AquaFlex Pulse Sensor Manual

image

Contents

1. Irrigation Management Made Easy Aquaflex Universal Soil Moisture Sensor Model SI 162 Pulse User Manual Pulse Version The AQUAFLEX Universal Sensor part SI 162 uses the unique AQUAFLEX measurement technique using a 3m 10 long flexible tape to measure a volume of 6 litres 370 cubic inches of soil The Aquaflex Universal Sensor Pulse Version has two separate outputs of soil moisture in volumetric percent and soil temperature These outputs facilitate easy connection to dataloggers irrigation controllers telemetry systems etc These signals may be used separately or simultaneously at any time without any changes to the sensor Sensor Installation Recommendations for sensor installation are given below Your local AQUAFLEX Distributor will be pleased to give advice about the most suitable method of installation for your application It is important that the sensor serial number and the location of the sensor are recorded see Page 6 There are two main methods for installing the sensors the choice of which to use depends on the required installation depth for the sensor For shallow installation eg turf applications the sensor can be simply slit into the turf For installations deeper than 100mm a trench should be dug for the sensor Installation Hints Always unroll the data cable Pulling cables off the side of a roll results in the cable coiling which makes it difficult to install in
2. contract tort or otherwise for any loss including but not limited to loss of profits and consequential loss of any kind whatever arising out of any published material or in connection with the performance or use of Aquaflex The serial number marked on each Aquaflex Sensor must be recorded and quoted for warranty claims AF 2223 00 14 May 2015 8 STREAT INSTRUMENTS Streat Instruments UK Office 4A Expo Place Garnett Group PO Box 24071 Unit 6 Great Russell Court Christchurch Fieldhead Business Centre New Zealand Bradford BD7 1JZ United Kingdom Ph 64 3 384 8900 Ph 44 1274 733 145 Fax 64 3 384 8901 Fax 44 1274 736358 mail streatsahead com mail streatsahead com www streatsahead com www streatsahead com AF 2223 00 14 May 2015
3. moisture and temperature pulse outputs can be configured in two ways a AOto 5v pulse driven both high and low b An open collector output See the specifications below for precise electrical details b Timing The pulses per minute of the moisture and temperature outputs can be configured over virtually any sensible ranges In the default configuration these ranges are as follows Pulses Per Minute PPM Volumetric Soil Soil Temperature Moisture 10 0 10 C 14 F 130 60 50 C 122 F These are the pulse rates for sand silt and sandy and silty loams For clay rich soils use the formula below For sand silt and sandy and silty loams Moisture 0 5 x pom 10 For clay and clay loams Moisture 4 9 0 51 x pom 0 0026 x ppm 0 0000205 x pom For temperature Temp TC 10 0 5 x ppom 10 Electrical Connections Res sensor ponerse 60we5VaKR SSS Note The Sensor Ground and pulse cores are connected internally within the sensor therefore this sensor is not suitable for situations that require fully isolated outputs AF 2223 00 14 May 2015 7 Sensor Fault Indicators If a fault occurs the sensor outputs special signals as follows Signal pulses per minute Fault condition 0 ppm A broken wire or possible failure in the sensor Check the wiring and repair Contact your distributor if wires are intact 2 5 ppm Moisture reading out of expected range If this output continues c
4. e in the bottom of the trench and cover it with soil Compact down with feet as you go so that the cable is flat and straight along the bottom of the trench 3 Connect the sensor s to the datalogger or controller see details in Electrical connections below 4 Use the cable ties to keep the data cable against the post so that cows or other animals don t chew it 5 Near the AQUAFLEX end leave the ditch open as it is easier to install the AQUAFLEX with flexibility in the data cable Installing the Upper Aquaflex Sensor Refer to Figure 1 for the location of the trench for the Upper Sensor When digging the data cable trench take note of how deep the topsoil is and where the majority of the roots are The top sensor should only be installed within the majority of the root zone and within the topsoil as a general rule we install the sensor to 300 mm at the deepest This removes the effect that a sub soil with different water holding capacity can have on the moisture measurement as the Aquaflex takes an average over the whole sensor 1 Lay aplastic sheet or similar alongside the area where the trench is being dug Dig out the turf and lay on the opposite side from the plastic sheet If soil is falling from the turf then it would be advisable to lay the turf onto the plastic sheet AF 2223 00 14 May 2015 3 Start at the shallow box end Dig down to 50mm The box contains the thermometer so needs to sit at 100 mm depth to give a sta
5. h from behind each side of the slit to close it Pack from the sides to recreate original density and remove air pockets Repair and smooth as necessary Apply a liberal amount of irrigation water to allow the sensor to bed in and remove air pockets Run the data cable in a slit or trench to the desired location e g the Datalogger or Controller Note ensure that the cable is buried deep enough to avoid damage during maintenance 7 7 y Completed Installation AF 2223 00 14 May 2015 2 Deeper Installations e g Agriculture or Vineyard If you have any questions please call Streat Instruments or your local agent Make sure you install in a place that will give readings that are representative for the whole irrigation area Please note that we recommend that the Aquaflex data cable is installed 90 degrees from the fence line and the Aquaflex sensor runs parallel with the fence See Figure 1 0 below Aquacom Unit attached S to post de Upper Aquaflex Sensor Aquaflex Data Cable 3 NN to 20m Lower Aquaflex Sensor Figure 1 Aquaflex Installation Diagram Fenceline Installing the data cable 1 Dig a data cable trench 400 500 mm deep from the base of the post out into the paddock This trench may be 3 metres 10 meters or 20 metres long depending on the length of data cable supplied with the Aquaflex Remove the turf and place on one side of the trench and the soil on the opposite side 2 Lay the data cabl
6. ndard temperature reading Remove the soil in its natural layers horizons and lay it out on the plastic sheet Dig a sloping trench from 10cm to the bottom of the topsoil across the 3 metre length of the Aquaflex Sensor Single Sensor Installation Ground Surface 50mm 100mm Nominated depth Once the trench has been dug make sure that the bottom of the trench is on an even slope Lay the Aquaflex Sensor down in the trench in its edge so that water cannot sit on the top of the sensor Shovel the soil back into the trench placing it around the sensor to give good contact with the sensor Make sure you apply the right layer of soil and stones in the appropriate order Move the soil around before packing it down to ensure any air gaps have been filled in by loose aggregates Pack tightly with either your feet or post hole rammer depending on the surrounding soil profile you want the soil to return to its original density as best as possible Make sure that you don t ram or stand on the Aquaflex as it may bend over or be damaged Stones are to be replaced in the trench as best as possible not directly beside or on the sensor as this may cause air gaps and possible sensor damage Place the stones in the trench where they will not cause damage to the sensor with compaction Insert a paver at each end of the Aquaflex sensor put 200 mm further out than the real end Installing the optional lower sensor Refer to Fig
7. ontact your distributor Note sensors will often give this output when in air before burial this is normal Low battery or supply voltage Replace the batteries or check power supply 7 5 ppm Critical sensor settings have been lost Contact your distributor Specifications Power supply voltage 6 0 to 26 Volts DC Power supply current 1mA average 150mA peak for 60 milliseconds during measurement Pulse outputs Driven pulse Voltage levels Ov 5v Sv max output current 2mMA Open collector Max external pull up voltage equal to sensor supply voltage Max sink current 200mA 1 5 seconds after power supplied typical 2 second maximum Time between measurements 1 minute if power applied constantly Operating Temperature 10 to 40 C 14 to 104 F Soil Moisture Measurement Range O to 60 volumetric moisture content Precision Repeatability 0 5 volumetric moisture content Accuracy 2 volumetric moisture content Soil Temperature Measurement The temperature is measured at the body of the sensor not along the moisture sensing cable Range 10 to 50 C 14 to 122 F Accuracy 0 5 C 0 9 F Conditions of Use Aquaflex must be installed as specified Use of Aquaflex data is entirely at the discretion of the user and should therefore be subject to current best practice principles of soil moisture management and agronomic management Neither Streat Instruments nor its Distributors shall be liable whether in
8. the trench Install the data cable in a metal or plastic conduit if there is risk of damage from spiking etc NOTE The flat sensor cable must not be similarly protected Ensure that the sensor cable is at least 150mm away from any foreign objects Make sure you install in a place that will give readings that are representative for the whole irrigation area If you have any questions please call Streat Instruments see footer below or your local agent Aquaflex NZ a division of Streat Instruments Limited 4a Expo Place PO Box 24071 Christchurch New Zealand Phone 64 3 384 8900 Fax 64 3 384 8901 info aquaflex co nz www aquaflex co nz Shallow Installations e g Turf 1 Select and mark the position of the sensor with a string line Position the sensor where it can be easily located in future e g on a marker line on a sports field or in a position on a golf green marked by sight markers e g between two known points Note If the soil is sandy it is easier to install the sensor when the soil is wet because it holds together better With a turf cutter or sharp flat blade carefully cut a slit in the turf Carefully insert the sensor into the slit to the desired depth Note The sensor must be installed on its edge For the electronics block at the end of the sensor carefully peel back sufficient turf to create a slightly larger and deeper cavity in which to bury the block Fold the turf back Gently pus
9. ure 1 for the location of the trench for the Lower Sensor in the opposite direction to where the Upper Sensor is installed from the end of the data cable trench 1 2 As with the upper sensor remove the soil in its natural layers horizons Dig the soil out in the determined layers and lay out on a plastic sheet ensuring that the soil layers do not get mixed up Dig the trench to a depth which is below the root zone this is most often 500mm in a grass pasture The lower sensor usually gets installed horizontally at one depth ie not on a slope Follow steps 5 to 9 as above Once the Aquaflex trench has been filled complete filling the cable trench and replace the turf AF 2223 00 14 May 2015 4 Helpful Pictures a ts at ESA p end LAI Soil removed and placed in three layers Top sensor installed to 250mm at the dee AF 2223 00 14 May 2015 Documentation i AQUAFLEX Records Sensor 1 S no Sensor 2 S no sensor 1 Depth 50 to mm Sensor 2 Depth mm Sensor Cable Length m Top sensor installed to depth mm Topsoil depth mm Topsoil Type Topsoil Stone size mm Topsoil Stone Subsoil Type Subsoil Stone size mm Subsoil Stone Upper Sensor _ to mm Data Cable m Lower Sensor 500 mm Please draw an Arrow to show North on the diagram Note the upper and lower can be installed in either direction AF 2223 00 14 May 2015 Details of the pulse output signals a Electrical The