1. 5 4 3 When push Man start ee GE will first output and start preheat delay when preheat delay is end fuel output 1 second preheat output will stop and crank output is start Here engine will start when crank successfully crank output stop Then engine comes into the safe time When the safe time is end then engine comes into the idle time When the safe time is end then idle output is out and engine will run at full tilt Auto state When push button the module will enter automatic state Here if remote start input is active connect to B the engine will start after the delay of start engine Preheat will first output and start preheat delay when preheat delay is end fuel output 1 second preheat output will stop and crank output is start Here engine will start when crank successfully crank output stop Then engine enter the safe delay When the safe delay is end then engine enter the idle delay When the safe delay is end then idle relay is close and genset raise high speed When remote start input is inactive the engine enter the idle process after the delay of engine stop idle relay disconnect fuel relays output after the idle delay ETS solenoid output genset will automatically stop ETS solenoid disconnect when genset stop steady TF AEAEE RATT Szen 3 ta IS HL H GOREN RS AAA LTT PRR PA ESRI TTT BI FEC Stop state Push the outon when engine is running the button beside led will lighten ent
2. Magnetic head signal input suggest using the shielded wire USB Interface Controller directly through the USB line connected to the computer for parametric programming 11 CASE DIMENSIONS HOLE 78mm 66mm o Engine Temp Input u Oil Pressure Input Configurable Input Gens L 1 el Remote Start Input Gens N 1 z Start Output SICH 1 amp Fuel Output Stop Output 1 N Em Stop Input Configurable Output fi 1 ES Magnetic Pickup 97 7mm LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 amp F 86 769 23 166296 fy www lixise com Page 15 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd 12 TYPICAL CONNECTIONS Q ETS output Idle Control User configurable output igurable input User confi iat coctent terme ie promus COENE A 13 PRODUCT PACKAGING Dongguan Tuancheng Automation Equipment Co LTD i i Tel 8 86 769 33263276 This product should be following sets EE 1 1 piece of controller model LXC706 http dgfeirui en alibaba com S http www lixise net 2 2 piece of fixed cards E mail sales smartgenset com Add 18 Chashang industrial zone WenTang Road Dongguan City 4 1 piece of product manual Guangdong China 3 1 piece of product certificate LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 7
3. when alternator P22 ei 0 30 0 V 6 0V D WL voltage has fallen below the set value and Warnina 0 30 0 remains for 5s It will initiate a shutdown alarm signal arning Return value is 1V Battery Over When battery voltage has exceeds the set value and remains for 20s It will initiate a warning alarm signal ia SE 12 0 40 0 V eg Only warning and not to shutdown the generator SS Return value is 1V Battery Under When battery voltage has fallen below the set value and remains for 20s It will initiate a warning alarm SS i echt BN signal Only warning and not to shutdown the Ang generator Return value is 1V When the temperature value of the external temperature sensor exceeds the set value high High temperature signal is sent Detecting only after P25 g 80 140 C 98 safety on delay is over If the set value is 140 high Temperature temperature signal will not be sent this only concerns external temperature sensor not high temperature signal via configuration input port When the external pressure sensor value falls below this set value low oil pressure signal is sent Detecting Low Oil only after safety on delay is over If the set value is 0 ee Pressure eee a Seok low oil pressure signal will not be sent this only concerns pressure sensor and does not concern low oil pressure warning signal via configurable input port When the liquid level of the external liquid level sensor 5 e is smaller than this value
4. CRANK DISCONNECT ENNEN 13 9 PARAMETERS RH LEE 14 10 TERMINAL iiinn a acest nical cease a a a lai 15 BR RTE a EE 15 12 TYPICAL CONNECTIONS EE 16 13 PRODUCT PAG IAG ING ce cise ve seatcsreetucesn et veteinqesastaipendeedhcnteeseed eeteee det tees stcovnandexenstetuntnsweivelndeciipsndencnendeates 16 LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 amp F 86 769 23 166296 y www lixise com Page2 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller 1 Dongguan Tuancheng Automation Equipment Co Ltd SUMMARY The Module LXC706 is an small Automatic Engine Control Module It selects 3 kinds of working state Manual Auto Stop can pass panel light touch buttons artificially start stop genset also can through remote start signal input automatic starting generator and can detect fault low oil pressure high water temperature emergency stop alarm over speed automatically disconnect fuel relays and stop electromagnet to electric suction close Panel LED indicator fault state provide real and effective fault alarm signal FEATURES Emerald green backlight generator parameters are clearly visible during the day and night LCD icon display alarm alarm information is visual universal d On the LCD digital display a variety of generator parameters The PC panel with durable waterproof The control panel easy realization of generator start stop reduce t
5. Temperature Under ce time 1 60 We speed Under volts and any other inputs configured as active from safety on f This is the amount of time that the start Idle speed is SE eee tine Jett Ge held active These allow the engine to hold low speed pos Warmingup 9 3600 s e 10s delay PO9 Cooling delay 0 3600 S 10s This is the amount of time that the stop Idle speed is O SERIES EEN as held active These allow the engine to hold low speed This timer is used if the unit is configured to operate an Energize to stop engine It dictates the duration that ETS solenoid the ETS output will remain active after the module has pan hold EE 20S detected the engine has come to rest If the ETS output is not configured this timer will still operate preventing an immediate restart Once the module has given a shutdown signal to the engine it expects the engine to come to rest It P12 Fail to stop delay 0 120 S Os monitors the Oil pressure and speed sensing sources and if they still indicate engine movement when this timer expires a Fail to stop alarm signal is generated Tooth number of the engine for judging of starter P13 Flywheel Teeth 100 300 118 crank disconnect conditions and inspecting of engine speed See the installation instructions P14 Poles 2 16 4 P15 Gen Abnormal 0 20 0 s 10 05 The alarm delay of generator over voltage and under Delay voltage LXC706 Product User Manual Dongguan Tuancheng Automation Equipment
6. range is 0 999 9 O the factory default is no sensor In setting fuel level sensor type when Should put the programmable input port type is set to 0 then set the fuel level sensor type 8 CONDITIONS OF CRANK DISCONNECT MBA tT ZS M Sg M SES M Lg M D SP 1 105 Eizo Hz fi vu gt 24 0 0 200 izen RPM 4 fi gt 24 0 0 200 ao kpa a i gt 200Kpa 0 1 000K a ERN S ah gt 30v 3 0 32 0 Pictured above select the desired options can be selected or not selected There are 4 conditions to make starter disconnected with engine that is speed sensor generator frequency Charge D and engine oil pressure They all can be used separately We recommend that engine oil pressure should be using with speed sensor and generator frequency together in order to make the starter motor is separated with engine immediately and can check crank disconnect exactly d Speed sensor is the magnetic equipment which be installed in starter for detecting flywheel teeth d When set as speed sensor must ensure that the number of flywheel teeth is as same as setting otherwise over speed stop or under speed stop may be caused fail or loss speed signal maybe caused d If genset without oil pressure sensor please don t select corresponding items If genset without speed sensor please don t select corresponding items otherwise start gt If not select generator in crank disconnect
7. setting controller will not collect and display the relative power quantity can be used in water pump set if not select speed sensor in crank disconnect setting the rotating speed displayed in controller is calculated by generator frequency and number of poles If the generator without magnetoelectric sensor and Oil pressure sensor the Charger D is optional as a starter motor separation conditions It is recommended to select Oil Pressure Charger D for safety LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 ZS F 86 769 23 166296 H www lixise com Page 13 of 16 LIKiSt SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd 9 PARAMETERS SETTING 1 The controller in standby mode simultaneously press the and K entering the password input interface following figure When the first digit flashing enter the password 0000 2 press the numerical plus 1 press the Numerical minus 1 Set the correct numerical value press the change 3 Set the second bit to fourth bit digital in accordance with the above method 4 If the input the correct password to enter parameter setting interface gt figure Displays the current settings of the serial number and parameter press the options flip up press the set options flip down 5 press the Oerter the parameter setting state the first digit flash
8. the module will alarm and stop engine Stop Failure when engine is stop fail the module will warn Battery over voltage The DC supply has risen above the high volts setting level for the duration of the high battery volts 20 seconds Battery under voltage The DC supply has low above the under volts setting level for the duration of the low battery volts 20 seconds Emergency Stop When emergency stop input ETS solenoid stop immediately output and then fuel disconnect preheat and start signal emit emergency stop alarm signal Gen Over Voltage When the continuous sampling voltage higher than the preset value at the end of the abnormal delay signal generator voltage is too high outage alarm at the same time Gen Under Voltage When sampling the voltage is lower than the preset value continuously at the end of the abnormal delay signal generator voltage is too low outage alarm at the same time Gen Over Frequency When the sampling frequency for 10 seconds after the signal generator frequency is too high outage alarm at the same time Gen Under Frequency When the sampling frequency for 2 seconds after the signal generator frequency is too low outage alarm at the same time Common Alarm when any alarm or warn is appear this alarm will active When the over speed under speed high temperature low oil pressure emergency stop no generator crank failure stop failure alarm battery over voltage battery under voltage comm
9. 69 33263276 ZS F 86 769 23166296 y www lixise com Page 16 of 16
10. Co Ltd T 86 769 33263276 ZS F 86 769 23166296 H www lixise com Page9 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd When generator voltage has exceed the set value and Gen Over the Gen abnormal delay has expired Gen Over PIG Voltage ER SEI Voltage is active When set the value as 620V the controller does not detect over voltage signal When generator voltage has fallen below the set value Generator Under and the Gen abnormal delay has expired Gen Under ea Voltage 20 020 SES Voltage is active When set the value as 30V the controller does not detect under voltage signal When engine speed has exceed the set value for 2s P18 Over Speed 0 6000 RPM 1710RPM Over Speed is active It will initiate a shutdown alarm signal When engine speed has fallen below the set value for P19 Under Speed 0 6000 RPM 1200RPM 10s Under Speed is active It will initiate a shutdown alarm signal When generator frequency has exceed the set value P20 Over Frequency 0 75 0 Hz 57 0Hz for 2s Over Frequency is active It will initiate a shutdown alarm signal nder When generator frequency has fallen below the set P21 F 0 75 0 Hz 45 0Hz value but Not equal to 0 for 10s Under Frequency is requency apt active It will initiate a shutdown alarm signal Charge Alt During generator is normal running
11. LIXiSe SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd LXC 06 Genset Controller User Manual Ver1 1 Date 2014 03 20 LXC706 SERIES AN STOP AUTO START o l Software version Date Versio Note 2013 05 10 1 0 Original release 2014 03 20 1 1 Added USB interface for directly connecting to PC LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 A F 86 769 23 166296 Q www lixise com Pagel of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd Contents 1 SUMMARY EE 3 SE tee 3 3 PII E esata nsec sve mS ee atenolol ees su tind shen aN NUN 3 ASSP ECPI TION pocissssacnissiudn ctsnelstarsehonasabusaiaseunnd a A a a O 4 5 DISPLAY SYMBOL EIERE 5 S PUSHBUTTON EE 5 S2 Eelere E 5 5 3 DISPLAY Ted lag e EE 6 54 OPERATION s i sss sxtanctsisispaieosacinad a a S a 7 5 4 1 Man start ET E O EA 7 5 4 2 Auto state cee Lae O een ere Te 7 5 4 3 Stop state EE eS EE a EE 7 6 PALA EN W fen TT a Nagle aed aab cana TEE R EN 8 7 PARAMETERS TABLEWQNLY ADJUST VIA PIG cccsssesssssccssecnssenssenssssssesenssenssensacsesesesenesenenencnsecaesenenenes 9 7 1 PARAMETER SET Tamer so GLA EE 9 7 2 PROGRAMMABLE OUTPUT TABLE E 12 7 3 PROGRAMMABLE INPUT ACTIVE WHEN CONNECTOGND GAOTABLE 3 12 ghee Ss S16 oes a TE 12 8 CONDITIONS OF
12. and lasts 10 seconds the SC ES Gen we signal level is too low Only warning and not to shutdown the generator 0 Not used Configurable 1 Common alarm pee output O p 2 Energized To Stop output 3 Idle control LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 ZS F 86 769 23166296 H www lixise com Page 10 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd 4 Preheat control 5 Close Gens 6 Reserved 0 not used 1 High temperature downtime input 2 Low oil pressure shutdown input 3 Low fuel warning input P29 Digital input type 0 8 0 4 External shut down input 5 High temperature thermal shutdown 6 Reserved 7 Reserved 8 Fuel level sensor P30 Digital input O0 20 s units 20s activation delay 0 1s 0 Freq 1 Engine speed 2 speed Electricity generation 3 Oil pressure P31 Crank 0 8 6 4 Oil pressure Electricity generation Disconnect 5 Oil pressure speed 6 Oil pressure speed Electricity generation 7 Charge D 8 Oil pressure speed Electricity generation 9 Invalid combination f 7 In the process of cranking when the gens frequency P32 Freq disconnect 01 203 14pm exceeds this value the starter will be separated P33 E kaea wk 0 3000 RPM 360RPM When engine speed higher than the set value starter ngine S
13. e is too high low low fuel level With idle speed control and ETS solenoid function LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 amp F 86 769 23 166296 y www lixise com Page3 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd s With 3 working state manual automatic stop d Through the software setting of controllers can be set to the engine controller not choose the power voltage input suitable for control of pump unit d Panel with a red light emitting diode LED display and alarm status A variety of temperature pressure oil level sensor can be used directly and can custom parameters Temperature pressure sensor respectively and temperature pressure alarm in parallel in providing the digital quantity at the same time increase the level of protection Many successful starting condition rotational speed sensor oil pressure power generation can choose Four fixed relay output fuel oil output starter output to stop the output Idle speed output A programmable output can be set to public alarm output stop failure output preheating output or idle speed control output function Allow the user to change the setting of parameters and memory in the internal FLASH memory will not be lost in the system when the power is off the controller from the front panel of the co
14. eng Automation Equipment Co Ltd T 86 769 33263276 ZS F 86 769 23 166296 H www lixise com PageS5 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd Rotation during normal operation LZ Over Crank k Pa Oil pressure unit Ww a Warning V Voltage unit NY VQ Stop alert A Current unit a 0 l Stop Failure A Fuel level units Percentage TA C Temperature unit flywheel tooth number Hz Frequency unit Battery voltage is H Total running time Kiel ao abnormal External alarm SET Parameter setup instructions Low fuel level L1 L2 L1 L2 Line voltage L2 L3 L2 L3 Line voltage L3 L1 L3 L1 Line voltage Li N L1 Phase voltage L2 N L2 Phase voltage L3 N L3 Phase voltage Q Pags P butan 5 3 DISPLAY DESCRIPTION Generate electricity Phase voltage Ua Frequency F Battery voltage Engine speed Oil pressure Water temperature Liquid level Total running time Parameter Settings LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 amp F 86 769 23 166296 Q www lixise com Page6 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd 5 4 OPERATION arse O Module has three states stop state man state auto state i 5 4 1 Man start 5 4 2
15. er idle process idle relay disconnect idle delay ended fuel disconnect ETS solenoid output genset stop ETS solenoid disconnect when genset stop steady When engine is waiting state push button 1 second above ETS solenoid will output and all led will be Lighten Loosen the stop buttons ETS solenoid output disconnect instantly and test lamps function is over When engine is waiting state only emergent stop alarm can be check LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 amp F 86 769 23 166296 y www lixise com Page7 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd 6 ALARM Li Ze d Ze Li Ze Low Oil Pressure check after the safe delay the duration of 5 seconds above the module will alarm and stop engine High Temperature check after the safe delay the duration of 10 seconds above the module will alarm and stop engine Low Fuel Level When the fuel level is consistently below the preset value of 10 seconds and issuing fuel level is too low signal this value is only a warning will not stop Over speed check after the preheat delay the duration of 2 seconds above the module will alarm and stop engine Under speed check when engine run at full tilt the duration of 15 seconds above the module will alarm and stop engine Over Crank when engine crank fail over the times of configure
16. he user connection All parameters can be set on the panel convenient debugging and maintenance Set all the configuration parameters and monitoring computer through USB connection Ultra small size suitable for small generator intelligent control is particularly suitable for small gasoline generator d Equipped with a shockproof rubber ring can achieve waterproof and shockproof panel Install the assembly flame retardant ABS shell pluggable terminal embedded installation compact structure convenient installation PERFORMANCE d The power supply a wide range 8 35 VDC can adapt different starting battery voltage environment The microprocessor as the core for the LCD screen display icon symbols light touch keys d With low oil pressure high water temperature over speed and emergency stop start failures and so on protection and instructions d Can detect and display of power are power voltage V power frequency Hz engine temperature C oil pressure kPa speed rpm total running time H the battery voltage V fuel level voltage of the generator battery voltage speed temperature pressure liquid level sensor threshold can be set can achieve the following alarm or warning low oil pressure water temperature cylinder temperature high speeding less speed emergency stop failure to start stop failure of power voltage is too high too low power frequency is too high or too low the battery voltag
17. ime 0 5s controller according to the power frequency and generator series automatic generator teeth LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 amp F 86 769 23 166296 Q www lixise com Page 14 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd 10 TERMINAL Terminal 1 B connect to the cathode of battery Terminal 2 B connect to the anode of battery Terminal 3 Em stop input emergent stop input connect to B is active Terminal 4 Fuel Output Fuel Output B 1A Terminal 5 Start Output Start Output B 1A Terminal 6 Remote Start Input Remote Start Input connect to B is active Terminal 7 Configurable Input Programmable input port By setting the input signal switch quantity or fuel level sensor signal switch input connect to B is active Terminal 8 LOP Input Low oil pressure input switch input connect to B is active Terminal 9 HWT Input High temperature input switch input connect to B is active Terminal 10 L 11 N Alternator Input Terminal 12 Idle Output Idle speed control output port B 1A Terminal 13 Stop Output ETS output B 1A Terminal 14 Configurable Output3 Configurable output B 1A Terminal 15 D Connect to charging starter s D terminal If there is no this terminal then be hang up Terminal 16 Magnetic pickup
18. ing set of numerical methods with the same password input method Password input interface Parameter Settings interface Matters needing attention 1 Please change the controller parameters when generator is in standby mode only e g Crank disconnect conditions selection digital input digital output various delay otherwise shutdown and other abnormal conditions may occurs 2 When set each parameter must be within the allowed range otherwise will not be able to change the parameters 3 Over voltage set value must be higher than under voltage set value otherwise the controller will not save the data 4 Over speed set value must be higher than under speed set value otherwise the controller will not save the data 5 Please set the generator frequency value as low as possible when cranking in order to make the starter be separated quickly as soon as possible 6 Set the serial number with reference to the front 7 1 Parameter setting list Table 1 7 In setting fuel level sensor type when the programmable output type is set to 0 set the fuel level sensor type again NOTE 1 In the process of setting up any time button will interrupt parameter settings NOTE 2 In manual mode startup success condition configuration 2 magnetic sensor generate electricity or 5 generate electricity magnetic sensor oil pressure power frequency and speed is not zero press the start button and flip keys at the same t
19. ntroller All the parameters can be adjusted or through the USB interface by the PC machine USB power supply controller through monitoring software for parameter setting SPECIFICATION project content Working Voltage DC8 OV to 35 OV Continuous Power Supply Overall Consumption standby mode 12V 0 3W 24V 0 4W working 12V 1W 24V 1 1W AC voltage Input Single phase 2 Wire 15V AC 360 V AC ph N Alternator Frequency 50 60Hz Speed Sensor Voltage 1V 24V effective value Speed Sensor Frequency maximum 10kHz The maximum total run time 99999 9 hours After the decimal point is 1 10 hours Six minutes once changes Start Relay Output 1Amp DC28V B power supply Fuel relay output 1Amp DC28V B power supply Shutdown relay output 1Amp DC28V B power supply Idle speed relay output 1Amp DC28V B power supply Programmable relay output 1Amp DC28V_ B power supply Switch input port After B effective Overall Dimensions 97mm x 78mm x 44mm Panel Cutout 78mm x 66mm LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 ZS F 86 769 23 166296 H www lixise com Page4 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd Working Conditions Temperature 25 70 C Relative humidity 20 90 Storage Conditi
20. on alarm LED illuminate and common alarm output LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 A F 86 769 23 166296 fy www lixise com Page8 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd 7 PARAMETERS TABLE ONLY ADJUST VIA PC 7 1 PARAMETER SETTING LIST TABLE 1 Set the content as follows NO Parameter Range Default Description It s the delay from remote start signal is active or GC Siar delay EE 13 mains is failure to start generator It s the delay from remote start signal is inactive or el Slop delay 0 30008 ii mains is normal to stop generator Number of P02 Crank 1 9 3 Numbers of crank cycles This timer dictates the duration that the pre heat output will be active before an attempt is made to start POS Est cee ue the engine Once this timer has expired cranking will commence This is the maximum amount of time that the module P04 Cranking time 1 60 S 8s will energize the starter motor for during starting attempts once the starter has engaged Cranikr si This is the amount of time the module will wait for DOS 3 60 S 10s between start attempts This is to allow the starter time motor to cool and the starter batteries to recover This timer dictates how long the module will ignore the Safe running Low oil pressure High Engine
21. ons Temperature 30 80 C Protection Level IP55 When waterproof rubber seal installed between the controller and panel fascia IP42 When waterproof rubber seal is not installed between the controller and panel fascia Insulation Intensity Object input output power Quote standard Test way AC1 5kV 1min leakage current 1mA IEC688 1992 Weight 0 13kg 5 DISPLAY SYMBOL AMD OPERATION 5 1 PUSH BUTTON Symbol Defined Description Manual start Push this button generator will start and the button module comes into manual state Auto state button Push this button the module comes into auto state Stop button Push this button generator will stop and the module comes into stop state In the standby mode if long pressing the button for 3 seconds all LED lights LCD page Change the page display used for LCD and can Ce button confirm move the cursor in the parameter Settings and button confirm set information A Alarm light When an alarm occurs exhibit of lanterns flicker 5 2 LED ICON Defined Symbol Defined High Temperature Automatic state Symbol SE 7 Low Oil Press Stop state Lo Over Speed M Manual states SD Under speed AC Generator voltage T Emergency Stop D C Battery voltage Vt High voltage Amount of fuel IV Low voltage R P M Speed units rpom minute LXC706 Product User Manual Dongguan Tuanch
22. peed will be disconnected P34 Disconnect Oil 0 400 kPa 200kPa When generator oil pressure higher than the set value Pressure starter will be disconnected P35 l D 3 0 32 0 V 8 0V When generator D higher than the set value starter Disconnect will be disconnected P36 e nia 0 10 3 VDO120 C urve pay ee 0 9 3 vD00 10BAR Sensor Curve P38 ual eansor 0 5 0 not used Using the fuel level sensor will switch input port is set to unused P39 Temperature 0 2 0 0 Never temperature sensor will show Sensor Open 1 Warn 2 Shutdown P40 Oil Pressure 0 2 0 0 Never temperature sensor will show Sensor Open 1 Warn 2 Shutdown P41 Fuel sensor open 0 1 0 0 NEVET temperature sensor will show 1 Warn P42 Device ID 1 247 1 P43 Power On Mode 0 2 0 0 Stop Mode 1 Auto mode 2 Manual Mode Zelt 0 9999 0000 password Pas operator 0 9999 1111 password LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 ZS F 86 769 23 166296 H www lixise com Page 11 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd 7 2 PROGRAMMABLE OUTPUT TABLE 2 No ITEM Description 0 Not Used When selected the output port is not output Includes all stop alarm and warning alarm when only warning ala
23. rm 1 c input this alarm is not self locking when outage alarm occurs the ommon Alarm f i alarm self locking until the alarm is reset Used for engines with ETS electromagnet Pull in when stop idle is 2 ETS Control over and pull out when set ETS delay is over Used for engine which has idles Pull in before starting and pull out 3 Idle Control after into hi speed warming Pull in during stopping idle mode and pull out after shutdown completed 4 Preheat Control Before the boot is closed power is disconnected before starter 5 Close Generator Generator load conditions are ripe for action 6 Reserved 7 3 PROGRAMMABLE INPUT ACTIVE WHEN CONNECT GND B TABLE 3 No ITEM Description 0 Not Used 1 Aux High Temp In after the success of the generator starting if the 2 Aux Low OP signal is effective generator alarm and shutdown 3 Low fuel If the signal is effective warn only not shutdown 4 External stop If the signal is effective warn only not shutdown generators Switch When this signal is effective and normal operation If input When the temperature is too high controller high speed l 5 jon Aire ish cooling delay until after the downtime When this signal perature is too SE high downtime is invalid If there is high temperature the controller directly to the high speed stop 6 Reserved 7 Reserved 8 Fuel level sensor Sensor selection table 4 7 4 SENSOR SELECT TABLE 4 No ITEM Content Description 0 Not used 1 Digital inpu
24. t low effective Digital input is the switch signal can 2 Digital input high effective choose low level or high level grounding is 1 Temperature 3 VDO 120 C low level suspend in midair is the high sensor 4 CURTIS level not plugged into a power supply for 5 VOLVO EC the Cathode Defined resistive range is 6 DATCON 0 999 9 Q the factory default is SGD 7 SGX sensor 8 SGD 9 SGH 10 PT100 LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co Ltd T 86 769 33263276 ZS F 86 769 23 166296 H www lixise com Page 12 of 16 LIXiSE SMART GENSET LXC706 Series Genset Controller Dongguan Tuancheng Automation Equipment Co Ltd 2 Pressure O Not used 1 Digital input low effective 2 Digital input high effective 3 VDOO0 10BAR Digital input is the switch signal can choose low level or high level grounding is low level suspend in midair is the high 3 Fuel level sensor 1 Digital input low effective 2 Digital input high effective 3 VDOO 1800hm 4 SGD 5 SGH sensor 4 CURTIS level not plugged into a power supply for 5 VOLVO EC the Cathode Defined resistive range is 6 DATCON 10BAR 0 999 9 Q the factory default is SGD 7 SGX sensor 8 SGD 9 SGH 0 Not used Digital input is the switch signal can choose low level or high level grounding is low level suspend in midair is the high level not plugged into a power supply for the Cathode Defined resistive