1. Dongguan Tuancheng Automation Equipment Co LTD Crank Freq 0 Freq Condition of 1 0il Pressure 17 Crank oil 0 1 0 Disable 2 Freq Oil Pressure Condition of 3 D 18 Crank D 0 1 0 Disable 4 Oil Pressure D Freq In the process of cranking when the gens frequency 19 disconnect UE 10RZ exceeds this value the starter will be separated 20 D disconnect 3 32 V 8V 91 Frequency On 10 70 Hz 48HZ Gens normal when the gens frequency is greater than Load the frequency on load 22 Gens over freq 0 75 Hz 57HZ When generator frequency is over than the point and hold great than 3 seconds generator over frequency is active When generator frequency is low than the point generator 29 Cons Under ren Rahe ane low frequency and hold great than 15 seconds is active When generator battery voltage is over than the point 24 Battery over volt 0 35 V 35V and hold for 20 seconds battery over voltage signal is active It s a warning alarm Battery under When generator battery voltage is less than the point and 25 0 30 V 8V hold for 20 seconds battery under voltage signal is volt A i active Its a warning alarm Charge failure During generator is running when charge alternator 26 volt 0 30 V 4V WL D voltage is low than this point and remain for 5 seconds generator will warning alarm 27 Configurable 0 16 5 Idle 0 notused 9 Close Gens output1 output 1 Common ala
2. This is the amount of time that the start Idle speed is held active These allow the engine to hold low speed 9 Warming up delay 0 3600 S Os 10 Cooling delay 0 3600 S Os This is the amount of time that the stop Idle speed is held Te eRe ume 2600S 1 active These allow the engine to hold low speed This timer is used if the unit is configured to operate an Energize to stop engine It dictates the duration that the 12 ETS solenoid 0 120 S 30s ETS output will remain active after the module has hold detected the engine has come to rest If the ETS output is not configured this timer will still operate preventing an immediate restart Once the module has given a shutdown signal to the engine it expects the engine to come to rest It monitors 13 Fail to stop delay 0 120 S Os the Oil pressure and speed sensing sources and if they still indicate engine movement when this timer expires a Fail to stop alarm signal is generated 14 Close ATS time 0 20 S Os Breaker close pulse If it is set to zero the output will held 15 Open ATS time 0 20 S Os Breaker open pulse If it is set to zero the output will held 16 Condition of 0 1 1 Enable The PC configuration choices Default 0 Freq LXC701 Product User Manual Dongguan Tuancheng Automation Equipment Co LTD T 86 769 23836636 E F 86 769 23 166296 7 www lixise com Page 6 of 8 UIXISE SMART GENSET LXC701 Series Genset Controller
3. and start preheat delay when preheat delay is end fuel output 1 second preheat output will stop and crank output is start Here engine will start when crank successfully crank output stop Then engine enter the safe delay When the safe delay is end then engine enter the idle delay When the safe delay is end then idle relay is close and genset raise high speed When remote start input is inactive the engine enter the idle process after the delay of engine stop idle relay disconnect fuel relays output after the idle delay ETS solenoid output genset will automatically stop ETS solenoid disconnect when genset stop steady 4 3 3 Stop State Push the button when engine is running the button beside led will lighten enter idle process idle relay disconnect idle delay ended fuel disconnect ETS solenoid output genset stop ETS solenoid disconnect when genset stop steady When engine is waiting state push button 1 second above ETS solenoid will output and all led will be Lighten Loosen the stop buttons ETS solenoid output disconnect instantly and test lamps function is over When engine is waiting state only emergent stop alarm can be check Alarm Low Oil Pressure check after the safe delay the duration of 2 seconds above the module will alarm and stop engine High Temperature check after the safe delay the duration of 3 seconds above the module will alarm and stop engine Over speed check after the preheat dela
4. e te e 7 eo LXC701 Product User Manual Dongguan Tuancheng Automation Equipment Co LTD T 86 769 23836636 E F 86 769 23 166296 7 www lixise com Page 7 of 8 UIXISE SMART GENSET LXC701 Series Genset Controller 8 Case dimensions HOLE 65 65mm Dongguan Tuancheng Automation Equipment Co LTD 34mm 9 Typical connections Gens L O Aitemator Gens N O Remote Start Input eo D AUX OUTPUT1 AUX OUTPUT2 AUX OUTPUT3 Battery Battery negative should be grounded Starter Motor 10 Product packaging This product should be following sets 1 1 piece of controller model LXC701 2 2 piece of fixed cards 3 1 piece of product certificate 4 1 piece of product manual LXC701 Product User Manual m OS o Charge Alt Explain Coarse wire of 2 5 was copper core LIXiSE SMART GENSET Dongguan Tuancheng Automation Equipment Co LTD Tel 86 769 23836636 Fax 86 769 23166296 http www lixise com http www lixise net E mail sales lixise com Add Wentang Road Chashang industrial zone 18 Dongcheng Dongguan Guangdong China Dongguan Tuancheng Automation Equipment Co LTD T T 86 769 23836636 amp F 86 769 23 166296 7 www lixise com Page 8 of 8
5. UIXISE SMART GENSET LXC701 Series Genset Controller Dongguan Tuancheng Automation Equipment Co LTD LXC 01 Genset Controller User Manual Ver1 1 Date 2012 12 18 LXC701 Series Running Emergency Stop AUTOSTART MODULE High Engine Temp Low Oil Pressure Over Speed Charge Failure Low Battery Over Crank Common Alarm Model LXC701 Software version Date Version Note 2011 10 12 1 0 Original release 2012 12 18 1 1 Add USB communication interface LXC701 Product User Manual Dongguan Tuancheng Automation Equipment Co LTD T T 86 769 23836636 E F 86 769 23 166296 y www lixise com Page 1 of 8 UIXISE SMART GENSET LXC701 Series Genset Controller Dongguan Tuancheng Automation Equipment Co LTD Contents 1 SUMMA ace Seah a dpsed pach A eM NU ps O EE Be pastes 6 51 01100672 LN 1 tota dove deseo Ee PO ee Pe 4 Display symbol ANd OPELAatiON nee ecceccseesceseessesesessesseesessecsecseeesesecseeeeessecsseessesecsaeeseseesesecsseeeeesecsaeeseseeseseens 4 41 Push DIAGN Is scceccascnint a pontaranentvenpionrceonsaniibea AE REAA EAE REA E a 4 A ienen a a a a a E N 4 IO PRO 4 AAA O A i Matai lana mace abe ae 4 92 AUO it ere reer 4 3 3 Stop State iii IO A bin 5 III AS T E vuduidodeacanente 6 Parameters table only adjust via pc a ME De oo cooccoccornccicorocnno naco nocnconacnass 6 MAA AN E MA A A 8 Case GIMEMSIONS ao crciononiricas Mik
6. display various operation and alarm state 2 relay fixed output port fuel output starting output 3 a programmable output port can set common alarm output preheat output idle control stop output and other functions Provide PC programming port genset work necessary various delay output port definition power threshold can via PC settings PC only need a USB port Built in watch dog can never be dead halt ensuring smooth program execution Standard holes 67 67 inserted type connection terminals flame retardant ABS plastic shell 32 bit ARM MCU Stable performance easy installation Specification DC supply 8 35 V Single phase AC input AC 15 300 V 20 50Hz 60Hz Five relay output B 5A Crank output Fuel output Configurable output1 Configurable output2 Configurable output3 3 Digit input port connect to B is active Power Consumption standby mode 12V 0 3W 24V 0 4W working 12V 1W 24V 1 1W Operating Temperature Range 30 70 C Dimensions 72mmx72mmx38mm Panel cutout 67mmx67mm Weight 0 2kg LXC701 Product User Manual Dongguan Tuancheng Automation Equipment Co LTD a T 86 769 23836636 E F 86 769 23 166296 7 www lixise com Page 3 of 8 UIXISE SMART GENSET LXC701 Series Genset Controller Dongguan Tuancheng Automation Equipment Co LTD 4 Display symbol and operation 4 1 Push button Symbol Defined Description O Manual Push th
7. is button generator will start and the module comes into manual start button state es Push this button the module comes into auto state Stop button Push this button generator will stop and the module comes into stop state P In the standby mode if long pressing the button for 3 seconds all LED lights 4 2 LED Symbol Defined Description Before module crank successful if there is no speed Running Running led frequency Light off Otherwise Flashing After module crank successful Lighten Emergency Emergency stop alarm led Lighten when emergent stop input is active High Water Temp High Water Temp alarm led Lighten when high water temperature alarm is appearing Lighten when the module detects that the engine oil Low Oil Press Low Oil pressure alarm led pressure has fallen below the low oil pressure pre alarm setting level Over Speed Over speed alarm led Lighten when the engine speed has risen above the over speed pre alarm setting Charge Failure Charge Failure alarm led Lighten if the module does not detect a voltage from the alarm light terminal on the auxiliary charge alternator Lighten if the module detects that the plant DC supply Low Banery Low Beijer alagn ed has fallen below the low voltage setting level Light off when the module standby Slow flashing when the module is in the process from Over Crank Over Crank alarm led preheating to crank Lighten when module crank failure Ligh
8. o o O corea le Roo AA AA A A eseereserserresisseserresessestssisorsetiesisseseseosessesresesssenee 8 10 Product packaging Wii oi o cli ida LXC701 Product User Manual Dongguan Tuancheng Automation Equipment Co LTD T T 86 769 23836636 E F 86 769 23 166296 y www lixise com Page 2 of 8 UIXISE SMART GENSET LXC701 Series Genset Controller 1 Dongguan Tuancheng Automation Equipment Co LTD Summary The Module LXC701 is an small Automatic Engine Control Module It selects 3 kinds of working state Manual Auto Stop can pass panel light touch buttons artificially start stop genset also can through remote start signal input automatic starting generator and can detect fault low oil pressure high water temperature emergency stop alarm over speed automatically disconnect fuel relays and stop electromagnet to electric suction close Panel LED indicator fault state provide real and effective fault alarm signal 2 eo te e te e te e te e te e 2e ee eo Y eo te ee e Features The power supply a wide range 8 35 VDC can adapt different starting battery voltage environment With low oil pressure high water temperature over speed and emergency stop start failures and so on protection and instructions Can provide charging generator excitation function With idle speed control and ETS solenoid function Speed signal depend on frequency of generator Panel LED
9. rm 10 Open Gens 6 2 Preheat output 11 Gen On Load Energize 3 Fuel relay output 12 Louver Control 28 Contiquiable 0 16 d To 4 Crank relay output 13 Pre Lubricate Output Saeta Stop 5 Idle control 14 Ahead Fuel Output output 6 Energized To Stop output 15 Air Flap Output m Configurable AS 1 Commo Ae output 16 Excitation Output output3 n Output g 7 Terminal Terminal 1 B Terminal 2 B Terminal 3 Em stop input emergent stop input connect to B is active Terminal 4 Fuel Output Fuel Output B 5A Terminal 5 Start Output Start Output B 5A Terminal 6 Remote Start Input Remote Start Input connect to B is active Terminal 7 D Connect to the terminal WL or D of charger Terminal 8 LOP Input Terminal 9 HWT Input Terminal 10 Configurable Output3 Configurable output B 5A Terminal 11 Configurable Output2 Configurable output B 5A Terminal 12 Configurable Output1 Configurable output B 5A Terminal 13 N 14 L gt Alternator Input USB Interface Controller directly through the USB line connected to the computer for parametric programming o eo connect to the cathode of battery te e connect to the anode of battery te e te ee te e te e te ee te e Low oil pressure input connect to B is active S e High temperature input connect to B is active 2e e S e te
10. t off when after crank successful Common Alarm Common Alarm led Common alarm indication Lighten off when there is no alarm Slow flashing when there is warning alarm Fast flashing when there is shutdown alarm Alarm include emergency stop high temperature low oil pressure over speed under speed charge failure battery over voltage battery under voltage crank failure stop failure no gen 4 3 Operation Module has three states stop state man state auto stato LXC701 Product User Manual Dongguan Tuancheng Automation Equipment Co LTD T 86 769 23836636 E F 86 769 23 166296 7 www lixise com Page 4 of 8 ULIXISE SMART GENSET LXC701 Series Genset Controller Dongguan Tuancheng Automation Equipment Co LTD 4 3 1 Man str When push Man start button O preheat will first output and start preheat delay when preheat delay is end fuel output 1 second preheat output will stop and crank output is start Here engine will start when crank successfully crank output stop Then engine comes into the safe time When the safe time is end then engine comes into the idle time When the safe time is end then idle output is out and engine will run at full tilt 4 3 2 Auto State When nush button the module will enter automatic state Here if remote start input is active connect to B the engine will start after the delay of start engine Preheat will first output
11. ver speed under speed high temperature low oil pressure emergency stop no generator crank failure stop failure alarm battery over voltage battery under voltage common alarm LED illuminate and common alarm output 6 Parameters table only adjust via pc Set the content as follows NO Parameter Range Default Remark 1 Start delay 0 3600s 1s It S the delay from remote start signal is active or mains is failure to start generator It s the delay from remote start signal is inactive or mains A Atop delay a ae is normal to stop generator 3 pling or 1 9 3 Numbers of crank cycles This timer dictates the duration that the pre heat output will be active before an attempt is made to start the q Preheat time aus s engine Once this timer has expired cranking will commence This is the maximum amount of time that the module will 5 Cranking time 1 60 S 5s energize the starter motor for during starting attempts once the starter has engaged Grank feat This is the amount of time the module will wait for 6 me 3 60 S 10s between start attempts This is to allow the starter motor to cool and the starter batteries to recover This timer dictates how long the module will ignore the 7 Safe running 1 60 S 40s Low oil pressure High Engine Temperature Under time speed Under volts and any other inputs configured as active from safety on 8 Start idle time 0 3600 S Os
12. y the duration of 1 5 seconds above the module will alarm and stop engine Under speed check when engine run at full tilt the duration of 15 seconds above the module will alarm and stop engine Charge Failure check when engine run at full tilt the duration of 3 seconds above and the module will warn but don t stop engine Over Crank when engine crank fail over the times of configure the module will alarm and stop engine lt Stop Failure when engine is stop fail the module will warn lt No generator check after the idle delay when generator frequency for zero and the duration of 5 seconds above the module will alarm and stop engine lt Battery over voltage The DC supply has risen above the high volts setting level for the duration of the high battery volts 20 seconds LXC701 Product User Manual Dongguan Tuancheng Automation Equipment Co LTD T 86 769 23836636 E F 86 769 23 166296 7 www lixise com Page 5 of 8 UIXISE SMART GENSET LXC701 Series Genset Controller Dongguan Tuancheng Automation Equipment Co LTD lt Battery under voltage The DC supply has low above the under volts setting level for the duration of the low battery volts 20 seconds Emergency Stop When emergency stop input ETS solenoid stop immediately output and then fuel disconnect preheat and start signal emit emergency stop alarm signal Common Alarm when any alarm or warn is appear this alarm will active When the o