1. 44 0 1794 521400 e mail sales bpc ups com www bpc ups com Certificate No 14135 3 Registration No 5325265 PowerPrem 5000 Spec Sheet PAGE 4 OF 8 BeC The British Power Conversion Company 1 5 3 Auto battery test function In normal mode of UPS the UPS will test its battery connection and status every 20 minutes when battery is NG open circuit or not well connected the UPS will emit low battery alarm at the same time its LCD will show battery NG mark The battery NG mark will not disappear until the battery is well connected or replaced by good ones 1 6 COMMUNICATION INTERFACE 1 6 1 1 6 2 The UPS provides both computer interfaces smart software RS 232 and dry contact DB 9 by using different software and cable the UPS shows different monitoring function The definition and setup for RS 232 is as following Baud Rate 2400 dps Data Length 8 bits Stop Bit bit Parity None 5432 1 9876 Pin 6 RS 232 data Tx out Pin 7 Common of Pin 6 and Pin 9 Pin 9 RS 232 data Rx In The definition and setup for DB9 optional is as following Pin 2 AC Power Failure Pin 4 Common GND of Pin 2 amp Pin 5 Pin 5 UPS Battery Low Pin 6 Turn off UPS Pin 7 GND of Pin6 The interface with computer is diagramed as above for your reference Use Pin 4 as the common of Pin 2 and Pin 5 Pin 2 and Pin 4 will become close loop from open when the utility fails Pin 5 and Pin 4 will beco
2. that the output is in the normal mode This symbol will show up in the following situations Timer is enabled 1 A turn on turn off schedule has been set using the monitoring software Refer to User s Manual 5 6 and the Readme file or Help function of the monitoring software 2 The Green Mode is enabled and the loading is under 25W approximately The UPS will turn itself off automatically in 30 seconds Refer to 4 2 5 of User s Manual Thermal alarm The temperature inside the UPS is over 55 C If the user does not reduce the load the temperature will continue to rise and the UPS will shut down automatically at 60 C ahs Fan 1s ON This symbol is used only on long back up L models The symbol will display whenever the cooling fan is running 10 LQ Alarm off The audible alarm has been silenced To reset the alarm in Back up J mode push the control button not available during low battery level 1S0 9001 CERTIFIED ORGANIZATION BPC EMEA Limited BPC House Romsey Industrial Estate Greatbridge Road ey Romsey Hampshire SO51 OHR UK GRD ukas Telephone 44 0 1794 521200 Fax 44 0 1794 521400 e mail sales bpc ups com OA www bpc ups com Certificate No 14135 3 Registration No 5325265 PowerPrem 5000 Spec Sheet PAGE 3 OF 8 The British Power Conversion Company The UPS has failed and must be repaired Contact a qualified service person 1 In normal operation this symbol indica
3. INT 2 21 of rated voltage TOO LOW VOLTAGE PROTECTION 32 of rated voltage 2 1 1 Inrush current initial start up Tested at 220 VAC RMS 25 deg C the UPS should not sink any inrush current from AC input when initial start up 2 1 2 Input line transient immunity No component failures or malfunction should be found when the UPS is subjected to an input line transient 2 1 3 Surge Protection Both the AC input and AC output should have surge protection with energy rating totally 800 joules By checking at the AC output of UPS the surge protection should have zero clamping response time 2 2 Output PowerPrem 5000 Power VA max 5000VA 1509001 CERTIFIED ORGANITATION BPC EMEA Limited BPC House Romsey Industrial Estate Greatbridge Road v4 Romsey Hampshire SO51 OHR UK GRD uras Telephone 44 0 1794 521200 Fax 44 0 1794 521400 e mail sales bpc ups com www bpc ups com See Ter Rees Registration No 5325265 PowerPrem 5000 Spec Sheet PAGE 6 OF 8 BeC The British Power Conversion Company Power Watts max 3500W Output Nominal Voltage 220 230 240VAC by DIP switch setting Transfer Time 2 5 ms typical 3 5ms maximum Line Mode Voltage Nom Range no load 220 230 240VAC 5 Battery Mode Voltage Regulation 920 230 240VAC 3 Transient Response 0 100 0 15 max Battery mode with R type load 5Oms to stable Peak Voltage 390V peak Transient Recovery Zero Ims Output Fre
4. The British Power Conversion Company PowerPrem Series Line Interactive Sine Wave UPS This specification covers the requirements amp quality assurance provisions for AC line powered uninterruptible power supplies UPS The UPS shall utilize line interactive UPS topology in which the inverter works in reverse charging the batteries during normal operation providing greater efficiency and reliability The UPS consists of an autotransformer battery charger control circuit battery Bi lateral inverter transfer switches and all associated controls monitoring and major protection devices The UPS automatically maintains continuity of electrical power within tolerances and time frames specified in this product specification 1 2 Modes of Operation In normal operation incoming AC power is fed directly to the output or via an autotransformer In this mode power is also derived from the utility for the battery charger The battery can be charged from the utility irrespective of whether the UPS is ON or OFF In the event of utility abnormalities sags and swells the AC output power shall be corrected by means of boost sag correction or buck swell correction compensation taps Operation of the compensation taps shall be seamless and automatically maintain the proper output voltage for the connected critical equipment The compensation taps shall be designed for indefinite operation at full rated load to their voltage limits w
5. ithout discharging the battery In the event of a utility outage the output is transferred from the utility power to the inverter which supports the load until the battery is discharged or the utility returns whichever occurs first 1 3 Built in SNMP web agent slot 150 S001 CERTIO CROANIATION BPC EMEA Limited BPC House Romsey Industrial Estate Greatbridge Road s vi Romsey Hampshire SO51 OHR UK GRD uras Telephone 44 0 1794 521200 Fax 44 0 1794 521400 e mail sales bpc ups com www bpc ups com Certificate No 14135 3 Registration No 5325265 PowerPrem 5000 Spec Sheet PAGE 1 OF 8 BeC The British Power Conversion Company With an optional SNMP agent card the UPS can be connected to a network as a node It can be accessed and managed from a worldwide network via a single SNMP management console located anywhere in the network Users can monitor their UPS with a web browser Users have secure access to their web server UPS information from anywhere on the Internet or Intranet 1 4 DIP switch setting 220V System 110V System 220V 60Hz 100V 50Hz 220V 50Hz 110V 60Hz 1 5 INDICATION AND CONTROL 1 5 1 LCD description 5 4 16 gt A 1 AF AC out V 13 AC in Hr to ON BATT Min toOFF 2 T temp l Hz 14 O A timer 2 m L L L E fiwon p xe 6 l 8 9 10 11 12 BPC EMEA Limited BPC House Romsey Industrial Estate Greatbridge Road v4 Romsey Ham
6. me close loop from open when the battery level is low If battery NG happen and is sensed by the UPS s auto battery test function Pin 5 and Pin 4 will also become close loop The UPS will shut down itself when the high level from RS 232 sustained for 3 seconds which is applied between Pin 6 and Pin 7 150 S001 CERTIO CROANIATION BPC EMEA Limited BPC House Romsey Industrial Estate Greatbridge Road v4 Romsey Hampshire SO51 OHR UK GRD uras Telephone 44 0 1794 521200 Fax 44 0 1794 521400 e mail sales bpc ups com www bpc ups com Certificate No 141353 Registration No 5325265 PowerPrem 5000 Spec Sheet PAGE 5 OF 8 d DCS N The British Power Conversion Company 2 0 Electrical Requirements 2 1 Input Input Range when it is with 5 Output Standard OVER HIGH VOLTAGE PROTECTION 22 of rated voltage HIGH VOLTAGE TRANSFER POINT 2 15 of rated voltage HIGH VOLTAGE TRANSFER POINT 1 5 of rated voltage AVR FUNCTION LOW VOLTAGE TRANSFER POINT 1 5 of rated voltage LOW VOLTAGE TRANSFER POINT 2 13 of rated voltage TOO LOW VOLTAGE PROTECTION 20 of rated voltage Input Range when it is with 8 Output Option upon request OVER HIGH VOLTAGE PROTECTION 36 of rated voltage HIGH VOLTAGE TRANSFER POINT 2 25 of rated voltage HIGH VOLTAGE TRANSFER POINT 1 8 of rated voltage AVR FUNCTION LOW VOLTAGE TRANSFER POINT 1 8 of rated voltage LOW VOLTAGE TRANSFER PO
7. pshire SO51 OHR UK GRD uras Telephone 44 0 1794 521200 Fax 44 0 1794 521400 e mail sales bpc ups com www bpc ups com Registration No 5325265 Certificate No 14135 3 PowerPrem 5000 Spec Sheet PAGE 2 OF 8 df aT The British Power Conversion Company No Symbol The loading exceeds the rating of UPS Ld 2 Load level The higher the loading the more bars will illuminate CL C CJ UPS is loaded When Green Mode is enabled this symbol will display if the loading is over 30W approximately and disappears when it is under 25W approximately Refer to User s Manual 4 2 5 If Green Mode is disabled the symbol will always display Normal or Inverter mode 1 The sine wave symbol will display steadily without battery symbol when UPS is in the normal mode 2 The sine wave symbol and battery symbol will blink when the UPS is in back up inverter mode 3 The sine wave symbol will display steadily with blinking battery symbol when the UPS is in testing mode 5 Buck mode The AVR Auto Voltage Regulator is reducing the output voltage of a a the UPS when the input voltage is too high and the sine wave symbol as mentioned in item 4 will also display steadily to indicate that the output is in the normal mode _ Boost mode The AVR is increasing the output voltage of the UPS when the input voltage is too low and the sine wave symbol as mentioned in item 4 will display to indicate
8. quency battery mode 50 60Hz 0 1Hz Output Voltage Distortion EEE R Load lt 4 before pre alarm lt 8 after pre alarm SMPS Load lt 7 before pre alarm lt 15 after pre alarm Et ecieney o Boost Buck Mode Short Circuit Protection J ooo 1S0 S001 CERTIO CROANIATION BPC EMEA Limited BPC House Romsey Industrial Estate Greatbridge Road s v4 Romsey Hampshire SO51 OHR UK GRD uras Telephone 44 0 1794 521200 Fax 44 0 1794 521400 e mail sales bpc ups com www bpc ups com RE VNS Registration No 5325265 PowerPrem 5000 Spec Sheet PAGE 7 OF 8 df aC The British Power Conversion Company 2 2 Battery all parameters are defined at 25 Deg C ee PowerPrem 5000 Type Rating Acceptable Manufacturers BPC Yuasa CSB Life Standard life 3 5 years Back up Time at full load gt 6 minutes typical Protection Battery Protection Low Batt Alarm Level 63 6V 3 Low Batt Shut Down Level 57 6V 3 RECHARGER VOLTAGE 82V RECHARGER METHOD ON OFF Control with Constant Voltage and Current Limiting RECHARGER CURRENT 10A maximum RECHARGER RECHARGER TIME 2 hrs to 90 6hrs to 100 Charging Voltage and Current Limited by control IC Over charge PROTECTION protected by CPU PowerPrem 5000 180mm W x 500mm D x 435mm H 435mm W x 500mm D x 180mm H Unit Weight 80Kgs inc Batteries 150 S001 CERTIO CROANIATION BPC EMEA Limited BPC House Romsey Industrial Estate Greatbridge Road v4 Romsey Hamp
9. shire SO51 OHR UK GRD uras Telephone 44 0 1794 521200 Fax 44 0 1794 521400 e mail sales bpc ups com www bpc ups com RE VNS Registration No 5325265 PowerPrem 5000 Spec Sheet PAGE 8 OF 8
10. tes a charged battery 2 When the battery charge level is low the word LOW will be added to the symbol 1 The higher the battery voltage the more bars will illuminate 2 When the UPS is charging the battery the battery symbol and the level indicator will blink together 15 Mode Value Acon Wv acin V AC out Hz BATT V meme fe TIMER Min to off The UPS will turn off when the displayed value reaches zero For example if the timer shows 0 5 Min to off the UPS will shut down in 30 seconds Hr to on The UPS will turn on when the displayed value reaches zero For example if the timer shows 48 0 Hr to on the UPS will turn on in 2 Min to off The estimated remaining run time in Back up mode The accuracy of the value is influenced by the loading type ambient temperature and battery condition old or new 1 5 2 Auto self test Function In normal mode of UPS turn on your computer and push the button on the front panel for self test The UPS will simulate a power outage and transfer your load to the UPS s battery If low battery warning sounds during the test it means that the battery set is weak and requires extended recharge If battery NG warning sounds it means that the battery set is damaged and requires replacement 1509001 CERTIFIED ORGANITATION BPC EMEA Limited BPC House Romsey Industrial Estate Greatbridge Road Romsey Hampshire SO51 OHR UK GRD UKAS Telephone 44 0 1794 521200 Fax