Home

USER`S MANUAL - Axiom Technologies, LLC

image

Contents

1. Polarity IS ea Important a q l l Blue Wire goes to Signal r K Py i White Wire goes to Common Wire Nuts High Axiom Technologies Level EOZ End Of line Zener Switch XP7 Wiring Diagram To be connected as shown Monitored Inputs for Safety Shutdown System Reference Sheet Date XP7 1of1 2 28 2011 Control panel external to the XP7 Example Only External Hi Lo Pressure Switchgage High Tank Level
2. performance Note When cleaning contacts do not use abrasives materials or fluids as they will cause damage and severely reduce system s reliability Note Avoid opening the enclosure in a rainy or dusty environment The batteries are expected to have a life of about 5 years before replacement is needed The XP7 routinely reads battery voltages and provides warning if the batteries need replacement When the batteries are beginning to go low the XP7 will alternatively blink the green and Lo Batt LEDs to indicate that battery replacement is needed If the batteries are not replaced within a few days the XP7 will blink only the Lo Batt LED and initiate shutdown as further reduction in voltage may prevent the system from protecting the process XP_7_ME_RS doc June 26 2014 Page 7 of 9 Axiom Technologies XP7 User s Manual 15711 W Hardy Rd Suite 1 Houston Texas 77060 Phone 281 931 0907 WARNING EXPLOSION HAZARD BATTERIES MUST ONLY BE CHANGED IN AN AREA KNOWN TO BE NON HAZARDOUS REPLACE BATTERY MODULE WITH AXIOM TECHNOLOGIES PART NUMBER AT LBP 36144 WARNING DO NOT ATTEMPT TO RECHARGE BATTERY MODULE AS THIS MAY TRIGGER AN UNSTABLE CONDITION WITHIN THE LITHIUM CELLS AND CAUSE AN EXPLOSION Return used battery modules to Axiom Technologies for safe disposal XP7 ENVIRONMENTAL SPECIFICATIONS Temperature range 40 to 85 C Humidity range 0 To 95 max non condensing Altitude 2 000 m max Hazardous
3. Area Classification Suitable for Class I Division 2 Groups C amp D Hazardous Locations Temp Code T3C XP7 PRESSURE RATINGS Sensing Pressure Ranges of up to 20 000 psi max Solenoid Valve Pressure 100 psi max standard up to150 psi available XP7 ELECTRICAL RATINGS Electrical Source Dual voltage lithium battery module3 6 amp 14 4 VDC Current consumption 285 mA max on 3 6VDC Circuits 435 mA 3 A max pulse on 14 4VDC Circuits XP_7_ME_R5 doc June 26 2014 Page 8 of 9 Axiom Technologies XP7 User s Manual 15711 W Hardy Rd Suite 1 Houston Texas 77060 Phone 281 931 0907 PLACING THE BATTERY MODULE Fig 5 Remove screws from cover Fig 6 Open front cover 4 3 9 ee S 8 4 0L n E Fig 7 Align the battery module with Fig 8 Secure battery module by reinstalling threaded studs and push it in nylon spacers Verify the green LED place gently The Axiom blinks about once per second to Technologies printing on the confirm successful battery module module is to be on the left installation XP_7_ME_R5 doc June 26 2014 Page 9 of 9 Appendix A XP7 Installation Notes 1 The XP7 operates with normally open contact and contact closure indicates that an alarm is 5 Each input sends a pulse of 14VDC to the alarm switch If the EOZ is connected as it present should then the voltage is cut down to 7 4VDC 0 3VDC and the XP7 accepts this voltage as a normal condition If the EOZ would b
4. can connect up to four 4 external alarm sensors and each external loop is independently monitored for detecting alarm conditions In addition to the above the unit monitors the wiring integrity for wiring interruption insulation degradation etc Each alarm loop is designed to be non incendive Each input channel has an End Of line Zener EOZ that is to be connected in parallel with the sensing element For example if channel 3 of the field alarms is to be connected to a level switch installed on a water tank then the EOZ is to be removed from the XP7 junction box and connected in parallel with the level switch as shown in Appendix A i 4 Z2 Z3 Z4 GREEN Inputs 4 Outputs 2 ee INPUT COMMONS CC TRA ERAD lt n SHUTDOWN TROUBLE ay Common aa AXIOM TECHNOLOGIES HOUSTON TX Aa Fig 3 Field Connection Box for nonincendive field wiring See Appendix A for field wiring details When in normal operation the XP7 sends a short pulse of current to the remote sensors for verifying wiring conditions and the existence of alarms XP_7_ME_R5 doc June 26 2014 Page 4 of 9 Axiom Technologies XP7 User s Manual 15711 W Hardy Rd Suite 1 Houston Texas 77060 Phone 281 931 0907 With the EOZ the input should have a voltage between 7 and 8VDC however given the shortness of the pulse this voltage can not be verified with a regular voltmeter To overcome the above difficulty the XP7 offers a mode whe
5. damage in the instrument and void warranty If the flow is prone to pressure spikes a pulsation dampener is to be installed between the sensing port and sensed fluid It is recommended that an isolation valve is installed between the sensing port and process to allow for maintenance and testing NOTES Do not exceed rated range When connecting pressure bourdon assembly bottom of XP7 pipe dope or use Teflon tape on connection threads Use wrench on shank to tighten or loosen bourdon connection Do not twist case when installing this will cause damage and void warranty Do not over tighten The typical connection the solenoid valve is as follows Port 1 normally closed Supply Pneumatic Pressure 100 PSI Typ Port 2 common Actuator Port 3 normally open Exhaust Port No 1 Pneumatic Supply 100 PSI Typical Port No 2 To Actuator Note Port numbers are stamped Port No 3 Exhaust near the ports Fig 2 Solenoid pneumatic hydraulic typical connection XP_7_ME_RS5 doc June 26 2014 Page 3 of 9 Axiom Technologies XP7 User s Manual 15711 W Hardy Rd Suite 1 Houston Texas 77060 Phone 281 931 0907 Adjusting High and Low Pressure Alarm The Low Limit contact is controlled by the knob on the left while the High Limit contact is controlled by the knob on the right To set the limit contact simply turn the knob to the desired position in the scale Connecting Remote Sensors As indicated before the XP7
6. Axiom Technologies L L C Telephone 281 931 0907 15731 W Hardy Road Suite 7 Fax 281 231 6562 Houston Texas 77060 www axiomsafety com XP7 USER S MANUAL COMPACT HIGH AND LOW PRESSURE SHUTDOWN SYSTEM Axiom Technologies XP7 User s Manual 15711 W Hardy Rd Suite 1 Houston Texas 77060 Phone 281 931 0907 GENERAL The XP7 alarm and shutdown system is a self supported compact shutdown device that has been designed to provide a safe and reliable mean to detect abnormal conditions on a production process and initiate a shutdown if any of the reading shows the operation is no longer within the pre set safety margins The system has been built to withstand the adverse conditions of the oil field environment and provides a straightforward interface with the operator Abnormal conditions are indicated by indicator lamps LEDs each associated with a label indicating the condition detected Powered by lithium batteries the system is expected to operate for about five years without replacing batteries and there is little or no maintenance needed besides recommended periodical functionality test and gentle cleaning of contact points In addition to the High and Low pressure alarms associated with the bourdon assembly included in the box the XP7 can connect up to four 4 loop monitored external alarms plus two solid state outputs for indicating shutdown and service needed respectively The external alarms channels can be connec
7. e missing or the wiring to the alarm 2 For supervising field wiring each input channel is provided with a 7 5V End Of line Zener switch disconnected then the voltage may rise up to about 14VDC which is considered a EOZ at the XP7 s input terminals At the time of installation the EOZ is to be moved to the Wiring Failure and cause a shutdown end of the loop and connected in parallel with the alarm switch If more than one switch f are daisy chained then the EOZ is to be installed at the very last switch The EOZ at the 6 Multiple XP7s may share a single alarm switch such as a tank level ESD station or any dry end of the alarm wiring allows the XP7 to confirm the wiring s integrity contact alarm switch 7 The output of an XP7 can be used as input for another XP7 or MI6 or MX16 Make sure the 3 The EOZ must be connected in the correct polarity Blue wire to Signal and White wire to EOZ is properly connected for wiring supervision Common Connecting the EOZ on a reverse polarity will cause the corresponding channel to stay on alarm 4 The alarm switch may be located at 3 000FT or more from the XP7 XP7 J unction Box SD COM TREL COM End Of line Zener EOZ on each input Typical of 4 supplied with XP7 EOZ must be removed and installed with remote alarm switch as shown on channels 1 through 5 of this sheet MUST BE CONNECTED FOR WIRING FAILURE ALARM TO GO AWAY
8. inks fast and then the system proceeds to slow blink each red LED to confirm all indicator circuits are operating normally The system is shipped in the RESET condition The needle of the gauge touching either the Low or High set point causes the XP7 to switch the solenoid valve into shutdown The corresponding alarm LED will blink once a second to indicate the actual cause of the shutdown even if the alarm goes away or another alarm is later detected EXAMPLE If an XP7 senses a High Pressure in a production line it will cause a shutdown and the High Pressure LED will blink After a number of hours because of the shutdown the sensed pressure may fall to the point where the high pressure clears and the needle of the gauge is now touching the low pressure alarm In this case the XP7 continues flashing the High Pressure alarm LED until the operator presses Reset If the operator wants to confirm the cause of alarm after the system is back to normal they XP_7_ME_R5 doc June 26 2014 Page 5 of 9 Axiom Technologies XP7 User s Manual 15711 W Hardy Rd Suite 1 Houston Texas 77060 Phone 281 931 0907 just need to press Test and the XP7 will blink the High Pressure LED to show the last recorded cause of shutdown After the XP7 is installed the operator is to set the high and low alarm settings and open the isolation valve to allow pressure into the sensing port If the operator pre
9. re the inputs are energized for a few seconds at a time by following the procedure below Open junction box and have voltmeter ready for reading voltage Press and hold the Test Reset switch down to Test for about three seconds and then release The first remote alarm blinks the corresponding LED for five seconds while the input is sending a current to the field connection Read the voltage on first remote channel and confirm it is between seven 7 and eight 8 volts around 7 3V being typical A voltage below three 3 Volts is considered as alarm Voltages above 8 VDC indicate the remote sensor is not connected A reading of about O VDC may indicate the corresponding sensor is close or there is a short circuit in the loop or the XP7 timed out the test on that channel A low voltage of about 0 5VDC may indicate the EOZ End Of line Zener has been connected backwards Other low voltages between 3 and 6 VDC may indicate insulation s deterioration in the field wiring Once the XP7 stops the blinking the first channel and moves to channel 2 repeat voltage reading OPERATION The system can be commanded to Reset or Test by pressing the toggle switch up or down respectively By pushing to Reset the operator commands the unit to return to the flowing condition Pushing the Test function allows the operator to see the last recorded cause of shutdown corresponding LED bl
10. sses Reset the existing alarm will be ignored for 30 minutes to allow the process to return to normal there is no need to disturb the set point before restoring the process It is recommended not to move the set points out of the alarm condition as this involves the risk of the operator forgetting to return the alarms to the proper setting once the process returns to normal If more than 30 minutes is needed then it is suggested that the operator press Reset again before the time expires re starting the 30 minute countdown If the pressure or temperature returns to normal before the 30 minutes expires the XP7 will re arm itself and will initiate shutdown again if an alarm is sensed Time Delay on Alarm Inputs In some cases it may be desirable to have a slower response to a given alarm channel e g a tank level sensor may respond to waves or fluid motion in a tank The XP7 offers the capability of introducing an eight 8 seconds delay on any of the four remote alarm channels For setting a time delay in any of the four field inputs proceed as follows 1 Open XP7 enclosure 2 While holding the Test Reset switch down momentarily depress the Initialize pushbutton on the controller board upper left corner as shown on Fig 4 Page 7 and then let go the Test Reset switch The green LED responds by flashing rapidly for a few seconds 3 Next the XP7 flashes the first field alarm LED rapidly to show tha
11. t there is no time delay set slowly if a time delay exists 4 If the flashing indicates the desired setting then take no action and the XP7 will move to the next channel 5 If a time delay is desired and the LED is flashing rapidly press the Test Reset down to set a time delay 6 If a time delay is not wanted and the LED is flashing slowly press the Test Reset up to remove the time delay 7 As the XP7 moves on to the next channel repeat step 4 through 6 for setting the desired operation mode 8 Once all channels have been set the operator may repeat step 2 and confirm each channel has been set correctly 9 Close the enclosure and confirm the actual delay by tripping the alarm channels and observing the response on the XP7 XP_7_ME_R5 doc June 26 2014 Page 6 of 9 Axiom Technologies XP7 User s Manual 15711 W Hardy Rd Suite 1 Houston Texas 77060 Phone 281 931 0907 gt a n ta r LaS om Mic 14 4 VOLTS 3 6 eo Fig 4 Initialize Pushbutton MAINTENANCE The XP7 requires little maintenance but a minimum of a monthly visual examination and testing is recommended to insure that the unit as well as the systems and devices associated with the safety shutdown are operating properly It is recommended that once a year the gauge pointer and High and Low limit points be cleaned with a soft piece of cloth and a non residue contact cleaner to insure optimum
12. ted to any dry contact or open collector type of sensor such as pressure or level switches manual ESD station telemetry shutdown commands etc Each remote loop is monitored for wire integrity for insuring that wiring faults are also detected Reset Test Indicator LEDs Switch Field Connection Box Four Input and two output Channels High Pressure Alarm Setting Low Pressure Alarm Setting Pressure Sensing Port Fig 1 XP7 General Layout XP_7_ME_RS doc June 26 2014 Page 2 of 9 Axiom Technologies XP7 User s Manual 15711 W Hardy Rd Suite 1 Houston Texas 77060 Phone 281 931 0907 INSTALLATION Typically the XP7 is shipped with the battery module installed in the storage position for shipment Remove the four studs holding the battery module rotate it 180 and carefully re install as shown on page 9 of this manual The XP7 is now energized and the green LED blinking every second The unit can be wall mounted directly on the process line The box is provided with a drain at the bottom to remove water condensation Do not mount the XP7 sideways or upside down as this may allow rainwater to ingress and accumulate in the enclosure NOTE XP7 DEVICE IS TO BE MOUNTED UPRIGHT IN THE VERTICAL POSITION ONLY XP7 Pressure Sensing Monitored pressure i e flow line pressure is to be connected to the Sensing Port Sensed pressure is not to exceed 10 over full scale as this would cause

Download Pdf Manuals

image

Related Search

Related Contents

at tention - Leroy Merlin  取扱説明書  Insignia NS-DPF8WW-09CA Digital Photo Frame User Manual  conditions generales. - Le Club FUJIFILM PRO  PH 101 - HJS Værktøj A/S  PM4-RT8 - Amalgamated Instrument Co Pty Ltd  ALW Push Pull Gun PPG 300 Instruction Manual  Installation/Service Manual VENTURE POST-MIX  manuale M1_moschettoni_Layout 1  取扱説明書 - 三菱電機  

Copyright © All rights reserved.
Failed to retrieve file