1. Main Menu Status Control Configuration Test And Diagnostics Log About Status Menu Control Menu Config Menu Test and Diagnostics Menu Log About Menu UPS UPS UPS Self Test Event Log UPS Battery Bypass Battery Runtime Test Battery Accessory Outlet Group 1 Outlets Alarm Test Accessory Outlet Group 2 Communication Outlet Group 3 Display Clear Alarms UPS Part Number UPS UPS Serial Number UPS Turn On Off Reboot Green mode Enable Disable E Date Efficiency Output Voltage Frequency Settings a me Output Power VA Watts Bypass Settings ate and lime ERE Current Frequency UPS Bypass Battery Settings nergy Usage Go into Bypass Self Test Schedule Battery State Of Charge Runtime Go outorB Default Setting ypass Input Voltage Frequency Reset Energy Meter Bypass Voltage Frequency Battery Self Test Part Number Runtime Test Outlet Group Install And Replace Date Turn On Off Reboot Battery Firmware Version Install Date Replace Notification Battery Replace Battery Alarm Battery Status Information Accessory MAC Address Outlets E Address Accessory Main Outlet Firmware Version Network Management Interface Information Outlet Group 1 Outlet Group 2 Outlet Group 3 Configuration UPS Settings There are four ways to select UPS configuration options 1 The first time the UPS is turned on the Setup Wizard screen will open On each menu screen select t
2. RISK OF DAMAGE TO EQUIPMENT OR PERSONNEL Adhere to all national and local electrical codes Wiring must be performed by a qualified electrician Always connect the UPS to a grounded outlet Failure to follow these instructions can result in equipment damage and minor or moderate injury Normally open contacts 1 If the EPO switch or relay contacts are normally open insert the wires from the switch or contacts at pins 1 and 2 of the EPO terminal block Use 16 28 AWG wire 2 Secure the wires by tightening the screws If the contacts are closed the UPS will turn OFF and power will be removed from the load Normally closed contacts 1 If the EPO switch or relay contacts are normally closed insert the wires from the switch or contacts at pins 2 and 3 of the EPO terminal block Use 16 28 AWG wire 2 Insert a wire jumper between pins 1 and 2 Secure the wires by tightening the three screws at positions 1 2 and 3 If the contacts are opened the UPS will turn OFF and power will be removed from the load Note Pin 1 is the power source for the EPO circuit it provides a few milliampere of 24 V power If the normally closed NC EPO configuration is used the EPO switch or relay should be rated for dry circuit applications the rating should be for low voltage and low current applications This normally implies the contacts are gold plated The EPO interface is a Safety Extra Low Voltage SELV circuit Connect the E
3. The model and serial numbers are on a small label located on the rear panel Battery Battery type Maintenance free leak proof sealed lead acid Replacement battery module APCRBC140 This UPS has hot swappable battery modules Replacement is a safe procedure isolated from electrical hazards Refer to the appropriate replacement battery user manual for installation instructions Contact your dealer or go the APC web site www apc com for information on replacement batteries Number of battery modules 4 battery modules Voltage for each battery module 96 VDC Total voltage for the UPS 192 VDC Ah rating 5 1 Ah per battery module XLBP cable length 500 mm 19 7 in 4 Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Electrical Models Rating SRTSKXLT SRTSKRMXLT SRTSKXLT IEC SRTSKRMXLT IEC SRT8KXLI SRT8KRMXLI SRT10KXLT SRT10KRMXLT SRTIOKXLT IEC SRTIOKRMXLT IEC SRT10KXLI SRT10KRMXLI 8 8 kW 10 10 kW Output Output Frequency 50 Hz 60 Hz 3 Hz Nominal Output SRTSKXLI SRTSKRMXLI SRTIOKXLI SRTIOKRMXLI 220Vac 230Vac 240 Vac SRTSKXLT SRTSKRMXLT SRTIOKXLT SRTIOKRMXLT 208Vac 240Vac SRTSKXLT IEC SRTSKRMXLT IEC SRTIOKXLT IEC SRTI OKRMXLT IEC 208Vac 240Vac Input Input Frequency 40 Hz 70 Hz Nominal Input SRTSKXLI SRTSKRMXLI SRTIOKXLI SRTIOKRMXLI 220Vac 230Vac 240Vac SRTSKXLT SRTSKRMXLT SRTIOKXLT SRTIOKRMXLT
4. 6 AWG 5 09 Nm 45 Ibf in 16 mm 4 AWG 5 09 Nm 45 Ibf in 2 5 mm 12 AWG 3 969 Nm 35 Ibf in Failure to follow these instructions can result in equipment damage and minor or moderate injury Single Feed Number Current Full External Input Circuit Wire Size System Wiring of Voltage Load Breaker Mains Mains typical Phases nominal typical Input 1 208 240 Vac 47A 60 A 2 pole 10 mm 6 AWG SRTSKXLT Output 1 208 240 Vac 40A 10 mm 6 AWG Input 1 208 240 Vac 56A 70 A 2 pole 16 mm 4 AWG SRTIOKXLT Output 1 208 240 Vac 49A 10 mn 6 AWG Input 1 220 230 240 Vac 44A 63 A 2 pole 10 mm 6 AWG Output 1 220 230 240 Vac 38 A 10 mm 6 AWG SRT8KXLI Input 3 380 400 415 Vac 15 A 63 A 4 pole 10 mm 44 A 6 AWG Output 1 220 230 240 Vac 38 A 10 mm 6 AWG Input 1 220 230 240 Vac 54A 80 A 2 pole 16 mm 4 AWG Output 1 220 230 240 Vac 47 10 mm 6 AWG SRTIOKXLI Input 3 380 400 415 Vac 18A 80 A 4 pole 16 mm 54 A 4 AWG Output 1 220 230 240 Vac 47 10 mm 6 AWG Phase 1 L1 current while in bypass mode Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 9 Dual Feed External External Number Current c Wire Size Wire Size System Wiring of Voltage Full Load Mains Bypass Phases nominal Breaker Bypass typical typical Mains Mains typical typical Inp
5. Not all units utilize XLBPs 4 Write the RMA provided by Customer Support on the outside of the package 5 Return the unit by insured prepaid carrier to the address provided by Customer Support 28 Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Limited Factory Warranty Schneider Electric IT Corporation SEIT warrants its products to be free from defects in materials and workmanship for a period of three 3 years excluding the batteries which are warranted for two 2 years from the date of purchase The SEIT obligation under this warranty is limited to repairing or replacing at its own sole option any such defective products Repair or replacement of a defective product or part thereof does not extend the original warranty period This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase Products may be registered online at warranty apc com SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse negligence improper installation testing operation or use of the product contrary to SEIT recommendations of specifications Further SEIT shall not be liable for defects resulting from 1 unauthorized attempts to repair or modify the product 2 incorrect or inadequate electrical voltage or connection 3 inappropriate on site operation c
6. Off EPO terminal allows the user to connect the UPS to a central EPO system Controllable outlet group 1 with circuit breaker Connect electronic devices to these outlets In the event an overload condition occurs disconnect nonessential equipment Then reset the circuit breaker Controllable outlet group 2 with circuit breaker Controllable outlet group 3 with circuit breaker Connect electronic devices to these outlets In the event an overload condition occurs disconnect nonessential equipment Then reset the circuit breaker Connect electronic devices to these outlets In the event an overload condition occurs disconnect nonessential equipment Then reset the circuit breaker AC output inspection panel AC input inspection panel AC hardwire knockouts Remove the panel to inspect the output terminal block wiring configuration The terminal block is located behind the inspection cover Refer to Wiring Specifications on page 9 for hardwire specifications Remove the panel to inspect the input terminal block wiring configuration The terminal block is located behind the inspection cover Refer to Wiring Specifications on page 9 for hardwire specifications Remove the 38 1 mm 1 5 in knockout panels for AC input and output hardwiring Install appropriate strain reliefs not supplied Hardwire box input output Remove the box to connect input and output wires to the hardwire term
7. SRT8KRMXLI SRT10KXLI SRT10KRMXLI 000 9 BATT COMM 192VDC O O E a O O is D 11 suo0771a GROUP 1 16 AMP MAX o HARDWIRED OUTPUT GROUP 2 16 AMP MAX Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 7 Key to identify rear panel features Network port Use the Network port to connect the UPS to the network e Console port Use the Console port to configure the network management features Universal I O port Use to connect Temperature sensor AP9335T supplied Temperature humidity sensor AP9335TH not supplied Relay input output connector AP9810 not supplied supports two input contacts and one output relay USB port The USB port is used to connect either a server for native operating system communications or for software to communicate with the UPS Note Serial and USB communication should not be used simultaneously Use either the Serial Com or the USB port Serial Com The Serial Com port is used to communicate with the UPS Use only interface kits supplied or approved by APC by Schneider Electric Any other serial interface cable will be incompatible with the UPS connector EPO terminal The Emergency Power
8. Shutdown Disconnects the power to connected equipment either immediately or after a configured delay Equipment reconnects after a configured delay when mains power becomes available and other configured conditions are met Each controllable outlet group can be configured separately to allow power sequencing for equipment connected to any controllable outlet group Reboot Disconnect the power to connected equipment either immediately or after a configured delay Reconnect equipment after a configured delay when either mains or battery power becomes available and other configured conditions are met Each controllable outlet group can be configured separately to allow power sequencing for loads connected to any controllable outlet group Sleep This mode is a reboot with an extended duration where a outlet s remain turned off Disconnect the power to connected equipment either immediately or after a configured delay Reconnect equipment after a configured delay when either mains or battery power becomes available and other configured conditions are met Each controllable outlet group can be configured separately to allow power sequencing for equipment connected to any controllable outlet group To configure Sleep mode use an external interface such as the Network Management web interface Automatically turn off or shutdown when certain conditions occur based on user configurations set using the Config Menu Outlets menus Refer to Configuratio
9. 208Vac 240Vac SRTSKXLT IEC SRTSKRMXLT IEC SRTIOKXLT IEC SRTIOKRMXLT IEC 208Vac 240Vac Front panel features urs Display Interface panel UPS battery compartment doors x2 e urs battery connectors x4 Bezels x2 y Smart UPS On Line SRT8K 10K Tower Rack Mount 6U suo0796a Rear panel features Note Refer to the table Key to identify rear panel features on page 8 that provides a key to the callout numbers for the rear panel graphics depicted in this manual SRTSKXLT SRTSKRMXLT SRTIOKXLT SRTIOKRMXLT L3 O o m 192VDC 00 DQ j suo0772a 9 e GROUP 1 20 AMP MAX HARDWIRED OUTPUT GROUP 2 20 AMP MAX SRT8KXLT IEC SRT8KRMXLT IEC SRT10KXLT IEC SRT10KRMXLT IEC 1 15 3 o OUTPUT 50 60Hz rn NIC 208 240VAC 0 O lt m 0 0 E C 5g D 2 2 D GET GED CE GROUP 3 15 AMP MAX GROUP 2 20 AMP MAX suo0770a 6 Smart UPS On Line SRT8K 10K Tower Rack Mount 6U SRT8KXLI
10. 240 V 264 to 270 V Bypass Wider Frequency Wider Frequency The on Wider enables IPS mode Frequency Use O P Fre operation for an input frequency range o 3 quency A Setting Setting 47 63 Hertz Battery Enable Enable Disable When enabled this setting conserves battery by Conserve Mode switching to Bypass source No Yes No The UPS will not go to Bypass mode Disable Bypass When UPS detects a fault the load will be dropped Low Runtime 150 seconds 0 to 1800 seconds The UPS will emit an audible alarm when the Warning remaining runtime has reached this threshold Startup every 14 days Never This is the interval at which the UPS will execute a Self Test since last test Startup Self Test Schedule Startup 14 days Startup 7 days Default Setting No Yes No Allows the user to restore the UPS factory default settings No Yes No The Energy Meter stores information on UPS output Reset Energy energy usage Meter The Reset feature allows the user to reset the Energy Meter to 0 kWh Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Parameters Default Value Options Description Confi Install Date Battery Installation Date Month Year Enter the installation date of the RBCs g Menu Battery 180 days 0 360 days To set the Near End of Life alarm select the number of days before the estimated battery end of life Repl t When this date is reached the UPS will emit an alarm ep Action and a message wil
11. 7 Parameters Default Value Options Description onii seconds seconds elect the amount of time the controllable outlet fig Power On 0 d 0 1800 d Select th f time th llabl 1 Menu groups will wait between receiving the command to Outlets y turn on and actual startup Power Off 90 seconds 0 32767 seconds Select the amount of time the controllable outlet Dela groups will wait between receiving the command to y shutdown and actual shutdown Reboot 8 seconds 4 300 seconds Select the amount of time the controllable outlet Duration groups will remain off before the UPS will restart Minimum 0 seconds 0 32767 seconds Select the amount of battery runtime that must be Return available before the controllable outlet groups will Runtime turn on using battery power after a shutdown Disable Disable To conserve battery power the UPS can disconnect Loadshed On Enable power from controllable outlet groups not in use Battery To configure the disconnect delay time for this feature use the Loadshed Time On Battery setting Loadshed Time seconds 5 327767 seconds Select the amount of time the controllable outlet On Batter groups will be allowed to function on battery power y before shutdown Loadshed On Disable Disable To conserve battery power the UPS can disconnect Runtime Enable power from controllable outlet groups when the Loadshed Runtime threshold is reached Loadshed 0 seconds 0 3600 seconds When the selec
12. Arc by Schneider Electric Operation Manual Smart UPS On Line SRT SRT8KXLI SRT8KRMXLI SRT8KXLT SRT8KRMXLT SRT8KXLT IEC SRT8KRMXLT IEC SRT10KXLI SRT10KRMXLI SRT10KXLT SRT10KRMXLT SRT10KXLT IEC SRT10KRMXLT IEC 208 220 230 240 Vac Tower Rack Mount 6U Product Description The by Schneider Electric Smart UPS On Line SRT is a high performance uninterruptible power supply UPS The UPS helps to provide protection for electronic equipment from utility power blackouts brownouts sags surges small utility power fluctuations and large disturbances The UPS also provides battery backup power for connected equipment until utility power returns to safe levels or the batteries are completely discharged This user manual is available on the enclosed Documentation CD and on the APC web site www apc com General Information Safety Messages Read the instructions carefully to become familiar with the equipment before attempting to install operate service or maintain the UPS The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure The addition of this symbol to a Danger or Warning product safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed The addition of this symb
13. BP An enclosure that contains RBC s and battery management electronics User Interface UD Any interface by which a user can interact with the system This may include a UPS display interface a network management interface or PowerChute Network Shutdown software NOTE Do not use a battery that is not APC approved The system will not detect the presence of a non APC approved battery and may adversely affect the operation of the system Use of a non APC approved battery will void the manufacturer warranty Features Smart Battery Management provides the following features Monitors and informs the user of the health of each RBC Monitors and shows on the UPS Display Interface screen the date for the end of useful life for each RBC The UPS emits an alarm and shows a message on the UPS Display Interface screen to indicate the estimated battery end of life On the UPS Display Interface screen the user can set the number of days before the alarm is heard and the message appears on the UPS Display Interface screen Automatically detects the addition or removal of XLBPs and RBCs Monitors the internal temperature of each XLBP and automatically adjusts the battery charging Maintenance RBC maintenance The APC RBC uses sealed lead acid battery cells and does not require maintenance Runtime Test Calibration This should be performed anytime the steady state load is changed significantly for example a new server is added to or r
14. LLY SEIT IS NOT LIABLE FOR ANY COSTS SUCH AS LOST PROFITS OR REVENUE WHETHER DIRECT OR INDIRECT LOSS OF EQUIPMENT LOSS OF USE OF EQUIPMENT LOSS OF SOFTWARE LOSS OF DATA COSTS OF SUBSTITUANTS CLAIMS BY THIRD PARTIES OR OTHERWISE NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT OR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW To obtain service under warranty you must obtain a Returned Material Authorization RMA number from customer support Customers with warranty claims issues may access the SEIT worldwide customer support network through the APC web site www apc com Select your country from the country selection drop down menu Open the Support tab at the top of the web page to obtain information for customer support in your region Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 29 APC by Schneider Electric Worldwide Customer Support Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways Visit the APC web site to access documents in the APC by Schneider Electric Knowledge Base and to submit customer support requests www apc com Corporate Headqu
15. PO interface only to other SELV circuits The EPO interface monitors circuits that have no determined voltage potential SELV circuits are controlled by a switch or relay properly isolated from mains power To avoid damage to the UPS do not connect the EPO interface to any circuit other than a SELV circuit Use one of the following cable types to connect the UPS to the EPO switch CL2 Class 2 cable for general use e CL2P Plenum cable for use in ducts plenums and other spaces used for environmental air e CL2R Riser cable for use in a vertical run in a floor to floor shaft CLEX Limited use cable for use in dwellings and for use in raceways nstallation in Canada Use only CSA certified type ELC extra low voltage control cable nstallation in countries other than Canada and the USA Use standard low voltage cable in accordance with national and local regulations 20 Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Network Management Interface Introduction The UPS has a network port and console port that can be used to access the Network Management Interface The Network Management Interface is very similar to an AP9630 Network Management Card NMC that is integrated into a UPS with one universal input output port The Network Management Interface and the AP9630 NMC have the same firmware operation modes and interaction with other APC products such as PowerChute Network Shutdown Refer to the Network Management Car
16. The preference for Standard or Advanced menu selections is made during initial installation and can be changed at any time through the Configuration menu The Standard menus include the most commonly used options The Advanced menus provide additional options Note Actual menu screens may differ by model and firmware version Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 13 LCD display interface angle adjustment 14 The angle of the LCD display interface can be adjusted for ease in viewing the displayed messages 1 Remove the front bezel 2 Locate the button on the bottom of the display interface panel 3 Press the button and slide the bottom of the LCD display interface screen out An audible click will be heard when the screen reaches the maximum angle 0 Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Communication Network IP Address Boot Mode MODBUS Address Menus are subject to change depending on the installed firmware version Available on the Advanced Menu Screens Options displayed will vary based on UPS state Options displayed will vary based on connected accessories Display Language Beeper Volume LCD Backlight Menu type Standard Advanced
17. all connected batteries To perform a UPS Self Test use the UPS Display Interface menu option Test and Diagnostics The UPS Display Interface screen shows the message Replace Battery Allow the battery to recharge for 24 hours To perform a Runtime test use the UPS Display Interface menu option Test and Diagnostics If the problem persists replace all of the batteries Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Problem and Possible Cause Solution The UPS display turns red or amber displays an alert message and emits a sustained audible alarm Red illumination indicates a UPS alarm that requires immediate attention Amber illumination indicates a UPS alarm that requires attention There is an internal UPS alert or warning Do not attempt to use the UPS Turn the UPS off and have it serviced immediately The UPS is experiencing an overload Reduce the load on the UPS Disconnect nonessential equipment condition The Replace Battery alert is displayed The battery has a weak charge Allow the battery to recharge for at least four hours Then perform a UPS Self Test If the problem persists after recharging replace the battery The replacement battery is not properly Be sure the battery cable is securely connected connected Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 27 Transport Shut down and disconnect all connected equipment Disconnect the unit from mains powe
18. arters Connect to localized APC web site for specific countries each of which provides customer support information www apc com support Global support searching APC by Schneider Electric Knowledge Base and using e support Contact the APC by Schneider Electric Customer Support Center by telephone or e mail Local country specific centers go to www apc com support contact for contact information For information on how to obtain local customer support contact the APC by Schneider Electric representative or other distributor from whom you purchased your APC by Schneider Electric product 2014 APC by Schneider Electric APC the APC logo PowerChute and Smart UPS are owned by Schneider Electric Industries S A S or their affiliated companies All other trademarks are property of their respective owners EN 990 4506A 06 2014
19. d utility CD supplied with this product Features The Network Management Interface allows the UPS to function as a web based IPv6 ready product The Network Management Interface can manage the UPS using multiple open standards such as Hypertext Transfer Protocol HTTP Secure SHell SSH Simple Network Management Protocol versions 1 and 3 SNMPv1 SNMPv3 Hypertext Transfer Protocol over Secure Sockets layer HTTPS File Transfer Protocol FTP Secure Copy SCP Telnet Syslog RADIUS The Network Management Interface Provides UPS control and Self Test scheduling features Provides data and event logs Enables you to set up notifications through event logging e mail and SNMP traps Provides support for PowerChute Network Shutdown Supports using a Dynamic Host Configuration Protocol DHCP or BOOTstrap Protocol BOOTP server to provide the network TCP IP values Supports use of Remote Monitoring Service RMS Provides the ability to export a user configuration ini file from a configured UPS to one or more unconfigured UPS without conversion to a binary file Provides a selection of security protocols for authentication and encryption Communicates with StruxureWare Central and InfraStruxure Manager Supports one universal input output port for connection to a Temperature probe AP9335T supplied Temperature humidity sensor AP335TH optional Relay input output connec
20. e for the weight of the equipment The batteries are heavy Remove the batteries before installing the UPS and external battery packs XLBPs in a rack Always install XLBPs at the bottom in rack mount configurations The UPS must be installed above the XLBPs Always install peripheral equipment above the UPS in rack mount configurations Additional safety information can be found in the Safety Guide supplied with this unit Deenergizing safety The UPS contains internal batteries and may present a shock hazard even when disconnected from the branch circuit mains Before installing or servicing the equipment verify the following Mains circuit breaker is in the OFF position Internal UPS batteries are removed XLBP battery modules are disconnected Electrical safety For models with a hardwired input the connection to the branch circuit mains must be performed by a qualified electrician 230 V models only In order to maintain compliance with the EMC directive for products sold in Europe output cords attached to the UPS must not exceed 10 meters in length The protective earth conductor for the UPS carries the leakage current from the load devices computer equipment An insulated ground conductor is to be installed as part of the branch circuit that supplies the UPS The conductor must have the same size and insulation material as the grounded and ungrounded branch circuit supply conductors The conductor will typically be g
21. ed backup time The UPS batteries are weak due to a Charge the batteries Batteries require recharging after extended outages and wear recent power outage or they are near the out faster when put into service often or when operated at elevated temperatures If end of service life the batteries are near the end of service life consider replacing the batteries even if the Replace Battery message is not displayed The UPS is experiencing an overload The connected equipment exceeds the specified maximum load Refer to the APC condition web site www apc com for product specifications The UPS will emit a sustained audible alarm until the overload condition is corrected Disconnect nonessential equipment from the UPS to correct the overload condition Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 25 Problem and Possible Cause Solution UPS operates on battery power while connected to mains power The input circuit breaker has tripped Reduce the load on the UPS Disconnect nonessential equipment and reset the circuit breaker Check the circuit breaker rating for the connected equipment There is very high very low or distorted input line voltage Navigate to the UPS Display Interface screen that shows input voltage Verify that the input voltage is within specified operating limits If no input voltage is indicated on the UPS Display Interface screen contact Customer Support through the APC
22. emoved from the UPS load Battery health monitoring The battery energy output and voltage are monitored to assess the health of the installed batteries when the UPS is operating on battery Battery health monitoring is done during a UPS Self Test a Runtime Calibration Test and when the UPS is operating on battery power The UPS can be configured to perform periodic automatic Self Tests End of useful life Near end of life notification A warning message will appear on the UPS display interface screen when each RBC is approaching the end of its useful life For configuration details refer to Replacement Notification Time and Replacement Battery Alarm Time The estimated replacement date for each RBC is available through the UI Needs replacement notification The UPS display interface screen shows when RBC replacement is required The RBC must be replaced as soon as possible When an RBC requires replacement the UPS display interface may recommend that additional RBCs be replaced if they will soon reach the end of their useful life CAUTION Continued operation after end of useful life notification may cause damage to the batteries Recycling Remove the RBC from the XLBP Recycle the RBC Do not disassemble an RBC Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 23 Replace the RBCs in a UPS An RBC should only be disconnected or removed from the UPS temporarily as part of the battery replacement procedure Disconnect all connec
23. ernal Battery Pack Installation Guide for installation and replacement instructions 24 Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Troubleshooting Use the table below to solve minor installation and operation problems Refer to the APC web site www apc com for assistance with complex UPS problems The UPS features firmware that can be upgraded Go to the APC web site www apc com Support or contact your local Customer Care Center for more information Problem and Possible Cause Solution UPS will not turn on or there is no output The UPS is not connected to mains Be sure the power cable is securely connected to the UPS and to the mains power power supply The UPS display interface screen shows Check the mains power supply to verify acceptable power quality very low or no mains power There is an internal UPS alert or warning The UPS Display Interface screen will show a message to identify the alert or warning and corrective action UPS emits an audible alarm Normal UPS operation when running The UPS is operating on battery power battery power Refer to the status of the UPS as shown on the UPS Display Interface screen Press any key to mute all alarms The UPS emits an audible alarm and has An Alarm or Warning condition exists a red or amber back light on the UPS Refer to the display interface screen for information Display Interface screen UPS does not provide expect
24. he desired settings Press OK after each UPS setting is selected Note The UPS will not turn on until all of the settings have been configured Startup configuration Function Language English Francais Italiano Setup Wizard Description Select the language required for the UPS Display Interface Language options will vary by model and firmware version Options English Francais Italiano Deutch Espanol Portugues Russian Voltage AC Setting 230 VAC 220 VAC 240 VAC Setup Wizard Menu Type Standard Advanced Setup Wizard Available output voltage selection will vary depending on the model Select the output voltage Options 208 Vac 220 Vac 230 Vac 240 Vac The Standard menu options are the most commonly used options The Advanced menu options will be used by IT professionals who need detailed configuration and reporting information Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 16 General settings Configure these settings at any time using the UPS Display Interface or the Network Management web Interface Config Menu UPS Parameters Default Value Options Description Green Mode Disabled Disable Disable or enable Green mode operation Enable User Choice 230 V 220 V 240V Set the output voltage for the UPS This setting can AC Setting 208 V only be changed when the UPS output is off These
25. he UPS Installation Guide 2 Connect equipment to the outlets on the rear panel of the UPS Refer to Controllable Outlet Groups on page 19 Turn the UPS On Off The first time the UPS is turned on the Setup Wizard screen will run Follow the prompts to configure UPS settings Refer to Configuration on page 15 To turn on the UPS and all connected equipment press the Power ON OFF button on the display panel Follow the prompts to either turn the UPS on immediately or after a delay then press OK NOTE When there is no input power and the UPS is off the cold start feature can be used to turn on the UPS and connected equipment using battery power To perform a cold start press the Power ON OFF button The display panel will illuminate and the Power ON OFF button will illuminate red To turn on the output power press the Power ON OFF button again Select the prompt Turn ON with NO AC and press OK To turn output power off press the Power ON OFF button Follow the prompts to either turn the UPS off immediately or after a delay then press OK NOTE Once the AC power has been turned off the UPS will continue operating on battery power for a short period of time To remove power completely press the Power ON OFF button Follow the prompt to select Internal Power Off then press OK Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 11 UPS Display Interface POWER ON OFF button Button illumination indications No illumina
26. inal blocks Chassis ground screws The UPS and XLBPs have ground screws for connecting the ground leads Prior to connecting a ground lead disconnect the UPS from mains power External battery Use the external battery power and communication cables to connect the UPS and XLBP power and XLBPs provide extended runtime during power outages communication The UPS will automatically recognize up to 10 external battery packs connectors SmartSlot The SmartSlot can be used to connect optional management accessories p PRLCOMM port This port is not used with these products eset button se the Reset button to restart the Network Management Interface Reset butt Use the Reset b he Network Management Interf Note A restart of the Network Management Interface does not affect UPS operation Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Wiring Specifications A CAUTION DAMAGE TO EQUIPMENT OR PERSONNEL Adhere to all national and local electrical codes Wiring should be performed by a qualified electrician Strain reliefs are not supplied with the unit 38 1 mm 1 1 2 in snap in type strain reliefs are recommended The UPS must be wired into a branch circuit equipped with a circuit breaker rated as specified in the tables below Actual wire size must comply with required amp capacity and national and local electrical codes Recommended input terminal screw torque 10 mm
27. l appear on the UPS Display ae ication Interface screen ime Example Using the default value the Near End of Life alarm will occur 180 days before the estimated end of life date Replacement 14 days 0 180 days The Near End of Life alarm can be muted Battery Alarm Enter the number of days between the time a Near Time End of Life alarm is acknowledged and the next Near End of Life alarm occurs Config English English Select the language required for the UPS Display Menu Francais Interface Display Language en Language options will vary by model and firmware Espanol version Portugues Russian Loud Disable When audible alarms are disabled the UPS will never Enable emit an audible alarm Beeper Volume Sof Select the volume level for alarms when Enable is oft selected Medium Loud Auto Dim Always On To conserve energy the LCD back light illumination LCD Auto Dim dims or turns off when no events are active Auto Off ee Back Light Full UPS Display Interface illumination returns when the UPS changes status as a result of an event or when any button on the UPS Display Interface is pressed Optimal Values Color Adjust the brightness and contrast individually for LCD Setting Brightness each LCD back light color Contrast User Choice Standard The Standard menus include the most commonly Menu Type Advanced used options The Advanced menu options include all parameters Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 1
28. mode The UPS is supplying conditioned mains power to connected equipment Bypass mode The UPS is in Bypass mode and the connected equipment will receive mains power as long as the input voltage and frequency are within the configured limits Green mode When in Green mode mains power is sent directly to the load In the event of a mains power outage there will be an interruption in power to the load of up to 8 ms while the UPS switches to On Line or Battery mode When enabling Green mode consideration should be given to devices that may be sensitive to power fluctuations 920 Battery mode The UPS is supplying battery power to connected equipment Controllable Outlet Group Icons Controllable Outlet Group Power Available The number next to the icon identifies the specific outlet groups that have available power ez ez Controllable Outlet Group Power Not Available The number next to the icon identifies specific outlet groups that do not have available power Battery Status Icons Battery Charge Status Indicates the battery charge status NI Battery Charge In Progress Indicates the battery is charging UPS Display Interface operation Use the UP DOWN buttons to scroll through the options Press the OK button to accept the selected option Press the ESC button to return to the previous menu Menu overview The UPS Display Interface has Standard and Advanced menu screens
29. n on page 15 Connect controllable outlet groups Connect critical equipment to one controllable outlet group Connect peripheral equipment to the other controllable outlet groups To conserve battery runtime during a power outage nonessential equipment can be configured to shut down Use Loadshed Time on Battery Enable Disable and Loadshed Time on Battery Setting defined in the General Settings section Refer to General settings on page 16 If equipment has dependent peripherals that must restart or shut down in a specific sequence such as an ethernet switch that must restart before a connected server can be restarted connect the devices to different outlet groups Each controllable outlet group can be configured independently of the other groups Use the Configuration menus to configure how the controllable outlet groups will react in the event of a power outage Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 19 Emergency Power Off Overview The Emergency Power Off EPO option is a feature that will immediately disconnect all connected equipment from mains power The UPS will immediately shut down and will not switch to battery power Connect each UPS to the EPO switch In configurations where multiple units are connected in parallel each UPS must be connected to the EPO switch The UPS must be restarted for power to return to connected equipment Press the ON OFF button on the front panel of the UPS A CAUTION
30. ol to a Warning or Caution product safety label indicates that a hazard exists that can result in injury and product damage if the instructions are not followed A CAUTION CAUTION indicates a potentially hazardous situation which if not avoided can result in minor or moderate injury CAUTION CAUTION addresses practices not related to physical injury including certain environmental hazards potential damage or loss of data Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Safety and General Information Adhere to all national and local electrical codes All wiring must be performed by a qualified electrician Changes and modifications to this unit not expressly approved by APC could void the warranty This unit is intended only for indoor use in a controlled environment Do not operate this unit in direct sunlight in contact with fluids or where there is excessive dust or humidity Be sure the air vents on this unit are not blocked Allow adequate space for proper ventilation For a UPS with a factory installed power cord connect the UPS power cable directly to a wall outlet Do not use surge protectors or extension cords The battery typically lasts for two to five years Environmental factors impact battery life Elevated ambient temperatures poor quality utility power and frequent short duration discharges will shorten battery life The equipment is heavy Always practice safe lifting techniques adequat
31. onditions 4 Acts of God 5 exposure to the elements or 6 theft In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered defaced or removed EXCEPT AS SET FORTH ABOVE THERE ARE NO WARRANTIES EXPRESS OR IMPLIED BY OPERATION OF LAW OR OTHERWISE APPLICABLE TO PRODUCTS SOLD SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED DIMINISHED OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF SEIT RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT S SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES IN NO EVENT SHALL SEIT ITS OFFICERS DIRECTORS AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT SPECIAL CONSEQUENTIAL OR PUNITIVE DAMAGES ARISING OUT OF THE USE SERVICE OR INSTALLATION OF THE PRODUCTS WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT IRRESPECTIVE OF FAULT NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES SPECIFICA
32. r Disconnect all internal and external batteries if applicable Tees im Follow the shipping instructions outlined in the Service section of this manual Service If the unit requires service do not return it to the dealer Follow these steps 1 Review the Troubleshooting section of the manual to eliminate common problems 2 Ifthe problem persists contact APC Customer Support through the APC web site www apc com a Note the model number and serial number and the date of purchase The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models b Call APC Support and a technician will attempt to solve the problem over the phone If this is not possible the technician will issue a Returned Material Authorization Number RMA c If the unit is under warranty the repairs are free d Service procedures and returns may vary internationally Refer to the APC web site for country specific instructions 3 Pack the unit properly to avoid damage in transit Never use foam beads for packaging Damage sustained in transit is not covered under warranty a Note When shipping within the United States or to the United States always DISCONNECT ALL UPS BATTERIES before shipping in compliance with U S Department of Transportation DOT and IATA regulations The internal batteries may remain in the UPS b Batteries may remain connected in the XLBP during shipment
33. reen and with or without a yellow stripe The ground conductor must be grounded to earth at the service equipment or if supplied by a separately derived system at the supply transformer or motor generator set Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Battery safety Before installing or replacing the batteries remove jewelry such as wristwatches and rings High short circuit current through conductive materials could cause severe burns Do not dispose of batteries by burning them The batteries may explode Do not open or mutilate batteries Released electrolyte is harmful to the skin and eyes and may be toxic Hardwire safety Verify that all branch circuit mains and low voltage control circuits are deenergized and locked out before installing cables or making connections whether in the junction box or to the UPS Wiring by a qualified electrician is required Check national and local codes before wiring Strain relief is required for all hardwiring not supplied All openings that allow access to UPS hardwire terminals must be covered Failure to do so may result in personal injury or equipment damage Select wire size and connectors according to national and local codes General information The UPS will recognize as many as 10 external battery packs connected to the UPS However there is no limit to the number of XLBPs that can be used with the UPS Note For each XLBP added increased recharge time will be req
34. settings may vary depending on the UPS model Output Lower 184 V for 208 V output 208 V 169 to 184 V Acceptable 201 Y 0 Y bun 310 b 155 E 2 M If the UPS input voltage is between the lower Voltage or outpu E x acceptable voltage and the higher acceptable voltage P 216 V for 240 V output 240 V 204 to 216 the UPS will operate in Green mode when enabled 220 V for 208 V output 208 V 220 to 235 V If the output voltage goes outside the acceptable range Output Upper d ee Ha the UPS will switch from Green mode to On Line Acceptable 242 V for 220 V output 220 V 242 to 253 V Voltage 253 V for 230 V output 230 V 253 to 265 mode or to Battery mode g 264 V for 240 V output 240 V 264 to 270 V Auto 50 60 x 3 Hz Auto 50 60 3 Hz Set the output frequency for the UPS Output 50 0 1 Hz Freak 50 3 0 Hz 60 0 1 Hz 60 3 0 Hz Output 1 Hz Sec 0 5 Hz Sec Select the rate of change for output frequency in Frequency 1 Hz Sec Hertz per second Slew Rate ne 4 Hz Sec Bypass Lower 160 V 208 V 160 to 184 V Acceptable 220 V 160 to 198 V Voltage 230 V 160 to 207 V 8 240 V 160 to 216 V If the UPS input voltage is between the lower acceptable voltage and the higher acceptable voltage Bypass Upper 250 V for 208 V output 208 V 220 to 250 V the UPS can enter Bypass mode when enabled Acceptable 255 V for 220 V output 220 V 242 to 264 V Voltage 265 V for 230 V output 230 V 253 to 270 V 8 270 V for 240 V output
35. ted battery modules in the UPS Slide the RBCs out of the UPS Slide the new RBCs into the UPS and connect the battery modules to the UPS Securely connect each battery module Press the battery connector into the UPS until it is firmly connected A battery that is not fully connected will cause erratic UPS operation abnormal error messages and connected equipment may not receive battery power during power outages After installing the RBC the UPS display interface may prompt the user to verify the status of the replaced battery modules If the battery module is new respond YES If the battery module is not new respond NO Recommended actions after installing new RBCs Verify that the UPS is connected to input power and the output power is turned on Refer to the Operation section in this manual for instructions Verify that the UPS load is greater than 400 watts This will appear on the UPS display interface screen Perform a UPS Self Test Verify on the UPS display interface that the installation dates for the replaced RBCs are set to the current date The installation dates can be changed manually on the UPS display interface If all RBCs have been replaced at the same time all installation dates can be changed simultaneously For configuration details refer to Battery Install Date on page 19 of this manual Allow the system to charge for 24 hours to ensure full runtime capability XLBP installation and replacement Refer to the Ext
36. ted runtime threshold is reached the Runtime UPS will shutdown the controllable outlet groups Disable Disable To conserve energy in the event of an overload Enable condition greater than 105 output the controllable Loadshed outlet groups will immediately turn off The Overload controllable outlet groups will only turn on again with a manual restart command once the overload condition has been corrected Config IP Address Manual DHCP Menu Mode BOOTP Network Refer to the Network Management Utility CD Manage IP Address Program IP Subnet Gateway 18 Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Controllable Outlet Groups Controllable Outlet Groups provide battery backup power to connected equipment Overview The controllable outlet groups can be configured using the Advanced menu options Refer to General settings on page 16 The controllable outlet groups can be configured to independently turn off turn on shutdown switch to Sleep mode and reboot connected equipment Turn Off Disconnect output power to connected equipment either immediately using the Turn Off Immediately feature or after a configured delay using the Turn Off With Delay feature NOTE Controllable outlet groups can be turned on only using the Turn On feature Turn On Connect output power to connected equipment either immediately using the Turn On Immediately feature or after a configured delay using the Turn On With Delay feature
37. tion the UPS and the output power are off White illumination the UPS and the LOAD output power are on Red illumination the UPS is and the output power is off Load icon Disable mute audible alarm icon UPS status information Operation mode icons ESCAPE button OK button UP DOWN buttons Controllable outlet group status icons 000 Battery status icons The icons on the LCD display interface screen may vary depending on the installed firmware version Load icon The approximate load capacity percentage is indicated by the number of load bar ef 0 0 0 sections illuminated Each bar represents 16 of the load capacity Xy Mute icon Indicates the audible alarm is disabled mute 2 UPS Status Information The status information field provides key information on the status of the UPS The Standard menu will allow the user to select one of the following screens The Advanced menu will scroll through the following five screens Input Voltage Output Voltage Output Frequency Load Runtime In the case of a UPS event status updates will be displayed defining the event or condition that has occurred The display screen illuminates amber to indicate a Warning and red to indicate an Alert depending on the severity of the event or condition 12 Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Operation Mode Icons On Line
38. tor that supports two input contacts and one output relay AP9810 Dry Contact I O Accessory optional Smart UPS On Line SRT8K 10K Tower Rack Mount 6U 21 Related Documents The Network Management Card Utility CD contains the following documentation UPS Network Management Card 2 User s Guide Network Management Card Upgrade Utilities Security Handbook PowerNet Management Information Base MIB Reference Guide IP Address Configuration 22 The default TCP IP configuration setting DHCP assumes that a properly configured DHCP server is available to provide TCP IP settings to the Network Management Interface If the Network Management Interface obtains an IPv4 address from a DHCP server use the UPS Display Interface menus About Interface to see the address To setup a static IPv4 address use the UPS Display Interface Config menu Set the IP address Subnet Mask and Gateway from the Config menu See the User s Guide on the Network Management Card Utility CD for user information about the Network Management Interface and for setup instructions Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Smart Battery Management Definitions Battery Module A string of battery cells arranged to produce a battery assembly with a connector Replaceable Battery Cartridge RBC An APC battery cartridge consisting of two battery modules Replacement RBCs can be ordered from the APC web site www apc com Smart External Battery Pack XL
39. uired The model and serial numbers are located on a small rear panel label For some models an additional label is located on the chassis under the front bezel Always recycle used batteries Recycle the package materials or save them for reuse Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Product Overview Specifications For additional specifications refer to the APC web site www apc com Environmental Operatin 0 to 40 C 32 to 104 F Temperature R 5 Storage 15 to 45 C 5 to 113 F Operati 0 3 000 m 0 10 000 ft Maximum Elevation oe A Storage 0 15 000 m 0 50 000 ft Humidity 0 to 95 relative humidity non condensing Protection Class IP 20 rating Note Charge the battery modules every six months during storage Environmental factors impact battery life Elevated ambient temperatures high humidity poor quality mains power and frequent short duration discharges will shorten battery life Physical The UPS is heavy Follow all lifting guidelines Lifting guidelines 255 kg 2120 Ib Unit weight without packaging 111 82 kg 246 Ib Unit weight with packaging Rack Mount models 130 kg 286 Ib Tower models 126 82 kg 279 Ib Unit dimensions without packaging 263 mm x 432 mm x 715 mm Height x Width x Depth 10 35 in x 17 in x 28 15 in Unit dimensions with packaging 461 mm x 600 mm x 1000 mm Height x Width x Depth 18 2 in x 23 62 in x 39 4 in
40. ut 1 220 230 240 Vac 44A 63 2 pole 63 A 2 pole 10 mm 10 mn 6 AWG 6 AWG 2 2 SRTSKXLI Input 3 380 400 415 Vac 15 A 20 4 pole 63 A 2 pole 2 5 mm 10 mm 12 AWG 6 AWG Output 1 220 230 240 Vac 38A 10 mm 10 mm 6 AWG 6 AWG Input 1 220 230 240 Vac 54A 80 A 2 pole 80 A 2 pole 16 mm 16 mm 4 AWG 4 AWG Input 3 380 400 415 Vac 18A 25 A 4 pole 80 A 2 pole 2 5 mm 16 mm SRTIOKXLI 12 AWG 4 AWG Output 1 220 230 240 Vac 47 10 mm 10 mm 6 AWG 6 AWG 10 Smart UPS On Line SRT8K 10K Tower Rack Mount 6U Connect Equipment A CAUTION DAMAGE TO EQUIPMENT OR PERSONNEL Disconnect the mains input circuit breaker before installing or servicing the UPS or connected equipment Disconnect internal and external batteries before installing or servicing the UPS or connected equipment The UPS contains internal and external batteries that may present a shock hazard even when disconnected from the mains UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time Disconnect equipment from the UPS before servicing any equipment Failure to follow these instructions can result in equipment damage and minor or moderate injury Note The UPS batteries will charge to 9096 capacity in the first three hours of normal operation Do not expect full battery runtime capability during this initial charge period 1 Connect the UPS to the building utility power Refer to t
41. web site www apc com The UPS Display Interface screen shows the message Waiting for Minimum Runtime The UPS has been configured to operate for a specified period of runtime The setting can be changed through the Config UPS menus UPS Display Interface Status screen shows Overload and the UPS emits a sustained audible alarm The UPS is experiencing an overload condition UPS Display Interface Status screen The UPS received a command to operate in Bypass mode The connected equipment exceeds the maximum load rating for the UPS The UPS will emit a sustained audible alarm until the overload condition is corrected Disconnect nonessential equipment from the UPS to correct the overload condition shows UPS is operating in Bypass mode No action is required The UPS has automatically switched to Bypass mode due to an internal UPS alert or warning The UPS Display Interface screen will show a message to identify the alert or warning and corrective action UPS Display Interface is red or amber and shows an alert or warning message The UPS emits a sustained audible alarm The UPS has detected a problem during normal operation The UPS Display Interface screen shows the message Disconnected Battery Follow the instructions on the UPS Display Interface screen Press any key to mute all alarms Be sure the battery cables are securely connected Perform a UPS Self Test to be sure the UPS detects