Home
Digital-Analog Converter Module User`s Manual (Hardware)
Contents
1.
2. s Moter drive module etc cH conversion to COM 6002 nl vV GND Moter drive module etc ge TE L i 1 Use a two core twisted shield cable 7 External Dimensions M Cable length 500mm 19 69inch 2 04 5 mounting holes M4 mounting screw oho 60 25 2 37 0 4 0 02 4 315 TT0 16 69 2 72 unit mm inch 11 MEMO Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi machine damage or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties AFor safe use This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi This product has been manufactured under strict quality control However when installing the product where major acciden
3. Configure an interlock circuit in a sequence program so that the system operates safely using the communication status information in the event the data link falls into a communication problem Otherwise erroneous output and malfunction may result in accidents N CAUTION Do not install control cables and communication cables together with the main circuit and or power cables Keep a distance of at least 100mm 3 94 inch Doing so may cause malfunction due to noise interference At power ON OFF voltage or current may instantaneously be output from the output terminal of the module In such case wait until the analog output becomes stable to start controlling the external device INSTALLATION PRECAUTIONS CAUTION Use the module in an environment shown in the general specifications in the detailed manual Using it outside the general specifications may result in electric shock fire or malfunction or may damage or degrade the module Do not directly touch the module s conductive parts Doing so could cause malfunction or failure of the module Fix the module securely using a DIN rail or installation screws within the specified torque range If the screws are too loose the module may drop from its installation position short circuit or malfunction If the screws are too tight the screws may be damaged which may cause the module to drop from its installation position or short circuit WIRING PRECA
4. et RPEED ETRE ESTE nek en NCEE See eR ERED 9 6 1 Wiring PFOCALHONS isois rnea e a r EA E 9 6 2 Wiring of Module with External Equipment 0 0 eee eee 10 7 External DIMENSIONS sieisen e tiie 11 A 5 About the Manuals The following manuals are also related to this product Order them if necessary Detailed Manual Manual name Manual No i Model code Digital Analog Converter Module User s Manual SH 080418E CL2DA2 B 13JP31 Related Manual Manual name Manual No Model code CC Link LT Master Module User s Manual QJ61CL12 PE 13JR62 CC Link CC Link LT Bridge Module type AJ65SBT CLB SH 080362E User s Manual 13JR63 Compliance with the EMC Directive and the Low Voltage Directive For details on making Mitsubishi PLC conform to the EMC directive and low voltage instruction when installing it in your product please see Chapter 3 EMC Directive and Low Voltage Instruction of the User s Manual Hardware of the CPU module to use The CE logo is printed on the rating plate on the main body of the PLC that conforms to the EMC directive and low voltage instruction By making this product conform to the EMC directive and low voltage instruction it is not necessary to make those steps individually A 6 1 Overview This user s manual explains the specifications names and setting of parts wiring and others of the CL2DA2 B digital analog converter module hereafte
5. it to strong shock A module damage may result Be sure to shut off all phases of the external power supply used by the system before mounting or dismounting the module to or from the panel Failure to do so may cause failure or malfunction of the module Touch the grounded metal to discharge the static electricity from the human body before handling the module Failure to do so may cause a failure or malfunctions of the module DISPOSAL PRECAUTIONS CAUTION When disposing of this product treat it as industrial waste A 3 Revisions The manual number is given on the bottom right of the top cover Print Date Manual Number Revision Nov 2004 IB NA 0800290 A First edition This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual 2004 MITSUBISHI ELECTRIC CORPORATION A 4 CONTENTS TAOVEIIOW ss nn ee eau aaa des 1 2 SDE CIICALONG anne nn annee naar an 1 2 1 Performance Specifications cece ee eeeeeee tee eeeeeee tee teeneneeeeteeneee 1 3 Names and Setting of Pats nn de nn A nn 3 Loading and Installations eme ee 4 1 Handling Precautions 5 Connection Cable Wiring Bei IEG aesae kerine e Siena
6. Link LT master module or the AJ65SBT CLB 1 To connect the CL2DA2 B to a VCTF or high flexible cable drop line the CC Link LT flat cable of the CL2DA2 B must be processed to the length of 20cm 7 87in or less 2 The CC Link LT flat cable of the CL2DA2 B can be wired downward using a cable guide The minimum allowable bend radius r is 15mm 0 59in Cable s allowable bend radius r 15mm 0 59in Slide the cable in this direction to install 6 Wiring 6 1 Wiring Precautions To obtain maximum performance from the functions of CL2DA2 B and improve the system reliability an external wiring with high protection against noise is required The precautions when performing external wiring are as follows 1 Use separate cables for the AC and CL2DA2 B external output signals in order to prevent the AC side surge or induction 2 Do not install cables together the main circuit line high voltage cables and or those connected to other than the PLC Noises surges or induction may affect the system 3 Ground the shield wires or shielded cables at one end on the external device side 6 2 Wiring of Module with External Equipment 1 For voltage output ao Moter drive module etc D A conversion 9 1 Use a two core twisted shield cable 2 For current output
7. MITSUBISHI Digital Analog Converter Module User s Manual Hardware CL2DA2 B Thank you very much for purchasing this product Prior to use please read both this manual and detailed manual thor oughly and familiarize yourself with the product MODEL CL2DA U HW MODEL CCLink LT 193m6 CODE IB NA 0800290 A 0411 MEE 2004 MITSUBISHI ELECTRIC CORPORATION SAFETY PRECAUTIONSe Read these precautions before using Please read this manual carefully and pay special attention to safety in order to handle this product properly These precautions apply only to this product Refer to the user s manual of the CPU module used for a description of the PLC system safety precautions In SAFETY PRECAUTIONS precautions are classified into two categories DANGER and CAUTION Procedures which may lead to a dangerous condition D DANG ER and cause death or serious injury if not carried out properly Procedures which may lead to a dangerous condition A CAUTION and cause minor or medium injury or physical damage only if not carried out properly Depending on circumstances procedures indicated by A CAUTION may also cause serious results In any case it is important to follow the directions for usage Keep this manual handy so that you can take it out and read it whenever necessary and always forward it to the end user DESIGN PRECAUTIONS
8. Paracelso 12 20041 Agrate B anan A Tech Co Ltd sty x Milano Italy 898 28 29 30 S V City Building Office Tel 39 039 6053344 Tower 2 Floor 17 18 Rama 3 Road Spain Mitsubishi Electric Europe B V Spanish Bangkpongpang Yannawa Branch Bangkok 10120 Carretera de Rubi 76 80 Tel 66 2 682 6522 08190 Sant Cugat del Valles Indonesia P T Autoteknindo SUMBER MAKMUR Barcelona Spain JI Muara Karang Selatan Block a Utara Tel 34 93 565 3131 No 1 Kav No 11 Kawasan Industri France Mitsubishi Electric Europe B V French Pergudangan Jakarta Utara 14440 Branch Tel 62 21 663 0833 25 Boulevard des Bouvets F 92741 India Messung Systems Put Ltd Electronic Sadan NO 111 Unit No15 Nanterre Cedex France M I D C BHOSARI PUNE 41 1026 India TEL 33 1 5568 5568 Tel 91 20 712 2807 South Africa Circuit Breaker Industries LTD Australia Mitsubishi Electric Australia Pty Ltd Tripswitch Drive Elandsfontein Gauteng 348 Victoria Road PostalBag No 2 South Africa Rydalmere N S W 2116 Australia Tel 27 11 928 2000 Tel 61 2 9684 7777 MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE 1 8 12 OFFICE TOWER Z 14F HARUMI CHUO KU 104 6212 JAPAN NAGOYA WORKS 1 14 YADA MINAMI 5 CHOME HIGASHI KU NAGOYA JAPAN When exported from Japan this manual does not require application to the Ministry of Economy Trade and Industry for service transaction permi Specifications subject to change without notice Printed in Japan on recycled paper
9. UTIONS Be sure to shut off all phases of the external power supply used by the system before installation or wiring Failure to do so may result in an electric shock or product damage A CAUTION Terminal screws which are not to be used must be tightened always Otherwise there will be a danger of short circuit against the bare solderless terminals Perform correct wiring for the module by checking the rated voltage and terminal layout Connecting to a power supply of incorrect voltage or faulty wiring may cause fire and or failure Fix terminal screws securely within the specified torque range Loose terminal screws may cause fire and or malfunction If the terminal screws are too tight it may cause short circuit or erroneous operation due to damage of the screws Make sure foreign objects do not get inside the module such as dust and wire chips Failure to do so may cause fire product failure or malfunction A 2 STARTING AND MAINTENANCE PRECAUTIONS Do not touch terminals when the power is on It may cause an electric shock or malfunction Be sure to shut off all phases of the external power supply used by the system before cleaning or retightening the terminal screws Failure to do so may cause failure or malfunction of the modules CAUTION Do not disassemble or modify the module Doing so may cause failure malfunction injury or fire The module case is made of resin do not drop it or subject
10. evice station Number of occupied stations 2 stations in 16 point mode Dielectric withstand voltage Insulation resistance Isolation Specific isolated area method Across communication system and analog output Isolation Photocoupler specifications Across power supply system isolation and analog output Transformer Between communication isolation system and power supply system 500V AC for 1 minute 500V DC 10MQ Between channels Not isolated Terminal block Direct type 14 point terminal block M3 screw Applicable wire size 0 3 to 1 25mm RAV1 25 3 in conformance with JIS C 2805 V1 25 3 Japan Solderless Terminal Mfg Co Ltd 1 25 3 TG1 25 3 NICHIFU TERMINAL INDUSTRIES Co Ltd Module installation DIN rail installation mounted by screws of type M4 x 0 7mm x 16mm or method lager Can be installed in six orientations Applicable DIN rail TH35 7 5Fe TH35 7 5Al in conformance with IEC 60715 Voltage 24V DC 20 4V DC to 28 8V DC ripple ratio within 5 Module Current power consumption supply Applicable crimping terminal 170mA Current on startup LOMA Protection class IP2X Weight 0 15kg 1 Reference accuracy 2 Accuracy per temperature change of 1 C 3 No of occupied I O points No of occupied stations differs depending on the last conversion enabled channel 4 Power is supp
11. g switch has been changed during operation The NC switch is ON Watchdog timer error Fault in hardware Normal communication Communication cutoff timeout error When the digital setting value is outside the Operation status range display LED The analog output setting switches for all channels are set to be conversion disabled When the analog output setting switch or the HOLD CLEAR setting switch has been changed during operation Communication cutoff timeout error The analog output setting switches for al channels are set to be conversion disabled Flickering at regular intervals 0 4s The station number setting switch was changed after power on Flickering at irregular intervals The terminating resistor has not been attached yet The module and or connection cable are affected by noise OFF Normal communication Description With 10 20 and 40 set the ten s place of the station number With 1 2 4 and 8 set the one s place of the station number Always set the station number within the range of 1 to 64 Setting a number other than 1 to 64 generates an error and L ERR LED turns on Duplication of the station number is not allowed Factory default All OFF Station Ten s place One s place number 40 20 10 4 2 1 OFF OFF OFF OFF 2 OFF OFF OFF ON 3 OFF OFF OFF ON 4 OFF OFF ON OFF Station nu
12. lied by a power supply module adapter 2 3 Names and Setting of Parts The part names and descriptions of the CL2DA2 B are provided in this section 9 Connector is not supplied Please obtain a dedicated flat cable connector 1 4 MELSEG CL2DA2B MITSUBISHI O 8 IE SWTOHWOOE fw RUN L RUN LERR Zo ee O 9 0 0 D EI EN CH av EN EE CRE CEE Pe TES EEET EST PST ECT ES El SIFF ONT ooN oje 7 TEI ON fon TON Ne CONVER Vv IIT i L CH2 Y Ne 6 7 2 3 4 5 Terminal numbers and signal names STATION NO CH1 CH2 NC T 3 5 7 9 11 73 aozo os 421 0 1 2012 CH1 CH1 CH2 CH2 12345678 9101234567 8910 V l V l 2 4 6 8 10 12 14 FG COM COM 7 QOO0CDO0 00 0000000000 1 2 3 4 5 6 7 8 9 10 123 4 5 6 7 8 9 10 Description ON Power supply on OFF The power supply is turned off The voltage drop is too large ON Normal operation Flickering When the digital setting value is outside the range The analog output setting switches for all channels are set to be conversion disabled When the analog output setting switch or the HOLD CLEAR settin
13. mber setting switch 10 OFF ON OF 11 OFF ON OF ON 64 ON ON OFF O ON OFF OFF Example Set the switches as below when setting the station number to 32 Station Ten s place One s place number 49 20 10 8 4 2 32 OFF ON ON OFF OFF ON Sets whether the analog value is held or cleared when HOLD CLEAR communications are interrupted One setting for all channels tti itch OFF CLEAR setting switc ON HOLD Factory default OFF CLEAR Description Set the D A conversion enable disable selection and the output range for each channel Set unused channels to be conversion disabled Setting switches 1 2 4 to 20mA OFF OFF Analog output Ono FOMA QET ON setting switch Conversion 1to 5V ON OFF enable 0 to 5V ON ON 10 to 10V ON OFF OFF 0 to 10V ON OFF ON ON ON OFF ON ON ON Factory default All OFF 4 to 20mA Output Range Conversion disable NC Use prohibited Not available as the system uses it Keep it to OFF If turned ON the RUN LED will flash Terminal block Terminal block for I O signal connections DIN rail hook Used to mount the module to the DIN rail A guide used for turning the CC link LT flat cable for the CL2DA2 Cable guide B downward CC Link LT Connector for connection of the CC Link LT communication line or inte
14. r abbreviated to the CL2DA2 B which is used as a remote device station in the CC Link LT system Confirm if the following is included in the package after unpacking Digital Analog Converter Module type CL2DA2 B 2 Specifications 2 1 Performance Specifications The performance specifications of the CL2DA2 B are shown below For general specifications refer to the detailed manual Specifications Voltage 15 bit signed binary 4096 to 4095 Current 15 bit signed binary 96 to 4095 Voltage 10 to 10V DC External load resistance 1kQ to 1MQ Current 0 to 20mA DC External load resistance 0 to 6009 Accuracy Analog al output Digital Ambient Ambient Max input Temperature Resolution range temperature temperature ont 2545 C 1 0 to 55 C 1 0 characteristics maximum resolution accuracy accuracy 0 to 10V 20mV 40mV relative to maximum EERTE analog output value Oto 5V Oto 4000 49 90 40 4 80ppm C 1 to 5V 10mV 20mv 0 0080 C 10 to 10V 4000 to 4000 4 00 40 4 0 to 20mA p A oto 4000 20 2 20 4 4 to 20mA 40HA 80pA Conversion speed 200us 2 channels Output short circuit Available protection Specifications Absolute maximum Voltage 12 V Current 21mA output Analog output points CC Link LT station type 2 channels 1 module Remote d
15. rface connector module power Sold separately 4 Loading and Installation 4 1 Handling Precautions The following is handling precautions for the module 1 Tighten the mounting or terminal screws for the module to the specified torque as shown below Module mounting screw M4 screw 78 to 108 Necm Terminal block terminal screw M3 screw 42 to 58 Necm 2 When using a DIN rail attach the DIN rail taking the following items into consideration a Applicable DIN rail types conform to IEC 60715 TH35 7 5Fe TH35 7 5Al b Interval between the DIN rail s installation screws Tighten the screws using a pitch of 200mm 7 87in or less when attaching a DIN rail 3 To attach the CL2DA2 B to the DIN rail press the centerline area of the DIN rail hook beneath the module until a click is heard 4 Maintain some distance between the module and other structures or parts at least 10mm 0 39in from the top and 60mm 2 62in from the bottom of the module in order to ensure ventilation and to make replacement of the module easy if the CL2DA2 B is installed to a panel 5 Install the CL2DA2 B on a level surface If the surface is uneven unnecessary force is applied to the printed circuit board causing malfunctions 5 Connection Cable Wiring For wiring of the cable to be connected between the CL2DA2 B and the CC Link LT master module or the AJ65SBT CLB refer to the User s Manual of the CC
16. ts or losses could occur if the product fails install appropriate backup or failsafe functions in the system Country Region Sales office Tel Country Region Sales office Tel U S A Mitsubishi Electric Automation Inc Hong Kong Ryoden Automation Ltd 500 Corporate Woods Parkway Vernon 10th Floor Manulife Tower 169 Electric Hills IL 60061 Road North Point HongKong Tel 1 847 478 2100 Tel 852 2887 8870 Brazil MELCO TEC Rep Com e Assessoria China Ryoden Automation Shanghai Ltd Tecnica Ltda 3F Block5 Building Automation Rua Correia Dias 184 Instrumentation Plaza 103 Cao Bao Rd Edificio Paraiso Trade Center 8 andar Shanghai 200233 China Paraiso Sao Paulo SP Brazil Tel 86 21 6120 0808 Tel 55 11 5908 8331 Taiwan Setsuyo Enterprise Co Ltd Germany Mitsubishi Electric Europe B V German 6F No 105 Wu Kung 3rd RD Wu Ku Branch Hsiang Taipei Hsine Taiwan Gothaer Strasse 8 D 40880 Ratingen Tel 886 2 2299 2499 GERMANY Korea HAN NEUNG TECHNO CO LTD Tel 49 2102 486 0 1F Dong Seo Game Channel Bldg U K Mitsubishi Electric Europe B V UK 660 11 Deungchon dong Kangsec ku Branch Seoul Korea Travellers Lane Hatfield Herts AL10 Tel 82 2 3660 9552 8XB UK Singapore Mitsubishi Electric Asia Pte Ltd Tel 44 1707 276100 307 Alexandra Road 05 01 02 Italy Mitsubishi Electric Europe B V Italian Mitsubishi Electric Building Singapore 159943 Branch Centro Dir Colleoni Pal Perseo Ingr 2 Thailand LEA 10 2308 Via