Home

ATXV-AC05-GPRS Gebruikershandleiding / Manual

image

Contents

1. ATAI ATAL 7 Connection cable kit ATP AC10 for data loggers ATP The kit is intended for the ATP data logger and the modem interconnection The kit consists of two cables the cable for the data logger and the modem interconnection via RS232 serial link and the cable for voltage distribution between the data logger and the modem Two pieces of contact tubes are also included along with the cable for voltage distribution The data logger The data logger is a target device The modem is intended for communication with this device Generally the data logger types ATV ATX and ATP are supported The paid version of program for data loggers ATXV WIN This program makes possible to change of modem settings to communicate with the data logger to read information about actual settings and data logger status to change parameters for data recording and to read measured data Minimal program version must be 2 2 18 0 The latest program versions are available on www atal nl A GPRS connection or a setting cable for example if the GPRS connection is not activated can be used for setting of the modem with this program The M2MTalk server service If you want use SMS messages only you will not have to activate this service For anything else like remote communication with the data logger including data downloading this service must be activated By default this service is not activated by manufacturer In addition if this service is use
2. SMS remote control Insert phone numbers from which modem accepts SMS commands Commands from other phone numbers will be ignored If the following list is empty modem accepts SMS commands from all phone numbers Phone number lis Add Edit Delete Phone number in international format e g 012345678901 Use 4 15 digits K Back Next ee X Cancel Communication via SMS messages can be restricted to selected phone numbers only If no phone numbers are in the list the modem will process the incoming SMS messages from all phone numbers If you add some phone numbers to this list the modem will process the incoming SMS messages only from these selected phone numbers After pressing Add button enter the phone numbers from which you want to send SMS command messages to the modem All phone numbers must have the international format for example 310123456789 After pressing Next button the window for settings of the alarm SMS messages parameters will be displayed ATAN AIH 33 amp GPRS modem settings Oe x Alarms SMS alarm settings Insert phone numbers of warning SMS recipients vV Send warning SMS Check alarm status 30 zj s Phone number list oo Add Edit Delete 420737123456 Phone number in international format e g 012345678901 Use 4 15 digits Back Hex L av x Cancel The informatio
3. GPRS Modem ATXV AC05 GPRS Manual ATAL B V Amperestraat 35 37 NL 1446 TR PURMEREND Postbus 783 NL 1440 AT PURMEREND T 431 0299 630 610 F 31 0299 630 611 E info atal nl l www atal nl Contents 1 Description of working of the modem sise si sab potko ei ob aba na ou kk a pab in a e kaba pan feb kat 4 2 GON SIGN tales b ik kin s k dan kk ka kk kk a ks ap se bb kn kk a ka ra ba kk n pd opa bk aaa Eih 5 3 AN WMO Geni ANJ its ACCESSOTICS ar a yn a ki tt a a ion a a an a kita a a ate ba kaa fel os ian 7 Daly Access riesnecded TO ON T AN ON fol kak n ko e oi ak bb pe ote ket oben a ke ia 7 THE Mea gates atann ks la dese aske ia gade a pakon ol seen dese ip kal pad kk its dou bese e E aA 7 The GSM UM sas a cach bach a j Geared po Saa l ne a aaee ae n n aai i eee Ap n 7 The electric power Supply iv s 4e ase voila bi ei ii kk er e ka san kk E kaa kra ss koka nil 7 e The COM adapter IP65 ATXV ACOIX for data loggers ATV ATX veerevorooorouoo 7 e Connection cable kit ATP AC10 for data loggers ATP 0000i 2eterooeoroooronooooonooononnon 8 Thedata 16 er age erect cededincnsabecc nen oi e n a n e e e e e a ED E sey aaa 8 e The paid version of program for data loggers ATXV WIN 0000 2eteeeeeerouoooonoosonooonoonnnon 8 a The MIO Tale server SEN VICE donnans a kalib pi a as n je pa ae bat a ad 8 3 2 PMU C CESS vite fe ii n n e a a e bk a kk a li a a kata ae
4. If the modem accepts the command the SMS message will be sent back And if the modem was logged on the M2MTalk server the modem will be restarted automatically ATAI 20 AIAL An example of the command with parameters gprs internet Setting of the parameter apn to the value internet The values of the parameters user password and dns will be deleted The response message GPRS parameters were set and stored AII parameters were set and stored correctiy An error occurred while setting GPRS An error occurred during setting parameters the parameters Their saving didn t succeed If all values to store are the same as the original already stored values executing the command will have no effect In this case the modem will only send back the same information as in the case of Information about the GPRS connection settings So if only the information is sent back though the user entered the setting command it means all parameters are already set as required it wasn t needed to change them ATA AG 21 5 2 6 Information about the M2MTalk server connection settings If the SMS message m2mtalk without any parameters is sent the modem will send back the SMS message with information about the M2MTalk server connection settings m2mtalk The command for reading of information about the M2MTalk server connection settings An example of the response message Enabled yes Autologin yes Information about the M2MTalk
5. Address 1234 User usr server connection settings Password psw Server example com Port 9999 Delt Setting of the M2MTalk server connection The first word of the message must always be m2mtalk After this keyword parameter values for an actual setting follows in specific order m2mtalk enabled autologin address user password server port If the trailing parameter values are not entered they will be unchanged Don t enter the square brackets in the SMS message Individual items of the message must be separated by spaces The parameters are optional from the back If any parameter isn t entered it will not be changed The meaning of the parameters is following e enabled enable the communication via M2MTalk server yes no e autologin automatic login on the server after switching on the modem yes no e address the modem address a number value e user the user name for login a text e password the password for login a text e server the M2MTalk server name or IP address a text e port the port number a number value If the modem accepts the command the SMS message will be sent back And if the modem was logged on the M2MTalk server the modem will be restarted automatically m2mtalk yes no 2006 2006 mypsw The communication via M2MTalk server will be enabled automatic login after switching on will be deactivated address will be 2006 user name will be 2006 and the password will be mypsw The
6. M2MTalk server name or IP address and the port number stay unchanged M2MTalk server parameters were set and All parameters were set and stored stored correctly An error occurred while setting M2MTalk An error occurred during setting server parameters the parameters Their saving didn t succeed ATA QE 22 AG If all values to store are the same as the original already stored values executing the command will have no effect In this case the modem will only send back the same information as in the case of Information about the M2MTalk server connection settings So if only the information is sent back though the user entered the setting command it means all parameters are already set as required it wasn t needed to change them 5 2 8 Information about permitting of the alarm SMS messages If the SMS message alarms without any parameters is sent the modem will send back the SMS message with information whether sending of the alarm SMS messages is enabled or not The command alarms The command for reading of information about permitting of the alarm SMS messages The possible response messages Sending of warning messages is switched Sending of the alarm SMS messages Sending of warning messages is switched off is disabled 5 2 9 Setting of permitting of the alarm SMS messages The syntax of this command is either alarms on or alarms off In the first case sending of the alarm SMS messages will be enable
7. equipment self adhesive Dual Lock wall holder DIN rail holder temperature from 40 C to 85 C 105 x 71 x 24mm without antenna and holders ca 180g without antenna and holders anodized aluminum 2 7 2 The modem interface 1 RS232 connector 9 pin male 2 SIM card holder and connector 3 antenna connector SMA female6 supply terminal block WAGO 4 yellow indicator LED 5 green indicator LED 36 A directory information about dimensions with the GSM antenna GSM ANT 7 3 7 4 Dimensional drawing for a wall mounting of the modem with GPRS AC01 ban 105 mm 24 mm AA A E E E Y g Y 2mm 13 mm ATAN 37 38 7 5 Dimensional drawing for a DIN rail mounting of the modem with GPRS AC02 105 mm 84 mm 7 6 Description of the indicator LEDs The green indicator LED does not light the modem isn t connected to a power supply lights blinks the modem power supply is on this is a correct operation switches off for a short time A A _ A a checking signal this is a correct operation every ca 30s the modem is restarting restart takes about 1 minute The yellow indicator LED does not light a GSM part is switched off blinks one time for a short time every ca 3s blinks two times for a short time every ca 3s blinks regularly the modem is successfully connected via the cellular network GSM i e the modem replie
8. limit for measured values and reaching of the chosen state for binary inputs are evaluated by the data logger To work it correctly following parameters must be set for the data logger e the data logger must be switched on e the alarm conditions must be set with desired means for all monitored channels e the alarm evaluating must be enabled for all monitored channels The incoming SMS message contains the same information as in the case of the query about the current values and their alarm settings The measured value exceeds the alarm limit The incoming alarm SMS message Example 1 The current values and their alarm 12345678 1 24 7C 19 0 26 0 2 settings from the data logger 45 5 RH 0 0 50 0 6 12 1C 0 0 10 0 Example 2 Logger Store_13 T 24 7C 19 0 26 0 RH 45 5 RH 0 0 50 0 DP 12 1C 0 0 10 0 ATAI 26 AIH The binary input state is equal to the chosen state data loggers A TP only The incoming alarm SMS message Example l The current values and their alarm 12345678 1 24 7C 19 0 26 0 1m 2 settings from the data logger 25 0C 10 0 24 0 2m 3 OFF lm 4 ON 10m Example 2 Logger Store 13 Templ 24 7C 19 0 26 0 lm Temp2 25 0C 10 0 24 0 2m Binl OFF lm Bin2 ON 10m 3 3 2 Other data logger states Data logger type detection failed A problem occurred while detecting a The modem is not unable to logger type determine type of data logger which is connected to it Mos
9. the server automatically after its switching on but it isn t a standard factory setting To login the modem on the M2MTalk server you can send a SMS message login to the modem phone number The modem will send back an acknowledge SMS message It is advisable to check the login status by sending SMS message gsmstatus to the modem phone number If the modem works correctly it will send back SMS message with information The login status is also including in these information M2MTalk online yes Attention Since the modem is logged on a limited data transferring also proceeds in case the remote communication with the device isn t in progress due to keeping the connection Transferred data is charged as per your GPRS tariff by the mobile operator AN Around 26 kB of data per day are transferred for keeping connection purposes If the full up data logger memory is about to be downloaded around 73 kB of data per day are transfered for data loggers ATV ATX and around 1162 kB of data per day are transfered for data loggers ATP Logout from the server is described in the chapter Logout from the M2MTalk server on page 19 4 7 Setting of the other parameters The information that the alarm is active and information about correct operation of the data logger can be periodically taken from the data logger by the modem These informations are processed and then the modem sends alarm SMS messages to a customer according to these analyses The pro
10. MS messages are accepted by the modem These are possibilities of usage the program for data loggers e downloading data from the connected data logger e reading of current values from the connected data logger e setting up the modem locally via RS232 link e setting up the modem remotely via GPRS networking e setting up the connected data logger remotely These are possibilities of usage the SMS messages e sending of alarm SMS messages to preconfigured phone numbers in case of beyond the set alarm limits for measured values and binary inputs or in case of error conditions e getting of current values from the connected data logger e setting up the modem remotely with restrictions Logge Current values rRxxx Alarms x Setting up a modem Sxxxx GPRS Modem SMS COM Adapter m Feeder cable and M2M GPRS communication nahla M2MTalk server MWEN Downloading data from logger Showing of current values Setting up a logger Working principle for the modem with the data logger block diagram ATAI 4 ATAL 2 General safety rules The following summary describes a basic safety features related to device installation and operation Please read it properly before device installation The following safety precautions must be observed during all phases of the operation usage installation or repair of the device Operate the instrument in accordance with this manual to prevent damage of this device
11. Talk server Modem startup is still in progress A command can t be processed please try it later because modem startup has not finished yet It is necessary to repeat the command later Logging on the server is already in A command can t be processed progress because modem is already logging on the M2M server Using server is disabled login is not A command can t be processed accepted because communication with M2M server is disabled 3 2 2 Logout from the M2MTalk server Since the modem is logged on a limited data transferring also proceeds in case the remote communication with the device isn t in progress due to keeping the connection Transferred data is charged as per your GPRS tariff by the mobile operator If you intend to use remote communication via GPRS no longer you can logout the modem from the M2MTalk server to reduce transferred data The command for logout from the M2MTalk server The response message The demand for logout on the server was Information about acceptance of accepted demand for logout from the M2MTalk server This module is not logged on the server The messag the modem wasn t logged on the M2MTalk server Modem startup is still in progress A command can t be processed please try it later because modem startup has not finished yet It is necessary to repeat the command later ATAI MAG 19 3 2 3 Restart of the modem This command is intended for the remote re
12. caus the data logger is switched off An error occurred during communication A query can t be processed becaus with the logger a communication error between the modem and the data logger has occurred Data logger type detecting is still in A query can t be processed becaus progress please try it later detecting of the data logger type is just in progress It is necessary to repeat the command later 31 2 The query about the current values and their alarm settings To take the current values from the connected data logger and their alarm settings send the SMS message values to the modem The content of the response message is similar to a query values Moreover if the measured value exceeds any alarm limit or if the binary input is in a state of active alarm the symbol will be displayed in front of the value This response message also includes alarm limits for measured values but not for binary inputs If a data logger ATP is connected to the modem information about adjusted alarm delays in minutes for all measured values and binary inputs will be displayed too The response message example data logger ATV or ATX Logger Store 13 Temp 24 7C 19 0 26 0 Hum 45 5 RH 0 0 50 0 DP 12 1C 0 0 10 0 The response message example data logger ATP Logger Store 13 Temp1 24 7C 19 0 26 0 1m Temp2 25 0C 10 0 24 0 2m Bin1 OFF 1m Bin2 ON 10m ATA LAG 17 values The command for reading o
13. ction ATA OE MAG 13 4 4 Switching on the modem The properly assembled modem is switched on by feeding of electric voltage into the modem supply terminal block The green LED diode lights up The modem will be prepared for communication after ca 1 minute from its switching on It is advisable to check the communication by sending SMS message gsmstatus to the modem phone number A response delivery time is generally dependent on a momentary cellular network load and state If the modem works correctly it will send back SMS message with its state information If you don t receive the response to this SMS message please check your SIM card settings power supply connection and aerial connection If communication with the modem via cellular network is impossible you can try to find a problem with the program for data loggers In this case you must interconnect the modem and the computer via the setting cable see the chapter The setting cable AT AC NULL on page 8 4 5 Setting up the modem If you don t intend to use remote communication with the data logger via GPRS you can go to the chapter Setting of the other parameters on page 15 4 5 1 Setting of GPRS connection parameters If you didn t specify the GPRS connection parameters before ordering the modem you must set it up now To do it you can send a special SMS message to the modem phone number The first word of the message must always be gprs After this keyword parame
14. d Alarm states will be checked periodically If any alarm occurs the alarm SMS message will be sent to the predefined phone numbers In the second case sending of the alarm SMS messages will be disabled alarms on Sending of the alarm SMS messages Sending of warning messages was switched Sending of the alarm SMS messages on from number 310123456789 was enabled from the phone number 420123456789 An error occurred while switching sending The error occurred saving of the of warning messages on parameter didn t succeed The command alarms off Sending of the alarm SMS messages will be disabled An example of the response message Sending of warning messages was switched Sending of the alarm SMS messages off from number 310123456789 was disabled from the phone number 420123456789 An error occurred while switching sending The error occurred saving of the of warning messages off parameter didn t succeed Attention If this setting is performed successfully the response message will be sent not only to sender s phone number but also to all phone numbers for the warning SMS messages recipients ATAI MAG 23 If the value to store is the same as the original already stored value executing the command will have no effect In this case the modem will only send back the same information as in the case of Information about permitting of the alarm SMS messages So if only the information is sent back thou
15. d GPRS must be activated on your SIM card Method and amount of payment for this service are determined by valid trading conditions 3 2 Additional accessories The setting cable AT AC NULL The cable is intended for setting of the modem with the program for data loggers from the computer via RS232 serial link It is needed for service purposes only possibly for local settings of the modem during its activation for example if the GPRS connection is not activated Using of standard RS232 crossover cable as current computer equipment is alternative variation New computers are not equipped with serial COM port generally For solution of this problem the converter AT USB232 RS232 USB is offered It is plugged between computer USB port and the setting cable After installing included driver a virtual serial port in the computer is created for communication with the instrument e The self adhesive Dual Lock TRA A C04 The industrial hook and loop fastener for easy installation of the modem on a flat surface e The modem wall holder GPRS ACO1 The modem wall holder includes 2 screws for mounting on the back side of the modem and set of 2 pieces of wall plugs 2 pieces of screws for mounting on the wall Attention This type of mounting MAY NOT be used if the modem is operated in a vehicle The metal covering of the modem is conductively connected with negative pole of power supply Therefore it cannot be conductively connected with a v
16. damage of three side devices or electric trauma N D x 8 Risk of electric shock Do not use the instrument without the cover Use only a safety adapter with the power voltage recommended by device manufacturer Before connecting check that the adapter has undamaged cables and cover Do not use the instrument if it does not work correctly If the instrument seems not to work correctly have it checked by a qualified service person Qualified service and installation Service should be performed by a qualified person only We recommend you use only original accessories to avoid possible damage When connecting to any other device read its user guide for detailed safety instructions Do not connect incompatible products It is forbidden to connect other devices while the device is under electric voltage If a damage of the device occurs due to gross violation of these rules a free guarantee repair will not have to be executed Usage in hospitals When in a hospital or other health care facility observe the restrictions on the use of mobiles Respect the directions and switch the cellular device off on places where using mobile phones is forbidden Medical equipment may be sensitive to RF energy Switch off in aircraft Switch off the cellular device before boarding an aircraft Make sure it cannot be switched on inadvertently The operation of wireless appliances in an aircraft is forbidden to prevent interference with communications sy
17. ed An error occurred while accessing the The error occured clearing the list of the alarm phone numbers list of phone numbers didn t succeed ATAI MAG 25 5 3 The alarm SMS messages These messages are being sent to the predefined phone numbers independently of the user see the chapter Settings of the communication with the modem and the modem parameters on page 29 The information that the alarm is active and information about correct operation of the data logger can be periodically taken from the data logger by the modem Concretely following states are monitored depending on the connected data logger the measured value exceeds the alarm limit the alarm is active the binary input state is equal to the chosen state the alarm is active data logger type detection failed communication error the data logger state switched on off the data logger real time clock error the data logger memory is 90 full the data logger memory is full the expected data logger battery life expired the data logger battery voltage is too low If GPRS connection isn t activated you will have to set up the alarm SMS messages parameters by using the setting cable Following parameters must be set with the program for data loggers e data logger reading interval e sending no sending of the warning SMS messages e phone numbers for the warning SMS messages recipients 5 3 1 Active alarms of the data logger Exceeding of the alarm
18. ehicle chassis ground e The modem DIN rail 35mm holder GPRS ACO2 The modem DIN rail 35 mm holders include 4 screws for mounting on the back side of the modem De nel tee ts Si a A No aan aa AN Attention This type of mounting MAY NOT be used if the modem is operated in a vehicle The metal covering of the modem is conductively connected with negative pole of power supply Therefore it cannot be conductively connected with a vehicle chassis ground ATAN AIA 9 4 Quick installation 4 1 Check of accessories Make sure you have available all accessories needed to operation the SIM card the GSM antenna the power supply adapter and the COM adapter IP65 or the connection cable kit according to the data logger the data logger the pay version of program for data loggers and access to the M2MTalk server service if you want to use it 4 2 Software installation Install the paid version of program for data loggers minimally the version 2 2 18 0 see also the page 7 on the computer from what you want to have access to the device The latest program version is available on www atal nl Please follow instructions of the installer during installation process If you have activated GPRS data services you will use the GPRS connection for setting of the modem In this case installation of any others drivers is not needed If you want to set up the modem by using the setting cable via RS232 interface for example wh
19. en you have not activated GPRS data services you must also install driver for GPRS modem configuration which is available on above web address too 4 3 The modem assembling 4 3 1 The SIM card You must have activated a GPRS data services if you want to communicate with the data logger remotely via GPRS If the modem and the data logger are operated in a vehicle it is necessary to have in mind that mobile operators will be allowed to change while crossing borders of various countries If you also want to communicate with the data logger remotely via GPRS in a foreign network you must have activated GSM and GPRS roaming data roaming on your SIM card Moreover the GPRS roaming contract must be concluded between home and foreign mobile operators It is advisable to ask the home mobile operator about it even before going abroad When in use GPRS roaming mode GPRS transferring prices can be markedly higher than in the case of a home network A PIN code entering must be deactivated on the SIM card Using the SIM card in any mobile phone is the simplest method how to make sure that a PIN code entering is deactivated If a demand for entering a PIN code is displayed after switching the mobile phone on you will have to deactivate a PIN code entering This procedure is dependent on a type of the mobile phone and it should be described in a mobile phone s user manual The SIM card is put in a holder The holder is a modem component The holder i
20. erated in a vehicle it will be necessary to use the cable for voltage distribution between the data logger and the modem For more detailed information see the chapter The data logger and the modem interconnection on page 12 4 3 4 The data logger and the modem interconnection The ATV or ATX data logger and the modem interconnection is provided with the COM adapter IP65 Connect the adapter connector to the RS232 connector on the modem and plug the adapter to the guide slots on the side of the data logger Heed to keep a minimum distance between the modem antenna and the data logger during installation to prevent the data logger interference This distance may not be in any case less than 50 centimeters Keeping the distance at least 1 meter is recommended The correct way to connect is shown in the picture given below Lmin 0 5m The ATV or ATX data logger the modem and other accessories interconnection ATAI 12 MAG The ATP data logger and the modem interconnection is provided with the connection cable kit ATP ACI0 Attention The metal covering of the modem is conductively connected with negative AN pole of power supply Therefore it cannot be conductively connected with a vehicle chassis ground Use the self adhesive Dual Lock TRA AC04 for mounting of the modem on a vehicle The cable for voltage distribution between the data logger and the modem must be cut to proper length Strip the insulation from the end of the wi
21. ers ssecesccesscecoeeeseeeteecenserconeescetseeeenseneonteeensaes 35 6 3 Setting of the modem using the setting Cable eee ceessecesneeceeececeeeeeceeeeeceeeeeseteeeeneees 35 Te Technical specification b yi ke a kk a n E a E a I dan kk 36 7 4 Techmcal PATAME ENS s kt tise ca bk kk kb ko kk pa e kl a koke e ba ii pik aa bije 36 T2 Themodem TSE ACC sisri e ia e t a ki a pa n n a kk ia nn eka kika aa 36 7 3 A directory information about dimensions with the GSM antenna GSM ANT 37 7 4 Dimensional drawing for a wall mounting of the modem with GPRS ACOQI 37 7 5 Dimensional drawing for a DIN rail mounting of the modem with GPRS AC02 38 7 6 Description of the indicator LEDS ssessesseeseesressessessrserssressresrestensessterresstesreseeeseeseessessre 38 S Technical SUpport gees ta ene en ve kon te seen E A TERR 39 95 EGWI AN on kika bak ech cecal a n a E ea AR T E di 39 ATAN AIH 3 1 Description of working of the modem The modem is intended for remote communication with data loggers ATV ATX ATP via cellular network GSM In light of a customer this way of communication offers the same functions like a direct connection between the data logger and the computer for example by using COM USB adapter The modem can be set and controlled with a program for data loggers and also with SMS messages but with restrictions It is possible to select phone numbers from which S
22. escription of the data logger location is displayed If this description isn t set the serial number of the data logger will be displayed If the total message length would exceed 160 characters the serial number of the data logger will be displayed instead of the description ATAI 16 MAG e measured values of single quantities and current binary inputs states the channel number or channel description if it is set is displayed If a measured quantity is assigned to the channel the measured value and the quantity unit will follow If a binary input is assigned to the channel the user s description of the current binary input state will be displayed The response message example Logger Store 13 Temp1 24 7C Temp2 25 0C Bin1 OFF Bin2 ON If it is not possible to take information about the values i e the data logger is switched off a communication error between the modem and the data logger has occurred or detecting of the data logger type is in progress the modem will send back a SMS message with a proper error description The command values The command for reading of the current values An example of the response message Logger Store 13 Temp 24 7C Hum 45 5 RH The current values from the data DP 12 1C logger ATV or ATX Logger Store 13 Templ 24 7C Temp2 The current values from the data 25 0C Binl OFF Bin2 ON logger ATP The logger is switched off A query can t be processed be
23. f the current values and their alarm settings An example of the response message 12345678 1 24 7C 19 0 26 0 2 The current values and their alarm 45 5 3RH 0 0 50 0 6 12 1C 0 0 10 0 settings from the data logger ATV or ATX 12345678 1 24 7C 19 0 26 0 lm 2 current values and their alarm 25 0C 10 0 24 0 2m 3 OFF 1m 4 ON tings from the data logger ATP 10m The logger is switched off A query can t be processed becaus the data logger is switched off An error occurred during communication A query can t be processed becaus with the logger a communication error between the modem and the data logger has occurred Data logger type detecting is still in A query can t be processed becaus progress please try it later detecting of the data logger type is just in progress It is necessary to repeat the command later 5 1 3 The query about the modem firmware version To take the modem firmware version send the SMS message firmware to the modem The command Firmware The command for reading of the modem firmware version An example of the response message Datalogger Communicator v 1 1 0 The modem firmware version 5 1 4 The query about the current modem state information To take the current modem state information send the SMS message gsmstatus to the modem The modem will send back a SMS message with followed information The command for reading of the current modem state inf
24. for communication with the data logger you will be allowed to set up the data logger remotely by using the program for data loggers For the remote connection you must select the item Select port manually in the window File Options Communication and confirm it with pressing OK button Then select the item Configuration Device setting in the main menu Choose the correct communication port name from the displayed list If you don t use GPRS connection for communication with the data logger you will be allowed to set up the data logger locally via the proper communication adapter COM adapter IP65 USB adapter Use the program for data loggers to set up data logger Attention The serial communication interface of data logger ATP is out of service while the data logger is connected with a computer via a USB communication cable It means that communication between the data logger and connected GPRS modem will not proceed during this period 6 3 Setting of the modem using the setting cable If GPRS connection isn t available you will have to use the setting cable for setting up the modem with no limitations In this case the program for data loggers must be run with the parameter service The available way how to achieve it click on the button Start select the item Run then select the item Browse find the program LOGGER EXE in your drive if the destination of this program wasn t changed during installation it will be placed in
25. gh the user entered the setting command it means the parameter 1s already set as required it wasn t needed to change it 5 2 10 Information about numbers for the alarm SMS messages If the SMS message alarms without any parameters is sent the modem will send back the SMS message with the list of all phone numbers for the warning SMS messages recipients The command alarms The command for reading of information about phone numbers for the alarm SMS messages An example of the response message The list of the alarm phone numbers The list of the phone numbers is empty empty The list of the alarm phone numbers The list contains phone numbers 420123456789 420987654321 420123456789 420987654321 5 2 11 Adding a number for the alarm SMS messages This command is intended for adding the current sender s phone number to the list of phone numbers for the warning SMS message recipients The list can contain up to 8 phone numbers The command alarms The command for adding a phone number for the alarm SMS messages An example of the response message The alarm phone number 420123456789 was The sender s phone number was added added to the list to the list The alarm phone number 420123456789 is The sender s phone number was not already contained in the list added to the list because this number already occurs in the list The list of the alarm phone numbers is The sender s phone number was not alread
26. gram for data loggers is used for setting of these parameters If GPRS connection isn t activated you will have to set up the modem by using the setting cable There are these parameters e data logger reading interval see the chapter 6 1 on page 29 e sending no sending of the warning SMS messages see the chapter 6 1 on page 29 e phone numbers for the warning SMS messages recipients see the chapter 6 1 on page 29 e phone numbers from which the incoming SMS messages will be accepted by the modem see the chapter 6 1 on page 29 e setting of the alarm conditions for the data logger if this functionality is required see the chapter 6 2 on page 35 ATAI MAG 15 5 Communication via SMS messages It is possible to control and monitor the device operation remotely via the special SMS messages which are being sent to the modem phone number The user can select phone numbers from which the SMS messages are accepted by the modem The factory configuration doesn t restrict the phone numbers for any incoming SMS messages that means any SMS messages are accepted regardless of the sender phone number Phone numbers restriction can be done with the program for data loggers see the chapter Settings of the program for data loggers to use it with the modem on page 29 Generally SMS command messages aren t case sensitive and the space serves as a parameter separator If the accepted command isn t supported or it hasn t a correct synta
27. ii ai 8 Whe setting cable ATRACAN III LI e seosotiaaionesinbs sona dsa bean abse sians kaa nkoddasd spo byaso io daya seke 8 e The self adhesive Dual Lock TRA ACO4 0vrerieetesetesayresteistosanpossonssdsssssosoannananisavoseesdrisote 9 e The modem wall holder GPRS ACO was seoebadadaseke desas tense bas noon kas roda desa tate bat iye sosa bade sesi 9 e The modem DIN rail 35mm holder GPRS ACO Z L 00L0ereteerooororoooaoossooooaoosonoonaoonooononoon 9 Ay CVI TAS aOR ii l a t ank al lk kk a a pak a ak alan a a a ik tk ka a kk al ke pk a ik ka 10 4 15 Check of ACCESSONIES ssiri ia eat aso e eee alan kk an a kaba pa ab a kes ai bo me ie 10 4 2 S ftWate OL CUO do oi Aa aj e a ka aaa e ana pla pe bj dedan jo ak ip Akan 10 4 3 Themodem ass mibling ki a be ap kan da kn ba ki e a t a ay e aa ke rate dim e opa 10 4 3 1 The SIM Card soon aki kk k d ak n s AEA Ea kk ko pa ok kk a kk anba ei ba 10 4 3 2 The GSM antenna bo eee kou do pen ok n ia n bo akte la de n pi ian eka bak an dokte e sake si ken aa dis 11 4 3 3 Connecting the power supply to the MOdEM eee eeeeeseceseetereesneessaeceseeeseeeaees 11 4 3 4 The data logger and the modem interconnection eeeeeeesseeesneceeeeeeeeeeaeecsaeeneeees 12 44 Switching on the TING OUI el ka fia ia kask esa na i a aa ason a ay n 14 43 SOUE Up the OU seek a lin ki dele en ko ek a repa eee 14 4 5 1 Setting of GPRS connection parameters seeeeeseseseeseeserereeree
28. ith your entered password Remember this password well it will have to be entered during setting of the modem later Continue with pressing Modem configuration button Communication with the modem begins If all previous settings are correct a following window will be displayed If not please check the settings described in the chapter Settings of the communication with the modem and the modem parameters on page 29 ATAN AIH 31 amp GPRS modem settings lel x M2MTalk server Insert parameters to establish connection between modem and M2M server This information is delivered to every modem lv M2M communication On Off Account Auto login to M2M server IV Ser Password talkserver m2msensor com 9999 Modem address 2003 Security communication key M ySecureKey EA _ Next gt ieee X Cancel In this window enter Security communication key according to setting in the window M2M port properties on page 31 If you require the modem s login on the server automatically after it s switching on so that GPRS communication can be available you will have to tick off the field Auto login to M2M server Don t change other parameters in this window gratuitously it can cause problem with communication After pressing Next gt gt button the window for settings of phone numbers restriction for communication via SMS messages will be displayed ATAN 32 AIH amp GPRS modem settings Oe x
29. n that the alarm is active and information about correct operation of the data logger can be periodically taken according to the item Check alarm status from the data logger by the modem These information are processed and then the modem sends alarm SMS messages to a customer according to these analyses If you require sending of the warning SMS messages by the modem you will have to tick off the field Send warning SMS and enter the phone numbers for the warning SMS messages recipients Attention Sending of warning SMS messages from the modem can be temporarily suspended during the executing of some operations which involve data transfers A between the data logger modem and remote computer e g downloading data from a data logger In such cases the SMS messages are stored in a queue and are sent after the operation is finished After pressing Apply button all settings are stored into the modem and then the modem will be restarted Confirm all opened windows with pressing OK button ATAN 34 AIH 6 2 Setting of the data logger parameters If you require sending of the warning SMS messages by the modem for example in the case of exceeding of the alarm limits you will have to set these data logger parameters at least e the data logger must be switched on e the alarm conditions must be set with desired means for all monitored channels e the alarm evaluating must be enabled for all monitored channels If you use GPRS connection
30. ormation An example of the response message Uptime Od Ohr 26min M2MTalk online Elapsed time from the modem s yes Operator T Mobile CZ T Mobile switching on CZ RSSI 66dbm Signal 99 Registered on The current M2MTalk server login network yes Roaming no status The name of GSM operator The signal strength dBm The signal quality The SIM card registration on the cellular network GSM The SIM card registration on the foreign network it says if the roaming is active ATAI 18 MAG 5 2 The statement SMS messages Using these messages you can control and set up the modem remotely 5 2 1 Login on the M2MTalk server If you intend to use remote communication with the modem or data logger via GPRS for example to set up this device remotely the modem always must be logged on the M2Mtalk server before starting the communication The modem can be set up to login on the server automatically after its switching on but it isn t a standard factory setting To login the modem on the M2MTalk server you can send a SMS message login to the modem phone number The modem will send back an acknowledge SMS message The command for login on the M2MTalk server The response message The demand for login on the server was Information about acceptance of accepted demand for login on the M2MTalk server This module is already logged on the The messag the modem was already server logged on the M2M
31. out the GPRS connection settings 0 0 0 cceeseeceeseeceeeeeceeeeeceteeeesteeeenaes 20 52 3 Setting of the GPRS CONNEC IM k k koka sis irine E EEE E Sn 20 5 2 6 Information about the M2MTalk server connection settings ccceeeeeeeeseeeeeeeeeeeees 22 52T Setting of the M2M Talk server connection ei ewo pok kiba ba ponk laa aka ld kb ik anan 22 5 2 8 Information about permitting of the alarm SMS messages 23 5 2 9 Setting of permitting of the alarm SMS messages c cccesseeceeceeceeeeeceeeeeceteeeesaeees 25 5 2 10 Information about numbers for the alarm SMS message L rreeveeeeeeooresoorosasooosone 24 ATAN 2 ATAL 5 2 11 Adding a number for the alarm SMS messages eeseeeeceeeeeeneeeeseeeeeeeseeeeneeeaeens 24 5 2 12 Removing a number for the alarm SMS message ec ceeceeceeesceeeteeeeeeeeeeeeneeeaeens 25 5 2 13 Removing all numbers for the alarm SMS messages ssseesecseseeseesrsererersererrrresee 25 5 3 The alarm SMS M SSAZESi ciisto biye kt da kaa yn vo ko dp ka EE kek EAEE SERERE R 26 5 3 1 Active alarms of the data logger anis s as ao daso pans Eklere sy see kota as kanva di saaa 26 JI Other data logger states fen bk kk a e ay sok kb a ai e ko NN 27 6 Settings of the program for data loggers to use it with the modem eee eee esse eseeeneeeees 29 6 1 Settings of the communication with the modem and the modem parameters 29 6 2 Setting of the data logger paramet
32. program for data loggers to use it with the modem Attention If GPRS connection isn t available you will have to use the setting cable Move ahead the chapter Setting of the modem using the setting cable on page 35 All following parameter settings are mentioned for an information only the correct values must be entered everywhere 6 1 Settings of the communication with the modem and the modem parameters Run the program for data loggers Select the item File Options in the main menu In the window Options select the item M2M connection on the left bar first A following window will be displayed 8 Options OF Xx Data storing Communication Data presentation Connection parameters M2M connection Autodownload Server talkserver m2msensar com M2M connection PC to M2M server PC s M2M address 2002 M2M login password 2220 p Connection test ce The items Server and Port are already pre filled don t change it gratuitously Fill the items PC s M2M address a M2M login password with data listed in the card which was delivered with the modem Confirm these settings with pressing Apply button Further in the window Options select the item Communication on the left bar A following window will be displayed ATAI FAIR 29 8 Options OF Xx Data storing Communication Communication Po Data presentation Serial ports Device models M2M connection C Search all serial port
33. res and twine it with separated insulated conductors of the supply line Be careful of the polarity The supplied contact tubes must be forced on the pairs of twisted stripped wires This preassembled set must be connected to a supply terminal block of the data logger On the modem side the contact tubes were already forced on the wires at the factory The correct way to connect wires for the feeder cable is shown in the table given below Connection to a supply terminal Connection to a supply terminal block of the data logger block of the modem red stripped the positive pole terminal U the positive pole terminal the negative pole terminal GND the negative pole terminal The connector of the communication cable must be connected to the RS232 connector on the modem and the wires of this cable must be connected to the supply terminal block on the data logger The correct way to connect wires for the communication cable is shown in the table given below a Connection to a supply terminal red yellow TxD black brown RxD GND Heed to keep a minimum distance between the modem antenna and the data logger during installation to prevent the data logger interference This distance may not be in any case less than 50 centimeters Keeping the distance at least 1 meter is recommended The correct way to connect is shown in the picture given below Lmin 0 5m The ATP data logger the modem and other accessories interconne
34. s Autodownload i vo Dataloggers He Se new C Search only ports BlackBoxes with or without display MM Mi vo Dataloggers BlackBou types L on Mains failure loggers dor Commeter D ka fe Select port manually List of ports co Select the item Select port manually and press the button List of ports The window List of communication ports will be displayed List of communication ports Name interface vpe COM1 Com1 Serial 1 COM2 Add port Delete port if Properties vo xc In this window press the button Add port The window Add communication port will be displayed ATAI 30 fot Fat Add communication port p Interface type J C Serial port COM C LAN Adapter C GSM Wavecom modem Select the item GPRS M2M modem here and then press the button Next gt M2M port properties f x Name required m2m7 alk Address 2003 Secure communication key M ySecureKey I Autodownload Modem configuration J OK X Cancel The window M2M port properties will be displayed Set the connection parameters for the modem here The item Name is intended for user s description of connection choose your own name Fill the item Address with data listed in the card which was delivered with the modem If you want to prevent unauthorized access to your modem data logger you will have to fill the item Secure communication key w
35. s for the SMS messages GPRS isn t connected GPRS connection is active i e it is possible to communicate with the data logger remotely the modem replies for the SMS messages the SIM card is not inserted a PIN code isn t deactivated on the SIM card the GSM antenna isn t mounted searching for the network is in progress login to the network is in progress 8 Technical support Technical support is provided by a distributor of this device 9 Liquidation The device must be liquidated ecologically after its disconnecting 39
36. s ejected by pressing the button beside the holder by using a fit instrument for example a pencil Insert the prepared SIM card into the holder See that the SIM card stays in alignment with the holder correctly for all its size After it the holder with the inserted SIM card is pushed in the modem The correct way to install the SIM card is shown in the picture ATAI 10 MAG The way to install the SIM card 4 3 2 The GSM antenna The GSM antenna must be mounted to the antenna connector by lightly tightening a sleeve nut 4 3 3 Connecting the power supply to the modem The power supply is connected on a WAGO terminal block which is a modem component Insert a flat bladed screwdriver to rectangle terminal hole and push the screwdriver towards away from you the contact is released Connect a wire to the released terminal and close the terminal by removing the screwdriver Connect positive pole of the terminal marked with and negative pole of the terminal marked with The correct way to connect wires is shown in the picture given below Way to connect wires The entire terminal block is possible to remove from the modem by pulling it up from the connector ATAI AIAL 1 In the case of using the power supply adapter PS ATM connect the white wire to positive pole and the black wire to negative pole m oe D Connecting of power supply adapter PS ATM If the modem and the data logger ATP are op
37. start of the modem for example in the event of the problem with GPRS connection The complete restart of the modem takes about 2 minutes The command The command for restart of the modem The response message The demand for application restart was Information about acceptance of accepted demand for restart of the modem 5 2 4 Information about the GPRS connection settings If the SMS message gprs without any parameters is sent the modem will send back the SMS message with information about the current GPRS connection settings The command The command for reading of information about the GPRS connection settings An example of the response message APN internet User Password DNS Information about the GPRS connection settings 3 2 3 Setting of the GPRS connection The first word of the message must always be gprs After this keyword parameter values for an actual setting follows in specific order gprs apn user password dns If the trailing parameter values are not entered they will be deleted Don t enter the square brackets in the SMS message Individual items of the message must be separated by spaces The meaning of the parameters is following e apn the access point name e user the user name for login e password the password for login e dns the DNS server name or IP address If any of the parameters user password or dns are not entered from the back they will be always deleted
38. stems ATAI ATAL 5 Avoid fire and explosion Do not use the instrument in an explosive environment Do not operate the cellular device in the presence of flammable gases or fumes Switch off the cellular device when you are near petrol stations fuel depots chemical plants or where blasting operations are in progress Operation of any electrical equipment in potentially explosive atmospheres can constitute a safety hazard Interference Your cellular device receives and transmits radio frequency energy while switched on Remember that interference can occur if it is used close to TV sets radios computers or inadequately shielded equipment Always switch off the cellular device wherever forbidden or when you suspect that it may cause interference or danger Service availability Devices operate using radio signals and cellular networks Because of this connection SMS GPRS etc cannot be guaranteed at all times under all conditions Therefore you should never rely solely upon any wireless device for essential communications emergency systems safety related systems Remember for hi reliability systems is redundancy necessary For more information please see IEC 61508 3 The modem and its accessories To use the entire facility not only the modem but proper accessories are also required 3 1 Accessories needed to operation The SIM card The SIM card is necessary for correct modem operation It makes possible
39. sttsrerrersersrerreesresersereess 14 4 5 2 Setting of M2MTalk client parameters cee ses das bs cesisecnseutd den cmdenda condeedencedavcnumeldeecndenates 14 4 6 Login the modem on the M2MTalk SETVOT sccccccccscccscsesscessscescecesseeceseestscdscsesntenssnvstdenasvde 15 4 7 Setting of the other parameters ok efo Heres ba kolan ea cedaseeteedaaatuaatesoeeetesasbeedncesteeuies 15 5 Communication via SMS messages s wa ouedv koedkd sa sevo eski don dwan t m si api sansa ks pass slap 16 5 1 Thequery SMS Messages vi wiieeb t bato baze pbdlis eki ak pi kw k rand kb ki a kek ons pk aso kin lipa ak es iisas 16 5 1 1 The query about the current values sovzeyokasasos koy boz asa s kn easy daanis ket aysssdl aspire e fk kitan dose 16 5 1 2 The query about the current values and their alarm SCttiDNQS vreerveroreororooonnooone 17 5 1 3 The query about the modem firmware version sssssreeseesrssrisresressrssresrersersrerreeseese 18 5 1 4 The query about the current modem state information seeseseeeeeeeeererersrrerresrreeee 18 5 2 Che Statement SMS Messages uerrini bos io ii a la an aa eee 19 5 2 1 Login on the M2MfTalk servet 3e 4e459lbseyos peso boss says yes kisia asse skaa sese fia ad oke disa bad 19 5 2 2 Logout from the M2MTalk server 44e se detan ask api byin ta ba bat ky ak a ki na a a 19 5 2 3 Restart of the Modem ii en p t onase beyen klik bout kai fe kek ka PC kk a pp ka isi k aba 20 5 2 4 Information ab
40. t likely communication between the data logger and the modem will not be functioning properly Communication error The incoming alarm SMS message An error occurred during communication An error occurred while with the logger communication between the modem and the data logger The data logger state switched on off data loggers ATV ATX only The incoming alarm SMS message The logger is switched off The data logger is switched off The incoming alarm SMS message The logger is switched on The data logger is switched on The data logger real time clock error The incoming alarm SMS message The logger real time clock error The data logger real time clock isn t adjusted correctly The data logger memory is 90 full data loggers ATV ATX only The incoming alarm SMS message The logger memory is 90 full The data logger memory is 90 full ATA UE LAG 27 The data logger memory is full The incoming alarm SMS message The logger memory is full The data logger memory is full The expected data logger battery life expired data loggers ATV ATX only The incoming alarm SMS message The end of the expected logger battery The expected data logger battery life life expired The data logger battery voltage is too low data loggers ATV ATX only The incoming alarm SMS message The logger power supply is low The data logger battery voltage is too low ATAI 28 AIAL 6 Settings of the
41. ter values for an actual setting follows in specific order see below gprs apn user password dns If the trailing parameter values are not entered they will be deleted Don t enter the square brackets in the SMS message Individual items of the message must be separated by spaces For more detailed information about setting this parameter values via SMS command see the chapter Setting of the GPRS connection on page 20 The example You can set up the parameter apn to value internet without other parameters user password and dns by sending the SMS message gprs internet For getting information about GPRS connection parameters please contact an appropriate mobile operator 4 5 2 Setting of M2MTalk client parameters These parameters are already preset at the factory don t change it gratuitously If you can verify a setting compare it with data listed in the card which was delivered with the modem M2MTalk client parameters can be set via the SMS command see the chapter Setting of the M2MTalk server connection on page 22 or via the setting cable see the chapter Setting of the modem using the setting cable on page 35 ATAI 14 LAG 4 6 Login the modem on the M2MTalk server If you intend to use remote communication with the modem or data logger via GPRS for example to set up this device remotely the modem always must be logged on the M2Mtalk server before starting the communication The modem can be set up to login on
42. the directory C Program Files AtaNLoggenLogger exe select it by using the mouse and click on the button Open In the displayed field Open write the char space followed by parameter service at the end of displayed path past the quotation mark Then click on the button OK After program start the submenu Service should appear in the main menu Select the item M2M modem in the submenu Service Choose the correct COM port number and confirm it with pressing OK button Now you can set up all modem parameters with no limitations ATAI MAG 35 Communication with the device Frequency band Output power SIM card type GPRS class Antenna Supply terminal block IP code Operating conditions Storage conditions Dimensions Weight Box material 7 Technical specification 7 1 Technical parameters RS232 connector Canon 9 for the COM adapter 850 900 1800 1900 MHz Class 4 33dBm 2dB for EGSM850 Class 4 33dBm 2dB for EGSM900 Class 1 30dBm 2dB for GSM1800 Class 1 30dBm 2dB for GSM1900 1 8V or 3V multislot class 12 50 ohm SMA connector removable WAGO 734 max size of conductors 1 5 mm IP30 The power supply external 9 32V DC peak input up to 10W The operating temperature range from 30 C to 65 C External characteristics determination by EN33 2000 3 Environment standard as per NM with these corrections AE1 AN1 ARI BEI Operating position arbitrary Device mounting optional
43. to send SMS messages and to communicate with the data logger remotely via GPRS In addition GPRS data services must be activated for data transferring via GPRS If the running modem is used among areas with different mobile operators GSM and GPRS roaming data roaming must be also activated Method and amount of payment for these services are determined by your mobile operator A PIN code entering must be deactivated on the SIM card For more details see the chapter The SIM card on page 10 The GSM antenna The GSM antenna is also necessary for correct modem operation the facility doesn t work without it It must be mounted into antenna SMA connector It is possible to use the compact GSM antenna GSM ANT which is offered by the manufacturer In case of need an external GSM antenna can be used The electric power supply The modem must be powered from an external power supply a power supply adapter an accumulator battery A power supply is connected to a supply terminal block The supply terminal block is a modem component It is possible to use the power supply adapter PS ATM which is offered as optional equipment by the manufacturer The COM adapter IP65 ATXV ACOIX for data loggers ATV ATX The adapter is intended for the ATV or ATX data logger and the modem interconnection via RS232 serial link This adapter provides a communication between the modem and the data logger The length of the cable is cca 160 centimeters J
44. x or parameters the modem will send back an SMS message with a proper error description This information will be returned only three times in maximum The fourth and every next incorrect command from the one phone number is ignored until the incoming command will be correct again 5 1 The query SMS messages Using these messages you can take the current measured values from the connected data logger the modem firmware version and the current modem state information 5 1 1 The query about the current values To take the current measured values from the connected data logger send the SMS message values to the modem If a data logger ATV or ATX is connected to the modem it will send back a SMS message with the following contents e data logger identification the user s description of the data logger is displayed If this description isn t set the serial number of the data logger will be displayed If the total message length would exceed 160 characters the serial number of the data logger will be displayed instead of the description e measured values of single quantities the channel number or channel description if it is set is displayed the measured value and the quantity unit follow The response message example Logger Store 13 Temp 24 7C Hum 45 5 RH DP 12 1C If a data logger ATP is connected to the modem it will send back a SMS message with the following contents e data logger location the user s d
45. y full added to the list the list is already full An error occurred while accessing the The error occured adding the list of the alarm phone numbers sender s phone number didn t succeed ATA UE 24 LAG 5 2 12 Removing a number for the alarm SMS messages This command is intended for removing the current sender s phone number from the list of phone numbers for the warning SMS message recipients The command alarms The command for removing a phone number for the alarm SMS messages An example of the response message The alarm phone number 420123456789 was The sender s phone number was removed from the list removed from the list The alarm phone number 420123456789 was The sender s phone number was not not contained in the list removed from the list because this number was not found in the list An error occurred while accessing the The error occured removing the list of the alarm phone numbers sender s phone number didn t succeed 5 2 13 Removing all numbers for the alarm SMS messages This command is intended for removing all phone numbers from the list of phone numbers for the warning SMS message recipients So the list of phone numbers will be cleared completely The command alarms The command for removing all phone numbers for the alarm SMS messages The possible response messages All alarm phone numbers were removed from The list of phone numbers was the list clear

Download Pdf Manuals