SP122E REV00 D Specifica Green Point 1000
Contents
1. Na OAN PIN SIGNAL lt O COND UB WINE Contact closed UPS failure Bypass Alarm TXD RXD SD remote shutdown GND 12Vdc interface power input PNP Signal Contact closed battery low pre alarm Contact closed battery mode a If a different cable is used it should be of the pin to pin type with a max length of 3 metres 2 Optoisolated contact max 35Vdc 15mA 6 SD With UPS in operation from battery the UPS will perform a complete shutdown when 5 15Vdc Is applied between PIN 3 and PIN 5 for at least 20 seconds Communication Slot All UPS come with an expansion slot for optional communication boards so that the unit is compatible with the main communication options Some examples Serial port duplexer Ethernet network agent with TCP IP HTTP and SNMP protocols RS232 RS485 port with J BUS MODBUS protocol For more details on the options available visit the manufacturer s web site SP122E Rev 000 Siel S p A Page 17 of 36 FR Issued Date 2005 05 27 GREEN POINT 8 2 Communication software MAIN CHARACTERISTICS 1 Sequential and prioritised shutdown GreenShield allows you to shutdown the network without having to switch off each PC individually and saves the work that was being done regardless of the application that was being used The user may define his or her own shutdown procedure and may also prioritise the shutdown of critical compon
2. re SPECIFICATIONS GREEN POINT 1000 3000VA SINGLE PHASE On line double conversion VFI technology SP122E Rev 000 Siel S p A Page 1 of 36 FR Issued Date 2005 05 27 Table of contents l 1 OBJECTIVE 4 2 DESCRIPTION OF THE SYSTEM 4 3 APPLICATIONS 5 4 CHARACTERISTICS 6 5 NORMATIVE REFERENCES 9 5 1 Main reference standards 5 2 Standards relating to systems and installation 10 6 SUPPLIED EQUIPMENTS AND ACCESSORIES 11 6 1 Tower version 11 6 2 Rack version 12 RA BLOCK DIAGRAM OF THE MACHINE 13 7 1 Block diagram of the UPS 13 7 2 Options 13 8 INTERFACING 17 8 1 Serial communication port 17 8 2 Communication software 18 8 3 Configuration software 20 9 OPTIONS 21 9 1 Summary table of the options available 21 9 2 Installation of the battery expansion module 21 9 2 1 Configuration of the battery expansion module 21 10 MIMIC PANEL 22 10 1 LED panel 22 10 2 Description of the mimic panel dial 22 10 3 UPS front views 25 11 REAR VIEWS 26 11 1 Rear panel 1000 2000VA Mod 26 11 2 Rear panel 3000VA Mod 27 12 TECHNICAL DATA 28 12 1 Tower models 28 12 2 Back up expansion modules for tower version 28 12 3 Summary data sheets 29 SP122E Rev 000 Siel S p A Page 2 of 36 FR Issued Date 2005 05 27 13 GREEN POINT RACK 13 1 Rack models 13 2 Back up expansion modules for rack versio 13 3 Rear panels views SP122E Rev 000 Siel
3. Slot for the installation of a mains adapter SP122E Rev 000 Siel S p A Page 8 of 36 FR Issued Date 2005 05 27 5 STANDARDS 5 1 Main standards The company quality system has been certified as conforming to ISO 9001 Certificate ITALCERT No 005 03 This covers all of the procedures operating methods and controls from the design stage right up to the production and sale of the machine This certification guarantees the following aspects for our customers the use of quality materials rigorous standards in production and testing receptiveness and openness to our customers constant support of all our customers As well as being covered by this company certification the company produces state of the art products as dictated by the requirements of the standards quoted below The advances that have taken place in Information Technology systems mean that the power supply systems used to power them must be able to provide an absolutely precise and even more importantly absolutely reliable source of power The standards produced by IEC CENELEC in the IEC EN62040 series cover all aspects of the product safety electromagnetic compatibility and performance EN62040 1 Uninterruptible power supply systems UPS general provisions and safety provisions EN62040 1 1 Uninterruptible power supply systems UPS general provisions and safety provisions used in areas accessible to the operator EN60950 CEI74
4. rear output this eliminates the need to keep a lateral space free and allows the machine to be placed next to other options or systems Reduced noise lt 40db A due to use of high frequency IGBT technology Innovations in the design of the magnetic parts Advanced Communication Selection via software of the operating parameters Through the supplied software is possible to personalize the UPS operating parameters depending on own necessities see page 19 Monitoring and shutdown software included GreenShield provides an efficient and intuitive system for controlling the UPS displaying all the most important information such as input voltage applied load battery capacity etc with a series of bar charts The software is able to provide detailed information even if the machine has malfunctioned enabling you to find out why the fault has occurred It has been developed using a client server architecture that renders it flexible and easy to use with multilingual support and on line help With UPSs in the GREEN POINT range GreenShield is provided free of charge with an SNMP agent for Windows 95 98 2000 Windows 2003 Server Me Xp NT4 0 Novell Mac OS Mac Osx Mac Os 9 x Linux operating systems The software also allows you to programme the automatic start up and shutdown of your system on a weekly basis The UPS also contains the following hardware interfaces RS232 serial port Signals interface
5. 000 Siel S p A Page 23 of 36 FR Issued Date 2005 05 27 Tab 3 input voltage Input Voltage 190V 200V 200V 230V 230V 250V 250V 260V gt 260V Tab 4 load level Load level 0 5 5 25 25 50 50 75 75 102 gt 102 LED on with steady light 25 GREEN POINT Battery LED bar 2 3 7 7 9 7 Load LED bar 50 75 9 9 9 9 9 22 LED with flashing light on 1 flash per second Overloads on the UPS 4 5 7 7 100 N X 7 7 The following table shows how the UPS reacts when mains and battery overloads occur and indicates the time that the UPS will remain powered OVERLOAD LEVEL 102 lt Load lt 109 110 lt Load lt 130 130 lt Load lt 150 Load gt 150 SP122E Rev 000 Siel S p A Issued Date 2005 05 27 LOAD POWER TIMES off mains Switches to bypass after 30 min Switches to bypass after 30 sec Switches to bypass after 10 sec Switches to bypass after 0 5 sec LOAD POWER TIME off battery Shutdown after 30 min if battery back up time allows Shutdown after 30 sec Shutdown after 10 sec Shutdown after 0 5 sec Page 24 of 36 FR GREEN POINT Models 1000 1500VA gt 10 3 UPS front views 2 im 3 Se GU _ Models 2000 3000VA 1 LED mimic panel 2 ON button 3 OFF button SP122E Rev 000 Siel S p A Page 25 of 36 FR Issued Date 2005 05 27 GREEN POINT 11 REAR VI
6. Substances 5 2 Standards relating to systems and installation The above product regulations refer specifically to uninterruptible power supply systems It is these regulations that manufacturers of uninterruptible power supply systems are obliged to adhere to However with regard to the electrical system the installer must refer to other standards These standards are Standard CEI 64 8 HD384 IEC 60364 for electrical systems in general Standard CEI 64 8 variant 2 for installation in hospital environments Standard CEI 11 20 for systems with UPS machines connected to category or Il networks Standard CEI 17 13 EN60439 1 concerning control equipment Standard EN50272 2 for battery installation shortly to be replaced by the European Standard EN50272 2 Standard CEI 20 for electrical cables SP122E Rev 000 Siel S p A Page 10 of 36 FR Issued Date 2005 05 27 6 SUPPLIED EQUIPMENTS AND ACCESSORIES 6 1 Tower version The tower version UPS is supplied together the following equipments O UPS O RS232 serial cable O IEC 10A o 16A Power cord O IEC 16A Power cord set only for model 3000VA O 2 IEC 10A connection cables O User S Manual SP122E Rev 000 Siel S p A Page 11 of 36 FR Issued Date 2005 05 27 6 2 Rack version The rack version UPS is supplie
7. in min N Batteries Battery rated voltage SP122E Rev 000 Siel S p A Issued Date 2005 05 27 1000VA 1500VA 3000VA INPUT 2000VA 1 220 230 240 V singlephase 300 V singlephase 110 5 Vsinglephase load 0 60 160 5 V singlephase load 80 100 Standard 50Hz settable through software to 50Hz 60Hz or self teaching 5Hz 5A 7 2 A 10 A 14 4 A lt In gt 0 97 lt 3 Thermal switch Thermal switch Thermal switch Thermal switch 7A 10 A 12 A 16 A lt 40ms BY PASS 264V singlephase 180V singlephase BATTERIES 8 8 13 8 3 4 8 8 36 V 48 V 96 V 96 V Page 29 of 36 FR Type of batteries Battery configuration Type of recharge Recharge current Recharge time Intervention time loss of mains power supply Battery ripple current Battery voltage stability batteries fully charged Battery protection Rated voltage Wave form Frequency Frequency converter function Current peak factor from EN62040 3 regulation Rated output VA Rated output W Static variation Dinamic variation with load impact from 0 to 100 Output frequency variation with mains absent Frequency variation velocity Hz sec Voltage reset after dynamic variation Voltage distortion linear load Voltage distortion non linear load SP122E Rev 000 Siel S p A Issued Date 2005 05 27 GREEN POINT 7Ah Sealed lead maintenance free In series At two volta
8. situation you need to turn the UPS off OFF button reduce the applied load and switch the UPS back on again ON button Mains out of tolerance The UPS is designed to function with a wide range of input voltages This ensures that the batteries do not intervene too often thus increasing the back up time should a real blackout occur The microprocessor continuously checks the input voltage and frequency to guarantee functioning and Switches the load onto the by pass within a wide tolerance range Overtemperature If the internal temperature exceeds acceptable limits the UPS will protect itself by shutting down This Situation is indicated by the Stop Stand by LED and the continuous sound of the buzzer Batteries depleted The microprocessor carries out a periodic battery efficiency test If the batteries fail the test the red Batteries need substituting efficiency lt 60 LED is lit In this case the UPS batteries should be replaced SP122E Rev 000 Siel S p A Page 16 of 36 FR Issued Date 2005 05 27 INTERFACING 8 1 Serial communication port The UPS has the following communication ports see UPS views RS232 serial port COMMUNICATION SLOTS expansion slots for additional interface cards RS232 serial port The RS232 serial port allows the connection of a PC COM port by means of a pin to pin serial cable provided RS232 CONNECTOR oo QO NASAN ED L12 345
9. that are connected to it Load power factor correction UPS input factor close to 1 The UPS absorbs power from the mains power supply with a power factor close to 1 even if the systems Supplied by the UPS have a power factor inferior to this For example if the UPS supplies a piece of IT equipment with a power factor of 0 65 the UPS input power factor will nevertheless still be close to 1 ensuring that the mains power supply power factor correction banks are not overtaxed Battery optimisation High level of battery reliability automatic battery test The UPS automatically carries out a battery test allowing the system to periodically check the efficiency of the batteries in order to prevent faults occurring to them The test does not in any way compromise the power supply to the users connected to the UPS and given the short duration Seconds does not affect the life or the back up time of the batteries either Wide Input Voltage tollerances from 110V to 300V without battery participations Unlimited back up expandability through external battery modules supplied with a UPS which includes an improved and upgraded battery charger SP122E Rev 000 Siel S p A Page 7 of 36 FR Issued Date 2005 05 27 Compact dimensions Thanks to the following characteristics the UPS is one of the smallest on the market microprocessor control IGBT technology Internal batteries ventilation frontal input
10. 2 ITE Information Technology Equipment safety EN62040 2 Uninterruptible power supply systems UPS electromagnetic compatibility provisions EN50081 2 Electromagnetic compatibility immunity IEC1000 4 2 Immunity Electro Static Discharge ESD IEC1000 4 3 Immunity electromagnetic fields IEC1000 4 4 Immunity transient overvoltages BURST IEC1000 4 5 Immunity current surges Surge IEC61000 4 11 Low frequency disturbances EN50141 Induced radio interference EN55022 Radio frequency disturbance ENV62040 3 Uninterruptible power supply systems UPS performance provisions and test procedures SP122E Rev 000 Siel S p A Page 9 of 36 FR Issued Date 2005 05 27 IEC146 CEI22 Semiconductor electronic converters IEC529 CEI70 1 Degree of protection of casings European Directives 73 23 Low voltage directive enforcing the obligatory CE marking from 1 1 97 This directive concerns all safety issues associated with the equipment 89 336 Electromagnetic compatibility directive enforcing the obligatory CE marking from 1 1 96 This directive concerns all issues of immunity and emissions relating to the UPS at its place of installation WEEE ROHS environments directives that supply indications and norms about elimination of the electronic and electrical material Waste of Electronic and Electric Equipments and limitations of use of injurious substances Restriction on use Of Hazardous
11. EC mains input plug 10 Output socket fuse boxes SP122E Rev 000 Siel S p A Page 27 of 36 FR Issued Date 2005 05 27 GREEN POINT 12 TECHNICAL DATA 12 1 Tower models DIMENSIONS WEIGHT MODEL POWER BACK UP min HxWxD mm Kg GP1000 1000VA 700W 8 internal batteries 231x158x400 14 GP1500 1500VA 1050W 8 internal batteries 231x158x500 19 GP2000 2000VA 1400W 13 internal batteries 340x192x460 34 GP3000 3000VA 2100W 8 internal batteries 340x192x460 35 12 2 Back up expansion modules for tower version MODEL to bind BACK UP min DIMENSIONS HxWxD mm WEIGHT Kg 17 231x158x455 13 P 1000VA erent 28 231x158x455 17 1 GP 1500VA 5 231x158x455 15 23 231x158x455 21 GP 2000VA 30 340x158x485 28 42 340x158x485 40 15 340x158x485 28 P VA ene 23 340x158x485 40 SP122E Rev 000 Siel S p A Page 28 of 36 FR Issued Date 2005 05 27 EMERGT amp GREEN POINT 12 3 Summary data sheets MODELS Input phases Rated Voltage Maximum input voltage before battery intervenes Minimum input voltage before battery intervenes applied load 100 Rated frequency Input frequency tolerance Maximum current In rush current Power factor Current distorsion THDI Input protection Hold up time interr To mains power supplies before batteries intervenes Maximum voltage acceptable for switching to mains power Minimum voltage acceptable for switching to mains power supply Back up
12. EWS 11 1 Rear Panel Mod 1000 2000 VA Green Point 1000 1500 o amaje g T O O O 0 0O00 8 6 O O lr e 6 o 5 un o i Green Point 2000 7 8 2 6 a 3 5 1 RS232 serial communication port 5 IEC mains input plug 2 Cooling fans 6 IEC output sockets max 10A 3 Telephone modem protection net or intranet 7 Communication expansion slot 4 Input thermal protection 8 Battery expansion connector SP122E Rev 000 Siel S p A Page 26 of 36 FR Issued Date 2005 05 27 GREEN POINT 11 2 Rear panel Mod 3000 VA Green Point 3000 1 RS232 serial communication port 6 IEC output sockets max 10A 2 Cooling fans 7 Communication expansion slot 3 Telephone modem protection net or intranet 8 Battery expansion connector 4 Input thermal protection 9 IEC 16A output socket 5 I
13. FHERGT amp SATETT 13 2 Back up expansion modules for rack version MODEL to bind BACK UP min DIMENSIONS HxWxD mm WEIGHT Kg 17 2Ux19 x390 12 Green Point Rack 1000VA 30 WEC 19 15 2Ux19 x480 15 Green Point Rack 1500VA 57 TEET 25 Green Point Rack 2200VA n Green Point Rack 3000VA ni i rendo Note 88mm 2U 176mm 4U 2U 2U 483mm 19 SP122E Rev 000 Siel S p A Page 34 of 36 FR Issued Date 2005 05 27 GREEN POINT FHERGT amp SATETT 13 3 Rear panels views MODELS REAR VIEWS i i Green Point rack 1000 55 cca i e Green Point rack 1500 oT TEMS NAW WAS tee Green Point rack 2200 SS O ci TE of n TE me teh Od he ae ee SP122E Rev 000 Siel S p A Page 35 of 36 FR Issued Date 2005 05 27 GREEN POINT ENERSG ioni ea TRS ot pian mali GS N SAMAN vi a A E HI Green Point rack 3000 Battery Box 1 RS232 serial communication port 2 Cooling fans SP122E Rev 000 Siel S p A Issued Date 2005 05 27 ce Input thermal protection IEC output sockets max 10A 5 IEC mains input plug 6 Battery expansion connector Da IEC output sockets 16A Page 36 of 36 FR
14. IBM NetView OPERATING SYSTEMS SUPPPORTED Windows 95 98 Me NT 4 0 Win 2000 Win 2003 Server XP Novell Netware 3 x 4 x 5 x IntraNetWare IBM OS 2 Warp and Server Mac OS 9 X OSX The most commonly available UNIX systems such as IBM AIX HP UNIX SUN OS SPARC SUN Solaris INTEL and SPARC SCO Unix and UnixWare Siemens SINIX Silicon Graphic IRIX Compaq True64 UNIX and DEC UNIX Linux BSD UNIX and FreeBSD UNIX SP122E Rev 000 Siel S p A Page 18 of 36 FR Issued Date 2005 05 27 GREEN POINT GREENSHIELD SOFTWARE FUNCTIONS 1 Graphical monitoring of the UPS status GreenShield is the easy to use yet powerful program that allows you to monitor and control the UPS systems There are various graphical versions including Windows J ava 05 2 and MacOS 2 MACOS version The GreenShield software is the only UPS control and shutdown software available for the Macintosh that has a client server architecture Allows you to access the Windows Novell IBM OS 2 and the most commonly available UNIX operating systems when using a TCP IP network It also allows you to support NetMan series network agents to control the UPS via a network and furthermore comes with multilingual support 3 Detailed display of all the ups data GreenShield provides all the data required to make an accurate and speedy diagnosis of UPS Operation 4 Block diagram and operating diagram of a UPS GreenShield also displays a block diagram of t
15. Rev 000 Siel S p A Page 13 of 36 FR Issued Date 2005 05 27 GREEN POINT FHERGT amp SAFTETT 3 Rectifier booster block protection fuse This fuse is dependent on the status of the input fuse 1 a fault occurring to the rectifier booster will open this protection before the input fuse intervenes ensuring that the power supply to the user is not interrupted as the by pass line remains powered 4 Rectifier Booster When the mains power supply is present this converts the mains alternating current into a direct current controlling the power factor If the mains power supply fails it elevates the battery voltage to an appropriate level to power the inverter stage 5 Inverter Converts the direct current into alternating current 6 Automatic by pass Device for switching from the inverter to the mains and vice versa without interrupting the power Supply Intervenes if overloads or faults occur 7 Output switch To isolate the UPS when carrying out maintenance work 8 Output EMI filter Output filter for protecting the load against electromagnetic disturbances 9 Maintenance free sealed lead batteries Allow the UPS to be installed in public places and to power the load when the mains power supply fails 10 Battery expansion from 1000 to 3000VA models Allows you to prolong the back up time 11 Battery charger This is a DC DC converter that converts the rectifier oooster output voltage to
16. S p A Issued Date 2005 05 27 n 34 34 35 36 Page 3 of 36 FR 1 OBJECTIVE This technical document is designed to be used by UPS designers and installers The objective of this documentis to provide or illustrate the technical information required to enable you to choose the correct UPS for your needs the information required to set up the system Information conceming the installation and location of the UPS the information the machine displays to the user or to the systems it is connected to control centres etc the list of the options available to adapt the machine to the user s particular requirements 2 DESCRIPTION OF THE SYSTEM The new Green Point family of UPS has been designed to offer versatility and reliability They use ON LINE technology which means that the AC power for the load is converted to DC and then back to AC again to ensure a perfectly sinusoidal output the frequency and voltage of which are established by microprocessor digital control and are independent of the input power source This family of UPS has an automatic by pass device that switches the load to mains power in the event of overvoltages or any other power problems to guarantee continuous power supply even in critical conditions This family of UPS is available in two versions rack or tower O Standard with batteries inside of the UPS The figures below show the various product versions mem Sel Latt
17. a titty w m gi O a L SP122E Rev 000 Siel S p A Page 4 of 36 FR Issued Date 2005 05 27 Tower version MODEL Green Point Nominal power VA 1000 Output nominal i Vac voltage Samen on Imm 231x158x400 HxWxD Weight Kg 14 8 Rack version Green Point MODEL rack Nominal power VA 1000 Output nominal i Vac voltage Dimensions HxWxD 1 Weight Imm 483x390x88 Kg 16 9 Nota 88mm 2U 176mm 4U 2U 2U 3 APPLICATIONS Personal computers Small IT networks Local Area Networks LAN Workstations Servers Point of sale POS systems Data centres Industrial PLCs Cash registers Electrical medical equipment Emergency devices lights alarms SP122E Rev 000 Siel S p A Issued Date 2005 05 27 Green Point Green Point Green Point 1500 2000 3000 220 230 240 340x192x460 231x158x500 340x192x460 19 34 14 35 14 Green Point Green Point Green Point rack rack rack 1500 2200 3000 220 230 240 483x480x176 483x480x176 483x480x868 483x480x838 483x480x88 21 38 13 39 14 483mm 19 Page 5 of 36 FR 4 CHARACTERISTICS Filtered stable and reliable voltage On Line double conversion VFI technology in accordance with regulation IEC 62040 3 with filters for suppressing atmospheric disturbances The on line technology provides the maximum protection for the loads the system is connected to The double conversion stage filters and stabilises the input vol
18. ctivated Frequency converter function The UPS can be programmed to function as a frequency converter using batteries from an input frequency of 50Hz to an output frequency of 60Hz or vice versa Selectable via softwarel Frequency auto selecting The UPS can be programmed to automatically select the output frequency 50 or 60Hz using the input frequency as its reference 50 or 60Hz Battery start up cold start The UPS can be switched on even if there is no mains power supply SP122E Rev 000 Siel S p A Page 6 of 36 FR Issued Date 2005 05 27 FHERGT amp SATETT _ Autorestart programmable automatic restart when the mains power supply returns In the event of a prolonged absence in the mains power supply the system will automatically restart when the mains power supply returns after it has shutdown on reaching the end of its back up time This can be programmed using the software provided with the machine Net Phone and computer protections avoid overvoltage on RJ 11 and RJ 45 connectors Restore input protection The UPS mounts one input standard protection restorable against overloads or short circuits Low consumption Low impact on the mains power supply sinusoidal absorption The UPS absorbs a sinusoidal current from the mains power supply This means that the system has a very low impact on the mains power supply network and as a consequence on the other electrical devices
19. d together the following equipments O UPS O IEC 10A or 16A power supply cable O 2 IEC IEC 10A connection cables O RS232 serial cable O SP122E Rev 000 Siel S p A Issued Date 2005 05 27 O IEC 16A loose plug only for 300 ONLY FOR GREEN POINT RACK 220 300 O BATTERY BOX MARU ULI NUTI O O Fuse 25A GL yy Page 12 of 36 FR GREEN POINT BLOCK DIAGRAM 7 1 Block diagram of the UPS The block diagram of the UPS is as follows 3 Qutput Input Input filter Input PFC Boost Inverter Output filter fuse fuse Output aa AHE Input 7 Restore backfeed relay 4 5 Automatic bypass input protection 6 Battery charger 12 vA DC DC Boost 13 Battery 10 Batteries Battery Expansion 14 16 16 17 Ld a a Ld Intelligent Net Tel RS232 Mimic slot protection interface panel Fig 2 Block diagram 7 2 Options Isolating transformer Back up extension Net Adapter USB Converter LEGEND 1 Restore Input protection 2 Input EMI filter back feed protection Input and output filters for electromagnetic disturbances Back feed protection intervenes if the mains power supply fails isolating the UPS from the input socket to prevent the mains power supply from returning This protection is required to prevent voltage from returning to the line which could put the operator at risk when carrying out maintenance work SP122E
20. ems or to increase the level of protection of the users TN systems The transformer may be connected to the input or to the output of the UPS 9 2 Installation of the battery expansion module Lines di rete ibi BOA NI ARMI Fig 5 9 2 1 Configuration of the battery expansion module Following the installation or one or more battery expansion units the correct total Ah value must be entered into the UPS memory This may be done by using the EXPAND battery expansion program which may be found in the same folder as the UPS management software once this has been installed correctly SP122E Rev 000 Siel S p A Page 21 of 36 FR Issued Date 2005 05 27 MIMIC PANEL 10 1 LED panel The LED panel enables the user to check the UPS status and operating mode It indicates in which mode the UPS is working on mains on by pass on battery it shows the load applied the battery charge level and warns about error conditions On line UPS Unit Vista pannello indicazioni led versione tower e rack ON lt TOWER VERSION Gy RACK VERSION gt eoy b BAT O Load level indicator Battery failure indicator 2 Battery level indicator Load powered by bypass indicator 3 Mains mode indicator Fault Stand by indicator 4 Battery mode indicator Battery low indicator 10 2 Description of the mimic panel dial Led indicator panel This chapter gives a detailed description of all LED indica
21. en mains power returns Remaining battery Battery low alarm charge level setting for the battery low alarm Allows the user to select Output frequency the output frequency Allows the user to select Output voltage the output voltage Selects the voltage range accepted for switching over to bypass Bypass voltage threshold Allow the user to set the Battery capacity capacity of battery SP122E Rev 000 Siel S p A Issued Date 2005 05 27 PREDEFINED Enabled 3 min 50Hz 230 Vac Low 180V High 264V Standard ER 7 2Ah 65Ah POSSIBLE CONFIGURATIONS e Disabled Enabled 1 99 in steps of 1 minute 50Hz 60Hz Auto depending on the UPS input frequency it will operate at 50 or 60 Hz e 220 Vac 230 Vac e 240 Vac Low 180 200 in steps of 1V High 250 264 in steps of 1V The user must set the capacity of battery if the actual capacity Is different from the default value Page 20 of 36 FR GREEN POINT 9 OPTIONS 9 1 Summary table of the options available DESCRIPTION DIMENSIONS HxWxD mm WEIGHT KG Isolating transformer module for 1000 1500 480x158x340 22 Isolating transformer module for 2000 3000 480x158x340 30 ISOLATING TRANSFORMER MODULE Allows the UPS output to be galvanically isolated from the input Allows you to modify the neutral regime for example from TT to TN or from TT to IT to increase the continuity of the power supply IT syst
22. ents within the system such as servers 2 Multiplatform compatibility GreenShield provides you with a standard control and monitoring capability as it uses the TCP IP communication protocol This allows you to monitor computers that use different operating systems from a single console For example not only could you monitor a UNIX server from a PC with Windows 98 you could also connect yourself to UPS systems situated in different locations by using either a dedicated network intranet or the Internet 3 Events scheduling GreenShield allows you to define your own shutdown switch off and on again procedures for the systems that are connected to the UPS Not only does this noticeably increase the degree of security of the system it also allows you to make significant energy savings 4 Message management GreenShield keeps the user constantly informed on the status of the UPS whether locally or by sending messages to users connected to the network It is also possible to create a list of the people who will receive messages by e mail fax and SMS should a fault or a sudden blackout occur 5 Integrated SNMP agent GreenShield contains an integrated SNMP agent for managing the UPS via SNMP This agent is able to send all the information pertaining to the UPS and is capable of generating traps using the RFC 1628 MIB standard This allows you to control the UPS using SNMP compatible workstations such as HP Open View Novell Managewise and
23. etal cabinet with an applied plastic frontal display IP215 lt 2G 77 T15 140 210 RAL 7035 1 mA OUTPUT PROTECTION FIGURES RECOMMENDED VALUES FOR SELECTIVITY Normal fuses GI Normal circuit breakers curve C Ultra rapid fuses UR URG Cable input SP122E Rev 000 Siel S p A Issued Date 2005 05 27 In Rated current 7 In Rated current 7 In Rated current 2 Rear Page 31 of 36 FR GREEN POINT FHERGT amp SAFETY Input connection IEC socket E 4 IEC sockets 1 Rs 232 1 6 prese IEC 1 Rs 232 1 p protezione Net Tel slot protezione Net Tel slot Cooling Forced ventilation Maximum installation 1000m altitude Power derating 10 every 1000m above 1000m above seal level SP122E Rev 000 Siel S p A Page 32 of 36 FR Issued Date 2005 05 27 GREEN POINT 13 GREEN POINT RACK 13 1 Rack models MODELS FRONT VIEWS REAR VIEWS Green Point Rack 1000 1500 VA Green Point Rack 2200 3000 VA Battery box included for models 2200 3000 VA MODELS POWER AUTONOMY min DIMENSIONS HWD mm WEIGHT Kg Green Point Rack 1000 1000 VA 700 W 8 88x483x390 16 Green Point Rack 1500 1500 VA 1050 W 8 88x483x480 21 Green Point Rack 2200 2200 VA 1540 W 12 88 88 x483x480 11 27 Green Point Rack 3000 3000 VA 2100 W 8 88 88 x483x480 12 27 Note 88mm 2U 176mm 4U 2U 2U 483mm 19 SP122E Rev 000 Siel S p A Page 33 of 36 FR Issued Date 2005 05 27 GREEN POINT
24. ge levels 0 9A Ah Zero lt 0 01C lt 0 7 Fuse OUTPUT 220 230 240 V selectable Sinewave 50 60 0 2 Hz selectable Yes with batteries 3 1 1000 VA 1500 VA 2000 VA 3000 VA 700 W 1050 W 1400 W 2100 W 15 5 Same as the mains for variations between 5 1 Hz s lt 20 ms lt 2 lt 6 OVERLOAD TIMES Page 30 of 36 FR GREEN POINT INVERTER OVERLOAD WITH MAINS ON LINE 100 lt Load lt 110 110 lt Load lt 130 Load 150 AC AC efficiency double conversion operation Maximum permanent operating temperature Ambient operating temperature Recommended operating temperature for batteries Humidity Protections Compliance with safety regulations EMC compliance Immunity to sudden Current surges Noise Height mm Width mm Depth mm Weight in Kg with Standard back up integrated batteries Mechanical characteristics Level of protection Resistance to vibrations G Power dissipated with load present W Colour Input differential current 30 30 a 10 VARIOUS 90 40 C 40 C 20 25 C lt 95 without condensation Excessive battery discharge overcurrent short circuit overvoltage undervoltage heat EN62040 1 1 Directives 73 23 EEC and 93 68 EEC EN62040 2 cl B directive 89 336 EEC 6kV 300 following IEC61000 4 5 lt 40 dB A atl mt DIMENSIONS 231 231 340 340 158 158 192 192 400 500 460 460 14 19 34 35 Shielded m
25. he UPS thus providing the user with conceptual information as to the status of the system 5 Automatic saving of the events log and graphical display of the most important values All of the events pertaining to operation of the UPS are saved and recorded thus allowing the user to also control the input voltage the applied load and the remaining back up time of the batteries 6 Alarm notification via e mail and SMS It is possible to configure GreenShield to automatically notify of an alarm via an e mail or SMS message 7 Programming the UPS commands Also allows you to program all the commands that are normally carried out by the user so that these are performed automatically for example shutting down and switching the server back on UPS battery test etc SP122E Rev 000 Siel S p A Page 19 of 36 FR Issued Date 2005 05 27 8 3 Configuration software Configuration Software GREEN POINT UPSTools software allows the user to configure the UPS and provides a full view of the system parameters and status through the RS232 serial port Refer to the paragraph UPS Configuration for a list of the possible configurations available UPS Configuration The following table lists all the possible configurations available so as to best adapt the UPS to user requirements The configuration may be modified only by using the configuration software provided UPSTools FUNCTION DESCRIPTION Automatic Restart Automatic restart wh
26. is permanently overloaded The inverter continues to power the load even when there is a temporary overload If this condition persists the inverter protection Is tripped and the UPS Is switched onto the by pass c When the voltage produced by the inverter exceeds allowed tolerance limits d When the inverter malfunctions BATTERY mode The UPS operates in this mode when the mains power supply fails micro interruptions or black outs During this mode the buzzer emits an intermittent beep a during the autonomy functioning mode b when the back up time limit has been reached Approximately 2 mins from the end of the back up time the yellow battery discharged LED will light up if the management software has been installed the programmed shutdown of the I T applications will begin at this point Error conditions The UPS is designed to function reliably and to automatically guarantee the protection of the applied load However particular operating conditions may exist which the operator should be aware of to ensure that the UPS provides the highest level of performance SP122E Rev 000 Siel S p A Page 15 of 36 FR Issued Date 2005 05 27 GREEN POINT Overload An overload occurs where the applied load requires a level of power higher than that for which the UPS has been designed This situation is indicated by the red overload LED on the load LED bar and by the sound of the buzzer To rectify this
27. tage and reproduces it free of any mains disturbance overvoltages variations in frequency and voltage etc The IEC62040 3 standard defines this technology as VFI Voltage and Frequency Independent because the output voltage and frequency are completely independent of any variation or disturbance to the voltage of the mains power supply High level of reliability versatile and easy to maintain High level of reliability of the UPS total microprocessor control The digital control of the system dramatically improves its overall reliability because it means that a reduced number of electronic components are required the microprocessor alone handles all the functions of an entire electronic control board This electronic control board can be used on a whole number of different machines even those belonging to different ranges thereby increasing the productivity and reliability of the system High overloads the UPS can feed loads up to 150 also in absence of the main Programmed shutdown timer programmable via software This function programmable via software allows you to program the timer to switch the system on and off in a completely automatic fashion Stand by The Stand by function may also be selected In this mode useful for example when the system is being stored the inverter is switched off and the batteries are fully charged When the UPS is switched off the stand by function is automatically a
28. the level required to recharge the batteries It is deactivated when the mains power supply fails 12 Battery protection Fuse 13 Intelligent slot for the auxiliary communication boards connectivity accessory cards 14 Net Tel protection on RJ11 and RJ45 to protectt phone and computer nets from overvoltage 15 RS232 interface for supervision and shut down software SP122E Rev 000 Siel S p A Page 14 of 36 FR Issued Date 2005 05 27 GREEN POINT 16 Mimic panel This is the board that provides the user with all the visual LED LCD and acoustic buzzer signals pertaining to the status of the UPS This board also allows you to control and send commands to the UPS Operating modes NORMAL mode This is the operating mode of the UPS where the power is drawn from the mains power supply The UPS output is switched onto the inverter refer to block diagram and the batteries are kept fully charged Automatic BY PASS mode The UPS enters to this operating mode in the following situations a Immediately after the UPS is switched on when the mains power supply is present the UPS output Is Switched onto the by pass line and the load is powered by the mains power supply This allows you to exceed the applied load in rush current without tripping the fuses to the inverter During this stage the microprocessor ensures that the inverter output is brought in phase with the mains power supply b When the inverter
29. tor panel ICON STATUS DESCRIPTION Red Steady Indicates an fault N rosati The UPS is in stand by mode Lyr Green Steady The UPS is operating on mains power SP122E Rev 000 Siel S p A Page 22 of 36 FR Issued Date 2005 05 27 GREEN POINT Green The UPS Is operating off the bypass Flashing The voltage input is out of the accepted range ENERGY amp The UPS is operating in battery mode and will beep at regular Green Steady RE ili dieani When operating off battery power the UPS signals that it is about to switch off due to end of discharge In this state it beeps at regular intervals of 1 sec See Tab 1 Red Steady Indicates battery failure D Yellow Steady The loads connected to the UPS are powered by the bypass Flashing Represents the estimated percentage of battery charge by 5 LEDs CO s e Green Active pee labicr Hold the ON button down for at least 10 seconds to show the input voltage value See table 3 25 so 75 10 A Seen Red Indicates the of load applied to the UPS in relation to the Active nominal value the last icon indicates overload see table 4 Tab 1 battery status Battery status LED battery working Normal Low oY LED with steady light on 22 LED with flashing light on 1 flash per second Tab 2 battery level Battery LED bar Battery level 1 2 3 4 5 0 20 20 40 40 60 60 80 80 100 7 SP122E Rev