1. onlinecomponents com THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Supplying Operating Voltages Termi nal Points Segment supply 24 V DC 12 22 Main supply bus coupler supply communications power and in terface supply 24 V DC 6137A008 1 3 2 3 Reference potential 1 4 2 4 Functional earth ground FE Figure 3 Terminal assignment for the PROFI BUS DP V1 bus coupler power con nector 4 ova V 24V U guy 9 PS PROFIBUS DP Arann Figure 4 Connection wiring plan for the PROFIBUS DP V1 bus coupler Connect the PROFIBUS DP V1 bus coupler ac cording to Figure 4 6 PHGNIX 6809_en_05 CONTACT onlinecomponents com THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Hardware Configuration Configure the hardware on the PROFIBUS DP V1 bus coupler using the 10 pos DIP switch The PROFIBUS address and other PROFIBUS DP V1 bus coupler settings can be set using this switch The meaning of the switches is given in the following table OL6E8L29GVECZCHL 6809A003 Figure 5 PROFIBUS DP V1 bus coupler DIP switches PROFIBUS address in binary format 0 127 in decimal format Switch 1 defines the least significant bit 2 and switch 7 defines the most significant bit 6 Inline station operating mode ON DP V1 mode with acyclic communication parameterization fail safe val ues etc OFF Can directly replace the pr
2. 6809A002 quired for the PROFIBUS DP V1 bus coupler Figure 1 Bus coupler with connector and end and the connected Inline terminals plate DIP switch 8 is particularly important see page 7 As default upon delivery it is in the The end plate is supplied with the OFF position This means that the device can PROFIBUS DP V1 bus coupler Place this plate directly replace the previous version IL PB BK at the end of the Inline station The end plate Order No 27 40 05 4 although it also offers does not have any electrical function It protects some new functions see above However the station against ESD pulses and the user these functions can only be used on the newde against dangerous contact voltage vices When configuring the device use the PXC_OOFO GSD GSD and the IL PB BK DP V1 DIP 8 OFF device entry in the hardware list 2 PHGNIX 6809_en_05 CONTACT THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Overview on Firmware Functions PROFIBUS IL PB BK PAC IL PB BK DP V1 PAC Order No PAC Order No PAC 28 62 24 6 28 62 30 1 Order No 27 18 68 8 Order No 2740054 DP VO0 mode DP V1 mode Support of DP VO cyclical communi Process data 184 bytes Process data Process data cation maximum 184 bytes 176 bytes maximum maximum PCP module operation Supporting DP V1 read and write acy clic communication Class 1 and Class 2 master Communication using PCP modul
3. 82 F to 131 F Ambient temperature storage 25 C to 85 C 13 F to 185 F Humidity operation 75 on average 85 occasionally Humidity storage Air pressure operation 80 kPa to 106 kPa up to 2 000 m 6 562 ft above sea level Air pressure storage transport 70 kPa to 106 kPa up to 3 000 m 9 843 ft above sea level Mechanical Requirements Vibration test 5g load 2 hours in each space direction Sinusoidal vibrations according to IEC 60068 2 6 24 V DC 120 V AC and 230 V AC areas EN 60068 2 6 2g load 2 hours for each space direction 400 V AC area Shock test according to IEC 60068 2 27 25g load for 11 ms half sinusoidal wave EN 60068 2 27 three shocks in each space direction and orien tation Broadband noise according to 0 78g load 2 5 hours in each space direction IEC 60068 2 64 EN 60068 2 64 Insertion withdrawal cycles Terminal Connector 6809_en_05 PHGNIX 13 CONTACT THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Conformance With EMC Directive 89 336 EEC Noise Immunity Test According to EN 61000 6 2 Electrostatic discharge ESD EN 61000 4 2 Criterion B IEC 61000 4 2 6 kV contact discharge 8 kV air discharge Electromagnetic fields EN 61000 4 3 Criterion A rowers lead strength 10 V m Fast transients burst EN 61000 4 4 Criterion A IEC 61000 4 4 All interfaces 1 kV Criterion B All interfaces 2 kV Surge voltage EN 61000 4 5 C
4. BUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Standard and Device Related Diagnostics for PROFIBUS Error Type Parameter error on PROFIBUS SET_PRM telegram Configuration error on PROFIBUS CHK_CFG telegram Detailed information about the PROFIBUS configuration error is represented by 14 different error numbers Configuration error in the Inline station Detailed information about the Inline station configuration error is represented by eight different error numbers INTERBUS error within the station six different error numbers More detailed information about error causes and remedies can be found in the user manual see Ordering Data for Documentation on page 16 10 PHGNIX 6809_en_05 CONTACT THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Technical Data General Data Order designation Order No IL PB BK DP V1 PAC 28 62 24 6 IL PB BK DP V1 27 18 68 8 Housing dimensions 91 mm x 120 mm x 71 5 mm width including latching x height x depth 3 583 in x 4 724 in x 2 815 in Weight 210 g without connectors Degree of protection IP20 according to IEC 60529 Class of protection Class 3 according to VDE 0106 IEC 60536 System Data Number of devices per station 63 maximum Sum of all I O data per station 184 bytes maximum in IL PB BK mode 176 bytes maximum in IL PB BK DP V1 mode Maximum bus coupler current for supplying the 2 A at UL I O terminal logic Maximum cu
5. IL PB BK DP V1 IL PB BK DP V1 PAC PROFIBUS DP V1 Bus Coupler Data Sheet 10 2004 Function The PROFIBUS DP V1 bus coupler is the link between PROFIBUS DP and the Inline installa tion system Inline terminals and Loop 2 modules can be con nected in any order to an existing PROFIBUS DP using the PROFIBUS DP V1 bus coupler In this way all the advantages of the installation system created using these terminals can also be used on PROFIBUS DP 6809 _en_05 THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS A Sou Sa CAR Sa sy 6809B001 Features The PROFIBUS DP V1 bus coupler has the fol lowing properties new functions in the IL PB BK compatible mode A maximum of 63 Inline devices or Loop 2 modules can be connected to PROFIBUS DP via the bus coupler The PROFIBUS DP V1 bus coupler and the Inline terminals create a station The total of all input and output data of the connected terminals must not exceed 176 bytes per station in the IL PB BK DP V1 mode DIP switch 8 ON 184 bytes maximum in IL PB BK mode DIP switch 8 OFF DP V1 for Class 1 and Class 2 masters Acyclic communication with e g RS 232 modules also in the process data channel I O terminal parameterization Fail safe values Various diagnostic formats Acknowledgment of I O errors from the user program Adaptation of the high byte low byte format in 16 channel input and output modules to the con
6. es via normal process data DP VO Parameterization of many I Os via dia logs in the configuration tool Presetting replacement values via the configuration tool Turning the byte for IB IL 24 DI 16 and X X IB IL 24 DO 16 for adaptation to the control format Acknowledging bus stops either auto matically or via the application pro gram Acknowledging bus stops either auto matically or via the application pro gram Diagnostics inthe IL PB BK format x X Diagnostics in the identification format a Diagnostics as status PDU as status Diagnostics as status PDU Stopping behavior adjustable via DIP switch 6809_en_05 PHGNIX 3 CONTACT THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC PROFIBUS IL PB BK PAC IL PB BK DP V1 PAC Order No PAC Order No PAC 28 62 24 6 28 62 30 1 Order No 27 18 68 8 Order No 2740054 DP v0 mode DP V1 mode Stopping behavior adjustable via pa xX rameter telegram Transmission invoke ID New for Firm New for Firm for example for IB IL POS 200 ware B or later ware B or later Dynamic configuration Reserving I Os in the PLC e g for easy expandability New for Firm ware B or later New for Firm ware B or later New for Firm ware B or later New for Firm ware B or later New for Firm ware B or later Presetting fail safe values via the con figuration tool Fail safe values also without connec tion to the PLC Im
7. evious version IL PB BK Order No 27 40 05 4 Reserved both switches must be in the OFF position PHCENIX CONTACT onlinecomponents com THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Local Diagnostic Indicators 6809A005 Figure 6 Indicators on the PROFIBUS DP V1 bus coupler LED Color Meaning State Description ofthe LED states Green U Main 24 V main circuit supply present pn com OFF Main circuit supply not present Green Usegment ON 24 V segment supply present po cen OFF Segment supply not present ON Nocommuntaton on PROFIBUS Corr Noe S Flashing PLC stopped Fail safe values are output If If FS is on FN indicates the error type is on FN indicates the error If FS is on FN indicates the error type OFF If FS is not on FN indicates the error number Failure Flashing The number of flashing pulses indicates the error type or the error number depending on whether FS is on or not 8 PHGNIX 6809_en_05 CONTACT onlinecomponents com THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Circuit Diagram PROFIBUS DP 6138033 Figure 7 Circuit diagram of the PROFIBUS DP V1 bus coupler Key J U Protocol chip Microprocessor Protocol chip Optocoupler Power supply unit with electrical isolation RS 485 RS 485 interface Interface fs We 6809_en_05 PHGNIX 9 CONTACT THE ONLINE DISTRI
8. proved diagnostics of I Os during startup Configuration can be stored addi tional verification using the latest valid configuration Freely assignable station IDs 2 bytes for improved identification on the net work 4 PH NIX 6809_en_05 CONTACT Connecting PROFIBUS 6809A004 Figure 2 Pin assignment of the 9 pos D SUB female connector Connect PROFIBUS to the PROFIBUS DP V1 bus coupler using a 9 pos D SUB connector e g SUBCON PLUS PROFIB Order No 27 44 34 8 Please refer to the pin assignment in the following table onlinecomponents com THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Reserved RxD TxD P receive transmit data cable B CNTR P control signal for repeater direction control DGND reference potential up to 5 V VP supply voltage 5 V for termina tion resistors Reserved RxD TxD N receive transmit data cable A Reserved Mains Termination Resistors Since PROFIBUS DP is a serial bus system ina line or tree structure the individual branches must be terminated using a termination resistor The PROFIBUS DP V1 bus coupler does not have a resistor of this type For additional infor mation please refer to your PROFIBUS docu ments Phoenix Contact recommends using the PROFIBUS connector SUBCON PLUS PROFIB Order No 27 44 34 8 This connector has a termination resistor that can be con nected 6809_en_05 PHGNIX 5 CONTACT
9. riterion B IEC 61000 4 5 DC supply lines 0 5 kV 1 kV symmetrical asymmetrical Fieldbus cable shielding 1 kV Conducted interference EN 61000 4 6 Criterion A IEC 61000 Oy PF act voltage 10 V Noise Emission Test According to EN 61000 6 4 14 PHGNIX 6809_en_05 CONTACT THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Ordering Data PROFIBUS DP V1 bus coupler with end plate IL PB BK DP V1 PAC 28 62 246 connector and labeling field PROFIBUS DP V1 bus coupler with end plate IL PB BK DP V1 2718688 B BK DP V1 Power connectors for the bus coupler IB IL SCN PWR IN CP 27 27 637 pack of 10 D SUB connector 9 pos with two cable feeds for SUBCON PLUS PROFIB 27 44 34 8 PROFIBUS up to 12 Mbit s terminal resistor can be connected using slide switch Ordering Data for Accessories Coding profile 100 pcs package IL CP 27 42 68 3 Zack markers for labeling terminals ZB6 see CLIPLINE catalog DIN EN 50022 DIN rail 2 meters 6 562 ft NS 35 7 5 perforated 0801733 NS 35 7 5 unperforated 08 01 68 1 End clamp CLIPFIX 35 30 22 21 8 Universal ground terminal block USLKG 5 04 41504 Screwdriver according to DIN 5264 blade SZF 1 0 6X3 5 1204517 width 3 5 mm 9 64 in Additional System Components The PROFIBUS DP V1 bus coupler can only be supplemented by further system componentes from the product spectrum of Phoenix Contact FO interface converters INTERFACE catalog for fiber op
10. rrent for supplying the analog terminals 0 5 A at Uana PROFIBUS DP Interface Copper cable RS 485 connected via D SUB shield connector electrically isolated supply shield ing directly connected to functional earth ground 24 V Main Supply U Main Supply Bus Coupler Supply Communications Power and Interface Supply Connection method Spring cage terminals Recommended cable lengths 30 m 98 43 ft maximum routing cables through outdoor areas is not permissible 6809_en_05 PH NIX 11 CONTACT THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC 24 V Main Supply U Main Supply Bus Coupler Supply Communications Power and Interface Supply Continued Minimum current consumption at nominal volt 0 1 A DC age no load operation i e incoming PROFIBUS is plugged in no Inline devices are connected Maximum current consumption at nominal volt 1 25 A DC consists of age 0 75 A DC for communications power 0 5 A DC for analog voltage supply Safety measure Surge voltage 24 V Segment Supply Us Connection method Spring cage terminals Recommended cable lengths 30 m 98 43 ft maximum routing cables through out door areas is not permissible Tolerance 15 20 according to EN 6113 1 2 Surge voltage 12 PHGNIX 6809_en_05 CONTACT THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Ambient Conditions Ambient temperature operation 0 C to 55 C
11. tic data transmission Power supply units INTERFACE catalog for supplying bus couplers 6809_en_05 PHGNIX 15 CONTACT THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC Ordering Data for Documentation Configuring and Installing the PROFIBUS DP V1 IL PB BK DP V1 UME 26 98 106 bus coupler for the Inline product range User Reference I O terminals at bus couplers AH IL BK IO LIST 9015358 Application note AH IL PB BK DP V1 PAC 90 18 48 1 To the address area of I O terminals at the address area PROFIBUS DP V1 bus coupler User Manual Automation Terminals of the Inline ILSYS INST UME 26 98 73 7 Product Range CD ROM with all Inline Loop 2 and other data CD IBS DB ELDOC 27 45 606 sheets PHOENIX CONTACT GmbH amp Co KG Flachsmarktstr 8 32825 Blomberg Germany 49 E 52 35 3 00 Ze 49 0 52 35 3 4 12 00 Za www phoenixcontact com amp Worldwide Locations www phoenixcontact com salesnetwork PHOENIX CONTACT 10 2004 Technical modifications reserved 9013613 16 PHGNIX 6809_en_05 CONTACT
12. trol system format The bus coupler can be installed with a data transmission speed of 9 6 kbit s to 12 Mbit s The bus coupler is automatically set to the speed specified by the PROFIBUS master PHCENIX CONTACT onlinecomponents com THE ONLINE DISTRIBUTOR OF ELECTRONIC COMPONENTS IL PB BK DP V1 PAC The operating voltage of the IL PB BK DP V1 In the ON position the device offers all the bus coupler is 24 V DC The operating tem functions mentioned above and has a new perature range is 0 C to 55 C PROFIBUS ID number Use the 32 F to 131 F PXC_O6CC GSD GSD and the Diagnostics is provided locally by LEDs on IL PB BK DP V1 DIP8 ON device entry in the bus coupler and on the Inline terminals the hardware list for configuring and para meter and Loop 2 modules All diagnostic informa izing the device The stop response which was tion can be forwarded to the PROFIBUS specified by this switch in the old device is then master via PROFIBUS set in the parameterization The intelligent wiring method used in the Inline terminals and Loop 2 modules enables the sta tions to be constructed quickly and easily be cause for example there is no need for time consuming wiring of terminal power supplies In the simplest case it is only necessary for the power supply units integrated in the PROFIBUS DP V1 bus coupler to be supplied with 24 V DC They then generate the operating voltage re

Download Pdf Manuals

image

Related Search

Related Contents

Omron Healthcare INTELLISENSE HEM-775 User's Manual  500005 - HOME PALACIO- ESQUEMA.cdr  DeLonghi Magnifica S ECAM 21.117.B    1 MANUAL DE INSTRUCCIONES Introducción  仕 様 書 R o H S 指 令 対 応 組込用1回路漏水検知器 A D − A S − 1  UPmusic TOP - Tez  Manual de usuario New Holland LS 170  P-10  Sony VGN-S67GP/S User's Manual  