1. Input Power 1 0x0434 0 65534 10 Watt Input Frequency 2 0x0435 0 999 0 1Hz Input Voltage 2 0x0436 0 9999 0 1 Voltage Input Current 2 0x0437 0 9999 0 1Amp Input Power 2 0x0438 0 65534 10 Watt Input Frequency 3 0x0439 0 999 0 1Hz Input Voltage 3 0x043A 0 9999 0 1 Voltage Input Current 3 0x043B 0 9999 0 1Amp Input Power 3 0x043C 0 65534 10 Watt Input Voltage 12 0x043D 0 9999 0 1 Voltage Input Voltage 23 0x043E 0 9999 0 1 Voltage Input Voltage 31 0x043F 0 9999 0 1 Voltage Reserved 0x0440 Reserved 0x0441 23 Output Status Description Address Value Unit Output Source 0x0442 10 Normal 1 Battery 2 Bypass Reserve 3 Reducing 4 Boosting 5 Manual Bypass 6 Other 7 None Output Frequency 0x0443 0 999 0 1Hz Output Number Lines 0x0444 0 9 Output Voltage 1 0x0445 0 9999 0 1Voltage Output Current 1 0x0446 0 9999 0 1Amp Output Power 1 0x0447 0 65534 10 Watt Output Load1 0x0448 0 999 Output Voltage 2 0x0449 0 9999 0 1Voltage 24 Output Current 2 0x044A 0 9999 0 1Amp Output Power 2 0x044B 0 65534 10 Watt Output Load 2 0x044C 0 999 Output Voltage 3 0x044D 0 9999 0 1 Voltage Output Current 3 0x044E 0 9999 0 1Amp Output Power 3 0x044F 0 65534 10 Watt Output Load 3 0x0450 0 999 Output Voltage 12 0x0451
2. Description Address Value Unit Temperature 0x0469 0 999 Degree Celsius Humidify 0x046A 0 999 Relay 1 0x046B 10 Off 1 On Relay 2 0x046C O Off 1 On Relay 3 0x046D 0 Off 1 On Relay 4 Ox046E 10 Off 1 On Reserved 0x046F Reserved 0x0470 29 Select Voltage Description Address Value Unit Selected Output Voltage 0x0471 0 999 Voltage Select Output Voltage1 0x0472 0 999 Voltage Select Output Voltage2 0x0473 0 999 Voltage Select Output Voltage3 0x0474 0 999 Voltage SRAM EXIST Description Address Value Unit SRAM EXIST 0x0475 10 Not Exist 1 Existed Remark Currently this field is not supported by UPS 30 TempStatus Description Address Value Unit TempStatus Byte 1 2 0x0476 Lo Byte1 Hi Byte2 TempStatus Byte 3 4 0x0477 TempStatus Byte 5 6 0x0478 TempStatus Byte 7 8 0x0479 TempStatus Byte 9 10 0x047A TempStatus Byte 11 12 0x047B TempStatus Byte 13 14 0x047C TempStatus Byte 15 16 0x047D TempStatus Byte 17 18 0x047E TempStatus Byte 19 20 0x047F Reserved 0x0480 Reserved 0x0481 31 Temp Byte1 Lo R Phase Inverter Temperature Temp Byte2 Hi BO Temperature Warning gt 75C B1 High Temperature Shutdown gt 85C B2 Inverter Voltage too Low B3 Inverter Voltage too High B4 Overload Warning B5 Overload Shutdown B6 Inverter Fuse Fail Shutdown B7 Inv PCB communication abn
3. 1 Connection Remark 1 Filed value OxFFFF in Input Registers represents that field is not supported by UPS 55
4. MODBUS Communication Card J Jo User Manual UL 1 Presentation 1 1 Overview MODBUS Card ID configuration switch RS 232 Port configuration switch RS 422 485 Port configuration switch RS 422 485 selection switch RS 422 485 and RS 232 communication port Diagnostic LEDs DUID AIN 1 2 Function Provide UPS the functionality of communication with PC through MODBUS protocol Implementation of MODBUS RTU protocol Provide MODBUS function including Read Coils Discrete Inputs Holding Registers Input Registers and Write Single Coil Single Register Provide RS 422 485 and RS 232 interfaces PC can communicate with UPS through RS 422 485 or RS 232 or both simultaneously Provide alarm LEDs users can tell communication status quickly Except MODBUS protocol also support 3Phase Regular Protocols Users can select communication protocol through function switches Provide firmware upgrade functionality through RS 232 port 2 Installation ID Configuration of MODBUS Card e Users can set card ID value from 0 to 255 through SW1 2 1 ON As above setting card ID will be 1 ID Configuration JHHHBEHL LSB 1 7 gt MSB Protocol Function MODBUS Card ID is equal to 0 Use UPS ID to get UPS Info Card ID is not equal to 0 Use Card ID to get UPS Info 3Phase Card ID is equal to 0 Use UPS ID to get UPS Info Card ID is not equal to 0
5. Use Card ID to get UPS Info Regular Card ID is equal to 0 Use UPS ID to get UPS Info Card ID is not equal to 0 Use Card ID to get UPS Info 4 2 2 Configuration of RS 232 Port e Use SW2 to configure RS 232 interface e Pin out CN3 p Pin Function 6 Card TxD transfer data to PC 7 Card RxD receive data from PC 8 GND e RS 232 Port Configuration Function Switch Value SW2 1 SW2 2 OFF OFF 2400 Baud rate ON OFF 4800 OFF ON 19600 ON ON 19200 OFF Disable Parity Check Parity SHE ON Enable Parity Check Check OFF Even Parity Ne ON Odd Parity SW2 5 SW2 6 Protocol OFF OFF MODBUS Protocol ON OFF Regular Protocol OFF ON 3Phase Protocol SW2 7 Reserved SW2 8 Reserved 6 2 3 Configuration of RS 422 485 Port e Use SW3 to configure RS 422 485 interface Pin out CN3 X Ering Pin Function 1 Card D T 2 Card D T 3 Card R 4 Card R RS 485 RS 422 Selection Switch Setting Function SW4 RS485 Enable RS 485 RS422 Enable RS 422 e RS 422 485 Port Configuration Function Switch Value SW3 1 SW3 2 OFF OFF 2400 Baud rate ON OFF 4800 OFF ON 9600 ON ON 19200 sw3 3 OFE Disable Parity Check Parity ON Enable Parity Check Check swaga LOFE Even Parity ON Odd Parity Protocol SW3 5
6. TBD B19 TBD B20 TBD 43 B21 TBD B22 TBD B23 Not calibrated used to indicate whether the power module has been calibrated 44 Power Module Charger Status Description Address Value Unit Power Module ID Charger Status 0x04AA Lo ID 1 4 Hi Status Power Module ID Charger Status 0x04AB Power Module ID Charger Status 0x04AC Power Module ID Charger Status 0x04AD Reserved Ox04AE Reserved Ox04AF Charger Status BO Charger circuit general fault B1 B7 Reserved 45 Power Module Temperature Status Description Address Value Unit Power Module ID 0x04B0 1 4 Temperature PFC 0x04B1 0 9999 0 1Voltage Temperature TBD 0x04B2 0 9999 0 1Voltage Temperature INV 0x04B3 0 9999 0 1Voltage Temperature INV R 0x04B4 0 9999 0 1 Voltage Temperature INV S 0x04B5 0 9999 0 1Voltage Temperature INV T 0x04B6 0 9999 0 1 Voltage Power Module ID 0x04B7 1 4 Temperature PFC 0x04B8 0 9999 0 1Voltage Temperature TBD 0x04B9 0 9999 0 1Voltage Temperature INV 0x04BA 0 9999 0 1Voltage Temperature INV R 0x04BB 0 9999 0 1Voltage Temperature INV S 0x04BC 0 9999 0 1Voltage Temperature INV T 0x04BD 0 9999 0 1Voltage Power Module ID 0x04BE 1 4 46 Temperature PFC 0x04BF 0 9999 0 1 Voltage Temperature TBD 0x04C0 0 9999 0 1 Voltage Te
7. 0 9999 0 1 Voltage Output Voltage 23 0x0452 0 9999 0 1 Voltage Output Voltage 31 0x0453 0 9999 0 1Voltage Reserved 0x0454 Reserved 0x0455 25 Bypass Status Description Address Value Unit Bypass Frequency 0x0456 0 999 0 1Hz Bypass Number Lines 0x0457 0 9 Bypass Voltage 1 0x0458 0 9999 0 1 Voltage Bypass Current 1 0x0459 0 9999 0 1 Amp Bypass Power 1 0x045A 0 65534 10 Watt Bypass Voltage 2 0x045B 0 9999 0 1 Voltage Bypass Current 2 0x045C 0 9999 0 1Amp Bypass Power 2 0x045D 0 65534 10 Watt Bypass Voltage 3 0x045E 0 9999 0 1 Voltage Bypass Current 3 0x045F 0 9999 0 1Amp Bypass Power 3 0x0460 0 65534 10 Watt Bypass Voltage 12 0x0461 0 9999 0 1 Voltage Bypass Voltage 23 0x0462 0 9999 0 1 Voltage Bypass Voltage 31 0x0463 0 9999 0 1 Voltage 26 Bypass STS Temperature 0x0464 0 999 Degree Celsius Reserved 0x0465 Reserved 0x0466 Test Status Description Address Value Unit Test Result 0x0467 No Test Performed Test Passed Test in Progress General Test Fault Battery Test Fault Deep Battery Test Fault 6 Test Aborted ARON 0O 27 Output Relay Description Address Value Unit Number of Output Relay 0x0468 0 Not Available gt 0 Available lt 99 28 Environment
8. 0x0400 0x051C Read Function 0x04 Rating Value Description Address Value Unit Series 0x0400 0 T 1 H 2 NT 3 NH Raging Input Voltage 0x0401 0 999 Voltage Rating Input Frequency 0x0402 0 999 0 1Hz Rating Output Voltage 0x0403 0 999 Voltage Rating Output Frequency 0x0404 0 999 0 1Hz Rating VA 0x0405 0 65534 10 VA Rating Output Power 0x0406 0 65534 10 Watt Low Battery Time 0x0407 0 99 Minutes Low Tx Voltage Point 0x0408 0 999 Voltage High Tx Voltage Point 0x0409 0 999 Voltage Low Tx Voltage Upper Bound 0x040A 0 999 Voltage 18 Low Tx Voltage Lower Bound 0x040B 0 999 Voltage High Tx Voltage Upper Bound 0x040C 0 999 Voltage High Tx Voltage Lower Bound 0x040D 0 999 Voltage UPS Type 0x040E 0 On Line 1 Off Line 2 Line Interactive 3 3Phase 4 Split Phase 5 Others Rating Battery Voltage 0x040F 0 999 Voltage Low Tx Frequency Point 0x0410 0 999 0 1Hz High Tx Frequency Point 0x0411 0 999 0 1Hz Bypass Rating Frequency 0x0412 0 999 0 1Hz Bypass Freq Max Tolerance 0x0413 5 50 0 1Hz Bypass Freq Set Tolerance 0x0414 5 50 0 1Hz Bypass Low Tx Voltage Point Bypass 0x0415 0 999 Voltage Rating Voltage 19 Bypass High Tx Voltage Point 0x0416 0 999 Voltage Bypass Low Tx Voltage Upper 0x0417 0 999 Voltage Bound Bypass Voltage Max Tolerance By
9. STS Over 0x012B OK Bypass STS Over Temperature Temperature Alarm Bypass STS Fault 0x012C OK Bypass STS Fault Reserved 0x012D Reserved 0x012E Reserved 0x012F Remark 1 UPS may not support all of fields 3 2 Coils Range 0x0200 0x020F Read Function 0x01 Write Function 0x05 Description Address Value 0 Value 1 UPS Buzzer 0x0200 Silence Alarm Shutdown Type 0x0201 UPS Output UPS System Economic Mode Setting 0x0202 Disable Enable ATX PC Reboot Function 0x0203 Disable Enable AG Fail amp Restore Auto Reboot 0x0204 Disable Enable 13 ATX PC Resume Function 0x0205 Disable Enable Enable Disable Buzzer 0x0206 Disable Enable EPO Setting 0x0207 Disable Enable Enable Disable Inverter 0x0208 Disable Enable Clear SRAM 0x0209 Clear SRAM Clear SRAM Cancel Shutdown Restart 0x020A Cancel Shutdown Cancel Restart Shutdown Restart Set Output On Off 0x020B OFF ON Reserved 0x020C Reserved 0x020D Reserved 0x020E Reserved 0x020F Remark UPS may not support all of fields 14 3 3 Holding Register Range 0x0300 0x0321 Read Function 0x03 Write Function 0x06 Description Address Value Unit Shutdown Action 0x0300 0 9999 0 Abort Seconds Shutdown Restart 0x0301 0 65535 Minutes Test 0x0302 10 Abort Test 1 General Test 2 BTV Test 3 Test for 10 seconds 4 Test until
10. SW3 6 2 4 OFF off MODBUS Protocol ON OFF Regular Protocol OFF ON 3Phase Protocol b e OFF Disable RS 485 422 Termination Resistor Termination ON Enable RS 485 422 Termination Resistor Resistor SW3 8 OFF Disable RS 422 Termination Resistor ON Enable RS 422 Termination Resistor LED Indicator LED Status Description Red LED Dark UPS is disconnected Flashing 1 second UPS is connected Green LED Light 0 2 second When receive PC request 3 Operation 3 1 Discrete Inputs Range 0x0100 0x012F Read Function 0x02 Description Address Value 0 Value 1 Alarm Temperature 0x0100 OK Over Temperature Alarm Input Bad 0x0101 JOK Input Bad Alarm Output Bad 0x0102 OK Output Bad Alarm Overload 0x0103 OK Overload Alarm Bypass Bad 0x0104 OK Bypass Bad Alarm Output Off 0x0105 Output On Output Off Alarm UPS Shutdown 0x0106 OK Shutdown Alarm Charger Failure 0x0107 OK Charger Failure Alarm System Off 0x0108 System On System Off Alarm Fan Failure 0x0109 OK Fan Failure Alarm Fuse Failure 0x010A JOK Fuse Failure Alarm General Fault 0x010B OK General Fault Alarm Awaiting Power 0x010C OK Awaiting Power Alarm Shutdown Pending 0x010D OK Shutdown Pending 10 Alarm Shutdown Imminent 0x010E OK Shutdown Imminent Buzzer Status 0x010F Silenc
11. battery low UPS Identification 0x0303 0 99 Low Transfer Voltage 0x0304 0 999 Voltage High Transfer Voltage 0x0305 0 999 Voltage Voltage Sensitivity 0x0306 0 Normal 1 Reduced 2 Low Last Battery Replace Date Year 0x0307 0 9999 15 Last Battery Replace Date Month 0x0308 1 12 Last Battery Replace Date Day 0x0309 1 31 Next Battery Replace Date Year 0x030A 0 9999 Next Battery Replace Date Month 0x030B 1 12 Next Battery Replace Date Day 0x030C 1 31 UPS Periodic Auto Test 0x030D 1 Disable 2 Daily 3 Weekly 4 Bi Weekly 5 Monthly Buzzer Test 0x030E 1 99 Seconds UPS Boot Delay 0x030F 0 999 Seconds Bypass Freq Tolerance 0x0310 5 50 0 1Hz Select Output Voltage 0x0311 0 999 Voltage Test Time 0x0312 1 60 Minutes Test Voltage 0x0313 0 999 Voltage Reserved 0x0314 16 Reserved 0x0315 External Battery Pack 0x0316 O 10 Dry Contact W1 0x0317 Dry Contact W2 0x0318 Dry Contact W3 0x0319 Dry Contact W4 0x031A Dry Contact W5 0x031B Dry Contact W6 0x031C Bypass Low Transfer Voltage 0x031D 0 999 Voltage Bypass High Transfer Voltage 0x031E 0 999 Voltage Bypass Voltage Tolerance 0x031F 0 999 Voltage Dry Contact Input Status 1 0x0320 Dry Contact Input Status 2 0x0321 Remark UPS may not support all of fields 17 3 4 Input Register Range
12. e Alarm Economic Mode 0x0110 No Yes Alarm Inverter Bad 0x0111 JOK Inverter Bad Emergency Power Off 0x0112 Off On Buzzer State 0x0113 Disable Enable Battery Ground Fault 0x0114 OK Battery Ground Fault Reserved 0x0115 Reserved 0x0116 Reserved 0x0117 Alarm Rectifier Main Fail 0x0118 OK Rectifier Main Fail Alarm Rectifier Hi DC Stop 0x0119 OK Rectifier Hi DC Stop Alarm Over Temperature or Fuse 0x011A OK Over Temperature or Fuse Fail Fail Alarm Battery Low 0x011B OK Battery Low Alarm Battery Low Stop 0x011C OK Battery Low Stop Alarm Battery Ground Fault 0x011D OK Battery Ground Fault 11 Inverter ON Ox011E Inverter OFF Inverter ON Alarm Inverter Overload 0x011F OK Inverter Overload Alarm Inverter Abnormal 0x0120 JOK Inverter Abnormal Alarm Load On Reserve 0x0121 Load Not On Load On Reserve Reserve Alarm Reserve Mains Fail 0x0122 OK Reserve Mains Fail Alarm Reserve Freq Abnormal 0x0123 OK Reserve Freq Abnormal Alarm Test In Progress 0x0124 No Test In Test In Progress Progress Alarm Test Error 0x0125 No Test Error Test Error UPS In Sleep Mode 0x0126 UPS Notin UPS In Sleep Mode Sleep Mode Reserved 0x0127 Alarm Bypass Volt Freq Bad 0x0128 OK Bypass Volt Freq Bad Alarm Bypass Phase Sequence 0x0129 OK Bypass Phase Sequence Bad Bad Alarm Bypass STS Overload 0x012A OK Bypass STS Overload 12 Alarm Bypass
13. mperature INV 0x04C1 0 9999 0 1Voltage Temperature INV R 0x04C2 0 9999 0 1Voltage Temperature INV S 0x04C3 0 9999 0 1Voltage Temperature INV T 0x04C4 0 9999 0 1Voltage Power Module ID 0x04C5 1 4 Temperature PFC 0x04C6 0 9999 0 1Voltage Temperature TBD 0x04C7 0 9999 0 1Voltage Temperature INV 0x04C8 0 9999 0 1 Voltage Temperature INV R 0x04C9 0 9999 0 1Voltage Temperature INV S 0x04CA 0 9999 0 1 Voltage Temperature INV T 0x04CB 0 9999 0 1Voltage Reserved 0x04CC Reserved 0x04CD Reserved 0x04CE Reserved 0x04CF 47 Reserved 0x04D0 Reserved 0x04D1 Reserved 0x04D2 Reserved 0x04D3 Reserved 0x04D4 Reserved 0x04D5 Reserved 0x04D6 Reserved 0x04D7 Reserved 0x04D8 Reserved 0x04D9 48 Power Module Inverter Voltage Description Address Value Unit Power Module ID 0x04DA 1 4 Inverter Voltage R 0x04DB 0 9999 0 1 Voltage Inverter Voltage S 0x04DC 0 9999 0 1Voltage Inverter Voltage T 0x04DD 0 9999 0 1Voltage Power Module ID 0x04DE 1 4 Inverter Voltage R 0x04DB 0 9999 0 1Voltage Inverter Voltage S 0x04DC 0 9999 0 1Voltage Inverter Voltage T 0x04DD 0 9999 0 1Voltage Power Module ID 0x04DE 1 4 Inverter Voltage R 0x04DF 0 9999 0 1Voltage Inverter Voltage S 0x04E0 0 9999 0 1 Voltage Inverter Voltage T 0x04E1 0 9999 0 1 Voltage Power Module ID 0x04E2 1 4 Inverter V
14. nt Log Report Format 0 NT 9 byte format 1 NH 8 byte format 37 Power Module Attribute Description Address Value Unit Power Module ID Attribute 0x0486 Lo ID 1 4 Hi Attribute Power Module ID Attribute 0x0487 Power Module ID Attribute 0x0488 Power Module ID Attribute 0x0489 Reserved 0x048A Reserved 0x048B Power Module Attribute which is used to identify the attribute of the power module B0 PFC B1 Rectifier B2 Charger B3 Inverter B4 Bypass B5 TBD B6 TBD B7 TBD 38 Power Module General Status Description Address Value Unit Power Module ID General Status 0x048C Lo ID 1 4 Hi Status Power Module ID General Status 0x048D Power Module ID General Status 0x048E Power Module ID General Status 0x048F Reserved 0x0490 Reserved 0x0491 Power Module General Status BO The power module exist or the power module is powered B7 Fault shutdown 39 Power Module PFC Status Description Address Value Unit Power Module ID 0x0492 1 4 PFC Status 0 1 0x0493 Lo Status 0 Hi Status 1 Power Module ID 0x0494 PFC Status 0 1 0x0495 Power Module ID 0x0496 PFC Status 0 1 0x0497 Power Module ID 0x0498 PFC Status 0 1 0x0499 Reserved 0x049A Reserved 0x049B Reserved 0x049C Reserved 0x049D PFC Status BO PFC fuse open shutdown B1 PFC over temperature warning B2 PFC over tempera
15. oltage R 0x04E3 0 9999 0 1Voltage 49 Inverter Voltage S 0x04E4 0 9999 0 1 Voltage Inverter Voltage T 0x04E5 0 9999 0 1 Voltage Power Module ID Ox04E6 1 4 Inverter Voltage R 0x04E7 0 9999 0 1Voltage Inverter Voltage S 0x04E8 0 9999 0 1Voltage Inverter Voltage T 0x04E9 0 9999 0 1Voltage Reserved 0x04EA Reserved 0x04EB Reserved 0x04EC Reserved 0x04ED Reserved Ox04EE Reserved Ox40EF Reserved 0x04F0 Reserved 0x04F1 50 Battery Cabinet Temperature Description Address Value Unit Battery Cabinet 1 Temperature 0x04F2 0 999 Degree Celsius Battery Cabinet 2 Temperature 0x04F3 0 999 Degree Celsius Battery Cabinet 3 Temperature 0x04F4 0 999 Degree Celsius Battery Cabinet 4 Temperature 0x04F5 0 999 Degree Celsius Reserved 0x04F6 Reserved 0x04F7 SI Manufacture Description Address Value Unit Manufacture Byte 0 1 0x04F8 Lo ByteO Hi Byte 1 Manufacture Byte 2 3 0x04F9 Lo Byte2 Hi Byte 3 Manufacture Byte 4 5 0x04FA Lo Byte4 Hi Byte 5 Manufacture Byte 6 7 0x04FB Lo Byte6 Hi Byte 7 Manufacture Byte 8 9 0x04FC Lo Byte8 Hi Byte 9 Manufacture Byte 10 11 0x04FD Lo Byte10 Hi Byte 11 Manufacture Byte 12 13 0x04FE Lo Byte12 Hi Byte 13 Manufacture Byte 14 15 0x04FF Lo Byte14 Hi Byte 15 Reserved 0x0500 Reserved 0x0501 Reserved 0
16. ormal Temp Byte3 Lo S Phase Inverter Temperature Temp Byte4 Hi BO Temperature Warning gt 75C B1 High Temperature Shutdown gt 85C B2 Inverter Voltage too Low B3 Inverter Voltage too High B4 Overload Warning B5 Overload Shutdown B6 Inverter Fail Shutdown B7 Parallel Communication Abnormal Temp Byte5 Lo T Phase Inverter Temperature 32 Temp Byte6 Hi BO Temperature Warning gt 75C B1 High Temperature Shutdown gt 85C B2 Inverter Voltage too Low B3 Inverter Voltage too High B4 Overload Warning B5 Overload Shutdown B6 Inverter Freq Abnormal Shutdown B7 Parallel Communication Fail Temp Byte7 Lo B3 BO The Summary of UPS Run at Inverter Test Mode B7 B4 The Summary of UPS Run at Inverter Mode Temp Byte8 Hi BO Power Fail B1 EPO Happen B2 MB_ON To Bypass B3 Battery Low Warning B4 Battery Low Shutdown B5 Master UPS Output Sync B6 Inverter DC Bus Abnormal Shutdown B7 Short Circuit Happen Shutdown Temp Byte9 Lo Heatsink Temperature 33 Temp Byte10 Hi BO Bypass Voltage Over Bypass Voltage Under Bypass Freq Abnormal Bypass Phase Abnormal Rectifier Voltage Over Rectifier Voltage Under Rectifier Freq Abnormal Rectifier Phase Abnormal Temp Byte11 Lo Ambient Temperature Temp Byte12 Hi BO Bypass Voltage Under SSW at Bypass Side SSW at Inverter Side Rectifier Voltage Over Rectifier Voltage Under Rectifier Input Over Current B7 Bypa
17. pass Low Tx Voltage Lower 0x0418 0 999 Voltage Bound Bypass Voltage Set Tolerance Bypass High Tx Voltage Upper 0x0419 0 999 Voltage Bound Bypass High Tx Voltage Lower 0x041A 0 999 Voltage Bound Reserved 0x041B Reserved 0x041C Reserved 0x041D 20 Battery Status Description Address Value Unit Battery Condition 0x041E 0 Good 1 Weak 2 Replace Battery Status 0x041F 0 OK 1 Low 2 Depleted Battery Charge 0x0420 0 Floating 1 Charging 2 Resting 3 Discharging Seconds On Battery 0x0421 0 65534 Seconds Estimated Minutes Remaining 0x0422 0 9999 Estimated Charge Remaining 0x0423 0 999 Battery Voltage 0x0424 0 9999 0 1Voltage Battery Current 0x0425 0 9999 0 1Amp 21 Temperature 0x0426 0 999 Degree Celsius Battery Level 0x0427 0 999 External Battery Pack 0x0428 10 10 Negative Battery Voltage 0x0429 0 9999 0 1 Voltage Negative Battery Current 0x042A 0 9999 0 1 Amp Negative Battery Temperature 0x042B 0 999 Degree Celsius Negative Battery Level 0x042C 0 999 Reserved 0x042D Reserved 0x042E Reserved 0x042F Input Status Description Address Value Unit Input Number Lines 0x0430 0 9 Input Frequency 1 0x0431 0 999 0 1Hz Input Voltage 1 0x0432 0 9999 0 1 Voltage Input Current 1 0x0433 0 9999 0 1 Amp 22
18. ss Voltage Over Rectifier Input Current Unbalance Temp Byte13 Lo Battery Temperature Temp Byte14 Hi BO Bypass Voltage Over 34 B1 Bypass Voltage Under B2 Low Battery Shutdown B3 Low Battery Warning B4 Rectifier Voltage Over B5 Rectifier Voltage Under B6 Rectifier Fail B7 DC Bus Over Voltage Temp Byte15 Lo BO TR1 Over Temperature O P TR Over Heat Shutdown B1 TR2 Input Choke Over Heat l P TR Over Heat Shutdown B2 Rectifier Over Temperature Warning gt 75C B3 Rectifier Over Temperature Shutdown gt 85C B4 Static Switch Over Temperature Warning gt 75C B5 Static Switch Over Temperature Shutdown gt 85C B6 Static Switch Overload B7 Static Switch Fail Temp Byte16 Hi BO Converter Board Power Abnormal B1 EPO Happen B2 Manual Bypass On B3 Converter Board Communication Error 35 B4 Battery Cabinet Over Temperature Warning gt 75C B5 Battery Ground Fault B6 Battery Test in Progress B7 Battery Test Fail Temp Byte17 Reserved Temp Byte18 Reserved Temp Byte19 Reserved Temp Byte20 Hi B5 Ambiance Over Temperature B7 Auxiliary Power Fail Remark 1 Currently TempStatus is not supported by UPS 36 Parallel Master ID Description Address Value Unit Parallel Master ID 0x0482 0 99 Available Event Log Description Address Value Unit UPS Event Log 0x0483 0 500 Event Log Report Format 0x0484 0 1 Event Reporting Method 0x0485 0 1 Eve
19. ture shutdown 40 B3 DC bus over voltage warning B4 DC bus over voltage shutdown B5 DC bus under voltage warning B6 DC bus under voltage shutdown B7 PFC circuit general fault B8 Fan failure B9 TBD B10 TBD B11 TBD B12 Inner communication failure B13 TBD B14 TBD B15 Not calibrated used to indicate whether the power module has been calibrated 41 Power Module Inverter Status Description Address Value Unit Power Module ID Status 0 0x049E Lo ID 1 4 Hi Status 0 Inverter Status 1 2 0x049F Lo Status 1 Hi Status 2 Power Module ID Status 0 0x04A0 Inverter Status 1 2 0x04A1 Power Module ID Status 0 0x04A2 Inverter Status 1 2 0x04A3 Power Module ID Status 0 0x04A4 Inverter Status 1 2 0x04A5 Reserved 0x04A6 Reserved 0x04A7 Reserved 0x04A8 Reserved 0x04A9 Inverter Status BO Inverter fuse open B1 Inverter over temperature warning B2 Inverter over temperature shutdown 42 etc B3 Fan failure B4 B5 Inverter short circuit B6 Inverter STS failure B7 Inverter voltage abnormal B8 Inverter circuit general fault B9 DC bus over voltage shutdown B10 Inverter overload B11 B12 Inner communication loss includes the comm to system or other modules B13 EPO shutdown B14 Inverter parallel communication loss B15 Inverter parallel failure which may due to any of ID or rating setting conflict B16 TBD B17 TBD B18
20. x0502 52 Model Description Address Value Unit Model Byte 0 1 0x0503 Lo Byte0 Hi Byte 1 Model Byte 2 3 0x0504 Lo Byte2 Hi Byte 3 Model Byte 4 5 0x0505 Lo Byte4 Hi Byte 5 Model Byte 6 7 0x0506 Lo Byte6 Hi Byte 7 Model Byte 8 9 0x0507 Lo Byte8 Hi Byte 9 Model Byte 10 11 0x0508 Lo Byte10 Hi Byte 11 Model Byte 12 13 0x0509 Lo Byte12 Hi Byte 13 Model Byte 14 15 0x050A Lo Byte14 Hi Byte 15 Reserved 0x050B Reserved 0x050C Reserved 0x050D 53 Firmware Version Description Address Value Unit Firmware Version Byte 0 1 0x050E Lo Byte0 Hi Byte 1 Firmware Version Byte 2 3 0x050F Lo Byte2 Hi Byte 3 Firmware Version Byte 4 5 0x0510 Lo Byte4 Hi Byte 5 Firmware Version Byte 6 7 0x0511 Lo Byte6 Hi Byte 7 Firmware Version Byte 8 9 0x0512 Lo Byte8 Hi Byte 9 Firmware Version Byte 10 11 0x0513 Lo Byte10 Hi Byte 11 Firmware Version Byte 12 13 0x0514 Lo Byte12 Hi Byte 13 Firmware Version Byte 14 15 0x0515 Lo Byte14 Hi Byte 15 Reserved 0x0516 Reserved 0x0517 Reserved 0x0518 54 CPU Description Address Value Unit CPU Byte 0 1 0x0519 Lo Byte0 Hi Byte 1 CPU Byte 2 3 0x051A Lo Byte2 Hi Byte 3 Reserved 0x051B UPS Connection Status Description Address Value Unit UPS Connection Status 0x051C 0 Disconnection

Download Pdf Manuals

image

Related Search

Manual manual manualslib manual car manuale digitale manually meaning manual timesheet manual transmission manual wheelchair manual arts high school manually update your device drivers windows manual definition manual for courts martial manual labor manual lawn mower manual muscle testing manually register devices with autopilot manual muscle testing grades manual transfer switch manualidades manual blood pressure cuff manual handling manual transmission cars for sale manual digital manual pdf manual autopilot enrollment