Home

Monitoring and Control System Implementation - MoCo

image

Contents

1. MoCoWorks 2010 877 360 2582 2010 06 20 106 of 116 100 Digital outputs are open collector transistors that pull down to 0 volts when fed with a logical 1 Because MoCo rights the logic a logical 0 from MoCo will cause a zero volt pulled down output When driving a solid state optical relay attach the relay s terminal to 5 volts and feed the negative terminal from the digital output This takes advantage of the board s strong pull down capability Use a solid state optical relay like Opto 22 Z120D10 that is guaranteed to turn on with 3 4 DC volts minimum Hooked up in this manner the logic will be inverted Consequently inversion will likely be desirable in MoCo Alternatively instead of using a simple terminal strip output board you can use a LED board or relay board all of which are available from Phaedrus Limited Manuals software and product information can are available at Phaedrus web site http www emacsys com As with any evolving high tech product be aware that the manufacturer s manual may not match the firmware version of the hardware you are using MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 107 of 116 Appendix E Troubleshooting E 1 General The mocom dump commands and unix style grep are arguably the most useful general purpose tools for troubleshooting a MoCo system A mocom dump command looks like this mocom rw OutTemp dump D
2. Basic point definition p sampleTime Point ID for software and reports name Sample Time Clock Point name for reports desc Sample Calc Time Clock Point Long point description units onoff Units for report display driver time_clock Handler subroutine name handler mocod9 Daemon 9 the handler for this point interval 60 Normal interval between evaluations If 0 then no interval processing MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 94 of 116 By default Time Clocks are digital but they can be analog if digital 0 To force point to be analog See parms in sampleIn cfg Specific to Time Clocks times is a required parameter times 0 wd0530 0 ss0600 1 wd1900 1 ss2000 Event times list pulse _sz Length of pulse in seconds if pulses specified in event list MoCo processing control All are optional amp assume reasonable defaults do_next pointl point2 point3 For rapid processing of result cng filter 1 If 1 do_next on leading edge only 1 trailing only enable out 1 If 1 do_next to output points 0 block trig of outs interval 0 If 0 no interval processing intv_only 1 If 1 process only on the interval disable 1 If 1 then totally disable the point stealth 1 If 1 don t show by default on reports Timers Aavailable with any kind of point all are optional timer
3. MoCoWorks 2010 877 360 2582 2010 06 20 2 of 116 5 7 3 Ladder Logic calc_ladder_logic 5 8 Counters and Stopwatch Timers 5 9 Creating Scenes 6 Alarms 6 1 Alarms Overview 6 2 Configuring Alarms 6 3 Handling Alarms 6 4 Alarms Triggering Shell Commands 7 Reports 7 1 Reports Overview 7 2 Status Reports 7 3 History Reports 7 4 Shell Scripts for Common Reports 7 5 Graphic Web Status Reports 7 6 Custom Database Reports 8 Programming State Machine Points 9 Example Task Snippets 9 1 Turn On Multiple Lights with Distributed Switches 9 2 Duty Cycle Calculation 9 3 Door Opening Counter 9 4 Scenes and Sequencing 10 Software Maintenance 10 1 Backups 10 2 Log FIle 10 3 Database 10 4 Shell Scripts 11 Basic Transducer Electronics 12 Example Projects 13 Creating a Web based User Interface 14 Configuring an Enterprise level Distributed Network 15 Writing a Custom Perl Snippet 16 Writing a Driver MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 3 of 116 Appendix A Parameters A 1 System wide Parameters in moco ini File A 2 Point Parameters in cfg Files A 3 Report Parameters in rpt Files A 4 User Parameters in usr Files Appendix B Sample cfg Files B 1 Input cfg File Sample B 2 Time Clock cfg File Sample B 3 Calculation Expression cfg File Sample B 4 Calculation Ladder Logic cfg File Sample B 5 Input cfg File Sample Ap
4. echo echo exit mocod stop xyz where xyz your initials fi echo Shutting down all MoCo handler daemons mocom 1 0 shutdown 5 Shutting down mocod0 mocom 1 1 shutdown 5 Shutting down mocodl mocom 1 2 shutdown 5 Shutting down mocod2 On a unix style operating systems enter the command chmod 755 moco stop to make anew script executable Enter moco stop on the command line to run the script It will safely shutdown the three handlers A moco start script is shown below It is more complicated because a person would not want to accidentally start another copy of the same handler if the handler is already running This simple script displays any running mocod handler daemons and gives the operator the opportunity to quit the script if daemons are seen to be operating bin bash mocod start Starts up all three mocod handler daemons Example mocod start rw Check for a cmd line parameter operator s initials if 0 then echo Ww echo This script will start up all mocod daemons USAGE echo MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 83 of 116 echo mocod start xyz where xyz your initials echo exit fi Display mocod handler daemaons that are currently running here echo n W echo Please be certain that no mocod daemons running echo In other words NO mocod 0 mocod 1 etc see below ps Af grep mocod Display
5. MoCo Monitoring an d Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 96 of 116 sampleLadr cfg Sample Calc Ladder Logic Point Basic point definition p sampleLadr Point ID for software and reports name Sample Lad Logic Point name for reports desc Sample Calc Ladder Logic Point Long point description units onoOff Units for report display driver calc ladder logic Handler subroutine name handler mocod9 Daemon 9 the handler for this point interval 30 Normal interval between evaluations If 0 then no interval processing By default Ladder Logic is digital but it can be analog if digital 0 To force point to be analog See parms in sampleIn cfg Ladder Logic rungs encoded as follows rung 0 predawnT amp amp temp in lt 70 rung 1 morningT amp amp sun morn or amp amp temp in lt 68 rung 2 aftnoonT amp amp temp in lt 72 rung 3 night amp amp It s ok to use another line temp out lt 20 amp amp temp in lt 65 temp in lt 63 MoCo processing control All are optional amp assume reasonable defaults do_next point1l point2 point3 For rapid processing of result I cng_filter 1 If 1 do_next on leading edge only 1 trailing only enable out 1 If 1 do_ next to output points 0 block trig of outs interval 0 If 0 no interval processing intv_on
6. MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 97 of 116 B 5 Output cfg File Sample sampleOut cfg Sample Output Point Basic point definition pointS Optional source point that can be specified ptA ptB ptc Source variables for output file driver only If parm force is true then force output to this value source pt variables val_force p sampleOut Point ID for software and reports name Sample Output Point name for reports desc Sample Output Point Long point description units degF Units for report display device _id TTL2 Output port ID channel 1 Some devices have a channel ID net_addr gt ini net_addr_webcontrol Actuator s web addr in moco ini driver output_webcontrol Handler subroutine name handler mocod9 Daemon 9 the handler for this point Output specific parameters all of the following are optional cmd_outf my scriptl Execute script if output file written force 1 If 1 force output to be value of val_force gate 255 Gates output Multiplies by the gate value invert If raw input is inverted and displ no_ output pointZ Blocks output if 1 If 1 overrides global blk out file filel Name of output file for driver output file pulse _sec 10 Pulse length in seconds if pulse trig specified pulse trig up Pulse trigger direction up down both snap f
7. 1000 Timer value usualy read only start pointXx Trigger s timer start on leading edge of true stop pointX Trigger s timer stop on leading edge of true reset pointY coing pt Reset counter on leading edge of true These read only parameters are specific to calc points not for cfg time_intv Precise time in sec for previous interval time_now Precise time in sec when the calc is performed time_prev Precise time is nsec when the previous calc was performed Counters Available with any kind of point all are optional counter Current count on counter Usually read only counting pointI Enables counting Most often run time controlled count_up pointdJ Count up on leading edge Run time controlled count _down pointK Count down on leading edge Run time controlled reset pointL Reset on leading edge Run time controlled ADDITIONAL USEFUL PARAMETERS See sampleiIn cfg for examples of the following other useable parameters alarms shell command triggers and overrides See MoCo doc especially Appendix A for complete list of parms NOTES Everything is case sensitive Quote any data that contains spaces Order of name value variables is not important B 3 Calculation Expression cfg File Sample sampleExpr cfg Sample Calc Expression Point Basic point definition p sampleExpr Point ID for software and reports name Sample Expression Point name for
8. If you need more such as analog and digital history and advanced HVAC control then you probably also need a system like MoCo Ina factory environment X10 would not be used but Insteon might cautiously be used in some commercial situations The ISY 991 can control AC devices with X10 and Insteon protocols X10 is typically one way you can control a device but you cannot in most cases determine its actual state on or off X10 communicates over the building s AC wiring although wireless remote control devices for X10 are commonly available Insteon takes the art of residential control somewhat further by providing two way communications and by providing dual band power line communications and air wave communications in their network It s mesh architecture also routinely repeats signals Insteon is the more reliable of the two and it effectively covers more square footage Because X10 is much older however the choice of devices is larger Some Insteon devices have X10 capability The two can inter operate to some degree The ISY 991 is targeted at Insteon but it has essential X10 capabilities The ISY 99i definitely facilitates interoperability and its interoperability features are improving with newer firmware In order to cover more than a couple thousand residential square feet with X10 extra hardware is needed to repeat signals Both X10 and Insteon need to be configured such that they cover both legs aka phases o
9. OAT This point s ID name Outside Air Temp Short name desc Outside Air Temperature Long description device_id DB000801214E9B10 Unique l wire ID net_addr gt ini net_addr_ha7net Indirect to network address the IP is in the ini file like http 192 168 0 240 driver input_ha7net_temp Driver subroutine name handler mocodod Pgm clone instance daemon MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 16 of 116 Data parameters units degF Physical units scale 1 8 C to F For conversion or calibration offset 32 C to F For conversion or calibration avg_size 5 Number of samples for average resolution 1 Resolution here a 1 s digit ramp 0 2 Limit ramp to 2 per min hysteresis 2 Hysteresis eliminates jitter interval 60 Scan interval 60 seconds A comprehensive description of required recommended and optional parameters for each kind of point can be found in Appendix A Appendix B provides similar information organized as sample cfg files After verifying functionality of the I O hardware and sensor with a browser verify that the new sensor works with a cfg file containing parameters similar to the above If mocod is running at the moment shutdown the daemon with mocom or kill the daemon by striking a control c In the future please use mocom todoa shutdown 1 whichis less likely to glitch the d
10. alarm Older WebControl documentation erroneously states that the analog input range is 0 5v It is actually 1 10v Input impedance is unspecified but leakage current has been measured at roughly 10ua The 10 volts is spread across the A D converter s 1024 10 bit resolution So that all analog input drivers are consistent MoCo s driver converts the 0 1024 to 0 100 The user can use MoCo s scale and offset parameters to scale to something else from there Digital input ports are specified at 0 5 volts TTL compatible Low voltage is logical 0 and high voltage is logical 1 The threshold is unspecified If 5v is applied to the input to produce a logical 1 the current draw measures 0 5 ma Consequently if your design uses a transistor or set of contacts to pull the input to ground consider adding a pull up resistor of 1K to 3 3K between 5v and the digital input Digital outputs are said to be TTL compliant Consequently the outputs will not directly power conventional mechanical relays without an additional transistor The WebControl outputs have stronger pull down than pull up capability Therefore when driving a solid state optical relay attach the relay s terminal to 5 volts and feed the negative terminal from the WebControl digital output so that the stronger pull down capability will drive the device Use a solid state optical relay like Opto 22 Z120D10 that is guaranteed to turn on with 3 4 DC volts minimum Hooked up in this
11. input_ha7net_temp A input Temperature 1 wire input via HA7Net input _isy99i D input Input Insteon and X10 device states via ISY 991 input_owserver D input Various l wire inputs via OW Server input _web_ page A input Inputs data in name value format from web input_webcontrol A D input Inputs analog and digital data via WebControl input_manual D input Inputs manual or programatic data output_emacsys D output Outputs digital data via EMACSYS output_ha7net_digital D output Digital 1 wire output via HA7Net output_file A output Outputs data to a file in name value format output_isy99i D output Output to Insteon and X10 devices via ISY 991 output_webcontrol D output Outputs digital data via WebControl time_clock D time Creates time clock events Note that the analog digital processing indicated above is the driver s default choice A user can override the default by setting parameter digital to 0 to force analog or to 1 to force digital processing MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 99 of 116 Appendix D I O Bridges When dealing with I O bridge hardware be aware that a manufacturers documentation might not include all the information that is needed The documentation may not be synchronized with the firmware and it may contain errors Besides reading the manufacturer s manual a must the user is often expected to search wikis search forums solicit user assistance via
12. TClocklo 1 1 Onoff 13 10 TClock1it 1 1 Onoff 13 10 testCalc 1222 6 1222 none 13 10 ladderc 1 1 logic 13 10 After awhile run report program mocor to view history of all points written to history within the MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 20 of 116 last four hours mocor Or add the e switch to pass through the FormEdit screen Try again with the e switch Strike enter to step through the FormEdit screen At any edit screen field you can type h space h to see a brief help screen that explains how to work the edit screen Just walk down through the screen by striking enter until at the bottom until mocor executes the report displaying the report as before For command line help enter mocor h This is a way to get help for any MoCo program If all of the above worked as expected congratulations You have a functional MoCo system 2 8 After Initial Startup After initial startup you are ready to begin adding the remaining sensors Seasoned control engineers have learned that for applications more complex than lighting or irrigation it is wise to monitor for awhile before implementing control logic This is because monitoring reveals information that will impact control design decisions In other words for complex projects get the monitoring working first If the system is to have more than several dozen points consider how to divide the sensors b
13. avg_size Number of readings in running average default 1 resolution How fine the value like 1 5 2 default 1 bad _ high Block data above this value from being processed bad_low Block data below this value from being processed high limit Prevent a converted value from going above this limit low _limit Prevent a converted value from going below this limit ramp How much to limit changes per minute default none hysteresis Eliminates jitter Default is 1 8 of resolution scale For calibration and conversions default 1 offset For calibration and conversions default 0 Analog data is processed and conditioned in the following order 1 Scaling and calibration 2 Checking for bad data data that is way beyond reasonable bounds 3 Applying high and low limits clamping the value s range 4 Running average for history value 5 Limiting ramp limiting rate of change per minute for the clean and history values 6a Hysteresis for the history value 6b 1 10 the value of hysteresis for the working value 7a Rounding the history value to specified resolution 7b Rounding the working value to 10x finer resolution than the history value 8 Programatic overrides 9 Manual overrides 10 Trigger shell commands 11 Alarms The number of decimal places for a value is automatically determined from the resolution parameter For example a resolution of 0 2 will create clean history values that look like 69
14. by sending a null from _mocom MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 25 of 116 Note that if the point does have an invert configured the output 1 or 0 will display as 1 or 0 in status reports or history reports The decimal points inform a trouble shooter that hardware and software values are inverted because hardware voltages are inverted Programatic overrides are performed by MoCo as determined by the point s parameters The results from non output digital points can be forced to fixed values or gated Programmatically setting force 1 forces the value or expression in the val_force parameter to override the point s result The force val_force and gate parameters can be fed by numbers other point variables or expressions like daytime amp amp shutdown For non output analog points the gate value is multiplied by the point s value to create clean and working result values If gate is 0 the the result of a point is forced to 0 If gate is 1 the point is enabled to work normally For output points gate is applied to the value that is sent to the output device If the output is digital the resulting value is converted to an integer For safety reasons force val_force and gate are inhibited from altering internal results on output points This is because a point s value could be made to appear different in reports than the actual state of the outpu
15. e DS2450 Quad A D Converter At the time of this writing a manual for OW Server has not been available from EDS The recently created MoCo driver supports the 1 wire temperature sensors and the 1 wire DS2406 digital I O devices mentioned above Support for more sensors is expected with the next MoCo software release The OW Server configuration screens are more user friendly than the HA7Net screens because they require a user to do less jumping from screen to screen The HA7Net screens offer more options such as output capability The OW Server constantly polls its inputs at approximately a 2 second cycle time which can offer a speed advantage in some cases Unlike the HA7Net the OW Server has no on board strapping that enables the user to select 5 volts or ground level to be supplied on pin 6 of the RJ 12 1 wire connectors Other than the differences described here the OW Server is similar to the HA7Net When making a purchase decision pay close attention to the devices supported by each and keep in mind that the OW Server apparently does not output to 1 wire devices See the above HA7Net description for additional setup details For current information check the Embedded Data Systems web site at http www embeddeddatasystems com D 3 WebControl The WebControl BRE bridge is a product of CAI Networks Inc It is a 4x4 inch circuit board that offers a big bang for the buck It is versatile cost effective choice for hobbyists an
16. manner the logic will be inverted Consequently inversion will likely be desirable either in WebControl or MoCo In order for MoCo to work with WebControl login security needs to be turned off in an administration screen Otherwise WebControl will not play with MoCo If the added security is desired try using a URL address like http admin password 192 168 0 240 There have been reports that a 6v power supply is inadequate Therefore use a good 7 5 9v supply A 12v supply will overheat the regulator device unless a heat sink is added to the regulator WebControl is configured via an ethernet connection It has its own web server and web page Login requires a user name and password The defaults are admin and password respectively A WebControl manual can be downloaded from the CAI Networks web site http www cainetworks com As with any evolving high tech product be aware that the manufacturer s manual may not match the firmware version of the hardware you are using MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 103 of 116 D 4 ISY 99i The ISY 991 is a server in a small black box that is designed primarily for high end home automation It raises the capabilities of X10 and Insteon power line control devices to a much higher level If your application is home automation that is limited to lighting sprinkler control and such then the IS Y 991 may be all you need
17. results tmp PARM ERROR none rpt_file 1 Default parameters and parameters from the command line will be immediately visible in the data entry fields of the form New parameters are entered at the bottom of the screen The form is displayed directly above the computer s cursor The long dashed line is FormEdit s cursor that shows the current field and indicates where the data will appear once it is entered If you want to alter or enter data for the current field just strike enter The cursor will move to the next field If data is to be entered for a field enter the data and strike enter The new text will replace whatever was in the field and the cursor will move down to the next field MoCo programs usually sniff a parameter as it is entered to see if it passes the smell test If the parameter has a flaw FormEdit will lock to the current field until acceptable parameter data is entered Error information is displayed at the bottom of the form When you get past the last FormEdit field FormEdit will display Strike Enter if done editing b to edit more q to quit If all the parameters are as you wish strike the enter key and the program will run Or continue editing by striking b enter b stands for backup MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 18 of 116 IMPORTANT All non data edit and navigation commands begin
18. temp in lt 63 units OnOff interval 60 snap_fmt 6 c In the above example ladder logic contacts were used to test for temperature levels MoCo ladder logic can also test for text This is useful when testing for a particular alarm condition If you want to test for alarm conditions then the conditional logic for the contact might look like this MyTemp alarm eq H Returns true if alarm H MyTemp alarm ne Returns true if any active alarm When ladder logic is being evaluated evaluation begins with the lowest available rung rung_1 It continues to evaluate rungs until a true condition is encountered or until no more rungs and then it MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 53 of 116 quits Up to a couple missing rungs are tolerated but no more than two The maximum number of rungs is 100 A non zero rung result is considered true and a zero or null is considered false The last true value that is evaluated on the first true rung is returned as the ladder logic value MoCo leverages this interesting characteristic of the perl language it returns values other than 0 or 1 if the last true value is something other than 1 Here is an example analog heater control where this characteristic can be quite useful rung 1 t33 alarm eq H amp amp 1 Cannot return 0 so do l rung 2 t33 gt 72 amp amp 20
19. to the ini file like this gt ini cmd_alarms The mechanisms described in this paragraph enable the implementer to centralize shell commands which can be a way reduce maintenance and human error on large systems The following parameters can contain shell commands cmd_c_0 A point s clean value has gone false cmd c_1 A point s clean value has gone true MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 26 of 116 cmd_o 0 A user has moved a point out of override cmd_o 1 A user has moved a point into override cmd aH Alarm H for example has been triggered and latched See the alarms chapter for a detailed description cmd_outf A file has been output from driver output file Example cmd_o 1 override mail sh TClockl Say point is now overridden All points have the ability to be alarmed assuming that alarms for the point have been enabled Up to 28 different user configurable alarms for different situations can be placed on a point and each one having its own priority Alarm thresholds and alarm text are setup in the point s cfg file A point s value and rate of change can be set to trigger an alarm Each alarm can be setup to latch or not Latched alarms will stay on until a user clears the alarm via communication program mocom Whenever a point s alarm has been triggered the point s highest priority alarm character is displayed in history and status
20. up to 40 characters digital 0 for analog point 1 for digital Default 0 or 1 is set by individual driver disable to disable the functionality of a point almost as though it does not exist do_next List of point or points to process immediately next doing pt Used to reset timer counter so that the reset occurs after the point is run driver Name of the subroutine that does the work for for this kind type of point enable out Enables do_next triggering of output points If not utilized default is enabled force If true force result or output to become the value from val_force gate Gates the point s result See details at analog and digital points Default is null handler Instance of mocod daemon to use for this point mocod0 is default interval Scan interval seconds Default 60 seconds If 0 then normal scanning is disabled intv_only If 1 the scheduler will run the point s driver only on the interval logic_cng Reports a logic change 1 for false gt true 1 for true gt false See cng filter name Point name up to 20 characters Recommended p Point d like IAT orHeat3 Must match cfg file 8 or less characters point type input output calc or time Set by mocod reset Resets timer counter to 0 on the leading edge of a value going from false to to true MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 88 of 116 start Starts the timer upon the leading edge
21. 75 Humw Humidity WX 17 08 0 mph WSpdw Wind Speed WX 17 10 1 OnOff TClocklt Time Clock 1 17 10 1 OnOff TClocklo Time Clock 1 Out 17 10 1 OnOff Tclono On pulse fr TClockl 17 10 61 F GATW GlassRm Air Temp WX _ 17 11 0 OnOff Tclono On pulse fr TClockl 17 11 30 08 in Barow Baro Pressure WX Report options are similar to mocos except there are more of them and mocor provides the benefit of an edit screen Consequently mocor offers three ways to enter report parameters the command line an optional edit screen or via rpt files As with other MoCo programs enter mocor h to view a help screen that explains the run parameters Here s what you get mocor pl reports history of IO points To display help enter mocor pl h MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 67 of 116 Usage mocor switches report file point mask duration more Switches hyphen followed by one more of the following characters Display FormEdit parameter edit screen Report everything covered by rpt file or point mask The default scope Report all points that have active alarms Report all points that have defined alarms Report all points that have overrides Report all points with any kind of remark Report all points with anything unusual 4 Print 4 tabular columns t7 columns Show only stealth points S Also show stealth points Batch No dialogue for script processing Delimited fields for
22. 8 70 0 70 2 70 4 and so on With the 0 2 resolution an internal raw value of 70 333333 is written to history as 70 4 For internal values and status displays MoCo uses a working value that is 10 times finer in resolution than the history value Continuing with the previous example the internal working MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 23 of 116 value is rounded to 70 34 note the additional decimal place Proper selection of the resolution parameter is desirable for a number of reasons Most engineers and scientists would agree that there is no point in displaying higher resolution than the accuracy of the sensor Some would go so far as to say that extra digits are a form of lying If for no other reason use appropriate resolution to keep the database from being flooded with redundant data ALERT When viewing status reports from the snapshot table with mocos you will see both the higher resolution working value and the clean value that was last written to history If the point has an unusual resolution like 0 3 the clean history value may not appear to round correctly Rest assured that it is being rounded exactly as requested in increments of 0 3 Keep in mind that both values are captured to the snapshot table whenever one of the values changes to an new value Of course the high resolution working value is captured to the snapshot database table much more frequ
23. Analog data can be highly processed as described below Digital data is minimally processed in a manner that does not change the appearance of the number unless there is an override of some kind or the true false sense of the value is inverted due to the invert parameter Unlike analog points a digital point s clean MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 22 of 116 and working values are identical Normally a user does not have to consider whether or not to specify analog or digital because the driver automatically selects the most appropriate type Why might a person want to deviate from the default A time clock is digital by default However if a user forces the time_clock to analog the analog conditioning parameters shift into gear With appropriate selection of ramp and interval a time clock can create a ramped output To override a driver s default data type set the point s digital parameter as follows digital digital 0 For analog processing resolution hysteresis etc 1 For digital processing true false can be inverted MoCo s analog data conditioning mechanisms are a series of algorithms that compress data and render it human friendly All analog points can have their data processed by the algorithms The following conditioning parameters can be configured for a point in it s cfg file interval Number of seconds between readings default 60
24. HAT c 4 Setup any other desired point parameters such as units resolution hysteresis etc An example ofa calc functions point which calculates the average of three temperatures is shown below IATavgC Average of Inside Air Temperatures p IATavgC name Inside Temp Avg desc Average of Inside Air Temperatures driver calc_functions function avg parameters IAT IATW w HAT c units degF interval 90 avg_size 1 resolution 5 hysteresis 06 interval 10 snap_fmt 5lc 5 7 2 Math Expressions calc_expression In situations where calc_functions does not meet meet a particular calculation need you can solve the problem with calc_expression This calc driver can solve math expressions like 3 14 vall val2 val3 val4 2 val5 c 2 Touse calc_expression do the following 1 Set parameter driver calc_expression MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 50 of 116 2 Setup the math expression for parameter expression Values may be a simple point id or a point id variant point id attribute To prevent the parser from misinterpreting the expression ALWAYS put a space between a variable and an operator like etc Most perl math and logic operators may be used such as and Although logic operators such as or amp amp will work logic calculations may more appropriately performed by calc_ladder_
25. Here follows a summary of useful variants W Working value override possible hides missing bad data the default value o Clean averaged value override possible hides missing bad data V High resolution value without override shown in status reports h Clean averaged value written to history shown in status amp history reports val_raw Raw value from input driver not yet scaled For troublesome startup startup scenarios involving calculations ladder logic or time clocks the above variants can be initialized in cfg files This tactic is seldom needed but can be quite useful when needed The point s name parameter is a 0 20 character name that is displayed in some reports Parameter desc isa 0 40 character description that is displayed in some reports Like most everything else that is point centric name and desc are setup in the point s cfg file By now it should be clear that each point has its own configuration file that is named after its point id like OATi cfg or IATi cfg As a software sanity check the cfg file also contains the point id inside the cfg file like p OATi Therefore take care when creating anew cfg file for a new point from an existing file or a template file which you will do many many times If you change the file name you must change the internal p point Both must match Here s a suggestion for reducing human error When cloninga cfg file always save to the new file name as the firs
26. System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 115 of 116 6 wire RJ 11 12 4 wire RJ 11 12 temp temp Pin 1 white sensor OR sensor Pin 2 black 12 25v gnd bk Pin 1 Pin 3 red 1l wire data rd Pin 2 2 2 data Pin 4 green retn gnd gn Pin 3 1 1 gnd Pin 5 yellow 5v yl Pin 4 3 3 Pin 6 blue l wire powered parasitic The powered wiring requires 5v but can be faster and is required by some bridges Most bridges supported by MoCo can supply the 5 volts The powered hookup has a wider temperature range The parasitic wiring s advantage is that it requires only two wires and that s why they call it 1 wire F 5 RJ 45 8 wire Ethernet Plug Note that in the case of the green and white green pair the twisted pairs do not go to adjacent pins as a logical person might expect Ethernet Colors Telephone Colors Pin 1 wh or gray Pin 2 OYr orange Pin 3 wh gn black Pin 4 bu red Pin 5 wh bu green Pin 6 gn yellow Pin 7 wh bn blue Pin 8 bn brown MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20
27. System managers can add their own parameters Both the documented parameters and a user s parameters can be read by MoCo s point processing software wherever a point id or expression is allowed When point software references ini parameters pre defined or user defined parameter names looks like the following ini rpt span or ini my_parm A parameter ina cfg file can indirect to a parameter inthe ini file To setup an indirect in MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 86 of 116 a cfg file precede the target s name with gt ini For example net_addr gt ini net_addr_ha7net This saves entering a specific network address in perhaps two dozen cfg files which facilitates future changes Just change the network address in one place the ini file Other ini parameters that may be of interest are listed below Except for the net_addr parameters few of these need be setup or adjusted for a single handler beginners system calc_loops Number of times to loop the calculation points before quitting Default 5 cfg dir Directory for configuration files other than the ini files Default pgm run dir db Database file location Default Sini pgmDir S ini pgmFamily db db run Database utility program Default S ini pgmDir sqlite3 exe dbi_auth Authentication password as needed by the db software and the DBI standard dbi_ driver Driver name string that is compli
28. alter the alarm_x parameter Ordinarily a user would not temporarily alter the alarm definition string because he might forget the original value But for the record here s how it is done mocom bc IATB alarm H 71 U 1 c Brewery too hot Those with little or no command line experience might say Gee this seems cryptic and old fashioned They are probably right But if versatility and speed of acknowledging or altering an alarm are worthy considerations the command line wins especially considering the time it takes to navigate to an applicable GUI screen Undoubtedly someone maybe MoCoWorks will create a GUI interface to overlay mocom Until then mocom rules by default mocom also has the ability to permanently change alarm parameters or other parameters in a point s cfg file and then to upload the modified file to a running mocod handler This is handy in 7x24 environments If you forget mocom s command syntax just request command help mocom h 6 4 Alarms Triggering Shell Commands Except perhaps in large enterprise factory situations most system managers do not stare at a terminal all day waiting for alarms In systems of any size it is more convenient to receive a phone text message and or email when a serious alarm occurs MoCo enables this functionality with shell commands Utility programs for network file copying and for sending messages differ from system to system MoCo does not attempt to anticipate and
29. any mocod daemons echo n n echo n Would you like to continue the startup y n read answer if Sanswer y then echo Preceding to startup MoCo else echo Aborting MoCo startup exit 0 fi Clear the snapshot and message tables in the database echo Clearing snapshot db table with script clear snapshot clear snapshot Script echo Clearing the message db table with script clear message clear message Script Startup the mocod daemons all in same terminal window mocod 2 amp sleep 10 mocod 1 amp sleep 10 mocod 0 amp This script starts all daemons in the same terminal window The trick is the amp at the end of the line which causes the daemons to be run in the background When programs are running in the background they cannot be aborted with a control c If they must be rudely killed they can be killed with the system s kill command on non windows systems However it is nicer safer more platform consistent and more convenient to use the mocom shutdown commands or better yet a script like the mocod stop script The above scripts will not produce the desired results if any of the three handlers are already running for mocod start In such cases the operator will need to clean up by individually starting or stopping handlers with the appropriate commands Scripts that are capable of handling all unusual situations become somewhat more complex MoCo Monit
30. are missing from perl they can be installed via the internet using CPAN The CPAN installer should be on your linux unix system CPAN can facilitate fully automated installation of thousands of perl modules cpan should be run by root or via sudo For more information on how to use CPAN enter man cpan visit www cpan org and surf other web sites for tutorials MoCo uses the following perl modules which can be obtained from CPAN LWP UserAgent For web communication Time HiRes For higher time resolution DBI Gen purpose database interface DBD SQLite sqlite3 database One way to install a perl module from CPAN is to run this command as root perl MCPAN e install Some Module Verify installation Run a quick test on all MoCo programs to verify that they can run without an execution failure Run the programs from the bin directory or from wherever the MoCo files were installed Test these programs mocod mocom mocor mocos If a program aborts with a fatal perl error begin troubleshooting with the hypothesis that a needed module is missing If the bash shell is attempting to interpret perl code as shell script then the first line of the perl program needs to be changed from the standard location of usr bin perl to point to the directory that contains the perl interpreter on your system Configuration files If no serious perl error messages messages were displayed then MoCo is probably ready to go MoCo cannot
31. bridge and the quality of the network MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 29 of 116 There are a variety of ways to run multiple daemons in the background on a computer and the methods are different on Windows vs unix style systems The more sophisticated techniques require systems expertise that is beyond the scope of this document Fortunately there is an easy way to run multiple instances daemons of mocod Just open multiple terminal windows on your system of choice and run one instance of mocod in each window For extra credit jump to the chapter on Scripts to see how to conveniently run all handler daemons in a single window Other MoCo programs can be run in other terminal windows as needed A list of MoCo programs follows Maintenance scripts are listed in the maintenance section mocod The main moco daemon aka handler mocos Display status of points mocor Display a historic report of points mocom Inter program communication user interface The programs listed above are run from the command line They can be setup to run from icon clicks as well While traditionalists believe that command line interfaces are fast and efficient most Windows and Mac users are more familiar with GUIs graphic user interfaces that are served directly from a program or from an internet browser At the time of this writing GUI interfaces have not yet been created for Mo
32. characters or less While MoCo software can handle point ids of any length reports will be difficult to read if point ids are greater than ten characters For the same reason keep the units name to five or less characters Point id characters must be a z A Z 0 9or_ Atleast one character in the point id must be a non numeric character so that MoCo will not mistake the ID for a number MoCo s point drivers can read constants and variables that have been input from the ini files and other system variables This is done via the reserved point id ini If ini is usedasa point id MoCo assumes that the variable is a system constant or variable and not a point variable Therefore do not use ini asa point id And for security reasons system and exec are also to be avoided as point ids Point ids are case sensitive for setup such as for cfg_ files and the database However to prevent case from being an annoyance when specifying reports the name masks selection criteria for specifying the scope of a status or history report are not case sensitive In many cases mocom is insensitive to case You can and should use upper or lower case for display aesthetics but avoid using upper and lower case to differentiate one point from another MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 34 of 116 Associated with each point are a number of parameters which originate from the point s cfg_ f
33. exterior hardware output port 5 minutes on and 5 minutes off forever Tclono is setup as a pulse output It pulses on for 10 seconds whenever the time clock turns on Tcloffo is also setup as a pulse output except that it pulses on for 10 seconds whenever the time clock turns off The latter two kinds of outputs might be used to pulse a contractor on or off The cfg file details for these output points are shown below Output Point for Time Clock Source is 5on5offt p TClocklo name Time Clock 5on5o0fft Out desc Output Point for Time Clock 5on5offt device _id ol net_addr gt ini net_addr_wc0 Points to ip addr in moco ini driver output_webcontrol WebControl bridge units OnOff snap_fmt 6 d As mentioned the above time_clock point alternates on for 5 minutes and off for 5 minutes The following two output points create pulses triggered from the time clock s up edge and down edge respectively On pulse Output Point for Time Clock Source is 5on5offt p OnPulseo name On pulse fr 5on5o0fft MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 47 of 116 desc device_id On pulse Output Point for Time Clock 5on5offt o2 net_addr gt ini net_addr_wc0 Points to ip addr in moco ini driver output_webcontrol WebControl bridge units OnOff pulse up Trigger on up edge of time clock result pulse_sec 10 Pulse length is 10 seconds snap_
34. file pulse sec Number of seconds of optional output pulse Default is null pulse trig Generate optional pulse on trigger up down both Default is null source pt Optional source point that can be specified to be used by an output point variables Source variables for output _file driver PointA PointB c PointCc val force If force is true then force the output to assume this value A 2 6 Specific to Calc Points expression calc_expression driver Math logic expression to be evaluated function calc functions driver sum avg min max abs or int parameters calc_ functions driver Parameters for the math function rung calc_ladder_ logic driver Ladder logic expressions Rungs 1 100 time _intv An accurate measure of the last interval in seconds time _now System time in seconds now time prev System in seconds at the previous interval A 2 7 Specific to Time Points pulse sz time_ clock Pulse length in seconds when p or d in times parameter times time_ clock List of time events such as times of day dates day of week etc MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 90 of 116 A 2 8 Useful Internal Real time Data Variables alarm The single character alarm status _ a z A Z c Clean value a point s smooth conditioned result value with override capability w Working value a point s higher resolution value with override capability v S
35. filetothe ini filelike gt ini net_addr_isy99i The ISY 991 is smarter than the other bridges and therefore more complicated Expect to spend time reading its manual reading its wiki and tips searching the forum for help In my experience Universal Data s email support is both responsive and competent Their web address is http www universal devices com D 5 EMACSYS The EMACSYS bridge is a product of Phaedrus Limited in England The controller is a 4x4 inch circuit board with a number of connectors that allow it to be connected to optional connector blocks and peripheral devices such as relays or optical isolators This physical architecture has some practical advantages You only pay for the terminal blocks if they are needed There is no need to fabricate cables And the processor board can be easily removed without unscrewing any wires The board has sixteen digital inputs sixteen digital outputs and eight 10 bit 0 3 3v inputs It does not support 1 wire devices The digital outputs are inverted meaning that a logical 0 is high 3 5 volts and logical 1 is low volts The MoCo driver silently corrects the inversion so that a logical 0 is zero volts and logical 1 is high volts If you want to invert the logic again use MoCo s invert parameter to cause another inversion Like the other bridges EMACSYS includes a web server Its software architecture allows and MoCo Monitoring and Control System Implementation MoCoWorks
36. in parasitic mode Parts that are mislabeled or misrepresented are being sold on the Internet so buy from a reputable source Parasitic DS18B20 PAR sensors will not work reliably or at all on a WebControl bridge PAR parts have a maximum functional temperature of 85 degrees C vs 125 degrees C for the powered parts 8 The WebControl 1 wire terminal block provides marginal Vdd voltage for a DS18B20 Therefore when powering DS18B20 temperature sensors use the 5v provided by the humidity sensor block at terminal 3 F 2 RJ 11 4 wire Telephone style Plug MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 114 of 116 The following is the wiring convention used at MoCoWorks for 4 wire telephone style hardware MoCo uses 4 wire hardware because it is more easy to obtain from local sources than 6 wire hardware To identify the pin outs hold the male plug so that you are looking at the end clip down This is the best way to view wire colors Pin numbers are 1 right to 4 left Because colors and pin numbers are sometimes reversed always verify what colors of wires are connected to the pins Pin 1 black optional 12 25v Pin 2 red l wire data Pin 3 green ground Pin 4 yellow 5 volts F 3 RJ 12 6 wire Telephone style Plug The following is the list of wiring assignments used by Embedded Data Systems for their HA7Net and OW Server ether
37. is usually HTTP the same protocol that is used for web pages This is very convenient because you can verify the functionality of interface hardware with a browser before MoCo attempts to talk to it and because HTTP or HTTPS protocols can usually communicate through firewalls without problems Directly viewing data I O points In order to display a I O bridge s web pages you need to know it s web address For initial testing the I O bridge should be connected on your own local network It may have a default address like 192 168 1 240 Or perhaps more likely the initial address will be automatically assigned by DHCP a floating address similar to 192 168 0 101 Some people use trial and error to locate the DHCP assigned address If the router assigns addresses in the range from 100 to 150 for example attempt connections with addresses 192 168 0 100 192 168 0 101 etc until a connection with the bridge is achieved Either way you directly enter this numeric IP address into the browser s URL address field in order to make contact with the bridge If initial contact is by DHCP one of the first tasks after locating the DHCP assigned address is to assign a static address like 192 168 0 240 The re assignment is done via a setup web page that is served by the bridge Use a browser to logon to the bridge with the initial IP address and logon with user name and password Then assign an available static IP address to the bridge Take care that
38. loops ramps All points have industrial strength features such as overrides averaging hysteresis resolution etc Multiple alarm capabilities per point with capabilities like command execution and sending email Point data is shareable between MoCo systems on a multiplicity of computers Inexpensive ethernet I O interfaces HA7Net WebControl OM Server ISY 991 EMACSYS etc Inexpensive devices 1 wire Insteon and X 10 as well as the traditional industrial standards Versatile command line interface easily expanded to web page or GUI interface in the future Versatile status history command line reports designed to feed graphic reports and web screens Graphic reports to be layered on top of command line reports often developed by future users Localizable for non English environments Under the Hood A kernel that can be reliably be built upon by others Built with a reliable fully portable programming language that has adequate speed Perl Usage of external perl software modules that are available for the targeted operating systems Consistent programming practices and data interfaces for easier enhancements by users Extensively commented code with intentional avoidance of programmer s tricks Simple design whenever possible yet complex when needed to meet essential objectives A multi tasking architecture that works on all platforms I O software that works at higher levels withou
39. microbrewery process control to a variety of distributed applications in a manufacturing plant in other words for industrial SCADA Supervisory Control And Data Acquisition systems A high priority has been given to building upon a solid foundation stable bullet proof software foundation such as perl with an architecture that enables painless upgrades and backups MoCo can be upgraded by replacing text based perl programs no compilation required Configuration data can be backed up simply by saving a group of human readable text files MoCo at its present stage of development is a functional monitoring and control engine While it does provide versatile status and history reports users who want customized color graphical reports will need to do this work themselves MoCo architecture enables user interface embellishments to be added with traditional unix linux techniques and without the need to modify MoCo software 1 2 System Design Goals MoCo s designer gained his knowledge and beliefs about monitoring and control system design from experiences in sawmill automation IC manufacturing automation and from corporate building automation After retiring from the corporate world he designed MoCo a system that strives to meet the following objectives MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 5 of 116 Zero cost software that can be enhanced by supportive users Fea
40. of a value going from false to to true stop Stops the timer upon the leading edge of a value going from false to to true snap_fmt Specifies sorting order and header text to be used in mocos status reports stealth 1 to prevent the point from being normally displayed in reports time prev System time in seconds of previous pass Useful for calc points Read only timer The current time accumulated on a timer Typically read only but may have avalue in cfg inorder to assure clean ladder logic startup in some situations units Physical units like degF or volts 5 or less characters Recommended val force If force is true then force the point s result or output to assume this value val_over Override value Normally set via mocom Default is null A 2 2 All Analog Points Analog points produce numeric results that have receive extensive processing which is controlled by the following parameters After processing the results usually look different cleaner than the original raw values avg_size Number of readings to average in the running average 1 to any size Default 1 bad_high Block data replacing with if above this value Helps detect bad sensors bad_low Block data replacing with if below this value Helps detect bad sensors gate Typically 0 or 1 gate is multiplied times a point s value to create the result high_limit Clamps the converted value to stay at or below the high_limit hysteresis Hysteresis a
41. parameters are specific to calc points time _intv Precise time in seconds for the previous interval time now Precise system time in seconds when the calculation is being performed time prev Precise system time in seconds when the previous calculation was performed Parameters start stop and reset can be programatically controlled from any value or expression Therefore can be used to invert a controlling value s logic as needed If point Startl1 isthe value ofa switch Start1 could beusedto start the timer and then Startl1 could be used to stop and reset the timer The time_ parameters are helpful for performing accurate time related calculations like duty cycle When combined with ladder logic timers are particularly handy for sequencing a scene or sequentially staging machinery In such applications point IJK ladder logic would contain tests for a set of contacts like IJK timer gt 123 This isa test to see if the point s timer has gone above 123 seconds The timer variable would normally be treated as a read only variable However there are occasions where altering it can prevent a good deal of ladder logic complexity Ladder logic can sometimes become complex just to work around system startup and initialization issues In some cases initializing a counter to a high value in the cfg file can remove the need for convoluted ladder logic whose sole purpose is to assure a clean startup Suggestion When creating
42. pl report This is optional but recommended for a finished system pipe is the field delimiter lst amp 2nd fields for sorting lines 3rd field is text for a prior break line between rows if any snap fmt a Dae Re ee fe Sts Sana ices ae 4 We whee ane We Aiea ee Ge we wate a Gave Alarms are optional usually for critical points only alarms H clwlc null for no alarms configured to allow just and alarms H C wlc example Mult alarms Upper case latched lower unlatched Multiple alarms defined below One example shown alarm H 72 5 U 2 c Getting warm in here Parameters for alarm lst Alarm threshold value required 2nd Direction U up or D down 3rd Hysteresis 3rd 1l char ID for display MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 93 of 116 4th Rate of change min threshold 5th Point s value variant like c w v h etc 6th Very short alarm description alarm_C etc additional alarms not shown here Triggering of shell scripts or programs from alarm events cmd_a_H my scriptl cmd_a_h my script2 cmd_a_bd my script3 cmd_a_ma my script4 cmd_a_mc my script5 cmd_a_ac mt script6 Sh SR RRR SR SR RR Alarm H for ex has been triggered amp latched Use any alarm id A Z If a no latch alarm do not use cmd_a_H Instead use cmd_a_h to trigger a shell command
43. point p name desc driver handler units interval and optionally snap fmt The coverage of input_alarm_tally is determined by the scope parameter If 0 the alarm tally covers only the handler s points If 1 it covers all of the node s computer s points If 2 it covers all points in a distributed system From this point on we discuss conventional input points that have sensors in the real world In addition to the description below sub chapter 2 5 Hardware Transducers and I O Interface Setup provides a practical overview of the setup process When setting up an external sensor a broad range of skills and knowledge can come into play physics electronics use of tools networking software trouble shooting skills operating system savvy manual reading skills and Googling for missing information Consequently the process can be a challenge for users who are new to monitoring and control The uninitiated might find that solving a simple problem takes longer than an episode of CSI where TV actors can solve a complex crime in less than one hour MoCo hardware is ethernet centric Therefore in many cases the implementer can use a browser on the network to verify that the interface hardware and sensors are working Do so before attempting to get the data into MoCo The following supported I O bridges can be configured and tested via a browser HA7Net OW Server WebControl IS Y 991 and EMACSYS Once the interface has been verified w
44. reports Also with mocom a user can trigger a point s manual alarm along with his or her remark This can be used to alert others in a maintenance team that there is an issue with the point The manual 1 alarm is a latching alarm of the highest priority See the chapter on Alarms for more details about alarms in general Missing data If external hardware or network fail MoCo will have no way to read current data from the sensor Rather than display old data or a zero both of which would be lying MoCo sets the data to a to show that current data is unavailable Bad Data Sometimes a sensor fails and consequently produces an extremely high or low value Other times extremely high or low values result from noise spikes This is bad data A user can trap bad data by setting the bad_high and bad_low parameters Any value above or below these thresholds is considered bad data which is replaced by a The flag replaces numeric data only in variants point h and point v Other variants contain the last known good value When status or history reports show a question mark it usually means that the sensor is unreadable at that moment or is in the process of failing But it also could be an indication of out of limits data or a configuration error Ifpoint h or point v are fed to a calculation point the is propagated through the calc point to prevent the results of calculations that were fed with missi
45. s val_force and force parameters other events can override the time clock s normal sequence In the simplest case a switch input point could drive the time clock s val_force override Sophisticated control logic is possible by feeding val_force froma calc_ladder_logic point or simply by directly feeding val_force with an expression like LiteLevel lt 20 Remember that points can send their result to multiple output points Therefore controlling multiple lights from a single time clock is easy As with the time clock point each individual output point also has the capability to have its output device be overridden via val_force and force controls This becomes useful in home automation when there is a need to override default scene settings with an external X10 or Insteon switch Another scheme for implementing a sequence of dynamic scenes is to implement a single time clock point that drives multiple calc_ladder_logic points each of which drives one or more output points Time clocks are not limited to producing just 0 or 1 A single time clock can output any numeric value for any of a multiplicity of events A time clock could be setup to produce a stepped result of 1 2 3 4 representing phases of a scene The time clock s phase numbers could then feed to each ladder logic s enable out parameter as part of an expression like enable out SceneX 3 The expression in quotes evaluates to 1 ifthe result from time cloc
46. stage3 goes false After 20 seconds stage2 goes false After 40 seconds stagel goes false Now they are all off At first glance the ladder logic implementation might look bug free However when creating programs and ladder logic there is often the risk of problems at system startup The timers trigger on the leading edge a change from false to true When starting up timer 2 is at zero Inspect the ladder logic and you can see why this creates a problem A simple solution is to initialize timer 2 to a value higher than 40 The initialization is done in the stage2 cfg file as shown above with timer 1000 A person proficient with ladder logic will find tasks like this easy and perhaps even boring A software programmer on the other hand would argue that writing program code is easier This is a classic argument akin to arguing politics and religion In any case be assured that software program style solutions will be added to MoCo so you can do it your way Or code it in pure perl code if you like MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 81 of 116 10 Maintenance 10 1 Backups Backup frequently The database file all configuration files log file and anything else that might have changed 10 2 Log File Archive and clear moco log once a month or so 10 3 Database The moco db database has three tables history For all that historic point data snapshot For stat
47. take care to not purchase the parasitic PAR version They will not work with WebControl Also terminal 3 on the WebControl s 1 wire terminal block does not provide enough voltage for the DS18B20 CAI Support recommends obtaining the required 5v from terminal 3 of the humidity sensor block While this pin also provides less than 5 volts and its voltage level pulses in sync the blinking LED it has nevertheless proven adequate for DS18B20s The Sv power terminals from the 1 wire temperature terminal block or the humidity sensor terminal block produce less than 5 volts are current limited and surge in voltage in sync with the unit s blinking light Therefore to power external interface electronics that requires over 5 ma use the 5v from pin 13 of the 16 pin Tyco connector or use an external regulated 5 volt supply In a pinch users have been known to solder directly to the Tyco connector pins Better yet order the mating connector and ribbon cable in advance The connector is a Tyco NOVO 1658622 3 which is available from Newark Electronics number 73K6221 and other suppliers The part number for hundred feet of 3M mating ribbon cable is 3365 16 Newark number 03F5907 If only several wires need be connected to the connector the cost of the ribbon cable can be avoided by soldering 28 wires directly to the mating connector In early firmware versions the WebControl bridge selected a seemingly random order for 1 wire tempera
48. the static address you pick is not used by any other device and not within the DHCP range typically not within 100 150 That s the basic concept for getting connected The details should be explained in the user manual for the interface device MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 15 of 116 Take note of the IP address Soon this address will be entered into cfg files orthe moco ini file so that MoCo knows where to find the bridge Connect several sample I O transducers to the bridge interface These transducers may be 1 wire devices like a temperature sensor digital input devices perhaps an on off switch digital outputs perhaps resistor and LED analog inputs perhaps an 1 55 volt AA cell or analog outputs Again the bridge s manual should provide the necessary information for this step The following technician s tools may be needed soldering iron volt ohm meter pliers screw drivers cable crimpers etc Associate a point The next challenge is to determine how to associate a particular physical I O point with a point name in MoCo For example a 1 wire device has a 16 char or 12 char unique ID depending upon how the bridge perceives it This long inconvenient ID must be associated with a short human friendly ID in MoCo Some bridges like WebControl require setup and association of I O devices in the bridge itself First the long manufacturer s ID must be associate
49. to the numeric value With s and S options mocor can display stealth points that are normally hidden from view Ifthe e switch is specified mocor displays a help screen before the FormEdit screen Strike enter and it displays the FormEdit screen Here you can edit the parameters entered on the command line and add new parameters See the section on FormEdit in this document for operating instructions Or while in FormEdit enter h remember the leading space for help on FormEdit commands Report definition files A system manager or user can embellish reports with custom header and footer by setting up rpt files To see how have a look at the sample rpt file that is included with the MoCo software package The report can be setup to run exactly as specified in the rpt file However if the end user wants to override point id scope parameters or select a specific kind of report overrides alarms etc then custom scope and switches that override settings inthe rpt file can be entered on the command line when mocos is run Outputting to a file If parameter out_file my file is placed on the command line mocor MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 68 of 116 will output to the specified file Set switch f to output delimited field data records suitable for sending to a database or spreadsheet Set switch F to have column names as the first recor
50. to true Parameters counting count_up count down and reset can be programmatically controlled from any value or expression Therefore can be used to invert a controlling value s logic as needed If point Switch1 is the value of a switch Switch1 could be usedto start the counter and then Switch1 could be used to stop and reset the counter Stopwatch timers Every point has stopwatch timer capability Although one point can use another s MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 54 of 116 timer accuracy is much higher if a calculation point uses its own timer In this case the error is less than 10 microseconds When using timers on other points the different intervals make timing somewhat less accurate but disassociated timers are usually good enough for controlling scenes or staging machinery Timers can be used for various purposes including Calculating time per day or unit time that a point is on or off Calculating duty cycle Creating delays Staging scenes or sequencing events These parameters are relevant to all timers timer The current time accumulated on the timer Usually read only start Starts the timer on the leading edge of a value going from false to to true stop Stops the timer on the leading edge of a value going from false to to true reset Resets the timer to zero on the leading edge of a value going from false to true These read only
51. value or working value has changed MoCo scheduling is fast enough for most situations so be nice and use this feature for non output points only as needed All points have their own stopwatch timer capability Stopwatch timers are useful for calculating on time per hour calculating duty cycle staging a scene etc Each point s timer can be started stopped and reset programmatically by other points A ladder logic point s result can be used to control its own timer Any point can use use the time values from any other point s timer See the section entitled Stopwatch Timers for details A point s data collection and processing can be totally halted by setting parameter disable 1 in the point s cfg file A point can also be disabled in a live mocod daemon with mocom by setting disable to 1 Infact mocom canchange any cfg or ini parameter ina live mocod daemon With the proper command mocom can also cause any or all of the values to be dumped displayed from a live mocod daemon a very helpful tool for debugging As an alternative to using a text editor mocom can also change parameters in cfg or ini files And if so commanded mocom can signal mocod to reload one orall cfg files to mocod while it is still live and running These latter features are primarily useful in situations where a system must stay up 24x7 Each time mocom executes a command the details are recorded in the moco log file See the chapter on mocom for a full d
52. when the alarm has gone active and auto acknowledged Alarm H has been acked now displayed as h A 2 bad data alarm triggered It does not latch The manual alarm has been triggered amp latched The manual alarm has been cleared All alarms are now clear Various Overrides all are optional force val_force 70 gate 1 val_over u alarm_to_H 75 If true val_force value is used as override The value to assuem if parameter force is ture For gateing the result value Manual override Usually altered via mocom Alarm threshold override alarm H mocom use MoCo processing control All are optional amp assume reasonable defaults do_next pointl point2 point3 For rapid processing of result do next on leading edge only 1 trailing only do next to output points 0 block trig of outs no interval processing process only on the interval then totally disable the point don t show by default on reports See MoCo doc especially Appendix A for complete list of parms cng filter 1 If enable out 1 If interval 0 If intv_only 1 If disable 1 If stealth 1 If ADDITIONAL USEFUL PARAMETERS NOTES Everything is case sensitive Quote any data that contains spaces Order of name value variables is not important B 2 Time Clock cfg File Sample sampleTime cfg Sample Calc Time Clock Point
53. will be the most recent versions B 1 Input cfg File Sample sampleIn cfg Sample Input Point Basic point definition p sampleIn Point ID for software and reports name Sample Input Point name for reports desc Sample Input Point Long point description units degF Units for report display device_id F20000013E41C828 Manufacturer s unique sensor ID net_addr gt ini net_addr_ha7net To sensor s web addr in moco ini device DS18B20 Mfgr s sensor part ID for info driver input_ha7net_temp Handler subroutine name handler mocod9 Daemon 9 the handler for this point For analog processing all optional some more important than others Choose the following numbers wisely avg_size 5 Number of samples for running average resolution 0 2 Clean resolution for risplay and history ramp 0 5 Allowed rate of change per minute hysteresis 0 03 To reduce history jitter amp inc data instability interval 10 Sampling cycle interval in seconds high limit 100 The value is clamped at or below this limit low_limit 30 The value is clamped at or above this limit bad_ high 110 If raw conv val at or above flagged as bad data bad_low 20 If raw conv val at or above flagged as bad data invert If raw input is inverted and displ do_next pointl point2 point3 for rapid processing of result snap fmt defines the display format for mocos
54. 116 of 116
55. 2 33 44 2 33 45 2 33 45 2 33 46 2 33 46 2 33 46 2 33 44 2 33 44 mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt mocod0 gt GATW GATW HumwW Humw TATW TATW OATW OATW WDirw WDirw WGusW WGusW WSpdw WSpdw OutFile OutFile testCalc testCalc TClock1t TClocklo Tcloffo 55 67 73 6 E w Yow HV OB 122 FPOOrRNE VN de Hj Hj degF degF degF degF deg deg mph mph mph mph pts pts none none OnOff OnOff OnOff startup startup startup startup startup startup startup startup startup Run mocos to see a status report of all installed sensors Typical results Alarm Val Val Hist Time Rem Age Remark Point OutFile 1 1 13 10 Alarms 0 00 0 00 cnt 13 10 Outside io sore recess 8055 ese oye 6 bb 5 a EE A Wad OAT 43 7 44 degF 13 10 28 startup OATW 36 3 35 degF 13 09 WGusW 14 14 mph 13 09 WSpdw 4 4 mph 13 09 WDirW 56 5 30 deg 13 09 HumW 62 65 13 09 DewPW 24 5 24 degF 13 09 Barow 29 972 29 98 in 13 09 TASTE ASS aie se dies signa Scares Soares vg E airs ndita es taal dy wer dae Le a aa de IATB 68 8 69 degF 13 10 28 startup IATH 70 52 70 5 degF 13 10 17 startup IATsets 70 70 degF 13 09 IATW 74 2 74 2 degF 13 09 GATW 55 55 F 13 09 Tcloffo 0 0 OnOff 13 06 Tclono 1 1 OnOff 13 10
56. 2010 877 360 2582 2010 06 20 105 of 116 encourages users to create their own custom web pages Some example web pages are included with the product When used with MoCo the MoCo driver uses a custom web page called emacsys moco htm which produces an output that includes all digital inputs digital outputs and analog inputs This web display is primarily for the driver and it looks like this on a browser di 1000000000000000 do 1011000000000000 ai 986 72 27 25 26 37 19 60 The controller can run a growing number of applications that are available from the manufacturer The MoCo driver requires the Phaedrus ethernet application firmware and the ethernet interface The firmware and web pages must be loaded into the controller before anything will work Installation requires a Windows machine with NET Framework installed Installation instructions follow 1 Download from http www emacsys com Control Manual pdf and Ethernet Manual pdf Read these short manuals paying particular attention to the instructions for installing application software Install the EMACSYS Ethernet Server Software 2 Download the software from the http www emacsys com site to a Windows machine 3 Place the software in a directory like D emacsys 4 Double click the msi file to install Install in D emacsys 5 Read the instructions from Phaedrus Ltd 6 Plug the little ethernet board into the controller card Run a USB cable between con
57. 32 C to F avg_size 5 Number of samples for running average bad_high 120 Block if above 120 Probably bad sensor bad_low 20 Block if below 20 Probably bad sensor high limit 100 Clamps the converted value to no more than 100F low_limit 40 Clamps the converted value to no less than 40F resolution 1 For numbers like 5 32 68 etc ramp 0 2 Restricts change to less than 2 per minute hysteresis 2 2 hysteresis 1 8 of resolution is default interval 60 Read point every 60 seconds snap fmt SoD INS TAS hc Sed ais senan ane ae oie eG OS ES OME ares Most of the above are optional If unable to decide on a data compression parameter s value for the moment rest assured that most have reasonable defaults Optional parameter snap_fmt is used for ordering and labeling the display ina mocos status MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 40 of 116 report It is made up of three sub fields separated by pipe characters The first two sub fields are used for sorting major and minor If for example the third Outside field is included it will be displayed as a header line before outside sensors are displayed inthe mocos report Ifparameter invert isinthe cfg file then a digital input is inverted and a decimal point is appended like 0 or 1 so that a person viewing a report will know that the value was inverted by the po
58. 77 360 2582 2010 06 20 33 of 116 5 Points Input Output Calculation and Time 5 1 Points in General MoCo processes external and internal units of variable data as points A point is a common industry term for an external transducer value Some monitoring and control systems have functional internal variables which their designers call blocks Because MoCo handles external and internal variables quite similarly all such variables in MoCo are called points input points time points calc points and output points For large systems point id naming strategy can be one of the most important decisions a designer makes This is be because MoCo reports provide wild card selection capability which enables a person to quickly specify a relevant report if his or her chosen naming strategy so enables For example if MoCo covers several buildings numbered 1 8 the point id might start with the building number The second character might be T for temperature L for lighting on off H for HVAC system points etc The last character could designate the type of point and so on The following wildcard characters same as for Linux and similar to Windows are supported by MoCo reports Zero or more characters Exactly one character abcde Exactly one character listed a e Exactly one character in the given range abcde Any character that is not listed a e Any character that is not in the given range Point ids should be ten
59. Co However MoCo s programs and data structures have been carefully designed such that GUI interface software can be layered on top of the command line programs without the programmer having to touch a line of underlying MoCo code Web page designers prefer to get their dynamic web page data from command line style programs MoCo is free open source software and we hope MoCo users will generously contribute their GUI interfaces to the project in the same spirit Enterprise Features MoCo and its I O bridges are designed to be network centric This architecture was selected in good part to enable a scalable failsafe architecture Although MoCo comes stock with a low fat database it is also designed to work with a server style database This option enables MoCo s nodes to be distributed across the intranet or internet Critical applications usually require a failsafe network of computers with redundant nodes and a distributed database MoCo facilitates this requirement by enabling one cluster of nodes to function as the master while one or more other clusters act as slaves The slaves monitor everything along with the master but their ability to output to a bridge is blocked This prevents more than one computer from sending output commands to an output point If the master goes down a slave can become the master Of course the transition procedure should be planned and tested in advance This capability is facilitated by the no_output p
60. If above 72 output 20 heat rung 3 t33 gt 71 amp amp 60 If above 71 output 60 heat rung 4 t33 gt 68 amp amp 75 etc rung 5 t33 gt 65 amp amp 85 rung_6 100 The calc_ladder_ logic point outputs the percent of power to feed to a heater in this case The numbers in each rung following the amp amp s are actually percentages Depending upon the temperature it outputs 1 20 60 75 or 85 The output point cannot output anything less than zero like 1 so it will output a 0 if there is a H alarm For on off controlled heaters the output from this ladder logic could feed a time _pulser point which would then feed pulse width modulated on off pulses through an output point to a heating element 5 8 Counters and Stopwatch Timers Counters Every point has counter capability Counters can be used for various purposes such as Counting the number of times a door opens Counting people or cars Counting telephone calls Counting the number of times a motor cycles on and off Counting valve cycles These parameters are relevant to counters counter The current count accumulated on the counter counting Enables counting when set to true count_up Increments counter on the leading edge of a value going false to to true count down Decrements counter on the leading edge of a value going false to to true reset Resets counter to 0 on the leading edge of value going from false
61. MoCo Monitoring and Control System Implementation Open Source Monitoring and Control How to Configure a Working System Start to Finish POB 992 La Veta CO 81055 info mocoworks com 877 360 2582 Draft Version 2010 06 20 Software Version 0 54 MoCoWorks 2010 MoCoWorks Reed White MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 1 of 116 Contents 1 Introduction 1 1 What is MoCo 1 2 System Design Goals 1 3 Design Strategies and Tactics 2 Small System Quick Start 2 1 Software Installation Overview 2 1 Installation on Linux or Unix 2 2 Installation on Apple Mac OS X 2 3 Installation on Windows 2 4 SQLite Notes 2 5 Hardware Transducers and I O Interface Setup 2 6 Using FormEdit 2 7 Initial MoCo Startup 2 8 After Initial Startup 3 Under the Hood 3 1 Data Processing 3 2 System Considerations 4 Changing System Parameters with mocom 4 1 What mocom Can Do 4 2 Operation 5 Points Input Output Calc and Time 5 1 Points in General 5 2 Points Scheduling 5 3 Input Points 5 4 Conventional Output Points 5 5 Outputting Points and Their Values to a File 5 6 Time Points 5 6 1 Time Clock time_clock 5 6 2 Pulse width Modulated Pulser time_PWM_pulser 5 6 3 PID Loop time_PID_loop 5 7 Calculation Points 5 7 1 Common Functions calc_functions 5 7 2 Math Expressions calc_expression MoCo Monitoring and Control System Implementation
62. MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 65 of 116 This program reports status of IO points Usage mocos switches dislpay intv report file point mask Switches following single chars with leading hyphen before the string h Display help Default scope Every point specified by rpt file or point mask a Report all points that are in alarm state A Report all points that have defined alarms o Report all points that have overrides r Report all points with any kind of remark u Report all points with anything unusual s Only show stealth points S Also show stealth points Switches and other arguments may be in any order A numeric like 10 is the interval between repeated displays A non numeric is first tried as the name of a report file rpt file If the file does not exist it is treated as a point mask Examples mocos h Help mocos 10 Display all points refresh every 10 sec mocos ar I O Alarms amp remarks ids starting with I or O mocos 0 Display all points with overrides mocos IAT OAT Display points IAT and OAT mocos inside Display report defined by file inside rpt QUOTE ANY PARMS ON COMMAND LINE IF THEY CONTAIN SHELL CHARS lt gt etc The example report shown at the beginning of this section has some but not much formatting Formatting in that report was limited to section lines beginning with Inside and Ou
63. The configured alarm character is displayed at the front of the remark An unacknowledged alarm displays as shown below The 10m to the left of ALARM L shows that 10 minutes have passed since the alarm triggered The 65 to the right is the alarm threshold L IATB 64 17 64 2 degF 09 26 10m ALARM L 65 Brewery cool For latched alarms a person may clear acknowledge the alarm when it is noticed or after the problem is fixed The procedure depends upon department policy After being acknowledged the above alarm would look like this h IATB 64 17 64 2 degF 11 25 23m ACK h rw Cool is nice Communication program mocom is used to acknowledge an alarm Note that when using mocom point ids may be entered in all lower case and that the point id can contain wild card characters allowing a user to acknowledge multiple commands with one command When using wild card characters remember to place double quotes around the point id argument To acknowledge an alarm or alarms enter a command that looks like one of the examples mocom user id point id Usage mocom rw IAT Actual example mocom rw iat Lower case works too mocom rw IATB IATH IATW Ack multiple alarms mcocm rw IAT Wildcards mocom user id point id remark mocom rw iat got it george Usage more verbose Actual wordy example In environments with multiple people on a maintenance team one person might notify the others of a
64. This can be done by a ladder logic point like TTcolor Choose your own name The rungs in the point might look like this rung 1 tankTemp gt 180 amp amp red rung 2 tankTemp gt 150 amp amp orange rung 3 tankTemp gt 130 amp amp green rung 4 tankTemp gt 100 amp amp blue rung_5 black Thanks to a characteristic of perl and some other programming languages the value that is returned from a logic expression is the last true value With perl this even works for text If the temperature is above 130 but not above 150 then the last true value is green The point will have the value green which will also display in status and history reports In order for this to work the point must be a digital point which is default for ladder logic points Continuing this example the developer would setup the TTcolor point to feed the template s html color attribute for the target object Similarly rather than displaying a numeric 1 or 0 text On or Off could be displayed in html or pure text reports If the result file needs to be sent to another computer the cmd_outf parameter can specify a user s shell command that will for example ftp the file to the web server Any ini or cfg parameter can be automatically inserted into the command string by placing point attribute in the string Such embellishments are not necessary for a perfectly functional monitoring an
65. W IATB IATH Three points to get and write out file OutFile txt Where to send the data see below interval 30 30 second write cycle An example of the output produced by the file follows Note that the file was one time edited for positioning and comments and thereafter the oroginal layout was preserved OutFile txt Several inside points IATH 73 03 HVAC Room IATW 73 6 Living Area Davis Weather Station IATB 65 8 Brewery Area datetime 2010 02 17 19 07 5 5 2 Template driven Files If a template file is to be stuffed with data parameter tmpl_ file must contain the name ofa template file The output file driver will then stuff a template with data values Although graphics web developers will find this feature a godsend it can also be used to quickly create a cosmetic text based display First the developer sets up a template The template canbe a html web page or just plain text Instead of including static numbers in the file which of course would be old history in seconds or minutes the variable name of each desired point is included within the text For example Wind Direction WindDir c deg Wind Speed WindSpd mph The driver will replace the WindDir c and WindSpd _ with their current numeric values The extra leading or trailing characters allow a person to define how many characters are to be used The final field length is the number of characters between and inclu
66. ame as point w except without ability to be overridden h Same as point c except without ability to be overridden val_raw A point s raw value as it leaves the driver but before being scaled and conditioned Various other real time control variables are described throughout this document A 3 Report Parameters in rpt Files The following are conventional parameter file parameters line Lines of text that are used for report headers and footers p_mask Specifies the scope of point ids for the report rpt_name Miulti word name for the report rpt_span_ Report duration like 30m 8h 7d 1mo rpt_type Event type scope of the report E a A O u r cC C The following are used within line parameters to pass program data to headers or footers S datetime Human readable date and time p_ mask Scope of point ids for the report actually used p_mask may have been overridden S rpt_file Actual name of this file Srpt_type Actual event type scope of the report rpt_type may have been overridden A 4 User identification Parameters in usr Files A usr file is needed for each user who will use mocom The usr files are merely the first step toward a real security system A user s handle should probably be short as two or three initials When users execute mocom commands as when acknowledging an alarm or setting an override they must enter their handle typically their initials Each command and the user s hanndle are r
67. amp Scfg on3 w LitesD 1 The 4 way switches say ON LitesD 0 The 4 way switches say OFF else The following deals with the night situation activates more lights If night turn on more lights night is a time clock result SLitesN S LitesD amp amp Scfg night w Note that we are creating 2 outputs Unusual concept but legal amp calc_ END LitesN SLitesN LitesN is a secondary output return amp calc_END LitesD SLitesD LitesD is the primary point END calc my 4way switch To assure proper operation LitesD cfg and LitesN cfg need to be setup with p driver and interval parameters The driver in this case is the name of the subroutine calc my 4way switch The calc in the subroutine name is required For custom subroutines two underscores follow the calc to prevent name conflicts MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 77 of 116 The second cfg file LitesN cfg is almost a dummy because the system expects only one result variable from a point Two outputs sneaky but functional LitesD is the primary output Its cfg file should contain the do next parameter that lists all 10 output points for the lights This custom driver is not a general purpose driver because it is hard coded for the variables shown With a little extra work the 4 way portion of the code could be made into a general purpose 4 wa
68. ant with the DBI standard DBI dbi_user User name as needed by the db software and the DBI standard db software Database software name Default SQLite dtFmt Default y2 mo md hr mi se gmt dvrs_ file File name of driver file Default mocod dvrs pl dvs_file File names of driver files if more than one hist_interval Longest time allowed between history writes Default 2000 seconds logFile Log file including optional path for errors and more Default Program s directory msg_interval Interval for polling for messages from mocom Default 13 seconds no output Blocks all outputs when 1 Useful for enabling disabling redundant systems net_addr_ha7net Example of indirect addr for input _webcontrol http 192 168 0 250 net_addr_wc0 Example of indirect addr for input_webcontrol http 192 168 0 240 net_addr_wx Example for input_web_page http bistrobrew com weather clean wx htm net_timeout Default 10 seconds node Usually the computer s name or a user s account name All node_names in a MoCo network must be unique A required parameter if more than one computer rpt_dir Directory for rpt report files Default is the ini s directory rpt_span Default span for mocor report Default 4h 4 hours time _now Current system time in seconds Useful for calc points Read only usr_dir Directory for usr_ user definition files Default found from search sequence A 2 Point Parameters in cfg Files Most of the following p
69. arameterin ini and cfg files MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 30 of 116 4 Changing System Parameters with mocom 4 1 What mocom Can Do for You mocom deserves its own chapter because it is the communications link between you and the mocod daemons that continuously run in their own private world mocom is a command line program that is both versatile and quick to use It works well over telnet and ssh terminal connections Because mocom is a command line program it s operation may be less intuitively obvious at first But its operation soon becomes second nature for most users You can do the following with mocom Acknowledge alarms Set the manual alarm Set or clear an override value for a point Send a remark to be displayed with its point on status displays and in history Change an ini or cfg parameter in a running mocod handler daemon Change parameters in ini files cfg files rpt report files usr user files and 1cl localization files Cause all ini or cfg parameters for a point to be dumped to the screen Cause cfg parameters to be re loaded from files to a running mocod daemon Shutdown a handler daemon When executing any of the above a short remark can be tacked on to the end of the command string Remarks are displayed in status and history reports along with alarm actions parameter changes or override act
70. arameters have reasonable system defaults and are therefore not required Required parameters are in bold Parameters that may be required depending upon the driver are identified with an asterisk Underlined parameters can accept parameter ids or expressions as well as a number Keep in mind that users can add their own parameters to cfg files Both the documented parameters and a user s parameters can be read by MoCo s point processing software wherever a point id or expression is allowed A custom parameter might look like OAT season when used as a point s parameter value MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 87 of 116 As mentioned above a parameter ina cfg file can indirect to a parameter ina ini file To setup an indirect ina cfg file precede the target s name with gt ini For example net_addr gt ini net_addr_ha 7net This saves entering a specific network address in perhaps two dozen cfg files which facilitates future changes A 2 1 All Points Most of the following have system defaults and are not required Required parameters are in bold Most of the parameters might be included in the cfg file but some are run time variables that are useful for reading at run time only Underlined parameters are numeric variables that can accept variable names or expressions as well as numbers alarms Enables alarms A prioritized list of alarm chara
71. asily implemented 9 1 3 Perl Solution for Steady On Off Switches Some system implementers especially the younger folks prefer writing software code to setting up ladder logic points In some cases writing perl code is just simpler Therefore MoCo provides the hooks for creating a solution snippet in perl code This is accomplished by creating a calculation style driver subroutine The subroutine is written in pure perl syntax at this time Expect MoCo to provide a less geek means for writing program code in the future Perl programmers will have no problem understanding the following subroutine If you are not a programmer please have a look anyway You might be able to see what is being done Hint The logic is the same as the preceding ladder logic sub calc my 4way_switch Custom perl snippet to implement a custom 4 way switch Get setup before the actual work my p pSource ae Get subr parms cfg Sp digital 1 Digital point if amp calc_BEGIN Sp SpSource 1 return Do housekeeping my SLitesD SLitesN Must declare custom variables This is the actual 4 way switch logic The w specifies that the working value variant is to be used if Scfg onl w amp amp Scfg on2 w amp amp Scfg on3 w S cfg onl w amp amp Scfg on2 w amp amp Scfg on3 w Scfg onl w amp amp Scfg on2 w amp amp Scfg on3 w Scfg onl w amp amp Scfg on2 w amp
72. at Windows and standard unix like operating systems are not capable of realtime operation And further Ethernet ruins any possibility of deterministic response Given these realities MoCo attempts to provide response times that are good enough for most monitoring and control applications and leaves millisecond response time to smart bridges at a lower level The inter operability dilemma was solved in a simplistic manner which has proven to work well enough for MoCo Instead of attempting a cross platform implementation of forks non blocking tricks software interrupts etc MoCo can run a number of mocod daemons If one daemon is momentarily blocked while waiting for an interface to respond the other daemons can take advantage of the wait time to do their work Because mocod s code execution time has been measured at less than 1 of the wait times I O blocking and sleep time efficient utilization of wait time is important something the user should consider when deciding how to assign I O interfaces to different daemons Other challenges for multi platform operability include inter process communications and distributed processing the ability to run MoCo on multiple computers at the same time even if they are distributed world wide and on different operating systems In short these challenges were were overcome by favoring ethernet as the hardware means for both computer to computer and computer to interface communications and by usin
73. at lease one extra ladder logic point Except for output points a point s processing usually occurs on its interval and occasionally at other times mentioned earlier An output point on the other hand is normally executed immediately after it s source point changes value The source point contains a list of target points in its do_next parameter like do next lights1 lights2 lights3 While do next is normally for output points it works as well for quick scheduling any kind of point The catch is that any point including output points that are triggered bya do next must be on the same handler as the source point MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 37 of 116 In cases where the source point is owned by another handler or on a different computer an output point s source pt parameter is the only way to link to a source point Parameter source _pt can even accept an expression that contains logic and math If source _pt contains a point or points that are not in the handler data for the foreign point will be automatically obtained via the database Note that the process of waiting for a source point s interval and obtaining data from the database introduces delays resulting from polling database write latencies and network delays Consequently the system designer is advised to keep associated calculation points and outputs within the same handler as often as possible In othe
74. atabase Then restart entering mocod 0 if instance 0 The points owned by that handler that mocod instance are both listed on the screen and written to log file moco log The new point should be visible in that list In another terminal window and at the programs directory level use mocos to see a quick status of points If numbers are displayed for the new point rather than nothing or a then MoCo is reading in data If there are problems don t panic Inspect moco log forclues Carefully re check the all the parameters Verify that the handler instance matches the instance of the mocod that you started etc The optional startup kit includes most of the wiring with MoCo s configuration files already setup and nearly ready to go Users who do their own initial wire hook up and point configuration should expect to invest additional time for study and experimentation When configuration is complete verify that the computer is connected to the router with wire or WiFi ethernet cable is connected from router to bridge interface and that all sensor wires are connected to the bridge interface Before attempting anything with MoCo ping each ethernet device to verify that everything can communicate The ping command looks like this ping 192 168 0 240 The response from ping will indicate if the connection has succeeded or failed 2 6 Using FormEdit Some MoCo programs such as mocor allow a user to specify a wide range of operating
75. atched Use any alarm id A Z If a no latch alarm do not use cmd_a_H Instead use cmd_a_h to trigger a shell command when the alarm has gone active and auto acknowledged cmd_ah Alarm H has been acknowledged now displayed as h cmd_abd A bad data alarm has triggered It does not latch cmd_ama The manual alarm has been triggered and latched cmd_amc The manual alarm has been cleared cmd_a_ac All alarms are now clear To trigger a command from one of the above set the parameter to be the desired shell command For example to send a text message when a water pipe is about to freeze setup a command similar to the following The F alarm is setup to indicate a freeze alarm Shell script send text msg sh needs to contain the actual commands for sending out messages to various people The p and alarm variables in curly braces are passed to the shell script along with the text that follows cmd_a F send text msg sh p alarm Pipe close to freeze Note in the above command that the p and alarm variables do not include a point id before the dot If the point id is missing MoCo assumes that the point id is the same as point id of the variable that is being alarmed If the variables are for a different point then include the point id An alarm can easily be setup to drive an annunciator directly from MoCo One way is to setup a calc_ladder_logic point to look for one or m
76. aults can be fine tuned by entering new values inthe moco ini file Most of a program s informative messages prompts error messages and column headers can be customized by creating a mocor 1cl localization file for the program 7 3 History Reports mocor is MoCo s basic history reporting program The data for the report is obtained from the history table in MoCo s SQL database The history table includes history from all points from all integrated MoCo systems This may include one computer several computers on a local network or a world wide system of computers mocor reports the history of selected point values with selected characteristics over a specified period of time The columns differ depending upon the kind of report specified However they usually include the following information one way or another date time history value units remark and override and alarm information To run a default report that covers the last four hours without passing through the edit screen enter mocor The report will look something like this segment except longer 10 02 25 17 01 70 degF IATset InsideTemp Setpoint 17 01 22 mph WGusW Wind Gusts WX 17 01 4 OutFile 17 02 66 degF IATB Brewery Air Temp 17 03 65 degF IATB Brewery Air Temp 17 05 0 OnOff TClockl Time Clock 1 17 05 0 OnOff TClocklo Time Clock 1 Out 17 05 1 OnOff Tcloffo Off pulse fr TClockl 17 05 43 degF OAT Outside Air Temp 17 06 0 OnOff Tcloffo Off pulse fr TClockl 17 07
77. be found on the web If you understand symbolic logic but have had no experience with ladder logic or relay wiring don t panic ladder logic is easily translated to and from ladder diagrams and symbolic logic expressions in most cases Below is a ladder logic diagram soon to be demonstrated as an example of point HeatL MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 51 of 116 predawnT temp in lt 70 morningT sun temp in lt 68 l morn or HeatL aftnoonT temp in lt 72 result nightT temp out lt 20 temp in lt 65 Points like predawnT and morningT are time_clock points Alternatively one time_clock could have been used for all of this ifa time clock with stepped output had been used See if you can figure out how temp in is inside temperature and temp out is outside temperature sun is true if the sun is shining morn or is a morning override switch In MoCo the above is represented in the ladder logic point s heatL cfg file as rung 0 predawnT amp amp temp in lt 70 rung 1 morningT amp amp sun morn or amp amp temp in lt 68 rung 2 aftnoonT amp amp temp in lt 72 rung 3 night amp amp It s ok to use another line temp out lt 20 amp amp temp in lt 65 temp in lt 63 The translation is straightforward i
78. be the first alarm character in the list Threshold style alarm characters follow the character They are delimited with the pipe character without spaces The alarm character canbe a z fornon latch alarms and A Z for latch alarms Choose a meaningful character like H for High alarm L for Low alarm w for too Warm and c for too Cool The choice is yours The individual alarms are are defined in parameters with names like alarm_H alarm_L alarm_w alarm_c etc Note that the alarm characters are case sensitive they must match the character inthe alarms list Each alarm definition parameter has up to six fields separated by the pipe character Ifa field is not specified a default is used Here is a summary of the six fields 1 Threshold value for the alarm Required field 2 The transition direction that will trigger the alarm U for Up and D for Down U is default 3 Hysteresis value Hysteresis can prevent nuisance alarm transitions With hysteresis the alarm still triggers at the threshold value but grants some slack before releasing 0 is default 4 Rate of change per minute If the value threshold has been crossed and if the rate of change threshold has been exceeded then the alarm becomes active The rate of change parameter would normally be negative for down direction value thresholds The rate of change test is not performed if the field is null empty 5 Point s value variant id c for point c w
79. c points in the last handler to be started Start up handlers containing input points first The recommended startup sequence assures that calc points and output points have valid data to work with With multiple handlers use mocod start and mocod stop scripts to assure proper startup and shutdown sequence This should not be an issue if only one handler is being used These symptoms can also be caused by multiple copies of the same handler with output points running at the same time Verify with the unix linux ps command that all handlers are shut down Then do a clean startup In multi computer systems verify that another copy of the same handler with same output points is not running elsewhere In a failsafe system with multiple handlers covering the same points make certain that only one of the same handlers is enabled to write to output points This behavior can also be due to ladder logic implementations that have not been designed to deal with startup conditions in other words a ladder logic design flaw E 2 MoCo Software In general Ifa problem just starts occurring there is a high probability that somebody made a change that has precipitated the problem It is important to write down the exact time that the problem was first observed Check moco log for changes or error messages prior to the noted time which might lead to the cause of the problem If MoCo can sense a configuration error it writes messages to the log fil
80. calculated until propagations cease to change the calculation points results The number of re calculations is limited by the ini file s calc_loops parameter The default is 5 loops However this recalculation process is prevented from occurring if the calculation point s intv_only parameter is 1 5 7 1 Common Math Functions calc_functions Certain math functions are so common that they have been hard coded into the system sum average max min etc These calculations are efficiently provided by the calc_functions driver Touse calc functions do the following MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 49 of 116 1 Set parameter driver calc_functions 2 Select the function by setting parameter function equal to the desired function The following functions are available and more will be added as needed sum Suma list of point values average or avg Average a list of point values minimum or min Return the minimum value from a list maximum or max Return the maximum value from a list positive or abs Return the absolute value integer or int Return the integer portion of a real number 3 Setup the value or list of values to be processed in parameter parameters Individual values are delimited with the pipe character Use no spaces Values may be a simple point id or a point id variant point id attribute Example parameters IAT IATW w
81. co home Suser home S user moco If moco ini is in another directory the path and name can be entered with MoCo program commands like this mocod 2 mocod dvrs ini file User reed bin moco ini Once a mocod daemon has found the moco ini file it looks fora ini file for it s instance or handler For the example above it would look for mocod2 ini This ini file is optional Next MoCo a program needs to know where to find the various other configuration files cfg rpt usr and lc1 files Unless it findsa cfg dir parameterina ini file it assumes the other configuration files are in the program s run directory If all MoCo files are in the same directory a user needs to worry about none of the above However the options described above provide the flexibility needed to setup a secure environment if needed In a small system all the needed driver subroutines will be in perl files mocod mocod segl pl mocod seg2 pl and mocod dvrs pl the defaults However drivers may also have other file names A mocod handler can load additional driver files One driver file can be specified in ini parameterdvrs_ file If there is more than one driver file the additionals can be specified in array parameters starting with dvrs_file 0 or dvrs_file 1 These can be isolated to a specific handler by placing the parameters in the appropriate mocod ini file Again this potential flexibility can be ignored for most small or medium systems
82. compilation of perl It does include SQLite3 and apparently functions with the CPAN repository Strawberry Perl has been earning itself a good reputation MoCo has not been tested on Strawberry Perl but please feel free to check it out Option 3 Cygwin at http www cygwin com is another worthy option Cygwin is a Linux like environment for Windows that consists of two parts 1 a DLL cygwin1 d11 which acts as a Linux API emulation layer providing substantial Linux API functionality and 2 a collection of tools that provide a taste of Unix Cygwin provides a command line and environment that looks and feels like linux unix Many of the time honored Unix utilities like grep and rsync have been ported to or emulated on Cygwin The advantage of Cygwin is its unix style command line To date MoCo has not been tested on Cygwin If you decide to give it a try first check the package list at http cygwin com packages SQLite3 is on the list and that is a good sign From past experiences with Cygwin it can be expected to be solid But it cannot provide all of the helpful Unix features that are unavailable on Windows The good news is that MoCo was intentionally designed to not require these Unix specific features So please give Cygwin a try and let MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 12 of 116 MoCoWorks know how it goes Option 4 Once MoCo is running on Windows it is theoret
83. cters staring with alarm Alarm definition is alarm ID Contains threshold direction remark etc alarm_to_ Alarm threshold override level is alarm ID Can be manipulated via mocom cmd_a_ If is A Z Alarm A Z is active and latched Execute shell cmd in this parameter If is a z Alarm a z acknowledged Execute shell cmd in this parameter cmd_a_ac When all alarms are cleared execute the the shell cmd in this parameter cmd _ a_bd When a bad data alarm occurs execute the the shell cmd in this parameter cmd_a_ma When a manual alarm occurs execute the the shell cmd in this parameter cemd_a_mc When a manual alarm is acknowledged execute the the shell cmd in this parameter cmd c 0 If clean value goes false execute the the shell cmd in this parameter cmd c 1 If clean value goes true execute the the shell cmd in this parameter cmd o 0 If a user turns off an override execute the the shell cmd in this parameter cmd o 1 If a user turns on an override execute the the shell cmd in this parameter cng_filter Allows only specified logic transition to do_next a point Set 1 for false gt true set 1 fortrue gt false Used with calc points where interval 0 count down Leading edge of the variable s pulse causes counter it decrement count _up Leading edge of the variable s pulse causes counter it increment counting Counting enabled Use in cfg_ to enable counting by setting equal to 1 desc Point description
84. d The standard column names for the F option are as follows datetime point value units alarm override remark If different names are needed create a header ina rpt file Perhaps you would rather have a comma as a delimiter Then enter l1d_sep with no spaces on the command line along with everything else mocor uses an ISO 8601 date format as the default for this report like 2010 02 26 17 05 33 If adifferent date format is desired you can change it from date_fmt Sy4 Smo S md S hr mi se toa preferred format These parameters can be changed temporarily via the command line or more permanently by placing them in the moco ini fileor a rpt file Use the b switch to suppress extra output for batch file situations A typical command to silently output delimited data to a file looks like this mocor bF I 24h out_file inside points dat Although the need to change defaults on a beginner s system is unlikely be aware that defaults can be changed by entering new values in the moco ini file When changing default parameters it is important to understand that the precedence for selecting run parameters is versatile and therefore complex mocor gets its final run parameters according to the following precedence from highest to lowest edit screen command line rpt file ini file and lastly mocor s internal defaults Most messages and column headers can be customized by creating a mocos 1cl localization file f
85. d can be a viable MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 101 of 116 cost effective solution for commercial environments Besides a diversity of I O capabilities WebControl has a number of other features that enable it to work as an intelligent controller If a temperature crosses a predefined threshold WebControl can send email or turn outputs on or off It does not however have features like averaging and hysteresis which are available in MoCo A new PLC model is in development as this document is being written The circuit board is the same as the BRE model but the PLC firmware is different The PLC model allows the user to create and install a control program which can be useful for low level fast control applications Because the commands are not compatible with the original BRE model MoCo needs to know which bridge you are using When using the PLC model place model PLC inthe cfg files for this bridge WebControl handles eight 1 wire temperature sensors one Honeywell humidity sensor eight digital inputs three 0 10v analog inputs and eight TTL digital outputs The 1 wire buss will work only with powered 1 wire devices not with parasitic 1 wire devices or witing The DS1822 works OK with a 3 3v supply but the DS18B20 needs more voltage than the 3 3v supplied on the 1 wire terminal block When purchasing DS1822 or DS18B20 1 wire temperature sensors
86. d control system But some users like a pleasing GUI display and many customers demand it 7 6 Custom Database Reports Users who feel that MoCo s existing tabular reports fall short of needs have another option The data MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 72 of 116 for more sophisticated reports can be pulled from the SQL database Enter sqlite3 moco db on the command line to have a first look at the database structure In Windows use sqlite3 exe sqlite3 accepts standard SQL commands enabling a SQL literate user to select and dump data data to the screen or to a file After the data has been dumped to a file it can be fed to a graphical report generator SQLite works well with perl Therefore a programmer may prefer to query the database with perl and create a report that meets his or her needs To see how to do this look at the database commands in MoCo s source code The Definitive Guide to SQLite by Michael Owens also has examples of querying SQLite from various computer languages MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 73 of 116 8 Programming State Machine Points MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 74 of 116 9 Example Task Snippets 9 1 Turn On Multiple Lights with Distributed Switches 9 1 1 Ladder Logic Solution for Steady Push on Push
87. d with a short predefined ID like t1 for temperature 1 in the bridge Then the t1 in turn must be associated with the user s preferred point name in a MoCo cfg file Other bridges like the HA7Net do not have any setup for the individual I O points In this case the long 1 wire ID is directly associated with the user s preferred point name in a MoCo point s cfg file The cfg file always has the same name as the point name except with a cfg suffix For example if the point is named OAT outside air temperature or IHum inside humidity the cfg files will be named OAT cfg and IHum cfg respectively In these files the association between external names and internal point names are represented like device_id t1 fora WebControl bridge For a HA7Net bridge the association looks like device_id DB000801214E9B10 where this long ID is the actual unique 1 wire temperature chip s ID When associating with Insteon or X10 devices the addresses looks like 0A 32 B6 and A7 respectively The cfg file can contain many other parameters or preferences take your pick Some parameters are required for a given driver p point id net_addr can optionally point to an internet address in moco ini and driver Others are optional handler resolution hist_size and hysteresis for example Here follows an actual example of OAT cfg The required parameters are in bold OAT Outside Air Temperature Device parameters p
88. ding the curly braces characters If the replacement data is shorter than the allotted field length as it should normally be the field is padded with spaces This keeps the page layout from jumping around and columns aligned even when the length of the data numbers changes The direction of the curly braces determines the justification to justify left and to justify right xyz causes xyz to be inserted into the template field without any padding MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 45 of 116 See chapter Reports for details and examples 5 6 Time Points 5 6 1 Time Clock time_clock The time clock is perhaps the most well known and most commonly utilized of the points that fall into the time category In MoCo the time_clock driver implements a versatile time clock The time clock is a means for turning devices on and off according to a schedule The schedule may be similar to the following examples 7 30pm 6 00 am weekdays 17 minutes after every hour 23 45 on the last day of the month 6 30 8 30 on weekend mornings On 5 minutes and off 5 minutes forever and so on Events similar to the above can be used to trigger and drive outputs drive calculation points or run programs or shell scripts on result variable transitions Parameters cmd_c_0 and cmd_c_1 can contain command line commands to be executed on the transition Co
89. do anything useful until the following configuration files are setup With a startup kit many of the following files will already match the startup kit hardware moco ini And possibly additional ini files for each mocod daemon instance in more complex configurations Ppppp cfg A cfg file for each point rrrrr rpt Optional report configuration files 11111 1cl Optional localization files moco hh usr User definition files In the above ppppp is the name of a point rrrrr is the name of a report and 1111 is the MoCo program name for non English localization text The hh inthe usr file name is a user s handle typically the initials of a user For security reasons a program may require that users enter their handle For now use the handle sm for System Manager The System Manager s file moco sm usr needs to be on the system so do not change its name or delete it The MoCo installation package contains example point files thatend in cfg anda moco ini file These files should work nearly as is with the hardware startup kit that is available from MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 10 of 116 MoCoWorks However even with a pre configured kit expect to change IP addresses in moco ini and to enter unique transducer IDs in cfg files Interface hardware may also need to be setup to work within your local network While the purpose of hardware start
90. dundant enterprise systems MoCo s output points additionally have the capability to create on pulses or off pulses of specified length which are triggered from a leading edge trailing edge or both edges of the incoming value This facilitates controlling contactors latching relays that are turned on and off from separate on or off pulses As with input points read notes in Appendix D regarding the specific bridge Then verify an output interface s functionality with a browser before attempting a connection with MoCo After verification setup the output point s cfg_ file To assure the fastest responses it is important to keep in mind that the the output point must be on the same computer and handled by the same handler mocod daemon instance as the point or points that send their values to the output point In other words the output point cannot receive rapid sent do_next values from outside its own handler This in practice should not be a hardship in most cases because the I O bridges are all on a network easily accessed for input or output by any computer or handler Therefore input values can be easily read into any handler and outputs can be sent from any handler to the network interface For performance reasons the following option should be left as a second choice an output point has the ability to call for and receive a point s value from any point in a networked MoCo cluster But because it may receive external values
91. e Changes made via mocom are written to history and are visible in history reports Sometimes mocos even displays configuration errors in status reports Typos are the most common cause of problems So use the log and history reports to locate the last change which probably is the cause of the problem grep can be useful here as well System managers with a passion for minimizing trouble may require 1 that changes be made via mocom whenever possible 2 that other changes such as edited or new cfg files be noted as a remark via mocom and 3 that backups be made prior to configuration changes One of MoCo s most powerful trouble shooting tools it its ability to dump all cfg and ini variables while mocod is running This is done witha mocom command Trouble shooting experiments can be run by using mocom to alter individual cfg or ini variables MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 109 of 116 If someone has made a troublesome change or a typo the unix style grep program is also invaluable for quickly locating the cause of the problem grep can search all files for the occurrence of a string Just after installation When mocod is run multiple database errors are displayed Verify that the MoCo files did not get copied in as read only files If they are read only then change them all to read write A calculation point is not working properly MoCo s most powerful diagn
92. e and not the read back value in reports For safety reasons force val_force and gate are inhibited from altering the internal result of an output point because altering the internal value could obscure the actual value of the output device in reports Digital output drivers have the ability to create an output pulse when the source changes logic level This feature is useful for triggering a contractor to turn on a room full of lights or a large motor for example To activate the pulse option set parameter pulse trig to trigger on the edge of the incoming source logic level by setting pulse trig equal to one of the following up down or both Set parameter pulse sec to the number of seconds desired for the pulse An example follows On pulse Output Point for Time Clock 1 Source is TClocklt p LitesONo name Lights on Pulse desc Lights on Output Pulse device _id 02 net _addr gt ini net_addr_wc0 Refs IP address in ini file driver output_webcontrol WebControl bridge units OnOff pulse trig up lt pulse sec 10 lt snap_fmt 8lc An output cfg file fora HA7Net I O bridge would look similar except that device_id would be the 16 character ID of a 1 wire output device and the driver name would be MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 43 of 116 output_ha7net_ digital 5 5 Outputting Points and Their Values to a File Th
93. e if x less than y x gt y Results true if x greater than y x lt y Results true if x less than or equal to y x gt y Results true if x greater than or equal to y For text tests useful tor testing for alarms x eq y Results true if text string x equals text string y x ne y Results true if text string x does not equal text string y IMPORTANT When creating a comparison test to see if text equals X use single quotes around the text character or string only like X 3 Setup any other desired point parameters such as units force val_force etc Because ladder logic is by default a digital point parameters like resolution hysteresis and avg_size are not relevant However a creative individual might solve a difficult problem by forcing a ladder logic point to be an analog point Do this by setting parameter digital 0 You have probably already guessed that the HeatL ladder logic example implements a kind of smart thermostat The HeatL cfg_ file could look like this HeatL Smart Thermostat to drive a heater p HeatL name Smart Thermostat desc Smart Thermostat to drive a heater driver calc ladder logic rung 1 predawnT amp amp temp in lt 70 rung 2 morningT amp amp sun morn or amp amp temp in lt 68 rung 3 aftnoonT amp amp temp in lt 72 rung 4 nightT amp amp It s ok to use another line temp out lt 20 amp amp temp in lt 65
94. e or percent character to trailing curly brace or percent character If the replacement data is shorter than the allotted field length as it will normally be the field is padded with spaces This keeps the page layout static even when the length of the data numbers changes The direction of the curley braces determines the justification xy z to justify left and xyz to justify right xyz causes xyz to be replaced without any padding If the field proves to be too long due to a long variable name like HvacTLwhri var_hist the index number in the list shown in step 4 below can be used instead of the variable name In this example point HvacTLwhri is the sixteenth variable in the list 16 2 Create an out_file point named whatever you like say webPagel cfg 3 Set parameter tmpl_ file infile webPagel cfg for example to the name of the template file the file created in the first step 4 Setup the list of points that are to have their data stuffed into the template These names must exactly match the variable names in the template file You can use any variable with optional attribute defined in the system including ini variables For example you might use OutsTemp units For this example we use the following variables OutsTW HumW DewPW BaroW WSpdW WGusW WDirw 1 7 LvrmTW RestTB RestTC FermTA HvacTAi GlasTWw 1 13 HvacTlwfi HvacTlwhi HvacTlwri HvacTuwhi HvacTuwri 14 18 5 Just fo
95. e output_file driver enables a person to output a number of points to a file While mocod treats this point as an output point it differs somewhat from other output points let s consider it a maverick because it differs in the following ways 1 The output file driver writes to a file rather than I O bridge connected to transducers 2 This point can output more than one point value 3 The point that gets displayed or written to history is the quantity of points written to the file Ifa file failure occurs gets written to history 4 Other points do not send their results to this output point The list of variables to be output are listed in its cfg parameter variables Example variables IAT OAT WSpd c Note that the latency can be several seconds plus the scan interval 5 As illustrated above variants of a value like point c can be written to the file which can be handy 6 This output point can automatically retrieve point values from any point in a networked MoCo cluster It can even get its value from an expression However if a point is external to the handler accessible variants are limited to the working value and the clean c value Also keep in mind that values from MoCo handlers external to the output point may be delayed some seconds due to scan intervals and database latency 7 Every time the file is written an external shell script can be triggered by the cmd_outf parameter The command script can be setup
96. e result every scan interval of 30 minutes with the help of the point s stopwatch timer The MotorDCx point uses the calc_expression driver to evaluate the following expression expression MotorDCx timer 100 MotorDCx time_intv The expression does the duty cycle calculation Timer MotorDCc timer runs when the motor is running and stops when the motor stops It resets from internal variable MororDCx doing pt just after processing the point Variable MotorDCx time_intv is an accurate measure of the interval over which the calculation is being performed The doing_pt variable is true only when the point is being processed and that is when we want the counter reset The counter s parameters are setup in MotorDCx cfg Relevant parameters look like this intv_only 1 Allow calcs only at interval time interval 1800 30 minute interval start Motor Motor on Starts with timer running stop Motor Motor off Stops the timer reset MotorDCx doing pt Reset the timer every 30 minutes MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 78 of 116 At the end of the cycle the timer might just keep on running But it is reset at 30 minute intervals at the end of each calculation To prevent such calculations from being performed at times other than the interval set the point s intv_only to 1 as shown above There are other ways to calculate duty cycle which are a better f
97. ecorded in the moco log file At this stage of development the option for passwords has not been implemented The system manager s usr file moco sm usr must be on the system All the other users usr files must be in the same directory When looking fora usr file programs search a half dozen likely directories starting with the directory specified in the optional usr_dir parameter in a ini file When the system manager s file is found searching stops at that directory Because the usr_dir parameter is security related and for more reasons ini files should be protected in a secure environment This scheme prevents a bogus user from simply inserting a usr file at an accessible directory in MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 91 of 116 the search path Better security passwords will be added in the future as needed The usr file must be named beginning with moco followowed by the user s handle followed by usr like moco rw usr Inside the file only the user s full name is required at this time my name Reed White MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 92 of 116 Appendix B Sample cfg Files These sample files are are included here as a reference for parameters that can be used with specific point types They are not intended to be practical files The files contained with the software
98. electrical output from the I O bridge will track the input each time the file is saved MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 42 of 116 A simple digital output cfg file for a WebControl I O bridge might look like the following Output Point for Sprinkler Zone 1 Source is ZonelL p Zonelo name Sprinkler Zone 1 desc Output Point for Sprinkler Zone 1 device _id ol net_addr gt ini net_addr_wc0 Refs IP address in ini file driver output_webcontrol WebControl bridge units OnOff snap fmt 8 b An output point s cfg_ file fora HA7Net I O bridge would look similar except that device_id would be the 16 character ID of a 1 wire output device and the driver name would be output_ha7net_ digital With the ISY 99i bridge an Insteon device s device_id would look like 3C 20 A1 and an X10 s like C3 An output point will invert logic levels if parameter invert is set to An output can be forced to a value by setting over override to the desired value in the cfg file A user can override a point s output via mocom while mocod is running An output point s actual output can also be programmatically forced to a specific value similar to a manual override by setting parameter val_force to the desired value and setting force to true Digital points invert this value if inversion is called for These variables impact only the state of the output devic
99. ently than the 10x lower resolution clean history value Averaging and hysteresis are usually desirable because they reduce jitter in the system reduce the noise on data written to history and keep calculation points from repeatedly being jacked around Note the that resulting values may be slightly different than expected particularly if hysteresis is larger than 1 8 of the resolution parameter An unusually small ramp and or unusually large avg_size can also produce surprising results Finding the sweet spot for these parameters typically requires thought and experimentation If the analog conditioning parameters are setup with care clean data will be written to the database and only when necessary Note that the extensive cleaning described above is applied to two internal result values only 1 point h the internal history value written to the history database and 2 to the internal clean value point c which has the potential of being manually overridden The c is for clean value The working value point w has 10x higher resolution than the previous two and is cleaned only to the extent that 1 it s value can be optionally clamped between high and low limits 2 it can have hysteresis applied to it and 3 itis rounded point w is intended for internal calculations where faster response is needed and where higher resolution can be beneficial The w is for working value When doing calculations w
100. es so backup the database first File moco schema sql contains the appropriate SQL statements to DROP and CREATE one or all tables sqlite3 can execute one or more SQL statements at a time Copy and paste the desired SQL statements to sqlite3 s command line and strike enter It will be done in a flash MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 82 of 116 10 4 Shell Scripts A shell script is a kind of program that resides in a file and contains a series of command line commands that are automatically run when the script file is interpreted by the computer system On Linux or the Mac the bash shell interpreter is default Windows interprets bat files which have less capabilities and different syntax Cygwin on windows however does provide a unix style shell System managers rely heavily on shell scripts because if they are written with care they can reliably automate routine tasks Simple scripts can be amazingly useful Two simple scripts follow as examples of what can be accomplished without the author being a bash script guru This first script shuts down three mocod daemons bin bash mocod stop handle Shuts down all three MoCo handler daemons Patameter handle_ is the operator s initials Example mocod stop rw Check for a cmd line parameter operator s initials if 0 then echo echo This script will shut down all mocod daemons USAGE echo
101. escription 3 2 System Considerations As mentioned in Chapter 1 MoCo s ability to run on common computer operating systems was a prime design objective Perl goes a long way toward making this objective achievable Yet because MoCo would like to be a realtime system the multi platform objective remains a challenge that perl cannot totally solve Windows proved to be stumbling block because it is different from the other operating systems in many ways it sometimes lacks some important operating system features that are available on the other operating systems The most critical needs of a realtime system are the following ability for multiple processes to run MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 28 of 116 simultaneously deterministic response or at least fast enough response to I O needs ability for activities to continue in parallel while waiting for an interface to respond viable inter process communications and for the system itself to be bullet proof no crashes ever While most of these features are in some way available on Windows they are often implemented differently than on the other three all of which have nearly identical system level functionality Purists might argue that MoCo architecture does not meet all the criteria of a realtime system They would be correct MoCo does not provide millisecond response to outside events Some would argue th
102. ession sing control All are optional amp assume reasonable defaults point1l point2 point3 For rapid processing of result If 1 do_next on leading edge only 1 trailing only If 1 do_next to output points 0 block trig of outs If 0 no interval processing process only on the interval If 1 then totally disable the point If 1 don t show by default on reports Fh Se Sk RR SR H Fh Il ilable with any kind of point Timer value usualy read only X Trigger s timer start on leading edge of true tX Trigger s timer stop on leading edge of true Y doing_pt Reset counter on leading edge of true only parameters are specific to calc points not for cfg Precise time in sec for previous interval Precise time in sec when the calc is performed Precise time is nsec when the previous calc was performed vailable with any kind of point Current count on counter Usually read only pointI Enables counting Unuslly run time controlled pointJ Count up on leading edge Run time controlled pointK Count down on leading edge Run time controlled pointL Reset on leading edge Run time controlled USEFUL PARAMETERS n cfg for examples of the following other useable parameters 11 command triggers and overrides c especially Appendix A for complete list of parms is case sensitive ata that contains spaces me value variables is not important B 4 Calculation Ladder Logic cfg File Sample
103. etween daemons Time clock calculation and output points should probably reside together in mocod handler 0 In typical a situation handler 0 should also be able to handle an additional two dozen inputs Depending upon interval times additional input points might be distributed 50 per handler To reduce the probability of swamping a bridge with bursts of I O requests match a handler to one or two bridges When running multiple handlers there is an easier way than spawning a terminal window for each handler Except on Windows instances of mocod can be started in the same terminal window by running them as background programs Enter the following on the command line to startup three handlers in the same window mocod 2 amp mocod 1 amp mococ 0 amp Except on Windows the amp tells the operating system to run the program in the background All three daemons will display log style data to the same window Furthermore reports and scripts can simultaneously be run from the same terminal s command line If data is displayed to the screen while you are typing a command don t worry the system will not garble any of your commands All this action can be confusing on an busy system but it works You can always resort to running programs from several windows if the above suggestion creates too much confusion Startup sequences as above and shutdown sequences can be automated with a script See the section on Shell Scripts in the Mai
104. f the 230v wiring A shortcoming of both X10 and Insteon is that neither of the two controls fluorescent lighting very well but Insteon is more immune to the RF noise created by such lighting The ISY 99i enables a user to setup control scenes It also is a great aid in linking Insteon devices that can operate even if the server is down For more complex situations the homeowner can create if than else style programs If the program feature is used the server must be up at all times A person who needs the capabilities of both ISY 99i1 and MoCo has choices The most fundamental choice is where to put the control intelligence in the ISY 991 or MoCo or both depending upon a number of debatable issues Control engineers argue such questions until it s time to quit work and go home so clearly the decision is yours MoCo s input _isy99i driver enables the user to read the state of Insteon devices or ISY 991 scenes Although X10 states cannot typically be read MoCo remembers the last X10 output sent and it displays this value for each X10 output point MoCo s output_isy99i driver can output to both Insteon and X10 devices For Insteon MoCo s driver understands 0 for off 255 for full on and 1 254 for in between dim levels However MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 104 of 116 an Insteon device can be made to respond to 0 for off and 1 for full on if the output po
105. file output f just data F with col names Execute immediately without edit Similar to b for batch xMmhOoUtoCH OPA HO Switches and other arguments can be in any order The report mask parm is first tried as the name of a report file rpt file If the file does not exist it is treated as a point mask Point masks can look like OAT Wind IAT IAT IATW OAT OATW no spaces in the mask The duration parm is the time covered by the report Examples of commands mocor 8h Display all points last 8 hours mocor u 30m Anything unusual in the last 30 minutes mocor a I 2d Alarms with ids beginning with I 2 days mocor c IAT OAT 2 column report limited to points IAT amp OAT mocor o l1mo Display all points with overrides 1 month mocor wx rpt 12h Display report defined by file wx rpt 12 hr mocor inside Display report defined by file inside rpt Note that cmd line parms override parameters defined in rpt files For example discrete times like from 080313 1230 to 080315 0600 The t4 switch displays data in up to 4 columns The t7 switch displays data in up to 7 columns but with truncated remark field Point ids and units are displayed in the header Of the 4 or 7 numbers in a row just one is the value that matches the time on the left This number is identified with an asterisk The other numbers are there to facilitate readability If an alarm or remark happened for a result a gt is displayed next
106. fmt je Now a 10 second pulse that triggers from the time clock s trailing edge down pulse Off pulse Output Point for Time Clock Source is 5on5offt p OffPulseo name Off pulse fr 5on5offt desc Off pulse Output Point for Time Clock 5on5offt device _id 03 net_addr gt ini net_addr_wc0 Points to ip addr in moco ini driver output_webcontrol WebControl bridge units OnOff pulse down Trigger on down edge of time clock result pulse _ sec 10 Pulse length of 10 seconds snap fmt 6 f To custom format the snapshot report The time clock s result can be programmatically forced off by setting val_force 0 and force 1 The 1 or any non zero value or 0 can be supplied by another MoCo point variable or expression Similarly the time clock can be forced on by setting val_force 1 The time clock s result can be gated with the gate parameter If the gate parameter evaluates to 0 the time clock s result is always 0 If gate evaluates to 1 then the time clock s result is the normal functional result The gate value is actually multiplied by the time clock s intermediate result As a safety precaution these programmatic overrides do not directly change the internal value of output points Instead they override the value that is sent toward the output actuator If inversion is called for the value is inverted before being sent The forced value does not get propagated to the output device un
107. for point w h for point h etc Variant c the clean value is default 6 An optional very short message to be displayed in reports when there is an active alarm Remember to surround the parameter in double quotes if there are any spaces in the text string 6 3 Handling Alarms MoCo software attempts to provide convenient tools for the managing of alarms It does so by providing useful status data alarm counts and shell commands that can be executed upon alarm events MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 59 of 116 Alarm information is written to database tables history and snapshot The alarm character events event times and remark are written to both An alarm character is not displayed if alarms are not enabled for the point If an alarm is enabled but not triggered a character is displayed When an alarm event occurs a remark is generated that includes the alarm character the threshold value and the pre defined short text string This information is displayed in MoCo reports For history data the alarm character is encapsulated within the history table s status field In mocor history reports it is displayed with the remark For status data the alarm character is encapsulated within the snapshot table s alarm field In mocos status reports it is displayed to the far left of the line upper case for not acknowledged or lower case for acknowledged
108. forums experiment and lastly use email support The following short descriptions are not a substitute for the afore mentioned process but they should help a new user avoid common pitfalls for a particular product If you have anything to add that will save others time and frustration please contact MoCoWorks We will add your insights to this document D 1 HA7Net The HA7Net bridge works with up to one hundred 1 wire sensors input devices and output devices According to the Embedded Data System s web site the HA7Net operates with the following devices e DS18B20 12 bit 1 Wire Digital Thermometer e DS18820 9 bit 1 Wire Digital Thermometer e DS1920 Temperature iButton e TAI8540D Humidity Module e DS2406 Dual Addressable Input Output Switch e GP1 Counter Pulse Counter DS2423 e T8A 8 Channel 0 5V Analog Input e Z2Ten 0 10V Analog Output e DS2438 Smart Battery Monitor e DSP7x4 Digital Display At this time MoCo s drivers support the 1 wire temperature sensors and 1 wire DS2406 digital I O devices mentioned above The Dallas Maxim DS18B20 temperature sensors are available from EDS as discrete devices and from numerous components suppliers The other EDS products are supplied as circuit boards with parts mounted The HA7Net is a small black box with one ethernet port and three 1 wire ports It requires a 6 12v power supply which is available from EDS as an extra The HA7Net works with both parasitic and powe
109. g a SQL database for software interprocess communications as well as for conventional storage of status and historical data Note that in multi computer enterprise environments SQLite must be replaced by a server style database such as PostgreSQL or Oracle Such enterprise databases use internet protocols to implement their distributed database features While MoCo is designed to work with these and other common SQL databases it is routinely tested only with SQLite In summary mocod is the MoCo program that does the time sensitive data acquisition and processing Multiple instances of mocod run as daemons so that interface communications can be serviced without objectionable delays The daemons on a single computer system are named like handler mocod0 mocod1 mocodz2 etc In a multi computer network the handler ID includes the node ofthe computer as handler robbie mocodo When configuring the system the user needs to consider how to assign the various interfaces to a daemon or handler It is usually wise to assign the time calc and output points to the same daemon and start this time calc output daemon last in the startup sequence Each I O interface might be assigned to another daemon or not On the other hand if the number of total points is below 50 and the sampling interval for input points is between 10 and 60 seconds then one instance of mocod should be adequate This decision hinges primarily on the response time of the
110. h they reside Consequently users are encouraged to develop web based user interfaces that utilize html or php code that works reliably on conventional web servers and browsers A variety of web servers are available for the common operating systems The Apache web server is free and a world wide standard It is already installed on Mac computers However it must be enabled in System Preferences and php must be enabled by uncommenting a line in the private etc apache2 conf file Apache with php can be downloaded to Windows from http www apache org Apache with php capability is already loaded on most Linux systems Once the web server with php has been enabled the system developer creates conventional web pages The web pages may be constructed of php code which has the ability to directly access data from MoCo reports or the MoCo database Or the page may be coded as html templates that are repeatedly stuffed with real time data With driver output_file MoCo provides a means for stuffing templates with real time data The result can be either used directly as a text style file for display oran html or php file that can be displayed on the web This feature enables the creation of animated screens where text and point values change in real time Real time data fields can be individually left justified centered or right justified Changeable labels can be displayed just like real time numeric data For html web pages MoCo s basic feature
111. handle every desired external action Instead MoCo provides a means to trigger a program or shell script The program or shell script can be setup to do almost anything that can be done on a computer send a phone text message send an email transfer a file to another system update a web site pop up a warning display display a mocos status report feed a large ticker display panel etc MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 61 of 116 For example suppose that an alarm triggers because a chiller temperature has gone too high or because the chiller has begun drawing higher than normal current The alarm could trigger command mocos Chil This would display current status for all chiller related temperatures pressures and power consumption In this simple example the status screen would display within the same window that mocod is operating within A more sophisticated script could cause the status screen to be displayed on terminals around the plant Or a copy of the status report could be emailed to the maintenance team whenever a serious chiller alarm triggers A shell command can be setup for each of a point s 28 different alarms And the trigger can occur on new alarm alarm acknowledge and alarm clear up to 58 possibilities for each point Here are some examples of a point s cfg_ file alarm commands cmd_aH Alarm H for example has been triggered amp l
112. his inconvenience PATH variables can be adjusted in files like etc profile for system wide changes or in the hidden profile file in user accounts You can view hidden and non hidden files in the current directory by entering 1s a File permissions for executable programs or scripts must be set with chmod to something like 755 so that the program will be allowed to execute The primary executable programs are mocod mocom mocor mocos Shell scripts must also be made executable in the same way To temporarily avoid these configuration steps just enter perl program name Run each of the above programs to see if they run without perl errors For mocod quit the program immediately after the short help message Otherwise it will need to be killed with a control C which is undesirable because in rare instances it can corrupt the database If there is a problem with any of the programs first check to verify that all needed perl modules are available Enter the following commands No response no error message from the following means MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 9 of 116 that the module is already installed perl e use LWP UserAgent For web communication perl e use Time HiRes For higher time resolution perl e use DBI Gen purpose database interface perl e use DBD SQLite sqlite3 database Install perl modules If modules
113. ically possible to convert each MoCo program to a Windows exe file using a program called per12exe In order to operate on Windows per12exe requires ActivePerl mentioned above or IndigoPerl The perl2exe program is free for evaluation from Indigo Star Software at http www indigostar com perl2exe php While this scenario has not yet been tested on MoCo it has a history of being reliable over the years The advantage of such an approach is that it would provide an easy installation for those who who do not know anything about perl or Linux Unix commands A disadvantage is that perl distributed in this manner cannot be easily read or modified ActivePerl Installation Procedure 1 Download the free Community version of ActivePerl from www activestate com downloads At time of writing the Windows x86 version was 5 10 1007 The download includes the perl modules needed by MoCo as well as SQLite 2 Double click the install icon It is recommended that you accept all the defaults The download is packaged asa msi file For older computers with an old version of Windows you may encounter the need to download the MSI installer software from the Microsoft site 3 Copy all of the MoCo software toa moco subdirectory like D moco 4 Windows requires that perl programs have the pl suffix If pl files are missing rename the following MoCo programs to end with the pl suffix mocod pl mocom pl mocor pl mocos pl 5 Verify with Exp
114. ile Once a program starts running it works with both the original constants and with new internal cfg variables The name we use for run time cfg constants or variables is attribute In this document if cfg does not have a leading dot it refers to a program s run time cfg constants and variables and not the original constants from the cfg file The same convention is used for ini constants and variables The software that implements a point can access not only the main point value but it can also access a large number of point attributes From the user s perspective a point attribute is represented as point attribute Replace point with the point id and replace attribute with the attribute name Think of attribute as directly representing a point s cfg constants and variables or properties Likewise user software can access ini constants and variables as ini attribute Replace attribute with the attribute name but leave ini as ini A subset of the attribute is the point s variant The point has a primary working value which is represented as point or with more verbosity as point w The point also has a number of other values which we shall call variants In this document when you see the form point variant you should understand this to mean one of a points s variant values For example h isa variant value that is written to the history database It is written as point h
115. inputs are 0 10v analog inputs like al to a3 The single humidity input is identified by h1 TTL outputs which can be read as inputs are identified as 01 to 08 Suggestion Each I O bridge has its own personality See Appendix D for details that may not be in the manufacturer s manual Verify that the new sensor works with the parameters you entered similar to those above If mocod0 is running at the moment terminate it with mocom by entering mocom 0 shutdown 5 The 5 in the above command is the number of seconds the driver is to wait before quitting Then restart entering mocod 0 if instance 0 The points owned by that mocod instance aka handler are both listed on the screen and written to log file moco log at startup The new point should be visible in that list On a different terminal window use mocos to view a quick status of points If numbers are displayed for the new point rather than nothing or a then MoCo is indeed reading in data If problems inspect moco log forclues Re check the accuracy of the parameters Verify that the handler name s trailing digit matches the instance of the mocod that you started etc The most difficult part is done Configure the point s data compression parameters similar to the following Data parameters units degF Physical units up to 5 characters in length scale and offset can be used for units conversion and for calibration scale 1 8 C to F offset
116. int s driver The feature is desirable because hardware inputs sometimes have reversed sense inverted voltage A comprehensive description of required recommended and optional parameters for each kind of point can be found in Appendix A Appendix B shows the parameters as they might appear in cfg files 5 4 Conventional Output Point After a developer has successfully setup input points from a bridge the steps for setting up an output point will be familiar Perhaps the biggest difference between input points and output points is how they receive and send their data Points other than output points specify the sources of their data and they can optionally send their results immediately to one or more other points usually output points Output points on the other hand do not normally choose their non output source points Rather the source points determine to which output points they send their result Although only one digital point ordinarily sends to a given digital output point it is theoretically possible for more than one time clock or ladder logic module to send their results to an output point Trouble shooters should keep in mind that two points sending to the same output can produce interesting results However as stated earlier it is quite normal for a non output point to send its result to more than one output point Points such as ladder logic points that send their result to output points by do_next triggers can be pr
117. int s gate parameter is set to 255 For X10 MoCo s driver understands 0 false for off and non zero true for on When controlling Insteon with MoCo via an ISY 991 you use Insteon s device address not the alias assigned in ISY 99i The address looks like 1A 34 B2 MoCo s driver massages the device address to look like 1A 34 B2 1 before it sent to the ISY 991 ISY scenes are identified with a number like 40518 which can be specified as an address When controlling a X10 device you use the traditional X10 house code unit address that looks like A7 or G12 As with other drivers these addresses are entered into the device_id field ofthe point s cfg file The ISY 99i s network address must be entered into the net_addr parameter of the point s cfg file or indirected to the address in the ini file The ISY 991 requires its current user id and password for requests received from MoCo These are entered into the URL address like the following Replace user password and 192 168 0 230 with your values http user password 192 168 0 230 Or https user password 192 168 0 230 for more security If this method of specifying user and password is determined to be insufficiently insecure it may be altered in a future software release As with other points the specific net_addr_ need not be stored in each point s cfg file It can be stored in one place in moco ini by indirecting from the cfg file using a pointer in the cfg
118. ions mocom can be run in the same window as mocod handlers if mocod was started with the amp option mocod 1 amp for example The amp tells the operating system to run the mocod daemon in the background This works on Linux Unix and Mac With MS Windows mocom is run from its own window And the mocod handlers are each run in their own windows 4 2 Operation mocom s help screen is shown below Except when requesting the help screen with h the first parameter is always the initials of the user the user s handle Take note that mocom will not allow the user to execute its commands unless the user hasa usr file configured with at least one parameter inside This is because mocom in unfriendly hands could do some damage MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 31 of 116 The object argument follows the user s handle onthe command line The object includes the names of entities like the ini parameters a point or a configuration file Next the user enters parameter name and parameter value followed by an optional remark This information is all entered on one line in one shot no fuss Alarm commands and the remark command are different than the others in that they need one less argument than the others The following help screen should make mocom s usage more clear Usage mocom is a command line MoCo communications program mocom Switches
119. ire more tries After logging on change the bridge s IP address to an unused static address like 192 168 0 240 Do not change the subnet numbers in other words keep the first three groups of numbers in the IP address the same Deluge of network failures and retrys There are three likely causes 1 the network is not functioning properly 2 typos in MoCo network address parameters and 3 the bridge is not responding Try these troubleshooting steps listed from easier to more time consuming 1 ping the IP address of the bridge as ping 192 168 0 250 2 If ping fails verify that the bridge is powered up Power cycle it 3 If ping works use a browser to connect to the bridge s web server 4 Attempt to read sensors using the bridge s web page 5 Verify that the IP address matches the addresses setup in MoCo parameters 6 Verify other parameters for a failing point in particular the device_id MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 111 of 116 7 If there is an indirect IP address pointer cfg to ini verify its accuracy Initially no network errors then an increasing number of network errors with time The performance of consumer routers especially wireless routers has been known to deteriorate with time since last re boot Network problems can be further aggravated by resource hogs like YouTube Intensive audio video applications that use the network can leave a
120. it for long on off cycles See if you can design one Hint You may need two timers 9 3 Door Opening Counter If a person needs to count how often a door is opened or how many people pass a sensor this example provides a start In this example we count the number of door openings per 15 minute interval The results indicate the busiest times of day The counts per 15 minute window are converted to door openings per hour This can be achieved witha calc_expression point that calculates the result every scan interval of 15 minutes and with the point s up down counter DoorCntxX is the point s ID The calc_expression driver evaluates the following expression for point DoorCntx expression DoorCntX counter 3600 DoorCntX time_intv The expression does the door openings per hour calculation Counter DoorCntX counter increments when the door opens It does not double count because the counter increments only on the leading edge of the door open pulse The counter resets from internal variable DoorCntX doing_ pt just after processing the point The counter s parameters are in file DoorCntX cfg Relevant parameters look like this intv_only 1 Allow calcs only at interval time interval 900 15 minute interval counting 1 Enables the counter to count count_up DoorOpen DoorOpen point increments the counter reset DoorCntX doing pt Reset the counter every 15 minutes The counter is always free to keep counti
121. itha calc point a user may choose one of a number of representations of a point s value The preferred variant of a point s value for calc inputs is the working value point w or simply point for short The working value has 10x greater resolution than the resolution specified by the history s resolution parameter Keep in mind that point w has the capability of being overridden by a user in case a sensor goes bad or for debugging purposes The afore mentioned clean value point c is a cleaner smoother value This value is exactly the same as the value written to history except that like point w itcan also be overridden by a user While very smooth and stable point c suffers ta disadvantage Due to averaging or a ramp limit it lags behind the less clean point w There are other options such as non overridden values but working point and clean point c are most likely to be used as inputs for calculations MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 24 of 116 The bad or null data flag will display in values point h history value or point v high resolution value in place of a number if the value cannot be read or if MoCo recognizes the value as outside of normal limits MoCo prevents the bad or null data flag from reaching point c and point w Instead these variants have the last known good value This prevents calculations and ladder logic from propagating spuri
122. iver input _web page inthepoint s cfg file and set the net_addr parameter in the cfg or ini file to look like net_addr http www whatever com my data html Or indirect to the address in ini file like gt ini net_addr_xyz If the point data comes from a local computer file specify driver input _file and set the in_file parameter in the cfg or ini file to look like in_file my data dat Or indirect to the address in ini file like gt ini in_ file xyz Similarly MoCo s output _file driver enables MoCo to output multiple point variables to a file It can obtain its point values from any computer in a MoCo network which facilitates testing Variables to be output are listed in the the output point s variables parameter However because output file obtains external point data via the database it can be slower than MoCo s normal fast output drivers Keep in mind that MoCo provides a means for input calc and time points to quickly send their result value to an output point or points An input on off switch for example can be routed through MoCo directly to an output actuator This is accomplished by setting the source point s do _next parameter to the point name of the output point This direct in out capability can be useful for startup and testing MoCo s hardware I O drivers connect to hardware interfaces or bridges that work via ethernet port or wireless WiFi port The communications protocol for these devices
123. k SceneX equals 3 otherwise the expression evaluates to 0 This enables each ladder logic point to send signals to output points only when the appropriate phase is active Note also that enable out prevents do_next output triggers from reaching output points only With this technique output points will only receive signals from a ladder logic point when the point is selected by its designated phase number By design the other ladder logic points will just have to twiddle their thumbs until it is their turn to send outputs If ignored and unused enable out defaults to true In other words outputs are enabled by default The enable out feature may seem uninteresting or confusing to early implementers MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 56 of 116 But please remember the capability it becomes quite useful in sophisticated systems While the afore mentioned time clock solution works well for a fixed schedule there are situations when the scene or staging sequence needs to be triggered at random times For example when a person walks into a room and flicks a light switch the scene lights would come up in a timed sequence In an industrial environment heavy machinery starts up in a staged sequence perhaps for the purpose of preventing power surges By using a point s timer ladder logic points can solve the problem The timer in the first ladder logic point
124. l conditioning features to create a smooth result DS18B20 Occasional readings of like 85C 185F from a sensor at room temperature The Vdd line is not tied to 5v or ground WebControl Sensors are not being seen by the bridge After connecting new sensors power cycle the bridge WebControl works only with powered parts and powered wiring Verify that PAR parasitic only 1 wire sensors are not being used Warning Mislabeled parts are being sold on the internet Verify that 5v is on all sensor Vdd terminals E 5 X10 and Insteon Device never responds Verify address settings in both device and MoCo cfg files X10 addresses can usually be mechanically set on the device If there is no visible way to set the address then follow the manufacturers instructions Sometimes a device s address is set with a button pushing procedure MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 112 of 116 Insteon addresses are hard coded and marked somewhere on the device Locate and write down the address six hex characters Then to reduce the possibility of noise place the transmitter and receiver close together on the same circuit and away from other electronics equipment such as computers UPS protective power strips home entertainment centers plasma TVs etc Device responds some places but not other places X10 and Insteon devices have a tough job They send weak signal over powe
125. l not work correctly unless their internal parameters match the sensor s hardware details such as device ID and network address To avoid confusion these sample files are named with the CFG suffix in capital letters MoCo will ignore these files After editing a sample file to match your hardware change the CFG to lowercase cfg The CFG files that begin with sample illustrate which parameters will work with a type of point They are reference files not intended to be functional cfg files as is Distribution files that will function properly without being edited to match specific hardware have the lowercase cfg_ suffix If you choose to have bridge IP addresses centralized in one place file moco ini will have to be edited to include the proper bridge IP addresses More about this in a moment Instead of using real sensors new users may instead soft test the software without connecting any hardware interfaces Do this by setting up points that use the input web page driver or the input file driver These drivers enable MoCo to input data from a web page or file instead of a hardwired sensor They extract points and values from text in a web page or file that looks like this OATemp 32 4 Or OATemp 32 4 TATemp 71 2 Or IATemp 71 2 MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 14 of 116 WindSp 12 Or WindSp 12 If the data comes from a web page specify dr
126. ladder logic solutions don t be afraid to think outside the box 5 9 Implementing Scenes The scene is a an important concept in home automation The term scene typically refers to a MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 55 of 116 lighting environment for a room or set of rooms It includes controllable lights that are set on or off More sophisticated scenes include the dim level and the rate at which lighting turns on or off Other aspects of the environment such as music or home theater can be setup as well Home automation systems often activate a scene at a particular time of day or after an event Because scenes are so important in home automation home automation software has special setup screens and files that define scenes Although MoCo is a more general purpose monitoring and control system its basic building blocks enable a person to configure scenes in the same spirit as a specialized home automation system Regardless of the system and its user interface the concepts are identical A set of devices are controlled as a function of time or events With MoCo scenes can be setup with time clock points and with ladder ladder logic Probably the simplest implementation would be to setup a time_clock point for each scene The time clock would turn a static scene on or off at different times of day which may be different on weekends etc Using the time clock
127. ldcard characters The following wildcard characters same as for Linux and similar to Windows are supported by MoCo reports Zero or more characters Exactly one character abcde Exactly one character listed a e Exactly one character in the given range abcde Any character that is not listed a e Any character that is not in the given range The search mask is case insensitive Multiple point ids or point id masks can be used like hvact hvacc lvrmtw restb While mocos and mocor can meet the basic needs for reporting they lack the color and class of a graphic plot Graphic reports have not yet been formally adapted to MoCo However MoCo report programs can optionally produce a format like database output that can be processed downstream to generate a GUI result Furthermore MoCo historic data is stored in a conventional SQL database Open source and commercial software is available that can create reports from SQL databases it just takes development time and possibly money 7 2 Status Reports mocos is MoCo s basic status reporting program The data for the report is obtained from the snapshot table in MoCo s SQL database The snapshot table includes all points from all integrated MoCo systems This may include one computer several computers on a local network or a world wide system of computers mocos reports the current status of points aligned in the following columns alarm status point id current worki
128. le with the alarms parameter which contains a list of alarms However alarms can be limited to the bad data and manual alarms by setting the alarms parameter thusly alarms i With driver input_alarm_tally one or more special alarm points can be created that display the number of active triggered alarms The display format looks like 2 04 where 2 is the number of active unacknowledged latched alarms and 4 is the total number of active triggered alarms The alarm point is a digital input point that behaves like any other digital input point You can even configure an alarm for the alarm point input_alarm_tally can be configured to cover one of three possible scopes Set parameter scope to 0 totally all alarms in the handler Set scope to 1 to cover the node the computer Set scope to 2 to cover all alarms on a MoCo system world wide The default scope is 0 6 2 Configuring Alarms MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 58 of 116 Alarms are configured in the point s cfg file Here is a short example alarms H L Enable alarms and set priority alarm_H 95 U 2 c Glass room too hot alarm_L 32 D 2 c Glass room freezing The alarms parameter enables alarms and lists possible alarms in order of priority highest priority to lowest priority The manual alarm is always the highest priority alarm If alarms are enabled must
129. les as follows Enter sqlite3 moco db After sqlite3 starts up and after the sqlite gt prompt enter read moco schema sql Then quit the program 4 Using your startup script probably moco start restart the mocod handlers with the new database Or restart each handlers like mocod 0 etc Whenever mocom is run it aborts asking if the user forgot to enter his or her handle Your handle must be registered witha usr file Try using the system manager s handle sm If this works setup a usr file for your handle E 3 Networking Cannot get new I O bridge to respond to a browser If connected through a router use standard cables not a cross connection cable For first contact and setup the router needs to have DHCP enabled which is typically the default The trick is to determine which IP address DHCP has assigned to the bridge If the subnet address range and starting DHCP address are not known get this information from the router s maintenance screen Let s suppose that you determine from this information that DHCP addresses start with 192 168 0 100 Power cycle the router unless terribly inconvenient to do so Start attempting to logon to the bridge with URL address 192 168 0 100 then 192 168 0 101 etc until the bridge s web page appears If your computer and the bridge are the only active nodes on the network you will strike gold within several tries If there are a number of other users locating the bridge may requ
130. lls it on your computer The installation process can be slow so please be patient sudo port install p5 dbi sudo port install p5 dbd sqlite sudo port install p5 libwww perl sudo port install p5 time hires NNW Now jump back to the linux unix instructions above and continue from the Verify installation paragraph 2 3 Installation on Windows Although Microsoft does not include perl with Windows there are a number of non Microsoft sources for perl on Windows 1 download the free Active State perl suite 2 download the Strawberry Perl suite 3 download the open source Cygwin suite 4 run MoCo perl programs that have been converted to Windows style exe files or 5 add a Linux virtual machine using VMware or one of the open source solutions Option 1 The Active State perl suite is free reliable and comprehensive ActivePerl can be downloaded from http www activestate com downloads Active State s included PPM manager provides access to over 3000 perl modules The perl modules required by MoCo are already included in the download Additional modules can be browsed at http aspn activestate com ASPN Modules Their SQLite documentation is at http docs activestate com activeper 5 8 lib DBD SQLite html A detailed step by step installation procedure is detailed below Option 2 Strawberry Perl at http strawberryperl com is similar in functionality to Active State s ActivePerl Strawberry Perl is a non corporate Windows
131. logic in the next section Example of a math expression expression OAT OATW 2 IAT IATW IATH c 3 4 Setup any other desired point parameters such as units resolution hysteresis etc Anexample ofa calc_expression point that computes the difference between average outside air temperatures and average indoor air temperatures follows TDiffc Diff between multiple outside and inside air temps p TDiffc name Out in Temp Diff desc Difference between outside and inside air temps driver calc_expression expression OAT OATW 2 IAT IATW IATH c 3 units degF interval 120 avg_size 3 resolution 5 hysteresis 06 snap_fmt 5 d While logic evaluations are usually performed by the calc_ladder_logic driver logic tests such as greater than or less than can also be used in calc_expression The following would evaluate to a if true or to a zero if false temp gt 70 Available test operators like lt are described below with ladder logic 5 7 3 Ladder Logic calc_ladder_logic Ladder logic is a means for making complex logic decisions Ladder logic will be quite familiar to anyone who has programmed a PLC Programmable Logic Controller Ladder logic simulates the wiring of relays but has been enhanced by various manufacturers to do even more The various implementations vary MoCo s implementation is described below If you are unfamiliar with ladder logic tutorials can
132. lorer Files gt Properties that the files did not somehow get copied in as read only files If they are read only select all and use the same screen to make all files read write 6 Run each of the above programs to see if they run without perl errors For mocod p1 quit the program immediately after the short help message Otherwise it will need to be killed with a control C which in rare instances might corrupt the database If there is a problem with any of the programs first check to verify that all needed perl modules are available Enter the following commands No response no error message from the following means that the module is already installed and available perl e use LWP UserAgent For web communication perl e use Time HiRes For higher time resolution perl e use DBI Gen purpose database interface perl e use DBD SQLite sqlite3 database If a perl module is missing run ActiveState s ppm from the command line to install the missing module The MoCo system should be ready to go after any errors are resolved From this point go to the linux unix instructions above and continue from the Configuration Files paragraph When entering file paths in MoCo parameters do not use Windows backward slashes MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 13 of 116 Remember to use forward slashes like the other operating systems 2 4 SQLi
133. ly 1 If 1 process only on the interval disable 1 If 1 then totally disable the point stealth 1 If 1 don t show by default on reports Timers Aavailable with any kind of point all are optional timer 1000 Timer value usualy read only start pointx Trigger s timer start on leading edge of true stop pointX Trigger s timer stop on leading edge of true reset pointY doing pt Reset counter on leading edge of true These read only parameters are specific to calc points not for cfg time_intv Precise time in sec for previous interval time_now Precise time in sec when the calc is performed time_prev Precise time is nsec when the previous calc was performed Counters Available with any kind of point all are optional counter Current count on counter Usually read only counting pointI Enables counting Most often run time controlled count_up pointdJ Count up on leading edge Run time controlled count _down pointK Count down on leading edge Run time controlled reset pointL Reset on leading edge Run time controlled ADDITIONAL USEFUL PARAMETERS See sampleiIn cfg for examples of the following other useable parameters alarms shell command triggers and overrides See MoCo doc especially Appendix A for complete list of parms NOTES Everything is case sensitive Quote any data that contains spaces Order of name value variables is not important
134. message 3 Verify that the required perl modules are installed Install any missing modules from CPAN 4 Run each of the above MoCo programs in step 2 to verify that they run without perl errors Apple Mac OS X Installation Overview 1 Copy all MoCo files to a convenient directory 2 Set file permissions on the following to be executable programs mocod mocom mocor mocos and shell script clear snapshot and clear message 3 Install MacPorts software from the web 4 Verify that the required perl modules are installed Use MacPorts to install any missing modules 5 Run each of the above step 2 MoCo programs to verify that they run without perl errors 2 1 Installation on Linux or Unix Perl is already installed on all conventional Linux and Unix systems so there is no need to install perl However additional perl utility modules maybe required as explained below If the objective is simply to evaluate MoCo copy the MoCo software files to a convenient directory like home your name bin moco The software can be easily moved to a more permanent directory at a later time In the following we make the assumption that readers who are using Linux or Unix already have experience with unix style commands Note that unless the bin directory or other directory of choice is setup in the shell s PATH variable program names may have to be preceded by before the program will run from your current working directory To remove t
135. mmon time_clock applications include lighting systems scenes HVAC chores sprinkler systems etc The means for communicating the schedule to MoCo is viaa cfg parameter called times The times parameter can contain one or more codes which programa time _clock point Here below are some examples of codes that can make up the times parameter Note the 1 0 987 p or d before the These characters specify the desired result 1 0 123 877 or p for up pulse and d for down pulse If p or d is specified the length of the pulse that is generated is determined by the pulse _sz parameter in seconds Characters in a group following the or represent a date and time times 1 100416 12 34 Specific date 2010 April 16 at 12 34 O lh Value becomes 0 in plus one hr 987 0416 2345 1 Month date with analog val of 987 p 01 23 Same time every day d 1212 Same time every day p 30m Previous time plus 30 min 123 12 1m Output 123 in 12 1 min after prev time 1 17 17 min after each hr 1 16 2345 Day 16 of mo at 23 45 1 30 2355 Day 30 of mo at 23 55 1 fr 2143 Fridays at 21 43 1 wd 1111 Weekdays at 11 11 1 ss 1212 Saturday and Sunday at 12 12 1 me 2121 Month end at 12 21 1 ye 1122 Year end at 11 22 1 080418 0600 local 1z080418 1200 gmt equiv with dst MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 46
136. mt defines the display format for mocos pl report This is optional but recommended for a finished system pipe is the field delimiter 1st and 2nd for sorting lines 3rd is text for a prior break line between rows if any snap fmt et ME 2 ING VS siete 55 5 orig Seay Scones s arta gover aw dso a Oa Sao Sia MoCo processing control all are optional Available for most points interval 0 If 0 no interval processing intv_only 1 If 1 process only on the interval disable 1 If 1 then totally disable the point stealth 1 If 1 don t show by default on reports ADDITIONAL USEFUL PARAMETERS See MoCo doc especially Appendix A for complete list of parms NOTES Everything is case sensitive Quote any data that contains spaces Order of name value variables is not important Appendix C Drivers Name Analog Digital Type Description calc_expression A calc Evaluates complex math and logic expressions MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 98 of 116 calc functions A calc Quickly performs math functions calc_ ladder logic A calc Evaluates multiple rungs of ladder logic input_alarm_ tally D input Tallies active and unacknowledged alarms input_emacsys A D input Inputs analog and digital data via EMACSYS input_file A input Inputs data in name value format from file input_ha7net_digital D input Digital 1 wire input via HA7Net
137. n Windows creates a customizable web page or pages and ftp s them to a web server MoCo driver input_from_web reads the web page and feeds the weather data to points on MoCo like OATW HumW DewPW BaroW WSpdW WGusW and WDirW This will probably be deprecated because calc_expression covers this functionality A manual input point is typically a manually entered value that can be used as a set point or limit A person might choose to implement a set point with a manual input so that the set point value will be visible in point reports The driver foramanual input pointis input _manual The data value comes not from a sensor but from parameter val_manual inthe point s cfg file The value for val_manual can also come from another system variable or expression that evaluates to a number Because there is no real sensor associated with a manual point only the following parameters are likely to be needed p name desc driver handler val_manual units and optionally MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 38 of 116 snap_ fmt which is used by mocos for status reports An alarm point is a system variable that displays total alarm counts It displays the information in a format like 12 34 where 12 is the number of unacknowledged alarms and 34 is total of active triggered alarms The driver inthis caseis input_alarm_tally The following parameters are recommended for an alarm
138. n most situations Invert character corresponds to normally closed contact Contacts in series are represented by amp amp logical AND Contacts in parallel are represented by logical OR In addition to being actuated by a point variable a contact can be actuated by a less than greater than equal to etc comparison expression Note that the comparison capability makes software ladder logic more capable than conventional relays and wire The following steps show how to setup the example HeatL point forthe calc_ladder_ logic driver 1 Set parameter driver calc_ladder_logic 2 Setup the ladder logic rungs rung_1 rung_2 rung_3 etc as shown above So that the parser will not misinterpret the logic expressions ALWAYS put a space between a variable and an operator like amp amp etc And use double quotes around the expression because it contains spaces Most perl math and logic operators may be used The following are common logical operators that you will frequently use MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 52 of 116 For numeric tests Logical OR two pipe characters Do not use perl s or operator amp amp Logical AND Do not use perl s and operator Inverts the logic of the following variable or parenthesis expression x y Results true if x equals y x y Results true if x does not equal y x lt y Results tru
139. nd unlatch the LL1 relay so that the whole deal turns off LL2 simply allows the second half of the lights to turn on at night The night variable comes from a time clock point that goes true at night The rungs shown above are translated to MoCo ladder logic as follows LL1 rung_1 onl MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 75 of 116 rung 2 on2 rung_3 on3 rung 4 LLI amp amp off1l amp amp off2 amp amp off3 LL2 rung 1 LLI amp amp night The best scan interval for the input points depends upon the input interface It needs to be frequent enough to capture the on pulses or off pulses The scan interval for the ladder logic should be frequent enough to capture the pulse from the input point unless the input point s do_next parameter is used to schedule the ladder logic immediately In the latter case the ladder logic scan interval could be quite long The following solutions might be considered more robust because they are much less dependent on short pulses and network response time 9 1 2 Ladder Logic Solution for Steady On Off Switches All but the most primitive X10 or Insteon I O bridges hide data bursts from switches and show the device as either on or off This is helpful because occasional network congestion due to a child or employee watching YouTube will not catastrophically interfere with reliable operation of the overall s
140. ne of the copies down by entering mocom jm 1 shutdown 5 Shutdown handler 1 in 5 seconds Values seem to be written to the history database in duplicate Values for a particular variable are not normally written by moco to history in duplicate within seconds of one another If duplicate values are observed in history reports then a second copy of a handler is probably running somewhere on the system Run a command like ps Af grep mocod to see all of the mocod processes that are running on the computer Shut down duplicate processes that should not be running Use the operating system s kill command if necessary Occasionally strange data is observed in mocos or mocor reports The database might have been corrupted This is rare but it can occur if someone is using control c instead of a mocom shutdown command to kill mocod daemons If they happen to kill mocod in the middle of a database write the database can become corrupted Once you are certain that the database has been MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 110 of 116 corrupted follow these steps to fix the problem 1 Shut down MoCo with for example the moco stop script 2 Rename moco db so the corrupted database is backed up It will most likely still be useable for running reports on old data 3 Start the database maintenance program sqlite3 sqlite3 exe on Windows create a new database and create new tab
141. net bridges Hold the male plug so that you are looking at the end clip down This is the best way to view wire colors Pin numbers are 1 right to 6 left Once again because colors and pin numbers are sometimes reversed always verify that you are connecting to the proper pin Pin 1 white NC Pin 2 black NC Pin 3 red l wire data Pin 4 green ground Pin 5 yellow NC Pin 6 blue 5 volts ground or floating F 4 6 wire to 4 wire to 2 wire Unfortunately there is no consistent standard for 1 wire wiring However the MoCo 4 wire pin outs are closest to the most common denominator The diagram below shows how to build an adapter cable that will convert Embedded Data Systems pin outs to MoCo pin outs To identify pins and colors hold the male plug so that you are looking at the end clip down Pin numbers are right to high number left Always verify that you are connecting to the proper pin because the colors are sometimes reversed The Dallas Maxim DS18B20 style 3 wire temperature sensor is shown connected below The device looks like a TO 92 package transistor To identify the pin numbers hold the DS18B20 flat side up with the pins pointing toward you The pins are numbered left to right pin 1 is ground pin 2 is data and and pin 3 is connected to 5v for powered hookup or to ground for parasitic hookup MoCo Monitoring and Control
142. ng but the configuration above causes it to reset every time the calculation runs every 15 minutes The point s intv_only parameter is setto 1 to prevent a calculation from being performed more frequently than the 15 minute interval Note that there are speed limits for the I O bridge and MoCo itself perhaps several seconds for propagation delays between the I O hardware network and computer Counting door openings should be reliable using the above scheme but measuring a flow meter s 3000 counts per minute would have to be done in an entirely different manner Rapid counting would need to be done at the T O bridge level MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 79 of 116 9 4 Scenes and Sequencing The following example turns on three ladder logic points in sequence and turns off three ladder logic points in sequence Each ladder logic result can be used to drive an output device This simulates sequencing lights motors heating elements etc When the on signal goes true the first ladder logic output goes true 30 seconds after start the second ladder logic point goes true 90 seconds after start the third ladder logic point goes true When the on signal goes false the third ladder logic goes false 20 seconds after start the second ladder logic point goes false 40 seconds after start the first ladder logic point goes false The implementation is done with three ladde
143. ng data to be misinterpreted as legitimate If a point s missing data lingers and if the point s alarms are enabled a alarm is set The alarm is not latched but it does overlay all other alarms except The will go away when the point is again functional All points except output points themselves have the ability to send their result to one or more output points for immediate transmission to the point s hardware interface This is highly MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 27 of 116 recommended for outputs because the tactic minimizes output latency thereby assuring that outputs have top priority A time_clock for example may send its output to several output points for a sprinkler system or lighting circuits However the time clock s result is not sent on to the hardware interface unless either the time clock s clean or working value have actually changed Redundant transmission of data would waste network resources Similarly all points except output points have the option to trigger other points to run immediately without delay in other words without waiting for the scheduler to run the point To make this happen you can include the list of points to trigger in the do_next parameter Multiple variables are separated by the pipe character Example do next pump30 valve22o0 sawlo The do_next trigger will occur only if a point s clean
144. ng value without override the last history value written to the history table the time when the last history value was written the age of the last remark being displayed and the last remark itself Concise override and alarm information is inserted before the remark if present MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 64 of 116 On a small system of about a dozen points mocos will produce a report that looks similar to the following Just run the command mocos ALARM VAL VAL HIST TIME REM AGE REMARK POINT OutFile 1 1 13 10 Alarms 1 02 1 02 cnt 13 10 OUTS LS orn sur Eear 6 Safes faites eh E EE Salva ENN OAT 43 7 44 degF 13 10 31 40 ALARM rw Fixing it OATW 35 3 35 degF 13 09 WGusW 14 14 mph 13 09 WSpdw 4 4 mph 13 09 WDirW 56 5 30 deg 13 09 HumW 62 65 3 13 09 DewPW 24 5 24 degF 13 09 Barow 29 972 29 98 in 13 09 ETS T AG erre shee te sain ates elves ANAE ese Suet Bites hs L IATB 55 8 56 degF 13 10 28 ALARM L Brewery cold h IATH 77 52 77 5 degF 13 10 17 ACK L rw HVAC room hot IATset 70 70 degF 13 09 The remark line to the far right is for displaying recent activity such as an override alarm or the last action triggered by the mocom program In the above example the OAT point has an override of 40 degF It also has an active unacknowledged manual alarm that was set by user rw User rw is apparently fixing a problem with the sensor and set the override to 40
145. nt the extreme alarms to be latched and the warning alarms to be non latched a variety of possibilities for different situations A latch alarm is an alarm that remains stuck on once it has been triggered Only an operator can acknowledge thereby unlatching the alarm Non latch alarms on the other hand go away as soon as the triggering condition goes away A person can acknowledge a latched alarm with program mocom Enter mocom h to view a help screen mocom expects a person to enter his or her handle initials or other ID In order to use mocom a user must have a file setup called moco id usr where id is the user s initials At this time there are minimal requirements for the contents of this file The only required entry is the user s full name like my name John Doe MoCo records all mocom commands in the moco log file along with the operator s initials MoCo allows up to 26 general purpose alarms to be configured per point The 26 alarms correspond to the 26 letters of the English alphabet In addition there are two special alarms is a non latch alarm that appears whenever data is unavailable due to network problems or to a sensor that has died 66 29 It goes away as soon as the problem is fixed is a manual alarm that can be triggered by a user from mocom Itis a latch alarm that requires acknowledgment via mocom Alarms are only functional for a point if they are enabled in the point s cfg fi
146. ntenance chapter for overview and tips MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 21 of 116 3 Under the Hood 3 1 Data Processing In short MoCo s job is to read sensors sanitize the data compress data and move the results to a database for storage While doing these chores MoCo can generate alarms and control output points based upon the values of input points and calculations MoCo also includes tools for displaying status and history of data The concept is simple but as users evolve a system they will find that complexity is the norm for any practical monitoring and control system Life is good but seldom simple Like most monitoring and control systems MoCo defaults to sampling data in a kind of round robin fashion Yet MoCo allows the user to select a custom sampling interval for each point For example sampling intervals of 100 seconds for an outside temperature sensor and 12 seconds for an inside control loop temperature sensor might be appropriate Because MoCo s most time consuming task is communicating with sensors the user should select scan intervals with care not too fast and not too slow Polling in general is inefficient and slow Unfortunately most sensor input hardware leaves no choice Traditional round robin execution of ladder logic and other calculation points can be even worse because changes might leisurely propagate through other calculation point
147. o color before soldering 4 A cost effective way to make sensor cables is to cut an inexpensive telephone extension cable in half and create two sensor cables with RJ 11 plugs on each end Many of these cables reverse the pin connections from one end to the other This does not prevent a telephone from working but it will prevent a sensor from working if wires are reversed Always verify pin to color before soldering Commercially made telephone cables with a female to female adapters may be used as extensions for 1 wire sensors as long as the pins at one end match the pins in the final female to female adapter 5 When using 1 wire sensors in powered mode pin 3 of the DS18B20 must be connected to 5v which is usually available from the bridge When using 1 wire sensors in parasitic mode the Vdd pin pin 1 must be connected to the GND pin pin 1 Never leave the Vdd pin disconnected 6 1 wire sensors such as DS18B20 can usually work in either parasitic 2 wire or powered 3 wire mode The HA7Net bridge will work with 1 wire devices that are wired for either powered or parasitic operation If there is a mix of powered and parasitic on the same buss some people speculate that the most conservative connection scheme is to strap the HA7Net for a grounded power line and be certain that all devices have their Vdd terminal connected to the grounded line 7 DS18B20 PAR parts have an internal connection that makes them work only
148. of 116 All of the above events can be setup for one time clock This is not intended to be a practical example it is intended so illustrate the possibilities Events for the day are decoded and put into a time list for the day just after midnight and whenever MoCo is started If MoCo is started at a time when a time clock has no initial value the software sets the time clock s initial result value to 0 A user can force an initial value by including an event at 00 00 with the desired initial value Or the time clock s value can be initialized by setting parameter v for value to the desired initial value in the cfg file Initial values are useful for preventing startup problems especially in complex control applications that involve interconnected time clocks calculations and ladder logic This next time clock example implements a series of events that turns on for 5 minutes and off for five minutes forever Its cfg_ file follows Time Clock 5 min on and 5 min off p 5on5o0fft name TC 5min on 5 off desc Time Clock 5 min on and 5 min off driver time_clock units OnOff do_next TClocklo Tclono Tcloffo Do these without delay interval 60 snap_fmt 6 c times 1 00 0 05 1 10 0 15 1 20 0 25 These two lines 1 30 0 35 1 40 0 45 1 50 0 55 will join into one Note that this time clock drives three other points which in this example are output points TClock1lo is driven on and off controlling an
149. off Switches Ok it s time to roll up the sleeves and do some control This example reads input values from distributed switches and sends outputs to ten other lights The switches to be used in this example are push button switches that send an on pulse or off pulse During the day only half the lights are turned on At night all the lights are to be turned on when an on button is pushed The ladder logic diagrams below simulate switch or relay contacts each of which activate an imaginary coil to the right The relays and contacts are simulated in by calc _ladder_logic points LL1 and LL2 onl Siy nosh oes oe on2 LL1 To output points on3 Light1l Lights Light5 Light7 Light9 LL1 foffl off2 off3 1 LL1 night To output points GLZ Weeieton jat _ Light2 Light4 Light6 Light8 Light10 Three sets of on off input points provide on and off pulses from the push switches Ladder logic LL1 turns the pulses into a steady on or a steady off Note the LL1 contacts within the fourth rung of LL1 These contacts sometimes called latching contacts or holding contacts cause LL1 to lock itself on when an on pulse arrives The LL1 relay remains latched on after the on pulse leaves The off contacts are inverted normally on contacts When an off button is pushed the contacts briefly open a
150. ogrammatically inhibited from triggering their configured output points To regulate output point XYZ s output in this manner the result from time clock ABC is fed to ladder logic IJK s enable out parameter If enable out evaluates to true outputs are propagated from ladder logic IJK to output point XYZ If false then results from point IJK are blocked from getting to the output point XYZ The enable _out parameter can accept an expression like timeclk3 5 Notethat mocod does not block non output points from receiving the trigger only output points are blocked when enable _out 0 Ifan enable out goes from false to true for a ladder logic point or any other non output point a trigger is generated so that the current state of the point will be propagated to the output point at that instant Yes the above scenario is difficult to comprehend in one reading But the technique can be very handy for situations where outputs are being sequenced in a complex manner MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 41 of 116 Output from all points will be blocked if ini variable no_output is set equal to 1 An output may be individually blocked with cfg variable no_output However if a point s no output parameter is set to 1 output is enabled for that point even if the global no output is 1 The no output capability is useful for testing and it is essential for setting up re
151. operation from the Microsoft Windows command line requires the pl suffix like program pl Note that the different operating systems expect different line termination characters in text files This can be a mysterious cause of problems when attempting to run perl programs for the first time Linux Unix and Mac use a single LF linefeed character in their shell scripts Windows uses CRLF carriage return linefeed characters Perl files with LF line termination characters work on all systems Therefore you should not experience problems with MoCo files unless someone modifies a file with a text editor that changes the line termination character If this does become a problem use a text editor to convert the line termination character to a LF character Windows Installation Overview 1 Download the free Community version of ActivePerl from www activestate com downloads 2 Double click the install icon It is recommended that you accept all the defaults 3 Copy all of the MoCo files toa moco subdirectory like D moco 4 Run each of the above MoCo programs to verify that they run without perl errors MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 8 of 116 Linux or Unix Installation Overview 1 Copy all MoCo files to a convenient directory 2 Set file permissions on the following to be executable programs mocod mocom mocor mocos and shell script clear snapshot and clear
152. or the program 7 4 Shell Scripts for Common Reports With wild cards and rpt files a report covering just about any scope can be specified But what if a person needs to run a report frequently without having to type more than a few characters A one line script may be the answer In the example below the user enters pool to get a history report on his solar pool system temperatures The pool script contains just one line mocor t7 waterTemp hotTemp retnTemp motorOn panelTemp 8h When creating a script that contains a one liner like this remember on unix style systems which includes Mac to change file permissions so that the file will be executable 7 5 Graphic Web Status Reports MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 69 of 116 Customers often desire graphic status reports that have diagrams with pictures with numbers and colors that change in real time Because such displays are different for each application no monitoring and control system can provide graphic displays that are perfect for every customer Instead the systems often provide tools that enable a user or developer to build the desired display Web based GUI solutions are portable and viewable world wide Platform based GUI interfaces are in practice specific to the operating system They require complex linkage which complicates installation and maintenance Viewing is limited to the platform on whic
153. ore alarms A ladder logic rung could be rung 1 pipe alarm eq F The ladder logic output would feed the digital output point that controls the annunciator If there are multiple annunciators all over the plant the ladder logic result can be sent to multiple output points MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 62 of 116 Another way to drive a general purpose alarm light would be to feed the output of an input_alarm_tally point toa digital output In this case the alarm light would turn on whenever any alarms occur within the alarm point s scope By setting a couple of point parameters the light could be caused to shine only for unacknowledged alarms MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 63 of 116 7 Reports 7 1 Reports Overview Two MoCo report programs are included with MoCo at this time mocos isa general purpose status reporting program mocor isa general purpose history reporting program Both produce textural reports They run on all MoCo supported platforms and they can be run on remote computers using terminal communications software like telnet or ssh Wildcard capability for the optional point argument enables the scope of reports to be constrained to a subset of points When wildcard characters are used the argument must be quoted to prevent the operating system from attempting to interpret the wi
154. oring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 84 of 116 11 Basic Transducer Electronics 11 Example Projects 12 Creating a Web based User Interface 13 Configuring an Enterprise level Distributed Network By Enterprise level we mean instances of MoCo that are running on multiple computers either on the same local area network or distributed world wide The most significant physical difference between a one computer configuration and a multi computer configuration is that a centralized server style database is used Although the server style database is the best way to go there are other ways to link distributed MoCo systems if a server style database is out of the question SQLite is not a server style database which is one reason why it is relatively easy to setup and maintain Databases such as Oracle mysql PostgreSQL and Informix have the required capability Their architectures have a central server that is accessed by distributed clients via the network MoCo is tested only on SQLite at this time However the larger databases should be useable without changing a line of MoCo code because the SQLite implementation uses the same standard DBI interface that the big boys use However it will be necessary to correctly setup the following three ini parameters dbi_auth Authentication password as needed by the db software and the DBI standard dbi_ driver Driver name
155. orking it is time to figure out how to associate the sensors with the internal MoCo point ids you have chosen For the HA7Net and OW Server I O bridges you use the web interface via a browser to identify the 16 character unique ID of a 1 wire sensor Using a simple text editor begin setting up the IATB cfg file Of course choose your own short point id for the point Enter the following except substitute values that match your situation IATB Inside Brewery Air Temperature Device parameters p IATB name Brewery Air Temp desc Inside Near Brewery Air Temperature device id B50000027B7C1A28 Unique l wire serial number part_id DS18B20 Optional for this driver net _addr gt ini net_addr_ha7net To 192 168 0 250 in ini file driver input_ha7net_temp handler mocod0 Program clone instance 0 1 2 3 If the I O interface had been a WebControl bridge then the device_id would have been t1 to MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 39 of 116 t8 for l wire temperature sensors On the appropriate WebControl bridge web page you need to associate the unique 12 character 1 wire serial number which WebControl displays with the t1 to t8 ID MoCo is then exposed only to IDs like t1 to t8 The following points on WebControl are not 1 wire I Os but individual I O ports Digital inputs are straight TTL level digital inputs like d1 to d8 and analog
156. ostic tool is its ability to dump all run time ini variables ora point s cfg variables at any time while the program is running This is done with mocon by entering mocom jd 0 dump User jd dumps the ini hash from handler 0 mocom sc HumWi dump User sc dumps cfg HumWi hash from handler 0 Results from the above will display on the same terminal window as where the relevant mocod handler is running At startup a trouble shooter can display some debug information by entering the d switch or even more diagnostic data with the D switch Some programs also have a v verbose switch which displays more information ora q quiet switch which displays less information See the program s help screen h switch for details Data is missing for a number of points Instead of numbers question marks are displayed If this is not due to network problems the most likely cause then perhaps one or more of the handlers did not get started Unless the operating system is Windows entera ps on the command line to see program status Verify that all handlers are running On Windows verify that all handlers have been started in their separate windows Strange behavior particularly with results from time related calculations and ladder logic Verify that there is only one copy of each handler running On unix style systems enter ps to see what is running If more than one copy of a mocod daemon with the same number is running use mocom to shut o
157. ous behaviors Here follows a summary of useful variants W Working value override possible hides missing bad data the default value o Clean averaged value override possible hides missing bad data ey High resolution value without override shown in status reports eh Clean averaged value written to history shown in status amp history reports val_raw Raw value from input driver not yet scaled For troublesome startup scenarios involving calculations ladder logic or time clocks the above variants can be initialized in cfg files This tactic is seldom needed but can be quite useful when needed When doing calculations and in other places where a parameter s value can be passed as a point id as well as a pure number MoCo can tell if the parameter s value is a pure number or a point id If it is a point id MoCo translates the point id and its attribute like Xyz c to the number it represents If the point id is prefixed with a like Xyz c it negates the the result If the point id is prefixed with a like Xyz c it inverts the logic of the evaluated result For example a will cause a false to become true 1 and a true to become false 0 wen The operator is particularly worth remembering because it is commonly useful in logic calculations and for inverting a parameter used for gating in other words for enabling or disabling As mentioned a point s value can be overridden manually o
158. parameters Before a program is run the operating parameters can be passed to the program by ini file defaults and by command line parameters Once the program is started up a FormEdit screen can optionally be displayed for some programs further enabling editing and adjustment of run time parameters MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 17 of 116 FormEdit is an exclusive MoCo parameter editing feature that was designed to work on any operating system any software or hardware terminal over remote telnet or ssh links and even witha low speed modem While it lacks the glitz of a GUI interface it gets the job done Ifa e switch is specified on the command line a FormEdit screen will appear when the program is run Depending upon the program a help screen may be displayed first The FormEdit screen for mocor looks like this Enter data on cmd line Remember SPACE BEFORE NAV COMMAND h for help rpt_file 1 Report File rpt_type 2 E everything a active alarms A defined alarms o overrides r remarks u anything unusual t4 4 columns t7 7 columns f amp F output files s only stealth points S also stealth points p_mask 30 Points Any 2 not 3 below rpt_span 4 4h Duration like 30m 8h 2d 2mo rpt_from 5 From time like 080123 1200 rpt_to 6 now To time 080210 0600 or now Optional out_file 7 Ex
159. pect to have several or more instances of the mocod daemon running Each one called a handler is numbered mocod0 mocod1 mocod2 etc The handler name is specified with the handler parameter in the point s cfg file For enterprise systems MoCo uses a trick to assure that each handler name remains unique for the total system At the enterprise distributed computers level the handler name includes both the computer node name and daemon instance like hal mocod3 For this initial test only the mocod0 handler is run Therefore all of the cfg files should properly include handler mocod0O for this startup test The following command starts an instance of mocod Without an instance number specified on the command line mocod defaults to being handler mocod0 For instances other than 0 an instance number is required mocod Start handler mocod0 mocod pl on Windows Because no parameters follow mocod in this case it is necessary to strike enter a second time after the short help message to get mocod running If all is well messages regarding sensor reads MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 19 of 116 are occasionally written to the screen The terminal window will look something like this except with only one to several input points at first 12 33 44 2 33 44 2 33 44 2 33 44 2 33 44 2 33 44 2 33 44 2 33 44 2 33 44 2 33 44 2 33 44 2 33 44 2 33 44
160. pendix C Drivers Appendix D I O Bridges D 1 NA7Net D 2 OM Server D 3 WebControl EDS and PLC D 4 ISY 99i D 5 EMACSYS Appendix E Troubleshooting E 1 General E 2 MoCo Software E 3 Networking E 4 1 wire E 5 X10 and Insteon Appendix F Transducer Wiring Details F 1 Pitfalls To Avoid F 2 RJ 11 12 4 wire Telephone style Plug F 3 RH 11 12 6 wire Telephone style Plug F 4 6 wire to 4 wire to 2 wire F5 RJ 45 8 wire Ethernet Plug MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 4 of 116 1 Introduction Mission Statement To provide an open source network centric industrial strength monitoring and control system that is scalable from small projects to a world wide network which will run on all major platforms and use low cost interface hardware NOTE We do appreciate your suggestions for this document and the MoCo software 1 1 What is MoCo Moco is a scaleable software system for monitoring and control of analog and digital I O points It is equally at home on a single computer or multiple computers networked world wide The computers operating systems may be Linux Unix Mac or Windows MoCo is built at MoCoWorks upon no cost open source software and it works with affordable I O hardware Its scalable architecture is suited for a wide range of applications ranging from home automation system energy management projects irrigation systems lighting control
161. pends upon bridge in file Name of input file for driver input _ file in_or_out input_ha7net digital input if an input only point and output if output point Both input and output points can be read by the driver invert If it inverts digital inputs to compensate for I O inversion Displays with net_addr Network address for bridge or web page Can point to web addr in moco ini scope input_alarm 0 to cover handler 1 to cover MoCo node 2 to cover all points A 2 5 Specific to Output Points channel Channel number or 0 for HA7Net digital input or output drivers cmd_outf Shell command to execute whenever a file from output file is written device Manufacturer s part ID Usually for information only and typically not required device_id ID of the output actuator or port like o3 ID depends upon the bridge force If true force the output to become the value from val_force gate Typically 0 or 1 The gate value is multiplied by the intermediate value and if digital is converted to an integer that is sent to the output device invert If causes an output point s value to be inverted to compensate for I O inversion net_addr Network address for bridge or web page Can point to web addr in moco ini no_output Blocks output when 1 If 1 enables output even if ini no_outputs 1 Useful for enabling disabling outputs in fail safe redundant systems out_file Name of output file for driver output
162. points With certain kinds of calculations a person might need point processing to be performed on the interval only To assure this set intv_only 1 This forces a driver to run only at the specified time It will not allow a calculation to be run in a recalculation loop which would be desirable in most other situations In other cases a person might desire to have a calculation performed only when quick scheduled by another point s do_next parameter For example an application might need a calculation triggered only when a time clock changes state In this case set interval 0 inthe calculation point s cfg file If the calculation point needs to be do_next triggered from the leading edge only set the target point s parameter cng_filter 1 If the calculation point needs to be do_next triggered from the trailing edge only set the target point s cng filter 1 The cng filter option is also useful for situations where a time clock or ladder logic point is setup to turn something on but you do not want the activating point to be able to turn the device off or visa versa In this case another source point s true to false transition might be setup to turn the output device off This is one of those rare situations where an output point might be fed from two sources one source to trigger the output on and the second source to trigger the output off The cng filter parameter makes this scheme easy to implement eliminating the need for
163. pplied to the history value and clean value Default 1 8 of resolution low_limit Clamps the converted value to stay at or above the low_limit offset For converting to different units like degC to degF or sensor calibration ramp Maximum allowed rate of change per minute of the clean value Default no limit resolution Resolution of history or clean value like 1 1 02 etc Default 1 scale For converting to different units like degC to degF or sensor calibration A2 3 All Digital Points Digital points can be any kind of number and even short strings of text They are not altered in any way by MoCo unless they are overridden gated inverted or have bad data bad_high Block data replacing with if above this value Helps detect bad sensors bad_low Block data replacing with if below this value Helps detect bad sensors gate Typically 0 or 1 The gate value is multiplied by the intermediate value and converted to an integer to create the final result invert causes an I O point s value to be inverted compensating for I O inversion A 2 4 Specific to Input Points channel Channel number 1 or 0 for HA7Net digital input or output drivers device Manufacturer s part ID Usually for information only and not required MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 89 of 116 device_id ID of the input sensor or port like t2 or F20000013E41C828 De
164. problem by triggering the manual alarm for a point To set the special manual alarm enter mocom user id point id remark Usage mocom bo iat Morning George Actual example mocom can also be used to temporarily override alarm thresholds while mocod daemons are running The following command overrides the configured threshold with a new value of 85 for point IAT The mocom command changes parameter IATW alarm_to_x to value 85 The to in the parameter name stands for Threshold Override The alarm character is always lower MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 60 of 116 case so that typing will be easier and so a person doesn t have to remember if the alarm is latching or non latching alarm_to_x does not alter the original value it just temporarily overrides it mocom gw IATW alarm to x 85 When an override is in effect it is displayed in history reports and status reports This is what it looks like in a status report 80 is the configured alarm threshold 85 is the threshold override X IATB 85 56 86 degF 09 36 15m ALARM X 80to085 Problem These mocom commands simply change a cfg variable in the proper mocod handler Runa similar command to remove the alarm threshold override Set the override to null like this mocom jc IATW C alarm to x The string of alarm configuration parameters for an alarm can be changed on the fly by using mocom to
165. r Linux unix users will be familiar with these conventions as they are nearly the same as for shell scripts Examples follow ramp 0 1 A number no quotes req handler mocod0 No quotes needed name Inside air Temp Spaces so quotes desc This is a very long sentence that takes up two lines They auto concatenate array 0 123 array 1l1 456 Array elements In cases where a numeric value is expected for a parameter in the cfg file it goes without saying that a numeric value can be entered More interestingly a point s variable name like point or point c can be entered in many cases where a numeric value is expected And even better an expression containing variable names logical operators and arithmetic operators will work In Appendix A parameters with this ability are underlined These subtle but powerful features enable a point s numeric parameters to be controlled from other variables in sophisticated ways at run time only to be limited by an implementer s imagination or his desire for obscuration When using an expression instead of a simple number remember to leave spaces between operators and variable names and to quote the expression if it contains spaces However parentheses and the two operators and can live without spaces As the number of points increases beyond 50 users may prefer to have points hidden from view in reports For example calculation points often contain in
166. r lines and sometimes wireless competing with heavy loads and very noisy electronics equipment Your problem is probably due to too many RF absorbing loads and or too much RF noise in the air and on the lines Communication problems get worse as the number of circuits and square footage of the building increases There are various ways to cope with communications problems 1 repeaters 2 filters and 3 judicious selection of locations for these devices and the interface bridge The web site http www smarthome com is a good place to start for information and remedial devices High tech home equipment can absorb the signals and or they can put noise on the building s power wiring A person can RF isolate the noisy devices from the building s wiring with filters such as SmartHome s 1626 10 FilterLink 30 each Plug each filter between the noisy device and the power socket Another common cause of problems is that essentially all houses in the U S are fed by 230 volts which is split in two 115 volt legs at the breaker panel One leg feeds part of the house and the other leg feeds the other part The X10 and Insteon signals that travel on the wiring have a difficult time getting from one leg to the other SmartHome sells devices to bridge the legs For X10 they sell a device that plugs into a 230v socket such as a clothes dryer circuit Insteon bridges the two legs with a wireless link between two access point devices This only wo
167. r logic points and with two of their timers A diagram of the ladder logic follows Timer Parameters on stagel start on stop on fon stage2 timer lt 40 reset on ca uuad Do aoon r Desees 20 05 on stagel timer gt 30 timer 1000 stage2 start on stop on fon stage2 timer lt 20 reset on o TA eaaa A a a on stagel timer gt 90 stage3 fon stage2 timer lt 1 Isense rt ai The three ladder logic points are called stagel stage2 and stage3 Timers from stagel and stage2 are used in this example Remember that all points have an available timer The timers cfg parameters are shown to the right They are setup in stagel cfg and stage2 cfg along with the ladder logic rungs shown above The rungs for stage3 are rung_1 rung 2 on amp amp stagel timer gt 90 lon amp amp stage2 timer lt 1 When point on becomes true stagel1 s timer begins counting up This behavior is enabled by the timer s start parameter shown to the right stagel1 s output becomes immediately true Stages 2 and 3 follow in 30 and 90 seconds respectively until all three are on MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 80 of 116 When point on goes false in other words off timer 1 is stopped and reset Timer 2 is started Almost immediately
168. r testing set the interval for 10 seconds even if it will later be set for a longer interval 6 Startup the mocod handler defined for this point Soon after the source points have been read the file named in tmpl_file should contain data that looks like the following Weather Inside Temperatures F Temperature 32 7 Living Room 69 7 Humidity 33 Brew Area 67 96 Dew Point 6 7 Big Cooler 60 34 Barometer 29 976 Ferm Room 58 66 Wind Speed 14 Garage Hvac 69 43 Wind Gusts 24 Glass Room 59 Wind Direction 328 MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 71 of 116 HVAC System Lo Water Temp Up Water Temp ETS Furnace Hot 71 77 Hot 100 76 108 68 Retn 70 33 Retn 76 09 If values change the file will be updated on the 10 second interval Some text editors like TextWrangler on the Mac will display the changing numbers as you watch While this is a simple example web developers will understand how easily a html web file can be animated in the same way What may not be immediately clear from this example is that the possibilities are even greater MoCo s points if digital have the ability to handle short text strings like green red ON OFF Startup Shutdown etc Such text strings can be used to control html attributes or to provide dynamic labels Suppose the customer wants the color of a tank or of temperature text to change color as a function of temperature
169. r with programatic overrides The user sets or removes a manual override via program mocom which is MoCo s general purpose program for communicating with programs that are running It enables a user to talk to a daemon in particular mocod0 mocod1 etc where the override actually occurs A user may choose to override a point s value for purposes of experimentation debugging or if a sensor has gone bad Because history is history the override will not re write or lie to history But a note is written to database s history and snapshot tables showing that the point has been overridden Unlike history and snapshot values internal values point w and point c canbe overridden so that calc points for example will receive the overridden values A manual override sent by a user via mocom behaves differently for an output point than for other points For an output point an override overrides the value that is sent to the output interface It does so before the optional logic inversion would take place if inversion were requested by cfg parameter invert Status and history reports show the value that is read back from the output interface with the any invert being performed transparently An output point override value is actually sent to the output device only if it is different than the previous output value and non null Therefore before removing an output point override override it to the desired value and then remove the override
170. r words do not use source _pt unless necessary If properly implemented these implementation tradeoffs will be transparent to the end user From the developer s perspective they will be of little interest for simple monitoring applications However they will become more interesting to the developer of larger systems as time clocks timers counters and ladder logic come into play 5 3 Input Points The typical input point receives data from a single external sensor processes the data and sends a sanitized result to history and various other places The processing includes units conversion scaling spike elimination averaging rounding to resolution and application of hysteresis The specific conditioning parameters must be setup in the point s cfg file These processing features were described in detail in Chapter 3 Under the Hood It s All About Data But before discussing typical sensor driven input points we look at several special categories of input points that do not receive their data from an external electronic sensor Point data can be input from a web page or file Drivers input _from_web and input_file are the means for inputting point data from a web page or file See 2 5 Hardware Transducers and I O Interface Setup for a more detailed explanation Obtaining data from a Davis Weather Station is a good example The Davis Weather Station has optional software and hardware that connects to a Windows PC The Davis software o
171. re points that perform internal mathematical and logical calculations Typically this means performing math or logic calculations on a number of point values and then producing a result Forall calc points mocod automatically sets the point type parameter to calc Calculation points have the same features alarms override capability etc as other points They can cause shell scripts to be executed whenever there are changes in logic value Calculation points also have their own timer and counter Like other points the calculations occur at their specified interval unless the designer decides to entirely disable interval processing and instead trigger a calculation froma do_next trigger Interval processing is totally disabled by setting interval 0 The cng_filter parameter can be used to filter the triggering froma do_next Rather than triggering on any logical value change it can limit the triggering to either the leading or trailing edge of the source point s variable Set cng filter to 1 to trigger on leading edge and to 1 to trigger on trailing edge For interval sensitive calculations like a duty cycle calculation it is necessary to restrict the calculation to interval times only This is done by setting intv_only 1 When a change occurs to the result ofa calc point other calculation points are immediately re calculated so that changes propagate through the calculation points without delay Furthermore they are repeatedly re
172. red wiring for 1 wire devices Each 1 wire port can be strapped to supply 5 volts a ground connection or an open circuit to the power pin pin 6 of the RJ 12 socket Note that 1 wire devices must have their power pin connected to 5 volts or ground but must not be left unconnected The HA7Net manual does not include the strapping details but the necessary instructions are printed on the circuit board in challengingly small print NA7Net is configured via an ethernet connection It has its own web server and web page Login MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 100 of 116 requires a user name and password The defaults are admin and eds respectively For more information download the manual from the Embedded Data Systems web site at http www embeddeddatasystems com D 2 OW Server The OW Server is a new I O bridge from Embedded Data Systems second generation to their HA7Net Not surprisingly it is similar to the HA7Net It handles a slightly different mix of sensors supports a maximum of 24 devices and costs a little less According to the Embedded Data System s web site the HA7Net operates with the following devices e DS18B20 12 Bit Temperature Sensor e DS18S20 9 Bit Temperature Sensor e DS2406 Dual Addressable Switch e DS2408 8 Channel Addressable Switch e DS2423 2 Channel Counter e DS2438 Battery Monitor with Temperature and A D
173. reports desc Sample Calc Expression Point Long point description units degF Units for report display driver calc_expression Handler subroutine name handler mocod9 Daemon 9 the handler for this point MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 95 of 116 For analog All are opt Choose the avg_size resolution ramp hysteresis interval high limit low_limit bad_high bad_low expression MoCo proces do_next cng_ filter enable _ out PRRPORPH interval intv_only disable stealth Timers ava timer 1000 start point stop poin reset point These read time_intv time_now time_prev Counters a counter counting count_up count_down reset ADDITIONAL See samplel alarms she See MoCo do NOTES Everything Quote any d Order of na kkk RRS processing ional some more important than others following numbers wisely 5 Number of samples for running average 0 2 Clean resolution for risplay and history 0 5 Allowed rate of change per minute 0 03 To reduce history jitter amp inc data instability 10 Sampling cycle interval in seconds 100 The value is clamped at or below this limit 30 The value is clamped at or above this limit 110 If raw conv val at or above flagged as bad data 20 If raw conv val at or above flagged as bad data pointA pointB 2 pointC c 30 Math expr
174. rks if the two are actually plugged into circuits that are on different legs The ISY 99i manufacturer recommends plugging in the bridge s PLM away from noisy equipment and as close to the breaker panel as possible Of course do not plug the PLM into a UPS because the UPS will block signals from getting to and from the building s wiring Intermittent problems can be difficult to diagnose and trace But you can isolate and eliminate the problems if you understand the issues and use the scientific method to isolate the problem one step at a time My advice is don t panic sit back and have a beer and plan a series of experiments to isolate the problem Then tackle the problem knowing that you will eventually win MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 113 of 116 Appendix F Transducer Wiring Details F 1 Pitfalls to Avoid 1 Trouble shooting can be time consuming and annoying Seasoned instrumentation people know that it is worth the time to do it right in the first place reliable connections good insulation heat shrink tubing wire labeling accurate notes consistent color coding standards etc 2 Verify that connectors do not have faulty or intermittent connections Even commercially made cables arrive new with defects 3 Wire colors in telephone style cables may not match the standard pin numbers shown below They are quite often reversed Always verify pin t
175. router confused even after the application is terminated Therefore power cycle the wireless router as a first step Microwave ovens create RF energy on nearly the same frequency as 2 4 GHz WiFi and they create as much as 10 000 times as much power as a wireless router In theory all this power is supposed to be kept inside the microwave In the real world some microwave ovens leak enough energy to be a problem Consequently given the choice it is better to avoid wireless and operate on a dedicated wired LAN especially if there are nearby sources of RF interference E 4 1 wire The NA7Net bridge has a handy monitoring feature that may be useful for solving difficult problems To monitor 1 wire activity at menu selectable severity levels enter telnet 192 160 0 250 where the IP address is the address of your NA7Net Then enter the current NA7Net login name default admin and password default eds Strike enter to view the menu All command entries from this point on must be in CAPITAL LETTERS Before setting up 1 wire devices please see the Cautions section of the Wiring Diagrams appendix This section includes tips that will prevent puzzling problems Erratic readings A device s Vdd line is not tied to 5v or ground or there is another intermittent connection First check the device that is showing errors Then check other devices on the bus Slight wandering of temperature readings This is normal Use MoCo s signa
176. s additionally enable a developer to implement real time changes of web page parameters such as color font style object or text position etc The steps for implementing a template follow 1 Create a template file Start with a simple one that has several points The template can be the beginnings of an html web page or just plain text Instead of including static numbers in the file which of course would be old history in seconds or minutes the variable name of each desired point is included within the text encoded as follows Weather Inside Temperatures F Temperature OutsTW Living Room LvrmTW Humidity Humw Brew Area RestTB Dew Point DewPW Big Cooler RestTC Barometer Barow Ferm Room FermTA Wind Speed WSpdw Garage Hvac HvacTAi Wind Gusts WGusW Glass Room GlasTW Wind Direction 7 MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 70 of 116 HVAC System Lo Water Temp Up Water Temp ETS Furnace Hot 15 Hot 17 HvacTlwfi Retn 16 Retn 18 Each time a data value changes the output file driver automatically replaces WSpdwW and GlasTW etc with their current numeric values or short text string The extra characters allow a person to define how many characters are to be used how large the field should be The field size is the number of characters from leading curly brac
177. s more slowly than desired MoCo minimizes if not eliminates this problem with fast response architecture features However response can be made even faster by allowing points to demand that their result be processed immediately by other calculation points A user can setup a point s do next parameter with the IDs of one or more points to execute immediately Output points are always immediately triggered in this manner unless the developer elects to do otherwise By default calculation points are automatically re calculated without interruption until all changes have propagated thereby eliminating propagation delays unless the developer disables re calculation for a point Recalculation can cause problems with some kinds of calculations such as duty cycle calculations Compared to humans ability to consciously and reliably monitor details MoCo is capable of monitoring an extraordinary amount of data Normally however a temperature or humidity value does not change from second to second unless there is unfiltered noise in the data The human brain is adept at filtering noise and ignoring static data and likewise MoCo has been designed to do the same From the computer s point of view the logging of static data can be the single biggest waste of disk storage space Therefore MoCo provides configurable mechanisms to prevent uneventful measurement data from swamping the database MoCo processes two types of data analog and digital
178. sec Alarm acknowledgments and remarks are sent more often than any other single command Therefore when mocom s object is an alarm or remark the point id can be all lower case Point ids for parameter changes overrides dumps and reloads are also insensitive to case However if the object is a file name the file name characters must be identical in case to the actual file name The point id argument in an alarm or remark command can contain wild card characters so that multiple alarms can be acknowledged with just one command As a safety precaution however wild card characters are not allowed in commands that change an ini or cfg parameter When using wild cards remember to place double quotes around the point id argument The quotes prevent the operating system from interpreting the wild characters before they get to mocom When asking mocom to cause mocod to dump its cfg or ini parameters to the screen be MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 32 of 116 aware that the handler dumps the result to the terminal screen on which the mocod daemon is running which may be different than the window in which mocom is running For security reasons mocom will refuse to function unlessa moco sm usr system manager s file is on the system and is in the same directory as the other usr files Do not delete it MoCo Monitoring and Control System Implementation MoCoWorks 2010 8
179. ses and fixes 1 A point name and its attribute contain a typo probably in an expression ladder logic or any parameter that contains a name instead of a number Verify accurate spelling in cfg files where the problematic name was used Use grep to locate the files 2 Someone changed a variable name from ABC to XYZ and the names were not changed where they are used in other cfg files Use grep to locate the files that need to be changed Forexample grep ABC cfg 3 A mocod handler is not running Use the unix style ps command to see what programs are running for the MoCo user Verify that all are running If one is missing MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 108 of 116 start it up 4 If the errors appear only at startup then consider adjusting the handler startup order Alter the startup order such that the handler containing calc points functions expressions ladder logic and output points starts up last The majority of a typical system s points are input points Handlers with the input points should be started first This enables the database snapshot table to be populated before the values are needed If there is just one handler this latter point should not be an issue Output devices are unexpectedly turned on and off by calc or output ports at startup Make certain that output drivers are in the last handler to be started up And preferably also include cal
180. string that is compliant with the DBI standard DBI The dbi_driver string will have multiple sub parameters dbi_user User name as needed by the db software and the DBI standard These parameters include the driver name database user name database password database name server URL and port number Unless a person knows precisely all the parameters setup can be difficult That is why corporate environments have database managers If you want to do this on your own read up on the perl DBI database interface module sift through the database documentation and make friends with your company s database manager 14 Writing a Custom Perl Snippet 15 Writing a Driver MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 85 of 116 Appendix A Parameters A 1 Parameters in moco ini Flle The primary file for MoCo s operating parameters is moco ini As a MoCo installation evolves the system builder may find reasons to put some of the system parameters in handler specific files like mocod0 ini or mocod2 ini The number just prior to the dot is the daemon number Parameters in these latter two ini files will override parameters of same name that are in moco ini or hard coded in the program When the system starts up it searches for relevant ini files MoCo programs search in the following places and in the following order for the ini files etc etc moco d home mo
181. t device However you can actually force an output device to a certain state with these programatic override variables which is what you would want The various programmatic override parameters can be used to help place output interfaces in a safe configuration at shutdown to zero for example The ini shutdown variable is set to true when a shutdown has been requested by mocom This variable can be used as a control signal for ladder logic or for forcing point values when a shutdown is about to occur Because a delay of many seconds is typically requested before the shutdown occurs internal logic will have time to react before the shutdown occurs When a point changes in some way a person may wish the value change to trigger a shell command A shell command command line command or shell script name can be setup in various cfg file parameters This command will be executed when the trigger situation occurs The command can be used to run programs that will transfer files send email or run a status report of relevant points for example The shell command string to be executed is placed in the point s cmd_whatever parameter The designer can cause ini or cfg variables to be automatically inserted into the command string by placing point attribute in the string for each variable inserted If the form is attribute then the current point s ID is used Ifthe formis point then point w is used The cmd_whatever parameter can indirect
182. t platform specific code Ethernet Interprocess communication that works on any platform and cross computer SQL database Data storage that can be extended from single computer to world wide network SQL database Parameter files that are human readable human editable and machine readable Extensive configurability for expandability with defaults for easier small system implementation MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 6 of 116 Detailed system logging Ability to increase reporting verbosity as needed Note that at this stage of development the software package does not include graphic report software For now system specific graphic displays and web interfaces are left to the user That said you may find that the existing tabular reports sufficiently meet practical needs If not keep in mind that command line programs are relatively easy to interface to web based user interfaces When considering a monitoring and control project please consider that such projects cover many many disciplines A basic understanding of software computers and electronics is important if not essential MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 7 of 116 2 Small System Quick Start 2 1 Software Installation Overview Software installation steps include 1 Installing perl only if Windows 2 installing perl utili
183. t step and always change the p point id as the second step MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 35 of 116 The cfg file can be edited with any text editor the simpler the better When using a word processor take care that it saves the text in pure text mode so that it does not insert invisible formatting code into the file Make certain that the line termination is LF line feed mocom also provides an alternate way to quickly change a parameter s value mocon logs all changes which would be of value to system mangers who run a tight ship Each cfg file contains from several to a couple dozen parameters Think of the parameters as a subset of the run time point attributes The parameters are represented in the file as name value or name value Positioning and spaces are not critical in the file except when there are spaces in the value string itself If there are spaces inthe value string then double quotes or some other means are required to encapsulate the text Never use single quotes for this purpose MoCo programs read and write parameters to configuration files using subroutines called nvGet and nvPut These subroutines are capable of handling arrays and difficult characters by using more sophisticated encoding techniques but we will stick with simpler examples here Note that comments can be placed to the right Comments must begin with a characte
184. te Notes SQLite is a low fat SQL database that has become very popular and is available for free for most any platform Compared to server style databases SQLite is very easy to setup and manage To soften the learning curve consider purchasing The Definitive Guide to SQLite by Michael Owens This book has its faults but it is worth the price as a specific reference for SQLite test sqlite pl isa simple program included with MoCo that reads the snapshot table from database moco db Run it to see if it runs without any errors If the snapshot table has any data in it test sqlite pl displays points and values from the table The other MoCo programs will undoubtedly work with SQLite and the MoCo database if this simple test program works SQLite also includes a versatile command line program called sqlite3 The Windows version is sqlite3 exe Both are included in the MoCo software distribution sqlite3 can be used to view anything about the database edit aspects of the database and execute SQL statements If a GUI interface is desired surf the web for a number of different GUI style programs for SQLite 2 5 Hardware Transducers and I O Interface Setup By now you should have installed MoCo and verified that the programs will run without errors Because the programs are rather useless without I O transducers or hardware points the next step is to connect test and configure I O hardware Point configuration files for external sensors wil
185. termediate results that will be of little interest once they are configured and properly working To hide a point set stealth 1 Reports provide a means to display or not display stealth points as desired The point s point _type need not be identified in the cfg_ file because MoCo can determine the point type fromthe driver that has been specified The different types are described in MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 36 of 116 more detail below Most parameters are optional but a few are required for each point Please take care when setting up these parameters in the cfg files Ifno driver name ora misspelled driver name is specified in the cfg file mocod will report an error or possibly even fail at startup 5 2 Point Scheduling By default points are scheduled to be processed at the interval specified in the point s cfg file With the exception of interval related math like duty cycle calculations the intervals selected for typical applications usually range from to 120 seconds If not specified 60 seconds is default However points can also be scheduled immediately by a do_next trigger from another point While do_next processing may not be needed for input points in simple monitoring applications it can become an important consideration with calculations such as ladder logic and math expressions and do next processing is the norm for scheduling output
186. the shell s PATH variable program names must be preceded by before the program will run Also program permissions must be set to something like 755 with the chmod command Yes basic knowledge of unix style commands is helpful even on a Mac It is likely that additional perl modules will be needed A good source for unix style software is MacPorts From http www macports org install the MacPorts installation program To avoid problems you should be on a recent version of OS X Check the fine print on the MacPorts site regarding versions supportability and bugs Once installed this software enables you to easily install perl modules and many thousands of other free programs from the Linux world Determine which additional perl modules need to be installed Enter the following commands No response no error message from the following means that the module is already installed perl e use LWP UserAgent For web communication perl e use Time HiRes For higher time resolution perl e use DBI Gen purpose database interface MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 11 of 116 perl e use DBD SQLite sqlite3 database The following MacPort installations will likely be necessary The MacPorts program assumes the name port after it is installed on the Mac Among other things port automatically obtains the new software from the internet and insta
187. through the database in this case values from MoCo handlers external to the output point can be delayed for some seconds plus scan intervals To enable this source of data set the output point s normally ignored source pt parameter to the source point id which is presumably configured on another computer The source point may be a variable or it s variant or even an expression source_pt if defined takes precedence over source points that are sent from other points via the do next parameter In other words if source pt is defined then do_next results are ignored Testing an output is slightly more complex than testing an input because you also need to setup a point or points to drive the output point One way to do this is to setup a time_clock that creates an on or off value every 5 minutes Even simpler setup an input that uses the input file driver to read values from a file as described in 2 5 Hardware Transducers and I O Interface Setup Setup the input point s cfg_ file so the input point will send its output value to the output point s driver as do_next Test7o Use your own point ids of course To control three outputs at the same time from the same source point configure the source point similar to this do next Test7o0 Test80 Test90 Then manually toggle the input point s source value in the file on and off using a simple editor Don t forget to save the file each time you make a change If everything is setup correctly the
188. til it is scheduled to output The forced value will be read back for reports as expected if the I O interface is working properly To directly force an output point to a fixed value programmatically set its val_force to the desired output value and set force 1 to enable the programmatic override These values will not override the values that are read back from an output point but they will cause the desired value to be sent to the hardware interface The actual state of the output device as read back is displayed in reports Because the time_clock s result can be numbers like 0 1 2 3 4 etc a single time clock can be used to create a stair step function that represents times of day such as dawn morning afternoon dusk and night The numbers can then be used by ladder logic for applications like a smart thermostat The time clock can also provide a ramp on and ramp off analog result ifthe time_clock s ramp and interval parameters are properly setup and digital is set to 0 MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 48 of 116 As other with points the time_clock driver supports parameters that cause shell scripts to be executed whenever there are logic changes As with other points time clock points have their own timer and counter 5 6 2 Pulse width Modulated Pulser modulated_pulser 5 6 2 PID Loop pid_loop 5 7 Calculation Points Calculation points a
189. to do things like ftp the file to another computer or web site The outf in the parameter name is derived from output file In the interest of efficiency output files are written only when a piece of data changes And consequently a script command is triggered only when data changes The output file can be created by two different means 1 by writing name value pairs toa file and 2 by populating a template with values 5 5 1 Name Value Files Once an output file has been written a user can edit the file to have a nicer layout Comments are allowed From that point on new data will be written to the file and yet the new format will be preserved When numeric data is written to the file it is written with a consistent number of decimal places attempting to be compatible with the point s resolution parameter Even after being edited the file can be read by the input file driver on another MoCo system MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 44 of 116 This trick is a worthy alternative for those who do not wish to use an enterprise style distributed database simply output a file on one computer input the file on another An example ofa cfg file forthe output _file driver follows OutFile cfg Output File p OutFile This point s ID driver output_file Output driver name handler mocod0 The daemon 0 in this case variables IAT
190. troller board and Windows computer Set the controller jumper for program load 7 Power up the EMACSYS controller board 8 Startup double click EMACSYSDownloader exe on the Windows machine 9 Click the Load Appware button Locate file Ethernet Server hex and Open for download Click Download Appware Configure EMACSYS server and load web pages 10 Remove power remove jumper installed earlier and restore power with USB cable connected 11 Startup double click EthernetServer exe on the Windows machine 12 Setup the IP address that you desire for the EMACSYS bridge like 192 168 0 220 13 Copy emacsys moco htm from a MoCo media or directory to sub directory WebPages 14 While still in program EthernetServer exe use the program to transfer web pages from the PC to EMCASYS The example web pages should be found in sub directory WebPages If this is unsuccessful you may need to install INET Framework from http www microsoft com 15 EMACSYS should be ready to go and you should now be able to access web pages on EMACSYS using the IP address assigned in step 12 16 Using a browser attempt viewing web pages on EMACSYS Example http 192 168 0 220 emacsys moco htm Io be consistent with other drivers MoCo s driver converts the 1024 levels of analog data to 0 100 The user can use MoCo s scale and offset parameters to scale to something else from the 0 MoCo Monitoring and Control System Implementation
191. tside The order of the points was in a predefined sorted order as specified by the person who configured the points This formatting is controlled by the snap_fmt line in each point s cfg file The first point in each section has a relatively long snap fmt line that looks like this Snap Pmt 2 aI nside o5 s 6s see see bin 88s o eae OF Oe See OE Sea ee The lines that follow in the same section look like this snap _fmt 2 b The snap_fmt line has up to three fields each separated with the pipe character The first field is a major sort field for the sections the second is a minor sort field and the third is the optional section header This scheme enables a person to specify sort order and to insert some headers Report definition files A system manager or user can embellish reports with custom header and footer by setting up rpt files To see how have a look at the sample rpt files that is included with the MoCo software package The report can be setup to run exactly as specified in the rpt file However if the end user wants to override point id scope parameters or select a specific kind of report overrides alarms etc then custom scope and switches can be entered on the command line when mocos is run Although the need to change defaults on a new system is unlikely be aware that some mocos MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 66 of 116 def
192. ture sensors and assigned them to ports T1 through T8 A configuration screen for output points obscured several links down from the home page gave users the impression that they could re assign sensor ROM codes to desired temperature ports That was a flaw in the early firmware Firmware v02 03 06 and beyond works properly The newer firmware enables a person to map temperature sensor ROM code to the desired port number T1 through T8 Obsolete firmware with the mapping flaw cannot be upgraded unless the board is sent to the factory for a 20 upgrade MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 102 of 116 Therefore when purchasing a new unit be advised to verify the firmware version With the BRE model if a 1 wire temperature sensor fails to operate WebControl returns no other warning than a temperature of 0 degrees centigrade Unfortunately 0C is a common temperature that is well within the range of the sensors A safer implementation would have returned an obviously impossible value like 99C when the sensor is unreadable The PLC model has improved upon this situation At this time there is no perfect workaround for this problem with the BRE model However if the temperature being read is an inside temperature or an outside temperature on the equator you could set the point s bad_low parameter to 33F or 1C Or you could setup an alarm for OC thereby creating a bad point
193. tures that are needed for complex enterprise level environments Yet usable for small projects such as home automation or alternative energy projects Runnable on Unix Linux Mac OS X and yes even Windows Fully remotely operable via standard means such as ssh or web interfaces An architecture that can be enhanced and expanded by world wide individual contributors Reliable history logging safe control and quick recovery from hardware glitches Relatively easy to maintain Built upon supported software layers that will not soon become obsolete Speed resolution of better than 1 second at single computer level and 5 seconds at Internet level Easily adapted for use in non English countries 1 3 Design Strategies and Tactics No system is perfect for all situations Even if there were a perfect system never will a group of control engineers agree MoCo is just one of many solutions that can do a job The following strategies and tactics reveal how MoCo s objectives are being achieved and if it can meet your needs External Aspects Less expensive than the norm in other words low total cost per point for software and hardware Points available at this time Input Output Calculation Time Clocks Setpoints and System Points Calculations available now math functions math expressions logic ladder logic perl snippets Future capabilities program sequences finite state machine modulated pulses PID
194. ty modules 3 copying MoCo software to the computer 4 verifying that the programs run with the installed perl 5 hookup and testing of monitoring interfaces and transducers and 6 configuring MoCo s software configuration parameters to match the monitoring and control hardware In the MoCo system configuration data is not hidden in binary files it is contained in human readable and human editable configuration files Prior to modifying a file new users should make copies of the original configuration files And to enable quick restoration of a system copies of functional configuration files should be methodically archived throughout the configuration process Installation of an enterprise system with multiple computers requires more effort than a single computer system In particular a server style database system of the user s choice is required for distributed systems This requires systems expertise IT departments know the drill Knowledge of unix style command line commands will be very helpful This documentation does not attempt to teach a person how to use a terminal command line but it does attempt to prevent the reader from common pitfalls and it attempts to point installers in the right direction This document refers to MoCo perl programs aka scripts without the normally optional p1 suffix on the program name This shorter name is preferred because it saves the user from unnecessary typing on the command line However
195. ump all OutTemp data values to screen grep canbe used to search cfg files or the moco 1log file for a specific string like point id on non Windows systems A grep command looks like this grep OutTemp cfg Looking for occurrences of OutTemp Often an important clue can be revealed when browsing the log file with a text editor To see additional run time diagnostic data runa mocod daemon withthe d or D switches set When a situation seems overwhelming please just sit back think and use these simple but powerful tools Individuals with perl experience can home in on the cause of an evasive problem by inserting print commands in the perl code Of course always save a copy of the original file before making any modifications Just after installation When mocod is run multiple database errors are displayed Verify that the MoCo files did not get copied in as read only files If they are read only then change them all to read write Error messages containing value gt complaining about a snapshot database problem Subroutine value s job is to look up the value of a point s alphanumeric parameter If unable to find the point in memory it looks in the database If it cannot find the variable in the database it issues a warning and returns as the value In other words subroutine value could not evaluate an expression ladder logic or parameter name because one of the elements was nowhere to be found Possible cau
196. up kits is primarily to shorten the learning curve at a minimum of expense the kit is not necessary for users who have technical savvy and who already have the hardware and transducers that are supported by MoCo Either way please be aware that monitoring and control systems require more expertise and sharper mental focus than operating a toaster More information about I O point configuration is included later in this document 2 2 Installation on Apple Mac OS X Installation on a Mac is similar to installation on Linux or Unix This is because the Mac is actually built upon an open source unix like system called OpenBSD The Apple implementation of OpenBSD is called Darwin Apple s OS X already has perl and SQLite since OS X 10 4 under the hood To get to the Unix style command line startup Apple s Terminal app from the desktop You will become very familiar with Terminal app If the objective is simply to evaluate MoCo copy the MoCo software files to any convenient directory such as Users your name bin moco But please note that there are better places for a permanent installation Take care that your text editor is set to utilize the standard LF line termination character when editing MoCo files Recommendation Download text TextWrangler from http www barebones com for a nice free program editor that works on Apple Macs When running MoCo programs in the following steps note that unless the local bin directory is setup in
197. us data for mocos and for sharing live data between systems message For sending messages from program mocom to other programs Because multiple handlers write to the snapshot database table MoCo programs never automatically clear it That would cause problems when more than one handler is running At enterprise level further care must be taken because distributed computers talk to the same database Therefore sometime after deleting or renaming points it is a good idea to run the script clear snapshot after shutting down all handlers that might be using the database The clear snapshot script simply deletes all records from the snapshot table It does not DROP and CREATE the table The sample mocod start script clears the snapshot table at startup For systems that are up 24x7 or distributed on different computers obsolete or re named point records can be removed from the snapshot table with the sqlite3 program Delete records with SQL s DELETE statement In this scenario there is no need to shut down anything Unless your startup script clears the message table at startup delete all the records in the message table at least once per year The clear message script will do the deed This operation can be done at low risk even if all systems are live The sample mocod start script clears the message table at startup If the database seems to have problems one solution is to DROP and CREATE the tables This destroys all data in the tabl
198. while he works on it Point IATB has an unacknowledged L alarm Brewery cold is the alarm remark text Point IATH has an acknowledged H alarm that was acknowledged by user rw For systems with dozens or hundreds of points people who run the status report are more likely to be interested in a small subset of points Therefore they will run the report with a wildcard pattern or a list of desired points Here are some examples mocos barow Just point Barow mocos IAT oat Just points IAT and OAT mocos I All points that begin with I mocos 1I O All points that begin with I or O mocos T Any lst T for 2nd char any trailing chars mocos 0 9 First character must be 0 to 9 Note that quotes must be used when wild card characters are present This is necessary because the wild card characters have special meaning to the operating system They must be quoted to keep the operating system from being confused The mocos display will refresh itself every 8 seconds if you enter the following command which is very handy for keeping a current display on the screen without repeatedly typing on the keyboard mocos 8 mocos has a number of other options such as being able to display only points that are in override or alarm With s and S options it can also display stealth points that are normally hidden from view The options are displayed inthe mocos h help screen
199. with a space character FormEdit provides various ways to navigate to the field you want to edit space b enter Move back to the previous field space enter Move forward to next field space n enter Where n isa parameter number jump to parameter n space a text enter To append text to the current field space enter Clear a field setting it to be null space x enter Exit FormEdit and continue the program space q enter Quit the program space h enter View a short help screen for FormEdit itself 2 7 Initial MoCo Startup To complete the following steps a few transducers should be connected to the bridge interface the bridge should be connected to the router and the router should be connected to the computer with MoCo installed on it Important Use the computer s browser to verify that there exists proper communication from computer to transducer If unsuccessful with a browser try pinging the I O bridge As problems arise use the Troubleshooting appendix to help find the solution Program mocod is the heart of the system It does the I O polls the sensors does significant number crunching checks for alarm conditions talks to the database and more A mocod daemon or multiple mocod daemons are the first programs to be started They continue to run as long as transducers are to be monitored and controlled Let s keep it simple start with only one daemon As the system grows more complex ex
200. would be triggered via the start parameter from an input point driven from a push button The first ladder logic point would turn on an outpoint immediately A second ladder logic point would turn on after 30 seconds using a test like XYZ timer gt 30 A third device could be turned on at 90 seconds in the same manner A power down sequence can be implemented using the same techniques and possibly by using the same ladder log points with additional rungs See the details in the Example Task Snippets chapter Although using industrial style logic to create scenes will be unfamiliar to most homeowners industrial logic does have the advantage of being somewhat more flexible than a pre defined scene mechanism In an industrial environment support personel are familiar with ladder logic so familiar it is said that control engineers and technicians can read ladder logic better than their native language MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 57 of 116 6 Alarms 6 1 Alarms Overview Alarms are the means by which MoCo notifies human operators that a point needs attention Typically a point needs attention when its value becomes too high or too low In the real world however it is not that simple System owners may desire warning level alarms that correspond to warning high warning low too high and too low They may be interested in an abnormal rate of change They may wa
201. y switch driver and maybe it will become a standard driver some day Heck why not a n way switch driver 9 1 4 Too easy MoCo Solution for Steady On Off Switches MoCo allows multiple sources to be sent to one or more outputs many to many Each input point for each of the switches can be fed to a single or multiple output points via the input point s do next parameter Whenever one of the switches is turned on the target output point will go true Whenever one of the switches goes off the output will go off This works as desired because a signal is propagated to the output point via the do_next parameter only when a change in input occurs Even though the switch inputs are being scanned on a 10 second interval changes are propagated by do_next only when a change in the point s value occurs 9 2 Duty Cycle Calculation Duty cycle is the percentage of time that a device heating element or machine is running Monitoring the duty cycle of a refrigeration system is for example a good way to keep an eye on the health of the system Duty cycle is a measurement that must be read over time It involves careful timings and simple calculations The following example shows how this might be done with MoCo We will monitor the on off states of a motor and calculate the duty cycle over a period of 30 minutes which repeats forever We want to display the result as a point This can be achieved with a calc_expression point that calculates th
202. your handle object parm name value remark msg to msg to_ lt seldom needed option Switches h for Help b for batch Object arg Single point points point mask file name ini cfg Description Communication program to change view parms in running daemons and configuration files Also control alarms amp send remarks Examples sw handle object parm name value remarks mocom h HELP mocom rw IAT Acknowledge alarm on point IAT mocom rw hat OK now Ack alarm on HAT pt with remark mocom rw HWP Fixing it Manually set alarm on HWP mocom rw HWP Hot water pump is in repair remark mocom rw iat override 70 Override point IAT to be 70 deg mocom rw IAT override Turn off the override mocom rw oat units C Change live pgm s OAT units units C mocom rw OAT c xyz Change live pgm s xyz to be null mocom rw CWT cfg units F Cng CWT units in cfg file units F mocom rw XY reload cfg file changed so reload XY cfg mocom rw IAT dump Display dump live pgm s IAT cfg hash mocom rw 0 dump Display dump live mocod0 s ini hash mocom rw 2 dump Display dump live mocod2 s ini hash mocom rw 3 xyz 123 Cng xyz to 123 in live mocod3 ini mocom rw moco ini ABC 456 Cng ABC to 456 in moco ini file mocom rw mocod2 ini R66 22 Cng R66 to 22 in mocod2 ini file mocom rw 1 reload Reload mocodl s cfg s amp restart mocom rw inside rpt rpt_span 6h Change parm in rpt file mocom rw 2 shutdown 60 Fixing UPS Shutdown mocod2 in 60
203. ystem The bridge can focus on doing a good job at low level and MoCo can do the same at supervisory level At MoCo s level selection of scan intervals becomes less of an issue if the switch values are either on or off and not pulses as in the above example The solution is a ladder logic emulation of the electrician s 4 way switch There are a number of correct solutions consider this one onl on2 on3 arias Cjeess s Jes se esses onl fonl on3 To output points LL1 Lightl Light3 lon1 lon1 on3 Light5 Light7 Ta gs A eel el MY Light9 tonl onl on3 SasSse _l LL1 night To output points EES Pee ae ae Light2 Light4 Light6 Light8 Light10 In LL1 note that if any one of the switches changes from their initial state LL1 goes false If any two simultaneously change LL1 s output does not change If the project s specifications required only the functionality of a 4 way switch X10 or Insteon could meet needs without a computer or other controller in the picture Yet a simple increase in MoCo Monitoring and Control System Implementation MoCoWorks 2010 877 360 2582 2010 06 20 76 of 116 complexity such as the night control requires intelligence that exceeds the basic capability of X10 or Insteon Add a control system to the picture and tasks like motion detector control or behaviors that differ on weekdays and weekends can be e

Download Pdf Manuals