1. LEE 15 CONFIGURING THE PANEL orate t b rU ss 18 ENGINEERING MENU iocos ttp ween spin b mee breiter eset iue 18 18 RELAYSIMENU Sa 20 RESET MENU S te cr Pete ert x II sere area eer 20 RESEM LOGS near n Pe A 20 RESELTIMINGS 20 20 SODNDER2 21 VERSION M em 21 Approved DocumentNo GLT 212 7 1 2 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual CHANGE PASSWORD LIL ti seep dates ete ede Ge dte ui re 21 LANGUAGE 21 PANEL OPERATION l w eee 22 NORMAL OPERATION lassie ses devas Sibel bodied Wika aden dad Weve di whey 22 2 22 WHAT O DO IN THE EVENT OF A FIRE eiie aee 22 RESETTING FROM AN ALARM 22 23 FIRST STAGE 22
2. 29 EXTINGUISHING CONTROL S ennt en nnns 29 Approved Document No GLT 212 731 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual INTRODUCTION THIS EXTINGUISING CONTROL PANEL IS CLASS 1 EQUIPMENT AND MUST BE EARTHED This equipment must be installed and maintained by a qualified and technically competent person HANDLING THE PCBS If the PCBS are to be removed to ease fitting the enclosure and cables care must be taken to avoid damage by static The best method is to wear an earth strap but touching any earth point e g building plumbing will help to discharge any static Hold PCBs by their sides avoiding contact with any components Always handle PCBs by their sides and avoid touching the legs of any components Keep the PCBs away from damp and or dirty areas e g in a small cardboard box USING THIS MANUAL This manual explains in a step by step manner the procedure for the installation of the EXPro combined fire and extinguishing control panel For full operational and maintenance information please refer to the document GLT MAN USER MANUAL MAINTENANCE GUIDE amp LOG BOOK It also contains a system set up table and installation certificate that must be completed by the commissioning engineer prior to system handover ABOUT THE EXPRO The Premier EXPRO is a 2 zone 1 area extinguishing panel It has 2 zones dedicated to the extinguishing section These are k
3. 23 SECOND STAGE ALARM ot upas e Gees 23 ABORT A SECOND STAGE AEARM rrr ea eet 23 MANUAL 24 RESET cte tee I eee De eu e E D o 24 FAULTS ento er te tete petit 24 BATTERY CALCU EAT IO 25 DEVICE CURRENT 5 25 EXPRO PANEL IN VARIOUS STATES eere ret ttr or ee i tte o re e a oret 25 EXPANSION BOARDS 7 1 eene nota ode dude aenea ee i to eaae eee qo xao enne 25 EXTERNAL DEVICES ioi ua erprobt i ease das ede vereor eoo eee oa usss 25 DETERMINING BATTERY SIZE uuu 5 cr ete rer e eene aene pun eo eee ae ve gap pube a aevo Nes ea pee uoa veo gun eu 25 EXAMPLE BATTERY SIZE CALCULATION ses cis ise reri eed Aaa alaq u a n ne Re ere RR uru s 26 CONNECTIONS EE 27 TERMINAL DESCRIPTION um hen ea Pea ve ae 27 PANEL SPECIFICATION reiten hetero re thee der bor ua a u isa i iN a iiiw ai ua 28 ENCLOSURE SPECIFICATION uns ku ota e a none oap 28 ELECTRICAL SPECIFICATIQNS 2222 eie reet an 28 5 irri edet ore dette oe reo ead oa deed 28 DESIGN SPECIFIGCAT IO NS oerte repetere eer EO epe eere ypas 29 FIRE ALARM CONTROL 5
4. BAT SPARE FUSES Figure 10 Bottom connections TERMINAL DESCRIPTION Connection Label Description 1 Zone 1 First Crossed Zone 2 Zone 2 Second Crossed Zone 3 Gas Fired Gas Fired Input from bottle 4 Manual Release Manual Release Input to manual release MCP SWITCH 5 Auto Manual Automatic Manual Mode Input 6 Abort Abort Input 7 S1A First Stage Sounder Circuit A 8 S1B First Stage Sounder Circuit B 9 52 Second Stage Sounder Circuit 10 Bottle Output To Bottle Solenoid 11 Bottle Monitoring Low Pressure Input 12 1 Stage Relay First Stage Relay Contacts 13 27 Stage Relay Second Stage Relay Contacts 14 Gas Fired Relay Gas Released Confirmation Relay 15 EXT Relay External Equipment Relay 16 Fault Relay Fault Relay Normally Energised 17 REPBA RS485 Connection 18 AUX 24VDC Auxiliary 24VDC output 200mA 19 BAT Battery 20 24VDC IN 24V DC Main Power Approved Document No GLT 212 7 1 Page 27 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual PANEL SPECIFICATION ENCLOSURE SPECIFICATION Description Value Enclosure Size Lx W x D 310 x 369 x 113 Top Cable Entries 20 ELECTRICAL SPECIFICATIONS Electrical Description Value Mains Voltage 230 115 VAC 10 15 50 60Hz Battery Voltage 2 x 12V SLA 27 6VDC 20 C 3 4Ah 7Ah Power Supply Non Integral Switch Mode DC output Vma
5. 2013 EXPro Installation Manual The EXPRO has the following LED indicators General indication LED Colour Function Meaning Power Green Power healthy Common Fire Red Indicates when the panel is in an alarm condition Common Fault Yellow Indicates when the panel fault condition General Disablement Yellow Indicates when an Input or Output has been disabled General Test Yellow Indicates when a zone is in test System Fault Yellow Indicates when there is a processor fault Crossed Zone LED Colour Function Meaning Fire zone 1 Red Indicates when zone 1 is in alarm Fire zone 2 Red Indicates when zone 1 is in alarm FLT Test Disable Yellow Indicates when a zone has a fault or in test or disable mode Alarm indications LED Colour Function Meaning Active 1 Stage Alarm Red Indicates when zone 1 or zone 2 isin an alarm condition Active 274 Stage Alarm Red Indicates when zone 1 or zone 2 isin an alarm condition 1 Stage FLT TEST DIABLED Yellow Indicates 1 stage status when lit 2 Stage FLT TEST DISABLED Yellow Indicates 2nd stage status when lit Release Status Colour Function Meaning Manual Mode Yellow Indicates manual release mode Auto Mode Green Indicates Automatic mode Abort Yellow Indicates the release has been aborted Released Red Indicates the gas has been released Activated Red Indicates when both 1 and 2
6. 72 hr Quiescent current in amps of control panel in fault condition because of mains failure Tgor Minimum time in hours required for the bottle output Isor Total current drawn by equipment connected to the bottle output Approved Document No GLT 212 7 1 Issue 1 0 Author MF Date 19 08 2013 Page 25 EXPro Installation Manual EXAMPLE BATTERY SIZE CALCULATION Consider a system consisting of e 4x 1 stage alarm Maxitone sounders e 4x2 stage alarm Maxitone sounders e system requires a 48hour standby time first stage alarm sounds for a minimum of 30 minutes e The bottle output activates 1 for 5 minutes Ispy 57mA 0 057 Tspy 48h Premier Alm 8x Maxitone Sounder 1 detector alarm 110mA 8 x 25mA 40mA 0 110A 0 2A 0 04A 0 35A 0 5h Igor 1 0 084h 5 minutes Battery size 1 25 x x To x Igor x 1 25 0 057 48 0 35 x 0 5 0 084 x 1 1 25 x 2 736 0 175 0 042 1 25 x 2 953 3 69Ah 7 2Ah batteries would be suitable for this installation Approved Document No GLT 212 7 1 Page 26 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual CONNECTIONS The following figures show the connections for the EXPro 52 BOTRE BOTRE ST 20 OUTPUT MONITORING RELAY REAY REAY REAY Figure 9 Top connections BATTERY FUSE 2A
7. FROM AN ALARM CONDITION After the relevant action has been taken the Premier EXPro fire alarm panel can be reset by the following 1 Gain user access to the panel by entering the password default 2222 2 Press Start Stop 1 Stage Sounder button this will silence the external sounders 3 Press Silence Buzzer button This will silence the panel s internal buzzer 4 Press the Reset button This will return the panel to its normal condition If the panel goes straight back into alarm then the cause of the alarm has not been cleared This could be a detector still exposed to smoke or a call point still in the active position Investigate for a call point or detector that still has its RED ALARM LED on Reset the call point or clear the smoke If the problem persists contact an engineer Approved Document No GLT 212 7 1 Page 22 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual MANUAL EVACUATION The first stage sounders can be started by activating the controls and pressing the START STOP 1 Stage Sounder Button The first stage relay is NOT operated by this action The common fire amp first stage sounder active LEDs will light FIRST STAGE ALARM On detection of a FIRE in either Zone 1 or Zone 2 the zone fire LED will be illuminated and the internal buzzer will be on The first stage LED and first stage sounder will be on The first stage relay output will be active The first stage repeat output will also be
8. In most instances the Standard sounder sequence should be used the Brazilian option is provided to comply with local Brazilian regulations Standard 1 stage 1 stage sounders on 27 Stage 1 stage sounders 274 stage sounders pulsed Release condition 1 and 2 stage sounders on Brazilian 1 stage alarm 1 stage sounders on 27 stage alarm 1 t and 2 9 stage sounders on Release condition 1 and 2 stage sounders on VERSION This menu display s the current software in the panel CHANGE PASSWORD In this menu the engineer is able to change the current passwords User or Engineer To change the passwords 1 Access Level 2 By pressing option 1 you will be asked to enter the new password and then press enter Enter the new password again and press enter Access level 2 has now been changed 2 Access Level 3 Follow the same steps as for access level 1 LANGUAGE This option allows the current language to be changed Please contact the manufacture for available options Approved Document No GLT 212 7 1 Page 21 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual PANEL OPERATION NORMAL OPERATION With the controls inactive under normal conditions the system will be silent and the green POWER LED illuminated The LCD will display SYSTEM NORMAL The system may either be in Automatic or Manual mode of operation This will be evident by the illumination of either the Automatic or Manu
9. Prevents the panel from responding to an alarm in zone 1 Zone 2 Prevents the panel from responding to an alarm in zone 2 Gas Fired input Prevents the panel from responding to the gas fired signal Manual release Prevents the panel from responding to a manual release Approved Document No GLT 212 7 1 Page 15 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual Auto Manual Prevents the external switching between auto and manual mode Switching between auto and manual mode can still be done from the panel Abort Input Disables the Abort input The panel will not enter the alarm condition if the abort input is disabled Low Pressure Input Prevents the panel from responding to a low pressure signal Sounder 1A Disables sounder 1A Sounder 1B Disables sounder 1B Sounder 2 Disables the second stage sounder The panel will not enter the alarm condition if the second stage sounder is disabled Bottle Output Disables the bottle output The panel will not enter the External Fan Disables the output to the external fan When an item is disabled the GENERAL DISABLEMENT LED will light along with the corresponding FLT TEST DISABLED LED Press CANCEL to exit out of the disablement menu the item will remain disabled until it is manually re enabled Test Allows the user engineer to put an input or output into test mode TEST MENU Low Pressure input Use the NEXT and PREV button to cyc
10. stage zones are in alarm Pre Activated Red Indicates when there is a first stage alarm Manual Release Red Indicates when the Manual release switch has been activated Flooding Zone FLT Yellow Indicates when there is a fault state in the flooding zone Gas Release Counter Colour Function Meaning More Data Yellow Indicates when there is more than one message to be displayed on the LCD Approved Document No GLT 212 7 1 Page 7 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual CONTROLS Label Use Start 1 Stage Sounders Used to start the 1 stage sounders Stop 1 Stage Sounders Used to silence the 1 stage sounders Silence Buzzer Used to silence the internal buzzer in a fault or alarm condition Reset Used to reset the fire detection zone Reset CIE Used to reset the control panel LED Test Used to test all panel LED s Note that the controls can only be used after the code has been entered and the CONTROLS ENABLED LED is ON Approved Document No GLT 212 7 1 Page 8 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual MOUNTING THE FIRE ALARM PANEL The Premier EXPRO comes with cable entry point on the top edge of the control panel It is strongly recommend that the PCB is removed before the entry holes are drilled With the PCB removed it also makes it easier while fixing the back box to the wall PLANNING CABLE ENTRY Fig 2 below shows the locatio
11. EXPro Installation Manual CROSSED SOUNDER ZONES INDICATION GENERAL INDICATIONS INSTALLATION MANUAL Approved Document No GLT 212 7 1 Page 1 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual Contents INTRODUCTION ua an eee a ta ua aska ste 4 HANDLUNG THE PCBS 4 USING THIS MANUAL 4 ABOUT THE EXP RO LL IDE M LE anka 4 INDICATIONS amp CONTROLS 6 I DICATIONS LLL 6 CONTRO M D 8 MOUNTING THE FIRE ALARM 9 PLANNING CABLE 4 T RT T 9 FIXING THE ENCLOSURE TO THE WALIL I tentent tenente tenente tenen 9 ELECTRICAL CONNECTIONS UM E DICE I DUE ML DI 10 CONNECTING TO THE MAINS etre tein 10 CONNECTING THE BATTERIES temas ttt abe dese DU DU Dd 11 DETECTORS AND SOUNDER E E EMI EE 12 WIRING THE DETECTORS 2 2 ponte iere nn 12 WIRING THE SOUNDERS eo ab cdt ge 12 OTHER CONNECTIONS uttter amet oed LUE LEE 13 FIELD MONITORING INPUTS 13 1 STAGE amp 2 STAGE FIRE RELAYS 13 FAULT RELAY 55 pM DE EI MM IM I REI 13 BOTTLE 14 EXTERNAL EQUIPMENT 14 PANEL
12. active To silence the sounder activate the controls and press S TART STOP 1 Stage Sounder Button The panel s internal tone and fire LEDs will remain active until the cause of the alarm has been removed and the panel has been reset A first stage alarm can be silenced amp reset when the panel is in automatic or manual mode SECOND STAGE ALARM As soon as a FIRE is detected in the second Zone the second stage alarm is initiated The second stage sounder will be pulsed on for 1 second then off for 1 second This will be repeated as the timer counts down The two zone alarm LEDs will be illuminated as well as first stage alarm second stage alarm and Activated LEDs The second stage cannot be silenced and after a delay period user programmable the extinguishing output will be initiated releasing the extinguishing agent and the second stage sounder will now be on constantly This will be followed by the GAS FIRED indication indicating that the extinguishing agent has been released Once the second stage alarm has been initiated it is advisable to evacuate and Seal the protected area prior to the release of the extinguishing agent Operation of the Manual Release call point will initiate the second stage alarm Lift the flap and push the switch up to activate A second stage alarm can only be silenced amp reset when the panel is in manual mode ABORT A SECOND STAGE ALARM If the abort input is used the pan
13. al LED In Manual Mode the bottle output will not beactivated automatically It must be started manually by pressing a manual release call point FIRE ALARM CONDITION The Premier EXPro signals an alarm by the following Turn on the General Fire LED Turn on the Zonal Fire Indicator Turn on internal buzzer Start any sounders connected to the panel s sounder circuits Activate the First Stage fire relay Note that the first stage repeater output will not activate This only operates on an alarm from one of the crossed zones WHAT TO DO IN THE EVENT OF A FIRE 1 Follow the building evacuation procedure and check that everyone has left the building safely The building fire officer or suitably trained responsible person should CAREFULLY enter the building and locate the area of the alarm from the fire alarm panel Investigate to determine the cause of the alarm Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM LED on If a small fire is found a suitably trained person could tackle this with a suitable fire extinguisher If a larger fire is found leave the building immediately and contact the fire brigade If no fire is found make a note of the detector that signalled fire and look for anything nearby that could be the cause of the activation eg cooking or use of a hot air gun etc Record findings in the fire alarm log book RESETTING
14. ating Equipment The Extinguishing control section has been designed in accordance with BSEN12094 1 2003 Fixed Fire fighting Systems Components for Gas Extinguishing Systems Requirements and Test Methods for Electrical Automatic Control amp Delay Devices The Power Supply Section has been designed in accordance with EN54 4 1998 1 A2 Fire Detection amp Fire Alarm Systems Power Supply Equipment FIRE ALARM CONTROL SECTION As well as meeting the requirements of EN54 2 1998 A1 A2 the Premier EXPro also has the following options with requirements Clause 7 8 Output to fire alarm devices Option with requirements Clause 10 Test Condition Option with requirements EXTINGUISHING CONTROL SECTION As well as meeting the requirements of BSEN12094 1 2003 the Premier EX8 also has the following options with requirements Clause 4 17 Delay of extinguishing signal Option with requirements Clause 4 18 Signal representing the flow of extinguishing agent Option with requirements Clause 4 21 Control of flooding time Option with requirements Clause 4 23 Manual Only Mode Option with requirements Clause 4 26 Triggering of equipment outside the system Option with requirements Clause 4 27 Emergency Abort Device Option with requirements Clause 4 30 Activation of alarm devices with different signals Option with requirements Approved Document No GLT 212 7 1 Page 29 Issue 1 0 Author MF Date 19 08 2013 EXPr
15. cess to live components inside this fire alarm enclosure Only authorised personnel should have access to the inside of the control panel Approved Document No GLT 212 7 1 Page 5 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual INDICATIONS amp CONTROLS INDICATIONS Here is the fascia for the Premier EXPRO panel GENERAL CROSSED SOUNDER RELEASE STATUS INDICATIONS ZONES INDICATION 1ST STAGE ZONE 1 SOUNDER RELEASED FIRE FLT ACTIVE T DISABLED DISABLED ACTIVATED 20 STAGE ZONE 2 SOUNDER GENERAL SYSTEM FIRE FLT ACTIVE FLT TEST FAULT TEST DISABLED MANUAL DISABLED L uras PRE ACTIVATED FLOODING RT OSABLED GAS RELEASE COUNTER CONTROLS SILENCE BUZZER RESET RESET LED CIE ECO TEST Figure 1 EXPro fascia layout Each function has its own indication LED There are Alarm Active Fault Test amp Disablement LEDs for most panel inputs and outputs For most functions more than one LED will light e g zone 1 fire and common fire The second stage sounder is pulsed during the activated condition and its sounder active LED will also pulse in time with the actual sounder output The second stage sounder and its associated LED will switch to constantly on The panel also has a 20 x 4 LCD display for easy setup of the engineering functions It also has event log which will store up to 100 events Approved Document No GLT 212 7 1 Page 6 Issue 1 0 Author MF Date 19 08
16. ed by an incorrect type Dispose of batteries according to the instructions supplied or local waste electrical equipment recycling regulations Approved Document No GLT 212 7 1 Page 11 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual DETECTORS AND SOUNDERS The detector and sounders must be connected using fire resisting 1 5mm 2 screen cable screen of each detector and sounder circuit must be connected to one of the terminations of the earth bar which is bolted to the back box above the terminations PCB WIRING THE DETECTORS The detection zone on the Premier EXPRO Co incidence Double Knock zones which use a 4 7 end of line resistor Up to two detectors can be connected to each zone Call points can NOT be connected to these zones Figure 5 Wiring the detectors WIRING THE SOUNDERS The Premier EXPRO has 2 first stage fire sounder circuits each rated at 150mA Each sounder circuit must be fitted with 18KO end of line resistor The EXPRO also has 1 x second stage sounder circuit rated at 250mA This also uses 18 end of line resistor This second stage sounder circuit is designed for an alarm device that gives a constant sound pattern either sounder or bell because it uses on off sound patterns to indicate different gas release conditions 18KQ Figure 6 Wiring sounders Approved Document No GLT 212 7 1 Page 12 Issue 1 0 Author MF Date 19 08 2013 EXPro Installa
17. el will abort the gas release and the panel will need to be reset Note that after the pre release timer has finished and the bottle output has activated the abort input will have no effect Approved Document No GLT 212 7 1 Page 23 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual MANUAL MODE In this mode operation Zone Fire and Fault alarms are still in operation and first amp second stage sounders will operate but the bottle output to the extinguishing agent will not operate RESET To reset panel from a first stage alarm condition activate the controls and press START STOP SOUNDERS followed by SILENCE BUZZER then RESET If the panel enters the second stage alarm while in automatic mode the panel cannot be reset until the bottle output has operated and the reset inhibit timer has ended The panel can NOT be reset from a fault condition All faults are non latching so when a fault clears from the panel it will be automatically cleared from the display In the event of an alarm in the peripheral fire zones amp crossed extinguishing zones simultaneously the reset button can be used to reset the peripheral zones but won t have an effect on the extinguishing zones until the reset inhibit timer has ended FAULTS When a fault is detected the relevant LED will illuminate and the buzzer will sound The LCD will display details of the fault s and show each detected fault in turn Enable the controls and pr
18. enoid Valve E Bottle Figure 8 Wiring diagram for the solenoid valve Bottle output EXTERNAL EQUIPMENT RELAY The Premier EXPRO has one volt free change over relay that operates AFTER the reset inhibit counter has finished It remains active for 3 minutes or until the reset button is pressed It is rated at lamp SELV This would normally be used for a ventilation fan Approved Document No GLT 212 7 1 Page 14 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual PANEL MENUS To access the panel requires the user code to be entered the default code is 2222 Once the Controls Active LED is on you will now be able to start and stop the first stage sounders reset silence the inter buzzer and access the relays configuration menu Press enter and you will then see a list of menu options ur sa Zone Logs Disable Test Engineer Relays Change Time Zone This menu allows the user engineer to view the following information 7one Viewing Zone 1 Normal Voltage Lvl 17 3v Logs The Log can store up to 100 events 12 00 05 02 Man Release Active 01 95 Disable Allows the user engineer to disable each of the inputs and outputs on the panel DISABLEMENT MENU Low Pressure input ENABLED Use the NEXT and PREV button to cycle through items that can be disabled pressing OK toggles the item between the enabled disabled states Zone 1
19. er EXT Fan Delay Timer e Fan Timer The Countdown Timer is the delay between the receipt of a second stage alarm and the gas being released It can be set from 0 to 60 seconds 1 second increments To setup the countdown time enter the engineers menu by selecting option 5 Then select option 3 and press next to view the countdown time now press enter to edit the time Using the keypad enter the time required and press enter to save the new time The default setting is 30 seconds Change Timings Countdown Time 00 45 Press ENT to Change The Release Timer determines how long the bottle output remains active The bottle output will then shut off because it is no longer needed This will prevent unnecessary power drain It can be set from 10 to 300 seconds in 1 second increments To set the release time enter engineers menu option 5 Then as for the countdown timer select option 3 timers and press the next key until the Release timer option is shown Press enter to set the release time using the keypad and then press enter to save the new time Change Timings Release Time 00 30 Press ENT to Change Approved Document No GLT 212 7 1 Page 18 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual The release timer can be set such that it does not automatically timeout by changing the release time to 99 99 the display will change to 100 39 An unlimited release must be manually reset by using the external ab
20. ess the Silence Buzzer button to silence the panel Press the NEXT and PREV buttons to manually cycle through the list of faults the display will show the number of faults in the lower right corner DEVICE FAULT BOTTLE OUTPUT O C 01 03 Approved Document No GLT 212 7 1 Page 24 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual BATTERY CALCULATION DEVICE CURRENT CONSUMPTION EXPRO PANEL IN VARIOUS STATES State Current Consumption Mains fail Buzzer silenced 52mA Mains fail Buzzer active 57mA Mains failed 1 Stage Alarm 110mA Mains failed 2 Stage Alarm 150mA Bottle released Gas fired 167mA EXPANSION BOARDS Option Current Consumption For each activated relay 12mA 3 relay expansion board Standard 40mA Max 8 relay expansion board Optional 100mA Max EXTERNAL DEVICES Item Quiescent Alarm Optical 100uA 35mA Heat 50uA 35mA Maxitone Sounder 25 DETERMINING BATTERY SIZE To calculate the required battery backup capacity we use the equation Minimum battery Size 1 25 x X Tsay X 5 Teor X lpor Where Minimum time in hours required for the alarm gt hour is most common time Total alarm current in amps for all devices connected to the alarm circuits Tspy Standby time in hours for the system after mains failure normally 24 48 or
21. le through items that can be placed in test mode pressing OK puts the input into test mode When an input or output is in test mode the panel will indicate if it has been activated but is prevented from entering the normal sequence of events such as activating sounders or bottle output associated with that input Note Only one input output can be programmed in test mode at any one time Zone In Test Zone 1 Time Left 15 00 The panel will automatically exit from a test condition after 15 minutes The test condition can be manually exited from the test menu Approved Document No GLT 212 7 1 Page 16 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual Change Time Allows the user engineer to set the system clock SET UP TIME 12 00 Approved Document No GLT 212 7 1 Page 17 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual CONFIGURING THE PANEL The Premier EXPRO has been designed to be easy to set up Zones 1 amp 2 are configured as a double knock pair so do not need to be configured as such ENGINEERING MENU Accesses the engineering menu the engineering menu requires the engineers password to be entered default 1111 The CONTROLS ACTIVE LED will flash when access has been granted Engineer Menu 1 Reset 4 Version 2 Sounder 5 Chg Pass 3 Timers 6 Language TIMERS There are 5 timers to set e Countdown Timer e Release Timer e Reset Inhibit Tim
22. n of the fixing holes and cable entry points If any knockout is removed but subsequently not used then it should be covered up The 230Vac Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting the mains FIXING THE ENCLOSURE TO THE WALL 113 43 310 249 er r Figure 2 Plan View inside enclosure without the PCB and side view for surface installation Check the build amp condition of the wall to decide a suitable screw fixing The mounting holes are designed for No 8 rounded or countersunk woodscrews or similar Remove any debris from the enclosure Take care not to damage FACP during installation Secure the enclosure to the wall using the three mounting holes provided Approved Document No GLT 212 7 1 Page 9 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual ELECTRICAL CONNECTIONS CONNECTING TO THE MAINS The mains supply to the panel is fixed wiring using Fire resisting 2 core screen cable between 1mm and 2 5mm fed from an isolating double pole switch fused spur fused at IT SHOULD NOT BE CONNECTED THROUGH AN RCD This should be secure from unauthorised operation and be marked FIRE ALARM DO NOT SWITCH OFF There should be a Mains Disconnect Device EG switch or fuse point located near the fire alarm panel to all
23. nown as crossed or co incidence zones Both circuits will need to be triggered in order to activate the extinguishing circuit This kind of operation also referred to as double knock The Extinguishing section is designed to BS EN 12094 1 2003 The panel has an integral Manual Release switch fitted to the front of the panel The panel has monitored inputs for field connections such as manual release abort etc The panel has relay outputs for first amp second stage alarms fault gas fired and EXT for extract fan The panel has an add on board that provides relay outputs for Auto Manual and Abort The Premier EXPRO can be in any of the following conditions e Quiescent condition i e System Normal e Fault condition e Disabled condition e Test condition e Pre activated condition Approved Document No GLT 212 7 1 Page 4 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual The Premier EXPRO will enter the pre activated condition first stage alarm within 1 second of a detector on one of the crossed zones signalling an alarm e Activated condition The Premier EXPRO will enter the activated second stage alarm condition within 1 second of the second crossed zone signalling an alarm e Released condition The Premier EXPRO will enter the released condition bottle output activated within 1 second of establishing the activated condition or after the delay configured in the bottle output timer WARNING Ac
24. o Installation Manual The extinguishing control section also has the following ancillary functions not required by the Standard e Serial repeater output e Automatic mode relay e Manual only mode relay e Abort relay e First Stage Alarm Relay common with fire alarm section e Second stage alarm relay e Gas Fired Relay Approved Document No GLT 212 7 1 Page 30 Issue 1 0 Author MF Date 19 08 2013
25. open NO default and normally closed NC The on board relays that can be configured in this manner are 1 stage relay 274 stage relay Gas Fired relay and External Fan The relays for the external add on cards where available can also be configured Reset Auto mode Manual mode Gas fired Abort 15 stage 274 stage Extractor fan The panel must be powered to hold a relay output in the normally closed NC position the installation engineer must therefore consider if it is acceptable for an output to be activated switched to the normally open condition in the event of the panel experiencing a total power failure RESET MENU RESET LOGS This option allows the engineer to reset the event logs To do this select option 1 you will then see the following options 1 Yes 2 No 3 Factory Reset By pressing option 1 the event log will be deleted The following message will be displayed on the LCD ALL EVENTS DELETED If option 2 is selected then the display will revert back to the Engineers Menu RESET TIMINGS This option will reset all panel timers back to the factory defaults FACTORY RESET Pressing option 3 will reset the panel back to factory default and the following message will be displayed on the LCD BACK TO FACTORY Approved Document No GLT 212 7 1 Page 20 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual SOUNDER The EXPRO has two sounder sequences Standard and Brazilian
26. ort input or by resetting the panel Reset CIE after the reset inhibit timeout The Reset Inhibit Timer prevents the panel being reset immediately after a release This prevents a panel from being reset so that the system can be investigated by the responsible person to determine the cause of the release It can be set from 0 to 30 minutes To set the reset inhibit timer press enter option 5 Then as for the countdown timer select option 3 timers and press the next key until the Reset inhibit timer option is shown Press enter to set the Reset inhibit time using the keypad and then press enter to save the new time Change Timings Reset Inhibit Time 01 00 Press ENT to Change Ext Fan Delay Timer delays the start of the extract fan so that it will not start the extraction while the extinguishing sequence is active To set the Ext Fan Delay Timer Change Timings EXT Fan Delay Start 01 00 Press ENT to Change Fan Time is the time the fan will run for once it has been started The timer is set in the same way as the other timers Change Timings EXT Fan Delay Start 01 00 Press ENT to Change Approved Document No GLT 212 7 1 Page 19 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual RELAYS MENU The relays menu allows the user engineer to set the normal condition of the output relays Relay config ENTER to Toggle 1 Stage Relay NO _ _ The relay outputs can be set between normally
27. ow a service engineer to power down the panel It should be an isolating double pole switch with contact separation 3mm The disconnect device should be marked FIRE ALARM DO NOT SWITCH OFF The supply must be exclusive to the fire panel The incoming mains cable should be fed through a cable gland secured to the entry hole closes to the mains termination Inside the enclosure the mains cable should be connected to the Live L and Neutral N terminals on the power supply cage The mains cable must not cross over the zone cables to help minimise mains interference Figure 3 Wiring the mains connection Approved Document No GLT 212 7 1 Page 10 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual CONNECTING THE BATTERIES The Premier EXPRO requires 2 x 12V sealed lead acid SLA batteries The two batteries are wired in SERIES The ve of one battery is connected to the RED battery lead The ve of the other battery is connected to the BLACK battery lead The ve of the first battery is connected to the ve of the second battery using the link wire supplied D MEETS GUISHING CONTROL PANE COMPLIES WITH RESET ECD Figure 4 Wiring the battery Although there are many sizes of suitable battery the enclosure has been designed for 12V 7Ah Use the battery calculation information later in this manual to work out the required standby battery size CAUTION risk of explosion if battery is replac
28. tion Manual OTHER CONNECTIONS The Premier EXPRO also has the following connections FIELD MONITORING INPUTS The EXPro has 5 field monitoring inputs e Gas Fired e Manual Release e Auto Manual Mode Low Pressure e Abort The inputs are monitored for Open Circuit amp Short Circuit To activate the input a load of 1KO must be switched between the ve amp ve lines If the equipment being connected has Normally Closed amp Normally Open contacts then connect the 18KO end of line resistor amp the 1 resistor as follows VE 18KQ 1KQ VE Figure 7 Wiring diagram for interfacing simple switched inputs 151 STAGE amp 2ND STAGE FIRE RELAYS The Premier EXPRO has one first stage amp one second stage volt free change over relay that operates on an alarm It is rated at lamp SELV The relay remains operated until the panel has been reset FAULT RELAY The Premier EXPRO has one volt free change over relay that operates on any fault condition The relay is normally energised so that it gives a signal in the event of total power failure mains amp battery backup It is rated at SELV The relay remains operated until the fault has been cleared Approved Document No GLT 212 7 1 Page 13 Issue 1 0 Author MF Date 19 08 2013 EXPro Installation Manual BOTTLE OUTPUT The bottle output on the Premier EXPRO is used to drive a gas release solenoid It is fused lamp Bottle Sol
29. x 31 5V Vmin 17 0V Imax A 2 5A CIE DC Input Voltage 21 5V 31 5V DC 29 9V DC Nominal Charger Voltage 27 6V Charger Capacity 3 4Ah to 7 2Ah Battery Deep Discharge Protection Battery Shutdown at lt 19 5V Number of Zones 2 Crossed Zones Maximum devices per zone 2 1 Stage Sounder Alarm Outputs 2x 150mA 29 5V DC Nominal 2 Stage Sounder Alarm Outputs 1x 250mA 9 29 5V DC Nominal Bottle Output 1x 1A 29 5V DC Nominal 1 Stage Relay Output 1 x Volt Free Relay SELV 1A Max 27 Stage Relay Output 1 x Volt Free Relay SELV 1A Gas Fired Relay Output 1 x Volt Free Relay SELV 1A Ext Relay Output 1 x Volt Free Relay SELV 1A Aux Output 1x 200mA 9 29 5V DC Nominal FUSE RATINGS Fuse Description Rating Battery Battery Protection Fuse 2A fast blow glass 250V For continued protection please ensure that any fuses that need to be replaced are replaced with fuses of the correct rating Approved Document No GLT 212 7 1 Issue 1 0 Author MF Date 19 08 2013 Page 28 EXPro Installation Manual DESIGN SPECIFICATIONS The Premier EXPro is a combined extinguishing control panel amp fire alarm control panel The Fire Alarm control Section has been designed in accordance with EN54 2 1998 A1 A2 Fire Detection amp Fire Alarm Systems Control amp Indic
Download Pdf Manuals
Related Search
Related Contents
Tecnostyl IC001 document holder Fiche Technique Bona Mega SuperMicro X5DPA-8GG (MBD-X5DPA-8GG 取扱説明書 - 第一電波工業 05/04/2012 : 2.086 Philips Remote control CRP664 dossier reçu le 20/12/2013 Laddec Laddec Laddec Limit FPAS8150 Power Amplifier Nokia FPS-8 Power Supply User Manual Copyright © All rights reserved.