1. AIRFLOWS OCCUPIED MIN ts MAX 40I s UNOCCUPIED gt s s MIN 511 s EL DUCT HEATER MIN Ol s AIRFLOW 14I s AIRFLOW SET 151 s DAMPER POS 32 COMMISSIONING MODE MAX FLOW VALVE COMM MODE INACTIVE PRESSURE SENSOR FLOW PRESS 45 2Pa 0 CALIB 1 4Pa DAMPER STROKE 55mm AIRFLOWS OCCUPIED This function is for setting the MIN and MAX max airflows in l s for the current product in occupied mode A Product marked with Default in the designation indiccates it is a stocked product with standard settings that most likely are not applicable to the current installation AIRFLOWS UNOCCUPIED The lowest airflow during unoccupied mode AIRFLOWS EL DUCT HEATER The min flow of the electric duct heater this value only applies to version 5 1 1024 or later If the function is activated i e set to a value higher than O l s the control ler will interpret this as an indication that the heating coil is located in the supply air duct If heating is required the min airflow will then be increased to the setpoint value The setpoint airflow should be adjusted to the setting that the air heater requires as its min airflow AIRFLOWS AIRFLOW The actual airflow through the product value in l s AIRFLOWS AIRFLOW SET This is the estimated setpoint calculated from the cooling heating demand in percent from the working area between the min and max airflow www swegon com TUNE
2. COMMISSIONING i LANGUAGE gt ADVANCED MENU TEST MENU At startup the unit displays a list of available menus The uppermost row is always reserved for the name of the currently displayed menu In root level the top row shows a Swegon header in later version also including the software version of the hand held unit Scroll by using the arrow keys to access the desired menu A selected row is indicated by highlighted text with dark background Use the ENTER button to confirm selected option or to continue into a desired submenu In some cases a confirmation is required YES NO before entering the selected submenu In the far right end of the display a scrollbar indicates if more menu rows are accessible in the list Use the arrow buttons to scroll up or down in the list USER MENU TUNE ADAPT V6 0 Fuser menu USER MENU AIRFLOW AIRFLOW SET 00 s ROOM TEMP 00 0 c SUPPLY TEMP 00 0 c CAC LEVEL 0 CAC CO EQU Oppm RH LEVEL 0 COOL VALUE 0 HEAT VALUE 0 HEAT VALVE POS 0 SLAVE OUTPUT 0 EXTERNAL INPUT 0 SW VERSION 0000 SERIAL NO 00000 AIRFLOW Shows the current actual airflow in I s AIRFLOW SET Shows the airflow set point in l s Swegon reserves the right to alter specifications Swegon ROOM TEMP Shows the measured room temperature in C from either the built in sensor external DETECT SME or DETECT T In certain applications for example ADAPT Damper f
3. Displays status from the built in occupancy sensor 1 oc cupancy The value returns to 0 after 1 minute if no new occupancy has been detected OCC STATUS DELAY The occupied mode including the delay The value applies to the entire system of interconnected master slave air dif fusers including external occupancy sensors OCC DELAY OFF Occupancy switch off delay Delay time until the con troller switches to unoccupied mode provided no new occupancy detection has occured OCC DELAY ON Occupancy switch on delay Delay time before the controller switches to occupied mode This must always be set to 0 if lighting control is to be used Otherwise the recommended value is 30 sec OCCUPANCY Allows for forced control of the occupied mode from automatic AUTO to manual MAN If manual mode i selected OCC UNOCC should also be set manually to either unoccupied UNOCC or occupied OCC For an ADAPT Damper in master version without a built in occupancy sensor this value should be set to continu ous occupancy if a DETECT O is not connected NOTE If a slave damper of ADAPT Damper type is used the corresponding setting must also be performed in the slave Description refers to built in occupancy detector and is not valid for external detectors such as DETECT O OCC DELAY ON and OCC DELAY OFF must be set in the external detector see separate instructions for the specific product OCC STATUS does not display any da
4. TEMP MENU d TEMPERATURE MENU mM COOLTEMP OCC 23 c HEATTEMP OCC 21 c 4 COOLTEMP UNOCC 25 c HEATTEMP UNOCC 20 CALC SETP 22 0 c ROOM TEMP DEV 0 0 c NIGHTCOOL 18 c MORNING HEAT 25 C HEAT VALVE TIME 350s SUPPLY TEMP DIF 0K ALLOWED T 10K COOLTEMP OCC Cooling temperature when occupied i e the temperature at which cooling control begins If the system has sufficient capacity this will be the maxi mum room temperature in the cooling mode HEATTEMP OCC Heating temperature when occupied i e the temperature at which heating control begins This will be the room s lowest temperature provided that the product steers heating control If this is not the case the value is insignificant COOLTEMP UNOCC Cooling temperature when unoccupied same functiona lity as described for the cooling occupancy temperature HEATTEMP UNOCC Heating temperature when unoccupied same functiona lity as described for the heating occupancy temperature CALC SETP Displays the calculated avarage setpoint for regulation as a value between the heating and cooling conditions The value is dependant of the occupied or unoccupied modes These temperature readings are shown when the unit is opera ting either night time cooling mode or morning heating mode Swegon reserves the right to alter specifications 20130214 Swegon If TUNE T is connected influence from the TUNE T is dis played at 3 from
5. performed upon activation of emergency closing or opening of valves CLOSE OPEN Only adjustable when TUNE Adapt is connected to a master diffuser EQUAL REVERSED Only adjustable when TUNE Adapt is connected to a slave diffuser Chang ing the parameter while connected to a master diffuser has no effect on any slave diffusers in the system for these the parameter must be set individually for each slave CONTROL SETTINGS MASTER SLAVE 20130214 www swegon com TUNE Adapt ADVANCED MENU APPLICATION MENU Used for setting of the primary functions in the product The screen examples illustrate activated AIR COOL mode ADVANCED MENU TEMP MENU OCCUPANCY INT COMMUNICATION EMERGENCY MENU APPLICATION MENU ON APPLICATION NORMAL FUNCTION AIR COOL LED INDICATOR FUNCTION TEMP SENSOR USE TYPE 0 HEATING PRESENT ACTUATOR TYPE NORMALLY CLOSED COOL PROTEC ACTIVE LEVEL COOL LIMIT VALVE EXERCISE TIME INTERVAL 5d CAC USE NOT PRESENT VENT BOOST BOOST DELAY BOOST TIME CAC CO AT UNOCC NOT ACTIVE APPLICATION MENU 00 50 72h 5m APPLICATION Select the application that corresponds with the description in the table The application defines how the external input control of the master product is used in older versions the aplication is only indicatad by numbers 0 7 however the order corresponds to the table li
6. the calculated average value ROOM TEMP DEV Room temperature deviation the difference between the actual values and the calculated set points for cooling hea ting when occupied or unoccupied If TUNE T is used for set point displacement the change can be read in this menu only Example Cooling set point is 23 C and heating set point is 21 C At a room temperature or 22 5 C the value 0 5 K is displayed as deviating temperature on the nonconforming temperature line If TUNE T is turned down as much as possible for reduced room temperature the cooling set point will be 20 C and the value 2 5 K will then be shown This means that it is 2 5 K too warm in the room and that the cooling control function will start NIGHTCOOL Set point for night time cooling This set point applies when the night time cooling function is enabled from a BMS and results in boosting the airflow until the flow reaches its max airflow set point MORNING HEAT Set value for morning time heating of premises when the function is enabled from a BMS HEAT VALVE TIME Indicates the required time it takes for a thermal actuator to open completely from a cold position The time is used for the time proportional opening when the heating load is lt 100 If the product is to control electric heating via a semi con ductor relay the time should be set to max 60 sec SUPPLY TEMP DIF Control limit for the airflow Specifies the lim
7. Adapt AIRFLOWS DAMPER POS Displays the current damper blade position When com missioning make sure that this value is at least 85 open for the dimensioning product in the zone AIRFLOWS COMMISSIONING MODE This function is used during the commissioning and fun ction control phase At delivery all products ar set to MAX FLOW During commissioning each setting parameter must be set manually After completed commissioning the setting INACTIVE must be chosen The product then goes into normal operation Parameter Explanation Function INACTIVE Normal operation UNOCC FLOW The min flow set point of the product in unoccupied mode MIN FLOW The min flow set point of the product in occupied mode MAX FLOW The max flow set point of the product AIRFLOWS VALVE COMM MODE Enabling this feature keeps the valves open for 20 days ON 20 DAYS in order to allow ventilation contractors to perform venting and commissioning This function can also be used for valve control The function must be ma nually disabled INACTIVE after performing the control AIRFLOWS PRESSURE SENSOR Displays the current flow pressure FLOW PRESS This pres sure is almost identical to the static pressure drop across the air diffuser Zero calibration O CALIB can be carried out ho wever this requires that you are sure that there is no airflow Shutting the damper by forced control will not help 0 calibra tion has
8. INTERNAL DC 29 3V REBOOT CONTROLLER NO YES NO COMMISSIONING MODE This function is used during the commissioning and performance check phase COMMISSIONING MODE is also accessible via COMMISSIONING AIRFLOWS COMMISSIO NING MODE For more details on this feature see section AIRFLOWS COMMISSIONING MODE on page 4 TEST MODE Test of the damper position DAMPER POS MAN With this function the damper position can be manually steered to a fixed value within 0 100 Do not forget to restore the test mode to OFF setting after performing a test When the test mode is enabled the product LED flashes orange NIGHTCOOL This function is used for status reading and for testing of the night cooling function do not forget to set this fun ction to AUTO after completing the test MORNING HEAT This function is used for status reading and for testing the morning heat function do not forget to set this function to AUTO after completing the test INTERNAL DC Displays the internal voltage level of the controller the value should be inbetween 29 36 V DC in order to obtain correct functionality REBOOT CONTROLLER This function allows you to perform a restart of the control ler in the product when not performing as expected NO YES e g due to many functions beeing changed Restart via this function does not reset changed set functions 20130214 www swegon com
9. NTS CAC SENSOR FAULT COMFORT ALARM TEMPERATURE AIR QUALITY AIR HUMIDITY 0 ey DAMPER STROKE Indicates a damper stroke error at startup the product per forms a stroke check If this check fails an alarm is initiated MOTOR FAULT This alarm is activated if the actuator of the product can not reach the damper position within the detected damper stroke area PRESSURE SENSOR If the pressure sensor transmits unreasonable values or if communication to this sensor ceases an alarm is initiated ROOM TEMP Refers to failure of the built in temperature sensor or the temperature sensor fitted inside the sensor module SUPPLY TEMP Refers to failure of the built in temperature sensor fitted in the supply airflow path of the product WRONG SETPOINTS An alarm is initiated if the heating set point and cooling set point cross one another The heating set point must always be lower than the cooling set point CAC SENSOR FAULT Indicates that the built in sensor is faulty or is missing COMFORT ALARM Alarm is initiated if the comfort alarm is activated when either temperature TEMPERATURE CO value AIR QUALITY or air humidity AIR HUMIDITY deviates more than set limit values Swegon reserves the right to alter specifications 20130214 Swegon COMMISSIONING AIRFLOWS Menus for setting of all controller set points TUNE ADAPT V6 0 USER MENU ALARM MENU COMMISSIONING COMMISSIONING AIRFLOWS
10. TUNE Adapt User Manual Version 6 0 Functionality TUNE Adapt is a hand held unit for setting and viewing the readings of all airoorn ADAPT products As standard Tune Adapt is delivered with an english manual Manuals in additional languages corresponding to the avai lable language packages can be downloaded from www swegon com For specific information about available languages and language settings in the software please see LANGUAGE MENU section E Figure 1 Hand held unit TUNE Adapt Button Functions Symbol Name Function KS ARROW Scrolls up and down through the me up down nus in the display Confirms selection Press to enter a submenu In the setup menus ENTER is press 4 ENTER sed recurrently to change a variable The accessed variable can then be changed Changing a value in these cases is in stant pressing ENTER is not required Plus Minus Increases decreases values x CROSS Back return to previous menu or step Built in LED The unit has a built in red LED Emitted or flashing LED when connected to a product indicates that either com munication is broken or that supply voltage is too low Wait a minute or two and then reconnect TUNE Adapt For information on LED operation of sensor modules or products the unit can connect to see the sections regad ring the menus LED INDICATOR and ALARM MENU Compatibility TUNE Adapt in version 6 0 is backwards comp
11. abling the valve output for 10 minutes The function is activated as standard Activation takes place after the first occurance of detected occupancy after the deadline CAC USE Activation of the built in air quality sensor in ADAPT Dam per on the extract air duct NOT PRESENT USED VENT BOOST Enables the function for forced airflow during a shorter time 5 minutes when the product has operated in unoccupied mode longer than the set time 72 hours Parameter Explanation Function ON OFF Activation of forced airflow Time limit for activation of the ventilation BOOST DELAY boost function BOOST TIME Time duration for forced airflow in minutes CAC CO AT UNOCC Provision for enabling the CAC CO function when the ven tilation system is operating in unoccupied mode NOT ACTIVE ACTIVE TEST MENU Intended for mandatory ventilation controls The functions are used for commissioning and performance checks When TEST MENU is selected a warning is displayed to remind you to be particularly cautious changing any data in these menus could cause the control system to stop operating 8 Swegon reserves the right to alter specifications TUNE ADAPT V6 0 USER MENU ALARM MENU COMMISSIONING LANGUAGE ADVANCED MENU TEST MENU TEST MENU COMMISSIONING MODE MAX FLOW AIRFLOW 000I s TEST MODE OFF DAMPER POS MAN 0 NIGHTCOOL AUTO MAN AUTO MORNING HEAT AUTO MAN AUTO
12. atible with previous versions of airborne ADAPT products For versions older than 6 0 the following applies e TUNE Adapt of an older version can always read a newer airborn ADAPT product however the newer variables will then be lacking in the TUNE Adapt unit e TUNE Adapt of later versions cannot read older versions of airborn ADAPT products The hand held unit must not be mistaken for the unit supplied with the GOLD air handling unit which runs a different software Art No 1545 197 20130214 Connection The unit is connected with an RJ12 type cable and also powered by the product it is connected to See figures 2 4 for connection examples When the unit is connected to a product the communica tion to the SuperWise BMS is interrupted Figure 2 To open the sensor module use a screw driver Be careful when reinstalling the module to avoid damaging the positioning pins Figure 3 TUNE Adapt can be connected to an air diffuser by using the RJ12 contact on the circuit board Figure 4 TUNE Adapt can be connected to a duct damper by plugging the RJ12 cable directly into the single contact on the side of the damper Swegon TUNE Adapt Display and menu structure The TUNE Adapt screen can only display four rows of text In this manual menu examples are illustrated in grey when occuring outside of the screen and in black when appearing within the screen TUNE ADAPT V6 0 USER MENU i ALARM MENU
13. been carried out at the factory prior to delivery AIRFLOWS DAMPER STROKE Displays the detected stroke in millimetres for the product COMMISSIONING AIR QUALITY TUNE ADAPT V6 0 USER MENU ALARM MENU COMMISSIONING COMMISSIONING AIRFLOWS AIR QUA AIR QUALITY MIN SET 800ppm MAX SET 1000ppm PPMPERVOLT 200ppm CAC SETPOINTS MIN SET 25 MAX SET 35 RH SETPOINTS MIN SET 65 MAX SET 90 REP ERO 10 Swegon reserves the right to alter specifications Swegon AIR QUALITY CO DETECT Q This menu is for setting the trigger and end values for the proportional airflow control function in relation to the CO value Parameter Explanation Function MIN SET Lower limit for the start of proportional airflow control Sate Sha B MAX SET Upper limit 100 airflow for the proportio nal airflow control Specifies the ratio between the measured CO and volt signal to the product Normally this is 200 ppm V PPM PER VOLT AIR QUALITY CAC SETPOINTS Set point values for control of a VOC sensor Parameter Explanation Function Lower limit from which airflow increase starts in MIN SET re order to vent off contamination MAX SET Upper limit when airflow increase has reached its max value AIR QUALITY RH SETPOINTS Set point values for control of a humidity sensor Parameter Explanation Function MIN SET L
14. ce Orange solid Commissioning mode max airflow During forced control e g commissioning Orange mode forced max airflow forced min flashing airflow forced occupancy emergency or manual damper positioning Red solid Supply voltage is too low or a function alarm Red Green Comfort alarm too high or low room alternating temperature or insufficient air quality TEMP SENSOR USE from software version 5 or later This APPLICATION Explanation Function nas NORMAK e an e enea variable defines how the built in temperature sensors are used ald Sei 9 l ee This function is programmed from the factory EXTERNAL 0 10V External control with a 0 10 V DC signal 7 7 Variable value Explanation Function DETECT Q Air quality and internal temperature sensor 9 ADAPT supply air diffuser and ADAPT Damper SLAVE Slave product for supply air with DETECT SME or DETECT T TUNE T External room temperature setpoint adjuster 1 ADAPT Extract and Damper for extract air DETECT T External room temperature sensor 2 ADAPT Damper for supply air DETECT RH Humidity sensor amp internal temperature sensor 3 ADAPT Damper for extract air with DETECT T 59 This function is not used in a standard setup 4 ADAPT Damper for extract air with DETECT SME In some configurations this application can be used as a 5 9 Not used in the current version ventilation function i e external button for flow boost Swegon reserves the righ
15. it for accep table supply air temperature in relation to room temperature is specified A positive value only allows increased airflow when the supply temperature is lower than the set point value A negative value allows supply air temperature to be higher than the desired need for cooling or heating with air e g if the value is set to 5 K airflow increase can be performed with supply air that is 5 K warmer than the room temperature The corresponding principle also applies for cooling mode The default value is set to 0 K which in practice means that the supplyair only needs to be 0 1 K lower in order for cooling to take place ALLOWED T Air heating AT set value of the maximum supply air tem perature when the product controls a duct heater The supply air temperature recieves a max limit room temperature the set value 0 15 K www swegon com TUNE Adapt ADVANCED MENU OCCUPANCY INT Menus for settings of the internal occupancy sensor ADVANCED MENU TEMP MENU OCCUPANCY INT E OCCUPANCY INT OCC SENS LEVEL 0000 OCC STATUS 0 OCC STATUS DELAY 0 OCC DELAY OFF 20m OCC DELAY ON Os OCCUPANCY AUTO MAN AUTO OCC UNOCC UNOCC OCC SENS LEVEL Indicates the signal level from the built in occupancy sensor When the value from the sensor exceeds 250 occupancy is detected For ADAPT Damper with DETECT SME the detection limit is 100 OCC STATUS
16. le to which the heat load corresponds Example Heating load 50 The valve is closed 50 out of 350 sec 175 sec and then open for 175 sec HEAT VALVE POS from software version 4 or later Displays the heating value of the valve output in percent If the cold down draught protection function is enabled the heating value can be 0 while the valve output can be e g 20 SLAVE OUTPUT Displays the airflow of the slave output 0 corresponds to minimum or unoccupied flow while 100 cor responds to the maximum airflow EXTERNAL INPUT Displays the signal level of the external input in percent 0 100 This corresponds to 0 10V DC for the applica tion EXTERNAL 0 10V variable value 1 in earlier versions and 2 8V DC for the aplication SLAVE variable value 3 in earlier versions The value is only reported for these two pa rameters displayed value for all remaining applications is O 20130214 www swegon com TUNE Adapt SW VERSION Displays the current software version of the controller in the product SERIAL NO Displays the serial number of the product ALARM MENU This parameters in this menu shows the value 1 if something is abnormal in the ADAPT product Simultan eously the LED in the sensor module is red TUNE ADAPT V6 0 USER MENU ALARM MENU COMMISSIONING ALARM MENU FUNCTION ALARM DAMPER STROKE MOTOR FAULT PRESSURE SENSOR 0 ROOM TEMP 0 0 SUPINE TEME 0 0 0 WRONG SETPOI
17. or supply air the room temperature cannot be shown The value 1 is given in this case At delivery the products are preset to commissioning mode set to max airflow this can cause the room to get cold see TEST MENU last in this manual SUPPLY TEMP Shows the value of the built in temperature sensor In certain applications such as ADAPT Damper for extract air the tem perature cannot be shown the value 1 is then given co INROOM If DETECT Q is connected and APPLICATION MENU APP LICATION is set to DETECT Q corresponding parameter 2 in older versions the carbon dioxide value in the room is displayed CAC LEVEL CAC CO EQU If Clean Air Control is enabled the air quality value CAC LEVEL and the corresponding value recalculated in CO ppm CAC CO EQU are displayed here Good air quality corresponds in this case to a CAC value lower than 35 RH LEVEL When using a humidity sensor the actual value is displayed in percent COOL VALUE Displays the cooling value 0 100 where 0 corresponds to the min flow in unoccupied or occupied mode and 100 corresponds to the max flow When 2 step cooling is activated the range extends to 0 200 where the 100 200 range shows the working area of the cooling valve HEAT VALUE Displays the the heating value in percent if the product is set for heating control Heating control is time proportio nal which means that the valve is only open during that part of the time cyc
18. ower start limit for airflow increase in order to vent out moisture MAX SET Upper limit when airflow has reached its max value Specifies the relation between the measu AIEEE VOLT red RH level and volt signal to the product LANGUAGE Use this menu to change language settings in TUNE Adapt TUNE ADAPT V6 0 USER MENU gt ALARM MENU COMMISSIONING LANGUAGE LANGUAGE ENGLISH SVENSKA Scroll down to the preferred language and press ENTER to change language The standard version of TUNE Adapt is delivered with a language package containing e english swedish finnish danish and norwegian TUNE Adapt can also be ordered with one of the following two language packages e english estonian russian and polish e english german french and dutch User manuals in each of the available languages above are available for download from www swegon com TUNE Adapt with language packages other than the standard version must be ordered separately 20130214 www swegon com TUNE Adapt ADVANCED MENU The Advanced menu is mainly used for deployment and commissioning Changes in the advanced menu should pri marily be done by experienced users e g service technicians o TUNE ADAPT V6 0 USER MENU i ALARM MENU COMMISSIONING LANGUAGE ee TEST MENU ADVANCED MENU TEMP MENU Menus for setting temperature settings displayed in C ADVANCED MENU
19. stings below e g SLAVE 3 Swegon FUNCTION Operation menu containing settings of the extra functions in the product Alternatives Function when activated AIR COOL Airborn cooling eventually in combination with radiator heating AIR COOL amp HEAT Airborn cooling and airborn heating Air and water in sequence at COOUNG heating is not possible Not selectable in the current version LED INDICATOR Here you can select whether the LED of the product you are connected to in applicable cases i e products with a sensor module should be switched off or used to indicate functionality or comfort alarm also see ALARM MENU Alternatives Functionality OFF The LED on the product is turned off The LED indicates normal operation but FUNCTION not the comfort alarm default setting COMFORT The LED only indicates the comfort alarm The LED indicates both normal FUNG SO MGORT operation and the comfort alarm The LED indicates normal operation but OFFAF UNOSE is turned off in unoccupied mode The LED indicates normal operation NO ALARM INDIG No function alarms are indicated Mode indications of the WISE sensor module LED Colour Explanation Green solid At normal functionality during night cooling morning heat and vent boost Green flashing During Startup boot sequen
20. t to alter specifications 20130214 www swegon com TUNE Adapt HEATING from software version 4 or later If the ADAPT controller is to be used for controlling radiators this function must be enabled PRESENT NOT PRESENT however radiator control cannot be combined with 2 step cooling For ADAPT products running verson 3 change over can only be done in Modbus via variable 0x0006 or correpsonding software not via TUNE Adapt ACTUATOR TYPE Here you can change the function of the vent type The default setting is NORMALLY CLOSED Parameter Explanation Function NORMALLY CLOSED Deenergized closed valve Deenergized open valve Used for NORMALLY OPEN heating systems with requirements for secured heating during power down COOL PROTEC from software version 4 or later Cold down draught protection the product can control heating even if there is no heating load This function is used for reducing cold down draughts by the windows ACTIVE LEVEL The heating control will be enabled to the set point level e g 20 until the cooling load has reached 50 COOL LIMIT VALVE EXCERCISE from software version 4 or later During the summer half of the year the valves may need to be exercised so that they will not jam The exercising feature can be enabled by setting the time between these occasions to gt 0 The time is set in 24 hour days TIME INTERVAL 0 14d Exercising takes place by en
21. ta from external detectors only OCC STAT DELAY is displayed as either 0 or 1 6 Swegon reserves the right to alter specifications Swegon ADVANCED MENU COMMUNICATION Contains the communication settings for the product to Su perWISE or a BMS see the table Note the specific setting demands for products connected to a SuperWISE system ADVANCED MENU TEMP MENU OCCUPANCY INT O A O COMMUNICATION MODBUS ADDRESS 000 BAUDRATE 38 4k PARITY NONE TORBI oe Adjustable parameters in the communication menu Parameter Function and selectable modes MODBUS ADDRESS Setting of the modbus address 1 248 a Communication rate adjustable in Be ve three levels 9 6k 19 2k 38 4k PARITY Parity check NONE ODD EVEN STOP BITS Oor1 Product connected to SuperWise should always have the follo wing settings BAUD RATE 38 4k PARITY NONE STOP BITS 1 ADVANCED MENU EMERGENCY MENU This menu allows for emergency settings to be read or tested ADVANCED MENU TEMPERATURE OCCUPANCY INT COMMUNICATION EMERGENCY MENU EMERGENCY MENU EMERGENCY i CONTROL OFF SETTINGS MASTER CLOSE SLAVE EQUAL Functions EMERGENCY MENU Menu Function OFF ON Activates the emergency test During the test the LED flashes orange Do not forget to reset CONTROL to OFF when the test is completed Refers to the action