Home
SDC 15 - United Automation
Contents
1. 2 Digital input 1 Event output 3 Event output 1 Digital input 2 communication Individual contact Available inputs and outputs may vary depending on the model 2 Preventive measures against noise of instru ment power supply 1 Reduction of noise Even though the noise is small the noise filter is used to eliminate the effect of the noise as much as possible Instrument power supply Noise filter Ci5T C158 100 to 240Vac Q 2 When noise is excessive If a large amount of noise exists appropriate isolation transformer and line filter are used to eliminate the effect of the noise Line filter Insulation Yamatake s model No i ODAN E81446364 001 nstrument Equivalent to ZAC2205 00U power supply 200 200V made by TDK Ci5T C15S 100 5 x Other circuit Grounding 11 Installation environment noise sources and preventive measures Generally the following may be the noise sources in the installation environment Relay and contact electromagnetic coil solenoid valve power supply line particularly 100Vac or more motor commutator phase angle control SCR radio communica tion device welding machine high voltage ignitor etc Preventive measures against fast rise noise Use of CR filter is effective to prevent fast rise noise Recommended filter Yamatake s model No 81446365 001 Equivalent to 953M500333311 made by Matsuo Electric 4 Wiring precautions 1
2. After taking the noise preventive measures do not bundle the primary and secondary power cables together or put both power cables in the same conduit or duct 2 Keep the input output and communication lines 50 cm or more away from the power lines and power supply lines having a voltage of 100Vac or more Additionally do not put these lines together in the same conduit or duct 5 Inspection after wiring After the wiring work has been completed always in spect and check the wiring status Great care should be taken since incorrect wiring may cause the instru ment to malfunction or severe personal injury ZN RESTRICTIONS ON USE This product has been designed developed and manufactured for general purpose application in machinery and equipment Accordingly when used in the applications outlined below special care should be taken to implement a fail safe and or redundant design concept as well as a periodic maintenance program e Safety devices for plant worker protection Start stop control devices for transportation and material handling machines Aeronautical aerospace machines Control devices for nuclear reactors Never use this product in applications where human safety may be put at risk Specifications are subject to change without notice YWAMATAKE Yamatake Corporation Advanced Automation Company International Business Headquarters Totate International Building 2 12 19 Shibuya Shibuya ku ee Pr
3. No according to the sensor type and range to be used 100 to 800 150 to 1500 RTD Pt100 200 to 500 300 to 900 JPt100 200 to 500 300 to 900 Pt100 200 to 200 300 to 400 JPt100 200 to 200 300 to 400 Pt100 100 to 300 150 to 500 JPt100 100 to 300 150 to 500 Pt100 50 0 to 200 0 50 to 400 JPt100 50 0 to 200 0 50 to 400 Pt100 50 0 to 100 0 50 to 200 JPt100 50 0 to 100 0 50 to 200 Pt100 0 0 to 200 0 0 to 400 JPt100 0 0 to 200 0 0 to 400 Pt100 0 to 500 0 to 900 Input type JPt100 Sensor type 0 to 500 0 to 900 Range Linear input 0 to 1V 1 to 5V 0 to 5V 0 to 10V 0 to 20mA 4 to 20mA The scaling is made in a range of 1999 to 9999 The decimal point position can be changed variably E Model Selection Guide l ll WE Ivey vey VET VII Example C15TROTA0000 IV v Control PV Power output input supply T S Specifications Single Loop Controller Panel mounting type Socket mounting type Control output 1 Control output 2 Relay output None Voltage pulse output For SSR drive None Voltage pulse output For SSR drive Current output Voltage pulse output For SSR drive Voltage pulse output For SSR drive Curren
4. Sub setting SP Ry SP high limit SP low limit Direct action Reverse action Direct action Reverse action THs ON oN pS Main setting Sse Main setting SP gt O ON HYS Main setting sP gt HYS ON Main setting SP high low limit MV high limit Direct action Reverse action Direct action Reverse action Ting on HS ON ps f ys f ON Main setting Sub setting SP Main setting Sub setting SP THs 3 ON oN H ad Main setting MV Main setting MV MV low limit MV high low limit Direct action Reverse action Direct action Reverse action HYS ON ON fs f ist ON ays on HYS Dams 7 Main setting MV gt Main setting MV gt Main setting Sub setting MV gt Main setting Sub setting MV gt Heater burno ut Over current Heater sh ort circuit Direct action Reverse action Direct action Reverse action ON buys 7 Avs fon Main setting Sub setting CT at output ON gt Tis Eont S9 Main setting Sub setting CT at output ON HYS ON Main setting CT at output OFF ON HYS Main setting CT at output OFF Event type shows that the ON OFF is changed at this value O shows that the ON OFF is changed at a point that 1U is added to this value Loop
5. the ST setting completion Timer status The direct and reverse action settings are disabled for the timer event When using the timer event it is necessary to set the operation type of the DI allocation to Timer Start Stop Additionally when setting the event channel designation of the DI allocation multiple timer events are controlled from individual internal contacts Dl Setting items ON delay time A period of time necessary to change the event from OFF to ON after DI has been changed from OFF to ON OFF delay time A period of time necessary to change the event from ON to OFF after DI has been changed from ON to OFF Operation specifications e The event is turned ON when DI ON continues for ON delay time or longer e The event is turned OFF when DI OFF continues for OFF delay time or longer In other cases the current status is continued DI ON ON delay OFF delay o n ON Internal event CAUTION Time When setting the ON delay and OFF delay it is necessary to put in Multi function setup The default settings of the ON delay and OFF delay before shipment are 0 0s The default setting of the event channel designation of the DI allocation before shipment is 0 In this case the timer event start stop can be set for all internal events from one internal contact DI Additionally as one or more event channel designation is set the timer event start stop can be set for one interna
6. No CP SS 1814E Single Loop Controller SDC15 E Features The DigitroniK SDC15 is a 48 x 48mm compact digital controller featuring group multi range inputs and PID control system using new algorithms Rationaloop PID Ra Pid and Just FiTTER Up to two control output points this number of points may vary depending on the model can be used which are selectable from the relay contact voltage pulse and current Two kinds of mounting methods are provided panel mounting type and socket mounting type Additionally this controller is compliant to the CE mark ing e Compact body with a depth of 60 mm The mask of the front panel is also only 2 mm thick e The accuracy is 0 5 FS e The input type can be changed among the thermocouple input group RTD group and linear group e The control method can be selected from any of the ON OFF control PID control using Rationaloop PID Ra Pid Just FiTTER and self tuning e The heat and cool control can be achieved using two con trol output points and event outputs e 18 kinds of operations such as set SP value selection RUN READY selection and latch cancellation etc can be set using two external switch input points e The process variable PV value can be corrected e The controller is applicable to the communication 3 wire RS 485 E Basic Function Block of SDC15 foe date ete eee it Pry tae are ed Up to eight points c
7. alue of the deviation PV SP becomes less than the sub setting The event is turned OFF regardless of other conditions when a period of time after starting of operation from the time that the power has been turned ON becomes less than the OFF delay time However the event is turned OFF when the absolute value of the deviation is the sub setting hysteresis value or less after the absolute value of the deviation has become the sub setting or more CAUTION When setting the ON delay and OFF delay it is necessary to put in Multi function setup The default settings of the ON delay and OFF delay before shipment are 0 0s Direct action Reverse action Heat control Cool control Main setting 0 or more PV to be used as reference PV Main setting 0 or more ea satisfying Mai Z 4 i w i setting i m H PA 4 i ditions 2 0 or more i 9 Main setting reference p f iis ees B ne 0 or more u 1 i reference i PV to be used as reference Area satisfying C i Area satisiying i i conditions2 i conditions 2 Area satisfying Area satisfying conditions 2 i j ual conditions 2 Conditions 3 Conditions3 Conditions 3 Conditions 3 ON delay f ON delay i ON delay i 1 ON delay Set time setting TON A Set time FON setting Toy ON delay is started when conditions 1 and 2 are satisfied ON delay is starte
8. an be registered for the parameter keys ensuring easy operation Use of mode key ensures easy operation RUN READY AUTO MANUAL and SP selections and EV relay latch cancellation Up to three event output points are provided In addition to temperature events such as PV DEV and SP status events such as CT heater burnout over cur rent and loop diagnosis can also be set The controller is compliant to the CE marking safety standards EN61010 1 and EN61326 1 Use of personal computer loader optional unit makes it possible to easily perform various settings such as setup and parameter setting Use of personal computer loader makes it possible to eas ily achieve the data logging from single unit to up to eight units 11 kinds of thermocouple selections 19 kinds of ranges Relay contact Voltage pulse output For SSR drive Control MV output 2 kinds of RTD selections 14 kinds of ranges 6 kinds of DC voltage current input selections Current PV value correction Current PV value filter Current PV value ratio Process variable PV input gt Control operation _ Current output gt Above outputs are combined 2 points PV upper limit lower limit upper lower limit Deviation upper limit lower limit upper lower limit Specification External switch input 2 points Set SP value 4 kinds of selections RUN READY selec
9. ce Max 2502 Allowable OFF contact resistance Min 100kQ Allowable ON state residual voltage Max 1 0V Open terminal voltage 5 5Vdct1V ON terminal voltage Approx 7 5mA at short circuit Approx 5 0mA at contact resistance of 250Q Number of output points 0 to 3 points depending on the model Number of internal event settings Up to 5 settings Event type shows that the ON OFF is changed at this value O shows that the ON OFF is changed at a point that 1U is added to this value PV high limit PV low limit Direct action Reverse action Direct action Reverse action firs 3 ON oN pys Main setting e i Main setting Pv gt ON HYS Main setting PV HYS ON Main setting PV high low limit Deviation high limit Direct action Reverse action Direct action Reverse action ON tuys f cr ON Tivs f on HYS f 1 HYS ON on H Main setting Sub setting PV Main setting Sub setting PV SP Main setting PV SP Main setting PV Deviation low limit Deviation high low limit Direct action Reverse action Direct action Reverse action ON HYS SP Main setting PV HYS SP Main setting PV ON Tirst ON q Wey ON est f nvs ON Main setting Sub setting SP PV Main setting
10. current Max 24mAdc Leak current at OFF Max 100unA Output type 0 to 20mAdc or 4 to 20mAdc Allowable load resistance Max 6009 Output accuracy 0 5 FS However 0 to 1mA 1 FS Cycle time s 5 to 120 0 1 0 25 0 5 1 to 120 PID control Proportional band FS 0 1 to 999 9 Integral time s 0 to 9999 PD operation when 0 Derivative time s 0 to 9999 PI operation when D 0 Manual set 10 0 to 110 0 only when I 0 Control output Just FiTTER Overshoot suppression coefficient 0 to 100 ON OFF control Operation clearance C 0 to 9999 or 0 0 to 999 9 Control operation selection Direct action or reverse action RUN READY selection Selected with the RDY key on the front panel or external contact input In READY mode Control output OFF Heat Cool control selection Control output and event o utput External contact digital input Number of inputs 2 points Function Up to four kinds of setting value SP selections RUN READY selection AUTO MANUAL section Auto tuning stop start Self turning disable enable Control action Direct Reverse selection SP ramp enable disable PV value hold Max PV value hold Min PV value hold Timer start stop All DO latch cancellation Input rating Non voltage contact or open collector Min detection holding time 1s or longer Allowable ON contact resistan
11. d when conditions 1 and 2 are satisfied PV alarm status Direct action Reverse action ON if PV alarm alarm code AL01 to 03 occurs OFF if PV alarm alarm code ALO1 to 03 occurs OFF in other cases ON in other cases READY status Direct action Reverse action ON in the READY mode OFF in the READY mode OFF in the RUN mode ON in the RUN mode MANUAL status Direct action Reverse action ON in the MANUAL mode OFF in the MANUAL mode OFF in the AUTO mode ON in RUN mode During AT Auto tuning Direct action Reverse action ON while AT is running OFF while AT is running OFF while AT is being stopped ON while AT is being stopped During SP ramp Direct action Reverse action ON during SP ramp OFF during SP ramp OFF when SP ramp is not performed or is completed ON when SP ramp is not performed or is completed Control operation status Direct action Reverse action ON during direct action cooling OFF during direct action cooling OFF during reverse action heating ON during reverse action heating Event type shows that the ON OFF is changed at this value O shows that the ON OFF is changed at a point that 1U is added to this value ST Smart Tuning setting standby status Direct action Reverse action ON in the ST setting standby OFF in the ST setting completion OFF in the ST setting standby ON in
12. diagnosis 1 The event is turned ON when any change in PV corresponding to increase decrease in MV Manipulated variable is not observed This event is used to detect any fault of final control devices Setting items e Main setting MV Manipulated variable e Sub setting PV ON delay time Diagnosis time Operation specifications The event is turned ON when the value does not reach the PV set in the sub setting within the diagnosis time ON delay time even though the MV exceeding the main setting is held CAUTION When setting the ON delay it is necessary to put in Multi function setup The default setting of the ON delay before shipment is 0 0s Direct action Reverse action Cool control PV PV Sub setting Heat control Area satisfying Sub setting han conditions 1 Area satisfying conditions 1 Area satisfying Area Area satsifying conditions 2 i conditions 2 Main setting Main setting Conditions 3 1 ON delay set time as Conditions 3 ON delay set time SE S ON ON EV EV Time gt ON delay is started when conditions 1 and 2 are satisfied Time On delay is started when conditions 1 and 2 are saisfied Loop diagnosis 2 The event is turned ON when any change in PV corresponding to increase decrease in MV Manipulated variable is not observed This event is used to detect any fault of final co
13. ed Fixed at 19200 bps Recommended cable Dedicated cable 2 m long Current transformer input Number of inputs 2 points Detection function Control output is ON Detection of heater line break or overcurrent Control output is OFF Detection of final control devices short circuit Input object Number of current transformer windings 800 turns QN206A 5 8mm hole diameter QN212A 12mm hole diameter Optional Optional Measurement current range 0 4 to 50A Indication range 0 0 to 70 0A Indication accuracy 5 FS 1 digit Current transformer input Indication resolution 0 1A Output Selected from control output 1 and control output 2 or event output 1 event output 2 and event output 3 Min detection time Burnout detection Min control output ON time 300ms or more Final control device short circuit detection Min control output OFF time 300ms or more General specifications Memory backup Semiconductor non volatile memory Power supply voltage AC power supply model 85 to 264Vac 50 60Hz 2Hz Power consumption AC power supply model 12VA or less Insulation resistance Between power supply terminal and secondary terminal 500Vdc 10MQ or more Dielectric strength AC power supply model Between power supply terminal and secondary terminal 1500Vac fo
14. etting before shipment is the RUN READY selection 5 para key Changes the display 6 lt v a key Increases or decreases the numeric value or shifts the digit 7 Loader connector Connects a personal computer using the dedicated cable supplied with the Smart Loader Package e Wiring of C15S Control output Event output Relay Relay Voltage pulse Relay individual contact Current Current 100 to 240Vac Voltage 100 to 240Vac RTD Thermocouple Socket terminal No Connection of RS 485 communication Digital input RS 485 is a 3 wire connection DA DB SG RS 485 RS 485 communication Example Connection with 5 wire instrument CJ Handling Precautions Do not connect any external terminating resistor since a de vice similar to the terminating resistor is built into this control ler Precautions on the use of self tuning function The final control devices must be powered up simul taneously with or prior to the instrument when the self tuning function is to be used Precautions on wiring 1 Isolation within instrument Solid line portions are isolated Dotted line portions are not isolated Power supply Control output 1 PV input Control output 2 CT input 1 Event output 1 CT input 2 Internal Event output 1 Individual contact Loader communication Circuit Event output
15. g bracket Accessory 48 gt lt Terminal screw M3 Sams F esnia eras Ee enoe i REI 1 LEVIN 2 GORG HRA 1 1 T J LH 2 T 1 oll Soe d a EP TA CoS BL CJ Handling Precautions Tighten the screws of the attached mounting bracket When the mounting bracket is secured firmly so that no play exists tighten the screws further by half turn to fix the bracket to the panel If the screws are tightened excessively this may cause the case to deform C15S Socket mounting type Socket 81446391 001 Optional unit l Terminal screw M3 5 4 l l l l hz 71 40 2 M4 mounting hole oo 0 ON E O 1 bo s y P j Stopper Socket 3 Put the stopper in the upper and lower holes in the main body of this controller and secure the socket firmly Panel cutout diagram Individual mounting Side by side mounting 0 5 30 min 45 poe OO 4axN 3 95 j a ry I T go i a ire i L ze ig po ee 2 i l i t E e N shows the number of mounted units 1 CJ Handling Precautions When mounting three or more units tightly in the horizontal direction pay special attention so that the ambient temperature does not exceed 40 C When the water proof structure is required always mount the unit indi vidually after the gasket supplied wit
16. h this controller has been mounted on the main body Keep a space of 50 mm or more in the vertical direction E Part Names and Functions WAMATAKE ai 1 sp 2 4 a 0000000 3 dy man A 2 e3 t1 t2 CYA E Terminal Connection Diagram e Wiring of C15T Relay Relay individual i contact Control output CT input O gt oh T as 23 CT2 D One Voltage pulse a Event ouput dace Voltage pulse One ore Current 24 Orel Voltage pulse Or rO OF DS Voltage pulse Bt 2 OR Or lole o 7 r Power supply Current za o D e Current O E ee ne ee 2 Current 2 PV input Thermocouple DI COM Cc 2 RTD B G De A Current wa DA 6 DB Voltage 6 SG 1 Display No 1 Shows the PV value current temperature etc or setting items 2 Display No 2 Shows the SP value set temperature etc or the set value of each setting item 3 Mode indicators rdy Lights in READY mode control stop man Lights in MANUAL mode manual opera tion mode ev1 to ev3 Lights when event relay output is ON ot1 to ot2 Lights when control output is ON 4 mode key When this key is kept pressed for Is or longer the operation which has been set pre viously can be performed The default s
17. inted in Japan H Tokyo 150 8316 Japan 1st Edition Issued in May 2003 URL http www yamatake com This has been printed on recycled paper 01 12
18. l event specified by one internal contact DI However when setting the event channel of the DI allocation it is necessary to put in Multi function setup Direct Reverse action standby and READY operations can be set when setting up each event E1 C1 to E5 C2 Operating differential 0 to 9999 or 0 0 to 999 9 Output operation ON OFF operation Output type SPST relay contacts Common for 3 points individual contact for 2 points Output rating 250Vac 30Vdc 2A resistive load Life 100 000 cycles or more Min opening and closing specifications 5V 10mA reference value Communication Communication system Communication protocol RS 485 Network Multidrop This device is provided with the slave station function 1 to 31 units max Data flow Half duplex Synchronization method Start stop synchronization Interface Transmission system Balance differential type Data line Bit serial Communication lines 3 transmit receive lines Transmission speed 4800 9600 19200 38400 bps Communication distance 500m max Protocol RS 485 3 wire type Message characters Character configuration 11 bits character Data length 7 or 8 bits Stop bit length 1 or 2 bits Parity bit Even parity odd parity or non parity Loader communication Communication line 3 wire Transmission spe
19. mocouple input RTD input Upscale alarm display AL01 RTD burnout Upscale alarm display A wire burnout Upscale alarm display B wire burnout Upscale alarm display ALO1 ALO3 C wire burnout Upscale alarm display ALO1 ALO3 2 or 3 wire burnout Upscale alarm display ALO1 AL03 A and B wire short circuit Downscale alarm display AL02 A and C wire short circuit Downscale alarm display ALO2 DC voltage input Downscale alarm display AL02 However a voltage input ranging from 0 to 10V cannot be detected Downscale alarm display ALO2 However a current input ranging from 0 to 20mA cannot be detected AL01 AL01 DC current input Indications and setting PV SP indication method 4 digit 7 segment LED PV Upper green display SP Lower orange display Number of setting points Max 4 points Setting method lt v ora key operation at each digit Setting range See Table 1 Indication accuracy 0 5 FS 1 digit In the negative area of the thermocouple the accuracy is 1 FS 1 digit at an ambient temperature of 23 2 C Indication range See Table 1 Indication and setting units Thermocouple input 11 C RTD input 11 C 0 1 C depending on the type of input DC voltage input DC current input programmable range 1 0 1 0 01 0 001 Settling value SP limit Lower limit Lower limit value of range to upper limit value of setting val
20. nged at variable is not observed this value This event is used to detect any fault of final control devices O shows that the ON Setting items OFF is changed at Main setting Change in PV from the point that the MV reaches the upper limit 100 or lower limit 0 a point that 1U is Sub setting Range of absolute value of deviation PV SP allowing the event to turn OFF added to this value ON delay time Diagnosis time e OFF delay time A period of time from power ON allowing the event to turn OFF Operation specifications e The direct action is used for the heat control The event is turned ON when the increase in PV becomes smaller than the main setting after the diagnosis time ON delay time has elapsed from the time that the MV had reached the upper limit or when the decrease in PV becomes smaller than the main setting from the time that the diagnosis time ON delay time has elapsed from the time that the MV had reached the lower limit The reverse action is used for the cool control The event is turned ON when the decrease in PV becomes smaller than the main setting after the diagnosis time ON delay time has elapsed from the time that the MV had reached the upper limit or when the increase in PV becomes smaller than the main setting after the diagnosis time ON delay time has elapsed from the time that the MV had reached the lower limit The event is turned OFF regardless of other conditions when the absolute v
21. ntrol devices Setting items e Main setting MV Manipulated variable e Sub setting Change in PV from the point that the MV exceeds the main setting ON delay time Diagnosis time Operation specifications The event is turned ON when the MV exceeding the main setting is held conditions 2 and the PV does not reach the value that the sub setting is added to subtracted from the PV at the point where the MV exceeds the main setting within the diagnosis time ON delay time conditions 1 CAUTION When setting the ON delay it is necessary to put in Multi function setup The default setting of the ON delay before shipment is 0 0s Direct action Reverse action Heat control Cool control PV PV to be used Sub setting as reference Area satisfying 0 or more un conditions 1 Sub setting 0 or more Area satisfying PV to be used conditions 1 as reference Area satisfying conditions 2 Area satisfying My conditions 2 Main setting Main setting Conditions 3 ON delay B set time Conditions 3 1 ON delay set time ON EV EV ON Time gt ON delay is started when conditions 1 and 2 are satisfied Time gt ON delay is started when conditions 1 and 2 are satisfied Event type Loop diagnosis 1 shows that the ON The event is turned ON when any change in PV corresponding to increase decrease in MV Manipulated OFF is cha
22. r 1 min Power ON inrush current AC power supply model 20A or less Operating conditions Ambient temperature 0 to 50 C 0 to 40 C for side by side mounting Ambient humidity 10 to 90 RH No condensation allowed Vibration resistance 0 to 2m s 10 to 60Hz for 2 hrs in each of X Y and Z directions Shock resistance 0 to 10m s Mounting angle Reference plane 10 Transportation conditions Ambient temperature 20 to 70 C Ambient humidity 10 to 95 RH No condensation allowed Package drop test Drop height 60cm 1 corner 3 sides 6 planes free fall Mask and case material Mask Polyester film Case Modified PPE Mask and case color Mask Dark gray DIC546 Case Light gray DIC650 Structure IP66 Conformed standards EN61010 1 EN61326 1 Installation category Category Il IEC644 1 EN61010 1 Mounting S type Socket mounting mounting with dedicated socket T type Panel mounting with dedicated mounting bracket Installation Gasket 1 81409657 001 1 Supplied only with C15T 2 Connected to C15T 3 Standard accessory Table 1 Input Types and Ranges Input type Sensor type Range C Range F Input type Weight S type Approx 200g including socket T type Appro
23. t output None Current output Current output Thermocouple input K J E T R S B N Wre5 26 DIN U DIN L RTD input Pt100 JPt100 DC voltage current input 0 to 1Vdc 1 to 5Vdc 0 to 5Vdc 0 to 10Vdc 0 to 20mAdc 4 to 20mAdc AC power supply 100 to 240Vac DC power supply 24Vdc available soon T R L Event relay output 3 points Event relay output 3 points Note 1 Current transformer input 2 points Note 3 Digital input 2 points Event relay output 3 points Note 1 Current transformer input 2 points Note 3 RS 485 communication Event relay output 2 points individual contact Event relay output 2 points individual contact Note 1 Current transformer input 2 points Note 3 Digital input 2 points Event relay output 2 points individual contact Note 1 Current transformer input 2 points Note 3 RS 485 communication NT o o No additional processing o o With inspection certificate lt o Traceability certificate available Note 1 This model cannot be selected for C15S Note 2 Only 1a contact is available for C15S Note 3 Current transformer is optional sold separately Note 4 Socket is optional sold separately E Dimensions C15T Panel mounting type Unit mm 2 60 Mountin
24. tion Latch cancellation etc 18 kinds Current transformer input 2 points Any of ON OFF control self tuning and PID control is selected Direct Reverse action Heat Cool operation SP upper limit lower limit upper lower limit MV upper limit lower limit upper lower limit gt Heater burnout Over current EV functions such as loop diagnosis Control output can be allocated Event output 3 points Communication input output RS 485 3 wire Power supply 85 to 264Vac 24Vdc Personal computer loader gt Loader communication Units marked an asterisk will be available in the near future E Specifications Input type Thermocouple RTD DC current DC voltage Selected by model See Table 1 Sampling time 0 5s Process variable PV correction 1999 to 9999 or 199 9 to 999 9 Input bias current Thermocouple input RTD input DC voltage input 0 2uA or less under standard conditions Approx 1mA flowed from A terminal 0 1V range 0 5V 1 5V range 0 10V range 1pA or less 3 5uA or less 7pA or less Effect of wiring resistance Thermocouple input RTD input DC voltage input 0 2uV Q or less 0 05 FS Q or less 0 1V range 1uV Q or less 0 5V 1 5V range 0 10V range 3 5uV Q or less 7uV Q or less Display at burnout Ther
25. ue SP limit upper limit Lower limit value of setting value SP limit to upper limit value of range Function display method Digital 4 digit 7 segment LED indication Common to the PV display displayed in green Status indication EV1 EV2 EV3 Red LED lamp indication 0T1 OT2 control output RDY READY MAN power Green LED lamp indication Display selection Process variable PV Setting value SP Control output value Heater current value Time event remaining time SP No Key lock Selected from the following three methods e Key lock is activated in all modes e Operable only for operation indications SP EV UF and parameter setting mode SP event Operable only for operation indications SP EV UF Password The data is protected by setting the password Control output Output type Current Relay contact Voltage pulse For SSR drive Control method Selected from the following three methods ON OFF control Control with fixed PID value PID control using Rationaloop PID Ra Pid and Just FiTTER e Self tuning Output rating Output rating Control output NO side 250Vac 30Vdc 3A resistive load Control output NC side 250Vac 30Vdc 1A resistive load Service life 50 000 cycles or more on NO side 100 000 cycles or more on NC side Min opening closing specifications 5V 100mA Open voltage 19Vdc 15 Internal resistance 82Q 0 5 Allowable
26. x 150g including dedicated mounting bracket Standard Part name Model Q ty Auxiliary parts Part name Model accessories Mounting bracket 81446403 001 4 optional parts Mounting bracket 2 81446403 001 User s manual CP UM 5287E 1 Gasket 3 81409657 001 Current transformer QN206A 6mm hole diameter QN212A 12mm hole diameter Socket 81446391 001 Hard cover 81446442 001 Soft cover 81446443 001 Terminal cover Sensor type 81446898 001 Range C Range F Thermo K 200 to 1200 300 to 2200 couple 0 to 1200 0 to 2200 0 to 800 0 to 1500 0 to 600 0 to 1100 0 to 400 0 to 700 200 to 400 300 to 700 0 to 800 0 to 1500 0 to 600 0 to 1100 200 to 400 300 to 700 0 to 600 0 to 1100 200 to 400 300 to 700 0 to 1600 0 to 3000 0 to 1600 0 to 3000 K K K K K J J J E T R S B 0 to 1800 0 to 3300 N 0 to 1300 0 to 2300 Wre5 26 0 to 1400 0 to 2400 Wre5 26 0 to 2300 0 to 4200 DIN U 200 to 400 300 ot 700 DINL C Handling Precautions The accuracy of the B thermocouple is t5 FS at a tem perature of 260 C or less and 1 FS at a temperature of 260 to 800 C e The range having the decimal point is displayed to the 1st digit after the decimal point e The setup is made using C01
Download Pdf Manuals
Related Search
Related Contents
WINPASS ind I- English Réalisation d`une liste éclair avec Généatique 2012 Mode d`installation 取扱説明書 - M DC220/05 Philips Clock radio for iPhone/ iPod Manuel d`instructions et livret des pièces détachées Verti Pro Latch R programme 2014 (pdf - 3,01 Mo) Samsung PL170 Korisničko uputstvo Copyright © All rights reserved.