Home
Instruction Manual
Contents
1. 61 CHAPTER 8 wire Reoguirement sese 62 CHAPTER 9 Compatible Devices eere 63 CHAPTER 10 Abbreviatton nennen 64 8 RE DD UM 2558 V 1 0 00 Chapter 1 Introduction This manual is intended as a complete guide to the 4 8 Zone Conventional Fire Alarm Control Panels This manual provides complete information on installation commissioning Operating Instructions programming guide service and maintenance procedures with full technical details 1 1 System Design and Planning It is assumed that the system of which this control panel is a part has been designed by a competent fire alarm system designer in accordance with the requirements of NFPA 72 and any other local codes of practice that are applicable The design drawings should clearly show the positions of the field devices and the control equipment 1 2 General The panel is self contained with integral power supply and space provision for two sealed lead acid standby batteries and comply with the requirements of NFPA 72 The panels functions are microprocessor controlled and test and isolate functions are included Provision is made for a repeater function of panel status output The panel can accept per zone automatic detectors with a total maximum loading of 2mA quiescent current rating refer to chapter 2 2 and an unlimited number of manual call points Installation The panel is easy to install and operate Control functions Programming functions are ena
2. 59 RE DD UM 2558 V 1 0 00 6 5 Trouble Shooting Condition Root Cause Remedy There is no No power to the Check Primary AC indication on Panel power and Standby the panel power During Mains fail condition Battery May be battery low 21 6V or the Check the Battery voltage and charge the fault LED is battery reaches the battery or replace the glowing de rated 19 5V battery Voltage The Battery The Battery Connect the battery fault and connected in properly charger fail reverse shown in LCD 60 RE DD UM 2558 V 1 0 00 Chapter 7 Battery Calculation Use Table 7 4 to calculate the total standby and alarm load in ampere hours AH This total load determines the battery size in AH required to support the control panel under the fail of the AC Power Supply Complete the table 7 4 as follows 1 Enter the NFPA standby and alarm times refer to NFPA requirements below 2 Calculate the ampere hours fro standby and Alarm and then sum the standby and alarm ampere hours 3 Multiply the sum by the derating factor of 1 2 to calculate the proper battery size in AH 4 Write the ampere hour requirements on the protected premises lable located inside the cabinet door TABLE 7 4 Total Secondary Power Requirements at 24 VDC Normal Condition X 2S Amps x Hrs Backup time required Alarm Condition Y F Amps x___ Hrs Backup time required Battery Ah requir
3. Y To move the cursor point in the LCD as required ENTER Key Y To accept the programmed or edited menu mode or value in the LCD MENU Key Y To enter into the Main Menu in the LCD CHANGE KEY Y To change the status of modes 2 32 Indications 2 3 2 1 LED indication System On Green Fire Red Fault Yellow Supervisory Yellow Mains Fail Yellow Battery Fault Yellow Earth Fault Yellow System Fault Yellow Silenced Yellow NAC Fault Yellow Walk Test Yellow Charger Fault Yellow Zone Fire Red Zone Supervisory Yellow Zone Fault Yellow Zone Disable W T Yellow 17 RE DD UM 2558 V 1 0 00 2 3 2 2 LCD Indic ation The LCD is mainly used for the programming of the panel It also indicates all events along with the LED indications except system on and system fault 2 3 2 3 Local Buzzer A piezo buzzer provides separate and distinct sounds for alarm trouble and supervisory conditions Alarm Continuous Fault pulse 0 5sec ON and 5sec OFF Supervisory pulse 0 25sec ON and 0 25sec OFF 2 4 Mechanical Construction The enclosure of the Panel is constructed by 18 gauge 1 22mm CRCA sheet with powder coated finish The 22225mm 219mm 11No s for Indian Std 10no s of knockouts are given for cable entry at the top of the cabinet The lockable hinged door is provided to access the inside the cabinet The panel also has sufficient space to accommodate 2 Nos of 12v 7Ah
4. 2 Ravel RE 2554 Fire Alarm Panel RE 2558 Automatic Fire Alarm Control Panel Protective premises Unit Installation Commissioning amp Operating User Manual Fire Alarm System Limitations An automatic fire alarm system typically made up of smoke detectors heat detectors manual Call Points audible warning devices and a fire alarm control with remote notification capability can provide early waming of a developing fire Such a system however does not assure protection against property damage or loss of life resulting from a fire The Manufacturer recommends that smoke and or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 NFPA 72 manufacturers recommendations State and local codes and the recommendations contained in the Guide for Proper Use of System Smoke Detectors which is made available at no charge to all installing dealers A study by the Federal Emergency Management Agency an agency of the United States government indicated that smoke detectors may not go off in as many as 35 of all fires While fire alarm systems are designed to provide early warning against fire they do not guarantee waming or protection against fire A fire alarm system may not provide timely or adequate warning or simply may not function for a variety of reasons Smoke detectors may not sense fire where smoke cannot
5. KS E YF Cees eee EEE Y WE S Bo 4 4 3 24 ES e 20 mm di p S PA ipa leer 3 4m LO KL gt zk x L i 1 t 274 mm 1 i E Z S e E r e Zo A e ds ts d l i E a 4 ie X 4 36 mm p L E mer i I KL K A y 2K C 380 mm 30mm 30 mm Figure 9 Remove all the Boards before placing the panel in its mounting position Place the panel in its mounting position and fix the panel to the wall using the slots of the four screws Ensure the enclosure and the inner parts of the panel are given sufficient protection during installation Fix the all boards in its position Refer Figure24 25 amp 26 All external cables are to be entered via the 20 numbers of g19mm preformed knockouts located at top of the panel When the installation of all the cables has been completed clean the interior of the enclosure ensuring all masonry debris and drilling swords are removed 24 RE DD UM 2558 V 1 0 00 3 3 Panel Wiring Warning Several different sources of power can be connected to this panel Disconnect all sources of power before servicing The panel and associated equipment may be damaged by removing and or inserting cards modules or inter connecting while this unit is energized Primary Power source AC and Earth Ground Connections AC Power connections are made inside the control panel cabinet The Primary source for the RE 2
6. Supervisory A Alarm Verification W Walk test D Disable The zone is selected by using the right left arrow keys the mode can change using the Change key Then press the Enter key to accept the changes This process can be continued in case of otherzone to be changed Note l At the time of Fire Supervisory events in a fire supervisory mode set zone that particular zone mode can only be disabled 2 To come out of the menu configuration press Menu key Fire Mode In this mode the zone will be in normal condition to detect the fire with detectors and manual pull station normally open devices This mode is represented as F at the time of setting Supervisory Mode In this mode the zone will detect normally open devices The optional feature of selecting resettable latching mode This mode is represented as S at the time of setting Disable Mode In this mode the zone is disabled with loop voltage cut off This mode is represented as D at the time of setting Note Avoid disabling any zone unless it is really essential Walk test In this mode the selected zone is used to check all the loop devices manually one by one The signal from the Initiating device will cause the panel in the alarm mode The panel automatically get silenced and reset after a specific period without activating the fire relay In this mode reset is done for only that particular zone When entering into this mode the Fire
7. reach the detectors such as in chimneys in or behind walls on roofs or on the other side of closed doors Smoke detectors also may not sense a fire on another level or floor of a building A second floor detector for example may not sense a first floor or basement fire Particles of combustion or smoke from a developing fire may not reach the sensing chambers of smoke detectors because Barriers such as closed or partially closed doors walls or chimneys may inhibit particle or smoke flow e Smoke particles may become cold stratify and not reach the ceiling or upper walls where detectors are located e Smoke particles may be blown away from detectors by air outlets e Smoke particles may be drawn into air returns before reaching the detector 1 RE DD UM 2558 V 1 0 00 The amount of smoke present may be insufficient to alarm smoke detectors Smoke detectors are designed to alarm at various levels of smoke density If such density levels are not created by a developing fire at the location of detectors the detectors will not go into alarm Smoke detectors even when working properly have sensing limitations Detectors that have photo electronic sensing chambers tend to detect smoldering fires better than flaming fires which have little visible smoke Detectors that have ionizing type sensing chambers tend to detect fast flaming fires better than smoldering fires Because fires develop in different ways and are oft
8. Auto Silence Disabled Mode Type 120 Secs Use Cursor Key to di al Increase Decrease 7 Auto Silence gt the time del ay 128 Secs 8 Silence Inhibit 1 4 Disabled Use Change Key to 8 Silence Inhibit Mode Type 060 Secs rotos AE 8 Silence Inhibit 4 Wen crease Decreas the time delay 065 Secs 9 AC Loss Delay 120 Mins 4 Use Cursor Key to Pu 9 AC Loss Delay 4 Increase Decrease 2 N gt the time delay 120 Mins Use Change Key to 9 AC Loss Delay M ode Type Disabled 10 Trouble Remin 720 Mins 4 Use Cursor Key to lt r Increase Decrease 10 Trouble Remin the time dela y Disabled lt p gt Use Change Key to 9 AC Loss Delay Mode Type Disabled 34 RE DD UM 2558 V 1 0 00 MENU KEY FLOW DIAGRAM RE 2554 58 Programme Flow Diagram p gt Use Change Key to 11 NAC1 OUTPUT Use Change Key M od e Type Steady to M ode Type WeSynch ronized p gt Use Change Key to 12 NAC2 OUTPUT Use Change Key c Mode Type Steady to M ode Type amp Synchronized p gt Use Change Key to 13 24V Output Mode Type Steady EX 11 NAC1 OUTPUT Temporal 12 NAC2 OUTPUT Temporal 13 24V Output Ressettable 14 Change User Password Enter Old Passwords Confirm New Passwords Enter New Passwords 15 Change Admin P3ssword Password Update d al 16 About a U
9. DD UM 2558 V 1 0 00 Chapter 9 Compatible Devices ID CD 01 The compatible devices which are connected with this panel are given below Compatible IDC s 1 Apollo 65A Series Model 55000 226 16 Nos Zone 2 System Sensor 100 Series Model 2151 16 Nos Zone 3 System Sensor Beam Smoke Detector Model BEAM 224 S 1No Zone Compatible NAC s 1 System Sensor Mini Horn Model MHR MHW 30 Nos Circuit 2 System Sensor Strobes Model MHR MHW 9 Nos 8 15cd setting Circuit End Of Line Devices 1 RE Monitor for RS24v O P 2 RE3K9 for IDC s RS sen and NACs 63 RE DD UM 2558 V 1 0 00 Chapter 10 Abbreviation The short forms which are given in this manual are abbreviated below RE NFPA AC DC CRCA LED O P mm no s P N E v Ah IEE EOL PCB CPU MCP S Nos mA Kgs C NO NC Ravel Electronics Pvt Ltd National Fire Protection Association Alternating Current Direct Current Cold Rolled Carbon Alloy Light Emitting Diode Output millimeter number s Phase Neutral Earth volt s Ampere per hour Institute of Electrical Engineering End Of Line Printed Circuit Board Central Processing Unit Manual Call Point Serial Numbers milli Ampere killo grams Common Normally Open Normally Close 64 RE DD UM 2558 V 1 0 00 Ravel Electronics Pvt Ltd 150A Electronic Industrial Estate Perungudi Chennai 600096 India Web www rav elfire
10. OF 4 1 Menu Key Flow Diagram senes 94 4 2 Programming tilo AZ SEUZONS ee EE 36 4 2 2 Suppressed Fault Events 39 4 2 3 Suppressed Supervisory Events 39 4 24 Zone Wiring sss ee eee e 39 4 2 5 Supervisory Mode 40 4 26 Walk tesina tira ias 40 4 2 7 Auto Gilence csse nennen 40 4 28 Silence Mhibit EE 41 RE DD UM 2558 V 1 0 00 4 29 AC Loss Delay ceder m eee ele bre tte ted 41 4 2 10 Trouble Reminder sse 42 AZ T NACT QUID cai A ed Edita ee S i cans 42 4 2 12 NAO2 Output E 43 AZ AVG ZA QUIDUL cda pore t ere Co Cerda e Pet dea 43 4 2 14 Change User Password ee eee eee eeeeeeee 44 4 2 15 Change Admin Password ee eee e eee e e 44 4 2 15 ABOUT oe be d vitse ee MED puc ba redeat d 45 CHAPTER 5 Operating Instructions sees ees O 5 1 Switch Functions caia osse eri dida 0 Tele e 48 ET odes acus t e mucosa ito Dues mutas ds 50 5 3 1 Normal Monitoring Mode 50 5 3 2 Fire Alarm COMGIUON sic derriere eer ek teta 50 5 9 9 SUDCIVISONY EE 51 53 4 Palla 53 5o Disabled Tories E eo e et ee 53 5 3 6 Alarm VertmtiGSllOnia ducas dunt dido oca tratos duh per paredes 55 CHAPTER 6 Servicing eeeeeeeeeeee seen nennen nnn nnn 56 6 1 Installation Replacement of PCB 56 ST ETU TES ascitis tl 58 ET EE 58 6 4 System Power 59 6 5 Trouble Shooting eric ete ERE Lu t een 60 CHAPTER 7 Calculation of Battery Size
11. Turn on the zone fault NAC fault power fault LED Turn on the panel buzzer tone with intermittent buzzer tone pulse 0 5ec ON and 5sec OFF Aclivate the fault relay The LCD screen will be as below Fault XX YY Type of Fault XX ni no of events YY Total no of events Restoral When the fault condition is cleared the panel will perform the following automatically Turn off the fault LEDs Turn off the zone fault LED NAC fault power fault LED Turns off the buzzer tone gt Deactivate the fault relay The LCD screen will be as below FIRE ALARM SYSTEM HEALTHY Note The Fault occurred will not affect the other normal functions of the panel 5 3 5 Disable W T Disable The any Zone can be Disabled Enabled in zone mode through the programming section 4 2 1 Page 35 The ON status indicates the zone is disabled and the OFF status of the LED indicates the enabled and blinking of that LED indicates the zone is in walk test mode In LCD the suppressed events are viewed in suppressed events from menu screen 53 RE DD UM 2558 V 1 0 00 Fault XX Y Y Zone X Disabled XX nth no of events YY Total no of events X Zone No Disabled Walk Test Disable W T LED Blinking identifies the corresponding Zone which is under walktest If this LED is illuminates continuously then it identifies that particular zone is disabled The walk test mode helps the user to test each
12. Key This key is used to get into the program menu and get back to the previous menu screen CURSOR KEYS The cursor keys Right Left arrows are used to move the cursor point wherever required CHANGE KEYS These key is used to change the status of modes And to clear the password entries 47 RE DD UM 2558 V 1 0 00 5 2 Indications Fault x y Type of Fault x nth no of fault y Total no of fault Figure 22 SYSTEM ON This LED will glow when the panel is energized by primary and standby power This is the only LED glowing in the normal monitoring condition The LCD Display as shown below FIRE ALARM SYSTEM HEALTHY MAINS FAIL Whenever the Main Supply 110 220v A C fails the Mains fail LED will be illuminated and it also indicated in LCD with toggle Buzzer tone The LCD Display as shown in the figure 22 Mains fail will be displayed in the fault screen BATTERY FAULT Whenever the backup battery fails the battery fault LED will be illuminated and it also indicated in LCD with toggle Buzzer tone Similarly the same LED will be illuminated when the battery voltage goes down below the 21 6v Battery Low The LCD Display as shown in the figure 22 Battery Fail Battery Low will be displayed in the Battery fail Battery low fault screen respectively CHARGER FAULT Whenever the battery charger section is fails the charger fault LED will be illuminated and it also indicated in LCD with tog
13. are Silence Reset Ack Evacuate and Enter keys SILENCE Key When the silence key is pressed after entering the user or admin password the following will occur The silenceable Notification Appliance Circuits will be turned OFF The Silence LED will be turned ON Upon the occurrence of a subsequent fire event Signal Silence is overridden and the control panel will respond to the new event RESET Key When the Reset key is pressed after entering user or admin password the control panel will 46 RE DD UM 2558 V 1 0 00 Clear the status LED s Bring back the LCD display to the healthy condition Turn off the Notification Appliance Circuits gt Reset fire zones by temporarily removing power Restore all system relays to normal gt Temporarily remove power from the resettable power output CN7 The Reset key is accessible only after silencing in alarm condition Any alarm supervisory or trouble condition that exists after a system reset will resound the system reactivating normal system activity ACK Key This key is used to acknowledge the buzzer tone during the fault and fire condition This key can be operated with user or admin password EVACUATE Key This key is used to energize the all external NAC s without actual fire It will operate at user or admin level Using the silence key NAC output can be silenced ENTER KEY This key is used to accept the entries and edit the programmed menu MENU
14. begins to stabilize all the detectors If no other detector alarm there will no alarm indication in FAP during Retard Reset restart period During the conformation period of 60 seconds the subsequent alarm in the same detector will cause FAP to activate immediately appropriate outputs and indicates alarm indication in the FAP During this conformation period or Reset amp Retard period if there is any alarm in other zone the panel activates immediately appropriate outputs in FAP Os 3 5s 15 5s 80s 12s 64 5s Restart Conformation Retard Detector Alarm Reset Verification 64 5s Same Detector Alarm ignored in same detector Control pane process alarm if same detector is still in alarm Goes into Alarm Control panel process alarm immediately Different Detector Alarm during First Detector s verification period Note Alarm Verification is available for only smoke detectors connected zones Figure 24 55 RE DD UM 2558 V 1 0 00 Chapter 6 Servicing 6 1 Installation Replacement of PCB Remove the screws of PCB which has to be change and remove the PCB from the mounting position and place the new PCB in that same position as shown below Mounting position for Main Circuit board RE 25XX ZB R1 Cable Entry Knock out Figure 25 56 RE DD UM 2558 V 1 0 00 Mounting position for Display board RE 2558 54 DISP R1 PCB Mounting 5 Hole WIFFFFEFEUIFIIEE dy e
15. device in that particular zone by a single person During walk test mode if any Fire is identified the panel will be silenced and reset automatically after 4 seconds and 2 seconds respectively In case of any other zone fire during this period it is considered as actual fire and it comes out from the walk test mode The LCD Display is as shown below WT Fire XX Y Y Zone X For More than One zone in Walk test fire condition the screen as follows WT Fire XX YY Jet oo Zone X Rt bb Note a If there is no more testing please ensure that the zone is brought back to the normal Condition b During in this mode the Fire Relay will not be activated while in fire condition c If the zone is kept in Walk test mode for 10 minutes with out any test the panel comes out of the walk test mode automatically d In other zone gets fire the walk test mode automatically removed 54 RE DD UM 2558 V 1 0 00 Restoral When the zone restored to normal condition from disable Walk test mode the zone which are all in disable W T mode the corresponding LED s goes off 5 3 6 Alarm Verification This Alarm verification feature is applicable only to the IDC s in the zone in which only smoke detectors are used If the alarm verification is selected IDC the smoke detector activation will cause the FAP to reset the detector by removing the power for 3 5 Seconds Power is reapplied to the detectors and restart period 12 Seconds
16. for the disable Alarm Verification In this mode the detectors connected in the selected zone are used to check and confirm that smoke detector activates the verification alarm The smoke detectors should be connected to the zone which going to select as for alarm verification Note Use only the alarm verification facility to zone loop in which the smoke detectors are used 38 RE DD UM 2558 V 1 0 00 4 2 2 4 2 3 4 2 4 Suppressed Fault Events From the Suppressed Fault Event program screen By pressing the Enter key the system enters into the Suppressed Fault Event In this mode the suppressed fault events other than fire events can be viewed sequentially using the right left arrow keys After entering the suppressed fault events screen will be as below Sup Fault x y EVENT Note Through suppressed events feature you can view the fault occurred currently during alarm condition Suppressed Supervisory Events From the Suppressed Supervisory Event program screen by pressing the Enter key the system enters into the Suppressed Fault Event In this mode the suppressed Supervisory events can be viewed sequentially using the right left arrow keys After entering ihe suppressed Supervisory events screen will be as below Sup Suprv x y EVENT Zone Wiring From the Zone Wiring program screen The zones circuit is designed for the class B wiring The style of wiring can be changed using this op
17. in a delay of the system alarm signal from the indicated circuits The total delay shall not exceed 80 Sec no other smoke detector shall be connected to these circuits unless approved by the local authority having jurisdiction 30 RE DD UM 2558 V 1 0 00 E O t RESISTOR 3K9 OHMS E 1 RESISTOR 3K9 OKMS Hb TD LON AN Zere smoke detecror Al J d LO Zare smote deteztor U KR e LU Mara i Station amp Mansa Ful Saxon O L RESISTOR 3K OMMSIOR UNUSED TONE LOOPS X f AJA fx fA EBE HEE z tt Tt 3H fH 1H leeeeeco geeoqe 18 17 16 15 14 13 12 11 Figure 16 3 5 Output Circuits 3 5 1 Notification Appliance Circuits No of NAC 2 Ckis Type i Class B Style Y Current 0 6A Each Terminals CN5 CN6 Monitoring Device 3K9 EOL Wire Size f 1 5 sq mm Max Compatible Device Refer Chapter 9 NOTE For Synchronized ANSI Pattern Output External Synchronizing Module to be used Refer Chapter 9 for Compatible Devices 31 RE DD UM 2558 V 1 0 00 Class B Notification Appliance Circuit supervised 3K9 ohms Watt Polanzed Bell Polarized Bell Polarized Horn Polarized Horn Polarized Horn Polarized Horn Note Notification Appliance Circuit polarity shown in alarm stote RETAIN E O L RESISTOR 3K9 OHMSFOR UNUSED CIRCUITS Figure 17 3 5 2 24V Output 300mA Output Voltage 24VDC Nominal Current 0 3A Max Output Terminal CN9 Wire Size 1 5sq mm Max Monitoring Devic
18. loss after the fime delay setting Press Change key to toggle between enabled 41 RE DD UM 2558 V 1 0 00 4 2 10 4 2 11 disabled option The AC Loss Delay timing can set 001 to 999min After setting the required time press Enter key to accept the time The default time is 120 Seconds When you enter into this mode the screen will be as below 9 AC Loss Delay 120 Min gt In AC Loss Delay is enabled condition to change the time press enter key and use left right key to increase decrease the timing Trouble Remainder The Trouble Reminder feature provides an audible reminder that a Fault still exists on the panel after the control panel has been silenced The factory default for this feature is Enabled When this feature is enabled the control panel buzzer will give a beep tone for every set time during a trouble condition after the Signal Acknowledge switch is pressed The buzzer tone will continue to sound at these rates until the trouble condition is cleared Press Change key to toggle between enabled disabled option The Trouble Reminder timing can set 1 to 999mins After setting the required time press Enter key to accept the time The default time is 720 Seconds When you enter into this mode the screen will be as below 10 Trouble Remin 720 Min gt NAC1 Output The NACI output can be configured as steady Temporal Synchronized In Temporal and synchronize mode the NAC1 output wil
19. 558 RE 2554 is 110 220 VAC 50 60Hz 2 5 Amps Run a pair of wires with Earth conductor from the protected premises main breaker box to connector CNT RE SMPS 4A RI of the power supply board As per National Electrical Code use 14 AWG 2 00 mm 1 6mm O D or heavier gauge wire with 600V insulation No other equipment may be connected to this circuit In addition this circuit must be provided with over current protection and may not contain any power disconnect devices A separate Earth Ground connection must be made to ensure the proper panel operation and lighting and transient protection Connect the Earth Ground wire Min 14AWG 2 00 mm to the connector CNT Standby Power Source Batteries Observe polarity when connecting the battery Connect the battery cable to connector CN10 on the Zone board RE 25XX ZB R1 using the connector and cable provided The battery charger is current limited and capable of recharging sealed lead acid type batteries upto 12Ah During alarm condition the charger section is disconnected from the battery hence there will not be any charging at that time 25 RE DD UM 2558 V 1 0 00 RE 2558 Power Supply Circuit Board RE SMPS 4A R1 Power Limited 30 VDC Output Power Limited To Zome Board RE 25XX ZB R1 110 220 VAC Main Supply input PNE ior v Con Sum umm con MOVZ ntt nU ie INE LA o q ey LE K gt RTT en e e Kap nnt 14 E Te 6 Fi
20. 558 is a 4 amp 8zone microprocessor based conventional Fire Alarm Control Panel The Panel accepts water flow devices conventional input devices like 2 wire and 4 wire smoke detectors Manual Call Points and other normally open contact devices The Outputs include two notification appliance circuits NACs Resettable 24v D C output Three Form C relays for alarm fault and supervisory This panel is field programmable via the front panel keypad It supervises all wiring AC voltage and Battery level 12 RE DD UM 2558 V 1 0 00 2 1 Product Feature VV Y Y Y Y Y NY N NY YN Y Y Y Y Y Y Y Y Y Y Y NY NY Y 4 8 Class B initiating device circuit IDC All zones accept smoke detectors and any normally open contact device Any Zone can be configured as Alarm or supervisory Zone 2 Class B Notification Appliance Circuits NAC Fully complies with UL 864 and NFPA 72 Rugged CRCA sheet with powder coated finish Operates on 110 220v 50 60 Hz AC Mains power supply Standby battery backup 24v DC power supply with built in charger 16x2 Dot Matrix LCD Display Error free Fire Fault status in unambiguous colored LED indication System ON indication Main Standby status audible and visual indication Battery Low visual waming with audible tone Form C relays for fire fault and supervisory Resettable uninterrupted 24v D C Output RS 485 Communication facility Optional Lamp Test facility Walk Test fa
21. Maximum End Of Line Resistor 3K9 1 2watt Standby Current 7mA 2mA for Detectors Notification Appliance Circuits CNS and CNA Class B Style Y wiring Operating Nominal Voltage 24VDC Special Application Current for all NACs 1 2Amps 0 6A per circuit Current Limit CN5 and CN6 via Thermal Fuse Line Drop 1 8V End Of Line Resistor 3K9 1 2watt Note For compatible devices refer Chapter9 CD 01 D C Power CN7 Operating Voltage Supervised 24VDC regulated 300mA Max for 4 wire smoke detector 15 RE DD UM 2558 V 1 0 00 Common Three Form C Relays CN2 CN3 CNA Relay Contact Rating 2Amps 30 VDC 2Amps O 30VAC Power Factor 0 6 2 3 Control and Indication FIRE ALARM PANEL Bi Ravel Leo T T zone Indication Common Faw indieatian Figure 2 2 3 1 Controls ACK Key Y To mute local buzzer in alarm condition Y To mute local buzzer in Supervisory or fault condition Y User or Admin password protected SILENCE Key Y To silence the external NACs in Fire Condition Y User or Admin password protected RESET Key Y To reset the particular zones in Fire alarm or Latched Supervisory condition Y User or Admin password protected Y Possible to access only after silence in alarm condition 16 RE DD UM 2558 V 1 0 00 EVACUATE Y To activate External NACs Manually Y User or Admin password protected CURSOR KEYS
22. UM 2558 V 1 0 00 Power Supply Board RE SMPS 4A R1 Figure 8 This Power supply Board gives the 30V DC output for the Zone Board This board is SMPS type it gives the output for 2 5Amps Max 4Amp During Initial condition Cabinet The Cabinet measures 440mm width X 340mm Height X 120mm Depth and space is provided for 2 x 12 Volt 7Ah Batteries main circuit board and display board 21 RE DD UM 2558 V 1 0 00 Chapter 3 Installation 3 1 Installation Precaution o J lt PO 1 M D WARNING High Voltage Take suitable precautions to avoid electric shock RELATIVE HUMIDITY Installation Precautions WARNING Several different sources of power can be connect ed to the fire alarm control panel Disconnect all sources of power before servicing Control unit and associated equipment may be damaged by removing and or inserting cards modules or interconnecting cables while the unit is energized Do not attempt to install service or operate this unit until this manual is read and understood CAUTION System Reacceptance Test after Soft ware Changes To ensure proper system operation this product must be tested in accordance with NFPA 72 after any programming operation or change in site specific software Reacceptance testing is required after any change addition or deletion of system components or after any modification repair or adjustment to system hardware or wiring All co
23. and subsequent zone fire LED will glow steadily The LCD screen will be as below Fre XX Y Y Ist aa Zone X Rt bb X index no of fire event Y Total no of fire events aa Origin Fire zone number bb Recent Fire zone number 50 RE DD UM 2558 V 1 0 00 Zone X Denotes the zone number which is recent fire zone To change the other indexed fire event zones which are suppressed use right left arrow keys Restoral Silence the NAC s by appropriate user or admin password after silencing the panel will perform the following Turn off the Internal Buzzer Turn off the External NAC s Turn on the silenced LED When the Fire condition is cleared and Reset key has been pressed after entering the user or admin password The Reset is accessed only after silencing the panel in alarm condition The panel will perform the following after clearing fire and resetting Turn off the common twin Fire LEDs Turn off the zone fire LED Turn off the Fire relay The LCD screen will be as below FIRE ALARM SYSTEM HEALTHY 5 3 3 Supervisory When the control panel detects supervisory signal via the any normally open contact devices the panel will cause the following Y The corresponding zone supervisory LED will blink Y The common supervisory LED will glow Y Turn on the panel buzzer with intermittent buzzer tone pulse 0 25sec ON and 0 25sec OFF Y Turn on the supervisory relay The LCD s
24. batteries Ravel FIRE ALARM PANEL RECH m lr lS 4 8 Doe la 1 18 RE DD UM 2558 V 1 0 00 15 mm 10 Nas imm 10Nos k 120mm P p 7 zm Feo S 340mm LHS View Fami View ion Roatan View Figure 4 2 5 Internal Arrangement Man Pawar Lied Cate Eny Fa oOo GO GO CO GO GO COOC CO C2 L LO LO LO LO m a ES Power Supply Coach Master Board DNE Y mele Co Board Bond 7 m SOREL RS SITE AA RO ERES ae SCT 12 n 12628 Saad Lead Acid Battery Sewed Lead Acid Battery Figure 5 19 RE DD UM 2558 V 1 0 00 2 6 Components Master Board RE 25XX ZB R1 115 mm 226 mm gt CN9 CNT CN6 CNS CN4 CNS CN2 it RL o RLI Da RLS asm Y l CNT CNT E 1 3 ex T BUZZER DI D2 H BR lt id 2 Ce oc g BR E Z D4 D3 ux SEN GP 235 mm Figure 6 The Zone board contains the primary components and wiring interface connectors Display Board RE 2558 54 DISP R1 The Display Board contains the system CPU LED Display LCD unit and Control keys 90 mm a LL 30 mm 112 mm NADA DK DB n Le N O NANRNA E AR YER RR e UI LJ e e eo 1 a e H E t dr au me 1 a pu sr 5 ve ew SR EX EX Z ee Se ps See E E qm CS em ve ce ES UK Um 2 A E X L Bez Gr We VS ex t ER em SS a SR E h E E pe pr rm Ff KE S EX A RS e BREE Figure 7 20 RE DD
25. bled by using password The panel fascia is retained by tamper proof screws 9 RE DD UM 2558 V 1 0 00 1 3 Fire Alarm Procedures In accordance with NFPA 72 written procedures should be laid down for dealing with alarms of fire fault wamings and the isolation of any part of the system The responsible person should ensure that users of the system are instructed in its proper use and are familiar with the procedures On hearing the fire alarm CARRY OUT THE PRESCRIBED PROCEDURE Subsequent actions will depend on the circumstances and may include silencing the audible alarms and resetting the system as described later To Evacuate the premises Press the Evacuate key and enter the password to OPERATE NAC s Sounders Fault Indication If the control panel indicates a Fault condition make a note of all illuminated indicators and proceed as described in chapter 6 Section 6 4 or call service engineer 1 4 User Responsibility In addition to the routine testing described on routine test the user has a responsibility for ensuring certain actions are taken following a fire or fault and for implementing remedial action following a specified incidence of false alarms As a minimum the user shall record any incident and inform the service organization who may be required to retest the system 10 RE DD UM 2558 V 1 0 00 1 5 Routine Testing In order to ensure that the system is fully operational and to comply with the r
26. ceptibility to nearby lightning strikes Consult with the Technical Services Department if any problems are anticipated or encountered Disconnect AC power and batteries prior to removing or inserting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer and printed circuit board location Do not tighten screw terminals more than 1 0168 N m Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal Though designed to last many years system components can fail at any time This system contains static sensitive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper installation by authorized personnel 23 RE DD UM 2558 V 1 0 00 3 2 Mounting Details SES EOS EJ Sa C23 o E d E A M E f y 2 Nh EN i RE x come
27. cility Zone Isolation facility with loop voltage cut off Earth fault annunciation facility at O ohms All field wiring circuits are Power limited except 110 220v AC and Battery All field wiring circuits are supervised AC Low voltage cutoff Programmable NAC s Programmable IDC s Programmable Supervisory Mode Programmable AC loss delay Alarm verification facility Programmable Trouble reminder facility 13 RE DD UM 2558 V 1 0 00 Notification Resetable O P Relay Output for Terminals Sense amp 24voc R Fire Fault Primary CN8 ICWT amp CN9 cy CNS Supervisory Source Input CN4 CN3 CN2 110 220V A C 50 60 Hz CN 1 26 Pin FRC Output to Display and control board CN11 Front Sticker Standby source 12 V Battery 12Ah Figure 1 14 RE DD UM 2558 V 1 0 00 2 2 Specification Primary Power CNT RE SMPS 4A R1 110 220VAC 10 50 Hz 2 5Amps Standby Power CN10 24v D C 2 Nos of 12v 12Ah Sealed Lead acid battery Operating Condition Operating Temperature O 49 C 32 120 F Relative Humidity 932 RH non condensing at 32 x2 C 90 3 F Charging Circuit Charging Voltage 28 2V 0 5V Charging Current 800mA Max Initiating Device Circuits CN 8 All zones are Class B Style B C operation Programmable Normal Operating Voltage 14 21 VDC Alarm Current 15 30mA Short Circuit Current 45mA Maximum Loop resistance 100 ohms
28. creen will be as below Suprvisry XX YY Zone X 51 RE DD UM 2558 V 1 0 00 In case of multiple zone supervisory the origin zone and recent zone supervisory LED wil be viewed in LCD screen The LCD screen will be as below Suprvisry XX YY Ist aa Zone X Rt bb X index no of supervisory event Y Total no of supervisory events aa Origin supervisory zone number bb Recent supervisory zone number Zone X Denotes the zone number which is recent fire zone To change the other indexed supervisory event zones which are suppressed use right left arrow keys Restoral When the supervisory condition is cleared and Reset key has been pressed after entering the user or admin password if the zones are programmed for latching the panel will perform the following gt Turn off the supervisory LEDs gt Turn off the zone supervisory LED Turn off the supervisory relay The LCD screen will be as below FIRE ALARM SYSTEM HEALTHY Note If the supervisory mode is selected as resettable the resetting the zone is not required The zone is retrieved automatically after clearing the supervisory condition 52 RE DD UM 2558 V 1 0 00 5 9 4 Fault The fault may any one of the following Zone fault disable earth fault NAC fault and power section fault When there is one or more fault condition the fire alarm control panel performs the following Turn on the common fault LED gt
29. e RE MONITOR Refer Chapter 9 Monitoring Terminal CN9 CN Link 3K9 Max Refer Chapter 9 NOTE The Link should be disconnected after connecting monitoring device Figure 18 Resettable O P 32 RE DD UM 2558 V 1 0 00 3 6 Standard Relay Output Circuits No of Relay Output 3 Fire Fault Supervisory Contact Voltage i 30 VDC Nominal Current Rating i 2A Type of Relay Form C Fire Fault l Supervisory Fire Fault Supervisory Relay Relay Relay Relay Relay Relay NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C Relay Contacts shown in normal condition and Relay Contacts shown in off normal condition no active fire fault or supervisory and with active fire fault or supervisory Figure 19 Figure 20 33 RE DD UM 2558 V 1 0 00 CHAPTER 4 Programming Instructions 4 1 Menu Key Flow Diagram MENU KEY FLOW DIAGRAM enu Key RE 2554 58 Programme SH 1 Set Zone lt Flow Diagram Mode 2 Suppressed t Sup Fault X Y If any Fault Events Fault fault 3 Suppressed Sup Suprv X Y ff any supervisory Events Zone Z fault 4 Zone Wiring 4 Zone Wiring Use Change Key to Class B Stye C Mode Type Class B Style B 5 Supervisory Mde Use Change Key to 5 Supervisory Mde Resetable Mode Type Latched 6 Walk Test Use Change Key to 6 Walk Test Audible Mode Type Silent 4 7 Auto Silence Use Change Key to 7
30. e AD Door Cutout panle ea for PCB fixing uL e E er NR meo dn a See ee em e em l an Ea x U t5 5 St Figure 26 Mounting position for Power supply unit RE SMPS 4A R1 Cable Entry a Knock ou Zone Board Mounting Hala sioh Bunurow Aiddng semog o 12v 12Ah Battery 12v 12Ah Battery Figure 27 57 RE DD UM 2558 V 1 0 00 6 2 6 3 Lamp Test The lamp test function done by pressing Enter key in system Panel is normal condition In this mode all the LED s are checked for good condition by glowing all LED s Walk Test Mode The RE 2558 provides the capability to perform a walktest of the system without triggering the Fire Relay alarm output NAC relay Walk test Mode allows for testing of all the eight zones An audible or silent walktest may be performed For an audible walktest the initiating device activated on a zone will cause the Notification Appliance Circuits to turn on for five seconds Any smoke detectors that are activated will be reset automatically Zonal faults open circuits will cause the NAC to remain on steadily Prior to entering Walktest Mode check to be certain that zone fault have been cleared Placing the control panel into Walktest Mode will only be possible if the system has no active alarms After entering into the walktest mode the fire relay contact disablement is activated automatically and it will go back to previous statu
31. ed AH X Y x 1 2 Derating Factor Note Refer specification Page 10 for Quiescent standby alarm currents System current S Quiescent Current Standby current X No of zone Fire current F Alarm Current x no of zones NAC Current x No of NAC s 61 RE DD UM 2558 V 1 0 00 Chapter 8 Wire Requirements Connecting external system accessories to the RE 2558 main circuits must be carefully considered to ensure proper operation It is important to use the correct type of wire wire gauge and wire run length per each RE 2558 circuit Reference the chart below to specify wire requirements and limitations for each RE 2558 TABLE 8 1 Wire Requirements CIRCUIT TY PE CIRCUIT FUNCTION WIRETYPE AND LIMITATIONS RECOMMEND ED MAX DISTANCE Feet meters WIRE GUAGE Initiating Device Circuit Connects to Initiating Devices Uniwisted unshielded wire Do not exceed 100 ohms 10 000 3 000 m 8 000 2 400 m 4 875 1 480 m 3 225 975 m 12AWG 3 25 mm2 Belden 9583 WPW999 14AWG 2 00 mm2 Belden 9581 WPW995 16 AWG 1 30 mm2 Belden 9575 WPW991 18 AWG 0 75 mm2 Belden 9574 WPW975 24V DC resettable nonresettable Connects to annunciators and other accessories No more than 1 2 volt drop allowed from supply source to end of any branch 62 Distance limitation set by 1 2 volt maximum line drop 12 AWG 3 25 mm2 18 AWG 0 75 mm2 RE
32. en unpredictable in their growth neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate waming of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc While a fire alarm system may lower insurance rates it is not a substitute for fire insurance Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a qualified fire protection specialist Heat detectors are designed to protect property not life IMPORTANT Smoke defectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alam transmission wiring communications signaling and or power If detectors are not so located a developing fire may damage the alarm system crippling its ability to report a fire Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building Any waming dev
33. equirements of UL864 Standard amp NFPA 72 the following routine attention is recommended Daily Check the panel to ascertain that it indicates normal operation If any fault is indicated check that it has been recorded and the appropriate actions have been taken e g informing to the maintaining company Weekly Test at least one detector or call point to confirm the operation of the panel and the audible alarms Test a different zone each week and if possible a different device Keep a record of the device and zone tested each week Record and report any malfunction Quarterly The responsible person should ensure that every three months the system is checked by a competent person Check the standby batteries and the charger voltage Test at least one device in each zone to check the panel functions Check the operation of the audible alarms and any link to a remote manned centre Central Station etc Carry out a visual inspection of the installation to check for alterations or obstructions and issue a certificate of testing Annually The responsible person should ensure that in addition to the quarterly checks each device on the system is tested and that a visual inspection is made of the cable fittings and equipment Note The control panel cabinet should be cleaned periodically by wiping with a soft damp cloth Do not use any solvents 11 RE DD UM 2558 V 1 0 00 Chapter 2 Product Description The RE 2554 amp RE 2
34. ge mode The display screen of this mode showed as below The Default Password is 1234 The Password should be four digit Enter Old Password Enter New Password Confirm New Password Password Updated 4 2 15 Change Admin Password From the Change Admin Password Mode screen By pressing the enter key from the change Admin Password screen system enters into the Admin Password change mode The display screen of this mode showed as below The Default Password is 54321 The Password should be five digit 44 RE DD UM 2558 V1 0 00 Enter Old Password Enter New Password Confirm New Password Password Updated Admin Password can be changed only by entering into the main menu by using the admin password 4 2 16 About It shows the details of the panel by pressing enter key in the about menu The LCD will show as below The model shown with respect to the no of zones for 4zone RE 2554 and for 8 zone RE 2558 16 About RE 2558 Version 1 0 Note Version shown is software version 45 RE DD UM 2558 V 1 0 00 Chapter 5 Operating Instruction T LED E E 3 E E IE eom mm mom mmm mmm mom e pm m mom Ws AS dE dm de m d ws e ee me eom me m n e Re e T Zone Indication Common Fault Inelieatimn Figure 23 5 1 Switch Functions The Keys which are non masked are used for the general operation of the Fire Alarm Panel The Non masked keys
35. gle tone EARTH FAULT Whenever the Initiating Device circuits IDCs and Notification Alarm Circuits NACs are gets contact with the Earth or Body of the cabinet the corresponding fault LED earth fault LED and common fault LED will be illuminated and it also indicated in LCD as corresponding circuit is earth fault with toggle Buzzer tone The Earth fault can be created through 0 Ohms resistor SYSTEM FAULT Glowing of this LED indicates the failure of the CPU 48 RE DD UM 2558 V 1 0 00 SILENCED This LED will glow when the silence key is pressed in fire condition only NAC FAULT Whenever there is any fault in Notification Appliances Circuits like NAC loop Open Short Earth fault it will be identified by COMMON NAC FAULT LED The LCD Display as shown in the figure 22 NAC Fault will be displayed in fault screen WALK TEST The Walk test and zone disable LED will glow whenever the zones are under walk test mode FIRE This twin fire LED will glow when any one or more of the zones are in fire condition SUPERVISORY This supervisory LED will glow when any one or more of the zones are in supervisory condition FAULT This fault LED will glow when any one or more of the zones are in fault condition ZONE FIRE This fire LED will glow when the zones are fire condition The first fired zone continuously in blink and other zone fire LED will glow steadily in fire condition The fired zone is displayed in the LCD fi
36. gure 10 RE 2558 Power Supply Monitor Circuit Board RE Monitor Power Limited 24 VOC Output Sense From Zone Board RE 285XX ZB R1 1 too Power Limited 24 VDC Intput From Zone Board RE 285XX ZB R1 D Figure 11 26 RE DD UM 2558 V 1 0 00 t Board RE 25XX ZB R1 Ir cul RE 2558 Main C IPS T 780047 SdWS 1104 anduj 2aA 0t pour 19m0g dii 480g qpuels Abz ES e es E OLND E E a m Le T 8 3 4322N8 END 010 SND 9ND ide bs inis dc PNW 940g Asosyasedng vay 2 ON ON Arjay Asosyasedng 03 01 VIMO AYOVSMIIANS NON 3 ON IN Anpan mug GIL MOS AUOWSIAAHSdOS NON J ON ON Aeon ond asny neg p ve INO 4 N 6 N rece IN 02 reses nding Ja opt OJOS PMT smog e indino 30 ap 9 EIEN papam 794 04 indino Z2eN APT Bai IOMO andino LIYN APT Papa 2994 L gene sjeunuda duaz D i 20M og LIND EL V preog Aejdsiq OI Yd Uld 92 RE DD UM 2558 V 1 0 00 27 Figure 12 Field Wiring Diagram D1 D2 Two wire detectors Initiating Device Circuit Bd1 Bd2 Four wire detectors IDC s are 1 to 8 Class B StyleB C EOL End Of Line Resistor End of Line 3K9 1 2W NAC Notification Alarm Circuit PN RE3K9 RE Monitor Note For Syncronised ANSI Pattern Output External Synchronising Module to be used Refer manual for Compatible Devices RE DD UM 2558 Vino Id CD 01 vote Relay 3 Potentia
37. ice may fail to alert people with a disability or those who have recently consumed drugs alcohol or medication 2 RE DD UM 2558 V 1 0 00 Please note that e Strobes can under certain circumstances cause seizures in people with conditions such as epilepsy e Studies have shown that certain people even when they hear a fire alarm signal do not respond or comprehend the meaning of the signal It is the property owners responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals n rare instances the sounding of a warning device can cause temporary or permanent hearing loss A fire alarm system will not operate without any electrical power If AC power fails the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly Equipment used in the system may not be technically compatible with the control It is essential to use only equipment listed for service with your control panel The most common cause of fire alarm malfunction is inadequate maintenance To keep the entire fire alarm system in excellent working order ongoing maintenance is required per the manufacturers recommendations and UL and NFPA standards At a minimum the requirements of NFPA 72 shall be followed Environments with large amounts of dust dirt or high air veloci
38. l Relays Note For Fire Fault Supervisory Power GAN the field wiring circuits are Fault Limited outputs supervised Relay NO Contact Rating i ircuits 204 30VDC GAII the field wiring circuits are Power E 2 04 30VAC limited except 110 220v A C and Passen DS Power Factor 0 6 Relay m AC Input ul E 28 RE DD UM 2558 V 1 0 00 Figure 13 Mounting OF RE Monitor a ES al O O E E 2 E amp E S e e 3 e u Ee AA U AT T L 15mm gt lt BD rn 15 mm Figure 14 RE DD UM 2558 V 1 0 00 29 Figure 15 3 4 Initiating Device Circuit v v No of Initiating circuit 4 Zone for RE 2554 8 Zone for RE 2558 Type Class B Style B C Programmable Wire Size 1 5sq mm Max Operating Voltage 14 21 VDC Nominal Max Terminal CN8 Loop Resistance 100 O Max Total No of Devices 20 Monitoring Device 3K9 EOL Refer Chapter 9 Compatible Devices Refer Chapter 9 All zones may be configured for general fire alarm applications or supervisory alarm zones Four wire smoke detectors may be connected to any zone Resettable power is provided via CN7 Note a Only smoke detectors can be connected in the zone with alarm verification b Only Same model detectors should be used in IDC C Manual Pull Station should not be used in the style C mode Warning This unit includes an Alarm Verification Feature that will result
39. l be as pulse as shown below In these modes all the Sounders will be evacuated simultaneously 42 RE DD UM 2558 V 1 0 00 To change the option press Change key to toggle between the options Steady Temporal Synchronized The NAC s should be in off condition to change the options TEMPORAL OUTPUT STEADY OUTPUT A Soc 1 Le SYNCHRONIZED OUTPUT 2 13 4 2 12 NAC2 Output The NAC2 output can be configured as steady Temporal Synchronized In Temporal and synchronize mode the NAC2 Output wil be as pulse as shown below In these modes all the Sounders will be evacuated simultaneously To change the option press Change key to toggle between the options Steady Temporal Synchronized The NAC s should be in off condition to change the options 4 2 13 24V Output The 24V output can be configured as Resettable or steady If four wire detectors are used in the panel then the 24V DC output should be configured as Resettable While resetting the panel this output will cut off for the 3 seconds The default setting is Resettable Output In this mode screen display as below 14 24V Output Resettable To change the option press Change key to toggle between the options Steady and resettable 43 RE DD UM 2558 V 1 0 00 4 2 14 Change User Password From the Change User Password Mode screen By pressing the enter key from ihe change user Password screen system enters into the user Password chan
40. mponents circuits system operations or software functions known to be affected by a change must be 100 tested In addition to ensure that other operations are not inadvertently affected at least 10 of initiating devices that are not directly affected by the change up to a maximum of 50 devices must also be tested and proper system operation verified This system meets NFPA requirements for indoor dry operation at 0 49 C 32 120 F and at a relative humidity of 93 2 RH non condensing at 32 2 C 90 t3 F However the useful life of the system s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity Therefore it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 0 49 C 32 120 F 22 RE DD UM 2558 V 1 0 00 Verify that wire sizes are adequate for all IDC s loops Most devices cannot tolerate more than a 1076 I R drop from the specified device voltage Adherence to the following will aid in problem free installation with long term reliability Like all solid state electronic devices this system may operate erratically or can be damaged when subjected to lightning induced transients Although no system is completely immune from lightning transients and interferences proper grounding will reduce susceptibility Overhead or outside aerial wiring is not recommended due to an increased sus
41. nabled disabled option 7 Auto Silence Disabled In auto silence is enabled condition to change the time press enter key and use left right key to increase decrease the timing 40 RE DD UM 2558 V 1 0 00 4 2 8 4 2 9 The Auto silence timing can be set from 001 to 999 seconds After setting the required time press Enter key to accept the time The default time set is 120 Seconds When you enter into this mode the screen will be as below 7 Auto Silence 120 Sec Silence Inhibit The Silence Inhibit feature prevents the silencing of Notification Appliance Circuits using the Silence switch or Reset switch for the amount of time corresponding to the selected option after the NAC s are activated The factory default for this feature is disabled Press Change key to toggle between enabled disabled option 8 Silence Inhibit Disabled In silence Inhibit is enabled condition to change the time press enter key and use left right key to increase decrease the timing The Silence inhibit timing can set 1 to 999 seconds After setting the required time press Enter key to accept the time The default time is 60 Seconds When you enter into this mode the screen will be as below 8 Silence Inhibit 060 Sec AC Loss Delay When AC power is lost the control panel trouble relay will activate The factory default option for this feature is Enabled the trouble relay activation on AC
42. otective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired 6 RE DD UM 2558 V 1 0 00 Table of Contents CHAPTER 1 kitroductioh rere eot enen e 1 1 System Design amp Planning 9 RE dll omis sivo idea eti De Ao De ooa et au scd 9 1 3 Fire Alarm Procedure sss esse e 10 1 4 User Responsibility seeee eese 10 1 5 ROUNE TOS Lua dues ofa xot ird rd CHAPTER 2 Product Description eee eeel 2 1 gt Prod ctFeat reS n pad aieo DP EDU T 13 2 2 SPECHIGAU OL EEN 15 2 3 Controls and n elle e EE 16 2 9 T COnIEolS eoa enim at Dae L lt 2 3 2 SAA uec eSa SEE waa 17 209 2 LED Indicato Nns assu deuten Exc e fae bate dett 17 2 9 22 LCD Indication us utet hee op ve voted tas 18 2 3 2 3 Local BUZZER AA setae Sce Nee x toe wed uud 18 2 4 Mechanical Construction ss ee eee errre 18 2 5 Internal Arrangement AA 19 2 6 Components ir 20 CHAPTER 3 IS tallatiOn sss ss se sees resse ec eoo io onu eZ 3 1 Installation Precaution e cece e eee eee eee ee eens 22 3 2 Mounting Details obs ad cei ut deta 24 CR ln e DEE 25 3 4 Initiating Device Crcufs sense 30 9 5 QUIPUL eiee nal 31 3 5 1 Notification Appliance Circuit eee eee eee eee ees 31 3 5 2 24V Output Ls eani eege 32 3 6 Standard Relay Oumput ss eee 33 CHAPTER 4 Programming Instructions
43. panels com Email marketingOravelfirepanels com 65 RE DD UM 2558 V 1 0 00
44. relay output disablement is activated automatically and it will go back to previous status while we are coming out from this mode For other zones that are not in walk test mode if they sense any fire then the panel will go to normal alarm mode and walk test zone changed to alarm mode automatically 37 RE DD UM 2558 V 1 0 00 This feature helps to perform the testing of devices by a single person In this mode if the zone detects any fire then after 4 seconds the panel wil get automatically silenced After 2 seconds of silence the zone will go to reset This mode is represented as W at the time of setting Notel If there is no more testing please ensure that the zone is brought back to the normal Condition To bring back the zone loop to normal condition same procedure is followed as for the test If the zone is kept in Walk test mode for 10 minutes with out any test the panel comes out of the walk test mode automatically During test condition that the other zones that are not in test mode fire will consider as actual fire Not e2 The supervisory mode is selected only in Admin level And mode changing from supervisory to fire mode is also under admin level After changing the mode should press the ENTER key Otherwise the change will not accept Avoid disabling any particular zone unless it is giving any false alam Fault Condition Reworking For zone disabling and their normalization use same procedure as
45. rst fire zone and total no of zone is displayed separately ZONE SUPERVISORY The zone supervisory LED is illumination indicates that the particular Zone is selected as Supervisory zone Contact Zone During supervisory fault condition the same LED starts blinking ZONE FAULT This fault LED will glow when there is an open or short or earth fault in that particular zone ZONE DISABLE W T This zone wise LED glows steadily in disabled condition and blinking in the Walk test mode 49 RE DD UM 2558 V 1 0 00 5 3 5 3 1 5 32 Operation Normal Monitoring Mode Normal Mode is the standard mode of operation In this mode the panel continuously monitors system status When no fire or supervisory or trouble conditions exist all LEDs will be off except the System On LED The Notification Appliance Circuits will be off all relays are in their normal state and the onboard buzzer will be off When the system is in normal condition the LCD screen will be as below FIRE ALARM SYSTEM HEALTHY Fire Alarm Condition When the control panel detects Fire via the Detector MCP the panel will cause the following Y The corresponding ZONE FIRE red LED will blink Y The common twin Fire LEDs wil glow Y Turn on the NAC s Y Turn on the panel buzzer with continuous tone Y Turn on the fire relay The LCD screen will be as below Fre XX Y Y Zone X In case of multiple zone fire the origin zone fire LED will be blinking
46. s while we are coming out from this mode For other zones that are not in test condition if they sense any fire then the Fire relay output will activate by considering it as actual fire This feature helps to perform the testing of devices by a single person In this mode if the panel detects any fire then after 4 seconds the panel will get automatically silenced After 2 seconds of silence the panel will go to reset This reset is done for only that particular zone Once in Walktest Mode the control panel will immediately Turn on the Notification Appliance Circuits for 4 seconds for the alarm on a zone if an audible walktest is performed For a silenced walktest mode all NAC outputs remain off Disable the fire relay e Display all alarm conditions as they occur 58 RE DD UM 2558 V 1 0 00 Display all zone troubles as they occur Display all system troubles as they occur Note 1 If any one zone is in walktest then other zones will operate normal condition 2 The actual alarm zone cannot be selected for walktest mode 3 By Reset the panel using the reset key then walktest selected zone goes to fire mode 6 4 System Power Power Current Max AH Derating Max Max Max Max Capacity Factor standby Alarm standby alarm current current time duration Priomary power 2 5A N A N A 0 04A 0 4A N A N A supply Secondary back up 23A 12Ah 10 0 4A 2 3A 24 Hrs 5 Min
47. se Enter Key to gt Model RE 2558 Mode Ty pe Version 1 0 Note 1 Use Cursor key lt gt to move the menu list and to interchange the status of the menu 2 Use Enter Key 4 to select the menu list and conform the change of the status Figure 21 35 RE DD UM 2558 V 1 0 00 4 2 Programming 4 2 1 The MENU key is used to enter into the programming mode for changing the zone details and other settings The various steps involved in this menu are shown as flow chart 4 1 After entering into the To menu screen will show the first menu as below 1 Set Zone Mode move the other next menu use the left right cursor key and press the enter key to change the settings The programmable menu list is as follows ONDARRUN 9 10 11 12 13 14 15 16 Set Zone Mode Suppressed Fault Events Suppressed Supervisory Events Zone Wiring Supervisory Mode Walk Test Auto Silence Silence Inhibit AC Loss Delay Trouble Remainder NACI Output NAC2 Output 24V Output Change User Password Change Admin Password About Set Zone Mode From the Set Zone Mode program screen By pressing the Enter mode key the system enters into the zone set mode In this the zone mode can be changed to supervisory fire walktest and disable mode After entering the zone mode screen will be as below 36 RE DD UM 2558 V 1 0 00 Y F S A W Dmode F Fire S
48. tion The Style of class B can be changed as Style B or Style C by pressing Change key from the panel key pad When you enter into this mode the screen will be as below 4 Zone Wiring Class B Style C 39 RE DD UM 2558 V 1 0 00 4 2 5 4 2 6 4 2 7 Supervisory Mode From the Supervisory Mode program screen The supervisory zones can be selected as resettable latching mode Press Change to toggle between options A supervisory zone programmed for latching requires manual reset to restore after the supervisory alarm is cleared A supervisory zone programmed for resettable will be automatically restored after the supervisory alarm is cleared 5 Superv sry Mde Resettable Walk Test In this mode the NAC s can programmed as Audible Silenced by using the key Change in this sceen For an audible walktest the panel detects any fire then after 4 seconds the panel will get automatically silenced After 2 seconds the panel will go to reset This reset is done for only that particular zone For an silenced walktest the panel will not activate the NAC s but buzzer tone is activated 6 Walk Test Audible Auto Silence Auto silence is the program feature that will automatically silence the Notification Appliance Circuits if they are programmed as silenceable circuits after a programmed time interval The factory default setting is auto silence disabled Press change key to toggle between e
49. ty require more frequent maintenance A maintenance agreement should be arranged through the local manufacturers representative Maintenance should be scheduled monthly or as required by National and or local fire codes and should be performed by authorized professional fire alarm installers only Adequate written records of all inspections should be kept 3 RE DD UM 2558 V 1 0 00 NOTES 4 RE DD UM 2558 V 1 0 00 RE DD UM 2558 V 1 0 00 It is imperative that the installer understands the requirements of the Authority Having Jurisdiction AHJ and be familiar with the standards set forth by the following regulatory agencies s Underwriters Laboratories Standards e NFPA 72 National Fire Alarm Code NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems Underwriters Laboratories Documents for Reference UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors Single and Multiple Station UL 228 Door Closers Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Pr
Download Pdf Manuals
Related Search
Related Contents
chèque transport : mode d`emploi - Région Ile-de 取扱説明書 型式 AET-Gー 3N TAXE DE SÉJOUR AU RÉEL MODE D`EMPLOI AppRadio - Autosound Philips AW 7250/00S User's Manual PC CHIPS A51G (V7.1) hyoushi no,7scan.xdw Copyright © All rights reserved.
Failed to retrieve file