LS Drive Series iG5A Catalog

image

Contents

1. Displayed when a fault condition occurs in the drive cooling fan Used for the emergency stop of the drive The drive instantly turns off the output when the EST terminal is turned on Caution The drive starts to regular operation when turning off the EST terminal while FX or RX terminal is ON When multi function input terminal 120 124 is set to 19 External fault signal input A Normal Open Contact the drive turns off the output When multi function input terminal 120 124 is set to 19 External fault signal input B Normal Close Contact the drive turns off the output When drive operation is set via analog input 0 10V or 0 20mA input or option RS 485 and no signal is applied operation is done according to the method set in 162 Operating method when the frequency reference is lost Fault Remedy a Z Z ER U a E n pl me ca Wal a EN pl Ges wt TI Ca Gs D L o I Keypad display me me fr fr lt Ca d Ca Gei D Ca Ca Ca za Ca fr r Daad a em Overcurrent Ground fault current Drive overload Overload trip Heat sink overheat Output Phase loss Cooling fan fault Over voltage Low voltage Electronic thermal External fault A contact input External fault B contact input Operating method when the freguency command is lost R
2. eee ren Ray Sea To B2 Vv R S T wire U V W wire Ground wire Terminal Screw Torgue mm AWG mm AWG mm AWG Screw Size kgf cm Ib in SVOOOJIGSA 1 2 14 2 14 3 5 12 M3 5 10 8 7 SV0008iG5A 1 2 14 2 14 3 5 12 M3 5 10 8 7 SV0015iG5A 1 2 14 2 14 3 5 12 M4 15 13 SV0004iG5A 2 2 14 2 14 3 5 12 M3 5 10 8 7 SVOOOBIGSA 2 2 14 2 14 3 5 12 M3 5 10 8 7 SV0015iG5A 2 2 14 2 14 3 5 12 M3 5 10 8 7 SV0022iG5A 2 2 14 2 14 3 5 12 M4 15 13 SV0037iG5A 2 3 5 12 3 5 12 3 5 12 M4 15 13 SV0040iG5A 2 3 5 12 3 5 12 3 5 12 M4 15 13 SV0055iG5A 2 5 5 10 515 10 55 10 M5 32 28 SV0075iG5A 2 8 8 8 8 5 5 10 M5 32 28 SV0110iG5A 2 14 6 14 6 14 6 M6 30 7 26 6 SV0150iG5A 2 22 4 22 4 14 6 M6 30 7 26 6 SV0185iG5A 2 30 2 30 2 22 4 M8 30 5 26 5 SV0220iG5A 2 38 2 30 2 22 4 M8 30 5 26 5 SV0004iG5A 4 2 14 2 14 2 14 M3 5 10 8 7 SVOOOBIGSA 4 2 14 2 14 2 14 M3 5 10 8 7 SV0015iG5A 4 2 14 2 14 2 14 M4 15 13 SV0022iG5A 4 2 14 2 14 2 14 M4 15 13 SV0037iG5A 4 2 14 2 14 2 14 M4 15 13 SV0040IG5A 4 2 14 2 14 2 14 M4 15 13 SV0055iG5A 4 3 5 12 2 14 3 5 12 M5 32 28 SV0075iG5A 4 3 5 12 3 5 12 3 5 12 M5 32 28 SV0110iG5A 4 5 5 10 5 5 10 8 M5 30 7 26 6 SV0150iG5A 4 14 6 8 M5 30 7 26 6 SV0185iG5A 4 14 6 8 8 14 6 M6 30 5 26 5 SV0220iG5A 4 22 4 14 6 14 6 M6 30 5 26 5 Drive Starvert iG5A Series 13 Terminal Configuration Control terminal specifications 41121212 131812 81812 1718181919 La Specification Output voltage 12V Max output current 100mA Potentiometer 1
3. During Decel During constant run During Accel Bit 2 Bit 1 Bit 0 0 1 NA 2 NA SM Es v 4 Iv 5 Is VA 6 Ba 7 x NA NA This parameter sets the amount of current to activate stall prevention function during Accel Constant or Decel run The set value is the percentage of the H33 Motor rated current In Stall prevention run during deceleration if you want to limit output voltage select 1 This parameter decides whether to save the specified frequency during up down operation When 1 is selected the up down frequency is saved in F64 If Save up down frequency is selected at F63 this parameter saves the frequency before the drive stops or decelerated We can select up down mode among three thing Increases goal frequency as a standard of Max freguency Min frequency 1 Increases as many as step frequency according to edge input 2 Available to combine 1 and 2 In case of choosing F65 as a 1 or 2 it means increase or decrease of frequency according to up down input 0 Drive doesn t run as a draw mode 1 V1 0 10V input draw run 2 1 0 20mA input draw run 3 V1 10 10V input draw run Sets rate of draw Factory Adj defaults during run 1 0 180 0 60 0 0 X 150 X 0 X 0 00 X 0 X 0 00 X 0 X 0 00 0 Drive Starvert iG5A Series 29 Function group 2 LED display communication HO H1 H2 H3 H4 H5 H6 H7 H8 H10 H11 H12 H13 H14 H15
4. H57 H58 H60 H61 2 H62 H63 H64 H65 H66 H67 H70 Address for display communication A332 A333 A334 A335 A336 A337 A338 A339 A33A A33C A33D A33E A33F A340 A341 A342 A343 A346 Parameter name PID F B select P gain for PID Integral time for PID Differential time for PID D gain PID control mode select PID output frequency high limit PID output frequency low limit PID standard value select PID control unit select Self diagnostic select Sleep delay time Sleep frequency Wake up level KEB drive select KEB action start level KEB action stop level KEB action gain Frequency Reference for Accel Decel 1 Set H49 to 1 PID control to display this parameter 2 Set H49 as a 1 Min Max range 0 1 O 999 9 0 1 32 0 sec 0 30 0 sec 0 1 0 1 400 Hz 0 1 400 Hz 0 4 0 1 0 2000 s 0 400 Hz 0 100 0 1 110 140 Ka 110 145 Ka 120000 0 1 Description 0 Terminal input 0 20 mA Compact amp Powerful Drive iG5A Factory Adj defaults during run i 0 X 1 Terminal V1 input 0 10 V 300 0 O This parameter sets the gains for the PID controller 1 0 O 0 0 O Selects PID control mode 0 Normal PID control 0 X 1 Process PID control This parameter limits the amount of the output frequency through 60 00 9 the PID control The
5. Compact amp Powerful Drive IGA LSS Drive STARVERT iG5A LS Starvert iG5A is very competitive in its price and shows an upgraded functional strength User friendly interface extended drive ranges up to 22kW superb torque competence and small size of iG5A provides an optimum use environment Gem MP GEERT mia saws User friendliness Lang t PERED EEG Ts gt Ce PS P 2 LSIS Co Ltd ans AAA mm D DD D Di D SO KEE EI j KN J Ba e A Sa s P M g f Pad Au e Contents Overview Model amp Type Standard Specifications Wiring Terminal Configurations Keypad Features Parameter Setting Trial Run l Dimensions Braking Resistors and Peripheral Devices Function List Protective Functions Fault Remedy 4 Powerful amp Upgraded Performance iGSA provides sensorless vector control PID control and ground fault protection through powerful built in functions Sensorless vector control Speed vs Torque Characteristics The built in sensorless vector control provides the superb speed control and powerful high torque Torque Ground fault protection during running The ground fault protection of output terminal is possible during running Condition Sensorless Vector Control Mi asing Measure main ode Auto tuning Meas torque 9 at each speed 1 5 10 20 30 40 50 60Hz Analog control
6. F11 F12 F13 F14 F20 F21 F22 F23 F24 F25 F26 F27 F28 F29 Address for A204 A208 A209 A20A A20B A20C A20D A20E A214 A215 A216 A217 A218 A219 A21A A21B A21C A21D Parameter name Stop mode select DC Brake start frequency DC Brake wait time DC Brake voltage DC Brake time DC Brake start voltage DC Brake start time Time for magnetizing a motor Jog frequency Max frequency Base frequency Start frequency Frequency high Now limit select Freguency high limit Freguency low limit Torgue Boost select Torgue boost in forward direction Torgue boost in reverse direction 1 Only displayed when F 4 is setto 1 DC brake to stop 2 If H40 is set to 3 Sensorless vector Max frequency is settable up to 300Hz 3 Only displayed when F24 Frequency high low limit select is set to 1 Min Max range 0 1 60 Hz 0 60 sec 0 200 0 60 sec 0 200 Ka 0 60 sec 0 60 sec 0 400 Hz 40 400 Hz 30 400 Hz 0 1 10 Hz 0 1 0 400 Hz 0 1 400 Hz 0 1 0 15 Compact amp Powerful Drive iG5A Description Z a O Decelerate to stop 1 DC brake to stop 0 x 2 Free run to stop 3 Power Braking stop This parameter sets DC brake start frequency Sen It cannot be set below F23 Start frequency When DC brake frequency is
7. 40 110 50 200 Ka 50 150 CH H 30 150 0 30 Sec 0 Linear 1 Square 2 User V F It is used only when V F pattern is set to 2 User V F It cannot be set above F21 Max frequency The value of voltage is set in percent of H70 Motor rated voltage The values of the lower numbered parameters cannot be set above those of higher numbered This parameter adjusts the amount of output voltage The set value is the percentage of input voltage This parameter decreases output voltage according to load status This parameter is activated when the motor is overheated time inverse This parameter sets max current capable of flowing to the motor continuously for 1 minute The set value is the percentage of H33 Motor rated current It cannot be set below F52 Electronic thermal level for continuous This parameter sets the amount of current to keep the motor running continuously It cannot be set higher than F51 Electronic thermal level for 1 minute Standard motor having cooling fan directly connected to the shaft 1 A motor using a separate motor to power a cooling fan This parameter sets the amount of current to issue an alarm signal at a relay or multi function output terminal see 154 155 The set value is the percentage of H33 Motor rated current This parameter issues an alarm signal when the current greater than F54 Overload warning level fl
8. India Tel 91 1244 930 077 Fax 91 1244 930 066 LSIS Moscow Office Russia 123610 Krasnopresnenskaya nab 12 building 1 office N21005 Moscow Russia Tel 7 495 258 1466 1467 Fax 7 495 258 1466 1467 e LSIS U K Office United Kingdom G17 Bedford I Lab Stannard Way Priory Business Park Bedford MK44 3RZ U K Tel 44 012 3483 4774 Fax 44 012 3483 4775 STARVERT iG5A E 2005 05 22 2014 06 Printed in Korea Pacomkorea
9. O P7 Middle 54 S W ma H Ge EE P1 Forward ok Q P2 Reverse CM 1 Please make sure that R S T are connected to 3 phase AC input and U V W are also motor connection terminals 2 After supplying the power please set the frequency of multi step among Low Middle and High 3 If P1 FX turns on the motor operates in forward And after turning off it stops according to the deceleration time 4 If P2 RX turns on the motor operates in reverse And after turning off it stops according to the deceleration time Parameter setting Step Command Code Description Default After change 1 Max frequency change FU1 F21 Change Max frequency 60Hz 80Hz 2 Multi step frequency DRV st1 Set Low step 10Hz 20Hz 3 Multi step frequency DRV st2 Set Middle step 20Hz 30Hz 4 Multi step frequency I O 130 Set High step 30Hz 80Hz 5 Forward run P1 FX 117 The default is FX This value may change FX FX 6 Reverse run P2 RX 118 The default is RX This value may change RX RX 18 LSIS Co Ltd Compact amp Powerful Drive iG5A Potentiometer Volume Run Stop via FX RX Accel Decel time change Operation condition Operation command Frequency command Accel Decel time Run Stop via FX RX 0 60Hz analog input via potentiometer Accel 10sec Decel 20sec Wiring Potentiometer 1 5kohm 1 2W TO OD va 3 phase V O vi AC input e O cm 0 60Hz 1 FX Forward 2 RX Reverse 1 Please
10. 5kohm Max input voltage 12V 12V input 0 20mA input Internal resistor 500ohm Max output voltage 11V Max output current 100mA Below DC 26V 100mA Max output current 100mA Wire size mm i 1 Terminal Description Screw size Torque Nm Single wire Stranded P1 P8 Multi function input T M 1 8 1 0 1 5 M2 6 0 4 CM Common terminal 1 0 1 5 M2 6 0 4 VR Power supply for external 10 15 M2 6 0 4 potentiometer Vi Input terminal for voltage operation 1 0 1 5 M2 6 0 4 l Input terminal for current operation 1 0 1 5 M2 6 0 4 AM Multi function analog output terminal 1 0 1 5 M2 6 0 4 MO Multi function terminal for open collector 1 0 1 5 M2 6 0 4 MG Ground terminal for external power supply 1 0 1 5 M2 6 0 4 AM 24V external power supply 10 SES M26 04 3A Multi function relay output A contact 1 0 1 5 M2 6 0 4 3B Multi function relay output B contact 1 0 1 5 M2 6 0 4 3C Common for multi function relays 1 0 1 5 M2 6 0 4 1 Use the recommended tightening torgue when securing terminal screws x When you use external power supply 24V for multi function input terminal P1 P8 apply voltage higher than 12V to activate x Tie the control wires more than 15cm away from the control terminals Otherwise it interferes front cover reinstallation Ma SELLAL LL Le bes bett 14 LSIS Co Ltd Below AC 250V 1A Below DC 30V 1A Keypad Features Display RUN STOP RESET A v KEY gt lt e FWD REV RUN S
11. BIT4 BIT3 BIT2 BIT1 BITO 125 A419 i O status display P8 Pi P6 P5 P4 P3 P2 P1 Output terminal BIT1 BITO 126 A41A Outp i 0 O status display 3AC MO Filtering time constant for If the value is set higher the responsiveness of the Input terminal 127 A41B A i 1 15 A 4 O Multi function is getting slower Input terminal Multi Ste 130 A41E j 30 00 O freguency 4 Multi Ste 131 AAF i step a 25 00 o requency 5 It cannot be set greater than F21 Max frequency Multi Ste Hz 132 A420 ane Hz 20 00 o frequency 6 Multi Ste 133 A421 T 15 00 o frequency 7 Multi Accel 134 A422 ee 3 0 o time 1 Multi Decel 0 6000 135 A423 Gees 3 0 time 1 sec Multi Accel 136 A424 ee 4 0 time 2 Drive Starvert iG5A Series 37 Function List Input output group LED Address for Parameter Min Max Descrintion Factory Adj display communication name range P defaults during run Multi Decel 137 A425 a SEH 4 0 time 2 Multi Accel 138 A426 5 0 time 3 Multi Decel 139 A427 5 0 time 3 Multi Accel 140 A428 6 0 time 4 Multi Decel 141 A429 annen 6 0 time 4 Multi Accel 0 6000 142 A42A 7 0 time 5 sec Multi Decel 143 A42B 7 0 time 5 Multi Accel 144 A42C Ls 8 0 time 6 Multi Decel 145 A42D La 8 0 time 6 Multi Accel 146 A42E eee 9 0 time 7 Multi Decel 147 A42F Weeen 9 0 time 7 A Output to 10 V Output item Su 200V 400V Analog output 0 Output freq Max frequenc 150 A432 poe 0 3 FE 0 o it
12. Decel time settable Basic function parameters to adjust output frequency and voltage Advanced function parameters to set parameters for such as PID Operation and second motor operation Parameters necessary to make up a sequence using multi function input output terminal as Moving to other groups Moving to other groups using the Right gt key 1 Tr E EEE i A q An L V Drive group mal 7 LI al M L kl 7 LI l FU group 2 Moving to other groups using the Left lt key 1 Target frequency can be set at 0 0 the 1st code of drive group Even though the preset value is 0 0 it is user settable The changed frequency will be displayed after it is changed 16 LSIS Co Ltd Compact amp Powerful Drive iG5A When changing ACC time from 5 0 sec to 16 0 sec Drive group nm 1 LI l G L i In the first code 0 00 press the Up A key once to go to the second code 2 arr e ACC Accel time is displayed Hhh Press the Ent e key once 3 En Preset value is 5 0 and the cursor is in the digit 0 al LA Press the Left key once to move the cursor to the left 4 d T The digit 5 in 5 0 is active Then press the Up 4 key once 5 E The value is increased to 6 0 ll Press the Left al key to move the cursor to the left 6 mEn 0 60 is displayed The first 0 in 0 60 is active Le 000 Press the Up 4 key once 16 0 is set 7 f nt Press the Ent e ke
13. H16 H17 H18 H19 H20 H21 Function List Address for A300 A301 A302 A303 A304 A305 A306 A307 A308 A30A A30B A30C A30D A30E A30F A310 A311 A312 A313 A314 A315 Parameter name Jump code Fault history 1 Fault history 2 Fault history 3 Fault history 4 Fault history 5 Reset fault history Dwell freguency Dwell time Skip frequency select Skip freguency low limit 1 Skip freguency high limit 1 Skip freguency low limit 2 Skip freguency high limit 2 Skip freguency low limit 3 Skip frequency high limit 3 S Curve accel decel start side S Curve accel decel end side Input output phase loss protection select Power On Start select Restart after fault reset selection Min Max range 0 95 0 1 400 Hz 0 10 sec 0 1 0 1 400 Hz 1 100 Ka 1 100 Ka Description ree Sets the code number to jump 1 nOn Stores information on the types of faults the frequency the nOn current and the Accel Decel condition at the time of fault The nOn latest fault is automatically stored in the H 1 Fault history 1 nOn nOn Clears the fault history saved in H 1 5 0 When run frequency is issued motor starts to accelerate after dwell frequency is applied to the motor during H8 Dwell time 5 00 Dwell frequency can be set within the range of F21 Max l frequency and F23 Start frequency Sets the t
14. Stop Trip 3 Reset when a fault occurs RST 4 Jog operation command 5 Multi Step freq Low 6 Multi Step freq Mid 7 Multi Step freq High See Chapter 14 Troubleshooting and maintenance for External trip A B contact Each multi function input terminal must be set differently 36 LSIS Co Ltd Factory defaults 1 0 00 0 00 10 0 60 00 10 0 00 10 60 00 10 4 00 0 00 20 00 60 00 Adj during run O 0 Compact amp Powerful Drive iG5A Input output group LED Address for Parameter Min Max Description Factory Adj display communication name range P defaults during run Multi function 8 Multi Accel Decel Low 121 A415 input terminal 4 O P5 define 9 Multi Accel Decel Mid Multi function 10 Multi Accel Decel High 122 A416 input terminal 5 O P6 define 11 DC brake during stop Multifunction 12 2nd motor select 123 A417 input terminal 6 0 P7 define 13 Reserved 14 Reserved 15 Frequency increase UP command Up down 0 27 16 Frequency decrease command DOWN 17 3 wire operation 18 External trip A Contact EtA 19 External trip B Contact EtB Multifunction 20 Self diagnostic function leg We input terminal 21 Change from PID operation to V F operation i S P8 define 22 2nd Source 28 Analog Hold 24 Accel Decel Disable 25 Up Down Save Freq Initialization 26 JOG FX 27 JOG RX Input terminal BIT7 BIT6 BIT5
15. Tech Industrial Development Area Wuxi214028 Jiangsu P T China el 86 510 8534 6666 8005 Fax 86 510 8534 4078 LS Hukai Electric Hubei Co Ltd Hubei China No 100 Tanjiahe Road Dianjun District Yichang City Hubei Province 443004 China el 86 717 667 7339 Fax 86 717 667 7559 e LS VINA Industrial Systems Co Ltd Hanoi Vietnam Nguyen Khe Dong Anh Hanoi Vietnam el 84 4 6275 8055 Fax 84 4 3882 0220 LSIS ME FZE Dubai U A E LOB 19 205 JAFZA View Tower Jebel Ali Free Zone Dubai United Arab Emirates el 971 4 886 5360 Fax 971 4 886 5361 e LSIS Europe B V Netherlands 1st Floor Tupolevlaan 48 1119NZ Schiphol Rijk The Netherlands el 31 20 654 1420 Fax 31 20 654 1429 e LSIS Japan Co Ltd Tokyo Japan fokyo Club Building 13F 2 6 Kasumigaseki 3 chome Chiyoda ku Tokyo 100 0013 el 81 3 6268 8241 Fax 81 3 6268 8240 e LSIS USA Inc _ Chicago U S A 2000 Millbrook Drive Lincolnshire Chicago IL 60069 United States el 847 941 8240 Fax 847 941 8259 Specifications in this catalog are subject to change without notice due to continuous product development and improvement 2015 01 Overseas Branches LSIS Shanghai Office China 32nd Floor International Corporate City No 3000 NorthZhongshan Road Putuo District Shanghai China 200063 Tel 86 21 5237 9977 Fax 86 21 5237 7189 e LSIS Beijing Office China Room 2306 Building B Landgent Center No 24 Mi
16. following can be monitored via vOL User display select 0 Output voltage V 1 Output power kW 2 Torque kgf m This parameter is used to change the motor rotating speed r 1 Exception Since SV004iG5A 2 SV004iG5A 4 is Natural convection type this code is hidden 34 LSIS Co Ltd Factory defaults 100 1 0 Adj during run O Compact amp Powerful Drive iG5A Function group 2 LED Address for Parameter Min Max DECIDON Factory Adj display communication name range P defaults during run nd t ue A351 E t 5 0 o Accel time 0 6000 2nd mot H82 A352 el sec 10 0 o Decel time and motor 30400 H83 A353 60 00 X base frequency Hz and motor H84 A354 WER 0 X V F pattern ias fake and motor forward E 7 torque boost 0 15 2Nd motor reverse H86 A356 A boost Pel This parameter actives when the selected terminal is ON after 5 X orque boos Sk 117 124 is set to 12 24 motor select H87 ne 2 motor stall 30 150 150 x prevention level and motor a H88 A358 Electronic thermal Pe 150 O level for 1 min 5 and motor H89 A359 Electronic 50 150 100 o thermal level for continuous and motor 0 1 100 H90 A35A 26 3 X rated current A Copy the parameters from drive and save them into remote H912 A35B Parameter read 0 1 BANG 0 x loader Copy the parameters from remote loader and save them into H92 A35C Parameter write 0 1 0 X drive This parameter is used to initialize pa
17. from 10V to 10V Inputting analog signals from 10V to 10V provides user friendly operation M Built in PID control The built in PID function enables to control flow rate oil pressure temperature etc without any extra controller Built in dynamic braking circuit The built in dynamic braking circuit minimizes deceleration time via braking resistors rm Time sie i Built in 485 communication mams The built in RS 485 communication supports remote control and monitoring between iG5A and other equipment IN Wide product range iG5A consists of the product range from 0 4 to 22KW LSIS Co Ltd MO MG 24 Pt 3 ar L x PS CM PS P7 PS VA VY mw wt v i e mm 4 D wd Wi JA lt ze HERR Compact amp Powerful Drive iG5A B Monitoring e Checking operation status Voltage Current Frequency etc e Checking modified parameters e Windows support Remote Control Convenient remote control to modify operation status Forward Reverse operation Frequency etc e Easy parameter setting e Available to control up to 31 Drives e RS 485 Modbus communication Connected to XGT panel STEE EI B Monitoring e Checking operation time e Automatic list up of trip record e Language support Korean English Chinese B Remote Control e Convenient remote control to modify operation status Forward Reverse operation Frequency etc e
18. make sure that R S T are connected to 3 phase AC input and U V W are also motor connection terminals 2 After supplying the power please set the frequency of multi step among Low Middle and High V CaN Potentiometer 3 If P1 FX turns on the motor operates in forward And after gt p 1 5kohm 1 2W turning off it stops according to the deceleration time CM 4 If P2 RX turns on the motor operates in reverse And after turning off it stops according to the deceleration time 5 Control the motor s speed via potentiometer Parameter setting Step Command Code Description Default Operation command 1 DRY group Drv Turn on off motor via terminal 1 FX RX 1 Analog input 2 DRV group Frq Change keypad command to analog voltage command 0 Keypad 1 3 Accel Decel time ACC Set Accel time to 10sec in ACC 5sec Accel DRV group dEC Set Decel time to 20sec in dEC 10sec Decel F 4 CH de 117 The default is FX This value may change FX 5 EN SH 118 The default is RX This value may change RX After change 1 FX RX 1 3 V1 0 10V 10sec Accel 20sec Decel FX RX Drive Starvert iG5A Series 19 Dimensions ss SVOOAIGSA 2 SVOOBIGSA 2 SVO04iG5A 4 SVOOBIGSA 4 W a mm inches SVOOJAIGSA 2 SV008IG5A 2 SV004IG5A 4 SV008IG5A 4 0 77 0 76 SVO15iG5A 2 SVO15iG5A 4 i 7 E H1 mm inches SV015IG5A 2 1 5 100 95 5
19. value is settable within the range of F21 Max frequency and F23 Start frequency 0 50 O Selects PID standard value Standard value is indicated in rEF of Drive group 0 Loader digital setting 1 1 Loader digital setting 2 0 X 2 V1 terminal setting 2 0 10V 3 I terminal setting 0 20mA 4 Setting as a RS 485 communication Selects a unit of the standard value or feedback amount 0 Frequency Hz 0 X 1 Percentage 0 Self diagnostic disabled 1 IGBT fault Ground fault 0 r 2 Output phase short amp open Ground fault 3 Ground fault This setting is unable when more than 11kW Sets a sleep delay time in PID drive 60 0 X Sets a sleep frequency when executing a sleep function in PID control drive 0 00 O You can t set more than Max frequency F21 Sets a wake up level in PID control drive 35 0 O Sets KEB drive 0 X Sets KEB action start level according to level 125 0 X Sets KEB action stop level according to level 130 0 X Sets KEB action gain 1000 X 0 Based on Max freq F21 0 X 1 Based on Delta freq 3 it is indicated when setting H64 KEB drive select as a 1 KEB does not operate when cut power after loading ting input about 10 Drive Starvert iG5A Series 33 Function List Function group 2 LED Address for Parameter Min Max display communication name range Accel Decel H71 A347 f 0 2 time scale H72 Power on A348 i 0 15 display Monitoring H73 A349 i 0 2 item select
20. 0 V Frequency 5 OR 1 4 Analog Terminal I 0 20 mA Frq2 A10F setting 0 7 A 0 X thod 2 5 Terminal V1 setting 1 Terminal m Se 6 Terminal V1 setting 2 Terminal 7 RS485 communication 8 Digital Volume 9 Setto Filed Bus Communication I If H58 is 0 it is expressed as a Hz unit PID control 0 400 Hz not che 2 If H58 is 1 it is expressed as a unit rEF A110 standard or 0 00 0 i In Hz unit you can t set Max frequency more than F21 value setting 0100 In unit 100 means Max frequency PID control It indicates a feedback amount in PID control Fbk 2 A111 feedback If H58 is 0 it is expressed as a Hz unit amount If H58 is 1 itis expressed as a unit 1 Only displayed when one of the Multi function input terminals 1 8 117 124 is set to 22 2 It is indicated when H49 PID control selection is 1 3 This function can be available with iG5A Communication Option Module Function group 1 LED Address for Parameter Min Max Description Factory Adj display communication name range P defaults during run FO A200 Jump code 0 71 Sets the parameter code number to jump 1 O Forward 0 Fwd and rev run enable F1 A201 Reverse run 0 2 1 Forward run disable 0 X disable 2 Reverse run disable F2 A202 Accel pattern 0 Linear 0 1 0 X F3 A203 Decel pattern 1 S curve 26 LSIS Co Ltd Function group 1 LED display communication F4 F8 F9 F10
21. 00 300 300 2 2 300 300 200 400 8 7 200 500 130 600 400V Series 5 5 120 700 85 1 000 149 90 1 000 60 1 200 11 0 60 1 400 40 2 000 15 0 45 2 000 30 2 400 18 5 35 2 400 20 3 600 22 0 30 2 800 20 3 600 1 The wattage is based on Enable Duty ED with continuous braking time 15sec Breakers Voltage Capacity Circuit Breaker MCCB Leakage Breaker ELCB Magnetic Contactor MC kW Model Rated Current A Model Rated Current A Model Rated Current A Model Rated Current A 0 4 5 15 5 MC 6a 9 Ki eg 0 75 ABS33c 10 UTE100 15 EBS33c 10 MC 9a MC 9b 11 1 5 15 15 15 MC 18a MC 18b 18 0 4 5 15 5 MC 6a 9 0 75 10 15 10 MC 9a MC 9b 11 1 5 15 15 15 MC 18a MC 18b 18 22 ABS33c 20 20 PE 20 MC 22b 22 3 7 30 UTE100 30 30 32 3 Phase 4 30 30 30 MC 32a 32 200V 5 5 ABS53c 50 50 EBS53c 50 MC 50a 55 7 5 ABS63c 60 60 EBS63c 60 MC 65a 65 11 100 90 100 MC 85a 85 15 ha 125 SE 125 EBS103c 125 MC 130a 130 18 5 150 150 150 MC 150a 150 0 4 3 15 5 7 0 75 5 15 5 Mee 7 1 5 10 15 10 MC 9a MC 9b 9 Se ABS33c d 15 EBS33c 10 MC 12a MC 12b 12 e ie 15 mc tea mcre 78 3 Phase 4 20 20 20 i 18 400V 55 30 wee 30 30 MC 22b 20 7 5 30 30 30 MC 32a 32 11 ABS53c 50 50 EBS53c 50 MC 50a 50 15 ABS63c 60 60 EBS63c 60 MC 65a 65 18 5 75 80 75 MC 75a 75 22 ABS103c 100 90 E 100 MC 85a 85 Note 1 The capacity of the MCCB should be 1 5 to 2 times the rated output current of the drive Drive Starvert iG5A Series 23 2 Use an MCCB keep the drive from faulting out instead of using o
22. 128 120 130 4 5 4 5 4 5 SV015IG5A 4 1 5 100 95 5 128 120 130 4 5 4 5 4 5 20 LSIS Co Ltd Compact amp Powerful Drive iG5A ss SVO22iG5A 2 SV037iG5A 2 SVO4OIGSA 2 SVO22iG5A 4 SVO37iG5A 4 SVO4OIGSA 4 W mm inches SV022IG5A 2 SV037IG5A 2 1 89 SV040IG5A 2 1 89 SV022IG5A 4 1 84 SV037IG5A 4 1 89 SV040IG5A 4 a SVOSSIGSA 2 SVO75iG5A 2 SVO55iG5A 4 SVO75iG5A 4 W mm inches SV055IG5A 2 SV075IG5A 2 SVO55IG5A 4 SV075IG5A 4 3 66 Drive Starvert iG5A Series 21 Dimensions ss SV110iG5A 2 SV150iG5A 2 SV110iG5A 4 SV150iG5A 4 mm inches 9 00 SV110iG5A 2 SV150iG5A 2 9 00 SV110iG5A 4 9 00 SV150iG5A 4 sa SVO185iG5A 2 SVO220iG5A 2 SV0185iG5A 4 SVO220iG5A 4 mm inches SV185iG5A 2 SV220iG5A 2 13 3 SV185iG5A 4 10 0 SV220iG5A 4 22 LSIS Co Ltd Compact amp Powerful Drive iG5A Braking Resistors and Peripheral Devices Braking resistors 3 100 braking 150 braking Voltage Drive Resistor 0 Watt Wi Resistor 0 Watt w 0 4 400 50 300 100 0 75 200 100 150 150 1 5 100 200 60 300 2 2 60 300 50 400 3 7 40 500 33 600 200V Series 5 5 30 700 20 800 7 5 20 1 000 15 1 200 11 0 15 1 400 10 2 400 15 0 11 2 000 8 2 400 18 5 9 2 400 5 3 600 22 0 8 2 800 5 3 600 0 4 1 800 50 1 200 100 0 75 900 100 600 150 1 5 450 2
23. ET LED Compact amp Powerful Drive iG5A Term Run key STOP RESET key Up key Down key Right key Left key Enter key Forward run Reverse run Run key Setting 1 4 LEDs above are set to blink when a fault occurs se Dimensions Description Run command STOP Stop command during operation RESET Reset command when a fault occurs Used to scroll through codes or increase parameter value Used to scroll through codes or decrease parameter value Used to jump to other parameter groups or move a cursor to the right to change the parameter value Used to jump to other parameter groups or move a cursor to the left to change the parameter value Used to set the parameter value or save the changed parameter value Lit during forward run Lit during reverse run Lit during operation Lit during parameter setting 34 65 6 Ing 23 1 Drive Starvert iG5A Series 15 Moving to Other Groups Parameter groups There are 4 different parameter groups in iG5A series as shown below Parameter group Drive group Function group 1 Function group 2 I O Input Output group Drive group FU group 1 E m i LI S e S T E ri LI I O group LI 1 I 7 EI i IL i 23 E D D Description Basic parameters necessary for the drive to run Parameters such as Target frequency Accel
24. Easy parameter setting e Available to control up to 31 Drives e RS 485 Modbus communication mmm Drive Starvert iG5A Series 5 User friendly Interface amp Easy Maintenance The parameter setting becomes easier by adopting the 4 directions key And iG5A supports easy maintenance via diagnosis and fan changeable structure Diagnosis of output module Through easy parameter setting iG5A can diagnose the status of output module Easy change of fan IGSA is designed to be the fan changeable structure in preparation for a fan breakdown 180 gt M Cooling fan control By controlling the cooling fan iG5A provides a virtually guiet environment according to the status of operation i User friendly interface The 4 directions key provides easy handling and monitoring IN External loader Optional The external loader away from a panel enables to control and monitor conveniently And the parameters made by external loader can be copied and applicable to other Drives Model name Remarks INV REMOTE KPD 2M SV iG5A 2m INV REMOTE KPD 3M SV iG5A 3m INV REMOTE KPD 5M SV iG5A 5m 6 LSIS Co Ltd Compact amp Powerful Drive iG5A Compact Size The compact size achieves cost efficiency and various applications Same height from 0 4 to 4 0kW 128mm Global standard compliance CE UL Global standard IGSA series complies with CE and UL standards PNP NPN input Bo
25. Gain for Motor 1 1000 STR E rpm display min to mechanical speed m mi and display it DB resistor 0 Unlimited H75 A34B operating rate 0 1 limit select 1 Use DB resistor for the H76 set time H76 Zem DB resistor 0 30 Setthe percent of DB resistor operating rate to be activated operating rate during one sequence of operation 0 Always ON Cooling fan Keeps ON when its temp is higher than drive protection H770 A34D 0 s sg E control 1 limit temp Activated only during operation when its temp is below that of drive protection limit ER 0 Continuous operation when cooling fan malfunctions method select H78 A34E h ina f 0 1 EE Ing an 1 Operation stopped when cooling fan malfunctions malfunctions H79 A34F S W version 0 10 0 This parameter displays the drive software version Description 0 Settable unit 0 01 second 1 Settable unit 0 1 second 2 Settable unit 1 second This parameter selects the parameter to be displayed on the keypad when the input power is first applied 0 Frequency command Accel time Decel time Drive mode Freguency mode Multi Step freguency 1 Multi Step freguency 2 Multi Step freguency 3 Output current Motor rpm 10 Drive DC link voltage 11 User display select H73 12 Fault display 13 Direction of motor rotation select 14 Output current 2 15 Motor rpm 2 16 Drive DC link voltage 2 17 User display select 2 OO Jo Oo WN One of the
26. XT HWT etc This parameter sets the time between restart tries 1 0 0 0 2 0 2kW 75 x 22 0 22 0kW This setting is displayed via rPM in drive group 4 X 1 Normal acceleration has first priority Even though 4 is selected along with other bits Drive performs Speed search 4 2 H30 is preset based on drive rating Drive Starvert iG5A Series 31 Function List Function group 2 LED Address for Parameter Min Max display communication name range Rated slip 0 10 H32 A820 frequency Hz Motor rated 0 5 150 H33 A321 current A H34 A322 No Load Motor 0 1 50 Current A 50 100 H36 A324 Motor efficiency 24 H37 A325 Load inertia rate 0 2 Carrier H39 A327 frequenc Je task kHz select Control mode H40 A328 0 3 select H41 A329 Auto tuning 0 1 Stator resistance 0 28 H42 A32A Rs 2 Leakage O 300 0 H44 A32C A g inductance Lo mH Sensorless He A32D alie P gain 0 32767 Sensorless H46 A32E I gain Sensorless 100 220 H47 A32F m torque limit PWM mode H48 A330 0 1 select H49 A331 PID select 0 1 1 H32 H36 factory default values are set based on OTIS LG motor 2 Set H40 to 3 Sensorless vector control to display this parameter 32 LSIS Co Ltd Description rpm X p 120 Where fs Rated slip frequency fr Rated frequency rpm Motor nameplate RPM p Number of Motor poles EI Enter motor rated current on the nameplate Enter th
27. as been operated at low speed for too long D The terminal set to 18 External fault A or 19 External fault B in 120 124 in I O group is ON No frequency command is applied to V1 and I Communication error between drive keypad and remote keypad EEP Parameter save error HWT Hardware fault Err Communication Error COM Keypad error Increase the Accel Decel time Replace the drive with appropriate capacity Resume operation after stopping the motor or use H22 Speed search Check output wiring Check the mechanical brake l Check the wiring of the output terminal Replace the motor Upgrade the capacity of motor and drive or reduce the load weight Reduce torgue boost scale Check for alien substances clogged in the heat sink Replace the old cooling fan with a new one Keep ambient temperature under 50 C gt gt Make connection of magnetic switch at output of the drive securely Check output wiring Check the ventilating slot and remove the clogged substances Replace the cooling fan Increase the Decel time Use Dynamic Brake Unit Check whether line voltage exceeds its rating Check whether line voltage is below its rating Check the incoming AC line Adjust the line capacity corresponding to the load Change a magnetic switch Reduce load weight and operating duty Change drive with high
28. ction List ss Drive Group LED display communication 0 00 ACC dEC drv Frq Sti St2 St3 CUr rPM dCL vOL 1 This function can be available with iG5A Communication Option Module Address for A100 A101 A102 A103 A104 A105 A106 A107 A108 A109 A10A A10B Parameter name Frequency command Accel time Decel time Drive mode Frequency setting method Multi Step freguency 1 Multi Step freguency 2 Multi Step freguency 3 Output current Motor RPM Drive DC link voltage User display select Min Max range O 400 Hz 0 6000 Sec O 400 Hz Compact amp Powerful Drive iG5A Factory Adj Description defaults during run This parameter sets the frequency that the drive is commanded to output During Stop Frequency Command During Run Output Frequency 0 00 O During Multi step operation Multi step frequency 0 It cannot be set greater than F21 Max frequency e A A 5 0 O During Multi Accel Decel operation this parameter serves as Accel Decel time 0 100 o 0 Run Stop via Run Stop key on the keypad FX Motor forward run RX Motor reverse run FX Run Stop enable 1 X RX Reverse rotation select RS485 communication Set to Field Bus communication Keypad setting 1 Keypad setting 2 V1 1 10 10 V V1 2 0 gt 10 V Analog Terminal I 0 20 mA Terminal V1 setting 1 Terminal Terminal V1 s
29. ddle Road East 3rd Ring Road Chaoyang District Beijing P R China Tel 86 10 5761 3127 Fax 86 10 5761 3128 LSIS Guangzhou Office China Room 1818 1820 Xinyuan Building NO 898 Tianhe North Road Tianhe District Guangzhou P R China Tel 86 20 8326 6784 Fax 86 20 8326 6287 LSIS Qingdao Office China Room 2001 Galaxy Building 29 ShanDong Road ShiNan District QingDao ShanDong P R China Tel 86 532 8501 6058 Fax 86 532 8501 6057 LSIS Chengdu Office China Room1710 17 F Huamin Empire Plaza NO 1 Fuxin Road Chengdu P R China Tel 86 28 8670 3200 Fax 86 28 8670 3203 e LSIS ShenYang Office China Room 803 Hongyuan Building 52 South Nanjing Road Heping District Shenyang P R China Tel 86 24 2321 9050 Fax 86 24 8386 7210 e LSIS Jinan Office China Room 317 Chuangzhan Center No 201 Shanda Road Lixia District Jinan Shandong P R China Tel 86 531 8699 7826 Fax 86 531 8697 7628 e LSIS Co Ltd Tokyo Office Japan Tokyo Club Building 13F 2 6 Kasumigaseki 3 chome Chiyoda ku Tokyo 100 0013 Tel 81 3 6268 8241 Fax 81 3 6268 8240 e LSIS Co Ltd Rep Office Vietnam Gema Dept Tower 18F 6 Le Thanh Ton District 1 HCM Vietnam Tel 84 8 3823 7890 e LSIS Detroit Office U S A 5700 Crooks Rd Suite 211 Troy MI 48098 USA Tel 1 248 792 2637 8 Fax 1 248 792 2642 e LSIS Co Ltd India Office India 109 First Floor Park Central Sector 30 Gurgaon 122 002 Haryana
30. during speed search Number of Auto H26 A31A Restart try Auto Restart H27 A31B i time Mot H30 A31E otor ype select Number of H31 A31F motor poles Min Max range 0 15 80 200 0 9999 0 9999 0 10 0 60 sec 0 2 22 0 2 12 Compact amp Powerful Drive iG5A Description Z erik This parameter is active to prevent any possible fault when the 0 O drive outputs its voltage to the running motor 1 H20 2 Restart 3 Operation 4 Normal Power afterinstant after fault accel On start power failure 0 l e 3 E 1 l i 2 i 3 E NA NA 4 NA 1 H20 2 Restart 8 Operation 4 Normal Power after instant after fault accel On start power failure Bit 3 Bit 2 Bit 1 Bit 0 5 NA NA 6 NA NA 7 N NA NA 8 Iv E i 9 v i 10 i NA IEN NA Ba 12 NA 5 13 Ww NA S Ba 14 we NA NA 15 we NA NA i This parameter limits the amount of current during speed search 100 o The set value is the percentage of the H33 Motor rated current It is the Proportional gain used for Speed Search PI controller 100 O It is the Integral gain used for Speed search PI controller 200 O This parameter sets the number of restart tries after a fault occurs Auto Restart is deactivated if the fault outnumbers the restart tries This function is active when drv is set to 1 or 2 0 O Run Stop via control terminal Deactivated during active protection function OHT LVT E
31. e current value detected when the motor is rotating in rated rpm after the load connected to the motor shaft is removed Enter the 50 of the rated current value when it is difficult to measure H34 No Load Motor Current Enter the motor efficiency see motor nameplate Select one of the following according to motor inertia 0 Less than 10 times 1 About 10 times 2 More than 10 times This parameter affects the audible sound of the motor noise emission from the drive drive temp and leakage current If the set value is higher the drive sound is quieter but the noise from the drive and leakage current will become greater 0 Volts frequency Control 1 Slip compensation control 3 Sensorless vector control If this parameter is set to 1 it automatically measures parameters of the H42 and H44 This is the value of the motor stator resistance This is leakage inductance of the stator and rotor of the motor P gain for Sensorless control gain for Sensorless control Limits output torque in sensorless mode If you want to limit a drive leakage current select 2 phase PWM mode It has more noise in comparison to Normal PWM mode 0 Normal PWM mode 1 2 phase PWM mode Selects whether using PID control or not Factory Adj defaults during run 2 33 x 26 3 x 11 x 87 x 0 x 3 o 0 x 0 x x E x 1000 o 100 o 180 0 x 0 x 0 x Function group 2 LED H50 H51 H52 H53 H54 H55 H56
32. em select 1 Output current 150 2 Output voltage AC 282V AC 564V 3 Drive DC link voltage DC 400V DC 800V Anal tput 10 200 Based on 10V 151 A433 eerste ee 100 o level adjustment F 01415 am o 0 400 Used when 154 or 155 is set to 0 4 Cannot be set higher than F21 153 Frequency Hz 10 00 O A435 detection bandwidth 0 FDT 1 12 154 Multi function 1 FDT 2 A436 output terminal 2 FDT 3 select 3 FDT 4 4 FDT 5 5 648 5 Overload OLt 155 i 6 Drive Overload IOLt 17 Multi function A437 7 Motor stall STALL relay select A 8 Over voltage trip Ovt 9 Low voltage trip Lvt 38 LSIS Co Ltd Input output group LED 155 156 157 159 160 161 162 Address for display communication A437 A438 A439 A43B A43C A43D A43E Parameter name Multi function relay select Fault relay output Output terminal select when communication error occurs Communication protocol select Drive number Baud rate Drive mode select after loss of frequency command Min Max range 0 19 0 7 0 1 1 250 074 10 12 13 14 15 16 17 18 19 N OO AR WN OH 0 1 2 3 0 Description Drive Overheat OHt Command loss During Run During Stop During constant run During speed searching Wait time for run signal input Multi function relay select Warning for cooling fan trip Brake signal select When setting the W
33. emote keypad communication error Cause Compact amp Powerful Drive iG5A Remedy Caution When an overcurrent fault occurs operation must be started after the cause is removed to avoid damage to IGBT inside the drive Accel Decel time is too short compared to the GD of the load Load is greater than the drive rating Drive output is issued when the motor is free running Output short circuit or ground fault has occurred Mechanical brake of the motor is operating too fast Ground fault has occurred at the output wiring of the drive The insulation of the motor is damaged due to heat Load is greater than the drive rating Torque boost scale is set too large Cooling system has faults An old cooling fan is not replaced with a new one Ambient temperature is too high Faulty contact of magnetic switch at output Faulty output wiring An alien substance is clogged in a ventilating slot Drive has been in use without changing a cooling fan Decel time is too short compared to the GD of the load Regenerative load is at the drive output Line voltage is too high Line voltage is low Load larger than line capacity is connected to line ex welding machine motor with high starting current connected to the commercial line Faulty magnetic switch at the input side of the drive Motor has overheated Load is greater than drive rating ETH level is set too low Drive capacity is incorrectly selected Drive h
34. ency Frequency accuracy Analog command 0 1 of Max output frequency Control V F pattern Linear Squared User V F Overload capacity 150 per 1 min Torque boost Manual Auto torque boost y Max braking Ge Dynamic torque 20 1 braking Max Duty 150 when using optional DB resistor 2 Operation mode Keypad Terminal Communication option Remote keypad selectable Frequency settin Analog 0 10V 10 10V 0 20mA aa iakhs Digital Keypad Operation features PID Up down 3 wire NPN PNP selectable Multi function FWD REV RUN Emergency stop Fault reset Jog operation Multi step Frequency High Mid Low Operation Input terminal Multi step Accel Decel High Mid Low DC braking at stop 2nd motor select Frequency UP Down P1 P8 3 wire operation External trip A B PID Drive V F operation bypass Option drive V F operation bypass Analog Hold Accel Decel stop Open collector terminal Fault output and Less than DC 24V 50mA drive status output Output Multi function relay N O N C Less than AC 250V 1A Less than DC 30V 1A Analog output AM 0 10Vdc less than 10mA Output freq Output current Output voltage DC link selectable Over voltage Under voltage Over current Ground fault current detection Drive overheat Trip Motor overheat Output phase open Overload protection Communication error Loss of speed command Hardware fault Fan trip Protective Alarm Stall prevention Overload function Below 15 msec Continuous operati
35. ency high limit and below 0 50 X F23 Start frequency 0 Manual torque boost 0 X 1 Auto torque boost This parameter sets the amount of torque boost applied to a motor 3 x during forward run Itis setin percent of Max output voltage This parameter sets the amount of torgue boost applied to a motor 5 x during reverse run It is set as a percent of Max output voltage Drive Starvert iG5A Series 27 Function group 1 LED F30 F31 F32 F33 F34 F35 F36 F37 F38 F39 F40 F50 F51 2 F52 F53 F54 F55 Address for display communication A21E A21F A220 A221 A222 A223 A224 A225 A226 A227 A228 A232 A233 A234 A235 A236 A237 Parameter name V F pattern User V F frequency 1 User V F voltage 1 User V F frequency 2 User V F voltage 2 User V F frequency 3 User V F voltage 3 User V F frequency 4 User V F voltage 4 Output voltage adjustment Energy saving level Electronic thermal select Electronic thermal level for 1 minute Electronic thermal level for continuous Motor cooling method Overload warning level Overload warning time 1 Set F30 to 2 User V F to display this parameter 2 Set F50 to 1 to display this parameter 28 LSIS Co Ltd Function List Min Max range 0 2 0 400 Hz 0 100 O 400 Hz 0 100 O 400 Hz 0 100 Ka 0400 Hz 0 100 Ka
36. er capacity Adjust ETH level to an appropriate level Select correct drive capacity Install a cooling fan with a separate power supply Eliminate the cause of fault at circuit connected to external fault terminal or cause of external fault input Check the wiring of V1 and I and frequency reference level Check for connection of communication line and connector Contact your LSIS sales distributor Drive Starvert iG5A Series 43 Green Innovators of Innovation Safety Instructions LSIS Co Ltd 2005 5 LSIS Co Ltd All rights reserved For your safety please read user s manual thoroughly before operating Contact the nearest authorized service facility for examination repair or adjustment Please contact a qualified service technician when you need maintenance Do not disassemble or repair by yourself Any maintenance and inspection shall be performed by the personnel having expertise concerned www lsis com H HEAD OFFICE LS Tower 127 LS ro Dongan gu Anyang si Gyeonggi do Korea a EMEA 82 2 2034 4901 bonseongkOlsis com a Asia Pacific Americas 82 2 2034 4620 mswoo lsis com Overseas Subsidiaries e LSIS Dalian Co Ltd Dalian China No 15 Liaohexi 3 Road Economic and Technical Development Zone Dalian 116600 China el 86 411 8730 7510 Fax 86 411 8730 7560 e LSIS Wuxi Co Ltd Wuxi China No 1 Lexing Road Wuxi National High amp New
37. etting 2 Terminal RS485 communication Digital Volume Set to Field Bus communication 1 1 Terminal operation IV Digital oO OAN 08 VI BK WN OO FW Sets Multi Step frequency 1 during Multi step operation 10 00 O Sets Multi Step frequency 2 during Multi step operation 20 00 O Sets Multi Step frequency 3 during Multi step operation 30 00 O Displays the output current to the motor Displays the number of Motor RPM S Displays DC link voltage inside the drive This parameter displays the item selected at H73 Monitoring item select vOL Output voltage vOL POr Output power tOr Torgue Drive Starvert iG5A Series 25 Function List ss Drive Group LED Address for Parameter Min Max Description Factory Adj display communication name range P defaults during run Displays the types of faults frequency and operating status at nOn A10C Fault Display p 4 Ja S 2 p S the time ofthe fault ee Sets the direction of motor rotation when drv Drive mode is set Direction of A A to either 0 or 1 drC A10D motor rotation Fr F O F Forward select Reverse 0 Run Stop via Run Stop key on the keypad FX Motor forward run Terminal operation RX Motor reverse run drv2 A10E Drive mode 2 0 3 FX Run Stop enable 1 X 2 RX Reverse rotation select 3 RS 485 communication 4 Setto Filed Bus Communication 0 Keypad setting 1 Digital JE 1 Keypad setting 2 2 V1 1 10 10 V 3 V12 0 1
38. g to I 14 Criteria for Analog Input Signal loss Multi function input terminal P1 define Multi function input terminal P2 define Multi function input terminal P3 define Multi function input terminal P4 define Min Max range 0 87 0 10 IV 0 400 Hz 0 10 IV 0 400 Hz 0 9999 0 10 V 0400 Hz 0 10 V 0400 Hz 0 9999 0 20 mA 0 400 Hz 0 20 mA 0 400 Hz 0 2 Description Sets the code number to jump Sets the minimum voltage of the NV 10V OV input Sets the drive output minimum frequency at minimum voltage of the NV input Sets the maximum voltage of the NV input Sets the drive output maximum frequency at maximum voltage of the NV input Adjusts the responsiveness of V1 input 0 10V Sets the minimum voltage of the V1 input Sets the drive output minimum frequency at minimum voltage of the V1 input Sets the maximum voltage of the V1 input Sets the drive output maximum frequency at maximum voltage of the V1 input Sets the input section s internal filter constant for input Sets the minimum current of input Sets the drive output minimum frequency at minimum current of I input Sets the Maximum current of input Sets the drive output maximum frequency at maximum current of I input 0 Disabled 1 activated belowhalfofset value 2 activated below set value D Forward run command 1 Reverse run command 2 Emergency
39. he cooling fan by detecting the temperature of the heat sink The drive turns off its output when the one or more of the output U V W phase is open The drive detects the output current to check the phase loss of the output The drive turns off its output if the DC voltage of the main circuit increases higher than 400V when the motor decelerates This fault can also occur due to a surge voltage generated at the power supply system The drive turns off its output if the DC voltage is below 180V because insufficient torque or overheating of the motor can occur when the input voltage of the drive drops The internal electronic thermal of the drive determines the overheating of the motor If the motor is overloaded the drive turns off the output The drive cannot protect the motor when driving a motor having more than 4 poles or multi motors Drive output is blocked when one of R S T is open or the electrolytic capacitor needs to be replaced Displayed when IGBT damage output phase short output phase ground fault or output phase open occurs Displayed when user setting parameters fails to be entered into memory Displayed when an error occurs in the control circuitry of the drive Displayed when the drive cannot communicate with the keypad Displayed when the drive and the remote keypad do not communicate with each other It does not stop drive operation Displayed after the drive resets the keypad when a keypad error occurs and this
40. hen the trip H26 Number of other than low auto restart try voltage trip occurs Bit 2 Bit 1 NA NA Ta E SE 5 NA NA NA NA Multi function relay Bit 1 Bit 0 s VA NA e Ba Ba Set communication protocol Modbus RTU LS BUS 1 Set for RS485 communication Select the Baud rate of the RS485 1200 bps 2400 bps 4800 bps 9600 bps 19200 bps Compact amp Powerful Drive iG5A When the low voltage trip occurs Bit 0 Multi function output terminal It is used when freq command is given via V1 I terminal or RS485 Continuous operation at the frequency before its 1 2 command is lost Free Run stop Output cut off Decel to stop Factory Adj defaults during run 17 O 2 0 0 O 0 X 1 O 3 0 0 O Drive Starvert iG5A Series 39 Function List Input output group LED Address for Parameter Min Max display communication name range Factory Adj Description defaults during run MA This is the time drive determines whether there is the input Wait time after 0 1 120 frequency command or not If there is no frequency command 163 A43F loss of frequency i De a AA 1 0 O sec input during this time drive starts operation via the mode command selected at 162 Communication 2 100 164 A440 j 8 Frame communication time 5 O time setting ms When the protocol is set the communication format can be set Parity stop bit 0 Parity None Stop Bit 1 arity sto
41. ime for dwell operation 0 0 Sets the frequency range to skip to prevent undesirable A resonance and vibration on the structure of the machine 10 00 15 00 Run frequency cannot be set within the range of H11 thru H16 bad The frequency values of the low numbered parameters cannot i be set above those of the high numbered ones Settable within the range of F21 and F23 29 90 30 00 35 00 Set the speed reference value to form a curve at the start during E i A 40 accel decel If it is set higher linear zone gets smaller Set the speed reference value to form a curve atthe end during ih i 40 accel decel If it is set higher linear zone gets smaller 0 Disabled 1 Outputphase protection Input phase 3 Input output phase 0 protection protection This parameter is activated when drv is set to 1 or 2 Run Stop via Control terminal Motor starts acceleration after AC power is applied while FX or 0 RX terminal is ON This parameter is activated when drv is set to 1 or 2 Run Stop via Control terminal 5 Motor accelerates after the fault condition is reset while the FX or RX terminal is ON 1 only displayed when H10 is set to 1 H17 H18 are used when F2 F3 are set to 1 S curve 30 LSIS Co Ltd Adj during run O Function group 2 LED Address for Parameter display communication name h He 1 A316 Speed Searc Select Current level H23 A317 during Speed search P gain during H24 A318 Speed search H25 A319 I gain
42. nal 0 10V 3A Acontact output 3C A B contact common 3B B contact output MO Multi function open collector output MG MO Common RS 485 communication terminal Wiring 11 0 22 0kW DB resistor Optional 3 phase AC input Rated input voltage D SV iG5A 24 24V output Multi function ore P1 FX Forward run OD analog output signal 0 10V OO P2 RX Reverse run CM Input signal common OO P3 BX Emergency stop P4 RST Trip reset OO P5 JOG Jog operation C 3A A contact output CM Input signal common 3C A B contact common O P6 Multi step freq Low a LU 3B B contact output E P7 Multi step freq Middle Ps Multi step freq High MO Multi function open Potentiometer collector output 1kohm 1 2W C MG MO Common VR 10V power supply for potentiometer V1 Freq Setting Voltage signal input 10 10V RS 485 communication terminal I Freq Current signal input 0 20mA CM Input signal common Compact amp Powerful Drive iG5A Wiring Specifications for power terminal block wiring e 0 4kW 0 75kW 1 phase e 0 4kW 1 5kW 3 phase e 1 5kW D phase e 1918 8 21919188 12 elle B1 B2 T Bi B2 Vv R T Vv Ww e 2 2 4 0kW 3 emeng 2121918 18 191918 T Bi B2 Vv e 11 22kW 3 phase
43. on Should be within rated input voltage rated output power Momentary power loss Above 15 msec Auto restart enable Protection degree IP 20 NEMAT Optional Ambient temp 10 C 50 C Storage temp 20 C 65 C Ps Humidity Below 90 RH No condensation Altitude Vibration Below 1 000m 5 9m sec 0 6G Atmospheric pressure 70 106 kPa Location Protected from corrosive gas Combustible gas Oil mist or dust 1 Means average braking torgue during Decel to stop of a motor 2 Refer to Chapter 16 of user s manual for DB resistor specification 10 LSIS Co Lid Wiring 0 4 7 5kW 3 phase AC input Rated input voltage Comnact amp Powerful Drive iGSA Compact amp Powertul Drive IGSA SV iG5A 24 24V output AM FX Forward run RX Reverse run CM Input signal common P3 BX Emergency stop P4 RST Trip reset P5 JOG Jog operation CO CM Input signal common P6 Multi step freq Low p7 Multi step freq Middle O O O P1 P2 Potentiometer 1kohm 1 2W KEN Ps Multi step freq High 10V power supply for potentiometer V1 Freq Setting Voltage signal input 10 10V Freq Current signal input 0 20mA CM Input signal common Multi function analog output sig
44. orced air cooling Weight kg 0 76 0 77 1 12 184 189 189 3 66 3 66 9 0 9 0 13 3 13 3 3 Phase 400V SV OOOiG5A 400 004 008 015 022 037 040 055 075 110 150 185 220 Max HP 0 5 1 2 3 5 5 4 7 5 10 15 20 25 30 capacity 1 kW 0 4 0 75 1 5 2 2 3 7 4 0 5 5 7 5 11 15 18 5 22 Capacity kVA 2 0 95 1 9 3 0 45 6 1 6 5 9 1 122 18 3 229 297 343 Output FLA A 3 1 25 2 5 4 6 8 9 12 16 24 30 39 45 rating Max frequency 400 Hz 4 Max voltage 3 phase 380 480V 5 Input Rated voltage 3 phase 380 480 VAC 10 15 rating Rated frequency 50 60 Hz 5 Cooling method N C amp Forced air cooling Weight kg 0 76 0 77 1 12 1 84 1 89 1 89 3 66 3 66 9 0 9 0 13 3 13 3 1 Indicate the maximum applicable motor capacity when using 4 pole LS standard motor 2 Rated capacity is based on 220V for 200V series and 440V for 400V series 3 Refer to 15 3 of user s manual when carrier frequency setting 39 is above 3kHz 4 Max frequency setting range is extended to 300Hz when H40 Control mode select is set to 3 Sensorless vector control 5 Max output voltage cannot be higher than the input voltage It can be programmable below input voltage 6 Self Cooling Drive Starvert iG5A Series 9 Standard Specifications Control method Frequency setting resolution V F Sensorless vector control Digital command 0 01Hz Analog command 0 06Hz Max freg 60Hz Digital command 0 01 of Max output frequ
45. ows to the motor for F55 Overload warning time Factory defaults 15 00 25 30 00 50 45 00 75 60 00 100 100 150 100 150 10 Adj during run Function group 1 LED Address for Parameter display communication name Overload F56 A238 trip select Overload F57 A239 i trip level Overload F58 A23A re trip time F59 A23B Stall prevention select Stall prevention F60 A23C PEN level When Stall revention durin F61 A23D eae ere deceleration voltage limit select Save up down F63 A23F frequency select F64 2 A240 Save up down frequency d F65 A241 Up down mode select d t F66 A242 up down step freguency Draw run mode F70 A246 select F71 A247 Draw rate 1 Itis indicated when setting bit 2 of F59 as 1 2 Set F63 to 1 to display this parameter Min Max range 0 1 30 200 Ka 0 60 Sec 30 200 0 1 0 2 0 400 Hz 0 3 0 100 Compact amp Powerful Drive iG5A Description This parameter turns off the drive output when motor is overloaded This parameter sets the amount of overload current The value is the percentage of H33 Motor rated current This parameter turns off the drive output when the F57 Overload trip level of current flows to the motor for F58 Overload trip time This parameter stops accelerating during acceleration decelerating during constant speed run and stops decelerating during deceleration
46. p bi 165 A441 GE 4 0 3 1 Parity None Stop Bit 2 O O S 2 Parity Even Stop Bit 1 3 Parity Odd Stop Bit 1 Read address 166 A442 i 5 register 1 Read address 167 A443 i 6 register 2 Read address 168 A444 A 7 register 3 Read address 169 A445 i 8 register 4 049999 The user can register up to 8 discontinuous addresses and read o Read address them all with one Read command 170 A446 9 register 5 Read address 171 A447 i 10 register 6 Read address 172 A448 i 11 register 7 Read address 173 A449 12 register 8 Write address 174 A44A i 5 register 1 Write address 175 A44B i 6 register 2 Write address 176 A44C i 7 register 3 Write address 177 A44D i A A register 4 042239 The user can register up to 8 discontinuous addresses and write o Write address them all with one Write command 178 A44E 5 register 5 Write address 179 A44F i 6 register 6 Write address 180 A450 i 7 register 7 Write address 181 A451 i 8 register 8 Brake open 0 180 Sets current level to open the brake 182 1 A452 Broe Wee 50 0 o current Itis set according to H33 s motor rated current size 1 It is indicated when choosing 154 155 as a 19 Brake signal 40 LSIS Co Ltd Compact amp Powerful Drive iG5A Input output group LED Address for Parameter Min Max Description Factory Adj display communication name range P defaults during run Brake open 0 10 183 A453 i p Sets Brake o
47. pen dely time 1 00 X delay time s Brake open FX 0 400 184 A454 l P Sets FX frequency to open the brake 1 00 X frequency Hz Brake open RX 0 400 185 A455 P Sets RX freguency to open the brake 1 00 X frequency Hz Brake close 0 19 186 A456 i Sets delay time to close the brake 1 00 X delay time s Brake close 0 400 187 A457 Sets frequency to close the brake 2 00 X frequency Hz Drive Starvert iG5A Series 41 Keypad display Protective functions ju ke LIL L Lei pw Ca Cas CET Za Mel Fr a z3 me L3 m Va fr Ti 3 ZE E i fe mm a Ca 2 l Dal md s o za a LX mm me pw CO fr a om mo ge Dal 42 LSIS Co Ltd Protective Functions Descriptions The drive turns off its output when the output current of the drive flows more than 200 of the drive rated current The drive turns off its output when a ground fault occurs and the ground fault current is more than the internal setting value of the drive The drive turns off its output when the output current of the drive flows more than the rated level 150 for 1 minute The drive turns off its output if the output current of the drive flows at 150 of the drive rated current for more than the current limit time 1 min The drive turns off its output if the heat sink overheats due to a damaged cooling fan or an alien substance in t
48. rameters back to the factory default value 0 All parameter groups are initialized to factory default H93 A35D ee 0 5 value 0 X 2 Only Drive group is initialized 3 Only Function group 1 is initialized 4 Only Function group 2 is initialized 5 Only I O group is initialized Password Password for H95 Parameter lock H94 A35E i 0 FFFF 0 O register Set as Hexa value This parameter is able to lock or unlock parameters by typing password registered in H94 125 ADE Edrameten ta UL Unlock Parameter change enable 2 o L Lock Parameter change disable 1 It is indicated when choosing 117 124 as a 12 2nd motor select 2 H91 H92 parameters are displayed when Remote option is installed Drive Starvert iG5A Series 35 Function List Input output group LED Address for display communication 10 A400 12 A402 13 A403 14 A404 15 A405 16 A406 17 A407 18 A408 19 A409 110 A40A 111 A40B 112 A40C 113 A40D 114 A40E 115 A40F 116 A410 117 A411 118 A412 119 A413 120 A414 Parameter name Jump code NV input Min voltage Frequency corresponding to I 2 NV input Max voltage Frequency corresponding to 4 Filter time constant for V1 input V1 input Min voltage Freguency corresponding to 7 V1 input Max voltage Freguency corresponding to 9 Filter time constant for input input Min current Frequency corresponding to I 12 I input Max current Frequency correspondin
49. reached the drive holds the output 04 7 for the setting time before starting DC brake This parameter sets the amount of DC voltage applied to a motor 50 S It is set in percent of H33 Motor rated current This parameter sets the time taken to apply DC current to a 10 x motor while motor is at a stop This parameter sets the amount of DC voltage before a motor starts to run 50 X It is set in percent of H33 Motor rated current DC voltage is applied to the motor for DC Brake start time before 0 X motor accelerates This parameter applies the current to a motor for the set time before motor accelerates during Sensorless vector control 0 1 X This parameter sets the frequency for Jog operation p quency g op 10 00 o It cannot be set above F21 Max frequency This parameter sets the highest frequency the drive can output It is frequency reference for Accel Decel See H70 A Caution 60 00 x Any frequency cannot be set above Max frequency except Base frequency The drive outputs its rated voltage to the motor at this frequency 60 00 X see motor nameplate The drive starts to output its voltage at this frequency 0 50 It is the frequency low limit This parameter sets high and low limit of run frequency 0 X Thi t ts high limit of the run freguency is parameter sets hig quency 60 00 7 It cannot be set above F21 Max frequency This parameter sets low limit of the run frequency It cannot be set above F25 Frequ
50. th PNP and NPN inputs become possible and these enable to use the outer power To do so users will be given wider choices of selecting the controller Drive Starvert iG5A Series 7 Model amp Type Applicable motor ranges 1 Phase 200V 3 Phase 200V 3 Phase 400V 0 18 5kW 25HP 22 0kW 30HP CD 0 EB A A A Motor rating kW 004 0 4kW 220 22kW IGSA series Input voltage 1 1 phase 200 230 V 2 3 phase 200 230 V 4 3 phase 380 480 V 8 LSIS Co Ltd Compact amp Powerful Drive iG5A Standard Specifications EE 1 Phase 200V SV 000 iG5A 1 00 004 008 015 Max HP 0 5 1 2 capacity 1 kW 0 4 0 75 1 5 Capacity kVA 2 0 95 1 9 3 0 Output FLA A 3 2 5 5 8 rating Max frequency 400 Hz 4 Max voltage 3 phase 200 230V 5 Input Rated voltage 1phase 200 230 VAC 10 15 rating Rated frequency 50 60 Hz 5 Cooling method Forced air cooling Weight kg 0 76 1 12 1 84 3 Phase 200V SV OODIG5A 2 CC 004 008 015 022 037 040 055 075 110 150 185 220 Max HP 0 5 1 2 3 5 5 4 7 5 10 15 20 25 30 capacity 1 KW 0 4 0 75 15 22 37 40 55 75 1 15 185 22 Capacity kVA 2 0 95 1 9 3 0 4 5 6 1 6 5 9 1 12 2 17 5 22 9 28 2 33 5 Output FLA A 3 2 5 5 8 12 16 17 24 32 46 60 74 88 rating Max frequency 400 Hz 4 Max voltage 3 phase 200 230V 5 Input Rated voltage 3 phase 200 230 10 15 rating Rated frequency 50 60 Hz 5 Cooling method N C F
51. verheat protection 150 for one minute at the rated output current 8 In case magnetic contactor is used on single phase product wire R and T phases Braking Resistors and Peripheral Devices Fuses 8 AC reactors Model 004iG5A 1 008iG5A 1 015iG5A 1 004iG5A 2 008iG5A 2 015iG5A 2 022iG5A 2 037iG5A 2 040iG5A 2 055iG5A 2 075iG5A 2 110iG5A 2 150iG5A 2 185iG5A 2 220iG5A 2 004iG5A 4 008iG5A 4 015iG5A 4 022iG5A 4 037iG5A 4 040iG5A 4 055iG5A 4 075iG5A 4 110iG5A 4 150iG5A 4 185iG5A 4 220iG5A 4 24 LSIS Co Ltd AC external fuse Current A 10 A 10 A 15 A 10 A 10 A 15 A 25 A 30 A 30 A 30 A 50 A 70 A 100 A 100 A 125 A 5A 10 A 10 A 10 A 20 A 20 A 20 A 30 A 35 A 45 A 60 A 70 A Voltage V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V AC reactor 4 20 mH 3 5 A 2 13 mH 5 7 A 1 20 mH 10 A 4 20 mH 3 5 A 2 13 mH 5 7 A 1 20 mH 10 A 0 88 mH 14 A 0 56 mH 20 A 0 56 mH 20 A 0 39 mH 30 A 0 28 mH 40 A 0 20 mH 59 A 0 15 mH 75 A 0 12 mH 96 A 0 10 mH 112A 18 0 mH 1 3A 8 63 mH 2 8A 4 81 mH 4 8A 3 23 mH 7 5A 2 34 mH 10 A 2 34 mH 10 A 1 22 mH 15A 1 14 mH 20 A 0 81 mH 30 A 0 61 mH 38 A 0 45 mH 50 A 0 39 mH 58 A DC reactor 0 74 mH 56 A 0 57 mH 71 A 0 49 mH 91 A 0 42 mH 107 A 2 76 mH 29A 2 18 mH 36 A 1 79 mH 48 A 1 54 mH 55A Fun
52. y once L000 16 0 is blinking 1 Press the Ent e key once again to return to the parameter name 8 H a E ACC is displayed Accel time is changed from 5 0 to 16 0 sec 1 Pressing the Left lt Right Up A Down key while a cursor is blinking will cancel the parameter value change Pressing the Ent e key in this status will enter the value into memory X In step 7 pressing the Left lt 4 or Right key while 16 0 is blinking will disable the setting Code change in Drive group 1 nm In the 1st code in Drive group 0 00 ALLA press the Up 4 key once arr The 2nd code in Drive group ACC is displayed 2 MILL Press the Up A key once rr The 3rd code dEC in Drive group is displayed 3 UCL Keep pressing the Up 4 key until the last code appears ILE The last code in Drive group drC is displayed 4 HI L Press the Up 4 key again 5 n p i Return to the first code of Drive group Use Down Y key for the opposite order Drive Starvert iG5A Series 17 Trial Run Multi step operation Run Stop via FX RX Max frequency change Operation condition Operation command Run Stop via FX RX Frequency command Wiring 5 o 0 PI Forward st O CO P2 Reverse Multi step operation Low 20 Middle 30 High 80 Max frequency change From 60Hz to 80Hz GE 3 phase 9 AC input o OO PS Low 3 s 0 o t O