Installation Instructions
Contents
1. Remove the seal screw at the end of the regulator stack 6 Turn the gas on and place the thermostat at the highest setting to cycle the ignition system 7 Allow the system to stabilize Adjust the screw in the regulator stack to the desired reading on the manometer Turn clockwise to increase the outlet pressure and counterclockwise to reduce the outlet pressure 8 Reinstall the seal screw which incorporates the proper size hole for venting to the atmosphere It may be necessary to cycle the valve several times to verify the desired outlet pressure 9 Turn off the gas supply and place the thermostat at the lowest setting 10 Remove the pressure manometer and reinstall the pressure tap plug 11 Turn the gas on and set the thermostat to the desired setting 12 Check for leaks at the pressure tap plug with a soap solution before leaving the site VLV49A Series Universal Replacement Gas Valve Technical Bulletin 11 Checkout 4 Procedure WARNING Fire or Explosion Hazard Avoid personal injury or property damage by making sure the valve functions properly and there are no gas leaks Follow this checkout procedure before leaving the installation Make sure all components are functioning properly by performing the following test 1 Test for leaks on all pipe joints and connections upstream of the gas valve with a soap solution 2 Turn the thermostat to a low setting Turn on the gas and purge the gas lines of all a
2. Universal Replacement Gas Valve Technical Bulletin 5 Installation IMPORTANT This technical bulletin is intended as a guide for authorized service personnel installing or servicing BASO Gas products Carefully follow all instructions in this bulletin and all instructions on the appliance Limit repairs adjustments and servicing to the operations listed in this bulletin or on the appliance A WARNING Fire or Explosion Hazard The system must meet all applicable codes Improper installation may cause gas leaks explosions property damage and injuries A WARNING Fire or Explosion Hazard To prevent leakage of upstream gas shut off the gas supply at the main manual shutoff valve before installing or servicing the VLV valve A CAUTION Equipment Damage Hazard To prevent damage to the valve when mounting to the manifold do not use a wrench on any surface other than the casting flats provided at the inlet and outlet ends of the valve body A CAUTION Equipment Damage Hazard Label all wires prior to disconnection when replacing the valve Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Perform the following procedure to install the replacement VLV49A valve 1 Turn off power to the appliance 2 Turn off the gas at the manual shutoff valve adjacent to the appliance If the manual shutoff valve services more than one appliance be sure to light the other pilots before l
3. ccording to the labels on the wires Do not connect the electrical supply at this time a On grounded versions part numbers ending with the letters H L G or J e g GGOQBG or G6OQBJ connect the black lead wire to one of the ground terminals on the ignition control Four ground spade terminals are located just below the terminal board on terminal board models see Figure 2 or in a Square arrangement on the end of the plug in Heyco models see Figure 3 On ungrounded versions part numbers ending with a K e g GGOQBK connect the black lead wire to Terminal 5 on the ignition control On systems using G600 ignition controls connect the black lead wire to a ground terminal on the ignition control b Connect the blue lead wire to Terminal on the ignition control 16 Check for leakage a Open the pressure connection between the manual shutoff valve and the VLV valve b Connect air tubing with a maximum pressure of 1 1 2 times the valve s maximum operating pressure as indicated on the valve to the opened pressure connection c Paint all valve body connections with a rich soap and water solution If bubbles occur this is an indication of a leak To stop a leak tighten joints and connections Replace the part if the leak cannot be stopped If bubbles do not occur remove the air tubing and close the pressure connection VLV49A Series Universal Replacement Gas Valve Technical Bulletin 9 17 After insta
4. eaving 3 With the gas and power to the appliance turned off disconnect the power supply transformer and the thermostat lead wire at the ignition control 6 VLV49A Series Universal Replacement Gas Valve Technical Bulletin 4 Disconnect the sensing probe lead from Terminal 4 on the ignition control Disconnect the high voltage cable from the spark transformer 6 Disconnect the Pilot Valve 1 and Main Valve 3 leads from the terminal board or end plug in Heyco terminals see Figures 2 and 3 Terminal Board Connections Ground Terminals Figure 2 Terminal Board Ignition Control with Mounting Plate Ground Terminals Heyco Terminal Connections G eaqy ICNIT DN CONTA Wis 3 l s Ea Liew rm P a ia ka Figure 3 Plug in Heyco Ignition Control VLV49A Series Universal Replacement Gas Valve Technical Bulletin 7 7 Remove Screws A and B holding the ignition control assembly to the valve and plate assembly see Figure 1 These two screws are located on the bottom surface of the ignition control assembly 8 Remove the ignition control 9 Disconnect the pilot burner tubing from the pilot tap connection on the gas valve see Figure 1 10 Verify when looking on the inlet of the valve that the location of the grommet and wire leads on the old valve and new replacement valve are on the same side If they are not on the same side remove the grommet of the new replacement valve and insert it
5. i A 5 Technical Bulletin VLV BASO Gas Products LLC Issue Date 0100 VLV49A Series Universal Replacement Gas Valve To Terminal 5 To Terminal 3 a Z5 or Ground To Terminal 1 Ss a Blue Red Black Grommet OES S 2 Screw B Screw A i we US Pilot Tap Connection Vave SSS Inlet Figure 1 Universal Replacement Gas Valve Application The VLV49A Series Universal Replacement Gas Valve is for the replacement of the valve assembly of an electronic proven pilot spark ignition control with a valve 1 e G60 and Q15 They are combination redundant valves available with or without a pressure regulator These valves can be used on appliances burning natural gas Liquefied Petroleum LP gas manufactured gas mixed gas or LP gas air mixtures including sulfur bearing gases depending on the regulator selection at pressures up to 35 mbar 0 5 psi 2004 BASO Gas Products 1 Part No 24 8711 455 Rev www baso com Table 1 Specifications Product o VLV49A Series Universal Replacement Gas Valves Maximum Operating 35 mbar 0 5 psi Pressure Ambient Temperature 40 to 80 C 40 to 175 F Electrical Rating 24 VAC 60 Hz 0 3 ampere draw Regulator Adjustment 7 5 to 15 mbar 3 to 6 in W C Range Inlet Pipe Size 1 2 in NPT Outlet Pipe Size 3 4 in NPT Pilot Outlet 1 8 in 27 NPT left and right Wiring Connections 216 mm 8 5 in lead wires Types of Gas Natural Liquefied Petroleum LP man
6. into the other side of the mounting plate see Figure 4 This allows the placement of the ignition control spark transformer over the outlet of the valve instead of the inlet Remove grommet and wires from here Removable Portion of Mounting Plate Replace grommet and wires here Removable Portion of Mounting Plate Figure 4 Grommet Locations 11 Remove the old valve from the manifold and install the new replacement valve Ensure the gas flows through the valve body in the direction indicated by the arrow on the valve body If the valve is installed with the gas flow opposite the arrow leakage can occur A thread lubricant has been factory applied to the first two or three threads of the valve inlet and outlet to avoid galling Use an approved pipe joint sealing compound on male threads before assembling Take care that excess compound does not work into the valve and get onto the valve seats Threads of pipe and nipples must be smooth and free of tears and burrs 12 Reconnect the pilot burner tubing at the pilot tap connection 13 Fasten the ignition control assembly to the valve and plate assembly with the screws provided with the replacement valve 14 Break off the portion of the plate that protrudes if it interferes with surrounding surfaces see Figure 4 8 VLV49A Series Universal Replacement Gas Valve Technical Bulletin 15 Reconnect the thermostat leads the sensing probe lead and the high voltage cable a
7. ir 4 Turn the thermostat to a high setting The appliance should operate in accordance with the manufacturer s specified sequence of operation 5 Test for leaks on all pipe joints and connections downstream of the gas valve with a soap solution 6 Turn the thermostat down for at least 30 seconds and then back up again Verify successful ignition at least three times before leaving the installation Repairs and The VLV49A replacement valves are not field repairable Do not Replacement attempt field repairs For a replacement valve contact the nearest BASO Gas Products distributor BASO Gas Products LLC 1007 South 12th Street PO Box 170 Watertown WI 53094 www baso com 1 877 227 6427 1 877 BASOGAS Printed in U S A 12 VLV49A Series Universal Replacement Gas Valve Technical Bulletin
8. llation of the replacement valve is complete except for the attachment of the red lead wire turn on the gas at the manual shutoff valve a Reconnect the power supply lead wire to the ignition control and turn the power On b Set the thermostat to the highest setting The pilot valve will open spark will be energized and the pilot will light Test for gas leaks in the pilot line with a soap solution d After the check is complete turn off the power and connect the red lead wire to Terminal 3 on the ignition control 18 Turn on the power and set the thermostat to the desired setting 10 VLV49A Series Universal Replacement Gas Valve Technical Bulletin Regulator IMPORTANT All adjustments must be made in conjunction with Adjustment the gas appliance and in accordance with the appliance manufacturer s instruction Only authorized personnel should make adjustments A WARNING Explosion Hazard The minimum flow rate of the valve must not be adjusted below the minimum safe working rate of the appliance The pressure regulator is adjustable and has been factory set If a different setting 1s desired follow these instructions 1 Shut off all gas to the appliance 2 Turn the thermostat to the lowest setting or Off position 3 Remove the pressure tap plug at the valve outlet or in the manifold pipe downstream of the valve 4 Install a manometer or pressure gauge suitable for measuring the desired orifice pressure
9. ufactured mixed and LP gas air mixtures Accessories Conversion Kits Natural gas to LP gas lever acting regulator Y71GF 4 direct acting regulator Y71GF 3 Agency Listings The performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these specifications consult BASO Gas Products BASO Gas Products shall not be liable for damages resulting from misapplication or misuse of its products Table 2 Universal Replacement Gas Valve Chart Valve Part Number Regulator Type VLV49A 600R Direct acting regulator VLV49A 601R Lever acting regulator VLV49A 602R No regulator 2 VLV49A Series Universal Replacement Gas Valve Technical Bulletin Table 3 Replacement Valve Selection Chart G60RHL 1 VLV49A 600R Continued on next page VLV49A Series Universal Replacement Gas Valve Technical Bulletin 3 Original Valve Ignition Part Number Replacement Valve Part Number Cont 4 VLV49A Series Universal Replacement Gas Valve Technical Bulletin Original Valve Ignition Part Number Replacement Valve Part Number Cont 24 VAC replacement gas valve for original 120 VAC valve A 24 VAC transformer is required Note All replacement valves come set up for use with natural gas If used on an LP system the appropriate Y71 conversion kit must be installed e Y71GF 3 Natural to LP for direct acting regulators e Y71GF 4 Natural to LP for lever acting regulators VLV49A Series
Download Pdf Manuals
Related Search
Related Contents
AquaLab 800-755-2751 C:\Documents and Settings\All Users\Documents\Shared Coons Release note Guía del usuario MobIR®M4 - Oropeza Ingenieros BGP Troubleshooting - PFS Internet Development 0 - Pontiac CLASSROOM MANAGEMENT SYSTEM USER MANUAL MANUAL DE INSTRUCCIONES DWS-61 Copyright © All rights reserved.