MODEL PC100 TEMPERATURE CONTROLLER USER MANUAL

image

Contents

1. The PC100 can be calibrated in two ways calibrate to a standard and calibrate at 0 and 100 deg C Calibrating at 0 and 100 deg C must be performed if the probe type is to be changed This method is explained in Section 7 Changing Probe Types Ifthe probe type is not changed the calibrate to a standard method can be used This method is explained below and is accessed from the menu Answering yes to this menu item will invoke a group of commands to calibrate the probe to your in house standard at your facility The basics of calibrating to a standard will be explained and then the menu prompts will be explained Before leaving the factory each unit is calibrated for the probe type specified when the PC100 was ordered However there is the ability to re calibrate the unit at your facility using an in house standard if so desired Calibrating the PC100 to a standard requires placing the probe at two temperatures and entering the values at these two temperatures into the unit The temperatures can be any two temperatures that you choose These readings would be obtained from the in house measurement device The menu is set up such that each temperature is entered separately Only one temperature can be entered each time through the menu After the first temperature is entered the menu must be exited and then re entered to enter the second temperature To obtain the best results the two temperatures should be reasonably far apart The first prompt d
2. examine PID coefficients 0 50 controller response P 0 25 controller response I 0 001 controller response D PC100 Manual ver 0709 PWMP Function Set or examine the pulse width modulator period Syntax PWMP nnn n set PWM period PWMP examine PWM period Description The PWMP command permits modification of the period allocated to the pulse width modulation algorithm When controlling temperature the controller uses a constant period of time of which the controller calculates the portion of time for which heat or cool should be turned on This is based on the feedback from the probe and the PID coefficients Shorter periods of time for pulse width modulation translate into faster tracking of changes in your system When changes are expected to be minimal for an extended time during long soak periods for example it is more economical not to adjust quite so frequently In this case increasing the PWM period thus reducing the modulation rate conserves power and coolant and reduces wear on coolant supply valves Restrictions Remote only command To change the PWM period from the front panel the MENU must be accessed Period range from 2 seconds to 30 seconds See Also PIDH PIDC Example PWMP 2 set PWM period to 2 seconds TEMP examine current temperature 25 0 controller response RATE 10 define new temperature segment WAIT 5 set wait for 5 min stabilize mass SET 35 0 set new temp to 35 0 after 1 min for ramp a
3. 26 the active remote device if the upper temperature limit is exceeded If the probe reading is higher than the upper temperature limit the controller will automatically turn off the HEAT ENABLE output PULSE WIDTH MOD This menu item permits examination and modification of the Pulse Width Modulation Period See PWMP command in the Detailed Command Description Section 10 for a full explanation of this feature For most applications the 2 second default value should be used MODIFY TIME The PC100 is equipped with a battery backed real time clock The current time of day can be modified and examined here To change the time simply type the new time into the controller in the format hh mm ss in 24 hour format military format POW DOWN RESTART The power down restart feature of the PC 100 will cause the controller to automatically restart if power is removed from the controller The value entered here is the number of minutes the controller will wait with the power off before disabling the automatic restart This number can range from 0 59 minutes Note that a valid time of day must be set before this feature will work LINE FREQ This tells the controller which line frequency is being used to power the controller The digital filtering for the probe signal is optimized for the line frequency that is being used WAIT TRIGGER This is the tolerance at which the controller detects that the set point has been reached and the WAIT
4. unlock the local keyboard The RTL command only applies to host computers communicating over the RS 232 serial interface Local keyboard function may be locked thru the use of the LLO command Local keyboard unlock operation for host processors communicating over the IEEE 488 interface varies according to the particular host computer syntax requirements Restrictions RS 232 remote interface command only GPIB interface host computers have unique methods for returning to local operation See Also LLO Example LLO lockout local keyboard run sensitive testing RTL amp unlock local keyboard PC100 Manual ver 0709 65 RUNn Function Starts the execution of the local program Syntax RUNn where n 0 9 Description The RUN command initiates the execution of the local program The local program is entered into the controller using the EDIT command from the local keyboard or downloaded from a remote host computer using the STORE command Local program execution may be prematurely terminated by issuing a STOP command Restrictions None See Also RUN TIME EDIT STOP STORE END Example This example down loads a simple program from remote processor and then executes the program Scale in deg C DEL delete current program STORE prepare controller for entering local program FOR I2 0 10 set FOR loop for 10 loops RATE 10 define temp segment 1 RATE 10 deg C m WAIT 15 wait 15 minutes SET 55 0 set final temp to 55 0 deg
5. 4 Wire Full Duplex and 2 Wire Half Duplex Bus 34 PC100 Manual ver 0709 PC100 Manual ver 0709 Convert From Full Duplex To Half Duplex Cut F Trace And Install H Jumper 6666666666 c4 Fig 8 Jumper for 2 Wire Half Duplex Setup FPGA PC100 CPU BOARD 6 97 REV D 35 36 6 CONNECTING A CHART RECORDER The PC100 is capable of driving a chart recorder that accepts a 0 5V input to chart the probe readings The 0 5V chart output is found on the process I O board D A A on left side wire screw header P4 PC100 Chart Recorder P4 pin 3 Ground gt _ Ground P4 pin 5 Output _ gt Positive input When setting up the chart recorder the MENU must be accessed At the menu prompt CHART TEMP answer YES The low and high chart values must then be entered This is the range of temperatures that you want the PC100 to output For instance if a process is running that goes from 20 deg C to 70 deg C you may want to make the low chart value 15 and the high chart value 75 This will give the best resolution and still handle all possible temperatures in the process PC100 Manual ver 0709 7 CHANGING PROBE TYPES The following procedure is required to change probe types on the PC100 note all commands can only be performed from the front panel 1 Unplug the controller 2 Insert the desired probe into the probe connector based on the probe hookup dia
6. Also UTL Example If scale is set to deg C LTL 100 0 set LTL to 100 deg C LTL examine LTL 100 0 controller response 100 deg C PC100 Manual ver 0709 M Function Set or examine the current wait at temperature time Syntax nnn nM Set the temperature segment wait time M Examine the current temperature wait time Description The M command is a TCO1 controller compatible command which either sets the current temperature segment wait time sometimes referred to as soak period or allows a remote interface to examine the current setting When setting wait times nnn nrepresents the wait time in minutes If wait time is equal to forever M returns 1999 Restrictions Remote command only See Also WAIT Example 12 1M Set wait time for 12 1 minutes M Examine wait time 12 1 Response from controller WAIT Examine wait time with WAIT command 00 12 06 Response from controller OFF Function Turn off PC100 Syntax OFF Description The OFF command turns off the PC100 As long as the PC100 is connected to an appropriate line voltage the controller is still powered on The OFF command turns off the front panel display indicators and switch functions except for the POWER switch In addition commands received over the remote interfaces are ignored except for the ON command and the STATUS command Depressing the POWER switch when the controller is ON results in the same function as the OFF command Restrictions Re
7. C SET 125 0 define temp segment 2 rate 10 deg C m WAIT 15 wait 15 minutes final temp 125 0 deg C NEXT Da mark end of FOR loop I2 END mark end of local prog and end of STORE RUN run local program PC100 Manual ver 0709 RUNnTIME Function Starts the execution of the local program at a specific time of day Syntax RUNnTIME hh mm ss where n 0 9 where hh hours mm minutes ss seconds in military time Description The RUNnTIME command initiates the execution of the local program at a specific time of day The local program is entered into the controller using the EDIT command from the local keyboard or downloaded from a remote host computer using the STORE command Local program execution may be prematurely terminated by issuing a STOP command Restrictions Remote only See Also RUN EDIT STOP STORE LIST END Example This program lists the current local program from aremote interface and then prepares for executing the program at 5 00 PM LIST1 list local program 1 controller response FOR 12 0 10 set FOR loop for 10 loops RATE 10 define temp segment 1 RATE 10 deg C m WAIT 15 wait 15 minutes SET 55 0 set final temp to 55 0 deg C SET 125 0 define temp segment 2 rate 10 deg C m wait 15 minutes final temp 125 0 deg C NEXT I2 mark end of FOR loop I2 END mark end of local prog and end of STORE RUNITIME 17 00 00 run local program 1 at 5 00 PM PC100 Manual ver 0709 67 S Function Transmit and
8. E EE EE OE EE E 55 LIST cig nd OE ER OE EE Ah AaB ts MA EER OT ER 56 RIA REEN EE OR EE N OE EE EI RE EE AE Re 56 bien RE EE EE RE RE OR OE DS 57 SN EE EE EE EE OE ER EO 58 M EE RE RE OE EE EE EE ON 59 QUE EE RE RE EE EE EE 59 ORE EE N OE EE EER EE EE AE EE N EE E 60 010M RR EE EE EE ME EE EE EE EE RE ageniiea 60 PUD cos EE OR EE AE AE RE EE EE OR EEN ORE AE 61 dip s EE EE EE EE OE ER N EE AE 62 AE EE EE HE EE RE EK OR RE EN EE ES 63 PC100 Manual ver 0709 10 MODEL TC01 COMPATIBILITY COMMANDS sss sees sesse sesse sees sesse sesse sesse SL 12 REPAIR INFORMATION sss ssssseesss ee es os te id dees see sesde es ee ke GE Ge oe ees kke gee Bd 13REPLACEMENI PARIS ees ede ede geed esse se sees ve ese de donava v OO PC100 Manual ver 0709 PC100 Manual ver 0709 1 GENERAL INFORMATION INTRODUCTION Congratulations on your purchase of the PC100 Temperature Controller Your new controller was manufactured under stringent quality control procedures to insure trouble free operation for many years of service If you should encounter difficulties with the use or operation of your controller contact Sun Systems Customer Service Department between the hours of 9 00 and 5 00 EST As with all Sun Systems products we would appreciate any comments suggestions or criticisms that you may have or develop regarding your evaluation of this equipment Please address your comments to Product Service Manager Sun Electronic Systems Inc 1845 S
9. SHIFT gt IN YES Performs two functions When in the MENU this key functions as YES When not in the MENU the key functions as the IN command The IN statement is fully ex plained in the Local Programming Section Section 4 and the Detailed Command Description Section Section 10 lt SHIFT gt FOR lt SHIFT gt NEXT Used in local programming Marks the beginning and the end of a FOR NEXT loop The FOR and NEXT state ments are fully explained in the Local Programming Sec tion Section 4 and the Detailed Command Description Section Section 10 lt SHIFT gt OUT NO Performs two functions When in the MENU this key functions as NO When not in the MENU the key functions as the OUT command The OUT statement is fully explainedinthe Local Programming Section Section 4 and the Detailed Command Description Section Sec tion 10 lt SHIFT gt GOSUB Used in local programs to call another program as a subrou tine Explained in Local Programming Section lt SHIFT gt HOLD Suspends WAIT timing when in single temp mode Sus pends local program when in RUN mode lt SHIFT gt lt SHIFT gt Numeric delimits lt SHIFT gt I I variable PC100 Manual ver 0709 21 22 3 MENU The PC100 contains one menu for configuration Listed below are the functions contained in the menu Many of these functions can also be accessed remotely The menu items are listed in order of appearance in the menu CAL TO STAND CALIBRATE TO A STANDARD
10. channel x Syntax CALBx access code standard reading where x 1 Ch 1 access code 9 standard Reading Known measurement value Description The CALBx command allows user to modify the gain on channel x See Calibrate to a Standard and Changing probe type sections for complete calibration procedure The CALBx command may be used only after CALA has been done on the channel Restrictions Remote command only See Also CALAx CALC Example Gain adjustment for channel 1 Ch 1 sensor is placed at 100 C After stabilizing Ch 1 sensor reads 100 5 C The command CALA1 9 100 0 is issued The sensor now reads 100 0 C CALC Function The CALC command allows the user to clear all offset and gain adjustments for the PC100 sensor Syntax CALC access code where access code 9 Description The CALC command allows user to clear the offset and gain adjustments See Calibration to a Standard and Changing probe types for complete calibration procedure Note The CALC command should only be used prior to calibration of Ch_1 sensor Restrictions Remote command only See Also CALAx CALBx Example CALC 9 All standard offset and gain adjustments are cleared PC100 Manual ver 0709 COFF Function Disable cooling Syntax COFF Description The COFF command permits a remote interface to disable cooling by the controller The front panel COOL switch also disables controller cool function when depressed if cooling was enabled When editing
11. controller to accept the command Each keys unshifted and shifted function is explained below The white back arrow is used to back space 0 9 Numeric data entry Negative sign Decimal point Left Arrow Backspace key during command entry STOP The STOP function when used in the MENU will cause the menu to exit Any changes made in the menu before the STOP key was pressed are saved by the controller If STOP is pressed when a local program is running the local program will terminate If STOP is pressed when in local PC100 Manual ver 0709 19 20 ENTER SET SEG HEAT ENABLE COOL ENABLE ON OFF lt SHIFT gt RUN n lt SHIFT gt UP lt SHIFT gt DOWN lt SHIFT gt MENU lt SHIFT gt EDIT n lt SHIFT gt DEL program edit the program is saved and the local program edit mode is exited If STOP is pressed when a valid set temperature is present the controller will stop controlling to that temperature and set SET NONE and WAIT FOREVER Enters commands into the PC100 All commands must be followed by the ENTER key for the PC100 to accept the command When in local program edit mode the ENTER key is used to insert the present line into the local program Allow for easy entry of the RATE WAIT and SET values When the command is entered the controller will display the current setting and prompt for the new values The user must then only enter the value desired using the numeric entry keys or just enter for no c
12. controllers local memory Once downloaded the local program may be executed by issuing a RUN command Prior to downloading a program to the controller the local program must be cleared by using the DEL command Local programs can be displayed or up loads to the remote interface by using the LIST command Restrictions Remote interface command only See Also LIST RUN DEL STOP Example DEL3 clear existing local program 3 STORE3 ready controller for accepting LP 3 commands FER send LP commands END terminate store operation LIST3 display new local program 3 FER controller displays local program RUN3 execute local program 3 KKK STOP terminate local program activity PC100 Manual ver 0709 75 T Function Examine current probe temperature in deg C Syntax T Description The T command is a TCO1 controller compatible command which examines the present probe temperature The response is always in degrees centigrade Restrictions Remote interface command only See Also TEMP Example SET 25 0 Set current set temperature to 25 deg C After ramp period ended TY Examine current temperature 25 1 Actual temperature returned TEMP Examine current temperature 25 1 Actual temperature returned TALK Function Sets the PC100 in talk mode Syntax TALK nn TALK NONE Description When the RS422 serial portis used for communication between the host computer and the PC100 unit s the TALK nn sets the PC100 nn i
13. ees 33 Fig 7 Wiring Diag for 4 Wire Full Duplex and 2 Wire Half Duplex BUS esse ese esse eee 34 Fig 8 Jumper for 2 Wire Half Duplex Setup esse eee eee 35 6 CONNECTING A CHART RECORDER cscsssssssssssscssscssessessessessssssessessesseres OO 7 CHANGING PROBE TYPES sad wies kp es es serde sees dee eon oes ee es ee ee es ese S7 USE OR ined EE EE OR OR EE ER OE EER HE N 39 COMPRESSOR CONTROL ER OE EE RE OE OR EA ER EE 39 REVERSE LOGIC FOR HEAT COOL COMPRESSOR amp BOOST COOL see ese ese ese ee ee 39 ANALOG OUTPUT RE EE RE EE EE N 40 Fig 9 Jumpers for Reverse Logic sss react GER Sick EG SERE See Tia gee ds sok codes Ge Dee nes sche den Ee seg Ne cee 41 9 DETAILED COMMAND DESCRIPTIONS sexes ss sesse esse esse ees sees sees sees vesse 2 BKPN TTT 42 li dy MERE EE ER EE EER EE Bag EE ER EE EE 43 je dy T 43 OE OE EE OE ER EE OE EE EE OE 44 CALAR ER EE EE EE EE ater EE 45 GAAR ated ein OE SG aA ae Ain oA EE NE OE ER HEET EE 46 AE EE NE AE OR EE EE EE OE ER ET 46 0 0 E es te bec E ER E E bed weeded aoe 47 ae EE ER EE EE OO EE EE OE ES 47 ed AE EE EE ier See EE ees Gide EE RE OE 48 IS 49 EE ARE EE EE OU EE ER EE ME HE ER 50 DUUR RE EE EE EE EE EE OE EE ON 51 BND REE EE EE OE EE E E E OE ER EO 51 BORINEX Tyee cesses E E EE EE EE EE OE N atte 52 Le 8 AR RO OE SE OR EE OE EE 53 TOLD es sss RE EE ER ER EE EO RE 53 led ER EE RE OE EE EO EE EO OE OE EO N 54 THON E E E E 54 IE Fly OR OE RE ER E EEE eT E NN EEEE 55 MR
14. on the left side of the board This connector provides for 2 TTL level digital inputs G1 amp G2 one analog 0 to 5 volt input AN0 two analog 0 to 5 volt outputs a fail safe contact closure input and 2 controller ground connections Contact closure between the fail safe input and ground will light the PC100 fail safe LED and turn off all of the process control outputs For ultimate safety this fail safe input should be connected to a normally open close on rise bi metal over temperature fail safe sensor The last step is to mount the temperature sensor Your PC100 has been set up for the type of probe requested when ordering the controller The unit is set for degree C temperature scale by default when shipped Figure 6 shows the connection diagram for all of the probe types accepted by the PC100 Probe type changing temperature scale changing and calibration is covered later in this manual When locating the temperature probe try to select a location that will minimize the thermal time delay between process temperature variations and the probes sensed temperature 4 WIRE 3 WIRE 2 WIRE RTD RTD RTD Si EF EE ADD S 7 JUMPER Q4 PROBE T AT S 5 eres Q 6 Z S 7 Os PROBE SENSOR CONNECTIONS TOP VIEW OF PROBE CONNECTOR THERMOCOUPLE Fig 6 Connection Diagram for Probe Sensor Connector located on back of controller At this point ma
15. port if command errors are detected In all cases the only data that is sent to the GPIB interface by the controller is that which is requested by a command received by the controller The GPIB port does not respond with OK after commands that do not send back data since hand shaking is an inherent feature of the GPIB The MENU allows you to examine the GPIB address and the GPIB LOCKUP TIME which is the length of time that the controller will wait for the host to accept data before generating a GPIB LOCKUP interrupt The SINT remote command also provides the ability to set up the parallel poll REMOTE INTERRUPT CHARACTERS Condition Serial Port GPIB Port HEX No Interrupt n a 00 Single T O INT I 41 Command Error INT 2 42 LP Timeout INT D 43 LP Done INT E 45 DEVIATION INT D 46 OVER Temperature INT O 47 UNDER Temperature INT U 4A GPIB Lock up INT n a 4F POWER Going Down none POWER Up no auto cont Z none POWER Up auto cont X none BKPNT B 50 PC100 Manual ver 0709 33 AS REC a TO A O aO REC BE rr i s lt sSOOC SSC n a Q 2 RAN 6 sae 1 to RAN DBS MALE RS422 FULL DUPLEX REMOTE CONNECTOR WIRING Sf RAN REC ae fo O Sto TRANZREC Z o EE 1 O L DBS MALE RS422 HALF DUPLEX REMOTE CONNECTOR WIRING Fig 7 Wiring Diag for
16. receive ASCII data from the GPIB to the RS 232 Serial Interface Syntax ISSS SSS transmit string sss sss to the serial intf S receive string from serial interface Description The S command is a TCO1 compatible command which allows the GPIB interface to transmit ASCII data to the RS 232 serial interface or receive data from the serial interface Care should be taken that a serial device does not transmit data to the controller until an command has been issued since data received from a serial device without an S command pending will be interpreted as command data for the controller An S command is required for each string of characters terminated with a carriage return and or line feed to be transferred to the GPIB interface GPIB lock up time is inhibited for the S command to allow time for a serial device to respond to a prompt message Restrictions GPIB remote interface command only See Also n a Example These commands must originate from the GPIB interface S GPIB interface sends request for reply prior to sending a prompt message to insure that the reply message is sent to the GPIB interface by the controller send status the string send status is sent from the controller s serial interface to prompt serial interface device Tm OK controller response transfers message received from serial inter face to the GPIB interface PC100 Manual ver 0709 SCALE Function Examine present scale for probe Syn
17. se ee se ee ee ee Ge esip HEE Ne poies REES ke 8 LOST OR DAMAGED EQUIPMENT T ee ees se ese ese ese ese ese ee see ee ee see eed Gee ee dee ee ee ee ee ee ee ES ee ee dO 8 PC100 GENERAL DESCRIPTION iese ese se oe vee e ee see th gee Ge eed er ee Ee eel eed see sb dee se 8 MOUNTING AND CONNECTING CONTROLLER sees sese see se ee see se ee se ee ee ee ee ee ee be ee 9 Fig 1 Standard 1 4 DIN Panel Opening 0 0 eee see eare Ge ee Se ee ee ee ee Re Ge GR Ge RA Re ee 9 Fig 2 Fixing Details For Remote Control Board iese ses ses se ee Ge Ge ee Se ee ee ee ee Re Ge Re ee 10 Fig 3 Fixing Details For The Process VO Board iese ese se se ee ee se Ge AR GR ee Ge ee Ge ee ee ee 11 Fig 4 Process VO Board Schematic sss sese esse eee 12 Fig 5 Example Hookup of Process I O Board to Chamber sss esse ses ses see ee ee ee ee ee ee ge ee ee ee 13 Fig 6 Connection Diagram for Probe Sensor esse ee see se ee ee Re Ge GR Ge GR GR ee Ge ee ee ee ee ee 14 SINGLE TEMPERATURE MODE EXAMPLE ses see se ese se se ese ee se ese ee see ee ee see ee dee ee ee ee ee ese ee ee ese ee 15 LOCAL PROGRAM MODE EXAMPLE esse sees see se ee ese ese ee ese ese ee ee ese ee see see eke ee dee Gee ee ke eke ee ee 15 GPIB IEEE 488 REMOTE CONTROL ee see see see ee ee see ee ee eke ee ee ee ese ese ese ese ee se ZN vdes 17 2 FRONT PANEL DESCRIPTION siese is sides os gese ige sense oe ses es gee dee se go dees dei esse se dee 19 Ien AE AM E HEET EER EE EE EE EE AE 19 LED INIDIS NIS
18. the PID control loop values or simply output a voltage from 0 5 Volt when written to using the OUT3 command The commands listed below control communication with the input output interfaces BIT VO OUTO n m where n 2 6 for the number of the output and m 1 or 0 for on off 1 on O off Bits 0 1 and 7 are used for heat cool and power on off respectively INO n Im where n 0 for G1 or 1 for G2 for the number of the input and m 0 9 for the I variable to store the state of the input The I variable can then be read via the In command COMPRESSOR CONTROL Bit 2 of the Bit I O can be configured to turn on off the compressor of a compressor based temperature chamber This feature is enabled via the menu from the front panel If enabled bit 2 will be on whenever cooling is required The bit will remain on to keep the compressor on for a minimum of 4 minutes If cooling is not required for 4 minutes bit 2 will be turned off to turn the compressor off If cooling is required any time the 4 minute counter is restarted If bit 2 is to be used for any other purpose Compressor Control must be disabled from the Menu from the front panel REVERSE LOGIC FOR HEAT COOL COMPRESSOR amp BOOST COOL The PC100 is initially configured for standard output logic for bits 0 1 2 and 3 of the Bit I O which is heat cool compressor control and boost cool respectively Standard logic means that if the action is required to be on the output w
19. the local program from the front panel keyboard depressing the COOL switch on the front panel enters either CON or COFF If the opposite action is desired backspace over the entry and re enter to get the correct action The local program defaults to CON when the local program begins running Restrictions None See Also CON HOFF HON Example COFF disable cooling CON Function Enable cooling Syntax CON Description The CON command permits a remote interface to enable cooling operation The COOL switch located on the front panel can also enable cooling operation if depressed when cooling is disabled When editing the local program from the front panel keyboard depressing the COOL switch on the front panel enters either CON or COFF If the opposite action is desired backspace over the entry and re enter to get the correct action The local program defaults to CON when the local program begins running Restrictions None See Also COFF HON HOFF Example CON Enable cooling operation PC100 Manual ver 0709 47 48 CSET Function Examine the present control value Syntax CSET Description The CSET command allows for examining the present value that the controller is attempting to control to During ramping this value is alternately displayed on LINE2 of the front panel LCD display Restrictions Remote only See Also TEMP Example assumes scale in degrees C RATE 10 define temperature segment RATE 10 deg C m WA
20. the probe and line two alternately displays the SET point and the WAIT time Line two also displays various responses from the controller as well as any data entry by the user from the front panel LED INDICATORS The front panel on the PC100 contains nine LED indicators The FAIL SAFE indicator lights whenever a fail safe condition occurs The HEAT and the COOL LEDs light when the controller turns on the heat and cool outputs These LEDs will not light unless the HEAT ENABLE and or COOL ENABLE are activated The REM CTL LED lights when either GPIB RS232 or RS422 remote control is active The LOCAL PROG LED lights when in local program edit mode or when a local program is running and blinks when the local program has been set to run at a time of day The TIME OUT LED lights when the wait time for a set point has timed out The LED next to the red SHIFT key is used to indicate that the SHIFT is active Using the SHIFT key allows entry of the commands printed in red on the controller front panel The remaining two LEDs indicate that the heat and or cool enables are active KEYPAD The keypad on the PC100 is labelled with white and red commands on and above the keys To access the commands labelled in white the key is simply pressed and the function will appear on line two of the display To access the commands labelled in red the red SHIFT key must first be pressed followed by the desired key The ENTER key must be pressed after all commands for the
21. time should begin counting down thus providing guaranteed temperature soaking The default is 1 deg C ENABLE BUZZER This menu item enables disables the buzzer RUN LP AT TOD This menu item enables disables the local program LP to run at a particular time of day TOD The YY or N on the second line of the display indicates if the local program is enabled to run at a time of day The time displayed is the time that the program is set to run Pressing ENTER only at this menu prompt will take you to the next item Entering NO will PC100 Manual ver 0709 disable the local program running at a time of day and take you to the next menu item Entering YES will enable the local program torun atatime of day The menu will then display PROG to RUN Enter the program number you wish to run The program will then display ENTER TIME The time that the program will run can now be entered If an error is made while entering the time and the ENTER key is pressed the local program running at a time of day will be disabled and the menu will go to the Run LP at TOD prompt to allow for correct entry The LOCAL PROG front panel LED will flash to signify that LP is set to run COMPRESSOR CTL This menu item enables the automatic compressor control feature of the PC100 When enabled Process output bit 2 acts as the control for the compressor See Section 8 for complete description of the compressor control feature COOL BOOST This men
22. tip into boiling water or use SUN s TCAL2 calibrator etc and let stabilize for 30 60 seconds 10 After waiting 30 60 seconds type YES lt ENTER gt 11 You must now select the desired scale deg C deg F or deg K Type 1 lt ENTER gt for deg C type 2 lt ENTER gt for deg F or type 3 lt ENTER gt for deg K 12 To fine calibrate to a house standard the calibrate to a standard can be performed from the MENU optionally if you wish See Section 3 Menu PC100 Manual ver 0709 8 INPUT OUTPUT The PC100 has 8 bits of on off output 2 bits of on off input and a fail safe input The 8 bits of on off output and the two bits of on off input will be referred to as Bit I O Of the 8 bits of output 5 are available to the user through the use of the OUTO command The remaining three Bit 0 1 amp 7 are always used by the controller for heat cool and power on off respectively Some of the 5 remaining outputs may be used if special functions such as compressor control etc are enabled in the MENU The inputs are available to the user through the use of the INO command The outputs are open collector 12 Volt 100 mA and are capable of controlling solid state relays or small 12 volt DC relays The two inputs can be used to sense TTL levels or dry relay switch closure contact to ground a 10k ohm pull up to 5 v is built in Also available on the PC100 is one analog output This port can be configured to drive a chart recorder output
23. 0 Manual ver 0709 41 9 DETAILED COMMAND DESCRIPTIONS BKPNT Function Local program breakpoint or pause command Syntax BKPNTnnn display number nnn at breakpoint BKPNTIm display I variable value at breakpoint Description The breakpoint command allows for local program operation to be suspended until the ENTER key is depressed on the front panel or until the remote controller issues a BKPNTC command The BKPNT command permits program debugging by providing convenient pauses in local program execution such that an operator may examine local program performance and is also useful when a host controller may wish to perform I O at a point in the local program One form of the breakpoint command displays a number on the front panel display when encountered which is useful for identifying different breakpoints within a program The other form of the breakpoint command displays the value of one of the I variables 0 9 which is useful for breakpoints that are placed within FOR NEXT loops Restrictions Breakpoint values displayed on front panel display To read over remote bus issue BKPNT command See Also BKPNT BKPNTC Example editing from the local keyboard EDIT edit program END controller response BKPNT100 _ set breakpoint 100 END controller response FOR 12 1 10 begin FOR NEXT loop END controller response BKPNTI2 set breakpoint for I variable 2 END controller response NEXTI2 end FOR NEXT loop END controller response ST
24. 4 44 esse Ss Eg ees be oog ie ske Seta eke Dee Veen ee bees de Rg busse A era RB eevee eas Reg He 26 RUN ERAT Lo D RE EE ER N EE EE EE EE 26 COMPRESSOR CTD epep a RE EE DE ER EE OE E 27 COOL BOOST erties aeea EE EE EE EE EE OG 27 PH P COEFFICIENT FOR HRA TT esse ese sees de sg esse eg deed gebie geoes be sees Ai be eeuse ees besk dae be ges geed 27 LH COEFFICIENT FOR HEAT iii ses SEE sessdeasees ERGE EE RR sege eek ae Rede MEES s EOAR EE SETE APESE T RST Etap host 27 D H D COEFFICIENT FOR HEAT cerute Ee sie EE Gee EEE bees ances EE see OE ee Se ee ds 27 P P COEFFICIENT FOR COOL es VEE tete SEDEER Re ER TOARE TREES De ee BEE RES 27 PC100 Manual ver 0709 I C Q COEFFICIENT FOR COOL EE GE EE Ar ee ee ST Eor 27 D C D COEFFICIENT FOR COOL sees BEE eed eie oe se ee es Re ee EP ee es trent 28 4 LOCAL PROGRAMMING se se sees sesse se ese Be Se See Ee Ee Re Ee Roe ee gegee 29 5 REMOTE CONTROL GPIB and R 232 and R422 sesse ssesseeseese esse sesse sese OL RS 232 SERTALPORTPROTOCO S ees Seer ees Bees Ee bee eed ge ese Ee Gee GE E GEN Ge Ge E eg 31 RS232 CABLE WIRING DIAGRAM FOR PC100 ou ee se se ese se see ee Ge ee ee Ge Gee AR ee 31 RS 422 485 SERIAL PORT PROTOCOLS ees sesse ee see se ese Bes se ese ese ee Be bee See Re Be ee ee ee SS Gee ee ee 32 GPIB PORT PROTOECOLS ss Ee ee oge eg Ve ee SE Ge EG Ee E De aa ee ee sos ee 33 REMOTE INTERRUPT CHARA COT RS Geseend sesse sege ede Ga beseer eb veg eie eaten lee ees ee ee
25. AE OE EO ER N EE N EE N S 19 KEY PA ARE EE ORE ER EE EE ER E 19 CAL TO STAND CALIBRATE TO A STANDARD se se ese esse se es se ee ee ee ee GR Gee Gee Se ee ee ee 22 MEDIESE AE AE ER RE EE EE OE EE NG 23 CHART TEMP CHART TEMP AND OUTPUT PIDS sees sesse se esse ee ee see ee ee ese ese ese eek ee see eke ee ee 23 DISABLE INTS DISABLE INTERRUPTS iese see rece see se ese se ese ese enen 24 GPIB amp 422 ADDRESS 0 31 issie sesse sees EES EE Re ESEG SEG R EG EER gee beg Re EG Res Gee Ge DEEG Ee REGSE BEES Re SR ERG ASe GEE Gee 24 GPIB EOCKUP TIME ii ie iseer dak oes sk Ge eg EE ives vende bedek Eie ek E NEER eg ie ee bees gee Ge ER eg ees Ee eke Dee 24 TIMEOUT N dei HO NE EE EE EE EE RR EE EE EG 24 SERIAL PORT MODE 2 62 is Ese sei oe Gegee EER E Pe Ee Bee eek eeue dbe dete wishes Asc dek E Bag bes bek gek 24 BAUD RATE MURE EE EE EE Eea b IEEE ap EE 25 AIS P E FCHO ON EE OE OE OE OR OE HEN N 25 RS DTR ETS ON saah reaR ES ESE as GEGEE TREDE TRT WER EES GED Ge EE EER abe GEGEE ERS T 25 DEVIATION LIMIT aie se ses hives nde Ee esel See beer Miata be Gog besks daa haere iW eg aA anand 25 TOW AD AD IG EE ER EE EE EE EE OE WEE 25 HIGH TEMP BIS MEE KEER RE RE RR EE ER 25 PULSE WIDTH MOD EE ORE EE ER ER EE OR OE 26 OOPS MYL EER ENE RE tet Rake EE EE OE EES 26 POW DOWN RESTART assant Hoge NES SG REG OTER ROTTE KOET bee bed KEES EERE GEE MEES ses Tn 26 FHINE FREQ ER EE N EA AE RE OE EE NG 26 WATT TRIGGER AE RE EE EE EE EE ME EE EE es EE 26 ENABLE BUZZER
26. C 1 to 65 535 FOR NEXT loop executions for 10 loops nesting supported PID algorithm Pulse width modulated pro grammable from keyboard or remote inter faces 20 key keypad 2 line 16 characters per line alphanumeric LCD display Built in IEEE 488 and RS232 interfaces 5 auxiliary outputs 2 auxiliary inputs 1 analog output channel PC100 Manual ver 0709 Safety Features Convenience Features PC100 Manual ver 0709 Open short probe detection adjustable upper and lower temperature limits Fail safe input Heat cool enable disable switches battery backed memory for local program configu ration menu remote interrupt operation time of day clock 83 84 12 REPAIR INFORMATION Due to the test system required it is not recommended that the PC100 be repaired in the field If a problem should arise call Sun directly to resolve the problem over the phone if possible or to arrange for the unit to be sent back to Sun for repair When calling to return a controller Sun Systems will issue a Return Material Authorization RMA number This RMA number should be on any paperwork sent with the controller and should also be displayed on the shipping box If a unit is returned without an RMA number the repair could be delayed Should there ever be a need to replace the software in the PC100 i e with a new version supplied by Sun Systems in an EPROM the following procedure should be performed 1 Write down
27. Controller returns an 11 character string where position A v L OSD 5 10 11 Description all remote interrupts off single timeout interrupt enabled deviation interrupt enabled Local program timeout interrupt enabled Local program done inter rupt enabled Buzz single timeout Buzz LP done Buzz LP timeout command error interrupt enabled BKPNT interrupt enabled no parallel pole 1 to 8 to define parallel pole bit The SINT command allows for setting or examining the interrupt parameters over the remote bus Restrictions Remote command only PC100 Manual ver 0709 STATUS Function Allows polling in lieu of interrupts for remote operation Syntax STATUS Description This command will allow polling to take place instead of interrupts when controlling the PC100 via one of the remote busses Restrictions Remote interface command only Example STATUS Returns with 18 character response where char position is Y power is on 2 Y command error last command 3 Y time out LED is on 4 Y waiting for timeout 5 Y heat output is enabled 6 Y cool output is enabled 1 Y valid set temperature 8 Y deviation limit exceeded 9 Y currently ramping 10 Y probetempslower limit 11 Y probe temp gt upper limit 12 Y waiting at a breakpoint 13 Y in LP run mode 14 Y in LP remote store mode 15 Y in local edit LP mode 16 Y waiting to run LP at time of day 17 Y GPIB bus timeout 18
28. ENU but not hardwired unit will not communicate RS 422 485 SERIAL PORT PROTOCOLS The RS422 serial port mode works as explained above for the RS232 except that there is no hardware handshake support Only Txd and RxD are used To allow for connection of multiple PC100 s to a single RS422 cable each PC100 must be addressed to talk and listen By providing unit addressing capability multiple PC100 s can be connected to acommon serial cable Figure 7 shows the wiring diagrams for a 4 wire full duplex bus and for a 2 wire half duplex bus To use the PC100 with the 2 wire half duplex setup jumper F must be cut and jumper H must be installed on the 840059 CPU board see figure 8 Up to 31 PC100 s can be on acable The end PC100 needs to have two 120 ohm 1 4 watt terminator resistors added to the remote connector module board in R1 and R2 places provided The following commands are provided to control data flow over the serial bus LISTEN nn Tell PC100 nn to listen to commands sent by host LISTEN ALL Tell all PC100 s on bus to listen LISTEN NONE All commands other than LISTEN and TALK are ignored TALK nn Tell PC100 nn to talk out over the bus to host TALK NONE Tell all PC100 s not to talk to host PC100 Manual ver 0709 GPIB PORT PROTOCOLS When CMD ERROR INT S are enabled the GPIB port sends a CMD ERROR SRQ interrupt on commands received with errors If command error interrupts are disabled then no response is sent to the GPIB
29. ER IN CONNECTION THEREWITH NO STATE MENT OR RECOMMENDATION NOT CONTAINED HEREIN SHALL HAVE ANY FORCE OR EFFECT UNLESS IN AGREEMENT SIGNED BY AN OFFICER OF SUN ELECTRONIC SYSTEMS INC INITIAL INSPECTION AND UNPACKING Inspect the shipping container for obvious damage If the shipping container is damaged then a written note on the bill of lading describing the damage should be made while the delivery person is still on the premises Unpack the PC100 and save all carton and cushioning material in case the unit needs to be returned Verify the contents of the carton matches that of the items listed on the packing slip LOST OR DAMAGED EQUIPMENT If you determine that the goods described on the packing slip are lost or damaged first notify the transportation company to obtain the correct procedure for returning merchandise for repair or replacement Then call Sun Systems for a return material authorization RMA number so that we may best handle the merchandise when it is returned PC100 GENERAL DESCRIPTION The Model PC100 is a 1 4 DIN size digitally controlled single channel ramping temperature controller that comes standard with GPIB IEEE 488 and RS232 422 remote control capabilities The PC100 consists of four components the main controller section the remote interface pod and cable the process I O board and cable and the temperature probe The controller section contains the keypad display and most of the electronics The remot
30. IT 30 wait 30 min TEMP examine present temperature 25 0 controller response 25 0 deg C SET 35 0 set new final temperature 35 0 deg C wait 30 seconds CSET examine present ramp target temperature 30 0 controller response 30 0 deg C PC100 Manual ver 0709 DEL Function Delete current line during local program edit and delete local program if not in local program edit Syntax DEL Front Panel Only DELn where n 0 9 Front Panel Only DELPn where n 0 9 Remote Only Description The DEL command allows for deleting program lines during local program editing on the front panel keyboard The line currently displayed will be deleted when the DEL command is entered If notin local program edit DEL deletes the entire local program If this command is entered from the front panel the controller will prompt with YOU SURE before the program will be deleted Ifthe DEL command is entered remotely no prompt will be displayed and the program will be deleted Before using the STORE command from a remote interface the local program must be deleted if any commands are present Restrictions DEL Local front panel command only When in local program edit mode this command deletes a program line When not in local program edit mode the command will delete the program n which you specified DELP remote only Example DEL Enter LCD displays DELL and deletes program line when in EDIT mode DEL 2 Enter LCD displays DELP 2 and delete
31. MODEL PC100 TEMPERATURE CONTROLLER USER MANUAL Covers Model PC100 The information in this document has been carefully checked and is believed to be entirely reliable No responsibility however is assumed for inaccuracies Further more such information does not convey to the purchaser of the product described any license under the patent rights of SUN ELECTRONIC SYSTEMS INC or others Sun Systems strives constantly to improve the quality and performance of all of its products in design construction and cost As a consequence SUN ELECTRONIC SYSTEMS INC reserves the right to change specifications or other data contained herein without notice Any software firmware designs and any other programs in Sun Systems products remain the sole property of SUN ELECTRONIC SYSTEMS INC and may not be copied by any means Purchase of said product constitutes agreement that software rights remain to the benefit of SUN ELECTRONIC SYSTEMS INC Upon purchase Sun Systems grants perpetual license for use by the customer Copyright December 1993 by SUN ELECTRONIC SYSTEMS INC REVA 0709 PC100 Manual ver 0709 PC100 Manual ver 0709 Contents 1 GENERAL INFORMATION isi sessies ese eise eden de eyes ee gese de pe Gesk ee keep Geek deeg degie 7 INTRODUGTION SEE chide GE Se RR ge gee Ee Ge Se ie Ee seen N e Re EE Se ee dees Re gee se dt T LIMITED WARRANTY INFORMATION sese 7 INITIAL INSPECTION AND UNPACKING eee pees esse see se OO se
32. OP terminate program entry PC100 Manual ver 0709 BKPNTC Function Remote bus command to continue from breakpoint Syntax BKPNTC Description When the BKPNT interrupt is enabled by the SINT remote command or from the MENU and a local program is started via a remote RUN command then when a BKPNT is reached during local program execution the breakpoint interrupt is sent to the appropriate remote bus The host controller upon receiving the breakpoint interrupt may issuea BKPNT command to read the value of the breakpoint and issue a BKPNTC to continue local program execution Restrictions Remote only command BKPNT Function Remote bus command to read value of breakpoint Syntax BKPNT Description When the BKPNT interrupt is enabled by the SINT remote command or from the MENU and a local program is started via a remote RUN command then when a BKPNT is reached during local program execution the breakpoint interrupt is sent to the appropriate remote bus The host controller upon receiving the breakpoint interrupt may issuea BKPNT command to read the value of the breakpoint and issue a BKPNTC to continue local program execution Restrictions Remote only command PC100 Manual ver 0709 43 44 C Function Set or examine the current set temperature in deg C Syntax nnn nC set current set temperature C examine current set temperature Description The C command is a TCO1 controller compatible command which either sets th
33. Y in local keyboard lockout mode PC100 Manual ver 0709 73 74 STOP Function Terminate local program execution terminate local program edit exit menu and terminate single temperature segment execution Syntax STOP Description If in Local Program operation the STOP command terminates local program execution in the controller Ifin local program edit from the front panel the STOP command from the front panel ends local program edit If in the MENU the STOP command from the front panel will exit the menu Ifrunning in single temperature mode then entering the STOP command terminates the temperature segment and sets SET NONE and WAIT FOREVER Restrictions None See Also RUN STOP 9 Function Restores controller to factory default settings and clears all local program data Syntax STOP 9 Description The STOP 9 command resets the controller to factory default settings deletes the local program and all limits You may wish to write down settings and the local program before issuing this command Calibration information is not affected The controller will go to the power off mode after this command is executed Restrictions None Example STOP 9 Reset controller to factory default settings PC100 Manual ver 0709 STOREn Function Stores a downloaded local program from a remote interface Syntax STOREn where n 0 9 Description The STORE command allows a remote interface to down load a local program to the
34. ace Do not over tighten the panel hold screws As the panel hold screws are tightened small levers will swing out and capture the rear side of the panel thus holding the controller in place To remove the controller turn the two panel hold screws counter clockwise until the hold levers swing back out of the way The remote control connector plate is mounted at any convenient place on your equipment Pick a location that is accessible for remote cable hookup Figure 2 provides recommended cutout information m 36200 _ 1 4 DIN PANEL OPENING 3 6200 M CONFORMING TO DIN 43700 Fig 1 Standard 1 4 DIN Panel Opening PC100 Manual ver 0709 10 RO 1250 K O 2 2500 2 5000 Fig 2 Fixing Details For Remote Control Board The process I O board provides all of the wiring connections to your equipment It should be mounted on a panel inside of your equipment enclosure in close proximity to the high power loads The board connects to your AC line and provides low level control signals to control your power control relays Figure 3 provides mounting hole information AC line voltage is brought into the board See Figure 4 on the 2 position screw terminal block labelled P5 located next to the fuse A switch is provided on the board for line voltage selection Push the slide switch to the right for 110 VAC operation to the left for 220 VAC Connect the HOT line wire to
35. ackspace over the entry and re enter to get the correct action The local program defaults to HON when the local program begins running Restrictions None See Also COFF CON HOFF Example HON Enable heat output PC100 Manual ver 0709 I variables Function Set or examine I variables Syntax Im lt value gt Im lt value gt set Im equal to value Im Im svalue _ Im Im lt value gt set Im egual to sum of values Im Im lt value gt Im Im lt valve gt set Im to difference of values Im Im examine I variable m Description I variables are used in local programs for loop control and general purpose Integer arithmetic A value may be any integer in the range of 32768 32767 or another I variable Ke 99 The controller supports 10 I variables where m ranges from 0 to 9 From the front panel wow a comma is used for the equal sign Restrictions None From the Front Panel a comma is used for the equal sign See Also FOR NEXT IN OUT BKPNT Example 10 52 set I variable 0 to 52 12 I0 set I variable 2 equal to I variable 0 I5 10 9 set I var 5 I var 0 9 43 16 10 I5 set I var 6 I var 0 I var 5 95 16 examine I variable 6 95 controller response IN Function Input data from the BIT I O Syntax IN lt device number gt lt address gt Im Description The IN command allows data read capability from the two inputs provided The device number for the two inputs is 0 D
36. all important settings you have entered into the PC100 as well as saving the local program The local program can be up loads to a host computer and saved on a floppy disk LOCAL PROGRAMS AND OTHER DATA MAY BE DESTROYED WHEN CHANGING SOFTWARE SAVE ANY IMPOR TANT INFORMATION BEFORE PERFORMING THE REST OF THIS PROCEDURE Un plug the unit Remove line power to equipment that the PC100 is connected to Remove the PC100 from the equipment panel by unscrewing 5 or 6 revolu tions counter clockwise the two panel hold screws on the units front panel Slide PC100 out amp remove two flat cables and probe connector to free controller from its wiring Unscrew the screw on the back of the PC100 until it is loose Pull off front panel Remove nut from screw that comes from back amp remove screw Remove 4 screws on the bottom of the unit then slide controller boards stack out The bottom board contains the firmware EPROM chip Remove bottom board from 3 board stack by removing four standoffs then unplug board Remove the EPROM carefully and replace it with the new one supplied by Sun Systems Check for proper pin orientation when installing IC 10 Reassemble the unit re connect the PC100 rear connectors and remount in equipment panel PC100 Manual ver 0709 11 Turn the controller on A new version number should be displayed on power up Next key in the command STOP 9 then ENTER to the controller This will
37. am done breakpoint and command error Answering NO will enable the interrupts To selectively enable disable the interrupts the remote SINT command should be used GPIB amp 422 ADDRESS 0 31 This prompt will display the current GPIB address and allow you to change it This address number is the GPIB device address as well as the unit address used by the RS422 485 TALK and LISTEN commands GPIB LOCKUP TIME This item allows entering of the maximum lockup time in seconds for the GPIB interface The range is 2 59 seconds If Ois selected then GPIB lockup interrupts are disabled The controller uses this value when deciding on how long to wait when trying to send a requested string out over the remote GPIB bus TIMEOUT PRETIME This value is the length of time before an actual wait period timeout that the controller will generate a single timeout interrupt The range is 0 59 seconds This allows readings to be taken before the controller begins ramping to the next set point SERIAL PORT MODE Used to select which serial port you wish to use Enter 1 for RS232 or 2 for RS422 485 PC100 Manual ver 0709 BAUD RATE SET This menu item allows changing and examining of the RS232 baud rate The range is 1 6 based on the following 1 9600 baud 2 4800 baud 3 2400 baud 4 1200 baud 5 600 baud 6 300 baud RS CHAR ECHO ON Answering YES to this prompt will enable RS232 character echo Character echo allows you to see what yo
38. ata values read are stored in I variables Restrictions The only device number allowed is 0 and the only device addresses allowed are 0 and See Also OUT I variables Example INO 0 12 Read device 0 bit 0 store in I var 2 PC100 Manual ver 0709 55 56 LIST Function List the local program from a remote interface Syntax LISTn where n 0 9 Description The LIST command permits a remote interface to up load the local program from the controller This command allows a remote operator to verify the results of a STORE instruction which down loads the program to the controller In addition some communica tion programs allow for capturing data to text files In this manner local programs can be maintained on a personal computer and downloaded or up loads if required Restrictions Remote interface command only See Also STORE Example DEL1 clear local program 1 STORE1 ready controller for local program 1 down load ERT send local program END end down load LIST1 request up load of local program 1 Kia local program displayed LISTEN Function Sets the PC100 in listen mode Syntax LISTEN nn LISTEN ALL LISTEN NONE Description When the RS422 serial port is used for communication between the host computer and the PC100 unit s the LISTEN nn sets the PC100 nn in listen mode The LISTEN ALL sets all the PC100 units on the bus in listen mode The LISTEN NONE indicates the units on the bus to ignore all commands other t
39. e 3 END end of LP 2 HOLD Function Pause execution of local program Syntax HOLD Description Pressing the HOLD button while the local program is executing pauses the program execution until the HOLD is pressed again HOLD command also pauses the WAIT time count if the local program was executing the WAIT time while the HOLD was pressed Restrictions Front Panel Operation only PC100 Manual ver 0709 53 54 HOFF Function Disable heat output Syntax HOFF Description The HOFF command permits aremote interface to disable the heat output The front panel HEAT switch also disables controller heat function when depressed if heat was enabled When editing the local program from the front panel keyboard depressing the HEAT switch on the front panel enters either HON or HOFF If the opposite action is desired backspace over the entry and re enter to get the correct action The local program defaults to HON when the local program begins running Restrictions None See Also CON COFF HON Example HOFF disable heat output HON Function Enable heat output Syntax HON Description The HON command permits a remote interface to disable the heat output The front panel HEAT switch also disables controller heat function when depressed if heat was enabled When editing the local program from the front panel keyboard depressing the HEAT switch on the front panel enters either HON or HOFF If the opposite action is desired b
40. e current set temperature or examines the controller for the current set temperature The set or response is in degrees centigrade always The C command returns with a value of 1999 if the current set temperature is equal to none Restrictions Remote command only See Also SET Example 150 0C Set current set temperature to 150 0 deg C C Send command to examine current set temp 150 0 Controller response temp 150 deg C SET Examine current set temp with SET command 150 0 Controller response PC100 Manual ver 0709 CALAx Function Syntax Description CALAx command allows for the offset adjustment on the measurement reading of channel x CALAx access code standard reading where xX 1 Ch_1 access code 9 standard Reading Known measurement value The CALAx command allows user to offset the measurement value on channel x See Calibrate to a Standard and Changing probe type sections for complete calibration procedure The CALAx command may be used after an initial calibration sequence to fine tune the calibration of a particular channel Restrictions See Also Example Remote command only CALBx CALC Offset adjustment for channel 1 Ch_1 sensor is placed at 0 C After stabilizing Ch_1 sensor reads 0 5 C The command CALA1 9 0 0 is issued The sensor now reads 0 C PC100 Manual ver 0709 45 46 CALBx Function CALBx command allows for the gain adjustment on the measurement reading of
41. e interface section is a small rectangular metal plate with a DB9 connector and a GPIB connector A 2 foot 26 conductor flat cable that connects the remote connectors to the PC100 is also supplied with the remote interface The process I O section consists of a PC board with a line transformer and barrier strips for input and output to the process you will be controlling The process I O board is equipped with a 2 foot long 20 conductor flat cable to be plugged into the PC100 The last item that makes up the PC100 package is the probe and its connector The PC100 was calibrated at the factory using the probe supplied with the controller if a probe was ordered Inspect all shipping material and containers for the items described above If you have not received all of the items listed call Sun Electronic Systems for assistance PC100 Manual ver 0709 MOUNTING AND CONNECTING CONTROLLER First make sure that line power is disconnected from the eguipment before work is started Connection of the PC100 to your equipment involves the following steps Mounting the main controller mounting the remote connector plate mounting the process I O board and wiring it to your equipment and finally mounting the temperature sensor The PC100 controller mounts in a standard 1 4 DIN panel opening See figure for mechanical details Simply slide the controller into the cutout then tighten the 2 screws on the front panel clockwise while holding the unit in pl
42. en allows other local programs to be called as subroutines To create a local program from the front panel you will do the following start edit mode prog 2 end is displayed signifying that prog 2 is empty If it was not empty you would press STOP ENTER to exit the edit mode and then pick another prog number or DEL the program to clear it We will loop 10 times The PC100 will prompt for RATE WAIT and SET values 20 ENTER you enter 20 for rate 3 ENTER you enter 3 minutes for wait 12 5 ENTER you enter 12 5 deg for setpoint SET SEG ENTER you want to enter the next temp segment The PC100 will prompt for RATE WAIT and SET ENTER you just press ENTER to use the same rate 0 4 30 ENTER you set the wait to 4 minute and 30 seconds 55 2 ENTER SET temp will be 55 2 deg lt shift gt NEXT 0 ENTER The matching NEXT to the FOR lt shift gt UP or DOWN You can use the red UP and DOWN arrows to move around in the local pro gram Let us assume that we wish to loop 5 times through the program rather than ten Use the UP arrow until the first line FOR command is displayed FORIO 0 10 Now use the backspace key to erase the 10 and type in 5 FORIO 0 5 Then press ENTER and the modified line is stored STOP ENTER Use stop enter to exit edit mode lt shift gt RUN 2 ENTER Use RUN to run the program The program will begin running The heat and cool enables will turn on and the LOCAL PROG LED will light up Starting with the current pr
43. ete line DEL command or by entering new commands which are placed in front of the command presently displayed on the front panel LCD display Local program editing is terminated by entering the STOP command Restrictions Local keyboard command only See Also STORE LIST END STOP END Function Terminate remote local program downloading Syntax END Description The END command terminates remote program downloading when using the STORE command from a remote host computer Restrictions Remote command only See Also EDIT STORE STOP PC100 Manual ver 0709 51 FOR NEXT Function Loop definition command for local programming Syntax FOR Im lt Beginning Value gt lt Ending Value gt or FOR Im lt Beginning Value gt lt Ending Value gt or FOR Im lt Beginning Value gt lt Ending Value gt NEXT Im Description The FOR NEXT loop command provides looping capability for local program operation Commands contained within the boundaries of the FOR statement and the NEXT statement are repeated as defined by the FOR statement The beginning or ending value may be any integer value or an I variable value The FOR NEXT loop either increments the beginning value until the beginning value is equal to or greater than the ending value or decrements the beginning value when the minus option is used until the beginning value is equal to or less than the ending value The number of loop executions is equal to the absolute va
44. gram figure 6 3 Plug the controller in and turn the controller on with the new probe in place You may geta PROBE ERROR message This is normal since the controller is set up for the previous probe type 4 Type MENU 9 lt ENTER gt This places the controller in the calibrate change probe menu The current type will display for a couple seconds The prompts for the new probe type will be displayed 5 Press the ENTER key until the desired probe type is on the display if the desired probe type is the first choice it is not necessary to press ENTER Continue to step 6 MENU 9 Calibrate Probes Yes or No If your response is Yes then RTD 385 PROBE Y N RTD 392 PROBE Y N J T C Y N J T C WIDE Y N K T C Y N K T C WIDE Y N T T C Y N SOLID STATE Y N U TO 5 VOLTIN Y N 0 TO 20 mA IN Y N _ PROBE IS CURRENT 6 When the desired probe type is on the display type YES lt ENTER gt 7 The controller will now ask if the probe is at O deg C At this point immerse the probe tip into ice water or use SUN s TCAL2 probe calibrator and let stabilize for 30 60 seconds It is recommended that if ice water is used that the water be stirred so that the ice water bath is the same temperature throughout If you answer no then rough default values will be set PC100 Manual ver 0709 38 8 After waiting 30 60 seconds type YES lt ENTER gt 9 The controller will now ask if the probe is at 100 deg C At this point immerse the probe
45. han LISTEN and TALK commands Restrictions Remote command only See Also TALK PC100 Manual ver 0709 LLO Function RS 232 Command to lockout local keyboard Syntax LLO Description The Local Lockout LLO command may be issued from a host processor to lockout the local keyboard The LLO command only applies to host computers communicating over the RS 232 serial interface Local keyboard function may be unlocked through the use of the RTL command Local keyboard lockout operation for host processors communicating over the IEEE 488 interface is a bus interface command The syntax varies according to the particular host computer Restrictions RS 232 remote interface command only Each host GPIB interface uses unique syntax for local lockout commands See Also RTL Example LLO lockout local keyboard run Sensitive testing RTL unlock local keyboard PC100 Manual ver 0709 57 58 LTL Function Set or examine the lower temperature limit Syntax LTL nnn n Set LTL variable units LTL Examine LTL variable units Description The LTL command allows for setting the lower temperature limit for which the controller will attempt to control The units for the LTL command are those as selected in the MENU for the probe Restrictions Remote command only Changing the LTL from the front panel can only be done through the MENU Temperature values for the LTL command must range between 200 deg C and the UTL setting See
46. hange Used to enable disable the heat and cool outputs If the LED is on the function is enabled If the LED is off the function is disabled The switches operate in a push on push off or alternate action fashion When in local pro gram edit depressing these switches enters HON or HOFF when HEAT ENABLE is pressed and CON or COFF when COOL ENABLE is pressed If the opposite action is desired backspace over the entry and re enter to get the correct action Turns the unit on and off 6699 Causes local program n in the PC100 s memory to begin 6699 running Program number n where n 0 to 9 Only valid in local program edit Allows for scrolling ARROW up and down through the local program Causes entry into the PC100 configuration menu This menu is fully explained in Section 3 Enables the local program edit mode To exit local pro gram edit the STOP command must be issued Performs two functions 1 delete current program line during local program edit or 2 delete a local program when not in local program edit mode If deleting a local program the controller will ask YOU SURE Y N before deleting the program PC100 Manual ver 0709 lt SHIFT gt BKPNT Used in local programming Either a number or an I variable I0 I19 must follow the BKPNT statement The BKPNT statement is fully explained in the Local Program ming Section Section 4 and the Detailed Command De scription Section Section 10 lt
47. hepard Drive Titusville FL 32780 Tel 321 383 9400 Fax 321 383 9412 Website www sunelectronics com Email sales sunelectronics com LIMITED WARRANTY INFORMATION PC100 Temperature Controller SUN ELECTRONIC SYSTEMS INC WARRANTS THIS PRODUCT TO THE ORIGINAL PURCHASER TO BE FREE FROM DEFECTS IN MATERIAL AND WORK MANSHIP AND TO OPERATE WITHIN APPLICABLE SPECIFICATIONS FOR A PERIOD OF TWO 2 YEARS FROM THE DATE OF SHIPMENT PROVIDED IT IS USED UNDER NORMAL OPERATING CONDITIONS THIS WARRANTY DOES NOT APPLY TO SEALED ASSEMBLIES WHICH HAVE BEEN OPENED OR TO ANY ITEM WHICH HAS BEEN REPAIRED OR ALTERED WITHOUT SUN SYSTEMS AUTHORIZATION RISK OF LOSS OR DAMAGE TO THE PRODUCT SHALL PASS TO THE CUSTOMER UPON DELIVERY BY SUN SYSTEMS TO THE CARRIER AT SUN SYSTEMS PREMISES WE WILL REPAIR OR AT OUR OPTION REPLACE AT NO CHARGE ANY OF OUR PRODUCTS WHICH IN SUN SYSTEMS JUDGMENT ARE FOUND TO BE DEFECTIVE UNDER THE TERMS OF THIS WARRANTY EXCEPT FOR SUCH REPAIR OR REPLACEMENT SUN SYSTEMS WILL NOT BE LIABLE FOR ANY LOSS OR DAMAGE TO PERSONS OR PROPERTY CAUSED EITHER DIRECTLY OR INDIRECTLY BY USE OF THIS PRODUCT OR FOR ANY INCIDENTAL DAMAGES PC100 Manual ver 0709 OR FOR ANY CONSEQUENTIAL DAMAGES AS THOSE TERMS ARE DEFINED IN SECTION 2 715 OF THE UNIFORM COMMERCIAL CODE BEFORE USING PUR CHASER SHALL DETERMINE THE SUITABILITY OF THIS PRODUCT VIA THIS DOCUMENT FOR HIS INTENDED USE AND PURCHASER ASSUMES ALL RISK AND LIABILITY WHATSOEV
48. ill be low or 0 Volts thus sinking current through your solid state relay Ifthe action is required to be off the output will be high Some systems require reverse logic however If your system requires reverse logic ie a freon PC100 Manual ver 0709 39 40 evaporator bypass valve for example jumper runs on Front Panel Logic PC board 840060 can be cut to enable reverse logic Figure 9 shows the location of the runs to cut To enable reverse logic for heat bit 0 H1 should be cut To enable reverse logic for cool bit 1 C1 should be cut To enable reverse logic for compressor control bit 2 H2 should be cut The PC100 must be disassembled to perform these cuts See repair section for controller disassembly procedure in Section 12 ANALOG OUTPUT OUT3 nn where nn 8 bit integer from 0 255 0 0 V 255 5 V PC100 Manual ver 0709 All Normally Active Low To Invert FS cut upper trace Heat cut next lower Cool cut next lower H2 cut next lower C2 cut next lower ae Y e z 6 uz a Col ers coel ja pes L e ye ss n ef Bauer dae L sd Mes DA el e oe 6 e e RIL Jee N ngs e el ee C8 w s e e dd L L e s 6 ES 6 e 6 eer sd 2 6 e dy v e Es s ax eee 2 an gg yd gt r w d e e aes L 9 Y N 29 5 s ND 5 E ae e ee ee 27 L s e de e o e D D te A 6 2 L L Pad Weeess o k Ta 5 ME Ie _s mcie n Fig 9 Jumpers for Reverse Logic PC100FP2 PCB 6 97 REV B PC10
49. isplayed after answering yes to CAL TO STAND is ENTER CAL ACCESS CODE The cal access code is 9 for the PC100 and this cannot be changed Having a cal access code should prevent unauthorized personnel from inadvertently calibrating the unit Once the correct cal access code has been entered the CLEAR STD CAL prompt is displayed Answering yes to this prompt will clear any previous calibration to a standard information If this is the first time through the menu to enter temperature 1 you should answer YES to CLEAR STD CAL However if temperature 1 has already been entered i e this is the second time through the menu then you must answer NO to CLR STD CAL to prevent erasing the information already obtained for temperature 1 The next prompt is TEMPERATURE 1 If you want to enter the first temperature answer YES If you answered YES the next prompt is ENTER TEMP 1 At this time the standard reading numeric value should be entered You can then either exit the menu by pressing STOP or continue with the other items in the menu You must eventually exit the menu however to enter temperature 2 If you answered NO to the TEMPERATURE 1 prompt the next prompt will be TEMPERATURE 2 Answering YES to this prompt causes ENTER TEMP 2 to be displayed At this time the second standard reading numeric value should be entered You can then either exit the menu or continue with the rest of the menu Shown below is a typical dialogue to calibrate the probe
50. ke sure that all the cables are plugged into the rear of the PC100 and then close up your equipment chassis Apply power to the controller and press the front panel ON button The unit will power up with its self test message and then begin displaying the temperature on the LCD top line Until a temperature is set the controller will not turn on your heat or cool loads so the temperature should not change much if the wiring is ok At this point you should check that the controller can turn on and off your process heating and cooling loads To check the heater enable the heat enable by pressing the front panel heat enable key LED on Next press the SET SEG key then the ENTER key The PC100 will prompt you for the RATE Just press enter to leave it unchanged Next it prompts for WAIT again press PC100 Manual ver 0709 enter Then it prompts for SET Type in 50 and press enter to set the target temperature for 50 deg You may use any other temperature above the probe temperature You will now see the HEAT LED turn on signifying that the heat process output Bit 0 is on If the heater is wired correctly the temperature should move higher To check the cooling side if your equipment cools press the cool enable and set a low temperature using the SET SEG key as above If you are using automatic compressor control and or cool boost these features must be enabled in the PC100 MENU See Section 3 To enable them press the SHIFT key then red MENU key and the
51. lue of the ending value minus the beginning value Without regard to the beginning and ending values the loop is always executed one time FOR NEXT loops may be nested four deep when considering the first loop as nest 1 Restrictions None Example DEL clear program remote STORE load local program FOR I5 1 5 FOR I variable 5 step 1 2 3 4 FOR 2 5 I5 FOR I variable 2 5 I variable 5 dec step 5 4 3 2 Pass 1 step 5 4 3 Pass 2 step 5 4 Pass 3 step 5 Pass 4 BKPNT I2 set breakpoint display I variable 2 NEXT Da end FOR NEXT nest 2 NEXT I5 end FOR NEXT nest 1 END end program store RUN run program When the program is run the breakpoint value will display the step sequence for the FOR NEXT I2 variable loop PC100 Manual ver 0709 GOSUB Function Execute local program m as a subroutine Syntax GOSUB m or GOSUB m Description The GOSUB command allows local programs to be called by other local programs as subroutines At the end of a local program called by a GOSUB command execution returns to the command following the GOSUB command in the calling program Nesting is supported for four levels considering the first calling programs nest 1 I variables are global to all local programs Restrictions Local program command See Also FOR NEXT Example Listing of local program 2 For 3 0 10 set FOR NEXT for 10 cycles GOSUB 0 execute LP 0 GOSUB 1 execute LP 1 NEXT 3 end FOR NEXT loop for I variabl
52. minutes or hour minutes seconds and press ENTER or just ENTER for no change The final prompt is for the SET temperature that you wish the PC100 to ramp to and control to Once the above three parameters have been set and the HEAT and COOL ENABLES are on the controller will ramp to the SET temperature During the ramping the PC100 will display the current set temperature that itis calculating CSET until it reaches the SET you typed in As soon as the probe temperature is within 1 0 deg C by default of the SET temperature the PC100 starts to count down the WAIT time When the wait time reaches zero the TIME OUT LED is turned on and the buzzer beeps The PC100 continues to hold the SET temperature until you set a new value via the SET SEG key You can at any time turn off the controlling function by pressing the STOP key then ENTER key or by just disabling the heat and or the cool enables That is about all there is to the single temp mode LOCAL PROGRAM MODE EXAMPLE The local program mode allows the PC100 to cycle through a number of RATE WAIT and SET segments automatically The PC100 provides for 10 separate local programs that are stored in the unit s battery backed memory FOR NEXT loop commands are provided so that whole programs or sections of a program may be repeated as specified by the user The PC100 Manual ver 0709 15 lt shift gt EDIT 2 ENTER END lt shift gt FOR 0 0 10 ENTER SET SEG ENTER GOSUB command ev
53. mote interface command only See Also ON Example OFF Turn OFF PC100 PC100 Manual ver 0709 59 60 ON Function Turn on PC100 Syntax ON Description The ON command enables power and function of the controller When the controller is plugged in to an appropriate line voltage the controller is powered on and can accept a power on command from either the front panel by depressing the power switch or from a remote interface by using the ON command Restrictions Remote interface command only See Also OFF Example ON Turn on PC100 OUT Function Output data to the BIT I O port or the Analog port Syntax OUT lt device number gt lt address gt lt data gt Bit I O device 0 Analog port device 3 Description The OUT command permits data to be transferred to an output device such as the Bit VO or digital to analog convertor port also referred to as Analog port in this manual For a complete description on operating with an I O device consult the Input Output Section 8 Restrictions None See Also IN Example OUTO 5 1 set Bit I O bit 5 OUT3 255 output 255 to D A port O 0V 255 5V PC100 Manual ver 0709 PIDC Function Set or examine PID coefficients for cool control Syntax PIDC nnn n nnn n nnn n set cool PID coefficients PIDC examine cool PID coefficients Description The PIDC command permits modification and examination of the proportional integral and derivative PID coefficients used in the alg
54. n ENTER Answer shift YES to enter menu then just press the enter key after each menu question until you reach the parameter you wish to change then press enter after each prompt until the menu terminates Now we can run through the major controller features in a simple example format First we will run the unit in its simple single temperature mode and then we will create a simple local program from the front panel and run it Finally we will connect an IBM compatible PC to the RS232 port and run SUN s data logging software that has been supplied with your PC100 to show remote control features SINGLE TEMPERATURE MODE EXAMPLE The single temperature mode is the most used mode You simply set a RATE of change in Deg per Minute set a WAIT at temperature time then SET the target temperature that you want the controller to go to All three of these parameters are prompted for when the SET SEG key is pressed followed by pressing the ENTER key First the current RATE setting is displayed on the LCD top line and the bottom line prompts for the new setting If you wish to keep the setting then just press ENTER key otherwise type in the new value you want and press ENTER Then the current WAIT time is displayed on the top LCD line and the PC100 prompts for your new setting Note that forever means that the time at temperature counting will not take place The PC100 will not beep and turn on the time out LED Type in the new WAIT time just the number of
55. n Set UTL variable units UTL Examine UTL variable units Description The TCO1 compatible commands provide for setting and examining the UTL in degrees centigrade only If temperature units are desired to be the same as that set in the menu for the SCALE variable then the UTL nnn n and UTL command formats should be used If the temperature exceeds the UTL setting then an over temperature interrupt will be generated to the active remote interface Restrictions TCO1 compatible commands operate from the remote interface only See Also LTL Example If scale is set to deg F 150 0UTL set UTL to 150 deg C UTL examine UTL in deg C 150 0 controller response 150 0 deg C UTL examine UTL in units of SCALE deg F 302 0 controller response 302 deg F PC100 Manual ver 0709 VER Function Examine the version of software in the PC100 Syntax VER request the version of software Description This command is used to determine the version of software that is in the PC100 Example VER request the version SUN SYSTEMS x xx controller response where x xx is the version number PC100 Manual ver 0709 79 WAIT Function Set or examine the temperature segment wait period Syntax WAIT hh mm ss set wait in hours minutes seconds WAIT mm set wait in minutes only mm 00 to 59 WAIT F OREVER set WAIT to forever WAIT examine current wait setting Description The WAIT command determines the time at which the controller will main
56. n TALK mode The TALK NONE indicates the units on the bus not to respond to the host computer Restrictions Remote command only See Also LISTEN PC100 Manual ver 0709 TEMP Function Examine current temperature Syntax TEMP Description The TEMP command provides the means for a remote interface to read the present value of the probe This value is normally displayed on the first line of the front panel LCD display The units for the probe are set in the menu for deg F C or K Restrictions Remote Interface command only See Also T Example TEMP read probe 25 0 controller response 25 0 units TIME Function Set or examine time of day Syntax TIME hh mm ss set time of day TIME examine present time of day Description The TIME command is useful for documenting report outputs and for starting local programs ata specific time of day Time is entered and displayed in a 24 hour format i e hours hh range from 00 to 23 minutes mm range from 00 to 59 and seconds ss range from 00 to 59 Restrictions Remote only command To change the time from the front panel the MENU must be accessed See Also RUN TIME hh mm ss Example TIME 13 30 00 set time to 1 30 PM TIME examine time of day 13 30 00 controller response PC100 Manual ver 0709 77 78 UTL Function Set or examine the upper temperature limit Syntax nnn nUTL TCO1 compatible set UTL in deg C UTL TCO1 compatible examine UTL in deg C UTL nnn
57. nd after 5 min for wait timeout PWMP 15 set PWM period for 15 sec WAIT 10 00 00 set long wait period 10 hrs SET 35 0 again set temperature PC100 Manual ver 0709 63 RATE Function Set the current rate of change for ramping Syntax RATE nnn n Set the current ramping rate RATE Examine the current ramping rate Description The RATE command allows for setting or examining the rate at which the controller will control the change from one set point to the next set point Rate is based on the probe and on the units of SCALE set up for the probe in the menu When setting or examining the rate nnn n represents units per minute Units may be deg F C or K Restrictions Remote only see SET SEGment in this section for front panel equivalent Your system dynamics will limit the maximum ramping rate See Also SET WAIT Example If SCALE for the probe is in deg C RATE 10 0 set ramping rate for 10 0 deg C minute RATE examine present ramping rate 10 0 controller response 10 0 deg C min TEMP read present temperature 25 0 controller response for example 25 0 deg C SET 35 0 set new set point for example 35 deg C after waiting 30 seconds TEMP read present temperature 30 0 controller response up 5 deg C in one half minute PC100 Manual ver 0709 RTL Function RS 232 Command to unlock local keyboard Syntax RTL Description The Return to Local RTL command may be issued from a host processor to
58. obe temperature the controller will ramp the temperature to 12 5 deg at a rate of 20 deg per minute Once the probe temperature is within 1 0 deg of the set temperature the unit will begin counting down the 3 minute wait time When the wait time reaches zero the time out LED will blink and the buzzer will beep The PC100 will then begin its ramp to 55 2 deg After the 4 and one half minute wait at 55 2 deg the program will loop back to the beginning and repeat the process described above The program will loop 5 times as directed by the FOR NEXT commands At any time while the program is running you may suspend program execution by pressing the HOLD key ENTER key and then resume from the hold by just pressing the HOLD key ENTER key Again the program may also be stopped by pressing the STOP and ENTER key PC100 Manual ver 0709 So now we have our local program but let us assume that we now want to do a few more things First we want the process to be at 30 deg for 1 minute before we start the cycling Secondly we want the process temperature to stay at 30 deg after the cycling until we manually stop it Let us edit the program as follows lt shift gt EDIT 2 ENTER Edit program 2 FORIO 0 5 the first line of the prog is displayed SET SEG ENTER we will store a new segment before the first line Answer the prompts 30 ENTER ramp at 30 deg per minute 1 ENTER wait for 1 minute 30 ENTER set for 30 deg Now use the red DOWN arrow to move to the las
59. orithm which controls the cooling process PID coefficients may be changed to accommodate varying changes in your system The PID Application note contains a procedure for tuning PID coefficients to a particular application Contact Sun for this Application note PID coefficients are stored in battery backed memory Restrictions Remote command only To change PIDs from the front panel the MENU must be accessed See Also PIDH PWMP Example PIDC 0 5 0 25 le 3 set PID coefficients PIDC examine PID coefficients 0 50 controller response P 0 25 controller response I 0 001 controller response D PC100 Manual ver 0709 61 62 PIDH Function Set or examine PID coefficients for heat control Syntax PIDH nnn n nnn n nnn n set heat PID coefficients PIDH examine heat PID coefficients Description The PIDH command permits modification and examination of the proportional integral and derivative PID coefficients used in the algorithm which controls the heating process PID coefficients may be changed to accommodate varying changes in your system The PID Application note contains a procedure for tuning PID coefficients to a particular application Contact Sun for this Application note PID coefficients are stored in battery backed memory Restrictions Remote command only To change PIDs from the front panel the MENU must be accessed See Also PIDC PWMP Example PIDH 0 5 0 25 1le 3 set PID coefficients PIDH
60. ote BKPNTC command is received BKPNT nn displays the value nn and BKPNT Im displays the value of Im when encountered during local program execution The remote BKPNT command is provided so that the host computer may determine the breakpoint value after receiving a breakpoint interrupt EDIT n EDIT local program n where n 0 to 9 RUN n RUN local program n where n 0 to 9 RUN n TIME hh mm ss RUN program n at time of day STOP Terminate a running LP or STOP an EDIT session DEL n DELETE LINE currently being displayed if in local program edit mode If not in local program edit 6699 mode used to delete the local program n BKPNT nnn BREAKPOINT suspends program operation displays Integer Bkpnt nnn value and generates an interrupt if enabled BKPNT Im BREAKPOINT suspends program operations displays current Im value and generates an interrupt if enabled PC100 Manual ver 0709 29 30 FORIm m 0 thru 9 starting integer value ending integer value GOSUB n NEXT Im END LIST n STORE n FOR statement marks the beginning of a loop Note that there is a comma after the FOR Im and not an as in normal for next loop programming This is due to the fact that there is no on the PC100 front panel keyboard The Im variable is either incremented default or decremented from the starting integer to
61. probe readings The next two prompts define the upper and lower chart values The prompt LOW CHART VALUE also displays the present setting of the low chart value To change the value simply enter the number The same is done for the next prompt HIGH CHART VALUE For a complete description on connecting a chart recorder see Section 6 PC100 Manual ver 0709 23 24 Answering NO to the CHART TEMP prompt will cause the OUTPUT PID prompt to be displayed This would be enabled when analog control is desired This will cause the PID loop control to be output in one of four different modes Both of these items the chart output and the PID output utilize the same analog port D A A Therefore only one of these can be enabled at a time If you answer YES to the OUTPUT PID you will be prompted with WHICH MODE 0 3 The four modes are described below Mode 0 OV full cool 2 5V off 5V full heat Mode 1 OV heat off 5V full heat Mode 2 OV cool off 5V full cool Mode 3 OV off 5V full heat cool If the process should be heating the D A output is for heat control and Bit I O bit 4 will be high If the process should be cooling the D A output is for cool control and Bit I O bit 4 will be low Bit I O and the D A output are fully discussed in Section 8 DISABLE INTS DISABLE INTERRUPTS Answering YES to this menu item will disable the following remote interrupts single timeout deviation local program timeout local progr
62. rams may be entered into the Model PC100 either from the local control panel or from either the GPIB or RS 232 422 interfaces The unit provides 10 global integer variables designated by the letter T The T variable may be used in 1 a FORIn NEXTIn statements for multiple pass loops 2 IN and OUT instructions for communication with Model PC100 I O interfaces and 3 arithmetic expressions containing additions and subtractions The END instruction designates the end of the program The STOP command is used to terminate the edit mode from the front panel A program is entered into the unit locally from the front panel by using the EDIT function The program may also be downloaded from a remote interface using the STORE command Command DEL permits deleting program lines during local program edit DEL n deletes the local program n when not in the local program edit mode A program is executed using the RUN n command or the RUN n TIME menu item or command and can be prematurely terminated with the STOP command Debug assistance and host computer synchronization is provided with the BKPNT nn or BKPNT Im commands and the breakpoint interrupts The commands permit the operator to place breakpoints in the program to suspend program execution The interrupts are provided to inform the host computer that a breakpoint has occurred The program will remain suspended until the enter key is depressed on the local control panel or untila rem
63. reset the controller to factory default settings stored in the new EPROM and reboot the controller PC100 Manual ver 0709 85 86 190001 190002 190003 190004 190006 190008 190009 190010 13 REPLACEMENT PARTS 3 Wire RTD Probe 100 C to 300 C 3926 3 Wire RTD Probe 100 C to 300 C 3850 2 Wire RTD Probe 100 C to 300 C 3926 2 Wire RTD Probe 100 C to 300 C 3850 Solid State Probe J Thermocouple 36 K Thermocouple 36 T Thermocouple 36 PC100 Manual ver 0709 14 ERROR CODES SRO OVERFLOW This message is just to inform you that an interrupt has not been serviced and can be ignored without causing any problem For further reference see Section 1 GPIB IEEE 488 REMOTE CONTROL PC100 Manual ver 0709 87
64. return if sent will be ignored Data sent by the PC100 to the bus controller will be ASCII characters terminated with carriage return then line feed with EOI set If any interrupts are enabled and the GPIB remote is active and an interrupt occurs the SRQ line will be asserted on the bus The system controller can then perform a serial poll or parallel poll if enabled in the PC100 MENU to service the PC100 Manual ver 0709 17 18 interrupt If you chose not to service the PC100 interrupts the PC100 will display a SRQ OVERFLOW message The message is just to inform you that an interrupt has not been serviced and can be ignored without causing any problem Since the PC100 has built in deviation limit upper and lower limit checking and wait at temperature timing itis suggested that the system programmer use these features rather than constantly reading the probe temperature and duplicating those functions in the bus controller software Some example GPIB programs are supplied on the floppy disk see PC1_GPIB Since there are so many different manufactures of GPIB computers or interface cards each with its own software particulars we are not able to provide examples for all possible platforms but the examples provided should be instructive PC100 Manual ver 0709 2 FRONT PANEL DESCRIPTION LCD DISPLAY The LCD display on the PC100 is a two line 32 character display When not in the MENU line one displays the present temperature reading from
65. s program number two when not in EDIT mode DELP2 When sent remotely program 2 will be deleted See Also STORE PC100 Manual ver 0709 49 50 DEVL Function Set or examine the deviation limit Syntax DEVL nnn n Set deviation limit DEVL Examine deviation limit Description The DEVL command sets the deviation limits for the probe If the deviation limit interrupt is enabled with the SINT remote command or from the MENU and the probe temperature varies by more than the set limit an interrupt will be generated to the active remote interface Restrictions Remote command only MENU must be accessed to set the deviation limit from the front panel Deviation Limit range is between 0 1 and 300 See Also UTL LTL SINT Example if SCALE C DEVL 2 5 set deviation limit to 2 5 deg C DEVL examine deviation limit 29 controller response 2 5 deg C RATE 30 define temp segment WAIT 03 00 00 wait for 3 hours SET 55 0 set final temp to 55 0 deg C if after 1 hour the tempera ture starts to rise and if deviation interrupts are enabled a deviation interrupt will be sent to the active remote inter face PC100 Manual ver 0709 EDIT Function Edit local program from the local keyboard Syntax EDITn where n 0 9 Description The EDIT command allows for program loading and editing from the local keyboard The PC100 allows up to ten local programs The local programs may be edited by using the up and down arrows del
66. t line of the program the END line END the END is displayed SET SEG ENTER we will store another segment before the END command Answer the prompts 30 ENTER rate equals 30 deg per minute 99 59 59 ENTER wait for about 100 hours 30 ENTER set for 30 deg STOP ENTER end edit Now when the program runs the process will go to 30 deg for 1 minute Then the 5 cycles will be done and then it will go to 30 deg and stay there for 100 hours You will use the STOP key to manually terminate the 100 hour 30 deg soak whenever you wish At this point you may wish to experiment with some of the other local program commands such as the GOSUB FOR NEXT loops within FOR NEXT loops BKPNT commands IN commands that read process bit on off inputs into I variables etc GPIB IEEE 488 REMOTE CONTROL SUN SYSTEMS has been producing GPIB remote controllable process controllers since 1978 Over the years hundreds of instruments have come on the market that provide a GPIB remote port from power supplies to network analyzers Due to its enhanced capabili ties over RS232 422 and wide spread acceptance GPIB remote control is the preferred interface for ATE systems The PC100 GPIB interface supports TALK and LISTEN as well as SERIAL and PARALLEL POLLING The PC100 s GPIB device address is set up in the front panel MENU To send a command to the PC100 you will send the ASCII string for the command as given in this manual witha line feed and or EOI terminator a carriage
67. tain the set temperature after the probe temperature is within the value specified in AT SET TRIGGER variable set in the menu Once the wait period begins the wait time continues regardless of changes in probe temperature Whenrunning a local program the next command in the program is executed after the wait period is timed out In single temperature mode the controller continues to maintain the set temperature after the wait period timeout During the wait period examination of WAIT returns the time remaining in the wait period After the end of a wait timeout the WAIT is reset to FOREVER For best operation the temperature segment should be entered RATE WAIT then SET Restrictions Remote only See SET SEG SET SEGment in this section for front panel control equivalent Range from 99 59 59 to 00 00 01 See Also SET RATE M Example RATE 10 define temperature segment rate 10 deg C min WAIT 00 10 30 wait 10 min 30 sec TEMP examine current temperature 25 0 controller response 25 0 deg C SET 35 0 set new temperature 35 deg C after 1 minute set temperature is reached wait period begins after 1 more minute WAIT examine wait setting 00 09 30 controller response 9 min 30 sec remaining PC100 Manual ver 0709 10 MODEL TC01 COMPATIBILITY COMMANDS The Model PC100 provides limited upwards compatibility with our Model TCO1 temperature controller as described below Consult your TCO1 manual for a complete defini
68. tax SCALE examine probe scale Description The SCALE command allows a remote interface to examine the present scale of units for the probe The scale of units for the probe is set in the MENU Restrictions Remote interface command only See Also MENU Example SCALE examine probe scale DEG C controller response degrees Centigrade SDEF Function Set or examine some of the default parameters Syntax SDEF xxxxx Sets SDEF parameters where x is Y or N SDEF Examines the SDEF parameters by returning a 5 character string Y RS echo is on Y chart temp where position 1 2 3 Y DTR CTS enabled 4 5 Y output PIDs to D A Y buzzer on v Description The SDEF allows for setting orexamining several ofthe default settings for the PC100 over the remote bus Restrictions Remote command only PC100 Manual ver 0709 69 SET Function Set or examine temperature segment final temperature Syntax SET nnn n Set segment final temperature SET Examine segment final temperature Description The SET command allows for setting or examining the final temperature within a temperature segment The temperature segment consists of the change of temperature defined by the RATE command from the present temperature to the temperature defined by the SET command plus the time specified by the WAIT command to soak at the temperature defined by the SET command The units accepted by the SET command are those chosen in
69. the endinginteger FOR statements may be nested 4 deep 66 99 Call program n as a subroutine nest 4 deep NEXTIm marks the end of the for next loop End of program statement List program n to a remote interface Store to program n from a remote interface 6699 Program n must be empty before storing is allowed PC100 Manual ver 0709 5 REMOTE CONTROL GPIB and RS232 and RS422 RS 232 SERIAL PORT PROTOCOLS The serial port s operation depends on whether CMD ERROR INT S are enabled or disabled via the SINT remote command The MENU item ENABLE INTS only enables or disables all of the interrupts For total control of the RS interrupts the remote SINT command should be used See the full description of the SINT command in Detailed Command Descriptions If command error interrupts are disabled no indication to the host computer communicating to the serial interface is given as to whether a command was accepted or rejected To determine last command status the command may be used If command error interrupts are enabled the controller responds with a message if the command received was rejected If the command was accepted and the type of command does not invoke a reply i e such as a SET nnn n command the controller will reply with an OK message If the accepted command invokes a reply then the reply is sent without the OK message The CMD ERROR INT ENABLED mode is convenient since ever
70. the menu For best results a temperature segment should be entered as RATE WAIT then SET Restrictions Remote only see SET SEGment in this section for front panel equivalent The value set by the SET command must range between the values set for the LTL and UTL commands See Also RATE WAIT LTL UTL Example If SCALE for the probe is in deg C RATE 10 0 set ramping rate for 10 0 deg C minute WAIT 5 set wait 5 minutes TEMP read present temperature 25 0 controller response for example 25 0 deg C SET 35 0 set new set point for example 35 deg C SET examine present set temp 35 0 controller response after waiting 30 seconds TEMP read present temperature 30 0 controller response up 5 deg C in one half minute PC100 Manual ver 0709 SET SEGMENT Function Allows the user to set the RATE WAIT and SET values Syntax lt SHIFT gt SET SEG Description Allows for easy entry of the RATE WAIT and SET values When the command is entered the controller responds on the display with the current settings and prompts for new values The user must then only enter the value desired using the numeric keys or just enter for no change Restrictions Front Panel Operation only See Also SET WAIT RATE PC100 Manual ver 0709 71 72 SINT Function Set or examine interrupt parameters Syntax SINT xxxxxxxxxxn Sets interrupt parameters where x is Y or N and nis a digit from 0 8 SINT Examines interrupt parameters
71. the top terminal and NEUTRAL to the lower terminal Along the top edge of the board is provided wire screw headers for the 8 process control outputs Figure 4 provides the schematic of the process I O board As can be seen the outputs start with bit 0 on the top left and run to bit 7 at the top right Each output consists of two terminal positions a 12 volt supply at left and the open collector output Note that the process outputs can not drive line powered loads directly Itis mandatory to use a relay between the I O board and your heater cool valve etc The most commonly used power driver for powering heaters or valves etc is a solid state relay module They are available in a multitude of voltage and current capacities that are easy to use and very reliable They are controlled by a 3 to 32 volt control signal provided by I O board and typically control a 110 240 VAC load The line side is isolated from the control side via its internal optical isolator and the line side turns on at line zero voltage crossings to minimize electrical noise To connect a process control output bit to a solid state relay SSR PC100 Manual ver 0709 simply connect the 12 volt output to the relay positive input and connect the open collector bit output to the SSR minus terminal The SSR should be mounted to a metal panel in your equipment for heat sinking If you require an analog voltage for control of your process load such as a phase controller then analog ou
72. tion of these commands nnn nC Set Temperature deg C C Examine Temperature deg C nnn nM Set Time at Temperature Wait time minutes M Examine Time at Temperature minutes T Examine Temperature in deg C always nnnUTL Set Upper Temperature Limit deg C UTL Examine Upper Temperature Limit deg C ISSS SSS Transfer String sss sss received from GPIB to R 232 422 interface S Transfer next string received from RS232 422 interface to GPIB PC100 Manual ver 0709 81 82 11 SPECIFICATIONS Power Requirements Mechanical Package Temperature Set Point Range Time at Temperature Range Temperature Ramping Rate Control Programmable Set Temps and Times Absolute Error Long Term Stability per month Temperature Resolution Line Voltage Sensitivity Local Junction Compensation Programmable Temperature Loop Control Temperature Control Technique Local Operation Remote Operation Additional I O Capability Power consumption 35 W Voltage 110 220 240 Frequency 50 60 Hz 1 4 DIN x 6 0 Deep Full range of probe selected 1 0 sec to 99 hr 59 min 59 sec or continuous Locally controlled from 1 deg C min up to the heat cool rate of change of the system Number of set temperatures and set times limited only by available program memory but typically 100 segments 25 deg C not including probe error 2 deg C 02 deg C 1 deg C for a 10 line voltage change 05 deg C deg C 5 deg C to 45 deg
73. to a standard using the PC100 Manual ver 0709 standard readings of 20 and 120 deg C The probe and standard must first be placed in a substance or area that is 20 deg C and let stabilize If the PC100 is being used to control a temperature chamber the chamber itself should be used as the area that is at 20 deg C With the standard probe and the PC100 probe very close together enter SET 20 and WAIT 00 15 00 into the unit After the wait time times out perform the procedure listed below The controller will still control to the set temperature while in the MENU as described below Controller User Input lt SHIFT gt MENU Enter Menu yes Cal to Stand yes Enter Cal Access Code 9 Clear Std Cal yes Temperature 1 yes Enter Temp 1 enter reading from your standard Modify Scale no Exit Menu yes Now place the probe and standard in a substance or area that is 120 deg Cand let stabilize If the PC100 is controlling a temperature chamber enter SET 120 and WAIT 00 15 00 into the unit and wait for the timeout to occur before proceeding Enter Menu Cal to Stand Enter Cal Access Code Clear Std Cal Temperature 1 Temperature 2 Enter Temp 2 Exit Menu MODIFY SCALE lt SHIFT gt MENU yes yes 9 no no yes reading from standard yes Allows changing of the temperature scale to deg C F or K CHART TEMP CHART TEMP AND OUTPUT PIDS Answering YES to this prompt will enable the 0 5 V chart output of the
74. tput D A B can be configured for PID output in the PC100 MENU see MENU section An example hookup of the process I O board to a temperature chamber is shown in figure 5 O O A A DRILL 4 A HOLES 089 DIA THEN TAP 4 40 3 0000 3 7000 Fig 3 Fixing Details For The Process I O Board PC100 Manual ver 0709 11 FAILSAFE INPUT 1 B T E Es TT TT HT HS C7 CD O CD O O CO Gl OC OCO CD O C EE 2468111118 20 PIN IDC 12579 b678 S LCT LL L D A A OUTPUT ANO INPUT G2 INPUT Gi INPUT Z vay c2 LM7812 XL RAW DC TO PC10O sie 2700uF TRANSFORMER LINE VOLTAGE SELECTOR SWITCH Swi 110 gt 110 POSITION POWER LINE INPUT LINE 1 CHOT 1A FAST LINE 2 SUN ELECTRONIC SYSTEMS Inc Fig 4 Process I O Board Schematic PC100 Manual ver 0709 12 110 VAC SPST RELAY HEATER AC HOT AC NEUTRAL Solid Sate Relay Solid Sate Relay Solid Sate Relay deeeeleeeeee B L e Pe FAILSAFE BIMETAL FAILSAFE CLOSE ON RISE N O K IR RRR RRR R C GND XI L LINE SELECT 1 q lt gt na n 1777 asi RiT k PS LINE TRANSFORNER TAMURA F D 5 AC NEUTRAL 840065 REV Fig 5 Example Hookup of Process I O Board to Chamber PC100 Manual ver 0709 13 Also available on the I O board see figure 4 is another 8 position connector
75. u have typed when communicating to the PC100 from a dumb terminal RS DTR CTS ON Answering yes will enable hardware handshake for the RS232 The PC100 will wait for Clear To Send CTS before transmitting and will drop Data Terminal Ready DTR when itis busy If you are in RS422 serial port mode this prompt will not be given and this function will be set to OFF DEVIATION LIMIT This item allows setting and examining of the deviation limit The range is between O1 and 300 If the deviation limit interrupt is enabled and the probe temperature varies by more than or the set limit an interrupt will be generated See Section 5 D Remote Interrupt Characters LOW TEMP LIMIT The lower temperature limit can be changed and examined with this menu item The temperature is entered in the current temperature scale Temperature SET points can not be made lower than the lower temperature limit In addition an interrupt will be generated to the active remote device if the lower temperature limit is exceeded Ifthe probe reading is less than the lower temperature limit the controller will automatically turn off the COOL ENABLE output HIGH TEMP LIMIT The upper temperature limit can be changed and examined with this menu item The temperature is entered in the current temperature scale Temperature SET points can not be made higher than the upper temperature limit In addition an interrupt will be generated to PC100 Manual ver 0709 25
76. u item enables the automatic boost cool output control feature When enabled Process output bit 3 acts as the control for a boost cooling valve Boost cooling is used on some closed cycle refrigerated temperature chambers P H P COEFFICIENT FOR HEAT This menu item allows examination modification of the Proportional coefficient of the PID coefficients for heating Factory Default 250 IH I COEFFICIENT FOR HEAT This menuitem allows examination modification of the Integral coefficient of the PID coefficients for heating Factory Default 001 D H D COEFFICIENT FOR HEAT This menu item allows examination modification of the Derivative coefficient of the PID coefficients for heating Factory Default 1 P C P COEFFICIENT FOR COOL This menu item allows examination modification of the Proportional coefficient of the PID coefficients for cooling Factory Default 25 I C I COEFFICIENT FOR COOL This menuitem allows examination modification of the Integral coefficient of the PID coefficients for cooling Factory Default 001 PC100 Manual ver 0709 27 28 D C D COEFFICIENT FOR COOL This menu item allows examination modification of the Derivative coefficient of the PID coefficients for cooling Factory Default 1 PC100 Manual ver 0709 4 LOCAL PROGRAMMING The Model PC100 provides commands to control the flow of local programs which permit automatic test operation by the controller Ten local prog
77. y command sent to the controller generates a reply back to the host computer thereby providing a handshake The RS port operating parameters are set up in the MENU The MENU allows setting of the BAUD RATE ECHO on off and whether to use hardware handshake The serial port sends a zero for the parity bit and does not check incoming parity When DTR CTS is not selected only the TRAN DATA REC DATA and GROUND signal lines are significant to the controller RS232 CABLE WIRING DIAGRAM FOR PC100 To communicate over the RS232 bus acable constructed with a male DB9 connector on the PC100 controller and a female DB9 connector on PC end and wired as follows is re quired PC100 CONTROLLER DB9 Male COMPUTER DB9 Female pin pin 3 TxD RxD 2 2 RxD TxD 3 5 GND GND 5 To communicate through Windows HyperTerminal use the following settings Connect using desired COM port Bits per second 9600 default setting in PC100 MENU Data bits 8 Parity NONE Stop bits 1 Flow Control NONE PC100 Manual ver 0709 31 32 If your computer is using a DB25 Male connector instead of the DB9 the wiring connec tions are as follows For example purposes this diagram also assumes DTR CTS control is selected PC100 DB9 Male COMPUTER DB25 Female Pin Pin 3 TxD RxD 3 2 RxD TxD 2 8 CTS DTR 20 V DCD 8 oe DSR 6 4 DTR CTS 5 5 GND GND 7 NOTE CTS amp DTR are Optional If selected in M

Download Pdf Manuals

image

Related Search

Related Contents

MANUAL DE USUARIO PARA EL SISTEMA DE  HE-760 - Commell  WARNING! - JT SplatMaster  膜厚計SWTシリーズ 8000Ⅱ.8100Ⅱ.8200Ⅱ.8300Ⅱ  Manuel d`utilisation  Nissan Qashqai (J11) 01/2014-  Texas Instruments TravelMate 2000 User's Manual  Quasar VHQ730 User's Manual  取扱説明書  Manual de instruções - equipamentos.cdr - E  