SE-704 MANUAL EARTH-LEAKAGE MONITOR

image

Contents

1. Littelfuse STARTCO 3714 Kinnear Place Saskatoon SK Canada 57 6 Ph 306 373 5505 306 374 2245 www littelfuse com relayscontrols SE 704 MANUAL EARTH LEAKAGE MONITOR REVISION 7 C 082814 RTCO LITTELFUSE STA TH LEAKAGE MONITOR TRIP EAR 300 300 B we 1000 200 60 3000 30 5000 3 LEVEL mA Copyright 2014 by Littelfuse Startco All rights reserved Document Number PM 1060 EN Printed in Canada Littelfuse Page i STARTCO SE 704 Earth Leakage Monitor Rev 7 C 082814 This page intentionally left blank Littelfuse STARTCO S 1 2 3 4 5 6 7 8 A SE 704 Earth Leakage Monitor TABLE OF CONTENTS ECTION PAGE Generali eos saco e dinars 1 Operation sess 1 2 1 Configuration Switch 2 444 4 1 2 1 4 Relay Operating Mode 1 2 1 2 0 0 1 2 1 3 CT Verification 1 2 1 4 Reset Mode sss 1 2 1 5 Analog Output 1 2 2 Front Panel Controls 1 2 2 1 Earth Leakage Trip Level 1 2 22 Earth Leakage Trip 1 2 2 3 Reset dicet oO Pers 1 e rrea 3 2 3 Front Panel Indication sss 3 23 1 POWGE 3 2 32
2. 300 0 500 300 80 1000 200 60 3000 100 0 000 55 wo 5 LEVEL mA TIME ms TEST BRACKET 55 mm 2 2 WIDE MONITOR FRONT VIEW SIDE VIEW INSTALLATION INSTRUCTIONS 1 REMOVE BEZEL AND LATCH MONITORTO IN BRACKET 2 0 0 08 RAD MAXIMUM INSERT BRACKETTHROUGH FRONT OF PANEL CUTOUT AND SECURE WITH FLAT WASHERS AND LOCKNUTS PROVIDED CONNECT WIRING TO TERMINALS c 4 3 0 17 n INSTALL BEZEL USING 6 32 x 0 31 SCREWS ALTERNATE PROVIDED CONFIGURATIONS 4 0 0 16 DIA NOTE j 1 DIMENSIONS IN MILLIMETRES INCHES PANEL CUTOUT DETAIL FIGURE 7 PMA 55 Panel Mount Adapter Littelfuse STARTCO SE 704 Earth Leakage Monitor Rev 7 C 082814 116 0 4 57 I PANELTHICKNESS 1 6 0 06 TO 4 8 0 19 pom LITTELFUSE STARTCO EARTH LEAKAGE MONITOR SE 704 100 100 500 500 80 1000 200 1000 60 3000 100 1500 15000 55 ET 2000 LEVEL mA TIME ms E Littelfuse 1 BRACKET mm 2 2 WIDE MONITOR TRANSPARENT FRONT VIEW COVER NOTE2 SIDE VIEW INSTALLATION INSTRUCTIONS 1 WITH COVER REMOVED LATCH MONITORTO BRACKET INSERT BRACKET THROUGH FRONT OF PANEL CUTOUT AND SECURE WITH FLAT WASHERS NO AND LOC
3. THD iiic etiem rere 3 2 3 3 CT Verification 3 2 4 Analog Outputs sess 3 2 5 Self Diagnostics 3 0 sse 3 SE 704 2 222 5 Technical Specifications 11 Sd SETO sedie tuns eS 11 9 2 Current SensOEs eee nitent or iren rein 13 Ordering Information 14 Warranty rone ERREUR 14 Earth Fault Performance Test 15 ppendix A SE 704 Revision History 16 Page ii Rev 7 C 082814 LIST OF FIGURES FIGURE PAGE 1 SE 704 Outline and Mounting Details 2 2 Typical Connection 4 3 Typical Three Phase Starter Connection 4 4 SE CS30 26 Current Sensor sss 6 5 SE C S30 70 Current Sensor sess 7 6 SE CS30 4 5 and 8 Current Sensors 8 7 55 Panel Mount 9 8 60 Panel Mount 10 9 PGA 0500 Analog Percent Current Meter 11 10 Earth Fault Test Circuit 15 LIST OF TABLES TABLE PAGE 1 Trip Features Comparison 5 2 Earth Fault Test Record 220 15 DISCLAIMER Specifications are subject to change without notice Littelfuse Startco is not liable for co
4. 50 60 Hz Trip Level Settings 10 30 60 80 100 300 500 1 000 3 000 and 5 000 mA Trip Time Settings 30 55 100 200 300 400 500 1 000 1 500 and 2 000 ms Accuracies Trip Level 5 1 000 to 5 000 mA 2 10 60 Hz 0 12 50 Hz 60 to 500 0 10 10 mA min IOMA aee ette 0 6 mA 4 1 mA Trip Time 5 of setting 20 ms min Input Algorithms 9 DFT Digital or Peak DFT 3 dB Frequency 32 to 86 Hz 1 000 mA Peak 3 dB Frequency 20 to 420 Hz 1 000 mA Peak 3 dB Frequency Response sss 20 to 120 Hz 21 000 mA ed rere SE CS30 Series Current Sensor CT Detection Open Circuit Detection Thermal Withstand Continuous sss 25 A Earth Fault Current 1 400 A Earth Fault Current 6 Littelfuse SE 704 Earth Leakage Monitor STARTCO Analog Output of 5 A or o of Trip Level Setting Range Terminal 3 Oto 1 mA Terminal 8 0to 5 Output Impedance Terminal 3 4 970 Q Terminal 8 2200 Output Relay Contact Configuration Isola
5. 98 Hn Hv SE CS30 26 CURRENT SENSOR Littelfuse cus STARTCO 4 0 0 16 RECESSED FOR 7 mm HEX NUT 3 0 0 12 DEEP M4 OR 8 32 TAP N L r al J 1 a be MOUNTING DETAIL 26 5 1 04 NOTES 9 S INSTALLATION CAT DETAIL A MOUNTING FOOT FIGURE 4 SE CS30 26 Current Sensor DIMENSIONS IN MILLIMETRES INCHES PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED DETAIL A MOUNTING SCREWS M4 OR 8 32 RoHS COMPLIANT EN 60044 1 COMPLIANT Littelfuse Page 7 STARTCO SE 704 Earth Leakage Monitor Rev 7 C 082814 MOUNTING DETAIL 25 0 30 0 0 98 1 18 1 SE CS30 70 Que 4 Littelfuse STARTCO us SCREWS 138 0 MAX 5 0 0 20 RECESSED FOR 8 mm HEX NUT 1 0 0 04 DEEP NOTES MOUNTING FOOT INSTALLATION DIMENSIONS IN MILLIMETRES INCHES IP gt TOOL S PRESS MOUNTING FEET IN PLACE USING gt INSTALLATION TOOL
6. Fig 1 2 1 1 RELAY OPERATING MODE Switch 1 is used to set the operating mode of the output relay In the fail safe mode the output relay energizes when the earth leakage circuit is not tripped In the fail safe mode non volatile memory retains the trip status of the SE 704 If tripped and the supply voltage is cycled the SE 704 will remain tripped with the trip relay de energized and the TRIP LED on until reset In the non fail safe mode the output relay energizes when an earth leakage trip occurs In the non fail safe mode trip status 1s not retained in non volatile memory 2 1 2 FILTER SELECTION Switch 2 is used to select the filtering algorithm for a fixed frequency 50 60 Hz or variable frequency application for earth leakage trip levels of 500 mA or less The peak detection algorithm is used for settings greater than 500 mA regardless of the filter selection The FIXED FREQUENCY setting uses a DFT filter that allows lower trip levels to be used by rejecting harmonics that can cause nuisance tripping The VARIABLE FREQUENCY setting uses a peak detection algorithm with a wider band width for fault detection in variable frequency drive applications SE 704 Earth Leakage Monitor Page 1 Rev 7 C 082814 2 1 3 CT VERIFICATION Switch 3 is used to enable CT verification In the ON position a trip will occur if the SE CS30 current sensor is disconnected 2 1 4 RESET MODE Switch 4 is used to select autoreset or latch
7. PROVIDED DETAIL A 3 MOUNTING SCREWS M4 OR 8 32 RoHS COMPLIANT 5 EN 60044 1 COMPLIANT DETAIL A FIGURE 5 SE CS30 70 Current Sensor 6 Littelfuse Pages STARTCO SE 704 Earth Leakage Monitor Rev 7 C 082814 MOUNTING DETAIL NOTES SE CS30 84 7 OUTLINE X ET E N DIMENSIONS IN MILLIMETRES INCHES MOUNTING SCREWS 5 OR 10 32 RoHS COMPLIANT CE COMPLIANT DIMENSIONS SE CS30 4 SE CS30 5 SE CS30 8 95 0 3 74 130 0 5 12 200 0 7 87 175 0 6 89 218 0 8 78 309 0 12 17 158 0 6 22 203 0 7 99 290 5 11 44 141 0 5 55 178 0 7 01 267 5 10 50 82 0 3 22 103 5 4 07 150 0 5 90 32 0 1 26 32 0 1 26 34 0 1 34 17 5 0 69 11 0 0 43 11 0 0 43 15 0 0 59 13 3 0 52 13 3 0 52 33 0 1 30 34 0 1 34 43 0 1 69 BOTTOM 9 0 0 35 11 0 0 43 11 5 0 45 40 0 1 57 40 0 1 57 50 0 1 97 5 3 0 21 7 0 0 28 7 0 0 28 FIGURE 6 SE CS30 4 5 and 8 Current Sensors Littelfuse Toget STARTCO SE 704 Earth Leakage Monitor Rev 7 C 082814 110 0 4 33 PANELTHICKNESS 1 6 0 06 TO 4 8 0 19 LITTELFUSE STARTCO EARTH LEAKAGE MONITOR SE 704 PWR TRIP
8. or from an incorrect reading from non volatile memory Press RESET or cycle supply voltage If the problem persists consult the factory Page 3 Rev 7 C 082814 3 INSTALLATION NOTE Mounting terminal block connections and wiring must conform to applicable local electrical codes Check all applicable codes prior to installation This earth leakage monitoring system consists of an SE 704 Earth Leakage Monitor and an SE CS30 series current sensor connected as shown in Figs 2 and 3 An SE 704 can be surface or DIN rail mounted See Fig 1 Panel mounting requires a PMA 55 or PMA 60 Panel Mount Adapter See Figs 7 and 8 Use terminal 11 L1 as the line terminal on ac systems or the positive terminal on dc systems Use terminal 10 L2 N as the neutral terminal on ac systems or the negative terminal on dc systems Connect terminal 9 to earth Pass the phase conductors through the CT window and position them in the centre of the opening for 4 wire and single phase systems also pass the neutral conductor through the CT window as shown in Figs 2 and 3 Do not pass earth conductors through the CT window In applications that require shields or drain wires to pass through the CT window return them through the CT window before connecting them to earth Connect the SE CS30 series current sensor to terminals 4 and 5 connect the shield to terminal 5 and earth terminal 5 See Figs 4 5 and 6 for SE CS30 current sensor dim
9. KNUTS PROVIDED q O 2 0 0 08 RAD i Bu MAXIMUM CONNECT WIRING TO TERMINALS 4 5 0 18 DIA ATTACH COVER USING SECURITY SCREWS 8 7 0 34 DIA ORTHUMB SCREWS PROVIDED 4 3 0 17 RAD NOTES ALTERNATE CONFIGURATIONS H DIMENSIONS IN MILLIMETRES INCHES MEETS NEMAS IP53 INCLUDESTWO TR20 TAMPER RESISTANT TORX SCREWS M4 0 7x16 mm INSTALLED ANDTWOTHUMB SCREWS PANEL CUTOUT DETAIL FIGURE 8 PMA 60 Panel Mount Adapter 6 Littelfuse STARTCO SE 704 Earth Leakage Monitor Page 11 Rev 7 C 082814 R1 25 0 049 MAXIMUM NOTES 1 CONVERSION KIT FOR 0 5 V ANALOG OUTPUT SEE PGA 0500 DOCUMENTATION 2 DIMENSIONS IN MILLIMETRES INCHES PGA 0500 ANALOG CURRENT METER FRONT FIGURE 9 PGA 0500 Analog Percent Current Meter 5 TECHNICAL SPECIFICATIONS 5 1 SE 704 Supply OU 5 VA 120 to 240 Vac 20 55 50 60 Hz 2 W 100 to 240 Vdc 20 25 OD 2 W 12 30 Vdc 20 25 OT 2 W 40 to 55 Vdc 20 25 03 2 5 VA 24 Vac 15 40
10. T KNOBS ARE REMOVABLE CONFIGURATION SWITCHES SHOWN IN DEFAULT POSITION FIGURE 1 SE 704 Outline and Mounting Details Pad Littelfuse SE 704 Earth Leakage Monitor STARTCO 2 2 4 TEST The TEST button is used to test the earth leakage circuit the indication and the output relay When the TEST button is pressed for one second a test signal is applied to the earth leakage detection circuit the circuit will trip the TRIP LED will light and the output relay will operate 2 3 FRONT PANEL INDICATION 2 3 1 PowER The green LED labelled PWR indicates presence of supply voltage 2 3 2 TRIP The red LED labelled TRIP indicates a trip A solid red LED indicates an earth leakage trip and a flashing LED indicates a trip initiated by a CT fault Two fast flashes of the TRIP LED indicate a diagnostic trip See Section 2 5 2 3 3 CT VERIFICATION The green LED labelled CT indicates that an SE CS30 sensor is connected even if CT verification is disabled 2 4 ANALOG OUTPUTS The non isolated 0 to 1 mA terminal 3 and 0 to 5 V terminal 8 analog outputs indicate earth leakage current sensed by the SE CS30 series current sensor The output is linear between zero and full scale Use a PGA 0500 Analog Percent Current Meter to indicate earth leakage current See Figs 2 3 and 9 2 5 SELF DIAGNOSTICS A diagnostic trip is indicated by two fast flashes of the TRIP LED It can be caused by a problem detected by the watchdog timer
11. TION 3 EFCT x figures updated SECTION 4 EMC Test specifications updated REVISION 7 B 052114 SECTION 4 Figs 2 3 4 5 6 and 9 updated SECTION 5 Update to include altitude and vibration specifications FCC certification added Update to trip level accuracy Added current sensor specifications SECTION 6 Ordering information updated SECTION 8 Fig 10 updated REVISION 7 A 040813 SECTION 3 Fig 2 updated to include PGA 05CV SECTION 4 Fig 6 updated SECTION 5 Environment section updated to include Fahrenheit temperature range APPENDIX A Revision history added PRODUCT REVISION HISTORY REVISION 04 Firmware Improved operation of front panel test button
12. ail safe relay operating mode Prior to hardware revision 01 a mechanical flag was used instead of non volatile trip memory The current revision of the SE 704 can directly replace previous revision 00 units The hardware revision number is listed on the SE 704 model serial number label affixed to the SE 704 enclosure SE 704 generations are compared in Table 1 SE 704 Earth Leakage Monitor Page 5 Rev 7 C 082814 The SE 704 was previously available with SE 704 01 120 Vac and SE 704 02 240 Vac control voltage options These have been discontinued An SE 704 0U universal 120 240 Vac Vdc unit can directly replace an SE 704 01 or SE 704 02 TABLE 1 TRIP FEATURES COMPARISON HARDWARE REVISION 00 gt 01 LED trip indication Yes Yes Mechanical flag trip indication Yes No Non volatile trip memory No Yes Device state after supply voltage Trip LED Off Trip relay Energized Trip flag Red Trip LED On Trip relay De energized cycled when tripped earth fault removed Non fail safe Trip LED Off Trip relay De energized Trip flag Red Trip LED Off Trip relay De energized Page 6 Rev 7 C 082814 Littelfuse STARTCO SE 704 Earth Leakage Monitor 170 2 68 0 67 10 0 0 43 WE o 0 TOP 25 0 0
13. ensional drawings Remove the connection to terminal 9 for dielectric strength testing all inputs and outputs have ANSI IEEE C37 90 surge protection circuits that conduct above 300 Vac J Page 4 WA Littelfuse STARTCO SE 704 Earth Leakage Monitor Rev 7 C 082814 SE CS30 SERIES SE CS30 SERIES SE CS30 SERIES 51 SE 704 51 704 1 CONNECTION 2 3 PHASE 4 WIRE N CONNECTION ISOLATED CONTACTS REMOTE RESET A SE 704 O ORS 750 LEAKAGE ANALOG o OUTPUT Do NOTE INDICATION 1 RELAY CONTACTS SHOWN WITH SE 704 55 Gf ew DE ENERGIZED i c i P d 9 8 TRIP 3 PHASE 3 WIRE CONNECTION RESET PGA 05CV PGA 0500 FIGURE 2 Typical Connection Diagrams SE CS30 SERIES A A TED CONTACTS L2 REMOTE RESET E SE 704 RS RESET 0O E cw I 1 PGA 05CV NOT REQUIRED WHEN NOTES U 90 J OUTPUT Do PGA 0500 CONNECTEDTO TERMINAL 3 ET INDICATION RELAY CONTACTS SHOWN WITH SE 704 TE DE ENERGIZED PWR v 4 FIGURE 3 Typical Three Phase Starter Connection Littelfuse STARTCO 4 SE 704 COMPATIBILITY The current SE 704 has been enhanced with the addition of non volatile trip memory for the f
14. for 5 10 20 50 100 amp 200 ms 3x each 61000 4 16 Zone A differential mode 150 Vrms Zone A common mode 300 Vrms 61000 4 18 1 differential mode line to line 2 5 kV common mode FCC Part 15 Subpart B Class A Unintentional Radiators CSA Canada and USA 6 amp LR 53428 05 UL Listed LISTED Ground Fault Sensing and Relaying Equipment 4FX9 40889 Australia N11659 FCC European Union Edition EN 61010 1 2001 2 Edition Safety Requirements for Electrical Equipment for Measurement Control and Laboratory Use Part 1 NOTES Page 13 Rev 7 C 082814 Detection limit A setting in mA 5 610 1 4 Q G 4 5 At 50 or 60 Hz unless otherwise noted SE CS30 series current sensor included Maximum lead resistance of 2 Trip Time at 3 x trip level setting 9 Peak algorithm for trip level setting 2 1 000 mA 5 2 CURRENT SENSORS Environment Operating Temperature Storage Temperature Compliance SE CS30 26 Current Ratio Insulation Window Diameter Shipping Weight Certifications SE CS30 70 Current Ratio Insulation Window Diameter Shipping Weight Certifications SE CS30 4 Current Rat
15. ing trips See Section 2 2 3 2 1 5 ANALOG OUTPUT Switch 5 is used to select analog output scaling Selecting OF 5A results in full scale output 1 mA or 5 V when earth fault current is 5 A Selecting OF SETTING results in full scale output when earth fault current equals the trip level setting See Section 2 4 2 2 FRONT PANEL CONTROLS 2 2 1 EARTH LEAKAGE TRIP LEVEL The LEVEL mA selection switch is used to set the earth leakage trip level For earth leakage detection the earth leakage trip level must be substantially below the prospective earth fault current To avoid sympathetic tripping the trip level must be above the charging current of the protected feeder 2 2 2 EARTH LEAKAGE TRIP TIME The SE 704 has a definite time trip characteristic The TIME ms selector switch is used to set the earth leakage trip time for coordination with upstream and downstream earth fault devices Coordination requires the same trip level for all earth leakage devices in a system and the trip time to progressively increase upstream The amount of equipment removed from the system will be a minimum if the first earth leakage device to operate is the one immediately upstream from the fault 2 2 3 RESET If the Reset Mode switch is in the LATCHING position a trip remains latched until the RESET button is pressed or the remote reset terminals 6 and 7 are momentarily connected In the non fail safe relay operating mode cycling the supply vol
16. io Insulation Window Diameter Shipping Weight Certifications SE CS30 5 Current Ratio Insulation Window Diameter Shipping Weight Certifications SE CS30 8 Current Ratio Insulation Window Diameter Shipping Weight Certifications 40 to 60 C 40 to 140 F 55 to 80 C 67 to 176 F RoHS REACH IEC 60044 1 30 0 05 A 600 V Class 26 mm 1 0 0 45 kg 1 0 Ib CSA UL CE 30 0 05 A 600 V Class 70 mm 2 7 1 2 kg 2 5 Ib CSA UL CE 30 0 05 A 600 V Class 95 mm 3 7 1 3 kg 3 0 Ib CE CSA pending UL pending 30 0 05 A 600 V Class 130 mm 5 17 2 1 kg 4 6 Ib CE CSA pending UL pending 30 0 05 A 600 V Class 200 mm 7 9 4 3 kg 9 4 Ib CE CSA pending UL pending Littelfuse STARTCO SE 704 Earth Leakage Monitor 6 ORDERING INFORMATION SE 704 0 Conformal Coating Blank Partial Conformal Coating CC Full Conformal Coating Supply 3 24 Vac Supply U Universal 120 240 Vac Vdc Supply D 12 24 Vdc Supply T 48 Vdc Supply 830 26 Current Sensor 26 0 mm 1 0 window SE CS30 70 isisisi Current Sensor c w Flux Condit
17. ioner 69 8 mm 2 8 window SE CS30 4 Current Sensor c w Flux Conditioner 95 0 mm 3 7 window 30 5 esse nein Current Sensor c w Flux Conditioner 130 0 mm 5 17 window SE CS30 8 Current Sensor c w Flux Conditioner 200 0 mm 7 97 window PGA 0500 enne Analog Percent Current Meter PGA 05CV included PMA S S ss esee Panel Mount Adapter NEMA 1 PMA 60 Panel Mount Adapter NEMA 3 IP53 Includes two TR20 tamper resistant Torx screws and two thumb Screws 700 00 TR20 tamper resistant Torx 0 25 insert bit AC700 HW 01 eee TR20 tamper resistant Torx driver PMA 3 issues Adapter Plate GEC MCGG 6 Adapter Plate FPL GFRM PMA 15 setis Adapter Plate MGFR Consult factory for custom mounting adapters Page 14 Rev 7 C 082814 7 WARRANTY The SE 704 Earth Leakage Monitor is warranted to be free from defects in material and workmanship for a period of five years from the date of purchase Littelfuse Startco will at Littelfuse Startco s option repair replace or refund the original purchase price of an SE 704 that 1s determined by Littelfuse Startco to be defective if it is returned to the factory freight prepaid within the warranty period This warranty does not apply to repairs required as a result of misuse negligence an accident impro
18. ntingent or consequential damages or for expenses sustained as a result of incorrect application incorrect adjustment or a malfunction FA Littelfuse Page ii STARTCO SE 704 Earth Leakage Monitor Rev 7 C 082814 This page intentionally left blank Littelfuse STARTCO 1 GENERAL The SE 704 is a microprocessor based earth leakage monitor for ac power supply systems that require earth leakage detection as low as 10 mA It is uniquely suited for very sensitive earth fault protection on systems with significant harmonic content Its output relay can operate in the fail safe or non fail safe mode for undervoltage or shunt trip applications The SE 704 has one output relay with isolated normally open and normally closed contacts for use in independent control circuits Additional features include LED trip and power indication autoreset or latching trips with front panel and remote reset trip memory test button self diagnostics 0 to 1 mA and 0 to 5 V analog outputs CT verification with LED indication digital selector switches and switch selectable algorithms for fixed frequency or variable frequency applications Earth leakage current is sensed by an SE CS30 series core balance earth fault current transformer CT The trip level of the earth leakage circuit is digital switch selectable from 10 to 5 000mA Trip time is digital switch selectable from 30 to 2 000 ms 2 OPERATION 2 1 CONFIGURATION SWITCH SETTINGS See
19. per installation tampering or insufficient care Littelfuse Startco does not warrant products repaired or modified by non Littelfuse Startco personnel Littelfuse Page 15 STARTCO SE 704 Earth Leakage Monitor Rev 7 C 082814 8 EARTH FAULT PERFORMANCE TEST Some jurisdictions require periodic earth fault SE CS30 performance tests A test record form is provided for FROM recording the date and the result of the performance ares tests The following earth fault system tests are to be conducted by qualified personnel a Evaluate the interconnected system in accordance with the overall equipment manufacturer s detailed 2 bg Rr P SE 704 instructions N Plo 12 Venfy proper location of the SE CS30 current B5 sensor Ensure the cables pass through the current sensor window This check can be done visually o OP1 with knowledge of the circuit The connection of the L tou current sensor secondary to the SE 704 is not polarity lo L2 sensitive oD SE 400 b wm Verify that the system is correctly earthed and that alternate earth paths do not exist that bypass the current sensor High voltage testers and resistance bridges can be used to determine the existence of 1 10 10W 1 R2 0 1 10W 1 alternate earth paths lest 1 10 SE 400 SETTING RMT1 REMOTE RMT2 d Verify proper reaction of the circuit interrup
20. tage will also reset the SE 704 If the Reset Mode switch is in the AUTORESET position a trip will reset when the fault is removed The reset circuit responds only to a momentary closure so that a jammed or shorted button will not prevent a trip The front panel RESET button is inoperative when the remote reset terminals are connected 6 Littelfuse Page STARTCO SE 704 Earth Leakage Monitor Rev 7 C 082814 CONFIGURATION SWITCHES ANALOG OUTPUT OF SA OF SETTING RESET MODE LATCHING AUTORESET SWITCHES LT orae FILTER SELECTION FIXED NON FAIL SAFE FREQUENCY AUTORESET RELAY OPERATING MODE FAILSAFE RESET MODE LATCHING 5 4 CONFIGURATION CT VERIFICATION OFF 2 1 4 1 3 11 CT VERIFICATION OFF FILTER SELECTION 2 ra FIXED VARIABLE RELAY OPERATING MODE 1 SAFE NON FAIL SAFE 0 MOUNTING DETAIL 113 0 NOTE 3 4 45 110 0 4 33 LITTELFUSE STARTCO EARTH LEAKAGE MONITOR SE 704 LEVEL mA TIME ms FA Littelfuse SIDE NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 9 10 1 12 13 14 15 16 OW O H P 2 MOUNTING SCREWS M4 OR 8 32 OVERALL DIMENSION WHEN MOUNTED ON DIN EN50022 35 mm 75 mm RAIL BOTTOM ADJUSTMEN
21. tand ANSI IEEE 37 90 1 1989 Oscillatory and Fast Transient Vibration 222 EN60255 21 1 Vibration Shock and Seismic EN60255 21 2 Shock and Bump EMC Tests Verification tested in accordance with EN 50263 2000 Radiated and Conducted Emissions eee CISPR 11 2009 CISPR 22 2008 55022 2010 Class Current Harmonics Voltage Fluctuation IEC 61000 3 2 and 61000 3 3 Class A Electrostatic Discharge TEC 61000 4 2 6 kV contact discharge direct and indirect 8 kV air discharge Radiated RF Immunity 61000 4 3 10 V m 80 1000 MHz 80 AM 1 kHz 10 V m 900 MHz 200 Hz pulse modulated Fast IEC 61000 4 4 4 kV on AC mains and I O lines Littelfuse STARTCO Surge Immunity Conducted RF Immunity Magnetic Field Immunity Voltage Interruption Power Frequency 1 MHz RFI Compliance Certification Complies to 61010 1 2001 214 5 704 Earth Leakage Monitor IEC 61000 4 5 Zone B X KV differential mode 2 kV common mode IEC 61000 4 6 10 V 0 15 80 MHz 80 AM 1 kHz IEC 61000 4 8 50 Hz and 60 Hz 30 A m and 300 A m IEC 61000 4 11 IEC 61000 4 29 0
22. ted N O and N C Operating Mode Fail Safe or Non Fail Safe CSA UL Contact Rating 8 A General Use 250 Vac 8 A Resistive 30 Vdc 0 25 HP 120 240 Vac Supplemental Contact Ratings Carry Current 8 A maximum Break BOW dG uices 240 W Resistive 170 W Inductive L R 7 ms 120 Vdc ee 24 W Resistive 17 W Inductive L R 7 ms AC 2 000 VA Resistive 875 VA Inductive PF 0 4 Subject to maximums of 8 A and 250 Vac 30 Vdc or 200 mA at 120 Vdc Trip Mode sss Latching or Autoreset Front Panel Button and Remote N O Contact Functional Test Front Panel Button Terminals ee Wire Clamping 24to 12 AWG 0 2 to 2 5 mm conductors Dimensions Height ences 75 mm 3 0 Width sss 55 mm 2 27 ariari 113 mm 4 5 Shipping Weight 0 45 kg 1 Ib Environment Operating Temperature Altitude lt 1 000 m 3 281 40 to 60 C 40 to 140 F Page 12 Rey 7 C 082814 3 000 m 9 843 40 to 55 C 40 to 131 F 5 000 m 16 404 40 to 50 C 40 to 122 F Storage Temperature 55 to 80 C 67 to 160 F 85 Non Condensing Alttude sss 5 000 m 16 404 maximum PWB Conformal Coating MIL 1 46058 qualified UL QMJU2 recognized Surge Withs
23. ting device in response to a simulated or controlled earth fault current To simulate earth fault current use CT FIGURE 10 Earth Fault Test Circuit primary current injection Fig 10 shows a test circuit using an SE 400 Ground Fault Relay Test Unit The TABLE 2 EARTH FAULT TEST RECORD SE 400 has a programmable output of 0 5 to 9 9 A DATE TEST RESULTS for a duration of 0 1 to 9 9 seconds Fig 10 shows the use of resistors that reduce the injected current to 10 of the SE 400 setting Set the test current to 120 of the SE 704 setting Inject the test current through the current sensor window for at least 2 5 seconds Verify that the circuit under test has reacted properly Correct any problems and re test until the proper reaction is verified e Record the date and the results of the test on the attached test record form NOTE Do not inject test current directly into current sensor input terminals 4 and 5 Retain this record for the authority having jurisdiction Littelfuse Page 16 STARTCO SE 704 Earth Leakage Monitor Rev 7 C 082814 APPENDIX A SE 704 REVISION HISTORY MANUAL MANUAL PRODUCT REVISION RELEASE DATE REVISION REVISION NUMBER ON PRODUCT LABEL August 28 2014 7 C 082814 May 21 2014 7 B 052114 04 April 8 2013 7 040813 MANUAL REVISION HISTORY REVISION 7 C 082814 SEC