Home
INSTALLATION MANUAL
Contents
1. 5 ZONES ZONES ZONES 9 TO 16 24 BUILT IN BUILT IN BUILT IN PPP amana 16 17 18 19 20 21 Connection No Description Use 1 ZONE 1 amp Connect to Zone 1 2 ZONE 2 amp Connect to Zone 2 3 ZONE 3 amp Connect to Zone 3 4 ZONE 4 amp Connect to Zone 4 5 ZONE 5 amp Connect to Zone 5 6 ZONE 6 8 Connect to Zone 6 7 ZONE 7 8 Connect to Zone 7 8 ZONE 8 amp Connect to Zone 8 9 SND 1 amp Connect to sounder circuit 1 sirens bells 10 SND 2 amp Connect to sounder circuit 2 sirens bells 11 SND 3 amp Connect to sounder circuit 3 sirens bells 12 SND 4 amp Connect to sounder circuit 4 sirens bells 13 FIRE RELAY NO CM NC Activates on fire including test mode 14 FAULT RELAY NO CM NC Activates on fault 15 EARTH MONITORING POINT FOR EARTH FAULTS 16 F A R E amp FIRE ALARM ROUTING EQUIPMENT 17 SERIAL amp B RS485 SERIAL REPEATER CONNECTION 18 AUX SUPPLY 250 mA Supply System voltage 29 31 V dc 19 BATTERY amp Connect 2 x 12V SLA batteries in SERIES ie 24V 20 THERM Thermistor Connector to protect batteries 21 AC AC Connected to transformer secondary 30VAC 22 ZONE 9 amp
2. SOUNDER ALARM OUTPUTS 4 x 150mA 29V DC Nominal ZONAL SOUNDER CIRCUITS OPTIONAL 8 12 16 20 24 x 5 29V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT 1 x RELAY SELV 1A MAX F A R E OUTPUT 1 X 100mA 29V DC NUMBER OF ZONES 24 28 32 36 40 44 48 MAXIMUM ZONE CAPACITY 32 DEVICES PER ZONE MAXIMUM ZONE RESISTANCE 70 ohms AUXILIARY SUPPLY 250mA 29 V dc NOMINAL SOUNDER ACTIVATION DELAY 0 9 MINUTES IN 1 MIN INCREMENTS ZONE END OF LINE DEVICE 100uF CAPACITOR STRIPE TO ZONE VE SOUNDER END OF LINE DEVICE 10 K RESISTOR CHARGER VOLTAGE 28 4V 25 C NO BATTERY CONNECTED CHARGER SHORT CIRCUIT PROTECTION Batteries less than 20V TOTAL PSU OUTPUT 3 Amp MAXIMUM CHARGING CURRENT 600mA PANEL LOAD FOR BATTERY VALUE CALCULATIONS PANEL CURRENT IN MAINS FAIL NO ZONE 150mA 125 mA with buzzer silenced SOUNDERS PANEL CURRENT IN MAINS FAIL WITH ZONE 175mA 150 mA with buzzer silenced SOUNDERS PANEL CURRENT IN ALARM 270mA Approved Document No GLT MAN 120 PAGE 22 Issue 1 2 Authorised GH Date 2 11 2007
3. NOMINAL SOUNDER ACTIVATION DELAY 0 9 MINUTES IN 1 MIN INCREMENTS ZONE END OF LINE DEVICE 100uF CAPACITOR STRIPE TO ZONE VE SOUNDER END OF LINE DEVICE 10 K RESISTOR CHARGER VOLTAGE 28 4 25 C NO BATTERY CONNECTED CHARGER SHORT CIRCUIT PROTECTION Batteries less than 20V TOTAL PSU OUTPUT 3 Amp MAXIMUM CHARGING CURRENT 600mA PANEL LOAD FOR BATTERY VALUE CALCULATIONS PANEL CURRENT IN MAINS FAIL NO ZONE 180mA 160 mA with buzzer silenced SOUNDERS PANEL CURRENT IN ALARM 250mA Approved Document No GLT MAN 120 PAGE 20 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER M PLUS 48 INSTALLATION MANUAL Approved Document No GLT MAN 120 PAGE 21 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER PLUS 48 INSTALLATION MANUAL 12 PANEL SPECIFICATIONS 12 1 ENCLOSURE SPECIFICATIONS DESCRIPTION VALUE ENCLOSURE SIZE 480 x 395 x 100 mm TOP CABLE ENTRIES 20 x 19mm DIA GROMMETED ENTRIES BOTTOM CABLE ENTRIES 10 x 19mm KNOCKOUT ENTRIES REAR CABLE ENTRIES 2 SNAP OUTS 60 x 20mm 12 2 ELECTRICAL SPECIFICATIONS ELECTRICAL DESCRIPTION VALUE MAINS VOLTAGE 230V AC 10 50 60 Hz BATTERY VOLTAGE 24V DC 2 X 12V SLA BATTERY SYSTEM VOLTAGE 24V DC NOMINAL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V
4. III III equation in section 10 but as a rough guide Panel 4 66Ah 50 Detectors 0 1 Ah 5 Bells 0 1Ah BATTERY CONNECTIONS The two batteries are wired in series The ve of one battery is connected to the red battery lead The ve of the other battery is connected to LINK WIRE the black battery lead The ve of the first battery is connected to the ve of the second battery using the link wire supplied 4 Battery location and connection details Approved Document No GLT MAN 120 PAGE 9 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER PLUS 48 INSTALLATION MANUAL 5 FIELD DEVICE TERMINATION 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS All cables entering the enclosure should have brass cable glands which will ensure a good ground to the EMC enclosure coating The Detector and Sounder circuits should be connected to the appropriate connector block on the Termination PCB as shown in Figure 6 below For detailed detector and alarm circuit wiring diagrams please refer to pages 4 and 5 X X X AASS GLANDS 1 SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE RUBBER GROMMETS III HIHI PROVIDED C 921 p LL LL LL RA co c 92 Ol SEALED LEAD ACID BATTERY SEALED ACID BATTERY 7 Ah UN 7 An Figure 6 Detector
5. Note possible fault is a detector head badly seated in a base that is not making a good connection c A short circuit on a zone could be caused by the end of line capacitor being fitted backwards d Check that the detectors are compatible with this FACP Note that some makes of detector will require a series resistor or diode to be fitted to work properly There is usually a spare connector on the base to accommodate this check instructions that came with the detector e Measure the resistance of the zone cabling Remove from panel and short out end of line Ideally this should be less than 50 ohms Above 70 ohms may cause an open circuit fault 9 2 SYSTEM FAULT A system fault is abnormal microprocessor running condition due to various unexpected phenomena This will result in the panel attempting to correct itself Should this fault occur the System Fault LED General Fault LED General Fault relay and fault internal buzzer will be constantly active until the control keyswitch is turned from off position to control enable position This should cause this fault condition to reset If not consult your supplier 9 3 SUPPLY FAULTS A power supply fault is indicative of one or more of the following faults 1 Loss of Mains power Remedy a Check mains fuse in fused mains block Also check that main power is present b Check charger fuse FS1 2 Loss of Battery power Remedy a Check battery fuse FS2 b Check th
6. and Sounder Circuit Connection 5 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS Connect auxiliary input and output cables to the appropriate connector block terminals on the Termination PCB See Page 15 Screened cables should be terminated as per figure 6 For a full description of the inputs and outputs available on the Premier M 48 range of Fire Panels including typical wiring diagrams please refer to pages 5 amp 6 Approved Document No GLT MAN 120 PAGE 10 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER PLUS 48 INSTALLATION MANUAL 6 CONFIGURING THE PANEL 6 1 SOUNDER ACTIVATION DELAY 6 2 1 DECIDING TO USE A DELAY A delay of up to nine minutes from the Fire Alarm Panel being triggered to its Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where the nuisance and panic caused by a false alarm must be avoided It should be noted that the delay period will apply to ALL zones When an Alarm occurs on any zone it is processed as normal However the activation of the sounders is postponed until the delay period has expired thus allowing the cause of the Alarm to be investigated by the User If the alarm is false the alarm can be cancelled 6 2 2 TO SET A DELAY Open the panel door and set the SND DELAY rotary switch 1 SW1 using a terminal screwdriver to the delay required SW2 Setting Ex
7. and maintained by a qualified and technically experienced person 1 1 HANDLING THE PCBS If the PCBs are to be removed to ease fitting the enclosure and cables care must be taken to avoid damage by static The best method is to wear an earth strap but touching any earth point e g building plumbing will help to discharge any static Hold PCBs by their sides avoiding contact with any components Always handle PCBs by their sides and avoid touching the legs of any components Keep the PCBs away from damp dirty areas e g in a small cardboard box 1 2 USING THIS MANUAL This manual explains in a step by step manner the procedure for the installation of the Premier M 48 Range of Fire Alarm Control Panels For full operational and maintenance information please refer to document GLT MAN 121 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK It also contains a System set up table and Design Installation and Commissioning Certificates that must be completed by the appropriate engineers prior to system handover Unlike the User Manual this Installation Manual must not be left accessible to the User 1 3 ABOUT THE PREMIER M 48 ALARM CONTROL PANEL amp INTEGRAL PSE e The PREMIER M PLUS Fire alarm control panel is available in 24 amp 48 Zone sizes e t has 4 common sounder output circuits each capable of supplying 400mA It has a 250mA auxiliary output t has a set of fire relay contacts voltage free rated at 1A SE
8. 0mA time delay 5 x 20mm glass FS6 AUX Supply 250 time delay 5 x 20mm glass FS7 Sounder circuit 3 400mA time delay 5 x 20mm glass FS8 Sounder circuit 4 400mA time delay 5 x 20mm glass INLET FUSE Mains Protection Fuse 3 15A Quick Blow HBC 5 x 20mm ceramic Approved Document No GLT MAN 120 Issue 1 2 Authorised GH Date 2 11 2007 PAGE 19 PREMIER PLUS 48 INSTALLATION MANUAL 12 PANEL SPECIFICATIONS 12 1 ENCLOSURE SPECIFICATIONS DESCRIPTION VALUE ENCLOSURE SIZE 680 x 480 x 135 mm TOP CABLE ENTRIES 40 x 19mm DIA GROMMETED ENTRIES BOTTOM CABLE ENTRIES 10 x 19mm KNOCKOUT ENTRIES REAR CABLE ENTRIES 2 SNAP OUTS 1X 100x35mm and 1 X 70x35 mm 12 2 ELECTRICAL SPECIFICATIONS ELECTRICAL DESCRIPTION VALUE MAINS VOLTAGE 230V AC 10 50 60 Hz BATTERY VOLTAGE 24V DC 2 X 12V SLA BATTERY SYSTEM VOLTAGE 24V DC NOMINAL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 4 x 400 29V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT 1 x RELAY SELV 1A MAX F A R E OUTPUT 1 X 100mA 29V DC NUMBER OF ZONES 24 28 32 36 40 44 48 MAXIMUM ZONE CAPACITY 32 DEVICES PER ZONE MAXIMUM ZONE RESISTANCE 70 ohms AUXILIARY SUPPLY 250mA 29 V dc
9. 7 1 WHY USE ZONE DISABLEMENT To aid commissioning and assist routine maintenance checks any of the zones or the sounder circuits can be disabled When zone or sounder circuit is disabled the panel will not respond to any fault or fire signals it receives from that zone This might be used if the system requires routine maintenance and the customer needs the system to continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of zones or the sounders can be disabled but it is good practice to only disable one zone at a time 1 Insert and turn control key to enabled position 2 Press Function button and the GENERAL DISABLEMENT LED will come on flashing fast 3 Press Scroll switch and the GENERAL DISABLEMENT LED will flash with a 3 quick flashes then off pattern Zone 1 fault and zone 1 Test Disablement LEDs will also flash with the same pattern The panel is now in SELECT DISABLEMENT MODE 4 Press select to disable Zone 1 or scroll to the item to disable The panel will scroll through zones 24 48 then zone sounder 24 48 then common sounders then F A R E Continue to press scroll until the desired Zone or sounder is flashing 5 When an item has been disabled the DISABLEMENT LED will be lit The item that has been disabled will now flash 3 quick flashes then on This means that it
10. ANNING CABLE ENTRY 3 2 FIXING THE BACKBOX TO THE WALL 4 CONNECTING MAINS amp BATTERY 9 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 FIELD DEVICE TERMINATION eene 10 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS 6 CONFIGURING THE PANEL 6 1 SOUNDER ACTIVATION DELAY 6 2 1 DECIDING TO SET A DELAY 6 2 2 TO SET A DELAY 6 223 DELAY INDICATION AND OVERRIDE 6 2 USING SOUNDER DELAY TO COMMON TIMER 7 ZONE DISABLEMENT cic u asss SET nuno rien sted 7 1 WHY USE ZONE DISABLEMENT 7 2 TO PROGRAM A ZONE OR SOUNDERS AS DISABLED 8 ZONE TEST a aes see Seat 8 1 WHY USE ZONE TEST 8 2 TO PROGRAM ZONE IN TEST 9 GENERAL FAULT FINDING irruere usa eee 9 1 ZONE FAULTS 9 2 SYSTEM FAULT 9 3 SUPPLY FAULTS 9 4 EARTH FAULTS 9 5 SOUNDER FAULTS 9 6 REPEATER FAULTS 9 7 F A R E FAULTS 10 STANDBY BATTERY CALCULATION GUIDE 11 PCB TERMINATION CONNECTIONS 11 1 11 2 12 CONTROL PANEL ELECTRICAL SPECIFICATIONS 12 1 12 2 CONNECTIONS FUSES ENCLOSURE SPECIFICATIONS ELECTRICAL SPECIFICATIONS 1 INTRODUCTION 13 14 15 17 18 19 Approved Document No GLT MAN 120 Issue 1 2 Authorised GH Date 2 11 2007 PAGE 3 PREMIER M PLUS 48 INSTALLATION MANUAL THIS FIRE ALARM CONTROL PANEL IS CLASS 1 EQUIPMENT AND MUST BE EARTHED This equipment must be installed
11. CP during installation Approved Document No GLT MAN 120 PAGE 8 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER PLUS 48 INSTALLATION MANUAL 4 CONNECTING MAINS amp BATTERY POWER 4 1 CONNECTING THE MAINS POWER The panel should be connected to 220 240V AC by INLET MAINS a 5A rated spur to the fuse box with 1mm to 2 5mm2 3 core cable Nothing else should be connected to SUPPLY I this supply This cable should be fire resistant The Live Earth and Neutral connections are marked by the Connection Block The Mains is protected by a quick blow 20mm 3 15A HBC fuse Also known as HRC The incoming mains cable should be kept separate from the zone cables to help minimise mains interference MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE RUBBER GROMMETS PROVIDED It is advisable to apply power to the panel before connecting any devices to check for correct operation and to familiarise yourself with the fire alarm panels controls figure 3 Power Supply PCB layout and Mains connection details 4 2 CONNECTING THE BATTERIES Although there are many sizes of suitable battery the sizes we usually recommend are 12V 7Ah The enclosure has been designed to hold this size battery calculate the exact requirement use the III
12. Connect to zone 9 23 ZONE 10 8 amp Connect to zone 10 24 ZONE 11 8 Connect to zone 11 Approved Document No GLT MAN 120 Issue 1 2 Authorised GH Date 2 11 2007 PAGE 18 PREMIER M PLUS 48 INSTALLATION MANUAL 25 ZONE 12 amp Connect to zone 12 26 ZONE 13 amp Connect to zone 13 27 ZONE 14 amp Connect to zone 14 28 ZONE 15 amp Connect to zone 15 29 ZONE 16 amp Connect to zone 16 30 ZONE 17 amp Connect to Zone 17 31 ZONE 18 amp Connect to Zone 18 32 ZONE 19 amp Connect to Zone 19 33 ZONE 20 amp Connect to Zone 20 34 ZONE 21 amp Connect to Zone 21 35 ZONE 22 amp Connect to Zone 22 36 ZONE 23 amp Connect to zone 23 37 ZONE 24 amp Connect to zone 24 The Premier M 48 fire alarm panel has 6 banks of detection zones The ones in bank 1 will for zones 1 8 bank 2 will be for zones 9 16 bank 3 will be for zones 17 24 bank 4 will be for zones 25 32 bank 5 will for zones 33 40 and bank 6 will be for zones 41 48 11 2 FUSES FUSE NO DESCRIPTION RATING FS1 ZONE Zone Fuse 500 time delay 5 x 20mm glass FS1 Charger Fuse 3 15A time delay 5 x 20mm glass FS2 Battery Fuse 3 15A time delay 5 x 20mm glass FS3 F A R E Fuse 100 time delay 5 x 20mm glass FS4 Sounder circuit 1 400mA time delay 5 x 20mm glass FS5 Sounder circuit 2 40
13. LV t has a set of fault relay contacts voltage free rated at 1A SELV normally energised e It has the ability to disable any zone or the common sounder circuits e thas a one man test mode which resets the zone in test after 4 seconds EN54 option with requirements e It has a sounder delay facility 0 9 minutes in 1 minute steps EN54 option with requirements 1 4 DESIGNING THE SYSTEM It has a maximum battery capacity of 7 Ah It has an in built capability of operating with Diode bases for line continuity on head removal It will operate in ambient temperatures of 5 to 40 It will operate in a relative humidity of up to 9396 non condensing It will withstand vibrations between 5 amp 150 Hz It has a maximum capacity of 32 devices per zone But for locating potential future problems or events we would usually recommend a practical maximum of 20 devices per zone The PSE is linear with a 3 0A output at system voltage 18 32V The charger amp battery are both fused at 3 15A TD The PSE will draw a maximum of 25uA from the battery in the event of mains failure The FACP will continue to take around 150mA The FACP amp PSE should be maintained as described in section 3 of the User Manual Maintenance Guide amp Log Book This manual is not designed to teach Fire Alarm System design It is assumed that the installer has an understanding of Fire Alarm System components and their use W
14. Premier 748 FIRE ALARM CONTROL PANEL DESIGNED TO CONPLY WITH EN54 PT2 amp PT4 1997 INSTALLATION MANUAL PREMIER M PLUS 48 INSTALLATION MANUAL PREMIER M 48 OVERVIEW The Premier M plus 48 is the latest large size conventional panel from Zeta Alarm Systems Its Features include Designed to EN54 Parts 2 amp 4 It is available in sizes from 24 to 48 zones in 4 zone increments Automatically uses diode bases for line continuity Four common sounder circuits 400mA Each Serial Repeater Output Fire amp Fault Relays SELV F A R E Output which can be disabled Auxiliary supply 29 Volts 250 mA Zone amp Sounder Disablement facility One man test mode Sounder delay facility 3 amp power supply Is a low cost alternative to the existing Premier L panel Approved Document No GLT MAN 120 Issue 1 2 Authorised GH Date 2 11 2007 PAGE 2 PREMIER M PLUS 48 INSTALLATION MANUAL CONTENTS 1 INTRODUCTION u usss ieee eet 4 1 1 HANDLING THE PCBS 1 2 USING THIS MANUAL 1 3 ABOUT THE PREMIER M PLUS 48 FACP amp INTEGRAL PSE 1 4 DESIGNING THE SYSTEM 1 5 EQUIPMENT GUARANTEE 2 FIRST FIX GUIDELINESx u Uu L erre 5 2 1 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS 2 2 MAINS WIRING RECOMMENDATIONS 2 3 DETECTOR CIRCUIT WIRING DIAGRAM 2 4 SOUNDER CIRCUIT WIRING DIAGRAM 2 5 AUXILIARY OUTPUT WIRING 3 MOUNTING THE FIRE ALARM PANLEL 8 3 1 PL
15. TALLATION MANUAL 3 MOUNTING THE FIRE ALARM PANEL is recommended that the panels door be removed to avoid accidental damage Also the termination PCB could be removed and stored in a safe place while fixing the back box to the wall 3 1 PLANNING CABLE ENTRY Fig 2 below shows the location of the cable entries to facilitate planning of wiring home runs to be brought to the panel The grommets can be easily removed by a push from inside the control panel box If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting the Mains on Page 8 3 2 FIXING THE BACK BOX TO THE WALL Figure 2 Plan view inside the enclosure without PCBs Side view for surface flush installation A TOTAL OF FORTY CABLE ENTRIES 0201089 4441089 406mm Fix the enclosure to the wall using the three mounting holes provided Check the build amp condition of the wall to decide a suitable screw fixing The mounting holes are designed for No 8 roundhead or countersunk woodscrews or similar Remove any debris from the enclosure Take care not to damage the FA
16. all point will allow it to work PONT Note if this is the last device the end of line ve will NEXT DEVICE connect to the connector block NOT the call point OR END OF LINE Other makes of detector will have different connections but in general they are wired in one of 2 ways SPLIT NEGATIVE IN amp OUT to same terminal IN to stripe side of continuity diode OUT to non stripe side of continuity diode Or SPLIT POSITIVE IN to non stripe side of continuity diode OUT to stripe side of continuity diode IN amp OUT to same terminal Some makes of detector will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly with European Fire Alarm Panels For more specific device wiring information please refer to the device manufacturers own instructions The termination of each detection circuit must be as indicated on the main PCB See page 15 The Earthing of the cable screens should be as shown on page 9 2 4 SOUNDER CIRCUIT WIRING DIAGRAM SND SND SOUNDER SOUNDER SOUNDER SOUNDER 10K E g et End of Line Resistor Note If non polarised alarm devices eg some types of old mechanical bell or a relay are used then a diode will have to be placed in line with the device to enable fault monitoring They may also need a back EMF protecti
17. at battery connections are secure 3 Low Battery Remedy a Check battery voltage replace if necessary Approved Document No GLT MAN 120 PAGE 15 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER M PLUS 48 INSTALLATION MANUAL 4 Wrong Charging Voltage The charging voltage should be 28 4V off load at 20 If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage If it is reading over 27 4 then the batteries are overcharged Try to run the panel on batteries only for half an hour or so to try to discharge the batteries If this doesn t solve the problem replacement batteries will be required 9 4 EARTH FAULTS An EARTH fault indicates that something is shorting to earth usually through the cable screen Disconnect the earth screens one at a time to determine the problem line Note connecting other equipment e g an oscilloscope to the panel can give an earth fault The voltage between battery and earth should be 14 16 volts If it is not the voltage measured should indicate what is shorting to earth 9 5 SOUNDER FAULTS Check that the correct END of Line resistor has been fitted 10K brown black orange gold Check that all sounder fuses are OK FS4 FS5 FS7 amp FS8 150mA If working on an existing installation check that the devices are polarised See Page 5 Check cable continuity remove from panel and measure c
18. comes with 24 28 32 36 40 44 or 48 Detection circuits Zones A maximum of 32 devices i e smoke detectors heat detectors or Manual Call Points can be fitted to each circuit ALL DEVICES MUST BE POLARISED Typical detector circuit wiring Fyreye Detectors ZONE Arrow CEN points ZONE 3 EV lt lt H 7 w v jl f 288 side tour m PR END of LINE CAPACITOR 100uF 25 100V END of H LINE 8 CAPACITOR 100uF 25 100V If ALL the call points are connected to the start of the zone then conventional bases can be used instead of diode bases Approved Document No GLT MAN 120 PAGE 5 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER M PLUS 48 INSTALLATION MANUAL An End of Line capacitor provided in the Panel must be connected across the terminals of the last device on each circuit to allow the wiring to be monitored It is polarity sensitive and connected with the arrows pointing to zone ve Using detector bases with continuity diodes fitted will allow all devices including Manual Call Points to remain operational if a detector is removed from its base Old Manual call points which just cause a short circuit CONNECIOR 470R are not directly compatible as they would cause a BLOCK RESISTOR short circuit fault Fitting a 470R resistor in line with the e c
19. dication device IS OPEN WHEN THERE IS 99 FAULT NO NC FAULT RELAY or OUTSTATION Here the relays are used to FIRE TO ADDRESSABLE communicate with a larger INPUT FIRE ALARM PANEL addressable fire alarm system An example use of this might be a FAULT eid warehouse which uses several INPUT flame detectors and needs to be 59 169 169 69 69 part larger system NO CM NC NO CM NC FIRE RELAY FAULT RELAY 2 5 3 Fire Alarm Routing Equipment Output F A R E Monitored 24V nominal output This is a 24V 100mA output that activates in any fire condition and is used for driving local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc It is active until the panel is reset It can be disabled through the zone sounder disablement function which may be useful during maintenance tests if the panel is connected to a central station via an autodialler 2 5 4 Serial Repeater Output The Premier M 48 has an optional serial repeater It is connected to the main panel by 4 cores 2 for power 2 for RS485 Data The Repeater is fully functional and can silence and reset the panel The termination for the above inputs must be as indicated on the main PCB See page 15 The earthing of the cable screens should be as shown on page 9 Approved Document No GLT MAN 120 PAGE 7 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER PLUS 48 INS
20. e for System Design Installation and Servicing are Standard fire resisting cable to PH30 classification of EN 50200 Enhanced fire resisting cable to PH120 classification of EN 50200 Note that all cables should be at least 1mm cross section On the Premier M Plus 48 Panel the general recommendation would be to use standard fire resistant cable such as Firetuff GLT Exports Fire Defence Cable FP200 or an equivalent These cables are screened and will provide good ECM shielding when properly grounded at the panel Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this fact Depending on the environment the cables may need mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire resisting 3 core cable Between 1 mm and 2 5mm or a suitable 3 conductor system fed from an isolating double pole switch fused spur fused at 5A IT SHOULD NOT BE CONNECTED THROUGH AN RCD This should be secure from unauthorised operation and be marked FIRE ALARM DO NOT SWITCH OFF The supply must be exclusive to the Fire Panel MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE GROMMETS PROVIDED For information on how to connect Mains to the Panel s Power Supply PCB see page 8 Also refer to rating information on the mains cover inside the FACP 2 3 DETECTOR CIRCUIT WIRING DIAGRAM The Premier M 48
21. e strongly recommend consultation with a suitably qualified competent person regarding the design of the Fire Alarm System The System must be commissioned and serviced in accordance with our instructions and the relevant National Standards Contact the Fire Officer concerned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 2002 Fire Detection and Alarm Systems for buildings Code of Practice for System Design Installation and Servicing available from the BSI or at your local reference library 1 5 EQUIPMENT GUARANTEE If this equipment is not fitted and commissioned according to our guidelines and the relevant National Standards by an approved and competent person or organisation the warrantee may become void Approved Document No GLT MAN 120 PAGE 4 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER PLUS 48 INSTALLATION MANUAL 2 FIRST FIX All wiring must be installed to meet BS5839 Pt1 2002 and BS 7671 Wiring Regs standards Other National standards of fire alarm system installation should be adhered to where applicable 2 1 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS Screened cables should be used throughout the installation to help shield the Panel from outside interference and ensure EMC compatibility The two categories of cable according to BS5839 Pt1 2002 Clause 26 Fire Detection and Alarm Systems for Buildings Code of Practic
22. ess scroll button to move to another Zone to test or turn the control key switch to off position to exit test mode Approved Document No GLT MAN 120 PAGE 14 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER PLUS 48 INSTALLATION MANUAL 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS The Zone Faults are non latching faults That is if the fault has been cleared the panel will automatically reset itself Open circuit faults will be indicated by zone s fault LED being lit steady the internal Fault Buzzer will sound and the General Fault LED will be lit Short circuit faults will be indicated by zone s fault LED and the short circuit LED Flashing the internal Fault Buzzer will sound and the General Fault LED will be lit Suggested Action a If a bank of 8 zones are all showing O C check zone fuse FS1 on the relevant zone expansion card b Check that the correct end of line device has been fitted 100uF capacitor c Disconnect the wiring for the zone showing fault and refit the end of line capacitor at that zone terminal in the panel If the fault condition for that zone clears this confirms there is a wiring fault d Double check the wiring and the end of line capacitor on the zone Trace the fault with consideration for the type of fault indicated HINT splitting the cable half way down the zone and fitting the end of line capacitor to the new end point helps to determine which section of cable is giving the fault
23. has been disabled but is still the focus of the disablement select mode If scroll is pressed once more the disabled part s LED will now be lit steady and the next item will flash 3 quick flashes then off 6 If more than one zone needs to be disabled then press scroll again until the required zone is selected T If the panel needs to be taken out of SELECT DISABLEMENT MODE e g to silence a fault on another part of the system turn the keyswitch off then back on again 8 Once all the work has been done the zones need to be enabled again If the panel is still in SELECT DISABLEMENT MODE jump to paragraph 9 otherwise turn the keyswitch to controls enabled press FUNCTION button GENERAL DISABLEMENT LED will flash fast Press scroll and it will flash with a 3 quick flashes then off pattern The panel is now in SELECT DISABLEMENT MODE 9 Press the scroll button until the disabled zone or sounder has been selected Press function button Scroll to any other disabled zone and enable in the same way When all zones are enabled again the GENERAL DISABLEMENT LED will flash 3 quick flashes then off Turn the keyswitch to off to return the system to normal Approved Document No GLT MAN 120 PAGE 13 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER PLUS 48 INSTALLATION MANUAL 8 ZONE TEST 8 1 WHY USE ZONE TEST aid commissioning and assist routine maintenance check a non latching one man test facility is availab
24. le When a detector or manual call point is triggered on any zone in Test the Alarm sounders operate for approximately four seconds on and four seconds off This cycle continues until the cause of the Alarm is removed either by the test smoke clearing from the detector or the manual call point being reset at which point the detector circuit also automatically resets Should an Alarm occur on a zone that is not programmed to test the Alarm will be processed in the normal way The testing of the zone in test will temporarily be suspended until the Alarm s from the other zones are investigated and then reset At this point zone retesting may resume 8 2 TO PROGRAMME ZONE IN TEST NOTE Only one zone can be programmed in test at any one time 1 Insert and turn control key to enabled position 2 Press FUNCTION button twice The General Zone test LED is now on flashing fast 3 Press Delay Override Silence Silence Delay Override The General Zone Test LED will now flash 3 quick flashes then off 4 Press scroll switch and Zone one fault amp test LEDs will flash in synchronisation with the General Zone test 5 Press scroll button to the desired Zone for test Once the desired Zone LED is flashing press select The LEDs will now flash on and off This Zone is now in test mode 6 Once testing of that zone is completed press select to exit test mode for that zone The LEDs will now flash 3 quick flashes then off 7 Pr
25. n sounder circuit The required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required TALM 0 5 Hr panel 0 270mA law 24 14 x 0 025 0 95A This typical bell current is 25 mA Most alarm Devices show their operating current Tspy 24 lap 0 150 laz 24 x 20 x 0 00006 0 0288 the quiescent current for a typical optical detector is 60 uA Therefore using the equation Battery Size Standby time in Amp Hours 1 25 x X larm X lap loz Battery Size Standby time in Amp Hours 1 25 x 0 5 x 0 270 0 95 24 x 0 150 0 0288 Battery Size Standby time in Amp Hours 1 25 x 0 61 24 x 0 1788 Battery Size Standby time in Amp Hours 1 25 x 0 61 4 2912 Battery Size Standby time in Amp Hours 1 25 x 4 9012 Battery Size Standby time in Amp Hours 6 13Amp Hours This system would require a minimum of 6 13Ah batteries so we would recommend using 7Ah batteries On a system with a heavier load it may be necessary to use larger batteries This may require a separate battery box to hold the batteries Approved Document No GLT MAN 120 PAGE 17 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER PLUS 48 INSTALLATION MANUAL 11 PCB TERMINATION CONNECTIONS 11 1 CONNECTIONS
26. on diode symptoms Chattering sounder relays that don t turn off SND CONNECTOR BLOCK POLARISING 10K End of Line Resistor Approved Document No GLT MAN 120 PAGE 6 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER PLUS 48 INSTALLATION MANUAL 2 5 AUXILIARY OUTPUT WIRING 2 5 1 Auxiliary Fire Output AUX Voltage free changeover contacts Changes over in any fire condition and is used for driving local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc AUTO Trigger DIALER The fire relay can be used to connect to various devices which are activated on a fire alarm E g Auto dialer magnetic door release 24V sprinkler 09109109 system etc NO CM NC FIRE RELAY 2 5 2 Fault Output FAULT Voltage free changeover contacts This Output is energised in the quiescent condition In a fault condition the output relay turns off to ensure failsafe operation even in the event of total power loss That is the normally open contact will be closed when there is no fault and open when there is a fault This should be taken into account when any device is connected to the fault relay FAULT Trigger I P INDICATION DEVICE The fault relay is used to connect to a remote NOTE THE NC CONTACT in
27. ontinuity Should read 10K 9 6 REPEATER FAULTS Check that the power and RS485 connections between the panel and repeater are correct Check The AUX supply fuse in the panel FS6 250m4A Check the supply fuse in the repeater 51 500mA 9 7 F A R E FAULTS Check that the correct END of Line resistor has been fitted 10K brown black orange gold Check there are no open or short circuits on the F A R E line Check that the fuse is OK FS3 100mA QB Approved Document No GLT MAN 120 PAGE 16 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER M PLUS 48 INSTALLATION MANUAL 10 STANDBY BATTERY CALCULATION In order to calculate the standby battery size required the following formula can be used Battery Size Standby time in Amp Hours 1 25 x Tatm X larm X lap loz ET Tam time in hours required for the alarm hour is most common time Total Alarm Current amps for all alarm devices connected to the alarm circuits Tspy Standby time in hours for the system after mains failure normally 24 48 or 72 hr lap Quiescent current in amps of control panel in fault condition because of mains failure loz Quiescent current in amps of all detection zones E g lon detector 0 00005 Amp 50 pA Optical Detector 0 0001 Amp 100 pA Typical Example A system comprises of 24 zones Each zone has 20 smoke detector 14 bells are connected to the commo
28. ternal sounder delay in minutes No delay 1 minute 9 2 minutes 9 3 minutes v 4 minutes 5 minutes V Co 6 minutes 7 minutes 8 minutes 9 minutes CO OO o INI I O EG The above example would have a delay of 1 minute Approved Document No GLT MAN 120 PAGE 11 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER M PLUS 48 INSTALLATION MANUAL 6 2 3 DELAY INDICATION AND OVERRIDE If a delay is set the fire panel will light the General Disablement LED and Sounder Delay LED to indicate that the sounders are delayed If an alarm occurs the fire LEDs will light as usual but the sounders will not start until the delay period has expired After the delay period the Gen Disablement and Delay LEDs will extinguish amp the sounders will start Pressing the OVERRIDE SOUNDER DELAY switch will override the delay at any time and results in the sounders being turned on immediately If on investigation the panel was activated by a false alarm turn the keyswitch to Controls Enabled and press the reset button This will return the system to normal without the sounders being activated Assuming the cause of the false alarm has been removed The delay can be removed by returning the rotary switch SW1 to position 0 Approved Document No GLT MAN 120 PAGE 12 Issue 1 2 Authorised GH Date 2 11 2007 PREMIER M PLUS 48 INSTALLATION MANUAL 7 ZONE DISABLEMENT
Download Pdf Manuals
Related Search
Related Contents
1 - Moxa Magnetic Effects on your compass, More Software releases 슬라이드 1 - AHA Information & Communication 取扱説明書 OPERATING INSTRUCTIONS PN 57.0009.0419 Copyright © All rights reserved.
Failed to retrieve file