Home

Evolis circuit breakers 17.5 kV

image

Contents

1. 1 1 1 IR 1 1 1 1 1 1 1 1 e je or1 or2 or3 or4 oF11 12 oF13 OF14 OF21 OF22 OF23 NOF24 ae Del 7 1 41 MX1 mx2 or H MN Mitop SE E LI LJ e e Remote control AMTED307010EN indd Auxiliary contacts Schneider 61 Electric Evolis 17 5 Description of functions withdrawable version Opening circuit inMC cassette Composition The opening circuit is produced using the following components m a shunt opening release MX1 m a second shunt opening release MX2 m undervoltage release MN m time delayed undervoltage release MNR MN time delay The time delay placed outside the circuit breaker can be disabled by an emergency stop button to give instant circuit breaker opening m low energy release Mitop Note see the table of the releases combinations on the following page 0 58081 Shunt opening release MX1 MX2 Energizing this release causes instant opening of the circuit breaker Circuit breaker equipped with a shunt opening release MX Permanent power supply to the MX unit locks the circuit breaker in the open position 23 Power supply See Order form page 8 Threshold 0 7 to 1 1 Ur Consumption VA or W Triggering 200
2. Padlocking Lead sealing DE57537 Locking of the circuit breaker in the open position The circuit breaker is locked in the open position by blocking the opening push button in the engaged position m by a padlock 1 to 3 padlocks not supplied m by a keylocks 1 or 2 different keylocks not supplied The keylocks are of captive key type with the key free after locking either Profalux or Ronis right turn and are proposed according to the options either with m 1 single keylock m 1 single keylock mounted on the circuit breaker 1 identical delivered separately for interlocking with another device m 2 different keylocks for double locking Profalux and Ronis keylocks are inter compatible DE57560 Cubicle door interlocking mechanism This device enables the circuit breaker to only be operated when the door is closed for the withdrawable version with a cradle Cubicle door interlocking mechanism 44 Schneider AMTED307010EN indd Electric Evolis 17 5 kV withdrawable version in NEX cradle Description of functions Safety functions This table describes the safety functions available on the withdrawable version of the Evolis 17 5 kV circuit breaker How to use the table Each of the boxes describes the functional status of each circuit breaker position and the associated parts Possible status Possible status impossible op
3. g 24 30 Vdc 24 V 50 60 Hz 59284 E 48 60 Vdc 48 V 50 60 Hz 59285 100 130 Vdc 50 60 Hz 59286 200 250 Vdc 50 60 Hz 59287 Undervoltage release MN z 24 30 Vdc 24 V 50 60 Hz 59288 i 48 60 Vdc 48 V 50 60 Hz 59289 100 130 Vdc 50 60 Hz 59290 200 250 Vdc 50 60 Hz 59291 Time delay for MN 8 48 60 Vdc 50 60 Hz 33680 E 100 130 Vdc 50 60 Hz 33681 200 250 Vdc 50 60 Hz 33682 i 59160 g 24 30 Vdc 47888 E 48 60 Vdc 47889 100 125 Vdc 47890 200 250 Vdc 47891 48 60 V 50 60 Hz 47889 100 130 V 50 60 Hz 47893 200 240 V 50 60 Hz 47894 5 Module of 4 contacts 47887 E LV terminal blocks i 1 terminal block 47074 n Ready to close contact PF 47080 DE58088 70 Schneider AMTED307010EN indd Electric DE57588 DE57582 Evolis 17 5 kV withdrawable version in MC cassette Offer structure Separated components cont MC cassette Indication of the CB racked in racked out position Rack in rack out operation MC1 51237324FR MC2 51237324FQ MC3 Ir up to 1250 A 51237324FW MC3 Ir gt 1250 A 51237324FS Module of 6 contacts AAA12951FA Module of 12 contacts AAA12951FB Operating shaft 03405140FO AMTED307010EN indd Schneider Electric 71 Evolis 17 5 kV Services withdrawable version in MC cassette The following components can only be adapted or replaced on site by staff trained by Schneider Electric m Re
4. Standard delivery 4 Maximum quantity 12 Breaking capacity A Standard Min load 100 mA 24 V Cos g 0 3 VAC 240 380 10 6 CA12 DC12 480 10 6 690 6 VDC 24 48 10 6 125 10 6 250 3 Low level Min load 2 mA 15 V DC VAC 24 48 6 240 6 380 3 VDC 24 48 6 125 6 250 3 Standard contacts 10 A optional contacts 6 A temperature derating Ready to close PF contact The circuit breaker is ready to close when shown by a mechanical indicator and a PF changeover contact This information simultaneously indicates that m the circuit breaker is open m the storage energy springs are armed m there is no permanent closing order m there is no permanent opening order caused by a safety opening order 2nd MX or MN keylocking of the device in the open position Standard delivery 0 Maximum quantity 1 Breaking capacity A Standard Min load 100 mA 24 V Cos q 0 3 VAC 240 380 5 CA12 DC12 480 5 690 3 VDC 24 48 3 125 0 3 250 0 15 Low level Min load 2 mA 15 V DC VAC 24 48 3 240 3 380 3 VDC 24 48 3 125 0 3 250 0 15 Operation counter CDM The operation counter is visible on the front panel Ittotalizes the number of switching cycles CO that the device has carried out Schneider 23 Electric Evolis 17 5 kV Description of functions fixed version Locking interlocking DE59417 Locking the circuit breaker in the open position Opening button C
5. E 8 3004 5 8 a a a el C mr ______ p i Service position Test position Disconnected position Note the arrows show the locked positions for the circuit breaker and the LV plug Functions m Adrive system combined with a threaded shaft gives easier racking in and out The racking in mechanism can be operated with the door closed m An interlock stops the user from inserting the lever as long as the racking truck has not been put in the racked in out position m An interlock between the circuit breaker status and the truck gives secure operation racking in or out is only possible if the circuit breaker is open m An interlock also exists between the LV connector and the truck It is only possible to rack in if the LV connector is connected The cradle floor has all the fixing holes needed to correctly position the earthing Shutters switch control mechanism and power circuit This makes earthing switch operation reliable and gives interlocking between the circuit breaker and the earthing switch m Earthing is automatic when the truck is fully racked in W Protective shutters stop fingers from touching the racking clusters when the device is extracted protection index IP2X m For maintenance operations it is possible to padlock the shutters in the closed position unlock the shutter mechanism to access the racking clusters m Afoolproof device enables correct matching of the cra
6. Power supply See Order form page Threshold Opening 0 35 to 0 7 Ur Closing 0 85 Ur Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Time delay 0 5s 0 9s 1 5s 3s Low energy release Mitop This release includes a low consumption unit and is specifically used with the Sepam 100LA self powered unit REFLEX MODULE or the VIP relay Power supply Direct current Threshold 0 6A 1 3A Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact provided with the Mitop This release also includes a coil reset enabling remote SDE contact reset Comment Use of the Mitop low energy release requires adjustment of the protection relay time delay in order to ensure that the circuit breaker trips between 45 50 ms Releases combinations table Shunt opening MX1 111111111111 Shunt opening MX2 1 1 Undervoltage MN 1 1 Mitop 1 1 1 Schneider 63 Electric 0 58085 0 58086 0 58082 Evolis 17 5 withdrawable version in MC cassette Electrical motor MCH Shunt closing release XF 64 Schneider Electric Description of functions Remote control Function Remote control enables the remote opening and closing of the circuit breaker The opening order always takes priority over the closing order In the event of simultaneous opening and closing orders the mechanism discharges under no load
7. amp Phase to phase mm E 145 185 240 le 1 o Dimensions mm 556 686 886 2 as ais ak a 1 H 980 980 980 a 2 D 1223 1223 1223 j F Weight kg 222 255 326 LL H H 370 805 1 F 3 lo o 6 q 300 he p 321 611 100 I D Electric 68 Schneider AMTED307010EN indd Evolis 17 5 kV withdrawable version in MC cassette Only one of the boxes ticked X orfilled by the needed value have to be considered between each horizontal line Green box x corresponds to none priced functions Releases combinations table MX1 1 1 1 1 1 1 MX2 1 1 MN 1 Mitop 11111 AMTED307010EN indd Order form Rated voltage Ur o Short circuit current Isc kA Rated current Ir A Phase to phase distance mm 145 185 _ 240 Colour for push buttons and indicators Push buttons open closed Red black Indicator open closed Black white Green red Operating mechanism charged discharged Yellow white Opening release see possible choices in combination table Shunt opening release MX1 24 Vac 24 30 Vcc 48 Vac 48 60 Vcc Shunt opening release MX2 24 Vac 24 30 Vcc 100 130 Vcc 200 250 Vcc 48 Vac 48 60 Vcc 100 120 Vac 200 240 Vac 100 130 Vcc 100 120 Vac 200 250 Vcc 200 240 Vac Undervoltage release MN 24 Vac 24 30 Vcc 48 Vac 48 60 Vcc Time delay for MN 48 60 Vac 100 130 Vcc ca
8. AMTED307010EN indd Contents Presentation Main characteristics Description of functions Racking in MV and LV connection P2 stored energy operating mechanism Wiring diagram Opening circuit Remote control Indication Interlocking Safety functions Dimensions Order form Offer structure Separated components Services Schneider Electric 53 54 Schneider AMTED307010EN indd Electric PE58089 Evolis 17 5kV withdrawable version inMC cassette Evolis circuit breaker 17 5 kV withdrawable version in MC cassette AMTED307010EN indd Presentation Description of the device The basic withdrawable version of the Evolis circuit breaker comprises m the circuit breaker unit with its operating mechanism three poles equipped with a vacuum interrupter a P2type spring operated stored energy control mechanism electrifiable This gives the device an opening and closing speed that is independent ofthe operator for both electrical and manual orders It enables reclosing cycles to be carried out a front panel housing the manual operating mechanism and status indicators m the components enabling it to be withdrawable the circuit breaker is equipped with racking arms and contact fingers and mounted n a racking in out drive device with a threaded shaft activated by a handle including all of the safety interlock systems a Harting type male LV connector allo
9. armed position of the mechanism springs armed Electrical motor is always inclusive of gear reducer DE58086 Power supply See Order form page Threshold 0 85 to 1 1 Ur Electrical motor MCH Consumption VA or W 180 Motor overcurrent 2to3Infor0 1s Arming time 6s maximum Operating rate 3 cycles maximum per minute CH contact 10 240 V 0 58082 Shunt closing release This release allows remote closing of the circuit breaker when the control mechanism is armed It can be permanently or briefly supplied power Power supply See Order form page Shunt closing release XF Threshold XF 0 85 to 1 1 Ur Consumption VA or W Triggering 200 for 200 ms Latched 4 5 22 Schneider AMTED307010EN indd Electric DE58087 DE58088 DE58089 Evolis 17 5kV fixed version Rotary type contacts OC Ready to close PF contact Operation counter CDM AMTED307010EN indd Description of functions Indication Open closed auxiliary position contacts OC These auxiliary contacts indicate the open or closed position of the circuit breaker m Rotary type changeover contacts directly controlled by the circuit breaker mechanism m Indicator contacts are proposed for standard relaying applications for low level control applications with plc s or electronic circuits This version is compatible with Sepam series 20 40 80 units
10. 100 130 Vcc 100 130 Vac 200 250 Vcc 200 240 Vac 200 250 Vcc 200 240 Vac OO EDI CT am Low energy release Mitop Remote control Electrical motor MCH 24 30 Vdc 100 125 Vdc 200 250 Vdc 48 60 Vdc ac 100 130 Vac 200 240 Vac Shunt closing release XF 24 Vac 24 30 Vcc 100 130 Vcc 200 250 Vcc 48 Vac 48 60 Vcc 100 130 Vac 200 240 Vac Module of 4 additional auxiliary contacts O C 1 2 Ready to close contact LV plug 42 pin LV plug instead of 18 Operating shaft Quantity one mini per switchboard MC cassette type MC1 MC2 MC3 Short circuit current Isc lt 31 5 Rated current Ir 1250 AL 2500A MC cassette accessories Racked in out position contact 6NO 6 NC Pictogram of the circuit breaker of the earthing sw Discharge of the circuit breaker control mechanism springs Extraction table Quantity Extra handle Quantity Door with handle windows and pictogram mc2 _ vca Door accessories local manufacture handle windows and pictogram with cover plate for mc2 _ Schneider 69 Electric Evolis 17 5 kV Offer structure withdrawable version Separated components in MC cassette The following components can be ordered separately and can be adapted or replaced by the customer MX1 MX2 XF shunt opening closing release
11. 2 changeover contacts see indication page Open closed position auxiliary contacts chapter An 42 pin version enabling connection of a shunt opening release MX1 a second opening release shunt type MX2 or undervoltage type MN a low energy release Mitop a fault trip indicator contact SDE a remote contact reset system SDE a remote control mechanism electrical motor shunt closing release XF a ready to close contact PF m amaximum number of auxiliary contacts 4 NC 5 NO 2 changeover contacts see indication page Open closed position auxiliary contacts chapter Note see the table of the releases combinations Order form page Interlocking function In conformity with IEC standard 6227 1 200 an interlocking function prohibits m racking in when the LV plug is not connected m disconnection of the LV plug if the circuit breaker is in the racked in position LV wiring kit A wiring kit with 42 wires 2 meters long equipped with pins that can be adapted to the LV plug can be supplied for connected in to the cubicle s LV compartment Flexible ducting This 525 mm long duct with a hinged LV plug enables protection of the LV wiring that connects the circuit breaker to the cubicle s LV compartment AMTED307010EN indd PE56600 DES9408EN Evolis 17 5kV withdrawable version in NEX cradle Circuit breaker open Operating mechanism loaded 1 1 1 1 Charged eady to close Description of
12. Undervoltage MN Mitop Schneider 21 Electric Evolis 17 5 kV Description of functions fixed version Remote control Function Remote control enables the remote opening and closing of the circuit breaker 0 58085 The opening order always takes priority over the closing order In the event of simultaneous opening and closing orders the mechanism discharges under no load without moving the main contacts The circuit breaker remains in the open position In the event of latched opening and closing orders the mechanism carries out anti pumping function as standard by blocking the circuit breaker in the open position Anti pumping function after opening on a fault or deliberate opening via the manual or electrical mechanism the closing order must be interrupted then reactivated to enable reclosing of the circuit breaker Composition The remote control comprises m an electrical motor equipped with a spring armed CH limit switch m a shunt closing release Electrical motor MCH The electrical motor carries out the automatic rearming of the storage energy springs as soon as the circuit breaker closes This allows instant reclosing ofthe device after opening The arming lever is only used as a backup control in the case of the absence of the auxiliary power supply An electrical motor MCH equipped with a spring armed CH limit switch This contact indicates the
13. VA or W Triggering 200 for 200 ms Latched 45 AMTED307010EN indd DE58087 DE58088 DE58089 Evolis 17 5kV withdrawable version in NEX cradle Rotary type contacts OC Ready to close PF contact Operation counter CDM AMTED307010EN indd Description of functions Indication Open closed auxiliary position contacts OC These auxiliary contacts indicate the open or closed position of the circuit breaker m Rotary type changeover contacts directly controlled by the circuit breaker mechanism m Indicator contacts are proposed for standard relaying applications for low level control applications with plc s or electronic circuits This version is compatible with Sepam series 20 40 80 units Standard delivery 4 Maximum quantity 12 Breaking capacity A Standard Min load 100 mA 24 V Cos g 0 3 VAC 240 380 10 6 CA12 DC12 480 10 6 690 6 VDC 24 48 10 6 125 10 6 250 3 Low level Min load 2 mA 15 V DC VAC 24 48 6 240 6 380 3 VDC 24 48 6 125 6 250 3 Standard contacts 10 A optional contacts 6 A temperature derating Ready to close PF contact The circuit breaker is ready to close when shown by a mechanical indicator and a PF changeover contact This information simultaneously indicates that m the circuit breaker is open m the storage energy springs are armed m there is no permanent closing order m there is no p
14. 1 1 e 7 E or1 or2 or3 NoF4 OF11 12 VorF13 OF14 OF21 OF22 OF23 NOF24 1 7 1 41 MX1 mx2 or H MN Mitop SE E LI LJ e e Remote control AMTED307010EN indd Auxiliary contacts Schneider 39 Electric Evolis 17 5 Description of functions withdrawable version Opening circuit in NEX cradle Composition The opening circuit is produced using the following components m a shunt opening release MX1 m a second shunt opening release MX2 m undervoltage release MN m time delayed undervoltage release MNR MN time delay The time delay placed outside the circuit breaker can be disabled by an emergency stop button to give instant circuit breaker opening m low energy release Mitop Note see the table of the releases combinations on the following page 0 58081 Shunt opening release MX1 MX2 Energizing this release causes instant opening of the circuit breaker Circuit breaker equipped with a shunt opening release MX Permanent power supply to the MX unit locks the circuit breaker in the open position 23 Power supply See Order form page 8 Threshold 0 7 to 1 1 Ur Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Shunt opening release MX1 and MX2 40 Schneider AMTED307010EN indd Electric DE5
15. 185 240 Colour for push buttons and indicators Push buttons open closed Red black Indicator open closed Black white Operating mechanism charged discharged Yellow white Opening release see possible choices in combination table Shunt opening release MX1 24 Vac 24 30 Vcc 48 Vac 48 60 Vcc Shunt opening release MX2 24 Vac 24 30 Vcc 100 130 Vcc 200 250 Vcc 48 Vac 48 60 Vcc 100 120 Vac 200 240 Vac 100 130 Vcc 100 120 Vac 200 250 Vcc 200 240 Vac Undervoltage release MN 24 Vac 24 30 Vcc 100 130 Vcc 200 250 Vcc 48 Vac 48 60 Vcc 100 130 Vac 200 240 Vac Time delay for MN 48 60 vac 100 130 Vccica 200 250 Vcc 200 240 Vac Low energy release Mitop Remote control Electrical motor MCH 24 30 Vdc 100 125 Vdc 200 250 Vdc 48 60 Vdc ac 100 130 Vac 200 240 Vac Shunt closing release XF 24 Vac 24 30 Vcc 100 130 Vcc 200 250 Vcc 48 Vac 48 60 Vcc 100 130 Vac 200 240 Vac Module of 4 additional auxiliary contacts O C iL 2 H Ready to close contact PF LV plug Without interlocking 18 pins 42 pins LV terminal blocks With interlocking 18 pins H 42 pins H Locking of the circuit breaker in the open position By padlock or by locks and keys Profalux Ronis If locks 1 lock O 2 identical locks 2 different locks Push buttons padlock of O C circuit breaker Fixed connections Upstream and downstream
16. 250 50 60 Hz 59287 24 30 Vdc 24 V 50 60 Hz DE58082 48 60 Vdc 48 V 50 60 Hz 59289 100 130 Vdc 50 60 Hz 59290 200 250 Vdc 50 60 Hz 59291 48 60 Vdc 50 60 Hz 100 130 Vdc 50 60 Hz 200 250 50 60 Hz DE58083 33681 33682 DE58084 24 30 Vdc DE58086 48 60 Vdc 47889 100 125 47890 200 250 47891 48 60 V 50 60 Hz 47889 100 130 V 50 60 Hz 47893 200 240 V 50 60 Hz Module of 4 contacts DE58087 8 47080 48535 AMTED307010EN indd Schneider 49 G Electric DE59419 DE57581 DE57551 DE57562 DE57561 Evolis 17 5 kV Offer structure withdrawable version Separated components in NEX cradle 8 Phase phase distance 145 mm 59316 Phase to phase distance 185 mm 59317 Phase to phase distance 240 mm 59318 1 full bushing 630 1250 A 59382 1 full bushing 630 2500 A 59383 you need at least 6 bushings per cradle ES SS 6 deflectors used to increase dielectric e e withstand from 75 to 95 kV 59283 C B ready to be operated PAF 1AC indicates that the C B is locked in place in the cradle 59174 2rails 59299 50 Schneider AMTED307010EN indd Electric EvolisTZ5kV Offer structure withdrawable version Separated components cont in N
17. 31 5 2500A Important Detailed installation instructions are given in the Evolis Installation Guide Please consult us AMTED307010EN indd DE57574 DE57575 DE57576 145414544 185 4 185 gt 185 185 DE57577 DE57577 DE57578 1140 Schneider Electric 47 Evolis 17 5 kV withdrawable version in NEX cradle Only one ofthe boxes ticked X orfilled Joy the needed value have to be considered between each horizontal line Green box x corresponds to none priced functions Releases combinations table MX1 12 4 4 4 MX2 1 1 MN 1 Mitop 111 48 Schneider Electric Order form Rated voltage Ur Short circuit current Isc Rated current Ir Phase to phase distance mm 145 185 240 Colour for push buttons and indicators Push buttons open closed Red black Indicator open closed Black white Operating mechanism charged discharged Yellow white Opening release see possible choices in combination table Shunt opening release MX1 24 Vac 24 30 Vcc 48 Vac 48 60 Vcc Shunt opening release MX2 24 Vac 24 30 Vcc 100 130 Vcc 200 250 Vcc 48 Vac 48 60 Vcc 100 120 Vac 200 240 Vac 100 130 Vcc 100 120 Vac 200 250 Vcc 200 240 Vac Undervoltage release MN 24 Vac 24 30 Vcc 48 Vac 48 60 Vcc Time delay for MN 48 60 Vac 100
18. E a L a E a a a m a E a E a a L a 25 31 5 40 2 25 31 5 40 2 25 31 5 25 31 5 400 25 31 5 400 25 31 5 400 25 31 5 40 25 31 5 40 25 31 5 25 31 5 40 25 31 5 40 25 31 5 40 63 79 100 63 79 100 63 79 63 79 100 63 79 100 63 79 100 65 82 104 65 82 104 65 82 65 82 104 65 82 104 65 82 104 1 Circuit breaker tested at Ud 42 kV 50 Hz 1 min 2 Class 1 2000 operations for Isc 40 m Available Not available AMTED307010EN indd Schneider 57 GElec tric Evolis 17 5 Description of functions withdrawable version Racking in inMC cassette Assembly components The racking in out function is achieved by m the withdrawable circuit breaker with its LV connector mobile part m the cassette with its bushings fixed part DE57579 Circuit breaker operation The withdrawable circuit breaker can be placed in 3 stable positions m service position circuit breaker racked in and locked in position LV plugs connected m test position circuit breaker racked out and locked in position LV plug connected m disconnected position circuit breaker extracted and locked in this position LV plug disconnected DE57584 Circuit breaker safety functions A drive system using a threaded shaft gives easier racking and unracking z Test position contact Operating position This is activated
19. an emergency stop button to give instant circuit breaker opening m low energy release Mitop Note see the table of the releases combinations on the following page 0 58081 Shunt opening release MX1 MX2 Energizing this release causes instant opening of the circuit breaker Circuit breaker equipped with a shunt opening release MX Permanent power supply to the MX unit locks the circuit breaker in the open position 2 Power supply See Order form page 8 Threshold 0 7 to 1 1 Ur Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Shunt opening release MX1 and MX2 20 Schneider AMTED307010EN indd Electric DE58082 DE58083 DE58084 Evolis 17 5 kV fixed version Undervoltage release MN Low energy release Mitop AMTED307010EN indd Description of functions Opening circuit cont Undervoltage release MN This release unit causes the systematic opening of the circuit breaker when its supply voltage drops below a value less than 35 of the rated voltage even if this drop is slow and gradual It can open the circuit breaker between 35 and 70 of its rated voltage If the release unit is not supplied power manual or electrical closing of the circuit breaker is impossible Closing of the circuit breaker is possible when the supply voltage of the release unit reaches 85 of its rated voltage Power supply See Order form page Threshold
20. carried out by the panel builder Schneider 59 Electric Evolis 17 5 Description of functions withdrawable version MV andLV connection in MC cassette MV connection The customer connection is easily made at the rear of the cassette on the connection terminals integrated in the bushings see drilling details in the Installation Guide ref 07897536EN g 5 a o UA o E ow IST O o e O e fe o o oo O o _ E B D D a O O i i MV connection LV connection With the withdrawable circuit breaker the LV cabling has an LV connector with m mobile part male Harting connector at the end of a flexible cable fully connected to the operating mechanism terminal by a sleeve m a fixed part female Harting connector compatible with the male part mounted atthe top inside the cassette Interlocking function In conformity with IEC standard 6227 1 200 an interlocking function prohibits m racking in when the LV plug is not connected m disconnection of the LV plug if the circuit breaker is in the racked in position DE57594 LV plug connection 60 Scbneider AMTED307010EN indd Electric PE56600 DES9408EN Evolis 17 5kV withdrawable
21. circuit breaker in the open position 24 Schneider AMTED307010EN indd Electric Evolis 17 5 kV fixed version Dimensions Phase to phase distance 145 mm Ur Isc Ir Weight 7 2kV 25 51kg 1250A 1250 12 KV 25 1250A 1250 Phase to phase distance 185 mm Ur Isc Ir Weight 7 2kV 25 55 kg 1250A ssa 1250A 40 kA 630A 1250A 12kV 25 kA 1250A sr 1250 A 40 KA 630 A 1250 A 17 5KV 25 kA 630 A 1250 A 1250 Phase to phase distance 240 mm Ur Isc 7 2kV 25 kA 31 5kA 40 kA 12 kV 25 kA 31 5 40 kA 17 5 kV 25 kA 31 5 40 kA Important Detailed installation instructions are given in the Evolis Installation Guide Please consult us AMTED307010EN indd DE57540 DE57542 240 240 90 DE57552 DE57552 DE57552 Schneider 25 Electric Evolis 17 5 kV fixed version Only one ofthe boxes ticked X orfilled Joy the needed value have to be considered between each horizontal line Green box x corresponds to none priced functions Releases combinations table MX1 1 111 MX2 1 1 MN 1 1 1 1 Mitop 1 1 1 1 1 26 Scbneider Electric Order form Rated voltage Ur o Short circuit current Isc kA Rated normal current Ir A Phase to phase distance 145
22. for 200 ms Latched 4 5 Shunt opening release MX1 and MX2 62 Schneider AMTED307010EN indd Electric DE58082 DE58083 DE58084 Evolis 17 5 kV withdrawable version in MC cassette Undervoltage release MN Low energy release Mitop AMTED307010EN indd Description of functions Opening circuit cont Undervoltage release MN This release unit causes the systematic opening of the circuit breaker when its supply voltage drops below a value less than 35 of the rated voltage even if this drop is slow and gradual It can open the circuit breaker between 35 and 70 of its rated voltage If the release unit is not supplied power manual or electrical closing of the circuit breaker is impossible Closing of the circuit breaker is possible when the supply voltage of the release unit reaches 85 of its rated voltage Power supply See Order form page Threshold Opening 0 35 to 0 7 Ur Closing 0 85 Ur Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Time delay for MN To eliminate spurious tripping of the circuit breaker when there are brief voltage drops the MN action is controlled with a time delay This function is achieved by adding a time delay unit outside of the undervoltage release MN circuit adjustable time delay This unit is placed outside the circuit breaker and can be inhibited by an emergency stop button to obtain instant circuit breaker opening
23. functions P2 stored energy operating mechanism Wiring diagram Operation of the P2 stored energy operating mechanism This gives the device an opening and closing speed that is independent of the operator whether the order is electrical or manual The electrical control mechanism carries out reclosing cycles and is automatically recharged by a geared motor each time after closing It consists of m the stored energy operating mechanism which stores in springs the energy required to open and close the device m agear motor electrical charging device with manual charging by lever useful on loss of auxiliary supply m manual order devices by push buttons on the front panel of the device m an electrical remote closing device containing a release with an antipumping relay m an electrical opening device containing one or more releases for example shunt opening undervoltage Mitop a low consumption release used only with the Sepam 100 LA protection relay m an operation counter m position indication device by mechanical indicator and 3 modules of 4 auxiliary contacts whose availability varies according to the diagram used m a device for indicating charged operating mechanism status by mechanical indicator and electrical contact Wiring diagram principle 1 1 1 1 1 IR 1 1 1 1 1 1
24. in NEX cradle 185 240 7 2 12 17 5 7 2 12 17 5 20 28 38 20 28 38 60 75 95 60 75 95 25 31 5 40 2 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 40 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 63 79 100 63 79 63 79 63 79 63 79 63 79 65 82 104 65 82 65 82 65 82 65 82 65 82 1 Circuit breaker tested at Ud 42 kV 50 Hz 1min 2 Class M1 2000 operations for Ir 2500 A m Available Not available AMTED307010EN indd Schneider 35 Electric Evolis 17 5 Description of functions withdrawable version Racking in in cradle Composition The racking in function is carried out by m the racking truck supporting the circuit breaker mobile part m the cradle with bushings fixed part m LV plug DE57557 Operation The circuit breaker can be placed in 3 stable positions W service position circuit breaker racked in and locked in position LV plugs connected m test position circuit breaker racked out and locked in position LV plug connected m disconnected position circuit breaker racked out and locked in position LV plug disconnected The circuit breaker can be unlocked and extracted from the cradle
25. without moving the main contacts The circuit breaker remains in the open position In the event of latched opening and closing orders the mechanism carries out anti pumping function as standard by blocking the circuit breaker in the open position Anti pumping function after opening on a fault or deliberate opening via the manual or electrical mechanism the closing order must be interrupted then reactivated to enable reclosing of the circuit breaker Composition The remote control comprises m an electrical motor equipped with a spring armed CH limit switch m a shunt closing release Electrical motor MCH The electrical motor carries out the automatic rearming of the storage energy springs as soon as the circuit breaker closes This allows instant reclosing ofthe device after opening The arming lever is only used as a backup control in the case of the absence of the auxiliary power supply An electrical motor MCH equipped with a spring armed CH limit switch This contact indicates the armed position of the mechanism springs armed Power supply See Order form page Threshold 0 85 to 1 1 Ur Consumption VA or W 180 Motor overcurrent 2to3Infor0 1s Arming time 6s maximum Operating rate 3 cycles maximum per minute CH contact 10 240 V Shunt closing release This release allows remote closing of the circuit breaker when the control mechanism is arm
26. 010EN indd Scbneider 29 Electric 30 Schneider AMTED307010EN indd Electric Evolis 17 5 kV withdrawable version in NEX cradle AMTED307010EN indd contents Presentation Main characteristics Description of functions Racking in MV connection LV connection P2 stored energy operating mechanism Wiring diagram Opening circuit Remote control Indication Locking interlocking Safety functions Service trucks Dimensions Order form Offer structure Separated components Services Schneider Electric 31 32 Schneider AMTED307010EN indd Electric PE57994 Evolis 17 5 kV withdrawable version in NEX cradle Evolis circuit breakers 17 5 kV withdrawable version in NEX cradle AMTED307010EN indd Presentation Description of the device The basic withdrawable version of the Evolis circuit breaker comprises m the circuit breaker unit with its operating mechanism three poles equipped with a vacuum interrupter a P2 type spring operated stored energy control mechanism electrifiable This gives the device an opening and closing speed that is independent of the operator for both electrical and manual orders It enables reclosing cycles to be carried out a front panel housing the manual operating mechanism and status indicators m the components enabling it to be withdrawable the circuit breaker is equipped with racking arms and contact fingers and mounted on a racking in out dri
27. 130 Vcc ca 100 130 Vcc 100 130 Vac 200 250 Vcc 200 240 Vac 200 250 Vcc 200 240 Vac OO LE I EE Low energy release Mitop Remote control Electrical motor MCH 24 30 Vdc 100 125 Vdc 200 250 Vdc 48 60 Vdc ac 100 130 Vac 200 240 Vac Shunt closing release XF 24 Vac 24 30 Vcc 100 130 Vcc 200 250 Vcc 48 Vac 48 60 Vcc 100 130 Vac 200 240 Vac Module of 4 additional auxiliary contacts O C 1 2 Ready to close contact PF LV plug with interlocking _ 42 pin LV plug instead of 18 Operating shaft Quantity one mini per switchboard Locking of the circuit breaker in the open position By padlock or by locks and keys Profalux Ronis If locks 1 lock L 2 identical locks 2 different locks Push buttons padlock of O C circuit breaker Phase to phase distance mm 145 185 240 Bushings 6 per cradle 630 1250A 630 2500A Cradle accessories Block of four position indication contacts CB racked in racked out One CB ready to operate indication contact Field deflectors for bushings AMTED307010EN indd Evolis 17 5 kV Offer structure withdrawable version Separated components in cradle The following components can be ordered separately and can be adapted or replaced by the customer 8 24 30 24 V 50 60 Hz 59284 48 60 48 V 50 60 Hz 59285 100 130 50 60 Hz 59286 200
28. 175 Insulation level power frequency withstand Ud kV 50 Hz 1 min 1 20 28 38 lightning impulse withstand Up kV peak 60 75 95 Rated current Ir A 630 1250 2500 2 x Short circuit current Isc kA 25 31 5 25 31 5 25 31 5 Short time withstand current Ik tk kA 3 s 25 1 5 25 31 5 25 31 5 Short circuit making current Ip kA peak 50 Hz 63 79 63 79 63 79 60 Hz 65 82 65 82 65 82 Rated switching sequence O 3 min CO 3 min CO 0 3 5 3 O 0 3 s CO 15 s CO Operating times Opening lt 50 ms Breaking lt 60 ms Closing lt 65 ms Service temperature C 25t0 40 Mechanical endurance Class M1 2 M2 Number of switching operations 2000 2 10000 Electrical endurance Class E2 Number of switching operations 25 100 at full Isc value 31 5kA 50 Capacitive current breaking capacity Class C1 Average relative humidity Over24h 9596 Over 1 month 9096 Switchingandprotectionofcapacitorbanks Evolis range circuit breakers are well suited for switching and protection of capacitor banks with installed power up to 2 Mvar installed in series with dampening reactor limiting inrush current to 2 kA Evolis is also well suited for capacitor banks system with installed power higher than 2 Mvar in conjunction with anti harmonic filtering system Please consult us 34 Schneider AMTED307010EN indd d Electric Evolis 17 5 kV Main characteristics cont withdrawable version
29. 8082 DE58083 DE58084 Evolis 17 5 kV withdrawable version in NEX cradle Undervoltage release MN Low energy release Mitop AMTED307010EN indd Description of functions Opening circuit cont Undervoltage release MN This release unit causes the systematic opening of the circuit breaker when its supply voltage drops below a value less than 35 of the rated voltage even if this drop is slow and gradual It can open the circuit breaker between 35 and 70 of its rated voltage If the release unit is not supplied power manual or electrical closing of the circuit breaker is impossible Closing of the circuit breaker is possible when the supply voltage of the release unit reaches 85 of its rated voltage Power supply See Order form page Threshold Opening 0 35 to 0 7 Ur Closing 0 85 Ur Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Time delay for MN To eliminate spurious tripping of the circuit breaker when there are brief voltage drops the MN action is controlled with a time delay This function is achieved by adding a time delay unit outside of the undervoltage release MN circuit adjustable time delay This unit is placed outside the circuit breaker and can be inhibited by an emergency stop button to obtain instant circuit breaker opening Power supply See Order form page Threshold Opening 0 35 to 0 7 Ur Closing 0 85 Ur Consumption VA or W Triggeri
30. EX cradle Standard 18 pins WITH interlocking 59114 Standard 42 pins WITH interlocking 59115 DE57523 Flexible conduct for LV wiring 59099 LV connecting kit 42 wires AAA10 087 PE56601 Earthing sliding contact on C B DE57563 Circuit breaker specific labels green red DE57553 5 Phase to phase distance Ur Ir Ith B 145 mm 7 2 17 5kV 1250A 25 59476 185 7 2 17 5 1250 31 5 59477 240 7 2 17 5 2500A 40 59478 Phase to phase distance Ur Ir Ith B 145 mm 7 2 17 5kV 1250A 31 5 59012 185 mm 7 2 17 5 1250A 31 5 59474 240 7 2 17 5 2500A 40 59475 R Operating shaft 59449 User manual 59069 CB extraction table 59130 DE57582 DE57556 51306830 AMTED307010EN indd Schneider 51 G Electric Evolis 17 5 kV Services withdrawable version in NEX cradle The following components can only be adapted or replaced on site by staff trained by Schneider Electric m Remote control mechanism comprising electrical motor shunt closing release operation counter m Operation counter m Low energy release Mitop m Interlocking between the open circuit breaker position and the LV plug m Racking truck m Circuit breaker front cover 52 Schneider AMTED307010EN indd Electric Evolis 17 5 kV withdrawable version in MC cassette
31. Medium Voltage Distribution Evolis circuit breakers 17 5 kV vacuum breaking fixed and withdrawable versions Catalogue 2014 Schneider Electric Evolis circuit breaker 17 5kV AMTED307010EN indd General contents General presentation Panorama Evolis 17 5 kV fixed version Evolis 17 5 kV withdrawable version in NEX cradle Evolis 17 5 kV withdrawable version in MCcassette Schn eide Electric General presentation Evolis Circuit breakers adapted to your needs Evolis a range of circuit breakers Description that takes account of your electrical Evolis a range of vacuum type circuit breakers from 7 2 kV to 24 kV A combining easy selection and comprehensive offer installations requirements today m a fixed frontal or lateral version and in the future m a withdrawable frontal version with a circuit breaker and its cradle or its cassette m a fixed lateral version equipped with an integrated protection chain m separately delivered accessories The Evolis circuit breaker is operated via a spring mechanism that gives an operating speed that is independent of the operator and that does not require an auxiliary power supply When the operating mechanism is motorized the circuit breaker can include telecontrol functions and carry out rapid reclosing cycles The various circuit breaker versions are easy to integrate in a cubicle environment An Installation Guide details the
32. Opening 0 35 to 0 7 Ur Closing 0 85 Ur Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Time delay for MN To eliminate spurious tripping of the circuit breaker when there are brief voltage drops the MN action is controlled with a time delay This function is achieved by adding a time delay unit outside of the undervoltage release MN circuit adjustable time delay This unit is placed outside the circuit breaker and can be inhibited by an emergency stop button to obtain instant circuit breaker opening Power supply See Order form page Threshold Opening 0 35 to 0 7 Ur Closing 0 85 Ur Consumption VA or W Triggering 200 for 200 ms Latched 4 5 Time delay 0 5s 0 9s 1 5s 3s Low energy release Mitop This release includes a low consumption unit and is specifically used with the Sepam 100LA self powered unit REFLEX MODULE or the VIP relay Power supply Direct current Threshold 0 6A 1 3A Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact provided with the Mitop This release also includes a coil reset enabling remote SDE contact reset Comment Use of the Mitop low energy release requires adjustment of the protection relay time delay in order to ensure that the circuit breaker trips between 45 50 ms Releases combinations table Shunt opening MX1 1 11111 1 1 1 1 1 1 1 1 1 1 1 1 1 Shunt opening MX2
33. Panorama Evolis circuit breakers cont Fixed version Withdrawable version Fixed version Fixed version Operating mechanism Operating mechanism Operating mechanism Integrated protection system on the front on the front on the side Operating mechanism on the side Rated voltage Ur kV 50 60 Hz Short circuit rated breaking capacity Isc from 16 to 31 5 kA from 16 to 31 5 kA from 12 5 to 25 kA from 12 5 to 20 kA Rated current Ir from 630 to 2500A from 630 to 2500A 630 and 1250A 630 and 1250A Separate catalogue AMTED307010EN indd Schneider 9 Electric Panorama Evolis circuit breakers cont Protection monitoring control VIP30 for phase protection VIP35 for phase and earthing protection VIP300P for phase protection VIP300LL for phase and earthing protection Sepam series 20 for normal applications Sepam series 40 for demanding applications Sepam series 80 for full applications Separate catalogue PM700 for basic metering PM800 for advanced metering CM3000 CM4000 for full metering and power quality AMTED307010EN indd Evolis 17 5 kV fixed version AMTED307010EN indd Contents Presentation Main characteristics Description of functions MV connection LV connection P2 stored energy operating mechanism Wiring diagram Opening circuit Remote control Indication Locking interlocking Dimensions Order form Offer struc
34. ar motor electrical charging device with manual charging by lever useful on loss of auxiliary supply m manual order devices by push buttons on the front panel of the device m an electrical remote closing device containing a release with an antipumping relay m an electrical opening device containing one or more releases for example shunt opening undervoltage Mitop a low consumption release used only with the Sepam 100 LA protection relay m an operation counter m position indication device by mechanical indicator and 3 modules of 4 auxiliary contacts whose availability varies according to the diagram used m device for indicating charged operating mechanism status by mechanical indicator and electrical contact Wiring diagram principle eady to close or1 or2 or3 NoF4 OF11 12 VorF13 OF14 OF21 OF22 OF23 OF24 Remote control AMTED307010EN indd Auxiliary contacts Schneider 19 Electric Evolis 17 5 kV Description of functions fixed version Opening circuit Composition The opening circuit is produced using the following components m a shunt opening release MX1 m a second shunt opening release MX2 m undervoltage release MN m time delayed undervoltage release MNR MN time delay The time delay placed outside the circuit breaker can be disabled by
35. breaker racking in out operations and for earthing switch opening and closing operations Extraction tool m Astandard tool allows the breaking device to be extracted from each cassette version whatever the installation height up to 800 mm from the ground m Asimplified extraction tool can be manufactured locally according to the installation height MC cassette options Circuit breaker racked in or racked out position indicator contacts 6 contacts 3 NO 3 NC or 12 contacts 6 NO 6 NC Operating mechanism spring discharge system Circuit breaker operating mechanism springs are automatically discharged when it is extracted from the cubicle This function avoids any risk of unwanted circuit breaker closing Mechanical circuit breaker racked in lock This option is included when the earthing switch is installed However it can be delivered separately if the earthing circuit breaker is not required it takes the space and volume of the earthing switch operating mechanism Equipped MV access door Possibility of delivering a fully equipped painted door RAL 9001 available with or without the manual circuit breaker closing mechanism Possibility of producing the door locally drawings and accessories available Foolproofing device This enables foolproofing of the circuit breaker rating relative to the cassette rating This system is mounted on the cassette side The corresponding combining of the right circuit breaker rating must be
36. contacts develop and engineer Evolis providing The dielectric strength of the vacuum allows the contact to contact distance customers with the very best of vacuum to be reduced This short distance together with the low opening speed allow technology the use of a low energy control mechanism A metal clusters provides the link between the mobile contact and the enclosure In order to keep the vacuum level required for the correct operation of the interrupter for 30 years the enclosure must be perfectly sealed and the various components have to be fully degased This is achieved by m choosing materials that are specifically selected for this application metals and ceramics m choosing an appropriate assembly process vacuum high temperature brazing m the use of a getter material to absorb the residual gas DE60163 Ceramic chamber Shield Fixed contact Mobile contact Current breaking in a vacuum interrupter In vacuum breaking the electrical arc generated on separation of the contacts is made up of a plasma of metal vapors produced by the vaporization of the contact material Metal bellows At low values of current these vapors very quickly condense on the shield and contacts when the arc disappears thus allowing m the vacuum to be re established m a contact to contact dielectric strength to be restored that is greater than m the recovery voltage breaking is then complete Fig 1 vacuum
37. ct control of the dielectric strength mechanic the short time withstand current and the temperature rise All of these characteristics have been validated in tests Connection Connection is easily done from outside the cradle W on vertical copper terminals integrated in the bushing m by a connector set also used on the base circuit breaker Note The dielectric strength values given in the performance table do not take these connectors into account The panel builder must check the whole cubicle connection configuration For circuit breakers with a rated voltage of Ur 17 5 kV with a phase to phase distance of 185 mm field deflectors are used to increase the dielectric strength by 75 kV to 95 kV Schneider 37 Electric Evolis 17 5 kV withdrawable version in NEX cradle 0 57523 0 57524 42 pin version LV plug Electric 38 Schneider Description of functions LV connection Main functions With the base circuit breaker the LV wiring uses a LV plug which comprises m the fixed part male mounted on the circuit breaker and fully connected to the control mechanism m the mobile part female compatible with the male part Two versions of the LV plug are available An 18 pin version enabling connection of m ashunt opening release MX1 m aremote control mechanism electrical motor shunt closing release XF m a ready to close contact PF m a maximum number of auxiliary contacts 1 NC 1 NO
38. dle and circuit breaker rating This system is mounted on the cradle base Part of the system must be assembled by the panel builder on the cubicle floor DE57559 DE57560 Accessories m One set of auxiliary contacts 4 circuit breaker racked in out position contacts 1 contact showing that the circuit breaker is locked in place on the cradle m Cradle earthing is provided by a sliding copper contact m Akey locking system Ronis or Profalux for the circuit breaker in the racked out position enables increased safety downstream of it during work This system is associated with an earthing switch m Locking of the circuit breaker compartment door This device enables the circuit breaker full version to only be operated DE57563 DE57561 oJ 0 57562 Circuit breaker Racked in out Earthing sliding when the door is closed position contact contacts device locked 36 Schneider AMTED307010EN indd Electric DE57564 DE57565 DE57566 Evolis 17 5 kV withdrawable version in NEX cradle Power circuit 3 connector sets gt Field deflectors AMTED307010EN indd Description of functions MV connection Composition The power circuit comprises m mobile contacts with disconnectable clusters and arms mounted on the circuit breaker m fingers attached to the cradle and insulated by bushings and metal shutters This assembly provides perfe
39. e vacuum interrupters are manufactured in an ultra modern production unit in France During manufacture each circuit breaker is subjected to systematic advanced testing Vacuum interrupter testing The level of vacuum in each interrupter is tested using the magnetron discharge method Using this sophisticated procedure measurement is very precise and does not require access to the inside of the interrupter thus not affecting the airtight seal Circuit breaker testing A rigorous set of tests and measurements is carried out on each circuit breaker The results are reported and signed off by the quality control department on each device s test certificate to ensure product traceability Compliance with standards m Evolis complies with IEC 62271 100 m Design and production are certified to ISO 9001 2000 m Production sites are certified to ISO 14001 environmental standard DE55746 ISO 9001 VERSION 2000 ISO 14001 Certification The certificate of conformity provides guarantees that the circuit breaker m has been subject to type tests according to EN 45001 standards procedures in accredited laboratories by independent organizations m is in conformity with recognized international standards Evolis is currently being certified by external EN 45011 accredited organizations members of the STL Short circuit Testing Liaison m EN 45001 general requirements for the competence of testing and calibration laborato
40. ed It can be permanently or briefly supplied power Power supply See Order form page Threshold XF 0 85 to 1 1 Ur Consumption VA or W Triggering 200 for 200 ms Latched 45 AMTED307010EN indd DE58087 DE58088 DE58089 Evolis 17 5kV withdrawable version inMC cassette Rotary type contacts OC Ready to close PF contact Operation counter CDM AMTED307010EN indd Description of functions Indication Open closed auxiliary position contacts OC These auxiliary contacts indicate the open or closed position of the circuit breaker m Rotary type changeover contacts directly controlled by the circuit breaker mechanism m Indicator contacts are proposed for standard relaying applications for low level control applications with plc s or electronic circuits This version is compatible with Sepam series 20 40 80 units Standard delivery 4 Maximum quantity 12 Breaking capacity A Standard Min load 100 mA 24 V Cos g 0 3 VAC 240 380 10 6 CA12 DC12 480 10 6 690 6 VDC 24 48 10 6 125 10 6 250 3 Low level Min load 2 mA 15 V DC VAC 24 48 6 240 6 380 3 VDC 24 48 6 125 6 250 3 Standard contacts 10 A optional contacts 6 A temperature derating Ready to close PF contact The circuit breaker is ready to close when shown by a mechanical indicator and a PF changeover contact This information simultaneo
41. er position and the associated parts Possible status Possible status impossible operation gt lt Impossible status Insertion Racking in Racking out Extraction Disconnected Test position 1 Cassette a Anti drop 2 No opening shutters Shutters padlocking possible 2 LV plug Disconnected No door closing a Connected No unplugging 3 Circuit breaker Closed No racking in No racking out Open No closing Open position circuit breaker locking available 4 Switchboard door Open No racking in qm Closed No door opening 3 5 Earthing switch Open No earthing switch closing Closed No racking in 5 1 This protection mechanism ensures that the performance levels of the circuit breaker correspond with those of the cassette 2 Device that prevents the circuit breaker from dropping when extracted from the cassette The device can be either unlocked manually or when the extraction rig is put in position 3 Interlocking device to be fitted to the cubicle door If there is no interlocking the circuit breaker device should be inhibited AMTED307010EN indd Schneider 67 Electric Evolis 17 5 kV Dimensions withdrawable version in MC cassette Basic withdrawable gt _E E Cassette Mc mc2
42. eration gt lt Impossible status M gt Cj gt 4 ZZ Extraction F Racking out Removed Disconnected Test position Service ee protection 1 Anti drop 2 No opening shutters Shutters padlocking possible 2 LV plug Disconnected No door closing Connected No unplugging 3 Circuit breaker Closed No racking in No racking out Open No closing Open position circuit breaker locking available 4 Switchboard door Open No racking in oo Closed No door opening 3 5 Earthing switch Open No earthing switch closing Closed No racking in Lr 1 This protection mechanism ensures that the performance levels of the circuit breaker correspond with those of the cradle 2 Device that prevents the circuit breaker from dropping when extracted from the cradle The device can be either unlocked manually or when the extraction rig is put in position 3 Interlocking device to be fitted to the cubicle door If there is no interlocking the circuit breaker device should be inhibited AMTED307010EN indd Schneider 45 Electric Evolis 17 5 kV Description of functions withdrawable version Service trucks in NEX cradle S Disconnecting truck 8 This device allows disconnection of the upstream and downstream circuits in the cubicle It is installed in the same location as the withd
43. ermanent opening order caused by a safety opening order 2nd MX or MN keylocking of the device in the open position Standard delivery 0 Maximum quantity 1 Breaking capacity A Standard Min load 100 mA 24 V Cos q 0 3 VAC 240 380 5 CA12 DC12 480 5 690 3 VDC 24 48 3 125 0 3 250 0 15 Low level Min load 2 mA 15 V DC VAC 24 48 3 240 3 380 3 VDC 24 48 3 125 0 3 250 0 15 Operation counter CDM The operation counter is visible on the front panel Ittotalizes the number of switching cycles CO that the device has carried out Schneider 43 Electric Evolis 17 5 Description of functions withdrawable version Locking interlocking in NEX cradle DE59417 Locking the circuit breaker in the open position Opening button Closing button Control mechanism status charged or discharged Push button padlock Circuit breaker position indicator Operation counter Push button padlock This transparent screen blocks access to the opening and closing push buttons on the circuit breaker The device enables the opening or closing push button to be locked independently DE57535 Locking is achieved either m by 2 screws m by 3 padlocks not supplied m by a lead seal N MN MN NY aA Wa p I Tr A PAPA n PA ro ZA X o v AUS 2 di 2 9 2 2 I A 2 lAl lA DE57536 DE57538 DE57539
44. errupters provides customer with a highly reliable eee and economic optimization considerations the axial magnetic range of circuit breakers m either by a coil outside of the interrupter fig 4 for rated voltages up to 17 5 kV These products are suitable for the most m or by a coil integrated in the interrupter contact structure fig 5 for the 24 kV demanding conditions with the guarantee of voltage level full compliance with international standards In both cases the AMF vacuum interrupters feature low arc voltages Uarc of around 50 V and maximum usage of the contact surface for very low contact erosion The advantages provided The above choices provide customers with the following advantages in MV circuit breaker applications m simple and compact vacuum interrupters m high electrical endurance meaning that there is no need for contact wear inspection in normal network protection applications including highly disturbed overhead line feeders I ES am Fig 5 24 kV internal coil type interrupter AMTED307010EN indd Scbneider 5 Electric PE55694 PE55695 General presentation Vacuum interrupter Industrial process expertise Electric 6 Schneider DE55745 Evolis The very best of vacuum technology Systematic advanced control The main components of the circuit breaker such as vacuum interrupter and operating mechanism are produced by Schneider Electric Th
45. ers the mechanism carries out anti pumping function as standard by blocking the circuit breaker in the open position Anti pumping function after opening on a fault or deliberate opening via the manual or electrical mechanism the closing order must be interrupted then reactivated to enable reclosing of the circuit breaker Composition The remote control comprises m an electrical motor equipped with a spring armed CH limit switch m a shunt closing release Electrical motor MCH The electrical motor carries out the automatic rearming of the storage energy springs as soon as the circuit breaker closes This allows instant reclosing ofthe device after opening The arming lever is only used as a backup control in the case of the absence of the auxiliary power supply An electrical motor MCH equipped with a spring armed CH limit switch This contact indicates the armed position of the mechanism springs armed Power supply See Order form page Threshold 0 85 to 1 1 Ur Consumption VA or W 180 Motor overcurrent 2to3Infor0 1s Arming time 6s maximum Operating rate 3 cycles maximum per minute CH contact 10 240 V Shunt closing release This release allows remote closing of the circuit breaker when the control mechanism is armed It can be permanently or briefly supplied power Power supply See Order form page Threshold XF 0 85 to 1 1 Ur Consumption
46. fety functions The MC cassette is designed to receive the Evolis circuit breaker and comprises the following components ensuring safety when racking in see details in the Installation Guide ref 07897536EN Metal structure with two guide rails The rails guide the Evolis circuit breaker during racking in out operations Fixed connection fingers insulated by bushings The three ends of the circuit breaker fitted with racking clusters provide the contact with these three fingers Metal shutters to insulate from the MV part Three shutters mounted on the structure stop access to the racking fingers when the circuit breaker is extracted protection index IP2X Safety interlocking systems When carrying out maintenance operations it is possible to m padlock the shutters in the closed position m unlock the access mechanism to the fixed contacts Anti drop function This function ensures operator safety during circuit breaker extraction Compulsory MC cassette accessories Female Harting low voltage connector Aconnector with a cable can either be delivered with the circuit breaker with the circuit breaker plus the cassette or separately Panel with circuit breaker operation pictograms Aself adhesive panel shows racking in and out operations for the circuit breaker This is systematically delivered when the circuit breaker is ordered either with the cassette or as a separate order Racking handle The handle is used for circuit
47. fixed connections Ir 3 fixed distance H or V 630 1250 A 18 3 variable distance 630 1250 A 630 2500 A 3 variable distance V 630 1250 A 630 2500 A AMTED307010EN indd DE58082 DE58082 DE58083 DE58084 0 58086 0 57544 DE58087 DE58088 DE58089 Evolis 17 5 kV fixed version The following components can be ordered separately and can be adapted or replaced by the customer AMTED307010EN indd Offer structure Separated components 24 30 Vdc 24 V 50 60 Hz 59284 48 60 Vdc 48 V 50 60 Hz 59285 100 130 Vdc 50 60 Hz 59286 200 250 Vdc 50 60 Hz 59287 24 30 Vdc 24 V 50 60 Hz 48 60 Vdc 48 V 50 60 Hz 59289 100 130 Vdc 50 60 Hz 59290 200 250 Vdc 50 60 Hz 59291 48 60 Vdc 50 60 Hz 100 130 Vdc 50 60 Hz 33681 200 250 Vdc 50 60 Hz 33682 24 30 Vdc 48 60 Vdc 47889 100 125 Vdc 47890 200 250 Vdc 47891 48 60 V 50 60 Hz 47889 100 130 V 50 60 Hz 47893 200 240 V 50 60 Hz Module of 4 contacts 48535 ur Schneider G Electric 27 DE57545 DE57548 DE57551 DE57523 PE56601 DE57533 51222737 DE57556 Evolis 17 5 kV Offer structure fixed version Separated components cont E 3 3 fixed d
48. ing impulse withstand Up kV peak 60 75 Rated current Ir A 630 1250 L 2500 Short circuit current Isc kA 25 31 5 25 31 5 Short time withstand current Ik tk kA 3 s 25 315 25 31 5 Short circuit making current Ip kA peak 50 Hz 63 79 63 79 60 Hz 65 82 65 82 Rated switching sequence O 3 min CO 3 min CO O 0 3 s CO 3 0 3 s CO 15 s CO Operating times Opening lt 50ms Breaking lt 60ms Closing 65ms Service temperature T C 25to 40 Mechanical endurance Class M1 2 M2 Number of switching operations 2000 10000 Electrical endurance Class E2 Number of switching operations 25 100 at full Isc value 31 5kA 50 40 kA 30 Capacitive current breaking capacity Class C1 Average relative humidity Over24h 9596 Over 1 month 9096 Switchingandprotectionofcapacitorbanks 0 0 Evolis range circuit breakers are well suited for switching and protection of capacitor banks with installed power up to 2 Mvar installed in series with dampening reactor limiting inrush current to 2 kA Evolis is also well suited for capacitor banks system with installed power higher than 2 Mvar in conjunction with anti harmonic filtering system Please consult us 56 Schneider AMTED307010EN indd d Electric Evolis 17 5 kV Main characteristics cont withdrawable version in MCcassette 185 240 MC2 MC3 7 2 12 17 5 7 2 12 17 5 20 28 38 20 28 38 60 75 95 60 75 95 a a
49. inger is a component designed specifically for the cluster regarding its shape tolerances and materials Contact between the finger and the cluster is guaranteed by type testing 1000 racking in out operations Arm and bushing m The arms cylindrical shape optimizes dielectric strength and avoids the need for any additional insulation m The bushing s cylindrical shape gives it outstanding dielectric strength m The previously described connectors can be mounted on bushing connection terminals Comment Performance levels of the whole assembled unit must be tested by the panel builder Installation conditions for the two units presented above are described in the Installation Guide For the 17 5 kV withdrawable circuit breaker phase to phase distance 185 mm field deflectors must be added to the bushings Field deflectors For circuit breakers with a rated voltage of Ur 17 5 kV with a phase to phase distance of 185 mm field deflectors are used to increase the dielectric strength by 75 kV to 95 kV y ad qued Le Arms clusters fingers and bushings busbars and field deflectors AMTED307010EN indd Schneider 17 Electric Evolis 17 5 Description of functions fixed version LV connection Two connection solutions m Directly on the LV terminal block The circuit breaker s LV wiring can be directly connected to the LV terminal block of the o
50. interrupter components At high currents the electrical arc in the vacuum switches to a concentrated mode which causes high localized temperature rises on the contacts The existence of these hot spots is detrimental to the quick restoring of the dielectric strength Current Two techniques can be used in order to avoid this stagnation of the static concentrated arc m the so called RMF Radial Magnetic Field technique involves rotating the arc DE60164 Electrode thanks to an electromagnetic effect generated by a radial magnetic field this therefore limits contact erosion AMF coil m a more recent technique called AMF Axial Magnetic Field involves applying It Contact disk an axial magnetic field parallel to the axis of the two contacts fig 2 which allows Arc plasma a diffuse arc to be maintained fig 3 even at high current values The arc energy is spread over the whole contact surface area therefore causing very low levels of erosion m Schneider Electric has chosen this last technique for the Evolis range Axial magnetic field Fig 2 cross section of AMF contact PE60042 Fig 3 diffuse vacuum arc AMF technology 4 Scbneider AMTED307010EN indd Electric 200110 DE60162 General presentation Evolis The very best of vacuum technology Schneider Electric s choices for Evolis AMF technology combined with its industrial expertise Evolis circuit breakers use AMF type vacuum int
51. istance H or V fig 1 630 1250 A 59400 ES gt gi i l 630 2500 A 59409 Fig 1 itl Fig 2 3 variable distance H fig 3 630 1250A 59401 630 2500 A 59410 3 variable distance V fig 2 630 1250 A 59402 630 2500 A 59411 For 40 kA you must take the 630 2500 A versions S 8 3 clusters 3 fingers 630 1250A 59369 wd a CO 630 2500A 59371 3 arms 630 1250A 59396 Finger 630 2500A 59397 For 40 kA you must take the 630 2500 A versions EN x E 6 deflectors used to increase dielectric e SS S withstand from 75 to 95 kV 59283 Standard 18 pins WITHOUT interlocking 59070 Standard 18 pins WITH interlocking 59114 All options 42 pins WITHOUT interlocking 59071 All options 42 pins WITH interlocking 59115 Flexible conduct for LV wiring 59099 LV connecting kit 42 wires AAA10 087 Circuit breaker specific labels green red 59100 Roller base The kit includes the roller base only Drawings are supplied to manufacture the frame locally 59050 28 Schneider Electric AMTED307010EN indd Evolis 17 5 kV Services fixed version The following components can only be adapted or replaced on site by staff trained by Schneider Electric m Remote control mechanism comprising electrical motor shunt closing release operation counter m Operation counter m Low energy release Mitop m Circuit breaker front cover AMTED307
52. losing button Control mechanism status charged or discharged Push button padlock Circuit breaker position indicator Operation counter Push button padlock This transparent screen blocks access to the opening and closing push buttons on the circuit breaker The device enables the opening or closing push button to be locked independently DE57535 Locking is achieved either m by 2 screws m by 3 padlocks not supplied m by a lead seal 5 MN MN NY HM x Q Z f PAPA n PA LU a ZA X o v AUS 2 di 2 9 2 2 I A 2 lAl lA DE57536 DE57538 DE57539 Padlocking Lead sealing DE57537 Locking of the circuit breaker in the open position The circuit breaker is locked in the open position by blocking the opening push button in the engaged position m by a padlock 1 to 3 padlocks not supplied m by a keylocks 1 or 2 different keylocks not supplied The keylocks are of captive key type with the key free after locking either Profalux or Ronis right turn and are proposed according to the options either with m 1 single keylock m 1 single keylock mounted on the circuit breaker 1 identical delivered separately for interlocking with another device m 2 different keylocks for double locking Profalux and Ronis keylocks are inter compatible Keylocking of the
53. mote control mechanism comprising electrical motor shunt closing release operation counter m Operation counter m Low energy release Mitop m Interlocking between the open circuit breaker position and the LV plug m Racking truck m Circuit breaker front cover 72 Schneider AMTED307010EN indd Electric Schneider Electric Industries SAS 35 rue Joseph Monier CS 30323 F 92506 Rueil Malmaison Cedex RCS Nanterre 954 503 439 Capital social 896 313 776 www schneider electric com AMTED307010EN As standards specifications and designs change from time to time please ask for confirmation of the information given in this publication 9 This document has been printed on ecological paper Publishing Schneider Electric Industries SAS Design Schneider Electric Industries SAS Printing Altavia Connexion 04 2014 ART 831041 Schneider Electric Industries SAS All rights reserved
54. ng This 525 mm long duct with a hinged LV plug enables protection of the LV wiring that connects the circuit breaker to the cubicle s LV compartment Interlocking kit For circuit breakers intended for withdrawable applications an interlocking kit can be adapted The kit enables the mechanical position status to be given connected disconnected of the LV plug By adding a link between this mechanical data by the customer and the open closed position of the circuit breaker interlocking can be achieved between the LV plug and the open closed position of the circuit breaker required by IEC standard 62271 200 A detailed explanation of operation is given in the Installation Guide 42 pin version LV plug 18 Schneider AMTED307010EN indd Electric PE56600 DES9408EN Evolis 17 5kV fixed version Circuit breaker open Operating mechanism loaded Charged A AS 1 ip Description of functions P2 stored energy operating mechanism Wiring diagram Operation of the P2 stored energy operating mechanism This gives the device an opening and closing speed that is independent of the operator whether the order is electrical or manual The electrical control mechanism carries out reclosing cycles and is automatically recharged by a geared motor each time after closing It consists of m the stored energy operating mechanism which stores in springs the energy required to open and close the device m a ge
55. ng 200 for 200 ms Latched 4 5 Time delay 0 5s 0 9s 1 5s 3s Low energy release Mitop This release includes a low consumption unit and is specifically used with the Sepam 100LA self powered unit REFLEX MODULE or the VIP relay Power supply Direct current Threshold 0 6A 1 3A Any tripping due to the Mitop release unit is momentarily indicated by an SDE type changeover contact provided with the Mitop This release also includes a coil reset enabling remote SDE contact reset Comment Use of the Mitop low energy release requires adjustment of the protection relay time delay in order to ensure that the circuit breaker trips between 45 50 ms Releases combinations table Shunt opening MX1 111111111111 Shunt opening MX2 1 1 Undervoltage MN 1 1 Mitop 1 1 1 Schneider 41 Electric 0 58085 0 58086 0 58082 Evolis 17 5 kV withdrawable version in NEX cradle Electrical motor MCH Shunt closing release XF 42 Scbneider Electric Description of functions Remote control Function Remote control enables the remote opening and closing of the circuit breaker The opening order always takes priority over the closing order In the event of simultaneous opening and closing orders the mechanism discharges under no load without moving the main contacts The circuit breaker remains in the open position In the event of latched opening and closing ord
56. ors Extendable connectors Extendable connectors horizontal H vertical V DE57516 DE57517 0 57511 An adjustable connector enables the connection distance to be increased from 0 to 25 mm 3 connector sets Mixed solution Example 0 57518 Comment The insulation withstand values given in the performance table do not take account of the connectors With these connectors it is possible to use unplated or tin plated copper conductors or tin plated aluminium conductors without any specific precautions being required The shape and dimensions of these conductors must be determined by the panel builder according to the dielectric withstand and temperature rise characteristics of the whole connection system Typical examples are provided in the Installation Guide 16 Schneider AMTED307010EN indd Electric DE57519 DE57520 0 57521 Evolis 17 5 kV Description of functions fixed version MV connection cont Composition Panels builders with own cubicle designs including the racking truck can transform a fixed device into a withdrawable device by adding the following assemblies m arms m clusters m fingers m bushings m field deflectors Cluster and finger m The tulip type cluster has a shape which provides maximum contact surface whilst optimising heat dissipation Moreover in the case of short circuit it offers good compensation characteristics for electrodynamic forces m The f
57. perating mechanism through a cable protection duct m With LV plug The fixed part male mounted on the circuit breaker and fully connected to the operating mechanism The mobile part female compatible with the male part DE57522 LVtermihal block Two versions of the LV plug are available An 18 pin version enabling connection of m a shunt opening release MX1 m remote control mechanism electrical motor shunt closing release XF anti pumping relay m a ready to close contact PF m a maximum number of 4 auxiliary contacts see indication page Open closed position auxiliary contacts chapter An 24 pin version enabling connection of an opening release shunt type MX1 or undervoltage type MN a second opening release shunt type MX2 or undervoltage type MN a low energy release Mitop a fault trip indicator contact SDE a remote contact reset system SDE a remote control mechanism electrical motor shunt closing release XF a ready to close contact PF m a maximum number of 11 auxiliary contacts see indication page Open closed position auxiliary contacts chapter DE57523 Note see the table of the releases combinations Order form page DE57524 LV wiring kit A wiring kit with 21 or 42 wires 2 meters long equipped with pins that can be adapted to the LV plug can be supplied for connected in to the cubicle s LV compartment Flexible ducti
58. range Evolis circuit breakers are positioned very favorably on the retrofit market Schneider 13 Electric Evolis 17 5 kV fixed version i Schneider PE58083 Main characteristics Phase to phase mm 145 Rated voltage Ur kV 50 60 Hz 7 2 12 Insulation level power frequency withstand Ud kV 50 Hz 1min 20 28 lightning impulse withstand Up kV peak 60 75 Rated current Ir A 630 1250 1600 2 2500 2 Short circuit current Isc kA 25 31 5 25 31 5 Short time withstand current Ik tk kA 3 s 25 31 5 25 31 5 Short circuit making current Ip kA peak 50 Hz 63 79 63 79 60 Hz 65 82 65 82 Rated switching sequence O 3 min CO 3 min CO 0 3 5 3 0 3 s CO 15 s CO Operating times Opening lt 50 ms Breaking lt 60 ms Closing lt 65 ms Service temperature T C 25to 40 Mechanical endurance Class M2 Number of switching operations 10000 Electrical endurance Class E2 Number of switching operations 25 kA 100 at full Isc value 31 5kA 50 Capacitive current breaking capacity Class C1 Average relative humidity Over 24h lt 95 Over 1 month lt 90 Evolis range circuit breakers are well suited for switching and protection of capacitor banks with installed power up to 2 Mvar installed in series with dampening reactor limiting inrush current to 2 kA Evolis is also well
59. rawable frontal version Evolis 24 kV withdrawable frontal version in NEX cradle in NEX cradle D a _ lt Evolis 17 5 kV withdrawable frontal version in MC cassette EVOset a fixed lateral version equipped with an integrated protection chain The EVOset is provided with a fully autonomous integrated protection chain with a VIP type control unit operating without an auxiliary power source The protection unit exists in 4 models VIP30 VIP35 VIP300P and VIP300LL VIP protection units are associated with functional current sensors The circuit breaker is delivered with its factory tested protection chain It therefore simplifies the panel builder s installation work PE58090 7 EVOset 24 kV fixed lateral version The Evolis 24 kV offer is covered in a separate catalog MV connection on the right hand side ref AMTED307011EN AMTED307010EN indd Schneider 3 Electric General presentation Evolis The very best of vacuum technology As a specialist in breaking technologies Make up of a vacuum interrupter Schneider Electric took natu rally aninterest Vacuum interrupters basically have two electrical contacts fig 1 one fixed and the in vacuum breaking techniques other mobile and a sealed enclosure The latter enables a high level of vacuum to be maintained inside the interrupter less than 10 2 Pa to provide insulation between Amajor R amp D investment was made to the open
60. rawable circuit breaker sti in the cradle It includes a device to lock it in the in service position Disconnecting truck Rated voltage Ur kV 7 2to 17 5 Phase distance mm 145 185 240 Rated normal current Ir A 1250 1250 2500 Short time withstand current 3 s Ik kA 25 31 5 40 Making capacity kA peak 2 5 Ik 50 Hz amp 2 6 Ik 60 Hz Earthing truck DE57573 This device is a safety accessory used in place of the withdrawable circuit breaker in order to earth the busbars Possibility of locking by padlocks in the service position Rated voltage Ur kV rms 12 17 5 17 5 Earthing truck Phase distance mm 145 185 240 Short time withstand current 3 s Ik kA 25 31 5 40 Making capacity kA peak 2 5 Ik 50 Hz amp 2 6 Ik 60 Hz 46 Schneider AMTED307010EN indd Electric Evolis 17 5 kV withdrawable version in NEX cradle Dimensions Phase to phase distance 145 mm Ur Isc Ir Weight 7 2kV 25kA 165 kg 1250A 31 5 630A 1250A 12kV 25kA 1250A 1250 17 5 kV 25 630A 1250A 31 5 630A 1250A Phase to phase distance 185 mm Ur Isc Ir Weight 7 2kV 25 174 kg 1250A 1250 12kV 25kA 630A 1250A 31 5 630A 1250A 17 5 kV 25kA 1250A 1250 Phase to phase distance 240 mm Ur Isc Ir Weight 7 2kV 25kA 2500A 272 kg 31 5 2500A 12kV 25 2500A 31 5 2500A 17 5 kV 25 2500A
61. required procedure Applications Evolis is intended for use in medium voltage network applications in new installations or renovation for utilities companies infrastructures the process industry and the tertiary sector It provides protection for all types of applications cables overhead lines motors capacitors transformers source busbar sections etc Evolis a fixed frontal or lateral version Here the circuit breaker is in its simplest version In this case it can be combined with additional accessories to meet various requirements For the fixed lateral version the MV connection can be on the right oron the left depending on the type of circuit breaker a Lu n d e _ PE58083 PE58084 Evolis 17 5 kV fixed frontal version Evolis 24 kV fixed frontal version PE58085 PE58086 Evolis 24 kV fixed lateral version Evolis 24 kV fixed lateral version MV connection on the left hand side MV connection on the right hand side The Evolis 24 kV offer is covered in a separate catalog ref AMTED307011EN 2 Scbneider AMTED307010EN indd d Electric General presentation Evolis Circuit breakers adapted to your needs cont Evolis a withdrawable frontal version In this version the circuit breaker is equipped with arms clusters a rack and cradle or cassette The cradle and the circuit breaker can be ordered and delivered separately PE57994 PE58001 Evolis 17 5 kV withd
62. ries W EN 45011 general requirements for bodies of operating product certification Systems Environmental care Product design takes account of the environmental constraints described in a Product Environment Profile dossier PEP An end of service life manual details procedures for dismantling and processing components AMTED307010EN indd PE58082 General presentation Circuit breaker m cradle Instrument transformer MV cubicle components m capacitor insulator m earthing switch m heating resistor voltage presence indicator mcrank m extraction table AMTED307010EN indd Evolis Extended products offer LV cubicle components m Mcb m protection relay mlamp m push button m terminal blocks connector Protection and control m UMI Metering m VPIS m PM700 or PM800 Electric Schneider 7 Panorama Circuit breakers Evolis circuitbreakers Fixed version Operating mechanism on the front Rated voltage Ur kV 50 60 Hz Short circuit rated breaking capacity Isc from 25 to 31 5 kA Rated current Ir from 630 to 2500 A 8 Schneider Electric Withdrawable version in NEX cradle Operating mechanism on the front from 25 to 31 5 KA from 630 to 2500 A Withdrawable version in MC cassette Operating mechanism on the front from 25 to 31 5 kA from 630 to 2500 A AMTED307010EN indd
63. suited for capacitor banks system with installed power higher than 2 Mvar in conjunction with anti harmonic filtering system Please consult us AMTED307010EN indd Evolis 17 5 kV Main characteristics cont fixed version 185 240 7 2 12 17 5 7 2 12 17 5 20 28 38 20 28 38 60 75 95 60 75 95 E a E ux E u a L a a E L a L a a a 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 25 31 5 63 79 63 79 63 79 63 79 63 79 63 79 65 82 65 82 65 82 65 82 65 82 65 82 1 Circuit breaker tested at Ud 42 kV 50 Hz 1min 2 Class 1 2000 operations for Ir 1600 A and 2500 A m Available Not available AMTED307010EN indd Schneider 15 Electric Evolis 17 5 Description of functions fixed version MV connection Composition The basic circuit breaker is equipped with drilled copper connection terminals at the top and bottom of the breaking units The connectors are fitted to the terminals using the corresponding bolts Several variants are possible DE57510 Fixed connectors Horizontal connectors H Vertical connectors V Mixed connectors DE57512 DE57513 DE57514 Connection tenninar An adjustable connector enables the vertical distance to be increased to enable rotation of 90 Adjustable gap connect
64. ture Separated components Services Schneider Electric 11 12 Schneider AMTED307010EN indd Electric PE58083 Evolis 17 5kV fixed version Evolis circuit breaker 17 5 kV fixed version AMTED307010EN indd Presentation Description of the device The Evolis circuit breaker comprises a basic fixed version m poles integrated in a sealed pressure system type insulating enclosure m aP2 type spring operated stored energy control mechanism electrifiable This gives the device an opening and closing speed that is independent of the operator for both electrical and manual orders It enables reclosing cycles to be carried out m a front panel housing the manual operating mechanism and status indicators m upstream and downstream terminals for the power circuit connection m aterminal block for connection of external auxiliary circuits Each device can also be fitted with the following options m a supporting frame equipped with rollers and ground fixing brackets for fixed installation m circuit breaker locking in the open position by a keylock installed on the front plate of the operating mechanism m a 18 pin or 42 pin Harting type LV connector Applications Evolis circuit breakers are three pole indoor MV circuit breakers They are mainly used for operation and protection of public industrial and tertiary distribution networks from 7 2 to 17 5 kV Through their compact dimensions and harmonized
65. usly indicates that m the circuit breaker is open m the storage energy springs are armed m there is no permanent closing order m there is no permanent opening order caused by a safety opening order 2nd MX or MN keylocking of the device in the open position Standard delivery 0 Maximum quantity 1 Breaking capacity A Standard Min load 100 mA 24 V Cos q 0 3 VAC 240 380 5 CA12 DC12 480 5 690 3 VDC 24 48 3 125 0 3 250 0 15 Low level Min load 2 mA 15 V DC VAC 24 48 3 240 3 380 3 VDC 24 48 3 125 0 3 250 0 15 Operation counter CDM The operation counter is visible on the front panel Ittotalizes the number of switching cycles CO that the device has carried out Schneider 65 Electric Evolis 17 5 Description of functions withdrawable version Interlocking in MC cassette Cubicle door interlocking mechanism This device enables the circuit breaker to only be operated when the door is closed for the withdrawable version with a cradle DE57587 Cubicle door interlocking mechanism 66 Schneider AMTED307010EN indd Electric Evolis 17 5 kV withdrawable version in MC cassette Description of functions Safety functions This table describes the safety functions available on the withdrawable version of the Evolis 17 5 kV circuit breaker How to use the table Each of the boxes describes the functional status of each circuit break
66. ve device with a threaded shaft activated by a handle including all of the safety interlock systems a Harting type male LV connector allows connection of the external auxiliary circuits Each device can optionally be fitted with locking of the circuit breaker in the following positions open by a key lock installed on the control panel racked out by a key lock installed on the drive device the basic NEX cradle comprising a metal structure and two guide rails fixed connection fingers insulated by bushings metal shutters to insulate from the HV part safety interlocking systems NEX cradle options circuit breaker racked in or out position indicator contacts a circuit breaker racked in blocking mechanism an extraction tool a foolproof device for the circuit breaker rating Applications Evolis circuit breakers are three pole indoor MV circuit breakers They are mainly used for operation and protection of public industrial and tertiary distribution networks from 7 2 to 17 5 kV Through their compact dimensions and harmonized range Evolis circuit breakers are positioned very favorably on the retrofit market Schneider 33 Electric Evolis 17 5 kV Main characteristics withdrawable version in NEX cradle i Phase to phase mm 145 Rated voltage Ur kV 50 60 Hz 7 2 12
67. version inMC cassette Circuit breaker open Operating mechanism loaded 1 1 1 1 Charged Description of functions P2 stored energy operating mechanism Wiring diagram Operation of the P2 stored energy operating mechanism This gives the device an opening and closing speed that is independent of the operator whether the order is electrical or manual The electrical control mechanism carries out reclosing cycles and is automatically recharged by a geared motor each time after closing It consists of m the stored energy operating mechanism which stores in springs the energy required to open and close the device m agear motor electrical charging device with manual charging by lever useful on loss of auxiliary supply m manual order devices by push buttons on the front panel of the device m an electrical remote closing device containing a release with an antipumping relay m an electrical opening device containing one or more releases for example shunt opening undervoltage Mitop a low consumption release used only with the Sepam 100 LA protection relay m an operation counter m position indication device by mechanical indicator and 3 modules of 4 auxiliary contacts whose availability varies according to the diagram used m a device for indicating charged operating mechanism status by mechanical indicator and electrical contact Wiring diagram principle eady to close
68. when the circuit breaker is in the test or service position Earthing is achieved throughout the operation via the racking carriage casters An addition earthing system can be supplied as an option DE57585 Interlocking mechanisms In conformity with IEC standards 62271 100 and 62271 200 the following interlocks are available m impossibility of racking in or out is the circuit breaker is not in the open position m impossible to rack in the circuit breaker when the LV plug is not connected m impossible to disconnect the LV plug if the circuit breaker is not racked out Cubicle door interlocking mechanism The carriage is equipped with a device that enables interlocking between the racking out of the circuit breaker and the cubicle door W possible to rack in the circuit breaker only if the door is closed m possible to open the door only if the circuit breaker is racked out This device must be disabled if the interlocking function is not present DE57586 Disconnected position DE57587 Interlocking door cubicle 58 Schneider AMTED307010EN indd Electric DE57588 DE57589 DE57590 DE57591 DE57592 Evolis 17 5 kV withdrawable version in MC cassette Extraction tool Discharge of the circuit breaker operating mechanism on extraction Cassette circuit breaker foolproofing device AMTED307010EN indd Description of functions Racking in cont MC cassette sa
69. ws connection of the external auxiliary circuits Each device can optionally be fitted with m locking of the circuit breaker in the following positions open by a key lock installed on the control panel racked out by a key lock installed on the drive device m the basic MC cassette comprising a metal structure and two guide rails fixed connection fingers insulated by bushings metal shutters to insulate from the HV part safety interlocking systems a female Harting type LV connector m MC cassette options circuit breaker racked in or out position indicator contacts a circuit breaker operating mechanism spring discharge system a circuit breaker racked in blocking mechanism an extraction tool an equipped door a foolproof device for the circuit breaker rating Applications Evolis circuit breakers are three pole indoor MV circuit breakers They are mainly used for operation and protection of public industrial and tertiary distribution networks from 7 2 to 17 5 kV Schneider 55 Electric Evolis 17 5 kV Main characteristics withdrawable version in MC cassette Phase to phase mm 145 Cassette type MC1 Rated voltage Ur kV 50 60 Hz 7 2 12 Insulation level power frequency withstand Ud kV 50 Hz 1min 20 28 lightn