Home

Manual

image

Contents

1. ii Each test group is constructed from a series of individual tests The tests are selected depending on the electrical construction of the asset under test The operator must understand the type of electrical construction of the asset before a correct selection of tests can be made The tests available on the PAT400 s are as follows Continuity amp bond testing Continuity and bond testing are both used to confirm the existence of a safety earth return path of a Class asset However they differ in how they work and both have their benefits and drawbacks Continuity low current or Soft testing This test uses a 200 mA test current at 4 to 5 Vdc The test current is low so that there is no risk of damaging earth connections that may only exist for functional rather than safety reasons High current Bond testing not available on the PAT410 Uses a 10 A or a 25 A AC test current at 8 9 V This test is used where concerns that an earth may be maintained by a few strands of wire or where poor surface contact by the probes or clips could give a misleading reading This test is frequently the preferred test by many organisations 68 iii iv v vi In situ bond testing In situ bond testing is the ability to measure the earth integrity of a class asset that is hard wired to the electrical supply Normally there would be no convenient method to connect the asset to the PAT400 without disconnecting
2. However the same Asset ID cannot be used in different locations under one client 67 12 13 To transfer data from the PAT4 to the PAT400 the transfer must be made using Megger PowerSuite Professional To ensure hardware and software compatibility refer to the Megger website for latest PowerSuite software and PAT400 firmware revisions www megger com Care and maintenance The PAT400 should only be opened or repaired by an approved Megger service centre or by Megger Instruments Limited To clean the instrument disconnect the instrument from the power supply then use a clean cloth dampened with water or isopropyl alcohol To clean the display window only use a lint free cloth For warranty repairs see appendix E Carry case The carry case for the appliance tester has a lead storage pouch in the lid of the case when opened This is designed for basic lead and document storage Further items can be stored in the pouch If it becomes difficult to close the case the storage pouch can be removed from inside the case and attached to the front using the straps on the reverse of the pouch These are passed through the D loops on the outside of the case and secured to the underside of the pouch using the Velcro fixings An additional storage pouch is available from Megger Limited for extended storage such that there is a pouch on both the inside and outside of the carry case Appendix A Test types explained A 1 i
3. Fuse Rating 4 Room ID Retest Frequency M cient Location Press SAVE to store asset data SAVE lis t TEST to store and test or Esc to abort results to memory To abort an Add Asset page press Esc or HOME key A warning will appear asking to confirm you wish to exit without saving data To edit asset information go to section 6 33 5 1 Adding assets to memory Assets can be saved to memory after they are tested as above or before any testing starts To copy a previously added asset using the COPY ASSET 2 Hotkey or COPY ASSET AND INCREMENT ASSET ID 2 Hotkey see Section 5 2 Alternatively Asset data can be loaded from PowerSuite via a USB stick Section 7 2 Adding assets to memory before testing 1 From the HOME screen press the ADD ASSET Hotkey The following empty asset screen will appear Add Asset COPY last ASSET Asset ID COPY last as Test Group Select test group vi Description ee E eos SerialNumber A Al Fuse Rating 8x7 Room ID TS Retest Frequency M Client default Location default Enter asset ID and select test group Press Esc to abort 2 Enter an ASSET ID using the keyboard or barcode scanner 3 Select a TEST GROUP from the drop down list 4 Completion of the remaining asset fields is optional Add Asset Asset ID 000234 PA Test Group x Description ad Serial Number Fuse Rating 4 Room ID Retest Frequency M C
4. PAT400 Series Portable Appliance Testers User Manual Thank you for purchasing the Megger PAT400 portable appliance tester For your own safety and to get the maximum benefit from your instrument please ensure that you read and understand the safety warnings and instructions before attempting to use the instrument These instruments are designed and manufactured by Megger Instruments Limited Archcliffe Road Dover Kent CT17 9EN England Megger Instruments Limited reserves the right to change the specification of these instruments at any time without prior notice CONTENTS X 1 Unpacking th Carton s eis erate eee on ede AS 5 X 2 A A ee etc ees 5 X 3 Symbols used on the Instrument scscieinceie el cee ee eee ee 6 e Instrument Lay OUR osred csect leper eee rete aes headend E ee eee a T 1 1 Overview of the PATADO ee ee ett ee tee 7 1 2 instrumenta yoUt ean ce ci ce sh cca as 8 1 3 B tton TUNCIONS 5 aes eee tse ee ee 9 1 4 HOTKEY GOS CAPO eave A a A NAA 9 1 5 Display INTO I AU ON oro ci 10 1 6 Screen Navigati n co ia 10 1 7 Text fields free form box and Drop down DOXES coooccooccccocccoccccocconcnoncnconcnoncncnnnnnncnnnnnoncncnnnonnss 10 1 8 Battery and fuse location fitting and replacemMent oooccoonccccncccncocnconcnoncncncncnncnoncnonnconanonnnnnonnss 11 Za E151 5 4 1S stated cacas 13 2 1 Switching ON the PA TAO ii ii bee 13 2 2 HOME screen explained nia a dan 15 2 3 Switching off t
5. Location Press SAVE to store asset data TEST to store and test or Esc to abort 4 Change any other asset information as necessary 5 Press the SAVE Hotkey to save the ASSET to memory 36 6 1 Editing and deleting assets and results All asset data can be edited or deleted as required For editing and deleting of Test Groups see section 8 For editing and deleting of Client and Locations see section 10 Editing asset data 1 From the HOME screen enter the SETUP menu option by pressing the RIGHT arrow key Home Setup Data 0 MA Client IVA Location Company Quick Test Keys Setup Date Time a Language Default Settings About for EDIT asset SS 2 Press the EDIT ASSET Hotkey The EDIT ASSET screen should be displayed Enter an Asset ID to be edited Alternatively to list the assets in the database press the FIND ASSET Hotkey This will produce a drop down box Edit Asset fo FIND ASSET Asset ID 1000632745 e Test Group Description serial Number Fuse Rating A Retest Frequency M Client Megger Group Y Th ADD asset Megger Instruments Lir Location Edit asset information press add or delete hotkey to add or remove an asset Assets are sorted alphanumerically in ascending order Press the OK key and then the DOWN arrow to scroll through the list or use the RIGHT arrow key to page through the list OR Type the desired Asset ID to jump
6. Visual Test Failure Case Socket IV Mains Plug f Environment IV Mains Lead Suitability M On Off Switch Other Notes Repair Code 0 Use the arrow keys to navigate and OK key to finish editing Notes Type in any applicable repair code Press TEST to complete or Esc to abort Three types of information can be entered a Notes To describe the type of failure b Check boxes Quick entry for standard failure types c Repair code See Section 3 10 below Press the TEST key to complete the test process The display will now show the TEST FAILED screen Press the SAVE Hotkey to save the results or the SAVE and PRINT Hotkey to save the results and print a barcode label 27 3 10 Repair code A repair code can be entered at the completion of testing Press the Hotkey and the following popup appears Test Results Repair Code Repair Code Use the arrow keys to navigate and OK key to finish editing Notes Type in any applicable repair code Press TEST to complete or Esc to abort Asset FAILED Enter any notes as appropriate then press OK followed by the DOWN arrow Enter an appropriate repair code Examples of the repair codes used in PowerSuite are given below 1 Replace internal fuse 18 Renew 3core 0 75mm flex 2 Refit plug 19 Renew 3core 1 00mrr flex 3 Refit socket 20 Renew 3core 1 50mrr flex 4 Replace cable 21 Renew Score 2 50mrr flex 5 Renew 415V 5 pin 16A 22 Tight
7. 110 V Tools Class 2 Flash Double Insulated Desk Fan Double Insulated PAT400 Factory Default Test Groups Test Visual Inspection Earth Bond at 10 A Insulation test at 500 V Operation test 230 V Differential Earth Leakage 230 V Visual Inspection Earth Bond at 10 A Operation test 230 V Differential Earth Leakage 230 V RCD 30 mA test Visual Inspection Earth Continuity Insulation test at 500 V Operation test 230 V Differential Earth Leakage 230 V Visual Inspection Earth Continuity Operation test 230 V Differential Earth Leakage 230 V RCD 30 mA test Visual Inspection Insulation test at 500 V Operation test 230 V Differential Earth Leakage 230 V Visual Inspection Earth Bond at 25 A Insulation test at 500 V Operation test 110 V Differential Earth Leakage 110 V Visual Inspection Earth Bond at 25 A Insulation test at 500 V Operation test 110 V Differential Earth Leakage 110 V Flash test at 1500 V Visual Inspection Insulation test at 500 V Operation test 110 V Differential Earth Leakage 110 V Visual Inspection Insulation test at 500 V Operation test 110 V Differential Earth Leakage 110 V Flash test at 3000 V Visual Inspection Insulation test at 500 V Operation test 230 V Differential Earth Leakage 230 V 5s 5s 5s 5s User controlled 5s 5s 5s User controlled PAT420 PAT450 PAT420 PAT450 PAT410 PAT420 PAT450 PAT41
8. Date Time Language Default Settings About EEE 30 3110 2 Press the TEST GROUP MANAGER LYA Hotkey Test Group fo Press add hotkey to add a test group Add a TEST GROUP Press edit hotkey to edit a test group Sy Edit a TEST GROUP Press delete hotkey to delete a test group Delete a TEST GROUP 3 Press the ADD Hotkey to add a new test group The Add Test Group screen will appear Add Test Group fo Peserpton Sd Supply 230 f Class E z E z E E m Ro E E NOTE 100 If the number of test groups reaches 100 the ADD Hotkey will change to a pos Icon 4 Complete the fields as required An example of a typical standard Class test may look like Add Test Group ame escription upply isual arth Bond ontinuity olarity Definitions to fields NAME DESCRIPTION SUPPLY VISUAL EARTH BOND CONTINUITY INSULATION Oy Class 1 Standard 230 Y Yo Flash m 2 E y V RCD e Next page Test group name This can be up to 10 characters For compatibility with PAT4 see section 11 Text string Keyboard or Barcode entry Asset operating voltage Check box Check box configuration options available on second page Check box configuration options available on second page Check box configuration options available on second page 47 8 2 POLARITY CLASS FLASH LEAKAGE LOAD RCD 1 Check box configuration options available on
9. Description YA Press once for direct entry Serial Number 34241 31130 Press twice for drop down Fuse Rating 4 box Room ID Retest Frequency M Client default Th Add ASSET Location default Enter asset ID or test group and press TEST to start a test or press Esc to abort Edit ASSET Check the asset information matches the ASSET to be tested If so Press TEST and go to section 3 3 TEST PROGRESS If the asset information does not match the asset to be tested check the CLIENT is correct The same ASSET ID can be used for different clients but one client cannot have duplicate asset IDs If the asset ID does not exist the screen will jump to Add Asset screen and automatically fill the ASSET ID field with the scanned barcode data NOTE When scanning an Asset ID that exists in the database under a location that is different to that set in the PATs current status a yellow warning indicator will show on the Location field as below Go to section 4 for additional information on Clients and locations 21 TestAsset iS Asset ID Test Group sC1 0 Lie Description Serial Number Fuse Rating A HAS Room ID Retest Frequency M Client Location Megger Group start a test or press Esc to abort amp Enter asset ID or test group and press TEST to Y ES Press the TEST button Go to section 3 3 TESTING PROGRESS for further information on the test sequence 3 3 Test progress T
10. IEAM TEET M ae P AU A UUM Extension lead 110V PC ME ONAMNI MI Room ID Kitchen K j t c h o r gt O A IR o r Y C a n t e e n KET Desk PC Base station MAR ili mt ETE Washroom Male A mM Washroom bo t T ba EL1 Laptop Power cord Male rae TAA ATAU A AA ill AR lll Laptop p owe r cord I t 1 5 EL2 Standard Class MOLL A nas a TTT Ma in office EL3 TU a ATUL ON 0 00M A A SS Lal UNAM M RCD UUM RCD FULL AAN UL Warehouse Wa re ho u s 6 Reception R e ception Appendix D Specification PAT PAT PAT SPECIFICATIONS 410 420 450 Electrical supply range PAT UK 230 V 110 1 V 50 Hz 1 0 1 Hz E E E 110 V 10 1V 50 Hz 1 0 1 Hz ia E E PAT EU 230 V 110 1 V 50 Hz 1 0 1 Hz E E PAT DE 230 V 110 1 V 50 Hz 1 0 1 Hz E E PAT AU 230 V 110 1 V 50 Hz 1 0 1 Hz m E E Instrument accuracy cannot be guaranteed when operated on supply frequencies other than those specified above Max operation supply range 90 V ac to 264 V ac 50 60 Hz E E E Bond test 10 A amp 25 A Al E Open circuit voltage 9Vaci 10 0 1V m 10 A rms 25 into 0 1 Q 230 V 50 Hz E E Current output 25 A rms 4 20 0 5 A into 0 1 Q 230 V 50 E Hz l 5 3 digits 0 to 0 49 Q E E Earth bond t E arth DONE resistance accuracy 450 5 digits 0 5 to 1 99 Q a 5 Earth bond resistance resolution 10 ma 0 to 1 99 Q El E Display range 0 01 to 1 99 Q E E Bond lead null range
11. RED LINK and a voltage 250 V or 500 V is applied between the shorted L N and the remote probe The probe is connected to any metallic locations on the appliance under test to ensure there is no breakdown of the insulation i o H The insulation test probe is i L connected to all exposed metal parts to ensure electrical T separation from earth i N i 1 500V i i Appliance under test i E I e do o a m a i yn PAT tester Test lead resistance null The resistance of the Bond lead can be nulled to remove the lead resistance from the measured resistance This is important when testing very low resistances where the test limit is set to 0 10hms To null the test lead resistance of a bond lead 1 From the HOME screen use the RIGHT arrow key to select the SETUP tab 2 Press the NULL Hotkey The Lead Null screen will appear as below with the Set Lead Null option highlighted fo If a lead null value is already set the lead null symbol will be displayed 23 3 4 Lead Null Remove Lead null Connect bond lead between 2 Probe Socket and Zero post Press test button to Null Connect the Black bond lead between the Bond socket and the Zero post on the front panel as below Press the TEST button The PAT400 will display the value of the test lead as a Null SET value Q and display the symbol in the top of the screen as below Lead Null oO Remov
12. RESULTS Hotkey The Test Results screen will be displayed for that asset as below TestResults Result Limits Asset ID 2 Test Date 19 07 2011 Time 12 06 Test Due Date 19 07 2012 SS d LAE 6 To exit this screen press HOME or Esc NOTE 53 wd imine Barcodes can be printed by using the PRINT BARCODE Hotkey 7 4 2 Printing barcode labels Duplicate barcode labels can be printed from the TEST RESULTS screen This allows replacement of labels if they are damaged or multiple labels are required for an asset To print a barcode label 1 Enter the Test Result screen as above 2 Ensure the Brother 2430PC barcode label printer is switched on and connected to the USB port of the PAT400 SS v d imine 3 Press the PRINT BARCODE Hotkey 45 8 1 Test groups Overview of test groups Test groups are used to simplify the testing of an asset A test group is a collection of tests that when run perform all the tests allocated to that test group The PAT400 s are shipped with a range of test groups for the majority of electrical equipment that will require testing as detailed below Additional test groups can be added up to a limit of 100 Existing test groups can be edited or deleted as required Creating a test group 1 From the HOME screen use the RIGHT arrow key to select the SETUP tab Home Setup Data fo gt 0 Client Mit TEST GROUP MANAGER Location Company Quick Test Keys Setup
13. Rating 4 Increment Room ID Room ID Asset ID Retest Frequency Mi Retest Frequency M Client Client Location Location Enter asset ID and select test group Press SAVE to store asset data Press Esc to abort TEST to store and test or Esc to abort 31 4 2 Definitions of fields Field Limit Description Asset ID 10000 Unique number or combined letters and numbers Enter by typing from the keyboard or scanning a barcode Separate clients can use the same ID But one Client cannot have two identical Asset IDs Test Group 100 Drop down box of available test groups Press OK to access list DOWN UP arrow to select and OK to enter Description General description of asset Cooling fan hand drill etc Serial Number The manufacturer s serial number Fuse Rating A Fuse fitted to the mains plug or internal fuse if using continental plugs Room ID Location of asset to room level Retest Frequency M Repeat test frequency in months The default is set to 12 months Client 100 Customers name This is created in SETUP Location 2000 Site details Each client can have multiple locations This is created in SETUP Fields marked are mandatory fields Data cannot be saved unless these are completed Either DEFAULT or Client name and Location required before data can be saved Note Spaces can be saved as a Client or Location but appear as blank fields when reviewed in
14. Test results and data transfer occooccccccccccncocnconnnoncnnnnnnnnnnnnnnnnnnnnnnonnnonnnnnnnnnnnnnnnnnnnnnnnnninnninos 39 7 1 Backup to USB memory SM le aia 39 7 2 Importing restoring data from USB memory SticCk coocccocccocncoocncnocnconcncncnconcnconononononoss 40 7 3 EXPO TesullS TO SV o pc aoa ac oe aed acne ee cs 42 7 4 Ac t ssing test results O 43 A E o o o AAA N A N 46 8 1 Creating a test gro UD adora 46 8 2 Allocating test groups to HotkeysS ooccoocccoccococooccocococonoconocononnnnnnnnoncnnnnnnnrnnnrnnnnnnnnnaronnronnnnanos 48 8 3 Editing atest CT OUND ct e dl 50 8 4 Deleting a testuroUD ii ee ee lee nae Neel eves 51 8 5 Repeat tesis it SS sands 52 9 QUICK ESOT haiti ete ae ete eee 53 10 SETUP MENU OPINAS ta ds 55 10 1 A e 55 102 LOCOS de ee ete eds 58 103 COMPA ld 61 10 4 Quick test configuration 00d eke ee i ld dla a a aa 61 199 Date Time SOU GS iia dades 63 10 6 GhANGING LANGUAGE xcs sida e A e E 64 10 7 Restoring defalllt SCtIngs oi loca ba 65 10 8 ABOUT PAT400 software version and Megger contact details ccocccocccconccocncnnos 65 11 PATA COMP AUN ICY ainsi ee Cems A a de cd 67 12 Care and Maintenance e de led 68 13 A e Gean oe eakona stance eke a 68 Appendix A Test types eXplalded ini sli id 68 A 1 C n nuity amp DONA GS CHING ersan bs 68 A 2 Lee LiKe ai testing eE LE EEE a O 70 A 3 Lea
15. To restore the PAT400 to the factory shipped configuration 1 From the HOME screen enter the SETUP menu option by pressing the RIGHT arrow key then select DEFAULT SETTINGS option as below Home Setup Data 0 3M Client VA Location Company Quick Test Keys Setup Date Time Language Default Settings LEE Existing records and test groups should be backed up prior to restoring factory settings 2 Press OK to access the Restore Defaults screen Restore Defaults fod Warning Instrument will be restored to factory settings All results and test groups will be reset to factory defaults All recorded or modified data will be lost Press OK to continue Esc to abort 3 Press OK to proceed or Esc to abort 4 A popup message will ask you to press OK to confirm restore to defaults 5 The PAT400 will then reboot with the default settings 10 8 ABOUT PAT400 software version and Megger contact details To select the product information and Megger contact details 1 Using the RIGHT arrow key select SETUP in the top menu option then the DOWN arrow to select ABOUT option 65 About 2 Press OK to access the ABOUT screen For technical support contact www megger com Or call 44 0 1304 502 102 serial Number 1000 752 101050025 Firmware Version 2 22 Build Date 09 38 59 Aug 17 2011 OS Version 15 0 10 0 20 Asset Database Version 1 03 3 To exit the ABOUT screen press Esc
16. appliance tester 1 PAT400 series appliance tester 1 Carry case carry handle and strap 1 Carry case carry handle and strap 1 Quick start guide 1 Quick start guide 1 Black test lead set with probe and clip 1 Black test lead set with probe and clip 1 IEC type power cord 30cm Extension 1 IEC type Power cord 30 cm Extension lead adaptor lead adaptor 1 PC power supply test adaptor 1 Warranty card 1 Warranty card 1 Owners CD manual 1 Owners CD manual 1 Flash test lead PAT450 ONLY 1 Flash test lead PAT450 ONLY X 2 Safety Warnings The following safety warnings and precautions must be read and understood before the instrument is used They must be observed during use E For safety only connect the PAT to a supply that is properly earthed If in doubt the supply should be checked by a qualified electrician E Do not use the instrument if there are any signs of damage E All test leads probes and clips must be in good order clean and with no broken or cracked insulation E Probes and clips should be held behind the finger guard E Test leads not used during a measurement should be disconnected from the appliance tester E For dual voltage testers both sockets can be live simultaneously E Only connect one asset to the PAT during testing El Tests should be carried out in the order recommended below An appliance that fails a test should be repaired before further testing is carried out Recommended sequence 1 Earth bond cont
17. ms The test result is stored as a single PASS or FAIL result as there is no value in storing the individual trip times Test button failure The RCD test sequences include an RCD test button check This works by automatically monitoring the 230 V supply through the RCD If the RCD test button fails to trip the RCD the RCD has failed However the PAT400 will wait for a trip In this case a manual fail is required PRESS THE F key This will log the test as a fail and allow the result to be saved Power lead extension lead testing Power cords and extension leads are tested in a similar way The principle differences are the need to use an extension lead adaptor when testing extension leads as the lead must be looped back to the PAT400 to allow bond and polarity testing Extension leads or power leads with surge protection should be tested with an Insulation test voltage of 71 A 7 A 8 250 V This prevents the surge protection from operating and artificially failing the lead Extension leads fitted with RCDs should be tested as per an ordinary plug in RCD In addition the following tests can be used Bond test continuity test Differential leakage test The RCD must be switched on manually during the test The Insulation test will not test beyond the RCD and consequently has little value Lead length up to 50m can be compensated However they can exceed the recommended length for their cross section Maximum recommend
18. second page Drop down box This is required so the instrument knows which test connectors are to be used Options Class 1 Class 2 EXT Check box configuration options available on second page Check box configuration options available on second page Check box configuration options available on second page Check box configuration options available on second page These fields require mandatory data They cannot be left blank 5 When complete press the NEXT PAGE Hotkey The test options for each of the selected tests will appear as below Selected Tests fo Visual eros oe a A Continuity pamon v eo js HA 1 8 Flash Z RCO bhi Save test group Now the test limits test times and repetition settings can de adjusted for each test if required Use the UP DOWN arrow keys to navigate the screen All options are drop down boxes Press OK to access each drop down list On completion press the SAVE Hotkey The test group can now be allocated to one of the test group HOT KEYS Allocating test groups to Hotkeys Test groups can be allocated to one of four TEST GROUP Hotkeys on the HOME screen To allocate a test group 1 Press one of the four TEST GROUP Hotkeys i 2 A list of test groups numbered 1 to 9 will appear Blank fields indicate a number that has not yet been allocated a test group 48 3 9 6 Class1 O Za Description El Kettle earthed
19. the equipment from the supply The PAT400 can be connected to an adjacent electrical outlet and a bond test conducted to the case of the asset The measured resistance will be The resistance of the asset to the earth circuit wall plate or fused spur The resistance of the fixed wiring through the building to the earth point into which the PAT400 is connected This could be a few metres or 10 s of meters Allowance should be made for the additional building fixed wiring resistance when deciding if the asset is safe to use Parallel earth paths Parallel earth paths warnings apply to a range of measurements See Appendix A 8 for further information 25 A Bond limit exceeded Testing a very low resistance circuit using the 25A Bond test can generate the message 25 A Bond limit exceeded 10 A Bond enabled To prevent the high current bond test from exceeding the 25 A limit testing of very low resistance typically lt 0 03 Q will automatically drop the test current to 10 A Excessive lead resistance The bond test may fail due to the excessive length of the equipment supply cord Extension leads may also fail due to increased resistance induced by long cable lengths When a bond test fails the PAT400 will display a lead compensation table allowing the pass limit to be modified See section 3 11 and Appendix A 6 for further details on lead compensation 69 A 2 A 3 Insulation testing This is used to confirm there is se
20. to AU AS NZ253112 16 A 1000 769 415 V adaptor lead 4 pin to BS BS1363 16A 1000 767 415 V adaptor lead 4 pin to SC CEE7 7 16A 1000 768 415 V adaptor lead 5 pin to AU AS NZ253112 16 A 1000 772 415 V adaptor lead 5 pin to BS BS1363 16A 4000 770 415 V adaptor lead 5 pin to SC CEE7 7 16A 1000 771 Bar code scanner USB 1001 047 Pass fail barcode label printer USB 1001 046 USB lead PAT Printer 25970 041 Barcode printer label refills Cartridge 90001 010 Appliance bar code labels 1 1000 6121 483 Roll of 1000 FAIL test labels 1001 227 Roll of 1000 PASS test labels 1000 971 PAT accessory pouch 2001 044 PAT test certificate book 1001 299 80 Appendix E Repair and Warranty The instrument contains static sensitive devices and care must be taken in handling the printed circuit board If an instrument s protection has been impaired it should not be used but sent for repair by suitably trained and qualified personnel The protection is likely to be impaired if for example it shows visible damage fails to perform the intended measurements has been subjected to prolonged storage under unfavourable conditions or has been subjected to severe transport stresses NEW INSTRUMENTS ARE GUARANTEED FOR 1 YEAR FROM THE DATE OF PURCHASE BY THE USER Note Any unauthorized prior repair or adjustment will automatically invalidate the Warranty CALIBRATION REPAIR AND SPARE PARTS For service requirements for Megger Instruments cont
21. to select the SETUP tab 30 Press the TEST GROUP LYA Hotkey Press the EDIT TEST GROUP Hotkey Edit Test Group 0 DR E escription air dryer Double insulated upply 230 isual arth Bond ontinuity 4 lass ash eakage TK 1 i A O O nsulation 141134 olarity Press the OK button to access the drop down list 50 8 4 Edit Test Group oy escription upply isual arth Bond ontinuity nsulation SIS ISIDISE L 1215 3 a olarity 5 Select the test group to be edited and press OK to accept 6 The test group settings can be adjusted and saved as per the test group ADD function above Deleting a test group To delete a test group 1 From the HOME screen use the RIGHT arrow key to select the SETUP tab gt Q 3M0 2 Press the TEST GROUP MANAGER LYA Hotkey 3 Press the DELETE Hotkey Delete Test Group O Kettle earthed Bumy Jevy Fash r 4 4 g 4 m Ro y E 4 Press OK to activate the drop down list Select the required test group then press OK 5 Press the DELETE Hotkey 6 The display will ask for confirmation that the test group is to be deleted 7 Press OK to accept Esc to exit Note A test group cannot be deleted whilst there are assets in the database that are using that test group 91 8 5 Repeated tests It is possible to create test groups with repeated Bond Continuity Insulation and Flash tests An example screen i
22. true short circuit but has a high inrush current 3 12 2 Reversed supply UK instruments The PAT400 will detect a reversed polarity Phase Neutral supply and abort the initialisation The display will show the warning ERROR 82 Mains polarity reversed European instruments The instrument will pass initialisation and display the Home screen The supply polarity will be shown as Reversed 3 12 3 Supply earth fault The PAT400 will test for a good supply earth during initialisation A faulty or missing earth will return the error Error 73 Mains supply Earth Fault 3 12 4 Parallel earth paths If the PAT400 detects more than one earth path the warning Unable to verify earth connection Parallel paths may exist Refer to user guide The PAT400 has detected more than one earth path during the Earth continuity Earth bond Insulation or Earth leakage tests Refer to Appendix A 8 for further details 3 12 5 Database full Exceeding the storage capacity of the database will create the following warning Error Database Full Unable to save data Press OK to continue The test result will NOT be saved To free up memory for further test results 1 Backup the existing database to a USB storage device 2 Delete records from the PAT400 See Section 4 for further information on PAT400 memory 30 Using the memory Important overview All records are stored under a client The PAT400 can store up to 100 50
23. 0 PAT420 PAT450 PAT410 PAT420 PAT450 UK only PAT450 UK only PAT450 PAT410 PAT420 PAT450 74 Group Test Applied Pass Limit Duration o KETB EL1B EL4B RCD FULL PC DRY ET EL EL2 EL3 EL4 RCD Personal Computer IT Equipment Hairdryers Double Insulated Kettles Earthed Kettles Earthed 200 mA Continuity Test 230 V Extension Leads 3 Core 230 V Extension Leads 3 Core 200 mA Continuity Test 230 V Extension Leads 2 Core 110 V Extension Leads 3 Core 4 way 230 V Extension Leads 3 Core 4 way 230 V Extension Leads 3 Core 200 mA Continuity Test Portable RCD 30 mA Portable RCD 5 tests Visual Inspection Earth Continuity Operation test 230 V Differential Earth Leakage 230 V Visual Inspection Insulation test at 500 V Operation test 230 V Differential Earth Leakage 230 V Visual Inspection Earth Bond at 25 A Insulation test at 500 V Operation test 230 V Differential Earth Leakage 230 V Visual Inspection Earth Continuity Insulation test at 500 V Operation test 230 V Differential Earth Leakage 230 V Visual Inspection Earth Bond at 25A Insulation test at 500 V Polarity Visual Inspection Earth Continuity Insulation test at 500 V Polarit Visual Inspection Insulation test at 500 V Polarity Visual Inspection Earth Bond at 25A Insulation test at 500 V Polarit Visual Inspection Earth Bond at 25A x4 Insulation test at 500
24. 0 to1 00 Q E E Continuity test 200 mA El E E Open circuit voltage 4 0 V dc 0 10 E E E Current output 200mA 0 20 into 20 load m E a Continuity resistance accuracy Sse ee E E E 8 d y 5 5 digits 1 00 to 19 99 Q a m a Continuity resistance resolution 10 mQ a a Display range 0 01 to 19 99 Q a E Continuity lead null range 0 to 9 99 Q E Insulation test 250 V amp 500 V E E El Insulation resistance accuracy 2 5 digits 0 to 19 99 MQ a E E 230 V supply 5 10 digits 20 to 99 99 MQ E a a Insulation resistance resolution 0 01 MO a a El Display range 0 10 to 99 99 MO a a E Substitute leakage test E E E Test voltage and frequency Nominal 40 V ac nominal mains frequency Leakage current accuracy 5 5 digits E E E Leakage current resolution 0 01 mA A a Display range O to 19 99 mA Bl Reading corrected to 230 Vac 10 or 110 Vac 10 Differential leakage current E E E Test voltage amp frequency Nominal mains supply pinetenval leakage current 5 5 digits i accuracy mete nia leakage current 0 01 mA resolution Display range 0 to 19 99 mA Reading corrected to 230 Vac 10 or 110 Vac 10 Touch current test Test voltage amp frequency Nominal mains supply E E El Touch current accuracy 5 5 digits E E E Touch current resolution 0 01 mA E a Display range O to 10 mA E E E Reading corrected to 230 Vac 10 or 110 Vac 10 Operational test E a Test voltage amp frequency No
25. 1 Timer 0s Bond 0 12 2 2 Press OK to access the Cable Resistance Calculator as below OR Press Esc to fail the Asset and save or abort the results OR Press R to re run the continuity test Test Results Cable Resistance Calculator Length Cross Section Ins 5 i Lass i dhnii pe Resistance 0 4875 o Use the drop dowen lists to specify the length and cross sectional area of the supply cable Press TEST to finish Tes Timer 0s Bond gt 1 99 Q 3 Enter the cable Length in metres and the conductor Cross Section mm OR a Resistance can be entered if this is known 4 Press TEST to complete the test The PAT400 will now proceed to the next test if the resistance was a PASS or to a fail screen if the resistance was still outside the modified limit See also Section A 6 for cable length limitations and RCD protection on long leads 29 3 12 3 12 1 Power On tests Running a leakage or load test will operate the asset under test Some assets such as vacuum cleaners disc cutters etc can draw high initial load currents Inrush current The PAT400 will under these circumstances report the asset has a short circuit If this warning is displayed it is recommended the following actions are taken 1 Where possible check the asset does not have a short circuit the fuse would normally be blown in such circumstances prior to it being replaced 2 Proceed ONLY if you believe the asset is not a
26. 66 11 PAT4 compatibility The PAT400 s have additional test capability that does not exist on previous PAT testers To maintain compatibility when transferring data between the PAT 4 and the PAT400s the following should be considered Test options The PAT400s include additional tests not available on the PAT4 These include 250 V Insulation testing RCD testing Touch leakage available on the PAT4E Substitute leakage available on the PAT4E Other differences to be considered PAT400 PAT4 Continuity test range 19 99 O 9 99 Q Continuity test resolution 0 01 O 0 001 O Parallel earth detection Yes No Insulation test range 99 99 MO 50 MQ Differential Leakage testing 19 99 mA 15 0 mA Flash test range 3 0 mA 3 5 MA In addition the PAT400 includes additional test limits that are not supported in the PAT4 Test groups Test groups that contain tests not available on the PAT4 should be avoided The PAT4 only allows 3 characters in the name of a test group Use test groups that conform to the PAT4 format Storage differences PAT400 PAT4 Test groups 100 50 Clients 100 10 Locations 2 000 20 Assets 10 000 1 000 Test records 10 000 1 000 Memory capacity The PAT400s have 10x the storage capability of the PAT4 storing up to 10 000 test records compared to 1 000 test records Asset ID The PAT400 can use the same Asset ID across multiple clients For example Client 1 Asset 0001 0002 0003 Client 2 Asset 0001 0002 0003
27. After the details have been changed press the SAVE Hotkey Delete Location Warning Deleting a Location will also delete all assets and test results associated with that Location 1 Select LOCATION from the SETUP menu and press OK In the Location screen select the DELETE Hotkey 59 Select Location Please selectthe location you wish to delete Megger Instruments Limited 2 Select the desired Location then press the NEXT PAGE Hotkey Delete location Client Megger Group Location Megger Instruments Limited Address 1 Archcelifte Road Address 2 Town City Dover County State Kent Postcode Zip CT17 SEN il 3 Press the DELETE Hotkey 4 A popup message will ask you to confirm 10 2 3 Changing Locations You may only change to a Location in the current client 1 In the SETUP tab press the SELECT LOCATION Hotkey 2 Select the desired Location and press OK 60 10 3 10 4 Select Location fo Please select the current location Megger Instruments Limited 3 Press the SAVE Hotkey to store the changes Company The Company page provides data entry for the testing company to add their company details to the PAT400 The Label Text is a field that is used to add text to printed labels For example you may wish to add the testers name to a label This field appears at the top of the barcode label 1 From the HOME screen enter the SETUP menu option by pressi
28. Asset data Saving a test result On completion of a test sequence the message asset PASSED and the SAVE key will appear ale 1 Press the SAVE E Hotkey or press the SAVE and PRINT a barcode label Hotkey to print a barcode label and save Note A Brother P Touch 2430PC must be connected to print a barcode label 2 Ifno Asset ID was entered before testing started the asset screen will be displayed as below The test group will already be set as this was selected when the test was run Add Asset Test Group Description AT E Fuse Rating a Sd Room ID AAA Retest Frequency M cient AA Location Enter asset ID and select test group Press Ezc to abort 32 3 Enter the Asset ID This can be via the keyboard or scanned in by barcode scanner If an Asset ID already exists in memory a duplicate Asset ID warning will be displayed In this case enter a different Asset ID number Examples of Asset ID formats Asset IDs are limited to 20 characters 0001 0002 0179 7082 MEGGERO0001 MEGGERO002 AA0001 AA0002 BF0001 BF0002 4 Press OK 5 Press the DOWN arrow and complete the additional asset data as required Test Group Client and Location cannot be changed in this screen 6 When completed Press the SAVE Hotkey The asset will be added to the memory under the current client and location Add Asset Asset ID 000234 Test Group Sct Yi Description Fan heater Y serial Number
29. HOTKEY options e OPTION 2 Press the TEST button this takes you to the TEST ASSET screen e OPTION 3 Scan the asset ID with a bar code scanner then press TEST asset details must already be stored in the PAT400 otherwise PAT400 defaults to ADD ASSET screen 17 Option 1 STARTING A TEST USING HOT KEYS 1 Select a Class I Class II IEC extension lead or RCD test group by pressing one of the HOT KEY options A list of TEST GROUPS are displayed that are relevant to that type of equipment Example Class test groups Class Class test groups Da Diescri IEA ctas 230 II r Personal Computer IT equip O Class Il test groups Kettle Earthed El Class IEC Power and Jiitandard Class An extension lead test groups Kettle Earthed 200mA cont A 110 Tools Class 1 RCD Plug In RCD test groups 110 Tools Class 1 Flash Add Asset fast access 2 Select one of the test groups by pressing the relevant number then the TEST button or Press the number twice to start the test sequence or Scroll down to the required test group and press TEST For more Information on test groups adding editing configuration or deletion go to section 8 Option 2 STARTING A TEST PROCESSING THE TEST BUTTON 1 From the HOME screen press the TEST button The display will show the TEST ASSET page as below Test Asset Test Group AU 1 Det a RT Search for TEST GROUPS aie bj e UNA VA Press once for direct entry
30. Kkade estudi sip 70 A 4 Evo Ve EStdt sit 11 A 5 A e eee re 71 A 6 Power lead extension lead testing ocooocccocccocncocnccncnoncnconcnonnnnnncnnnnnonononnnnnnnnnnnnnnnnonnnnnnnnnnnss 71 A 7 Flash testing PAT450 Only oooocooocccoccccocccononocncncnonncnnonncnnconncnnnnnnnnnnnncnnnrnnnnrnnnnnnnnnonnncnninnnnnnanes 72 A 8 Parallel Earth Path WARNING ooccocccoccoocccoccoccoocccoccoccconccocccncononconnnnnnonnonnnnnnnnnnonnnonnnnnnnnonnnnnnonananos 12 A 9 PAT400 Factory Default Test GroupS oocccoccccoccccocncoccnncnconcncncnnoncnonnnnnnnnnnnnonnnnnnnnnnnnnnnnnnnnonaninnnnenares 74 Appendix B Barcode sample table ooccoccocccccccncococcnocncncconocnnononononcnononnnnnnonnnnnnnnnnnnonnnnnnnnnnnnnnninanes 76 Appendix C Specification asses ts 78 Appendix C Specification ci sd 79 Appendix E Repair and Warranty o coocoocccccocccocccccococcnnnncoconnnonnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnninninanes 81 X 1 Unpacking the carton Unpack the carton contents carefully There are important documents that you should read and keep for future reference Please complete the pre paid warranty card and return it to Megger Instruments Limited as soon as possible to help us reduce any delays in supporting you should the need assistance UK carton contents European carton contents PAT410 PAT420 and PAT450 PAT410 PAT420 and PAT450 1 PAT400 series
31. S in the TEST GROUP Enter asset ID and select test group box and the cursor will jump to SC1 Press Esc to abort If no contents start with that letter or number nothing will happen Battery and fuse location fitting and replacement Battery type 1 x 8 4 V NiMH rechargeable PP3 IEC6F22 NEDA 1604 6HR61 Fuse type PAT400 EU DE AU US 2x 2A F HBC 50 kA 600 V Part No 90000 939 PAT400 UK 1 x 250 Vac 100 mA HBC 1 5 KA Part No 25413 295 An 8 4V IEC6F22 NiMH rechargeable battery is fitted to all PAT400s The battery is continuously charged whilst the PAT400 is powered The battery provides a fast re boot function when the PAT400 is unplugged moved between locations and re started within 5 minutes The battery shall only be replaced by an equivalent rechargeable battery when the re boot facility ceases to work To replace the rechargeable battery Switch off the instrument Disconnect the instrument from any electrical circuits Remove the battery cover Remove the old battery and refit new battery following correct polarity as marked on the battery compartment Replace the battery cover Warning Only use NiMH batteries Do not attempt to recharge non rechargeable Primary cells in the PAT400 Doing so may result in instrument damage and may cause personal injury 11 For Fuse replacement ao DE e o a Warning Fuses are at mains potential The electrical supply MUST be disconnected prior to removing the
32. SB Export to USB CSV View results 2 3 Switching off the PAT400 2 3 1 Normal Power Off To switch off the tester press the RED off button The display will show the message It is now safe to remove power Now the mains plug can be removed from the supply Switching off using this button prevents the FAST Re start battery from discharging unnecessarily 2 3 2 FAST Re start If the tester is to be moved to a new location and testing continued simply unplug the unit from the mains supply and reconnect it in the new location The appliance tester will enter a hibernation mode during the move and restart instantly from the point power was disconnected without any delay Any test results are retained On reconnection the previous test result can still be saved The rechargeable 8 4 V NIMH battery is used to maintain hibernation status whilst unplugged This battery is continuously charged whilst the appliance tester is connected to the mains supply Continuous use of the hibernation mode will discharge the battery Should the move take longer than 5 minutes the appliance tester will leave hibernation mode and complete a full power down 15 3 Testing with a PAT400 3 1 Connecting an asset to the PAT400 Assets are tested through the test connectors on the top of the instrument An asset is simply plugged into the appropriate socket A power cord IEC lead or an extension lead needs to be wrapped back to th
33. SCIB Y Standard Class 1 200mA con gt Power cord Extension lead Kettle earthed 200mA cont G 110 Tools Class 1 ia El AH Using the DOWN arrow navigate to the desired row 1 9 as below Class1 ID Re Mame gt EC set af standard class 1 earthed BC Fe Persona computer IT equip EC e Hikme 7 Ey sci el standard Ciass 1 200mA con Bi ee EL 2 7 RCD Press OK to access the drop down list of available test groups Class fo Jame Description fl Standard class 1 earthed Personal computer IT equipm Kettle earthed Standard Class 1 200mA con gt Kettle earthed 200mA cont 110 Tools Class 1 RCD Select the required TEST GROUP and press OK The TEST GROUP will be allocated to the selected field 49 8 3 Class1 O Description El INE 3 Enar class eared BO E Hke 7 Ey sce el standard Class 1 200mA conl Kettle earthed 200mA cont TOV Tools Class 1 TOIF 3 110 Tools Class 1 Flash NOTE The TEST GROUPS can be freely allocated to any of the nine fields and in any of the four Hotkeys If desired a CLASS TEST GROUP can be allocated to the RCD Hotkey for example Editing a test group Each test group can be edited or deleted NOTE When restoring a database the test groups will also be overwritten Always backup your test records before restoring a database To edit a test group 1 2 3 4 From the HOME screen use the RIGHT arrow key
34. V Polarity Visual Inspection Earth Continuity x4 Insulation test at 500 V Polarit Visual Inspection RCD 30 mA test Visual Inspection RCD full test sequence 0 5 Q 27 MO lt 0 5 Q 27 MO 25 MO lt 0 5 Q 27 MO lt 0 50 27 MO IV IA Ne did did Notes Description of RCD says Portable RCD in FW version 2 01 and below Description of RCD FULL says Portable RCD 30mA 5 tests in FW version 2 01 and below mn o1 On o1 On o1 on al ai on ai on ar OI O1 Ol nn nn nn nn nn NNNNA PAT410 PAT420 PAT450 PAT410 PAT420 PAT450 PAT420 PAT450 PAT410 PAT420 PAT450 PAT420 PAT450 PAT410 PAT420 PAT450 PAT410 PAT420 PAT450 PAT420 PAT450 PAT410 PAT420 PAT450 PAT410 PAT420 PAT450 PAT410 PAT420 PAT450 Appendix B Barcode sample table The following sheet is an example of a bar code sheet that can be used in conjunction with the optional OPTICON barcode scanner The sheet allows fast input of standard data which would otherwise need to be manually typed in or selected from a drop down list 76 Barcode look up sheet Test Groups Description Fuse rating A SC1 Kettle 3 i MN TU K e t t o SC1 RCD 5 I ARA MT SC1B i 0000010 a es o UM PLATE o SC2 i N00 DAN 1 O P owe r Till T ii Extension lead 2 way 13 Extension lead 2 w a y k 3 TO1F UE OL 16 TO2 Extension lead 4 way UNI ML A AE TO2F Extension lead 4 way
35. a maximum of 2 000 To add a LOCATION select the LOCATION option from the SETUP menu Follow the same process as adding Clients in Section 10 1 Firmware revisions earlier than 2 2 were limited to 50 locations per Client 10 2 1 Adding Locations 1 Select LOCATION from the SETUP menu and press OK The Location screen will be displayed with the Add Edit and Delete Location Hotkeys as below Location fo Press add hotkey to add a location Press edit hotkey to edit a location Press delete hotkey to delete a location sll 2 Selectthe ADD Hotkey to add a new Location to the current Client Add Location fo Client Megger Group Location Ja address 1 Address 2 towo County State PostcodeiZip 3 Complete the text fields with the necessary Location information Only the Location name is mandatory 4 On completion press the SAVE Hotkey 58 10 2 2 Editing and Deleting Locations Edit Location 1 Select LOCATION from the SETUP menu and press OK In the Location screen select the EDIT Hotkey 2 Select the desired Location then press the NEXT PAGE 9 Hotkey Select Location Please select the location you wish to edit Megger Instruments Limited 3 Change the Location details as required It is not possible to change the associated Client Delete location Client Megger Group Location Address 1 Address 2 PARA Town City CountyState Postcode Zip 4
36. act Megger Instruments Limited Archcliffe Road Dover Kent CT17 9EN England Tel 44 0 1304 502 243 Fax 44 0 1304 207 342 Megger operate fully traceable calibration and repair facilities ensuring your instrument continues to provide the high standard of performance and workmanship you expect These facilities are complemented by a worldwide network of approved repair and calibration companies to offer excellent in service care for your Megger products Returning your product to Megger UK and USA service centres 1 When an instrument requires recalibration or in the event of a repair being necessary a Returns Authorisation RA number must first be obtained from the address shown above You will be asked to provide the following information to enable the Service Department to prepare in advance for receipt of your instrument and to provide the best possible service to you e Model e g PAT400 e Serial number to be found on the underside of the case or on the calibration certificate e Reason for return e g calibration required or repair e Details of the fault if the instrument is to be repaired 2 Make a note of the RA number A returns label can be emailed or faxed to you if you wish Pack the instrument carefully to prevent damage in transit 4 Ensure the returns label is attached or that the RA number is clearly marked on the outside of the package and on any correspondence before sending the instrument
37. afety IEC 61010 1 CAT II 300 V 1 E E EMC IEC 61326 1 2006 IEC 61326 2 2 2005 E a E Weight PAT410 instrument E with packagin 21 KG 9 2K9 PAT420 instrument 4 4 kg 4 9 kg with packaging PAT450 instrument with packaging SH R27 E Dimensions Instrument mm 120 H x 255 W x 320 L m Instrument mm 155 H int x 180 H UK x 255 W x 320 L E El Dimensions mm Packaging 210 H x 280 W x 390 L o o all instruments Appendix D Ordering information ORDERING INFORMATION Product Order Code PAT410 AU 1000 753 PAT410 DE 1000 748 PAT410 EU 1000 747 PAT410 UK 1000 745 PAT420 AU 1000 746 PAT420 UK 1000 752 PAT450 AU 1000 749 PAT450 DE 1000 751 PAT450 EU 1000 750 PAT450 UK 1000 755 Included accessories relevant to territory Printed quick start guide Full user guide on CD Calibration certificate Continuity earth bond lead probe black 2000 870 Extension lead adaptor 13 A BS 2000 881 Extension lead adaptor 110 V BS 6220 639 Extension lead adaptor ELA 230 V AU AS NZ2531 12 2000 883 Extension lead adaptor ELA 230V SC CEE7 7 2000 882 Extension lead adaptor ELA 120V US 2001 290 Flash lead 3 0 kV 3 5 mA red 5310 401 Carry case with lead document pouch 2000 962 Plug adaptor IEC C6 C13 3way 5A PSU 2000 551 Optional accessories PowerSuite software Extension lead adaptor ELA 110 V BS4343 6220 639 110 V mains lead adaptor BS1363 BS4343 1000 766 415 V adaptor lead 4 pin
38. arrow to select Date Time as below Home Setup Data fan Client Location Company Quick Test Keys Setup Date Time Language Default Settings About xie keje 3 Press OK to accept 4 For DATE settings use LEFT RIGHT arrow keys to select the field to be changed Enter the desired values using the keyboard For TIME settings use the DOWN arrow key to select TIME then the LEFT RIGHT arrow keys to select the fields to be changed Date Time O Enter date and time below Date Ml flor 2011 DD SMM YYYY Time 12 fso 14 HH MM SS 5 Press the save Hotkey to accept changes 63 10 6 Changing Language 1 From the HOME screen enter the SETUP menu option by pressing the RIGHT arrow key then select LANGUAGE as below Home Setup Data Otan Client Location Company Quick Test Keys Setup Date Time Default Settings About 2 Press the OK key and the language selection screen will be displayed Set Language O SES ACI Y English Wahlen Sie Ihre Sprache vor Deutsch Selecteer uw taal Nederlands 3 Use the UP DOWN arrow keys to select the required language 4 Press OK to save 64 10 7 Restoring default settings WARNING Restoring factory default settings will overwrite all stored data and settings Stored data will be lost Megger strongly recommend backing up all data prior to restoring factory settings Backups can be restored if necessary
39. ate a relay error and necessitate restarting the PAT tester Power should be disconnected and reconnected Start up initialisation The first time the PAT tester is started the instrument will ask for the operating language time and date to be set Set Language Y English Wahlen Sie Ihre Sprache vor Deutsch Selecteer uw taal Nederlandisch 1 Use the UP DOWN arrows to select the operating language from the options listed 2 Press OK when complete Date Time Enter date and time below Date MA oz 2011 DD MM YYYY Time fog 56 fos HH MM SS l 13 3 Using the RIGHT LEFT and OK keys to enter the date and time Date format is DD MM YY YY Hr Min Sec Time format is 24 Hr 4 Press the SAVE Hotkey to accept changes Further changes can be made in the menu SETUP options section 10 5 On completion of the initialisation the following warning screen is displayed when the PAT tester is switched on UK configured PAT400 instruments Warning WARNINGS The folowing warnings must be read and understood before proceeding e Ensure only one asset is connected and tested at a time e Faulty appliances can present a shock hazard Avoid contact with all connectors and conductive parts during testing e All tests that include a load or leakage test will run the asset Ensure asset is switched on and safe before starting the test sequence Press OK to confirm these warnings have
40. been read and understood Non UK configured PAT400 instruments Warning oO WARNINGS The following warnings must be read and understood before proceeding e Faulty appliances can present a shock hazard Avoid contact with all connectors and conductive parts during testing e All tests that include a load or leakage test will run the asset Ensure asset is switched on and safe before starting the test sequence Press OK to confirm these warnings have been read and understood NOTE This screen is not displayed if the PAT tester is re started within five minutes of being un plugged or when the PAT tester restarts from the same screen as before 5 Press OK to confirm you have read and understood these warnings The instrument will display the following HOME screen when all initial tests pass 14 2 2 HOME screen explained The HOME screen is the start point of all testing Menu functions Home ae lt Class test groups Test launch screen sath are ti ity lass Il test groups netumentetatas Supply Polarity Normal group Serial Number 1000 743 080908 100 Client Self Tests Passed y Class IEC Power and Client default extension lead test groups Location Location default Company Time 09 56 Plua In RCD Quick tests RCD ug In test groups Date 05 07 2011 Date Time y isen i Language ee Add asset fast access Client Test Results O a Default settings About Backup to USB Restore from U
41. e Lead null Null set 0 02 Q To remove the Lead Null select the Remove Lead Null and press the TEST or OK button The for symbol will disappear 24 3 9 3 6 3 7 Short circuit assets Some assets may appear to the PAT400 to be short circuit This can be caused by large inductive loads In such cases the following warning messages will be displayed Warning Asset may be short circuit Press TEST to continue ESC to abort Only if the operator is certain the equipment is not a short circuit press TEST otherwise press Esc to abort the test Aborting a test All tests can be aborted at any time by pressing the TEST button or Esc escape button Completion of testing On completion of testing all test fields should turn green as below The test results are displayed in the centre column with the pass limits for that test group on the right Test Results Limits Repeat test sequence Hp Print bar code label amp SAVE PE results to memory id a SAVE results to memory e aL On completion of testing the following options are available m gt Retest asset using current test group Warning test data will not be saved for the previous test PA Repair codes Allows repair details to be added to asset test results see section 3 8 below Save the test results to memory and print a barcode label a Megger USB barcode printer must be connected prior to requesting this function D
42. e small IEC socket on the top of the instrument This allows automatic testing of continuity and polarity without connecting the remote probe Standard Class and Class ll assets will also use the additional remote probe for BOND INSULATION or LEAKAGE testing The instruction to connect it is displayed on the screen at the appropriate time The following drawings show how the asset under test should be connected at the start of testing NOTE The dotted line indicates where a 110 V asset would be connected UK PAT testers only Other test leads may need to be connected during the test sequence Follow on screen instructions NEVER CONNECT MORE THAN ONE ASSET AT A TIME 3 1 1 Connecting a Class I or Class ll asset To connect standard Class I or Class Il equipment to the PAT400 gop 1 Plug the asset into the 230 V test socket on the PAT400 TEST To connect 110 V equipment to the PAT400 1 Plug the asset into the 110 V test socket on the PAT400 3 1 2 Connecting an IEC type power cord or 110 V Power lead To connect a standard IEC type power cord computer type power lead to the PAT400 1 Connect the mains plug to the mains test socket on the PAT400 2 Connect the IEC plug to the IEC socket To connect a 110 V power lead use the 110 V to IEC plug adaptor see optional accessories 1 Connect the 110 V mains plug to the 110 V test socket 2 Connect the free end of the 110 V power lead to the 110 V adaptor p
43. ed Esc to cancel Client Location EUR Enter asset ID or test group and press TEST to start a test or press Esc to abort A blank Add Asset screen will appear as below This only contains the Asset ID entered in the previous screen plus current client and location Press OK to add a new asset If no client and location have been added these will say DEFAULT 19 Add Asset El Copy last asset added Asset ID A E vein let Test Group Select test group Yi E A Copy last asset added a in increments Asset ID o serial Number o next available number Fuse Rating a LS CF Room ID Retest Frequency M Client Location Enter asset ID and select test group Press Esc to abort Indicates mandatory fields that are required to save the asset data Further information on the COPY LAST ASSET and COPY amp INCREMENT ASSET ID Hotkeys can be found in section 5 A new asset ID can be added and saved at this stage but it is recommended that this is added after testing is completed Press the DOWN arrow to access TEST GROUPS Press OK to access the drop down list of test groups Add Asset Asset ID Test Group Select test group Description Y Serial Number Fuse Rating 4 Room ID Retest Frequency M Client Location Enter asset ID PC Press Esc to abort Use the UP DOWN arrows to scroll through the list of test groups and then press OK OR Start typing t
44. ed length for extension leads CSA of cores mm Maximum length m 1 25 12 1 5 15 2 5 25 Any lead longer than the recommended length should be fitted with a Residual Current Device RCD with a rated operating current not exceeding 30mA as the earth resistance can be high enough that the operation of standard protective devices cannot be guaranteed Flash testing PAT450 only Flash testing measures the leakage current when high test voltages are applied to an asset Flash testing is NOT recommended for portable appliance testing as it is a destructive test Repeated use on an asset can cause premature failure or possible electrical damage Parallel Earth Path WARNING Occasionally there may be a parallel earth path between the asset under test and the system earth This can arise from a Class asset touching other earthed metal equipment or being electrically in contact with the floor This can create a resistance path back to the electrical supply earth that is in parallel with the asset s own earth return Under these circumstances the PAT400 will warn the operator by displaying the message Warning Unable to verify earth path connection parallel earth paths may exist Refer to User Guide Press TEST to proceed Esc to fail This warning may be repeated on other tests while potential parallel paths exist This message can appear on all tests and is caused by o The equipment under test has an alternative earth pat
45. en Cord Restraints 6 Renew 415V 4 pin 32A 23 Replace Control Knobs 7 Renew 415V 5 pin 32A 24 Tighten Case fixings 8 Renew IEC connector 6A 25 Replace Indicator Lamps 9 Renew IEC connector 10A 26 Replace case parts 10 Renew IEC connector 16A 11 Replace Main Switch 12 Replace Fuse Holder 13 Replace Missing Screws 14 Replace Warning Labels 15 Renew 2core 1 00mn flex 16 Renew 2core 1 50mm flex 17 Renew 2core 2 50mm flex On completion of the repair code screen press the TEST key to log the changes then press the SAVE i lin or SAVE AND PRINT Hotkeys to store the results 28 3 11 Cable compensation A power cord appliance lead or extension lead will frequently exceed the nominal length and consequently the resistance limit set in the standard test groups Rather than having many test groups with different lead lengths the Cable Resistance Calculator screen allows the limit of a Bond or Continuity test to be modified after the measurement On a failed test entering the length of the lead and the conductor cross section the pass limit is adjusted to the correct resistance The result is then passed or failed as necessary To apply cable resistance calculation 1 When a continuity or Bond test fails the screen message alert will be displayed TestResults Test failed do pou wish to apply lead compensation OK to continue Esc to cancel A to repeat test Test Group C
46. est results for each asset can be viewed through the View Results menu option of the DATA tab as es results belonging to the current Client and Location can be viewed 7 4 1 To view a test result 1 From the HOME screen use the RIGHT arrow key to select the DATA tab 2 Use the DOWN arrow to select VIEW RESULTS and press OK 43 Home Setup Data oO Backup To USB Restore From USB Export Results To USB View Results Search and view last recorded test results of an asset Press OK to begin Esc to abort The View Test Results screen will be displayed as below View Test Results toy FIND asset Asset D C Test Group RAN Description PESO Serial Number O Fuse Rating 4 Ses Room ID LONE Retest Frequency M AAN ea 7 cent PAU ADD asset Enter asset ID press search hotkey for list or manual entry Press Esc to abort EDIT asset 3 Enter the Asset ID or press the FIND ASSET Hotkey If there are a large number of Assets IDs this may take a few seconds 4 When the desired Asset ID has been found Press OK to accept The VIEW TEST RESULTS y X Hotkey will appear as below view Test Results oy 5 M Asset ID MUNI Test Group Serial Number Fuse Rating 4 Room ID Retest Frequency M AA Client Location Megger Instruments Limit Enter asset ID press search hotkey for list or manual entry Press Esc to abort 44 5 Press the VIEW TEST
47. ey on the keyboard The display will show a numerical list of options Example of QT screen options for a PAT450 Quick Test Options 0 1 25Amp Bond Test 2 10Amp Bond Test 3 200mA Continuity Test 4 Insulation Test Options 5 Operational Test 6 Earth Leakage Test Options RCD Test 8 Flash Test Options 2 Press the number key associated with the test you wish to run Example Earth Leakage Leakage Menu fo select voltage and press OK or TEST Class 230 V Class Il 230 Differential Leakage Touch Current 2304 Substitute Leakage Asset will operate Ensure only one socket is used asset is switched on and safe Note that for Class Il appliances use the remote probe Test Duration 5s NOTE Where a test has several options such as Earth Leakage a sub menu of options will appear 3 Navigate through the sub menu options if available 4 Press OK or TEST key to start testing 5 Follow on screen instruction as necessary 6 On completion of the test the final measurement will be displayed 93 Timer Os Leakage 0 00mA 7 Quick test times can be changed in SETUP Refer to section 10 4 94 10 SETUP menu options The SETUP menu options allow changes to the instrument configuration that cannot be accessed by Hotkeys 10 1 Clients The PAT400s are shipped with the CLIENT and LOCATION set to DEFAULT This can be changed or additional Clients and locatio
48. freight paid to Megger Copies of the original purchase invoice and packing note should be sent simultaneously by airmail to expedite clearance through customs In the case of instruments requiring repair outside the warranty period an immediate quotation can be provided when obtaining the RA number 5 You may track the progress of your return on line at www megger com Approved Service Centres A list of Approved Service Centres may be obtained from the UK address above or from Megger s website at Www megger com 81 Megger Limited Archcliffe Road Dover Kent CT17 9EN England Tel 44 0 1304 502100 Fax 44 0 1304 207342 Megger 4271 Bronze Way Dallas TX 75237 1017 U S A Tel 1 800 723 2861 U S A only Tel 1 214 330 3203 International Fax 1 214 337 3038 Megger Valley Forge Corporate Centre 2621 Van Buren Avenue Norristown PA 19403 USA Tel 1 610 676 8500 Fax 1 610 676 8610 Megger SARL Z A Du Buisson de la Couldre 23 rue Eugene Henaff 78190 TRAPPES France Tel 33 1 30 16 08 90 Fax 33 1 34 61 23 77 This instrument is manufactured in the United Kingdom The company reserves the right to change the specification or design without prior notice Megger is a registered trademark PAT400 UG en VO3_0711 www megger com 82
49. fuse cover Switch off the instrument Disconnect the instrument from any electrical circuits Remove the fuse cover on the underside of the PAT tester Remove each fuse in turn and check for failure Replace as necessary If no fuses have failed contact Megger Technical services group on 44 0 1304 502 102 Replace fuse cover when complete Note The X symbol on the batteries is a reminder not to dispose of them with general waste at the end of their life Spent NiMH batteries are classified as Portable Batteries and should be disposed of in the UK in accordance with Local Authority requirements For disposal of batteries in other parts of the EU contact your local distributor Megger is registered in the UK as a supplier of batteries The Registration number is BPRN00142 12 2 1 1 Getting started Switching ON the PAT400 Connect the instrument to a suitable electrical supply either 230 Vac or 110 Vac for UK instruments For testing 230 V electrical equipment connect the PAT tester to a 230 V electrical outlet For testing 110 V electrical equipment connect the PAT tester to a 110 V electrical outlet using the optional 110 V to 230 V supply lead adaptor Refer to section 3 for further details The appliance tester will automatically start when connected to the mains supply IMPORTANT DO NOT connect any equipment to the PAT tester until it has been switched on and passed self test Connected equipment will cre
50. gai fri Save test results to memory and return to the initial screen Go to Section 4 to learn about using the memory or Section 4 2 saving a result to memory 25 To return to the HOME screen without saving the results press HOME button 3 8 Test fail screen Should an asset fail a test at any stage the test sequence is stopped and the screen message ASSET FAILED is displayed Test Results 2 Repeat test sequence Load s 3000 VA Print bar code label amp SAVE results to memory Asset FAILED Example Asset has failed the insulation test Pass limit set to 1 0 MQ Measurement recorded at less than 0 01 MO The same options are available as an asset that has passed See Section 3 7 for completion of testing 3 9 Visual failure If the current test group contains a visual test sequence then the visual test popup will appear This allows the user to log mechanical faults on the asset under test such as a broken plug or damaged appliance cord the Esc key should be used to exit the test sequence during the Visual Inspection and initiate a Visual Failure as below 1 During the visual inspection option the Visual Test will be highlighted in yellow as below Test Results Load BESTE E ity Press TEST to Pass or Esc to Fail Test Group C1 230Y Appliance 26 2 Press the Esc key to initiate a visual failure The display will show a Visual Test Failure screen as below Tent Mannila
51. h This could be via the outer case of the equipment touching other earthed equipment or from touching the ground Parallel earth paths affect measurement accuracy and in worst case situations can lead to equipment being passed as safe when there is no proper earth connection through the electrical outlet o A hardware fault in the PAT400 o A combination of the above Any reports of parallel paths should be investigated Check to ensure the BOND continuity lead is not connected to the null post on the PAT400 If not the asset must be checked for additional earth paths These could be as high as 1 2 kQ 12 The PAT400 can be checked by disconnecting the equipment under test and re starting the PAT400 If the PAT400 does not report a fault the problem exists on the equipment under test Testing an asset with multiple earth paths does not confirm the asset is safely earthed Additionally parallel earth paths can affect the accuracy of the measured earth resistance insulation test or leakage measurements therefore creating an unreliable PASS 73 Standard Class 1 Earthed Equipment Standard Class 1 Earthed Equipment with RCD Protection Standard Class 1 Earthed Equipment 200 mA Continuity Test Standard Class 1 Earthed Equipment with RCD Protection 200 mA Continuity Test Typical Class 2 Double Insulated 110 V Tools Earthed Equipment 110 V Tools Class 1 Flash Earthed Equipment 110 V Tools Double Insulated
52. he PAT400 displays all tests to be performed within the selected test group Each test is run sequentially and the results displayed for each test before proceeding to the next test A FAIL on any test will prevent further testing for safety purposes Test screen example Class l asset Test results screen List of tests in test group Test results column Result Limits Green Test passed Amber Test in progress Grey Test pending B Pass limit set for this test Test Group C1 Current test values or Instructions during the test Timer 5s Bond 0 04 2 Actual measurement result Test limits column 3000 YA sequence Interruption to automatic testing Testing proceeds automatically unless an action is required from the operator Follow on screen instructions as they appear 3 4 3 4 1 Remote probe and clip Some tests will require the use of the remote probe and clip These are used where the asset under test has no earth return Class ll assets Test using the remote probe include Insulation testing on Class ll equipment Continuity bond testing on Class equipment Touch leakage testing Differential leakage test on Class II Substitute leakage on Class ll The PAT400 will instruct the operator when the remote probe needs to be connected Example of remote probe application Class Il insulation test Riso Live and neutral are shorted together automatically in the PAT
53. he PAT400 nas oie sah iia Abd 15 Os gt POSTING WENA OO tice tic Sata e tare cand accdane cumeem ance ance eanauoneanoe A A Ea 16 3 1 Connecting an asset to the PAT400 oocccocccoccccnccccccccocncnccncncnononnnncnnnnnnonononnnonnnnnnnnnnnnnnnnnnnnnnnnnnonnnos 16 3 2 TESUNO AMAS O esa ene sr er ON eC ae ee 17 3 3 MCS UDI a 2 eoea tie sasacecous E neeaeias EE ET 22 3 4 Remote DFODE AlN Cll desconectes tdi I 23 3 5 Short CIRCUIT ASS OS css tra adosada 25 3 6 ooo UC AAA O ceases EE eoana cae E ON EATE 25 3 7 Completion Of testing sitas oi REI lio 25 3 8 A o A EE A A ONEN 26 3 9 A ec ec eee ERA ee 26 3 10 ROMAIN COG Casio uU ae ccncare a a sat ae natouse semana a a AE Rereuatoten 28 3 11 Cable compensatio resna a A Aa 29 312 WARNINGS cds Se ee eee ee eee ee eee eer 30 Ay Usmo Ne MEMO a e dd de a 31 5 Adding assets tO memory coocooccocccncccoconnconocononnnconono ono nn eee nn n nn nn rra rnnnnnnnnrnnnnnrnnnrnrrrrenanenass 34 5 1 Adding assets to memory before testing coooccoocccocccoccconcncnoncnnnnnnnnnnnnonononncnnnnnnnnnnnnnnonninons 34 5 2 Copying the previously added asSset ooocccoocccocccocncocnncnocnnonnnoncnononnnnnnonnnnnrnnnnnnnnnnnnnnnnnnnnnnnnnnnnos 35 6 Editing and deleting assets and results occooccconcoccccncccncocnnoncnnnonnnnnnnnnnnncnnnnnnnnonnnonnnnnnnnarennnnnnnnnnos 37 6 1 Eding asset data Sar ees ag cee ae SE es a eee eee 37 6 2 1 E E E cc ee eee 38 7 DATA
54. he name of the test group The cursor will jump to the relevant test groups with that letter or number Entering more than one letter will refine the search further Then press OK Add any additional data in the available fields as required Press TEST to commence testing Go to section 3 3 Test Progress NOTE Only a TEST GROUP is required to start testing 20 Option 3 1 On completion of a test only Asset IDs and Test groups have to be added before the test is completed All other data is optional a MO If NO Asset ID is entered press the TEST GROUP Hotkey and type in the test group Q a MO Alternatively press the Hotkey twice to select the test group drop down box Press OK to list all test group options scroll down the list to select desired test group and press OK to accept Pressing the RIGHT arrow key will Page Down the list Press TEST to start the test sequence Go to section 3 3 TEST PROGRESS FURTHER DETAILS ON ADDING ASSETS CAN BE FOUND IN SECTION 5 STARTING A TEST USING A BARCODE SCANNER From the home page scan the Asset barcode with the optional barcode scanner If the ASSET ID does NOT exist in the PAT database the PAT will jump to the ADD ASSET screen and the ASSET ID will appear If the asset information matches the asset to be tested the completed TEST ASSET screen will appear as below Test Asset gt Find Asset Asset ID 22355 O O OOO O aor EN q Search for TEST GROUPS
55. heir own supply 70 A 4 A 5 A 6 Warning A touch current test will operate the asset during the test Make sure the asset is safe before the test commences Load testing Also called Operation Also called VA Measuring the load VA of an appliance is a good indication of its operating condition By setting a load VA limit in the test groups an appliance can be assessed automatically for excessive load The Load VA limit is usually set based on the fuse rating in the appliance or in the mains connector Example 230 Vac with 3 A fuse maximum VA Rating should be 230 x 3 690 VA Select 750 VA pass limit However some equipment can draw very high inrush currents when starting This should be considered when setting pass limits Warning A Load test will operate the asset Make sure the asset is safe before the test commences RCD testing The PAT400 is capable of testing portable plug in 30 mA RCDs used to protect the user from electrical faults on individual items of electrical equipment Test options include a 30mA test or FULL test 30mA test Tests the manual test button on the RCD and the trip function at 30mA fault current FULL test Tests the following Manual test button Ensures correct operation 1 2x test Ensures the RCD does not trip too easily 1xl test 30 mA trip to ensure trip function works correctly ie lt 300 ms 5 X Ensures trip function works quickly on large fault currents ie lt 40
56. inuity of the protective earth conductor Class devices 2 Insulation test or earth leakage In addition further tests can be performed but ONLY AFTER 1 amp 2 above 3 Operation test 4 Leakage test si Only perform an operational test after the earth bond and insulation tests have been completed as this test operates at mains voltage E During testing ensure no hazard will exist as a result of normal running or under fault conditions E During testing the unit under test asset should not be touched other than using the appropriate accessories as faulty appliances can present a shock hazard E Do not touch the exposed parts of test leads during tests as hazardous voltages may be present due to potentially faulty appliance a Do not touch the IEC extension lead socket pins especially during a test as hazardous voltages may be present due to a potentially faulty appliance a Assets should not be routinely flash tested Where flash testing is required refer to further guidance on Flash testing section A7 X 3 A A CE N13117 D Eix Replacement fuses must be of the correct rating and type Refer to section 1 8 The USB connection marked thus lt should only be used by approved service personnel nothing should be connected to the USB port during testing Only use a NiMH rechargeable 8 4 V PP3 battery do not use a non rechargeable type as this could become dangerous if charged by the instrument Serviceable fuses sh
57. lient Location Press SAVE to store asset data SAVE results to TEST to store and test or Esc to abort memory 5 Press the SAVE Hotkey The asset data will be saved to memory The screen should display the SAVED message and return to the HOME screen 34 5 2 Copying the previously added asset 1 From the HOME screen press the ADD ASSET Hotkey The following empty asset screen will appear Add Asset Asset D II Y Test Group select test group y Description ms MN SerialNumber OOS Fuse Ratinga L o L sd Room ID Retest Frequency M Client Location Enter asset ID and select test group Press Esc to abort To recall the last asset to the screen press the COPY ASSET 2 Hotkey This will recall the last asset added to the database of the current Client The Asset ID can then be edited as required Change the Asset ID the SAVE Hotkey is becomes available after the ASSET ID has been changed Add Asset Asset ID 00023 Test Group Description Fan heater Y serial Number Fuse Rating 4 Room ID Retest Frequency M Client Location efault Enter asset ID and select test group Press Esc to abort OR To recall the last asset to the screen and INCREASE the Asset ID by one press the COPY ASSET AND INCREMENT ASSET ID Hotkey 35 Add Asset Asset ID M o o e Test Group Sct hd Description Serial Number Fuse Rating 4 Room ID Retest Frequency M Client
58. lit Press twice for drop down Fuse Rating az AN box Room D CRUE Retest Frequency Mi Client ERA Add ASSET Location A Enter asset ID or test group and press TEST to start a test or press Esc to abort Edit ASSET 2 Type in the Asset ID and press OK 18 If the asset is already in the database the details of the asset will be displayed as below TestAsset 3 Asset D m Test Group 2 Description VA Serial Number Fuse Rating A ES Room ID ETT Retest Frequency M Client Megger Group T Location Archcliffe Road Enter asset ID or test group and press TEST to start a test or press Esc to abort 3 2 Press the TEST button and the test sequence will commence Go to 3 3 TESTING PROGRESS 2 Alternatively to search through the asset database press the FIND ASSET Hotkey A drop down box of Asset IDs will appear If you know the Asset ID you wish to find start typing in the Asset ID The search engine will jump to the Asset IDs that start with those characters Otherwise use the UP or DOWN arrow key to locate and OK key to select the Asset ID from the list To ADD an asset simply press the ADD ASSET Hotkey If the entered asset is not in the database the following information box will appear TestAsset O Asset ID Cid Testor MN Desrrintinn Seri i no YA Fus Asset does not exist Roo Do you wish to add this asset ret Press OK to proce
59. lug 3 Connect the 110 V adaptor IEC connector to the IEC socket on the PAT400 16 3 1 3 Connecting an extension lead To connect an extension lead to the PAT400 1 Connect the mains plug to the mains test socket on the PAT400 2 Using the extension lead adaptor connect the furthest socket on the extension lead to the IEC socket on the PAT400 To connect a 110 V power lead use the 110 V to IEC plug adaptor optional accessory 1 Connect the 110 V mains plug to the 110 V test socket 2 Connect the free end of the 110 V power lead to the 110 V adaptor plug Connect the 110 V adaptor IEC connector to the IEC socket on the PAT400 3 1 4 To connect a portable RCD to the PAT400 1 Connect the RCD to the 230 V test socket on the PAT400 2 Using the IEC test lead adaptor connect the IEC plug of the adaptor lead into the IEC socket on the PAT400 3 Connect the MAINS plug of the IEC test lead adaptor into the RCD 3 2 Testing an asset The PAT400 s are designed to automatically test electrical equipment using TEST GROUPS A TEST GROUP is a specific group of tests suitable for the type of asset being tested The PAT tester is shipped with a pre defined set of test groups However others can be added as required up to a maximum of 100 see section 8 Before a test will run a TEST GROUP must be selected There are three options to start the test sequence e OPTION 1 Select a test group from the
60. minal mains supply E VA Accuracy 5 10 digits 0 to 99 VA El a E 78 15 50 digits 100 VA 999 VA E E 5 100 digits 1000 VA 3700 VA E Resolution 1 VA 0 to 3700 VA E ES El Display range O to 3990 VA E Extension lead test E Tests performed Bond insulation amp polarity E E E Polarity test voltage 12 V dc E Lead Ok i Polarity checks Eve neue Live neutral reversed Live neutral O C ES E Flash test a Nominal 1500 V ac for Class 1 a Flash test voltage Nominal 3000 V ac for Class 2 a Flash tact cument lt 3 5 mA short circuit 253 V primary supply E voltage Flash test breakdown current 5 5 digits ACCU AC Ye Flash a current 0 01 mA resolution Display range 0 1 to 3 00 mA E Portable RCD test E Test voltage and frequency Nominal mains supply a El Test current accuracy li at a 5 a 2 to 8 1 xl 5 xl a a a Trip time accuracy 1 5 digits E Trip time resolution 0 1 ms E E 0 to 1999 ms 1 2 xl El E Display range O to 300 ms 1 xl E O to 40 ms 5 xl E Fuse test a E Test voltage 3 3 V dc a a Warning Audible beep if fuse is OK E E E Environmental Operating temperature 10 C to 50 C a E Storage temperature 20 C to 60 C E E E O O O Ml Ml El Humidity 90 RH 10 C to 30 C 75 RH 30 C to 50 C a E Maximum altitude 2000 m E E a Dust and water ingress protection IP40 E E E Design standards S
61. n be caused by a faulty USB stick Replace the USB stick with another type and try again NOTE A USB stick may take a few seconds to be recognised by the PAT400 Importing restoring data from USB memory stick Importing data from PowerSuite to the PAT400 or restoring data from a saved file are the same The file must be in a db format and located in the root directory of the memory stick This would either have been created by the PAT400 as a backup file or created from PowerSuite for import into the PAT400 1 Connect a USB stick containing the db file to either of the Type A USB sockets on the front of the PAT400 E Type A USB socket 40 2 Select the Restore From USB option in the DATA menu as below Home Setup Data fo Backup To USB Restore From USB Export Results To USB View Results Warning Instrument will be restored to backup file data All current results test groups and settings will be over written Press OK to begin Esc to abort Warning Importing or restoring a file will overwrite the existing assets results test groups clients and locations in the database 3 Press OK to continue 4 The PAT400 will search for any database files in the root directory A drop down box appears Press the OK key and then the DOWN arrow to scroll through the list or use the RIGHT arrow key to page through the list OR Type the desired file name to jump to the matching item in the lis
62. navigate around the menu and asset screens Use the OK button or CR enter key on the keyboard to select or confirm an action Use the HOME Gay button to return to the main menu Use the ESC button to exit or abort a function Text fields free form box and Drop down boxes When entering basic ASSET data two types of text fields exist 1 Free form boxes Add Asset Asset ID A Test Group Select test group y By 4 Description ae o E Serial Number E Fuse Rating 4 SS Free form box Room ID O l Text or numbers can be entered as Retest Frequency M required Client Location Enter asset ID and select test group Press Esc to abort Text can be entered from a keyboard or barcode scanner 10 1 8 SAN In some instances a free form box can become a drop down box such as the asset ID field In this case it will appear with the drop down icon as below 2 Drop down boxes Drop down boxes already contain a list of items To access the list navigate to the drop down box using the UP DOWN arrows then press the OK button Add Asset Asset ID Test Group Description Drop down box Serial Number O O Press OK to select from the available Fuse Rating ay OOOO ist Room ID O O Alternatively enter the first letter or Retest Frequency M number of the contents you require i and the search engine will jump to Client default o that entry ae ie Eg Enter
63. ng the RIGHT arrow key 2 Select Company from the menu options and press OK 3 Enter the Company details all of these fields are optional Company fo Name Address 1 Address 2 Town City County State CTITIEN Postcode Zip CT17 SEN Contact No 01304 502100 Label Text Tested By Megger ma 4 Press the SAVE Hotkey to store the changes Quick test configuration QUICK TESTS are available to aid in commissioning and repair of electrical equipment The QUICK TEST keys allow direct access to individual tests without the need to use test groups The test times of the QUICK TESTS can be adjusted independently of test groups 61 Test times can be adjusted for the following tests Insulation test Bond test Load Operational test Leakage test To adjust the QUICK TEST time settings 1 Select QUICK TEST KEYS from the SETUP menu options Home Setup Data Client Location Company Quick Test Keys Setup Date Time Language Default Settings About y y y SR EGE 2 Press OK to display the Quick Test Config screen Quick Test Config Ins Test Time Bond Test Time 5s v Load Test Time 5s X Leakage Test Time 5s v 3 Navigate to the desired field to adjust the test time 4 Press ESC to save and exit 62 10 5 Date Time settings To change the Time or Date settings 1 From the HOME screen enter the SETUP menu option by pressing the RIGHT arrow key 2 Use the DOWN
64. ns can be added edited or deleted The DEFAULT CLIENT and LOCATION can only be deleted after other additional CLIENTS AND LOCATIONS are added 10 1 1 Adding Clients 1 Select CLIENT from the SETUP menu and press OK Home setup Data O 30 YA Location Company Quick Test Keys Setup Date Time Language Default Settings About 2 The Client screen will be displayed with the Add Edit and Delete Client Hotkeys as below Client for Press add hotkey to add a client Press edit hotkey to edit a client Press delete hotkey to delete a client 3 Select the ADD Hotkey to add a new Client to the database 4 Complete the text fields with the necessary Client information Client Name is mandatory once it has been saved the name can not be changed Additional data is optional 55 5 On completion press the SAVE Hotkey 6 The display automatically jumps to the ADD LOCATION screen 7 Add the location details Only Location name is mandatory 8 On completion press the SAVE Hotkey A new CLIENT and LOCATION has been added to the database The current CLIENT and LOCATION has been updated to the new CLIENT and LOCATION automatically 10 1 2 Editing and Deleting Clients This function should be used to change the details of a Client If you wish to change to a different client go to Section 10 1 3 below It is not possible to edit a Client name once it has been created Edit Client 1 Selec
65. on firmware releases prior to 2 20 clients Each client can have up to 2 000 50 on firmware releases prior to 2 20 Locations There is a maximum of 25 000 total locations per database The client and locations are configured in SETUP refer to Section 10 The PAT400s are shipped with the client and first location set to default All results will be stored under this default client and location unless changed in SETUP These can be left as default but it is recommended these are changed to the name of the client and location of the test site See Section 10 Assets are stored with a minimum of an Asset ID and a Test Group A client CANNOT have duplicate Asset IDs even if they are in several locations However the same Asset ID can be used for different clients Test results are stored and referenced to an Asset ID The internal memory will store up to 10 000 test results Entering an asset ID that already exists in the current client will generate a duplicate asset ID warning Change the asset ID then press save Assets can be saved to memory before or after testing The add asset screen is shown below Default Add Asset screen Add Asset screen with asset data to be saved Add Asset Add Asset set N Asset ID LoS E Asset ID 000234 Test Group Select test group vi E Test Group Sci vi Description Description COPY last Serial Number O Serial Number ASSET and Fuse Rating A O Fuse
66. ould only be replaced with those that are suitably rated In case of an emergency use an easily accessible power point Only use Megger approved accessories with this product Symbols used on the instrument Caution risk of electric shock Caution refer to accompanying notes Equipment complies with relevant EU Directives Equipment complies with C tick requirements Fuse This equipment should be recycled as electronic waste HV test lead in unlocked position HV test lead in locked position NIMH BAV Battery type fitted 230V Do NOT connect to mains supply 1 1 Instrument Layout Overview of the PAT400 The PAT400 series of portable appliance testers are fully automated testers for the fast safety testing of portable electrical equipment The PAT400s will operate from 230 Vac or for UK variants 230 Vac and 110 Vac supplies The PAT400 s are ready to start testing however the warnings must be read and understood before the testers are used All operators should also be competent in the safety testing of electrical equipment and meet all the local legal requirements before testing 1 2 Instrument layout IEC Extension lead l 110 V test socket UK Only return test socket Mains test socket Flash test socket Fuse checker Bond continuity socket Lead null post USB interfaces Power OFF Home button Escape button Qwerty keypad w 1 3 Button functions Button functions Esp Powe
67. paration between the live conductors live and neutral and any accessible conductive parts The instrument will short together the live and neutral conductors and then apply a 500 V or 250 V insulation test between the temporarily connected live neutral and the earth Typically a test voltage of 500 V is used However on sensitive equipment or especially where there are surge protection devices fitted a 250 V option is available For Equipment with no return earth Class II the use of an external probe is required to provide the return In situ testing In situ insulation testing is not possible on the PAT400 However the Touch Leakage test can be used in the same situation as the In situ Bond test in Section A1 iii above as an alternative to the insulation test Leakage testing i Differential earth leakage test IDIFF Also called protective conductor current Test voltage 230 Vac 50 Hz 319 99 mA 110 Vac 50 Hz 319 99 mA UK models only The differential earth leakage test determines whether any current is flowing to earth Normally appliances should have no or very little earth leakage current Class 2 double insulated appliances could exhibit earth leakage through its mountings or by operator contact During the test the actual mains voltage is also measured at the appliance socket In order to ensure that the equipment is safe even when the mains supply rises to its maximum permitted value 253 V or 121 V the PAT calc
68. r down Prevents battery discharge Cap Returns to HOME screen Esc Escape Exit screen without saving 1 4 HOTKEY descriptions Home screen SETUP screen zee Pp Class 1 test groups Class Il test groups Change client P Y Ulale Power extension leads pa A O Portable RCDs Bond lead null a Sib Add asset Edit asset OQ D z ther Hotkeys Find asset Copy last asset op m 4 o WM o lt a 0 Save print label OU D o e 0 Next page Previous page aja mi Repair code pop up box activation Test group manager Change location Copy last asset 8 increment asset ID Hot keys Function depends on adjacent display icon Used for fast selection of options I 44 View test result lt p Pp List test groups Re run test SSvd m ma 2 Print barcode 1 5 1 6 1 7 Display information Menu bar Provides navigation path and menu options Home setup Data Supply Voltage 230 9 VAC Main display area Supply Frequency 60 0 Hz Supply Polarity Normal Hotkeys Display and test Serial Number 1000 743 080908 100 Quick access to result information frequently used test Self Tests Passed o gt groups and other Additional menu Client default options options Location default Time 09 50 Date 05 07 2011 Memory Used 0 slim Client Test Results 0 Fj Screen navigation Use the UP DOWN and LEFT RIGHT arrows to
69. r options are displayed as below Home Setup Data Backup To USB Restore From USB Export Results To USB View Results USB operations require a FAT orFAT32 formatted USB memory stick ee 3 Use the DOWN arrow to select backup to USB and press OK 4 Enter the name of the file you wish to create The file name can be up to eight characters A to Z and 0 to 9 Do not use any other characters 39 7 2 Home Setup Data Backup To USB File name Restore From USB 14092011 Export Results To USB View Results Please enter backup file name maximum 8 alphanumeric characters Press OK to continue Esc to abort 5 Press OK to initiate backup If the file name clears without backup starting the file name contains excluded characters Only 0 to 9 and A to Z should be used 6 On completion the display will show the message Backup complete There are no limits to the number of times you can backup a database The stored file is a db file Do not attempt to edit this file as this can corrupt the data and prevent further use of that file If the USB device is not recognised the following message will be displayed Home Setup Data Backup To USB File name Restore From USB 14092011 Export Results To USB ee No USB mass storage device detected Please connect USB storage device Press OK to continue Esc to abort Press OK to continue Esc to abort This error ca
70. s shown below Selected Tests g Visual a AT ZA A bso fa o Hs HA Load gt Repeated tests are setup by choosing an option in the Cycles column Bond and Continuity test have the ability to be repeated a set number of times 1 to 10 or repeated indefinably by choosing the CO symbol For example you may wish to test a multi way extension lead which has 4 sockets In this case you would set the Bond Cycles option to 4 this will automatically perform 4 Bond test and record the worst Bond resistance An example screen is shown below TestResults Result Limits Test next socket Press TEST to proceed or Esc to abort Test Group EXAMPLE Timer 0s Bond 0 05 2 lf a Bond or Continuity test fails then the user is always allowed to repeat the test If the test is repeated then the failed results is disregarded You may wish to repeat a test in this way if the test probe did not make proper contact with the appliance Insulation and Flash test can also be repeated by selecting the OO symbol in the Cycles column This feature is convenient for testing appliances that have multiple exposed conductive areas 92 Quick test QT The Quick Test QT key provides instant access to continuity bond insulation leakage RCD load Operational and flash testing without having to create a test group NOTE Some tests shown below may not be available depending on the instrument being used 1 Press the QT k
71. s to the same firmware version Databases restored from different PAT models may have tests that are incompatible with the model being imported into For example a PAT450 can have Bond testing setup where PAT410 models do not have this test In this case the test will be skipped during testing Export results to CSV WARNING CSV file format should NOT be used for backup of data as it cannot be restored to the PAT400 Assets and test results can be exported to a CSV file format This file can be opened with a CSV viewer To export data and test results to CSV 1 Connect a USB stick to either of the type A USB sockets on the front of the PAT400 42 7 4 2 Select Export Results to USB and press OK The following screen will appear Home setup Data 0 Backup To USB File name Restore From USB Export0 Export Results To USB View Results Please enter export CS file name maximum 8 alphanumeric characters Press OK to continue Esc to abort 3 Enter a name for the CSV file Up to 8 characters can be used Use letters and or numbers Press OK when ready 4 The CSV file will be saved to the USB memory stick On completion the following message will be displayed and the buzzer will sound Message USB Operation complete Press OK to continue NOTE Exporting large amounts of data to CSV can take a significant time to complete Once started a CSV export cannot be aborted Accessing test results T
72. splayed 2 3 Scroll down the Asset ID field as in 6 1 above When the required asset is displayed press the DELETE Hotkey 4 A screen message to confirm the deletion is displayed 5 Press OK to confirm or Esc to abort WARNING The asset and its associated test records will be deleted This deletion is not reversible For Deletion of Clients and Locations see Section 10 38 7 1 DATA Test results and data transfer Data storage backup and restore The PAT400 can store up to 10 000 electrical assets with associated test records Megger STRONGLY RECOMMEND this data is backed up frequently MEGGER CANNOT ACCEPT RESPONSIBILITY OR ANY LOST DATA HOWEVER CAUSED The backup and recall operations are extremely fast 10 000 records can be backed up to a USB stick in lt 20 seconds Smaller databases are significantly faster The file format for data backup is a db file DO NOT ATTEMPT TO EDIT THIS FILE Corruption of this file shall prevent further transfer back to the PAT400 or to PowerSuite Export to CSV file Test results can also be exported to a CSV comma separated value file This can be viewed with Microsoft Excel See Section 7 1 7 2 or 7 3 for full details of Backup and Export options Backup to USB memory stick 1 Connect a USB stick to either of the type A USB sockets on the front of the PAT400 E Type A USB socket 2 Use the RIGHT arrow to select DATA in the main menu options The data transfe
73. t The search engine will find the closest match as you type Home Setup Data fo Backup To USB O3sept11 v Restore From USB O3sept11 10sept11 17sept11 24sept11 31sept11 Press OK to continue Esc to abort Export Results To USB View Results Please select restore fi 5 Press OK to accept the file for import or restore The PAT400 will display a message 41 7 3 Home setup Data fo Backup To USB 17sept11 v Restore From USB Export Results To USB ni This operation over writes all current data Are you sure you want to proceed Press OK to confirm Esc to cancel 6 Press OK to accept the file for import restore 7 The file will be imported On completion a message will be displayed and the buzzer will sound Home Setup Data fo Backup To USB 17sept11 v Restore From USB Export Results To USB View Maarten Message USB operation complete Press OK to continue DO NOT SWITCH OFF THE PAT400 DURING THE USB OPERATION WARNING Importing or restoring a file will overwrite the existing assets results test groups clients and locations in the database Always ensure existing data has been backed up prior to importing new data NOTE Databases restored from previous firmware versions will be automatically upgraded Once upgraded the database will no longer be compatible with older firmware versions To maintain compatibility between multiple PAT400s upgrade all PAT
74. t CLIENT from the SETUP menu and press OK In the Client screen select the EDIT Hotkey 2 Select the desired Client then change the details as required Edit Client oO Client Name Megger Group Address 1 Address 2 TowniCity County State E CC Postcode Zip 3 After the details have been changed press the SAVE Hotkey Delete Client Warning Deleting a Client will also delete all assets locations and test results associated with that Client 1 Select CLIENT from the SETUP menu and press OK In the Client screen select the DELETE Hotkey 2 Select the desired Client 56 Delete Client fo Client Name Megger Group Bi address 1 address 2 Town CountyiState MOS Postcode Zip CT1 SEN 3 Press the DELETE Hotkey 4 A popup message will ask you to confirm 10 1 3 Changing Clients To change between different Clients in the PAT400 A 1 From the SETUP tab press the SELECT CLIENT Hotkey Select client fo Please select the current client Megger Group 2 Press the OK key to open the drop down list 3 Select the desired Client and press OK 4 Press the SAVE Hotkey to store the change 5 The display will now change to the SELECT LOCATION screen 6 Select the appropriate Location from the drop down list 7 Press OK to accept the new location 57 8 Press the SAVE Hotkey to store the change 10 2 Locations Multiple locations can be added to one CLIENT up to
75. to the matching item in the list The search engine will find the closest match as you type 37 6 2 Note The first 2 000 Asset IDs are loaded into the drop down list To access the next 2 000 assets press and hold the RIGHT arrow to scroll down to the bottom of the first 2 000 assets Select Next from the bottom of the list The Asset ID list will now load the next 2 000 assets OR Where available type next to jump to the end of the list or previous to jump to the start of the list Edit Asset O Asset ID 1000632745 w Test Group NEW 12656709954 Description NEVV1 12716019492 Serial Number NEVV1 127160227 NEV 12831563244 Fuse Rating 4 NEY 12986097994 T Room ID NEAM 13033342290 Retest Frequency M NEY113115069761 NE NEV 1321332613 o NEV 1326018462 Location NEV 13379267337 Edit asset informi delete hotkey to add or remove an asset Edit the asset details as required and press the SAVE key to store changes NOTES To move the location of an asset simply change the location in the Location list It is not recommended to change the Client Changing the Client will also change the appropriate asset list However on exiting this screen the Client will revert to the original Client prior to any changes made here Deleting assets 1 From the HOME screen use the RIGHT arrow key to select the SETUP tab A Press the EDIT ASSET Hotkey The EDIT ASSET screen should be di
76. ulates and displays the leakage current that would flow at this value Warning A differential earth leakage test will operate the asset during the test Make sure the asset is well secured before the test commences ii Substitute leakage test IPE Also called alternative earth leakage Also called equivalent earth leakage Test voltage 40 Vac 50 Hz gt 19 99 mA For this test the appliance has its phase conductors joined together within the PAT and a 40 V supply is applied between both phase conductors and the protective conductor connection of the equipment under test in the case of Class 1 equipment In the case of Class 2 appliances the test lead and probe is connected to the PAT This probe is applied to any conductive parts on the appliance under test The actual voltage is measured at the appliance socket From these readings the earth leakage current of the appliance is calculated and scaled depending upon appliance supply voltage 253 V or 121 V iii TOUCH current Test IF Also called absence of potential Test voltage 230 Vac 50 Hz gt 10 mA 110 Vac 50 Hz gt 10 mA During this test the appliance under test is powered from its normal mains supply and the test lead and probe is connected to the PAT terminal This probe is applied to any conductive parts on the appliance under test This probe performs a current measurement with respect to earth This test can also be performed on three phase appliances powered from t

Download Pdf Manuals

image

Related Search

Related Contents

StarTech.com 3 port USB 3.0 hub for laptops & Windows-based tablets + fast-charge port & device stand  3 2 フロントグリル 取付/取扱説明書 1  ASUS Z87 User's Manual  Buffalo 1.0TB DriveStation  User Manuals  

Copyright © All rights reserved.
Failed to retrieve file