         Contents
1.       0000e cece eee cence 28  Measuring the DC bus voltage            0 0 cece eee eee 28  Installing the drive    0 2    0    ee eee 29  Installing the line reactor on ATV61HeeeY drives              00 e ee eee 29  Installing the line reactor on ATV61HeeeM3XD and ATV61ee N4D drives      29  Installing the transformer s  on ATV61HeeeY drives             002 000 30  Recommendations             0 00 cee ee ees 30  Installing the DC choke or the transformer s             000 0c eee eee eee 31  Example of installing a transformer on an ATV61HC25Y drive                34  POWER ia fusion ana wt ae tA ad ee eee ee od ER a ee GET 37  Power TerminalS    seus ss pras fob ia oe He DENG Seed 39  Access to the power terminals            0 0 00 e cece eee eee 39  Functions of power terminals              0 0 e eee eee 40  Accessing the power terminals on ATV61HeeeY drives                    41  Characteristics and functions of power terminals                    05  41  Maximum wire size and tightening torque               0    e eee eee 42  Control Terminals nesse as eea ace Mabaso een 2A oe a nn ce ee ee 43  Access to the control terminals              00 0  e eee ee eee 43  Operation on an IT system and corner grounded system                    47  Disconnecting filters         0 00 2 eee eee 49  Principle and precautions          0    eee teens 52  Drive settings  factory configuration             0    cece eee ee 53  Power switching via line contactor          0 0    eects 54  Statin
2.       Altivar 61 Drive  i Max   iaiia ct Part Number  is wit Careia Ea  Plate  Rating Current Rating  kW hp kA kA kA A  90 125 ATV61HD90N4 100 35 10 250  110 150 ATV61HC11N4 100 35 10 300 315  132 200 ATV61HC13N4 100 35 10 350  160 250 ATV61HC16N4 100 50 18 400  220 350 ATV61HC22N4 100 50 18 500  250 400 ATV61HC25N4 100 50 18 550 600  280 450 ATV61HC28N4 100 50 30 700  315 500 ATV61HC31N4 100 50 30 800  400 600 ATV61HC40N4 100 50 30 900  500 700 ATV61HC50N4 100 50 30 2x600 2  x630  630 900 ATV61HC63N4 100 50 30 2x800                      These power ratings are given for an ambient temperature of 45   C  113   F  and at the factory set switching  frequency of 2 5 kHz  used in continuous operation     The drives are provided with a DC choke as standard  The DC choke can be omitted by adding the letter D to  the catalog number  For example  ATV 61HD90N4 becomes ATV 61HD90N4D  A customer supplied input line  reactor must be used in place of the DC choke  See the installation manual for more information           2009 Schneider Electric USA All Rights Reserved 15    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Three phase motor 500 V to 690 V 4 2009    Three phase motor 500 V to 690 V    For drives with an input line voltage of 500 V to 690 V  a Class J time  delay or non time delay fuse is required  Table 3 shows the fuse size  required and available short circuit current rating associated with  each drive     Table 3  500 V to 690 V  50 60 Hz Th
3.     9 84     25 59     5 91     2 95     1 18     0 45  a  D75M3X  C11N4   163   360 1022 298 758 150 72 30 11 5 80  C13N4  D90M3X   14 17     40 23     11 73     29 84     5 91     2 83     1 18     0 45   176   C16N4  340   1190   285   920   150 75 30   115   MO 116  C11Y   C20Y  13 39     46 62     11 22     36 22     5 91     2 95     1 18     0 45   255   C22N4 440 1190 350 920 150 75 30 11 5 163   17 32     46 62     13 78     36 22     5 91     2 95     1 18     0 45   358   C25N4  C31N4    595   1190   540   920   150   75 30   11 5 207  C25Y   C40Y  23 43     46 62    21 26     36 22     5 91     2 95     1 18     0 45   455   22    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Dimensions and Weights    With 0 or 1 option card  1  With 2 option cards  1  ATV61H C40N4 to C50N4 AILV61HU63N4                J I H R CO m d A     x     Ri    o a ne    RU E  ae enn                                                                                                                                                                               1x8        14x9     E     4 E    377mm_  392 mm      le       lt e   ele   14 77 in   15 43 in  iii i x gi rt  a b G J J1 H K K1 K2    For Weight  ATV61H mm mm mm mm mm mm mm mm mm mm screws kg   in      in      in      in      in      in      in      in      in      in    Ib    C40N4 oa  890   1390   417   75   380   1120   150   75   30   11 5  Mo  70
4.     Disconnecting filters    ATV61H D90N4 to C13N4 and ATV61H C11Y to C20Y                    l Normal  e  filter connected               IT system   filter  disconnected         ATV61H C16N4 to C22N4                                   Eis Normal IT system      filter connected  x  filter disconnected       sm  44 TES  S L       NAO                                                                                                                                            dia o o  7  gt   o  O   5 N  o  lic b     O  Iy w  o ale    IIe     O  JO  olo o  lo       H             2009 Schneider Electric USA All Rights Reserved 49    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  4 2009    Disconnecting filters    ATV61H C25N4 to C31N4 and ATV61H C25Y to C40Y     IT system    Normal     filter disconnected        filter connected     Fpl ea                                                  A                                                              oh         0                                                                                                                                                                         o  JA oo oo  flo offs oo o Fr ES o trono   N N  ATV61HC40N4   Norma IT system  x  filter disconnected        filter connected                                                                                                                                                                                         ATV61HC50N4   IT system
5.    0 45    MO  176   330   950   285   920 15 11 5 80  C16N4D  12 99     37 4     11 22     36 22     0 59     045    M10  176   430   950   350   920 5 11 5 110  C22N4D  16 33     37 4     13 78     26 22     0 59     0 45    MO  242  585   950   540   920 15 11 5 140  C25N4D  C31N4D  23 03     37 4    21 26     36 22     0 59     0 45    MO  309                          24    2009 Schneider Electric USA All Rights Reserved    30072 452 65  4 2009                         Altivar   61 Variable Speed Drive Controllers Simplified Manual  Dimensions and Weights                                                                                                                                     With 0 or 1 option card  1  With 2 option cards  1  ATV61H C40N4D to C50N4D ATV61H C63N4D  SE  k TT E ED   ER  q U  a T  5x       6x            r 4 E i  th fil  377 mm 392 mm     L G a G      G ale G gl        14 84 in      15 43 in  a a  a b G H F    For Weight  ATV61H mm   mm   mm   mm mm mm screws kg   in      in      in      in    in    in    Ib    C40N4D 215  880   1 150   417 5   1 120   415 11 5 M10  474    35 65     54 72     16 44     44 09     16 34     0 45 225  C50N4D   496   1 110   1 150   532 5   1 120   532 5 11 5 300  C63N4D  43 49     54 72     20 96     44 09     20     045    M10  661                             1 For the addition of I O extension cards  communication cards  the multi pump card or the  Controller Inside   programmable card           2009 Schneider Electric
6.    FRF    Drive at fallback speed       FST    Fast stop       NLP    No line power  no line supply on L1  L2  L3        NST    Freewheel stop       OBR    Auto adapted deceleration       PRA    Power Removal function active  drive locked        RDY    Drive ready       RUN    Drive running       SOC    Controlled output cut in progress       TUN    Auto tuning in progress       USA       Undervoltage alarm    The first time the drive is powered on  the user is automatically  guided through the menus as far as  1  DRIVE MENU      The parameters in the  1 1 SIMPLY START  submenu must be  configured before the motor is started up  To optimize performance   perform an auto tune  see Table 10 on page 66      Only the  1 1 SIMPLY START  menu is described in this document   For more information about the content of the other menus  consult  the Programming Manual and the CD ROM supplied with the drive           2009 Schneider Electric USA All Rights Reserved    57    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Drive state codes 4 2009    Figure 11  First time drive power on menu    Displayed for 3 seconds following  power up    ATV61HU22N4    2 2kW 3HP 380 480V  Config  n  1       3 seconds t    English Switches to  5 LANGUAGE  menu    automatically     Select the language and press ENT        Chinese    Switches to  2 ACCESS LEVEL     menu  consult the Programming  i Manual on the CD ROM supplied    with the drive     Select the access level and p
7.    Figure 7  Connecting a 500 V 50 Hz or 600 V 60 Hz supply  transformer  use X2A     Parking position  T  X2B    X2A    4  Used position    Figure 8  Connecting a 690 V 50 Hz supply transformer   use X2B     Parking position  T  X2A  X2B  4  Used position    The ATV61HC50Y to ATV61HC80Y models include 2 transformers   Set up this connection for each transformer     A CAUTION    DRIVE TRANSFORMER DAMAGE    Ensure the transformer connection corresponds to the line voltage           Failure to follow these instructions can result in injury or  equipment damage                 36    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Wiring    Wiring    Power    Ground the drive to local and national code requirements  A minimum  wire size of 13 29 mm   6 AWG  may be required to meet standards  limiting leakage current     A DANGER    HAZARD OF ELECTRIC SHOCK  EXPLOSION  OR ARC  FLASH    Ground equipment using the provided ground connecting point as  shown in the figure below  The drive panel must be properly  grounded before power is applied     Failure to follow these instructions will result in death or  serious injury                 e Ensure that the resistance of the ground is 1 O or less     e  f grounding several drives you must connect each one directly  as  shown in the figure above     e Do not loop the ground cables or connect them in series          2009 Schneider Electric USA All Ri
8.   250 MCM  10 AWG    360 Ib in 360 Ib in 360 Ib in 212 Ib in 12 Ib in  ATV 61HC25N4 4x 185mm    __ 4x 185 mm    4x 185 mm       5 5 mm    ATV 61HC31N4  41 Nem 41 Nem 41 Nem 1 4 Nem  ATV 61HC25Y  ATV 61HC31Y 3x 350 MOM   __ 3x350 MCM   3x350MCM      10 AWG  ATV 61HC40Y   360 Ib in 360 Ib in 360 Ib in 12 Ib in  4x 185mm    __ 4x 185 mm    8 x 185 mm       5 5 mm     41 Nem 41 Nem 41 Nem 1 4Nem  ATV 61HC40N4  4 x 500 MCM 4x500 MCM   4x500MCM    __ 10 AWG    360 Ib in 360 Ib in 360 Ib in 12 Ib in    2x2x 185 mm   4 x 185 mm    8 x 185 mm     __ 5 5 mm     41 Nem 41 Nem 41 Nem 1 4Nem  ATV 61HC50N4  es 4x500 MCM  4x500MCM   4x500MCM      10 AWG   360 Ib in 360 Ib in 360 Ib in 12 Ib in  be 2x4x185mm  6x 185mm   8x185mm      5 5 mm    41 Nem  41 Nem  41 Nem 1 4 Nem  ATV 61HC63N4  o 3x 500 MCM  5x500MCM   5x500MCM      10 AWG   360 Ib in 360 Ib in 360 Ib in 12 Ib in  M 4 x 185 mm  6x185mm   8x185mm      5 5 mm  1 4  ATV 61HC50Y  41 Nem  41 Nem  41 Nem Nem  ATV 61HC63Y  ATV 61HC80Y ua 3x 500 MCM  5x500MCM   5x500MCM     10 AWG   360 Ib in 360 Ib in 360 Ib in 12 Ib in  42    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Control Terminals    Control Terminals  Access to the control terminals    1  To access the control terminals  open the  cover on the front panel of the control  section     2  To make it easier to wire the drive control  section  remove the control terminal card  by loosening the s
9.   serious injury                 1 The word drive as it is used in this manual refers to the controller portion of the  adjustable speed drive as per the NEC           2009 Schneider Electric USA All Rights Reserved 7    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65    Before you begin    3 2009       A WARNING          LOSS OF CONTROL      The designer of any control scheme must consider the potential    failure modes of control paths and  for certain critical control  functions  provide a means to achieve a safe state during and  after a path failure  Examples of critical control functions are  emergency stop and overtravel stop     e Separate or redundant control paths must be provided for critical    control functions     e System control paths may include communication links     Consideration must be given to the implications of unanticipated  transmission delays or failures of the link     e Each implementation of an Altivar 61 drive must be individually    and thoroughly tested for proper operation before being placed  into service     Failure to follow these instructions can result in death  serious  injury  or equipment damage           1    For additional information refer to NEMA ICS 1 1  latest edition      Safety Guidelines for  the Application  Installation  and Maintenance of Solid State Control    and to NEMA ICS  7 1  latest edition      Safety Standards for Construction and Guide for Selection   Installation and Operation of Ad
10.   x  filter disconnected     Normal     filter connected                                                                            pe a  OO lo T ont o NO Oe    i HO                                                                                                                                                                                                    o ot o  o o O o  HAN E dk  o Oo          50    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Disconnecting filters    ATV61HC63N4 and ATV61H C50Y to C80Y          Normal x IT system       filter connected      filter disconnected                                                                                                                                                                                                     2009 Schneider Electric USA All Rights Reserved 51    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Electromagnetic Compatibility  Wiring 4 2009    Electromagnetic Compatibility  Wiring    Principle and precautions    Important  The high frequency equipotential ground connection  between the drive  motor  and cable shielding does not eliminate the  need to connect the ground  PE  conductors  green yellow  to the  appropriate terminals on each unit  To help accomplish this  the user  must follow the following points     Grounds between the drive  motor  and cable shielding must have  h
11.  61 Variable Speed Drive Controllers Simplified Manual  3 2009 Before you begin    Before you begin    Read and understand these instructions before performing any  procedure on this drive        A DANGER    HAZARD OF ELECTRIC SHOCK  EXPLOSION  OR ARC  FLASH    e Read and understand this manual before installing or operating  the Altivar 61 drives  Installation  adjustment  repair  and  maintenance must be performed by qualified personnel    e The user is responsible for conforming to all applicable code  requirements with respect to grounding the equipment    e Many parts in this drive  including printed circuit boards  operate  at the line voltage  DO NOT TOUCH  Use only electrically  insulated tools    e DO NOT short across DC bus capacitors or touch unshielded  components or terminal strip screw connections with voltage  present    e Before servicing the drive        Disconnect all power including external control power that  may be present before servicing the drive        Place a    DO NOT TURN ON    label on the drive disconnect        Lock disconnect in the open position        WAIT 15 MINUTES for the DC bus capacitors to discharge   Then follow the DC bus voltage measurement procedure on  page 28 to verify that the DC voltage is less than 42 V  The  drive LEDs are not indicators of the absence of DC bus  voltage     e Install and close all covers before applying power or starting and  stopping the drive     Failure to follow these instructions will result in death or
12.  USA All Rights Reserved    25    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65                                                                                                                                                                                                       Dimensions and Weights 4 2009  With 0 or 1 option card  1  With 2 option cards  1  ATV61H C11Y to C20Y ATV61H C25Y to C40Y with braking  a a 670  26 37   x  i Dne m  se   c  t o   _      _      ___      __       L i  i ial  l  x    8x9       e RES 2 e k     1          a  377 mm 392 mm   G   540 mm  21 26 in    14 77 in   15 43 in  E       1025mm 27 5mm   403in   1 08in   a b G H K K1 K2    For Weight  ATV61H mm   mm   mm   mm mm   mm   mm   mm Screws kg   in      in      in    in    in    in    in    in    Ib    340   1 190    285 920 150 75 30 11 5 110  C11Y   c20Y  13 39    46 62     11 22     36 22     5 91     2 95     1 18     0 45  M10  242   595  1 190    540 920 150 75 30 11 5 190  C25Y   C40Y  23 43    46 62     21 26     36 22     5 91     2 95     1 18     0 45  Mae  418                                   26    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Dimensions and Weights                                                                                                                         With 0 or 1 option card  1  With 2 option cards  1  ATV61H C50Y to C80Y  e a   
13.  careta o teed eta si abas des E Pb ce eens Bae aud a wl ai eed slau a Ra ED    54  Test on a low power motor or without a motor  using motors in parallel       55      2009 Schneider Electric USA All Rights Reserved 3    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65    3 2009   Graphic Display Terminal             0 00 c cece tees 56  Drive sState codes    isa suar ee Se bee Pee ete Spee 57  Integrated Display Terminal             0    eee ett 59  Access to  Menus 24 2 cae eee ook ec ie dee Reed eee een ee 60  Macro configuration   2 ass pos Ria set tata  vate ease ea Ge Ges 62  Parameters that can be changed while the drive is running or stopped          67  Drive does not start  no detected fault code displayed                        68  Conditions requiring a power reset        0 0    cee eee 68  Auto Reset Conditions  customer configured              0 0 cece eee eee 71  Auto Reset Conditions           0    cece tenes 75       4    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  3 2009 Hazard Categories and Special Symbols    Hazard Categories and Special Symbols    The following symbols and special messages may appear in this  manual or on the equipment to warn of potential hazards or to call  attention to information that clarifies or simplifies a procedure     A lightning bolt or ANSI man symbol in a    Danger    or    Warning    safety  label on the equipme
14.  catalog   The braking resistor is connected on the braking unit           2009 Schneider Electric USA All Rights Reserved 41    Altivar   61 Variable Speed Drive Controllers Simplified Manual    30072 452 65                                                                            Maximum wire size and tightening torque 4 2009  Maximum wire size and tightening torque  Table 6  Wire size and tightening torque  R L1 1   R L1 2   L1 R  L2 S   S L2 1 U T1  V T2 RO  SO  Drive terminals       4  gt   PC    PAM  PA  PB aces  L3 T S L2 2  W T3 7    TO  T L3 1   T L3 2  ATV 61HD55M3X  2x 100mm      2 x 100 mm    2 x 100 mm    60mm    5 5 mm    ATV 61HD75M3X   24 Nem 24 Nem 41 Nem 12 Nem 1 4Nem  ATV 61HD9ON4    2 x 250 MCM   __ 2x 250 MCM   2 x 250 MCM   250 MCM    10 AWG  ATV 61HC11N4    212 Ib in 212 Ib in 360 Ib in 106 bin  12 Ib in  2x 100mm    __ 2 x 100 mm    2 x 150 mm    60mm    5 5 mm    ATV 61HD90M3X  24 Nem 24 Nem 41 Nem 12 Nem 1 4 Nem  ATV 61HC13N4   2x250MCM   2x250 MCM   2 x 250 MCM    250 MCM    10 AWG    212 bin 212 Ib in 360 Ib in 106 Ib in  12lbin  ATV61HC16N4 2x120mm    __ 2x 120 mm    2 x 120 mm    120 mm    5 5 mm    ATV 61HC11Y  24 Nem 24 Nem 41 Nem 24 Nem 1 4Nem  ATV 61HC13Y  ATV 61HC16Y 2x250MCM   __ 2 x 250 MCM    2 x 250 MCM   250 MCM   10 AWG  ATV 61HC20Y   212 Ib in 212 Ib in 360 Ib in 212 Ib in 12 b in  2x 150mm    _ 2x 150 mm    2 x 150 mm    120 mm    5 5 mm     41 Nem 41 Nem 41 Nem 24 Nem 1 4Nem  ATV 61HC22N4  2x 350 MOM   __ 2 x 350 MCM   2 x 350 MCM 
15.  ing J1 J J1 E  elas  1                   4  m          ams      E S  L    ia q    i E     14x     o q o          377 mm 392 mm   G G     14 77 in   15 43 in  a kre                For the addition of I O extension cards  communication cards  the multi pump card or the  Controller Inside   programmable card           2009 Schneider Electric USA All Rights Reserved 27    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  DC Bus Voltage Measurement Procedure 4 2009    DC Bus Voltage    Measurement Procedure    Measuring the DC bus voltage    A DANGER       HAZARD OF ELECTRIC SHOCK  EXPLOSION  OR ARC  FLASH    Read and understand the instructions on page 7 before performing  this procedure     Failure to follow these instructions will result in death or  serious injury           The DC bus voltage can exceed 1 000 V    Use a properly rated  voltage sensing device when performing this procedure  To measure  the DC bus voltage     1   2   3     Disconnect the drive power supply   Wait 15 minutes to allow the DC bus to discharge     Measure the voltage of the DC bus between the PO and PC   terminals to ensure that the voltage is less than 42 V       If the DC bus capacitors do not discharge completely  contact    your local Schneider Electric representative  Do not repair or  operate the drive        28       2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Installing th
16.  mounted side    by side  observing the following mounting recommendations     NOTE  The  enclosure size and  ventilation must be  considered since  drives dissipate a lot  of heat  The  dimensions on this  page indicate the  minimum free space  required around the  drives when  adequate forced  cooling is provided   For more information  about enclosure  mounting  refer to  the installation  manual on the  CD ROM provided  with the drive        2250                                                             2 250    21000   i             2009 Schneider Electric USA All Rights Reserved    Altivar   61 Variable Speed Drive Controllers Simplified Manual                                                                                                    30072 452 65                                                                                                       Dimensions and Weights 4 2009  Dimensions and Weights  With or without 1 option 2 option cards  1  Common front view ATV 61HC25N4  HC31N4  card  1  with braking unit VW3 A7 101  Front view  a g 670  26 37     m       x  Le L _ v T a  S i 1    i U   q    j j7    8x8       pRS E n E   Hi m  377 mm 392 mm E G A 540 mm  21 26 in    14 77 in   15 43 in  102 5 mm 27 5 mm       4 03in   1 08 in   a b G H K K1 K2    Weight  For  ATV61H mm   mm mm   mm   mm   mm   mm   mm screws kg   in      in      in      in      in      in      in      in    Ib    60  D55M3X  D9ON4  320 920 250 650 150 75 30 11 5  132   Do  12 60     36 22 
17.  on the drive nameplate or in document  30072 451 38 to achieve published short circuit current ratings    e Do not connect the drive to a power feeder whose short circuit  capacity exceeds the controller short circuit current rating listed  on the controller nameplate or in document 30072 451 38        Failure to follow these instructions can result in death   serious injury  or equipment damage                 38       2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Power Terminals       CAUTION    IMPROPER USE OF A BRAKING RESISTOR    Wire the thermal protection contact on the resistor so that the drive  power supply is disconnected immediately in the event of a  detected fault  refer to the manual supplied with the resistor         Failure to follow these instructions can result in equipment  damage              Power Terminals  Access to the power terminals    To access the power terminals  unscrew the front panel and remove  the cover     Figure 9  Accessing power terminals    Terminals for DC choke    Fan power supply DC bus power supply                                                                                    Power section line supply    Output to the motor    Connections to ground    Output to braking resistor   up to ATV61HC16N4 rating only           2009 Schneider Electric USA All Rights Reserved 39    Altivar   61 Variable Speed Drive Controllers Simplified Manual 3007
18.  the motor thermal  small for the application current parameter  Check the motor load   Overload setting Wait for the motor to cool down before  incorrect for the motor restarting   full load rating  Output phase loss  see  OPF I   72    2009 Schneider Electric USA All Rights Reserved    30072 452 65    Altivar   61 Variable Speed Drive Controllers Simplified Manual                               4 2009 Auto Reset Conditions  customer configured   Table 13  Auto Reset Conditions  customer configured   continued   Code Name Probable cause Remedy  OFF      1 motor phase loss    Loose connection   Check the connections from the drive to  causing loss of one the motor   phase at controller output  OPF 2    3 motor phase loss    Motor not connected or   Check the connections from the drive to  motor power too low the motor     Output contactor open   If an output contactor is being used     Instantaneous instability consult the Programming Manual on the  in the motor current CD ROM supplied with the drive      Test on a low power motor or without a  motor  In factory settings mode  motor  phase loss detection is active   Output Phase Loss   OPL     Yes   YES    To check the drive in a test or  maintenance environment without having  to switch to a motor with the same rating  as the drive  particularly useful in the case  of high power drives   deactivate motor  phase loss detection  Output phase loss    OPL     No   nO       Check and optimize the parameters   Rated motor volt    U
19.  to follow these instructions can result in injury or  equipment damage                    2009 Schneider Electric USA All Rights Reserved 47    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65       Operation on an IT system and corner grounded system 4 2009  A WARNING       RISK OF ELECTRIC SHOCK    ATV61HCeeeY drives must not be connected on a corner grounded  system     Failure to follow these instructions can result in death  serious  injury or equipment damage              IT system  Isolated or impedance grounded neutral  Use a  permanent insulation monitor compatible with non linear loads  such  as a Merlin Gerin type XM200     Altivar 61 drive controllers feature built in common mode RFI  EMC   filters  When an ATV61HCeeY drive controller is operating on an  isolated or resistance grounded electrical distribution system  the  filters must be isolated  disconnected   For any other drive controller  referenced in this manual the filter should be isolated  disconnected      Corner Grounded System  The ATV61HCeeY drive controllers must  never be connected on a corner grounded electrical distribution  system  When any other drive controller referenced in this manual is  connected to a corner grounded electricaldistribution system the  filters must be isolated  disconnected         48       2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Disconnecting filters
20.  to open it  or handle it  Handle with care           Failure to follow these instructions can result in death or  serious injury           A WARNING    DAMAGED DRIVE EQUIPMENT    Do not operate or install any drive or drive accessory that appears  damaged        Failure to follow these instructions can result in death or  serious injury                    2009 Schneider Electric USA All Rights Reserved 17    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Unpacking and Handling 4 2009    Unpacking and Handling    The packaging contains one or more items depending on the model     e ATV61HeeeM3X and ATV61HeeeN4 comprises the drive and a DC  choke    e ATV61HeeM3XD and ATV61 HeeeN4D comprises the drive only    e ATV61HeeeY comprises the drive and one or two transformers    In Figure 1  the drive and the DC choke or transformer s  are    mounted on a pallet with screws  A   The DC choke or transformer s   are supplied pre assembled for easy transport     Figure 1  Unpacking and handling the drive    DC choke or transformer s                                   18       2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Unpacking and Handling    The unit should be unpacked in the following order  see Figure 1 on   page 18     1  Disassemble the components of the DC choke or transformer s    B  for installation later  and use a hoist to remove the choke or  transformer
21. 072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Macro configuration    The following table describes the codes  adjustment range  and    factory settings     Table 10  Codes  adjustment range  and factory settings     2 wire   2C         2 wire   2C    3 wire   3C     2 wire control AN Example of source wiring   Maintained control     24 un tx   LM  forward   Maintained closed to run Lix  reverse   and maintained opened to   stop    3 wire control  ATV 64   Example of source wiring    Pulse control   A forward or   24 i 2 ix    reverse pulse is sufficient to EINE LM  stop  command starting  a stop Li2  forward  pulse is sufficient to Lix  reverse  command stopping     To change the assignment of  2 3 wire control   tCC  press and hold the ENT key for 2 s  The   2 wire type   tCt  function and the functions assigning the logic inputs and analog inputs will  return to the factory settings  The selected macro configuration will reset  losing its custom  settings     A DANGER    UNINTENDED EQUIPMENT OPERATION    e Ensure that this parameter is configured before configuring the  1 6 COMMAND   Ctl   and   1 7 APPLICATION FUNCT    FUn       e Ensure that this assignment change is compatible with the wiring scheme used  For more  information  consult the CD ROM with the drive     Failure to follow these instructions will result in death or serious injury                 2009 Schneider Electric USA All Rights Reserved 63    Altivar   61 Variable Spee
22. 1 Safety function as defined by IEC61508        Ensure that the motor is present during  auto tuning    If an output contactor is being used  close it  during auto tuning        70       2009 Schneider Electric USA All Rights Reserved    30072 452 65    4 2009    Altivar   61 Variable Speed Drive Controllers Simplified Manual  Auto Reset Conditions  customer configured     Auto Reset Conditions  customer configured     A DANGER    LOSS OF PERSONNEL AND EQUIPMENT PROTECTION  FEATURES    e Enabling the fault inhibition  InH  will disable the drive protection  features     e InH should not be enabled for typical applications of this  equipment    e InH should be enabled only in extraordinary situations where a  thorough risk analysis demonstrates that the presence of  adjustable speed drive protection features poses a greater risk  than personnel injury or equipment damage     Failure to follow these instructions will result in death or  serious injury              Table 13 lists the conditions that can be reset with the automatic  restart function after the cause has been removed  These conditions  can also be reset by turning the drive off then on again  or by means  of a logic input or control bit  consult the Programming Manual on the  CD ROM supplied with the drive      The following conditions can be inhibited and cleared remotely by  means of a logic input or control bit  APF  CnF  COF  EPF1  EPF2   FCF2  LFF2  LFF3  LFF4  nFF  ObF  OHF  OLC  OLF  OPF1  OPF2   OSF  OtF1  
23. 2 452 65  Functions of power terminals 4 2009    Functions of power terminals                                           Terminals Function Drive   3x   Ground connection terminals All ratings   R L1     S L2     T L3  Power section line supply All ratings   PO DC choke connection Aa ESRA ns   PO 1  PO 2 DC choke connection ATV61H C40N4  C63N4   PA   DC bus   polarity and DC choke connection All ratings   PC  DC bus     polarity All ratings   PA Output to braking resistor ATV61H D55M3X  D90M3X    PB Output to braking resistor ATV61H D90N4 to C22N4    U T1     V T2   W T3 Outputs to the motor All ratings   RO   0  70 te DO bus tr the CD ROM supplied wits he  ATVETH D75M3X  D9OM3X    BU   BU    and   polarities to be connected to the braking unit   ATV61H C25N4 to C63N4   refer to the User s Manual   X20  X92  X3 Braking unit control cable connection for the braking unit        1 ATV61H C40N4 to C63N4 drives have two input bridges  The power section AC supply is connected on    terminals R L1 1     R L1 2  S L2 1     S L2 2 and T L3 1     T L3 2     2 From the ATV61HC25N4 upwards  there are no braking resistor connection terminals on the drive as the  braking unit is optional  please refer to the catalog   The braking resistor is connected on the braking unit        40    2009 Schneider Electric USA All Rights Reserved    Altivar   61 Variable Speed Drive Controllers Simplified Manual  Accessing the power terminals on ATV61HeeY drives    30072 452 65  4 2009    Accessing the pow
24. 4    35 04     54 72     16 44     2 76     14 96     14 09     5 91    2 95     1 18     0 45  330  C50N4   726   ce3n4   1120   1390   532 5   70   495   1120   150   75   30   115   M10 435   44 09     54 72     20 96     2 76     1949     44 09     5 91     2 95     1 18     0 45   957     1 For the addition of I O extension cards  communication cards  the multi pump card or the  Controller Inside     programmable card           2009 Schneider Electric USA All Rights Reserved 23    Altivar   61 Variable Speed Drive Controllers Simplified Manual                                                                                                                   30072 452 65                                                                                                                                                    Dimensions and Weights 4 2009  With 0 or 1 option card  1  With 2 option cards  1  ATVOR Si ervey i ATV 1 eenn to can Nab  with braking uni  4x  s  4x    e  mS   mo A               m it        ir    r     l r e E  l STA     G TIE 97 5 540 mm  21 17 in        22 5  Ee ane    a  3 82 in  560 mm  26 87 in   0 88 in   a b G H h    For Weight  ATV61H mm   mm   mm   mm mm mm Screws kg   in     in     n     in     in     in   Ib    D55M3XD  D90N4D ae  310   680   250   650 15 11 5 mio  132    12 20     26 77     9 84     25 59     0 59     0 45  74  D75M3XD  C11N4D  163   350   782   298   758 12 11 5 80  C13N4D  DIOM3XD    13 78     30 79     11 73     29 84     0 47  
25. ACb   Reverse   This parameter can be used to reverse the rotation direction of the motor without reversing the  wiring        Parameters that can be changed while the drive is running or stopped    Table 11    Parameters that can be changed while the drive is running or  stopped    Name Description Factory setting    HE H    Mot  therm  current  Oto 1 1 0r1 2In   Varies with the     1  according to drive rating   rating       Motor thermal overload current  to be set to the rated current indicated on the nameplate    Acceleration  0 1t09999s   3 0s       Time to accelerate from 0 to the  Rated motor freq    FrS   page 65   Ensure that this value is  compatible with the inertia being driven      Deceleration  0 1 to 999 9 s 3 0s          Time to decelerate from the  Rated motor freq    FrS   page 65  to 0  Ensure that this value is  compatible with the inertia being driven     L5P   Low speed  0  Motor frequency at minimum reference  can be set between 0 and  High speed   HSP       High speed        Motor frequency at maximum reference  can be set between  Low speed   LSP  and   Max frequency   tFr   The factory setting changes to 60 Hz if   Standard mot  freq   bFr     60 Hz    60          1     In    corresponds to the rated controller current indicated in the installation manual and on  the controller nameplate           2009 Schneider Electric USA All Rights Reserved 67    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Detected Faults and Tr
26. CONTACTOR SWITCHING    e Avoid operating the contactor frequently to avoid premature  aging of the filter capacitors     e Do not have cycle times less than 60 seconds        Failure to follow these instructions can result in equipment  damage              NOTE  The factory setting for the programming parameter    2 wire type  is set to  Transition   when input line power is applied   n 5 may display as the drive state and the controller will not start   This could indicate that a run command was present before the input  line power was applied and a transition or change of state must be  made to this command before the drive will start     If it is desired that the drive starts when the input line power is applied  without a transition of the run command  make the following change  to the program configuration  Go to the menu    1 5 Inputs Outputs CFG  and change parameter  2 wire type  from   Transition  to  Level   When the change is made  the drive can begin       54       2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Test on a low power motor or without a motor  using motors in parallel    running immediately on application of the input line power if a run  command is present  For more information  see page 58     Test on a low power motor or without a motor  using motors in parallel    Consult the Programming Manual on the CD ROM supplied with the  drive           2009 Schneider El
27. Instruction Bulletin  30072 452 65    Retain for future use     Altivar   61  Variable Speed Drive Controllers  Simplified Manual    75 125 hp  55 90 kW    200 240 V  125 900 hp  90 630 kW    380 480 V  125 800 hp  110 800 kW    500 690 V    For Use in the United States of America       Schneider    LF Electric    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  4 2009       2    2009 Schneider Electric All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual    3 2009    TABLE OF CONTENTS       Hazard Categories and Special Symbols                 00 0c eee eee eee 6  Please  Note    Sirrini dice oka eet ba ek dio eee alee Oa eh ad oe 7  Before  you  begin  asia beri eee kee lit lea iin i ae ed 8  Product Suppolts   curas ssa de ee Be ee nee ede tee pater PE Bae AR 10  Output Interrupting Rating            0    eee ete ee 12  Input Withstand Current Rating  without line reactor or choke                 12  Drive Containment Rating with OCPD             0 0 0 e eee eee 13  Three phase motor 200 V to 240 VV    Lees 14  Three phase motor 380 V to 480 V     6  es 15  Three phase motor 500 V to 690 V     a 16  Handling and storage            cee tte 17  Unpacking and Handling            0    eee tt eee 18  Before You Begin             0  eee eee ees 20  Mounting recommendations             0 0 0 cee eee eee 21  Dimensions and Weights             2 0    cece ete 22  DC Bus Voltage Measurement Procedure        
28. OtF2  OtFL  PHF  PtF1  PtF2  PtFL  SLF1  SLF2  SLF3   SPIF  SSF  tUF  and ULF  consult the Programming Manual on the  CD ROM supplied with the drive         Table 13    Auto Reset Conditions  customer configured   Code Name Probable cause Remedy  APF  Application fault    Controller Inside card   Check the card programming  Refer to the  card documentation   EnF    Com  network    Communication   Check the environment  electromagnetic       interruption compatibility       Check the wiring      Check the time out      Replace the option card      Contact Schneider Electric Product  Support              O 2009 Schneider Electric USA All Rights Reserved 71    Altivar   61 Variable Speed Drive Controllers Simplified Manual    Auto Reset Conditions  customer configured     30072 452 65  4 2009       Table 13  Auto Reset Conditions  customer configured   continued   Code Name Probable cause Remedy  COF  CAN com   Interruption in   Check the communication bus   communication on the   Check the time out   CANopen bus   Refer to the CANopen user s manual   EFF      External fit LI Bit  An external device    Correct the device and reset the drive     depending on user                                              E PF      External fault com   A communication   Correct the communication network and  network reset the drive   FCF      Out contact  open   The output contactor   Check the contactor and its wiring   remains open although   Check the feedback circuit   the closing condition
29. S  menu     Contact Schneider Electric Product  Support   SL F 1    Modbus com    Interruption in   Check the communication bus     ER     PowerSuite com      communication on the  Modbus bus    Communication with  PowerSuite    software      Check the time out     Refer to the Modbus User s Manual      Check the PowerSuite connecting cable     Check the time out        at Ea     HMI com      Communication with the  graphic display terminal      Check the terminal connection     Check the time out        SP hE     PI Feedback     PID feedback below the  lower limit      Check the PID function feedback      Check the PID feedback supervision  threshold and time delay  consult the  Programming Manual on the CD ROM  supplied with the drive            SSF    E JF     Torque current lim      IGBT overheat     Switch to torque limitation    Drive overheated      Check if there are any mechanical  problems      Consult the Programming Manual on the  CD ROM supplied with the drive     e Check the size of the load  motor  and  controller      Reduce the switching frequency      Wait for the drive to cool before restarting        ULF        Proc  Underload Flt        Process underload         Check and remove the cause of the  underload      Consult the Programming Manual on the  CD ROM supplied with the drive        74       2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Auto Reset Conditions    A
30. Support   time meas   electronic time  measurement component  In FE    internal  CPU  Internal microprocessor Turn off the drive to reset  Contact Schneider  event Electric Product Support   DCF    Overcurrent  Motor parameters are not Check the motor parameters   set correctly Check the size of the motor  controller  and load   Excessive inertia or load Check the state of the mechanism   Mechanical locking  Pre Power Detected fault with the Contact Schneider Electric Product Support   removal  drive   s Power Removal  safety function   SCF     Motor Short circuit or grounding Check the cables connecting the drive to the  short circuit  at the drive output motor  and the insulation of the motor  Perform the diagnostic tests via the  Significant ground leakage  1 10 DIAGNOSTICS  menu   SCF 2    Impedant current at the controller Reduce the switching frequency   sh  circuit  output if several motors Connect chokes in series with the motor   SEF 3    Ground are connected in parallel  short circuit   SOF _    Overspeed  Instability Check the motor  gain and stability parameters   Overhauling load Add a braking resistor   Check the size of the motor  controller  and load   SPF _    Speed Encoder feedback signal Check the wiring between the encoder and the  Feedback missing  drive   Loss  Check the encoder   E nF    Auto tuning   Special motor  or motor Ensure that the motor and drive are compatible           power not suitable for the  drive   Motor not connected to the  drive    
31. aling of drive  status     Installation of a  load reactor or  motor filter is  recommended for  all 575 V  installations     Install interference suppressors on all inductive circuits near the drive  or coupled to the same circuit  such as relays  contactors  and    solenoid valves      e Use shielded cable for PWR input connections     e See page 52 for factory configurations for logic inputs  analog    inputs  relays and analog inputs       46       2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Operation on an IT system and corner grounded system    Power terminal connection diagram  ATV61H C50N4  C63N4  C50Y  C63Y and C80Y    1 Line reactor  if used  for ATV61H   M3X and  ATV61H   N4  This line reactor is compulsory  for ATV61He Y drives  to be ordered  separately  if a special transformer is not used   for example  12 pulse            ATV61H C25N4 to C63N4 and ATV61H C25Y to C80Y    For these drive ratings  braking resistors are connected to the  external braking unit  Please refer to the braking unit User s Manual     Drive supplied by the DC bus  Consult the CD ROM supplied with the drive     Operation on an IT system and corner grounded system       A CAUTION    RISK OF DAMAGE TO THE DRIVE    Certain precautions have to be taken when using the drive on an IT  system  please refer to the Installation Manual on the CD ROM  supplied with the drive for more information        Failure
32. als section on page 44 for more information about the  Power Removal Input     Failure to follow these instructions will result in death or  serious injury           CAUTION    INCOMPATIBLE LINE VOLTAGE    Before turning on and configuring the drive  ensure that the line  voltage is compatible with the supply voltage range shown on the  drive nameplate  The drive may be damaged if the line voltage is  not compatible        Failure to follow these instructions can result in equipment  damage              NOTE  The Power Removal function takes priority over any run  command  For use as an emergency stop  this function requires the  use of connection diagrams conforming to category 3 of standard  EN 954 1 and safety integrity level 2 according to IEC EN 61508   Consult the ATV61 Installation Manual on the CD ROM supplied with  the drive        20    2009 Schneider Electric USA All Rights Reserved    30072 452 65  4 2009    Altivar   61 Variable Speed Drive Controllers Simplified Manual  Mounting recommendations    Mounting recommendations    ATV61HD55M3X to ATV61HD90M3X  ATV61HD90N4 to    ATV61HC63N4  ATV61HC611Y to ATV61HC80Y          Figure 2   N 9     A                           WV                   7    ATV61H x2   D55M3X   D90M3X    D90N4  C11N4 100  100  C13N4   C22N4    C11Y   C20Y FOO  11100  C25N4  C31N4    C25Y   C40Y 150   200  C40N4  C50N4 250 1300  C63N4  C50Y   c80Y  250  400       All dimensions are in mm        When forced cooling is provided  These drives can be
33. ansformer s  on ATV61HeeeY drives    ATV61H CeeY to C80Y drives are supplied with one or two  transformers to power the fan  The transformer s  must be installed  on top of the drive and wired in accordance with the  recommendations set out in this document     Recommendations    If the safety of personnel requires the prohibition of unwanted or  unintended operation  electronic locking is performed by the Altivar  61   s Power Removal function     This function requires the use of connection diagrams conforming to  category 3 of standard EN 954 1 and safety integrity level 2  according to IEC EN 61508  refer to the catalog or the CD ROM  supplied with the drive   The Power Removal function takes priority  over any run command        A CAUTION    INCOMPATIBLE LINE VOLTAGE       Before turning on and configuring the drive  ensure that the line  voltage is compatible with the supply voltage range shown on the  drive nameplate  The drive may be damaged if the line voltage is  not compatible     Failure to follow these instructions can result in injury or  equipment damage                 30    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Installing the DC choke or the transformer s     Installing the DC choke or the transformer s     Figure 3  Installing DC chokes on an ATV61HC22N4 drive                              Mountthe DC choke chassis  1  on the wall  on top of the drive   Ensure th
34. ar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Example of installing a transformer on an ATV61HC25Y drive    Location of transformers              ATV61HC11Y to C20Y mm   ATV61HC25Y to C40Y   61HC25Y to C40 ml  ATV61HC50Y to C80Y Emo   1 to 2 transformers can be connected as illustrated in the following  examples   Table 5  Drive and transformer combinations  Drive Number of transformers  ATV61HC11Y to C20Y 1  ATV61HC25Y to C40Y 1  ATV61HC50Y to C80Y 2    Figure 6  Examples of drive and transformer combinations    Example 1  Example 2   ATV61H C11Y to C20Y ATV61H C25Y to C40Y    Unused XO connectors are put into the parking position    Grounding  strips          Transformer connectors    Example 3   ATV61H C50Y to C80Y    Unused X0 connectors are put into the parking position                                                                                                                                                       z  ma         e e  eal I e 9 o        q HOS   rae  Tolo    RSE i  E   o                                                       Transformer connectors Grounding strips          O 2009 Schneider Electric USA All Rights Reserved 35    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Example of installing a transformer on an ATV61HC25Y drive 4 2009    Each transformer is equipped with a 500 V 600 V connector and a  690 V connector  See Figure 7 and Figure 8  The unused connector  is put into the parking position  
35. arted  compliance with functional  safety standard EN 954 1 and IEC EN 61508      NOTE  AO   temperature change       Arrangement of the control terminals    Logic input switch    Factory    Sink       setting   Int Source             LI6 input switch   Factory  PTC   L   setting   f LI    Maximum wire size   2 5 mm   14 AWG           RJ45 connector Max  tightening torque     0 6 Nem  5 3 Ib in           0000000000          Note  The ATV61 controller is supplied with links between the PWR and  24 terminals  and the Al1  and COM terminals           2009 Schneider Electric USA All Rights Reserved 45    Altivar   61 Variable Speed Drive Controllers Simplified Manual  Connection diagrams    Connection diagrams           30072 452 65  4 2009       CAUTION       CONTROLLER DAMAGE    ATV71HCeeyY drive controller installations        A 3 5  impedance input line reactor is required on all    Failure to follow these instructions can result in equipment          damage   ATV61ee0e NOTE  Line reactor  if required  for  3 phase supply ATV61HeeeM3X and ATV61HeeN4  This line    reactor is compulsory for ATV61HeeeY drives  to  be ordered separately  if a special transformer is    not used  for example  12 pulse               Reference  potentiometer  Braking resistor    if used    Line reactor is  required for 575 V  installations     Refer to the drive  nameplate or  document  30072 451 38 or  to Tables 1  2  3 of  this document for  recommended  fuses     Rirelay contacts  for remote  sign
36. at the chassis is tightly secured to the drive to maintain  the IP54 seal of the ventilation duct     e Install the DC choke  2  on the chassis  1  using the nuts  provided    e Connect the choke between the PO and PA   terminals on the  drive  see Figure 4 on page 33     e Connect the grounding strip between the DC choke chassis  1   and the drive           2009 Schneider Electric USA All Rights Reserved 31    Altivar   61 Variable Speed Drive Controllers Simplified Manual  Installing the DC choke or the transformer s     30072 452 65    4 2009    e Mount the cover  3  on the chassis and secure it with the nuts  provided       Mount panels  5  and  6  using the screws provided     Once the choke has been installed  the degree of protection for the  top of the drive is IP31     NOTE  The number of DC chokes supplied with the drive varies    according to the drive rating     Between 1 and 4 chokes can be connected in parallel as illustrated in  the following examples                                            Table 4  Drive and choke combinations   Drive Number of chokes in parallel Choke model  ATV61HD55M3X  D75M3X 1 DC CHOKE 5  ATV61HD90M3X 1 DC CHOKE 6  ATV61HD90N4  C11N4 1 DC CHOKE 1  ATV61HC13N4 1 DC CHOKE 2  ATV61HC16N4 1 DC CHOKE 4  ATV61HC22N4 2 DC CHOKE 1  ATV61HC25N4 2 DC CHOKE 3  ATV61HC31N4 2 DC CHOKE 4  ATV61HC40N4 3 DC CHOKE 3  ATV61HC50N4 4 DC CHOKE 2  ATV61HC63N4 4 DC CHOKE 7  32    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Va
37. ax  30 V   power supply   Power 30 W  OV Logic input common and 0 V of ov  external P24 power supply  Li Programmable logic inputs     424V    SW1 Switch State 0 State 1  Li2  max  30 V  Source  lt 5V  SAVE  LI3   Impedance 3 5   factory  Ll4 kQ setting   LI5   Reaction time   2ms 0 5 ms Sink Int or  gt 16V   lt 10V   Sink Ext  LI6 Depending on the position of the   SW2   LI  factory setting         SW2 switch   LI  Programmable logic input  or  PTC  Input for PTC probes          Same characteristics as logic inputs LI1 to LI5  SW2   PTC      Trip threshold 3 KQ  reset threshold 1 8 KQ     Short circuit detection threshold  lt  50 Q       NOTE  AO   temperature change       44       2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Access to the control terminals    Table 7  Characteristics and functions of the control terminals  continued     Terminals   Function Electrical characteristics        24 Logic input power supply SW1 switch in Source or Sink Int position      Internal  24 V    power supply  min  21 V  max  27 V    protected against short circuits and overloads     200 mA max    SW1 switch in Sink Ext position      Input for external  24 V     power supply for the logic  inputs   PWR Power Removal input    24V     max  30 V      Impedance 1 5 kQ      State 0 if  lt  2 V  state 1 if  gt  17 V    Reaction time  10 ms          When PWR is not connected to 24 V  the motor cannot be st
38. crew until the spring is  fully extended     3  Remove the card by sliding it downwards        NOTE  For control wiring the maximum wire  size is 2 5 mm   14 AWG   The maximum  tightening torque is 0 6 Nem  5 3 Ib in      A DANGER    UNINTENDED EQUIPMENT OPERATION    The accidental grounding of logic inputs configured for Sink Logic  can result in unintended activation of drive functions     e Protect the signal conductors against damage that could result in  unintentional conductor grounding     e Follow NFPA 79 and EN 60204 guidelines for proper control  circuit grounding practices     Failure to follow these instructions will result in death or  serious injury              CAUTION    IMPROPERLY SECURED TERMINAL CARD    When replacing the control terminal card  it is essential to fully  tighten the captive screw  Torque the captive screw to 1 1 to 1 7  Nem  9 7 to 15 Ib in         Failure to follow these instructions can result in equipment  damage                    2009 Schneider Electric USA All Rights Reserved 43    Altivar   61 Variable Speed Drive Controllers Simplified Manual    Access to the control terminals       30072 452 65  4 2009                                  Table 7  Characteristics and functions of the control terminals  Terminals   Function Electrical characteristics  R1A 1 relay logic output  one N C  Minimum switching capacity  3 mA for 24 V    R1B contact and one N O  contact with   Maximum switching capacity   R1C common point  R1A to R1C is   on res
39. ct Schneider Electric Product Support        76       2009 Schneider Electric USA All Rights Reserved    Altivar   61 Variable Speed Drive Controllers Simplified Manual    Instruction Bulletin    Schneider Electric USA  8001 Knightdale Blvd   Knightdale  NC 27545 USA  1 888 SquareD  1 888 778 2733   www Schneider Electric us    Electrical equipment should be installed  operated  serviced  and  maintained only by qualified personnel  No responsibility is assumed  by Schneider Electric for any consequences arising out of the use of  this material     30072 452 65  O 2009 Schneider Electric All Rights Reserved    3 2009    
40. ctions on page 44     E 6 Select the language  page 58    if the drive is equipped with a graphic display terminal     E 7 Configure the menu   SIMPLY START   SIM    page 61        2 wire or 3 wire control            Macro configuration    Motor parameters  ce Optimize performance     To optimize performance     Refer to the auto tuning section on 66       Motor thermal current    NOTE  Ensure that the wiring of the  drive is compatible with its  configuration       Acceleration and deceleration ramps      Speed variation range       E 8 Start           2009 Schneider Electric USA All Rights Reserved 11    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Short Circuit Marking System Applied to Schneider Electric AC Drives 4 2009    Short Circuit Marking System Applied to  Schneider Electric AC Drives    Altivar drives have a prospective short circuit rating that is based on  three performance attributes that affect all drives  The performance  attributes are characterized by three rating parameters described  below and listed in Tables 1 3 on pages 14 16  The overall  maximum rating of the drive is the lowest of the three ratings  Higher  ratings can be attained for Altivar drives  Contact Schneider Electric  for tested combinations of overcurrent protective devices  OCPD    line reactors  and enclosures or refer to the Altivar 61 and 71  Supplementary Short Circuit Protection Information bulletin shipped  with the drive     Output Interrupting Ra
41. d Drive Controllers Simplified Manual 30072 452 65  Macro configuration 4 2009    Table 10  Codes  adjustment range  and factory settings  continued     Name Description Adjustment range   Factory setting     Macro configuration   Pumps Fans   PnF         Start Stop   StS   Start stop    Gen  Use   GEn   General use    PID regul    Pld   PID regulation   Network C    nEt   Communication bus   Pumps Fans   PnF   Pumps fans    To change the assignment of  Macro configuration   CFG  press the ENT key for 2 s     A DANGER    UNINTENDED EQUIPMENT OPERATION  Ensure that the selected macro configuration is compatible with the wiring scheme used     Failure to follow these instructions will result in death or serious injury         Customized macro     Read only parameter  visible only if at least one macro configuration parameter has been  modified     e  Yes   YES      Standard mot  freq   50 Hz IEC   50           50 Hz IEC   50   IEC  e  60 Hz NEMA   60   NEMA    This parameter modifies the presets of the following parameters     Rated motor power   nPr    Rated motor volt    UnS    Rated mot  current   nCr    Rated motor  freq    FrS    Rated motor speed   nSP  and  Max frequency   tFr   see below  and  Mot  therm   current   ItH  and  High speed   HSP   see page 67      Input phase loss  Varies with the drive  rating         Ignore   nO   A detected phase loss is ignored  To be used when the drive is supplied via a  single phase supply or by the DC bus     Freewheel   YES   A de
42. e drive    Installing the drive    e Mount the drive on a wall or the back of the enclosure in  accordance with the recommendations described in this  document  before installing the DC choke or transformer s      e Mount the DC choke or the transformer s  on the back of the  enclosure or on the wall above the drive and connect it them up   Installation and connection instructions are given on page 31 for  the choke and page 34 for the transformer s     e Make sure that the seal between the drive and the choke or  transformer is properly seated     Installing the line reactor on ATV61HeeeY drives  The use of an AC line reactor  which must be ordered separately  is    mandatory on these drives if a special transformer is not used  for  example  12 pulse         CAUTION    CONTROLLER DAMAGE       A 3 5  impedance input line reactor is required on all  ATV61HCeeY drive installations     Failure to follow these instructions can result in equipment  damage              Installing the line reactor on ATV61HeeeM3XD and ATV61eeN4D drives    ATV61H D55M3XD to D9OM3XD and ATV61H D90N4D to C63N4D  drives are supplied without a DC choke  A minimum 3  impedance  input line reactor  ordered separately  must be used for connecting   these drives to a three phase line supply           2009 Schneider Electric USA All Rights Reserved 29    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Installing the transformer s  on ATV61HeeeY drives 4 2009    Installing the tr
43. ectric USA All Rights Reserved 55    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Display Terminals 4 2009    Display Terminals    Graphic Display Terminal    The graphic display terminal can be disconnected and connected  remotely  for example  on the door of an enclosure  using the cables  and accessories available as options     1 Graphic display    2 Function keys    F1  F2  F3  F4  7 ESC key     Cancels a value  a parameter  or a menu to return to the  previous selection    3 STOP RESET  button    4 RUN button 6 Button for reversing the    rotation direction of the motor             5 Navigation button       Press  ENT     To save the current value    To enter the selected menu or parameter      Turn CW CCW    To increase or decrease a value    Togoto the next or previous line    Toincrease or decrease the reference if control  via the graphic display terminal is activated    NOTE  Buttons 3  4  5  and 6 can be used to control the drive directly   if control via the graphic display terminal is activated        56    2009 Schneider Electric USA All Rights Reserved    30072 452 65  4 2009    Drive state codes    Table 9     ACC    Altivar   61 Variable Speed Drive Controllers Simplified Manual    Drive state codes    Drive state codes    Acceleration       CLI    Current limiting       CTL    Controlled stop on input phase loss       DCB    DC injection braking in progress       DEC    Deceleration       FLU    Motor fluxing in progress    
44. egul    Network C    Pumps Fans   output  AM Ref 1 channel    Ref 1 channel   Ref 1 channel   Ref 2 channel   Ref 1 channel    PID reference    Ref 1 channel     integrated Modbus   Al2 No   Summing ref  2  PID feedback   No   Ref 1B channel   AO1  Motor freq    Motor freq   Motor freq   Motor freq    R1 No drive fit   No drive fit  No drive fit  No drive fit   R2 No   No  No  No   LI  2 wire    Forward   Forward   Forward  Forward   LI2  2 wire    Fault reset   Reverse  Fault reset   Fault reset   LI3  2 wire    No   Jog   PID integral reset    Ref  2 switching     Ref 1B switching   LI4  2 wire    No   Fault reset  2 preset PID ref     Forced local   Fault reset   LI5  2 wire    No   Torque limitation    4 preset PID ref     No   LI6  2 wire   No   No  No  No   LI1  3 wire   Stop Stop Stop Stop  LI2  3 wire    Forward   Forward  Forward  Forward   Forward   LI3  3 wire    Fault reset   Reverse  Fault reset  Fault reset   No   LI4  3 wire    No   Jog  PID integral reset    Ref  2 switching    Ref 1B switching   LI5  3 wire    No   Fault reset  2 preset PID ref     Forced local   Fault reset   LI6  3 wire    No   Torque limitation    4 preset PID ref     No   No   The assignment of inputs LI1 to LI6 differs in 3 wire control    4 Factory settings  NOTE  All settings listed in the preceding table can be modified   adjusted and reassigned  Consult the ATV61 Programming Manual  on the CD ROM supplied with the drive   62       2009 Schneider Electric USA All Rights Reserved    30
45. enclosure structure  This  rating applies to drives with a listed enclosure rating or to drives that  have a listed enclosure rating with the addition of conduit box     A DANGER    HAZARD OF ELECTRIC SHOCK  EXPLOSION  OR ARC  FLASH    e Only use the overcurrent protective device marked on the drive  or in the manual        Do not operate the drive on an input mains line with a prospective  input short circuit current greater than the Drive Containment  Rating    e Ensure that the drive has a listed enclosure rating or uses the  conduit kit to achieve an enclosure rating     Failure to follow these instructions will result in death or  serious injury              Use of the drive with different prospective short circuit currents may  be possible  Contact Schneider Electric for tested combinations of  OCPD  line reactors  drives and enclosures or refer to the Altivar 61  and 71 Supplementary Short Circuit Protection Information bulletin  shipped with the drive           2009 Schneider Electric USA All Rights Reserved 13    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Three phase motor 200 V to 240 V 4 2009    Three phase motor 200 V to 240 V  For drives with an input line voltage of 200 V to 240 V  a Class J time  delay or non time delay fuse is required     Table 1 on page 14 shows the maximum available short circuit  current value for each of the rating parameters     Table 1  200 V to 240 V 50 60 Hz Three Phase Supply Voltage          Altiva
46. er terminals on ATV61HeeeY drives    To access the power terminals  unscrew the front panel and remove  the cover     Figure 10  Accessing power terminals    DC bus power supply    Fan power supply                                                                                  Power section line supply  Output to the motor  Connections to ground   Output to braking resistor  up to                      ATV61HC20Y rating only   Characteristics and functions of power terminals  Terminals Function Drive  3x   Ground connection terminals All ratings  R L1     S L2     T L3  Power section line supply All ratings  PA   DC bus   polarity and DC choke connection All ratings  PC  DC bus     polarity All ratings  PA Output to braking resistor 2  ATV61H C11Y to C20Y   PB Output to braking resistor       UT     V T2     W T3    Outputs to the motor    All ratings       Separate fan supply when the drive is only powered by          RO  SO  TO the DC bus ATV61H C11Y to C80Y  BU   BU    and   polarities to be connected to the braking unit  ATV61H C25Y to C80Y   i 7 7  refer to the User s Manual  X20  X92  X3 Braking unit control cable connection for the braking unit           1 ATV61H C50Y to C80Y drives have two input bridges  The power section AC supply is connected on terminals  R L1 1     R L1 2  S L2 1     S L2 2 and T L3 1      T L3 2     2 From the ATV61HC25Y upwards  there are no braking resistor connection terminals on the drive as the braking  unit is optional  please refer to the
47. et to 60 Hz      Nom motor speed  0 to 60000 rpm Varies with the drive  rating              Rated motor speed given on the nameplate    0 to 9999 rpm and 10 00 to 60 00 krpm on the integrated display terminal    If  rather than the rated speed  the nameplate indicates the synchronous speed and the slip in Hz  or as a    calculate the rated speed as follows         eli 9  Nominal speed   Synchronous speed x 100   slip as a    o 50     slip in Hz  Nominal speed   Synchronous speed x  gt p  50 Hz motors   or    Nominal speed   Synchronous speed x     amp 0 slipinhz  60 Hz motors      Max frequency  10 to 1000 Hz       The factory setting is 60 Hz  or preset to 72 Hz if  Standard mot  freq   bFr  is set to 60 Hz    The maximum value is limited by the following conditions      It must not exceed 10 times the value of  Rated motor freq    FrS      Values between 500 Hz and 1000 Hz are possible only in V F control and for powers limited to  37 kW  50 HP  for ATV61Heee and 45 kW  60 HP  for ATV61Weee  In this case configure   Motor control type   Ctt  before  Max frequency   tFr               2009 Schneider Electric USA All Rights Reserved 65    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Macro configuration 4 2009    Table 10  Codes  adjustment range  and factory settings  continued     Name Description Adjustment range   Factory setting     Auto tuning   No   nO     A DANGER    HAZARD OF ELECTRIC SHOCK  EXPLOSION  OR ARC FLASH    e During auto tuni
48. ghts Reserved 37    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65    Power    4 2009       A WARNING       IMPROPER WIRING PRACTICES   e The ATV61 controller will be damaged if input line voltage is  applied to the output terminals  U T1 V T2 W T3     e Check the power connections before energizing the ATV61 drive     e If replacing another drive  verify that all wiring connections to the  ATV61 controller comply with all wiring instructions in this  manual     Failure to follow these instructions can result in death  serious  injury  or equipment damage              Where local and national codes require upstream protection by  means of a residual current device  use a Type A device for single   phase drives and a Type B device for three phase drives as defined  in the IEC 60755  Choose a suitable model integrating     e Harmonic Frequency  HF  current filtering    e A time delay that helps prevent tripping caused by the load from  stray capacitance on power up  The time delay is not possible for  30 mA devices  in this case  choose devices with immunity  against nuisance tripping     If the installation includes several drives  provide one residual current  device per drive        A WARNING    INADEQUATE OVERCURRENT PROTECTION    e Overcurrent protective devices must be properly coordinated     e The Canadian Electrical Code and the National Electrical Code  require branch circuit protection  Use the over current protective  device recommended
49. igh frequency equipotentiality    When using shielded cable for the motor  use a 4 conductor cable  so that one wire will be the ground connection between the motor  and the drive  Size of the ground conductor must be selected in  compliance with local and national codes  The shield can then be  grounded at both ends  Metal ducting or conduit can be used for  part or all of the shielding length  provided there is no break in  continuity    When using shielded cable for the Dynamic Brake  DB  resistors   use a 3 conductor cable so that one wire will be the ground  connection between the DB resistor assembly and the drive  Size  of the ground conductor must be selected in compliance with local  and national codes  The shield can then be grounded at both  ends  Metal ducting or conduit can be used for part or all of the  shielding length  provided there is no break in continuity     When using shielded cable for control signals  if the cable is  connecting equipment that is close together and the grounds are  bonded together  then both ends of the shield can be grounded  If  the cable is connected to equipment that may have a different  ground potential  then ground the shield at one end only to  prevent large currents from flowing in the shield  The shield on the  ungrounded end may be tied to ground with a capacitor  for  example  10 nF  100 V or higher  in order to provide a path for the  higher frequency noise     Keep the control circuits away from the power circuits  For c
50. istive load  cos q   1   5 A for 250 V a or 30 V V    N O   R1B to R1C is N C     on inductive load  cos q   0 4 and L R   7 ms    ROA 7 relay lai 2 A for 250 V a or 30 V    relay logic output Max  response time  7 ms  0 5 ms  R2C one N O  contact Electrical service life  100 000 operations   10  10 V    power supply for    10 V    10 5 V  0 5 V   reference potentiometer 1 to   10 mA max   10 KQ  AM  Differential analog input Al e    10 to  10 V    max  safe voltage 24 V   AM    Reaction time  2 ms  0 5 ms  11 bit resolution   1 sign bit  e Accuracy  0 6  for AO   60   C  140   F   linearity  0 15   of max  value  COM Analog I O common ov  Al2 Depending on the software   Analog input 0 to  10 V     configuration   max  safe voltage 24 V   impedance 30 kQ  Analog voltage or current input   Analog input XY mA  X and Y programmable from 0 to  20 mA  impedance 250 Q    Reaction time  2 ms  0 5 ms  e 11 bit resolution  accuracy  0 6  for AQ   60   C  140   F    linearity 0 15  of max  value  COM Analog I O common ov  AO1 Depending on the software   Analog output 0 to  10 V c  min  load impedance 50 KQ  configuration    Analog output X Y mA  X and Y can be programmed from  Analog voltage or current output 0 to 20 mA  max  load impedance 500 Q  or logic output   10 bit resolution  reaction time  2 ms  0 5 ms  e Accuracy  1  for AO   60   C  140   F   linearity  0 2  of  max  value    Logic output  O or 10 V  O to 20 mA  P24 Input for external  24 V c control     24 V    min  19 V  m
51. justable Speed Drive Systems              2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  3 2009 Product Support       CAUTION    RISK OF PERMANENT DAMAGE TO DRIVE       e If no power is applied to the drive for a long period  the  performance of its electrolytic capacitors will be reduced     e Apply power to the drive every two years using the following  procedure  Without a motor connected to the drive  gradually  increase the voltage using an adjustable AC source connected  between drive terminals L1 and L2         25  of rated voltage for 30 minutes      50  of rated voltage for 30 minutes      75  of rated voltage for 30 minutes      100  of rated voltage for at least 5 hours  e Check the drive operation before placing into service     Failure to follow these instructions can result in equipment  damage              Product Support    For more information  call  fax  or write     Schneider Electric AC Drives Product Support Group  8001 Knightdale Blvd  Knightdale  NC 27545    For support and assistance  contact the Product Support Group  The  Product Support Group is staffed Monday through Friday from   8 00 am until 6 00 pm Eastern time to assist with product selection   start up  and diagnosis of product or application problems   Emergency phone support is available 24 hours a day  365 days a  year     Toll free  1 888 SquareD  1 888 778 2733   E mail  drive products support   us schneide
52. nS  and   Rated mot  current    nCr  and perform an   Auto tuning   tUn     OSF    Mains overvoltage    Line voltage too high   Check the line voltage   e Disturbances in the line  supply  OEF      PTC1 overheat    Overheating of the PTC1    Check the motor load and motor size   probes detected   Check the motor ventilation     e Wait for the motor to cool before  Dt Fo    PTC2 overheat    Overheating of the PTC2 restarting   probes detected   Check the type and state of the PTC  DE FL    PTC LI6 overheat    Overheating of PTC probes   probes detected on input  LI6   PEF     PTC1 probe  e PTC1 probes open or   Check the PTC probes and the wiring  short circuited between them and the motor controller   PEF      PTC2 probe    PTC2 probes open or  short circuited  PEFL   LIG PTC probe    PTC probes on input LI6  open or short circuited  SEF  4   IGBT short circuit    Power component   Perform a test via the              1 10 DIAGNOSTICS  menu   Contact Schneider Electric Product  Support           O 2009 Schneider Electric USA All Rights Reserved    73    Altivar   61 Variable Speed Drive Controllers Simplified Manual    Auto Reset Conditions  customer configured     30072 452 65  4 2009       Table 13  Auto Reset Conditions  customer configured   continued   Code Name Probable cause Remedy  SC FS    Motor short circuit    Short circuit at drive   Checkthe cables connecting the controller  output to the motor  and the motor insulation     Perform a test via the   1 10 DIAGNOSTIC
53. ng  the motor operates at rated current     Do not service the motor during auto tuning                      Failure to follow these instructions will result in death or serious injury     A DANGER    UNINTENDED EQUIPMENT OPERATION      The following motor parameters must be correctly configured before starting auto tuning    Rated motor volt    UnS    Rated motor freq    FrS    Rated mot  current   nCr     Rated motor speed   nSP   and  Rated motor power   nPr     e  f one or more of these parameters is modified after auto tuning has been performed  Auto  tuning  tUn  will be set to  No  and the procedure must be repeated           Failure to follow these instructions will result in death or serious injury                  No   nO   Auto tuning not performed     Yes   YES    Auto tuning is performed as soon as possible  then the parameter automatically   changes to  Done   dOnE      Done   dOnE   Use of the values given the last time auto tuning was performed    Important     Itis essential that all motor parameters    Rated motor volt    UnS     Rated motor freq    FrS    Rated mot  current    nCr    Rated motor speed   nSP     Rated motor power   nPr    are configured correctly before starting auto tuning   If one or more of these parameters is modified after auto tuning has been  performed   Auto tuning   tUn  will return to  No   nO  and the procedure must be  repeated   Auto tuning is performed only if no stop command has been activated  If a freewheel  stop or fast sto
54. ng power to the drive after the  cause of the condition has been removed        68    2009 Schneider Electric USA All Rights Reserved    30072 452 65    Altivar   61 Variable Speed Drive Controllers Simplified Manual                                              4 2009 Conditions requiring a power reset  Al2F  EnF  SOF  SPF  and tnF conditions can also be reset remotely  by means of a logic input or control bit  consult the Programming  Manual on the CD ROM supplied with the drive     EnF  InFA  InFb  SOF  SPF  and tnF conditions can be inhibited and  cleared remotely by means of a logic input or control bit  consult the  Programming Manual on the CD ROM supplied with the drive    Table 12  Conditions requiring a power reset  Code Name Probable cause Remedy  A 12 F    Al2 input    Al2 signal out of range Check the wiring of analog input Al2 and the  value of the signal   4b OF    DBR overload      Incorrect DB resistor Check the size of the resistor and wait for it to cool  settings down   Check parameters  DB Resistor Power   brP  and   DB Resistor value   brU   consult the CD ROM  supplied with the drive    bUF    DB unit   Short circuit output from Check the wiring of the braking unit and the  sh  Circuit  braking unit resistor   Check the braking resistor   Cr F      Precharge    Charging relay control Turn the drive off and then back on again   condition or charging Check the internal connections   resistor damaged Contact Schneider Electric Product Support   Crre  Thyr  
55. nt indicates an electrical hazard which  as  indicated below  can or will result in personal injury if the instructions  are not followed     The exclamation point symbol in a safety message in a manual   indicates potential personal injury hazards  Obey all safety messages   introduced by this symbol to avoid possible injury or death   Symbol Name    Lightning Bolt       ANSI Man       Exclamation Point          PY     A DANGER    DANGER indicates an imminently hazardous situation which  if not  avoided  will result in death or serious injury           A WARNING    WARNING indicates a potentially hazardous situation which  if not  avoided  can result in death or serious injury              A CAUTION    CAUTION indicates a potentially hazardous situation which  if not  avoided  can result in minor or moderate injury                    2009 Schneider Electric USA All Rights Reserved 5       Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Please Note 3 2009       CAUTION    CAUTION  used without the safety alert symbol  indicates a  potentially hazardous situation which  if not avoided  can result in    property damage                 Please Note    Electrical equipment should be installed  operated  serviced  and  maintained only by qualified personnel  No responsibility is assumed  by Schneider Electric for any consequences arising out of the use of  this material           2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar  
56. ntact Schneider Electric Product Support                          2009 Schneider Electric USA All Rights Reserved    69    Altivar   61 Variable Speed Drive Controllers Simplified Manual    Conditions requiring a power reset       30072 452 65  4 2009                                                             Table 12  Conditions requiring a power reset  continued   Code Name Probable cause Remedy  In F 4    Internal MFG Internal data inconsistent Contact Schneider Electric Product Support to  area  have the drive recalibrated   In FE    Internal  The option installed in the Check the catalog reference and compatibility of  option  controller is not recognized the option   In F 7    Internal  Initialization of the drive is Turn off the drive to reset   hard init   incomplete  In FB    Internal  The control section power Check the control section power supply   ctrl supply  supply is incorrect  In F 4    Internal  The current measurements Replace the current sensors or the power card     measure  are incorrect Contact Schneider Electric Product Support   In FA    Internal  The input stage is not Perform the diagnostic tests via the  mains circuit  operating correctly  1 10 DIAGNOSTICS  menu   Contact Schneider Electric Product Support   In F h    Internal  The drive temperature Replace the temperature sensor   th  sensor  sensor is not operating Contact Schneider Electric Product Support   correctly  In FC    Internal  Detected fault on the Contact Schneider Electric Product 
57. ontrol  and speed reference circuits  use of shielded twisted cables with a  pitch of between 25 and 50 mm  0 98 and 1 97 in   is  recommended    Ensure maximum separation between the power supply cable   line supply  and the motor cable and also ensure maximum  separation between the control cables and any power cables        52       2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Setup   Preliminary Recommendations      The motor cables must be at least 0 5 m  20 in   long     e Do not use surge arresters or power factor correction capacitors  on the variable speed drive output     e  f using an additional input filter  refer to the Installation Guide for  more information     e For installation of the EMC plate provided with the drive and  instructions for meeting EN55011 Class A directive  refer to the  Installation Guide     Setup   Preliminary Recommendations    Drive settings  factory configuration     The Altivar 61 drive is factory set for the following operating                            conditions    Table 8  Factory configurations   Macro configuration Pumps fans   Motor frequency 50 Hz   Motor control type Energy saving variable torque applications  Normal stop mode on deceleration ramp   Stop mode  Freewheel  in the event of a detected fault   Linear  acceleration  and     3s   deceleration ramps   Low speed 0 Hz   High speed 50 Hz   Motor thermal current Rated drive curren
58. oubleshooting 4 2009    Detected Faults and Troubleshooting    Drive does not start  no detected fault code displayed    e If the display does not light up  check the power supply to the  drive    e If the drive displays  Freewheel   nSt  or  Fast stop   FSt    The Fast Stop and Freewheel functions help prevent the drive  from starting if the corresponding logic inputs are not powered up   This is normalthese functions are active at zero so that the drive  will stop if there is a wire break    e Make sure that the run command input or inputs are activated  according to the selected control mode          2 3 wire control   tCC  parameter  described on page 63         2 wire type   tCt  parameter  described on page 54 and in the  ATV61 programming manual on the CD ROM supplied with  the drive     Conditions requiring a power reset    A DANGER    LOSS OF PERSONNEL AND EQUIPMENT PROTECTION    FEATURES   e Enabling fault inhibition  InH  will disable the drive protection  features    e InH should not be enabled for typical applications of this  equipment     e InH should be enabled only in extraordinary situations where a  thorough risk analysis demonstrates that the presence of  adjustable speed drive protection features poses a greater risk  than personnel injury or equipment damage     Failure to follow these instructions will result in death or  serious injury              Table 12 on page 69 lists the conditions requiring a power reset  A  power reset is accomplished by cycli
59. p function has been assigned to a logic input  this input must be set  to 1  active at 0    Auto tuning takes priority over any run or prefluxing commands  which will take  effect after the auto tuning sequence   If auto tuning is unsuccessful  the drive displays  No   nO  and  depending on the  configuration of  Autotune fault mgt   tnL   consult the CD ROM supplied with the  drive   may switch to  Auto tuning   tnF  detected fault   Auto tuning may last for 1 to 2 seconds  Do not interrupt  wait for the display to  change to  Done   dOnE  or  No   nO    NOTE  During auto tuning the motor operates at rated current        66    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Parameters that can be changed while the drive is running or stopped    Table 10  Codes  adjustment range  and factory settings  continued     Name Description Adjustment range   Factory setting        Auto tuning status   Not done   tAb            for information only  cannot be modified      Not done   tAb   The default stator resistance value is used to control the motor    Pending   PEnd   Auto tuning has been requested but not yet performed     In Progress   PrOG   Auto tuning in progress     Failed   FAIL   Auto tuning unsuccessful     Done   dOnE   The stator resistance measured by the auto tuning function is used to  control the motor      Output Ph rotation   ABC   AbC        e  ABC   AbC   Forward   e  ACB   
60. parameters in other menus may change the   1 1 SIMPLY START   SIM   parameter settings     e Read and understand the ATV61 Programming Manual before  configuring parameter values     Failure to follow these instructions will result in death or  serious injury              The  1 1 SIMPLY START   SIM   menu can be used to quickly  configure key parameters to get the drive and motor running     Modifying parameters in other menus may modify the parameter  settings in the  1 1 SIMPLY START   SIM   menu  As an example   configuration of motor parameters in  1 4 MOTOR CONTROL   drC    will be reflected in the  1 1 SIMPLY START   SIM   parameters     The  1 1 SIMPLY START   SIM   menu can be used for quick startup   which is sufficient for many of applications     NOTE  The parameters of the  1 1 SIMPLY START   SIM   menu  must be entered in the order in which they appear  as the later ones  are dependent on the first ones     For example  2 3 wire control   tCC  must be configured before any  other parameters           2009 Schneider Electric USA All Rights Reserved 61    Altivar   61 Variable Speed Drive Controllers Simplified Manual    30072 452 65  Macro configuration    4 2009    Macro configuration    Selecting a macro configuration allows you to quickly configure the    drive with settings that are suitable for a specific application                                                                                                           Input   Start Stop   Gen  Use   PID r
61. r 61 Drive  Motor Power Output Input Drive Max   Indicated on Part Number  Interrupting   Withstand  Containment  Fuse  Plate  Rating Current Rating Size  kW hp kA kA kA A  55 75 ATV61HD55M3X 100 35 10 350  75 100 ATV61HD75M3X 100 35 10 350  90 125 ATV61HD90M3X 100 35 18 450                      1 These power ratings are given for an ambient temperature of 45   C  113   F  and at the factory set switching  frequency of 2 5 kHz  used in continuous operation    2 The drives are provided with a DC choke as standard  The DC choke can be omitted by adding the letter D to  the catalog number  For example  ATV 61HD90N4 becomes ATV 61 HD90N4D  A customer supplied input line  reactor must be used in place of the DC choke  See the installation manual for more information        14    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Three phase motor 380 V to 480 V    Three phase motor 380 V to 480 V    For drives with an input line voltage of 380 V to 480 V  a Class J time  delay or non time delay fuse is required  Table 2 on page 15 shows  the fuse size required and available short circuit current rating  associated with each drive     NOTE  The ATV61HC31N4 and ATV61HC63N4 uses a Class T  rather than a Class J  The ATV61HC40N4 uses a semiconductor fuse  rather then a Class J time delay or non time delay fuse     Table 2  380 V to 480 V  50 60 Hz Three Phase Supply Voltage                            
62. r electric com  Fax Line  919 217 6508          2009 Schneider Electric USA All Rights Reserved 9    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Product Support 3 2009       10    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Setting Up the Drive    Setting Up the Drive          E 1 Take delivery of the drive       Ensure that the catalog number printed on the label is the same as that on the purchase  order     Remove the drive from its packaging and ensure that it has not been damaged in transit     E 2 Check the line voltage       Ensure that the line voltage is compatible with the voltage range of the drive     E 3 Mount the drive  page 21      Mount the drive according to the instructions in this document       Install any internal and external options       Install and connect the line reactor  page 29  or the transformers       Steps 1 4  page 30   d E 4 Wire the drive  page 37    H   Connectthe motor  ensuring that its connections correspond to  with the the voltage   power off    With power off  connect the line supply                Connect the control wiring       Connect the speed reference       5 Energize drive with no inputs active     Removing the control terminal card ensures no active inputs     See page 43 for control terminal card removal procedure     If you are using a separate power supply for the control  section follow the instru
63. ree Phase Supply Voltage                                           Altivar 61 Drive    Max   Motor Power ind essa Part Number  ra diana im Ps  on Plate     Rating Current Rating  kW h kW   500 V   575 V     690 V  KA k   KA A  90 125 110 ATV61HC11Y 100 22 28 160  110 150 132 ATV61HC13Y 100 28 28 200  132   160 ATV61HC16Y 100 28 35 250  160 200 200 ATV61HC20Y 100 35 35 300 315  200 250 250 ATV61HC25Y 100 35 35 400  250 350 315 ATV61HC31Y 100 35 35 500  315 450 400 ATV61HC40Y 100 35 42 630  400 550 500 ATV61HC50Y 100 35 42 2x400  500 700 630 ATV61HC63Y 100 42 42 2x500  630 800 800 ATV61HC80Y 100 42 42 2x630             These power ratings are given for an ambient temperature of 45   C  113   F  and at the factory set switching  frequency of 2 5 kHz  used in continuous operation     2 The 500 V to 690 V drives must use a customer supplied input line reactor or special transformer for all  installations  See the installation manual for more information        16    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Receiving  Handling  and Storage    Receiving  Handling  and Storage    Handling and storage    To help protect the drive prior to installation  handle and store the  device in its packaging  Ensure that the ambient conditions are  acceptable  Refer to    Dimensions and Weights    on pages 22 27     A WARNING    DAMAGED PACKAGING    If the packaging appears damaged  it can be dangerous
64. ress  ENT     Switches to  1 DRIVE MENU     1 1 SIMPLY START    1 2 MONITORING  consultthe Programming Manual on    1 3  SETTINGS the CD ROM supplied with the drive   1 4  MOTOR CONTROL    1 5  INPUTS   OUTPUTS CFG       ESC y       58 O 2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Integrated Display Terminal    Figure 11  First time drive power on menu  continued     ROY Temi   U UO REM Press ESC to return to  MAIN    MENU     1 DRIVE MENU  2 ACCESS LEVEL    3 OPEN   SAVE AS       Integrated Display Terminal    The graphic display terminal described on page 56 is supplied as  standard  In addition to the removable graphic display an integrated  display terminal with a 7 segment 4 digit display will be provided     a E                   Exits a menu or parameter   Returns to the previous  D    jp     or cancels the displayed  menu or parameter  or   value to return to the  increases the displayed    previous value in the memory  value    ia Enters a menu or    Goes to the next menu or  parameter  or decreases  the displayed value    parameter  or saves the  displayed parameter or  value    e Pressing  A  or V  does not store the choices     e Press and hold down   gt 2 s   A  or V  to scroll through the data  quickly     e Press ENT to save and store the selection   The display flashes once a value is stored           2009 Schneider Electric USA All Rights Reserved 59    Altivar   61 Va
65. riable Speed Drive Controllers Simplified Manual    Access to Menus    30072 452 65  4 2009    A normal display has no detected fault present and no startup     43  O  Display of the parameter  selected in the SUP menu  default  selection  motor frequency     CL i   CEL   loss  df b   FLU   FrF   PSE     Current limit  Controlled stop on input phase    DC injection braking in progress  Motor fluxing in progress   Drive at fallback speed   Fast stop    n L P  No line power  no line supply on  L1  L2  L3     n 5 E  Freewheel stop    O h r  Auto adapted deceleration   Pr A  Power Removal function active   drive locked    r d 4  Drive ready   r Un  Drive running   5 O E  Controlled output cut in progress  E Un  Auto tuning in progress   U5 A  Undervoltage alarm    The display flashes continuously to indicate the presence of a    detected fault     Access to Menus    Power up       Displays the drive state          Menus                 L o O    SIMPLY START Il    Simplified menu for fast startup    Consult the Programming Manual or  the CD ROM supplied with  the drive              A dash appears after menu and submenu codes to differentiate them    from parameter codes     Example  SIM  menu  ACC parameter       60       2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009  1 1 SIMPLY START   SIM   Menu     1 1 SIMPLY START   SIM   Menu    A DANGER    UNINTENDED EQUIPMENT OPERATION    e Changes to 
66. riable Speed Drive Controllers Simplified Manual  4 2009 Installing the DC choke or the transformer s     Figure 4  DC chokes connected in parallel    Example 1  Example 3   ATV61H DeM3X to D90M3X  ATV61HC40N4  ATV61H D90N4 to C16N4    Grounding strips                Example 2  Example 4   ATV61H C22N4 to C31N4 ATV61H C50N4 to C63N4    Grounding strips    el                            PO PA            2009 Schneider Electric USA All Rights Reserved 33    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Example of installing a transformer on an ATV61HC25Y drive 4 2009    Example of installing a transformer on an ATV61HC25Y drive    Figure 5  Installing a transformer on an ATV61HC25Y drive                     Mount the transformer chassis  1  on the wall  on top of the drive   Ensure that the chassis is tightly secured to the drive to maintain  the IP54 seal of the ventilation duct       Mount the transformer  2  on the chassis  1  using the nuts  provided     e Connect the transformer connector to the drive  see Figure 7 and  Figure 8 on page 36      e Connect the grounding strips between the transformer chassis 1  and the drive       Mount the cover  3  on the chassis and secure it with the nuts  4   provided       Mount panels  5  and  6  using the screws provided     Once the transformer has been installed  the degree of protection of  the top of the drive is IP31        34    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altiv
67. s  C     2  Remove the screws  C  from the choke or transformer support on  the pallet        A WARNING       RISK OF CUTS   e Take every precaution and use protective gloves to avoid this risk  of cutting your hands    e The screws that hold the choke or transformer support on the  pallet are difficult to access     Failure to follow these instructions can result in death or  serious injury              3  Remove the screws holding the drive on the pallet and use a hoist  to lift it off  It has lifting lugs for this purpose  D      A WARNING          RISK OF TOPPLING    Do not stand the drive upright  Keep the drive on the pallet until it is  installed     Failure to follow these instructions can result in death or  serious injury                    2009 Schneider Electric USA All Rights Reserved 19    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Before You Begin 4 2009    Before You Begin    You must observe the following precautions     A DANGER    UNINTENDED EQUIPMENT OPERATION      Before turning on and configuring the Altivar 61 drive  ensure that  the PWR  POWER REMOVAL  input is deactivated  at state 0  in  order to help prevent unintended operation     e Before turning the controller on or upon exiting the configuration  menus  ensure that the inputs assigned to the run command are  deactivated  at state 0  since they can cause the motor to start  immediately    e Refer to the characteristics and functions table in the Control  Termin
68. s  have been met  L CF    input contactor  The drive is not turned on    Check the contactor and its wiring   even though   Check the time out    Mains V  time out   LCt      Check the line contactor controller  has elapsed  connection   LFF g    Al2 4 20mA loss  Loss of the 4 to 20 mA   Check the connection on the analog  LFF J    AI3 4 20mA loss  reference on analog input inputs   LFF 4    Al4 4 20mA loss  Al2  AI3 or Al4  m FF    No Flow Fault  Zero fluid   Check and correct the cause of the low  flow     Check the zero fluid detection parameters   consult the Programming Manual on the  CD ROM supplied with the drive    ObF    Overbraking  Braking ramp too short   Increase the deceleration time   Overhauling load   Install a braking resistor if necessary     Activate the  Dec ramp adapt    brA   function  consult the Programming  Manual on the CD ROM supplied with the  drive   if it is compatible with the  application   OHF    Drive overheat  Ambient temperature too     Check the motor load  the drive  high ventilation  and the ambient temperature   Drive ventilation blocked Wait for the controller to cool down before  Drive cooling fan restarting   OLE    Proc Overload Fit  Process overload   Check and remove the cause of the   consult the programming overload   manual on the CD ROM      Check the parameters of the   PROCESS UNDERLOAD   OLd    function  consult the CD ROM supplied  with the controller    OLF    Motor overload  Motor power rating too   Check the setting of
69. soft   Improper DC bus charging  charge  condition  thyristors   EEF      Control   Control card Internal Check the environment  electromagnetic  Eeprom  memory compatibility     F 2    Power  P d int   Turn off  reset  return to factory settings   KENE Em mea e Contact Schneider Electric Product Support   FEF     Out contact    The output contactor Check the contactor and its wiring    stuck  remains closed although Check the feedback circuit   the opening conditions  have been met  HdF   IGBT   Short circuit or grounding Check the cables connecting the drive to the  desaturation  at the drive output motor  and the motor insulation   Perform the diagnostic tests via the   1 10 DIAGNOSTICS  menu   ILF    internal   Communication condition Check the environment  electromagnetic  com  link  between option card and compatibility    drive Check the connections   Ensure that no more than 2 option cards  max   permitted  have been installed on the drive   Replace the option card   Contact Schneider Electric Product Support   Im F      Rating error    The power card is different Check the catalog number of the power card and  from the card stored ensure that it is compatible with the drive   In FE    Incompatible   The power card is Check the catalog number of the power card and  PB  incompatible with the ensure that it is compatible with the drive   control card  In F 3    Internal   Communication condition Check the internal connections   serial link  between the internal cards Co
70. sult the  Programming Manual on the CD ROM  supplied with the drive                     CF 1    Invalid config     Invalid configuration  Check the configuration loaded previously   The configuration loaded Load a compatible configuration   in the controller via the  bus or network is  inconsistent    HEF    Cards pairing    The  CARDS PAIRING  Consult the Programming Manual on the   PPI   function has been CD ROM supplied with the drive   configured and a drive  card has been changed   PHF  Input phase loss    Controller incorrectly Check the power connection and the fuses   supplied or a fuse blown     Loss of one phase Use a 3 phase mains supply    3 phase ATV61 used on  a single phase line supply Disable  Input phase loss   IPL     No   nO      Unbalanced load  Monitors only with the drive  on load   Pr EF    Power Ident    The Enter the correct parameter  reserved for   Power Identification  Schneider Electric product support     Prt  parameter is Check that there are no card errors   incorrect   If the control card was changed deliberately     Control card replaced by consult the Programming Manual on the  a control card configured CD ROM supplied with the drive   on a drive with a different  rating  USF    Undervoltage    Line supply too low Check the voltage and the voltage            Transient voltage dip    Damaged pre charge  resistor       parameter  consult the Programming  Manual on the CD ROM supplied with the  drive     Replace the pre charge resistor    Conta
71. t       Standstill injection braking current  0 7 x rated drive current  for 0 5 s       Automatic starts No automatic starts after a detected fault is cleared       Switching frequency 2 5 kHz to 12 kHz depending on drive rating       e Li  forward  1 operating direction   2 wire control  type is transition  See    Starting    on page 54    e LIZ  inactive  not assigned    e LIS  switching of and speed reference   If LI3   O the speed reference All is active   If LI3   1 the speed reference Al2 is active    e Ll4  fault reset   e LI5  LIG  inactive  not assigned     Logic inputs             2009 Schneider Electric USA All Rights Reserved 53    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Power switching via line contactor 4 2009    Table 8  Factory configurations  continued     e Alt  1St speed reference 0 to 10 V  e Al2  ond speed reference 0 to 20 mA    NOTE  For 4 20 ma  go to Menu   1 5 Input Output CFG   then to   Al2 configuration  and change   Al2 min  value  from 0 to 4     R1C to R1A contact opens and R1C to R1B contact  Relay R1 closes in the event of a detected fault or when the  drive is powered off     Analog inputs          Relay R2 R2A to R2C contact closes when the drive is running           Analog output AO1 0 to 20 mA  motor frequency    For programming instructions  refer to the ATV61 programming  manual on the CD ROM included with the drive     Power switching via line contactor    Starting       CAUTION    EXCESSIVE LINE 
72. tected phase loss with freewheel stop    If one phase is lost  the drive indicates mode  Input phase loss   IPL   but if 2 or 3 phases are  lost  the drive continues to operate until it trips due to undervoltage    This parameter is only accessible in this menu on ATV61H037M3 to HU75M3 drives  used  with a single phase supply       Rated motor power  According to Varies with the drive  drive rating rating     Rated motor power given on the nameplate  in kW if  Standard mot  freq   bFr     50 Hz IEC   50    in HP if  Standard mot  freq   bFr     60 Hz NEMA   60               64    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Macro configuration    Table 10  Codes  adjustment range  and factory settings  continued     Name Description Adjustment range   Factory setting        Rated motor volt   According to Varies with the drive  drive rating rating and  Standard  mot  freq   bFr              Rated motor voltage given on the nameplate   ATV61  eM3  100 to 240 V   ATV61e  N4  200 to 480 V   ATV61  Y  400 to 690 V     Rated mot  current  025t0110r12   Varies with the drive    Hz depending on rating and  Standard  rating P 9 mot  freq   bFr        Rated motor current given on the nameplate      Rated motor freq   10 to 500 or 1000    Hz depending on  rating       Rated motor frequency given on the nameplate   The factory setting is 50 Hz  or preset to 60 Hz if  Standard mot  freq   bFr  is s
73. ting    The maximum prospective input short circuit current at which the  drive is capable of interrupting a short circuit at its motor output  terminals  The output interrupting rating conforms to the existing  short circuit requirements of UL508C 3rd edition with revisions  effective February 15  2008     Input Withstand Current Rating  without line reactor or choke     The maximum prospective input short circuit current at the drive input  terminals with which the drive was designed to operate  The input  withstand current rating is an important parameter in determining the  maximum thermal and electrical operating limits for the drive   Exceeding the maximum prospective input short circuit current rating  may cause overheating with reduction of drive life expectancy or  damage to the drive        CAUTION    DRIVE OVERHEATING       Ensure the prospective input short circuit current does not exceed  the input withstand current rating     Failure to follow these instructions can result in equipment  damage                 12    2009 Schneider Electric USA All Rights Reserved    30072 452 65 Altivar   61 Variable Speed Drive Controllers Simplified Manual  4 2009 Drive Containment Rating with OCPD    Drive Containment Rating with OCPD    The maximum prospective input short circuit current at the drive input  terminals with the marked OCPD present at which an internal  component breakdown in the drive will not create a shock  flame  fire  or expulsion hazard outside the marked 
74. uto Reset Conditions    A DANGER    LOSS OF PERSONNEL AND EQUIPMENT PROTECTION    e Enabling the fault inhibition parameter  InH  will disable the drive  protection features     e InH should not be enabled for typical applications of this  equipment    e InH should be enabled only in extraordinary situations where a  thorough risk analysis demonstrates that the presence of  adjustable speed drive protection features poses a greater risk  than personnel injury or equipment damage     Failure to follow these instructions will result in death or  serious injury              Table 14 on page 76 lists the conditions that can be reset as soon as  the cause of the condition has been removed  The USF condition can  be inhibited and cleared remotely by means of a logic input or control  bit   Fault inhibit assign    INH   consult the CD ROM supplied with the  drive            2009 Schneider Electric USA All Rights Reserved 75    Altivar   61 Variable Speed Drive Controllers Simplified Manual 30072 452 65  Auto Reset Conditions    Table 14     Code    CFF    Name     Incorrect config      Auto Reset Conditions    Probable cause    Option card changed    or removed      The current configuration  is inconsistent    4 2009    Remedy    Check that there are no card errors    If the option card was changed or removed  deliberately  consult the Programming  Manual on the CD ROM supplied with the  drive     Return to factory settings or retrieve the  backup configuration  if it is valid  con
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Tripp Lite SU3000RTXL3U User's Manual  5645 Plant Operating Software ACS715  Pompes de dosage  Samsung CE2975N manual de utilizador  Pliego de Bases Técnicas  Type J - Toyotomi  Sony XS-S680CX Operating Instructions  Operating Instructions  REENAMORATE DE TU CASA      Copyright © All rights reserved. 