logging FDC nCompass 7 9 f FuTUReEDESIGN N T R O nCompass i4 3 7 7 Add View Digital Signatures The Signature screen allows the user to add digital signatures to historical data log files and view any digital signatures currently associated with the loaded historical log file Signature Data file is not active Lf1 f2013 2 03 PM User Device Manager When a historical data file is loaded the Signature screen will display any signatures currently associated with the file To verify a digital signature and insure that the data file has not been altered touch the signature in the list box and press the Verify button nCompass will compare the signature to the log file to see if any alterations to the data have been made nCompass will then indicate if the signature is valid or not If the signature is valid the historical data file is intact and has not been altered If the signature is invalid the data has been altered at some time after the signature was assigned to the file For data integrity nCompass automatically si
111. e a new file is started To do this turn off the Fixed Interval option and enter in the desired logging rate in seconds NOTE Logging at shorter intervals allows nCompass to capture fast changing processes but the data files can become extremely large Files that exceed the capability of the nCompass data viewer gt 520KB in size will have to be extracted from nCompass using a USB memory stick or FTP file transfer in order to be viewed remotely on a PC Files larger than the 520KB limit will not be automatically digitally signed by nCompass If the files are to be digitally signed this must be done manually by extracting the files and using the FDC data viewer program running on a remote PC To manually start data logging press the Data button Any time logging is enabled the indicator on the Data button will be illuminated To stop data logging press the Data button again Data logging can also be started automatically by turning on the Start or Program option The Start option automatically turns data logging on whenever nCompass is first powered on This action simulates that of a standard chart recorder The Program option is a convenient method for gathering information that pertains only to the operation of an automated ramp soak program When selected nCompass will turn the data logger on at the beginning of a program and off once the program is completed This eliminates the need to scan through extensive da
112. e same event selections selecting Clone from the Step menu will then copy the selections to all other steps of the program This feature can be used on any step of the program so if event selections then change on step 5 the function can be used again and all steps after step 5 will then have event selections of step 5 copied to them leaving steps 1 4 with the previous Selections 5 1 4 Setting Wait For Conditions The Wait For function is a powerful tool for pausing a program until selected process variables loops and or monitors reach a predefined set point This differs from the guaranteed soak function by being a single shot monitor With the guaranteed soak the process variable is monitored throughout the whole step If the process exceeds the limit the program will pause until the process returns to within the limit setting The wait for function pauses the program and waits for the process to reach a particular value that is set for the step Once the process reaches this set point value the program automatically resumes operation The program can also be set to wait for a digital input This allows any of the available inputs on the nCompass control module to be selected input must also be configured as a wait for input When the step is reached it will wait for the input to change state before continuing the step Any combination of loops monitors and inputs can be set for a step but all of them must meet the w
113. e used for remote set point inputs Each of the available analog inputs can be configured from the Analog Input screen Analog Input 1 Se Minimum 0 0 Maximum Type Destination Cam E Function None The left and right navigation buttons at the upper right of the screen allow the user to scroll through each available input To make changes to the analog input s configuration select the desired input type by pressing the voltage Vdc or current mA button to select a 2 10V or a 4 20mA input signal NOTE Ifthe analog input type is changed from voltage to current or vice versa power must be cycled to the nCompass controller in order for the input to switch signal types Select the desired loop by pressing the Destination button to select from the list of available control loops Destination opt LOOP 2 OFF LOOP 3 Select the desired control loop and press the Return button to return to the Analog Input screen Enter the desired minimum and maximum values for the loop set point that the input is to represent The input range is 32760 to 32760 for a decimal point resolution of zero 3276 0 to 3276 0 for a decimal point of one 327 60 to 327 60 for a decimal point of two and 32 760 to 32 760 for a decimal point resolution of three 9 8 FDC nCompass Offline Setup nCompass ia3 ff eurupenesron N T R O The function select buttons None and SP enable and disable the analog input
114. e user can access control loop and nCompass runtime settings Offline Setup FDC nCompass 9 25 f FuTUReEDESIGN N T R O nCompass i4 3 10 Communications This section provides instructions on how to use the nCompass communication interfaces As a standard nCompass is equipped with an Ethernet interface and offers an optional RS485 serial interface for user communications 10 1 Ethernet Communications nCompass provides two forms of Ethernet communication interfaces for monitoring and controlling the system across a network The web server interface provides a monitor only connection while the VNC server interface allows a user to manipulate and control the nCompass remotely by viewing the nCompass display directly on their PC screen NOTE n order to use Ethernet communications nCompass must be properly connected to a network To connect nCompass to a network connect the touch screen s Ethernet port to your network using a Standard CAT5 cable connection Note that after connecting the network cable it may be necessary to cycle power to nCompass in order for it to obtain a valid IP address 10 1 1 Guide to Smart Networking Practices The expansion of Ethernet onto the industrial floor has brought forth a new realm of possibilities from the gathering of information to the inherent control of equipment from anywhere around the world The flexibility and convenience that this provides makes it a very desirable feature for new equipment
115. ected the output turns on When the event is not selected the output turns off NOTE Outputs can be assigned to specific events in the nCompass configurator If an output is assigned as a system event in the configurator the output function will not be able to be changed Consult your OEM configuration for output assignments Program is in Operation When selected the output will turn on when a ramp soak program is active The operating condition is defined as a ramp soak guaranteed soak or wait for condition The output will not be on if the program is in autostart since it has not yet started or when it is placed in hold by an operator Program Paused When selected the output will turn on when the program is in hold When the program is in any other condition the output will be off Step Change When selected the output will provide a one shot pulse each time the program changes steps This also includes an output pulse each time the program is manually advanced to the previous or next step while in hold When used in conjunction with the delay stop time this can be used for a brief audible visual alert signal to tell operators that a step of the process has completed and the next one is starting NOTE When a program is started the output will pulse when the first step of the program is entered Offline Setup FDC nCompass 9 17 f FuTUReEDESIGN Remote Alarm NO Analog Input Alarm Digital Input Alarm Digi
116. ed nCompass display and Control Module Idec PLC software listed as SOFTWARE in this document is protected by copyright laws and international copyright treaties as well as other intellectual property laws and treaties The SOFTWARE is licensed at no charge to the end user when all components including but not limited to the Control Module Idec PLC components and CE Color Touch Screen display are purchased from Future Design Controls All ownership and rights remain with Future Design Controls I LICENSE GRANT This LICENSE grants you the following rights A You may use Future Design s SOFTWARE with Future Design Controls products or products marketed by Future Design Controls only Products are considered Future Design Controls products and products marketed by Future Design Controls when the sale or shipment originates from our main headquarters in Bridgeview IL or one of our authorized office locations Products purchased from Future Design Controls distributors or OEM s with brand labels other than Future Design controls are not considered Future Design Controls products and cannot be used with Future Designs SOFTWARE Using Future Design s SOFTWARE with any other manufacturer or distributor of hardware is a violation of this license and applicable copyright laws The SOFTWARE is considered in use when it is installed into permanent or temporary memory e g CE display unit PLC or other storage device B Solely with respect
117. ed to the DC ground bar This insures that any electrical noise or stray voltages that come across the AC power wiring or DC power wiring is distributed evenly across the DC ground bar to reduce the chance for voltage imbalances between different components of the control system Es E E oe a EA i LVEOTYV OJ amp d i i ai JIS YS94 LOD Lett LVEOTVPO4 o L P oO ES S i Power Supply Ground Control Module Card Grounding Conductors Central Earth Ground K Isolated DC E Ground Bar Cu e around from he 10 awg minimum ground wire a Touch Screen Wiring FDC nCompass 30 f FuTUReEDESIGN N T R O nCompass i4 3 3 3 Connecting to the nCompass Interface Power wiring lengths should be kept to a minimum and it is preferable to have the power wiring run using a minimum of 18 2 twisted shielded cable This keeps the hot and common wires paired to minimize the affects of external noise To make a connection strip about AT of insulation off the end of the wire turn the connector screw counterclockwise until the gap is wide open insert the wire all the way in and turn the screw clockwise until it s tight Connect positive DC line to the terminal and the negative DC line common to the terminal The other end of the cable should be properly terminated at the 24Vdc power source and the shield connected to the main earth ground NOTE Upon application of power
118. eight FCIAKIAL Saa FGALOSAPI FOMAI 24V DC 20 4 to 28 8V BC S Analog 0 Modul Terminal Arrangament on pages 247 and 2 18 MCL 6 1 7 6 3 81 BK Phoenix Contact 100 times minimum BO ma B DE EO m GY DC GO mA SV D BO mA GY DE O mA 24 DE D mA 24 DC OmA LAV D O mA 24V DE 45 mA 24V DC 40 m 24V 00 35 m 24V DO 40 mA 24V D Bog Note The extemal current draw is the value when all analog inputs ar used and the analog output value is at 100 Analog Input Specifications Analog Input Signal Type Input Ranga Input Impedance Allowable Conductor Resistance per wire Input Detection Current Sample Duration Tine Sample Repetition Time Total Input System Transfer Time Type of Input Operating Mode Conversion Method Maximum Error at 25 C WW i Resistance Type K A to ps F 100 Oto 10V DC dro 20 m DC ype Swine type 0 to 12000 Type T 0 to 400 C 1 MA minimu 20 msec madmium it to bm i MD minimum 200 masimu 1 0 m maximum ZU mas maximum 20 msec maximum 20 msec maeimunm 105 meec 1 scan time Note 1 200 mess 1 aan time Note 1 Input Error Temperature Coefficient 0 006 of full scale C Repeatability after Stahilization Time Nonmlineality 0 2 of full scale 1 of fill 2a Digital Resolution Input Value of LSB A 10 FDC nCompass Singkendec ipui Differential ri put Self acan EA type ADC 20 2 of ful Sak plus refe
119. er login security settings and audit trail viewing if the security system is enabled The Data menu provides access to data log functions file utilities FTP WAN back up settings as well as the historical data viewer Basic Operation f FuTUReEDESIGN N T R O nCompass i4 3 4 3 1 2 Icon Slide Page Based Home Menu 6 28 2013 Slide page 1 provides navigation to 6 41 AM Aa my all standard view screens These include the Single and Dual views Events control Charts Digital I O monitor Alarms monitor and Alarm File Events It also provides quick access to the A nCompass Settings and Data file d 5 functions which include file utilities Alarm FTP WAN back up settings as well as the historical data viewer Alarm File SS AE 6 28 2013 i Slide page 2 provides access to 6 42 AM Aa m automatic ramp soak program actions Entry and Status views Start Hold and Halt program menu items allow quick access to these functions if a program is already downloaded to the nCompass control module 6 28 2013 Slide page 3 provides access to a l security settings Audit trail viewing 6 42 AM l current User information user Password editing and user Login and Log Off functions Configure Password Basic Operation FDC nCompass 4 5 f FuTUREDESIGN nCompass ia3 N T R O 4 3 2 Automatic Ramp Soak Program Menu The automatic ramp soak program menu is provided when the user selects either Entry
120. erator events into the historical data file there is no limit to the number of events that may be entered manually or with a bar code scanner Note If Serial Communication is used the RS 485 module must be included i e if bar code reader is used both the RS 485 and the RS 232 used for bar code reader modules must be specified A 24 FDC nCompass nCompass i4 3 NOTES Language Configuration nCompass provides a one button language configuration for the following languages e Afrikaans Albanian Arabic Basque Belarusian Chinese Simplified Chinese Traditional Czech Danish Dutch English Finnish French German Greek Hebrew Hungarian Icelandic Italian Japanese Korean Norwegian Polish Portuguese Russian Spanish Swedish Turkish P O Box 1196 888 751 5444 Sales Bridgeview IL 60455 888 307 8014 Fax Technical Support 866 342 5332 http www futuredesigncontrols com APPENDIX nCompass i4 3 ff eurupenesron N T R O SOFTWARE VERSIONS FOR FDC nCompass Control System The software version levels for the nCompass Control system can be viewed in the offline system setup from the System menu select About nCompass Both the HMI Human Machine Interface color touch screen and Control Module Idec PLC firmware and software versions will be displayed CE Net Yersion 6 0 CM Firmware 2 24 HMI ersion 1 0 CM Program 1 4 FD30 CE Image Yer 1 23 FDC CE BSP Yer 1 44 FDC When obta
121. es and prevent malfunction that can be caused by rising or falling voltage at the power supply output during power interruption NOTE It is recommended that the time delay on relay be set for a minimum period of 12 15 seconds to insure proper operation of the nCompass control system AC Power Source SM KIC M howen GEIA on GE1A C Delayed DPDT D ACIDC Power ZN Supply pe oF LF PH Ore nloampass 3 2 FDC nCompass Wiring nCompass ia3 ff eurupenesron N T R O 3 2 Grounding Requirements Proper grounding is critical to the performance and reliability of nCompass Most of the problems in electrical systems can be attributed to poor or improper grounding techniques as well as poor earth grounds at the installation site Control systems like nCompass which contain sensor and communication wiring as well as sensitive electronics are particularly acceptable to stray electrical transients Proper wire routing away from sources of high power AC or inductive DC circuits and the use of shielded cables for sensor and communications wiring must be considered carefully Ground conductors should be as short and as large in size as is feasible Each ground conductor should be individually run back to the central earth grounding point for the system Ground conductors should not be daisy chained or branched off from one device to another This can cause an imbalance in the ground potential at each device in the system which can induce elec
122. es that are not intended for use with the current hardware configuration of nCompass Once the import or configuration reset is complete you must cycle power to nCompass so that the configuration data is properly loaded into the nCompass runtime and control module memory locations 9 24 FDC nCompass Offline Setup f FuTUReEDESIGN N T R O nCompass i4 3 9 14 About nCompass The About nCompass screen provides operating system version numbers for the currently installed firmware and program of both the nCompass HMI and control module This information should be recorded prior to any service request so that proper assistance can be provided for your control model CE Net ersion 6 0 CM Firmware 2 24 HMI ersion 1 0 CM Program Y1 4 FD30 CE Image Yer 1 43 FOC CE BSP Yer 1 44 FBC 9 15 Exit Application The Exit Application screen allows the user to quit the nCompass runtime software and return to the CE Net operating system This operation is NOT recommended with the exception of users who are in charge of system configuration due to the danger of editing or removing files by accident Exit Application Exit application automatic mode startup Exit application configuration mode startup The automatic mode startup option will return nCompass to normal operation on the next power up The configuration mode startup option will start the nCompass configurator program on the next power up so that th
123. eset button is pressed The concurrent Minimum Time is shown when redundancy is configured for concurrent operation This entry defines the minimum amount of time that the back up system will operate when a redundancy alarm occurs This field can be set from 0 to 32767 minutes The Alternate button is provided when redundancy is configured to switch after defrost It provides access to the Alternate settings screen Alte rnate iibi Stamm Alternate HH MM Interval minute The Alternating HH MM fields are used to set the time of day 24 hour clock at which the equal run time interval will begin If it is 8AM for example and the time of day is set for 12 00 the equal run time interval will begin at noon NOTE If redundancy was operating in manual mode and not placed into auto until 12 01 the equal run time interval would not begin until the following day at noon Redundancy must be in auto mode when the time of day elapses for the interval timer to begin Each time redundancy is placed in manual mode or redundancy is inactive due to the system being turned off the interval timer will be reset and will not begin again until redundancy is active in auto mode and the time of day Is reached The alternating switch Interval defines the equal run time duration for each system when redundancy is operating in auto mode Once the interval timer is activated according to the time of day entry the primary system will alternate
124. ess the Save button at the lower right of the screen in order to save the changes to the alarm If you do not press Save prior to leaving the screen or going to the next alarm all changes will be lost and the alarm will maintain its previous configuration The alarm number AL in the upper left of the display shows the current alarm being configured The left and right scroll buttons at the upper right of the screen allow the user access each alarm in the system by pressing left or right to go to the previous or next alarm The Input selection is used to select the loop or monitor input that will be monitored by the alarm The same loop or monitor input can be used more than once for any alarm The alarm Type selection is used to set the type of alarm When set to Off the alarm is disabled Available alarm type selections are as follows Absolute An absolute alarm uses one or two set points to define a specific alarm value An absolute alarm can be set for high only low only or both high and low Deviation A deviation alarm uses one or two set points that are defined relative to the control set point High and low alarm set points are calculated by adding and or subtracting offset values from the control set point If the set point changes the window defined by the alarm set points automatically changes with it A deviation alarm can be set for high only low only or both high and low NOTE The deviation alarm type i
125. etal Detals S Communication Ports Interfaces USB Host A USB Host General Specifications A 2 FDC nCompass APPENDIX f FuTUReEDESIGN N T R O nCompass i4 3 FDC 0450 Touch Screen Interface Specifications page 2 of 3 Standards Certificates and Approvals Details UL 508 and CSA C22 2 No 142 2006 95 EC 2004 108 EC Requirements for Emission EN 61000 6 4 2007 EN 61000 6 2 2005 AS NZS CISPR 11 2004 FCC Part 15 Subpart B Class A Base Standards for EMC amp Safety Details EC 61000 4 2 2008 EC 61000 4 3 2006 A1 2007 A2 2010 EC 61000 4 4 2004 A1 2010 EC 61000 4 5 2005 Conducted disturbances induced by radio IEC 61000 4 6 2008 frequency fields IEC 61000 4 8 2009 Voltage dips short interruptions and voltage IEC 61000 4 11 2004 variations CISPR 11 2009 A1 2010 Class A IEC61000 3 2 2005 A1 2008 A2 2009 IEC61000 3 3 2008 EN61010 1 2001 Protective class IP 66K Front IP20 housing and terminals Transport amp Storage conditions Details 20C to 60C Relative Humidity 10 to 90 no condensation Altitude 2000 meters maximum Sinusoidal vibration conforming to IEC 60068 2 6 5 to 10 Hz 3 5 mm amplitude 10 to 150 Hz 2g 1o0ct min 40 sweeps Shock conforming to IEC 60068 2 29 3 shocks per direction 11ms 15g Best conditions for storage of LCD display modules Room ambient temperature 15 C to 35 C and 65 RH or less Do not store in surroundings containing orga
126. event recipients from receiving the email It can also be useful for identifying a particular unit on the factory floor Once all settings have been made be sure to press the Save button to begin using the new values and store them so that on the next power up the settings will be retained The body of the email SMS text message will contain the description of the alarm condition as it would appear on the alarm screen If the mail server is down or nCompass is not connected to the network the message will not be sent and a local alarm message on the alarm screen will indicate a transmission failure 8 10 4 Email Message nCompass provides the user with the ability to send short email messages to users configured in the nCompass email server To send a message select Message from the device settings Email menu Email Message Compose Press the Compose button to create a brief message using the keypad up to 100 characters When you are finished entering the message press the Done button The completed message will then be shown in the message window Press the Send button to select the email recipients you wish to receive the message and send the message Device Settings FDC nCompass 8 23 f FuTUReEDESIGN N T R O nCompass i4 3 9 Offline The offline setup options are available from the Device Settings menu These settings do not include the OEM setup of nCompass
127. for Honeywell 2500 3200 note 1 3 1O 8AIIS 8 input module 0 20 4 20mA isolated 4 HWDL CM software for Honeywell 3500 note 2 4 1O 8AIVS 8 analog input 0 10 2 10Vdc isolated 5 WTSD CM software for Watlow SD 6 WTPM CM software for Watlow PM Combination Monitor Input Modules maximum of 2 amp 15 points 7 DHPL CM software for Danaher West Partlow Plus A Item 1 qty 2 F ltems1 amp 3 8 YKGS CM software for Yokogawa UT Green Series B Item 2 qty 2 G Items 1 amp 4 9 Special C Item 3 qty 2 H ltems2 amp 3 D ltem 4 qty2 l Items 2 amp 4 E ltems1 amp 2 J Items3 amp 4 2 Optional Serial Communications DIN Rail Mount plug into CM Note Maximum of 2 monitor input cards monitoring a maximum of 15 monitor card 0 None inputs 1 FC5A SIF4 RS485 Modbus RTU port slave port 3 2 FC5A SIF2 RS232 port for Barcode Reader port 4 7 Special Note If Item 2 is specified Item 1 is included and must be installed for proper operation of the barcode reader 0 None RS 485 Modbus RTU port allows R W access by FDC EnVision amp 3rd party software Bar Code Reader input is compatible for serial based barcode readers Note 1 Maximum of 2 monitor input cards monitoring a maximum of 15 monitor card inputs With specific CM software the loop control s input 2 may be configured as a monitor point System maximum of 15 monitor points made up of 3 Optional Digital Inputs DIN Rail Mount plug into CM loop cont
128. for the opening AmbentOperating Temperature Ci AIIDEC power supplies ara listed to UL OR which allows The chart above show thatthe PS5A Slim GOW at 55 C operation at 100 capacity inside a panel This eliminates meet the ambient temperatura required by the UI S508 and the need to use oversize power supplies or utilize two power EN 60950 standards to operate at an output current of 100 supplies derated 50 of their rated output The output current starts to dearate beyond the required tamperature A Mounting B Mounting Mounting Style A RR istandard Mou nting style B Facing upward Jere Dimensions PSSR SD24 60W Height 95 0 mm Width 36 0 mm Depth 108 0 mm p ELF A 18 FDC nCompass APPENDIX E Power On Delay Relay Specifications page 1 of 2 FUTUREDESION c O N T R O nCompass i4 3 GE1A C10MA110 Speciications LL cUL Listed WS File No E9 CH TUY Rheinland Z AL ZIL Rated parating Vokage 100 t0120 AC 220 to z4 AC AC t0110 Vo kage Tobrance CO to 110 240 AL EA Contact Rating say DE Contact Form OPOT or SPOT instantaneous SPOT Repeat En or 402 ClUrees maxim Voltage bro 405 Clees maximurn mgwrabure Eno 3 Maximum Setting bro 10 maximum Reset Tine 01 sx maximum mu hiin Aes ktanma TDW minimum UN DE megge 3 Betweay Daer 3 nd output terminals 1500 AC 1 minute EE Between contact CH uRS o0 A 1 minute oo Carnage limits Amplitude 075mm 10 to 5
129. gns a data file when logging is stopped however this only occurs if the Auto Interval is selected on the Log screen If a different logging interval is used nCompass will not automatically sign the file and it must be signed by a user To add a digital signature to the historical log file touch the Entry field at the bottom of the screen and enter in the comment line for the signature up to 16 characters maximum Press the Add button and the signature will be added to the log file The signature includes the date and time of the signature the user name and comment line If a user is not logged into the system the default user name Device Manager will be used as the user NOTE The Signature screen is not available if security is disabled The nCompass security module must be enabled in order to digitally sign data log files See Section 6 Security 7 10 FDC nCompass Data Logging FUTUREDESION c O N T R O nCompass i4 3 fil 8 Device Settings This section covers the use of extended controller features that enhance the functionality of your system To gain access to the nCompass setup options select Settings from the home Device menu To assist in setup and documentation of nCompass see the Orion M iSeries Configuration and Worksheets Excel file provided on the Future Design Controls website http www futuredesigncontrols com Orion M htm This document provides setup and configuration form
130. gs Set Limit applies to loop controls does not apply to loop monitor alarms Adjust Alarms Device Settings Set Alarm applies to all loop and monitor point alarms O 4 FDC nCompass Security FUTUREDESION c O N T R O nCompass i4 3 fil Service Device Settings Offline View Service applies to counter set point entry and clearing counters Options service Device Settings Offline View Options service notification enable disable Calibrate Touch Device Settings Offline System Display access to the touch screen calibration utility Backlight Device Settings Offline System Display access to edit backlight settings for brightness and off delay time Alarm Volume Units Clock S 7 Daylight Savings evice Settings Offline Set Clock enable Daylight Savings Time DST Offset Calibration evice Settings Offline Calibrate Offset Analog Inputs Device Settings Offline Hardware configure Analog Input s to act as remote set points for Analog Inputs specific loop controls Analog Outputs Device Settings Offline Hardware configuration of PV SP or out retransmission from Analog Outputs specific loop controls Digital Inputs Device Settings Offline Hardware configure Digital Inputs Digital Inputs NTP evice Settings Offline Set Clock enable amp choose National Time Server location Digital Outputs Device Settings Offline Hardware configure Digital Outputs Digital Outputs Force Device Settings Offline Hardware Force access to for
131. h the ability to adjust the date time calibrate the touch screen configure digital and analog lO etc It also includes access to the optional Barcode reader as well as the Redundancy operation setup screen FDC nCompass 4 9 f FuTUREDESIGN nCompass i4 3 N T R O 4 3 4 Offline Menu The offline menu is provided when the user selects Offline from the device settings Offline menu See section 9 on Offline Settings for information on these settings and their use NOTE Offline settings can only be accessed when an automated ramplsoak program is not running and data logging is turned off When entering offline setup nCompass will go offline This means that all outputs and control functions provided by the control module will stop and be disabled If the current control process can not be interrupted DO NOT enter offline setup until the process can be properly stopped 4 3 4 1 Text Based Offline Menu The View menu provides navigation back to the device settings menu and to the Service items view and Service Options screens d Settings Set Options Hardware Calibrate System gt The Set menu provides access to the temperature Units selection NTS Clock and Language settings Hardware gt Clock Calibrate Language System gt Analog Input The Hardware menu provides configuration access to the nCompass digital and analog inputs and outputs if av
132. hange independently of the other set points in order to arrive at the target set point when the time left in the step reaches zero To enter the set points and time for a step touch the time set point list view at the bottom of the Entry screen This will display the Step Data screen To enter the step time touch the individual Hours Minutes and Seconds fields to enter in the desired time duration To enter the set point for a loop touch the set point field for the loop and enter the desired set point ll S1 Step Data Retur o Minute Second 0 A LOOP 1 C orr Mex LOOP 2 oRH OFF EE LOOP 3 C OFF I Soak The set point entered for a loop will be the target set point value that nCompass is to achieve by the end of the step Thus based on the time entered and the set point for the loop from the previous step the step will either be a ramp step or a soak step Entering a Soak Step The set point entry for a step defines the target set point i e the set point that will be achieved by the end of the step Thus if the set point of the step matches the set point for the control loop from the previous step the loop will soak i e remain at that set point for the entire step creating a soak step Entering a Ramp Step A ramp step is merely a step with a set point that is different from the previous step The loop s set point will then ramp from the previous set point to the set point of the cur
133. he OK button This will set the selections to the default start settings for the VNC viewer FUTUREDESIGN nCompass ia 3 VNC Viewer Options Display Inputs Connection Printing Expert Menukey Monitor MRUEntries 20 a O e e Hextile True Betten Us Zeep Proxy ype ProxyUserName RelativePtr False ScalePrintQutput True Scaling None SecurityNotificationtimeout 2500 SelectDesktop SendkeyEvents False SendPointerEvents True Caora aT awt Esleo M Use these settings for all new connections sei cana 10 1 4 2 Recommended VNC Viewer Settings for Tablets The VNC clients for tablets have been found to offer limited flexibility for use with nCompass Most clients have default settings requiring security to be enabled on the server in order to connect If you have trouble connecting with a VNC viewer through an iPad iPhone or even an Android based phone start by enabling the security on the nCompass VNC server and be sure to enter those settings in the client viewer Color and encoding options can also affect the connectivity If the client offers the option leave color and encoding options to automatically detect or server decides If the client is still unable to connect try default encoding of Hextile and set the color option to limited colors such as 256 bit color Future Design Controls does not write or create VNC clients 3rd party software so final selecti
134. he reading The offset range is 32760 to 32 760 for a decimal point resolution of zero 3276 0 to 3276 0 for a decimal point of one 327 60 to 327 60 for a decimal point of two and 32 760 to 32 760 for a decimal point resolution of three Be sure to press the Save button to save the new offset value before proceeding onto other inputs or exiting the monitor input offset screen or the offset value will revert back to its original value NOTE If using the monitor input offset of nCompass to offset the reading for the second input of a loop control the value for the monitor input as shown on nCompass will not match that on the loop controller s display The monitor input offset of nCompass only offsets the reading on the display not on the loop control Therefore to avoid confusion when using the second input of the loop controls for monitor points it is recommended that any input offset is applied through the loop controller s input bias setting and not the monitor input offset of nCompass 9 20 FDC nCompass Offline Setup f FuTUReEDESIGN N T R O nCompass i4 3 9 12 Display Settings The Display screen provides access to the touch screen calibration utility back light settings and alarm volume Display Calibrate Touch Back Light Alarm Yolume Alarm Test 10 The Alarm Volume adjusts how loud the internal alarm buzzer of nCompass will be when activated under an alarm condition The volume can be set from O
135. he code and insert it as an annotation into a running log file If multiple bar codes are scanned too quickly nCompass may miss a scan because it is still processing the previous bar code 8 20 FDC nCompass Device Settings FUTUREDESION c O N T R O nCompass i4 3 fil 8 10 Email The nCompass email server has the ability to send alarm messages to email and SMS addresses Up to 30 addresses can be programmed into the system Each one can be configured to receive emails SMS text messages or both When an alarm occurs nCompass will send an alert to the specified address for each user in the list The email settings are accessed by selecting Email from the setup Email menu 8 10 1 Email Address Entry Select the New tab to add new email addresses to the system For each entry enter the recipients Name Email Address and or SMS Number up to 50 characters each Turn on the Email Alarm and or SMS Alarm options to specify which addresses the alarm messages are to be sent to Press the Create button to add the user to the list New Addresses Settings SMS Number Bill Smith 01734567890phone com Email Address smith mycompany on Create NOTE The SMS address is specific to the service provider Each service provider has their own unique address however the phone number is always the name for the address entry Below are common examples for some of the more common cell phone providers
136. he environment Shielded twisted pair STP cable is naturally more noise immune and is preferable to unshielded twisted pair or UTP in noisy situations STP should have at least 40dB CMRR and less than 0 1pF capacitance unbalance per foot Ground STP cable making sure the ground is connected only at one end CAT5 STP patch panels normally provide a grounding strip or bar Hubs and switches don t provide grounding use cables It s wise to be pessimistic about a cable s ability to reject noise from 230 VAC and 460 VAC power lines and electrically noisy equipment in the area Capacitance imbalance in cables greater than 7OpF per 100m can introduce harmonic distortion resulting in bit errors The cost of cable is quite small compared to total equipment cost so if you re looking to save money this is not a place to do it Choose a well designed cable to minimize bit error rate after installation and that will give faster throughput with fewer glitches 10 1 2 Configuring the nCompass Network In order to connect to the VNC server or web server of nCompass you will need to Know the IP address of nCompass on the network It is important to note that if using DHCP in your network router the nCompass address may change on re power requiring you to access the nCompass controller directly in order to obtain the new IP address This could result in VNC web server connection issues if the address regularly changes Therefore it is recommended that
137. his screen to observe program operation LOOP 1 d Target SP 275 00 i Status Start End Step Time Wait Jump Cycles Wait SP Status indicates the current operating mode of the program i e active hold ramp steady waiting etc Start indicates the date and time at which the program was started End is the calculated stop date and time for the program Step indicates the step number currently being executed Time is the time remaining in the current step Wait indicates the input s being monitored if a wait for condition is present Wait SP shows the set point or digital input number for the wait for condition if active Jump indicates the step number that program will jump to at the completion of the current step Cycles indicates the number of jumps remaining for the step if any The loop set points for the current step can be viewed at the top of the screen by pressing the left and right scroll buttons to cycle through each loop configured in the system Note that the set points shown here are the target set points not the actual set points the loops are controlling to To view the actual control set point see the Single or Dual view screens 5 12 FDC nCompass Automatic Program Operation f FuTUReEDESIGN N T R O nCompass i4 3 5 4 Common Questions About Ramp Soak Program Operation 1 How do I start or run a ramp soak program To select and start a program you must be on the Entry or Statu
138. hown on your desktop The image will be a duplicate of what is on the nCompass As you manipulate the screen the display of nCompass will also be manipulated so that any local operator will be able to see what is happening and vice versa 100 0 a REPRAP AE AARP EI PAERATA JOKER E Manual Control a Automatic Tune Multiple instances of the VNC viewer can be started on your PC By running multiple viewers you can have access to multiple nCompass controllers right from your desktop The heading of each VNC viewer window will use the VNC Device Name entry for the header By entering a unique name for each nCompass you can identify each VNC connection and know which system you are accessing The VNC viewer is meant to be used for short term control access to nCompass It is not meant for long term monitoring of system operation If long term monitoring access is desired use the built in web server of nCompass or a PC with FDC software to monitor and control nCompass over its serial communications port The web server interface and PC software is designed for long term monitoring and status updates Due to the nature of VNC operation and for security reasons the VNC viewer connection should not be left open on your desktop The viewer connection should be opened in order to perform the necessary control and or status check of system operation and then closed once the task is complete Accidental manipulation of
139. i A LOS APA 130 msec FOAAK LAL BO mes FA ALO LO meee 1 scan time Total Output System Transfer Time FCA A LOSAPH 130 msec 1 sean tire FOAAK TAL BO meee 1 scan time Maximum Error at 25 C 0 2 of full scale Repeatability after BY i Stabilization Time 0 5 of full scale Output 0 2 of full scale 1 LSE maximum om 1 of full scale Digital Resolution 4096 increments 12 bits 0 te 4095 12 bit data 32768 to 32767 optional range designation Note 2 Data Type in Application Program APPENDIX FDC nCompass A 11 FUTUREDESION c O N T R O nCompass i4 3 Analog Input Output Card Specifications page 3 of 3 A 12 Analog Output Signal Type Voltage Out part Current Output Moanotonicity yes Current Loop Open ee EE Maximum Temporary Deviation during I mamun Moise Electrical Noise Tests Resistance Twisted pair shielded cable is recommended for improved noise irimunity Ho crosstalk because of 1 channel output leclated hetveen output and power circuit lealation Photocouperisalsted between output and intemal creuit Effect of Improper Output Connection No damage Selection of Analog Output Signal Type Using software programming Calibration of Verification to Maintain Rated Accuracy Impossible FDC nCompass APPENDIX nCompass i4 3 c O N T R O Digital Output Card Specifications page 1 of 2 TranskBtor Source Output Module Specilcathns Type No
140. ides navigation to 6 45 AM tm my the program Status Entry guaranteed Soak limits and 7 mmm AutoStart screens l It also provides access to the Entry Status functions needed to create open save and delete automatic ramp soak programs Autostart Save As ci CH 6 28 2013 Slide page 2 provides all of the 6 45 AM functions needed to edit programs These include Copy Paste Insert and Remove step as well as the F Clone event function which allows Ee the user to transfer the current step Insert event selections to all following program steps to simplify and speed program entry Remove Clone 6 28 2013 Slide page 3 provides the program 6 45 AM Am my control selections such as Start Hold Halt and Off It also provides the functions for adjusting the operation of a program while it is running These items are available when the program is placed in hold and include adjust step Time and advance to the Next Previous or Previous step Basic Operation FDC nCompass 4 7 f FuTUREDESIGN nCompass i4 3 N T R O 4 3 3 Device Settings Menu The device settings menu is provided when the user selects Settings from the main Device menu See section 8 on Device Settings for detailed information on these settings and their use 4 3 3 1 Text Based Device Settings Menu The View menu provides navigation to the Defrost and Redundancy operation setup screens The Set menu provides access to the nCom
141. ification to purchaser or user to materials or processing that do not affect compliance with any applicable specification Future Design makes no warranties when using the nCompass system Warranty Future Design Controls products described in this book are warranted to be free from functional defects in material and workmanship at the time the products shipped from Future Design Controls facilities and to conform at that time to the specifications set forth in the relevant Future Design Controls manual sheet or sheets for a period of one year after delivery to the first purchaser Future Design Controls FDC 0450 products are warranted to be free from functional defects in materials and workmanship at the time the products shipped from Future Design Controls facilities and to conform at that time to the specifications set forth in the relevant Future Design Controls manual sheet or sheets for a period of one year after delivery to the first purchaser for use There are no expressed or implied Warranties extending beyond the Warranties herein and above set forth Limitations Future Design Controls provides no warranty or representations of any sort regarding the fitness of use or application of its products by the purchaser Users are responsible for the selection suitability of the products for their application or use of Future Design Controls products Future Design Controls shall not be liable for any damages or losses whether direct indirec
142. ign Controls C Rental You may not rent or lease the SOFTWARE D Software Transfer You may NOT transfer any of your rights under this LICENSE E Termination Without prejudice to any other rights Future Design Controls may terminate this LICENSE if you fail to comply with the terms and conditions of this LICENSE In such event you must destroy all copies of the SOFTWARE and agree not to modify distribute the software or download to any hardware not purchased from Future Design Controls F The selection application and use of Future Design products and or software is the sole responsibility of the purchaser or end user No claims will be allowed for any damages or losses whether direct indirect incidental special or consequential In addition Future Design reserves the right to make changes without notification to purchaser or user to materials or processing that do not affect compliance with any applicable specification Future Design Controls makes no warranties when using Future Design Controls SOFTWARE system A 26 FDC nCompass APPENDIX FUTUREDESION N T R O nCompass i4 3 fil Software Usage Note The selection application and use of Future Design Control products or software is the sole responsibility of the purchaser or end user No claims will be allowed for any damages or losses whether direct indirect incidental special or consequential In addition Future Design reserves the right to make changes without not
143. ing status including active file name and the length and logging rate set e Security status including the current user e Audit trail active inactive status e Web server active inactive status e VNC server active inactive status e nCompass IP address e Available SD storage memory remaining The appearance of the items is based on the configuration of nNCompass If defrost or redundancy functions are disabled in the configurator for example their status items will be removed from the list as well NOTE The notification items do not update while the list is shown The information shown in the list is a snapshot of the data at the time the window was shown Therefore the PV or SP shown for a loop may not be the actual values for the loop if the notification window is left open for extended periods of time The notification window is not available in the offline setup 4 14 FDC nCompass Basic Operation nCompass ia3 ff eurupenesron N T R O 4 5 Control Loops Single Set point Operation The loop view screens provide direct viewing options for the control and monitoring of the nCompass control loops and process monitor inputs The loop screens allow the user to adjust the current loop set points SP and view the process variables PV and percentages of output for each loop If the loop is a process monitor input only the set point and percentage of output will not be displayed since no control is associated with the input NO
144. inimum range of the vertical access with a minimum value of 32 760 and a maximum of 32 760 Automatic Scale When on the vertical axis will automatically adjust its zero and span as needed to display the selected plot channels Basic Operation FDC nCompass 4 19 f FUTUREDESICN N T R O nCompass i4 3 4 7 2 Digital IO Monitor The Digital IO monitor screen is accessed from the home View menu It provides simple at a glance status monitoring of all digital inputs and outputs configured on the nCompass control module To view input status press the Inputs button To view output status press the Outputs button Digital e Suse Digital E oe DIG IN 1 DIG IN 2 DIG IN 3 DIG IN 4 DIG OUT 1 DIG OUT 2 DIG OUT 3 DIG OUT 4 DINNER SBE amp DIG IN 5 DIG ING DIG IN 7 DIG IN DIG OUT 5 DIG OUT 6 BIG OUT 7 BIG OUT amp WW RI RW WW If more than eight inputs or outputs are configured the left and right arrow buttons will be shown Pressing either scroll button will allow the user to switch between screens in order to view all of the available system inputs or outputs NOTE Input status is shown by default whenever the Digital IO screen is first viewed 4 20 FDC nCompass Basic Operation nCompass ia3 ff eurupenesron N T R O 4 8 System Alarms nCompass offers the ability to program system alarms using any of the available digital inputs and also offers 30 alarms that can be programmed to respond to any of
145. ining replacement parts or to get assistance for setup and or troubleshooting purposes it is important to have this information available to insure that your request is processed properly and in a timely manner It is recommended that this information be written down and kept in a readily accessible location along with this manual so that it is available when required CE Net Version CM Firmware Version HMI Version CM Program Version CE Image Version CE BSP Version The CE Net version of the HMI and firmware versions of the Control Module and FDC loop A controllers of the nCompass control system are proprietary and only available directly from Future Design Using similar or like components obtained from a source other than Future Design will cause unexpected operation and or malfunction of the nCompass control system Any attempts to do so will be at the user s own risk and void any and all claims or warranties with Future Design Controls In addition installing Future Design nCompass software on hardware not obtained directly from Future Design is a violation of the software license agreement See the Future Design Software License agreement on the following page By installing and or using the nCompass Control System you are accepting the terms of the software license APPENDIX FDC nCompass A 25 ff FUTUREDESIGN nCompass i4 3 FUTURE DESIGN SOFTWARE LICENSE For FDC nCompass Controller Future Design Controls Windows CE bas
146. inned coils and provide a means of pausing operation at preset intervals in order to remove the build up of ice to restore efficient operation NOTE While the defrost function was intended for refrigeration systems it may also be used as an interval timer to perform a specific operation at preset intervals Consult you OEM configuration regarding the use and operation of defrost Defrost cycles are intended to keep ice from accumulating excessively on an evaporator coil Ice accumulation reduces the capacity of the refrigeration system and lowers the evaporator coil s operating temperature This causes more ice to form and if not controlled allows liquid refrigerant to flow back to the compressor which can cause permanent damage and failure of the compressor The control of ice accumulation is the primary function of the defrost operation The second goal is to minimize excess use of energy from too frequent defrost cycles The heat put into the system during the defrost operation must be removed by the refrigeration system to bring the system back to its operating temperature The shortest defrost period and the minimum number of defrost cycles provides the most efficient operation These goals are accomplished by the proper setting of the first two parameters defrost interval and defrost duration The third goal is to minimize the increase in temperature during and after the defrost cycle This is controlled by the fan delay The fan delay fe
147. ital Output 12 function determined by nCompass configuration Q34 Digital Output 13 function determined by nCompass configuration Q35 Digital Output 14 function determined by nCompass configuration Q36 Digital Output 15 function determined by nCompass configuration Q37 Digital Output 16 function determined by nCompass configuration 3 18 FDC nCompass Wiring nCompass i4 3 f FuTUReEDESIGN N T R O 3 6 6 Optional Analog Input Output Expansion Card Wiring NOTE The following information covers basic input output connection information for the nCompass analog expansion card Since nCompass Is a fully configurable control system the use of each input output is dependant upon the application therefore the input and output devices and real world connections are determined by the system designer The number of analog expansion cards in the system will also vary depending upon the application nCompass can support up to 4 analog inputs and 2 analog outputs for a total of 2 analog expansion cards FC4A LO3A1 Analog 1 0 Module Screw Terminal Type Applicable Terminal Block FC4A PMTILP supplied with the analog O module JAV DN Fuse Terminal No Channel w bag Analog voltage current EES L OUT input device po NC Analog voltage current PS ae output device fo Analog voltage current EE ee eel IN1 output device E Connect a fuse appropriate for the applied voltage and current dr
148. ital Outputs DO CPU includes 8 digital output 6 relay amp 2 TTL with optional 8 output card 24VDC or relay max of 16 DO Digital Outputs are configurable as Loop monitor point or digital input alarms Event outputs used in ramp soak programs Event output for automatic program status run hold amp step change Event outputs as a result of Digital Inputs Configurable cycle times to pulse an output or no cycle on 100 Configurable time delay to automatically turn DO off Configure DO with counter amp alarm message Digital Inputs DI CPU includes 8 digital inputs with optional 8 digital input card for maximum of 16 digital inputs Digital Inputs are configurable as Configurable time delay timers System Run Alarm Input Data Acquisition start and stop Automatic Program functions start stop hold previous next step Defeat Logic disable specific or groups of DO Disable Communication to loop control SP SP communication disabled SP values may be changed at loop controls while still monitor amp data log all values NOTES Analog UO Optional DIN Rail Mount to CM Analog I O Input Output Control Module Remote Setpoint Cards accept two 4 20mA or 2 10Vdc inputs to be transmitted as SP values via the serial link to specific DIN controllers Retransmission Cards have one 4 20mA or 0 10VDC signals configurable as PV Setpoint or Out values from specific DIN controls Maximum
149. l so no user action is required The historical graph provides the same zoom feature as the real time charts so the user can zoom in on a particular area of the historical plot by dragging their finger across the screen to draw a rectangle around the desired plot area Chart e Legend Return Start 4 26 2012 End 4 26 2012 107 8 39 0 70 2 531 5 32 7 13 9 04 28 10 05PM 04 28 10 08PM Pressing the Legend button will provide the user with channel information by displaying the names of the selected plot channels which axis they are associated with and the color used to display the plot channel Pressing the button again will toggle the display back to the historical chart C ha rt Legend Return LOOP 2 SP Left Axis NOTE When pressing the Legend button to toggle between the historical chart and the legend screen it may take several seconds for the chart to become visible depending on the size of the data file and number of channels selected to plot When finished viewing the historical chart you must press the Return button to exit the historical data viewer and return to the main data log screen Data Logging FDC nCompass 7 5 f FuTUReEDESsIGN N T R O nCompass i4 3 7 4 USB File Transfer A quick note about file storage data and setup files programs alarm log and audit trail files need some maintenance every now and then After a period of time storage devices fill up and files
150. larm will then activate The start delay feature is typically used on processes that when in the off state are in an alarm condition This allows the process to be started prior to the alarm s being activated and shutting down the process NOTE The alarm start delay when activated inhibits alarm action from power up of nCompass or when entering online mode The Digital Output assignment can be used to assign one of the nCompass digital outputs to the alarm When the alarm activates the output will work in conjunction with the alarm and turn on when the alarm is active and off when the alarm is cleared NOTE The selected digital output must be configured as a process alarm output If the digital output selected is not configured to be a process alarm output it will not function according to the alarm settings See Section 9 12 Digital Outputs for information on how to configure the digital outputs Device Settings FDC nCompass 8 9 f FuTUREDESIGN nCompass i4 3 N T R O 8 3 1 Set Points and Alarm Message The alarm set points and alarm message are accessed by pressing the Setpoints button at the lower left of the Alarm screen Alarm Settings Return Low G9 High C Differential C 0 0 Delay seconds Start Delay seconds Alarm Message ALMA 1 NOTE The low and high alarm set point fields are shown for Absolute Deviation A Out alarm types Although both set point fields are shown
151. lates for all of the nCompass features including ramp soak programs The menu provides navigation to the following functions View menu Entry Status View program operation step time remaining etc SE Entry Functions for creating editing profiles Race Soak Settings for guaranteed soak limits AutoStart Settings for automatically starting a program File menu New Clears all current program entries o Open Provides file open dialog to select a program from memory pen Step gt Save Saves the current program being edited emar SEXES Save As Saves the program being edited under a new name es Save As Delete Deletes the current program from internal memory Adjust gt Delete View gt Step menu Insert Insert Inserts a step into the program at the current step number File T emaye Delete Deletes the current step SECH Copy Copy Copies current step data including events Paste Pastes previously copied step data to the current step Paste Clone Copies and pastes current step events to all following steps Program Adjust gt Clone Program menu Start Transfers current program to the control module and starts it Hold Places a running program in hold Halt Stops a running program and returns the loop controls to single set point static operation while leaving all events are their current state Program Off Stops a running profile turning off all system events and returns the
152. loop controls to single set point static operation Adjust menu Time Add subtract time from the current step of a running program when first placed in hold Next Advances the running program to the next step when in hold Time Previous Advances the running program to the previous step when in hold Next Previous Automatic Program Operation FDC nCompass 5 1 f FuTUREDESIGN nCompass i4 3 N T R O 5 1 Entering a Ramp Soak Program Ramp Soak programs are created and edited from the program Entry screen The program Entry screen can also be accessed directly from the Program menu To create an automatic ramp soak program 1 From the File menu select New to create a new program 2 Enter the number of steps that will be in the program you want to create The default setting and minimum number of steps is one You can only adjust settings for step numbers within the range of 1 to the Max Steps entered maximum of 99 Thus to adjust settings for step 5 you must have the Max Steps set to a value of at least 5 NOTE The number of steps can be changed at any time during the program entry to shorten or lengthen the program as required without affecting steps already programmed 3 For each step enter the step events any wait for conditions set points and time duration or ramp rate depending upon OEM configuration Example shown below with step time HH MM SS 4 From the File menu select Save to sa
153. me period for history review Chart Plots historical data after time and points are selected USB Allows the user to access file utility functions FTP WAN Provides access to the automatic file back up settings Memory Displays memory capacity remaining on nCompass FDC nCompass 7 1 P 7 41 Selecting Points for Logging FUTUREDESION nCompass i4 3 N T R O In order for the data logging function of nCompass to operate you must first select what variables are to be logged to the data file To choose which points are to be logged select Assign from the Data menu This screen allows the user to select any point s from the system for data logging LOOP 1 SP LOOP 1 Cut Select the desired items from the list by turning each one on or off Control loops offer PV SP and Out selections while monitor points provide only the process value PV selection When selections are completed press the Save button to save the point selection to memory New selections will not take effect until the Save button is pressed 7 2 Starting Stopping Data Logging nCompass logs data to its SD card Current data for each variable is written to the log at a fixed interval based on the settings entered in the Length and Interval fields File names are automatically generated using mm_dd_yyyy_hh_mm_ss format To enter a new alphanumeric file name touch the File Name field and enter the desired value up to 16 characters
154. mer has the ability to do nested looping It has the ability to set up jumps on every step throughout the program It even has the ability to jump forward skipping steps only to allow them later by other jump steps returning to the skipped steps However this can become confusing Use caution with nested loops to prevent product loss The program may not operate as expected due to multiple jump paths within the program Setting Program Auto Start AutoStart Month Day Hour 0 Year Minute 0 Save 5 8 FDC nCompass Automatic Program Operation f FuTUReEDESIGN N T R O nCompass i4 3 When AutoStart By Date is selected the exact date and time must be entered Enter the month day year and time of day in hours and minutes for when the program is to start The day of week is not required to be set Itis not used for this function When AutoStart By Day is selected only the day of week and time is required to be entered The date settings are ignored nCompass simply looks for the day of week and time to begin the program NOTE The time is entered in a 24 hour format To convert time from a 12 hour format AMIPM into 24 hour format add 12 to the hours for PM time For example 2pm will be a value of 14 2 12 for hours A time of 5 30pm will be 17 hours 30 minutes 5 1 7 Setting Guaranteed Soak Limits The guarantee soak limits are used to set the control tolerance for each loop during guaranteed soak steps when
155. mm_dd_yyyy hh_mm_ss Data files directory Data Files_mm_dd_yyyy hh_mm_ss The purpose for using the date and time as part of the directory name is to make sure the user can track the date and time of the file transfer If a user transfers a file type more than once in a single day the files will be grouped logically by time When accessing the data files saved to the USB memory stick the data files will be in csv format These files can be opened directly with Microsoft Excel or any program that opens a comma separated file format You can copy or empty the Data Files directory by simply plugging the USB device into a PC s USB port The device then becomes like any removable disk attached to the computer and can be manipulated once plugged into the PC The FDC Data Viewer program is a free Windows accessory program that allows users to view plot and print data files and is available from Future Design Controls or any manufacturer that markets the nCompass product It is required when using the digital signature feature of nNCompass IMPORTANT Once files are deleted from nCompass storage devices they are gone and cannot be retrieved Once again do not edit move or delete any other files from the internal SD memory card unless using the nCompass file utilities nCompass may not operate properly if you do so Windows XP and Excel are trademarks of the Microsoft Corporation Data Logging FDC nCompass T T f FUTURE
156. mmediately stop a program and turn off any equipment controlled by the control module digital outputs NOTE The program Off selection does not affect loop controller outputs 5 2 1 Hold Resume Ramp Soak Program Operation At any time during the operation of a program it can be manually placed into hold This stops the program timer however nCompass continues operation under the current step settings at the time the program was put into hold To pause a program select Hold from the Program menu To resume the program from the point in which it was paused select Start from the Program menu NOTE When a program is in hold the set points and system events can be manually changed to make on the spot adjustments to system operation in that step without changing the original program When program operation is resumed nCompass will continue the step using the adjustments made to the set points and system events 5 2 2 Adjusting Step Time During program operation the length of time remaining in a step can be adjusted to increase or decrease the time left The adjust step time function allows you to add or subtract time from the current step however the program must be first put into hold Once in hold the Adjust Time menu item is enabled When selected the Adjust Time screen will be shown Enter the time adjustment in hours and minutes and press Set when finished The time remaining in the step will be adjusted b
157. mmunication wiring between port 2 of the control module and the loop controller indicated by tagname Verify that the loop control has the proper communications address and communications settings Verify that set point ranges set in the nCompass configurator for the control loop do not exceed the loop controller s input range NOTE A tagname of CM RS485 indicates that the communications to the optional input monitor module s is at fault Alarm Codes and Troubleshooting FDC nCompass 11 1 N T R O f FuTUREDESIGN nCompass i4 3 Alarm Monitor Description Explanation Corrective Action tagname Sensor Break Check sensor wiring for the indicated tagname This alarm applies to all control loop and optional monitor input points Verify lead connections If sensor requires power verify power to sensor NOTE Often times the loop control will indicate an error code regarding input trouble Reference the specific loop controller manual for information regarding its error codes for further diagnostics 11 2 FDC nCompass Alarm Codes and Troubleshooting nCompass i4 3 ff FUTUREDESIGN Appendix APPENDIX FDC nCompass A f FUTUREDESICN N T R O nCompass i4 3 FDC 0450 Touch Screen Interface Specifications page 1 of 3 Technical Specifications ize Resolution W X H in pixels Display type 65536000 Colors Jee Touch screen Type Resistive analog 95X54 95 X 54 Main Hardware Description
158. mpass for the program is a calculated value based on the sum total of all step times This time can be affected by any guaranteed soaks or wait for conditions entered into steps of the program The affects of these times is an unknown and can cause the program to run longer than calculated because they pause the program until their conditions are met NOTE nCompass does update the estimated stop date based on these conditions as they occur however it does make the stop date a moving target 7 Guaranteed soak is turned on why are the loops not following the programmed ramp Guaranteed soak is typically not turned on in ramp steps Guaranteed soak is used to pause a step until the selected input is within the soak limit band around set point On a ramp step if the step time is paused due to an input leaving the soak band the ramp rate is then affected because program timer stops and the set point is no longer changing It will hold at that set point until the input returns to the soak band Since the purpose of a ramp step is to change the set point over time the input could be repeatedly falling in and out of the soak band limit throughout the step thus causing the program to pause and resume operation multiple times This will elongate the overall step time and change the rate of change of the set point Guaranteed soak is typically enabled on soak steps only 8 am using the program ramp rate configuration option so why do the contr
159. n Select Start Over to automatically restart the program that was running at power failure Use this option if it is critical for a program to run from start to finish without interruption Device Settings FDC nCompass 8 15 f FuTUReEDESIGN N T R O nCompass i4 3 Select Resume to have nCompass pick up where it would be at the current time if power had not been lost lf a program was running prior to the power outage nCompass will advance forward through the program to the point where it would be at the current time and resume operation from that point NOTE When a program is NOT running and a power down up sequence occurs nCompass will return with the same set points and system events active as when the power was lost If a program stays in hold regardless of power recovery configuration refer to the OEM configuration provided by the installer Digital inputs may be used to place a program in hold This input may have to be reset to allow the program to continue 8 16 FDC nCompass Device Settings nCompass ia3 ff eurupenesron N T R O 8 8 Communications The communications screen provides settings for the Modbus serial interface web server and VNC interfaces It also provides the nCompass IP address which is required for using the VNC or web server interfaces Modbus Address YNE Address YNE Device Name nCompass YNE Password IP Address 192 168 0 6 The Modbus Address sets the address of nCompass on
160. n com plisnce with eectromagnetic innmunity Connector on Mother Board hMC1 6 1045 S 827 BR Phoenim Contact Connector Insertion Removal Durability 100 times minimum 25 EW DC All Inputs ON 1 ip e Internal Current Draw e 5 m EY DC All Inputs OFF 9 mA 24 DC Weight S52 Input Operating Range Input intemal Circuit The nput operating range of the Type 1 ATR EC S113127 input modula is shown PURNA bakya EIS LA Input Usage Limits zu a Je i D a 42 To 84 Input Curent im Ai When using the FOAA ANOSE1 all inputs can be tumed on simultaneously at BSC input voltage 25 8 DC ae 28 8 284 H F 24 0 E Ei k i S a R 5 Si E D 0 TO I D AO To g0 100 Input Simukans as ON Ratio 8 Inpak irre tree ue OH Rat E A 8 FDC nCompass APPENDIX nCompass i4 3 E FUTUREDESION c O N T R O Digital Input Card Specifications page 2 of 2 AC Input Module Specifications Type No Input Points and Common Lines Rated Input Voltage Input Voltage Range Rated Input Current Input Type Input Impedance Turn ON Time Turn OFF Time Isolation External Load for 1 0 Interconnection Signal Determination Method Effect of Improper Input Connection Connector on Mother Board Connector Insertion Removal Durability Internal Current Draw Sa Input Operating Range Weight The input operating range of the Type 1 2 3 IEC 61131 2 input module is shown below FC4A NO8A
161. nal equipment related to the application through software switches called events or be programmed to act as system alarm or status outputs All outputs have adjustable delay times for on off and cycle times nCompass can be operated in single set point or automatic program control mode Program entry is made easy through the use of copy paste and delete menu selections Programs can be copied to the external USB memory stick and then imported to another nCompass controller which eliminates the need to enter duplicate ramp soak programs into multiple systems When running in automatic program mode the operator can place the system into hold and change any control parameter without modifying the original program This gives the operator maximum flexibility over the controlled process Data file analysis tools auto trend make looking at historical data a simple task Any control variable saved to the nCompass SD memory can be plotted on the historical data trend for any time frame within the data file s total time range The built in Ethernet functionality includes a Web Server to provides access to all nCompass data view only a VNC interface for remote control and monitoring and an NTS clock all available via a local Intranet connection wired or wireless or the World Wide Web using standard software like Microsoft s Internet Explorer What is nCompass FDC nCompass 1 1 f FuTUREDESIGN nCompass i nCompass provides a ri
162. nd the front of any high voltage devices mounted in the enclosure when the enclosure door is closed It is required that a minimum separation of 2 be maintained so plan a depth to accommodate at least 4 102mm behind the panel Proper clearance must also be maintained above below and on both sides of the interface to allow for heat dissipation and to facilitate mounting A minimum of 2 is recommended Note that additional space may be required below and to the right of the interface from rear of unit to accommodate the communications wiring depending upon the type of communications cables used 2 2 Environmental Considerations Do not subject the nCompass touch screen interface to operating temperatures below 0 C 32 F or above 50 C 122 F The operating temperature for the Control Module is limited from 0 C 32 F to 55 C 131 F Minimum and maximum relative humidity levels are limited between 10 and 90 non condensing The nCompass touch screen interface is to be used indoors only The unit should not be installed where fast temperature variations may occur as this can cause condensation of water vapor on the device nCompass should not be exposed to excessive dust dirt salt direct sunlight or shock and vibration Do not operate the nCompass controller in an area where chemicals or flammable gases are present Permitted storage temperature extremes for the nCompass control system are limited to 10 C 14 F and 60 C 14
163. nic solvent or corrosive gas Store HMI in anti electrostatic container or bag APPENDIX FDC nCompass A 3 f FUTUREDESICN N T R O nCompass i4 3 FDC 0450 Touch Screen Interface Specifications page 3 of 3 Operating conditions OC to 50C Relative Humidity 10 to 90 no condensation Altitude 2000 meters maximum IEC 60068 2 6 58 to 150Hz 1g 10ct min 1 sweep NOTE In temperatures below 0 C the response time of liquid crystal display becomes slower and color of the display will be darker than normal Do not operate HMI in ambient temperature less than 0C LCD specifications Touch operations 1 000 000 times using R 0 8 Polyacetal stylus with force 250g Vibration test 10 55 Hz Stroke 1 5mm 2 hrs for each direction of X Y Z Shock test 100 G 6 ms X Y Z 3 times for each direction 6bB Octave from 200 500 Hz 2 hrs for each direction of X Y Z surfaces Typical Viewing Angle Description Details Vertical Up Down 50 70 Horizontal Left Right 70 70 A 4 FDC nCompass APPENDIX d FUTUREDESION c O N T R O nCompass i4 3 Main CPU Specifications Nomal Operating Conditions CPU Module Operating Temperature Storage Temperature Relative Humidity Pollution Degree Degree of Protection Corrosion Imanaunity Artitude Vibration Resistance Shock Resistance ESD Immunity Weight Power Supply Rated Power Voltage Allowable Vottage Ranga Maximum Input C
164. nk The PSWRD password field is used in conjunction with the user name field and is for entering a password if required by your FTP site so that nCompass can access the site If security is not used this field can be left blank The Server field is used to enter the server directory where the files are to be backed up When the automatic back up occurs nCompass will place the historical data files in this directory on the FTP site nCompass will automatically create an Alarms directory and an Audit directory within the specified server directory for backup of the alarm files and audit trail files When the Automatic Transfer 2 00AM option is turned on nCompass will perform an automatic backup of all historical data files alarm files and audit trail files contained in its internal memory to the designated FTP site If data logging is currently active the active file will not be copied NOTE f the barcode reader option is enabled and set for Start the automatic program the automatic transfer will be skipped if it occurs while a program has been selected through the barcode reader but has not yet been started by the user See section 8 9 Barcode Reader for more information 7 8 FDC nCompass Data Logging nCompass ia3 ff eurupenesron N T R O When the Delete internal files when done option is turned on nCompass will delete all data log files alarm files and audit trail files within its memory after completing the
165. nnection typically requires a qualified network System Administrator Typically a permanent IP address and specific port address are assigned to nCompass support on this action is beyond the scope of this guide Consult your network system administrator for assistance in setting up an Internet connection If the IP address of the LAN is 69 216 64 69 and the configured VNC Address is 1 port 5901 has been opened and assigned to this specific nCompass controller from the remote PC outside of the site Servers LAN in the VNC Viewer address field enter 69 216 64 69 5901 to access the device 5901 relates to address 1 5902 to address 2 5903 to address 3 etc note the double colon VNC Viewer A VNC Server Encryption NOTE The IP address shown on the communications screen of nCompass is the LAN address and would not typically be used for an Internet connection security Example lf the VNC server password is enabled on nCompass for either example above upon pressing the Connect button to make the connection the VNC viewer will prompt for the proper password The connection will only be established once the valid password is entered Communications FDC nCompass 10 11 f FuTUReEDESIGN N T R O nCompass i4 3 IE VNC Viewer Authentication a VNC Server 192 168 3 5 1 VU Username Password Kenna Cancel Once the connection is established the current nCompass display will be s
166. number of cards is 2 4 remote set point inputs and 2 retransmitted PV Setpoint or Output values Loop Controls The loop control model used may offer Retransmission capability although it along any other outputs are not accessible from the nCompass control system FDC nCompass A 23 q FUTUREDESIGC c O N T R O NOTES System Configuration nCompass has an embedded configuration program and normal runtime allowing full customization amp configuration directly from the GUI Simple Import Export function allows complete configurations to quickly amp easily imported to other nCompass CM control systems Configuration Program allows Number of Loop Controls Monitor Points Digital Inputs Digital Outputs Events and Analog I O with naming assignment for all types Program Setup Time or Ramp Rate based program operation Main startup view and menu options used not used configuration NOTES Loop Controls Serial connection to CM Control Module CM Software for Loop Controls Up to 3 loops of control and up to 15 monitor points 8 T C 6 RTD or 8 mA or VDC inputs Supports DIN style loop controls or board only control modules B41 single SP B42 profiler Loop controllers control boards ordered separately The FD30 amp FD10 CM software allows connection to Future Design Controls 300 amp 100 Series DIN controllers Both Series are available in 1 32 1 16 1 8 and 1 4 DIN sizes with DIN rail mounting av
167. ock synchronization or communication alarms between nCompass and the control module 9 18 FDC nCompass Offline Setup f FuTUReEDESIGN N T R O nCompass i4 3 9 9 Digital Input Monitor The Monitor screen provides the on off status of all digital inputs available on the nCompass control module It is useful for offline troubleshooting to verify input operation If more than eight inputs are available on the system the left and right navigation buttons at the upper right of the screen will allow the user to switch back and forth between inputs 1 8 and 9 16 Monitor DIG IN 1 DIG IN 2 DIG INS DIG IN 4 m Ei IS DIG IN 5 DIG IN 6 DIG IN F DIG IN 9 10 Digital Output Force The Force screen allows the user to force any of the digital outputs on the nCompass control module on to test output functionality and verify proper operation of equipment controlled by the output If more than eight outputs are available on the system the left and right navigation buttons at the upper right of the screen will allow the user to switch back and forth between outputs 1 8 and 9 16 Time seconds DIG OUT 2 DIG OUT 3 DIG OUT 4 DIG OUT 6 DIG OUT 7 DIG OUT amp The Time setting limits the maximum amount of time the outputs can be forced on The force time can be set from 0 to 32 760 seconds This provides an automatic method to help prevent runaway conditions in case an operator leaves an output on but has to walk away to a
168. of Contents FDC nCompass iii FUTUREDESION P ae nCompass i4 3 S OME eege 9 1 Ge 9 2 IT E e dee 9 3 92 Degrees C F alts mes 611 6 EE 9 4 GE Oe elei e EE 9 5 oe Ge ee Ree 9 5 9 3 1 1 Local Time Server Settings cccccccccsscccssecceeeeceeceseeccueeceucessucessueesaeeceueecsueessueesseeseueeesagss 9 6 922 Davi VNOS eee ee E anne E EEEE E eee ae eee ne eee eee ee nee 9 6 o gt MOUTE EE 9 7 oS MY Mee Le e E 9 8 9 5 1 Remote Set Point Operation 9 9 PAO bel e LC 9 10 9 6 1 Retransmitting Loop Percentage Of Output 9 11 9 7 EG MEI oe EEE RE EET E E A ee O oe 9 12 Ze GE te et RTE 9 15 9o 2 8 1 2 GW 6 E 9 16 99 EG MOO ON eebe 9 19 Os ONE A ee 9 19 9 11 Montor Onset CAND ratene a aiis a aeaii sinini 9 20 UZ E dl e 9 21 CEA We E 9 21 9 122 TACHIOML SOUNS EE 9 22 FO COn T aap rE E E E E OEE EAE E E E NEE EE AER E reine 9 23 Se ADOUNC OMD lo er E e S EA E E EEE R E ee E a eee 9 25 d Eat EXA PIL e eee ee eee EE E EES ee ee E E eee E eee 9 25 10 ee vlt e d Le E 10 1 10 1 Ethernet Communications nnnannannnnannennnnnnnnenrnnnnrnrnrnnrrnrrnnrrsnrnsrrnnrrsrrnnrrsnrrnrrenrnnrrnnrnrrrnnrrenrenrrenene 10 1 10 1 1 Guide to Smart Networking Hrachces 10 1 10 1 2 Configuring the NCOMPASS Network 10 2 10 1 2 1 Obtaining the nCompass MAC Address 10 2 10 1 2 2 Setting a Static e el 10 4 IUT OSING TIC EE BEE EE 10 6 POAC USO ME VNC SCIVO EE 10 8 10 1 4 1 Recommended VNC Viewer Settings DCMAC 10 8
169. of automatic programs each with up to 99 steps and up to 16 configurable events per step Step Advance Hold Stop and other Wait For logic per step is standard The Wait For step advance logic includes digital inputs loop monitor points achieving a wait for SP Configurable Loop Control Each of the control loops may be configured via the operator interface as single loop controls or as components in Cascade or RH values Alarm Configuration system Alarms System Alarms include loss of communication with loop amp monitor points configurable call back audible and more may be mapped to one of the standard or optional digital outputs DIN Control Loop Alarms a maximum of 30 alarms for loop amp monitor The loop controls up to 3 may have up to 30 alarms configured per loop The alarms may be configured as latching or not inhibit logic and to defeat any digital output Alarms may be mapped to one or more of the standard or optional digital outputs maximum of 16 digital outputs Alarm types include Process Deviation Percent Output and Rate of Change ROC low high or both Monitor Input a maximum of 30 alarms for Loop amp monitor Each channel may be configured with Process or Rate of Change ROC latching or not inhibit and or to defeat any digital output Alarms may be mapped to one or more of the standard or optional digital outputs max of 16 digital outputs Digital IO Configuration Dig
170. off to 100 To edit the alarm volume touch the entry field and enter the desired volume level To test the buzzer press the Alarm Test button 9 12 1 Calibrate Touch After extended use and many hours of operation it may be necessary to recalibrate the touch screen of nCompass A typical sign that the screen may be out of adjustment is inaccurate responses when attempting to press buttons check boxes or adjust fields on the display The calibration utility is provided in order to readjust the screen when this happens To begin the calibration process press the Calibrate Touch button An alert message will appear stating that the application will be disabled to perform the calibration procedure Press Yes to continue The calibration utility will start and crosshairs will appear on the screen At each crosshair position touch the screen at the center of the crosshairs Repeat this for each position in order to set the calibration The calibration requires five points the center and four corners Offline Setup FDC nCompass 9 21 f FUTUREDESICN N T R O nCompass i4 3 NOTE Itis recommended that you use your finger rather than a stylus when calibrating the screen The touch response will be more fluid after calibrating it with your finger Carefully press and briefy hold stylus on the center of the target Repeat as the target moves around the screen Once complete the calibration
171. ol loop set points jump to a different value when the program starts The ramp rate feature was designed for the stress relieving market When a program is started nCompass checks the actual process values of each control loop nCompass then uses the highest process value as the starting set point and sets that set point to all control loops This synchronizes all control loops to the same initial control value and then the desired ramp rate entered for step 1 of the program is then used for the duration of the step until the programmed set point is achieved 5 14 FDC nCompass Automatic Program Operation f FuTUReEDESIGN N T R O nCompass i4 3 6 Security The nCompass security model provides an administrator with the tools to add up to 30 users to the system Each user must have a unique ID full name and password Four user levels are provided which include system user supervisor and administrator levels Specific access rights can be assigned to each user level and password aging can be implemented Verification is provided if enabled for any parameters that will change a control parameter which could upset the process i e loop set point start stop automated ramp soak programs etc Verification requires that the logged in user must log in again before the process value at the controller will actually be changed This feature is provided for extra security The following example will make re authentication clearer A super
172. om the list and press Open to load the file Once the file is loaded the import process can begin Pressing the Import button will begin the process When the import is complete you must cycle power to nCompass in order for the new configuration data to be loaded into runtime memory for proper operation The Reset default configuration button can be used to clear the current nCompass configuration and reset the system back to default values This function clears all user and or OEM configuration values and returns the system to an as new factory state allowing the system to be configured from scratch This function is provided as a means to start over in the event that the system configuration has been altered to an unknown state and is not operating properly and a known good configuration is not available to import Rather than go through every setting of every feature to try and determine where the configuration error exists this allows the system to be cleared so that it can be reconfigured from a clean slate NOTE The configuration functions do not affect the VNC server configuration The enable state VNC address device name and password fields must be manually changed as these settings are specific to each device and must be set independently for proper VNC server operation over a network IMPORTANT When importing a configuration file to nCompass all of the current settings in nCompass will be overwritten Do not import fil
173. ompass 2 5 P 2 3 4 1 Installing the RS485 Communication Module FUTUREDESIGN c O N T R O nCompass i4 3 When using a small screwdriver to remove the communication connector cover from the CPU insert the screwdriver carefully to avoid damage to the connector and components within the CPU When pushing in on the communication connector cover to break support tabs use caution to avoid injury to your finger i Carefully push in the communication connector cover at position 1 to break bridges as shown in either figure below 2 The other end 2 of the communication connector cover will come out as shown at left below Push in this end 3 Then the opposite end 3 will come out If the end does not come out insert a thin screwdriver into the gap and pull out the end 3 Hold the communication connector cover at 3 and pull off the communication connector cover to break bridges EI 2 6 FDC nCompass Installation N T R O nCompass i4 3 f FuTUREDESIGN 2 3 4 2 Installing the Control Module in a Panel The control module must be mounted horizontally on a vertical plane as shown below All other mounting directions are not allowed Be sure to leave adequate spacing between the sides of the enclosure and or wiring duct and the control module for proper ventilation 20 mm minimuni BO mm wd minimum 20 mm minimum Peer AN Wiring Duct Incorrect Mounting Direction Incorrect Moun
174. ompass data logging features are accessed via the home Data menu item The system data logging provides the ability to select individual points for logging view data log files and start stop logging operations The logging ability of nCompass provides an easy to use convenient method to obtain electronic data without the need for additional data acquisition equipment The Data Log menu provides navigation to the following functions Utilities Chart Data Logging Utilities menu UGTA Annotation View menu Fle Signature Annotation Allows the user to insert a notification into the currently running log file or view all annotations associated with the Data gt currently loaded historical data file Signature Allows the user to digitally sign a file to prevent data Chart tampering and view all digital signatures associated with the ena currently loaded historical data file Utilities File menu ei Open Opens a history file for review File d Open Delete Allows the user to delete the currently loaded history file DALEY Delete g NOTE The Delete log file function does not affect data from a Chart file that is running only the current data log file loaded a for review Utilities Data menu Data Displays main data log screen with status of logger Assign Allows the user to select what variables are to be logged Chart menu Set Selection of data file points and ti
175. on is used each controller on the link must have a different address so that each one can be identified separately If two or more nCompass controllers have duplicate addresses communications with those controllers will fail because they will all try to respond to the same message For single nCompass connections the address only needs to match that of the commands being sent from the host device NOTE See the FDC Orion M Communications Reference Manual for details on using the optional serial interface Communications FDC nCompass 10 13 f FuTUReEDESIGN N T R O nCompass i4 3 11 Alarm Codes and Troubleshooting This section provides explanations of standard nCompass alarms to help in diagnosing and resolving the alarm conditions Note that the information provided here covers standard alarms only and not alarms configured by the OEM for system If you are unable to diagnose a problem through the use of this guide contact your OEM for further assistance Some of the troubleshooting procedures may require access to live circuitry Dangerous AN accidental contact with line voltage may be possible Only qualified service personnel should be allowed to perform these procedures Alarm Monitor Description Explanation Corrective Action Communications read error Check Communication wiring between the nCompass touch screen and control communication cable module CM faulty or not properly connected If alarm will not clear check comm
176. on of client and testing is the end user responsibility The following settings are provided as an example for the Remotix client for the iPad When adding an nCompass server to the Remotix client use the following settings Note that the VNC server in nCompass must have security enabled in order for this client to connect Connection Type VNC Host IP IP address of nCompass Port VNC address of nCompass 5900 0 5907 1 etc Use SSH Tunnel Off VNC Authentication VNC Password VNC Password VNC password of nCompass VNC Server Type AutoDetect Operating System Windows Preferred Encodings Hextile Color Depth 16 bits 10 10 FDC nCompass Communications nCompass ia3 ff eurupenesron N T R O 10 1 4 3 Accessing nCompass through a VNC Viewer The following examples are based on the use of the RealVNC viewer for PC MAC Once the default settings have been entered just enter the IP address and port number for nCompass and click the Connect button to access nCompass over the network Intranet Example f the IP address assigned is 192 168 3 5 and the configured VNC Address is 1 from the PC s VNC Viewer address field enter 192 168 3 5 1 to access the device address 1 relates to port 5901 address 2 to port 5902 etc which is the port opened by the VNC interface in order to allow communications with nCompass over the network VNC Viewer A VNC Server Encryption Internet Example Internet co
177. on the first step When the Annotation option is turned on the scanned data will be written to the currently running data log file as operator event The Prefix field allows the user to enter up to 16 characters that will then be used as a prefix to the scanned value when matching a ramp soak program name or when it Is inserted into the active data log file This can be used as a tag to describe what the scanned value represents i e Lot or Batch number for example NOTE Any changes made to the above settings must be saved in order for them to take affect When changes are complete press the Save button to save the new settings in order to use them The Bar Code Test field allows the operator to test the operation of the barcode scanner As a bar code is swiped by the reader the scanned value will appear in this field If upon scanning a bar code no value appears in this field check the wiring and communication settings of the barcode scanner to be sure that it is connected and set up properly 8 18 FDC nCompass Device Settings f FuTUReEDESIGN N T R O nCompass i4 3 8 9 1 Barcode Reader Communication Settings In order for the barcode reader to communicate properly with nCompass it must be set with the proper communication settings This includes baud rate data bits stop bits parity and start end of transmission characters as follows Baud rate 9600 baud Data bits 7 Stop bits 1 Parity even Preamble S
178. ons address This is done by setting DIP switch 5 to the on up position for card 1 address 16 or DIP switches 5 and 1 to the on up position for card 2 address 17 DIP switches 2 4 6 7 and DIP switch 10 must be set to the off position or the module will not work correctly with nCompass DIP switches 8 and 9 are used to select the input scaling and failure mode for the module See the following sections on how to set DIP switch 8 and 9 for each module Switch 10 Gaetan Pir 3 ik E Zu i ee Bh Tro Cov D I d R485 A nme 8 Ei Em 8 Wm DIP Switch Card 1 address 16 Ip LEI KW DIP Switch Card 2 DER E OH HI Ih HHH CR address 1 Connect 4 1de mA H RG m onmect to Termin zl a EN Control Module E Enemies opnect to Terminal B of Control Module d REAREA NOTE The IO modules can be connected at any point in the communication link between the nCompass control module and process controllers as long as the communication wiring is properly daisy chained between units Wiring FDC nCompass 3 7 f FuTUReEDESIGN N T R O nCompass i4 3 3 5 1 Thermocouple Module IO 8TCS Input Wiring The IO 8TCS is an 8 isolated thermocouple input module The module uses differential inputs to reduce effects of electrical noise The thermocouple inputs are isolated from the internal logic and from each other The module has built in cold junction compensation Be sure to use the correct
179. oop currents to flow in that section of the cable shield which can disrupt communications NOTE FDC recommends the use of shielded wire for all installations in order to maintain optimum performance and minimize the possibility of communications errors R5485 Communication Module AC4AHPCS a BSC G IE ER e e A Cable leleleleleieiel 91011 12 13 14 15 16 B K Twisted pair wire shielded Connect Shields Shield wire ted to ground Le 2088000 Maximum af 3 units 7 D a 13 11 E J Communications Wiring Example FDC 9300 controller shown 3 6 FDC nCompass Wiring nCompass ia3 ff eurupenesron N T R O 3 5 Connecting to the nCompass Process Monitor Modules nCompass can connect with four different versions of monitor modules Each version of module provides a different input type so that it can be tailored to match the application The IO 8TCS provides up to eight thermocouples the IO 8AIIS or IO 8AIVS provide up to eight current or voltage inputs and the IO 6RTD provides up to 6 RTD inputs While the input connections to each module are dependant on the input type each module requires the same power and communications connections to the nCompass control module The power and communications wiring are via the 4 terminal connector located on the bottom of the module In addition to power and communications the module must be configured for the proper communicati
180. oop or monitor input rising or falling over the time period set in the Time field The time period Time minute defines the minimum period of time that the input must take to change by the amount set in the Delta field If the input changes by more than the set point amount in less than the set time period the alarm is activated For example if an alarm was to be generated on a control loop if its input exceeds a rate of change of 100 degrees per hour the alarm would be entered with a Delta of 100 and a Time of 60 minutes 1 hour The Differential often referred to as alarm hysteresis is subtracted from the Delta set point in order to define the rate of change that the loop or monitor input must fall below in order for the alarm to clear For example if the alarm set point was 100 degrees per hour and a dead band of 10 was entered the rate of change of the input would have to slow to less than 90 degrees per hour 100 10 in order for the alarm to clear Device Settings FDC nCompass 8 11 FUTUREDESION c O N T R O nCompass i4 3 High Sade Alarm Range Alarm High Rate of Change x N NW Alarm Hysteresis S 7 B g Normal Operating Range Alarm Hysteresis b Li A fa Alarm Low Rate of Change Log Side Abm Range 8 3 2 Output Defeat The alarms can be used to disable outputs of nCompass when in an alarm condition To assign which outputs are to be disabled when the alarm occurs press the
181. owed file name length for a program If nCompass does not find an exact match it will ignore the scan Thus it is up to the user to insure that a matching program exists for each bar code that will be scanned lf an automatic ramp soak program is already in operation or a program download is active from a remote PC nCompass will ignore any barcode scan made during that time nCompass will also ignore a barcode scan if the FTP data backup Is active The user must manually stop the currently running program or wait for the remote PC download to complete before scanning the barcode to begin the matching program The user also has the option of cancelling the FTP data backup while it is in progress if necessary in order to scan and start a program If the automatic FTP data backup is set to occur while an automatic program start is in progress by a barcode scan but the user has not yet acknowledged the request to start the program the FTP data backup will be skipped The automatic FTP data backup will then occur at the next scheduled interval This allows the user to proceed without interruption however it does prevent the scheduled backup of data If necessary a manual FTP backup can be performed once the program has been started 8 9 2 2 Using the Barcode Reader to Annotate a Data Log File When scanning bar codes a minimum time period of 3 seconds is required between each code scanned This provides the time necessary for nCompass to acquire t
182. owing information is provided as an overview of the full navigational menus for nCompass Basic Operation FDC nCompass 4 3 f FuTUReEDESsIGN 4 3 1 Home Menu The home menu is the top level default menu provided when nCompass first powers on Pressing the menu icon will display the main menu offering the selections shown below 4 3 1 1 Text Based Home Menu View Program gt Device Security gt View gt Program Device Security gt View Program gt Device Security Single Dual Chart Alarm Alarm File Digital Events Entry Status Start Hold Halt Off Configure Login Log Off Audit User Password 4 4 FDC nCompass nCompass i4 3 N T R O The View menu provides navigation to all standard view screens These include the Single and Dual loops views real time Charts Alarm monitor Alarm File Digital IO monitor and Events control screen The Program menu provides access to the automatic ramp soak program actions Entry and Status views The program Start Hold Halt and Off menu items allow quick access to these functions if a program is already downloaded to the nCompass control module The Device menu provides access to the nCompass controller settings These include loop set point entry limits alarm set points communication settings email setup as well as access to offline settings for date time etc The Security menu provides access for us
183. pass Process LOOP Controllers cccccccceccsececeeeceeeeeeeeeeeeaeeeeeecseeeeeeeaeeees 3 6 34 1 COMMUNICA ONS VV UNAS EE 3 6 3 5 Connecting to the nCompass Process Monitor Modules aannnnnnnnnnnnnnnnnnnnnnnnnnnnnnrnrnnrrnrrnrrnrrnrrerenne 3 7 3 5 1 Thermocouple Module lO 8TCS Input Winmg 3 8 3 5 2 Current lIO 8AIIS and Voltage IO 8AIVS Module Input WM ing 3 8 3 5 3 RTD Module lO 6RTD Input Wumg 3 10 3 6 Connecting to the nCompass Control Module ccc ecccccccceeeeceeeeceeeeeeeeaeeeseeseeseeeeaeeeseeeeseeeeseeeeaes 3 11 E MINC POVINN EE 3 12 3 6 2 Optional User COMMUNICATIONS Card Wdng 3 13 3 6 3 Optional Barcode Scanner COMMUNICATIONS Card Wing 3 14 3 6 4 Optional Digital Input EXPANSION Card Wug 3 16 3 6 5 Optional Digital Output Expansion Card ug 3 17 3 6 6 Optional Analog Input Output Expansion Card Wug 3 19 Table of Contents FDC nCompass i f FUTUREDESICN 4 5 nCompass i4 3 N T R O Basic Cl QUOI NEE 4 1 AT OR eut e EE e uk 0 0 EE 4 1 4 1 1 OEM Control Loop Configuration Options 0 cccsccccscccsseccsseecsseesseeessessueesseeesseeessusesseesseessneessneess 4 1 4 1 11 Cascade Control Loop ee LE 4 1 4 1 1 2 Calculated RH Loop Mode 4 1 4 2 Touch Screen Interface ccccccccscccsscccsececsecccseeceuceceueesaeeecueeceucessueessueesseeseueessaueesseeseueessueesnsesseeseas 4 2 43 Men INA de EE 4 3 LT FOTE M EE 4 4 4 3 1 1 Text Based Home Menu 4 4 4 3 1 2 Icon Slide
184. pass setup screens for Alarms power Recovery control loop setpoint Limits Event tagnames and Navigation type selection Navigation Recovery The Comms menu allows the user to adjust the communications settings for the web page VNC server and optional Modbus user communications as well as settings for the optional barcode reader The Email menu provides settings for the email server to send SMS text messages and or emails on alarm and allows the user to compose and send messages to any user configured in the system duia Email The Offline menu provides access to the nCompass offline setup screens which provide the user with the ability to adjust the date time calibrate the touch screen configure digital and analog IO etc Offline 4 8 FDC nCompass Basic Operation nCompass i4 3 4 3 3 2 Icon Slide Page Based Device Settings Menu Alarm Defrost Message Barcode Redundancy Basic Operation f FuTUReEDESIGN N T R O Slide page 1 provides access to the primary nCompass setup screens These include options for Navigation type control loop setpoint Limits Alarm setup Event tagname entry power Recovery Defrost operation setup and email server settings and messaging It also includes access to the communications settings for the web page VNC server and optional Modbus user communications Slide page 2 provides access to the nCompass offline setup screens which provide the user wit
185. pe settings The redundancy Status indicates the current operating condition of redundancy These include System 1 2 Inactive System 1 Active automatic System 1 Active manual system 2 Active automatic Redundancy not operating control outputs off system 1 and 2 Redundancy operating system 1 as primary system in auto Redundancy operating system 1 as primary system in manual Redundancy operating system 2 as primary system in auto Redundancy operating system 2 as primary system in manual Redundancy operating system 1 in auto primary system 2 failed Redundancy operating system 2 in auto primary system 1 failed Redundancy operating system 1 and 2 concurrently alarm activated Redundancy operating system 1 and 2 off dual system failure system 2 Active manual System 1 Active fail Mode System 2 Active fail Mode System 1 2 Active System 1 2 Failed The operational Mode selection indicates the redundancy mode and allows the user to place redundancy in auto or manual operation When in manual mode only the primary system will operate and equal run time switching will not take place System failure alarm inputs and the redundancy process alarm are ignored When in auto mode systems will perform equal run time switching based on user time settings and alternate automatically upon system failure and redundancy process alarms The Primary system selection allows the user to select system 1 or system 2 for operation The prima
186. pen file button will display a dialog box where the user can select any alarm file to view NOTE Ifno alarms occurred on a given day an alarm file will not be created for that day Alarm File FTF failure Check cable and serwer 1 10 2013 10 20 AM The send email icon Eed allows the user to send a copy of the currently opened alarm file to any user configured in nCompass When the email icon is pressed an Add Recipients window will be displayed where the user can select recipients for the file from any of the email addresses configured under the nCompass email settings For information on how to add email recipients to nCompass see the section 8 9 Email 4 22 FDC nCompass Basic Operation nCompass i4 3 f FuTUREDESIGN 5 Automatic Ramp Soak Program Operation A ramp soak program is a set of instructions set points and events programmed as a timed sequence of steps When a program is run nCompass executes each step of the program automatically in sequence based on the time duration and settings for each step nCompass can store hundreds of automatic ram soak programs depending on storage usage for data history with up to 99 steps in each program To assist in setup and documentation of nCompass see the Orion M iSeries Configuration and Worksheets Excel file provided on the Future Design Controls website http www futuredesigncontrols com Orion M htm This document provides setup and configuration forms and temp
187. point limits outside of these configuration values Consult your OEM or equipment installer regarding the maximum set point limits permitted for your system Device Settings FDC nCompass 8 13 f FuTUReEDESsIGN N T R O nCompass i4 3 8 5 Event Names The Event names screen allows the user to change the names of the system events in order to describe what function they perform The event names are limited to nine alphanumeric characters Event Names EV1 DO 1 EV2 DO 2 EV3 DOS EVA DO 4 EVS DO 5 EV6 DO 6 To change the name of the event select the event by touching its current tag name in the list Press the Edit button and enter the new tag name using the alpha numeric keypad and press Done when finished The new name will then appear in the event name list box and will be used throughout all nCompass screens wherever the event is shown 8 6 Navigation nCompass provides both text based PC style menus and icon based slide page navigation menus similar to today s smart devices The user can select either type at any time from the Navigation screen Navigation E Menu Navigation E Icon Navigation Press the button for the desired menu type to make the selection The choices are mutually exclusive so when one selection is made the other will be de selected The button indicator for the active selection will illuminate to show the current selection 8 14 FDC nCompass Device Settings f F
188. pports over 25 languages e 30 000 hour LED display 1 2 FDC nCompass What is nCompass nCompass ia3 ff eurupenesron N T R O 2 installation The following two sections will explain how to install the nCompass control system nCompass controllers are pre loaded with all operating software and firmware before leaving the factory so it is ready to install when you receive it Refer to Section 2 for mounting information and Section 3 for power signal and control wiring Before beginning installation read through these sections to gain an understanding of the entire installation Consider the installation carefully Plan the power signal and control wiring before installing nCompass Also consider the cabinet space hardware dimensions and environmental conditions Use good wiring practices to minimize problems that may occur due to electrical interference To avoid potential electric shock and other hazards all mounting and wiring for nCompass must conform to the National Electric Code NEC and other locally applicable codes Special expertise is required to install wire configure and operate the nCompass controller Personnel without such expertise should not install wire or operate nCompass Prevent metal fragments and pieces of wire from dropping inside the housing of any nCompass component If necessary place a cover over the components during installation and wiring Ingress of such fragments and chips may cause a fire hazard
189. r concurrent systems nCompass will always operate in fail mode on the system that does not have a system failure If both 1 and 2 system failures occur the digital outputs configured for Redundant System 1 or 2 will be de energized During any system failure 1 2 or 1 and 2 the alarm must be reset from the main alarm screen and the condition cleared that caused the system failure Once the alarm condition is acknowledged and cleared the Reset button on the Redundancy screen must be pressed in order for normal system operation to resume at which point the backup system will become the primary system The user can switch from Auto to Manual mode at any time to run system 1 or 2 in manual operation while performing maintenance on the systems NOTE System 1 2 failures are defined by the OEM configured digital input selections When the assigned alarm input s for the system is active the system failure occurs Consult your OEM configuration for information on which inputs are configured for system 1 2 failure if any Device Settings FDC nCompass 8 7 f FuTUREDESIGN nCompass i4 3 N T R O 8 3 Alarms The Alarm screen provides access to the nCompass alarm module which contains up to 30 user configurable alarms These alarms can be assigned to any loop or monitor input in the system Pa t cad Setpoints NOTE After any and all changes made to any of the following alarm settings you MUST pr
190. r the use of nor makes any claims as to the security of the web server interface over your network The use of the web server is the responsibility of the end user To access and view the nCompass web page enter the following link in your PC s browser address window http IPaddress orion html From the example address shown on the screen above then entry would be http 192 168 0 6 orion html The following example is typical of the nCompass web page appearance The web page updates automatically every 30 seconds and provides information on each individual control loop ramp soak program status alarm status and system event status 10 6 FDC nCompass Communications nCompass ia3 f FuTUREDESIGN Untitled Document deet Explorer optimized for Bing and MSN Go E hitp 192 168 0 6 orion hi Ea fler SH Googe edid Sa lt p Favorites Untitled Document Es me Page Safety Toos h FUTURE DESIGN CONTROLS nCompass CM BRIDGEVIEW IL 888 751 5444 CONTROL DATA LOOP 1 PY 24 4 SP 25 0 LOOP 2 PV 50 2 SP 0 0 LOOP 3 PY 54 8 SP 0 0 AUTOMATED PROGRAM Program Name WAT Program Status Inactive o o Start Date Time 00 00 00 00 00 Est Complete Date Time 00 00 00 00 00 Current Step 0 Wait For LOOP 3 Target SP 0 0 SYSTEM ALARMS SYSTEM EVENTS EV1DO 1 OFF EV2 DO 2 OFF EV3 DO3 OFF EV4 DO 4 OFF
191. rd enclosure CM Firmware SD CM CM Control Module Firmware inserted into display SD slot Control Module CM 0000 010 Base CM no optional serial communications DI DO Al or AO and 1 8 chanel monitor card T C Options Power Supply PS5R SD24 85 264VAC power input Output 24VDC 60W 2 5A Cable CA2011 8A Cable from Display to Control Module DB9 connector display mini DIN on CM 8ft Loop Controls 9300 413001 FDC 9300 1 16 DIN control input 1 universal T C RTD mA amp Vdc Input 2 linear mA amp Vdc may be used as monitor input Output 1 mA PID RS485 communications Item 1 Model FDC 0450 4 3 Color Touch Screen WO EELER Order Matrix 1 Power Input 6 Software 1 11 to 36 VDC 0 None 2 Sound Output 7 Enclosure 0 None 0 Standard 3 SD Card Slot 8 Overlay Color 1 Yes B Black Overlay 4 Ethernet 9 Special Code 1 Yes N Neutral Overlay no name logo 5 Network 0 None Control System Options ordered separately as appropriate Control Loops Order appropriate loop controls separately Printed Operator Manual Part Number Orion nCompass_CM_i4 3 User Manual pdf Cable Control Module to Display FDC Orion nCompass CM i4 3 User Manual CA2011 8A Cable from FC5A CPU to display 8ft Note consult factory for other lengths and options Printed Configuration Manual Part Number Orion nCompass CM _i4 3 Config Manual pdf System Power Supply input 100 240VAC Output 24VDC FDC Orion nComp
192. rence 0 2 of full scale Junction compet seg SE sation accuracy 24 C mamun 0 5 of full scale 4025 increments 12 bita K O 325 C 2 5 mY J 000g O 1boC T O 200 C APPENDIX c O N T R O nCompass i4 3 d FUTUREDESION Analog Input Output Card Specifications page 2 of 3 r Resistance Analog Input Signal Type Voltage Impart Ta 0 to 4095 12 bit data 32758 to S2767 optional range cesignation Mote 2 Monotonicity Yes Input Data Out of Range Detectable Mote 31 Maximum Temporary Accuracy is not Deviation during 3 maximum assured wher Electrical Noise Tests noise is applied Common Moda Common mods reject ratio CMD 50 dB Noise Characteristics Data Type in Application Program Resistance Common Mode Voltage 16V DC Ne Cable Twisted pair shielded cable is rom mended for improved nose immunity 258 maximum Isolated between Input and power circuit lolation Photeoouplerisolated between input and mtemal circuit Effect of Improper Input Connection No damage Maximum Permanent Allowed Overload iN pe An m DC Mo Damage Selection of Analog Input Signal Type Using software programming Calibration or Verification to Maintain Rated Accuracy Irripetes sib Analog Output Specifications Analog Output Signal Type Voltage Output Current Output Out put Ranga to 10W DE dro 20 mA OC Load Impedance EE Applicable Load Type Resistive load FEA ALOSAL BO msec Settling Time F
193. rent step linearly over the time entered for the step This creates a ramp step NOTE A step time of zero can be entered for a step to implement an immediate set point change When coupled with a wait for condition on the following step there is no need to know the time it takes for the process to reach set point The wait condition can be used to trigger the next step typically a soak so that the desired soak time is achieved without having to determine what additional time may be needed in order to make sure that the process reaches set point before starting the soak time The Soak selections are used to turn on the guaranteed soak option for one or more of the controlled loops To enable guaranteed soak for a loop turn on the Soak selection for the corresponding loop When the step executes the program will automatically enter a hold condition if the loop s PV deviates from its set point by more than the soak limit setting for the loop as entered on the Soak limits screen Automatic Program Operation FDC nCompass 5 0 FUTUREDESIGN nCompass i4 3 c O N T R O NOTE Guaranteed soak is typically not used during set point ramping steps as the ramp rate will be affected if any process variable deviates from its soak band because the program will be placed into hold When the program is in hold the step length will be extended and all set points will no longer ramp at the desired rate They will maintain their current value until the timer
194. require backup or file deletion when no longer needed The Utilities section of the nCompass interface provides all the functionality required for maintaining the internal SD memory card The internal SD card should not be removed from the nCompass interface Any change to SD directory structure moving or deleting files with a PC may cause the nCompass interface to stop operating and a new SD card will need to be ordered Never move or delete the directories unless using the provided nCompass file utilities functions NOTE The data log files programs alarm log and audit trail directories are saved to the internal SD card not the USB memory stick device plugged into the nCompass interface Never unplug the SD card when nCompass Is powered up or loss of data may result The USB file transfer screen allows the user to copy or erase files from the internal SD card Complete file directories for all nCompass file types can be copied to the USB memory stick and erased from the internal SD card The current status for file functions is displayed for the operator during copy delete operations nCompass also allows automatic programs to be imported from the USB memory stick Programs must be exported from another nCompass device to the memory stick first before this function can be used nCompass will look for Program directories on the memory stick for import and alert the user if none exist NOTE AU file transfer functions can be used while
195. rol input 2 inputs of monitor cards or combination of both 0 None Note 2 Dual loop HW3500 is limited to 1 controller maximum 2 loops 1 FC4A N08B1 8 digital input card 24Vdc 2 FC4A N08A11 8 digital input card 120Vac Note 3 CM XXXXXXX includes the additional standard components Note The above optional digital inputs DI are in addition to the eight 24Vdc digital inputs that are standard on the CM system maximum of 16 digital inputs Part FC4A HPC3 Note A Comms Card RS485 comms to loop controls and monitor cards 4 Optional Digital Outputs DIN Rail Mount plug into CM Part FCOA DIORAL 7 Control Module with 8 Digital Inputs DI and 8 Digital Outputs DO 0 None 1 FC4A T08S1 8 digital output TTL 24Vdc source Part FC4A PT1 Note B 2 FC4A R081 8 digital output Relay 240Vac 2 amps Real Time Clock module Note The above optional digital outputs DO are in addition to the 8 DO that are Part FC4A PM64 Note B standard on the CPU 6 relay amp 2 TTL 24Vdc maximum of 16 DO Memory Module Note A FC4A HPC3 must be plugged into the FC5A D16RA1 control module during installation as described in the manual 5 Optional Analog UO DIN Rail Mount plug into CM 0 None NoteB The FC4A PT1 and FC4A PM64 modules are assembled and 4 One AI O card FC4A L03A1 4 20mA or 0 10Vdc IO contained within the FC5A D16R1 Control Module 2 Two Al O cards FC4A L03A1 4 20mA or 0 10Vdc IO All other CM Control Mo
196. roll through each available input To make changes to the input s configuration select the desired transition mode and function for the input Once all selections have been made press the Save button to save the changes If you do not press the Save button all changes will be lost if you leave the screen or navigate to another digital input NOTE More than one digital input can be configured for the same function If more than one is set for the same function make sure that they do not interfere with each other or the selected function they are to perform may not operate as expected The Delay is used to delay the input function for a period of time in seconds once the input transition state is detected and maintained It can be used to debounce an input or act as an alarm delay to prevent false alarms The time is configurable from 0 0 to 3276 0 seconds The Transition select buttons set the input state that makes the input perform the required function High This setting sets the input up to perform the desired function when the input goes from an off state to an on state This requires the application of 24Vdc power to the input Low This setting sets the input up to perform the desired function when the input goes from an on state to an off state That requires the removal of 24Vdc power from the input The digital input Function defines what event is to happen when the input meets the transition state The Inpu
197. rols will maintain the last set point value prior to power loss with loop control outputs active ON Select Hold to have nCompass return to operation at the same point it was prior to the power outage Ifa program was running the program will still be active however it will remain in hold with the active set points and events that it was operating under prior to losing power until manually set to continue select Continue to have nCompass pick up where it left off on loss of power If a program was running prior to the power outage it will resume where it left off and continue through the rest of the program Note that the set point ramp will continue from the set point value at the time of power interruption unless the program is in the ramp rate configuration If the program is running under ramp rate mode the program will continue a ramp step from the highest process value of all loops at the time power is restored This insures that the ramp rate can not be exceeded if power was off for an extended period of time in which the process temperature was able to fall significantly If the program was running a dwell step at the time power was lost the program will automatically advance to the previous step ramp rate step when power is restored This will ramp the temperatures back up to the dwell temperature from the highest process value based on the ramp rate entry of the previous step and then begin the entire dwell step over agai
198. rom scratch within minutes In addition to a maximum of three loops of control nNCompass can also provide up to an additional 15 inputs for process monitoring for a total of 18 process inputs The system is provided with eight 24Vdc digital inputs two 24Vdc outputs and 6 relay outputs standard nCompass can be expanded to a total of 16 digital inputs and 16 digital outputs nCompass also provides the capability of accepting analog inputs for remote set point control and analog outputs capable of retransmitting system variables PV SP or Out to other devices such as a chart recorder The 0 10Vdc or 4 20mA user selectable signals are provided through the addition of optional analog expander cards Individual process controllers one for each loop in the system provide reliable consistent and accurate control by distributing the process control requirements of the system among multiple processors Each loop controller provides full auto tune functionality with high resolution universal process inputs When coupled with the built in ramping programmer of nCompass it allows for automatic timed control of all processes and outputs of the system 1 1 Features The nCompass digital inputs can be configured as alarm inputs with adjustable delay timers as control inputs for controlling automatic program operation or for direct control of the system s digital outputs The nCompass digital outputs can be used as direct outputs for controlling exter
199. rupenesron N T R O The defrost Duration field is used to set the defrost duration The time can be entered in minutes from 0 999 If O is entered for the defrost duration defrost will not operate The defrost duration must be set from 1 999 minutes in order to activate defrost Setting the field to zero allows the user to disable defrost operation for testing purposes or to prevent it from operating if its use is not required The Fan Delay field is used to adjust the fan delay The time can be set from 0 999 seconds Pressing Defrost while programmed for timed defrost will activate a single defrost cycle If defrost is configured for timed process defrost will only activate if the OEM configured loop SP or monitor point PV is below the enable set point that is entered in the nCompass configurator 8 1 1 Defrost Description of Operation The defrost interval timer is activated when the OEM configured defrost enable output s are on for timed defrost In order for the interval timer to be activated when defrost is configured for timed process the OEM configured loop set point or monitor point value must also be below the enable set point If at any time the enable outputs are turned off or the loop or monitor point rises above the enable set point the interval timer will be reset NOTE When a loop is selected as the enable point the loop set point must be equal to or below the defrost enable set point When a monitor point is selected
200. ry system selection can only be made when redundancy is placed in manual mode When in auto mode the primary system selection will automatically alternate according to the alternating time settings 8 4 FDC nCompass Device Settings nCompass ia3 ff eurupenesron N T R O The product Load Timer button allows the user to activate the alarm start delay of the OEM configured redundancy process alarm This alarm is one of the 30 alarms provided by nCompass and can be configured by the user for process high low deviation or rate of change see section 8 3 Alarms By activating the product load timer the alarm will be reset and the alarm start delay will become active Once the start delay expires if the alarm condition is present the alarm delay will become active and once expired the redundancy alarm will be activated NOTE Ifthe product load timer alarm inhibit is already active pressing the Load Timer button will cause nCompass to prompt the user if they wish to reset the timer This allows the user to reset the start delay each time the button is pressed should more time be required to clear the condition that will cause the redundancy alarm to occur The Reset button is used to reset a redundancy system failure system 1 fail system 2 fail system 1 2 fail and reset alternating redundancy upon a redundancy alarm Normal system switching will only resume once the alarm condition has been reset and cleared on the Alarm screen and the R
201. s screen Using the File menu choose the Open menu item to select from a list of all available programs stored on nCompass Open the desired program from the list and then select Start from the Program menu Enter the desired start step and press the Start button 2 How do I know which program is running When a program is running the name is displayed on Status view screen as well as the Single and Dual view screens nCompass will indicate that the program is running when it is in operation If a program is not running nCompass will display the name of the currently loaded program i e present in memory and ready to be run 3 Why is the program name not appearing correctly nCompass only uses the first ten characters of the program name for display updates and record keeping even though programs can be saved with names of up to 16 characters long When naming programs try to keep the names limited to ten characters if the desire is to have the full program name shown or use the first ten characters as a means of more clearly identifying the program when more than ten characters are used 4 How do I enter a jump step A jump step is a normal step however instead of continuing to the next step of the program when the step is complete the program jumps to a specified step To enter a jump set the step number you want to the program to jump to and the number of times that the jump is to take place into
202. s and templates for all nCompass features including those provided under the Setup menu The Device Settings menu provides navigation to the following functions VII Defrost View menu Redundancy Defrost Provides access to defrost settings i Redundancy Provides access to redundancy settings Set menu Alarms Provides access to the alarm module Alarm Limit Sets minimum maximum set points allowed for each loop _ Limit Event Allows the user to edit names used to describe events Comms Event Navigation Allows the user to choose text based or icon based slide page Email gt EEN navigation menus Navigation Recovery Allows user to set program recovery action on power failure Offline Recovery acl Email Offline Message Offline Device Settings Comms menu Offline menu Offline Comms Allows user to set nCompass communication settings MDE Barcode Provides access to the barcode reader settings eua Comms T Barcode Offline Email menu Email Provides access to the nCompass email system manager Message Allows the user to send an email message to users entered in the system Provides access to offline system settings FDC nCompass 8 1 f FuTUREDESIGN nCompass i4 3 N T R O 8 1 Defrost The nCompass defrost function was designed for use with refrigeration or other types of cooling systems that may accumulate ice on cooling surfaces such as f
203. s configured for Redundant System 1 or Redundant System 2 that correspond with the selected primary system will be turned on The opposing system then becomes the backup system by default When the redundancy process alarm exists nNCompass will switch to the backup system turn off the primary system output and turn on the backup system output and operate in fail mode on the backup system until the alarm condition is cleared and the Reset button is pressed If the redundancy alarm is set for latching the user must press the alarm reset button on the main alarm screen to acknowledge the alarm in order for it to clear Once the alarm condition is cleared and the redundancy Reset button is pressed the backup system becomes the primary system and normal redundancy operation resumes The user can switch from Auto to Manual at any time to select primary systems or run a single system in manual mode 8 2 3 Equal Run Time Switching Equal run time switching when no redundancy alarms exist is provided for both alternate and concurrent systems Equal run time switching is OEM configured for Before Defrost or After Defrost operation NOTE If defrost is not configured equal run time switching if configured will correspond to the After Defrost mode of operation however no defrost action would take place prior to the system switch 8 2 3 1 Before Defrost Switching Before defrost operation pro
204. s not available for the monitor inputs The monitor inputs are not associated with a control set point Out A percent output alarm uses one or two set points to define a specific alarm value The alarm can be set for high only low only or both high and low NOTE The percent output alarm type is not available for the monitor inputs Monitor inputs do not have control outputs 8 8 FDC nCompass Device Settings nCompass ia3 ff eurupenesron N T R O ROC A rate of change alarm looks for an amount of change in the input over a pre determined period of time It uses a single delta set point to define the amount of change allowed and a single time set point to define a time period in which the amount of change is allowed to occur A rate of change alarm can be set for increase only alarm on rise decrease only alarm on fall or both The alarm mode selections are used to select the alarm action Available selections are as follows Latch When latching is enabled the alarm will remain active even after the alarm condition has passed until acknowledged by the user Latched alarms are acknowledged by the user when pressing the Reset button on the Alarm screen or by activating a digital input configured for Remote Alarm Reset An alarm that does not having latching enabled self clearing will deactivate automatically when the alarm condition has passed NOTE Latching alarms are acknowledged even when the alarm condition i
205. s still present when the user activates the alarm reset The latched alarm will then automatically clear once the alarm condition is no longer present If the alarm reset was not activated during the alarm period the alarm will remain latched until the user activates the alarm reset Silent This is used to control the method by which an alarm is reported When turned off an alarm condition will trigger the audible alarm and the alarm notification icon will flash to indicate the alarm condition The buzzer must then be manually silenced by pressing the reset button on the alarm screen If silent mode is on the audible alarm will not sound when the alarm condition occurs If the alarm latch is turned off the alarm will not be reported on the alarm screen If the alarm latch is turned on which requires manual reset by the operator the alarm will be reported on the alarm screen in order to notify the user to reset the alarm however the alarm notification icon will not flash The user must navigate to the alarm screen in order to determine if a latched alarm is present Start Delay When the start delay is off the alarm will activate immediately when the input exceeds the alarm set points as programmed When the start delay is on the input must first enter the normal operating range be above the low alarm set point and or below the high alarm set point before the alarm can be activated Upon the next excursion beyond the alarm set points the a
206. s the Accept button to change the password no spaces allowed 4 character minimum and 16 characters maximum Password New Password Contirm Password Save Cancel 6 3 Setting User Access The Access tab provides the administrator the ability to assign rights to each user level System User Supervisor and Administrator To enable or disable specific program functions user rights for each user level select the user right from the list and press the corresponding on off button for the user level you want to change access rights for If the button is set to on user access will be enabled for the user group System User Supervisor Administrator System User Supervisor Administrator OFF TR WOR on User access for Security can not be disabled for the administrator group This is a safety feature to make sure that any administrator with the proper user ID and password can access security If the administrator losses his her ID or password there is no back door to the system and it will have to be reset and reprogrammed in order to return to normal operation Security FDC nCompass 6 3 f FuTUReEDESsIGN c O N T R O nCompass i4 3 6 3 1 Security System User Access Shown below is a list of the available user rights where to find the menu item s applicable to the user right and a description of what it applies to Note that the OEM configuration allows many menu items to be disable
207. sible Computer Link Modem Communication Pe Possible 31 slaves max Modbus Communication Possible dert All JN 2 port 2 Maximum Cable Length 200m Note 3 Isolation between Internal Circuit and oe See Not isolated Communication Port Note 3 Recommended cable for R5485 Twisted pair shielded cable with a minimum core wire of 0 3 mm Conductor resistance 85 2 km maximum shield resistance 20 2 km maximum Connector Se SSS ASS ED mi communication 1 ud Z a a a i x Communication Method Data Link Communication The proper tightening torque of the terminal screws on the R5485 communication adapter and R5485 communication module is 0 2 to 0 25 N m For tightening the screws use screwdriver 525 0 4 x 2 5 Phoenix Contact APPENDIX FDC nCompass A 15 P RS232 485 Communications Card Specifications page 2 of 2 N T R O FUTUREDESION nCompass i4 3 Optional User RS485 RS232 Barcode Reader Card Specifications Type No FCSA SIF2 FCSA SIF4 Electrical Characteristics EIA RS232C compliant EIA R5485 compliant Shielded twisted pair cable with a mini Cable T Shielded multi core cable 24AWG x 6 cane Ieemgegenemmeeg LEE Cable Specifications Dielectric strength 2000W min 2000W min 700V AC min Insulation resistance 100 M 2 kmi Maximum Nodes 2 1 1 Communication 32 MC1 5 10 G 3 81BK Phoenix Contact Applicable terminal block FC4 A PMTLOP Connector Insertion Removal Durability 1
208. ss i4 3 d FUTUREDESION WNC Viewer Options Display inputs Connection Printing Expert Scaling Ce No scaling C Scale to window size Custom scaling I Preserve aspect hablar IT Full screen mode T Enable toolbar I Adapt to network speed recommended Best quality Best mompressian M Use these settings for all new connections Basic Cancel Next select the Inputs tab and deselect all entries except for Enable mouse input and Rate limit mouse move events The Inputs drop down selection box will automatically change to Custom when the settings are made VNC Viewer Options Display Inputs Connection Printing Expert Custom T Enable keyboard input Inputs Pass special keys direct bo vie Server M Enable mouse input T Enable 3 button mouse emulation h Rateimit mouse move events Share dipboard with VNC Server T Enable file transfer Enable chat Menu key none M Use these settings for all new connections Basic Cancel Communications FDC nCompass 10 9 P Proceed to the Expert tab Scroll down the list of settings until you find the PreferredEncoding and Protocol3 3 options Set the preferred encoding to Hextile and the Protocol 3 3 option to true Verify that the Use these settings for all new connections checkbox at the bottom of the window is checked and click t
209. system events on and off select Events from the home View menu Press the switch for each event that you want to turn on or off to toggle the on off state of the event If more than eight events are configured the left and right arrow buttons will be shown Pressing either scroll button will allow the user to switch between screens in order to view and set all of the available system events Basic Operation FDC nCompass 4 17 FUTUREDESIGN nCompass i4 3 P 4 7 Process Monitoring The loop view screens provide the current process values of nCompass In order to view the process inputs over time nCompass provides real time charts Four user configurable trends are provided with up to six plot points per trend allowing a total of 24 process inputs to be monitored In addition nNCompass provides status monitors for all of the digital inputs and outputs of the system This allows an operator to keep track of all inputs and outputs of the control module 4 7 1 Charts The Trends screen is accessed from the home View menu The real time trends can be configured to display the process variable PV set point SP and percentage of output of control loops and the process variable of monitor points over a selectable period of time The vertical axis determines the range of displayed data while the horizontal axis determines the history period The maximum time period that can be shown in a trend is 24 hours The rate at which
210. t incidental special consequential or any other damages costs or expenses excepting only the cost or expense of repair or replacement of Future Design Control products as described below Future Design Controls sole responsibility under the warranty at Future Design Controls option is limited to replacement or repair free of charge or refund of purchase price within the warranty period specified This warranty does not apply to damage resulting from transportation alteration misuse or abuse Future Design Controls reserves the right to make changes without notification to purchaser to materials or processing that do not affect compliance with any applicable specifications Return Material Authorization Contact Future Design Controls for Return Material Authorization Number prior to returning any product to our facility q FUTUREDESION T R 7524 West 98th Place Bridgeview IL 60455 Phone 888 751 5444 Fax 888 307 8014 http www futuredesigncontrols com APPENDIX FDC nCompass A 27
211. t Function list is shown when the function selection button is pressed The input functions selections are mutually exclusive i e only one can be made ata time If Alarm Input is currently selected for the input function and another function such as Hold Program is then selected as the input function the alarm input function will automatically be off An input can also be disabled by turning off all of the input functions Once the desired selection has been made press the Return Button to return to the Digital Input screen 9 12 FDC nCompass Offline Setup nCompass ia3 ff eurupenesron Alarm Input Start Program Hold Program Continue Program End Program Wait Input Control Output Defeat Output Offline Setup N T R O Function ON Alarm Input OFF Hold Program When selected the input will provide a visual alarm notification on alarm screen Using the Defeat selection the input can be configured to disable specific digital outputs on the nCompass control module The alarm condition will be maintained as long as the input is activated The alarm will not clear until the input returns to its deactivated state and the alarm is reset on the alarm screen or through a digital input configured as Reset Alarm When selected the input will start the currently loaded program at step one Ifa program is currently running no action will occur This is a single shot
212. t press the Save button the change will be lost if you leave the screen or navigate to another digital output NOTE More than one output can be set for the same function Each output is independent of the others thus they each perform their own task The Delay Start delays the output from coming on for the period of time entered for any output function selected The delay time can be set from 0 0 to 3276 0 seconds The Delay Stop maintains the output for the time period entered once the condition requiring the output to be on is removed The delay time can be set from 0 0 to 3276 0 seconds The Interval time can be used to pulse the output on and off when the condition requiring the output to be on is present The interval time is used for both the on period and off period For example if the interval is set to 1 second the output will be on for 1 second then off for 1 second and so on A value of zero indicates a constant on condition output does not cycle The interval time can be set from 0 0 to 3276 0 seconds The Repeat time is shown when the digital output is configured as a Remote Alarm NO or Remote Alarm N C It can be used to re activate the output after a period of time if an alarm is still active ring back If the repeat time is set to zero the feature is disabled When disabled once the output activates on a new alarm and the alarm is then reset the output will not activate again for the same alarm con
213. t the step number Start Start Step a gt Once the desired start step number is entered press the Start button The program will then be transferred to the control module s memory and then started once the transfer is complete The Status screen will then be displayed NOTE Ifthe program was set up with the auto start feature enabled the program will enter the auto start mode immediately upon start Once the set date or day and time is reached the program will begin running The start date shown on the Status view screen indicates when the program will start based on the auto start settings To stop a program select Halt or Off from the Program menu When a program is stopped the loops will return to single set point static mode operation 5 10 FDC nCompass Automatic Program Operation nCompass ia3 ff eurupenesron N T R O The Halt selection stops the running program but leaves the set points and system events at their current values when the program stops This allows you to stop a program and continue in static mode without disrupting any processes and causing a hiccup in operation The Off selection stops the running program and turns all system events off The loop control set points will remain at their current values when the program is stopped and their outputs will continue to operate according to the set point value however all system events will be turned off This allows you to i
214. ta records to find the specific information you are looking for from a particular time period NOTE nCompass will automatically use the program name as the filename for the log file This provides a simple identifier for log files that pertain only to a automatic program operation Any entry made in the File Name field will be ignored 7 2 1 Calculating Log File Size nCompass saves the log file in a text based format csv so the amount of memory consumed for each reading is dependant upon the number of digits required to accurately display the value This optimizes memory usage but also makes calculating an exact file size difficult To obtain a worst case approximation of the resultant file size use the following formula File Size KB 1 0 023 0 006 number of log points number of readings Data Logging FDC nCompass 7 3 f FuTUREDESIGN nCompass i4 3 N T R O 7 3 Reviewing Historical Data Historical files can be opened and viewed using the historical viewer In order to view a historical data file it must first be opened by selecting Open from the File menu Once the file has been opened nCompass will automatically plot the first eight channels of the historical data file or the user can choose to cancel the plot select which channels should be plotted as well as adjust the specific time period to plot 7 3 1 History Plot Setup The history plot setup allows the user to select any time frame zoom in out from
215. tal Input Control Remote Alarm NC Defrost Precool Redundant System 1 Redundant System 2 nCompass i4 3 N T R O When selected the output acts as a general fault output Any alarm in nCompass will activate this output A common use would be for connection to an audible visual alarm to alert operators of a problem When the alarm Reset button is pressed on the Alarm screen the output will be turned off When used in conjunction with the repeat time setting the output will automatically turn back on after the repeat time period if any alarm condition is still present When selected the output can be controlled directly by a loop monitor alarm The alarm must be configured to control the output See Section 8 3 Alarms for information on assigning the alarm to the digital output NOTE If more than one loop monitor alarm is assigned to the output the output will not operate correctly and may cycle on and off uncontrollably Do not assign more than one alarm to an output When selected the output will turn on when the selected digital input alarm occurs The output will stay on until the alarm is silenced The selected digital input must be configured as an alarm input or the output will not operate When selected the output will turn on and off based on the selected input status The input acts as the switch to turn the digital input on and off The selected digital input must be configured for digital output
216. tection circuit can be used when the load impedance 1s smaller than the KC impedance in an AC load power circuit R Resistor of approximately the same resistance value as the load C 0 1 to 1 pF This protection circuit can be used for both AC and DC load power circuits R Resistor of approximately the same resistance value as the load C 0 1 to l pF This protection circuit can be used for DC load power circuits Use a diode with the following ratings Reverse withstand voltage Power voltage of the load circuit x 10 Forward current More than the load current l Output OC This protection circuit can be used for both AC and DC load power circuits Wiring FDC nCompass 3 11 P 3 6 1 Main CPU Wiring NOTE The following information covers basic input output connection information for the nCompass control module Since nCompass is a fully configurable control system the use of each input and output is dependant upon the application therefore the input and output control devices and real world connections are determined by the system designer FUTUREDESION nCompass i4 3 N T R O FCSA D16R 1 16 1 0 Relay and Transistor Source High speed Output Type CPU Module Applicable Terminal Blocks TBI Left Side FCSA PMTISP supplied with the CPU module TB2 Right Side FC4A PMTSI16P supplied with the CPU module Sink Input Wiring Source Output Wiring TB1 CR 2 wire Sensor b i E Vi P d eh EI Pr
217. tems are also configured consult the following section 8 2 Redundancy for additional information on defrost operation in conjunction with redundant system operation Device Settings FDC nCompass 8 3 f FUTUREDESICN N T R O nCompass i4 3 8 2 Redundancy nCompass can be configured by the OEM to operate redundant systems These systems could be pump stations refrigeration units etc This feature would be typically used when two identical systems share a common process and the failure of one system would turn on the back up system so that the process can continue operation with interruption nCompass allows the systems to be configured for alternate or concurrent modes operation Alternate and concurrent mode operation both provide equal run time switching for each system when a redundancy alarm high low alarm system failure does not exist Redundancy Status Primary System 1 a System 2 Automatic al Manual Alternate ES Load Timer Minimum Time minute 0 The redundancy settings are accessed by selecting Redundancy from the device settings View menu They allow the user to set the redundancy mode of operation select the primary system and adjust the concurrent minimum runtime and or alternating times The user can also activate the product Load Timer which enables the alarm inhibit of the OEM configured redundancy alarm Consult your OEM configuration for the redundancy ty
218. that any Ethernet capable devices themselves have any security features at all The nCompass VNC server only provides minimal single password based security access Separating the control LAN from the office LAN using a firewall would increase security and only allow control access that is based on a combination of IP source address destination address and port number This is by no means completely hacker proof but it should keep the well meaning co workers out Another hazard is connecting consumer plug and play devices to your control LAN A printer for example might flood the network with traffic in a broadcast storm as it tries to self configure or advertise its presence to all nodes on the network Faulty devices for example defective NIC cards can transmit large amounts of bad packets i e runts which are abnormally short Ethernet frames into your network Using switches instead of hubs will limit the effect of such problems Communications FDC nCompass 10 1 f FuTUReEDESIGN N T R O nCompass i4 3 The most commonly overlooked source of problems is cabling Not all cables are created equal Electrical noise generated by factory equipment or other electrical equipment in the area could easily corrupt transmitted data over the network and cause devices to lock up or shut down the VNC server both of which then require nCompass to be shut down and restarted to clear the problem Select the right cable for t
219. the step you want to jump from When that step is complete the jump settings will tell the program to jump to the specified step until all jumps have taken place The next time the jump step is executed after all jumps have taken place the program will continue on to the next step 5 Why is the program not coming out of a Wait For When a wait for condition is applied to a step the step will not begin until the wait for condition is met When using a wait condition to initiate a soak time be sure to place the wait for condition on the soak step If the wait for is applied to the ramp step the program will not continue because the set point will not change until the wait for condition is met i e the ramp can not take place until the step is executed Since the set point does not change the input will not change to meet the wait for set point and the program will wait indefinitely If the wait for condition is a digital input the selected input must meet its configured transition state after the wait for has been initiated If the input turns on or off before the wait for step has been entered the program will not continue because the change in state of the input must be seen after the wait has been initiated Automatic Program Operation FDC nCompass 5 13 f FuTUREDESIGN nCompass i4 3 N T R O 6 Why has the program not completed its run by the stop date given when I started it The estimated stop date provided by nCo
220. thermocouple extension wire to avoid reading errors DIP switch 9 is used to select upscale or downscale burnout A value of 32 768 is used to indicate upscale burnout and a value of 32 767 is used to indicate downscale burnout When DIP switch 9 is turned on the module will use the upscale burnout value and when turned off the module will use the downscale burnout value NOTE DIP switch 8 is not used with the thermocouple module so its position does not affect operation i BTCISO I WA WW A 8 ae Tale fem e to ho 1 Li 2 2 3 3 A a 2 LH I k Oo oo A G bed did ad bel k 1 zb 1 zb 1 zech onl a loo r a D E LG ch d Lm 3 5 2 Current IO 8AIIS and Voltage lO 8AIVS Module Input Wiring The analog input modules are supplied as either a current input module IO 8AIIS or a voltage input module 1O 8AIVS The inputs are fully isolated from the internal logic and between inputs The standard setting for the IO 8AIIS module is 0 20mA input current which represents the minimum to maximum range setting in nCompass To obtain an input signal of 4 to 20mA the offset switch DIP switch 8 must be switched on The same applies to the IO 8AIV module An input voltage of 0 10Volts represents the minimum to maximum range setting in nNCompass To obtain an input signal range of 2 to 10V the offset switch DIP switch 8 must be switched on NOTE DIP switch 9 is used to select
221. ting Direction Incorrect Mounting Direction Installation FDC nCompass 2 7 f FuTUReEDESIGN N T R O nCompass i4 3 2 3 5 nCompass I O Modules The nCompass I O modules provide connections for user communications interfaces additional digital inputs and outputs and analog remote set point input and retransmit outputs The I O modules attach to the right side of the main CPU As each I O module is added it will connect to the right side of the previous module In order to connect each module the protective sticker that covers the connecter on the module must be removed in order to expose the connector for the next module to be plugged in When adding I O modules it is recommended that communication adapters be connected first then digital input and output modules and lastly analog input output modules 2 3 5 1 User Communication Modules nCompass offers an RS 485 FC5A SIF4 communications interface which allows multiple nCompass systems to be connected to a single PC interface In addition an RS 232 FC4A SIF2 is offered which allows a bar code reader to be connected to the controller 28 235 Communications Connector Cover sticker Remove ONLY when attaching additional O modules 2 3 5 2 Digital Input Module The digital input card FC4A N08B1 or FC4A N08A11 provides eight additional control inputs to the system SEHR 235 Cover sticker Remove ONLY when attaching additonal O modules
222. to 1 866 332 8014 Monday thru Friday 8 00 a m to 5 00 p m Eastern Standard Time You can also email your request to support futuredesigncontrols com An applications engineer will discuss your application with you Please have the following information available e Complete Model Ze and or Serial s for Component s in Question e Complete Software Version s e All Configuration Information e All User Manuals Warranty and return information is on the back cover of this manual Your Comments Your comments or suggestions on this manual are welcome Please send them to Future Design Controls P O Box 1196 Bridgeview Illinois 60455 Telephone 1 888 751 5444 fax 1 888 307 8014 csr futuredesigncontrols com The Orion nCompass CM i4 3 Multi loop Controller User Manual is copyrighted by Future Design Controls Inc 2012 all rights reserved http www futuredesigncontrols com nCompass htm FDC nCompass Preface nCompass ia3 ff eurupenesron N T R O 1 What is leie E TK 1 1 i a E E E E E E eee eee ee E A E 1 1 E E UE oe Te DEE 2 1 2 1 Enclosure Guidelines AA 2 1 2 1 1 Locating the NComMpass TOUCH Screen Interace cece cceccc neces seeeseeecseccseeccseessaeesseessueesseeseeeess 2 2 2 2 Environmental CONSIGSIATIONS cicisessiecescscenvaseasencostncunseciatgansnteabessaiaadacnaiacen en taakedebalguesntaabecsatendaceteatenses 2 2 23 Mounino Dimensi ns E 2 2 2 3 1 nCompass Touch Screen Jnteriace 2 2 23 2 N
223. to electronic documents included with the SOFTWARE you may make a copy either in hardcopy or electronic form provided that the software is not resold without the knowledge and acceptance of terms by Future Design Controls ll TITLE COPYRIGHT All title and copyrights in and to the SOFTWARE including but not limited to any images photographs animation video audio music text and applets incorporated into the SOFTWARE the accompanying printed materials and any copies of the SOFTWARE are owned by Future Design Controls or its suppliers The SOFTWARE is protected by copyright laws and international treaty provisions Therefore you must treat the SOFTWARE like any other copyrighted material except that you may either A make one copy of the SOFTWARE solely for backup or archival purposes or B install the SOFTWARE on each system purchase from Future Design Controls CE display PLC provided you keep the original solely for backup or archival purposes You may not copy the printed materials accompanying the SOFTWARE lll ADDITIONAL RIGHTS AND LIMITATIONS A Reverse Engineering De compilation and Disassembly You may not reverse engineer decompile disassemble or modify the SOFTWARE CE display software and or Control Module PLC code B No Separation of Components The SOFTWARE is licensed as a single product and the software programs comprising the SOFTWARE may not be separated for use on any hardware not supplied by Future Des
224. to run the sensor communication and control wiring for each controller to and from an enclosure door 2 3 3 nCompass Process Monitor Modules The monitor module as shown below mounts directly onto an industry standard DIN rail Field sensor wiring is on the front of the module via a plug in connector The module power and RS485 communications wiring is on a separate plug in connector on the bottom side of the housing Allow at least 25mm 1 in front of and below the module to accommodate the wiring Ensure that enough space is available above and below the module for adequate ventilation 97 5 3 64 86 5 3 41 109 0 4 99 a z 3 A E E Z D Lal E 10 lt a he lmla zl HE 2 4 FDC nCompass Installation N T R O nCompass i4 3 f eurupenesron 2 3 4 nCompass Control Module The basic nCompass control module consists of the RS 485 communications module FC4A HPC3 and the main CPU FC5A D16RS1 The components mount directly onto an industrial standard DIN rail Prior to mounting the components on the DIN rail they should be assembled and latched together NOTE If additional I O modules are used in the application they should also be connected to the CPU prior to mounting on the DIN rail See the following section 2 3 5 for dimensional information on the optional I O modules Communiction Connecion Cover dulebaie iellalfeiabahy RS425 Communication Module Installation FDC nC
225. trical currents to flow between devices along the ground path and result in damage to or malfunction of the device 3 2 1 Special Considerations for Low Voltage System Grounding A typical installation of the nCompass controller will result in a combination of both high voltage possibly 120Vac or higher and low voltage 24Vdc components and wiring While all components that are required to be grounded must all attach to the central ground point of the system randomly combining the grounds from both AC and DC components to a central ground bar can introduce noise into the DC grounds This is due to small ground loop currents that can come across the ground bar due to leakage from AC components such as variable speed drives It is good design practice and is recommended if the installation includes variable speed drives to install a separate DC isolated ground bar that is then connected to the central earth ground of the equipment through a single conductor This prevents ground currents of AC equipment from traveling across this ground bar and inducing small voltage imbalances across the DC component grounds While this may not be practical in all installations if problems arise in the system due to electrical interference installing this type of grounding system may reduce or eliminate the source of the problem NOTE Even though the DC power supply for the nCompass is powered from an AC source the ground of the power supply should be connect
226. try screen This will display the step Events screen You can then select which events are to be on during the step by touching each event toggle switch to turn the events on or off The light on the event buttons will illuminate bright yellow to indicate that an event is on lf more than 8 events are configured in the system the Group button will be shown Pressing this button will toggle between the first 8 and second group of up to 8 events so that all events can be edited for the step Pressing the left or right arrow button will allow you to scroll through each step of the program and not have to leave the step Events screen To return to the Entry screen press the Return button or select Entry from the View menu 5 4 FDC nCompass Automatic Program Operation FUTUREDESION N T R O nCompass i4 3 fil 5 2 Event Group WI est E 1 DO 1 E 2 DO 2 a DO 3 E 5 DO 5 E 6 DO 6 EYF DO 7 EY DOG NOTE The step events must be set individually for each step Even though a ramp soak program may be in operation if the events are not set the associated loop control output will not turn on To make setting step events quick and easy nCompass provides the Clone function from the Step menu When selected all event selections of the current step will be copied to all following steps This requires the user to only enter event selections for one step step 1 for example and if all following steps use th
227. tting or zoom normal to return to the full display NOTE When a chart is zoomed in it will not update with new information The chart must be in normal view mode in order to update at each time interval The chart will return to normal automatically when selecting a different screen to view 4 18 FDC nCompass Basic Operation f FuTUReEDESIGN N T R O nCompass i4 3 4 7 1 1 Chart Setup To configure a chart press the Set button in the upper right corner of the display The setup screen will be shown To assign channels to the chart simply touch the on off button for the desired items in the list to select them Select the left or right vertical axis for each item by selecting the item in the list and press the button for the desired Left or Right axis The left axis is the default axis selection If none of the channels are assigned to the right axis the axis will not be shown on the chart Once the channel selections have been made press the Axis button to adjust the time period and vertical axis ranges of the graph Axis 1 Return Time Period minutes 60 Maximum 100 Maximum 100 Minimum o Minimum 199 Time Period Adjusts the displayed time period for the graph The allowable range is from 4 to 1440 minutes 24 hours Maximum The maximum value sets the maximum range of the vertical access with a minimum value of 32 760 and a maximum of 32 760 Minimum The minimum value sets the m
228. uTUReEDESIGN N T R O nCompass i4 3 8 7 Recovery The power recovery settings allow the user to set the startup state of the system in the event of a power failure when an automatic ramp soak program was running at the time power was lost When power is restored nCompass compares the amount of time it was off to the recovery time setting and takes whatever action is selected for the recovery state To configure the power recovery settings first determine how long the system can be off without adversely affecting the process Set the Recovery Time to this value 0 32760 seconds maximum If power is returned in less time than this setting the program will continue from where it left off at the time power was lost If power is restored after a time period longer than the recovery time setting nCompass will take action based on the recovery state selection To set the power recovery action push the recovery mode button for the desired setting to set it as the power up state The selections are exclusive to one another i e only one can be selected at a time As a new selection is made the previous setting will be automatically turned off Recovery J Continue J Start Over J Resume Recovery Time seconds 60 Select Off to have nCompass default to the off state on power up If a program was running when power was lost the program will be stopped In addition all system events will be turned off Note that loop cont
229. unication wiring between the touch screen and port 1 of the CM NOTE Intermittent alarms do not affect the operation of nCompass or shut down the system The system will continue to operate according to its last given commands including ramp soak program operation Data logging may be affected depending upon the logging rate selected No audible alert is associated with this alarm Frequent alarms indicate a problem that should be resolved Insure that the communication wiring is properly shielded and routed away from control and power wiring Email Error Check cable or server Indicates that nCompass was unable to send an alarm message through the down mail server Verify that nCompass is properly connected to the network and that the email settings and addresses are valid FTP Check cable or server down Indicates that the FTP back up attempt of the data files failed Verify that nCompass is properly connected to the network and that the FTP settings are valid If nCompass is not connected to a network disable the FTP data back up to prevent seeing this alarm NTP Ping Failed Check Cable Indicates that nCompass was unable to synchronize its clock with the selected national time server Verify that nCompass is properly connected to the network and the selected time server is accessible If nCompass is not connected to a network disable the NTS clock to prevent seeing this alarm tagname Communications Error Check co
230. upscale or downscale failure when the input signal is too far above or too far below the selected input range A value of 32 768 is used to indicate upscale failure and a value of 32 767 is used to indicate downscale When DIP switch 9 is turned on the module will use the upscale failure value and when turned off the module will use the downscale value 3 8 FDC nCompass Wiring nCompass i4 3 f FUTUREDESICN N T R O The following diagram shows how the analog inputs are connected to a 0 4 20mA source Note that all of the common terminals are isolated from each other E DW RB 4 fa E ak H A S 2 3 d J S 4 5 5 a q T T e B Tve Wire Transmitter 4 Aer hela ma oe om ae ce r ZE ch _i ca isa The following diagram shows how the analog inputs are connected to a 0 2 10Vdc source Note that all of the common terminals are isolated from each other Wiring D A H A H 4 T F 2 E 3 3 4 4 D 5 6 G F m oo I E d Op ZU Jeer 3 cr Dee SI J gt el S l O al eg SC S 10 __ fe a 12 tl ol Jee Fett 44 an 7 i5 ee Common 8 16 G 17 e l ei FDC nCompass 3 9 f FuTUREDESIGN nCompass i4 3 N T R O 3 5 3 RTD Module IO 6RTD Input Wiring The IO 6RTD module is a 6 RTD input module The module can accommodate either 2 or 3 wire RTD sensors The RTD inputs are isolated from the internal logic
231. urrent Maximum Power Consumption Allowable Momentary Power Interruption Dielectric Strength Insulation Resistance Noise Resistance Inrosh Current Grounding Wire Power Supply Wire Effect of Improper Power Supply Connection FCSADLGRS1 Oto bn foperating ambient temperature 25 to 7080 10 te OES non condensing operating and storage humidity ZUEC 60664 1 IP20 EC 60525 Atrmceplere free from corrosive gases Oto 2 000m 0 ta 6 565 feet O to 3 000m OO to 9 8540 feet When mounted on a DIN rail o panel surface Gto 9 Hz amplitude 3 5 mm 9 to 150 Hz acceleration 9 8 mrs CLG 2 hours per as on each of three mutually perpendicular anes IEC 51131 3 Operation Transport 447 m s7 156 11 ms duration 3 shocks per axis on three mutually perpendicular axes EC 51131 2 Contact discharge 4 kV Air discharge 8 kV IEC GLOOG4 2 230g 24V BC 20 4 te 25 4 DC fincluding ripple TOO m Oe AV D CPU module 7 LO modus expansion module S 0 modules Joe OG AV DC 10 ma tat 24 DC GOO AC 1 minute Low AC 1 minute 10 Mi minimum 5007 DN meer LOMoOmpntroum GON DO meager 1 0 kV 5O ns to L ps 1 5 kW 50 ns to i ps B tween power and aw terminals Between V0 and ae terminals Between power and aa terminals Between 0 and aie terminals DC power terminals VO terminals coupling clamp BOA masimum 2a DO ULT OT AWG 2 ULIO ANGLS UL OT ae G33 ULOQ ANGLA Reverse polarity
232. utility will provide a notification message that the new calibration settings have been measured and to touch the screen to register the new calibration data just touch anywhere on the screen to close the window and return to the nCompass application to resume normal operation Mew calibration settings have been measured Touch the screen to register saved data 9 12 2 Backlight Settings The backlight settings allow the user to adjust the screen brightness as well as set a time period for dimming the backlight after a period of inactivity which can extend the life of the display To adjust the backlight settings press the Back Light button An alert message will appear stating that the application will be disabled to enter the backlight settings press Yes to continue Select the Backlight tab from on the Display Properties window Press the Advanced button to access the settings for the backlight NOTE The checkboxes on the Backlight tab for Automatically turn off backlight while on battery power and Automatically turn off backlight while on external power have no affect on backlight operation and should be left unchecked 9 22 FDC nCompass Offline Setup FUTUREDESION N T R O nCompass i4 3 To save re life you can adjust when the backlight automatically shuts off a off after js seconds l of continuous idle time Automatically turn off aa while on external
233. utomatic mode the loop will automatically adjust its output based on its PID settings When the loop is in manual operation the percentage of output for the loop can then be set manually to a fixed output percentage To switch the loop between auto and manual operation press the button and select Yes to put the loop in auto or manual mode To exit without changing the current loop mode select No When in manual mode the button s indicator will be on To adjust the loop output percentage when in manual operation touch the percent output display field and enter a positive value for heating or negative value for cooling Auto Tune This button initiates the loop controller s auto tune function To initiate the auto tune function press the button and select Yes During the auto tune procedure the Auto Tune button indicator will be on to show the tune is in progress When the tune is complete the button s indicator will automatically turn off to indicate the tune is off If at any time during the tune process you want to cancel the auto tune press the button and select Yes to cancel the tune NOTE The manual mode and auto tune functions may not be available with all controller options and or configurations Consult the FDC Controller Configuration Guide for the specific brand and model controller being used 4 5 2 Dual Loop View The Dual loop view shows two control loop and or process monitor inputs at a time
234. ve the program NOTE Programs can be saved with names of up to 16 characters long However nCompass only uses the first 10 characters of the program name for display updates and record keeping When naming programs try to keep the name limited to 10 characters in order to have the full program name shown or use the first 10 characters as a means of more clearly identifying the program when more than 10 characters are used in the name Max Steps Jump To Step 1 Cycle Count 0 LOOP 3 OC To assist with program entry the Step menu provides additional tools to help with the programming process Step Menu Options Insert Inserts a step into the program at the current step number Remove Deletes the current step Copy Copies the current step data including any event and wait settings Paste Pastes previously copied step data to the current step Clone Copies the current step events and pastes them to all following steps 5 2 FDC nCompass Automatic Program Operation f FuTUReEDESIGN N T R O nCompass i4 3 5 1 1 Setting Step Set Points and Time Ramp in Time Option When the program ramp in time configuration option is selected the length of each step is entered as a period of time in hours minutes and seconds The set points entered for each control loop are then used as the target set points for the step i e the set point that each control loop will arrive at by the end of the step Each set point will then c
235. vides equal run time switching at each timed defrost cycle No defrost cycle is performed during system switching in this mode Since system switching is done at each defrost cycle the system not running will naturally defrost due to normal ambient conditions between defrost intervals If a redundancy alarm occurs process alarm system 1 2 fail defrost cycles will be performed under fail mode operation based on timed or timed process defrost settings Pressing the demand defrost button while redundancy alarm conditions exist will perform a single defrost cycle based on timed or timed process defrost settings Pressing the demand defrost button while no redundancy alarm conditions exists will switch between system 1 and 2 with no defrost cycle being performed Primary systems and actual system digital outputs 1 2 will only switch when no redundancy alarm conditions exist and concurrent operation is not active 8 6 FDC nCompass Device Settings f FuTUReEDESIGN N T R O nCompass i4 3 When a defrost cycle is performed and the system is running in concurrent mode due to a redundancy alarm the backup system will be turned off and the primary system will go through the defrost cycle The redundancy alarm will be reset when defrost activates so that upon completion of the defrost cycle the redundancy alarm delay if any will have to expire again prior to turning on the backup system again This provides for a smart recovery action
236. visor logs on the system The supervisor then steps away from the system to take a phone call but does not log out before leaving If another user tries to change the control set point on any loop the system will require another login by an authorized user for that level before the control set point is actually changed This provides an extra level of protection to make the system more tamper proof The Security menu accessed from the home menu provides access to the security section of nCompass Configure Login Log Off Audit User Password The Security menu provides the following functions Configure Provides access to security setup to add users set rights and options Login Log on a user if security is enabled Log Off Log off a user if security is enabled Audit Allows the user to view any of the saved audit trail files User Shows the current user logged into the system Password Allows the current user to change their password To assist in setup and documentation of nCompass see the Orion M iSeries Configuration and Worksheets Excel file provided on the Future Design Controls website http www futuredesigncontrols com Orion M htm This document provides setup and configuration forms and templates for all of the nCompass features including Security Security FDC nCompass 6 1 f FUTUREDESICN N T R O nCompass i4 3 6 1 Adding Users The New user tab provides the ability
237. voltage is applied to the input If low is selected the input is on when voltage is removed from the input Functions performed via the digital inputs such as starting or stopping a ramp soak program are not logged to the audit trail These are external inputs to the control module and are not protected by security FDC nCompass Offline Setup FUTUREDESION c O N T R O nCompass i4 3 fil If a digital input is programmed for the Halt Setpoint Control function and the input is active any set point change entered by an operator for a control loop will be logged to the audit trail however the set point on the loop control will not change This will cause a discrepancy in the audit trail file as it will log the new set point entry even though the loop control is prevented from taking it 9 7 1 Digital Input Defeat The Defeat selections are only available for specific digital input functions Output defeat selections are available for the Alarm Input and Output Defeat functions Any of the available nCompass control module outputs can be selected for defeat and multiple outputs can be selected for defeat when the input is activated If more than eight outputs are available in the system the Group button will be shown allowing the user to toggle between the first eight outputs and the second group of up to eight outputs 16 max Defeat C Group Return DIG OUT 1 DIG OUT 2 DIG OUTS DIG OUT 4 DIG OUTS DIG O
238. wer the nCompass controller and highly inductive DC loads or input circuitry to other equipment with the same power supply used for nNCompass In order to insure that nCompass properly starts and stops due to power failure momentary power interruptions or brown out conditions it is recommended that a time delay on relay be installed in the power supply wiring to all components of nCompass This will insure that the system starts and stops correctly If the relay is not installed it may cause the analog input output cards if equipped to stop operating and or prevent the nCompass interface from booting up properly when subjected to momentary power interruptions less than 500ms Wiring FDC nCompass 3 1 f FuTUReEDESIGN N T R O nCompass i4 3 3 1 1 Installing the Power On Delay Relay Due to the rate at which AC DC power supplies reach their nominal supply voltage after application of power the relay contact of the timer should be installed between the output of the power supply and the power input of the nCompass control system components This allows the power supply output voltage to reach its nominal value prior to connecting nCompass to its output terminals In order to properly sense the loss of power due to the hold up times associated with AC DC power supplies the time delay relay coil should be wired to the AC power source for the DC power supply of nCompass This will insure that nCompass is turned off on at the proper tim
239. y nCompass configuration 135 Digital Input 14 function determined by nCompass configuration 136 Digital Input 15 function determined by nCompass configuration 137 Digital Input 16 function determined by nCompass configuration 3 6 5 Optional Digital Output Expansion Card Wiring NOTE The following information covers basic output connection information for the nCompass digital output expansion cards Since nCompass is a fully configurable control system the use of each output is dependant upon the application therefore the output load devices and real world connections are determined by the system designer FC44 TO8S1 point Transistor Source Output Module Screw Terminal Type Applicable Terminal Block FC4A PMT10P supplied with the output module Load Teminat Wo Output oll ar oa _4 Fuse LL D o LONG COM Connect a fuse appropriate for the load Wiring FDC nCompass 3 17 P FUTUREDESION nCompass i4 3 N T R O FC4AROS1 8 point Relay Output Module Screw Terminal Type Applicable Terminal Block FC4A PMT11P supplied with the output module COMO and COMA terminals are nat interconnected Connect a fuse appropriate for the load Q30 Digital Output 9 function determined by nCompass configuration Q31 Digital Output 10 function determined by nCompass configuration Q32 Digital Output 11 function determined by nCompass configuration Q33 Dig
240. y nCompass to log in to your company s mail server You can use your login if one is not set up specifically for the nCompass on your network Contact your network administrator for assistance The Return Address is the address given for nCompass on your company s mail server nCompass does not accept email messages however this field is required for proper email delivery for security anti soam purposes If using your personal login name you can also use your personal email address if one is not set up specifically for nCompass on your network Contact your network administrator for assistance 8 22 FDC nCompass Device Settings f FuTUReEDESIGN N T R O nCompass i4 3 The Password field is used for entering a password if required by your network server to send email Contact your system administrator for assistance This SMTP Address field is for entering the address of the email server used for sending emails This must be a valid mail server for which the above settings allow nCompass access Contact your system administrator for assistance This Subject field is used to enter a subject line for emails and or SMS text messages It can be used to provide an identifier to the recipients of the alarm message to know which chamber it is coming from NOTE It is recommended to put some form of entry in this field It can be left blank however many firewalls and spam filters will filter out messages without subject lines That may pr
241. y the total time entered Once complete resume the program by selecting Start from the Program menu NOTE When adjusting the time of a set point ramp step the ramp rate will be altered for the remainder of the step The ramp rate will decrease if time is added and increase if time is removed To subtract time from a step enter negative values for hours and or minutes 2 Adjust Time Set Hour Minute Automatic Program Operation FDC nCompass 5 11 f FuTUREDESIGN nCompass i4 3 N T R O 5 2 3 Advance Previous Next Step The advance step functions allow you to skip certain program steps or repeat them by advancing to the desired step To advance to a previous or next step in the program it must be first put into hold Once the program is in hold the advance step menu items are enabled under the Adjust menu By selecting Previous or Next the program will jump back or jump forward by one step each time the menu item is selected When the program is on the desired step place it back into run and the program will resume operation from the beginning of the selected step 5 3 Monitoring Automated Ramp Soak Program Operation The Status view provides all status information regarding the operation of the current program It can be accessed directly from the home Program menu as well as the program View menu When a ramp soak program is first started nNCompass automatically directs the user to t
242. you to cycle through each loop and monitor point available in the system By pressing either button the previous or next loop will appear in sequential order When the first or last loop is reached nCompass will automatically wrap around to the beginning or end of the list to show the next loop If the system has only one loop or monitor point the arrow buttons will not be shown as there is no other loop or monitor point to scroll to The loop name shown at the top right of the loop view will update as each loop or monitor point is selected The unit display field will update as well in order to provide the user with the units of measurement for the selected loop or monitor point Basic Operation FDC nCompass 4 15 f FuTUReEDESIGN N T R O nCompass i4 3 The set point entry field is the area where the screen can be touched in order to bring up the keypad entry window Using the numeric entry keypad a new set point can be entered Once entered the new set point will be shown in the set point entry field Adjustment of the set point is locked out if the loop is under ramp soak program control The special loop control function buttons Manual Mode and Auto Tune are used to define the mode of operation of the loop These buttons will not be available for process monitor inputs since there is no control function for the input Manual Mode This button switches the loop mode between automatic and manual operation When the loop is in a