Powerware® 9125 User`s Guide

image

Contents

1. 40 95 Powerware 9125 User s Guide www powerware com 13 Safety Warnings
2. 1 5 MM AKK O Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD IM PORTANTES Este SIE contiene VOLTAJ ES M ORTALES Todas las reparaciones y el servicio t cnico deben ser efectuados SOLAM ENTE POR PERSONAL DE SERVICIO TECNICO AUTORIZADO No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE ADVERTENCIA e Este SIE contiene su propia fuente de en
3. X Slot 5 15 Receptacles Battery Connector Network Transient Protector Power Cord e REPO Port with 5 20P m Figure 13 2000 VA 120V Rear Panel with 5 20R Communication Port IEC 320 Input Connector X Slot IEC 320 Receptacles Battery Connector REPO Port Network Transient Protector Figure 14 700 2000 VA 230V Rear Panel Powerware 9125 User s Guide www powerware com 25 Installation 26 Powerware 9125 User s Guide www powerware com 4 OPERATION This section describes Operating modes Operating Modes Turning the UPS on and off Starting the UPS on battery Initiating the self test Powerware 9125 s front panel indicates the UPS status through the UPS indicators Figure 15 shows the UPS front panel indicators and controls a Normal M ode Indicator e Battery M ode Indicator Bypass M ode Indicator Test Alarm Reset Button e TO GST 1 te Alarm Indicators see page 55 Bar Graph Indicators Indicator Legend o Unlit e Lit Off Button On Button Figure 15 UPS Front Panel Powerware 9125 User s Guide www powerware com e Flashing ZIN 27 Operation 28 Normal M ode During Normal mode the indicator illuminates and the front p
4. LEDs and Options BarGraph Indicators Option LED Status Explanation 120 230V On default Nominal input voltage on low voltage models is 120V and on 0000 Nominal Input high voltage models is 230V all other nominal input voltages AN Voltage are disabled OS Flashing 120 230V is disabled one of the other input voltage options is selected 110 220V On Selecting this option changes the nominal input voltage on low 000 p Input voltage models to 110V and to 220V for high voltage models Flashing 110 220V is disabled one of the other input voltage options is default selected 127 240V On Selecting this option changes the nominal input voltage on low ES ds ae Input voltage models to 127V and to 240V for high voltage models 9 Flashing 127 240V is disabled one of the other input voltage options is default selected Site Wiring On default Alarm sounds when the polarity of the outlet is reversed or the NU Fault Alarm ground connection 5 missing have qualified electrician i AR s repair the outlet wiring Flashing Alarm DOES NOT sound when the polarity of the outlet is reversed or the ground connection is missing Site Wiring Fault is not available for 230V models Flashing is the default v AC Input Failure On default Alarm sounds when there is an AC input failure INA eoooo ZIN Flashing Alarm DOES NOT sound w hen there is an AC input fai
5. DISCONNECT the batteries while the UPS is in Battery mode Powerware 9125 User s Guide www powerware com UPS Maintenance How to Replace Extended Battery M odules Usethe following procedure to replace EBM s 1 Unplug the EBM cable from the UPS and remove the EBM brackets 2 Replace the EBM See Recycling the Used Battery on page 50 for proper disposal 3 Reinstall the EBM brackets Plug the new EBM into the UPS as shown in Figure 27 5 For additional EBMs plug the EBM cable of the second cabinet into the battery connector on the first EBM UPS Battery A 11 Connector ms SNEJE EBM Bracket nau W EBM Cable EBM Battery EBM Bracket Connector Figure 27 EBM Connections 120V Model Show n NOTE The battery connectors are designed to ensure proper connection with the correct EBM model use EBM model PW 9125 24 EBM with 700 1000 VA UPSs and EBM model PW 9125 48 EBM with 1250 2000 VA UPSs Powerware 9125 User s Guide www powerware com 47 UPS Maintenance How to Replace Internal Batteries CAUTION Pull the battery out onto a flat stable surface The battery is unsupported when you pull it out of the UPS Usethe following procedure to replace internal batteries 1 Using a flat head screwdriver open the right side of the front panel and pull the front panel forward to access the batt
6. Powerware 9125 User s Guide 700 VA 2000 VA W W w erw are com Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonic standards and EU directives e Harmonic Standards EN 50091 1 1 and EN 50091 2 EU Directives 73 23 EEC Council Directive on equipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC 89 336 EEC Council Directive relating to electromagnetic compatibility 92 31 EEC Amending Directive 89 336 EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark For copies of the EC Declaration of Conformity contact Powerware Corporation Koskelontie 13 FIN 02920 Espoo Finland Phone 4358 9 452 661 Fax 358 9 452 665 68 Class B EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception
7. 2 Attach the mounting handles to the bracket with the screws provided in the accessory kit see Figure 2 3 Align the mounting brackets with the screw holes on the side of the UPS and secure with the supplied screws see Figure 2 4 Ifinstalling optional Extended Battery Modules repeat Steps 1 through 3 for each cabinet M ounting Bracket M ounting Handle Figure 2 Installing the Mounting Brackets 18 Powerware 9125 User s Guide www powerware com Installation NOTE The EBM s must be installed below the UPS as shown in Figure 3 5 Slidethe UPS and any optional EBMs into the rack Continueto Installing the UPS on page 21 to complete the installation UPS eso TRIN N Optional BERTI Il EBMs e 2 u Figure 3 Rack M ount UPS with EBM s Cabinet Setup You can position the UPS cabinets horizontally or vertically When positioning the cabinets horizontally the EBMs must be placed below the UPS seeFigure 4 UPS em ERN Op
8. De kan explodera Powerware 9125 User s Guide www powerware com 3 INSTALLATION This section explains Equipment inspection UPSsetup and installation UPSrear panels Inspecting the Equipment If any equipment has been damaged during shipment keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To filea claim for shipping damage or concealed damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service representative UPS Setup The Powerware 9125 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet If you are installing the UPS in a rack continue to the following section Rack M ount Setup otherwise continue to Cabinet Setup on page 19 Powerware 9125 User s Guide www powerware com 17 Installation Rack M ount Setup The UPS can be installed in 19 or 23 inch racks and needs only 2U of valuable rack space NOTE M ounting rails are required for each cabinet If rails are not already installed in your rack contact your local distributor to order a rail kit Usethe following procedure to install the UPS in a rack 1 Placethe UPS on a flat stable surface with the front of the UPS facing toward you
9. Bpoyveveiduato AAUBOVETE TIG KOTG ANAEG Anorteita ODOTTI SLAHEEN tov ovocopeut v ELTE KAVOVLOLLOVS TOU TIG UTOLTNGELG 6 6 TOUS Tlot unv TET TE TOLG OVOCWPEVT G otn HOTL YLATL UTOPEL vo expayodv batterie Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuit non collegato con una fonte di alimentazione corrente alternata Non rimuovere n scollegare il cavo di ingresso quando il gruppo statico di continuit acceso poich in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuit e dell apparecchiatura ad esso collegata Powerware 9125 User s Guide www powerware com Safety Warnings e Per ridurre il rischio di incendio o di scossa elettrica installare il gruppo statico di continuit in un ambiente interno a temperatura ed umidit controllata privo di agenti contaminanti conduttivi La temperatura ambiente non deve superare i 40 C Non utilizzare l unit in prossimit di acqua o in presenza di umidit eccessiva 95 max conformit con gli standard internazionali e con le norme in merito al cablaggio tutta l apparecchiatura collegata con l uscita del gruppo statico di continuit non deve avere una corrente di dispersione di terra superiore a 1 5 milliampere ATTENZIONE Le batterie possono presentare rischio di scos
10. Output Receptacles UPS Battery Connector EBM Cable EBM Battery Connectors Figure 9 Typical UPS Installation 120V Model Shown 22 Powerware 9125 User s Guide www powerware com Installation 7 If you are installing power management software connect your computer to the UPS communication port using the supplied communication cable 8 Plugthe equipment to be protected into the appropriate UPS output receptacles see page 43 for more information on load segments DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements 9 On 230 models plug the detachable UPS power cord into the input connector on the UPS rear panel 10 Plug the UPS power cord into a power outlet All front panel indicators flash briefly and the UPS conducts a self test When the self test is complete the indicator flashes indicating the UPS is in Standby mode with the equipment offline If the or amp indicator flashes see page 57 1 OT Battery Service O G O O Site Wiring Fault Indicator Indicator Figure 10 Fault Indicators 11
11. T m UPS sis lt HEN GEN VAARALLISIA J NNITTEIT Kaikki korjaukset ja huollot on j tett v VAIN VALTUUTETUN HUOLTOHENKILON TOIM EKSI UPS ei sis ll MITAAN K YTT J N HUOLLETTAVIA OSIA VAROITUS e Tama UPS sis lt oman energial hteen akuston Ulostuloliittimiss voi olla j nnite kun UPS ei ole liitettyn verkkoj nnitteeseen e l poista tai irrota sis ntulojohtoa kun UPS on kytkettyn T m poistaa turvamaadoituksen UPS laitteesta ja siihen liitetyst laitteistosta e V hent ksesi tulipalon ja s hk iskun vaaraa asenna t m UPS sis tiloihin joissa l mp tila ja kosteus on s dett viss ja joissa ei ole virtaa johtavia ep puhtauksia Ymp rist n l mp tila ei saa ylitt 40 C Al k yt l hell vett ja v lt kosteita tiloja 95 maksimi e Kansainv liset normit johdotusm r ykset vaativat ett kaikkien t m n UPS laitteen ulostulokytkent jen yhteinen maavuotovirta ei ylit 1 5 milliampeeria mA 6 Powerware 9125 User s Guide www powerware com Safety Warnings VARO e Akusto saattaa aiheuttaa s hk iskun tai sytty tuleen jos akusto kytket n oikosulkuun Noudata asianmukaisia ohjeita e Akusto t ytyy h vitt s d sten mukaisella tavalla Noudata paikallisia m r yksi e l koskaan heit akkuja tuleen Ne voivat r j ht Consignes de s curit CONSIGNES DE S CURIT IMPORTANTES CONSERVER CES INSTRUCTI
12. amp onAvou nov ELVOL OLV ESELLE VOG UPS Tia va UELMGETE tov KLV VVO TUPKAYL G N EKTPOTANELAC EYKATAOTIOTE TO GVYKEKPLU VO UPS EOWTEPLKO ENEYNOUEVN OEPUOKPAOLA KOL vypaota o OTOLOS vo UTV TEPL XEL ayoy na H Sepuoxpacia SEV TPETEL va amp enepv er 40 C Mn to UPS vep 1 VITEPBOALKI vypoota u yrorm vum 95 O Powerware 9125 User s Guide www powerware com Safety Warnings Avvisi di sicurezza IM PORTANTI ISTRUZIONI DI SICUREZZA CONSERVARE QUESTE ISTRUZIONI QUESTO MANUALE CONTIENE IM PORTANTI ISTRUZIONI DI SICUREZZA PERICOLO la TENSIONE contenuta in questo gruppo statico di continuit LETALE Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAM ENTE DA PERSONALE TECNICO AUTORIZZATO All interno del gruppo statico di continuit NON vi sono PARTI RIPARABILI DALL UTENTE AVVERTENZA Questo gruppo statico di continuit contiene una fonte di energia autonoma le 10 Tia va ouuooveit ta SLEOVI KOL TOUS KOAWSLWONG TO vappori yn OAGKANPOD tov ESOTALOLOD NOV ELVOL OVV LSELEVOG LE tnv 6060 tov GVYKEKPLUEVOL UPS dev TPETEL VO eivat WEyaADtEpo 1 5 mA NPOZOXH e Ot GVLGGMPEVT G UNOPEL VA TPOKOAE EGOLV N EKTPOTANELO 1 yKOVHA ond VYT peua
13. energiebron batterijen De uitgangsaansluitingen kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten e Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw met temperatuur en vochtigheidregeling te worden geinstalleerd waar geen geleidende verontreinigingen aanwezig zijn De omgevingstemperatuur mag 40 C niet overschrijden Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid max 95 aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele apparatuur die op de uitgang van deze UPS is aangesloten geen aardlekstroom van meer dan 1 5 milliampere hebben Powerware 9125 User s Guide www powerware com Safety Warnings OPGELET Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als gevolg van un hoge kortsluitstroom Volg de desbetreffende aanwijzingen op De batterijen moeten op de juiste wijze worden opgeruimd Raadpleeg hiervoor uw plaatselijke voorschriften Nooit batterijen in het vuur gooien De batterijen kunnen ontploffen Tarkeita Turvaohjeita T RKEIT TURVAOHJ EITA SUOMI S ILYT N M OHJEET _ TAMA OPAS SIS LT T RKEIT TURVAOHJ EITA VAARA
14. on the rear panel of the UPS Pinl Pin2 Figure 23 REPO Connector 5 Verify that the externally connected REPO switch is off to enable power to the UPS output receptacles 6 Plugin the UPS and start the UPS by pressing the On button 7 Turn on the external REPO switch to test the REPO function 8 Turn off the external REPO switch and restart the UPS Powerware 9125 User s Guide www powerware com 41 Additional UPS Features Netw ork Transient Protector TheNetwork Transient Protector shown in Figure 24 is located on the rear panel and has jacks labeled IN and OUT This feature accommodates a single RJ 45 10BaseT network connector Low voltage models can also accommodate an RJ 11 telephone connector that provides protection for modems fax machines or other telecommunications equipment As with most modem equipment it is not advisable to use this jack in digital PBX Private Branch Exchange environments Connect the input connector of the equipment you are protecting to the jack labeled IN Connect the output connector to the jack labeled OUT IN OUT NETWORK TRANSIENT PROTECTOR Figure 24 Network Transient Protector 42 Powerware 9125 User s Guide www powerware com Additional UPS Features Load Segments Load segments are sets of receptacles that can be controlled by power management software providing an orderly shutdown and startup of your equipment For example during a power outage you
15. the UPS oniBattery i e eneen C COM EUER Mat eui DA ne 30 Turningthe UP OTT we pues Foot Atte oed Ada kuta Lo et RA te 31 initiating th Self Test mat n ne EE ee ee 31 Configuration acd CX AAA AREAS Configuration Mode caer vet Mar A deg esee se or SER 33 Additional UPS Features iia ne EX Yr a 37 X Slot Modules irc ae Se n enge eee bd eod e tol nen 37 Single Port M odule furent e ee rp NOR Semb RHET Mitts ein 38 USB Module icc ats t er ra Mec REIR 40 Remote Emergenty Pow c c e c e CAR cen 40 Network Transient Protector er Ce iis hak pa Bene der re E DOR 42 Load S egments eese SSE ee e Sh fate luna ia 43 Powerware 9125 User s Guide www powerware com Table of Contents 7 UPS Maintenance Landene da UPS ahd Battery Care s ue mes Sed os 45 Storing the UPS and Batteries 45 When to Replace Batteries sir eR Een Oe AEE RE S ER K 45 Replacing B tterles ee t Gases m n KaU ATS ee D a AS 46 How to Replace Extended Battery Modules 47 How to Replace Internal 48 Testing New Batteries gt secs eere He ERU PUDE nee fag EIE ee eee ras 49 Recycling the Used Battery ett era poe tp a wet 50 8 S PeCIHCADONS ae 9 Troubleshooting 44 44 vussa yas i
16. which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and the receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help ICES 003 This Class B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES 003 Cet appareil num rique de la classe B respecte toutes les exigences du Reglement sur le mat riel brouilleur du Canada Powerware is a registered trademark and Advanced Battery M anagement Plus ABM Plus Fourth Generation Online X Slot and ConnectUPS are trademarks of Powerware Corporation Copyright 1999 2000 Powerware Corporation Raleigh NC USA All rights reserved No part of this document may be reproduced in any way without the express written approval of Powerware Corporation VCCI Notice for Class B Equipment IDEEN FRAARESRRESAERMBRBA OB I 3472ABfSSIWIBEBECT CORBA FERE CEN E LCWETA TOREO DA VEV a VERGIL T ZREHEZBIARITIERDU ET BURMA EIT HES TIE LU LT EL Special Symbols The following are examples of symbols used on the UPS to alert you to important information RISK OF ELECTRIC SHOCK Indicates that
17. DENNA BRUKSANVISNING INNEHALLER VIKTIGA SAKERHETSFORESKRIFTER A Denna UPS enhet inneh ller LIVSFARLIG SPANNING ENDAST AUKTORISERAD SERVICEPERSONAL far utf ra reparationer eller service Det finns inga delar som ANVANDAREN KAN UTFORA SERVICE PA inuti UPS enheten VARNING e Denna UPS enhet har en egen energikalla batterier De utgaende kontakterna kan vara stromforande n r UPS enheten inte r ansluten till en v xelstr mk lla Ta aldrig bort n tsladden UPS enheten r p slagen Detta tar bort skyddsjordningen fran bade UPS enheten och den anslutna utrustningen Powerware 9125 User s Guide www powerware com 15 Safety Warnings 16 e Minska risken f r brand eller elektriska st tar genom att installera denna UPS enhet inomhus dar temperatur och luftfuktighet ar kontrollerade och d ringa ledande f roreningar f rekommer Omgivande temperatur far ej verstiga 40 C Anv nd inte utrustningen vatten eller vid h g luftfuktighet max 95 96 F ratt verensst mma med internationell standard och installationsf reskrifter far inte den totala utrustning som anslutits till uttagen pa denna UPS enhet ha l cksstr m som verstiger 1 5 milliampere VIKTIGT e Batterierna kan ge elektriska st tar eller br nnskador fr n h g kortslutningsstr m F lj till mpliga anvisningar e Batterierna m ste avyttras enligt anvisningarna i lokal lagstiftning e Anv nda batterier f r aldrig br nnas upp
18. Do not operate near water or excessive humidity 95 max Tocomply with international standards and wiring regulations the total equipment connected to the output of this UPS must not have an earth leakage current greater than 1 5 milliamperes Powerware 9125 User s Guide www powerware com Safety Warnings CAUTION Batteries can present a risk of electrical shock or burn from high short circuit current Observe proper precautions Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries Proper disposal of batteries is required Refer to your local codes for disposal requirements Never dispose of batteries in a fire Batteries may explode when exposed to flame Sikkerhedsanvisninger VIGTIGE SIKKERHEDSANVISNINGER GEM DISSE ANVISNINGER DENNE BRUGERVEJ LEDNING INDEHOLDER VIGTIGE SIKKERHEDSANVISNINGER Denne UPS indeholder LIVSFARLIG H J SP NDING Alle reparationer og vedligeholdelse b r kun udf res af en AUTORISERET SERVICETEKNIKER Ingen af UPS ens indvendige dele kan repareres af brugeren ADVARSEL Denne UPS indeholder egen energiforsyning batterier Udgangsnetstikkene kan lede str m selv n r UPS en ikke er tilsat en AC energikilde Netledningen m ikke fjernes og stikket m ikke tr kkes ud mens UPS en er t ndt Dette fjerner sikkerhedsjorden fra UPS en og fra de
19. M odels Load UPS Internal 1EBM 2EBMs 3EBMs 4EBMs Batteries 200 VA 140W 37 271 546 400 VA 280W 19 142 278 700 VA 490W 9 72 156 850 VA 595W gt 6 59 124 1000 VA 700W 5 48 104 Run times do not apply for 700 VA models 1250 2000 VA M odels Load UPS Internal 1EBM 2EBMs 3EBMs 4EBMs Batteries 400 VA 280W 46 177 331 501 682 700 VA 490W 25 96 180 272 370 850 VA 595W 21 76 142 214 292 1000 VA 700W 16 61 115 174 237 1250 VA 875W 1 46 87 131 179 1500 VA 1050W 8 37 10 106 144 1800 VA 1260W 6 30 57 85 116 2000 VA 1400W 5 26 49 74 100 Run times do not apply for 1250 VA models Run times do not apply for 1250 VA and 1500 VA models NOTE Battery times are approximate and vary depending on the load configuration and battery charge 54 Powerware 9125 User s Guide www powerware com 9 TROUBLESHOOTING This section explains e UPS alarms and conditions How to silence an alarm Service and support Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems Use Table 10 to determine and resolve the UPS alarms and conditions NOTE Some alarms such as the Overtemperature and Overload alarms have to be Cleared by shutting down and restarting the UPS see page 57 for more information Site Wiring Fault Battery Service m Overtemperature
20. ONS CE MANUEL CONTIENT DES CONSIGNES DE S CURIT IMPORTANTES A Cet onduleur contient des TENSIONS M ORTELLES Toute op ration d entretien et de r paration doit tre EXCLUSIVEM ENT CONFIEE A UN PERSONNEL QUALIFIE AGREE AUCUNE PIECE REPARABLE PAR L UTILISATEUR ne se trouve dans l onduleur AVERTISSEMENT e Cet onduleur renferme sa propre source d nergie batteries Les prises de sortie peuvent tre sous tension m me lorsque l onduleur n est pas branch sur le secteur e Ne pas retirer le cordon d alimentation lorsque l onduleur est sous tension sous peine de supprimer la mise la terre de l onduleur et du mat riel connect e Pour r duire les risques d incendie et de d charge lectrique installer l onduleur uniquement l int rieur dans un lieu d pourvu de mat riaux conducteurs ou la temp rature et l humidit ambiantes sont contr l es La temp rature ambiante ne doit pas d passer 40 C Ne pas utiliser proximit d eau ou dans une atmosph re xcessivement humide 95 maximum e Afin d tre conforme aux normes et r glements internationaux de c blage le courant de fuite la terre de la totalit du mat riel branch sur la sortie de l onduleur ne doit pas d passer 1 5 mA D Powerware 9125 User s Guide www powerware com Safety Warnings ATTENTION Les batteries peuvent pr senter un risque de d charge lectrique ou de br lure par des courts circuits de haute in
21. Self Test Overload N e ji al CR Er a EE o a Indicator Legend o Unlit Test Alarm 1 o Lit Reset Button o Flashing ZIN Figure 28 Alarm Indicators Silencing an Audible Alarm To silence the alarm for an existing fault press the 4 button If UPS status changes the alarm beeps overriding the previous alarm silencing Powerware 9125 User s Guide www powerware com 55 Troubleshooting Table 10 Troubleshooting Guide Alarm or Condition Possible Cause Action The indicator is not on the UPS does not start The power cord is not correctly connected Check the power cord connections The wall outlet is faulty Have a qualified electrician test and repair the outlet The indicator is flashing power is not available at the UPS output receptacles The UPS is in Standby mode Press the button to supply power to the connected equipment Output circuit breaker trips Load fault Check the load Disconnect faulty load equipment W ait 2000 VA only several minutes before resetting the UPS circuit breaker The UPS does not provide The batteries need charging or Plug the UPS into a power outlet for 24 hours to charge the the expected backup time service battery After charging the battery press and hold the button for 3 seconds then check the indicator If the indicator is still on see UPS M aintenance on page 45 to replace
22. Start the UPS by pressing the On button see Figure 15 on page 27 The indicator stops flashing and the bar graph indicators display the percentage of load being applied to the UPS The UPS is now in Normal mode and supplying power to your equipment To learn how to operate the UPS see Operation on page 27 To change the factory set defaults see Configuration on page 33 NOTE The batteries charge to 80 capacity in approximately 2 hours How ever it is recommended that the batteries charge for 24 hours after installation or long term storage Powerware 9125 User s Guide www powerware com 23 Installation UPS Rear Panels This section shows the rear panels of the Powerware 9125 models Communication Port X Slot 5 15 Receptacles Battery Connector Network Transient Protector Power Cord e REPO Port with 5 15P 5 Figure 11 700 1500 VA 120V Rear Panel Communication Port Circuit Breakers X Slot 5 15 Receptacles Battery Connector Netw ork Transient Protector Power Cord e REPO Port with 5 20P E gt Figure 12 2000 VA 120V Rear Panel 24 Powerware 9125 User s Guide www powerware com Installation Circuit Breakers Communication Port 5 20 Receptacles
23. Storing the UPS and Batteries If you store the UPS for a long period recharge the battery every 12 months by plugging the UPS into a power outlet The batteries charge to 80 capacity in approximately 2 hours However it is recommended that the batteries charge for 24 hours after long term storage When to Replace Batteries When the indicator illuminates the batteries may need replacing Conduct a self test by pressing and holding the 4 button for three seconds If the 2 indicator stays on contact your service representative to order new batteries Powerware 9125 User s Guide www powerware com 45 UPS Maintenance Replacing Batteries 46 With the hot swappable battery feature UPS batteries can be replaced easily without turning the UPS off or disconnecting the load If you prefer to remove input power to change the battery press and hold the Off 1 button for approximately three seconds then unplug the UPS Consider all warnings cautions and notes before replacing batteries A WARNING A Batteries can present a risk of electrical shock or burn from high short circuit current The following precautions should be observed 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries e ELECTRIC ENERGY HAZARD Do not attempt to alter any battery wiring or connectors Attempting to alter wiring can cause injury NOTE DO
24. a risk of electric shock is present and the associated warning should be observed CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as important operating and maintenance instructions This symbol indicates that you should not discard the UPS or the UPS batteries in the trash The UPS may contain sealed lead acid batteries Batteries must be recycled lt PP TABLE OF CONTENTS Powerware 9125 The Ultimate Online UPS 1 Safety Wan NGS enden racemase iat rate etn PR CRUCE Re EUER 3 Installatl h ta binn bor ha K k RC ea inspecting the EQUIPMENT Armee n pos comer s Om t opt eae ane TX 17 UPS Setup aa N t tp DN RR Cede est 17 Race M ount Setup are oc oed euge aed 18 Cabinet S GtUp sr pa da dr EE KYT 19 installing o pe er TS Ni OA 21 UPS Rear Panel Seran utat s aec docte d ah pe o s ed det ya oo 24 Operat on d is dus CES Er oia 27 Operating MONES sic anserina dn Bande di AE ei 2 Normal Mode thats ue roe vn Te e a S eee dn 28 Battery Mode ici ee CH ge ost et 29 Bypass Mode esos Sure Mat det BONG O Deb Ta HORDE POT 30 Standby Moden ccce erac as us ette S Ve e NR Qo EAS AR 30 Sleep Mode 4 i io Alda dte ce d c t c tote Ot 30 Turning the UPS ON eoo rete E n Come geo der Stade 30 Starting
25. al The UPS is receiving utility power that may be unstable or in brow nout conditions The UPS continues to supply power to your equipment If conditions worsen the UPS may switch to battery power The battery may be fully Battery Service discharged Sec GN Plug the UPS into a pow er outlet for 24 hours to charge the battery After charging the battery press and hold the 4 button for 3 seconds then check the 62 indicator If the indicator is still on see UPS M aintenance on page 45 to replace the battery The battery is not connected correctly Check the battery connections Call your service representative if the problem persists 120V models only AN neutral wires are reversed in the wall outlet Have a qualified electrician correct the wiring To disable this alarm see Configuration M ode on page 33 SE UPS internal temperature is Turn off and unplug the UPS Clear vents and remove any v Overtemperature too high The UPS switches to heat sources Ensure the airflow around the UPS is not AN Bypass allowing the UPS to restricted W ait at least 5 minutes and restart the UPS If cool the condition persists contact your service representative Power requirements exceed Turn off and unplug the UPS Remove some of the 9 v UPS capacity 101 11096 for equipment from the UPS Wait at least 5 seconds until all 2 minutes or 111 150 for LEDs are off and
26. anel displays the percentage of UPS load capacity being used by the protected equipment see Figure 16 The UPS monitors and charges the batteries as needed and provides power protection to your equipment o O O O O O 4 O O O O 10 25 O O O 26 50 O 51 75 76 100 1 4 gt 00 ZIN ss Figure 16 Load Level Indicators The LEDs do not illuminate when the UPS load is less than approximately 10 Each LED represents 1 4 of a full load rating When all of the bar graph indicators are illuminated and the indicator flashes power requirements exceed UPS capacity see page 57 for more information Powerware 9125 User s Guide www powerware com Operation Battery M ode When the UPS is operating during a power outage the alarm beeps once per second and the indicator illuminates The front panel displays the approximate percentage of battery capacity remaining see Figure 17 When the utility power returns the UPS switches to Normal mode operation while the battery recharges O so 5 5 O O 5 O O My m O 3 Minute Warning 1 4 00000 Shutdown Imminent AN 0 Figure 17 Battery Capacity Indicators If battery capacity becomes low while in Battery mode the indicator flashes and the alarm sounds continuously indicating approximately three minutes of battery time remaining When shut
27. arder og forkablingsbestemmelser FORSIKTIG e Batterier kan for rsake elektriske st t eller forbrenning p grunn av h y kortslutningsstr m F lg instruksene e Batterier m fjernes p korrekt m te Se lokale forskrifter vedr rende krav om fjerning av batterier e Kast aldri batterier i flammer da de kan eksplodere hvis de utsettes for pen ild Regulamentos de Seguranca INSTRUCOES DE SEGURANCA IM PORTANTES GUARDE ESTAS INSTRUCOES ESTE MANUAL CONTEM INSTRUCOES DE SEGURANCA IM PORTANTES CUIDADO A UPS cont m VOLTAGEM M ORTAL Todos os reparos e assist ncia t cnica devem ser executados SOM ENTE POR PESSOAL DA ASSIST NCIA TECNICA AUTORIZADO N o h nenhuma PE A QUE POSSA SER REPARADA PELO USU RIO dentro da UPS ADVERT NCIA A e Esta UPS cont m sua pr pria fonte de energia baterias Os recept culos de sa da podem conter voltagem ativa quando a UPS nao se encontra conectada a uma fonte de alimentac o de corrente alternada e N o remova ou desconecte o cabo de entrada quando a UPS estiver ligada Isto remover o aterramento de seguranca da UPS e do equipamento conectado e Para reduzir o risco de inc ndios ou choques el tricos instale a UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condut veis A temperatura ambiente n o deve exceder 40 C N o opere pr ximo a gua ou em umidade excessiva m x 9596 e Para estar de acordo com os padr es interna
28. ating the Self Test Press and hold the button for three seconds to initiate the self test During the five second test the bar graph indicators cycle through twice If the UPS finds a problem an LED indicates where the problem is For more information see Troubleshooting on page 55 NOTE The batteries must be fully charged and the UPS must not be in Battery mode to perform the self test Powerware 9125 User s Guide www powerware com 31 Operation 32 Powerware 9125 User s Guide www powerware com 5 CONFIGURATION This section describes how to reconfigure options using the Configuration mode including input voltage site wiring fault and AC input alarm Configuration M ode When the UPS isin Configuration mode the bar graph indicators represent the configuration options The control buttons On button and button are used to modify the UPS configuration Figure 18 shows the LEDs and Table 1 explains the corresponding options NOTE The UPS can be configured while in Battery mode If the UPS switches to battery power while in Configuration mode the UPS remains in Configuration mode and indicates Battery mode on the front panel CAUTION DO NOT press the Off 1 button while the UPS is in Configuration mode pressing the Off 1 button removes all power to your equipment immediately and the UPS enters Standby mode 1 Press the On button and the 4 button simultaneousl
29. can keep key pieces of equipment running while you turn off other equipment This feature allows you to save battery power See your power management software manual for details NOTE If the power management software is not used the individual load segments cannot be controlled Each UPS has two load segments as shown in Figure 25 and Figure 26 Figure 25 shows the load segments for all models except the PW 9125 2000 20 model shown in Figure 26 Load Segment 2 Load Segment 1 Figure 25 UPS Load Segments 120V Model Shown Load Segment 1 Load Segment 2 Figure 26 UPS Load Segments for PW 9125 2000 20R Powerware 9125 User s Guide www powerware com 43 Additional UPS Features 44 Powerware 9125 User s Guide www powerware com 7 UPS This section explains how to Carefor the UPS and batteries Replacethe batteries Test new batteries Recycle used batteries UPS and Battery Care For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the system with a vacuum cleaner For full battery life keep the UPS at an ambient temperature of 25 C 77 F
30. cionais e os regulamentos de fia o equipamento total conectado sa da desta UPS n o deve ter uma corrente de fuga terra maior que 1 5 miliamp res 12 Powerware 9125 User s Guide www powerware com Safety Warnings As baterias podem apresentar o risco de chogue el trico ou gueimaduras provenientes de alta corrente de curto circuito Observe as instru es adequadas Siga as instruc es apropriadas ao desfazer se das baterias Consulte os c digos do local para maiores informac es sobre os regulamentos de descarte de produtos Nunca jogue as baterias no fogo porque h risco de explos o
31. down is imminent the V indicator flashes NOTE Depending on the UPS load the 3 minute warning may occur before the batteries reach 2596 capacity the front panel immediately displays the 3 minute warning For UPS and Extended Battery M odule run times see Table 9 on page 54 These warnings are approximate and the actual time to shutdown may vary significantly Once these warnings are indicated immediately complete and save your work to prevent data loss and similar difficulties When utility power is restored after the UPS shuts down the UPS automatically restarts Powerware 9125 User s Guide www powerware com 29 Operation Bypass Mode In the event of a UPS overload or internal failure the UPS transfers your equipment to utility power Battery mode is not available however the utility power continues to be passively filtered by the UPS The alarm sounds and the indicator illuminates The UPS switches to Bypass mode when TheUPS has an overtemperature condition TheUPS has an overload condition of 101 to 11096 for 2 minutes TheUPS has an overload condition of 111 to 15096 for 30 seconds TheUPS detects a fault in the battery or UPS electronics Standby M ode When the UPS is turned off and remains plugged into a power outlet the UPS is in Standby mode The indicator flashes and the bar graph indicators are off indicating that power is not available from the UPS output receptacles The battery recharg
32. eature shuts down the protected equipment immediately and does not follow the orderly shutdown procedure initiated by any power management software Any devices that are operating on battery power are also shut down immediately When the REPO switch is re opened the equipment will not return to battery power until the UPS is manually restarted If the Off 5 button is pressed after the REPO is activated the UPS remains in Standby mode when restarted until the On button is pressed Powerware 9125 User s Guide www powerware com Additional UPS Features A The REPO circuit is an IEC 60950 safety extra low voltage SELV circuit This circuit must be separated from any hazardous voltage circuits by reinforced insulation CAUTION To ensure the UPS stops supplying power to the load during any mode of operation the input power must be disconnected from the UPS when the emergency power off function is activated NOTE The REPO function activates when the REPO contacts close Use the following procedure to install the REPO switch 1 Verify that the UPS is off and unplugged 2 Remove the REPO connector from the accessory kit 3 Connect isolated normally open dry contacts rated at 60 Vdc maximum 30 Vac RMS maximum and 20 mA maximum across the REPO device to Pin 1 and Pin 2 see Figure 23 Use stranded non shielded wiring size 18 22 AWG 0 75 mm2 0 4 Connectthe REPO connector to the port
33. ergia las bater as Los recept culos de salida pueden transmitir corriente el ctrica aun cuando el SIE no est conectado a un suministro de corriente alterna c a e No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido Esto suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE 14 Powerware 9125 User s Guide www powerware com Safety Warnings Para reducir el riesgo de incendio de choque el ctrico instale este SIE en un lugar cubierto con temperatura y humedad controladas libre de contaminantes conductores La temperatura ambiente no debe exceder los 40 C trabaje cerca del agua o con humedad excesiva 9596 m ximo e Para cumplir con los est ndares internacionales y las normas de instalaci n la totalidad de los equipos conectados a la salida de este SIE no debe tener una intensidad de p rdida a tierra superior a los 1 5 miliamperios PRECAUCI N as bater as pueden presentar un riesgo de descargas el ctricas o de quemaduras debido a la alta corriente de cortocircuito Preste atenci n a las instrucciones correspondientes e Es necesario desechar las bater as de un modo adecuado Consulte las normas locales para conocer los requisitos pertinentes e Nunca deseche las bater as en el fuego Las bater as pueden explotar si se las expone a la llama Sakerhetsforeskrifter VIKTIGA SAKERHETSFORESKRIFTER SPARA DESSA FORESKRIFTER
34. ery NOTE 00 attempt to open the left side mm 2 Unscrew and set aside the battery retaining bracket Disconnect the battery cable from the UPS and remove the battery cable from the wire clips Battery Retaining Bracket 48 Powerware 9125 User s Guide www powerware com UPS Maintenance 3 Pull the battery out onto a flat stable surface See Recycling the Used Battery on page 50 for proper disposal BEN VE m AJ lt 4 Slidethenew battery into the UPS Reconnect the battery cable and secure the battery cable in the wire clips 5 Reinstall the battery retaining bracket and screws removed in Step 2 Replace the front panel Testing New Batteries Press and hold the button for three seconds to initiate a self test After the test is finished the indicator should turn off If the indicator stays on check the battery connections Call your service representative if the problem persists Powerware 9125 User s Guide www powerware com 49 50 UPS Maintenance Recycling the Used Battery Contact your local recycling or hazardous waste center for information on proper disposal of the used battery A e Do not dispose of the battery or batteries in a fire Batteries may explode Proper disposal of batteries is required Refer to your local codes for disposal requirements e Do not open or mut
35. es when necessary Sleep Mode If the UPS is on battery for approximately five minutes and supporting a small electrical load 10 the UPS shuts down the load This feature conserves battery power To enable this feature contact your service representative Turning the UPS On 30 After the UPS is connected to a power outlet it conducts a self test and enters Standby mode To turn on the UPS press the On button on the front panel shown in Figure 15 on page 27 The indicator illuminates and the bar graph indicators display the percentage of load being applied to the UPS Starting the UPS on Battery To turn on the UPS without using utility power press and hold the On button for at least four seconds The UPS supplies power to your equipment and goes into Battery mode When the UPS starts on battery it does not conduct a self test to conserve battery power Powerware 9125 User s Guide www powerware com Operation Turning the UPS Off To turn off the UPS 1 Press and hold the Off cl button for approximately three seconds The UPS switches to Standby mode and removes power from the UPS output receptacles 2 Unplug the UPS from the power outlet the UPS shuts down in five seconds All front panel indicators flash briefly prior to shutdown If you do not unplug the UPS it remains in Standby mode Pressing the Off b button while the UPS is in Battery mode causes the UPS to shut down immediately Initi
36. ilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic CAUTION Do not discard the UPS or the UPS batteries in the trash This product contains sealed AN lead acid batteries and must be disposed of properly For more information contact pb your local recycling or hazardous waste center Powerware 9125 User s Guide www powerware com 8 SPECIFICATIONS This section provides the following specifications for the Powerware 9125 models Electrical input and output Weights and dimensions Environmental and safety Battery Table 3 Model List 120V M odels 230V M odels UPS Models PW 9125 700 PW 9125 700i PW 9125 1000 PW 9125 1000i PW 9125 1250 PW 9125 1250i PW 9125 1500 PW 9125 1500i PW 9125 2000 PW 9125 2000i PW 9125 2000 20R NOTE The model numbers shown are for gray units model numbers for black units end with BLK Table 4 Electrical Input 120V M odels 230V M odels Nominal Voltage 120V default 110 120 127V selectable 230V default 220 230 240V selectable Voltage Range 80 144V for 110 120 127V nominal 160 288V for 220 230 240V nominal Nominal Frequency 45 65 Hz 50 60 Hz auto sensing Noise Filtering M OVs and line filter for normal and common mode noise Connections 700 1500 VA 6 ft 5 15P power cord 10A IEC 320 input connector 2000 VA 6 ft 5 20P power cord 100V 200V and 208V nominal i
37. l part of power protection is power management software the Powerware 9125 comes fully equipped with a communication port serial cable and a CD containing both LanSafe 111 for networked systems and FailSafe 111 for standalone systems Powerware 9125 User s Guide www powerware com 1 Powerware 9125 TheUltimate Online UPS Providing outstanding performance and reliability the Powerware 9125 s unique benefits include the following Fourth Generation Online design with pure sine wave output The UPS filters and regulates incoming AC power and provides consistent power to your equipment without draining the battery 2U rack height conserves valuable rack space Advanced Battery Management Plus ABM Plus doubles battery service life optimizes recharge time and provides a warning up to 60 days before the end of useful battery life With the two in one form factor you can usethe UPS in a rack mount configuration or as a standalone cabinet Hours of extended run time with up to four EBM 5 Sequential shutdown and load management through separate receptacle groups called load segments Network Transient Protector guards your network communications equipment from surges Low voltage models can also guard modems fax machines or other telecommunications equipment Hot swappable batteries simplify maintenance by allowing you to replace batteries safely without powering down the critical load Emergency shutdown control
38. le To establish communication between the UPS and a computer connect your computer to the UPS communication port using the supplied communication cable When the communication cable is installed power management software can exchange data with the UPS The software polls the UPS for detailed information on the status of the power environment If a power emergency occurs the software initiates the saving of all data and an orderly shutdown of the equipment The cable pins are identified in Figure 20 and the pin functions are described in Table 2 00000 0000 Figure 20 Communication Port Table 2 Communication Port Pin Assignment Pin Signal Name Function Direction Number from the UPS 1 Low Batt Low Battery relay contact Out 2 RxD Transmit to external device Out 3 TxD Receive from external device In 4 DTR PnP Plug and Play from external device In tied to Pin 6 5 GND Signal common tied to chassis 6 DSR To external device tied to Pin 4 Out 7 RTS PnP from external device default or In Out On Bypass relay contact jumper selectable 8 AC Fail AC Fail relay contact Out 9 Power Source V 8 to 24 volts DC power Out Powerware 9125 User s Guide www powerware com Additional UPS Features The On Bypass Relay Contact You can enable the O n Bypass relay using the jumper on the single port module The jumper default is disabled To enable the O n Bypass relay 1 Remove
39. lure NOTE 100V 200V and 208V nominal input voltages are available Contact the help desk at one of the telephone numbers on page 58 for assistance Powerware 9125 User s Guide www powerware com 35 Configuration 36 Powerware 9125 User s Guide www powerware com 6 ADDITIONAL UPS FEATURES This section describes e X Slot modules Remote Emergency Power Off e Network Transient Protector Load segments X Slot M odules X Slot modules allow the UPS to communicate in a variety of networking environments and with different types of devices The Powerware 9125 is compatible with any X Slot module including Single Port Module has one serial communication port USB Module connects to a USB port on your computer Multi Port Module has six serial communication ports that can communicate with UPSs terminals computers and modems ConnectUPS MX SNMP Module has Ethernet modem and SNMP capabilities The Powerware 9125 is factory installed with a Single Port Module or USB Module depending on the customer order o M ulti Port M odule CR ED He ConnectUPS MX Single Port M odule USB Module o Figure 19 X Slot Modules Powerware 9125 User s Guide www powerware com 37 Additional UPS Features 38 Single Port M odu
40. may occur when connecting an Extended Battery M odule to the UPS This is normal and will not harm personnel Insert the EBM cable into the UPS battery connector quickly and firmly NOTE Do not make unauthorized changes to the UPS otherwise damage may occur to your equipment and void your warranty 1 If installing an optional EBM continue to Step 2 otherwise skip to Step 7 Steps 2 4 are not required for rack mount installations 2 Remove the adjacent corner screws from the rear panels as shown in Figure 8 to install the EBM brackets 3 Align each EBM bracket with the screw holes and secure with the screws removed in Step 2 Powerware 9125 User s Guide www powerware com 21 Installation 4 Ifinstalling additional 5 repeat Steps 2 and 3 for each cabinet EBM Bracket EBM Bracket Figure 8 Installing the EBM Brackets 5 Plugthe EBM cable into the battery connector on the UPS rear panel see Figure 9 6 If additional EBMs are to be installed plug the EBM cable of the second cabinet into the battery connector on the first EBM Repeat for each additional EBM Up to four EBMs may be connected to the UPS Communication Port PowerCord
41. n Ausgang dieser USV angeschlossenen Ger te zusammen einen Erdschlu strom von insgesamt 1 5 M illiampere nicht berschreiten Powerware 9125 User s Guide www powerware com Safety Warnings VORSICHT Batterien k nnen aufgrund des hohen Kurzschlu stroms Elektroschocks oder Verbrennungen verursachen Die entsprechenden Vorsichtsma nahmen sind unbedingt zu beachten Die Batterien m ssen ordnungsgem entsorgt werden Hierbei sind die rtlichen Bestimmungen zu beachten Batterien niemals verbrennen da sie explodieren k nnen AoMaAELas 2HMANTIKE2 OAHTIE2 AZOAAEIAZ AYTE gt TIZ OAHTIEZ TO ET XEIPIAIO 2HMANTIKE2 OAHTIE2 AZOAAEIAZ KINAYNO2 A to UPS nep exe OANATHDOPA Oleg 01 EMOKEV S KOL OL OVVINPNGELS TPETEL va yivovtat MONO EZOYZIOAOTHMENO TIA TH YYNTHPH gt H IIPOXOIIIKO To UPS AEN ITEPIEXEI KANENA E APTHMA TOY NA MIIOPEI NA EIIIEKEY AXTEI ANO TO XPHZTH NPOEIAONOIHZHK A e To ocvyxexpi vo UPS nepiexei tov amy evepyeiag cucompevt OL pevuatoddtes 0600 UNOPEL va Exovv EVEPY ax un zav to UPS dev eivar ovvdeden vo miyn EVOAAAOOOLEVOD peduoros AC e By lete mv Kaldo to UPS eivor AVotyt avt tov TH YELOON TO UPS tov
42. nput voltages are available Contact the help desk at one of the telephone numbers on page 58 for assistance Powerware 9125 User s Guide www powerware com 51 Specifications Table 5 Electrical Output 120V M odels 230V M odels Power Levels rated at PW 9125 700 700 VA 490W PW 9125 700i 700 VA 490W nominal inputs PW 9125 1000 1000 VA 700W PW 9125 10001 1000 VA 700W PW 9125 1250 1250 VA 875W PW 9125 12501 1250 VA 875W PW 9125 1500 1500 VA 1050W PW 9125 15001 1500 VA 1050W PW 9125 2000 2000 VA 1400W PW 9125 20001 2000 VA 1400W PW 9125 2000 20R 2000 VA 1400W Regulation Nominal output voltage 3 Normal mode Regulation Nominal output voltage 3 Battery mode Voltage Waveform Normal mode Sine wave 5 THD with full PFC and nonlinear load Output Receptacles 6 5 15R PW 9125 2000 20R 4 5 15R 2 5 20R 6 IEC 320 Table 6 Weights and Dimensions UPS Extended Battery M odule Dimensions 17 0 x 19 0 x 3 5 20 17 0 x 19 0 x 3 5 20 W xDxH 43 2 x 48 2 x 8 9 43 2 x 48 2 x 8 9 cm Weight 700 1000 VA 34 Ib 15 kg 65 Ib 29 5 kg 1250 2000 VA 50 Ib 23 kg 52 Powerware 9125 User s Guide www powerware com Specifications Table 7 Environmental and Safety 120V M odels 230V M odels Operating Temperature 0 C to 40 C 32 F to 104 F Optimal battery performance 25 C 77 F Storage Temperature 0 C to 25 C 32 F
43. o ce ci O Audible Alarms and UPS Conditions 55 Silencing an Audible 55 Service and Support pr a pa er el LE ere 58 ii Powerware 9125 User s Guide www powerware com 1 POWERWARE 9125 THE ULTIMATE ONLINE UPS The Powerware 9125 uninterruptible power system UPS protects your sensitive electronic equipment from the most common power problems including power failures power sags power surges brownouts line noise high voltage spikes frequency variations switching transients and harmonic distortion Power outages can occur when you least expect it and power quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With the Powerware 9125 you can safely eliminate the effects of power disturbances and guard the integrity of your equipment Figure 1 shows the Powerware 9125 UPS with an optional Extended Battery Module EBM voor NN 5920000 800 Tann NE UU U f NN UU UU UL Figure 1 The Powerware 9125 Because an integra
44. restart the UPS You may need to obtain a Overload 30 seconds or the load is larger capacity UPS fective Continuous audible alarm EIER Powerware 9125 User s Guide www powerware com 57 Troubleshooting Service and Support 9 58 If you have any questions or problems with the UPS call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative In the United States 1 800 365 4892 In Canada 1 800 461 9166 All other countries 1 919 870 3149 Please have the following information ready when you call the Help Desk Model number Serial number Version number if available Date of failure or problem Symptoms of failure or problem Customer return address and contact information If repair is required you will be given a Returned Material Authorization RMA Number This number must appear on the outside of the package and on the Bill Of Lading if applicable Use the original packaging or request packaging from the Help Desk or distributor Units damaged in shipment as a result of improper packaging are not covered under warranty A replacement or repair unit will be shipped freight prepaid for all warrantied units NOTE For critical applications immediate replacement may be available Call the Help Desk for the dealer or distributor nearest you Powerware 9125 User s Guide www powerware com
45. sa elettrica o di ustioni provocate da alta corrente dovuta a corto circuito Osservare le apposite istruzioni Le batterie devono essere smaltite in modo corretto Per i requisiti di smaltimento fare riferimento alle disposizioni locali e Non gettare mai le batterie nel fuoco poich potrebbero esplodere se esposte alle fiamme Viktig Sikkerhetsinformasion Denne UPS en inneholder LIVSFARLIGE SPENNINGER All reparasjon og service ma kun utfgres av AUTORISERT SERVICEPERSONALE BRUKERE KAN IKKE UTFORE SERVICE NOEN AV DELENE i UPS en e Denne UPS en har en egen energikilde batterier Stikkontaktene kan v re str mf rende selv om UPS en ikke er tilsluttet en vekselstr mforsyning e Strgmforsyningskabelen m ikke fjernes eller trekkes ut n r UPS en er slik at ikke sikkerhetsjordingen fjernes fra UPS en og det utstyret som er forbundet med den e For redusere fare for brann eller elektriske st t bor denne UPS en installeres i et innendgrs milj med kontrollert temperatur og luftfuktighet som er fritt for ledende forurensende stoffer Romtemperaturen ma ikke overskride 40 C Den ikke brukes i n rheten av vann eller ved meget h y luftfuktighet 95 maks Powerware 9125 User s Guide www powerware com 11 Safety Warnings e Altutstyrsom er forbundet med utgangen av denne UPS en ma ikke ha en sterkere total lekkasjestr m enn 1 5 milliampere for v re i overensstemmelse med internasjonale stand
46. t udstyr der er sat til Installer denne UPS i et temperatur og fugtighedskontrolleret indendgrsmiljg frit for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stad Rumtemperaturen ikke overstige 40 C UPS en bar ikke betjenes n r vand eller h j fugtighed maksimalt 95 overensstemmelse med internationale normer og bestemmelser for el installation m det udstyr der er forbundet til udgangen af denne UPS tilsammen ikke overskride en jordafdelingssp nding p mere end 1 5 milliampere Powerware 9125 User s Guide www powerware com Safety Warnings ADVARSEL e Batterier kan udg re en fare for elektrisk st d eller forbr ndinger for rsaget af h j kortslutningsspaending De korrekte forholdsregler bar overholdes e Korrekt bortskaffelse af batterier er p kr vet Overhold g ldende lokale regler for bortskaffelsesprocedurer e Skaf dig aldrig af med batterierne ved at br nde dem Batterierne kan eksplodere ved ben ild Belangrijke Veiligheidsinstructies BELANGRIJ KE VEILIGHEIDSINSTRUCTIES BEWAAR DEZE INSTRUCTIES DEZE HANDLEIDING BEVAT BELANGRIJ KE VEILIGHEIDSINSTRUCTIES GEVAAR A Deze UPS bevat LEVENSGEVAARLIJ KE ELEKTRISCHE SPANNING Alle reparaties en onderhoud dienen UITSLUITEN D DOOR ERKEND SERVICEPERSON EEL te worden uitgevoerd Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD WAARSCHUWING A e Deze UPS bevat zijn eigen
47. tensit Prendre les pr cautions n cessaires Une mise au rebut r glementaire des batteries est obligatoire Consulter les r glements en vigueur dans votre localit Ne jamais jeter les batteries au feu L exposition aux flammes risque de les faire exploser Sicherheitsw arnungen WICHTIGE SICHERHEITSANWEISUNGENANLEITUNGEN AUFBEWAHREN DIESES HANDBUCH ENTHALT WICHTIGE SICHERHEITSANWEISUNGEN Die USV f hrt lebensgef hrliche Spannungen Alle Reparatur und Wartungsarbeiten sollten nur von Kundendienstfachleuten durchgef hrt werden Die USV enth lt keine vom Benutzer zu wartenden Komponente ACHTUNG Diese USV ist mit einer eigenen Energiequelle Batterie ausgestattet An den Ausgangssteckdosen kann auch dann Spannung anliegen wenn die USV nicht an einer W echselspannungsquelle angeschlossen ist Das Eingangskabel nicht entfernen oder abziehen w hrend die USV eingeschaltet ist weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Ger ten entfernt wird Um die Brand oder Elektroschockgefahr zu verringern diese USV nur in Geb uden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren in denen keine leitenden Schmutzstoffen vorhanden sind Die Umgebungstemperatur darf 40 C nicht bersteigen Die USV nicht in der Nahe von Wasser oder in extrem hoher Luftfeuchtigkeit max 95 betreiben Um internationale Normen und Verdrahtungsvorschriften zu erf llen d rfen die an de
48. the battery The UPS is in Sleep mode If the UPS is on battery and supporting a small electrical load 596 the UPS shuts down the load in approximately 30 seconds This feature conserves battery power To disable this feature contact your service representative UPS on battery see Battery M ode on page 29 for more information Battery Intermittent audible alarm The UPS is powering the equipment with battery power Check the bar graph indicators for available battery capacity and prepare your equipment for shutdown oo mine battery warning ZIN M Warning Low Battery 3 minutes or less of battery power remains depending on load configuration and battery charge Prepare for a shutdown Save your work and turn off your equipment m A j j e 0000 Shutdown imminent Shutdown Low Battery Prepare equipment for shutdown gt e Bypass UPS is in Bypass mode Continuous audible alarm The equipment is transferred to utility pow er how ever the utility power continues to be passively filtered by the UPS Check for one of the following alarms Overtemperature Overload UPS Failure or Battery Service 56 Powerware 9125 User s Guide www powerware com Troubleshooting Alarm or Condition Possible Cause Action p W Bypass Bypass is not available Input voltage is not within 12 of nominal or input frequency is not within 3 of nomin
49. the single port module on the UPS rear panel Retain the screws see Figure 21 Figure 21 Removing the Single Port Module 2 MovetheJ3 jumper to the AS 400 position to enable the On Bypass relay as shown in Figure 22 On Bypass Disabled On Bypass Enabled gt AS 400 A Z Z On Bypass Relay umper 3 Figure 22 On Bypass Relay J umper Powerware 9125 User s Guide www powerware com 39 Additional UPS Features 3 To prevent electrostatic discharge ESD place one hand on a metal surface such as the UPS rear panel Align the single port module with the slot guides and slide the module into the slot until it is firmly seated 4 Securethe single port module with the screws removed in Step 1 USB Module With this module the UPS can communicate with a USB compliant computer using LanSafe IIl FailSafe 111 v4 15 or higher power management software To establish communication with your computer 1 Connectthe USB cableto the USB port on your computer 2 Install the LanSafelll FailSafe 111 software and USB drivers according to the instructions provided with the CD Remote Emergency Pow er Off 40 The Powerware 9125 includes a REPO port that allows power to be switched off at the UPS output receptacles from a customer supplied switch in a remote location The REPO f
50. through the Remote Emergency Power Off REPO port Start on battery capability allows you to power up the UPS even if utility power is not available Optional X Slot modules provide enhanced communication capabilities for increased power protection and control The Powerware 9125 is backed by worldwide agency approvals Powerware 9125 User s Guide www powerware com lo ar CHAPTER 2 SAFETY WARNINGS Read the following precautions before you install the UPS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating the equipment and save this manual for future reference This UPS contains LETHAL VOLTAGES All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY There are NO USER SERVICEABLE PARTS inside the UPS e This UPS contains its own energy source batteries The output receptacles may carry live voltage even when the UPS is not connected to an AC supply Do not remove or unplug the input cord when the UPS is turned on This removes the safety ground from the UPS and the equipment connected to the UPS Toreduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled indoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F
51. tional i 5 Am T Figure 4 Horizontal Cabinet Setup Powerware 9125 User s Guide www powerware com 19 Installation NOTE The air vents should be at the top of the unit when positioned vertically 2 le Air Vents prem eoo m m Figure 5 Vertical Cabinet Setup When single UPS cabinet is positioned vertically the UPS stands must be attached to the bottom of the cabinet tower 1 Placethe UPS horizontally so that the left end of the unit is accessible 2 Slide and position the UPS stands over the end of the unit so that the weight of the UPS is evenly distributed see Figure 6 Secure the stands with the screws provided in the accessory kit Figure 6 Installing the UPS Stands 3 Carefully position the unit upright on the UPS stands see Figure 7 Continue to the following section Installing the UPS 20 Powerware 9125 User s Guide www powerware com Installation Figure 7 UPS Cabinetwith Stands Installing the UPS The following steps explain how to install the UPS Figure 9 shows typical installation only See UPS Rear Panels on page 24 for the rear panel of each model CAUTION A small amount of arcing
52. to 77 F Transit Temperature 25 C to 55 C 13 F to 131 F Relative Humidity 5 90 noncondensing Operating Altitude Up to 3 000 meters above sea level Transit Altitude Up to 10 000 meters above sea level Audible Noise Less than 45 dBA Normal mode typical load Less than 50 dBA Battery mode Surge Suppression ANSI C62 41 Category B formerly IEEE 587 Safety Conformance UL 1778 UL 497A UL 1778 UL 497A CAN CSA C22 2 No 107 1 107 2 CAN CSA C22 2 No 107 1 107 2 NOM 019 SCFI EN 50091 1 1 and IEC 60950 NOM 019 SCFI Safety M arkings UL CSA EMC Class B FCC Part 15 ICES 003 VCCI EN 50091 2 FCC Part 15 ICES 003 VCCI Table 8 Battery Configuration 700 1000 VA 2 12V 9 Ah internal batteries 1250 2000 VA 4 12V 9 Ah intemal batteries EBM Configuration PW 9125 24 EBM 8 12V 9 Ah PW 9125 48 EBM 8 12V 9 Ah Type Sealed maintenance free valve regulated lead acid Charging Internal battery approximately 2 hours to 8096 usable capacity at nominal line voltage after full load discharge External battery no more than 10x discharge time to 9096 usable capacity at nominal line voltage after full load discharge Monitoring Advanced monitoring for earlier failure detection and warning auto detection of additional EBM s Powerware 9125 User s Guide www powerware com 53 Specifications Table 9 Battery Run Times in Minutes 700 1000 VA
53. y for one beep The UPS switches to Configuration mode The bar graph indicators flash briefly and then display the enabled options 2 Pressthe On button to scroll through the options Each time you press the button the UPS beeps The LED for the selected option indicates the current setting flashing represents disabled options see Figure 18 and Table 1 If you press the On button and nothing happens the UPS is still in Operation mode Repeat Step 1 for one beep ONLY to enter Configuration mode and then perform Step 2 Powerware 9125 User s Guide www powerware com 33 Configuration 3 Press the button ONCE to toggle the selected option on off Repeat Steps 2 and 3 for each option Scrolling past the last LED returns to the first configuration option NOTE The UPS exits Configuration mode automatically after two minutes 4 Press the On button and the 4 button simultaneously to exit Configuration mode at any time H O o o Bar Graph Indicators O 0 0 Press the Test Alarm Reset CD Press the On and Test Alarm Reset button to toggle an option buttons simultaneously to toggle betw een on or off Configuration and Operation mode Test Alarm On Button Reset Button Press the On button to scroll to the next option Figure 18 Using the Configuration M ode 34 Powerware 9125 User s Guide www powerware com Configuration Table 1 Configuration