         Contents
1.       NIVCEO     P EM UF E  351 uU MAL    NUPS22 6000U 10000U  Rack Tower Online UPS    Uninterruptible Power Supply System    Version  1 2       Please comply with all warnings and  operating instructions in this manual  strictly  Save this manual properly and  read carefully the following instructions  before installing the unit  Do not operate  this unit before reading through all safety  information and operating instructions    carefully     Table of Contents    1  Safety and EMC instructions                  eere nennen nnn 4  1 1  Transportation and Storage                     eere nnm 4  1 2  PrebDatatolasesnesiused x epa RE UV aa V AO CR AE LT AL LA AE A RA 4  EAE E E SIN el LL LIU DETTO 4  1 4  A connecion WarniNgS et E EA 5    25  OPEO inna 5  1 6  Stendal dS ssrareri aE anea N O RU dp ETO 6  2  NStala UO Maene a a aa an 7  2 1 packing and  INSPEC ed vlde hast vata VE ELO Orr G6s 7  2 2  Rear Panel VIEW sicco osx an cx RR US RE VER EMPXUNERN IVA MER DNO ERN NS OE ROMAE 7  2 3  RACK  LOWER InstallatlODizuausiekE ee eviaad i bepRi DEN emis a dan verb Pacis dia Fe digi e 9  2 4  Single UPS Installation                                eeeeeeeneer nnne 10  2 5  Parallel UPS  Thstallatloliassesesvba cre E ips ace e t Fu RR TDPEF VE MEE aM EN bMS 11  CM OPEra RN T m ILLNM 12  3 1  Operating Mode Status Description                       eennnnnne 12  3 2 BUttOn  ODebatlOD essa dsfusez ave dcus Scusa ha a fa ti ated tus s 12  9 3  EEDAIBOIICOEOES a ensiac  kr toned Doecdar d
2.     AN Ensure that no liquid or other foreign objects can enter into the UPS system     The UPS can be operated by any individuals with no previous experience     1 6  Standards      Safety  IEC EN 62040 1    EMI    Category C3  Category C3    Warning  This is a product for commercial and industrial application in the  second environment installation restrictions or additional measures may be  needed to prevent disturbances        2  Installation      Please refer to the following model table   Type    6000U Standard model 6KVA  10000U   Standard model 10KVA       2 1  Unpacking and Inspection    Unpack the package and check the package contents  The shipping package contains    e One UPS   e One user manual   e One monitoring software CD   e One RS 232 cable  option    e One USB cable   e One parallel cable and one share current cable  option    e One battery cable  option    e Two sets of tower stands including feet and extensions   e Mounting ears  NOTE  Before installation  please inspect the unit  Be sure that nothing inside the package is damaged during  transportation  Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or  lacking of some parts  Please keep the original package in a safe place for future use     2 2  Rear Panel View       Diagram 2  6KVA 10KVA Input Output Terminal    Eo me IP Or prm e DX       Q Lm LR oL LR LR  un BR c N e Oo       Diagram 3  Battery Pack Rear Panel    RS 232 communication port   USB communica
3.     e This UPS should be connected with TN earthing system     e The power supply for this unit must be single phase rated in accordance with the equipment nameplate  It  also must be suitably grounded    e Use of this equipment in life support applications where failure of this equipment can reasonably be  expected to cause the failure of the life support equipment or to significantly affect its safety or  effectiveness is not recommended  Do not use this equipment in the presence of a flammable anesthetic  mixture with air  oxygen or nitrous oxide     e Connect your UPS power module s grounding terminal to a grounding electrode conductor     e The UPS is connected to a DC energy source  battery   The output terminals may be live when the UPS is  not connected to an AC supply     Before working on this circuit    Isolate Uninterruptible Power System  UPS     Then check for Hazardous Voltage between all  terminals including the protective earth     AN Risk of Voltage Backfeed       1 5  Operation    AN Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any    time since this would cancel the protective earth of the UPS system and of all connected loads     If the external battery cabinet is connected  the UPS output Anderson connector may be  electrically live even if the UPS system is not connected to the building wiring outlet     In order to fully disconnect the UPS system  first press the  OFF  button and then disconnect the  mains 
4.    gt DisChg Protect   Fnable  990 Minute  Batt Test Type   Short Time   10 Minute       1  Dischg Protect    1 1   Enable  Battery discharge protection function is enabled  When UPS  have been continuously working in    battery battery test mode     the  UPS will automatically shut down when the running time set by option  1 2 below is up    Disable  Battery discharge protection function is disabled    1 2   0000 1500  The maximum discharge time ranging from O to  1500mins  UPS will shut down to protect battery after backup time  arrives when the    Dischg Protect    is enabled  If    Dischg protect    is    disabled  then this setting does not make sense whatever the setting   is  The default value for this setting is 990mins    2  Batt Test Type    2 1 Short Time  Battery test will last for 10 seconds    2 2 Long Time  Battery test could last for longer time  which is able  to be adjusted within 01 99 minutes     2 3 Till Batt Low  Battery test will not stop until battery voltage is    low     Battery         gt DisChg Protect   Fnable  990 Minute  Batt Test Type   Short Time   10 Second       5  Calibration    1  Batt  Calibrate the battery voltage measurement  Calibration  range is from OV to 5 7V  The default value is OV  It is available on  all operation modes       Batrs X0 TU   Inv  Adjust the inverter output voltage  the adjustable range is  Inv  209 0  0     from OV to 6 4V  the default value is OV  It is only available in line     battery   converter mode      Chg
5.   2  Press the  ON ENTER  button to start up the internal power  the UPS will enter into bypass mode  without output     3  When LCD is on home page  press the  ON ENTER  button  LCD will show a prompt page of  Turn  On   Move the arrow to    Yes    by up or down button  then press  ON ENTER   the UPS will be starting  up with beeping once  You could also enter the  control menu    to select the instruction  Turn On  to  startup the UPS  Please refer to the section of  LCD operation      4  A few seconds later  the UPS will enter into Battery mode     Battery mode  will be displayed on LCD   In Battery mode  it will shutdown automatically when battery is depleted  If the utility power is restored   it will auto restart to Line mode      3 5 3  Connect devices to UPS  After the UPS is turned on  you can connect devices  load  to the UPS     1  Turn on the UPS first and then switch on the devices one by one  the LCD panel will display total load  level     2  Ifinductive loads needed to be connected  such as a printer  the in rush current should be calculated  carefully to see if capacity of the UPS can cover due to the huge starting power consumption of this  kind of load     3  Ifthe UPS is overload  the buzzer will beep twice every second     4  When the UPS is overload  please remove some loads immediately  It is recommended to have the  total loads connected to the UPS less than 80  of its nominal power capacity for system safety     5  If the overload time is over duratio
6.   Adjust the Charger output voltage  the adjustable value is  from OV to 6 9V  the default value is OV  It is only available in  bypass   line   ECO  converter mode     NOTE  Before making charger output voltage adjustment  be  sure to disconnect all batteries first to get the accurate charger  voltage  Be careful that the adjustment should be suitable to  battery specifications  or the battery maybe destroyed       6  Other settings  available on all operation modes     Others  Hot standby     Enable  Hot standby function is enabled  It means that the current  UPS is set to be host of hot standby system  and it will automatically      gt Hot Standby restart after AC recovery even without battery connected   Disable  Hot standby function is disabled  The UPS is running at  normal mode and can t restart without battery   Disable is default setting     Calibration     Chg        Backup Time       Hot Standby          Status  Disable    Others     Hot Standby      gt Backup Time    Backup Time         gt Batt Groups     Batt Cap   Factor     1  9AH  1 0    Backup Time Parameters Setting    Batt Groups  Set the number of battery group ranging from 1 to 6   The default value is 1 group    Batt Cap  Set the battery capacity such as 7AH  9AH  10AH  12AH   17AH  26AH  40AH  65AH  100AH and so on  The default value is 9AH   Factor  Calibrate the displayed backup time by adjusting this  multiplier factor  The formulation is listed below     Displayed backup time  Original calculated ba
7.   Forbid range is from  Rated Output Volt  11V  to 276V and the default  value is 264V   264V   LowLoss V  Set the acceptable low voltage for bypass  Setting  Dac range is from 110V to  Rated Output Volt   11V  and the default  LowLoss V  l110V value is 110V   HighLoss F  54Hz   HighLoss F  Set the acceptable high frequency for bypass   iHz 50 Hz  Setting range is from 51Hz to 54 Hz   60 Hz  Setting range is from 61Hz to 64Hz   The default value is 54 0Hz 64 0Hz     LowLoss F  Set the acceptable high frequency for bypass   50 Hz system  Setting range is from 46 0Hz to 49 0Hz   60 Hz system  Setting range is from 56 0Hz to 59 0Hz   The default value is 46Hz 56Hz     2  ECO setting  only available or effective on bypass mode       Status  Enable  Enable ECO Function  Disable  Disable ECO Function  ECO  If ECO function is disabled  voltage range and frequency range for  ECO mode still can be set  but it is meaningless unless the ECO  Saatte     UNE function is enabled   Cs ee MN Co DR   HighLoss V  High voltage point in ECO mode  The setting range  HighLoss V  232V is from  5  to  10  of the nominal voltage   LowLoss V   184V   LowLoss V  Low voltage point in ECO mode  The setting range is  HighLoss F   52Hz from  5  to  10  of the nominal voltage   Lewloss Be HB   HighLoss F  Set low frequency point for ECO mode   50 Hz system  Setting range is from 46Hz to 48Hz   60 Hz system  Setting range is from 56Hz to 58Hz   The default value is 48Hz 58Hz   LowLoss F  Set high frequency p
8.   lllProduct specifications are subject to change without further notice     
9.  Shut down and restart the  because of mains input or load system to see if it happens  transient current  again    2  The internal converter failed  2  Contact the dealer to repair     Fault 03  Bus Under The internal converter failed  so the   Contact the dealer to repair   DC bus voltage is too low           04  Bus Unbalance 1  The load is special or abnormal    Contact the dealer   so the internal positive and    negative DC bus voltages are  unbalanced   2  The internal converter failed     Fault 11  Inv Start Fail The internal inverter failed  so the   Contact the dealer to repair   inverter voltage could not start up  correctl       inverter voltage is too high   inverter voltage is too low   output     Fault 1A  NegPower UPS output power is negative  It   Contact the dealer   means there is energy feedback  into the internal of UPS from  output  It may be caused by  regenerative load or current control  failure in the parallel system     and short   Fault 24  Inv Rly Short The internal inverter relay is stick to   Contact the dealer to repair   ee oa  Transfer Switch  is short   Fault 35  Para Comm Fail   Parallel cable for communication is   Connect the parallel cable well   not connected well in the parallel  system     Fault 36  OP I Unbalance   The output current is extremely   Contact the dealer to repair   unbalanced between the paralleled   UPSs or there is an error in the   parallel system     Fault 41  Over Temp The internal temperature is too   1  Make sure
10.  device is protection device   open     Warning 07  Over Charge Battery numbers and setting Correct the battery number  are not matching  or its setting   Charger voltage is too high or Disconnect the battery and  charger failure  check the charger output  voltage  Then  contact the  dealer to repair     Warning 08  Batt Low 1  Battery is discharged deeply to   1  Recharge the battery   low level  2  Correct the battery number   2  Battery number is not correct    3  Replace the battery   3  Battery is in the end of life     09  Over load The load is too heavy  Remove excess loads from UPS  output     Warning OA  Fan Error 1  Fan is blocked  1  Make sure fan is  2  Fan is in the end of life  blocked   3  Fan detection circuit failed  2  Contact the dealer to replace  the fan   3  Contact the dealer to repair     Warning OB  EPO Enable EPO plug  jumper  is removed or   Connect the EPO plug  jumper   the external EPO switch is off  well or switch on the external  EPO switch           OE  Charger Fail Charger failed  Contact the dealer for repair     10  IP Fuse Open Input fuse on the power stage   Check and replace the input  board is burnt  fuse     Warning 33  Overload 3Times   Locked in bypass after overload 3   Remove excess loads from UPS  times in 30 minutes  output first  Then  shut down  the UPS and restart it     3A  Maintain Open EMBS port is open or the maintain   If the EMBS port is   switch sensor  connected to EMBS   short circuited  the warning will   port  is tr
11.  menu  to select the instruction   Turn Off  to turn off the UPS  Please refer to the section of  LCD operation      NOTE  Here   Turn Off  means that UPS is not working on line   converter   ECO   battery   battery  test mode  So even though the UPS is turned off  if input or bypass voltage is normal  the internal  power supply will be still working  and if bypass status has been set to  enable   the output voltage of  the UPS will be still exist     2  If you need to fully cut off the output  please switch off the external input breaker  A few seconds later   there is no display shown on the panel and UPS is completely off     3 5 8  Turn off the UPS without utility power supply in Battery mode    1  When LCD is on home page  press the    OFF ESC    button  LCD will show a prompt page of  Turn Off    Move the arrow to    Yes    by up or down button  then press  ON ENTER    the UPS will be turning off to  bypass mode with beeping once  You could also enter the  control menu  to select the instruction   Turn Off  to turn off the UPS  Please refer to the section of  LCD operation      2  If there is no bypass input voltage  the UPS will cut off all power supply and there is no display shown  on the panel     3 5 9  Changing battery quantity  number   The default battery  12V  quantity of this UPS system is 20  for one series   but 18  19 could also be applied in    this system  However  before changing the battery quantity  the UPS should be fully shutdown and the cabinet  cov
12.  the UPS module to the rack with  screws  nuts and washers  user provided  through  its mounting ears and into the rack rails  Please  refer to chart 2     BEBBRBESEBEREBBEESSBSE       2 4  Single UPS Installation    Installation and wiring must be performed in accordance with the local electric laws regulations and execute  the following instructions by professional personnel     1  Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid  the hazards of electric shock or fire     NOTE  Do not use the wall receptacle as the input power source for the UPS  as its rated current is less than  the UPS s maximum input current  Otherwise the receptacle may be burned and destroyed     2  Switch off the mains switch in the building before installation   3  Turn off all the connected devices before connecting to the UPS     4  Prepare wires based on the following table     Wiring spec  AWG   Output Battery    6KVA   10   10   10   10      8           10    10KVA   8   8   8      NOTE 1  The cable for 6KVA should be able to withstand over 40A current  It is recommended to use  10AWG or thicker wire for safety and efficiency   NOTE 2  The cable for 10KVA should be able to withstand over 63A current  It is recommended to use    8AWG or thicker wire for safety and efficiency     NOTE 3  The selections for color of wires should be followed by the local electrical laws and    regulations     AN Warning     e For standard battery pack  there ar
13.  the ambient  high and reach the fault level temperature not over 40  C    shutdown   Make sure the fan is OK   1  Maybe the environment is hot  Make sure ventilation is well   2  Maybe the fan is blocked or Remove some loads if  failed  possible   3  Maybe ventilation is blocked by  the wall or other goods   4  Load is too heavy     between CPUs    Fault 43  Over load Overload time is out of the   Remove excess loads from UPS  specification and the UPS shuts   output and restart it   down automatically               H  CU  Cc  ct    5  Storage and Maintenance    5 1  Storage    Before storing  charge the UPS at least 7 hours  Store the UPS covered and upright in a cool  dry location   During storage  recharge the battery in accordance with the following table     Storage Temperature Recharge Frequency Charging Duration   25  C   40  C Every 3 months 1 2 hours       5 2  Maintenance    AN The UPS system operates with hazardous voltages  Repairs may be carried out only by qualified  maintenance personnel     Even after the unit is disconnected from the mains  components inside the UPS system are still  connected to the battery packs which are potentially dangerous     Before carrying out any kind of service and or maintenance  disconnect the batteries and verify that  no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as  BUS capacitors     Only persons are adequately familiar with batteries and with the required precaution
14. 2 5  Setting  This menu is used to configure the parameter settings or do the calibrations     setting       gt Bypass  ECO  Output    Battery  Calibration  Others       NOTE  Some settings will be only available in some operation modes  If the setting is not available in current  mode  the LCD will show prompt message with    Item can not be set in this mode     Press any button or just  wait for several seconds until this message fades     1  Bypass setting    1  Status  only available in bypass   AC mode   1 1 Open Forbid   Open  Bypass allowed  When selected  UPS will run at Bypass  Bypass  mode depending on bypass enabled disabled setting     Forbid  Bypass not allowed  When selected  it   s not allowed for    l running in Bypass mode under any situations   status    pen 1 2 Enable Disable  Enable This option appears only when Bypass status is set to  Open    HighLoss 264V Enable  Bypass enabled  When selected  Bypass mode is  l   ue activated   LowLoss V  110  Disable  Bypass disabled  When selected  automatic bypass is  HighLoss P  54Hz acceptable  but  manual bypass  is not available   Manual bypass   LowLoss   46Hz means users manually operate UPS to Bypass mode  for example   in AC mode turning off the UPS to Bypass mode   Then  the UPS  will go to bypass mode but without output if it is turned off in AC  mode   Bypass  mE  l NOTE  The following items are only available in bypass mode     HighLoss V  Set the acceptable high voltage for bypass  Setting      gt Status
15. TE  Before executing this action  you must check if the system cables and connections are connected    correctly and safely  Please read the related contents in the section of trouble shooting     Control     Turn On  Batt Test  Mute       gt  Para Unlock    3 7 2 3  Measurement       Is single or  parallel cable OK     Bypass Mode  Parallel Master  IP 208  0V 50  OHz  OP  208  0V 50  OHZ  Batt  273  0V 99   Load  096        gt Yes  No    Measurement displays the measurement value of the parameters such as voltage   current   frequency      power   capacity   time etc  Press  UP  or  DOWN  to explore the pages     220  OV  50  OHz    Output     Volt   Curr   Freq   Inv     Apparent Power        Charger  5 5    Volt  273  OV  Status     Battery     Volt  23  0V   Cap  100    Dischg Time   00 00 00          3 7 2 4  Information  Information displays all parameter setting value and status  Press  UP  or  DOWN  to explore the pages     Bvpass   6 ECO  2 6    Output     Status  Open    Status  Open   Volt  208V  Enable HighLoss V  232V Freq  Auto   HighLoss V  264V LowLoss V  184V   CVCF  Disable   LowLoss V  110V HighLoss F  52Hz   HighLoss F  54Hz LowLoss F  48Hz   LowLoss F  46Hz    Battery  4 6 UPS Info  5 6 Others  6 6    Backup Time  UPS Model   10KL Hot Standbv   990 Miniute   DSP Ver  99 00 Disable   Batt Test Type  MCU Ver  97 00 Bypass Mute   Short Time  Unit Name  Disable   10 Second XXXXXXXXX Batt Mute   Manufacturer  Disable   XXXXXXXXX Fault Mute   Disable       3 7 
16. UPS   2  Battery Test  It is to check if the UPS could work well in battery mode and test the battery performance  This selection will  be displayed under all UPS modes  However  it couldn t execute this test in Battery Fault Eco mode and  reminder will pop up in the screen  When battery test is selected  the screen will return back to home page  with  Battery Test Mode  displayed on top  If the test is completed  the displayed status will change back to  UPS current mode   Control Batt Test Mode  Batt Test      Turn On IP 208  0V 50  OHz  S BEP Tegi OP  208  0V 50  OHz  Mute  gt Yes Batt  245  0V 50     Para Unlock    Load  096  Backup Time  10H       3  Mute  It is to mute the buzzer only when UPS is in battery bypass fault mode  After the selection is confirmed  it  will return back to home page and mute icon will be displayed  Although this selection will display in other    modes  it can t be mute alarm and reminder will pop up at the same time     Control     Turn On  Batt Test    gt  Mute  Para Unlock    4  Para Unlock       ai  x    Battery Mode  Mute      IP  0 0V  0 0Hz  0P 208  0V 50  OHz  Batt  245  0V  50   Load  100   Backup Time  10M        Yes  No    It s to allow UPS startup with parallel function  It only appears when the LCD shows the warning of  3F     Para Protect   It means the parallel system is in protection and could not startup because of parallel    communication failure  Before restart the parallel system  please confirm this selection first     NO
17. UT  Output voltage  AC Voltage Regulation  Frequency Range   Synchronized Range   requency Range  Battery Mode        200V 208 220 230 240VAC    1   46Hz   54 Hz   50Hz system  56Hz   64 Hz   60Hz system  50 Hz   0 1 Hz or 60Hz   0 1 Hz  10090 11090  10min   Line mode 11090713090  imin    gt 130    1sec  10090 11090  30sec   Battery mode 11090 13090  10sec    gt 130    1sec  3 1 max   lt  2    100  Linear Load    lt  4    100  Non linear Load    Overload    i    urrent Crest Ratio    Harmonic Distortion                Line        gt  Battery 0 ms  Transfer  T Inverter amp         Bypass 0 ms  ime  Inverter          ECO  lt 10 ms  EFFICIENCY  Battery Mode       ype  amp  Numbers 12V 7Ah x 20 12V 9 Ah x 20    Recharge Time 7 hours recover to 90  capacity 9 hours recover to 9096 capacity    harging Current  harging Voltage  Type          UPS unit  580X438 X133 UPS unit  668X438 X133         UPS unit  20 UPS unit  23 5  ENVIRONMENT  MANAGEMENT       mart RS 232 or USB Supports Windows    2000 2003 XP Vista 2008  Windows   7  Linux  Unix  and MAC  Optional SNMP Power management from SNMP manager and web browser    If the UPS is in converter mode  the power capacity will be derated to 60  of full capacity     Tf the battery number is 18  the power capacity will be derated to 90   if it is 19  the power capacity will be derated to 95        Tf the UPS is installed or used in a place where the altitude is above than 1000m  the output power must be derated one percent per 100m        
18. ary measures  may replace batteries and supervise operations  Unauthorized persons must be kept well away from the  batteries     Verify that no voltage between the battery terminals and the ground is present before maintenance  or repair  In this product  the battery circuit is not isolated from the input voltage  Hazardous voltages may  occur between the battery terminals and the ground     Batteries may cause electric shock and have a high short circuit current  Please remove all  wristwatches  rings and other metal personal objects before maintenance or repair  and only use tools with  insulated grips and handles for maintaining or repairing     When replace the batteries  install the same number and same type of batteries     Do not attempt to dispose of batteries by burning them  This could cause battery explosion  The  batteries must be rightly deposed according to local regulation     Do not open or destroy batteries  Escaping electrolyte can cause injury to the skin and eyes  Tt may  be toxic     Please replace the fuse only with the same type and amperage in order to avoid fire hazards     AN Do not disassemble the UPS system     6  Specifications                INPUT   110 VAC   3   at 50  Load   Voltage   176 VAC   3   at 100  Load  Range Low Line Loss Voltage   10V   300 VAC   3 96   High Line Loss Voltage   10V       46Hz   54 Hz   50Hz system  56Hz   64 Hz   60Hz system  Single phase with ground    0 99 at 100  Load    Frequency Range    hase  ower Factor  OUTP
19. ation is used to check the battery status     Warning Status If some errors occur in the UPS  but it is still running normally   buzzer will alarm  and warning code will appear in the LCD for trouble shooting     Fault Mode When fatal error occurs in the UPS  it will beep continuously and go to fault mode   It will display fault codes in LCD     3 2  Button Operation                                  LCD panel  A  o e   amp  KZ we 3   SO SO JO                     e LED indicators    3 7                        Buttons     e  e S SS S  ki   v Qa a    There are 4 buttons on front panel    gt  Press this button to turn on the UPS   ON ENTER  gt  Or press it to confirm the selection in the menu      Pressthis button to turn off the UPS   OFF ESC    Or press it to return to last menu     Press this button to select the previous item in the menu   UP Or press this button to jump to previous page in the screen   Or press this button to increase the number in the setting   Press this button to select the next item in the menu   DOWN Or press this button to jump to next page in the screen    Or press this button to decrease the number in the setting   To allow LCD display to rotate 90  automatically  press these two buttons at the   UP   DOWN same time  This operation is used to configure the UPS in rack or tower display     3 3  LED Indicators       There are 4 LEDs on front panel to show the UPS working status        Note      means LED is lit  O means LED is faded      means LED is f
20. ckup time x Multiplier  factor   The value of default factor is 1 0  and it ranges from 0 5 to 2    These parameters are for the battery backup time calculation       3 7 2 6  Alarm page    Alarm Info  Fault    14 0utput Short  Warning    Ol Bat Open       This page records and displays the faults or warning events happened in history     4  Trouble Shooting    4 1  Warning status    When Fault LED flashes and the buzzer beeps once every second  it means that there are some  problems with UPS  Users can see the warning code from LCD panel and refer to the trouble  shooting table to check what problem probably happen     4 2  Fault mode    1  When Fault LED illuminates and the buzzer beeps continuously  it means that there is a fatal error  about UPS  Users can get the fault code from LCD panel  Please refer to the trouble shooting table to  check what problems probably happen     2  Don   t try to turn on the UPS again before the problem is clear  If the problems can t be fixed  please  contact the distributor or service people immediately     3  For emergency case  please cut off the connection from utility  external battery  and output  immediately to avoid more risk or danger     4 3  Trouble shooting table    If the UPS system does not operate correctly  please solve the problem by referring to the table below     LCD display Remedy    Warning 01  Batt Open The battery is not connected   1  Connect the battery well   well  2  Replace or restore the  The battery protection
21. devices or save data  Otherwise  there is a risk of data loss  or load failure     2  In Battery mode  if buzzer sounds annoying  you could enter  Control 2 Mute  on LCD to silence it   Please refer to the section of  LCD operation      3  The backup time of the long run model depends on the external battery capacity   4  The backup time may change under different environment temperature and load type     5  The maximum backup time is limited by default 16 5 hours  After discharging 16 5 hours  UPS will  shut down automatically to protect the battery   The time could be modified through LCD panel or  communication port     3 5 6  Test the batteries    1  If you need to check the battery status or performance when the UPS is running in Line   Converter    ECO mode  you could enter  Control    Batt Test  to instruct the UPS to do battery test  Please refer to  the section of  LCD operation      2  Users also can set battery test through monitoring software     3  Ifthe UPS is in battery testing   Battery test mode  will be displayed on LCD  the buzzer indication  will be the same as Battery mode  but both line LED and battery LED will be lit     3 5 7  Turn off the UPS with utility power supply in Line mode    1  When LCD is on home page  press the  OFF ESC  button  LCD will show a prompt page of  Turn Off      Move the arrow to    Yes    by up or down button  then press  ON ENTER   the UPS will be turning off to  bypass mode with beeping once  You could also enter the  control
22. e one DC breaker to disconnect the battery pack and the UPS  But for  other external battery pack  make sure a DC breaker or other protection device between UPS and external  battery pack is installed  If not  please install it carefully  Switch off the battery breaker before installation     NOTE  Set the battery pack breaker in  OFF  position and then install the battery pack     e Pay highly attention to the rated battery voltage marked on the rear panel  If you want to change the  numbers of the battery pack  please make sure you modify the setting simultaneously  The connection  with wrong battery voltage may cause permanent damage of the UPS  Make sure the voltage of the  battery pack is correct    e Pay highly attention to the polarity marking on external battery connector and make sure the correct  battery polarity is connected  Wrong connection may cause permanent damage of the UPS     e Make sure the protective earth ground wiring is correct  The wire current spec  color  position  connection  and conductance reliability should be checked carefully     e Make sure the utility input  amp  output wiring is correct  The wire current spec  color  position  connection and  conductance reliability should be checked carefully  Make sure the L N site is correct  not reverse and  short circuited     2 5  Parallel UPS Installation    For parallel UPS installation  please contact your dealer for more professional support     3  Operations    3 1  Operating Mode Status Descript
23. er should be removed  and the jumpers on the control board should be re set as below table     Battery Number JP1 on control board     one series  pin1  amp  pin2 pin3  amp  pin4 Pin5  amp  pin6 pin7  amp  ping   18   X   x   0   0         Note  1   insert with jumper  0   no jumper  x   these pins are for other functions   NOTE  This operation should be done by professional technicians  please contact the dealer for support    3 6  Parallel UPS Operation    For parallel UPS operation  please contact your dealer for more professional support     3 7  LCD Operation    The entire LCD structure is demonstrated as diagram below        Turn On          Press button    Enter          Batt Test  Control  e  Press button  Esc Mute    Para Unlock                                     Page 1  Input             Page 2  Output          Press button    Enter             Page 3  Battery       Measurement    Press button    Esc                   Page 4  Bypass                Page 5  Charger          Page 1  Bypass                Page 2  ECO          Press either button    UP    or    DOWN          Press button    Enter       Information      P 3  Output  Main Interface Press button    ESC    age 3  Outpu                         Page 4 Battery                   Page 5  UPS Info                Page 6  Others             Bypass             ECO          Press button    Enter       1 Press button    Esc     mm eg Pres baton    Ese    O       Output                Battery                   Calibrat
24. iaenido yeataan Porra Oba d DUE 0B vies E 13  3 4  Audible ala Mi ssi esas er a x Y HN SA VER ORDRE AEN AUN UR Y RR URL LL UN M 13  3 5  lrigie UPS  ODerdallOllas sisi cia vr ipe YER VER E REIR Edd ER UIS 13  3 6  Parallel UPS Operation                   enne nnn 16  CST ECD OPEO T r a O 17  Ae Ttouble Shootl19 sssini 27  A  te Wanna StatUS neniarn E AEA TAE a 27  2 2  FaU IOC Eeoa ia 27  7 3  Trouble SNOOUNG tables vicia vb a ia beiohs PER s   6 27  5  otorage  and  MalhterariCe   a euxo npa ks x DRUREN EXER OVER TX PARE EUR NUMAE SRI UFBAT RATER EXE 30  SL DUO Ge mec a cei ene ses etn eee 30  3 2  MAINE ANCE ananin nenni an wana a taux Ya Sidi PS Das 30    Os SSC ICAU ONG esis ive TE STEREO 31    1  Safety and EMC instructions    Please read carefully the following user manual and the safety instructions before installing the unit or using  the unit     1 1  Transportation and Storage    AN Please transport the UPS system only in the original package to protect against shock and impact   The UPS must be stored in the room where it is ventilated and dry   1 2  Preparation  AN Condensation may occur if the UPS system is moved directly from cold to warm environment  The  UPS system must be absolutely dry before being installed  Please allow at least two hours for the UPS  system to acclimate the environment   Do not install the UPS system near water or in moist environments   Do not install the UPS system where it would be exposed to direct sunlight or nearby heater   AN Do no
25. igged   The UPS is   disappear    transferred to bypass     3F  Para Protect Parallel cable is still not connected   1  If the system is still needed   well when restart after the parallel to be operated in parallel   system is fault because of parallel mode  please connect the   communication failure   When this parallel cable well  And    warning appeared  the UPS could choose  Para Unlock  in   not start up because it is system control menu to remove the   protection for parallel system  warning  Then  the UPS  could start up   If the UPSs in the system are  separated to single UPS   please disconnect the output  to other UPSs and choose   Para Unlock  in control  menu to remove the  warning  Then  the UPS  could start up     Warning OD  Over Temp The internal temperature is too Make sure ambient   high and reach the warning level  temperature not over 40  C   Maybe the environment is hot  Make sure the fan is OK   Maybe the fan is blocked or Make sure ventilation is well   failed  Remove some loads if  Maybe ventilation is blocked by possible   the wall or other goods    4  Load is too heavy     NOTE  Be careful to check  the UPS operation mode   parallel or single  and the  connections  If the parallel  cable is not connected in the  parallel mode  the UPS may  be damaged     Fault 01  Bus Start Fail The internal converter failed  so the   Contact the dealer to repair   DC bus voltage could not be  boosted correctly    Fault 02  Bus Over 1  DC bus voltage is too high  1 
26. ion             Others                      Press button    Enter    Fault Info                Press button    Esc                Warning Info             3 7 1  Main interface  home page   Bypass Mode Bypass Mode      0V 50  OHz IP 208  0V 50  OHz    V  50  OHz 0P 208  0V 50  OHz   Batt  273  0V 99  Batt  273  0V 99   Load  0  Load  0     Warning  01       1  In the first line  it will display the UPS running status mode     2  When alarms happen  the warning or fault information will display below the    load    line     3  When the front panel is not operated for 10 minutes  the display page will return back to home page   4  Press the  UP  or  DOWN  button to enter the operation menu  see 3 7 2 1      5  When it displays home page in LCD  if UPS is in bypass  you could press the  ON ENTER  button to turn on  the UPS to AC   converter   ECO   battery mode according to the setting and input status  in reverse  you  could press the  OFF ESC  button to allow UPS to bypass mode or shut down   Refer to section of  Single  UPS Operation      3 7 2  Operation menu   3 7 2 1  Main menu    Line Mode     2Control     P 208  0V 50  OHz  OP 208  0V 50  OHz Measurement  Batt  273  0V 99     Load  100  Information    Setting       Alarm  1  After pressing the    UP    or    DOWN    button at the home page  it will display five items in operation menu   Control   Measurement   Information   Setting   Alarm   2  Press    UP    or    DOWN    button to select item   3  Press  ON ENTER  butt
27. ion   UPS Power On When UPS is powered on  it will enter into this mode for a few seconds for  initializing the CPU and system    AC Mode When the input voltage is within acceptable range  and the UPS is turned on  the  inverter is running   the UPS will provide pure and stable sine wave AC voltage  The    UPS will also charge the battery in AC mode     ECO Mode When the input voltage is within voltage regulation range and ECO mode is  enabled  the UPS will bypass voltage to output for energy saving  If the input  voltage is out of the regulation range but it is still within acceptable range of AC  mode  the UPS will transfer to inverter supplying the power to load  similar as AC  mode    Converter Mode When input frequency is within 46 to 64Hz  the UPS can be set with a constant  EE output frequency  50 Hz or 60 Hz  through the inverter  The UPS will still charge  battery at this mode  There is no bypass at this mode   Battery Mode When the input voltage is out of the acceptable range or power failure  and the UPS  CMT i tumed on  he mere mig  te UPS wil Backup poner fom batie    Bypass Mode When input voltage is within acceptable range and bypass is enabled  and the UPS     inverter  is not turned on or the inverter can t support the load  the UPS will supply  power to the load through b  Battery Test Mode   When the UPS is in AC mode or Converter mode  and the battery test command is    enabled through LCD or monitoring software  the UPS will start Battery Test  This  oper
28. lashing     3 4  Audible alarm    UPS status                         Buzzerstatus   Muted    Beeping continuously  Warnings  except overload  Beeping once every second No         3 5  Single UPS Operation    3 5 1  Turn on the UPS with utility power supply  to Line mode     1  Make sure mains input and battery are connected well  and the battery pack breaker is at  ON   position  Set the external mains input breaker to  ON  position  then the fan will be running and the  UPS supplies power to the loads via bypass   The UPS is operating in Bypass mode      NOTE  When UPS is in Bypass mode  the output voltage comes directly from utility  so the load is not  protected by UPS  To protect the precious load  the UPS should be turned on to Line mode     2  When LCD is on home page  press the  ON ENTER  button  LCD will show a prompt page of  Turn On      Move the arrow to  Yes  by up or down button  then press  ON ENTER   the UPS will be starting up  with beeping once  You could also enter the  control menu  to select the instruction  Turn On  to  startup the UPS  Please refer to the section of  LCD operation      3  Afew seconds later  the UPS will enter into Line mode   Line mode  will be displayed on LCD   In line  mode  if the utility power is abnormal  the UPS will transfer to Battery mode without interruption      3 5 2  Turn on the UPS without utility power supply  to Battery mode   1  Make sure the battery is connected well and the battery pack breaker is at  ON  position   
29. n listed in spec at Line mode  the UPS will automatically transfer to  Bypass mode  After the overload is removed  it will return to Line mode  If the overload time is over  duration listed in spec at Battery mode  the UPS will become fault status  At this time  if bypass is  enabled  the UPS will power to the load via bypass  If bypass function is disabled or the input power  is not within bypass acceptable range  it will cut off output directly     3 5 4  Charge the batteries    1  After the UPS is connected to the utility power  the charger will charge the batteries automatically  except in Battery mode or during battery test     2  Suggest to charge batteries at least 10 hours before use  Otherwise  the backup time may be shorter  than expected     3  Make sure the battery numbers setting on the control board  Please refer to the section of changing  battery quantity  is consistent with actual connection     3 5 5  Battery mode operation    1  When the UPS is in Battery mode  the buzzer will beep according to different battery capacity   Normally  the buzzer will beep once every 4 seconds in battery mode  but when the battery voltage  drops to the alarm level  the buzzer will beep once per second and the UPS will shut down  automatically soon  Users could switch off some non critical loads to disable the shutdown alarm and    prolong the backup time  If there is no more load to be taken off at that time  you have to shut down  all loads as soon as possible to protect the 
30. oint for ECO mode   50 Hz  Setting range is from 52 0Hz to 54 0 Hz   60 Hz  Setting range is from 62 0Hz to 64 0Hz   The default value is 52 0Hz 62 0Hz     HighLoss    LowLoss          3  Output setting  only available or effective on bypass mode     Output       Nobts 208V  Freq  50Hz  GWGF  Enable    1  Volt    208  Presenting the rated output voltage with 208Vac  220  Presenting the rated output voltage with 220Vac  230  Presenting the rated output voltage with 230Vac  240  Presenting the rated output voltage with 240Vac     Freq   50Hz  The output frequency is setting for 50Hz   60Hz  The output frequency is setting for 60Hz   ATO  If selected  output frequency will be decided according to  the latest normal utility frequency  If it is from 46Hz to 54Hz  the  output frequency will be 50 0Hz  If it is from 56Hz to 64Hz  the  output frequency will be 60 0Hz  ATO is default setting      CVCF   Enable or disable converter mode   Enable  The output frequency will be fixed at 50Hz or 60Hz  according to setting of    Freq     The input frequency could be from  46Hz to 64Hz   Disable  The output frequency will synchronize with the input  frequency within 46 54 Hz for 50Hz system or within 56 64 Hz  for 60Hz system   NOTE  CVCF means Constant Voltage and Constant Frequency  it  represents converter mode        4  Battery setting  available on all operation modes     Battery         gt DisChg Protect   Fnable  990 Minute  Batt Test Type   Short Time   Till Batt Low    Battery      
31. on to confirm the selection     4  Press  OFF ESC  button to return back to home page   3 7 2 2  Control       Batt Test  Mute    Para Unlock       NOTE 1   Para Unlock  appears only when parallel communication failure happens   NOTE 2   Turn On  will be displayed if UPS is not turned on   Turn Off  will be displayed if UPS is turned on   Generally speaking  these two messages will not be displayed at the same time or in all operation modes   1  Turn On Turn Off  This item is for turning on off the UPS   a  On Bypass mode  it will display  Turn On  in control menu  If it is selected and confirmed  the UPS will  transfer to AC mode or converter mode or ECO mode or battery mode according to the setting and  input status        ine Mode       Turn On      IP 208  0V 50  OHz  Batt Test OP  208  0V 50  OHz  Mute Batt  273  0V 99   Para Unlock Load  100              NOTE  You may simply turn on UPS by pressing    ON ENTER    button in home page  It   s not necessary  to enter control menu to turn on the UPS    b  On AC mode or converter mode or ECO mode or battery mode  it will display    Turn Off    in control  menu  If it is selected and confirmed  the UPS will transfer to bypass mode or shut down     Bypass Mode       Turn Off      IP 208  0V 50  OHz  Batt Test OP   208  0V 50  OHz  Mute Batt  273  0V 99   Para Unlock Load  0                 NOTE  You may simply turn off UPS by pressing    OFF ESC    button in home page  It s not necessary  to enter control menu to turn off the 
32. t block ventilation holes in the UPS housing   1 3  Installation  AN Do not connect appliances or devices which would overload the UPS  e g  big motor type  equipment     Place cables in such a way that no one can step on or trip over them     Do not block air vents in the housing of UPS  The UPS must be installed in a location with good  ventilation  Ensure enough space on each side for ventilation     UPS has provided earthed terminal  in the final installed system configuration  equipotential earth  bonding to the external UPS battery cabinets     The UPS can be installed only by qualified maintenance personnel     An appropriate disconnect device as short circuit backup protection should be provided in the  building wiring installation     An integral single emergency switching device which prevents further supply to the load by the  UPS in any mode of operation should be provided in the building wiring installation     Connect the earth before connecting to the building wiring terminal     AN Installation and Wiring must be performed in accordance with the local electrical laws and  regulations     1 4  ZN connection Warnings    e There is no standard backfeed protection inside  please isolate the UPS before working according to this  circuit  The isolation device must be able to carry the UPS input current     External Distribution Panel    Coil Remote Switch   Magneto  Thermal Input Main Switch   AC Contactor as backfeed protection device  Neutral L2   L1 Line Input   
33. tion port   EPO  Emergency Power Off  connector  Share current port  for parallel function   Parallel port  for parallel function    Intelligent slot   EMBS  External Maintain Bypass Switch  port  Cooling fan   External battery connector      Input circuit breaker     Input Output terminal    Input terminal     Ground     Output terminal      Battery pack output circuit breaker    2 3  Rack Tower Installation    2 3 1 Tower Installation  The UPS system is shipped with two sets of feet and 6 extensions  2 short extensions plus 4 long extensions   that can be used to tower install the UPS module in 3U or UPS module with one battery bank in 6U    Install UPS module in 3U   Assemble two feet and one short extension as    Short extension    one tower stand shown in step 1  Align the  two stands approximately 35cm apart in step  2  Then  put UPS module in the stands as  shown in step 3     Install UPS module and one battery bank in  6U  Assemble two feet and two long extensions as       one tower stand shown in step 1  Align the  two stands approximately 35cm apart in step   f  2  Then  put UPS module and battery bank in  the stands as shown in step 3     2 3 2 Rack Installation    Please follow below steps to mount UPS into 19  rack or rack enclosure     Step 1  Attach mounting ears to the side mounting Chart 1  holes of UPS using the screws provided and the  ears should face forward  Please refer to chart 1     Step 2  Lift the UPS module and slide it into rack  enclosure  Attach
    